icount Particle MonitoringACM20, ACM20 Z2, IPD and IBSAviation fuel + hazardous zones monitoring
Contents
icountACM20 Aviation Fuel Monitor .............................. 3 - 6
icountACM20 Z2 ATEX Approved Monitor ................. 7 - 12
icountPD Online Particle Detector ............................. 13 - 22
icountBS Bottle Sampler .............................................. 23 - 29
Parker Hannifin Corporation
A global Fortune 300 companywith customers in 48 countries,Parker Hannifin is the world’sleading supplier of hydraulic,pneumatic, and electro-mechanical systems andcomponents. Customers relyon Parker for engineeringexcellence, world-class manu-facturing and outstandingcustomer service to providecomprehensive applicationsolutions that are second to none.
• More than USD 12.1 billionin sales
• 298 plants worldwide• 12,000 distributors• 449,000 customers• Serving 1,200 distinct markets• Listed as PH on the New York
Stock Exchange
Let Parker become part of yourdesign team. Whether you need todevelop new products, redesignexisting applications, or designcompletely new systems, Parkeroffers unparalleled engineeringexpertise.
Fluid contaminationmonitoringParker Filtration continues, throughtechnical expertise and proven products, toretain a world class position as an innovatorin designing andmanufacturing fluidcontaminationmonitoring and analysisequipment ensuring our customers canmaintain the cleanliness of their hydraulicsystems.More recently Parker Filtration’s CMCdevelopment engineers have beenworking successfully on designingandmanufacturing a ‘family’ of icountcontamination analyzers, particle detectorsand bottle samplers intended to provideaccurate and repeatable monitoringof contamination in AvTur and otherhydrocarbon fuels in accordance with theEnergy Institute (EI) Method IP564.
The ParkerBrand PromiseParker is the global leader inmotionand control technologies, partneringwith its customers to increase theirproductivity and profitability.
2Parker HannifinHydraulic Filter Division Europe
3
Customer ValueProposition:DEFSTAN 91-91 Issue 6 Jet A-1FuelSpecification, adopts particle counting.
Development work carried out by the CMCengineers, in conjunction with Exxon MobilAviation, highlighted the need for an alternativetest method to determine the levels of dispersedcontamination in Jet fuel. 5 years of field testingand development of the already establishedand successful LCM20 Hydraulic LaserParticle Counter saw the introduction of theParker icountACM20 with enhanced softwareproviding the user with a better understandingof the contamination present in a sample.As the benchmark particle counter for use inmeasuring the levels of contamination in fuels,the icountACM20, as per the UK’s EnergyInstitute Test Method IP564, has now beenincluded in the DEFSTAN 91-91 Issue 6 JetFuel Specification as a report only test alongsidethe current Gravimetric test method (IP423 orASTM D5452) and Clear & Bright Visual testmethod (IP216 or ASTM D2276)
icountACM20 Lab UnitAviation Fuel Contamination Monitoring
Contact Information:Parker HannifinHydraulic Filter Division Europe
European ProductInformation CentreFreephone: 00800 27 27 5374(from AT, BE, CH, CZ, DE, EE, ES,FI, FR, IE, IT, PT, SE, SK, UK)[email protected]
www.parkerhfde.com
Product Features:
icountACM20 monitors•aviation fuel contamination toDEFSTAN 91-91 Issue 6 JetA-1 fuel specification.Energy Institute Test Method•IP 564.2-minute test procedure.•
Laser optical scanning•analysis.Multi-standard ISO cleanliness•reporting.On-board, rear-mounted•pump enables monitoringpossibilities.For example: Fuel storagetanks and fuel storage drums.Vehicle fuel tanks.•
The Parker icountACM20 Portable Particle Counterhas been developed from existing technologyfor monitoring contamination in AvTur and otherhydrocarbon fuels, in accordance with the EnergyInstitute (EI) Method IP 564.
In addition, the ACM can also be used to monitorvarious fuels from existing sampling points inlocations from refineries, pipelines, distributionterminals, airport fuel supply systems all the waythrough to the point of uplift into aircraft*.
* Hot works permit required for online sampling (ATEX Zone 2 unit
available). Page 7.
• Fuel Testing Laboratories – DEFSTAN 91-91Issue 6In order to better understand dispersedcontamination in jet fuel, particle counting isnow included alongside existing laboratorytechniques
• Bottle Sampling - Energy Institute (EI) - IP 564Laboratory determination of the level ofdispersed contamination in aviation kerosineusing an Automatic Particle Counter (APC)
• Replace Clear & Bright and GravimetricWith the introduction of the icount ACM20,all subjectivity surrounding Clear & Bright andGravimetric methods can be removed
• Also for use on petroleum based hydraulicapplications (Skydrol compatible available)Suitable for use with mineral oil andpetroleum based fluid as per standardhydraulic particle counter, reporting fluidcleanliness to ISO 4406:1999
Test Time:2 minutes
Repeat Test Time:Every 2 minutes (Manual testing)
Principle of Operation:Optical scanning analysis and measurement of actual particles andinference to water presence
Primary Output:≥4µ(c), ≥6µ(c), ≥14µ(c), ≥21µ(c), ≥25µ(c), ≥30µ(c) counts per ml
Secondary Diagnostic Output:% Volume Distribution, via graphical display on handset and printout
International codes:ISO 7-22 in accordance with ISO 4406-1999
Data entry:32 character two line dot matrix LCD. Full alpha numeric entryfacility on keypad
Data retrieval:Memory access gives test search facility for up to 300 saved tests
Calibration:In accordance with Parker Calibration Procedure CM20-N, whichcomplies to ISO11171:1999, Clause 6 (Omitting Annex F)
Re-calibration:Every 12 months by a dedicated Parker Service Centre (ConsultParker)
Max. working pressure:420 bar
Operating Temperature:+5°C to +80°C
Memory store:300 test capacity
Computer compatibility:Interface via RS 232 connection @ 9600 baud rate (USB serial cableto RS232 option available)
Laboratory sampling:Utilizes on-board rear mounted gear pump
Portability:Only 8 kg. icount ACM20 has its own battery pack and carry case withwheels
Power requirement:12vDC input, 6 x ‘D’ Cell or rechargeable batteries
Printer facility:Integral 16 column printer for hard copy data
Certification:Complies with all relevant EC declarations of conformity
icount ACM20 Case Mounted PumpIntegrated Pump assembly incorporated onto the ACM20 unit.•Powered directly from ACM20 unit, LED power indication with no•additional power supplies required.Direct sampling from fuel sample bottles or tank via 3 metre inlet•suction tube.Incoporated double speed flush and test sequence.•Managed flow rate/correct volume sample as per IP 564 test•method.
icountACM20 Lab UnitAviation Fuel Contamination Monitoring
Features & Benefits
Applications
4Parker HannifinHydraulic Filter Division Europe
icountACM20 - rear view
Construction:Case-Lexan structural foam and ABSHand-held display - ABSKeypad flurosilicone rubber
Mechanical Components:Brass, plated steel, stainless steel and aluminium
Seals:Fluorocarbon
Hoses:Nylon (Kevlar braided microbore). St. steel armoured ends
Flow Rate:25 - 28ml/min (dictated by CMP) 100ml/min with additional flush button
Fluid Compatability:Hydrocarbon Fuel, Mineral Oil. For other fluids consult Parker
Fuse:1.25 amp fast blow fuse included for overload protection (sparesupplied)
icountACM20 Technology:Patented flow cell, light obscuration
Repeatability/Accuracy:As per or better than ISO 11171
Coincidence:40,000 particles per ml
Viscosity Range:1 -100 centistokes
icountACM20 Weight:8 kg
Monitor Carrying Case:Astra Board case
Carrying Case Weight:5 kg
Specification
Ordering Information
Note 1: Part numbers featured with bold highlighted codes will ensure a ‘standard’ product selection.Note 2: Alternate displayed part number selection will require you to contact Parker Filtration for availability.Note 3: Selected spare parts - for a full list contact Parker.* Hot works permit required for online sampling.
Standard products table - icount ACM20
Product number
ACM202022UKACM202022USACM202022EURACM202024UKACM202024USACM202024EURB84794B84816P843855B84746B84745B84645B84609B84817B84830B84831B84832SERMISC067B84702P843702
Description
Particle counter UK*Particle counter US*Particle counter Euro*
Particle counter with lab kit UK (DEFSTAN 9191)Particle counter with lab kit US (DEFSTAN 9191)Particle counter with lab kit Euro (DEFSTAN 9191)
1m process cable assemblyParsmart downloader software
Carry caseWash BottleThrottle kit
Millipore adaptor assyRe-chargeable battery pack
UK power supplyUS power supplyEuro power supply
Laboratory kit500ml Verification fluidPrinter paper (5 rolls)
Printer ribbon
5
Field Monitoring -icountACM202022For use in non-hazardous areas, theicountACM202022 is designed for online samplingof hydrocarbon fuels and hydraulic systems, utilisingexisting “quick connect” sampling points such asthe Millpore Adaptor.
Input Power Socket (note that youmay have to remove the plasticdust cap to access the 12Vdcpower socket).A fast blow 1.25A fuse and theRS232 connection are locatedbehind the removable cover plate.The RS232 interface is providedto download all test data stored inthe instrument. See the ParSmartDownloader software for moreinformation.
DEFSTAN 91-91 Issue 6Defence Standard 91-91 is thespecification for aviation turbinefuel, which the United KingdomCivil Aviation Authority (CAA)has agreed is under thetechnical authority of theDirector of the Defence FuelsGroup.
IP 564Laboratory determination of thelevel of dispersed contaminationin aviation kerosene using anAutomatic Particle Counter (APC).This standard describes amethod for determining the levelof dispersed contaminationin aviation kerosene fuels,specifically dirt particles andwater droplets in the range from≥4µ(c) to ≥30µ(c).This method relates specifically toAviation fuels but the equipmentcan be used on all fuels,petroleum and mineral basedfluids.
Note:The mandatory implementationdate for IP 564 test method“Determination of the level ofcleanliness of aviation turbinefuel - laboratory automatic particlecounter” is July 1st 2009. It is thespecification authorities intentionto replace current test methodswith particle counting at the earliestopportunity.
icountACM20 Lab UnitAviation Fuel Contamination Monitoring
IP 564 ProcedureStep 1The apparatus shall be set upin accordance with Parker’soperating instructions.
Step 2Test Portion Preparation:Decant a minimum of 450ml ofthe field sample into a clean testportion container.
Step 3Prior to starting a test,tumble the test portionend over end for 60 seconds toensure any settled particles areredistributed.
Step 4Turn on the Case Mounted Pumpand flush for 60 seconds.Do not press the fast flush button.While flushing, enter the testidentifier (see manual).
Step 5Following the flush, start a testby turning the blue valve in thedirection indicatedPerform a further 3 tests. (4 intotal).
6Parker HannifinHydraulic Filter Division Europe
Customer ValueProposition:icountACM20 Z2 is designed tobe used to monitor various fuelsfrom existing sampling pointsin hazardous locations fromrefineries, pipelines, distributionterminals, airport fuel supplysystems all the way through tothe point of uplift into aircraft. WithZone 2 classification, the icountACM20 Z2 is the worlds onlyATEX approved particle counter.
Product Features:
• Assembled in an approvedand certified stainless steelenclosure to comply with ATEXDirective 94/9/EC and EN50021 requirements.
• Can be used in explosiveand hazardous areas,including offshore and miningapplications.
• ATEX Zone II
• Certified to CE Ex II 3 G Ex nR/nL IIC T6
• “A” Class product defined forthe Aviation market.
• ATEX approved Handset andkeypad.
• Suitable for use with mineraloil and petroleum based fluidas per ACM20/LCM20 particlecounters.
icountACM20 Z2ATEX Approved Portable Particle Counter
Contact Information:Parker HannifinHydraulic Filter Division Europe
European ProductInformation CentreFreephone: 00800 27 27 5374(from AT, BE, CH, CZ, DE, EE, ES,FI, FR, IE, IT, PT, SE, SK, UK)[email protected]
www.parkerhfde.com
7
icountACM20 Z2ATEX Approved Portable Particle Counter
Features & Benefits
Test Time:2 minutes.
Repeat Test Time:Every 2 minutes (Manual testing) Every 6 minutes (Automatic).
Principle of Operation:Optical scanning analysis and measurement of actual particles andinference to water presence.
Primary Output:≥4µ(c), ≥6µ(c), ≥14µ(c), ≥21µ(c), ≥25µ(c), ≥30µ(c) counts per ml.
Secondary Diagnostic Output:% Volume Distribution, via graphical display on handset.
International codes:ISO 7-22 in accordance with ISO 4406-1999
Data entry:32 character two line dot matrix LCD. Full alpha numeric entry facilityon keypad.
Data retrieval:Memory access gives test search facility for up to 300 saved tests.
Calibration:In accordance with Parker Calibration Procedure CM20-N, whichcomplies to ISO11171:1999, Clause 6 (Omitting Annex F).
Re-calibration:Every 12 months by a dedicated Parker Service Centre (ConsultParker).
Max. working pressure:420 bar.
Operating Temperature:+5°C to +80°C
Memory store:300 test (scrolling memory) capacity.
Computer compatibility:Interface via RS 232 connection @ 9600 baud rate.
Portability:15 kg. ACM20 has its own battery pack and carry case with wheels.
Power requirement:Rechargeable battery powered or via the 12vDC input.
System connection:Via Millipore adaptor with flow restriction through supplied needle valve.
Certification:Complies with all relevant EC declarations of conformity.
Printer facility:No printer. Data download only.
Online Commission Kit
a – icountACM20 Zone II Particle Counterb – Battery Chargerc – Process Cabled – User Manuale – Downloader Softwaref – Throttle Kitg – Millipore Adaptor Assemblyh – Aluminium Casei – Bottle Assembly
a
b
h
d
c
g
i
f
e
8Parker HannifinHydraulic Filter Division Europe
Specification Using icountACM20 Z2
Construction:Unit: Stainless SteelCarrying case: ABSHand-held display: ABSKeypad: polyester membrane
Mechanical components:Brass, plated steel, stainless steel and aluminium
Seals: Fluorocarbon
Hoses: Nylon (Kevlar braided microbore)
Fluid compatibility:All fuels. For other fluids consult Parker
Internal rechargeable battery:Note: ONLY to be charged outside of the hazardous area,with the unit switched off
Fuse:1.25A fast blow fuse included for overload protectionReturn to Parker Hannifin if fuse is blown
icountACM20 2032 technology:Unique optical scanning system
Applications in Fuels
Oil Refineryo To count and verify the levels of dispersed
contamination in accordance withspecification limits. (Consult Parker CMC).
Distribution Terminals/Hubso For use on receipt and outbound supply.
Also to provide filtration performance, tankcleanliness and product quality checks.
Storageo Settling times can be reduced by monitoring
with the ACM by ensuring that levelsof dispersed contamination are belowacceptable levels.
Airport Fuel Farmo Monitoring of the fuels into storage, through
the fuel farm, hydrant system and uplift intowing.
Pipeline Commissioningo Fast real time monitoring of pipelines
following pigging and cleaning processes.Oil and Gas Platformso Used to monitor the filtration performance,
system cleanliness and quality of deliveredproduct.
icountACM20 Z2 is designed to be used tomonitor various fuels from existing sampling pointsin hazardous locations from refineries, pipelines,distribution terminals, airport fuel supply systems allthe way through to the point of uplift into aircraft.With Zone II classification, the icountACM20 Z2 isthe worlds only ATEX approved particle counter.
9
Installation Details
icountACM20 Z2ATEX Approved Portable Particle Counter
Product number Description
Particle counter with online kit & UK power supplyParticle counter with online kit & US power supplyParticle counter with online kit & Euro power supply
Particle counter with online & lab kit + UK power supplyParticle counter with online & lab kit + US power supplyParticle counter with online & lab kit + Euro power supply
UK battery chargerUS battery chargerEuro battery charger
2m process cable assemblyParsmart downloader software
Carry caseBottle assembly
Throttle kitMillipore adaptor assy
Standard products table - icountACM20 Z2
Ordering Information
ACM202032UKACM202032USACM202032EURACM202034UKACM202034USACM202034EURB84647B84652B84653B84650B84816P843066B84746B84745B84645
10Parker HannifinHydraulic Filter Division Europe
Applications in hydraulics
Solutions in the offshore industry.In addition, the icountACM20 Z2 can be used in manyhydraulic system applications as detailed below.
In many industries, worker awareness needs to be maintainedat a high level to ensure the safety of their operation. Thisis particularly relevant to offshore oil-drilling and gas-drillingcrews, given the interactive and hazardous nature of theirwork. The Zone II ACM portable particle analyser is a tried andtested technology designed, proven and approved as a fluidcontamination monitor that crews are using and trusting insuch hazardous and demanding environments.
• Certified to CE Ex II 3 G Ex nR/nL IIC T6
• Can be used in explosive and hazardous areas, includingOffshore and Mining.
• Primary Output. Six cumulative particle size channelsranging from ≥4µm(c) to ≥30µm(c) and numbers per mlin accordance with ISO4406-1999.
icountACM20 Z2 – operational in oil refineries and fuel fields.Already operational in oil refineries and designed to be used inside commercial airfieldfuel locations and at the point of upload of fuel into the aircraft, icountACM20 Z2 hasan impressive success record in this approval sensitive area of operation.
With a number of safety features designed in as operational standards, theicountACM20Z2 can be taken to the point of use, connected in moments andreporting in little more than 2 minutes to ISO approved standards.
• Assembled in an approved and certified stainless steel enclosure to comply withATEX Directive 94/9/EC and EN50 021 requirements.
• ‘A’ Class product defined for the aviation market.
• Designed for on-line operation, connecting to the process line via existingMillipore™ fittings, already in use for other industry equipment.
Applications in other hazardous environments.
• Railroad equipment manufacturer - Warranty protection.
• Power generation stations - Preventative maintenance.
• Mobile equipment - Roll-off cleanliness testing.
• Mining operations - Service tool.
• Steel mills - Preventative maintenance.
11
icountACM20 Z2ATEX Approved Portable Particle Counter
Average Particle Counts in AV System
The table below gives estimated counts found in a typical aviation fuel distribution system, and is given as guidance, in whichAPI/EI filtration equipment is installed.
Receipt into MicrofilterExpect 2,500 counts per mlor cleaner @ 4µ(c)
Receipt into Microfilter
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count2,50035010
High Count Code181510
MF
Receipt into FWS (After MF)
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count500505
High Count Code16139
FWSReceipt into FWS (After MF)Expect 500 counts per mlor cleaner @ 4µ(c)
Receipt into Storage (After FWS/MF)
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count100101
High Count Code14107
Airport storageReceipt into Storage (After FWS/MF)Expect 100 counts per mlor cleaner @ 4µ(c)
FWS Out of Storage
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count500505
High Count Code16139
FWSFWS out of storageExpect 500 counts per mlor cleaner @ 4µ(c)
After FWS Into Hydrant
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count100101
High Count Code14107
To Hydrant/RefuellerAfter FWS into HydrantExpect 100 counts per mlor cleaner @ 4µ(c)
After Monitor Into Plane
≥4µ(c)≥6µ(c)≥14µ(c)
ISO Code - 4406 1999
High Count100101
High Count Code14107
After Monitor Into AircraftExpect 100 counts per mlor cleaner @ 4µ(c)
Note: Figures will vary from location to location.Key: MF=Microfilter (API/EI 1590)
FWS=Filter Water Separator (API/EI 1581)
12Parker HannifinHydraulic Filter Division Europe
Customer ValueProposition:The icountPD Particle Detectorfrom Parker represents the mostup to date technology in particledetection. The design dynamics,attention to detail and mouldingcompactness of the permanentlymounted, on-line particle detectormodule, combined with on-board,laser based, leading-edgetechnology, brings to all industriesa truly revolutionary, particledetector as a remarkable costeffective market solution to fluidmanagement and contaminationcontrol.
icountPDOnline Particle Detector
Contact Information:Parker HannifinHydraulic Filter Division Europe
European ProductInformation CentreFreephone: 00800 27 27 5374(from AT, BE, CH, CZ, DE, EE, ES,FI, FR, IE, IT, PT, SE, SK, UK)[email protected]
www.parkerhfde.com
Product Features:
Independent monitoring of•system contamination trends.Warning LED or digital display•indicators for Low, Mediumand High contamination levels.Visual indicators with power•and alarm output warnings.Moisture %RH indicator•(optional).Cost effective solution to•prolong fluid life and reducemachine downtime.
Continuous performance for•prolonged analysis.Fuel, Hydraulic and phosphate•Ester fluid compatibleconstruction.Self diagnostic software.•Fully PC/PLC integration•technology such as:- RS232and 0-5Volt, 4-20mA,CAN(J1939) (Contact Parkerfor other options).Set up and Data logging•support software included.
13
Diagnostic Self Check Start-up Time:5 secondsMeasurement Period:5 to 180 secondsReporting interval through RS232:0 to 3600 secondsDigital LED display update time:Every secondLimit Relay Output:Changes occur +/- 1 ISO code at set limit (Hysteresis ON) or customerset (Hysteresis OFF)4-20mA Output Signal:ContinuousPrinciple of operation:Laser diode optical detection of actual particulates.Reporting Codes:ISO 7 – 21, NAS 0 – 12, (AS 00 – 12 Contact Parker)Icount will also report less than ISO 7, subject to the statisticaluncertainty defined in ISO4406:1999, which is shown in the RS232,reporting results as appropriate e.g “>6”Calibration:By recognised on-line methods, confirmed by the relevant InternationalStandard Organisation procedures.Calibration Recommendation:12 monthsPerformance:+/- 1 ISO Code (Dependant on stability of flow)Reproducibility / Repeatability:Better than 1 ISO CodePower Requirement:Regulated 9 to 40VdcMaximum Current Draw:150mAHydraulic Connection:M16 x 2 hydraulic test points (5/8” BSF foraggressive version)
Recommended Flow Range through the device:40 to 140 ml/min (Optimum Flow = 60ml/min)Online Flow Range via System 20 Inline Sensors (Hydraulicsystems only):Size 0 = 6 to 25 l/min - (Optimum Flow = 15 l/min)Size 1 = 24 to 100 l/min - (Optimum Flow = 70 l/min)Size 2 = 170 to 380 l/min - (Optimum Flow = 250 l/min)Required Differential Pressure across Inline Sensors:0.4 bar (Minimum)Viscosity Range:1-500 cStTemperature:Operating Environment -20°C to +60°C (-4°F to +140°F)Storage -40°C to +80°C (-40°F to +176°F)Operating Fluid 0°C to +85°C (+32°F to +185°F)Working pressure:2 to 420 bar (0-420 bar)Moisture sensor calibration (Not offered with the fuel version):±5% RH (over compensated temperature range of +10°C to +80°C)Operating humidity range:5% RH to 100% RHMoisture sensor stability:±0.2% RH typical at 50% RH in one yearCertification:IP66 ratedEMC/RFI – EN61000-6-2:2001
EN61000-6-3:2001Materials:User friendly Abs construction.Stainless Steel hydraulic block.Viton seals.Dimensions:182mm x 155mm x 86mm (7.2” x 6.1” x 3.4”)Weight:1.3kg (2.9lb)
icountPDOnline Particle Detector
Features & Benefits
14Parker HannifinHydraulic Filter Division Europe
Field Data - Major International Airport
First 3 measurements represent fuelfrom a previous cargo followed by aregular clean delivery, thus demonstratingthe range of fuel cleanliness beingexperienced at this particular location.
>4µ >6µ >14µ >21µTest 1 81058.3 62126.1 17817.6 6066.2Test 2 87834.5 74763.0 35454.1 18044.4Test 3 51383.4 32796.9 4424.8 1213.4Test 4 1593.3 422.7 9.6 1.7
>4µ >6µ >14µ >21µTest 5 1226.1 261.5 2.4 0.4Test 6 1085.7 210.9 1.3 0.1Test 7 1037.9 198.7 1.3 0.1
Dimensions / Installation Details
Typical Applications
Mobile Equipmento Earth Moving Machineryo Harvestingo Forestryo Agriculture
Monitoring of the hydraulics, enabling the vehiclesto function to their best capability under loadconditions through pistons, servo valves, controlrams and gear pumps.
Industrial Equipmento Production Plantso Fluid Transferso Pulp & Papero Refineries
To monitor the cleanliness of the equipmentthroughout the production line, from the machinetool controlled hydraulics through to contaminationof fluid transfer. Ensuring the integrity of the fluid ismaintained throughout the refining process.
Power Generationo Wind Turbineso Gearboxeso Lubrication Systems
With continuous monitoring the optimum level isachieved in the least amount of time.
Maintenanceo Test Rigso Flushing Stands
To increase efficiency of your equipment bycontinuously monitoring the cleanliness level of thehydraulic fluid.
Maximum Torque 5Nm
15
1
2
3
4
5
6
7
8
NOT USED
RS232 Ground (Pin 5**)
Channel A, ISO 4µm(c)*
Channel B, ISO 6µm (c)* or NAS
(if selected)
RS232 Receive (Pin 3**)
RS232 Transmit (Pin 2**)
Moisture sensor channel (if fitted)
Channel C, ISO 14µm (c)*
NOT USED
RS232 Ground (Pin 5**)
Channel A, ISO 4µm(c)*
Channel B, ISO 6µm (c)* or NAS
(if selected)
RX232 Receive (Pin3**)
RS232 Transmit (Pin 2**)
Moisture sensor channel (if fitted)
Channel C, ISO 14µm (c)*
M12 Communication cable: wiring configuration
(Limit Relay Wiring Instructions)NORMALLY OPENNORMALLY CLOSEDCOMMON
Pin 4-20mA option connections 0-5v/0-3v option connections
M12 Communication cable
Important Note: It is the responsibility of the end user to ensure that the cable’s braided screenis terminated to a suitable earth bonding point.
* Optional – refer to the ‘IcountPD part number specifier’ section in this manual.
** A standard USB serial adaptor can be used with the recommended 9-way D-typeconnector to convert RS232 to USB.
Limit relay alarm levels
The IcountPD can be specified with a built-in limit switch relay which can be triggered when a preset alarm levelis reached. The relay contacts can be used to switch on or off an external device.
Pin Current loop options connections
1
2
3
4
5
6
7
8
Product supply 9-40Vdc
4-20mA Supply 12-20Vdc
Relay (Normally Closed)*** (if fitted)
Relay (Normally Open)*** (if fitted)
NOT USED
NOT USED
Main supply 0Vdc
Relay (Common)*** (if fitted)
0-5v/0-3v option connections
Product supply 9-40Vdc
0-5 / 0-3V Supply 12-24Vdc
Relay (Normally Closed)*** (if fitted)
Relay (Normally Open)*** (if fitted)
NOT USED
0-5V / 0-3V Supply 0 Vdc
Product supply 0Vdc
Relay (Common)*** (if fitted)
M12 Supply and Relay (if fitted) cable
Note: If the moisture sensor is fitted without either option then the output is RS232.
Parker Hannifin recommend that the mating M12 connector cables are screened. Thesecables are available from Parker Hannifin – ordering information section.
*** Optional – refer to ordering information section.
icountPDOnline Particle Detector
Comms Cable
Supply & limit RelayCable
16Parker HannifinHydraulic Filter Division Europe
Variable mA output settings
4-20mA output settings
ISO SettingmA current = (ISO Code / 2) +4 eg. 10mA = (ISO 12 / 2) +4orISO Code = (mA current - 4) *2 eg. ISO 12 = (10mA -4) *2
NAS SettingmA current = NAS Code +5 eg. 15mA = NAS 10 +5orNAS Code = mA current -5 eg. NAS 10 = 15mA – 5
The following table can be used to equate the analogueoutput to an ISO or NAS Code.
Example ISO code 12 is equal to 10mA
4.04.55.05.56.06.57.07.58.08.59.09.510.010.511.011.512.012.513.013.514.014.515.015.516.016.517.017.518.018.519.019.520.0
0123456789101112131415161718192021****************
OVERRANGE
OVERRANGE
ERROR
mA ISO4567891011121314151617181920
000123456789101112****
ERROR
mA NAS
0.0
2.04.0
6.0
8.010.0
12.0
14.0
16.018.0
20.0
201918171615141312115 6 7 8 9 1043210 21
ISO CODE
Mill
iam
pO
utp
ut
ISO V MILLIAMP (MA)
0
24
6
810
12
14
1618
20
1312115 6 7 8 9 1043210
NAS CODE
Mill
iam
pO
utp
ut
NAS V MILLIAMP (MA)
The following table can be used to equate theanalogue output to an ISO or NAS Code.
Example ISO code 12 is equal to 10mA
Variable voltage output settings
The variable voltage output option has the capability of two different voltage ranges: a 0–5Vdc range asstandard, and a user-selectable 0–3Vdc range. The ‘Full list of commands’ on how to change the voltageoutput, are available from Parker.The following tables can be used to relate the analogue ouptut to an ISO or NAS code.For example, in a 0–5Vdc range, ISO code 16 is equal to an output of 3.5Vdc. In a 0–3Vdc range, ISO code 8is equal to an output of 1.0Vdc.
ISO Err
0–5Vdc
0–3Vdc
<0.2
<0.15
0
0.3
0.2
1
0.5
0.3
2
0.7
0.4
3
0.9
0.5
4
1.1
0.6
5
1.3
0.7
6
1.5
0.8
7
1.7
0.9
8
1.9
1.0
9
2.1
1.1
10
2.3
1.2
11 >
2.5
1.3
Table relating ISO codes to Voltage output
cont. ISO 12
0–5Vdc
0–3Vdc
2.7
1.4
13
2.9
1.5
14
3.1
1.6
15
3.3
1.7
16
3.5
1.8
17
3.7
1.9
18
3.9
2.0
19
4.1
2.1
20
4.3
2.2
21
4.5
2.3
22
4.7
2.4
Err
>4.8
>2.45
ISO Err
0–5Vdc
0–3Vdc
<0.4
<0.2
00 0
0.6
N.S.
1
0.9
0.3
2
1.2
0.5
3
1.5
0.7
4
1.8
0.9
5
2.1
1.1
6
2.4
1.3
7
2.7
1.5
8
3.0
1.7
9
3.3
1.9
10
3.6
2.1
11 12 Err
3.9
2.3
4.2
2.5
4.5
2.7
>4.6
>2.8
Table relating NAS codes to Voltage output
17
Digital display parameters (ISO 4406/NAS 1638)
Digital display indicationThe digital display will show the actual measured codes, the channel (µ) size and the user definable limits.Note that the channel size and limits will alternate between the two.The Moisture Sensor reading (%RH) will also be shown – if the Moisture Sensor option is fitted.The order of trigger for both the codes and Moisture Sensor option is:• Solid digit(s) = code(s) that are at or below the set point (limit)• Flashing digit(s) = code(s) that are above the set point (limit)The display for ISO4406 and NAS1638 are identical. The ISO display is shown below.
Error detection:In the unlikely event of a error occurring, the digital display on the icountPD will simply display the actualerror code only – i.e. ERROR 13 (A full list of error codes are detailed in the IcountPD User Manual).
Channel sizes/Limits
Automatic light sensor
MTD calibrated
Measured ISO codes
Moisture sensor reading
Saturation 4–20mA 0–3Vdc 0–5Vdc
4.8
8
12
16
20
0.15
0.75
1.50
2.25
3.00
0.25
1.25
2.50
3.75
5.00
Start up1. Once the icountPD has been connected to a regulated power supply, the product logo is displayed for
approximately five seconds as the IcountPD performs a self system diagnostic check.2. The IcountPD then automatically starts monitoring using factory default test parameters.
Moisture sensor output settingsThe Moisture Sensor is an option that can be included when specifying the icountPD.The Moisture Sensor reports on the saturation levels of the fluid passing through the icountPD sensing cell.The output is a linear scale, reporting within the range of 5% saturation to 100% saturation.
Table relating Saturation levels in the sensing cell to icountPD outputs
icountPDOnline Particle Detector
5%
25%
50%
75%
100%
ISO 19/18/15 andMS = 70% RH if fitted
18Parker HannifinHydraulic Filter Division Europe
Auxiliary Flow Device
Icount PD – Oil Cleanliness Indicator (icount PD OCI)
The pressure compensated, Flow control device(Part Number S840074) has been developedto give the icountPD user greater flexibility. TheFlow control device will enable testing where flowranges are outside the icountPD specifications(40 – 140 ml/min), or where pipe diameters do notallow the icountPD to be installed.The Flow control device fits onto the downstream(outlet) side of the icountPD, connecting through amanifold block, via a self-sealing quick connection testpoint and is fitted with a differential pressure valve.This Flow control device automatically compensatesfor pressure and viscosity changes, whilst maintainingits setting even as the workload changes.Simply position the valve to match the viscosity of theoil you are testing.The chart can be used to determine the valveposition:
New and under development in the detection of•contaminates distribution in various Aviation fuels.Portable monitoring tool providing fluid•qualification to ISO 4406:1999 standards.Supplements the icount ACM20 product•portfolio.Quick, simple to use monitoring tool for sampling•fluids from containers, fuel bunkers and holdingtanks.Field solution to Laboratory methods for the•detection of solid contamination and free waterinference.
Example:If the fluid you wish to analyse has a viscosity of50cSt under normal operating conditions then thecontrol knob on the Flow Control Device should beset to valve position ‘3’The flow device will now automatically control theflow rate through the icountPD to within its workingrange of 40-140ml/min.
Note: The Flow control device will still operate correctly even with thehigh pressure side at 200bar and the return back to an open systemof 0 bar (DP = 200bar)
19
Valve Position cSt Range
3
3.8
4.2
5
up to 100
90 - 200
190 - 320
310 - 500
Hydraulic Connection Diagram Dimensions
2 bar check valveTo Atmosphere
Actuator Manual flow rate adjustable via control knobMounting Type 4 off mounting holes to suit M6 screws (not supplied)Mounting position AnyWeight 1.7kg (3.7lb)Fluid Temperature 5°C to +80°C (+41°F to 176°F)Ambient storage temperature -20°C to +40°C (-4°F to +104°F)Viscosity range 20cSt to 500cSt (If lower than 20cSt contact Parker)Differential pressure range 5 to 315 barMaximum pressure 315 barFlow direction ‘IN’ to ‘OUT’ flow control functionPort thread detail 1/8” BSPP (test points not supplied)Internal Seals Fluoroelastomer
IcountPD
P1P2
High PressureLine Side
Low PressureReturn Side
OutIn
Flow ControlDevice
90.0
20.0 78
.211
3.2
58.2
78.2
46.550.0
G1/8 ports either sideof mounting block
“In”
4 holes 6.60 Thro’
“Out”
38.0 Ctrs
62.0
80.0
Ctrs
49.2
icountPDOnline Particle Detector
20Parker HannifinHydraulic Filter Division Europe
This application shows uploadingfuel into an aircraft with theicountPD in use to monitor as a‘go/no go’ device.
Communication Protocol
Communication Options
The icountPD may be configured using the icountPD Setup Utility. For more direct control of the device using itscommunications protocol, you may also use the Microsoft Windows® HyperTerminal program, but note that thisprogram is not currently supplied with the Windows Vista™ operating system. These two ways of communicatingwith icountPD are described in the following section.
The Communication protocol for the serialcommunication link is to be used withMicrosoftWindows HyperTerminal. The settings are as follows:
Baud rate 9600Data bits 8Parity NoneStop bits 1Flowcontrol None
The commands used with this product are made upof Read, Set and Start / Stop commands.• Set commands allow the value or values of
parameters to be set• Read commands allow the value or values or
parameters to be read• Start/Stop allows the user to start and stop tests.
Example:[SDF dd/mm/yy] - sets the date format.[RDF] - reads the product date format.
All commands are sent in ASCII characters, andthe protocol accepts both upper and lower casecharacters as the examples below:
SDFSdF
Note: A full list of commands are detailed in the usermanual
icountPD Setup Utility software
21
NoRS232
Ordering Information
Part number Fluid type Calibration Display Limit relay Communications Moisture sensor Cable connector kit Future option
IPD12212130
IPD12212230
IPD12222130
IPD12222230
IPD12312130
IPD12312230
IPD12322130
IPD12322230
Mineral
Mineral
Mineral
Mineral
Mineral
Mineral
Mineral
Mineral
MTD
MTD
MTD
MTD
MTD
MTD
MTD
MTD
LED
LED
LED
LED
Digital
Digital
Digital
Digital
No
No
Yes
Yes
No
No
Yes
Yes
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
RS232 / 4-20mA
No
Yes
No
Yes
No
Yes
No
Yes
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
M12 - 8 pin
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1 metre hose length2 metre hose length5 metre hose length
1/4” BSP fitting1/8” BSP fitting1/8” NPT fitting
Single point samplerInternal flow device
12Vdc Regulated Power supply2x 5 Metre, M12
8 Pin Plug and Socket Cable Kit*Deutsch Connector Kit
RS232 To USB Converter
Description Part numberMineralB65946B94802B94804P653109P653110P653512SPS2021S840074
B84829
Contact ParkerB84654P843130B84011
AggressiveB84827* *B94801* *B84828* *P843081P853008P853005SPS2061
Contact Parker
* M12 Cable kit consists of two 5 metre cables to enable all output options(Communications cable and Relay/Power Supply cable)* * Note that the aggressive fluid hoses are provided as a single hose, not in pairs.
Note: Moisture Sensor (%RH) option not available with ‘Fluid Type’ 3 and 4.
Accessories
Standard Products Table
Part number Supercedes Size Flow range l/min
STI0144100
STI1144100
STI2144100
STI0148100
STI1148100
STI2148100
STI.0144.100
STI.1144.100
STI.2144.100
STI.0148.100
STI.1148.100
STI.2148.100
0
1
2
0
1
2
6-25
20-100
80-380
6-25
20-100
80-380
Fluid type
Mineral
Mineral
Mineral
Aggressive
Aggressive
Aggressive
Port threads3/83/4
11/43/83/4
11/4
Key Fluid type Calibration Display Communications Cable connector kit Future optionMoistureLimit relay
Product Configurator
IPD 12
#3
#
¤4
¤
MineralAggressiveAviation fuel
hazardous areas
Contact Parker for further information
Aviation fuelnon-hazardous
area
Only available with Display option 2
123
ACFTDMTD
AS4059
NoneLED
DigitalGSM
12
NoYes
12 RS232 / 4-20mA3#45
RS232 / 0-5VRS232 / RS485
RS232 / CANBUS
13
0 0Yes
NoDeutsch DT Series ConnectorM12, 8 Pin Plug Connector*
22
Parker HannifinHydraulic Filter Division EuropeFDHB200UK.
icountPDOnline Particle Detector
123
#4
12
Customer ValueProposition:Parker Filtration’s icountBS is aunique and complete solutionto providing in-the-field fluidbottle sampling using provenon-board, laser based technology.icountBS is a product from thenext generation of Parker’s fluidparticle analysis and monitoringproducts and provides an effectivealternative to external laboratoryservices.
icountBSBottle Sampler
Contact Information:Parker HannifinHydraulic Filter Division Europe
European ProductInformation CentreFreephone: 00800 27 27 5374(from AT, BE, CH, CZ, DE, EE, ES,FI, FR, IE, IT, PT, SE, SK, UK)[email protected]
www.parkerhfde.com
Product Features:
Quick sample bottle analysis•with variable test time optionsfrom 15 seconds and volumecapacities from 10ml.Repeatable and re-producible•result performance toISO4406:1999 and NAS1638particle count distributions.On-board compressor and•‘shop’ air capability.
Design concept allowing•for portability. DC andrechargeable battery packpower option built in.6 fixed channel size analysis.•Fluid resistant touch type•screen panel.Internal thermal printer.•
23
The complete solution - industrialdesign combinedwith stateof the art technologyThe icountBS - Bottle Samplerfrom Parker with its innovativeindustrial design has beendeveloped for customerslooking for state ofthe art technology, attentionto detail and the compactnessof a permanent laboratoryparticle analysis model.Combine this with on-board, laserbased, leading edge technologyto bring to all industries a trulyrevolutionary Particle Counter.The icountBS is a product fromthe next generation of Parker’sfluid particle analysis andmonitoring innovations.The IBS features an easy to useinteractive touch screen,environmentally controlledpressurized bottle chamber for airbubble suppression via aninternal compressor pump, withautomated door lockingmechanism, sample tubecleaning sleeve minimizingcontamination cross over, andan internal printer.The icountBS benefits from
Parkers knowledge andexperience of providing bottleanalysis equipment to the marketover the last 15 years.This experience comes fromselling market leading innovativesolutions and by having front linecondition monitoring products forall sectorsof fluid analysis opportunities. Theunit was at every stage developedwith the customers voice in mind.
24Parker HannifinHydraulic Filter Division Europe
icountBS - BottleSampler Features& Benefits• Quick sample bottle analysiswith variable test time optionsfrom 15 seconds and volumecapacities from 10ml.
• Repeatable and re-producibleresult performance toISO4406:1999 and NAS1638particle count distributions. Forother calibration standards consultParker CMC.
• On-board compressor and ‘shop’air capability.
• Design concept allowing forportability. DC and rechargeablebattery pack power options built in.
• Cost-effective and economicalalternative solution to externallaboratory services.
• 6 fixed channel size analysis.
• Fluid resistant touch typescreen panel.
• Sample tube self cleaning sleeveminimizing contaminationcross over.
• Internal thermal printer.
25
Analysing the test results
Targetcontamination
class toISO 4406: 1999
Suggested maximumparticle level Sensitivity Type of system Typical components
4 μm(c) 6 μm(c) 14 μm(c) 4 μm(c) 6 μm(c) 14 μm(c)
15 13 9 16,000 4,000 250 Supercritical
Silt-sensitive controlsystems with very highreliability. Laboratory
or aerospace
High performanceservo valves
17 15 11 64,000 16,000 1,000 Critical
High performance servoand high pressure long life
systems, e.g. aircraft,machine tools etc.
Industrial servo valves
18 16 13 130,000 32,000 4,000 Veryimportant
High quality reliablesystems. General machine
requirements
Piston pumps, proportionalvalves, compensated flow
controls
20 18 14 500,000 130,000 8,000 ImportantGeneral machinery andmobile systems. Mediumpressure, medium capacity
Vane pumps, spool valves
21 19 15 1,000,000 250,000 16,000 Average
Low pressure heavyindustrial systems,
or applications where longlife is not critical
Gear pumps, manual andpoppet valves, cylinders
23 21 17 4,000,000 1,000,000 64,000 Mainprotection
Low pressure systemswith large clearances Ram pumps
Notes:
Tables have been generated by organisations in various industries.
Some of the tables are defined in cumulative counts, e.g. ‘>6µm’ and others are represented as differential counts e.g. ‘6-14µm’.
All µm(c) refer to MTD distributions. All µm references will refer to ACFTD distributions.
All standards are in counts per 100ml and provide easy methods for converting particle counts into limits that are simpleto interpret. By noting the requirements of the standard, particle counts can be accurately converted to contamination levels.
Once the automatic oil sampletest has been completed, whatnext?Solid contaminants in fluid powersystems vary in size, shape, formand quantity. The most harmfulcontaminants are normally between6 microns and 14 microns. The ISOcode is the preferred method ofreporting quantity of contaminants.
The ISO code number correspondsto contamination levels relatingto three sizes.
The first scale number representsthe number of particles larger than
4µm(c) per 100 milliliters of fluid,the second number for particleslarger than 6 µm(c) per 100 millilitersof fluid and the third number forparticles larger than 14 µm(c) per100 milliliters of fluid.
For example: An ISO code 20/18/14indicates that there are between500,000 and 1,000,000 particleslarger than 4µm(c), and between130,000 and 250,000 particles largerthan 6 µm(c), and between 4,000and 8,000 particles larger than14µm(c).
icountBS reporting and dataIn addition to the ‘raw data’ printoutof ISO compliant data from theicountBS’s on-board printer, icountMini-lab described on page 7 offersthe user the advantage of a 2-pagereport template providing hardcopy data on ISO and NASindividual counts and averagecontamination results.
Component Cleanliness GuideSuggested acceptable contamination levels for various hydraulic systems
*Did you know the best human eye can only see particles above40µ(c)?
26Parker HannifinHydraulic Filter Division Europe
icountBS Product Specification
Order your icountBSNow!
Principle of Operation Laser based light obscuration
Calibration Dust MTD or ACFTD
Dimensions H=530 x W=190 (210 Door) x D=410 (mm)
Weight 18Kg
Mechanical Composition Stainless steel 316, plated mild steel and aluminium
Plastics Composition Precision polyurethane RIM mouldings and ABS plastic
Environmental Operating Temperature(Tested) +5°C to + 60°C
Operating RH range 20 – 85% (Tested at 30oC, no condensation)
Storage Temperature -40°C to + 90°C
Storage RH range 10 – 90% (Tested at 30oC, no condensation)
Channel Sizes MTD - ≥4μ(c),≥6μ(c),≥14μ(c),≥21μ(c),≥38μ(c), ≥70μ(c) ACFTD - ≥2μ,≥5μ,≥15μ,≥25μ,≥50μ,≥100μ
Analysis Range ISO 7 to 21, NAS 0 to 12
Contamination Standards MTD - ISO 4406:1999 & NAS 1638 ACFTD - ISO 4406:1987, ISO 4406:1991 & NAS 1638For further contamination standards consult Parker CMC
Calibration Standard ISO MTD and ACFTD calibration to traceable ISO Standards. (Contact Parker CMC for further details).
Fluid Management Maximum single sample = 100ml Minimum single sample = 10ml
Possible Test Configurations User selectable from single test up to 5 tests per run (eg.1x100ml up to 5 x50ml per run)
Pre-Test Flush Volume Minimum = 10ml, Maximum = 100ml
Viscosity Range 1-400 cSt
Fluid CompatibilityMineral oils, petroleum and hydrocarbon based fluids (consult manufacturer)and some esters (consult manufacturer).
Sample Bottle Size No specific bottle required. Maximum size = 75 (Dia) x 150 (H) mm. Maximum Volume = 250ml
Memory Storage 500 Tests (capacity warning after 450 tests)
Output Display Backlight 256 Colour STN Transmissive
Output Display Resolution 320 x 3(R.G.B)(H) x 240(W) dots
Display Active Area 115(H) x 86(W) mm
Data Input Via icon driven resistive touch screen
Printer Thermal dot-line printing
Printer Paper Ø50mm – (57mm x 25mm)
Test Certification Calibration & Certificate of Conformity
Power Supply 12Vdc@ 6.60Amps, 80 watts max.
Battery Power 2 Hours (recommended to be fully charged every 3 months)
Battery Stand-By Time 1 month (then 1 hour of operation)
Battery Fuse 6.3 Amps (anti-surge)
Air pressure Source 3.5 bar internal Mini-compressor ors 7 Bar shop air
27
icountBS – Bottle SamplerOrdering InformationKey Fluid Type Calibration Future Option
FutureOption
FutureOption
FutureOption
TransportationCase
Power SupplyRegion
IBS 1 Mineral 1 ACFTD 0 Lab Unit 0 0 1 0 None 0 UK
2 MTD 1# Mini-labPackage 1# Case 1 USA
# Contact Parker for furtherdetails 2 Europe
Key Fluid Type Calibration Future OptionFutureOption
FutureOption
FutureOption
TransportationCase
Power SupplyRegion
IBS 1 2 0 0 0 1 0 0
IBS 1 2 0 0 0 1 0 1
IBS 1 2 0 0 0 1 0 2
Accessories Part Number
250ml Sample Bottle ACC6NW001
Sample Bottle Pack (50) ACC6NW002
Vapour/Waste Bottle ACC6NW003
Printer Paper Reel (x1) ACC6NW005
UK Power Supply ACC6NW006
USA Power Supply ACC6NW007
European Power ACC6NW008
Transit Case Contact Parker
1m Waste Tube (Clear) ACC6NW009
1m Vapour Hose (Blue) ACC6NW010
USB Memory Stick ACC6NW011
icountBS CD Manual ACC6NW012
Verification Fluid SERMISC049
WARNING – USER RESPONSIBILITY
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTSDESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURYAND PROPERTY DAMAGE.
- This document and other information from Parker Hannifin Corporation, its subsidiariesand authorized distributors provide product or system options for further investigationby users having technical expertise.
- The user, through its own analysis and testing is solely responsible for making the finalselection of the system and components and assuring that all performance, endurance,maintenance, safety and warning requirements of the application are met. The usermust analyze all aspects of the application, follow applicable industry standards,and follow the information concerning the product in the current product catalogue andin any other materials provided by Parker or its subsidiaries or authorized distributors.
- To the extent that Parker or its subsidiaries or authorized distributors providecomponent or system options based upon data or specifications provided by the user,the user is responsible for determining that such data and specifications are suitableand sufficient for all applications and reasonably foreseeable uses of the componentsor systems.
Offer of salePlease contact your Parker representation for a detailed ‘offer of sale’.
28
Obtain your sampleof hydraulic oil.Step 1
Take the 2 minute off-lineoil sample test.
Step 2
View your results and runa report immediately.Step 3
Introducing the NEW icount‘Mini-lab’ – The effective wayof utilising your icountBS
Kit comprises: icountBS. Flat-pack trolley. 30 sample bottles. Optional Laptop/software/printer and cables
NEWPRODUCT
How clean is your hydraulic system?Contamination Control is only an oil sampleaway with our easy, 3-Step fluid analysis service.For more details contact: [email protected]
29
30Parker HannifinHydraulic Filter Division Europe
Improving aftermarket support for condition monitoring products.
CMC Service CentresGlobal Support for CMC products
Parker’s fluid Condition Monitoring Service Centres canbe found currently in 10 locations around the globe, onalmost every continent. Our experience and expertise influid condition monitoring and analysis ensure we are THEauthority within our industry.
Each location offers first class aftermarket support forCondition Monitoring products, giving:
Direct Contact for End Users.•
Quick and confident technical support to assist you•in maintaining an efficient and trouble free monitoringprocess.
Faster turn around for annual calibration verification,•resulting in the product not having to come back tocountry of manufacture.
Parker also offers on the icountACM20 laboratory unit:
A six monthly field use verification sample for•confident product performance.
An extended two year warranty, giving confidence in•product readiness.
Visit www.parkerhfde.com/condition/service/ to find yournearest location and contact details.
Parker returns policy andcalibration procedureEach product returned to anapproved Parker Service Centre willhave the following:
A visual inspection of all casecomponents.
If any components from the support case requirereplacing, please notify the Service Centre at the time ofreturn.
Parker holds no responsibility for case contents and willonly replace parts if required or deemed necessary.
An external inspection of the complete assembly.
The particle counter will be thoroughly checked for signsof damage or misuse and if necessary an estimate of thecost of repair will be provided.
Full function test, including pressuretest up to 420 bar (6,000 psi) andflow test.
This includes visual inspection ofinternal parts, checking for leakages ordamage.
Replacement of any defective or damaged parts.
No corrective work will be carried out on the particlecounter without the authorization from the end user. Onlyupon the go-ahead, will the unit be repaired.
Recalibration (with a Certificate valid for 12 months).
Each unit is calibrated to the relevant ISO standards.
The recalibration procedure does not include thereplacement of any damaged components that havebeen deemed defective through negligence or misuse.
AEROSPACEKey Markets( Aircraft engines( Business & general aviation( Commercial transports( Land-based weapons systems( Military aircraft( Missiles & launch vehicles( Regional transports( Unmanned aerial vehicles
Key Products( Flight control systems
& components( Fluid conveyance systems( Fluid metering delivery
& atomization devices( Fuel systems & components( Hydraulic systems & components( Inert nitrogen generating systems( Pneumatic systems & components( Wheels & brakes
CLIMATE CONTROLKey Markets( Agriculture( Air conditioning( Food, beverage & dairy( "'*, !+',#+,! $ %,)'+-&( Precision cooling( Processing( Transportation
Key Products( CO2 controls( Electronic controllers( Filter driers( Hand shut-off valves( Hose & fittings( Pressure regulating valves( Refrigerant distributors( Safety relief valves( Solenoid valves( Thermostatic expansion valves
FILTRATIONKey Markets( Food & beverage( Industrial machinery( Life sciences( Marine( Mobile equipment( Oil & gas( Power generation( Process( Transportation
Key Products( Analytical gas generators( Compressed air & gas filters( Condition monitoring( Engine air, fuel & oil filtration
& systems( Hydraulic, lubrication &
coolant filters( Process, chemical, water
& microfiltration filters( Nitrogen, hydrogen & zero
air generators
ELECTROMECHANICALKey Markets( Aerospace( Factory automation( Life science & medical( Machine tools( Packaging machinery( Paper machinery( Plastics machinery & converting( Primary metals( Semiconductor & electronics( Textile( Wire & cable
Key Products( AC/DC drives & systems( Electric actuators, gantry robots
& slides( Electrohydrostatic actuation systems( Electromechanical actuation systems( Human machine interface( Linear motors( Stepper motors, servo motors,
drives & controls( Structural extrusions
PNEUMATICSKey Markets( Aerospace( Conveyor & material handling( Factory automation( Life science & medical( Machine tools( Packaging machinery( Transportation & automotive
Key Products( Air preparation( Brass fittings & valves( Manifolds( Pneumatic accessories( Pneumatic actuators & grippers( Pneumatic valves & controls( Quick disconnects( Rotary actuators( Rubber & thermoplastic hose
& couplings( Structural extrusions( Thermoplastic tubing & fittings( Vacuum generators, cups & sensors
FLUID & GAS HANDLINGKey Markets( Aerospace( Agriculture( Bulk chemical handling( Construction machinery( Food & beverage( Fuel & gas delivery( Industrial machinery( Mobile( Oil & gas( Transportation( Welding
Key Products( Brass fittings & valves( Diagnostic equipment( Fluid conveyance systems( Industrial hose( PTFE & PFA hose, tubing &
plastic fittings( Rubber & thermoplastic hose
& couplings( Tube fittings & adapters( Quick disconnects
HYDRAULICSKey Markets( Aerospace( Aerial lift( Agriculture( Construction machinery( Forestry( Industrial machinery( Mining( Oil & gas( Power generation & energy( Truck hydraulics
Key Products( Diagnostic equipment( Hydraulic cylinders
& accumulators( Hydraulic motors & pumps( Hydraulic systems( Hydraulic valves & controls( Power take-offs( Rubber & thermoplastic hose
& couplings( Tube fittings & adapters( Quick disconnects
PROCESS CONTROLKey Markets( Chemical & refining( Food, beverage & dairy( Medical & dental( Microelectronics( Oil & gas( Power generation
Key Products( Analytical sample conditioning
products & systems( Fluoropolymer chemical delivery
fittings, valves & pumps( High purity gas delivery fittings,
valves & regulators( Instrumentation fittings, valves
& regulators( Medium pressure fittings & valves( Process control manifolds
SEALING & SHIELDINGKey Markets( Aerospace( Chemical processing( Consumer( Energy, oil & gas( Fluid power( General industrial( Information technology( Life sciences( Military( Semiconductor( Telecommunications( Transportation
Key Products( Dynamic seals( Elastomeric o-rings( EMI shielding( Extruded & precision-cut,
fabricated elastomeric seals( Homogeneous & inserted elastomeric
shapes( High temperature metal seals( Metal & plastic retained composite
seals( Thermal management
Parker’sMotion&Control TechnologiesAt Parker, we’re guided by
a relentless drive to help
our customers become more
productive and achieve
higher levels of profitability
by engineering the best sys-
tems for their requirements.
It means looking at customer
applications from many
angles to find new ways to
create value. Whatever the
motion or control technology
need, Parker has the experi-
ence, breadth of product and
global reach to consistently
deliver. No company knows
more about motion and con-
trol technology than Parker.
31
Parker Hannifin (UK) Ltd.Hydraulic Filter Division EuropeCondition Monitoring CentreTel: +44(0)1842 763299Email: [email protected]
AE – UAE, DubaiTel: +971 4 [email protected]
AR – Argentina, Buenos AiresTel: +54 3327 44 4129
AT – Austria, Wiener NeustadtTel: +43 (0)2622 [email protected]
AT – Eastern Europe,Wiener NeustadtTel: +43 (0)2622 23501 [email protected]
AU – Australia, Castle HillTel: +61 (0)2-9634 7777
AZ – Azerbaijan, BakuTel: +994 50 2233 [email protected]
BE/LU – Belgium, NivellesTel: +32 (0)67 280 [email protected]
BR – Brazil, Cachoeirinha RSTel: +55 51 3470 9144
BY – Belarus, MinskTel: +375 17 209 [email protected]
CA – Canada, Milton, OntarioTel: +1 905 693 3000
CH – Switzerland, EtoyTel: +41 (0) 21 821 02 [email protected]
CL – Chile, SantiagoTel: +56 2 623 1216
CN – China, ShanghaiTel: +86 21 5031 2525
CZ – Czech Republic, KlecanyTel: +420 284 083 [email protected]
DE – Germany, KaarstTel: +49 (0)2131 4016 [email protected]
DK – Denmark, BallerupTel: +45 43 56 04 [email protected]
ES – Spain, MadridTel: +34 902 33 00 [email protected]
FI – Finland, VantaaTel: +358 (0)20 753 [email protected]
FR – France, Contamine s/ArveTel: +33 (0)4 50 25 80 [email protected]
GR – Greece, AthensTel: +30 210 933 [email protected]
HK – Hong KongTel: +852 2428 8008
HU – Hungary, BudapestTel: +36 1 220 [email protected]
IE – Ireland, DublinTel: +353 (0)1 466 [email protected]
IN – India, MumbaiTel: +91 22 6513 7081-85
IT – Italy, Corsico (MI)Tel: +39 02 45 19 [email protected]
JP – Japan, TokyoTel: +(81) 3 6408 3901
KR – South Korea, SeoulTel: +82 2 559 0400
KZ – Kazakhstan, AlmatyTel: +7 7272 505 [email protected]
LV – Latvia, RigaTel: +371 6 745 [email protected]
MX – Mexico, ApodacaTel: +52 81 8156 6000
MY – Malaysia, Shah AlamTel: +60 3 7849 0800
NL – The Netherlands,OldenzaalTel: +31 (0)541 585 [email protected]
NO – Norway, SkiTel: +47 64 91 10 [email protected]
NZ – New Zealand, Mt WellingtonTel: +64 9 574 1744
PL – Poland, WarsawTel: +48 (0)22 573 24 [email protected]
PT – Portugal, Leca da PalmeiraTel: +351 22 999 [email protected]
RO – Romania, BucharestTel: +40 21 252 [email protected]
RU – Russia, MoscowTel: +7 495 [email protected]
SE – Sweden, SpångaTel: +46 (0)8 59 79 50 [email protected]
SG – SingaporeTel: +65 6887 6300
SK – Slovakia, Banská BystricaTel: +421 484 162 [email protected]
SL – Slovenia, Novo MestoTel: +386 7 337 [email protected]
TH – Thailand, BangkokTel: +662 717 8140
TR – Turkey, IstanbulTel: +90 216 [email protected]
TW – Taiwan, TaipeiTel: +886 2 2298 8987
UA – Ukraine, KievTel +380 44 494 [email protected]
UK – United Kingdom,WarwickTel: +44 (0)1926 317 [email protected]
US – USA, ClevelandTel: +1 216 896 3000
VE – Venezuela, CaracasTel: +58 212 238 5422
ZA – South Africa,Kempton ParkTel: +27 (0)11 961 [email protected]
Bulletin: FDCB417UK 06/2009
Your local authorized Parker distributor
© 2009 Parker Hannifin Corporation. All rights reserved.
Parker Worldwide
European Product Information Centre
Free phone: 00 800 27 27 5374
(from AT, BE, CH, CZ, DE, DK, ES, FI, FR, IE,
IT, NL, NO, PL, PT, RU, SE, UK, ZA)