GHG EMISSION CONTROL- A PROACTIVE ELECTRICAL ASSET MANAGEMENT
THROUGH ULTRASOUND TECHNOLOGY
Event/Meeting
Date & Venue
2
Problem Definition
RMU Flashover SF6 Gas Leakage
High Revenue Losses due to R&M Cost
Unsafe WorkingEnvironment
High Down Time
Customer dissatisfaction
3
Present technology not sufficient to prevent RMUs failure and gas leakage
SF6 gas Leakage from RMUs adding to Global warming
Switch Gears produce sound before the abnormality becomes critical
Sound is produced due to ionization which in infant stage is in Ultrasound region and the sound is variable
Corresponding to the sound, there must be a pattern as well
Analysis of the wave pattern produced due to ionization can be used to identify the nature of fault and the criticality
Outcome of Analysis
Need of a Technology:Proactively Detects the Abnormality in the RMUs
Fix the Gas Leakage Problem
They are more directional and travel in a straight line. Localized to the source of emission.
Discharges in Power system that generally produce Ultrasonic Frequency:
Characteristic Phenomena
Arcing
Tracking
Corona
Not possible to capture at the
initial stage
Not possible to detect by other
methods like Infrared Scanning
No standard guideline
4
CORONA IDENTIFICATION
• Hissing Noise• Uniform peaks at equal
intervals of time• Frequency domain pattern
has harmonics of the line frequency and they are visible in its pattern
• Corona discharge happens at the peak of the cycle
• Corona discharge produces ozone and nitrous oxide
5
• Low current pathway from top to ground through the insulator.
• Can happen anywhere in the positive cycle.
• Harmonics are not present.
• Less uniformity in pattern and popping sound occurs.
• Advantage: Identification at this stage can prevent the switch gear failure
TRACKING IDENTIFICATION
6
• High Current pathway from top to ground through insulator which don’t even require high voltage.
• It is quick and abrupt with buzzing sound.
• Burst of Energy extending for large periods of time.
• Most random pattern so it is easily recognizable.
ARCING IDENTIFICATION
7
8
2012-20130
200
400
600
800
1000
1200
1400
1600
1800
20001845
240
No. of RMUs ScannedNo. of RMU Failed
Global and Local Impact Greenhouse gas leads to Global
Warming Amount of SF6 Gas in each RMU
breaker chamber= 3 Kg Global Warming Potential of SF6 gas=
23900 For a Failure of one RMU, SF6 Gas
escaped= (23900*10-9 *3=) 0.0000717 Million Metric Tons of Carbon-di-Oxide Equivalent (MMTCDE).
In 2012-2013, 240 Nos. of RMUs failed resulting into the escaping of SF6 gas equivalent to(0.0000717*240=) 0.017208MMTCDE
9
Ultrasound Scanning
Abnormality Frequency(Hz) Intensity
Corona50,100,150,200,250,300,350…all harmonics
Between -8.0 dBμV to -5 dBμV
Tracking 50,100,150,200.Between -5.0 dBμV to -2.0 dBμV
Arcing No component of Line Frequency
Greater than -2.0 dBμV
10
Proactive SF6 Gas Leakage Detection and Fixing
Proactive SF6 gas Leakage Detection in the Switch Gears is done using a gas leakage detector.
Leakage points are marked for further action.
Unique compound consisting of poly chlorides is used as corrective action for the leakage points identified
Refurbishment of 5 nos. of breaker chambers that have even exploded using the unique compound thus reusing and revenue saving is also ensured
GAS Leakage Detector
11
No. of RMUs
ScannedAbnormal
RMUsRMUs Failed
RMUs Saved
SF6 Escaped/ Prevented(MMTCDE)
2012-2013 1845 NA 240 0 0.0172080
2013-2014 2200 238 30 208 0.0149136
2014-2015 2565 250 14 236 0.0169212
2015-2016 3200 268 7 261 0.0187137
SF6 Gas Escaped Into Atmosphere
SF6 Gas Prevented From Escaping Into Atmosphere
Curtailed SF6 Gas Emission
Ultrasound Technology accompanied with Gas Leakage Detection have made it possible to diagnose Switch Gears in a way like a Doctor diagnoses patients
From 2013-14 to 2015-16, around 750 nos. of RMUs have been prevented from failure accounting to stopping of 0.05 MMTCDE from escaping into the environment which is around 2% of GHG emitted in India per year
12
Another Step: App for Carbon Reduction Man-Hour Optimization Earlier 20 Switch Gears Inspected per
dayNow 30 to 35 Switch gears are Scanned per day using the App. For Scanning the same number of switch
gears, number of vehicle based trips reduced by 50% reducing carbon emission.
Centralized Data Record Center Earlier paper was used to record
data on site.Now data recording through app has quashed the use of Paper. Scanning Data is available to
everybody at all the time without using paper.