(Hazardous Materials and Risk Assessment) Initial Survey : Noel Arnold & Associates : 06 - Apr - 2008 Parsons Brinckerhoff : 03 - Jan - 2017 School : Sydney Technical High School (8141) Asbestos Register Region : Sydney State Electorate : Kogarah Local Government Area : Rockdale Reviewed By : Register Issue Date : Thursday, 23 Mar 2017 Page 1 of 22 8141 - Sydney Technical High School
Transcript
Page 1: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

(Hazardous Materials and Risk Assessment)

Initial Survey : Noel Arnold & Associates : 06 - Apr - 2008

Parsons Brinckerhoff : 03 - Jan - 2017

School : Sydney Technical High School (8141)

Asbestos Register

Region : Sydney

State Electorate : Kogarah

Local Government Area : Rockdale

Reviewed By :

Register Issue Date : Thursday, 23 Mar 2017 Page 1 of 228141 - Sydney Technical High School

Page 2: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00A - Administration/Various - 1958 - Brick/Block (Brick/Block)

Exterior

Ceiling Void Packing

8141/B00A/Ceiling Void/S23

1m2 Variable positions

Some Damage - Unsealed (3)

Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Medium Priority (4-5)

Ceiling Void AC Fragments/Debris

8141/B00A/Ceiling Void/S24

500m2 Throughout Poor Condition - Extensive Damage (4)

Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Medium Priority (4-5)

Underfloor Voids No Asbestos Found

Interior

B00A - R0001 - General Storeroom

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R0002 - Computer Learning Space

No Asbestos

B00A - R0003 - General Learning Space

No Asbestos

B00A - R0004 - General Learning Space

No Asbestos

B00A - R0005 - General Learning Space

No Asbestos

B00A - R0006 - General Learning Space

No Asbestos

B00A - R0007 - General Learning Space

No Asbestos

B00A - R0008 - General Learning Space

No Asbestos

B00A - R0009 - General Learning Space

No Asbestos

B00A - R0010 - Staff Study

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R0012 - Staff - Toilet

No Asbestos

B00A - R0014 - Main Switchroom

No Asbestos

B00A - R0015 - General Storeroom

No Asbestos

B00A - R0016 - General Storeroom

No Asbestos

B00A - R0017 - Staff - Toilet

No Asbestos

B00A - R0018 - Leading Teacher

No Asbestos

B00A - R0019 - Staff - Toilet

No Asbestos

B00A - R0020 - General Learning Space

Register Issue Date : Thursday, 23 Mar 2017 Page 2 of 228141 - Sydney Technical High School

Page 3: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R0021 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R0022 - Laboratory L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R0023 - Preparation

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R0024 - Laboratory L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R0025 - Staff Study

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R0026 - General Storeroom

No Asbestos

B00A - R0037 - Pupil Entry

No Asbestos

B00A - R0038 - Pupil Entry

No Asbestos

B00A - R0039 - External Movement

No Asbestos

B00A - R0040 - Clinic-Toilets

No Asbestos

B00A - R0041 - Clinic - Boys

No Asbestos

B00A - R0042 - Leading Teacher

No Asbestos

B00A - R0043 - Deputy Principal Office

No Asbestos

B00A - R0044 - Principal Office

No Asbestos

B00A - R0045 - Interview/Office - Type 1

No Asbestos

B00A - R0046 - Movement

No Asbestos

B00A - R0047 - Duplicating Workroom

No Asbestos

B00A - R0048 - Interview/Office - Type 1

No Asbestos

B00A - R0049 - Interview/Office - Type 1

No Asbestos

B00A - R0050 - Public Entry

No Asbestos

B00A - R0051 - External Movement

No Asbestos

B00A - R0054 - Administration - Clerical

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 3 of 228141 - Sydney Technical High School

Page 4: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00A - R0055 - General Storeroom

No Asbestos

B00A - R0056 - Pupil Entry

No Asbestos

B00A - R0058 - Staff Study

No Asbestos

B00A - R0059 - Stairs

No Asbestos

B00A - R0060 - Stairs

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R0061 - Stairs

No Asbestos

B00A - R0062 - Sport Equipment Store

No Asbestos

B00A - R0063 - Movement

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R0065 - Toilet - Lobby

No Asbestos

B00A - R0066 - Staff - Toilet

No Asbestos

B00A - R0067 - Toilet - Lobby

No Asbestos

B00A - R0068 - Staff - Toilet

No Asbestos

B00A - R0069 - Movement

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00A/R0069/Floor Coverings Res/Textile/S31 No Asbestos Detected

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R0070 - Movement

No Asbestos

B00A - R0071 - External Movement

No Asbestos

B00A - R1001 - Cleaning Supplies Store

No Asbestos

B00A - R1002 - Staff Study

No Asbestos

B00A - R1003 - Computer Store

No Asbestos

B00A - R1004 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1005 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1006 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1007 - General Learning Space

Register Issue Date : Thursday, 23 Mar 2017 Page 4 of 228141 - Sydney Technical High School

Page 5: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1008 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1009 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1010 - General Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1011 - Interview/Office - Type 1

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00A/R1011/Floor Coverings Res/Textile/S32

12m2 Throughout Minimal Damage (2) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00A - R1012 - Staff Study

No Asbestos

B00A - R1013 - Interview/Office - Type 1

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R1014 - Security Store

No Asbestos

B00A - R1015 - General Storeroom

No Asbestos

B00A - R1016 - Security Store

Non Accessible

B00A - R1017 - Staff - Toilet

No Asbestos

B00A - R1018 - General Storeroom

No Asbestos

B00A - R1019 - Commonroom

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1020 - Performance Workspace

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1021 - General Storeroom

No Asbestos

B00A - R1022 - Laboratory L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1023 - Preparation

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1024 - Laboratory L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00A/R0057/Ceiling Structures/Linings/S2 No Asbestos Detected

B00A - R1025 - Staff Study

No Asbestos

B00A - R1027 - Computer Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R1028 - Movement

Register Issue Date : Thursday, 23 Mar 2017 Page 5 of 228141 - Sydney Technical High School

Page 6: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R1029 - Stairs

No Asbestos

B00A - R1030 - Stairs

No Asbestos

B00A - R1031 - Stairs

No Asbestos

B00A - R1032 - Movement

Ceiling Structures/Linings Vermiculite

8141/B00A/R0063/Ceiling Structures/Linings/S30 No Asbestos Detected

B00A - R1033 - External Stairs

No Asbestos

B00A - R9001 - Office/Store

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R9002 - Student Canteen

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R9003 - Office/Store

Floor Coverings Res/Textile

Vinyl Tiles (Under Floor Covering/Carpet)

8141/B00A/R0010/Floor Coverings Res/Textile/S33 No Asbestos Detected

B00A - R9004 - Staff - Toilet

No Asbestos

B00A - R9005 - Movement

No Asbestos

B00A - R9006 - Toilets-Boys

No Asbestos

B00A - R9007 - Movement

No Asbestos

B00A - R9008 - General Storeroom

No Asbestos

B00A - R9009 - Cleaning Store - Distributed

No Asbestos

B00A - R9010 - External Movement

No Asbestos

B00A - R9011 - External Movement

No Asbestos

B00A - R9012 - Stairs

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 6 of 228141 - Sydney Technical High School

Page 7: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00B - Physical Education/Performing Arts - 1958 - Brick/Block (Brick/Block)

Exterior

Ceiling Void Non Accessible Area

- No safe access - Ceilings > 6m high

Underfloor Voids No Asbestos Found

Interior

B00B - M0001 - Plant

No Asbestos

B00B - M0002 - Performing Arts Store

No Asbestos

B00B - M0003 - Performing Arts Store

No Asbestos

B00B - M0004 - Stairs

No Asbestos

B00B - R0001 - Gymnasium

No Asbestos

B00B - R0002 - Staff Kitchen

No Asbestos

B00B - R0003 - Sport Equipment Store

No Asbestos

B00B - R0004 - General Storeroom

No Asbestos

B00B - R0005 - Staff - Toilet

No Asbestos

B00B - R0006 - Multi-Purpose Space

No Asbestos

B00B - R0008 - Movement

No Asbestos

B00B - R0009 - Movement

No Asbestos

B00B - R0010 - Performing Arts Changeroom

No Asbestos

B00B - R0011 - Stage

Wall Linings Internal Flat AC Sheeting

8141/B00B/R0011/Wall Linings Internal/S8

20m2 North facing, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00B - R0014 - Movement

No Asbestos

B00B - R0015 - Public Entry

No Asbestos

B00B - R0016 - Pupil Entry

No Asbestos

B00B - R0017 - General Assistants

No Asbestos

B00B - R0018 - Toilets-Unisex

No Asbestos

B00B - R0019 - Music Store

No Asbestos

B00B - R0020 - Toilets-Unisex

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 7 of 228141 - Sydney Technical High School

Page 8: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00B - R0021 - Movement

No Asbestos

B00B - R0022 - Control Room

No Asbestos

B00B - R0023 - Multi Media Store

No Asbestos

B00B - R0024 - Cleaning Store - Distributed

No Asbestos

B00B - R0025 - Stairs

No Asbestos

Ceiling Void Non Accessible Area

- No Safe Access - Ceiling >6m high

B00B - R0026 - Movement

No Asbestos

B00B - R0027 - External Movement

No Asbestos

B00B - R0028 - External Movement

No Asbestos

B00B - R9003 - Shower/Change

No Asbestos

B00B - R9004 - Staff Study

No Asbestos

B00B - R9006 - Sport Equipment Store

No Asbestos

B00B - R9007 - Chair Store

No Asbestos

B00B - R9008 - General Storeroom

No Asbestos

B00B - R9009 - External Movement

No Asbestos

B00B - R9010 - Movement

No Asbestos

B00B - R9011 - Staff Study

No Asbestos

B00B - R9012 - Stairs

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 8 of 228141 - Sydney Technical High School

Page 9: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block)

Exterior

Ceiling Voids - Flat Roof No Asbestos Found

Eaves Linings Flat AC Sheeting

Assumed Asbestos - Not possible to sample - Heights

120m2 North facing, South facing

Good Condition (1) Low (1) Low Priority (2-3)

Underfloor Voids No Asbestos Found

Interior

B00C - R0001 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0002 - Staff - Toilet

No Asbestos

B00C - R0003 - Cleaning Store - Distributed

No Asbestos

B00C - R0004 - Staff Study

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00C/R0004/Floor Coverings Res/Textile/S11

40m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00C - R0005 - Staff Study

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0006 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0007 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0008 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0009 - General Storeroom

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0010 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0011 - Distribution Board Cupboard Note: No inspection of live electrical installation.

No Asbestos

B00C - R0012 - Art Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0013 - Resources Store

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0014 - Art Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0015 - Resources Store

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

Register Issue Date : Thursday, 23 Mar 2017 Page 9 of 228141 - Sydney Technical High School

Page 10: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00C - R0016 - Resources Store

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0017 - Kiln Space

No Asbestos

B00C - R0018 - Resources Space

No Asbestos

B00C - R0019 - Staff - Toilet

No Asbestos

B00C - R0020 - Cleaning Store - Distributed

No Asbestos

B00C - R0021 - External Movement

No Asbestos

B00C - R0022 - Movement

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R0023 - Stairs

Ceiling Structures/Linings Vermiculite

8141/B00C/R0024/Ceiling Structures/Linings/S29 No Asbestos Detected

B00C - R0024 - Stairs

Ceiling Structures/Linings Vermiculite

8141/B00C/R0024/Ceiling Structures/Linings/S29 No Asbestos Detected

B00C - R1001 - General Storeroom

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1017/Ceiling Structures/Linings/S12

7m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00C - R1002 - Staff Study

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1003 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1004 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1005 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1006 - General Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1007 - Computer Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1008 - Computer Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1009 - Computer Resource

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1010 - General Storeroom

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1017/Ceiling Structures/Linings/S12

7m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Register Issue Date : Thursday, 23 Mar 2017 Page 10 of 228141 - Sydney Technical High School

Page 11: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00C - R1011 - Leading Teacher

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1012 - General Storeroom

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1013 - Cleaning Store - Distributed

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1014 - Distribution Board Cupboard Note: No inspection of live electrical installation.

No Asbestos

B00C - R1015 - Music Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1016 - Music Learning Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1017 - General Storeroom

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1017/Ceiling Structures/Linings/S12

7m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00C - R1018 - Staff Study

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R1019 - Movement

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1017/Ceiling Structures/Linings/S12

109m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00C - R1020 - Stairs

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1021/Ceiling Structures/Linings/S26

12m2 Throughout Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Low Priority (2-3)

B00C - R1021 - Stairs

Ceiling Structures/Linings Flat AC Sheeting

8141/B00C/R1021/Ceiling Structures/Linings/S26

12m2 Throughout Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Low Priority (2-3)

B00C - R9001 - General Assistants

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R9002 - General Storeroom

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R9003 - Darkroom Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R9004 - Darkroom Space

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R9005 - Toilets-Boys

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

B00C - R9006 - Maintenance Bulk Store

Ceiling Structures/Linings Vermiculite

8141/B00C/R0022/Ceiling Structures/Linings/S10 No Asbestos Detected

Register Issue Date : Thursday, 23 Mar 2017 Page 11 of 228141 - Sydney Technical High School

Page 12: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00D - Library/Science Learning - 1977 - Brick/Block (Brick/Block)

Exterior

Ceiling Voids - Raked Ceiling

No Asbestos Found

Underfloor Voids - Slab on Ground

No Asbestos Found

Eaves Linings Flat AC Sheeting

Assumed Asbestos - No safe access - Eaves >6m high

90m2 All surfaces Good Condition (1) Low (1) Low Priority (2-3)

Interior

B00D - M1001 - Seminar

No Asbestos

B00D - M1002 - Main Area

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - M1003 - General Storeroom

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - M1004 - Plant

Ceiling Structures/Linings Loose Fill

8141/B00D/M1004/Ceiling Structures/Linings/S9 No Asbestos Detected

B00D - M1005 - Stairs

Ceiling Structures/Linings Vermiculite

8141/B00D/R1016/Ceiling Structures/Linings/S28 No Asbestos Detected

B00D - M1006 - Stairs

Ceiling Structures/Linings Vermiculite

8141/B00D/R1016/Ceiling Structures/Linings/S28 No Asbestos Detected

B00D - R0001 - Laboratory L.S.

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

93m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00D - R0002 - Preparation

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

48m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00D - R0003 - Laboratory L.S.

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

93m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00D - R0004 - Apparatus Store

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

16m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

B00D - R0005 - Distribution Board Cupboard Note: No inspection of live electrical installation.

No Asbestos

B00D - R0006 - Laboratory L.S.

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

93m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Register Issue Date : Thursday, 23 Mar 2017 Page 12 of 228141 - Sydney Technical High School

Page 13: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R0007 - Preparation

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

48m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R0008 - Laboratory L.S.

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00D/R0004/Floor Coverings Res/Textile/S4

92m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R0009 - Movement

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R0011 - Main Switchroom

No Asbestos

B00D - R0012 - Cleaning Store - Distributed

No Asbestos

B00D - R0013 - External Movement

No Asbestos

B00D - R0014 - External Stairs

No Asbestos

B00D - R0015 - External Movement

No Asbestos

B00D - R1001 - Seminar

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1002 - Distribution Board Cupboard Note: No inspection of live electrical installation.

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1003 - Cleaning Store - Distributed

No Asbestos

B00D - R1004 - Seminar

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1005 - Seminar

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1007 - Audio Visual Workroom

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1008 - Workroom

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1009 - Librarian

Ceiling Structures/Linings Vermiculite

8141/B00D/R0002/Ceiling Structures/Linings/S5 No Asbestos Detected

B00D - R1010 - Staff - Toilet

No Asbestos

B00D - R1011 - Staff - Toilet

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 13 of 228141 - Sydney Technical High School

Page 14: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00D - R1012 - External Stairs

No Asbestos

B00D - R1013 - Stairs

No Asbestos

B00D - R1014 - Stairs

No Asbestos

B00D - R1015 - External Movement

No Asbestos

B00D - R1016 - Laboratory L.S.

Ceiling Structures/Linings Vermiculite

8141/B00D/R1016/Ceiling Structures/Linings/S28 No Asbestos Detected

Register Issue Date : Thursday, 23 Mar 2017 Page 14 of 228141 - Sydney Technical High School

Page 15: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00E - Technological & Applied Studies - 1958 - Brick/Block (Brick/Block)

Exterior

Underfloor Voids Flat AC Sheeting

8141/B00E/Underfloor Voids/S22

1m2 Throughout Some Damage - Unsealed (3)

Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Medium Priority (4-5)

Ceiling Void AC Fragments/Debris

8141/B00E/Ceiling Void/S25

1m2 Variable positions

Poor Condition - Extensive Damage (4)

Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Medium Priority (4-5)

Interior

B00E - R0001 - Design L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

80m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

20m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0002 - Staff Study

No Asbestos

B00E - R0003 - Design L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

80m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0004 - Resource/Project Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

5m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0005 - Materials Technology L.S.

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

20m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0006 - Materials Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

5m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0007 - Resource/Project Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

4m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0008 - Materials Technology L.S.

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

20m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0009 - Resource/Project Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

8m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0010 - Materials Technology L.S.

Register Issue Date : Thursday, 23 Mar 2017 Page 15 of 228141 - Sydney Technical High School

Page 16: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

8m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0011 - Materials Technology L.S.

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

30m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0012 - Materials Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

5m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0013 - Resource/Project Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

3m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0014 - Materials Technology L.S.

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

80m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

10m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0015 - Resource/Project Store

Wall Linings Internal Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

3m2 All surfaces, Upper portion

Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0016 - Computer Learning Space

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

80m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0017 - Resource/Project Store

No Asbestos

B00E - R0018 - Resource/Project Store

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0001/Ceiling Structures/Linings/S6

13m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00E - R0019 - Cleaning Store - Distributed

Ceiling Structures/Linings Flat AC Sheeting

8141/B00E/R0019/Ceiling Structures/Linings/S27

4m2 Throughout Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Low Priority (2-3)

B00E - R0020 - General Storeroom

No Asbestos

B00E - R0021 - Staff - Toilet

No Asbestos

B00E - R0022 - Staff Study

Floor Coverings Res/Textile

Vinyl Tiles

8141/B00E/R0022/Floor Coverings Res/Textile/S7 No Asbestos Detected

B00E - R0023 - Staff Study

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 16 of 228141 - Sydney Technical High School

Page 17: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00E - R0024 - Resource/Project Store

No Asbestos

B00E - R0025 - Welding Store

No Asbestos

B00E - R0026 - Welding Area

No Asbestos

B00E - R0027 - Resource/Project Store

No Asbestos

B00E - R0028 - Movement

No Asbestos

B00E - R0029 - Pupil Entry

No Asbestos

B00E - R0030 - Pupil Entry

No Asbestos

B00E - R9001 - General Storeroom

No Asbestos

B00E - R9002 - Movement

No Asbestos

B00E - R9003 - General Storeroom

No Asbestos

B00E - R9005 - Dust Extraction Space

No Asbestos

B00E - R9006 - General Storeroom

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 17 of 228141 - Sydney Technical High School

Page 18: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00F - General Learning - 2003 - Brick/Veneer (Brick/Veneer)

Exterior

Eaves Linings Flat AC Sheeting

8141/B00F/Eaves Linings/S15

30m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Gable Ends Flat AC Sheeting

8141/B00F/Eaves Linings/S15

10m2 East facing, West facing

Good Condition (1) Low (1)

Chrysotile (white asbestos)

Low Priority (2-3)

Wall Cladding Flat AC Sheeting

8141/B00F/Wall Cladding/S16 No Asbestos Detected

Ceiling Voids No Asbestos Found

Eaves Linings Flat AC Sheeting

8141/B00F/Eaves Linings/S17

30m2 Throughout Good Condition (1) Low (1)

Chrysotile (white asbestos) , Crocidolite (blue

asbestos)

Low Priority (2-3)

Gable Verge Lining Flat AC Sheeting

8141/B00F/Gable Verge Lining/S19

20m2 East & West Minimal Damage (2) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos) , Crocidolite (blue asbestos)

Low Priority (2-3)

Gable Ends Flat AC Sheeting

8141/B00F/Gable Ends/S20

20m2 East & West Good Condition (1) Low (1)

Chrysotile (white asbestos) , Crocidolite (blue

asbestos)

Low Priority (2-3)

Underfloor Voids No Asbestos Found

Wall Cladding Flat AC Sheeting

8141/B00F/Wall Cladding/S21 No Asbestos Detected

Interior

B00F - R0001 - General Learning Space

No Asbestos

B00F - R0002 - Administration - Clerical

No Asbestos

B00F - R0003 - Movement

No Asbestos

B00F - R0004 - Movement

Wall Linings Internal Flat AC Sheeting

8141/B00F/R0005/Wall Linings Internal/S13

20m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00F - R0005 - General Storeroom

Wall Linings Internal Flat AC Sheeting

8141/B00F/R0005/Wall Linings Internal/S13

8m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00F - R0006 - Shower/Change

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 18 of 228141 - Sydney Technical High School

Page 19: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00G - Building Services - 2003 - Brick/Veneer (Brick/Veneer)

Exterior

Underfloor Voids - Slab on Ground

No Asbestos Found

Ceiling Voids No Asbestos Found

Interior

B00G - R0001 - General Storeroom

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 19 of 228141 - Sydney Technical High School

Page 20: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

B00H - General Learning - 1965 - Brick/Block (Brick/Block)

Exterior

Eaves Linings Flat AC Sheeting

8141/B00H/R0004/Ceiling Structures/Linings/S14

20m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

Eaves Linings Flat AC Sheeting

8141/B00H/Eaves Linings/S18

20m2 Throughout Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

Underfloor Voids No Asbestos Found

Ceiling Void No Asbestos Found

Interior

B00H - R0001 - General Learning Space

No Asbestos

B00H - R0002 - General Learning Space

No Asbestos

B00H - R0003 - Staff Kitchen

No Asbestos

B00H - R0004 - Movement

Ceiling Structures/Linings Flat AC Sheeting

8141/B00H/R0004/Ceiling Structures/Linings/S14

3m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00H - R0005 - Laundry

Ceiling Structures/Linings Flat AC Sheeting

8141/B00H/R0004/Ceiling Structures/Linings/S14

5m2 All surfaces Good Condition (1) Low (1)

Chrysotile (white asbestos) , Amosite (brown

asbestos)

Low Priority (2-3)

B00H - R0006 - Movement

No Asbestos

B00H - R0007 - Toilets-Unisex

No Asbestos

B00H - R0008 - Shower/Change

No Asbestos

B00H - R0009 - General Learning Space

No Asbestos

B00H - R0010 - General Learning Space

No Asbestos

B00H - R0011 - Movement

No Asbestos

Register Issue Date : Thursday, 23 Mar 2017 Page 20 of 228141 - Sydney Technical High School

Page 21: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Demountables

There are no Demountable(s) located at this school as per the AMS records as of 15 Feb 2017.

Register Issue Date : Thursday, 23 Mar 2017 Page 21 of 228141 - Sydney Technical High School

Page 22: (Hazardous Materials and Risk Assessment) · 8141 Sydney Technical High School 2017 Test Result B00C - General Learning/Art - 1964 - Brick/Block (Brick/Block) Exterior Ceiling Voids

ProductMaterial

Description ExtentLocation

ReferenceMaterial

ConditionRisk

Status

Sample No

ControlPriority

8141 Sydney Technical High School 2017

Test Result

Listing of Electronic Attachments as of 22/03/2017

Available Asbestos Related Electronic Files8141_ASB_010313_AMP.pdf

* Note : Refer to AMS for details of the attachment(s).

Register Issue Date : Thursday, 23 Mar 2017 Page 22 of 228141 - Sydney Technical High School