HGM400 Automatic Genset Controller (HGM410/HGM420) USER MANUAL Smartgen Technology
Transcript
  • HGM400 Automatic Genset Controller

    (HGM410/HGM420)

    USER MANUAL

    Smartgen Technology

  • Chinese trademark

    English trademark

    Smartgen make your generator smart

    Smartgen Technology Co., Ltd.

    No. 28 Jinsuo Road

    Zhengzhou City

    Henan Province

    P. R. China

    Tel: +86-371-67988888/67981888

    +86-371-67991553/67992951

    +86-371-67981000(overseas)

    Fax: 0086-371-67992952

    Web: http://www.smartgen.com.cn

    http://www.smartgen.cn

    Email: [email protected]

    All rights reserved. No part of this publication may be reproduced in any material form

    (including photocopying or storing in any medium by electronic means or other) without

    the written permission of the copyright holder.

    Smartgen Technology reserves the right to change the contents of this document

    without prior notice.

    Software Version

    Date Version Note

    2011-07-06 1.0 Original release.

    2012-03-15 1.1 Modify typical application.

    2012-10-30 1.2 Modify some details.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 3 of 30

    This manual is suitable for HGM400 series controller only.

    Clarification of notation used within this publication.

    SYMBOL INSTRUCTION

    NOTE

    Highlights an essential element of a procedure to ensure

    correctness.

    CAUTION!

    Indicates a procedure or practice, which, if not strictly observed,

    could result in damage or destruction of equipment.

    WARNING!

    Indicates a procedure or practice, which could result in injury to

    personnel or loss of life if not followed correctly.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 4 of 30

    Table of Contents

    1 SUMMARY.................................................................................. 5

    2 PERFORMANCE AND CHARACTERISTICS ............................. 5

    3 SPECIFICATION ......................................................................... 6

    4 OPERATION ............................................................................... 7

    4.1 PANEL KEYS ........................................................................................... 7

    4.2 PANEL DESCRIPTION ............................................................................ 8

    4.3 AUTOMATIC START/STOP OPERATION ............................................... 8

    4.4 MANUAL START/STOP OPERATION ................................................... 10

    5 PROTECTION .......................................................................... 10

    5.1 WARNINGS ........................................................................................... 10

    5.2 SHUTDOWN ALARM ............................................................................. 11

    6 CONNECTIONS ....................................................................... 13

    7 DEFINITION AND RANGE OF PARAMETERS ......................... 15

    7.1 PARAMETER CONTENTS AND RANGE (TABLE 1) ............................. 15

    7.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2) ......................................... 20

    7.3 PROGRAMMABLE INPUT 1-4 TABLE (ACTIVE WHEN CONNECT GND (B-)

    (TABLE 3) ...................................................................................................... 21

    7.4 SENSOR SELECT (TABLE 4) ............................................................... 22

    7.5 CONDITIONS OF CRANK DISCONNECT (TABLE 5) ........................... 22

    8 PARAMETERS SETTING ......................................................... 23

    9 SENSOR SELECT .................................................................... 24

    10 COMMISSIONING .................................................................... 25

    11 TYPICAL APPLICATION ........................................................... 26

    12 INSTALLATION ......................................................................... 28

    12.1 FIXING CLIPS ....................................................................................... 28

    12.2 OVERALL DIMENSION AND PANEL CUTOUT ..................................... 29

    13 FAULT FINDING ....................................................................... 30

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 5 of 30

    1 SUMMARY

    HGM400 series automatic controller, integrating digital, intelligent and network

    techniques, is used for automatic control system of generator. It can achieve automatic

    start/stop, data measuring and three remote functions (SG485 module is needed).

    The controller uses LCD display, optional Chinese, English, Spanish and Russian

    display interface with easy and reliable operation.

    HGM400 series automatic controller uses micro-processing technique which can carry

    out precision measuring, constant value adjustment, timing and threshold setting and

    etc.. All the parameters can be adjusted from front panel or through programmable

    interface (USB to LINK, can use SG72 adaptor) via PC. It can be widely used in all

    types of generator automatic control system for compact structure, simple connections

    and high reliability.

    2 PERFORMANCE AND CHARACTERISTICS

    HGM400 series controller has two variants:

    HGM410: Automatic Start Module, it controls generator to start/stop by remote start

    signal;

    HGM420: Based on HGM410, add mains AC monitoring, mains/generator automatic

    switching control (AMF), especially suitable for automatic control system composed by

    mains and generator.

    132x64 LCD with backlight, optional language interface (Chinese, English, Spanish

    and Russian), push-button operation;

    Adapt to 3 phase 4 wire, single phase 2 wire, 3 phase 3 wire and 2 phase 3 wire

    (120/240V), 50/60Hz power supply;

    Can measure and display 3-phase voltage, 3-phase current, frequency, and power;

    Mains Generator

    Line Voltage (Uab, Ubc, Uca) Line Voltage (Uab, Ubc, Uca)

    Phase Voltage (Ua, Ub, Uc) Phase Voltage (Ua, Ub, Uc)

    Frequency (HZ) Frequency (HZ)

    Load

    Current (IA, IB, IC)

    Active Power (KW)

    Reactive Power (KVar)

    Apparent Power (KVA)

    Power Factor (PF)

    Accumulated Energy (kWh)

    For mains: Over/under voltage, lack of phase; for generator: over/under voltage,

    over/under frequency, over current;

    Precision measure and display engine parameters,

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 6 of 30

    Temperature (WT), C/ F both are display

    Oil pressure (OP), kPa/Psi/Bar all be display

    Speed (SPD), RPM (unit)

    Voltage of Battery (VB) V (unit)

    Voltage of Charger (VD) V (unit)

    Hours counter (HC): Max. 999999 hours.

    Start times: Max.999999 times.

    Control protection: Automatic start/stop, switch on/off (ATS control) and fault

    display;

    With ETS, idle control, pre-heat control, acceleration and deceleration control, all

    are relay output;

    Parameters setting: Allow user to modify parameters and store them in internal

    FLASH, which cannot be lost even when power off. All the parameters can be

    adjusted from the front panel, or by PC via an SG72 adaptor;

    Types of temperature and pressure sensor can be directly used and user defined;

    Conditions of crank disconnect can be selected.(magnetic pickup, oil pressure,

    generator);

    Power supply range is (8~35)VDC, accommodating to different starting voltage;

    All parameters use digital modulation, abandoning analog modulation of

    conventional potentiometer, more reliability and stability;

    Modular design, flame retardant ABS shell, plug-in terminals, embedded mounting,

    compact structure, easy installation.

    3 SPECIFICATION

    Items Contents

    Working Voltage DC8.0V to 35.0V, continuous

    Power Consumption

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 7 of 30

    Programmable Relay Output 3 5A DC28V power supply

    Programmable Relay Output 4 5A AC250V voltage-free output

    Programmable Relay Output 5 5A AC250V voltage-free output

    Overall Dimensions 130mm x 112mm x 39mm

    Panel Cutout 110mm x 90mm

    CT Secondary Current 5A (rated )

    Working Condition Temperature: (-25~70)C;

    Humidity: (20~93)%RH

    Storage Condition Temperature: (-30~+80)C

    Protection Level

    IP55: when waterproof rubber gasket added

    between controller and its panel.

    IP42: when waterproof rubber gasket not added

    between controller and its panel.

    Insulation Intensity

    Object: among in input/output/power

    Quote standard: IEC688-1992

    Test way: AC1.5 kV/1min 3mA leakage current

    Weight 0.26kg

    4 OPERATION

    4.1 PANEL KEYS

    Stop/ Reset

    Can stop generator under Manual/Auto mode;

    Can reset shutdown alarm;

    Pressing this key at least 3 seconds can test panel

    indicators (Lamp Test),;

    During stopping process, pressing this again can stop

    generator immediately.

    Start To start genset under Manual or Manual Test mode.

    Manual

    Pressing this key will set the module into manual mode.

    Pressing this and up key can adjust LCD contrast.

    Automatic Pressing this key will set the module into auto mode.

    Set/Confirm

    Enter into Set menu after pressing this key;

    Shift cursor to confirm.

    Up/Increase

    Turning pages up;

    In parameter setting, shift cursor and increase values.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 8 of 30

    Down/Decrease

    Turning pages down;

    In parameter setting, shift cursor and decrease values.

    4.2 PANEL DESCRIPTION

    HGM410 Panel Indicators

    HGM420 Panel Indicators

    4.3 AUTOMATIC START/STOP OPERATION

    This mode is activated by pressing . LED indicator beside the key is illuminating

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 9 of 30

    which confirms this action.

    Start Sequence,

    1) HGM420: when mains is abnormal (over/under voltage, lack of phase), enter into

    Mains Abnormal Delay and LCD displays count-down timer. When the delay is

    over, Start Delay begins.

    2) HGM410: genset enters into Start Delay when Remote Start is active.

    3) Count- down timer of Start Delay is displayed in LCD.

    4) When start delay is over, preheat relay is outputting (if configured), Preheat Delay

    XX s is displayed in LCD.

    5) When preheat delay is over, fuel relay is outputting 1s and then start relay outputs; if

    genset failed to start during Start Time, fuel and start relays stop outputting and

    enter into Crank Rest Time and wait for next cranking.

    6) If genset failed to start within specified start times, the fourth line of LED will turn

    black and Fail to Start alarm will be displayed.

    7) Whatever time to start successfully, genset will enter into Safety on Run Time.

    During this period, alarms of low oil pressure, hi-temperature, under speed, charge

    failure and auxiliary input (be configured) are disabled. As soon as this delay is over,

    genset will enter into Start Idle Delay (if configured).

    8) During start idle delay, alarms of under speed, under frequency, under voltage are

    disabled. As soon as this delay is over, genset will enter into Warming Up Delay (if

    configured).

    9) When Warming Up Delay is over, the indicator is illuminating if gens normal. If

    engine voltage and frequency reach the load demand, closing relay outputs, genset

    takes load and indicator illuminates; if engine voltage and frequency appear

    abnormal, controller will alarm to shutdown (alarm is displayed in LCD).

    Stop Sequence,

    1) HGM420: during genset running, if mains normal, enters into Mains Normal Delay.

    When mains indicator illuminates, Stop Delay begins.

    2) HGM410: genset enters into Stop Delay when Remote Start is inactive.

    3) When stop delay is over, genset enters into Cooling Delay. Gens closing relay is

    open. After switch Transfer Rest Delay, mains closing relay outputs, mains will take

    load, power indicator of gens eliminates while indicator of gens illuminates.

    4) When entering Stop Idle Delay (if configured), Idle relay is energized to output.

    5) When entering ETS delay, ETS relay is energized to output, fuel relay is open.

    6) When entering Genset at Rest, automatically judge whether genset is stopped or

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 10 of 30

    not.

    7) When genset has stopped, enters into standby mode; if failed to stop, controller will

    alarm (Fail to Stop alarm will be displayed in LCD).

    4.4 MANUAL START/STOP OPERATION

    1) HGM420: Manual Mode is activated when press and its indicator illuminates.

    Press key, choose Manual Test Mode. Under the two modes, press key to

    start genset, it can automatically judge crank disconnect and accelerate to hi-speed

    running. If high temperature, low oil pressure, over speed and abnormal voltage

    occur during genset running, controller can effectively protect genset to stop (detail

    procedures please refer to No.4~9 of Auto start operation). Under Manual Mode ,

    if mains normal, load switch wont transfer; if mains abnormal, load switch will transfer

    to gens. Under Manual Test Mode, after genset normally runs in high speed, no

    matter mains normal or not, load will be transferred to gens.

    2) HGM410: Manual Mode is activated when press key and its indicator illuminates.

    Then press key to start generator, it can automatically judge crank disconnect and

    accelerate to hi-speed running. If hi-temperature, low oil pressure, over speed and

    abnormal voltage occur during genset running, controller can effectively protect

    genset to stop (detail procedures please refer to No.4~9 of Auto start operation).

    Controller will send closing signal when genset runs in high speed.

    3) Manual stop: pressing key can shut down the running genset. (detail procedures

    please refer to No.3~7 of Auto stop operation)

    5 PROTECTION

    5.1 WARNINGS

    When controller detects the warning signal, only alarm and not stop genset. The alarms

    are displayed in LCD.

    Warnings as following,

    No. Items Description

    1 High

    Temperature

    When controller detected the temperature is higher than

    preset and shutdown is prohibited, it will send a stop alarm

    signal and it will be displayed in LCD.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 11 of 30

    2 Low Oil

    Pressure

    When controller detected oil pressure is lower than the

    preset and shutdown is prohibited, it will send a stop alarm

    signal and it will be displayed in LCD.

    3 Gens Over

    Current

    When controller detected genset current is over the preset

    and delay value is more than preset, it will send a stop alarm

    signal and it will be displayed in LCD.

    4 Fail To Stop

    When generator cannot stop after the stop delay/ETS

    delay, controller will send warning alarm signal and it will be

    displayed in LCD.

    5 Low Fuel Level

    When controller detected the Low Fuel Level input is active,

    controller will send warning alarm signal and it will be

    displayed in LCD.

    6 Charge Failure

    When controller detected the charger voltage is lower than

    threshold, controller will send warning alarm signal and it will

    be displayed in LCD.

    7 Battery Low

    Voltage

    When controller detected the battery voltage is lower than

    threshold, controller will send warning alarm signal and it will

    be displayed in LCD.

    8 Battery Over

    Voltage

    When controller detected the battery voltage is higher than

    threshold, controller will send warning alarm signal and it will

    be displayed in LCD.

    9 Auxiliary

    Warning

    When controller detected the input port external warning is

    active, controller will send warning alarm signal and it will be

    displayed in LCD.

    10 Loss Of Speed

    Signal

    When controller detected engine speed is 0 (the delay is 0),

    a warning alarm signal will be sent and displayed in LCD.

    11 Low Coolant

    Level

    When controller detected the low coolant level input is active,

    controller will send warning alarm signal and it will be

    displayed in LCD.

    12 Temp. Sensor

    Open

    When temperature sensor opens circuit and the input is

    active, controller will send a stop alarm signal and it will be

    displayed in LCD.

    13 Oil Pressure

    Sensor Open

    When oil pressure sensor opens circuit and the warning

    input is active, controller will send warning alarm signal and it

    will be displayed in LCD.

    5.2 SHUTDOWN ALARM

    When controller detected shutdown alarm, it will send signal to open switch and stop the

    unit. The alarms are displayed in LCD.

    No Items Description

    1 Auxiliary

    Shutdown

    When controller detected the input port external warning is

    active, controller will send shutdown alarm signal and it will

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 12 of 30

    No Items Description

    be displayed in LCD.

    2 High

    Temperature

    When controller detected the temperature of water/cylinder

    is higher than preset, it will send a stop alarm signal and it

    will be displayed in LCD.

    3 Low Oil

    Pressure

    When controller detected oil pressure is lower than the

    preset, it will send a stop alarm signal and it will be displayed

    in LCD.

    4 Over Speed When controller detected genset speed is over the preset, it

    will send a stop alarm signal and it will be displayed in LCD.

    5 Under Speed When controller detected genset speed is under the preset, it

    will send a stop alarm signal and it will be displayed in LCD.

    6 Loss Of Speed

    Signal

    When controller detected genset speed is 0 (the delay is not

    0), it will send a stop alarm signal and it will be displayed in

    LCD.

    7 Gens Over

    Voltage

    When controller detected genset voltage is over the preset, it

    will send a stop alarm signal and it will be displayed in LCD.

    8 Gens Under

    Voltage

    When controller detected genset voltage is under the preset,

    it will send a stop alarm signal and it will be displayed in

    LCD.

    9 Gens Over

    Current

    When controller detected genset current is over the preset

    and delay is not 0, it will send a stop alarm signal and it will

    be displayed in LCD.

    10 Fail To Start During the start attempt times, if genset start failed, it will

    send a stop alarm signal and it will be displayed in LCD.

    11 Over Frequency

    When controller detected genset frequency is over the

    preset, it will send a stop alarm signal and it will be displayed

    in LCD.

    12 Under

    Frequency

    When controller detected genset frequency is under the

    preset, it will send a stop alarm signal and it will be displayed

    in LCD.

    13 Genset Failed When controller detected genset frequency is 0, it will send a

    stop alarm signal and it will be displayed in LCD

    14 Low Fuel Level

    When controller detected genset fuel level low input is active,

    it will send a stop alarm signal and it will be displayed in

    LCD.

    15 Low Liquid

    Level

    When controller detected genset water level low input is

    active, it will send a stop alarm signal and it will be displayed

    in LCD.

    16 Temp. Sensor

    Open

    When temperature sensor opens circuit and the input is

    active, controller will send a stop alarm signal and it will be

    displayed in LCD.

    17 Oil Pressure When oil pressure sensor opens circuit and the input is

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 13 of 30

    No Items Description

    Sensor Open active, controller will send a stop alarm signal and it will be

    displayed in LCD.

    6 CONNECTIONS

    Compared with HGM420, HGM410 is lack of a 3 phase AC input terminal of mains.

    The rear panel of HGM410 and HGM420 is as below.

    Description of terminal connections:

    Pin Function Cable Size

    Description

    1 DC Power Supply B- 1.5mm2 Connect battery negative.

    2 DC Power Supply B+ 1.5mm2

    Connect battery positive. If longer than

    30m, parallel connection with 2 cables.

    Recommend using maximum 20A fuse.

    3 Programmable Relay

    Output 1 1.0mm2

    Plant Supply B+ from pin 2, 5 A rated.

    4 Start Relay Output 1.0mm2 Plant Supply B+ from pin 2, 5 A rated.

    Connect starting coil.

    5 Programmable Relay

    Output 2 1.0mm2 Plant supply B+ from pin 2, 5 A rated.

    6 Programmable Relay

    Output 3 1.0mm2 Plant supply B+ from pin 2, 5 A rated.

    7 Auxiliary Input 1 1.0mm2 Connect to GND (B-) See Table 3

    8 Auxiliary Input 2 1.0mm2 Connect to GND (B-)

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 14 of 30

    Pin Function Cable Size

    Description

    9 Auxiliary Input 3 1.0mm2 Connect to GND (B-)

    10 Auxiliary Input 4 1.0mm2 Connect to GND (B-)

    11 Temperature Sensor

    Input 1.0mm2

    Connect a temperature

    resistance sensor. See Table 4

    12 Oil Press Sensor Input 1.0mm2 Connect to a pressure

    resistance sensor.

    13 CT A Phase Sensing 1.5mm2 Connect current transformer secondary

    coil (rated 5A)

    14 CT B Phase Sensing 1.5mm2 Connect current transformer secondary

    coil (rated 5A)

    15 CT C Phase Sensing 1.5mm2 Connect current transformer secondary

    coil (rated 5A)

    16 CT Common 1.5mm2 See INSTALLATION in the manual.

    17 Speed Sensor Input 0.5mm2

    Connect magnetic pickup.

    Recommend using screen.

    Connect battery negative at one end.

    18 Charger D+ Input 1.0mm2 Connect D+ terminal. If there is no, this

    input remains Not Connect.

    19 Programmable Relay

    Output 4 1.0mm2

    Terminal 19 and 21 are relay N/O contact,

    rated 5A.

    20 Programmable Relay

    Output 5 1.0mm2

    Terminal 20 and 21 are relay N/O contact,

    rated 5A.

    21 Common Port 1.5mm2 Common port of programmable relay

    output 4 and 5.

    22 Generator U Phase

    Sensing 1.0mm2

    Connect U phase of generator

    Recommend 2A fuse

    23 Generator V Phase

    Sensing 1.0mm2

    Connect V phase of generator

    Recommend 2A fuse

    24 Generator W Phase

    Sensing 1.0mm2

    Connect W phase of generator

    Recommend 2A fuse

    25 Generator N2 Output 1.0mm2 Connect neutral output of generator.

    26 Mains R Phase

    Sensing 1.0mm2

    Connect R phase of mains

    Recommend 2A fuse (HGM410 without)

    27 Mains S Phase

    Sensing 1.0mm2

    Connect S phase of mains

    Recommend 2A fuse (HGM410 without)

    28 Mains T Phase

    Sensing 1.0mm2

    Connect T phase of mains

    Recommend 2A fuse (HGM410 without)

    29 Mains N1 Sensing 1.0mm2 Connect neutral line of mains

    (HGM410 without)

    NOTE: LINK interface is programmable interface for parameters that can be

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 15 of 30

    programmed by PC via an SG72 adapter. If there is need to remote start the genset,

    please use the SG485 module.

    7 DEFINITION AND RANGE OF PARAMETERS

    7.1 PARAMETER CONTENTS AND RANGE (TABLE 1)

    No Items Range Default Description

    1 Mains Normal

    Delay (0-3600)s 10

    Mains transient delay, suitable for

    ATS (automatic transfer switch).

    2 Mains Abnormal

    Delay (0-3600)s 5

    3 Mains Under

    Voltage (30-620)V 184

    When mains voltage is under the

    point, Mains Under Voltage is

    active. When the point is 30V, not

    detect low voltage signal.

    4 Mains Over

    Voltage (30-620)V 276

    When mains voltage is over the

    point, Mains Over Voltage is

    active. When the point is 620V,

    not detect high voltage signal.

    5 Transfer Rest

    Time (0-99.9)s 1.0

    Its the delay from mains is open

    to gens closing or from gene

    open to mains closing.

    6 Start Delay (0-3600)s 1

    Its the delay from remote start

    signal is active or mains

    abnormal, to start generator.

    7 Stop Delay (0-3600)s 1

    Its the delay from remote start

    signal is inactive or mains

    normal, to stop generator.

    8 Start Times (1-10)times 3

    Maximum start times, if failed to

    start within the specified times,

    controller will send Fail To Start

    signal.

    9 Preheat Time (0-300)s 0 Time to power the glow plug

    before cranking.

    10 Crank Time (3-60)s 8 The starter adds the time of the

    electricity each time.

    11 Crank Rest Time (3-60)s 10 Delay of waiting for another

    cranking.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 16 of 30

    No Items Range Default Description

    12 Safety Run On

    Time (1-60)s 10

    During this period, Low Oil

    Pressure, High Temperature,

    Under Speed, Under Frequency

    and Charge Failure alarms are

    inactive.

    13 Start Idle Time (0-3600)s 0 Idle running time when starting.

    14 Warm Up Time (0-3600)s 10 Delay for warming up before

    closing.

    15 Cooling Time (3-3600)s 10 Delay of cooling time before

    stopping.

    16 Stop Idle (0-3600)s 0 Idle running time when stopping.

    17 ETS Solenoid

    Hold (0-120)s 20

    Its the delay for energizing to

    stop.

    18 Over Stop Delay (0-120)s 0

    When set ETS solenoid hold as

    0s, from idle delay over to over

    stop timer; if not 0s, its from ETS

    delay over to genset at rest.

    19 Switching On (0-10)s 5.0

    Pulse width of mains or closing

    gens. When it is 0s, output is

    continuous.

    20 Flywheel Teeth (10-300) 118

    Used for judging crank

    disconnect and detecting rotating

    speed. See INSTALLATION in

    this manual.

    21 Generator

    Abnormal Delay (0-20.0)s 10.0

    Gens high voltage and low

    voltage alarm delay.

    22 Generator Over

    Voltage (30-620)V 264

    When voltage is over the point,

    Gens Over Voltage is active.

    When the point is 620V, Gens

    Over Voltage is disabled.

    23 Generator Under

    Voltage (30-620)V 196

    When voltage is under the point,

    Gens Under Voltage is active.

    When the point is 30V, Gens

    Under Voltage is disabled.

    24 Under Speed (0-6000)RPM 1200

    When engine speed is under the

    point and holds for 10s, Gens

    Under Speed is active.

    25 Over Speed (0-6000)RPM 1710

    When engine speed is over the

    point and holds for 2s, Gens

    Over Speed is active.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 17 of 30

    No Items Range Default Description

    26 Under Frequency (0-75.0)Hz 45.0

    When generator frequency is

    lower than the point and holds for

    10s, Gens Under Frequency is

    active.

    27 Over Frequency (0-75.0)Hz 57.0

    When generator frequency is

    over the point and holds for 2s,

    Gens Over Frequency is active.

    28 High Temperature (80-140)C 98

    When engine temperature sensor

    value is over this point, send

    alarm signal. Active from end of

    safety run on timer. When the

    value is 140, high temperature

    alarm is disabled. (only suitable

    for temperature sensor)

    29 Low Oil Pressure (0-400)kPa 103

    When engine oil pressure sensor

    value is under this point, send

    alarm signal. Active from end of

    safety run on timer. Low oil

    pressure alarm is disabled. (only

    suitable for oil pressure sensor)

    30 Loss of Speed

    Signal (0-20.0)s 5.0

    If set the delay as 0, only warn

    not to stop the generator.

    31 Charge Failure (0-30)V 6.0

    During generator is running,

    when alternator WL/D+ voltage is

    under this point and remains for

    5s, generator will send shutdown

    alarm.

    32 Battery Over

    Voltage (12-40)V 33.0

    When battery voltage is over the

    point and holds for 20s, Battery

    Over Voltage is active. Its a

    warning alarm.

    33 Battery Under

    Voltage (4-30)V 8.0

    When generator battery voltage

    is under the point and holds for

    20s, Battery Under Voltage is

    active. Its a warning alarm.

    34 CT Rate (5-6000)/5 500 Current transformer rate

    35 Full Load Current (5-6000)A 500 Maximum rated current, used for

    calculating over current.

    36 Over Current

    Percentage (50-130)% 120

    When the load current is over the

    point, over current delay begins.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 18 of 30

    No Items Range Default Description

    37 Over Current

    Delay (0-3600)s 1296

    When load current is over the

    pre-set value, over current is

    initiated. When set delay timer as

    0, only warning no shutdown,

    38 Digital Output 1 (0-17) 14 Factory default: Fuel Relay

    Output

    39 Digital Output 2 (0-17) 2 Factory default: Energized To

    Stop

    40 Digital Output 3 (0-17) 3 Factory default: Idle Control

    41 Digital Output 4 (0-17) 5 Factory default: Gens Closed

    42 Digital Output 5 (0-17) 6 Factory default: Mains Closed

    43 Auxiliary Input 1 (0-15) 1 Factory default: High

    Temperature Alarm

    44 Auxiliary Input 1

    Active (0-1) 0 Factory default: Closed

    45 Auxiliary Input 1

    Delay (0-20.0)s 2.0

    46 Auxiliary Input 2 (0-15) 2 Factory default: Low Oil Pressure

    Alarm

    47 Auxiliary Input 2

    Active (0-1) 0 Factory default: Closed

    48 Auxiliary Input 2

    Delay (0-20.0)s 2.0

    49 Auxiliary Input 3 (0-15) 10 Factory default: Remote Start

    50 Auxiliary Input 3

    Active (0-1) 0 Factory default: Closed

    51 Auxiliary Input 3

    Delay (0-20.0)s 2.0

    52 Auxiliary Input 4 (0-15) 11 Factory default: Low Fuel Level

    Warn

    53 Auxiliary Input 4

    Active (0-1) 0 Factory default: Closed

    54 Auxiliary Input 4

    Delay (0-20.0)s 2.0

    55 Module Mode (0-2) 0

    0: Stop Mode

    1: Manual Mode

    2: Auto Mode

    56 Module Address (1-254) 1 Communication address of

    controller.

    57 Passwords (0-9999) 1234

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 19 of 30

    No Items Range Default Description

    58 Crank Disconnect (0-5) 2

    Conditions of crank disconnect

    includes gens, magnetic pickup

    and oil pressure which make

    starter separate with engine.

    See Table 5

    59 Engine Speed (0-3000)RPM 360 When engine speed is over this

    point, starter will disconnect.

    60 Engine

    Frequency (10.0-30.0)Hz 14.0

    When generator frequency is

    over this point, starter will

    disconnect.

    61 Engine Oil Press (0-400)kPa 200 When engine oil pressure is over

    this point, starter will disconnect.

    62 High Temp. Inhibit (0-1) 0

    Factory default: when the

    temperature is too high, alarm to

    shutdown. Note 1.

    63 Low OP Inhibit (0-1) 0

    Factory default: when oil

    pressure is lower, alarm to

    shutdown. Note 2

    64 Voltage Input (0-3) 0 0: 3P4W; 1:2P3W

    2:1P2W; 3: 3P3W Note 3

    65 Temp. Sensor

    Select (0-9) 08 SGX

    66 Pressure Sensor

    Select (0-9) 08 SGX

    67 Number Of Poles (2-32) 4

    68 Temperature

    Sensor Open (0-2) 1

    0: Indication (temperature sensor

    will show +++);

    1:Warning; 2:Shutdown

    69 Oil Pressure

    Sensor Open (0-2) 1

    0: Indication (oil pressure sensor

    will show +++);

    1:Warning; 2:Shutdown

    70 Defined Sensor

    Curve (0-1) 0

    Temperature and oil pressure

    sensor curve can be defined.

    Note 1, if high temperature stop inhibit is configured, or set programmable input

    as high temperature stop inhibit and this input is active, when temperature is higher

    than preset, or high temperature alarm input is active, controller will send warning

    signal only and not stop unit.

    Note 2, if low oil press stop inhibit is configured, or set programmable input as

    low oil press stop inhibit and this input is active, when oil pressure is lower than

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 20 of 30

    preset, or low oil pressure alarm input is active, controller will send warning signal only

    and not stop unit.

    Note 3, if 3P3W is selected, maximum shutdown threshold of Mains Over

    Voltage and Gens Over Voltage can be 620V; when select others, maximum

    shutdown threshold can be 360V. .

    7.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2)

    No Items Description

    0 Not Used

    1 Common Alarm

    Including all shutdown alarms and warning alarms.

    When there is warning alarm only, it is not self-lock;

    when a shutdown alarm occurs, it is self locking until

    the alarm is reset.

    2 ETS Solenoid Hold

    Suitable for genset with electromagnet and will pick up

    after stop idle delay. The output will remain energized

    until engine has come to a complete stop, then

    de-energizes.

    3 Idle Control

    The designated programmable output relay will

    energize when the idle delay is not zero. The output

    contact would typically be connected to the idle/run

    input control of an electronic governor.

    4 Preheat Control

    The designated programmable output relay will

    energize until the engine receive a crank success

    signal. The preheat output is typically used for an

    engine starting aid such as glow plugs.

    5 Close Generator When closing time is 0, its continuous output.

    6 Close Mains When closing time is 0, its continuous output.

    (HGM410 without)

    7 Switching Off When closing time is 0, its disabled.

    8 Acceleration Control Pull-in during warm-up delay. Open when auxiliary

    acceleration input is active.

    9 Deceleration Control

    Pull-in when entering stop idle or ETS solenoid

    process, (alarm to shutdown). Open when auxiliary

    deceleration input is active.

    10 Genset Run

    Outputting when genset in normal running and

    disconnect when rotating speed is under engine speed

    after started.

    11 Fuel Pump Control Close when fuel level is lower than the set threshold;

    open when low fuel level warning input is inactive.

    12 High Speed Control Outputting when entering into Warming Up and

    disconnect when Cooling Down is over.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 21 of 30

    No Items Description

    13 System In Auto

    Mode The controller work in automatic mode.

    14 Fuel Relay Output To control fuel relay output.

    15 Reserved

    16 Reserved

    17 Reserved

    7.3 PROGRAMMABLE INPUT 1-4 TABLE (ACTIVE WHEN CONNECT GND (B-) (TABLE 3)

    No Items Description

    0 Not Used

    1 High Temp. Alarm When safety on run delay is over, if the signal is active,

    generator will immediately alarm to shutdown. 2 Low OP Alarm

    3 Auxiliary Alarm If the input is active, only warning, no shutdown.

    4 Auxiliary Shutdown If the input is active, stop the genset immediately.

    5 Coolant To Stop

    During engine running, if the engine temperature is too

    high, the controller will stop the unit after cooling delay;

    when the input is inactive, controller will stop the unit

    immediately.

    6 Generator Closed

    7 Mains Closed HGM410 without

    8 High Temp. Stop

    Inhibit

    When it is active, prohibit stopping when high

    temperature occurs. Note 1

    9 Low Oil Pressure

    Stop Inhibit

    When it is active, prohibit stopping when oil low

    pressure occurs. Note 2

    10 Remote Start Input HGM420 without

    11 Low Fuel Level

    Warn

    12 Low Liquid Level

    Warn

    13 Low Fuel Level

    Shutdown

    14 Low Liquid Level

    Shutdown

    15 Auto Start Inhibit

    In Auto mode, if this input is active, when mains failure

    (HGM420) or a remote start signal occurs (HGM410),

    the controller will not give a start command to the

    generator. If generator is running, stop command wont

    be executed. When this input is inactive, genset will

    automatically start or stop according to the mains

    normal or abnormal.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 22 of 30

    7.4 SENSOR SELECT (TABLE 4)

    No Content Description

    1 Temperature

    Sensor

    0 Not used

    1 Defined Res. Type

    2 VDO

    3 SGH(Huanghe sensor)

    4 SGD(Dongkang sensor)

    5 CURTIS

    6 DATCON

    7 VOLVO-EC

    8 SGX

    9 Reserved

    Defined input resistance

    range is (0~6000).

    Factory default is SGX.

    2 Pressure

    Sensor

    0 Not used

    1 Defined Res. Type

    2 VDO 10Bar

    3 SGH(Huanghe sensor)

    4 SGD(Dongkang sensor)

    5 CURTIS

    6 DATCON

    7 VOLVO-EC

    8 SGX

    Defined input resistance

    range is (0~6000).

    Factory default is SGX.

    7.5 CONDITIONS OF CRANK DISCONNECT (TABLE 5)

    No Content

    0 Magnetic pickup

    1 Generator

    2 Magnetic pickup + Generator

    3 Magnetic pickup + Oil pressure

    4 Generator + Oil pressure

    5 Generator + Magnetic pickup + Oil pressure

    1) The crank disconnect condition has three kinds, the magnetic pickup and the

    generator voltage can be used alone, oil pressure must be used with the magnetic

    pickup and the generator voltage, in order to make the starter disconnect as soon

    as possible.

    2) Magnetic pickup is installed in the engine for testing flywheel.

    3) When choosing magnetic pickup, ensure the number of flywheel teeth is same as

    the set, otherwise over speed or under speed shutdown may appear.

    4) If the generator is not installed with magnetic pickup, please don't select

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 23 of 30

    corresponding item.

    5) If the generator has no oil pressure sensor, please don't choose corresponding.

    6) If the generator is not selected, controller will not measure and display relative

    parameters (This can be applied to the pump set), if not choose magnetic pickup,

    the speed signal will come from the generating AC signal.

    8 PARAMETERS SETTING

    After controller powered on, press to enter into the parameters setting menu, see fig 1

    below:

    Set Parameters

    When entering password interface, inputting 1234 can set part of the parameter

    items in table 1; inputting 0318 can set all the items. (Table 1) If there is need to

    set more parameters, please contact the factory.

    NOTES:

    1. For HGM410, there are no items from 1 to 5 in table 1; there are no digital outputs

    about mains in auxiliary output 1-5.

    2. Please modify the parameters (such as crank disconnection, auxiliary input/output

    and various timers) in standby mode, otherwise alarm to shutdown or other

    abnormal conditions may happen.

    3. The over-voltage threshold must be greater than the under-voltage threshold;

    otherwise over-voltage and under-voltage will occur at the same time.

    4. The over-speed threshold must be greater than under-speed threshold, otherwise

    over speed and under speed will occur at the same time.

    5. Set the frequency (crank disconnect) as low as possible, in order to separate the

    starter quickly when crank disconnect.

    6. Auxiliary input 1-4 cannot be set as the same item, or will cause incorrect functions.

    But auxiliary output 1-5 can be set as the same item.

    7. If need to shut down after cooling, please set any auxiliary input as Coolant To

    1 Set Parameters

    2 Information

    3 Set Language

    4 Mode Select

    Fig1

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 24 of 30

    Stop, then connect this input to GND.

    Information

    LCD will display software version, issue date of the controller.

    Note: Pressing will display the states of digital inputs and outputs.

    Set Language

    Chinese, English, Spanish and Russian interface can be selected.

    Mode Select

    The controller can be set as Manual Test Mode, Manual Mode or Auto Mode.

    Note: Pressing key at any time will quit the setting and return to the previous

    setting menu.

    9 SENSOR SELECT

    1) When choosing sensor, standard of sensor curve will be needed. If set

    temperature sensor as SGH (120C resistance type), sensor curve should be SGH

    (120oC resistance type); If set as SGD (120C resistance type), sensor curve

    should be SGD curve.

    2) If there is difference between standard sensor curve and chosen sensor, select

    "defined sensor", and then input defined sensor curve.

    3) When inputting sensor curve, X value (resistance) must be in accordance with the

    order of higher to lower, otherwise errors will occur.

    4) When select sensor "Not used", temperature, pressure and fuel level will be

    display as" - - -" in LCD.

    5) If there is no pressure sensor, but only has low pressure alarm switch, then you

    must set pressure sensor as "Not used", otherwise oil pressure low alarm

    shutdown may appear.

    6) Can set several points of forehand or backmost as the same ordinate, like the

    following picture:

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 25 of 30

    Common unit conversion table

    1N/m2 (pa) 1kgf/cm2 1bar (1b/in2) psi

    1Pa 1 1.02x105 1x10

    5 1.45x104

    1kgf/cm2 9.8x104 1 0.98 14.2

    1bar 1x105 1.02 1 14.5

    1psi 6.89x103 7.03x102 6.89x10

    2 1

    10 COMMISSIONING

    Before operation, the following checking should be carried out:

    1) Check and ensure all the connections are correct and wires diameter is suitable.

    2) Ensure that the controller DC power has insurance; battery positive and negative

    have correctly connected.

    3) Take proper actions to prevent engine to disconnect crank (for example, to remove

    the connections of fuel value). If checking is OK, connect start battery, select Manual

    Mode, controller will execute the program.

    4) Set controller as Manual Mode, press start button to start genset. If failed within the

    setting crank times, controller will send Failed to Start signal; then press Reset to

    reset controller.

    5) Recover actions of preventing engine to disconnect crank (e. g. Connect wire of fuel

    value), press start button again, genset will start. If everything goes well, genset will

    normal run after idle running (if configured). During this period, watch for engines

    running situations and voltage and frequency of alternator. If abnormal, stop genset

    and check all connections according to this manual.

    6) Select the Auto Mode from front panel, connect to mains signal. After the mains

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 26 of 30

    normal delay, controller will transfer ATS (if configured) and into mains load. After

    cooling, controller will stop genset and into standby state until mains abnormal again.

    7) When mains abnormal again, genset will start automatically and into normal running,

    send signal to make gens close, transfer ATS and make genset take load. If not like

    this, please check connections of ATS according to this manual.

    8) If there are any other questions, please contact our technical personnel.

    11 TYPICAL APPLICATION

    HGM410 Typical wiring diagram

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 27 of 30

    HGM420 Typical wiring diagram

    Single Phase 2 Wire (HGM420)

    2 Phase 3 Wire (HGM420)

    CAUTION! Recommend expanding relay with high capacity in start and fuel

    output.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 28 of 30

    CAUTION! Use expansion relay in mains/gens closing outputs.

    CAUTION! Let its normally closed contact series connect between fuel relay

    output port and electromagnetic valve when you connect emergency stop button on

    the controller. Emergency stop alarm can be displayed if you configure a input port as

    external stop input (one end connect to normally open contact, the other end connect

    to ground).

    12 INSTALLATION

    12.1 FIXING CLIPS

    The module is held into the panel fascia using the supplied fixing clips.

    1) Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.

    2) Pull the fixing clip backwards (towards the back of the module) ensuring four clips

    are inside their allotted slots.

    3) Turn the fixing clip screws clockwise until they make contact with the panel.

    Note: Care should be taken not to over tighten the screws of fixing clips.

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 29 of 30

    12.2 OVERALL DIMENSION AND PANEL CUTOUT

    1) Battery Voltage Input

    HGM400 series controller can be applicable to (8-35) VDC battery voltage. Battery

    negative must be reliably connected engine shell. The connection between

    controller power and battery should not be less than 1.5mm2, if a float charger is

    fitted, please directly connect output line of the charger with battery, then from

    battery positive and negative separately connect power input, in case that charger

    will interfere with the normal running of controller.

    2) Speed Sensor Input

    Speed sensor is installed in the engine for testing flywheel teeth. The connection

    with controller uses 2-core screen, shield layer should connect terminal1 of

    controller with the other end vacant. The other two signal lines are respectively

    connected to terminal 1 and terminal 17. At full speed, output voltage range is

    1-24VAC (RMS). Recommend using 12VAC (rated speed) voltage. During

    installing, make the speed sensor contact the flywheel firstly, then pour out 1/3

    laps, finally lock nut on the sensor.

    3) Output And Expansion Relay

    All outputs of the controller are relay contact outputs, if expansion relay is needed,

    please add free-wheeling diode at both ends of the relay coil (expansion relay coil

    links DC) or increase RC loop (expansion relay coil links AC) in order to prevent

    from interfering controller or other equipment.

    4) AC Input

    HGM400 series controller must externally connect current transformer, CT

  • HGM400 Series Automatic Control Module

    HGM400 Series Genset Controller ISSUE 2012-10-30 Version 1.2 Page 30 of 30

    secondary current must be 5A. Besides, the phase of CT and input voltage must

    be correct, or the sampling current and active power may be incorrect.

    CAUTIONICOM must connect battery anode of the controller.

    WARNING! When there is load current; the CT secondary side cannot open

    circuit.

    5) Withdraw Voltage Test

    When the controller has been installed in the control panel, during the test please

    disconnect all the terminals, lest high voltage damages the controller.

    13 FAULT FINDING

    Symptom Possible Remedy

    Controller inoperative

    Check starting battery;

    Check connections of the controller;

    Check the DC fuse.

    Genset stops

    Check if water/cylinder temperature too high.

    Check alternator voltage.

    Check the DC fuse.

    Emergency shutdown

    Check if an emergency stop button is fitted; Ensure

    battery positive is connected to the emergency stop

    input.

    Check if connection is open circuit.

    Low oil Pressure alarm

    (after crank success) Check oil pressure sensor and connections.

    High Temp. alarm (after

    crank success) Check temperature sensor and connections.

    Shutdown Alarm During

    Running

    Check switch and connections according to information

    on LCD.

    Check configuration inputs.

    Crank Not Disconnect

    Check connections of fuel solenoid.

    Check starting battery.

    Check speed sensor and its connections.

    Refer to engine manual.

    Starter Inoperative Check connections of starter;

    Check starting battery.

    Genset Running but ATS

    Not Transfer

    Check ATS;

    Check connections between ATS and controller.


Recommended