Date post: | 11-Sep-2018 |
Category: |
Documents |
Upload: | truongthien |
View: | 214 times |
Download: | 0 times |
CONDAIR RSResistive steam humidifierWith advanced scale management
Humidification and Evaporative Cooling
CONDAIR RSResistive steam humidifier
Stainless steel boiling cylinderCleanable cylinder eliminates the needto buy disposable plastic boilingcylinders, reducing operating costs.
Resistive heating elements give close controlConsistent and accurate humiditycontrol is offered with resistance heatertechnology. Steam output is directlycontrolled by the heat given from theelements. This is unlike electrode boilerhumidifiers, which pass currentthrough the water and control outputby varying the water level.
The Condair RS can provide ±3%RHhumidity control with mains water and±1%RH with RO water.
Plastic inner linerProvides thermal insulation to createtwo temperature zones inside thecylinder.
Cold water pool prevents inlet and drain blockagesBy locating the water inlet and drainbetween the twin walls of the outercylinder and inner plastic liner, thetemperature by these orifices is kept ata level that inhibits the formation ofscale. This prevents blockages andfurther enables extended operationalperiods between servicing.
Scale collector tankAn externally located tank under theboiling cylinder collects scale thatdetaches from the heating elementsand plastic liner. It can be drained,removed, emptied of scale andreattached within minutes. Thisextends the periods between majorservices by up to three times.
Innovative scale management extendsperiods between servicing
Steam distribution options
Large outputs from single unitThe Condair RS is available with asingle cylinder for outputs up to40kg/hr and a double cylinder modelfor outputs up to 80kg/hr. Up to foursingle units can be controlled on amaster/slave configuration for outputsup to 160kg/hr.
Touch screen controlAdvanced user interface offers moredetailed operational control anddiagnostic reporting than ever before. AUSB connection allows performancedata to be downloaded in Excel, as wellas software updates to be loaded.
Standard connection using ModbusRTU, BACnet IP and BACnet MS/TP -slave only. Option required forLonWorks - Lon standards certified,BACnet MS/TP - master/slave orBACnet IP - BTL certified.
The Condair RS resistive steamhumidifier provides reliable andaccurate humidity control without theexpense of replaceable boiling cylinders.
Patented scale management featuresallow scale to be removed from thesystem quickly and efficiently. Thisextends the periods of operationbetween major services by up to three
times when compared to any otherresistive humidifier.
Accurate humidity control can beachieved of up to ±1%RH with ROwater and ±3% with mains water.
Condair RS with fan unit for direct room humidification.
Condair RS with steamhose for use in duct.
O U T S TAN
DIN
G QUALITY • V
DE-
CE
RT I
F I E D •
geprüfteSicherheit
DVE
Scale that forms on the elements detaches and falls into the scale collector tank where it is easily removed.
When operated on mains water, allsteam humidifiers build up limescale inthe boiling cylinder as waterevaporates. How a humidifier managesthis scale determines how easy thesystem is to use and service.
The Condair RS’ patented scalemanagement system sets it aside fromall other humidifiers in its class andmakes it the most user-friendlyresistive humidifier in the world.
Scale that forms on the heatingelements is dislodged during normaloperation and falls into the externallylocated collector tank. To remove the
scale, the unit is drained, allowed tocool and then the collector tank can bedisconnected.
This allows intermittent servicing totake place quickly and easily withouteven needing to open the humidifier’scabinet and extends the periodsbetween major services by up to threetimes.
Pumped drainBy locating a pumped drain above thescale collector tank, scale is collectedrather than being flushed into abuilding’s drainage pipework. Thisavoids scale blockages of the pump andpipework.
Cold water poolLocating the water inlet and drainorifices between the inner plastic linerand outer metal casing of the cylinderprotects them from blockages due toscale. Scale can neither fall into thisarea nor form here, as the temperatureis maintained at around 55°C. Thisinnovative design further enables longoperational periods between majorservices.
Patented scale management
Cold water pool
High performance and low operating cost
Resistive humidifiers create steamthrough the transfer of heat from theresistance heater elements to thewater. This is unlike electrode boilerhumidifiers that pass electrical currentthrough the water. This differentheating strategy has several benefitswhen comparing the two technologies.
No disposable plastic cylinders As electrical current is not applied tothe water, cleanable metal cylinderscan be used, significantly reducingoperating costs.
Very close controlSteam output is controlled by applyingmore or less heat to the water ratherthan controlling water level orconductivity. This results in responsiveand close humidity control of ±3%RHwith mains water and ±1%RH with ROwater.
Can use RO waterAs the mineral content of the water hasno impact on steam output, resistivehumidifiers can operate on RO water.This virtually eliminates scale build-up,thus reducing servicing, and improveshumidity control by removing the needfor mineral dilution cycles to controlfoaming.
The benefits of resistive humidifier technology
Touch screen controller for intuitive operational control and advanced reporting
The Condair RS incorporates the latesttouch screen control panel, providingintuitive operation and extensivereporting information.
All operating parameters can be seen ata glance with on-screen featuresoffering the user further informationon operation and detailed trouble-shooting suggestions.
A USB connection allows allperformance data to be recorded andexported into Excel for advanceddiagnostics. Upgrades to software canalso easily be made via the USB port.
BMS connectivity is included asstandard with Modbus RTU, BACnet IPand BACnet MS/TP - slave only.LonWorks - Lon standards certified,BACnet MS/TP -master/slave) orBACnet IP - BTL certified are availablewith options.
Control at your fingertips
Operational status, fault and maintenance data isrecorded via USB and analysed in Excel.
Comprehensive range of accessories and options
Hygiene packA solenoid valve on the scale collectortank will ensure the system completelydrains without any standing water. Inaddition, an activation signal can besent to a building-side valve to purgethe supply line for a totally hygienicstatus during periods of inoperation.
Drain water temperTo reduce the temperature of the drainwater to below 60°C, waste water ismixed with fresh water.
Process versionAdvanced semi-conductor Triac controlfor improved humidity accuracy.
Mounting rackAdjustable mounting rack for easyinstallation on-site at different heights.
Condair RS options
Fan unitFor direct room humidification of up to40kg/h. The fan unit can be locateddirectly on top of the humidifier orremotely.
RO water filter Removes 95% of minerals from thesupply water to reduce maintenanceand improve humidity control.
Short evaporation steam manifold The Optisorp steam manifold offersvery short evaporation distances inAHUs.
Condair plc - the new name for JS HumidifiersArtex Avenue, Rustington, Littlehampton, West Sussex, BN16 3LN, UKTel: +44 (0)1903 850200 - [email protected] - www.condair.co.uk
07/2016
Typical system overview
Stainless steel steam cylinderPatented scale managementExternal scale collection tankRemote ON/OFF, operation andfault indicationTouch screen operationSelf-diagnostic systemReal-time clockBMS connectivity - Modbus RTU, BACnet IPor BACnet MS/TP - slave only
Options
OptiSorp multiple steam distribution systemHumidity sensor for duct/room installationDuct/room hygrostatPressure compensation set (up to 10,000 Pa)RO water filterMounting rackHygiene packBMS connectivity - LonWorks -Lon standardscertified, BACnet MS/TP (master/slave) or BACnet IP - BTL certified
Accesssories
1 Steam distribution system for ducted installation2 Steam distribution hose3 Ventilation unit for direct room humidification 4 Condensate hose5 Filter valve
1
23
4
5
Technical data
Housing sizes Small Medium Large 2x MediumMaster-Slave
3x MediumMasterSlave
4x MediumMaster-Slave
Product reference RS 5 RS 8 RS 10 RS 16 RS 20 RS 24 RS 30 RS 40 RS 50 RS 60 RS 80 RS 50 RS 60 RS 80 RS 100 RS 120 RS 140 RS 160
Dimensions WxHxD mm 420 x 987 x 370 530 x 1,097 x 406 1,000 x 1,097 x 406 2x 530 x 1,097 x 406 3x 530 x 1,097 x 406 4x 530 x 1,097 x 406
Operating weight kg 40.2 65.8 132.0 131.6 197.4 263.2
Heating voltage Maximum steam output
400V 3Ph 50-60Hz kg/h 5.1 8.1 9.9 16.1 19.8 24.2 29.8 40.0 49.6 59.6 80.0 19.8 +29.8
2x29.8
2x40.0
2x29.8 +40.0 3x40.0 2x29.8
+2x40.0 4x40.0
230V 1Ph 50-60Hz kg/h 5.0 8.0 9.8 - - - - - - - - - - - - - - -
Control voltage 230V 1Ph 50-60Hz
Conformity CE, VDE, SVE