2010 International Conference on Power System Technology
A Novel Algorithm of Wide Area Backup Protection Based on Fault Component Comparison
Zhiqin He, Zhe Zhang, Xianggen Yin, Hua Wang
Abstract--This paper proposes a novel wide area back-up protection algorithm that measures synchronized information from
different buses in region. The amplitude of voltage fault component from different buses is compared, and the bus with
maximum magnitude will be selected. Hence, suspected fault line
set could be established according to the sub-graph and complete incidence matrix of selected buses. Then, voltage fault component
amplitude at two sides of each suspected line could be calculated from another side, and the amplitude comparison between
computed and measured value could be implemented. The ratio would be 1 when external fault occurs, and it would be greater
than 1 when internal fault occurs. Thus, the fault line could be
identified finally. The technique doesn't need high precision synchronization of wide area information, and could response to
different faults. The simulation of lO-unit and 39-bus New England system using PSCADIEMTDC illustrates the effective
ness of this method.
Index Terms--Wide area protection, phasor measurement
unit(PMU), fault component comparison, lO-unit and 39-bus
New England system, PSCADIEMTDC.
I. INTRODUCTION
PROTECTIVE relaying is the "first defense line" of bulk power grid. If relay device could trip correctly and reliably,
the stability and security of grid could be sustained. Otherwise,
the emergency would be amplified [1]. The wide area blackout events in worldwide in Recent 30 years demonstrate
that protection mal-operation and cascading trips caused by
flow transferring is one of the significant factors which accelerate wide area blackout. In addition, traditional relay set
values off-line. This setting style couldn't keep sensitivity and
selectivity at the same time for system's complicated network topology. And the setting value rectifying work depends on
manual work, so hidden failure would exist [2]. Therefore,
researching fault rapid location and isolation algorithm and improving traditional setting method is the focus for relay
engineers in future. Meanwhile, these discussions are the main
self-healing function of smart gird [3]. The blackout investigators found that remote backup
protection (such as: Zone3 of distance protection) contribute
This work was supported by the National Natural Science Foundation of China (No. 50837002 and No. 5087703 1), and the National High Technology Research and Development of China (863 Programme) (2009AA05Z208).
Z. He, Z. Zhang, X Yin, and H. Wang are with the Electrical Power Security and High Efficiency Lab, Huazhong University of Science and Technology, Wuhan 430074, China (e-mail: [email protected]).
978-1-4244-5940-7/1 0/$26.00©20 1 0 IEEE
to the acceleration of the blackout. However, if a contingency
of a failure of the station battery occurs, Zone3 still is the most effective method to protect grid [4]. A flow transferring
identification algorithm with consideration of flow transfer
factor (FTRF) based on phasor measurement unit (PMU) is presented in [5]. The transfer current value caused by single
feeder could be calculated off-line. Then, the flow transferring
could be found by comparing measured current value and calculated value.
Wide area protection is a new path for relay engineer to
explore. Because of the time delay problem, wide area backup
protection is easier to realize than main protection. Genetic algorithm is used to identify fault location in [6]. Information
fault tolerance could be obtained, and protection device could
make proper decision even the information distortion reaching 5/32. Traditional current differential protection and direction
pilot protection are introduced to wide area backup protection
in [7]-[10]. The protection Agent has fault forecast and identification functions. Traditional main relay operation
information and wide area current differential protection are
combined to use [8]. The differential protection needs wide area data to be high precise synchronized measured. On the
contrary, directional comparison protection only need transmit
logic component, it is easier to realize in actual gird [9]. Utilizing bus positive sequence voltage to reduce calculation
scope is presented in [11]. But it is hard to reflect high
resistance fault. Negative and zero sequence voltage could be used to locate fault position. However, they could only
identify asymmetrical fault [12].
There are two structure types have been discussed: distributed and centralized. The former sets every intelligent
electronic device (lED) as a trip decision making unit. Each
lED only communicates with relative IEDs which belong to its protection scope [7]. However, producing high intelligent
lED and using it widely is a long term scheme for the price
and technology problem. Existing wide area protection
systems are all based on regional centralized structure [13][15]. The idea is setting a critical substation as central station
to realize wide area protection function. Information from
other substations will be transmitted to central station in order to realize fault location and implement trip strategy.
A novel wide area protection algorithm is proposed in this
paper. It is based on region centralized structure and only uses voltage and current fault component amplitude to locate fault
position. Firstly, positive voltage superimposed component,
negative and zero sequence voltage are used to select the bus
which is the most adjacent to fault line. Then, sub-graph and
complete incidence matrix of this bus is utilized to find suspected fault line set. Finally, the ratio between estimated
and measured value of bus voltage is calculated in order to
locate fault line. This method couldn't be affected by high
grounding resistance, and doesn't have high demand to data synchronization.
II. SUSPECTED FAULT LINES SELECTION
A. Bus Sort f
VM(l)
�1I(2)
(a) Phase to phase fault
(b) Single-phas grounding fault
�/(I)
(c) Two·phase grounding fault
Fig. 1. Sequence voltage distribution of two source system Post-fault
As is shown in Fig.1, when asymmetrical fault occurs in
the middle of transmission line, the sequence voltage
distribution has several characteristics as follows: • The peak value of positive sequence voltage is at equ
ivalent source point. In contrast, the minimum value is at
fault point;
• The peak value of negative and zero sequence voltage
could be found at fault point. When the measured point is further, the magnitude of negative and zero sequence
voltage would be smaller. At source point, negative se
quence voltage value falls to zero. Zero sequence voltage
would fall to zero on the delta side of transformer.
According to above characteristics, the amplitude of posit
ive sequence voltage superimposed component, negative and
zero sequence voltage from each buses in power grid could
be sorted. Then, the buses which are most incident to fault line could be found. The pickup criterion is as follows:
(iw .... 1 "KU, ) u (lu .... 1 " KU, ) u (iu, .. 1 " KU, ) (1)
Where I'.U"
., , u"
., and u"., are the amplitude of positive
sequence voltage superimposed component, negative and zero
sequence voltage of bus n. u, is the rated phase voltage of bus
n. K is a proportional coefficient. It's value ranges 0.3 to 0.5.
2
Let the pickup bus number is I, m, k. These buses would
be sorted, and the bus which has maximum value of fault
superimposed component would be selected. The sort criterion
is:
{MAX = (il'.u.,l.ll'.u ,.I. ... ll'.u.I)} u
{MAX = (lu,,l.lu,,I. ... lu,,.I)} u (2)
{MAX = (iu ... ,I,lu",I. ... lu . ...I)} Where the amplitude of positive sequence voltage sup
erimposed component, negative sequence voltage and zero
sequence voltage are measured synchronously by PMU of
each substations in regional girdo If the voltage of one bus is
the maximum, it represents that this bus is the nearest bus to
fault point. If there is more than one bus satisfY formula (2), the
subsequent calculation should be implemented according to
these buses.
B. Suspected Fault Lines Search Let bus m is chosen after former step. Then, all the tran
smission lines connected to bus m would composite suspected
fault line set. These lines could be found according to the sub
graph and adjacent matrix of bus m. the sub-graph represents protection scope of IEDs in bus m.
Fig.2 shows IEEE 3-unit and 9-bus system structure. A
fault occurs on Line 6 about 10% of total length. B8
B3
L6
IED7 IED5
L2 L4
IED8 [ED6
B5 B6 IEDI! IED9
LI L3
IEDI2 IEDIO -_ ........ _--..,.....--_ ...... - B4
TI
--t-- BI
01
Fig.2. 3-unit and 9-bus system with line fault
Let Bus8 is selected, and the scope of line protection doesn't exceed transformer low voltage side. The sub-graph
could be obtained as follow:
Bus5
e8
Line2
e7 e2
Bus7 Line5
Fig.3. Sub-graph of Bus8
el e3 e4 Bus9
Bus8 Line6 e5
Line4 e6
Bus6
In this paper, the buses and transmission lines compose
vertexes and the intelligent electric devices (lED) compose edges in sub-graph. The direction of each lED is from bus to
feeder. The sub-graph scope of BusS should extend to Line2
and Line6, because el and e3 which represent lED 1 and IED3
should play remote backup protection role. The complete incidence matrix M of this sub-graph is:
el e2 e3 e4 e5 e6 e7 e8
B8 1 0 0 0 0 0 0
L6 0 0 -I -I 0 0 0 0
B9 0 0 0 0 0 0
L5 -1 -1 0 0 0 0 0 0 (3)
M=B7 0 0 0 0 0 0
L4 0 0 0 0 -1 -1 0 0
B6 0 0 0 0 0 0 0
L2 0 0 0 0 0 0 -I -1
B5 0 0 0 0 0 0 0 1
The feeders and IEDs which is incident to BusS could be search as follow steps:
• Searching non-zero elements in row BS. Then, el and e3
could be found;
• Non-zero elements in column el and e3 could be found.
And L5 and L6 could compose suspected fault line set; • Searching non-zero elements in row L5 and L6, and el,
e2, e3, e4 could be found. These edges represent the IEDs
which are needed to implement subsequent calculation in
order to find fault line finally.
Apparently, the sub-graph and complete incidence matrix
could be formed off-line and rectified accompany with grid topology's change.
III. FAULT LOCATION BASED ON VOLTAGE COMPARISON
A. Theory of Algorithm The method is using voltage and current fault component
from relative buses and feeders to form criteria. Fault component could be classified to two types: superimposed com
ponent (positive sequence) and stable state component
(negative and zero sequence). The superimposed component could reflect symmetrical and asymmetrical faults. However,
it could only exits in a short time (about 40ms) after fault
occurring. Thus, it is necessary to add stable state component
to improve this criteria.
If the transmission line operates normally, one side voltage
could be calculated by relative variables from another side.
For instance, the negative voltage of side M and N of one line could be calculated as follows:
(4)
Where Uw and u;, represent bus negative sequence
voltage estimated value. U'M ' U,. represent bus negative
sequence voltage actual value. i'M , i,. represent branch
current, of which the positive direction is from bus to feeder.
3
z" represents line impedance.
When external fault occurs, the negative sequence network could be presented as follow:
ZM2 Uw
Fig.4. Negative Sequence network
Where a is a coefficient in order to present fault location.
It's value is [0, I]. Z, is transitional impedance. The relation
formulas are as follows:
. • ZM 2U2! U2M = (-I2M)ZM2 = -----....:::..:--"-----Zg + (ZM 2 + aZL2) / /(ZN2 + (1- a)ZL2) ZN2 + (1- a)ZL2
ZM 2 +aZL2 ZM 2 + ZL2 + ZN2
(5)
(6)
According to (5), (6), (7), the ratio between U;M and
U2M could be presented as follow:
��M=(l+�). ZN2 ZM2+aZL2 (S) U2M ZN2 ZN2+(1-a)ZL2 ZM 2 Where transient impedance component disappears, and the
final equation could be acquired:
U2M ZN2 +(I-a)ZL2 ZM 2 (9)
{ I�;M I=I ZN2+ZL2 . ZM 2+aZL2 1 I�;N I=I ZM 2+ZL2 . ZN2 +(I-a)ZL2 1 U2N ZM 2 + aZL2 ZN2
When internal fault occurs, the value of lu,l!lu,1 at two
sides would be higher than I. In contrast, when external fault
occurs, this value would be equal to 1 approximately. Let the
margin is 20%, the fault location criterion is:
IMY I lv' I lv' I «� > 12)u(� > 12)u(� > 12» ILlUIM I IU2M I IUOM I ILlV' I lv' I lv' I U« __
IN_ > 12u�> 1.2u(� > 12» ILlV IN I IV2N I IVON I
( 10)
This is a comprehensive criterion which consists of six
small criteria. The logic relationship among these small
criteria is "or". It means that the protection would operate if any criteria could be satisfied. Apparently, this criterion only
uses voltage amplitude without angle to identifY fault. Thus, it
doesn't need a high demand to data synchronization.
B. System Impedance Influence Analysis According to formula (9), it is clear that the value of
lu,. I u,.1 and Iv,. I U,.I is affected by the ratio between system
impedance and line impedance. If the ratio in Fig. 4 is:
(1 I)
Hence, the influence of system and line resistance is
neglected. The following equation could be deduced:
U2M U'M (I-a)x+xy (12)
{ I�;M I = �;M = (1+ y)(a+x)
I�;N I = �;N = (1+X)[(1-a)+ y ] U2N U'N ay+xy In order to find the extreme value of (12), an equation
should be supposed:
V;M = V;N V'M V'N
� (x-y)a' -2a(x+xy)+x+xy = 0
The value of a is:
a= x(y + I) ± .Jx(y + I)y(x + I) x-y
( 13)
(14)
(15)
(15) could be substitutes into (12) , and a new expre-
ssion is as follow:
v'", V;N (x + Y + I) [ .J x(y + l)y(x+ I) -y(x + I)] -=-=1+ (I6) V'M V2N Y[ x(x+ I) -.J x(y + I)y(x+ I) ] Let K = .J x(y + I)y(x + I) , and the value of ( 16) is lower
than 1.2. It could be deduced as:
[y + (x + I)]K -[x + (y + I)] y(x + I) "'---'--.;.;;....-"---"--;.;;.;...-'----'- < 0.2
y[x(x + I) -K ] (x+I)[K -y(y+l)]
�-I <0.2 Y[K-x(x+l)] The final formula could be presented as follow:
x+1 -1+--· y
( 17)
(18)
CI9)
I I � (1+-)'( 1+-) <1.44 (20) x y If the scope of x, y is [1, 5], (20) could be presented as
follow figure:
• •
FigS Extreme value distribution of voltage fault component ratio
4
Where z axis represents the value of Iv; I / lv, I . It can be
seen that the extreme values of Iv; I / lv, I are all above the sec
tion which value is 1.44.
IV. CASE STUDY
A. Simulation Model This paper build 10-unit and 39-bus New England test
system model to test the performance of this algorithm using
PSCADiEMTDC software. The voltage level of transmission line is 345kV. The frequency of power grid is 60HZ and fault
point is set in the middle of the line between bus 4 and bus 14.
Six types of fault are tested, and the protection programme is compiled using MATLAB 2009.
Let bus16 represents area central station of wide area
backup protection system. The single line figure and bus
number of simulation system is as follow:
39
9 _L...-...I....
Fig.6. lO-unit and 39-bus New England test system
B. Bus Sort Test There is only listing the voltage amplitude variable quantity
of bus3, 4, 5, 13, 14 and 15 for paper length restriction. The test results are shown in Table I-III.
When metal fault occurs, the positive sequence voltage
superimposed component, negative sequence and zero sequence voltage of the buses which are adjacent to fault point
are changes in different extent. Bus4 and 14 change more
remarkable than other buses for they are more adjacent to fault point than other buses. Positive sequence voltage super
imposed component could reflect all types of metal faults. But,
it couldn't reflect high resistance grounding fault. Negative sequence voltage could reflect all types of metal asymmetrical
faults and has the same problem with the former.
Only the zero sequence voltage of bus 14 starts up normally
when high resistance grounding fault occurs. Therefore, adding zero sequence voltage is helpful to identify nonmetal fault
5
in power grid. fault point is in the middle of line. Thus, it is possible that bus
According to the sort criteria presented before, bus 14 could 4 and 14 would be both selected in actual grid. But it would be selected as the bus which is the most adjacent to fault point. not add too large calculation scale and would not miss any
The value span between bus 14 and 4 is small, because the suspected event.
TABLEr POSITIVE SEQUENCE VOLTAGE SUPERIMPOSED COMPONENT RATIO OF BUSES
Fault ILw,l/kv Type
Bus3 Bus4 Bus5 Bus 13 Busl4 Busl5
AG 17.529 34.754 18.550 25.425 35.535 18.2 12
AG(3000)
Be 38.342 76.090 40.545 55. 185 77.683 39.622
Be (250) 24.934 45.009 26.208 34.068 45.627 25. 179
BeG 45.007 89.349 47.709 64.787 9 1.328 46.694
ABe 76.56 1 152.202 8 1.225 1 10.303 155.603 79.325
TABLE II NEGATIVE SEQUENCE VOLTAGE OF BUSES
Fault lu,! IkV Type
Bus3 Bus4 Bus5 Bus 13 Busl4 Busl5
AG 17.866 34.954 18.88 1 25.345 35.654 18.409
AG(3000)
Be 38.778 76.268 41. 13 1 55.395 78.025 39.885
Be (250) 29. 123 57.278 30.865 4 1.605 58.59 1 29.964
BeG 32.067 63.070 33.996 45.754 64.488 32.930
ABe
TABLE III ZERO SEQUENCE VOLTAGE OF BUSES
Fault Type
Bus3 Bus4 Bus5
AG 37.08 1 79.026 27. 15 1
AG(3000)
Be
Be (250)
BeG 28.234 56.563 20.696
ABe
C. Fault Location Test There is only listing the ratio result of line 4-14, 3-4 and
14-15 which are incident or sub-incident to bus 14. The test results are shown in Table IV-VI.
As is shown in test results, the ratio of positive voltage seq
uence superimposed component, negative and zero sequence voltage from two sides of line 4-14 could be higher than 1.200
lu,! IkV Bus 13 Busl4 Busl5
39.689 79.3 13 3 1.704
6.207
30.205 60.0 19 24.055
when grounding fault happens, and the sensitivity of zero sequence criterion is higher than others. The voltage ratio of
line 3-4 and 14-15 is near 1.000. The transient resistance
couldn't affect this algorithm. So the mal-operation and refusing operation could be forbidden reliably.
When phase to phase and symmetrical fault occurs, posi
tive sequence voltage superimposed component or negative
voltage criterion could identifY fault line correctly.
6
TABLE IV POSITNE SEQUENCE VOLTAGE SUPERIMPOSED COMPONENT RATIO
Fault ILlU;I/ILlUII
Type Bus3 Bus4 Busl4 Bus4 Busl5 Busl4 (L3 .. ) (L3-4) (LI4 .. ) (LI4 .. ) (LI4-l5) (LI4-1S)
AG 1.000 1.003 1.602 1.599 1.008 1.003
AG (300n) 1.006 1.004 1.609 1.592 1.008 1.005
BC 1.002 1.003 1.609 1.595 1.009 1.004
BC (25n) 0.996 1.002 1.6 1 1 1.594 1.0 10 1.00 1
BCG 1.005 1.00 1 1.608 1.597 1.006 1.003
ABC 1.004 1.00 1 1.608 1.594 0.999 1.00 1
TABLE V NEGATIVE SEQUENCE VOLTAGE RATIO
Fault lu;l/lu,1 Type Bus3 Bus4 Busl4 Bus4 Busl5 Busl4
(L3 .. ) (L3 .. ) (LI4 .. ) (LI4 .. ) (LI4-1S) (LI4-1S)
AG 1.000 1.003 1.602 1.599 1.007 1.002
AG (300n) 1.006 1.002 1.609 1.589 1.006 1.005
BC 1.00 1 1.003 1.609 1.595 1.009 1.004
BC (25n) 0.997 1.002 1.607 1.593 1.009 1.00 1
BCG 1.005 1.005 1.6 1 1 1.598 1.005 1.005
ABC
TABLE VI ZERO SEQUENCE VOLTAGE RATIO
Fault Type Bus3 Bus4 Busl4
(L3 .. ) (L3-4) (LI4 .. )
AG 0.999 1.005 1.862
AG (300n) 1.000 1.005 1.88
BC
BC (25n)
BCG 1.033 0.992 1.859
ABC
V_ CONCLUSION
The paper proposes a novel wide area backup protection algorithm for power grid fault location using PMU technique
based on centralized system structure. This algorithm could
realize region grid fault location by two steps and has been proved its effectiveness in simulation test. It could be adopted
with wide area differential current protection as protection
double configuration for many reasons. • The relay only uses voltage and current fault component
amplitude information to identify fault position and doe-
lu; I/luo I Bus4 Busl5 Busl4 (LI4-4) (LI4-1S) (LI4-1S)
1.826 1.0 14 0.998
1.826 1.020 1.00 1
1.806 1.0 18 0.994
sn't have a strict demand to data synchronization;
• The relay criterion doesn't affected by transient resistance and system non-all phase operation;
• Only the sub-graph and complete incidence matrix of all
buses should be calculated in central station off-line. There are many further work should be done for improving
this algorithm. The next work is as follows:
• Test and improve this algorithm in order to meet different power system operation condition. Such as: flow
transferring, system oscillation, multi-fault and so on;
• Simulate actual communication network and test the
communication delay of this method in order to verify its
real-time performance.
VI. REFERENCES
[I] Damir Novosel, George Bartok, Gene Henneberg, et al. "IEEE PSRC report on perfonnance of relaying during wide-area stressed conditions," IEEE Trans. Power Delivery, vo1.25, pp.3-16, Jan. 20 10.
[2] AG.Phadke, Synchronized Phasor Measurements and Their Applications, New York: Springer, 2008, p.2 1 1.
[3] Li Bin, Bo Zhiqian. "Investigation on Protection and Control of Smart grid," Automation of Electric Power Systems(in Chinese), vo1.33, pp.7-12, Oct. 2009.
[4] S. H. Horowitz, A G. Phadke. "Third zone revisited," IEEE Trans. Power Delivery, vo1.2 1, pp.23-29, Jan. 2006.
[5] XU Huiming, BI Tianshu, HUANG Shaofeng, et al. "Flow transferring identification algorithm for Multi-branches removal event with consideration of transient phenomena," Proceedings of the CSEE(in Chinese), vo1.27, pp.24-30, Aug. 2007.
[6] WANG Yang, YIN Xianggen, ZHAO Yijun, et al. "Regional power network intelligent protection based on genetic algorithm," Automation of Electric Power Systems(in Chinese), voL32, pp. 40---44, Sep. 2008.
[7] SU Sheng, K. K. Li, W. L. Chan, et al. "Agent-based self-healing protection system," IEEE Trans. Power Delivery, vo1.2 1, pp.6 10-618, Apr. 2006.
[8] Xiaoyang Tong, Xiaoru Wang, Kenneth Hopkinson. "Agent-based selfhealing protection system," IEEE Trans. Power Delivery, vo1.24, pp.6 1-72, Jan. 2009.
[9] Cong Wei, Pan Zhencun, Zhao Jianguo. "A wide area relaying protection algorithm based on longitudinal comparison principle," Proceedings of the CSEE(in Chinese), vo1.26, pp.8-14, Jul. 2006.
[ 10] Yang Zengli, Shi Dongyuan, Duan Xianzhong. "Wide-area protection system based on direction comparison principle," Proceedings of the CSEE(in Chinese), vo1.28, pp.77-8 1, Aug. 2008.
[II] M. M. Eissa, M. E1shahat Masoud, M. Magdy Mohamed Elanwar, et al. "A novel back up wide area protection technique for power transmission grids using phasor measurement unit," IEEE Trans. Power Delivery, vo1.25, pp.270-278, Jan. 20 10.
[ 12] Zhang Yagang, Zhang Jinfang, Ma Jing, Wang Zengping. "Fault detection and identification based on DFS in electric power network," KAM Workshop IEEE International Symposium, 2008, pp.742-745.
[ 13] Miao Shihong, Liu Pei, Lin Xiangning, et al. "A new type of backup protective system in wide area network based on data network," Automation of Electric Power Systems(in Chinese), voL32, pp.32-36, May. 2008.
[ 14] Zhao manyong, Zhou hongjiang, Chen Zhaohui, et al. "A new wide-area Integrated protection scheme based on IEC6 1850," Automation of Electric Power Systems(in Chinese), vo1.34, pp.58--{50, Mar. 20 10.
[ 15] Xiangning Lin, M. Zhengtian Li, Kecheng Wu, et al. "Principles and implementations of hierarchical region defensive systems of power grid," IEEE Trans. Power Delivery, vo1.24, pp.30-37, Jan. 2009.
VII. BIOGRAPHIES
Zhiqin He was born in Jiangxi province, China, on February 5, 1982. He received the B.S. and M.S. degrees from East China Jiaotong University, Nanchang, in 2003 and 2006. He is currently pursuing the Ph.D degree in electrical power engineering at the Huazhong University of Science and Technology, Wuhan, China.
His research interests include power system wide area protection and control.
7