+ All Categories
Home > Documents > IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

Date post: 30-Mar-2015
Category:
Upload: joy-joyce-pickett
View: 232 times
Download: 11 times
Share this document with a friend
Popular Tags:
115
IEEE PESC-02 JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias
Transcript
Page 1: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

IEEE PESC-02 JUNE 20021

HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS

Presented by

Stefanos Manias

Page 2: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-022

CONTACT INFORMATION

Stefanos N. ManiasNational Technical University of AthensPhone: +3010-7723503FAX: +3010-7723593E-mail: [email protected]

Mailing AddressNational Technical University of AthensDepartment of Electrical and Computer Engineering9, Iroon Polytechniou Str, 15773 ZografouAthens, Greece

Page 3: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-023

PLAN OF PRESENTATION

1. DEFINITIONS

2. CATEGORIES OF POWER QUALITY VARIATIONS

3. HARMONIC DISTORTION SOURCES IN INDUSTRIAL POWER SYSTEMS

4. EFFECTS OF HARMONICS ON ELECTRICAL EQUIPMENT

5. HARMONIC MEASUREMENTS IN INDUSTRIAL POWER SYSTEMS

6. HARMONIC STANDARDS

7. HARMONIC MITIGATING TECHNIQUES

8. GENERAL PASSIVE AND ACTIVE FILTER DESIGN PROCEDURES

9. DESIGN EXAMPLES

10. CONCLUSIONS

Page 4: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-024

WHY HARMONIC ANALYSIS ?

When a voltage and/or current waveform is distorted, it causes abnormal operating conditions in a power system such as:

Voltage Harmonics can cause additional heating in induction and synchronous motors and generators.

Voltage Harmonics with high peak values can weaken insulation in cables, windings, and capacitors.

Voltage Harmonics can cause malfunction of different electronic components and circuits that utilize the voltage waveform for synchronization or timing.

Current Harmonics in motor windings can create Electromagnetic Interference (EMI).

Page 5: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-025

Current Harmonics flowing through cables can cause higher heating over and above the heating that is created from the fundamental component.

Current Harmonics flowing through a transformer can cause higher heating over and above the heating that is created by the fundamental component.

Current Harmonics flowing through circuit breakers and switch-gear can increase their heating losses.

RESONANT CURRENTS which are created by current harmonics and the different filtering topologies of the power system can cause capacitor failures and/or fuse failures in the capacitor or other electrical equipment.

False tripping of circuit breakers ad protective relays.

Page 6: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-026

a) Current Source nonlinear load

Diode rectifier for ac drives, electronic equipment, etc

HARMONIC SOURCES

Thyristor rectifier for dc drives, heater drives, etc.

Per-phase equivalent circuit of thyristor rectifier

b) Voltage source nonlinear load

Per-phase equivalent circuit of diode rectifier

Page 7: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-027

0 10 20 30 40-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

0 10 20 30 40-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

0 10 20 30 40-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

 TYPE OF

NONLINEAR LOAD

 TYPICAL WAREFORM

 THD%

 1-φ

Uncontrolled Rectifier

 

 80%

(high 3rd component)

  

1-φSemicontrolled Rectifier Bridge

 

 2nd, 3rd, 4th ,......

harmonic components

6 –Pulse Rectifierwith output voltage filtering and without input reactor filter

  

80% 

5, 7, 11, ……….

INPUT CURRENT OF DIFFERENT NOLINEAR LOADS

 

Page 8: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-028

010 20 30 40

-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

0 10 20 30 40-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

0 10 20 30 40-1.0

-0.5

0.0

0.5

1.0

Time (mS)

Cur

rent

6 - Pulse Rectifierwith large output

inductor

  

28%5, 7, 11, ………..

 6 - Pulse Rectifier

with output voltage filtering and with 3% reactor filter or with

continues output current

  

40%5, 7, 11, ………..

  

12 - Pulse Rectifier 

  

15%11, 13, ………..

Page 9: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-029

CURRENT HARMONICS GENERATED BY 6-PULSE CSI CONVERTERS

HARMONIC P.U PULSE

1 1.005 0.27 0.143

11 0.0913 0.07717 0.05919 0.05323 0.04

CURRENT HARMONICS GENERATED BY 12-PULSE CSI CONVERTERS

HARMONIC P.U PULSE IEEE 519 std

1 1.00 -

5 0.03-0.06 5.6%7 0.02-0.06 5.6%

11 0.05-0.09 2.8%

13 0.03-0.08 2.8%THD 7.5%-14.2% 7.0%

Page 10: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0210

RECENT CURRENT MEASUREMENTS TAKEN IN ANINDUSTRIAL PLANT WITH 600 KVA, 20 KV/400 V

DISTRIBUTION TRANFORMER

Current waveform and its respective spectrumat the inputs of a motor drive system

Page 11: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0211

Current waveform and its respective spectrum

at the inputs of a motor drive system

Page 12: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0212

Current waveform and its respective spectrum

at the secondary of the distribution transformer

( i.e. at the service entrance)

Page 13: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0213

DEFINITIONS

f (t) = Fourier Series of a periodic function f (t) =

1hhho θtωh cosCC (1)

Too dttf

T

1C ,)( (2)

Toh dt)tωhcos()t(f

T

2A (3)

Toh dt)tωhsin()t(f

T

2B (4)

h = harmonic order

2h

2hh BAC

Page 14: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0214

% υTHD

100V

V

1

2h

2h

(5)

% iTHD

100I

I

1

2h

2h

(6)

Percentage of the Total Harmonic Distortion of a nonsinusoidal voltage waveform

Percentage of the Total Harmonic Distortion of a nonsinusoidal current waveform

hthVh

hthIh

harmonic component of the voltage

harmonic component of the current

V~

H RMS value of the voltage distortion V~

2h

2h

Page 15: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0215

I~

1h

2hI

~ (7)

V~

V~1h

2h

(8)

100VAk SC

kVA DriveHF %υTHD (9)

15h

2h

2 I/Ih

(10)

RMS value of a nonsinusoidal current =

RMS value of a nonsinusoidal voltage =

HF Harmonic Factor =

I~H RMS value of the current distortion I

~

2h

2h

Page 16: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0216

kVA Drive

kVA SC

SINUSOIDAL VOLTAGE NONSINUSOIDAL CURRENT

1i,1 φcosI~ V

~P

I~ V

~S , φsinI

~ V

~Q 1i,1

(11)

(12)

(13)

Full load kVA rating of the Drive system

Short Circuit kVA of the distribution system atthe point of connection

222 QPS VA DistortionD

Page 17: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0217

2h

2h,i

221,i

222 I~

V~

I~

V~

SD (14)

S

PFactor Power True 1

1,i φcosI

(15)

Factorment Displace Factor Distortion

NONSINUSOIDAL VOLTAGE AND NONSINUSOIDAL CURRENT

1h 1hhhh , hhh φsinI

~V~

QφcosI~

V~

P (16)

SSSSPower DistortionD

mnm n

*mn

*nm

mnmn

nm

(17)

Page 18: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0218

2222 DQPS (18)

2 N

21

2HH

21H

2H1

211

1h

2h

2h

SS I~

V~

I~

V~

I~

V~

I~

V~

I~

V~

S

(19)

111 I~

V~

PowerApparent lFundamenta S

PowerApparent ntalNonfundame SN

2HH2

1H2

H12N I

~V~

I~

V~

I~

V~

S

Page 19: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0219

Power DistortionCurrent I~

V~

H1 (20)

Power Distortion Voltage I~

V~

1H (21)

PowerApparent Harmonic I~

V~

HH (22)

Power ActiveNon Harmonic Total

Power Active Harmonic Total NP S 2H

2H

2H

(23)

phase32

L-LC VAR/V capacitor theof Reactance X

Page 20: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0220

Harmonic sequence is the phase rotation relationship with respect to the fundamental component.

Positive sequence harmonics ( 4th, 7th, 10th , ……. (6n+1) th ) have the same phase rotation as the fundamental component. These harmonics circulate between the phases.

Negative sequence harmonics ( 2nd, 5th, 8th ……… (6n-1) th ) have the opposite phase rotation with respect to the fundamental component. These harmonics circulate between the phases.

Zero sequence harmonics ( 3rd, 6th, 9th, ….. (6n-3) th ) do not produce a rotating field. These harmonics circulate between the phase and neutral or ground. These third order or zero sequence harmonics, unlike positive and negative sequence harmonic currents, do not cancel but add up arithmetically at the neutral bus.

Page 21: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0221

EXAMPLE 1

A periodic, sinusoidal voltage of instantaneous value tωsin2200v Is applied to a nonlinear load impedance. The resulting instantaneous current is

given by: ooo 60tω3sin1060tω2sin1045tωsin202i Calculate the components P, Q, D of the apparent voltamperes and hence calculate the displacement factor, the distortion factor and the power factor.

Solution

tωsin2200v

ooo 60tω3sin1060tω2sin1045tωsin202i The presence of the nonlinearity causes frequency components of current (i.e. the

second and third harmonic terms) that are not present in the applied voltage.

The rms voltage and current at the supply are:

V200V~

2222 101020I~

22A106

SINUSOIDAL VOLTAGE-NONSINIMUSOIDAL CURRENT

Page 22: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0222

The apparent voltamperes at the input is therefore given by

2622222 VA1024106200I~

V~

S

In this example only the fundamental frequency components are common to both voltage and current. Therefore, the real power P and the apparent power Q are

11 ψcosI~

V~

P

o45cos20200

W2

4000

11 ψsinI~

V~

Q o45sin20200

VA2

4000

1ψ = displacement angle between the fundamental of the voltage and the fundamental of the current

Page 23: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0223

21

222 I~

I~

V~

D

232

2 I~

I~

V~

26222 VA1081010200 22222 I

~V~

DQP

Displacement factor 707.02

1ψcos 1

Distortion factor 817.0600

20

I

I1

Therefore, the power factor is

577.06

2

2

1PF

1111 ψcosI

I~

I~

V~

ψcosI~

V~

S

Pfactorpower PF

Page 24: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0224

EXAMPLE 2

A periodic, sinusoidal voltage given by o30tω5sin200tωsin2002v is applied to a series, linear, resistance-inductance load of resistance 4Ω and

fundamental frequency reactance 10Ω. Calculate the degree of power factor improvement realizable by capacitance

Solution. The rms terminal voltage is given by25

21 V

~V~

V~

Compensation when .HZ50f1

22 200200

V~

Therefore

V283V~

10j4Z1

8.10Z1

o2.684/10tan 11

NONSINUSOIDAL VOLTAGE-RL LOAD

Page 25: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0225

505 15

50j4Z5

50Z5

o15 4.854/50tan

The instantaneous load current is given by

ooo 4.8530t5sin

50

2002.68tsin

8.10

2002i

The rms load current I~

is therefore given by

2

5

5

2

1

125

21

2

Z

V~

Z

V~

I~

I~

I~

222 A359452.18

Page 26: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0226

Average power P In this case is

...cosI~

V~

cosI~

V~

cosI~

V~

Pn

1222111Lnn

oo 4.85cos42002.68cos52.18200

W1440

The power factor before compensation is therefore

27.01072.28

1440

S

PPF

6

26222 VA1072.28I~

V~

S

Apparent voltamperes S at the load terminals in the absence of capacitance is

therefore

Page 27: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0227

EXAMPLE 3

A periodic, nonsinusoidal voltage with instantaneous value given by

o30-tω2sin200tωsin2002v

Solution.

is applied to a nonlinear impedance.

The resulting current has an instantaneous value given by

oooL 60tω3sin1060tω2sin1045tωsin202i Calculate the components LDLXLR S,S,S of the load apparent voltamperes

and compare thee with the classical values LLL D,Q,P respectively.

o30-tω2sin200tωsin2002v

oooL 60tω3sin1060tω2sin1045tωsin202i

Note that the presence of the load nonlinearity causes a frequency component of load current (I.e. the third harmonic term) that is not present in the supply voltage.

NONSINUSOIDAL VOLTAGE AND NONSINIMUSOIDAL CURRENT

Page 28: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0228

The rms voltage and current at the supply are given by

24222 V108200200V~

222222L A106101020I

~ The load apparent voltamperes LS therefore has a value defined in terms V

~ andLI

~

262L

22L VA1048I

~V~

S

Instantaneous expressions of the hypothetical currents DXR i,i,i are given by

o0oR 30t2sin30cos10tsin45cos202i

222o2o2LR A10

4

1130cos1045cos20I

~

o0oX 30tω2cos30sin10tωcos45sin202i

222o2o2LX A10

4

930sin1045sin20I

~

oD 60t3sin10 2i

222LD A10I

~

Page 29: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0229

Note that current components XR i,i contain only those harmonic terms which

are common to both voltage and current. These are therefore consistent with the

1n terms.

The rms load current components LDLXLR I~

,I~

,I~

are found, as expected to sum

to the total rms load current LI~

2L

222LD

2LR

2LD I

~106

4

9

4

11110I

~I~

I~

Components LDLXLR S,S,S of the apparent voltamperes can now be obtained

26422LR

22LR VA102210810

4

11I~

V~

S

26422LX

22LX VA101810810

4

9I~

V~

S

26422LD

22LD VA10810810I

~V~

S

Page 30: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0230

The component voltamperes are seen to sum to the total apparent voltamperes

8182210SSS 62LD

2LX

2LR

26 VA10482LS

Components LLL D,Q,P of LS are found as follows:

2n

11n1n1n

2L ψcosI

~V~

P

2oo 30cos1020045cos20200

22 310220100

2LR

6626 S108.2064381032210

Page 31: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0231

2n

11n1n1n

2L ψsinI

~V~

Q

2oo 30sin1020045sin20200

2LX

66 S106.1412210

2L

2L

2L

2L QPSD

2LD

266 SVA106.12106.148.2048 From the possible compensation viewpoint it is interesting to note that LXSand LQ differ by significant amount.

LXS could be defined as “that component of the load apparent voltamperes that

Is obtained by the combination of supply voltage harmonics with quadrature

Components of corresponding frequency load current harmonics”.

Page 32: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0232

Similarly the definition of active voltamperes LRS could be given by “that

component of the load apparent voltamperes that is obtained by the combination

of supply voltage harmonics with in-phase components of corresponding

frequency load current harmonics”.

Both LRS and LXS are entirely fictitious and non-physical. The active

voltamperes LRS Is not to be compares in importance with the average power

LP which is a real physical property of the circuit. Term LRS Is merely the

analytical complement of term LXS

Term LXS the energy-storage reactive voltamperes, is that component

of the load apparent voltamperes that can be entirely compensated (for sinusoidal

supply voltage) or minimized (for nonsinusoidal supply voltage) by energy-storage

methods.

Page 33: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0233

Voltage and current profiles in a commercial building

Page 34: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0234

HARMONIC STANDARDS

International Electrotechnical Commission (IEC) European Standards.

- EN 61000-3-2 Harmonic Emissions standards were first published as IEC 55-2 1982 and applied only to household appliances. It was revised and reissued in 1987 and 1995 with the applicability expanded to include all equipment with input current 16A per phase. However, until January 1st, 2001 a transition period is in effect for all equipment not covered by the standard prior to 1987.

- The objective of EN 61000-3-2 (harmonics) is to test the equipment under the conditions that will produce the maximum harmonic amplitudes under normal operating conditions for each harmonic component. To establish limits for similar types of harmonics current distortion, equipment under test must be categorized in one of the following four classes.

Page 35: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0235

CLASS-A: Balanced three-phase equipment and all other equipment

except that stated in one of the remaining three classes.

CLASS-B: Portable electrical tools, which are hand held during normal

operation and used for a short time only (few minutes)

CLASS-C: Lighting equipment including dimming devices.

CLASS-D: Equipment having an input current with special wave shape

( e.g.equipment with off-line capacitor-rectifier AC input

circuitry and switch Mode power Supplies) and an active

input power 600W.

- Additional harmonic current testing, measurement techniques and instrumentation guidelines for these standards are covered in IEC 1000-4-7.

Page 36: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0236

• IEEE 519-1992 United States Standards on harmonic limits

- IEEE limits service entrance harmonics.

- The IEEE standard 519-1992 limits the level of harmonics at the customer service entrance or Point of Common Coupling (PCC).

- With this approach the costumer’s current distortion is limited based on relative size of the load and the power supplier’s voltage distortion based on the voltage level.

IEEE 519 and IEC 1000-3-2 apply different philosophies, which effectively limit harmonics at different locations. IEEE 519 limits harmonics primarily at the service entrance while IEC 1000-3-2 is applied at the terminals of end-user equipment. Therefore, IEC limits will tend to reduce harmonic-related losses in an industrial plant wiring, while IEEE harmonic limits are designed to prevent interactions between neighbors and the power system.

Page 37: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0237

POWER QUALITY STANDARDS – IEEE 519-1992 STANDARDS

TABLE ICURRENT DISTORTION LIMITS FOR GENERAL DISTRIBUTION SYSTEMS

(120-69000 V)

Isc/IL <11 11<h<17 17<h<23 23<h<35 35<h TDD

<20* 4.0 2.0 1.5 0.6 0.3 5.0

20<50 7.0 3.5 2.5 1.0 0.5 8.0

50<100 10.0 4.5 4.0 1.5 0.7 12.0

100<1,000 12.0 5.5 5.0 2.0 1.0 15.0

>1,000 15.0 7.0 6.0 2.5 1.4 20.0Source: IEEE Standard 519-1992.Note: Even harmonics are limited to 25 percent of the odd harmonic limits above.

Current distortions that result in a direct current offset; for example, half wave converters are not allowed.

Table I is for 6-pulse rectifiers. For converters higher than 6 pulse, the limits for characteristic harmonics are increased by a factor o f q/6 , where q is the pule number, provided that the amplitudes of noncharacteristic harmonics are less than 25 percent. *All power generation equipment is limited to these values of current distortion, regardless of actual ISC/IL.

Where ISC = Maximum short circuit at PCC.

And IL = Average Maximum demand load current (fundamental frequency

component at PCC).

Page 38: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0238

TABLE IILOW VOLTAGE SYSTEM CLASSIFICATION AND DISTORTION LIMITS

IEEE 519-1992 STANDARTS

Special Applications

General System

Dedicated System

Notch Depth 10% 20% 50%

THD (Voltage) 3% 5% 10%

Notch Area

(AN)*

16,400 22,800 36,500

Source: IEEE Standard 519-1992.Note: The value AN for another than 480Volt systems should be

multiplied by V/480 . The notch depth, the total voltage distortion factor (THD) and

the notch area limits are specified for line to line voltage. In the above table, special applications include hospitals and

airports. A dedicated system is exclusively dedicated to converter load.*In volt-microseconds at rated voltage and current.

Page 39: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0239

TABLE III

LIMITS OF THD%

IEEE 519-1992 STANDARDS

SYSTEM Nominal Voltage

Special Application

General Systems

Dedicated Systems

120-600V 3.0 5.0 8.0

69KV and below - 5.0 -

Page 40: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0240

TABLE IVPROPOSED IEC 555-2 CLASS D STANDARDS for power from 50 to 600W

Harmonic Relative limits

Milliamps/Watt

Absolute Limits Amps

3 3.4 2.30

5 1.9 1.14

7 1.0 0.77

9 0.5 0.40

11 0.35 0.33

13 linear extrapolation

0.15 (15/n)

Page 41: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0241

METHODOLOGY FOR COMPUTING DISTORTION

Step 1: Compute the individual current harmonic distortion at each dedicated bus using different Software programs (i.e. SIMULINK, SPICE, e.t.c.) or tables that provide the current distortion of nonlinear loads.

Step 2: Compute the voltage and current harmonic content at the Point of Common Coupling (PCC) which is located at the input of the industrial power system.

- Each individual harmonic current at the PCC is the sum of harmonic current contribution from each dedicated bus.

- The load current at PCC is the sum of the load current contribution from each dedicated bus.

- The maximum demand load current at PCC can be found by computing the load currents for each branch feeder and multiply by a demand factor to obtain feeder demand. Then the sum of all feeder demands is divided by a diversity factor to obtain the maximum demand load current.

Page 42: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0242

Step 3: Choose a base MVA and base KV for the system use the following equations in order to compute individual and total current and voltage harmonic distortions at PCC and any other point within the power system.

Ib= Base current in Amps Ampsb

3b

kV3

10MVA

= System impedance = p.u. MVA

MVA

sc

b

MVAb= Base MVA, MVAsc= short circuit MVA at the point of interest

VH= Percent individual harmonic voltage distortion =

Volts 100ZhI

Is

b

h

(24)

(25)

(26)

sZ

Page 43: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0243

h = harmonic order

100V

21V

%THD1

2h

2h

υ

100I

I

%THD1

2

2h

2h

i

IH = Percent individual harmonic distortion = 100I

I

L

h

Isc = Short Circuit current at the point under consideration.

IL = Estimated maximum demand load current

S.C. Ratio = Short circuit Ratio D

sc

L

scMVA

MVA

I

I

MVAD = Demand MVA

(27)

(28)

(29)

Page 44: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0244

K Factor = Factor useful for transformers design and specifically from transformers that feed Adjustable Speed Drives

1h

2

L

h2

I

Ih

ONCE THE SHORT CIRCUIT RATIO IS KNOWN, THE IEEE CURRENT HARMONIC LIMITS CAN BE FOUND AS SPECIFIED IN TABLE I OF THE IEEE 519-1992 POWER QUALITY STANDARDS

USING THE ABOVE EQUATIONS VALUES OF IDIVINDUAL AND TOTAL VOLTAGE AND CURRENT HARMONIC DISTORTION CAN BE COMPUTED AND COMPARED WITH THE IEEE LIMITS

(30)

Page 45: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0245

Step 4: If the analysis is being performed for CSI-type drives then the area of the voltage notch AN should also be computed.

- At this point an impedance diagram of the under analysis industrial power system should be available.

- The Notch Area AN at the PCC can be calculated as follows.

AN = AN1 + AN2 + …………. V . microsec

AN1 , AN2 , …… are the notch areas contribution of the different busses

ANDR1 : Notch area at the input of the drive

1NDR1N Adrive the toPCC from sinductance of sum the inductance Source

inductance SourceA

(31)

(32)

Page 46: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0246

Step 5: Determine preliminary filter design.

Step 6: Compute THDv and THDi magnitudes and impedance versus frequency plots with filters added to the system, one at a time. SIMULINK or PSPICE software programs can be used for final adjustments.

Step 7: Analyze results and specify final filter design.

Page 47: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0247

EXAMPLE OF A SYSTEM ONE LINEDIAGRAM

Page 48: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0248

System impedances diagram which can be used to calculate its resonance using PSPICE or SIMULINK

programs

Page 49: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0249

1) Parallel-passive filter for current-source nonlinear loads

TYPES OF FILTERS

• Harmonic Sinc• Low Impedance• Cheapest• VA ratings = VT (Load Harmonic current + reactive current of the filter)

Page 50: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0250

2) Series-passive filter for voltage-source nonlinear loads

• Harmonic dam• High-impedance• Cheapest• VA ratings = Load current (Fundamental drop across filter + Load Harmonic Voltage)

Page 51: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0251

3) Basic parallel-active filter for current source in nonlinear loads

Page 52: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0252

4) Basic series-active filter for voltage-source in nonlinear loads

Page 53: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0253

5) Parallel combination of parallel active and parallel passive

6) Series combination of series active and series passive

Page 54: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0254

7) Hybrid of series active and parallel passive

8) Hybrid of parallel active and series passive

Page 55: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0255

9) Series combination of parallel-passive and parallel-active

10) Parallel combination of series-passive and series-active

Page 56: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0256

11) Combined system of series-active and parallel-active

12) Combined system of parallel-active and series-active

Page 57: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0257

A SIMPLE EXAMPLE OF AN INDUSTRIAL POWER DISTRIBUTION SYSTEM

Page 58: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0258

HARMONIC LIMITS EVALUATION WHEN POWER-FACTOR-CORRECTION CAPASITORS

ARE USED

- As it can be seen from the power distribution circuit the power-factor-correction capacitor bank, which is connected on the 480 Volts bus, can create a parallel resonance between the capacitors and the system source inductance.

- The single phase equivalent circuit of the distribution system is shown below.

Using the above circuit the following equations hold:

Source AC

totL SI

C

inZ

hI

fI

SV

HarmonicLoad

totR

Page 59: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0259

,

R

Xtancos

MVA

kVR 1

sc

2LL

sys 2sys

sysα

RR

,

R

Xtansin

MVA

kVX 1

sc

2LL

sys 2sys

sysα

XX

tr

2LL

putr kVA

kV1000RR

tr

2LL

putr kVA

kV1000XX

α = The turns ratio of the transformer at PCC

(33)

(34)

(35)

(36)

Page 60: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0260

trsystot XXX

cap

2cap

c kVAR

kV1000X

ω

XL tot

tot fπ2

Xtot

1C

c

1Xc

trsystot RRR (37)

(38)

(39)

(40)

(41)

(42)

Page 61: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0261

Cω1

jLωjR

Cω/jLωjRZ

tottot

tottotin

, Cω

1Lω

ototo

oo πω2

1f

The impedance looking into the system from the load, consists of the parallel combination of source impedance and the capacitor impedance tottot jXR

inZ

The equation for can be used to determine the equivalent system impedance for different frequencies. The harmonic producing loads can resonate (parallel resonance), the above equivalent circuit. Designating the parallel resonant frequency by (rad/sec) or (HZ) and equating the inductive and capacitive reactances.

inZ

oω of

(43)

(44)

Page 62: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0262

- Harmonic current components that are close to the parallel resonant frequency are amplified.- Higher order harmonic currents at the PCC are reduced because the capacitors are low

impedance at these frequencies.- The figure below shows the effect of adding capacitors on the 480 Volts bus for power factor

correction.

This figure shows that by adding some typical sizes of power factor correction capacitors will result in the magnification of the 5th and 7th harmonic components, which in turns makes it even more difficult to meet the IEEE 519-1992 harmonic current standards .

- Power factor correction capacitors should not be used without turning reactors in case the adjustable speed drives are >10% of the plant load.

Page 63: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0263

Let us examine an industrial plant with the following data:- Medium voltage = 20KVLL

- Low voltage = 0.4 KVLL

- Utility three phase short circuit power = 250 MVA- For asymmetrical current, the ratio of system impedance

R

X 4.2

The Transformer is rated:

1000 KVA, 20 KV-400 Y/230 V

Rpu = 1%, Xpu = 7%

- The system frequency is: fsys = 50 HZ.

- For power factor correction capacitors the following cases are examined:

a. 200 KVAR

b. 400 KVAR

c. 600 KVAR

d. 800 KVAR

EXAMPLE

Page 64: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0264

The parallel resonant frequencies for every case of power factor correction is calculated as follows:

Ω6154.04.2tancos250

20R 1

2

sys

Ω4769.14.2tansin250

20X 1

2

sys

504.0

20α

Ω000246.0506154.0R 2sys

Ω000591.0504769.1X 2sys

Ω00160.0

1000

4.0100001.0R

2

tr

Ω0112.0

1000

4.0100007.0X

2

tr

Page 65: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0265

Ω 001846 . 0 0016 . 0 000246 . 0 Rtot

Ω011791.00112.0000591.0Xtot

H1055.3750π2

011791.0L 6

tot

Case a:

Ω 8.0

200

4.01000X

2

c

F1098.38.050π2

1C 3

HZ18.4121098.31050.37π2

1f

36o

For 200 KVAR, the harmonic order at which parallel resonance occurs is:

24.85018.412h

Page 66: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0266

Case b:

Ω 4.0

400

4.01000X

2

c

F1096.7C 3

HZ45.291fo

83.5h

Case c:

Ω 267.0

600

4.01000X

2

c

F1094.11C 3

HZ97.237fo

76.4h

Page 67: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0267

Case d:

Ω 2.0

800

4.01000X

2

c

F1092.15C 3

HZ08.206fo

12.4h

It is clear for the above system that in the 600 KVAR case, there exists a parallel resonant frequency close to the 5th harmonic.of

Page 68: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0268

POWER FACTOR CORRECTION AND HARMONIC TREATMENT USING TUNED FILTERS

- Basic configuration of a tuned 3-φ capacitor bank for power factor correction and harmonic treatment.

Simple and cheap filter Prevents of current harmonic magnification

Page 69: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0269

- IN ORDER TO AVOID HARMONIC MAGNIFICATION WE CHOOSE A TUNED FREQUENCY < FITH HARMONIC (i.e 4.7)

- The frequency characteristic of the tuned filter at 4.7 is shown below

As it can be seen from the above figure significant reduction of the 5th harmonic is achieved. Moreover, there is some reduction for all the other harmonic components.

Page 70: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0270

The single phase equivalent circuit of the power distribution system with the tuned filter is shown below

Using the above circuit the following equations hold:

Page 71: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0271

0Cω

1LωLω

ofototo

21

ftot

oCLLπ2

1f

Cω1LωLωjR

LωjRII

ftottot

tottothf

cap2

os

2cap

2os

c2

osf

kVARfπ2

kV1000f

fπ2

Xfπ2

fπ2C

1L

(parallel resonance)

= resonance frequency of the equivalent distribution circuit

21

f

osCLπ2

1f

= Resonant frequency of the series filter

The new parallel combination is having resonant frequency when

Also

(45)

(46)

(47)

(48)

Page 72: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0272

Cω1

jLωjLωjR

Cω1

jLωjLωjRZ

ftottot

ftottot

in

Cω1

LωLω jR

Cω1

jLωjLωjR

ftottot

ftottot

tottotsh LωjRIV

Cω1LωLω jR

Cω/1Lω jII

ftottot

fhs

(49)

(50)

(51)

Page 73: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0273

As it was discussed before Selecting HZ235fo or 4.7 th harmonic

With KVcap= 0.4 , KVARcap= 600

Hμ45.38H1045.68600235π2

4.0100050L 6

2

2

f

The new parallel combination is having resonant frequency:

CLLπ2

1f

ftoto

with H1055.37L 6tot

H1045.38L 6

f

F1094.11C 3

we have

HZ16.1671094.111076π2

1f

36o

43.350/16.167h (without Lf was 4.76)

Page 74: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0274

The following table shows the variation of Parallel resonant frequencyWith and without resonant inductor

KVAR C(mF)

Parallel Resonant f0

Without Lf With Lf

200 3.98 8.80 115.3μH 4.08

400 7.96 6.22 57.7μH 3.66

600 11.94 5.08 38.45μH 3.43

800 15.92 4.40 29.5μH 3.08

Page 75: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0275

voltage

motor

+i -

i tot

compens

chock2%5

chock2%3 chock2%1

+- v

Voltage Measurement3

+- v

V1

+- v

V

T1

T

Source1

Source

Series RLC Branch3 Series RLC Branch2

Series RLC Branch1

Series RLC Branch

Scope4

Scope3

Scope2

Scope1

Scope

Ground (output)1

Ground (output)

Ground (input)8

Ground (input)5 Ground (input)4

Ground (input)3 Ground (input)2

Ground (input)1

Ground (input)

Gnd

+ i-

Current Measurement6

+i-

Current Measurement5+

i -Current Measurement4

+ i-

Current Measurement3

+i -Current Measurement1

+ i-

C

Bus Bar (horiz)7

Bus Bar (horiz)6

Bus Bar (horiz)5

Bus Bar (horiz)4

Bus Bar (horiz)3

Bus Bar (horiz)2

Bus Bar (horiz)1

Bus Bar (horiz)

AC Voltage Source

AC Current Source8

AC Current Source7

AC Current Source6

AC Current Source5

AC Current Source4

AC Current Source3

AC Current Source2

AC Current Source1

AC Current Source

50m cable 4x1

380kw/490rpm

200m cable 4x240

.

SIMULATED RESULTS USING MATLAB/SIMULINK

Page 76: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0276

SIMULINK RESULTS

Page 77: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0277

SIMULINK RESULTS

Page 78: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0278

ACTIVE FILTERING

Parallel type Series type

Page 79: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0279

-2500

-1500

-500

500

1500

2500

0 5 10 15 20 25 30 35 40

I[A]

Time [ms]

0

5

10

15

20

25

30

2 5 8 11 14 17 20 23

[% I

1]

Harmonics

-5000

-2500

0

2500

5000

0 10 20 30 40

Time [ms]

I D

ynacom

p [

A]

0%

5%

10%

15%

20%

25%

30%

35%

2 5 8 11 14 17 20 23

Harmonics

[%I1

]

RESULTS OF ACTIVE FILTERING

Input current of a 6-pulse Rectifier driving a DC machine without any input filtering

Input current with Active Filtering

Page 80: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0280

-1000

-500

0

500

1000

0 5 10 15 20 25 30 35 40

U [

V]

Time [ms]

0

2

4

6

8

10

12

14

2 5 8 11 14 17 20 23

[% U

1]

Harmonics

-1000

-500

0

500

1000

0 5 10 15 20 25 30 35 40

U [

V]

Time [ms]

0

2

4

6

8

10

12

14

2 5 8 11 14 17 20 23

[% U

]

Harmonics

Typical 6-pulse drive voltage waveform

Voltage source improvement with active filtering

Page 81: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0281

SHUNT ACTIVE FILTERS

By inserting a parallel active filter in a non-linear load location we can inject a harmonic current component with the same amplitude as that of the load in to the AC system.

C

FL

Equivalent circuit

Page 82: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0282

Low implementation cost.

Do not create displacement power factor problems and utility loading.

Supply inductance LS, does not affect the harmonic compensation of parallel active filter system.

Simple control circuit.

Can damp harmonic propagation in a distribution feeder or between two distribution feeders.

Easy to connect in parallel a number of active filter modules in order to achieve higher power requirements.

Easy protection and inexpensive isolation switchgear.

Easy to be installed.

Provides immunity from ambient harmonic loads.

ADVANTAGES OF THE SHUNT OR PARALLELACTIVE FILTER

Page 83: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0283

WAVEFORMS OF THE PARALLEL ACTIVE FILTER

Source voltage

Load current

Source current

A. F. output current

Page 84: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0284

G1Z

Z

VI

G1Z

Z

ZI

LS

SLH

LS

LS

G1Z

Z

V

G1

1I

G1Z

Z

G1Z

IL

S

SLH

LS

L

L

hSh

L ZG1

Z

LhC II

0Z

VG1IG1I

L

ShLHhSh

(53)

(54)

(55)

(56)

(57)

1G h 0G1

LC GII (52)

If

Then the above equations become

PARALLEL ACTIVE FILTER EQUATIONS

Page 85: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0285

L

ShLHhLh Z

VII (58)

G1I

I

LH

S

LHI

LZ

G

= Source impedance

= Is the equivalent harmonic current source

= Equivalent load impedance

= equivalent transfer function of the active filter

For pure current source type of harmonic source SL ZZ

and consequently equations (53) and (55) become

SZ

(59)

1G1 h (60)

Equation (55) is the required condition for the parallel A.F. to cancelthe load harmonic current. Only G can be predesign by the A.F. whileZs and ZL are determined by the system.

Equation (59) shows that the compensation characteristics of the A.F. are not influenced by the source impedance, Zs. This is a major advantage of the A.F. with respect to the passive ones.

Page 86: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0286

• The DC bus nominal voltage, , must be greater than or equal to line voltage peak in order to actively control

• The selection of the interface inductance of the active filter is based on the compromise of keeping the output current ripple of the inverter low and the same time to be able to track the desired source current.

• The required capacitor value is dictated by the maximum acceptable voltage ripple. A good initial guess of C is:

Cmax

t

0 C

dtimaxC

dt

dimax

VV32

LLφ

nφdCF

dCV.iC

nφV

= peak line-neutral voltage

dCV = DC voltage of the DC bus of the inverter

Lφi = Line phase current

CmaxvΔ = maximum acceptable voltage ripple,

Ci = Phase current of the inverter

dCV

C

Also

Page 87: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0287

For identifying the harmonic currents in general the method of computing instantaneous active and reactive power is used.Transformation of the three-phase voltages and and the three-phase load currents and into α-β orthogonal coordinate.

w

v

u

β

α

v

v

v

2/3

2/1

2/3

2/1

0

1

3

2v

v

Lw

Lv

Lu

βL

αL

i

i

i

2/3

2/1

2/3

2/1

0

1

3

2i

i

, vu vv wv, iLv Lui Lwi

P-Q THEORY

Page 88: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0288

Then according to theory, the instantaneous real power and the instantaneous imaginary (reactive) power are calculated.

βL

αL

αβ

βα

L

L

i

i

vv

vv

q

p

where

LLLL p~ppp

LLLL q~qqq

DC + low frequency comp. + high freq. comp.

DC + low frequency comp. + high freq. comp.

Lp

Lqq-p

Page 89: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0289

The conventional active power is corresponding to , the conventional reactive power to and the negative sequence to the 2 f components of and .

The commands of the three-phase compensating currents injected by the shunt active conditioner, , and are given by:

q

pvv-

vv

2/3

2/3

0

2/1

2/1

1

3

2

i

i

i 1

αβ

βα

Cw

Cv

Cu

Lp~

Lq~ Lp Lq

Cui

Cvi Cwi

p

q

= Instantaneous real power command

= Instantaneous reactive power command

Page 90: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0290

L

L

q~q

p~p

LL

L

q~qq

p~p

LL

LL

q~qq

p~pp

Current Harmonics compensation is achieved

Current Harmonics and low frequency variationComponents of reactive power compensation

Current Harmonics and low frequency variationComponents of active and reactive power compensation

Substituting

Page 91: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0291

HARMONIC DETECTION METHODS

i) Load current detection iAF= iLh It is suitable for shunt active filters which are installed near

one or more non-linear loads.

ii) Supply current detection iAF= KS iSh Is the most basic harmonic detection method for series

active filters acting as a voltage source vAF.

iii) Voltage detection It is suitable for shunt active filters which are used as

Unified Power Quality Conditioners. This type of Active Filter is installed in primary power distribution systems. The Unified Power Quality Conditioner consists of a series and a shunt active filter.

Page 92: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0292

SHUNT ACTIVE FILTER CONTROL

a) Shunt active filter control based on voltage detection

Page 93: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0293

Using this technique the three-phase voltages, which are detected at the point of installation, are transformed to and on the dq coordinates. Then two first order high-pass filters of 5HZ in order to extract the ac components and from and . Next the ac components are applied to the inverse dq transformation circuit, so that the control circuit to provide the three-phase harmonic voltages at the point of installation. Finally, amplifying each harmonic

voltage by a gain Kv produces each phase current reference.

dv~ qv~

dv qv

dv qv

hVAF vKi

The active filter behaves like a resistor 1/KV ohms to the external circuit for harmonic frequencies without altering the fundamental components.The current control circuit compares the reference current with the actual current of the active filter and amplifies the error by a gain KI . Each phase

voltage detected at the point of installation, v is added to each magnified error signal, thus constituting a feed forward compensation in order to improve current controllability. As a result, the current controller yields three-phase voltage references. Then, each reference voltage is compared with a high frequency triangular waveform to generate the gate signals for the power semiconductor devices.

AFi

AFi

iv

Page 94: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0294

b) Reference current calculation scheme using source currents (is), load currents (iL) and voltages at the point of installation (vS).

Page 95: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0295

3-φ HYBRID ACTIVE-PASSIVE FILTER

Compensation of current harmonics and displacement power factor can be achieved simultaneously.

Page 96: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0296

In the current harmonic compensation mode, the active filter improves the filtering characteristic of the passive filter by imposing a voltage harmonic waveform at its terminals with an amplitude

ShCh KIV

Page 97: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0297

• THDi decreases if K increases.• The larger the voltage harmonics generated by the active filter a better filter

compensation is obtained.• A high value of the quality factor defines a large band width of the passive

filter, improving the compensation characteristics of the hybrid topology.• A low value of the quality factor and/or a large value in the tuned factor

increases the required voltage generated by the active filter necessary to keep the same compensation effectiveness, which increases the active filter rated power.

SF

F

Lh

ShZZK

Z

I

I

1S

2h SF

FLh

i I

ZZKZ

I

THD

If the AC mains voltage is pure sinusoidal, then

Page 98: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0298

Displacement power factor correction is achieved by controlling the voltage drop across the passive filter capacitor.

TC VβV

Displacement power factor control can be achieved since at fundamental frequency the passive filter equivalent impedance is capacitive.

Page 99: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-0299

HYBRID ACTIVE-PASSIVE FILTER

Single-phase equivalent circuit Single-phase equivalent circuit for 5th Harmonic

Page 100: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02100

This active filter detects the 5th harmonic current component that flows into the passive filter and amplifies it by a gain K in order to determine its voltage reference which is given by

5FAF iKv

As a result, the active filter acts as a pure resistor of K ohms for the 5th harmonic voltage and current. The impedance of the hybrid filter at the 5th harmonic frequency, Z5 is given by

KrCω5j

1Lω5jZ f

FF5

0K The active filter presents a negative resistance to the externalCircuit, thus improving the Q of the filter.

FrK , 0V 5BUS 5ST

5S VLω5j

1I

Page 101: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02101

CONTROL CIRCUIT

The control circuit consists of two parts; a circuit for extracting the 5th current harmonic component from the passive filter iF and a circuit that adjusts automatically the gain K. The reference voltage for the active filter

5FAF iKv

HARMONIC-EXTRACTING CIRCUIT

The extracting circuit detects the three-phase currents that flow into the passive filter using the AC current transformers and then the α-β coordinates are transformed to those on the d-g coordinates by using a unit vector (cos5ωt, sin5ωt) with a rotating frequency of five times as high as the line frequency.

Page 102: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02102

SERIES ACTIVE FILTERS

By inserting a series Active Filter between the AC source and the load where the harmonic source is existing we can force the source current to become sinusoidal. The technique is based on a principle of harmonic isolation by controlling the output voltage of the series active filter.

Equivalent Circuit

Page 103: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02103

- The series active filter exhibits high impedance to harmonic current and consequently blocks harmonic current flow from the load to the source.

SC KGIA.F. theof tageOutput vol V

KGZZ

V

KGZZ

IZI

LS

S

LS

LLS

(61)

(62)

= Equivalent transfer function of the detection circuit of harmonic current, including delay time of the control circuit.

G

, 0G1 1G h (63)

Page 104: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02104

K = A gain in pu ohms

The voltage distortion of the input AC source is much smaller than the current distortion.

ShV

If hLZK and hLS ZZK

Then

ShLhLC VIZV

0IS

(64)

(65)

(66)

Page 105: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02105

HYBRID SERIES AND SHUNT ACTIVE FILTER

At the Point of Common Coupling provides:

• Harmonic current isolation between the sub transmission and the distribution system (shunt A.F)

• Voltage regulation (series A.F)• Voltage flicker/imbalance compensation (series A.F)

Page 106: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02106

SELECTION OF AF’ S FOR SPECIFIC APPLICATION CONSIDERATIONSAF Configuration with higher number of * is more preferred

Compensation for Specific Application

Active Filters

Active Series

Active Shunt

Hybrid of Active Series and Passive

Shunt

Hybrid of Active Shunt and Active

Series

Current Harmonics ** *** *

Reactive Power *** ** *

Load Balancing *

Neutral Current ** *

Voltage Harmonics *** ** *

Voltage Regulation *** * ** *

Voltage Balancing *** ** *

Voltage Flicker ** *** *

Voltage Sag&Dips *** * ** *

Page 107: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02107

CONCLUSIONS

Solid State Power Control results in harmonic pollution above the tolerable limits. Harmonic Pollution increases industrial plant downtimes and power losses. Harmonic measurements should be made in industrial power systems in order (a) aid

in the design of capacitor or filter banks, (b) verify the design and installation of capacitor or filter banks, (c) verify compliance with utility harmonic distortion requirements, and (d) investigate suspected harmonic problems.

Computer software programs such as PSPICE and SIMULINK can be used in order to obtain the harmonic behavior of an industrial power plant.

The series LC passive filter with resonance frequency at 4.7 is the most popular filter. The disadvantages of the the tuned LC filter is its dynamic response because it

cannot predict the load requirements. The most popular Active Filter is the parallel or shunt type. Active Filter technology is slowly used in industrial plants with passive filters as a

hybrid filter. These filters can be used locally at the inputs of different nonlinear loads.

Active Filter Technology is well developed and many manufactures are fabricating Active filters with large capacities.

A large number of Active Filters configurations are available to compensate harmonic current, reactive power, neutral current, unbalance current, and harmonics.

The active filters can predict the load requirements and consequently they exhibit very good dynamic response.

LC tuned filters can be used at PCC and the same time active filters can be used locally at the input of nonlinear loads.

Page 108: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02108

REFERENCES

RECOMMENDED PRACTICES ON HARMONIC TREATMENT[1] IEEE Std. 519-1992, ΄΄IEEE Recommended Practices and

Requirements for Harmonic Control in Electric Power Systems΄΄, 1993.

[2] IEC Sub-Committee 77B report, ΄΄Compatibility Levels in Industrial Plants for Low Frequency Conducted Disturbances΄΄, 1990.

[3] IEC Sub-Committee 77A report, ΄΄Disturbances Caused by Equipment Connected to the Public Low-Voltage Supply System Part 2 : Harmonics ΄΄, 1990 (Revised Draft of IEC 555-2).

[4] UK Engineering Recommendation G.5/3: ΄΄Limits for Harmonics in the UK Electricity Supply System΄΄, 1976.

[5] CIRGE WG 36.05 Report, ΄΄Equipment producing harmonics and Conditions Governing their Connection to the Mains power Supply΄΄, Electra, No. 123, March 1989, pp. 20-37.

[6] Australian Standards AS-2279.1-1991, ΄΄Disturbances in mains Supply Networks-Part 2: Limitation of Harmonics Caused by Industrial Equipment΄΄, 1991.

Page 109: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02109

DEFINITIONS

[7] J. Arriilaga, D.A. Bradley, and P.S. Bodger, ΄΄Power System Harmonics΄΄,New York: Wiley, 1985.

[8] N. Shepherd and P. Zand, ΄΄Energy flow and power factor in nonsinusoidal circuits΄΄, Cambridge University Press, 1979.

EFFECTS OF HARMONICS

[9] J.M. Bowyer, ΄΄Three-Part Harmony: System Interactions Leading to a Divergent Resonant System΄΄, IEEE Trans. on Industry Applications, Vol. 31, No. 6, Nov/Dec 1995, pp. 1341-1349.

[10] R.D. Hondenson and P.J. Rose, ΄΄Harmonics: the Effects on power Quality and Transformers΄΄, IEEE Trans. on Industry Applications, Vol. 30, No.3, May/June 1994, pp. 528-532.

[11] J.S. Subjak and J. S. McQuilkin, ΄΄Harmonics-Causes, effects, Measurements and Analysis: An Update΄΄, IEEE Trans. on Industry Applications, Vol. 26, No. 6, Nov/Dec 1990, pp. 103-1042.

[12] P.Y. Keskar, ΄΄Specification of Variable Frequency Drive Systems to Meet the New IEEE 51 Standard΄΄, IEEE Trans. on Industry Applications, Vol.32, No.2, March/April 1996, pp. 393-402.

Page 110: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02110

[13] T.S. Key, ΄΄Cost and Benefits of Harmonic Current Reduction for Switch-Mode Power Supplies in a Commercial Building΄΄, IEEE Trans. on Industry Applications, Vol. 32, No. 5, September/October 1996, pp. 1017-1025.

PASSIVE HARMONIC TREATMENT TECHNIQUES

[14] M.F. McGranaghan and D.R. Mueller, ΄΄Designing Harmonic Filters for Adjustable-Speed Drives to comply with IEEE-519 Harmonic limits΄΄, IEEE Trans. on Industry Applications, Vol. 35, No 2, March/April 1999, pp. 312-18.

[15] F.Z. Peng, ΄΄Harmonic Sources and filtering Approaches΄΄, IEEE Industry Applications Magazine, July/August 2001, pp. 18-25.

[16] J.K. Phipps, ΄΄A transfer Function Approach to Harmonic Filter Design΄΄, IEEE Industry Applications Magazine March/April 1997.

[17] S.M. Peeran, ΄΄Application, Design, and Specification of Harmonic Filters for Variable frequency Drives΄΄, IEEE Trans. on Industry Applications, Vol. 31, No. 4, July/August 1995, pp. 841-847.

Page 111: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02111

[18] J. Lai and T.S. Key, ΄΄Effectiveness of Harmonic Mitigation Equipment for Commercial Office Buildings΄΄, IEEE Trans. on Industry Applications, Vol. 33, No. 4, July/August 1997, pp. 1104-1110.

[19] D.E. Rice,΄΄A Detailed Analysis of Six-Pulse Converter harmonic Currents΄΄, IEEE Trans. on Industry Applications, Vol. 30, No. 2, March/April 1994, pp. 294-304.

[20] R.L. Almonte and Ashley, ΄΄Harmonics at the Utility Industrial Interface: A Real World Example΄΄, IEEE Trans. on Industry Applications, Vol. 31, No. 6, November/December 1995, pp. 1419-1426.

[21] K. A. Puskarich, W.E. Reid and P. S. Hamer, ΄΄Harmonic Experiments with a large load-Commutated inverter drive΄΄, IEEE Trans. on Industry Applications, Vol. 37, No. 1, Jan/Feb. 2001, pp. 129-136.

[22] L.S. Czarnecki and O. T. Tan, ΄΄Evaluation and Reduction of Harmonic Distortion Caused by Solid State Voltage Controller of Induction Motors΄΄, IEEE Trans. on Energy Conversion, Vol. 9, No. 3, Sept. 1994, pp. 528-421.

Page 112: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02112

[23] R.G. Ellis, ΄΄Harmonic Analysis of Industrial power Systems΄΄, IEEE Trans. on Industry Applications, Vol. 32, No. 2, March/April 1996, pp. 417-421.

[24] D. Adrews et al, ΄΄ Harmonic Measurements, Analysis and Power factor Correction in a Modern Steel Manufacturing Facility΄΄, IEEE Trans. on Industry Applications, Vol. 32, No. 3, May/June 196, pp. 617-624.

[25] D. Shipp and W. S. Vilcheck, ΄΄Power Quality and Line Considerations for Variable Speed AC Drivers΄΄, IEEE Trans. on Industry Applications, Vol.32, No.2, March/April 1996, pp. 403-410.

[26] J. A Bonner et al, ΄΄Selecting ratings for Capacitors and Reactors In Applications Involving Multiple Single-Tuned Filters΄΄, IEEE Trans. on Power Delivery, Vol. 10, No. 1, Jan. 1995, pp. 547-555.

[27] E. J. Currence, J.E Plizga, and H. N. Nelson, ΄΄Harmonic Resonance at a medium-sized Industrial Plant΄΄, IEEE Trans. on Industry Applications, Vol. 31, No. 4, July/August 1995, pp. 682-690.

Page 113: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02113

[28] G. Lemieux, ΄΄Power system harmonic resonance. A document case΄΄, IEEE Trans. on Industry Applications, Vol. 26, No. 3, pp. 483-487, May/June 1990.

[29] D. D. Shipp, ΄΄Harmonic Analysis and Suppression for electrical systems΄΄, ΙEEE Trans. on Industry Applications Vol. 15, No. 5, Sept./Oct. 1979.

ACTIVE HARMONIC TREATMENT TECHNIQUES[30] H. Akagi, ΄΄New trends in active filters for Power conditioning΄΄,

IEEE Trans. on Industry Applications, Vol. 32, Nov/Dec. 1996, pp. 1312-1322.

[31] Bhim Singh et al, ΄΄A Review of Active Filters for Power Quality Improvement΄΄, IEEE Trans. on Industrial Electronics, Vol. 46, No. 5, Oct. 1999, pp. 960-971.

[32] F. Z. Peng, ΄΄Application Issues of Active Power Filters΄΄, IEEE Industry Applications Magazine, Sep./Oct. 1998, pp. 22-30.

[33] S. Bhattacharga et al, ΄΄Active Filter Systems Implementation΄΄, IEEE Industry Applications Magazine, Sep./Oct. 1998, pp. 47-63.

Page 114: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02114

[34] S. Bhattacharya et al, ΄΄Hybrid Solutions for improving Passive Filter Performance in high power Applications΄΄, IEEE, Trans. on Industry Applications, Vol. 33, No. 3, May/June 1997, pp. 732-747.

[35] H. Akagi, ΄΄Control Strategy and site selection of a shunt active filter for damping of harmonies propagation in power distribution systems ΄΄, IEEE Trans. on Power Delivery, Vol. 12, Jan. 1997, pp.354-363.

[36] H. Fujita, T. Yamasaki, and H. Akagi, ΄΄A Hybrid Active Filter for Damping of Harmonic Resonance in Industrial Power Systems΄΄, IEEE Trans. on Power Electronics, Vol. 15, No. 2, March 2000, pp. 215-222.

[37] H. Akagi et al, ΄΄ Α shunt Active Filter Based on Voltage Detection for Harmonic Termination of a Radial power Distribution Line΄΄, IEEE Trans. on Industry Applications, Vol. 35, No. 3, May/June 1999, pp. 638-645.

[38] D. Rivas et al, ΄΄ A simple control scheme for hybrid Active Power Filter΄΄, IEE PESC-00, pp. 991-996.

Page 115: IEEE PESC-02JUNE 2002 1 HARMONIC TREATMENT IN INDUSTRIAL POWER SYSTEMS Presented by Stefanos Manias.

JUNE 2002IEEE PESC-02115

[39] L. Zhou and Zi Li, ΄΄A Novel Active Power filter Based on the Least compensation Current Control Method΄΄, IEEE Trans. on Power Electronics, Vol. 15, No. 4, July 2000, pp. 655-659.

MODELING[40] IEEE Task Force on Modeling and Simulation, ΄΄Modeling and

Simulation of the propagation of harmonies in electric power networks, Part I: Concepts, models, and simulation techniques΄΄, IEEE Trans. on Power Delivery, Vol. 11, No. 1, Jan. 1996, pp. 452-465.

[41] IEEE Task Force on Modeling and Simulation ΄΄Modeling and Simulation of the propagation of harmonies in electric power networks, Part II: Sample systems and examples΄΄, IEEE Trans. on Power Delivery, Vol. 11, No. 1, Jan. 1996, pp. 466-474.

[42] W. Jewel et al, ΄΄Filtering Dispersed harmonic Sources on Distribution΄΄, IEEE Trans. on Power Delivery, Vol. 15, No. 3, July 2000, pp. 1045-1051.

[43] N.K. Madora and A. Kusko, ΄΄Computer-Aided Design and Analysis of Power-Harmonic Filters΄΄ IEEE Trans. on Industry Applications, Vol. 36, No. 2, March/April 2000, pp.604-613.


Recommended