International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 40
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Indirect Evaporative Cooling Availability and
Thermal Effectiveness Characteristics in Air-Water
Systems of Hot and Dry Climates
Waleed A. Abdel-Fadeel Assistant professor, Faculty of Energy Engineering, Aswan University, Egypt
Tel: +20 1142951507, Fax: +20 97 3481234,
E-mail address: [email protected], P. O.: 81528 Aswan, Egypt.
Abstract-- The success of evaporative cooling technology as a
significant means of a cooling in modern application is the ability to generate cooling water, in an indirect circuit, at a temperature
which closely approaches the ambient adiabatic saturation
(AST). Evaporative cooling, can be used to provide effective
cooling in building by means of contemporary water based
sensible cooling system, such as fan coil systems and ceiling cooling convertors (chilled beams). In this research a diurnal
variation for May, June, and July was measured .A comparison
between measured and calculated cooling water temperatures
result from evaporative cooling was done. Also a comparison
between previous work and present study carried out which gave the same trend. Finally this research quantifies evaporative
cooling availability and thermal effectiveness in depth for
southern Egypt (Aswan city) which has hot and dry climates that
suitable for evaporative cooling. The results of this research confirm a major potential for the generation of cooling water by
evaporative means. Where Cooling water could be generated at
range of (20 – 22) oC during months May, June, and July, and at
range of (15 – 18) oC in March and April months for 87%
availability during these months.
Index Term-- Evaporative cooling ; Cooling tower ; Indirect
evaporative; Hot and dry climate; Availability; Thermal
effectiveness.
NOMENCLATURE
IEC Indirect evaporative cooling
DEC Direct evaporative cooling
Tas Ambient adiabatic saturation temperature (AST) o
C
Tpa primary approach temperature (PAT) oC
Tpr primary loop return temperature oC
Tps primary loop supply temperature oC
Tsa secondary approach temperature (SAT) oC
Tsr secondary loop return temperature oC
Tss secondary loop supply temperature oC
WBT Wet bulb temperature
GREEK LETTERS
ηtp primary thermal effectiveness
ηts secondary thermal effectiveness
SUBSCRIPTS
as adiabatic saturation
pa primary approach
pr primary return
ps primary supply
pa secondary approach
pr secondary return
ss secondary supply
tp thermal primary
ts thermal secondary
1. INTRODUCTION
Today’s high cost of energy together with its
environmental impact are reasons enough to warrant a
reduction in energy consumption in current air conditioning
systems, or those at the design stage. Any study of an air
conditioning system in a building should focus mainly on
thermal comfort, energy saving and environmental protection.
The use of indirect evaporative cooling has a high potential for
meeting air conditioning needs at low energy cost.
Buildings, which have significant latent loads and
which require high rates of air supply for ventilation purposes
are often treated with all air-air conditioning systems, in which
all conditioning equipment is confined to a central location
and from which the treated air supply to the building is
distributed. This system require chilled water at low
temperatures typically 5-8 0C, to produce dehumidification on
the coils. These systems generally rely on vapor compression
refrigeration to generate the required chilled water
temperatures.
Not all buildings, however, need high rates of air
supply for ventilation purposes or have significant latent loads
or require close control of humidity. Such buildings are often
successfully treated with air-water systems in which a smaller
central air system (the primary air) is used to supply
ventilation air and offset latent gains. A cooling water
distribution system is also used (the secondary water) to
supply local sensible cooling equipment in each zone.
The temperatures required for the secondary cooling
water circuit also depend on the system employed. For
example, dry mode fan coil units require a supply at 10-14 oC,
while chilled ceilings require water at 14-18 oC. The sensible
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 41
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
cooling output of these systems is reduced as the cooling
water temperature rises; however this reduction can be
compensated for, if required, by increasing the area of the heat
transfer surface.
A crucial feature of the feas ibility of the evaporative
cooling in temperate climates is the achievement of a low
temperature difference between the water exiting from the
cooling tower and the ambient WBT (the primary approach
temperature, PAT). This is necessary, in order to ensure a
significant level of cooling water availability, especially in
summer. To separate the tower water circuit from the building
cooling circuit by means of a heat exchanger. Hence, the
crucial design parameter becomes the temperature difference
between the water exiting from the heat exchanger and the
ambient WBT (the secondary approach temperature , SAT ).
B. Costelloe and D. Finn [1, 2, 3] confirm a major
potential for the generation of cooling water by evaporative
means, which can be used to provide effective cooling of deep
plan buildings by means of contemporary water based sensible
cooling systems, such as fan coil, radiant chilled ceiling panels
and chilled beams. Also the thermal effectiveness of water
side, of open indirect evaporative cooling has been presented.
Finally the experimental performance of an open industrial
scale cooling tower, utilizing small approach temperature
difference has examined. The performance and energy
reduction capability of combined system has been evaluated
by Shahram Delfani et al [4] through the cooling season. The
results indicate IEC can reduce cooling load up to 75 %
during cooling season. Ala Hasan [5] presents a method to
produce air at sub-wet bulb temperature by indirect
evaporative cooling without using a vapor compression
machine. Cooling performance of two stage indirect/direct
evaporative cooling system is experimentally investigated by
Ghassem Heidarinejad et al [6] in the various simulated
climatic condition. An experimental system of two stage
evaporative cooling was constructed and tested in Kuwait
environment by Hisham El-Dessouky et al [7]. The system is
formed of an IEC unit followed by DEC unit. Results show
that the efficiency of IEC/DEC varies over a range of 90 -
120%.
An analytical evaluation us ing the field performance
results of 1180 L/s IEC unit and the recorded weather data in
coastal and interior location in Kuwait was presented by G.P.
Maheshwari et al [8]. Several types of materials, namely
metals, fibers, ceramics, zeolite, and carbon was investigated
by X. Zhao et al [9], which have potential to be used as heat
and mass transfer medium in the indirect evaporative system,
and the results show that thermal properties of the materials
have little impact on system heat/mass transfer. A new heat
and mass transfer model based on basic principles has been
developed by J.Fsan et al [10] for thermal calculation of an
indirect evaporative cooler. A simplified model for indirect
cooling towers behavior is presented by Pascal Stabat and
Dominique Marchio [11] the model is devoted to building
simulation tools and fulfills several criteria such as simplicity
of parameterization, accuracy, and possibility to model the
equipment under different operation condition. An analysis
was carried out by Francisco Javier et al [12] for the influence
of factors such as temperature, flow, relative humidity, water
flow rate, etc. on the basic characteristics defined by the
mixed system, heat flow, heat efficiency and COP.
Chilled ceiling panels can operate with a s upply
water temperature as high as 18-20 oC [13]. These elevated
secondary cooling water temperatures raise the possibility of
generating the required cooling in cooling towers. Hence, the
view has developed that tower based evaporative cooling
ought now to be the subject of major review as a practical and
low energy means of cooling modern buildings.
At present, cooling systems generally use
conventional vapor compression refrigeration to generate all
cooling water at temperature suitable for primary air
dehumidification and subsequently raise the water temperature
to the required secondary temperature by means of a mixing
arrangement or a heat exchanger. While water side
evaporative cooling arrangements are occasionally used with
air water systems, particularly in more arid climates, the use of
the technique falls far short of its potential. This is particularly
the case in west Egypt Aswan city of hot and dry climates
where high difference between dry and wet bulb temperature
compared to Egyptian cities as in table I that make it suitable
for evaporative cooling, many opportunities to benefit from
evaporative cooling technique are often overlooked. Also from
previous work carried out on evaporative cooling availability
and effectiveness no author touched this point especially for
hot and dry climate . So our present research was directed to
study indirect evaporative cooling availability and thermal
effectiveness characteristics for hot and dry climates.
2. EXPERIMENTAL TEST RIG
At present, however, there is little in depth research
and analysis of the performance, energy efficiency and year
round availability of this alternative form of cooling,
especially in dry and hot climates at very low approach. To
address these issues, an experimental research program has
been established. So laboratory scale of indirect evaporative
cooling was designed and erected at refrigeration and air
condition laboratory at Aswan faculty of energy engineering
Aswan University. The test rig as in Fig. 1 is consists of an
open counter-flow cooling tower, optimized for close
approach conditions and incorporating a shell and tube heat
exchanger which designed also for close approach conditions
with two shell and two tube pass . The heat exchanger length
of 1 m and a diameter of 0.16 m.. The tower is upset
truncated pyramid in shape as in Figure 1 . Its lower base
dimensions are 82 cm wide and 62 cm deep and its upper base
dimension are 100 cm wide and 80 cm deep and the tower
height is 2 m. The tower has a forced draft fan of a power
0.37 kw and a revolution per minute of 1425. The cooling load
is provided by two electric immersion heaters each of which
1200 w connected parallel to give a load of 1200 W and 2400
W that put in a vertical cylindrical container of 0.5 m length
and 0.32 m diameter. A key issue in this research is the
detailed evaluation of the extent of cooling availability which
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 42
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
can be expected, a range of cooling water supply
temperatures, and thermal effectiveness. The test rig was
instrumented to measure both the water supply and return
temperatures of primary and secondary loops using
thermometer.
3. OPERATING PROCEDURE
1-check the cooling tower water and make sure that it
sufficient for whole operation
2-turn on the cooling tower pump and fans
3-check the boiler water level and adjust the electric heater at
required load Loads (1200w-2400w)
4-turn on the secondary pump and electric heater
5-check air valve of the secondary pump to release vapor from
boiling water to protect pump from failure
6-recording the results from measuring devices and plot
results curves
4. EXPERIMENTAL RESULTS
In this part, the obtained experimental results will be
comprehensively discussed. The results include diurnal
variation, availability of cooling water, and thermal
effectiveness of primary and secondary loops of water side.
4-1 diurnal variations
In this section the results of climate graph through all
year and diurnal variation in conditions during May, June ,
and July will be discuss.
Table II confirms that a PAT of no greater than 2.8 K
is feasible for no load. Also a PAT of no greater than 3.6 K is
feasible for 1200 W load. This research confirms that open
cooling towers in cooperating modern high surface density
packing designs and operating under very close approach
considerations. Also it could be noted from table II that PAT
depends on the ambient AST or WBT. From features of the
test results shown in table II that using PAT of 2K will be
approximated value for most runs .
Figures 2-4 show the diurnal variation in conditions
during May, June, and July month 2010. The figures 2-4 could
be considered to represent a typical design day in Aswan
(Egypt) with a maximum ambient dry bulb temperature
reaching 39 oC and minimum WBT reaching 17.5
oC.
Nevertheless, it was possible under these conditions, to
produce cooling water temperatures of 20 -22 oC, which
could provide or contribute towards building cooling
depending on the thermal conditions considered acceptable. In
figure 2 a primary cooling water temperature of 21oC were
produced in June, while in figure 3 a primary cooling water
temperatures of 20 oC were produced in July a condition
which would suit a dry mode fan coil application. While in
Fig. 4 cooling water temperature of 22 oC were produced in
May.
4-2 Availability analysis
4-2-1 Determination adiabatic saturation temperature
In order to quantify the evaporative cooling
availability which can be expected for any given location it is ,
therefore, necessary to establish the typical yearly record
pattern of the ambient AST. This can be achieved by using,
either a meteorological test reference weather year or
alternatively, where such is available. The method has been
used in this research as it is now readily available in [14]. For
wide range of world wide locations.
The available data based on record of hourly weather
data for 12 typical months. The hourly weather records
typically include data on dry bulb temperature, relative
humidity, wind speed and solar radiation. By using the dry
bulb temperature and relative humidity a new data has been
developed which lists a hourly record of standard
psychometric properties included the WBT a long Aswan city.
4-2-2 Evaporative Cooling Potential
Having established the hourly psychometric data for
the site (Aswan Egypt), the data can now be analyzed to
determine the evaporative cooling potential using the
percentage annual availability of cooling water A where it
could be defined as
A= (1)
where Σ(Htas) is the statistically typical total number of
annual hours, during which, the ambient AST is less than or
equal to (Tpf _ Tpa). Tpf is the primary flow temperature (0C),
Tpa the PAT (K), 8760 the number of hours in a year. In the
first instance the occurrence of the ambient WBT is calculated
and then, using a 2K PAT the potential for cooling water
generation is determined.
Figure 5 shows the percentage occurrence of the
cooling water temperature for Aswan based on the hourly
prediction of the ambient condition. The results show that the
WBT of 13 oC required to supply cooling water at 15
oC (as in
Figure 5) is statistically available for 35% of the year in
Aswan. The annual occurrence is calculated on a 24 h day
basis and is defined as the percentage of the total annual hours
(8760 h) during which a temperature at or below a particular
temperature, occurs.
4-3 Calculation of cooling water temperature through year
2010
In this section a daily cooling water temperature
possible for all year month at Aswan will be calculated based
on [14] and using 2 k PAT, monthly possible average cooling
water temperature , and finally a comparison between
calculated and measured cooling water temperature for some
days will be discuss. Figure 6 shows calculated cooling water
temperature versus days from November to April through
2010 year. It could be seen that cooling water temperature
fluctuating with days for all months, also it could be seen that
the lowest values in temperature are (second half of January
and First half of February). Finally the higher values of
cooling water are through November and December.
Figure 7 shows calculated cooling water temperature
versus days from May to October through 2010 year. It could
be seen that cooling water temperature fluctuating with days
for all months, also it could be seen that the lowest values in
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 43
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
temperature are through May month. Finally the higher values
of cooling water are through July and August.
Figures 8 and 9 show comparison between measured
and possible cooling water temperature versus time for July 5
and May 17. It could be seen that there is a good agreement
between measured and calculated cooling water temperature
for May and July. Also the maximum deviations between
measured and calculated cooling water temperature is less
than 20%.
4-4 Thermal effectiveness
A suitable means of assessing the thermal
performance of the process is the thermal effectiveness ( ηt ).
This is defined as the cooling achieved, expressed as a fraction
of the maximum possible cooling which could have been
achieved in the ambient conditions pertaining . For the
secondary circuit this parameter is defined by equation (1 ) as
in [2]; a similar equation defines the primary circuit. As this
parameter involves both the approach and range condition.
The two key determinants of energy performance, it is also a
suitable parameter from this point of view. In particular the
secondary thermal effectiveness (STE) is an important
parameter as it assesses the performance of the indirect system
as a whole, as distinct from the performance of the tower. It is
also an important indicator of availability of cooling water
generation potential.
The STE can be defined with reference to figure 1 in
terms of the following equation:
ηt = Tsr-Tss / Tsr-Tas = Tsr-Tss / [ (Tsr-Tss) + (Tss-Tas)]
(1)
which can be expressed qualitatively as
secondary range / (secondary range) +(secondary approach)
Tests were conducts to investigate the impact of a
range of operating variables on the thermal effectiveness
achieved. These variables are (time, ambient dry bulb
temperature, and wet bulb temperature ). For testing purposes
the parameter being examined was varied while the other test
rig variables were maintained constant. As there is no control
over the ambient dry bulb temperature and ambient wet bulb
temperature so a large number of tests were conducted and
those tests with different values was selected.
Figure 10 shows secondary effectiveness versus time
in Aswan for June 27 2010. It could be seen that the secondary
effectiveness fluctuating with time. Also the average
secondary effectiveness increase with time up to a certain time
after that it decrease. As this could be attributed to change of
dry bulb temperature with time which affect the cooling water
temperature produced and affect secondary effectiveness as
well
Figure 11 shows comparison between primary and
secondary thermal effectiveness versus ambient dry bulb
temperature. It can be seen that the primary thermal
effectiveness has higher values than secondary thermal
effectiveness. Also it could be seen that both primary and
secondary thermal effectiveness increase with dry bulb
temperature. And this could be attributed to increasing dry
bulb temperature increase the range between dry bulb and wet
bulb which affect secondary effectiveness by increasing it .
Figure 12 shows thermal effectiveness versus wet
bulb temperature through May , June, and July 2010 at
Aswan. It could be seen from the figure that thermal
effectiveness at wet bulb temperature of (18-21 oC) increase
with wet bulb temperature. Also it could be seen that primary
effectiveness has a higher values than that the secondary
effectiveness. And this could be explained as primary
effectiveness is occur as a first exchange between air and
water and occur at relative high temperature. At the opposite
side secondary effectiveness occurs at relative low
temperature and as we know that the efficiency is increase
with temperature. So primary effectiveness is higher than
secondary effectiveness as in figure 12.
4-5 Comparisons with previous work
A comparisons of Measured diurnal variation and annual
availability between reference 1 (a) and present study (b) was
shown in Figures 14-15. It could be seen that the result of
reference 1 and present study has the same trend although the
result different in values according to different conditions
which could be attributed to changed meteorologic condit ions
such as ambient temperature, solar radiation, and wind
velocity where reference 1 carried out at temperate climates
condition where present study carried out at hot and dry
climates. Also comparisons of variation in primary and
secondary approach temperatures and thermal effectiveness
versus wet bulb temperature for both reference 2 and present
study was shown in figures 16-17. It could be seen that the
result of reference 2 and present study has the same trend
although the result different in values according to different
conditions which could be attributed to changed meteorologic
conditions such as ambient temperature, solar radiation, and
wind velocity where reference 2 carried out at temperate
climates condition where present study carried out at hot and
dry climates.
CONCLUSIONS The results of a detailed meteorological analysis of
evaporative cooling availability for south Egypt Aswan city
have been presented and discussed. The results confirm a
major potential for the generation of cooling water, which can
be used to provide effective cooling of modern building by
means of contemporary water based sensible cooling system,
such as fan coils and chilled ceiling panels and beams. While
the technique offers most potential in location as Aswan
where the difference between dry bulb and wet bulb
temperature is the highest over all Egypt. Also this paper
outlines how the thermal effectiveness can be used as a
measure of the degree to which the evaporative cooling
system has succeeded in exploiting the cooling potential of the
ambient air.
The following specific conclusions can be drawn:-
1-Cooling water could be generated at range of (20 – 22) oC
during months May, June, and July, which implies that
buildings, such as educational institutes which are occupied
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 44
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
during these months may be successfully sensibly cooled
through the year.
2- Cooling water could be generated in March and April
month at range of (15 – 18) oC for chilled ceiling panel and
beams for 87% availability during these months.
3-The test results indicate that thermal effectiveness is not
affected by change in load.
4-The results of the tests indicate that both primary and
secondary thermal effectiveness are significantly affected by
both dry and wet bulb temperature.
5- Comparison between previous work and present study
carried out which gave the same trend.
REFERENCES [1] B. Costelloe and D. Finn “Indirect evaporative cooling potential in
air water system in temperate climates” Energy and building, 35 (2003) 573-591
[2] B. Costelloe and D. Finn “Thermal effectiveness characteristics of
low approach indirect evaporative cooling systems in buildings” Energy and building, 39 (2007) 1235-1243
[3] B. Costelloe and D.P. Finn “ Heat transfer correlations for low
approach evaporative cooling systems in buildings” Applied Thermal Engineering 29 2009 105-115
[4] Shahram Delfani, Jafar Esmaeelian, Hadi.P,and Maryam Karami “ Energy saving potential of an indirect evaporative cooler as a pre-
cooling unit for mechanical cooling systems in iran” Energy and buildings 42 2010 2169-2176
[5] Ala Hasan “ Indirect evaporative cooling of air to a sub-wet bulb temperature” Applied Thermal Engineering 30 2010 2460-2468
[6] Ghassem Heidarinejad, Mojtaba Bozorgmehr, Shahram Delfani, and Jafar Esmaeelian “ Experimental investigation of two stage
indirect/direct evaporative cooling system in various climatic conditions” Building and Environment 44 2010 2073-2079
[7] Hisham El-Dessouky, Hisham Ettouney, and Ajeel Al-Zeefari “Performance analysis of two stage evaporative coolers”
Chemical Engineering Journal 102 2004 255-266 [8] G.P. Maheshwari, F.Al-Ragom, and R.K. Suri” Energy saving
potential of an indirect evaporative cooler” Applied Energy 69 2001 69-76
[9] X. Zhao, Shuli Liu, and S.B. Riffat “ Comparative study of heat and mass exchanging materials for indirect evaporative cooling systems” Building and Environment 43 2008 1902 - 1911
[10] J.FSan Jose Alonso, F.J.Rey Martinez, E.Velasco Gomez,
M.A.Alvarez-Gurra Plasencia” Simulation model of an indirect evaporative cooler” Energy and buildings 29 1998 23-27
[11] Pascal Stabat and Dominique Marchio” Simplified model for
indirect contact evaporative cooling tower behaviour” Applied Energy 78 2004 433-451
[12] Francisco Javier, Mario Antonio, Eloy Velasco, Fernando Varela, and Ruth Herrero” Design and experimental study of a mixed
energy recovery system, heat pipes and indirect evaporative equipment for air conditioning” Energy and Buildings 35 2003 1021-1030
[13] J. Fa Cao, A.C. Oliveira, Thermal behavior of closed wet cooling
towers for use with chilled ceilings, Applied Thermal Engineering 20 2000 1225-1236
[14] http://www.wunderground.com\global\EG.html
T ABLE I
AVERAGE EXTERNAL CONDITIONS FOR SOME EGYPTIAN CITIES THROUGH MAY TO JULY 2010
DBT-WBT WBT°C RH% DBT°C CITY
5 21 65 26 ALEXANDRIA
9 20.5 64 29.5 CAIRO
4 21.5 27 25.5 PORT SAID
14.5 72 77 31.5 ASUIT
14.5 19 24 33.5 LOXUR
16.6 18 18 34.6 ASWAN
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 45
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
T ABLE II
SUMMARY OF SOME EXPERIMENTAL TEST RESULTS FROM COOLING
TOWER TEST RIG.(ASWAN) THROUGH MAY TO JULY 2010
Nominal
load
AST oC
Primary
flow
temperature
Secondary
flow
temperature
PAT SAT
No load 18.5 21.3 - 2.8 -
No load 19 20.7 - 1.7 -
No load 20 21.4 - 1.4 -
1200 21 24.6 30.3 3.6 9.3
1200 22.5 23.4 29.5 0.9 7
1200 24.9 25.4 32.9 0.5 7.5
2400 19.5 25.1 37.4 5.6 17.9
T ABLE III ANNUAL AVAILABILITY OF COOLING WATER TEMPERATURE IN ASWAN AT
2 K PAT
Mont
h
Cooling water temperature, oC
4 6 8 1
0
1
2
14 16 18 20 22 24
Jan. 0 3 7
4
5
5
8
7
71
1
71
1
71
1
71
1
71
1
71
1
Feb. 0 2 7
6
3
4
4
8
87 88 84 10
0
10
0
10
0
Mar. 0 1 3 7
1
5
8
27 86 86 10
0
10
0
10
0
Apr. 0 1 1 3 3
1
41 81 71
1
71
1
71
1
71
1
May 0 1 1 1 4 38 82 71
1
71
1
71
1
71
1
Jun. 0 1 1 1 1 1 71 82 71
1
71
1
71
1
Jul. 0 1 1 1 1 1 4 55 22 86 71
1
Aug. 0 1 1 1 1 1 1 74 82 82 71
1
Sept. 0 1 1 1 1 1 2 22 71
1
71
1
71
1
Oct. 0 1 1 1 1 1 73 81 71
1
71
1
71
1
Nov. 0 7 3 7
1
7
6
35 68 83 84 88 71
1
Des. 0 1 1 6 6 72 74 38 26 28 38
Annu
al
0 7 3 7
1
7
6
35 68 83 84 88 71
1
Open counter cooling tower
Primary circuit Tpr Lood
Tss
Fan Tps Secondary
Circuit
Shell & tube Tsr
Heat exchanger
Air Fig. 1 Simplified schematic of indirect evaporative cooling syst em
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 46
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
0
5
10
15
20
25
30
35
40
6 8 10 12 14 16 18
Tem
pe
ratu
re C
o
Time hr
Tps
Tpr
Tss
Tsr
TDB
TWB
Fig. 2. Measured diurnal variation for June 27 2010 in Aswan at constant
1.2 kw load.
0
5
10
15
20
25
30
35
40
45
6 8 10 12 14 16 18
Tem
pe
ratu
re C
o
Time hr
Tps
Tpr
Tss
Tsr
TDBT
Twbt
Fig. 3. Measured diurnal variation for July 3, 2010 in Aswan at constant
2.4 kw load.
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 47
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
0
5
10
15
20
25
30
10 12 14
Tem
pe
ratu
re C
o
Time hr
Fig. 4. Measured primary supply loop temperature for May 18, 2010 in
Aswan at no load.
Fig. 5. Percentage annual occurrence of cooling water temperature in Aswan
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 48
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Fig. 6. Calculated cooling water temperature for November to April At 2 k PAT in Aswan.
Fig. 7. Calculated cooling water temperature for May to October
At 2 k PAT in Aswan.
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 49
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Fig. 8. Comparison between measured and calculated cooling water temperature using 2K PAT for July 5, 2010.
Fig. 9. Comparison between measured and calculated cooling water temperature using 2K PAT for May 17, 2010.
Fig. 10. Thermal effectiveness versus time for June 27, 2010.
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 50
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Fig. 11. Primary and secondary thermal effectiveness versus ambient
dry bulb temperature through (May, June, and July) 2010.
Fig. 12. Primary and secondary thermal effectiveness versus wet bulb temperature through (May, June, and July) 2010.
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 51
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Fig. 13. Primary and secondary approach temperature versus wet bulb temperature through (May, June, and July) 2010 .
a Measured diurnal variation in conditions for 6 September b Measured diurnal variation for July 3 2010 2000, in Dublin at a constant 20 kW and maximum fan power. in Aswan at 2.4 constant kw load.
Fig. 14. comparison of Measured diurnal variation between reference 1 (a) and present study (b)
a Comparison of annual availability with direct and b Percentage annual occurrence of cooling water temperature in indirect system for Dublin and Milan. Aswan
International Journal of Engineering & Technology IJET-IJENS Vol:13 No:02 52
I J E N S IJENS 3201 AprilIJENS © -IJET-1818-200231
Fig. 15. comparison of annual availability between reference 1 (a) and present study (b)
a Variation in primary and secondary approach temperature with annual. b Primary and secondary approach temperature range of AST in Dublin (load 20 kW, flow rates: tower water flux 2.9 kg/s m2, versus wet bulb temperature through (May, June, tower air flux 4.0 kg/s m2, secondary water 1.6 kg/s). The mean AST of 10.5 8C and July)2010 is shown with associated 3 K SAT
Fig. 16. comparison of variation in primary and secondary approach temperatures between reference 2 (a) and present study (b)
a Variation in thermal effectiveness with typical annual range of AST in b Primary and secondary thermal effectiveness versus wet Dublin (load 20 kW, flow rates: tower water flux 2.9 kg/s m2, tower air bulb temperature through (May, June, and July) 2010 flux 4.0 kg/s m2, secondary water 1.6 kg/s).
Fig. 17. comparison of thermal effectiveness between reference 2 (a) and present study (b)