Installation and operation manualVRV IV compressor unit for indoor installation English
Installation and operationmanual
VRV IV compressor unit for indoor installation
RKXYQ5T7Y1B
3P397286-2BCE - D
ECLA
RATIO
N-OF-C
ONFO
RMITY
CE - D
ECLA
RACIO
N-DE-C
ONFO
RMIDA
DCE
- DEC
LARA
ÇÃO-
DE-CO
NFOR
MIDA
DECE
- ERK
LÆRIN
G OM-
SAMS
VAR
CE - I
ZJAV
A-O-US
KLAĐ
ENOS
TICE
- IZJ
AVA O
SKLA
DNOS
TICE
- ATIT
IKTIES
-DEKL
ARAC
IJACE
- KON
FORM
ITÄTS
ERKL
ÄRUN
GCE
- DICH
IARAZ
IONE-D
I-CON
FORM
ITACE
- ЗАЯ
ВЛЕН
ИЕ-О
-СООТ
ВЕТС
ТВИИ
CE - I
LMOIT
US-YH
DENM
UKAIS
UUDE
STA
CE - M
EGFE
LELŐ
SÉGI-
NYILA
TKOZ
ATCE
- VAS
TAVU
SDEK
LARA
TSIOO
NCE
- ATB
ILSTĪB
AS-DE
KLAR
ĀCIJA
CE - D
ECLA
RATIO
N-DE-C
ONFO
RMITE
CE - Δ
HΛΩΣ
Η ΣΥΜ
ΜΟΡΦ
ΩΣΗΣ
CE - O
VERE
NSST
EMME
LSES
ERKL
ÆRING
CE - P
ROHL
ÁŠEN
Í-O-SH
ODĚ
CE - D
EKLA
RACJ
A-ZGO
DNOŚ
CICE
- ДЕК
ЛАРА
ЦИЯ-З
А-СЪО
ТВЕТ
СТВИ
ЕCE
- VYH
LÁSE
NIE-ZH
ODY
CE - C
ONFO
RMITE
ITSVE
RKLA
RING
CE - F
ÖRSÄ
KRAN
-OM-
ÖVER
ENST
ÄMME
LSE
CE - D
ECLA
RAŢIE
-DE-CO
NFOR
MITA
TECE
- UYG
UNLU
K-BEY
ANI
Dai
kin
Euro
pe N
.V.
01
02
03
04
05
06
07
08
decla
res un
der it
s sole
resp
onsib
ility th
at the
air c
ondit
ioning
mod
els to
which
this d
eclar
ation
relat
es:
erklär
t auf
seine
allein
ige Ve
rantwo
rtung
daß d
ie Mo
delle
der K
limag
eräte
für di
e dies
e Erkl
ärung
bestim
mt ist
:dé
clare
sous
sa se
ule re
spon
sabili
té qu
e les
appa
reils d
'air co
nditio
nné v
isés p
ar la
prése
nte dé
clarat
ion:
verkl
aart h
ierbij
op ei
gen e
xclus
ieve v
erantw
oorde
lijkhe
id da
t de a
ircon
dition
ing un
its wa
arop d
eze v
erklar
ing be
trekki
ng he
eft:
decla
ra ba
ja su
única
resp
onsa
bilida
d que
los m
odelo
s de a
ire ac
ondic
ionad
o a lo
s cua
les ha
ce re
feren
cia la
decla
ración
:dic
hiara
sotto
sua r
espo
nsab
ilità ch
e i co
ndizio
nator
i mod
ello a
cui è
riferi
ta qu
esta
dichia
razion
e:δη
λώνει
με απ
οκλει
στική
της ε
υθύν
η ότι τ
α μον
τέλα τ
ων κλ
ιματισ
τικών
συσκ
ευών σ
τα οπ
οία αν
αφέρε
ται η
παρο
ύσα δ
ήλωσ
η:de
clara
sob s
ua ex
clusiv
a res
pons
abilid
ade q
ue os
mod
elos d
e ar c
ondic
ionad
o a qu
e esta
decla
ração
se re
fere:
09
10
11
12
13
14
15
16
заявл
яет, и
сключ
итель
но по
д сво
ю отв
етстве
ннос
ть, чт
о мод
ели к
онди
цион
еров
возд
уха, к
котор
ым от
носи
тся на
стоящ
ее за
явле
ние:
erklæ
rer un
der e
nean
svar, a
t klim
aanlæ
gmod
ellerne
, som
denn
e dek
larati
on ve
drører
:de
klarer
ar i e
gens
kap a
v huv
udan
svarig
, att l
uftko
nditio
nerin
gsmo
deller
na so
m be
rörs a
v den
na de
klarat
ion in
nebä
r att:
erklæ
rer et
fullst
endig
ansva
r for a
t de l
uftko
ndisjo
nerin
gsmo
deller
som
berør
es av
denn
e dek
laras
jon, in
nebæ
rer at
:ilm
oittaa
yksin
omaa
n oma
lla va
stuulla
an, e
ttä tä
män i
lmoit
ukse
n tark
oittam
at ilm
astoi
ntilait
teide
n malli
t:pro
hlašu
je ve
své p
lné od
pově
dnos
ti, že
mod
ely kli
matiza
ce, k
nimž
se to
to pro
hláše
ní vzt
ahuje
:izja
vljuje
pod i
sključ
ivo vla
stitom
odgo
vorno
šću da
su m
odeli
klima u
ređaja
na ko
je se
ova i
zjava
odno
si:tel
jes fe
lelőssé
ge tu
datáb
an kij
elenti
, hog
y a klí
mabe
rende
zés m
odelle
k, me
lyekre
e ny
ilatko
zat v
onatk
ozik:
17
18
19
20
21
22
23
24
25
dekla
ruje n
a włas
ną i w
yłączn
ą odp
owied
zialno
ść, że
mod
ele kli
matyz
atorów
, któr
ych do
tyczy
niniejs
za de
klarac
ja:de
clară
pe pr
oprie
răsp
unde
re că
apara
tele d
e aer
cond
iţiona
t la ca
re se
refer
ă ace
astă
decla
raţie:
z vso
odgo
vorno
stjo izj
avlja,
da so
mod
eli klim
atskih
napra
v, na
kater
e se i
zjava
nana
ša:
kinnit
ab om
a täie
likul va
stutus
el, et
käes
oleva
dekla
ratsio
oni a
lla ku
uluva
d kliim
asea
dmete
mud
elid:
декла
рира
на св
оя от
говор
ност,
че мо
дели
те кли
матич
на ин
стала
ция,
за кои
то се
отна
ся та
зи де
клара
ция:
visišk
a sav
o atsa
komy
be sk
elbia,
kad o
ro ko
ndicio
navim
o prie
taisų
mod
eliai, k
uriem
s yra
taiko
ma ši
dekla
racija:
ar piln
u atbi
ldību
apliec
ina, k
a tālā
k uzsk
aitīto
mod
eļu ga
isa ko
ndicio
nētāj
i, uz k
uriem
attie
cas š
ī dek
larāc
ija:vyh
lasuje
na vla
stnú z
odpo
vedn
osť, ž
e tiet
o klim
atiza
čné m
odely
, na k
toré s
a vzťa
huje
toto v
yhlás
enie:
tamam
en ke
ndi so
rumlulu
ǧund
a olm
ak üz
ere bu
bildir
inin ilg
ili oldu
ǧu kli
ma m
odelle
rinin
aşaǧ
ıdaki g
ibi old
uǧun
u bey
an ed
er:
RD
XYQ
5T7V
1B*,
RK
XYQ
5T7Y
1B*,
* = ,
, 1,
2, 3,
…, 9
01 02 03 04 05 06 07
are in
confo
rmity
with t
he fo
llowing
stan
dard(
s) or
other
norm
ative
docu
ment(
s), pr
ovide
d tha
t thes
e are
used
in ac
corda
nce w
ith ou
r instr
uctio
ns:
der/d
en fo
lgend
en No
rm(en
) ode
r eine
m an
deren
Norm
doku
ment
oder
-doku
mente
n ents
prich
t/ents
prech
en, u
nter d
er Vo
rausse
tzung
, daß
sie ge
mäß
unse
ren An
weisu
ngen
eing
esetz
t werd
en:
sont
confo
rmes
à la/
aux n
orme(s
) ou a
utre(s
) doc
umen
t(s) n
ormati
f(s), p
our a
utant
qu'ils
soien
t utilis
és co
nform
émen
t à no
s instr
uctio
ns:
confo
rm de
volge
nde n
orm(en
) of é
én of
mee
r and
ere bi
nden
de do
cume
nten z
ijn, op
voorw
aarde
dat z
e word
en ge
bruikt
overe
enko
mstig
onze
instru
cties:
están
en co
nform
idad c
on la
(s) sig
uiente
(s) no
rma(s
) u ot
ro(s)
docu
mento
(s) no
rmati
vo(s)
, siem
pre qu
e sea
n utiliz
ados
de ac
uerdo
con n
uestr
asins
trucci
ones
:so
no co
nform
i al(i)
segu
ente(
i) stan
dard(
s) o a
ltro(i)
docu
mento
(i) a c
aratte
re no
rmati
vo, a
patto
che v
enga
no us
ati in
confo
rmità
alle
nostr
e istr
uzion
i:είν
αι σύ
μφων
α με τ
ο(α) α
κόλο
υθο(α
) πρό
τυπο(α
) ή άλ
λο έγ
γραφ
ο(α) κ
ανον
ισμών
, υπό
την π
ροϋπ
όθεσ
η ότι χ
ρησιμ
οποιο
ύνται
σύμφ
ωνα μ
ε τις ο
δηγίε
ς μας
:
08 09 10 11 12 13 14 15
estão
em co
nform
idade
com
a(s) s
eguin
te(s)
norm
a(s) o
u outr
o(s) d
ocum
ento(
s) no
rmati
vo(s)
, des
de qu
e este
s seja
m uti
lizado
s de
acord
o com
as no
ssas in
struç
ões:
соотв
етству
ют сл
едую
щим с
танда
ртам и
ли др
угим н
орма
тивны
м доку
мента
м, пр
и усл
овии
их ис
поль
зован
ия со
гласн
о наш
им ин
струкц
иям:
overh
older
følge
nde s
tanda
rd(er)
eller
ande
t/and
re ret
nings
given
de do
kume
nt(er)
, forud
sat a
t diss
e anv
ende
s i he
nhold
til vo
re ins
trukse
r:res
pektiv
e utru
stning
är ut
förd i
övere
nsstä
mmels
e med
och f
öljer fö
ljande
stan
dard(
er) el
ler an
dra no
rmgiv
ande
doku
ment,
unde
r förut
sättn
ing at
tan
vänd
ning s
ker i
övere
nsstä
mmels
e med
våra
instru
ktione
r:res
pektiv
e utst
yr er
i ove
rensst
emme
lse m
ed fø
lgend
e stan
dard(
er) el
ler an
dre no
rmgiv
ende
doku
ment(
er), u
nder
foruts
setni
ng av
at di
sse br
ukes
ihe
nhold
til vå
re ins
trukse
r:va
staav
at se
uraav
ien st
anda
rdien
ja m
uiden
ohjee
llisten
doku
mentt
ien va
atimu
ksia e
dellyt
täen,
että n
iitä kä
ytetää
n ohje
idemm
e muk
aises
ti:za
před
pokla
du, ž
e jso
u vyu
žíván
y v so
uladu
s na
šimi p
okyn
y, od
povíd
ají ná
sledu
jícím
norm
ám ne
bo no
rmati
vním
doku
mentů
m:u s
kladu
sa sli
jedeć
im st
anda
rdom(
ima)
ili drug
im no
rmati
vnim
doku
mento
m(im
a), uz
uvjet
da se
oni ko
riste
u skla
du s
našim
uputa
ma:
16 17 18 19 20 21 22 23 24 25
megfe
lelnek
az al
ábbi
szabv
ány(o
k)nak
vagy
egyé
b irán
yadó
doku
mentu
m(ok
)nak,
ha az
okat
előírá
s sze
rint h
aszn
álják:
spełn
iają wy
mogi
nastę
pując
ych no
rm i in
nych
doku
mentó
w norm
alizac
yjnych
, pod
warun
kiem
że uż
ywan
e są z
godn
ie z n
aszym
i instr
ukcja
mi:
sunt
în co
nform
itate
cu ur
mător
ul (ur
mătoa
rele)
stand
ard(e)
sau a
lt(e) d
ocum
ent(e
) norm
ativ(e
), cu c
ondiţ
ia ca
aces
tea să
fie ut
ilizate
în co
nform
itate
cuins
trucţiu
nile no
astre
:skl
adni
z nas
lednjim
i stan
dardi
in dr
ugim
i norm
ativi,
pod p
ogoje
m, da
se up
orablja
jo v s
kladu
z na
šimi n
avod
ili:on
vasta
vuse
s järgm
is(t)e
stan
dardi
(te)ga
või te
iste no
rmati
ivsete
doku
menti
dega
, kui
neid
kasu
tatak
se va
stava
lt meie
juhe
ndite
le:съ
ответс
тват н
а сле
дните
стан
дарти
или д
руги
норм
ативн
и доку
менти
, при
усло
вие,
че се
изпо
лзва
т съгл
асно
наши
те ин
струкц
ии:
atitin
ka že
miau
nurod
ytus s
tanda
rtus ir
(arba
) kitu
s norm
inius d
okum
entus
su są
lyga,
kad y
ra na
udoja
mi pa
gal m
ūsų n
urody
mus:
tad, ja
lietot
i atbi
lstoši r
ažotā
ja no
rādīju
miem
, atbi
lst se
kojoš
iem st
anda
rtiem
un cit
iem no
rmatī
viem
doku
menti
em:
sú v
zhod
e s na
sledo
vnou
(ými) n
ormou
(ami) a
lebo i
ným(
i) norm
atívn
ym(i)
doku
mento
m(am
i), za
pred
pokla
du, ž
e sa p
oužív
ajú v
súlad
e s na
šimná
vodo
m:ürü
nün,
talim
atları
mıza
göre
kullan
ılmas
ı koş
uluyla
aşağ
ıdaki s
tanda
rtlar v
e norm
belirt
en be
lgeler
le uy
umlud
ur:
EN
6033
5-2-
40,
01 02 03 04 05 06 07 08 09
follow
ing th
e prov
isions
of:
gemä
ß den
Vorsc
hrifte
n der:
confo
rmém
ent a
ux st
ipulat
ions d
es:
overe
enko
mstig
de be
paling
en va
n:sig
uiend
o las
disp
osicio
nes d
e:se
cond
o le p
rescri
zioni
per:
με τήρ
ηση τ
ων δι
ατάξεω
ν των
:de
acord
o com
o pre
visto
em:
в соо
тветст
вии с
поло
жени
ями:
10 11 12 13 14 15 16 17 18
unde
r iagtt
agels
e af b
estem
melse
rne i:
enligt
villko
ren i:
gitt i
henh
old til
beste
mmels
ene i
:no
udatt
aen m
ääräy
ksiä:
za do
držen
í usta
nove
ní pře
dpisu
:pre
ma od
redba
ma:
köve
ti a(z)
:zg
odnie
z po
stano
wienia
mi Dy
rektyw
:în
urma p
reved
erilor
:
19 20 21 22 23 24 25
ob up
oštev
anju
določ
b:va
stava
lt nõu
etele:
след
вайки
клау
зите н
а:laik
antis
nuos
tatų,
patei
kiamų
:iev
ērojot
pras
ības,
kas n
oteikta
s:od
ržiav
ajúc u
stano
venia
:bu
nun k
oşulla
rına u
ygun
olara
k:
Mac
hine
ry 2
006/
42/E
CE
lect
rom
agne
tic C
ompa
tibili
ty 2
004/
108/
EC
** *
01 02 03 04 05 06 07 08 09
Direc
tives,
as am
ende
d.Dir
ektive
n, ge
mäß Ä
nderu
ng.
Direc
tives,
telles
que m
odifié
es.
Richtl
ijnen,
zoals
geam
ende
erd.
Direc
tivas,
segú
n lo e
nmen
dado
.Dir
ettive
, com
e da m
odific
a.Οδ
ηγιών
, όπω
ς έχο
υν τρ
οποπ
οιηθεί
.Dir
ectiva
s, co
nform
e alte
ração
em.
Дире
ктив с
о все
ми по
прав
ками.
10 11 12 13 14 15 16 17 18
Direk
tiver, m
ed se
nere
ændri
nger.
Direk
tiv, m
ed fö
retag
na än
dring
ar.Dir
ektive
r, med
foret
atte e
ndrin
ger.
Direk
tiivejä
, sella
isina k
uin ne
ovat
muute
ttuina
.v p
latné
m zn
ění.
Smjer
nice,
kako
je izm
ijenjen
o.irá
nyelv
(ek) é
s mód
osítá
saik r
ende
lkezé
seit.
z póź
niejsz
ymi p
opraw
kami
.Dir
ective
lor, c
u ame
ndam
entel
e res
pectiv
e.
19 20 21 22 23 24 25
Direk
tive z
vsemi
sprem
emba
mi.
Direk
tiivid
koos
muu
datus
tega.
Дире
ктиви
, с те
хните
изме
нени
я.Dir
ektyv
ose s
u pap
ildyma
is.Dir
ektīv
ās un
to pa
pildinā
jumos
.Sm
ernice
, v pl
atnom
znen
í.De
ǧiştiri
lmiş h
alleriy
le Yö
netm
elikler
.
01 No
te*
02 Hi
nweis
*
03 Re
marqu
e*
04 Be
merk*
05 No
ta*
as se
t out
in <A
> and
judg
ed po
sitive
ly by <
B>ac
cordi
ng to
the C
ertific
ate <C
>.wie
in <A
> aufg
eführt
und v
on <B
> pos
itivbe
urteilt
gemä
ß Zert
ifikat
<C>.
tel qu
e défi
ni da
ns <A
> et é
valué
positi
veme
nt pa
r <B>
confo
rmém
ent a
u Cert
ificat
<C>.
zoals
verm
eld in
<A> e
n pos
itief b
eoord
eeld
door
<B>
overe
enko
mstig
Certif
icaat
<C>.
como
se es
tablec
e en <
A> y
es va
lorad
opo
sitiva
mente
por <
B> de
acue
rdo co
n el
Certif
icado
<C>.
06 No
ta*
07 Ση
μείω
ση*
08 No
ta*
09 Пр
имеч
ание
*
10 Be
mærk*
deline
ato ne
l <A>
e giu
dicato
positi
vame
nte da
<B>
seco
ndo i
l Cert
ificato
<C>.
όπως
καθο
ρίζετα
ι στο
<A> κ
αι κρ
ίνεται
θετικ
άαπ
ό το <
B> σύ
μφων
α με τ
ο Πιστ
οποιη
τικό <
C>.
tal co
mo es
tabele
cido e
m <A
> e co
m o p
arece
r pos
itivo
de <B
> de a
cordo
com
o Cert
ificad
o <C>
.как
указа
но в
<A> и
в со
ответс
твии с
поло
жител
ьным
реше
нием
<B> с
оглас
но Св
идете
льств
у <C>
.so
m an
ført i
<A> o
g pos
itivt v
urdere
t af <
B> i h
enho
ld til
Certif
ikat <
C>.
11 In
forma
tion*
12 M
erk*
13 Hu
om*
14 Po
znám
ka*
15 Na
pome
na*
enligt
<A> o
ch go
dkän
ts av
<B> e
nligt
Certif
ikatet
<C>.
som
det fr
emko
mmer
i <A>
og gj
enno
m po
sitiv
bedø
mmels
e av <
B> ifø
lge Se
rtifika
t <C>
.jot
ka on
esite
tty as
iakirja
ssa <A
> ja j
otka <
B>on
hyvä
ksyny
t Sert
ifikaa
tin <C
> muk
aises
ti.jak
bylo
uved
eno v
<A> a
poziti
vně z
jištěn
o<B
> v so
uladu
s os
vědč
ením
<C>.
kako
je izl
ožen
o u <A
> i po
zitivn
o ocije
njeno
od st
rane
<B> p
rema C
ertifik
atu <C
>.
16 M
egjeg
yzés*
17 Uw
aga*
18 No
tă*
19 Op
omba
*
20 M
ärkus
*
a(z) <
A> al
apján
, a(z)
<B> i
gazo
lta a
megfe
lelést,
a(z)
<C> t
anús
ítván
y sze
rint.
zgod
nie z
doku
menta
cją <A
>, po
zytyw
nąop
inią <B
> i Św
iadec
twem
<C>.
aşa c
um es
te sta
bilit în
<A> ş
i apre
ciat p
ozitiv
de <B
>în
confo
rmita
te cu
Certif
icatul
<C>.
kot je
določ
eno v
<A> i
n odo
breno
s str
ani <
B>v s
kladu
s ce
rtifika
tom <C
>.na
gu on
näida
tud do
kume
ndis <
A> ja
heak
s kiide
tud<B
> järg
i vasta
valt s
ertifik
aadil
e <C>
.
21 За
беле
жка*
22 Pa
staba
*
23 Pi
ezīme
s*
24 Po
znám
ka*
25 No
t*
както
е изл
ожен
о в <A
> и оц
енен
о пол
ожите
лно о
т <B>
съгла
сно С
ерти
фикат
а <C>
.ka
ip nu
statyt
a <A>
ir ka
ip tei
giama
i nus
pręsta
<B> p
agal
Sertif
ikatą
<C>.
kā no
rādīts
<A> u
n atbi
lstoši <
B> po
zitīva
jam vē
rtējum
amsa
skaņā
ar se
rtifikā
tu <C
>.ak
o bolo
uved
ené v
<A> a
pozití
vne z
istené
<B> v
súlad
es o
sved
čením
<C>.
<A>’d
a belir
tildiği
gibi ve
<C> S
ertifik
asına
göre
<B>
tarafı
ndan
olum
lu ola
rak de
ğerle
ndirild
iği gib
i.
<A>
<B>
<C>
TÜV
(NB
1856
)
1208
0901
.T30
DA
IKIN
.TC
F.03
0A17
/06-
2015
01**
02**
03**
04**
05**
06**
Daikin
Europ
e N.V.
is au
thoris
ed to
comp
ile the
Tech
nical
Cons
tructio
n File.
Daikin
Europ
e N.V.
hat d
ie Be
rechti
gung
die T
echn
ische
Kons
truktio
nsak
te zu
samm
enzu
stellen
.Da
ikin Eu
rope N
.V. es
t auto
risé à
comp
iler le
Dossi
er de
Cons
tructio
n Tec
hniqu
e.Da
ikin Eu
rope N
.V. is
bevo
egd o
m he
t Tec
hnisc
h Con
struc
tiedo
ssier
same
n te s
tellen
.Da
ikin Eu
rope N
.V. es
tá au
toriza
do a
comp
ilar el
Arch
ivo de
Cons
trucci
ón Té
cnica
.Da
ikin Eu
rope N
.V. è
autor
izzata
a red
igere
il File
Tecn
ico di
Costr
uzion
e.
07**
08**
09**
10**
11**
12**
Η Daik
in Eu
rope N
.V. είν
αι εξο
υσιοδ
οτημέν
η να σ
υντάξ
ει τον
Τεχν
ικό φά
κελο κ
ατασκ
ευής.
A Daik
in Eu
rope N
.V. es
tá au
toriza
da a
comp
ilar a
docu
menta
ção t
écnic
a de f
abric
o.Ко
мпан
ия Da
ikin Eu
rope N
.V. уп
олно
моче
на со
стави
ть Ко
мпле
кт тех
ниче
ской д
окуме
нтаци
и.Da
ikin Eu
rope N
.V. er
autor
iseret
til at
udarb
ejde d
e tek
niske
kons
truktio
nsda
ta.Da
ikin Eu
rope N
.V. är
bemy
ndiga
de at
t sam
mans
tälla
den t
eknis
ka ko
nstru
ktions
filen.
Daikin
Europ
e N.V.
har ti
llatels
e til å
komp
ilere d
en Te
knisk
e kon
struk
sjons
filen.
13**
14**
15**
16**
17**
18**
Daikin
Europ
e N.V.
on va
ltuute
ttu la
atima
an Te
knise
n asia
kirjan
.Sp
olečn
ost D
aikin
Europ
e N.V.
má o
právn
ění k
e kom
pilaci s
oubo
ru tec
hnick
é kon
struk
ce.
Daikin
Europ
e N.V.
je ov
lašten
za izr
adu D
atotek
e o te
hničk
oj ko
nstru
kciji.
A Daik
in Eu
rope N
.V. jo
gosu
lt a m
űsza
ki kon
struk
ciós d
okum
entác
ió ös
szeállí
tására
.Da
ikin Eu
rope N
.V. m
a upo
ważn
ienie
do zb
ieran
ia i o
praco
wywa
nia do
kume
ntacji
kons
trukcy
jnej.
Daikin
Europ
e N.V.
este
autor
izat s
ă com
pileze
Dosa
rul te
hnic d
e con
struc
ţie.
19**
20**
21**
22**
23**
24**
25**
Daikin
Europ
e N.V.
je po
oblaš
čen z
a ses
tavo d
atotek
e s te
hničn
o map
o.Da
ikin Eu
rope N
.V. on
volita
tud ko
ostam
a teh
nilist
doku
menta
tsioon
i.Da
ikin Eu
rope N
.V. е
отори
зиран
а да с
ъстав
и Акта
за те
хнич
еска
констр
укция
.Da
ikin Eu
rope N
.V. yr
a įga
liota s
udary
ti šį te
chnin
ės ko
nstru
kcijos
failą.
Daikin
Europ
e N.V.
ir au
torizē
ts sa
stādīt
tehn
isko d
okum
entāc
iju.Sp
oločn
osť D
aikin
Europ
e N.V.
je op
rávne
ná vy
tvoriť
súbo
r tech
nicke
j konš
trukci
e.Da
ikin Eu
rope N
.V. Te
knik Y
apı D
osya
sını d
erlem
eye y
etkilid
ir.
Shi
geki
Mor
itaD
irect
orO
sten
d, 1
st o
f Sep
tem
ber,
2015
Table of Contents
Installation and operation manual
3RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Table of Contents
1 About the documentation 41.1 About this document.................................................................. 4
For the installer 4
2 About the box 42.1 Compressor unit ........................................................................ 4
2.1.1 To remove the accessories from the compressor unit 42.1.2 To remove the transportation stay .............................. 4
3 About the units and options 53.1 About the compressor unit and heat exchanger unit................. 53.2 System layout............................................................................ 5
4 Preparation 54.1 Preparing installation site .......................................................... 5
4.1.1 Installation site requirements of the compressor unit.. 54.2 Preparing refrigerant piping....................................................... 5
4.2.1 Refrigerant piping requirements.................................. 54.2.2 Refrigerant piping material.......................................... 54.2.3 To select the piping size ............................................. 64.2.4 To select refrigerant branch kits.................................. 6
4.3 Preparing electrical wiring ......................................................... 64.3.1 Safety device requirements ........................................ 6
5 Installation 75.1 Opening the units ...................................................................... 7
5.1.1 To open the compressor unit ...................................... 75.2 Mounting the compressor unit ................................................... 7
5.2.1 Guidelines when installing the compressor unit.......... 75.3 Connecting the refrigerant piping .............................................. 7
5.3.1 Using the stop valve and service port ......................... 75.3.2 To remove the pinched pipes...................................... 85.3.3 To connect the refrigerant piping to the compressor
unit .............................................................................. 95.4 Checking the refrigerant piping ................................................. 10
5.4.1 About checking the refrigerant piping ......................... 105.4.2 Checking refrigerant piping: General guidelines ......... 105.4.3 Checking refrigerant piping: Setup.............................. 105.4.4 To perform a leak test ................................................. 115.4.5 To perform vacuum drying .......................................... 11
5.5 To insulate the refrigerant piping............................................... 115.6 Charging refrigerant .................................................................. 11
5.6.1 Precautions when charging refrigerant ....................... 115.6.2 To determine the additional refrigerant amount .......... 125.6.3 To charge refrigerant .................................................. 125.6.4 Error codes when charging refrigerant........................ 135.6.5 To fix the fluorinated greenhouse gases label ............ 13
5.7 Connecting the electrical wiring................................................. 135.7.1 Field wiring: Overview................................................. 135.7.2 Guidelines when connecting the electrical wiring ....... 145.7.3 To connect the electrical wiring on the compressor
unit .............................................................................. 145.8 Finishing the compressor unit installation ................................. 15
5.8.1 To finish the transmission wiring................................. 15
6 Configuration 156.1 Making field settings.................................................................. 15
6.1.1 About making field settings ......................................... 156.1.2 To access the field setting components...................... 156.1.3 Field setting components ............................................ 156.1.4 To access mode 1 or 2 ............................................... 166.1.5 To use mode 1 (and default situation) ........................ 166.1.6 To use mode 2 ............................................................ 176.1.7 Mode 1 (and default situation): Monitoring settings .... 17
6.1.8 Mode 2: Field settings.................................................. 186.1.9 To connect the PC configurator to the compressor
unit ............................................................................... 20
7 Commissioning 207.1 Precautions when commissioning .............................................. 207.2 Checklist before commissioning................................................. 207.3 Checklist during commissioning ................................................. 21
7.3.1 About test run............................................................... 217.3.2 To perform a test run (7-LEDs display)........................ 217.3.3 Correcting after abnormal completion of the test run... 227.3.4 Operating the unit ........................................................ 22
8 Troubleshooting 228.1 Solving problems based on error codes..................................... 22
8.1.1 Error codes: Overview ................................................. 22
9 Technical data 249.1 Piping diagram: Compressor unit and heat exchanger unit ....... 249.2 Wiring diagram: Compressor unit ............................................... 24
For the user 25
10 About the system 2510.1 System layout............................................................................. 25
11 User interface 25
12 Operation 2512.1 Operation range ......................................................................... 2512.2 Operating the system ................................................................. 26
12.2.1 About operating the system ......................................... 2612.2.2 About cooling, heating, fan only, and automatic
operation ...................................................................... 2612.2.3 About the heating operation......................................... 2612.2.4 To operate the system (WITHOUT cool/heat
changeover remote control switch) .............................. 2612.2.5 To operate the system (WITH cool/heat changeover
remote control switch).................................................. 2612.3 Using the dry program................................................................ 27
12.3.1 About the dry program ................................................. 2712.3.2 To use the dry program (WITHOUT cool/heat
changeover remote control switch) .............................. 2712.3.3 To use the dry program (WITH cool/heat changeover
remote control switch).................................................. 2712.4 Adjusting the air flow direction.................................................... 27
12.4.1 About the air flow flap .................................................. 2712.5 Setting the master user interface ............................................... 27
12.5.1 About setting the master user interface ....................... 2712.5.2 To designate the master user interface (VRV DX)....... 28
13 Maintenance and service 2813.1 After-sales service and warranty ................................................ 28
13.1.1 Warranty period ........................................................... 2813.1.2 Recommended maintenance and inspection............... 28
14 Troubleshooting 2814.1 Error codes: Overview................................................................ 2914.2 Symptoms that are not air conditioner troubles.......................... 30
14.2.1 Symptom: The system does not operate ..................... 3014.2.2 Symptom: Cool/Heat cannot be changed over ............ 3014.2.3 Symptom: Fan operation is possible, but cooling and
heating do not work...................................................... 3014.2.4 Symptom: The fan strength does not correspond to
the setting .................................................................... 3014.2.5 Symptom: The fan direction does not correspond to
the setting .................................................................... 3014.2.6 Symptom: White mist comes out of a unit (Indoor
unit) .............................................................................. 3014.2.7 Symptom: White mist comes out of a unit (Indoor
unit, heat exchanger unit) ............................................ 30
1 About the documentation
Installation and operation manual
4RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
14.2.8 Symptom: The user interface display reads "U4" or"U5" and stops, but then restarts after a few minutes. 30
14.2.9 Symptom: Noise of air conditioners (Indoor unit, heatexchanger unit) ........................................................... 30
14.2.10 Symptom: Noise of air conditioners (Indoor unit,compressor unit, heat exchanger unit)........................ 31
14.2.11 Symptom: Noise of air conditioners (compressorunit, heat exchanger unit) ........................................... 31
14.2.12 Symptom: Dust comes out of the heat exchangerunit .............................................................................. 31
14.2.13 Symptom: The units can give off odours..................... 3114.2.14 Symptom: The heat exchanger unit fan does not spin 3114.2.15 Symptom: The display shows "88".............................. 3114.2.16 Symptom: The compressor in the compressor unit
does not stop after a short heating operation ............. 3114.2.17 Symptom: The inside of an compressor unit is warm
even when the unit has stopped ................................. 3114.2.18 Symptom: Hot air can be felt when the indoor unit is
stopped ....................................................................... 31
15 Relocation 31
16 Disposal 31
1 About the documentation
1.1 About this documentTarget audienceAuthorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trainedusers in shops, in light industry and on farms, or forcommercial use by lay persons.
Documentation setThis document is part of a documentation set. The complete setconsists of:
▪ General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the accessory bag of the compressor unit)
▪ Compressor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the accessory bag of the compressor unit)
▪ Heat exchanger unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the accessory bag of the heat exchangerunit)
▪ Installer and user reference guide:
▪ Preparation of the installation, technical specifications,reference data,…
▪ Detailed step-by-step instructions and background informationfor basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available onthe regional Daikin website or via your dealer.
The original documentation is written in English. All other languagesare translations.
For the installer
2 About the box
2.1 Compressor unit
2.1.1 To remove the accessories from thecompressor unit
1 Remove the accessories (part 1).
a1×
b1×
c1×
d1×
e1×
f3×
2 Remove the service cover. See "5.1.1 To open the compressorunit" on page 7.
3 Remove the accessories (part 2).
1× 1×1×1×i jhg
a General safety precautionsb Compressor unit installation and operation manualc Fluorinated greenhouse gases labeld Multilingual fluorinated greenhouse gases labele Screw (for shield of transmission wiring)f Cable tieg Gas piping accessory (circuit 1: to heat exchanger unit)
(Ø19.1 mm)h Liquid piping accessory (circuit 1: to heat exchanger unit)
(Ø12.7 mm)i Liquid piping accessory (circuit 2: to indoor units)
(Ø9.5 mm)j Gas piping accessory (circuit 2: to indoor units)
(Ø15.9 mm)
2.1.2 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached,abnormal vibration or noise may be generated.
The transportation stay installed over the compressor leg forprotecting the unit during transport must be removed. Proceed asshown in the figure and procedure below.
1 Slightly loosen the fixing nut (a).
2 Remove the transportation stay (b) as shown in the figurebelow.
3 Tighten the fixing nut (a) again.
3 About the units and options
Installation and operation manual
5RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
·
3
1
(10.1 N·m)
2
a
b
3 About the units and options
3.1 About the compressor unit andheat exchanger unit
The compressor unit and heat exchanger unit are intended for indoorinstallation and aimed for air to air heat pump applications.
Specification RKXYQ5+RDXYQ5Maximum capacity Heating 16 kW
Cooling 14 kWOutside ambientdesign temperature
Heating –20~15.5°C WBCooling –5~46°C DB
Ambient design temperature of compressorunit and heat exchanger unit
5~35°C DB(26°C WB)
3.2 System layoutNOTICE
Design of the system must not be done at temperaturesbelow –15°C.
d d
c c
a
b
VRV DX VRV DX VRV DX EKEXV
AHU
d d
1 2
1 In case of VRV DX indoor units2 In case of VRV DX indoor units combined with an air
handling unita Heat exchanger unitb Compressor unitc Refrigerant pipingd User interface (dedicated depending on indoor unit type)
VRV DX VRV direct expansion (DX) indoor unitEKEXV Expansion valve kit
AHU Air handling unit
4 Preparation
4.1 Preparing installation site
4.1.1 Installation site requirements of thecompressor unit
▪ Service space. Mind the following requirements:≥10 a ≥10
≥10
≥500
≥10
(mm)
3D098835-1
b
a Top viewb Front view
NOTICE
This is a class A product. In a domestic environment thisproduct may cause radio interference in which case theuser may be required to take adequate measures.
4.2 Preparing refrigerant piping
4.2.1 Refrigerant piping requirements
NOTICE
Refrigerant R410A requires strict cautions for keeping thesystem clean and dry. Foreign materials (including mineraloils or moisture) should be prevented from getting mixedinto the system.
NOTICE
The piping and other pressure-containing parts shall besuitable for refrigerant. Use phosphoric acid deoxidisedseamless copper for refrigerant.
▪ Foreign materials inside pipes (including oils for fabrication) mustbe ≤30 mg/10 m.
4.2.2 Refrigerant piping material▪ Piping material: Phosphoric acid deoxidised seamless copper.
▪ Piping temper grade and thickness:
Outer diameter(Ø)
Temper grade Thickness (t)(a)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Annealed (O) ≥0.80 mmt
Ø
15.9 mm (5/8") Annealed (O) ≥0.99 mm19.1 mm (3/4") Half hard (1/2H) ≥0.80 mm
(a) Depending on the applicable legislation and the unit'smaximum working pressure (see "PS High" on the unitname plate), larger piping thickness might be required.
4 Preparation
Installation and operation manual
6RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
4.2.3 To select the piping sizeDetermine the proper size referring to following tables and referencefigure (only for indication).
A
a
B
D
D
CD
D
bEKEXV
AHU
VRV DX
VRV DX
c c
a Heat exchanger unitb Compressor unitc Refrigerant branch kit
VRV DX VRV DX indoor unitEKEXV Expansion valve kit
AHU Air handling unitA Piping between heat exchanger unit and compressor unitB Piping between compressor unit and (first) refrigerant
branch kit (= main pipe)C Piping between refrigerant branch kitsD Piping between refrigerant branch kit and indoor unit
In case the required pipe sizes (inch sizes) are not available, it isalso allowed to use other diameters (mm sizes), taken the followinginto account:
▪ Select the pipe size nearest to the required size.
▪ Use the suitable adapters for the change-over from inch to mmpipes (field supply).
▪ The additional refrigerant calculation has to be adjusted asmentioned in "5.6.2 To determine the additional refrigerantamount" on page 12.
A: Piping between heat exchanger unit andcompressor unitUse the following diameters:
Compressor unitcapacity type (HP)
Piping outer diameter size (mm)Gas pipe Liquid pipe
5 19.1 12.7
B: Piping between compressor unit and (first)refrigerant branch kitIf the equivalent pipe length between the heat exchanger unit andthe furthest indoor unit is 90 m or more, it is recommended toincrease the size (size-up) of the main gas pipe (betweencompressor unit and first refrigerant branch kit). If the recommendedgas pipe (size-up) is not available, you must use the standard size(which might result in a small capacity decrease).
Compressor unitcapacity type (HP)
Piping outer diameter size (mm)Gas pipe Liquid pipe
Standard Size-up5 15.9 19.1 9.5
C: Piping between refrigerant branch kitsUse the following diameters:
Indoor unit capacityindex
Piping outer diameter size (mm)Gas pipe Liquid pipe
<150 15.9 9.5
D: Piping between refrigerant branch kit andindoor unitUse the same diameters as the connections (liquid, gas) on theindoor units. The diameters of the indoor units are as follows:
Indoor unit capacityindex
Piping outer diameter size (mm)Gas pipe Liquid pipe
15~50 12.7 6.463~140 15.9 9.5
4.2.4 To select refrigerant branch kitsFor piping example, refer to "4.2.3 To select the piping size" onpage 6.
Refnet jointWhen using refnet joints, choose from the following table inaccordance with the capacity of the compressor unit. Example:Refnet joint c.
Compressor unit capacity type(HP)
Refrigerant branch kit
5 KHRQ22M20T
Refnet headersWhen using refnet headers, choose from the following table inaccordance with the capacity of the compressor unit.
Compressor unit capacity type(HP)
Refrigerant branch kit
5 KHRQ22M29H
INFORMATION
Maximum 8 branches can be connected to a header.
4.3 Preparing electrical wiring
4.3.1 Safety device requirements
NOTICE
When using residual current operated circuit breakers, besure to use a high-speed type 300 mA rated residualoperating current.
Power supply: Compressor unitThe power supply must be protected with the required safetydevices, i.e. a main switch, a slow blow fuse on each phase and anearth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance withthe applicable legislation based on the information mentioned in thetable below.
Model Minimum circuitampacity
Recommendedfuses
RKXYQ5 13.5 A 16 A
▪ Phase and frequency: 3N~ 50 Hz
▪ Voltage: 380-415 V
Transmission wiringTransmission line section:
Transmission wiring Sheathed + shielded cable (2wires)
Vinyl cords
0.75~1.25 mm²
5 Installation
Installation and operation manual
7RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Maximum wiring length
(= distance between compressorunit and furthest indoor unit)
300 m
Total wiring length
(= distance between compressorunit and all indoor units, andbetween compressor unit andheat exchanger unit)
600 m
If the total transmission wiring exceeds these limits, it mayresult in communication error.
5 Installation
5.1 Opening the units
5.1.1 To open the compressor unit
DANGER: RISK OF BURNING
DANGER: RISK OF ELECTROCUTION
1 Remove the service cover of the compressor unit.
2 If you want to make field settings, remove the inspection cover.
3 If you want to connect electrical wiring, remove the switch boxcover.
2
3
1
5× 4×
5.2 Mounting the compressor unit
5.2.1 Guidelines when installing thecompressor unit
Check the strength and level of the installation ground so that theunit will not cause any operating vibration or noise. If the vibrationmight be transmitted to the building, use a vibration-proof rubber(field supply).
You can install the compressor unit directly on the floor or on astructure.
▪ On the floor. You do NOT have to fix the unit with anchor bolts.
▪ On a structure. Fix the unit securely with anchor bolts, nuts andwashers (field supply) to the structure. The foundation (steel beamframe or concrete) must be larger than the grey marked area.
a
≤480
516
≥666
426
≥640
(mm)
Minimum foundationa Anchor point (4×)
INFORMATION
The recommended height of the upper protruding part ofthe bolts is 20 mm.
20 m
m
5.3 Connecting the refrigerant pipingDANGER: RISK OF BURNING
5.3.1 Using the stop valve and service port
To handle the stop valve▪ Make sure to keep all stop valves open during operation.
▪ The stop valve is factory closed.
To open the stop valve1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stopvalve counterclockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now open.
To fully open the Ø19.1 stop valve, turn the hexagonal wrench until atorque between 27 and 33 N•m is achieved.
Inadequate torque may cause leakage of refrigerant and breakage ofthe stop valve cap.
1
23
4
5 Installation
Installation and operation manual
8RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
NOTICE
Pay attention that mentioned torque range is applicable foropening Ø19.1 mm stop valves only.
To close the stop valve1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stopvalve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now closed.
Closing direction:
To handle the stop valve cover▪ The stop valve cover is sealed where indicated by the arrow. Take
care not to damage it.
▪ After handling the stop valve, make sure to tighten the stop valvecover securely. For the tightening torque, refer to the table below.
▪ Check for refrigerant leaks after tightening the stop valve cover.
To handle the service port▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the serviceport cover securely. For the tightening torque, refer to the tablebelow.
▪ Check for refrigerant leaks after tightening the service port cover.
Tightening torques
Stop valvesize (mm)
Tightening torque N•m (turn clockwise to close)Shaft
Valve body Hexagonalwrench
Cap (valvelid)
Serviceport
Ø9.5 5.4~6.6 4 mm 13.5~16.5 11.5~13.9Ø19.1 27.0~33.0 8 mm 22.5~27.5
5.3.2 To remove the pinched pipes
WARNING
Any gas or oil remaining inside the stop valve may blow offthe pinched piping.
Failure to observe the instructions in procedure belowproperly may result in property damage or personal injury,which may be serious depending on the circumstances.
Use the following procedure to remove the pinched piping:
1 Remove the valve cover and make sure that the stop valves arefully closed.
c
d
a
b
a Service port and service port coverb Stop valvec Field piping connectiond Stop valve cover
2 Connect the vacuuming/recovery unit through a manifold to theservice port of all stop valves.
You have to recover gas and oil from all 4 pinched pipes. Dependingon your available tools, use method 1 (manifold with refrigerant linesplitters required) or method 2.
Manifold Connections Compressor unit
p< p>
e
B
A Method 1:
Connect to all serviceports at once.
C
abA
cdB
CC
C
D
D
cd
ba
Method 2:
First connect to thefirst 2 service ports.
C
C
bBaA
Then connect to thelast 2 service ports.
dBcA
C
C
a, b, c, d Service ports of stop valvese Vacuuming/recovery unit
A, B, C Valves A, B and CD Refrigerant line splitter
3 Recover gas and oil from the pinched piping by using arecovery unit.
CAUTION
Do not vent gases into the atmosphere.
4 When all gas and oil is recovered from the pinched piping,disconnect the charge hose and close the service ports.
5 Cut off the lower part of the gas and liquid stop valve pipesalong the black line. Use an appropriate tool (e.g. a pipe cutter,a pair of nippers).
5 Installation
Installation and operation manual
9RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
WARNING
Never remove the pinched piping by brazing.
Any gas or oil remaining inside the stop valve may blow offthe pinched piping.
6 Wait until all oil is dripped out before continuing with theconnection of the field piping in case the recovery was notcomplete.
5.3.3 To connect the refrigerant piping to thecompressor unit
NOTICE
▪ Be sure to use the supplied accessory pipes whencarrying out piping work in the field.
▪ Be sure that the field installed piping does not touchother pipes, the bottom panel or side panel.
1 Remove the service cover. See "5.1.1 To open the compressorunit" on page 7.
2 Choose a piping route (a or b).
b
a
a
a To the backb To the top
3 If you have chosen the piping route to the top:
a b c d
a Cut the insulation (under the knockout hole).b Hit on the knockout hole, and remove it.c Remove the burrs.d Paint the edges and areas around the edges using repair
paint to prevent rusting.
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing.
▪ After making the knockout holes, we recommend youremove the burrs and paint the edges and areasaround the edges using repair paint to prevent rusting.
▪ When passing electrical wiring through the knockoutholes, wrap the wiring with protective tape to preventdamage.
4 Connect piping (by brazing) as follows:
a1
c1
c2c3
a2a3
b1
b2b3
d3d1d2
a Liquid line (circuit 2: to indoor units)b Gas line (circuit 2: to indoor units)c Gas line (circuit 1: to heat exchanger unit)d Liquid line (circuit 1: to heat exchanger unit)1 Pinched piping2 Piping accessory3 Field piping
5 Reattach the service cover.
6 Seal all gaps (example: a) to prevent small animals fromentering the system.
a
a
a
a
WARNING
Provide adequate measures to prevent that the unit can beused as a shelter by small animals. Small animals thatmake contact with electrical parts can cause malfunctions,smoke or fire.
5 Installation
Installation and operation manual
10RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
5.4 Checking the refrigerant piping
5.4.1 About checking the refrigerant pipingRefrigerant piping works are finished?
The indoor units, compressor unit and/or heat exchanger unit were already powered ON?
Use procedure:"Method 2: After power ON".
Finish piping work.
Use procedure:"Method 1: Before power ON (regular method)".
Yes
No
No
Yes
It is very important that all refrigerant piping work is done before theunits (compressor unit, heat exchanger unit or indoor units) arepowered on.
When the units are powered on, the expansion valves will initialise.This means that they will close. Leak test and vacuum drying of fieldpiping, heat exchanger unit and indoor units is impossible when thishappens.
Therefore, there will be explained 2 methods for initial installation,leak test and vacuum drying.
Method 1: Before power ONIf the system has not yet been powered on, no special action isrequired to perform the leak test and the vacuum drying.
Method 2: After power ONIf the system has already been powered on, activate setting [2‑21](refer to "6.1.4 To access mode 1 or 2" on page 16). This settingwill open field expansion valves to guarantee a R410A pipingpathway and make it possible to perform the leak test and thevacuum drying.
NOTICE
Make sure that the heat exchanger unit and all indoor unitsconnected to the compressor unit are powered on.
NOTICE
Wait until the compressor unit has finished the initialisationto apply setting [2‑21].
Leak test and vacuum dryingChecking the refrigerant piping involves:
▪ Checking for any leakages in the refrigerant piping.
▪ Performing vacuum drying to remove all moisture, air or nitrogenin the refrigerant piping.
If there is a possibility of moisture being present in the refrigerantpiping (for example, water may have entered the piping), first carryout the vacuum drying procedure below until all moisture has beenremoved.
All piping inside the unit has been factory tested for leaks.
Only field installed refrigerant piping needs to be checked.Therefore, make sure that all the compressor unit stop valves arefirmly closed before performing leak test or vacuum drying.
NOTICE
Make sure that all (field supplied) field piping valves areOPEN (not compressor unit stop valves!) before you startleak test and vacuuming.
For more information on the state of the valves, refer to"5.4.3 Checking refrigerant piping: Setup" on page 10.
5.4.2 Checking refrigerant piping: Generalguidelines
Connect the vacuum pump through a manifold to the service port ofall stop valves to increase efficiency (refer to "5.4.3 Checkingrefrigerant piping: Setup" on page 10).
NOTICE
Use a 2-stage vacuum pump with a non-return valve or asolenoid valve that can evacuate to a gauge pressure of–100.7 kPa (5 Torr absolute).
NOTICE
Make sure the pump oil does not flow oppositely into thesystem while the pump is not working.
NOTICE
Do not purge the air with refrigerants. Use a vacuum pumpto evacuate the installation.
5.4.3 Checking refrigerant piping: SetupThe system contains 2 refrigerant circuits:
▪ Circuit 1: Compressor unit → Heat exchanger unit
▪ Circuit 2: Compressor unit → Indoor units
You have to check both circuits (leak test, vacuuming drying). Howto check depends on your available tools:
If you have amanifold…
Then
With refrigerant linesplitters
You can check both circuits at once. To doso, connect the manifold via the splitters toboth circuits, and check.
Without refrigerantline splitters
(takes twice as long)
You have to check the circuits separately. Todo so:
▪ First connect the manifold to circuit 1,and check.
▪ Then connect the manifold to circuit 2,and check.
Possible connections:
Manifold Connections Compressor unit
p< p>
R410AN2
b c e
ad
B
A Circuit 1 and 2together
C
ghA
fiB
CC
C
D
D
hi
gf
Only circuit 1
iBhA
C
C
Only circuit 2
C
C
fBgA
5 Installation
Installation and operation manual
11RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
a Pressure reducing valveb Nitrogenc Weighing scalesd Refrigerant R410A tank (siphon system)e Vacuum pumpf Liquid line stop valve (circuit 2: to indoor units)g Gas line stop valve (circuit 2: to indoor units)h Gas line stop valve (circuit 1: to heat exchanger unit)i Liquid line stop valve (circuit 1: to heat exchanger unit)
A, B, C Valves A, B and CD Refrigerant line splitter
Valve State of valveValves A, B and C OpenLiquid line and gas line stopvalves (f, g, h, i)
Close
NOTICE
The connections to the indoor units and to the heatexchanger unit, and all indoor units and the heatexchanger unit itself should also be leak and vacuumtested. Keep any possible (field supplied) field pipingvalves open as well.
Refer to the indoor unit installation manual for more details.Leak test and vacuum drying should be done before thepower supply is set to the unit. If not, see also the flowchart earlier described in this chapter (see "5.4.1 Aboutchecking the refrigerant piping" on page 10).
5.4.4 To perform a leak testThe leak test must satisfy the specifications of EN378‑2.
To check for leaks: Vacuum leak test1 Evacuate the system from the liquid and gas piping to
–100.7 kPa (–1.007 bar/5 Torr) for more than 2 hours.
2 Once reached, turn off the vacuum pump and check that thepressure does not rise for at least 1 minute.
3 Should the pressure rise, the system may either containmoisture (see vacuum drying below) or have leaks.
To check for leaks: Pressure leak test1 Break the vacuum by pressurising with nitrogen gas to a
minimum gauge pressure of 0.2 MPa (2 bar). Never set thegauge pressure higher than the maximum operation pressure ofthe unit, i.e. 4.0 MPa (40 bar).
2 Test for leaks by applying a bubble test solution to all pipingconnections.
3 Discharge all nitrogen gas.
NOTICE
Make sure to use a recommended bubble test solutionfrom your wholesaler. Do not use soap water, which maycause cracking of flare nuts (soap water may contain salt,which absorbs moisture that will freeze when the pipinggets cold), and/or lead to corrosion of flared joints (soapwater may contain ammonia which causes a corrosiveeffect between the brass flare nut and the copper flare).
5.4.5 To perform vacuum dryingTo remove all moisture from the system, proceed as follows:
1 Evacuate the system for at least 2 hours to a target vacuum of–100.7 kPa (–1.007 bar/5 Torr).
2 Check that, with the vacuum pump turned off, the targetvacuum is maintained for at least 1 hour.
3 Should you fail to reach the target vacuum within 2 hours ormaintain the vacuum for 1 hour, the system may contain toomuch moisture. In that case, break the vacuum by pressurisingwith nitrogen gas to a gauge pressure of 0.05 MPa (0.5 bar)and repeat steps 1 to 3 until all moisture has been removed.
4 Depending on whether you want to immediately chargerefrigerant through the refrigerant charge port or first pre-chargea portion of refrigerant through the liquid line, either open thecompressor unit stop valves, or keep them closed. See"5.6.3 To charge refrigerant" on page 12 for more information.
5.5 To insulate the refrigerant pipingAfter finishing the leak test and vacuum drying, the piping must beinsulated. Take into account the following points:
▪ Make sure to insulate the connection piping and refrigerant branchkits entirely.
▪ Be sure to insulate the liquid and gas piping (for all units).
▪ Use heat resistant polyethylene foam which can withstand atemperature of 70°C for liquid piping and polyethylene foam whichcan withstand a temperature of 120°C for gas piping.
▪ Reinforce the insulation on the refrigerant piping according to theinstallation environment.
Ambienttemperature
Humidity Minimum thickness
≤30°C 75% to 80% RH 15 mm>30°C ≥80% RH 20 mm
Condensation might form on the surface of the insulation.
▪ If there is a possibility that condensation on the stop valve mightdrip down into the indoor unit or into the heat exchanger unitthrough gaps in the insulation and piping because the compressorunit is located higher than the indoor unit or higher than the heatexchanger unit, this must be prevented by sealing up theconnections. See below figure.
ab
a Insulation materialb Caulking etc.
5.6 Charging refrigerant
5.6.1 Precautions when charging refrigerant
WARNING
▪ Only use R410A as refrigerant. Other substances maycause explosions and accidents.
▪ R410A contains fluorinated greenhouse gases. Itsglobal warming potential value is 2087.5. Do NOT ventthese gases into the atmosphere.
▪ When charging refrigerant, always use protectivegloves and safety glasses.
5 Installation
Installation and operation manual
12RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
NOTICE
If the power of some units is turned off, the chargingprocedure cannot be finished properly.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
NOTICE
If operation is performed within 12 minutes after thecompressor unit, heat exchanger unit and indoor units areturned on, the compressor will not operate before thecommunication is established in a correct way between thecompressor unit, heat exchanger unit and indoor units.
NOTICE
Before starting charging procedures, check if the 7‑LEDsdisplay is as normal (see "6.1.4 To access mode 1 or 2" onpage 16), and there is no malfunction code on the userinterface of the indoor unit. If a malfunction code ispresent, see "8.1 Solving problems based on errorcodes" on page 22.
NOTICE
Make sure all connected units (heat exchanger unit +indoor units) are recognised (setting [1‑5]).
5.6.2 To determine the additional refrigerantamount
Additional refrigerant to be charged=R (kg). R should be rounded offin units of 0.1 kg.
R=[(X1×Ø12.7)×0.12+(X2×Ø9.5)×0.059+(X3×Ø6.4)×0.022]×0.8+B
X1...3=Total length (m) of liquid piping size at Øa
Model B parameter (kg)RKXYQ5 3.1
When using metric piping, please take into account following tableconcerning the weight factor to be allocated. It should be substitutedin the formula for R.
Inch piping Metric pipingSize (Ø) (mm) Weight factor Size (Ø) (mm) Weight factor
6.4 0.022 6 0.0189.5 0.059 10 0.065
12.7 0.12 12 0.097
5.6.3 To charge refrigerantCharging refrigerant consists of 2 stages:
Stage DescriptionStage 1: Pre-charging Recommended in case of larger systems.
Can be skipped, but charging will take longerthen.
Stage 2: Manualcharging
Only necessary if the determined additionalrefrigerant amount is not reached yet bypre-charging.
Stage 1: Pre-charging
Summary – Pre-charging:
Refrigerant bottle Connected to the service ports of the stopvalves. Which stop valves to use dependson the circuits you choose to pre-charge to:
▪ Circuits 1 and 2 together (manifold withrefrigerant line splitters required).
▪ First circuit 1, then circuit 2 (or vice versa).
▪ Only circuit 1
▪ Only circuit 2Stop valves ClosedCompressor Does NOT operate
1 Connect as shown (choose one of the possible connections).Make sure that all compressor unit stop valves, as well as valveA are closed.
Possible connections:
Manifold Connections Compressor unit
p< p>
R410AN2
b c e
ad
B
A Circuit 1 and 2together
C
ghA
fiB
CC
C
D
D
hi
gf
Only circuit 1
iBhA
C
C
Only circuit 2
C
C
fBgA
a Pressure reducing valveb Nitrogenc Weighing scalesd Refrigerant R410A tank (siphon system)e Vacuum pumpf Liquid line stop valve (circuit 2: to indoor units)g Gas line stop valve (circuit 2: to indoor units)h Gas line stop valve (circuit 1: to heat exchanger unit)i Liquid line stop valve (circuit 1: to heat exchanger unit)
A, B, C Valves A, B and CD Refrigerant line splitter
2 Open valves C (on line of B) and B.
3 Pre‑charge refrigerant until the determined additional refrigerantamount is reached or pre‑charging is not possible anymore, andthen close valves C and B.
4 Do one of the following:
If ThenThe determined additionalrefrigerant amount is reached
Disconnect the manifold fromthe liquid line(s).
You do not have to perform the"Stage 2" instructions.
Too much refrigerant ischarged
Recover refrigerant until thedetermined additionalrefrigerant is reached.
Disconnect the manifold fromthe liquid line(s).
You do not have to perform the"Stage 2" instructions.
The determined additionalrefrigerant amount is notreached yet
Disconnect the manifold fromthe liquid line(s).
Continue with the "Stage 2"instructions.
5 Installation
Installation and operation manual
13RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Stage 2: Manual charging(= charging in the "Manual additional refrigerant charge" mode)
Summary – Manual charging:Refrigerant bottle Connected to the service port for refrigerant
charge.
This charges to both circuits, and to thecompressor unit's internal refrigerant piping.
Stop valves OpenCompressor Operates
5 Connect as shown. Make sure valve A is closed.
p< p>
R410A
a c
b
A
e
d
a Weighing scalesb Refrigerant R410A tank (siphon system)c Vacuum pumpd Refrigerant charge porte Heat exchanger unitA Valve A
NOTICE
The refrigerant charging port is connected to the pipinginside the unit. The unit's internal piping is already factorycharged with refrigerant, so be careful when connectingthe charge hose.
6 Open all compressor unit stop valves. At this point, valve Amust remain closed!
7 Take all the precautions mentioned in "6 Configuration" onpage 15 and "7 Commissioning" on page 20 into account.
8 Turn on the power of the indoor units, compressor unit and heatexchanger unit.
9 Activate setting [2‑20] to start the manual additional refrigerantcharge mode. For details, see "6.1.8 Mode 2: Field settings" onpage 18.
Result: The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automaticallystop within 30 minutes. If charging is not completed after30 minutes, perform the additional refrigerant chargingoperation again.
INFORMATION
▪ When a malfunction is detected during the procedure(e.g., in case of closed stop valve), a malfunction codewill be displayed. In that case, refer to "5.6.4 Errorcodes when charging refrigerant" on page 13 andsolve the malfunction accordingly. Resetting themalfunction can be done by pushing BS3. You canrestart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible bypushing BS3. The unit will stop and return to idlecondition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additionalrefrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant chargemode.
NOTICE
Make sure to open all stop valves after (pre-) charging therefrigerant.
Operating with the stop valves closed will damage thecompressor.
NOTICE
After adding the refrigerant, do not forget to close the lid ofthe refrigerant charging port. The tightening torque for thelid is 11.5 to 13.9 N•m.
5.6.4 Error codes when charging refrigerant
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm themalfunction code and take corresponding action, "8.1 Solvingproblems based on error codes" on page 22.
5.6.5 To fix the fluorinated greenhouse gaseslabel
1 Fill in the label as follows:
d
c
b
a
a From the multilingual fluorinated greenhouse gases labelpeal off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name platec Additional refrigerant amount chargedd Total refrigerant charge
2 Fix the label on the inside of the compressor unit. There is adedicated place for it on the wiring diagram label.
5.7 Connecting the electrical wiring
5.7.1 Field wiring: OverviewField wiring consists of:
▪ Power supply (always including earth)
▪ Communication (= transmission) wiring between the compressorunit, the heat exchanger unit, and the indoor units.
Example:
g
fF1/F2(16 V)
F1/F2(16 V)
220-240 V1~ 50 Hz
e
c
a
d
b
220-240 V1~ 50 Hz
380-415 V3N~ 50 Hz
a Main switch
5 Installation
Installation and operation manual
14RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
b Earth connectionc Power supply wiring (including earth) (sheathed cable)
F1/F2 Transmission wiring (sheathed + shielded cable)d Compressor unite Heat exchanger unitf Indoor unitg User interface
BranchesNo branching is allowed after branching.
D
B
C
b2
b3
c1
c2
b1
a
A
A Central user interface (etc...)B Compressor unitC Indoor unitD Heat exchanger unita Main line. The main line is the line to which the
transmission wiring of the heat exchanger unit isconnected.
b1, b2, b3 Branch linesc1, c2 No branch is allowed after branch
5.7.2 Guidelines when connecting the electricalwiring
Tightening torques
Wiring Screw size Tightening torque(N•m)
Power supply wiring
(power supply +shielded ground)
M5 2.0~3.0
Transmission wiring M3.5 0.8~0.97
5.7.3 To connect the electrical wiring on thecompressor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,located on the switch box cover).
▪ Make sure the electrical wiring does NOT obstructproper reattachment of the service cover.
1 Remove the service covers of the compressor unit and theswitch box.
2 Connect the transmission wiring as follows:
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
d
X2MX2MTO OUT/DTO IN/D
F1 F2 F1 F2
ba
c
a Compressor unitb Heat exchanger unitc Sheathed + shielded cable (2 wires) (no polarity)d Terminal board (field supply)
WARNING
You must use shielded wire and connect the earth to thetransmission terminal.
X2MF1 F2
a
a Earth (use the screw delivered as accessory)
3 Connect the power supply as follows:3N~ 50 Hz380-415 V
L1 L2 L3
L1 L2 L3
N X1M
ab
c
a Earth leakage circuit breakerb Fusec Power supply cable
4 Route the wiring through the frame, and fix the cables (powersupply and transmission wiring) with cable ties.
INFORMATION
To make routing the wiring easier, you can turn the switchbox horizontally by loosening the screw on the left side ofthe switch box.
1×
6 Configuration
Installation and operation manual
15RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
X1MX2M c
c
b
a≥50 mm
ba
X2M
b a
X1ML1
F1 F2
L2 L3 N
c ca Transmission wiringb Power supplyc Cable tie
5 Reattach the service covers.
6 Connect an earth leakage circuit breaker and fuse to the powersupply line.
5.8 Finishing the compressor unitinstallation
5.8.1 To finish the transmission wiringAfter installing the transmission wires inside the unit, wrap themalong with the on-site refrigerant pipes using finishing tape, asshown in figure below.
a bc de
a Liquid pipeb Gas pipec Insulatord Transmission wiring (F1/F2)e Finishing tape
6 ConfigurationINFORMATION
It is important that all information in this chapter is readsequentially by the installer and that the system isconfigured as applicable.
DANGER: RISK OF ELECTROCUTION
6.1 Making field settings
6.1.1 About making field settingsTo configure the heat pump system, you must give input to thecompressor unit's main PCB (A1P). This involves the following fieldsetting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
▪ DIP switches (only change the factory settings if you install a cool/heat selector switch).
Field settings are defined by their mode, setting and value. Example:[2‑8]=4.
PC configuratorYou can also make field settings through a personal computerinterface (for this, option EKPCCAB is required). The installer canprepare the configuration (off-site) on PC and afterwards upload theconfiguration to the system.
See also: "6.1.9 To connect the PC configurator to the compressorunit" on page 20.
Mode 1 and 2
Mode DescriptionMode 1
(monitoringsettings)
Mode 1 can be used to monitor the currentsituation of the compressor unit. Some fieldsetting contents can be monitored as well.
Mode 2
(field settings)
Mode 2 is used to change the field settings ofthe system. Consulting the current field settingvalue and changing the current field settingvalue is possible.
In general, normal operation can be resumedwithout special intervention after changing fieldsettings.
Some field settings are used for specialoperation (e.g., 1 time operation, recovery/vacuuming setting, manual adding refrigerantsetting, etc.). In such a case, it is required toabort the special operation before normaloperation can restart. It will be indicated inbelow explanations.
6.1.2 To access the field setting componentsSee "5.1.1 To open the compressor unit" on page 7.
6.1.3 Field setting componentsThe components to make field settings are as follows:
A1P
A2P
X1M X2M
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H1P H2P H3P H4P H5P H6P H7P H8P
1 2OFFON DS1
MULTIDEMANDL.N.O.P.SLAVEMASTERINDTEST/HWLMODE
DS1 DIP switchesBS1~BS5 Push buttonsH1P~H7P 7‑LEDs display
H8P LED for indication during initialisationON ( ) OFF ( ) Flashing ( )
6 Configuration
Installation and operation manual
16RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
DIP switchesOnly change the factory settings if you install a cool/heat selectorswitch.
DS1‑1 COOL/HEAT selector (refer to the manual of thecool/heat selector switch). OFF=notinstalled=factory setting
DS1‑2 NOT USED. DO NOT CHANGE THE FACTORYSETTING.
Push buttonsUse the push buttons to make the field settings. Operate the pushbuttons with an insulated stick (such as a closed ball-point pen) toavoid touching of live parts.
BS1 MODE: For changing the set modeBS2 SET: For field settingBS3 RETURN: For field settingBS4 TEST: For test operationBS5 RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
7‑LEDs displayThe display gives feedback about the field settings, which aredefined as [Mode-Setting]=Value.
H1P Shows the modeH2P~H7P Shows the settings and values, represented in binary code
H8P NOT used for field settings, but used during initialisation
Example:
H1P H2P H3P H4P H5P H6P H7P
- + + + + +[H1P 32 16 8 4 2 1] Description
(H1P OFF)
Default situation
(H1P flashing)
Mode 1
(H1P ON)
Mode 2
+ + + + +0 0 8 0 0 0
(H2P~H7P = binary 8)
Setting 8
(in mode 2)
+ + + + +0 0 0 4 0 0
(H2P~H7P = binary 4)
Value 4
(in mode 2)
6.1.4 To access mode 1 or 2After the units are turned ON, the display goes to its defaultsituation. From there, you can access mode 1 and mode 2.
Initialisation: default situation
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
Turn on the power supply of the compressor unit, heat exchangerunit, and all indoor units. When the communication between thecompressor unit, heat exchanger unit, and indoor units is establishedand normal, the display indication state will be as below (defaultsituation when shipped from factory).
10~12 min
b
c
a
a Power ONb Default situationc LED indication when there is a malfunction
If the default situation is not displayed after 10~12 minutes, checkthe malfunction code on the indoor unit user interface. Solve themalfunction code accordingly. First, check the communication wiring.
Switching between modesUse BS1 to switch between the default situation, mode 1 andmode 2.
BS1 [5 s]BS1BS1 BS1
a
cba Default situation (H1P OFF)b Mode 1 (H1P flashing)c Mode 2 (H1P ON)
BS1 Press BS1.BS1 [5 s] Press BS1 for at least 5 s.
INFORMATION
If you get confused in the middle of the process, press BS1to return to the default situation.
6.1.5 To use mode 1 (and default situation)In mode 1 (and in default situation) you can read out someinformation.
Example: 7‑LEDs display – Default situationYou can read out the status of low noise operation as follows:
# Action Button/display1 Make sure the LEDs are
showing the default situation.(H1P OFF)
2 Check the status of LEDH6P. H6P OFF: Unit is currently
not operating under low noiserestrictions.
H6P ON: Unit is currentlyoperating under low noiserestrictions.
Example: 7‑LEDs display – Mode 1You can read out setting [1‑5] (= the total number of connected units(heat exchanger unit + indoor units)) as follows:
# Action Button/display1 Start from the default
situation.
6 Configuration
Installation and operation manual
17RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
# Action Button/display2 Select mode 1. BS1 [1×]
3 Select setting 5.
("X×" depends on the settingthat you want to select.)
BS2 [X×]
(= binary 5)4 Display the value of setting 5.
(there are 8 units connected)
BS3 [1×]
(= binary 8)5 Quit mode 1. BS1 [1×]
6.1.6 To use mode 2In mode 2 you can make field settings to configure the system.
Example: 7‑LEDs display – Mode 2You can change the value of setting [2‑8] (= Te target temperatureduring cooling operation) to 4 (= 8°C) as follows:
# Action Button/display1 Start from the default
situation.2 Select mode 2. BS1 [5 s]
3 Select setting 8.
("X×" depends on the settingthat you want to select.)
BS2 [X×]
(= binary 8)4 Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"depends on the currentvalue, and the value that youwant to select.)
c: Enter the value in thesystem.
d: Confirm. The system startsoperating according to thesetting.
BS2 [X×]b
a
BS3 [1×]c
BS3 [1×]d
BS3 [1×]
5 Quit mode 2. BS1 [1×]
6.1.7 Mode 1 (and default situation): Monitoringsettings
In mode 1 (and in default situation) you can read out someinformation.
7‑LEDs display – Default situation (H1P OFF)You can read out the following information:
Value / DescriptionH6P Shows the status of low noise operation.
OFF
Unit is currently not operating under low noiserestrictions.
ON
Unit is currently operating under low noiserestrictions.
Low noise operation reduces the sound generated by theunit compared to nominal operating conditions.
Low noise operation can be set in mode 2. There are twomethods to activate low noise operation of the compressorunit and heat exchanger unit.
▪ The first method is to enable an automatic low noiseoperation during night time by field setting. The unit willoperate at the selected low noise level during theselected time frames.
▪ The second method is to enable low noise operationbased on an external input. For this operation an optionalaccessory is required.
H7P Shows the status of power consumption limitation operation.OFF
Unit is currently not operating under powerconsumption limitations.
ON
Unit is currently operating under power consumptionlimitation.
Power consumption limitation reduces the powerconsumption of the unit compared to nominal operatingconditions.
Power consumption limitation can be set in mode 2. Thereare two methods to activate power consumption limitation ofthe compressor unit.
▪ The first method is to enable a forced power consumptionlimitation by field setting. The unit will always operate atthe selected power consumption limitation.
▪ The second method is to enable power consumptionlimitation based on an external input. For this operationan optional accessory is required.
7‑LEDs display – Mode 1 (H1P flashing)You can read out the following information:
Setting( )
Value / Description
[1‑5]
Shows the total number ofconnected units (heat exchangerunit + indoor units).
It can be convenient to check ifthe total number of units whichare installed (heat exchanger unit+ indoor units) match the totalnumber of units which arerecognised by the system. Incase there is a mismatch, it isadvised to check thecommunication wiring pathbetween compressor unit andheat exchanger unit, andbetween compressor unit andindoor units (F1/F2communication line).
6 Configuration
Installation and operation manual
18RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Setting( )
Value / Description
[1‑14]
Shows the latest malfunctioncode.
When the latest malfunctioncodes were reset by accident onan indoor unit user interface, theycan be checked again throughthis monitoring settings.
For the content or reason behindthe malfunction code see"8.1 Solving problems based onerror codes" on page 22, wheremost relevant malfunction codesare explained. Detailedinformation about malfunctioncodes can be consulted in theservice manual of this unit.
To obtain more detailedinformation about the malfunctioncode, press BS2 up to 3 times.
[1‑15]
Shows the 2nd last malfunctioncode.[1‑16]
Shows the 3rd last malfunctioncode.
6.1.8 Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The LEDs give a binary representation of the setting/value number.
Setting
(= binary)
ValueDescription
[2‑8]
Te target temperature during cooling operation. (default)
Auto
6°C7°C8°C9°C
10°C11°C
[2‑9]
Tc target temperature during heating operation. (default)
Auto
41°C43°C46°C
[2‑12]
Enable the low noise function and/or power consumption limitationvia external control adaptor (DTA104A61/62).
If the system needs to be running under low noise operation orunder power consumption limitation conditions when an externalsignal is sent to the unit, this setting should be changed. Thissetting will only be effective when the optional external controladaptor (DTA104A61/62) is installed in the indoor unit.
(default)
Deactivated.
Activated.
[2‑15]
Fan static pressure setting (in heat exchanger unit).
You can set the external static pressure of the heat exchanger unitaccording to the ducting requirements.
30 Pa
(default)
60 Pa
90 Pa120 Pa150 Pa
6 Configuration
Installation and operation manual
19RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Setting
(= binary)
ValueDescription
[2‑20]
Manual additional refrigerant charge.
In order to add the additional refrigerant charge amount in amanual way (without automatic refrigerant charging functionality),following setting should be applied.
(default)
Deactivated.
Activated.
To stop the manual additional refrigerantcharge operation (when the required additionalrefrigerant amount is charged), push BS3. Ifthis function was not aborted by pushing BS3,the unit will stop its operation after 30 minutes.If 30 minutes was not sufficient to add theneeded refrigerant amount, the function can bereactivated by changing the field setting again.
[2‑21]
Refrigerant recovery/vacuuming mode.
In order to achieve a free pathway to reclaim refrigerant out of thesystem or to remove residual substances or to vacuum the systemit is necessary to apply a setting which will open required valves inthe refrigerant circuit so the reclaim of refrigerant or vacuumingprocess can be done properly.
(default)
Deactivated.
Activated.
To stop the refrigerant recovery/vacuumingmode, push BS1. If BS1 is not pushed, thesystem will remain in refrigerant recovery/vacuuming mode.
[2‑22]
Automatic low noise setting and level during night time.
By changing this setting, you activate the automatic low noiseoperation function of the unit and define the level of operation.Depending on the chosen level, the noise level will be lowered.The start and stop moments for this function are defined undersetting [2‑26] and [2‑27].
(default)
Deactivated
Level 1 Level 3<Level 2<Level 1Level 2Level 3
[2‑25]
Low noise operation level via the external control adaptor.
If the system needs to be running under low noise operationconditions when an external signal is sent to the unit, this settingdefines the level of low noise that will be applied.
This setting will only be effective when the optional external controladaptor (DTA104A61/62) is installed and the setting [2‑12] wasactivated.
Level 1 Level 3<Level 2<Level 1
(default)
Level 2
Level 3
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
20h00
(default)
22h00
24h00[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
6h007h00
(default)
8h00
[2‑30]
Power consumption limitation level (step 1) via the external controladaptor (DTA104A61/62).
If the system needs to be running under power consumptionlimitation conditions when an external signal is sent to the unit, thissetting defines the level power consumption limitation that will beapplied for step 1. The level is according to the table.
60%
(default)
70%
80%
[2‑31]
Power consumption limitation level (step 2) via the external controladaptor (DTA104A61/62).
If the system needs to be running under power consumptionlimitation conditions when an external signal is sent to the unit, thissetting defines the level power consumption limitation that will beapplied for step 2. The level is according to the table.
30%
(default)
40%
50%
7 Commissioning
Installation and operation manual
20RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Setting
(= binary)
ValueDescription
[2‑32]
Forced, all time, power consumption limitation operation (noexternal control adaptor is required to perform power consumptionlimitation).
If the system always needs to be running under powerconsumption limitation conditions, this setting activates and definesthe level power consumption limitation that will be appliedcontinuously. The level is according to the table.
(default)
Function not active.
Follows [2‑30] setting.Follows [2‑31] setting.
[2‑41]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
Eco
(default)
Mild
QuickPowerful
[2‑42]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
Eco
(default)
Mild
QuickPowerful
6.1.9 To connect the PC configurator to thecompressor unit
a b
X41A
A1P
23
45
H JS
T
a PCb Cable (EKPCCAB)
X41A ConnectorA1P Compressor unit main PCB
7 CommissioningAfter installation and once the field settings are defined, the installeris obliged to verify correct operation. Therefore a test run must beperformed according to the procedures described below.
7.1 Precautions when commissioningCAUTION
Do not perform the test operation while working on theindoor units or the heat exchanger unit.
When performing the test operation, not only thecompressor unit will operate, but the heat exchanger unitand the connected indoor units as well. Working on anindoor unit or the heat exchanger unit while performing atest operation is dangerous.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
During test operation, the compressor unit, the heat exchanger unitand the indoor units will start up. Make sure that the preparations ofthe heat exchanger unit and all the indoor units are finished (fieldpiping, electrical wiring, air purge, ...). See installation manual of theindoor units for details.
7.2 Checklist before commissioningAfter the installation of the unit, first check the following items. Onceall below checks are fulfilled, the unit must be closed, only then canthe unit be powered up.
You read the complete installation and operationinstructions, as described in the installer and userreference guide.Installation
Check that the unit is properly installed, to avoid abnormalnoises and vibrations when starting up the unit.Field wiring
Be sure that the field wiring has been carried outaccording to the instructions described in the chapter"5.7 Connecting the electrical wiring" on page 13,according to the wiring diagrams and according to theapplicable legislation.Power supply voltage
Check the power supply voltage on the local supply panel.The voltage must correspond to the voltage on theidentification label of the unit.Earth wiring
Be sure that the earth wires have been connectedproperly and that the earth terminals are tightened.Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulationresistance of 2 MΩ or more is attained by applying avoltage of 500 V DC between power terminals and earth.Never use the megatester for the transmission wiring.
7 Commissioning
Installation and operation manual
21RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locallyinstalled protection devices are of the size and typespecified in the chapter "4.3.1 Safety devicerequirements" on page 6. Be sure that neither a fuse nor aprotection device has been bypassed.Internal wiring
Visually check the electrical component box and theinside of the unit on loose connections or damagedelectrical components.Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that theinsulation work is properly executed.Stop valves
Be sure that the stop valves are open on both liquid andgas side.Damaged equipment
Check the inside of the unit on damaged components orsqueezed pipes.Refrigerant leak
Check the inside of the unit on refrigerant leakage. If thereis a refrigerant leak, try to repair the leak. If the repair isunsuccessful, call your local dealer. Do not touch anyrefrigerant which has leaked out from refrigerant pipingconnections. This may result in frostbite.Oil leak
Check the compressor for oil leakage. If there is an oilleak, try to repair the leak. If the repairing is unsuccessful,call your local dealer.Air inlet/outlet
Check that the air inlet and outlet of the unit is notobstructed by paper sheets, cardboard, or any othermaterial.Additional refrigerant charge
The amount of refrigerant to be added to the unit shall bewritten on the included "Added refrigerant" plate andattached to the rear side of the front cover.Installation date and field setting
Be sure to keep record of the installation date on thesticker on the rear of the front panel according toEN60335‑2‑40 and keep record of the contents of the fieldsetting(s).Insulation and air leaks
Make sure the unit is fully insulated and checked for airleaks.
Possible consequence: Condensate water might drip.Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.External static pressure
Make sure the external static pressure is set.
Possible consequence: Insufficient cooling or heating.
7.3 Checklist during commissioningTo perform a test run.
7.3.1 About test runThe procedure below describes the test operation of the completesystem. This operation checks and judges following items:
▪ Check of wrong wiring (communication check with indoor unitsand heat exchanger unit).
▪ Check of the stop valves opening.
▪ Check of wrong piping. Example: Gas or liquid pipes switched.
▪ Judgement of piping length.
Make sure to carry out the system test operation after the firstinstallation. Otherwise, the malfunction code will be displayed onthe user interface and normal operation or individual indoor unit testrun cannot be carried out.
Abnormalities on indoor units cannot be checked for each unitseparately. After the test operation is finished, check the indoor unitsone by one by performing a normal operation using the userinterface. Refer to the indoor unit installation manual for more detailsconcerning the individual test run.
INFORMATION
▪ It may take 10 minutes to achieve a uniform refrigerantstate before the compressor starts.
▪ During the test operation, the refrigerant running soundor the magnetic sound of a solenoid valve may becomeloud and the display indication may change. These arenot malfunctions.
7.3.2 To perform a test run (7-LEDs display)1 Make sure all field settings you want are set; see "6.1 Making
field settings" on page 15.
2 Turn ON the power to the compressor unit, heat exchanger unit,and the connected indoor units.
NOTICE
Be sure to turn on the power 6 hours before operation inorder to have power running to the crankcase heater andto protect the compressor.
3 Make sure the default (idle) situation is existing (H1P is OFF);see "6.1.4 To access mode 1 or 2" on page 16. Push BS4 for 5seconds or more. The unit will start test operation.
Result: The test operation is automatically carried out, thecompressor unit H2P flashes and the indication "Test operation"and "Under centralised control" will display on the user interfaceof indoor units.
Steps during the automatic system test run procedure:
Step DescriptionControl before start up (pressureequalisation)Cooling start up controlCooling stable conditionCommunication checkStop valve checkPipe length checkPump down operationUnit stop
INFORMATION
During the test operation, it is not possible to stop the unitoperation from a user interface. To abort the operation,press BS3. The unit will stop after ±30 seconds.
4 Check the test operation results on the compressor unit 7‑LEDsdisplay.
8 Troubleshooting
Installation and operation manual
22RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Completion DescriptionNormalcompletionAbnormalcompletion Refer to "7.3.3 Correcting after abnormal
completion of the test run" on page 22 to takeactions for correcting the abnormality. Whenthe test operation is fully completed, normaloperation will be possible after 5 minutes.
7.3.3 Correcting after abnormal completion ofthe test run
The test operation is only completed if there is no malfunction codedisplayed. In case of a displayed malfunction code, performcorrecting actions as explained in the malfunction code table. Carryout the test operation again and confirm that the abnormality isproperly corrected.
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
INFORMATION
Refer to the installation manual of the indoor unit for otherdetailed malfunction codes related to indoor units.
7.3.4 Operating the unitOnce the units are installed and test operation of compressor unit,heat exchanger unit and indoor units is finished, the operation of thesystem can start.
For operating the indoor unit, the user interface of the indoor unitshould be switched ON. Refer to the indoor unit operation manual formore details.
8 Troubleshooting
8.1 Solving problems based on errorcodes
In case of a displayed malfunction code, perform correcting actionsas explained in the malfunction code table.
After correcting the abnormality, press BS3 to reset the malfunctioncode and retry operation.
INFORMATION
If a malfunction occurs, the error code is displayed on theuser interface of the indoor unit.
8.1.1 Error codes: Overview
Main code Cause Solution▪ Heat exchanger fan malfunction.
▪ Drain pump feedback contact is open.
In the heat exchanger unit:
▪ Check connection on PCB: A1P (X15A)
▪ Check connection on terminal block (X2M)
▪ Check the fan connectors.▪ The stop valves of the compressor unit are left closed.
▪ Refrigerant overcharge
▪ Open the stop valves on both the gas and liquid side.
▪ Recalculate the required amount of refrigerant from thepiping length and correct the refrigerant charge level byrecovering any excessive refrigerant with a refrigerantrecovery machine.
▪ The stop valves of the compressor unit are left closed.
▪ Insufficient refrigerant
▪ Open the stop valves on both the gas and liquid side.
▪ Check if the additional refrigerant charge has beenfinished correctly. Recalculate the required amount ofrefrigerant from the piping length and add an adequateamount of refrigerant.
Electronic expansion valve malfunction
Heat exchanger unit: (Y1E) - A1P (X7A)
Compressor unit: (Y1E) - A1P (X22A)
Check connection on PCB or actuator.
▪ The stop valves of the compressor unit are left closed.
▪ Insufficient refrigerant
▪ Open the stop valves on both the gas and liquid side.
▪ Check if the additional refrigerant charge has beenfinished correctly. Recalculate the required amount ofrefrigerant from the piping length and add an adequateamount of refrigerant.
Refrigerant overcharge Recalculate the required amount of refrigerant from thepiping length and correct the refrigerant charge level byrecovering any excessive refrigerant with a refrigerantrecovery machine.
Ambient temperature sensor malfunction
Heat exchanger unit: (R1T) - A1P (X16A)
Check connection on PCB or actuator.
Discharge temperature sensor malfunction: open circuit /short circuit
Compressor unit: (R2T) - A1P (X12A)
Check connection on PCB or actuator.
8 Troubleshooting
Installation and operation manual
23RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Main code Cause SolutionHeat exchanger gas sensor malfunction
Heat exchanger unit: (R2T) - A1P (X17A)
Check connection on PCB or actuator.
Suction temperature sensor malfunction
Compressor unit: (R3T) - A1P (X12A)
Compressor unit: (R5T) - A1P (X12A)
Check connection on PCB or actuator.
Coil temperature sensor malfunction
Heat exchanger unit: (R3T) - A1P (X18A)
Check connection on PCB or actuator.
Liquid temperature sensor (after subcool HE) malfunction
Compressor unit: (R7T) - A1P (X13A)
Check connection on PCB or actuator.
Gas temperature sensor (after subcool HE) malfunction
Compressor unit: (R4T) - A1P (X12A)
Check connection on PCB or actuator.
High pressure sensor malfunction: open circuit / short circuit
Compressor unit: (BIPH) - A1P (X17A)
Check connection on PCB or actuator.
Low pressure sensor malfunction: open circuit / short circuit
Compressor unit: (BIPL) - A1P (X18A)
Check connection on PCB or actuator.
Transmission compressor unit - inverter: INV1 transmissiontrouble
Check connection.
INV1 unbalanced power supply voltage Check if power supply is within range.Heat exchanger unit capacity setting malfunction. Check the type of heat exchanger unit. If necessary, replace
the heat exchanger unit.Insufficient supply voltage Check if the supply voltage is supplied properly.Malfunction code: System test run not yet executed (systemoperation not possible)
Execute system test run.
▪ No power is supplied to the compressor unit.
▪ Transmission wiring malfunction
▪ Check if all units are powered on.
▪ Check the transmission wiring.▪ System mismatch. Wrong type of indoor units combined
(R410A, R407C, RA, etc). Indoor unit malfunction
▪ Heat exchanger unit malfunction
▪ Check if other indoor units have malfunction and confirmindoor unit mix is allowed.
▪ Check the transmission wiring to the heat exchanger unit.▪ Improper type of indoor units are connected.
▪ Mismatch of compressor unit and heat exchanger unit.
▪ Check the type of indoor units that are currentlyconnected. If they are not proper, replace them withproper ones.
▪ Check if the compressor unit and heat exchanger unit arecompatible.
▪ The stop valves of the compressor unit are left closed.
▪ The piping and wiring of the specified indoor unit or heatexchanger unit are not connected correctly to thecompressor unit.
▪ Open the stop valves on both the gas and liquid side.
▪ Confirm that the piping and wiring of the specified indoorunit or heat exchanger unit are connected correctly to thecompressor unit.
9 Technical data
Installation and operation manual
24RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
9 Technical dataLatest information can be found in the technical engineering data.
9.1 Piping diagram: Compressor unit and heat exchanger unit
R2T
R3T
R1T
M1FM2F
Y1E
Y3E
R2T
M1C
R3TR7T
R4T
Y1S
S1NPL
S1PH
S1NPH
A B
R5T
f fc
bf
g
a
df h
f i
jk
e
l
3D098825-1A Heat exchanger unitB Compressor unita Stop valve (gas) (circuit 2: to indoor units)b Stop valve (liquid) (circuit 2: to indoor units)c Stop valve (liquid) (circuit 1: to heat exchanger unit)d Stop valve (gas) (circuit 1: to heat exchanger unit)e Service port (refrigerant charge)f Filter (5×)g Subcool heat exchangerh Pressure regulating valvei Capillary tubej Accumulator
k Compressor accumulatorl Heat exchanger
M1C CompressorM1F-M2F Fan motor
R1T (A) Thermistor (air)R2T (A) Thermistor (gas)R3T (A) Thermistor (coil)R2T (B) Thermistor (discharge)R3T (B) Thermistor (suction accumulator)R4T (B) Thermistor (subcool heat exchanger gas)R5T (B) Thermistor (suction compressor)R7T (B) Thermistor (liquid)S1NPH High pressure sensorS1NPL Low pressure sensor
S1PH High pressure switchY1E, Y3E Electronic expansion valve
Y1S Solenoid valve (4‑way valve)HeatingCooling
9.2 Wiring diagram: Compressor unitThe wiring diagram is delivered with the unit, located on the switchbox cover.
Symbols:
X1M Main terminal
Earth wiring
15 Wire number 15
Field wire
Field cable
**/12.2 Connection ** continues on page 12 column 2
10 About the system
Installation and operation manual
25RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
1 Several wiring possibilities
Option
Not mounted in switch box
Wiring depending on model
PCB
Legend for wiring diagram RKXYQ5:
A1P Printed circuit board (main)
A2P Printed circuit board (inverter)
BS* Push button (A1P)
C* Capacitor (A2P)
DS1 DIP switch (A1P)
F1U, F2U Fuse (T 31.5 A / 250 V) (A1P)
F3U, F5U Fuse (T 6.3 A / 250 V) (A1P)
H*P LED (service monitor orange) (A1P)
HAP Running LED (service monitor green) (A*P)
K1M Magnetic contactor (A2P)
K1R Magnetic relay (A*P)
L1R Reactor
M1C Motor (compressor)
M1F Motor (fan)
PS Switching power supply (A2P)
Q1DI Earth leakage circuit breaker (field supply)
R* Resistor (A2P)
R2T Thermistor (discharge)
R3T Thermistor (suction accumulator)
R4T Thermistor (subcool heat exchanger gas)
R5T Thermistor (suction compressor)
R7T Thermistor (liquid)
R10T Thermistor (fin)
S1NPL Low pressure sensor
S1NPH High pressure sensor
S1PH High pressure switch
S*S Cool/heat selector switch (optional)
V1R IGBT power module (A2P)
V2R Diode module (A2P)
X1M Terminal strip (power supply)
X2M Terminal strip (transmission wiring)
X*Y Connector
Y3E Electronic expansion valve
Y1S Solenoid valve (4‑way valve)
Z*C Noise filter (ferrite core)
Z*F Noise filter (A1P)
For the user
10 About the systemThe VRV IV heat pump for indoor installation can be used forheating/cooling applications.
NOTICE
Do not use the air conditioner for other purposes. In orderto avoid any quality deterioration, do not use the unit forcooling precision instruments, food, plants, animals orworks of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for futuresystem extensions) is available in technical engineeringdata and should be consulted. Contact your installer toreceive more information and professional advice.
10.1 System layout
d d
c c
a
b
VRV DX VRV DX VRV DX EKEXV
AHU
d d
1 2
1 In case of VRV DX indoor units2 In case of VRV DX indoor units combined with an air
handling unita Heat exchanger unitb Compressor unitc Refrigerant pipingd User interface (dedicated depending on indoor unit type)
VRV DX VRV direct expansion (DX) indoor unitEKEXV Expansion valve kit
AHU Air handling unit
11 User interfaceCAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside aredangerous to touch and appliance problems may happen.For checking and adjusting the internal parts, contact yourdealer.
This operation manual will give a non-exhaustive overview of themain functions of the system.
Detailed information on required actions to achieve certain functionscan be found in the dedicated installation and operation manual ofthe indoor unit.
Refer to the operation manual of the installed user interface.
12 Operation
12.1 Operation rangeUse the system in the following temperature and humidity ranges forsafe and effective operation.
12 Operation
Installation and operation manual
26RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Specification RKXYQ5+RDXYQ5Outside ambientdesign temperature
Heating –20~15.5°C WBCooling –5~46°C DB
Ambient design temperature of compressorunit and heat exchanger unit
5~35°C DB(26°C WB)
Indoor humidity ≤80%(a)
(a) To avoid condensation and water dripping out of the unit. Ifthe temperature or the humidity is beyond these conditions,safety devices may be put in action and the air conditionermay not operate.
Special operation ranges are valid in case of using AHU. They canbe found in the installation/operation manual of the dedicated unit.Latest information can be found in the technical engineering data.
12.2 Operating the system
12.2.1 About operating the system▪ Operation procedure varies according to the combination of
compressor unit, heat exchanger unit, and user interface.
▪ To protect the unit, turn on the main power switch 6 hours beforeoperation.
▪ If the main power supply is turned off during operation, operationwill restart automatically after the power turns back on again.
▪ When stopping the unit, the unit might still operate for a fewminutes. This is not a malfunction.
12.2.2 About cooling, heating, fan only, andautomatic operation
▪ Changeover cannot be made with a user interface whose displayshows "change-over under centralised control" (refer toinstallation and operation manual of the user interface).
▪ When the display "change-over under centralised control"flashes, refer to "12.5.1 About setting the master userinterface" on page 27.
▪ The fan may keep on running for about 1 minute after the heatingoperation stops.
▪ The air flow rate may adjust itself depending on the roomtemperature or the fan may stop immediately. This is not amalfunction.
12.2.3 About the heating operationIt may take longer to reach the set temperature for general heatingoperation than for cooling operation.
The following operation is performed in order to prevent the heatingcapacity from dropping or cold air from blowing.
Defrost operationIn heating operation, freezing of the heat exchanger unit's air cooledcoil increases over time, restricting the energy transfer to the heatexchanger unit's coil. Heating capability decreases and the systemneeds to go into defrost operation to be able to deliver enough heatto the indoor units:
The indoor unit will stop fan operation, the refrigerant cycle willreverse and energy from inside the building will be used to defrostthe heat exchanger unit coil.
The indoor unit will indicate defrost operation on the displays.
During defrost operation, ice melts and possibly evaporates.Possible consequence: Mist might be visible during or directly afterdefrost operation. This is not a malfunction.
Hot startIn order to prevent cold air from blowing out of an indoor unit at thestart of heating operation, the indoor fan is automatically stopped.The display of the user interface shows . It may take sometime before the fan starts. This is not a malfunction.
12.2.4 To operate the system (WITHOUT cool/heat changeover remote control switch)
1 Press the operation mode selector button on the user interfaceseveral times and select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system startsoperating.
12.2.5 To operate the system (WITH cool/heatchangeover remote control switch)
Overview of the changeover remote control switch
a
b
a FAN ONLY/AIR CONDITIONINGSELECTOR SWITCH
Set the switch to for fan onlyoperation or to for heating orcooling operation.
b COOL/HEAT CHANGEOVER SWITCH
Set the switch to for cooling or to for heating
To start1 Select operation mode with the cool/heat changeover switch as
follows:
Cooling operation Heating operation Fan only operation
1
1
1
1 1
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system startsoperating.
To stop3 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stopsoperating.
NOTICE
Do not turn off power immediately after the unit stops, butwait for at least 5 minutes.
12 Operation
Installation and operation manual
27RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
To adjustFor programming temperature, fan speed and air flow direction referto the operation manual of the user interface.
12.3 Using the dry program
12.3.1 About the dry program▪ The function of this program is to decrease the humidity in your
room with minimal temperature decrease (minimal room cooling).
▪ The micro computer automatically determines temperature andfan speed (cannot be set by the user interface).
▪ The system does not go into operation if the room temperature islow (<20°C).
12.3.2 To use the dry program (WITHOUT cool/heat changeover remote control switch)
To start1 Press the operation mode selector button on the user interface
several times and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system startsoperating.
3 Press the air flow direction adjust button (only for double-flow,multi-flow, corner, ceiling-suspended and wall-mounted). Referto "12.4 Adjusting the air flow direction" on page 27 for details.
To stop4 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stopsoperating.
NOTICE
Do not turn off power immediately after the unit stops, butwait for at least 5 minutes.
12.3.3 To use the dry program (WITH cool/heatchangeover remote control switch)
To start1 Select cooling operation mode with the cool/heat changeover
remote control switch.
1
1
2 Press the operation mode selector button on the user interfaceseveral times and select (program dry operation).
3 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system startsoperating.
4 Press the air flow direction adjust button (only for double-flow,multi-flow, corner, ceiling-suspended and wall-mounted). Referto "12.4 Adjusting the air flow direction" on page 27 for details.
To stop5 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stopsoperating.
NOTICE
Do not turn off power immediately after the unit stops, butwait for at least 5 minutes.
12.4 Adjusting the air flow directionRefer to the operation manual of the user interface.
12.4.1 About the air flow flap
Double flow+multi-flow units
Corner units
Ceiling suspended units
Wall-mounted units
For the following conditions, a micro computer controls the air flowdirection which may be different from the display.
Cooling Heating▪ When the room temperature is
lower than the settemperature.
▪ When starting operation.
▪ When the room temperature ishigher than the settemperature.
▪ At defrost operation.▪ When operating continuously at horizontal air flow direction.
▪ When continuous operation with downward air flow is performedat the time of cooling with a ceiling-suspended or a wall-mountedunit, the micro computer may control the flow direction, and thenthe user interface indication will also change.
The air flow direction can be adjusted in one of the following ways:
▪ The air flow flap itself adjusts its position.
▪ The air flow direction can be fixed by the user.
▪ Automatic and desired position .
WARNING
Never touch the air outlet or the horizontal blades while theswing flap is in operation. Fingers may become caught orthe unit may break down.
NOTICE
▪ The movable limit of the flap is changeable. Contactyour dealer for details. (only for double-flow, multi-flow,corner, ceiling-suspended and wall-mounted).
▪ Avoid operating in the horizontal direction . It maycause dew or dust to settle on the ceiling or flap.
12.5 Setting the master user interface
12.5.1 About setting the master user interface
d d
c c
a
b
VRV DX VRV DX VRV DX EKEXV
AHU
d d
1 2
1 In case of VRV DX indoor units
13 Maintenance and service
Installation and operation manual
28RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
2 In case of VRV DX indoor units combined with an airhandling unit
a Heat exchanger unitb Compressor unitc Refrigerant pipingd User interface (dedicated depending on indoor unit type)
VRV DX VRV direct expansion (DX) indoor unitEKEXV Expansion valve kit
AHU Air handling unit
When the system is installed as shown in the figure above, it isnecessary to designate one of the user interfaces as the master userinterface.
The displays of slave user interfaces show (change-overunder centralised control) and slave user interfaces automaticallyfollow the operation mode directed by the master user interface.
Only the master user interface can select heating or cooling mode.
12.5.2 To designate the master user interface(VRV DX)
1 Press the operation mode selector button of the current masteruser interface for 4 seconds. In case this procedure was not yetperformed, the procedure can be executed on the first userinterface operated.
Result: The display showing (change-over undercentralised control) of all slave user interfaces connected to thesame compressor unit flashes.
2 Press the operation mode selector button of the controller thatyou wish to designate as the master user interface.
Result: Designation is completed. This user interface isdesignated as the master user interface and the displayshowing (change-over under centralised control)vanishes. The displays of other user interfaces show (change-over under centralised control).
13 Maintenance and serviceNOTICE
Never inspect or service the unit by yourself. Ask aqualified service person to perform this work.
WARNING
Never replace a fuse with a fuse of a wrong ampere ratingsor other wires when a fuse blows out. Use of wire orcopper wire may cause the unit to break down or cause afire.
CAUTION
Do not insert fingers, rods or other objects into the air inletor outlet. Do not remove the fan guard. When the fan isrotating at high speed, it will cause injury.
CAUTION
After a long use, check the unit stand and fitting fordamage. If damaged, the unit may fall and result in injury.
NOTICE
Do not wipe the controller operation panel with benzine,thinner, chemical dust cloth, etc. The panel may getdiscoloured or the coating peeled off. If it is heavily dirty,soak a cloth in water-diluted neutral detergent, squeeze itwell and wipe the panel clean. Wipe it with another drycloth.
13.1 After-sales service and warranty
13.1.1 Warranty period▪ This product includes a warranty card that was filled in by the
dealer at the time of installation. The completed card has to bechecked by the customer and stored carefully.
▪ If repairs to the air conditioner are necessary within the warrantyperiod, contact your dealer and keep the warranty card at hand.
13.1.2 Recommended maintenance andinspection
Since dust collects when using the unit for several years,performance of the unit will deteriorate to some extent. As takingapart and cleaning interiors of units requires technical expertise andin order to ensure the best possible maintenance of your units, werecommend to enter into a maintenance and inspection contract ontop of normal maintenance activities. Our network of dealers hasaccess to a permanent stock of essential components in order tokeep your air conditioner in operation as long as possible. Contactyour dealer for more information.
When asking your dealer for an intervention, always state:▪ The complete model name of the air conditioner.
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
WARNING
▪ Do not modify, disassemble, remove, reinstall or repairthe unit yourself as incorrect dismantling or installationmay cause an electric shock or fire. Contact yourdealer.
▪ In case of accidental refrigerant leaks, make sure thereare no naked flames. The refrigerant itself is entirelysafe, non-toxic and non-combustible, but it willgenerate toxic gas when it accidentally leaks into aroom where combustible air from fan heaters, gascookers, etc. is present. Always have qualified servicepersonnel confirm that the point of leakage has beenrepaired or corrected before resuming operation.
14 TroubleshootingIf one of the following malfunctions occur, take the measures shownbelow and contact your dealer.
WARNING
Stop operation and shut off the power if anythingunusual occurs (burning smells etc.).
Leaving the unit running under such circumstances maycause breakage, electric shock or fire. Contact your dealer.
The system must be repaired by a qualified service person:
Malfunction MeasureIf a safety device such as a fuse, abreaker or an earth leakage breakerfrequently actuates or the ON/OFFswitch does not properly work.
Turn off the main powerswitch.
If water leaks from the unit. Stop the operation.The operation switch does not workwell.
Turn off the power.
14 Troubleshooting
Installation and operation manual
29RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Malfunction MeasureIf the user interface display indicates theunit number, the operation lamp flashesand the malfunction code appears.
Notify your installer andreport the malfunctioncode.
If the system does not properly operate except for the abovementioned cases and none of the above mentioned malfunctions isevident, investigate the system according to the followingprocedures.
Malfunction MeasureIf the system does notoperate at all.
▪ Check if there is no power failure. Waituntil power is restored. If power failureoccurs during operation, the systemautomatically restarts immediately afterthe power supply is recovered.
▪ Check if no fuse has blown or breakerhas worked. Change the fuse or reset thebreaker if necessary.
If the system goes intofan only operation, butas soon as it goes intoheating or coolingoperation, the systemstops.
▪ Check if air inlet or outlet of heatexchanger unit or indoor unit is notblocked by obstacles. Remove anyobstacle and make it well-ventilated.
▪ Check if the user interface display shows (time to clean the air filter). (Refer to
"13 Maintenance and service" onpage 28 and "Maintenance" in the indoorunit manual.)
The system operatesbut cooling or heatingis insufficient.
▪ Check if air inlet or outlet of heatexchanger unit or indoor unit is notblocked by obstacles. Remove anyobstacle and make it well-ventilated.
▪ Check if the air filter is not clogged (referto "Maintenance" in the indoor unitmanual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your userinterface.
▪ Check for open doors or windows. Shutdoors and windows to prevent wind fromcoming in.
▪ Check if there are too many occupants inthe room during cooling operation. Checkif the heat source of the room isexcessive.
▪ Check if direct sunlight enters the room.Use curtains or blinds.
▪ Check if the air flow angle is proper.
If after checking all above items, it is impossible to fix the problemyourself, contact your installer and state the symptoms, the completemodel name of the air conditioner (with manufacturing number ifpossible) and the installation date (possibly listed on the warrantycard).
14.1 Error codes: OverviewIn case a malfunction code appears on the indoor unit user interfacedisplay, contact your installer and inform the malfunction code, theunit type, and serial number (you can find this information on thenameplate of the unit).
For your reference, a list with malfunction codes is provided. Youcan, depending on the level of the malfunction code, reset the codeby pushing the ON/OFF button. If not, ask your installer for advice.
Main code ContentsExternal protection device was activatedEEPROM failure (indoor)Drain system malfunction (indoor)Fan motor malfunction (indoor)Swing flap motor malfunction (indoor)Expansion valve malfunction (indoor)Drain malfunction (indoor unit)Filter dust chamber malfunction (indoor)Capacity setting malfunction (indoor)Transmission malfunction between main PCB and subPCB (indoor)Heat exchanger thermistor malfunction (indoor; liquid)Heat exchanger thermistor malfunction (indoor; gas)Suction air thermistor malfunction (indoor)Discharge air thermistor malfunction (indoor)Movement detector or floor temperature sensormalfunction (indoor)User interface thermistor malfunction (indoor)Fan or drain pump malfunction (heat exchanger unit)PCB malfunction (compressor unit)Current leakage detector was activated (compressorunit)High pressure switch was activatedLow pressure malfunction (compressor unit)Compressor lock detection (compressor unit)Electronic expansion valve malfunction (compressorunit or heat exchanger unit)Discharge temperature malfunction (compressor unit)Abnormal suction temperature (compressor unit)Refrigerant overcharge detectionHigh pressure switch malfunctionLow pressure switch malfunctionAmbient temperature sensor malfunction (heatexchanger unit)Pressure sensor malfunctionCurrent sensor malfunctionDischarge temperature sensor malfunction(compressor unit)Heat exchanger gas temperature sensor malfunction(heat exchanger unit)Suction temperature sensor malfunction (compressorunit)De-icing temperature sensor malfunction (heatexchanger unit)Liquid temperature sensor (after subcool HE)malfunction (compressor unit)Gas temperature sensor (after subcool HE)malfunction (compressor unit)High pressure sensor malfunction (BIPH)Low pressure sensor malfunction (BIPL)INV PCB abnormalFin temperature abnormalInverter PCB faultyCompressor over current detectedCompressor lock (startup)Transmission compressor unit - inverter: INVtransmission trouble
14 Troubleshooting
Installation and operation manual
30RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation4P408443-1 – 2015.07
Main code ContentsINV unbalanced power supply voltageFin thermistor malfunctionHeat exchanger unit capacity setting malfunction.Abnormal low pressure drop, faulty expansion valveReversed power supply phase malfunctionINV voltage power shortageSystem test run not yet executedFaulty wiring indoor/heat exchanger unit/compressorunitAbnormal user interface - indoor communicationAbnormal main-sub user interface communicationSystem mismatch. Wrong type of indoor unitscombined. Indoor unit malfunction. Heat exchangerunit malfunction.Connection malfunction over indoor units or typemismatch (wrong type of indoor units or heatexchanger unit)Centralised address duplicationMalfunction in communication centralised controldevice - indoor unitAuto address malfunction (inconsistency)Auto address malfunction (inconsistency)
14.2 Symptoms that are not airconditioner troubles
Following symptoms are not air conditioner troubles:
14.2.1 Symptom: The system does not operate▪ The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamplights, the system is in normal condition. To prevent overloading ofthe compressor motor, the air conditioner starts 5 minutes after itis turned ON again in case it was turned OFF just before. Thesame starting delay occurs after the operation mode selectorbutton was used.
▪ If "Under Centralized Control" is displayed on the user interface,pressing the operation button causes the display to blink for a fewseconds. The blinking display indicates that the user interfacecannot be used.
▪ The system does not start immediately after the power supply isturned on. Wait one minute until the micro computer is preparedfor operation.
14.2.2 Symptom: Cool/Heat cannot be changedover
▪ When the display shows (change-over under centralizedcontrol), it shows that this is a slave user interface.
▪ When the cool/heat changeover remote control switch is installedand the display shows (change-over under centralizedcontrol), this is because cool/heat changeover is controlled by thecool/ heat changeover remote control switch. Ask your dealerwhere the remote control switch is installed.
14.2.3 Symptom: Fan operation is possible, butcooling and heating do not work
Immediately after the power is turned on. The micro computer isgetting ready to operate and is performing a communication checkwith all indoor units. Please wait 12 minutes (max.) till this process isfinished.
14.2.4 Symptom: The fan strength does notcorrespond to the setting
The fan speed does not change even if the fan speed adjustmentbutton in pressed. During heating operation, when the roomtemperature reaches the set temperature, the compressor unit goesoff and the indoor unit changes to whisper fan speed. This is toprevent cold air blowing directly on occupants of the room. The fanspeed will not change even when another indoor unit is in heatingoperation, if the button is pressed.
14.2.5 Symptom: The fan direction does notcorrespond to the setting
The fan direction does not correspond with the user interfacedisplay. The fan direction does not swing. This is because the unit isbeing controlled by the micro computer.
14.2.6 Symptom: White mist comes out of a unit(Indoor unit)
▪ When humidity is high during cooling operation. If the interior of anindoor unit is extremely contaminated, the temperature distributioninside a room becomes uneven. It is necessary to clean theinterior of the indoor unit. Ask your dealer for details on cleaningthe unit. This operation requires a qualified service person.
▪ Immediately after the cooling operation stops and if the roomtemperature and humidity are low. This is because warmrefrigerant gas flows back into the indoor unit and generatessteam.
14.2.7 Symptom: White mist comes out of a unit(Indoor unit, heat exchanger unit)
When the system is changed over to heating operation after defrostoperation. Moisture generated by defrost becomes steam and isexhausted.
14.2.8 Symptom: The user interface displayreads "U4" or "U5" and stops, but thenrestarts after a few minutes
This is because the user interface is intercepting noise from electricappliances other than the air conditioner. The noise preventscommunication between the units, causing them to stop. Operationautomatically restarts when the noise ceases.
14.2.9 Symptom: Noise of air conditioners(Indoor unit, heat exchanger unit)
▪ A "zeen" sound is heard immediately after the power supply isturned on. The electronic expansion valve inside an indoor unitstarts working and makes the noise. Its volume will reduce inabout one minute.
▪ A continuous low "shah" sound is heard when the system is incooling operation or at a stop. When the drain pump (optionalaccessories) is in operation, this noise is heard.
▪ A "pishi-pishi" squeaking sound is heard when the system stopsafter heating operation. Expansion and contraction of plastic partscaused by temperature change make this noise.
▪ A low "sah", "choro-choro" sound is heard while the indoor unit isstopped. When another indoor unit is in operation, this noise isheard. In order to prevent oil and refrigerant from remaining in thesystem, a small amount of refrigerant is kept flowing.
15 Relocation
Installation and operation manual
31RKXYQ5T7Y1BVRV IV compressor unit for indoor installation4P408443-1 – 2015.07
14.2.10 Symptom: Noise of air conditioners(Indoor unit, compressor unit, heatexchanger unit)
▪ A continuous low hissing sound is heard when the system is incooling or defrost operation. This is the sound of refrigerant gasflowing through the compressor unit, heat exchanger unit andindoor units.
▪ A hissing sound which is heard at the start or immediately afterstopping operation or defrost operation. This is the noise ofrefrigerant caused by flow stop or flow change.
14.2.11 Symptom: Noise of air conditioners(compressor unit, heat exchanger unit)
When the tone of operating noise changes. This noise is caused bythe change of frequency from the compressor or the fans.
14.2.12 Symptom: Dust comes out of the heatexchanger unit
When the unit is used for the first time in a long time. This isbecause dust has gotten into the heat exchanger unit.
14.2.13 Symptom: The units can give off odoursThe unit can absorb the smell of rooms, furniture, cigarettes, etc.,and then emit it again.
14.2.14 Symptom: The heat exchanger unit fandoes not spin
During operation. The speed of the fan is controlled in order tooptimise product operation.
14.2.15 Symptom: The display shows "88"This is the case immediately after the main power supply switch isturned on and means that the user interface is in normal condition.This continues for one minute.
14.2.16 Symptom: The compressor in thecompressor unit does not stop after ashort heating operation
This is to prevent refrigerant from remaining in the compressor. Theunit will stop after 5 to 10 minutes.
14.2.17 Symptom: The inside of an compressorunit is warm even when the unit hasstopped
This is because the crankcase heater is warming the compressor sothat the compressor can start smoothly.
14.2.18 Symptom: Hot air can be felt when theindoor unit is stopped
Several different indoor units are being run on the same system.When another unit is running, some refrigerant will still flow throughthe unit.
15 RelocationContact your dealer for removing and reinstalling the total unit.Moving units requires technical expertise.
16 DisposalThis unit uses hydrofluorocarbon. Contact your dealer whendiscarding this unit. It is required by law to collect, transport anddiscard the refrigerant in accordance with the "hydrofluorocarboncollection and destruction" regulations.
4P408443-1 0000000L
4P408443-1 2015.07
Cop
yrig
ht 2
015
Dai
kin