INSTALLATION GUIDE FOR QJ SOLAR
PHOTOVOLTAIC MODULE
Contents
●Purpose of this guide
General
Safety precaution for installing a solar photovoltaic system
●Product Identification
●Mechanical Installation
Selecting the location
Selecting the proper support frame
Ground mount
Roof mount
Pole mount
General Installation
●Electrical Installation
Grid-connected electrical system
Grounding
General installation
●Commission and Maintenance
Blocking diodes and bypass diodes
Testing, commissioning and troubleshooting
Maintenance
Testing and replacing bypass diodes
●Disclaimer of Liability
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
2
QJ
Purpose of this guide
This guide contains information regarding the installation and safe handling of OVIERA
SOLAR photovoltaic module (hereafter is referred to as "module "). QJ SOLAR hereafter
is referred to as "QJ".
All instructions should be read and understood before attempting to install. If there are any
question, please contact our sales department for further explanation. The installer should
conform to all the safety precautions listed in this guide when installing the module. Local
codes should also be followed in such installations.
Before installing a solar photovoltaic system,the installer should become familiar with the
mechanical and electrical requirement for such a system. Keep this guide in a safe place for
future reference (care and maintenance) and in case of sale or disposal of the module at the
end of its useful life.
General
●Installing solar photovoltaic systems may require specialized skills and knowledge.
Installation should be performed only by qualified person.
●The installer should assume the risk or all injury that might occur during installation,
including without limitation, the risk of electric shock.
●One individual module may generate DC voltages greater than 30 volts when exposed to
direct sunlight. Contact with a DC voltage of 30V or more is potentially hazardous.
●When disconnecting wires connected to a photovoltaic module that is exposed to
sunlight, and electric arc may result. Such arcs may cause burns, may start fires and may
otherwise create problems. Therefore, be extremely careful!
●Photovoltaic solar modules change light energy to direct-current electrical energy. They
are designed for outdoor use. Modules may be ground mounted, mounted on rooftops,
vehicles or boats. Proper design of support structures is the responsibility of the system
designer and installer. Proper use of mounting holes is suggested in a following
paragraph.
●Do not attempt to disassemble the module, and do not remove any attached nameplates
or components.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
3
QJ
●Do not apply paint or adhesive to module top surface.
●Artificially concentrated sunlight shall not be directed on the module or panel.
●When installing the system, abide with all local, regional and national statutory
regulations. Obtain a building permit where necessary. Abide with any local and national
regulations when mounting on vehicles or boats.
Safety precaution for installing a solar photovoltaic system
●Solar modules produce electrical energy when light shines on their front surface. The DC
voltage may exceed 30V. If modules are connected in series, the total voltage is equal to the
sum of the individual module voltages. If modules are connected in parallel, the total
current is equal to the sum of individual module currents.
●Keep children well away from the system while transporting and installing mechanical
and electrical components.
●Completely cover the module with an opaque material during installation to keep
electricity from being generated.
●Do not wear metallic rings, watchbands, ear, nose, lip rings or other metallic devices
while installing or troubleshooting photovoltaic systems.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
4
QJ
●Use only insulated tools that are approved for working on electrical installations.
●Abide with the safety regulations for all other components used in the system, including
wiring and cables, connectors, charging regulators, inverters, storage batteries and
rechargeable batteries, etc.
●Use only equipment, connectors, wiring and support frames suitable for use in a solar
electric systems. Always use the same type of module within a particular photovoltaic
system.
●The electrical characteristics are within ±3% of the indicated values of Pmax under
standard test conditions (irradiance of 100mW/cm2, AM 1.5 spectrums, and a cell
temperature of 25℃{77ºF})
●Under normal conditions, a photovoltaic module is likely to experience conditions that
produce more current and/or voltage than reported at standard test conditions. Accordingly,
the values of ISC and VOC marked on this module should be multiplied by a factor of 1,25
when determining component voltage ratings, conductor current ratings, fuse sizes, and
size of controls connected to the PV output."
●Refer to Section 690-8 of the National Electrical Code for an additional multiplying
factor of 125 percent (80 percent derating) which may be applicable.
Product identification
Each module has three labels on its rear and front sides providing the following
information:
●Nameplate: describes the product type; rated power, rated current, rated voltage, open
circuit voltage, short circuit current, all as measured under standard test conditions;
dimension etc., the maximum system voltage for TUV listed modules is 1000 volts DC and
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
5
QJ
is shown on the nameplate.
●Barcode: each individual module has a unique serial number. There are two barcodes on
module. One is permanently attached to the interior of the module visible when viewing
from the front of the module. This barcode is inserted at the beginning of laminating.
●Do not remove any label. If the label is removed, the product warranty will no longer be
honored by QJ.
Mechanical Installation
● Selecting the location
⊙Select a suitable location for installation of the module.
⊙The module should be facing true south in northern latitudes and true north in southern
latitudes for best power production.
⊙For detailed information on the best elevation tilt angle for the installation, refer to
standard solar photovoltaic installation guides or a reputable solar installer or systems
integrator.
⊙The module should not be shaded at any time of the day.
⊙Do not use module near equipment or in locacollected.
●Selecting the proper support frame
⊙Always observe the instructions and safety precautions included with the support frame
to be used with the module.
⊙No attempt must be made to drill holes in the glass surface of the module. To do so will
void the warranty.
⊙Do not drill additional mounting holes in the frame of the module. Doing so will void the
warranty.
⊙Modules must be securely attached to the mounting structure using four mounting points
for normal installation. If additional wind or snowloads are anticipated for this installation,
additional mounting points are also used. Refer to the drawing, below, load calculations are
left to the system designer or installer.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
6
QJ
⊙The support module mounting structure must be made of durable, corrosion-resistant
and UV-resistant material..
●Ground mount
⊙Select the height of the mounting system to prevent the lowest edge of the module from
being covered by snow for a long time in winter in areas that experience heavy snowfalls.
In addition, assure the lowest portion of the module is placed high enough so that it is not
shaded by plants or trees or damaged by sand and stone driven by wind.
●Roof mount
⊙When installing a module on a roof or building, ensure that it is securely fastened and
cannot fall as a result of wind or snow loads.
⊙Provide adequate ventilation under a module for cooling (5cm minimum air space
between module and mounting surface).
⊙When installing module on a roof, ensure that the roof construction is suitable. In
addition, any roof penetration required to mount the module must be properly sealed to
prevent leaks.
⊙In some cases, a special support frame may be necessary.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
7
QJ
⊙The roof installation of solar modules may affect the fireproofing of the house
construction.
⊙The modules are rated fire Class C, and are suitable for mounting over a Class A roof.
⊙To maintain the corresponding fire prevention level, the tilt angle should be no less
than 5 in/ft (127 mm/305 mm) when the modules are mounted on the roof.
⊙The National Electric Code required the use of a properly sized GFDI on photovoltaic
arrays installed on dwellings. Refer to the NEC for further information on earth ground
fault breakers.
For field connections, use minimum 12 AWG copper wires insulated for a minimum of
90 °C.
Recommended maximum series/parallel module configurations; ([1000
V/(1.25*Voc)]/[fuse rating/Isc+1],如 QJP300-72,Voc is43.4V,Ifuse is15A,Isc is 9.27A,
for 72 cells modules series,Recommended maximum series/parallel module
configuration :18/2.
⊙When installing the module on a roof or building, do so in calm winds. Installing a
module during strong winds may cause accidents.
Mechanical Installation
●Pole mount
⊙When installing a module on a pole, choose a pole and module mounting
structure that will withstand anticipated winds for the area.
●General installation
⊙Module mounting must use the pre-drilled mounting holes in the frame.
⊙The most common mounting is achieved by mounting the module using the four
symmetry points close to the inner side on module frame.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
8
QJ
⊙If excessive wind or snow loads are expected, all eight mounting holes must be used.
⊙Do not lift the module by grasping the module’s junction box or electrical leads.
⊙Do not stand or step on module.
⊙Do not drop module or allow objects to fall on module.
⊙To avoid glass breakage, do not place any heavy objects on the module.
⊙Do not set the module down hard on any surface.
⊙Inappropriate transport and installation may break the glass of the module.
Electrical Installation
●Grid-connected electrical system
⊙The DC electrical energy generated by photovoltaic systems may also be converted to AC
and connected to a utility grid system. As local utilities’ policies on connecting renewable
energy systems to their grids vary from region to region, consult a qualified system
designer or integrator to design such a system. Permits are normally required to install such
a system and the utility must formally approve and inspect such a system before it can be
connected to the grid.
●Grounding
⊙The module frame must be properly grounded (refer to NEC clause 250). The grounding
wire must be properly fastened to the module frame to assure good electrical contact. Use
the recommended type, or an equivalent, connector for this wire.
⊙If the support frame is made of metal, the surface of the frame must be electroplated and
have excellent conductivity.
⊙We recommend the lay-in lug (Cat.No.GBL4-DBT;company:ILSCO) when grounding.
First strip 16mm insulating jacket from the end of the ground wire (4-14STR) carefully to
avoid nicking or cutting conductors, insert the wire into the slot of the lug (see the picture),
and screw down the slotted screw.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
9
QJ
Electrical Installation
Next assemble the recommended ILSCO grounding lug to the aluminum frame using
stainless steel M3 or M5 screw and hardware as shown below. Note: there are two different
size grounding holes, the smaller of which is being phased out. Further, buildup of
hardware for mounting the grounding lug are the same---except for the M3 screw, and
added flat washer is mounted directly under the M3 screw head. The star waher is fitted
directly under the grouding lug and makes electrical contact by penetrating the anodized
coating of the aluminum frame. The screw assembly is further fitted with a flat washer,
then a split lock washer and finally a nut to secure the entire assembly, as shown.
Recommended torque of M3 or M5 screw assembly is 0.8NM or 1.5NM.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
10
QJ
Electrical Installation
●General installation
⊙Do not use module of different configurations in the same system.
⊙Several modules are connected in series and then in parallel to form a PV array,
especially for application with a high operation voltage. If modules are connected in series,
the total voltage is equal to the sum of individual voltages.
⊙For applications requiring high currents, several photovoltaic modules can be connected
in parallel; the total current is equal to the sum of individual currents.
⊙Module is supplied with Multicontact connectors(PV-KBT4 and PV-KST4) to use for
system electrical connections. Use the National Electric Code to determine system wiring
size (refer to NEC clause 310), type and temperature rating of conductors to be connected
to the module’s connectors. Wiring connected to the module’s wiring should be #12AWG
(minimum) and must be temperature rated at 90℃ (minimum).
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
11
QJ
⊙In Canada installation shall be in accordance with CSA C22.1, Safety Standard for
Electrical Installations, Canadian Electrical Code, Part1.
⊙The cross section area of cable and the capacity of connector must be selected to suit the
maximum system short circuit current, otherwise the cable and connector will be
overheated under large current. Refer to NEC for details.
⊙Module overcurrent protection, rated for DC use.
⊙The junction box is fitted with a breather port. The breather port must be mounted facing
down and can not be exposed to rain. Therefore, the junction box must be on the higher
side of the module when it is mounted.
Commission and Maintenance
QJ recommends that all work in commissioning and maintenance of a system must be
performed by a qualified solar PV technician.
●Blocking diodes and bypass diode
⊙Blocking diodes prevent current flowing from the battery to the module when no
electricity is being generated. It is recommended to use blocking diodes when a charging
regulator is not used. Your specialist dealer can advise you with regards to suitable types,
such as Schottky diodes.
⊙In systems with more than two modules in series, high reverse current can flow through
cells that are shaded partially or outright when part of a module is shaded and the rest is
exposed to the sun. These currents can cause the affected cells to get very hot and could
even damage the module. To protect module from such high reverse currents, by-pass
diodes are used in module. All modules rated greater then 55 watt have bypass diode
already integrated in the junction box. In the unlikely event of diode failure, OVIERA
recommends a qualified service technician be employed to determine if diodes have failed
and to make replacement.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
12
QJ
⊙Protect yourself against electricity shocks while commissioning and maintaining the solar
power system.
●Testing, commissioning and troubleshooting
Test all electrical and electronic components of your system before commissioning it.
Follow the instructions in the guides supplied with the components and equipment.
⊙Testing modules connected in series before they are connected to system. To determine
Voc and Isc in the following tests, the module(s) must be exposed to the sun and not
connected to a load. Observe personal safety when making these measurements.
⊙Check the open-circuit voltage (Voc) of every series module using a digital multimeter
(Fluke 170 series are recommended). The measured system Voc should correspond to the
sum of the Vocs of the individual module. You will find the rated voltage in the technical
specifications of the type of the module used and in the tables at the end of this installation
guide. If the measured value is significantly lower than the expected value, proceed as
described under “Troubleshooting an excessively low voltage”.
⊙Determine the short-circuit current (Isc) of every series circuit. It can be measured
directly by connecting the digital multimeter connected in the two terminals of series
circuit or module. Attention, the rated scale of the ammeter or the rated current of load
should more than 1.25 times than the rated short-circuit current of series module. You will
find the rated current in the technical specifications of the type of module used. The
measured value can vary significantly, depending on weather conditions, the time of day
and shading of the module.
⊙Troubleshooting low voltages
To identify the commonly low voltage and excessively low voltage, the commonly how
voltage mentioned here is the decrease of open-circuit voltage of the module, which is
caused by the temperature rising of solar cells or lower irradiance. Excessively low voltage
is typically caused by improper connections at the terminals or defective bypass diodes.
Commission and Maintenance
⊙First check all wiring connections to make sure it is not open-circuit or is not connection
well.
⊙Check the open-circuit voltage of each module.
⊙Fully cover the modules with an opaque material.
⊙Disconnect the wiring at both terminals of the modules.
⊙Remove the opaque material from the module to be checked and measure the open-circuit
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
13
QJ
voltage at its terminals.
⊙If the measured voltage is only half of the rated, this indicates a defective bypass diode.
Refer to “Testing and replacing bypass diodes”.
⊙In the case of not very low irradiance, if the voltage across the terminals differs from the
rated value by more than 5 percent, this indicates a bad electrical connection.
●Maintenance
QJ recommends the following maintenance in order to ensure optimum performance of the
module.
⊙Clean the glass surface of the module as necessary. Always use water and a soft sponge
or cloth for cleaning. A mid, non-abrasive cleaning agent can be used to remove stubbom
dirt.
⊙Check the electrical and mechanical connections every six months to verify that they are
clean, secure and undamaged.
⊙If any problem arises, have them investigated by a competent specialize. Observe the
maintenance instructions for all components used in the system, such as support frames,
charging regulators, inverters, batteries, etc.
●Testing and replacing bypass diodes
Removing the bypass diodes should be done only by a competent PV technician and after
the module has been disconnected from the system.
⊙Place module face down on a soft, flat surface insert a 3mm flat screwdriver into the slot
on the junction box cover. (The cover has a sign of screwdriver). Gently pull up the four
slots until the cover been opened.
⊙Insert the 3mm flat screwdriver into a hole alongside of diode and near one mounting
hole of the diode, pry the screwdriver in the opposite direction of diode and gently pull the
diode up until the lead comes free. Do the same in the other mounting hole of the diode,
and repeat until the diode is free.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
14
QJ
Commission and Maintenance
●Note the orientations of the polarity markings on the diodes.
●Check the resistance of the diodes by using the digital multimeter’s ohms scale.
Resistance should be low in one direction, then when leads are reversed on the diode’s
terminals the resistance should be high, as illustrated in the two pictures below. If a diode
has a low resistance in both directions, it is probably shorted. If it has high resistance in
both directions it is probably open. In either case it should be replaced.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
15
QJ
●Replace a defective diode with a diode of the same type, and ensure that its polarity
making is oriented the same way as the original diode.
●Finally, check the open-circuit voltage (Voc) of the module, as described previously, and
replace both covers.
Disclaimer of liability
●Because the use of this manual and the conditions or methods of installation, operation,
use and maintenance of photovoltaic (PV) product are beyond QJ’s control, QJ does not
accept responsibility and expressly disclaims liability for loss, damage, or expense arising
out of or in any way connected with such installation, operation , use or maintenance.
●No responsibility is assumed by QJ for any infringement of patens or other rights of third
parties, which may result from use of the PV product. No license is granted by implication
or otherwise under any patent or patent rights.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
16
QJ
●The information in this manual is based on QJ knowledge and experience and is believed
to the reliable; but such information including product specification (without limitations)
and suggestions do not constitute a warranty, expresses or implied. QJ reserve the right to
change the manual, the PV produce, the specifications, or product information sheets
without prior notice.
Electrical Characteristics
Please refer to QJ Catalogue.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
17
QJ
products catalogue
Maximum System Voltage: 1000VDC
Power Tolerance: ±3%
Application classes: Class A
Class A: General access, hazardous voltage, hazardous power applications
Modules rated for use in this application class may be used in systems operating at greater
than 50 V DC or 240 W, where general contact access is anticipated. Modules qualified for
safety through this part of IEC 61730 and IEC 61730-2 and within this application class are
considered to meet the requirements for safety class II.
Model Module
Dimensions
Weigh
t
Isc Voc Imp Vmp Pmax Maxi
mum
serie
s
Fuse
Rain
g
QJP335 1956x992x40
(mm)
20.3kg 9.69A 44.4V 9.06A 37V 335W 15A
QJP330 1956x992x40
(mm)
20.3kg 9.58A 44.28V 8.95A 36.9V 330W 15A
QJP325 1956x992x40
(mm)
20.3kg 8.91A 44.16V 8.32A 36.8V 325W 15A
QJP320 1956x992x40 20.3kg 9.33A 44.04V 8.72A 36.7V 320W 15A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
18
QJ
(mm)
QJP315 1956x992x40
(mm)
20.3kg 9.22A 43.92V 8.61A 36.6V 315W 15A
QJP310 1956x992x40
(mm)
20.3kg 9.11A 43.8V 8.5A 36.5V 310W 15A
QJP305 1956x992x40
(mm)
20.3kg 8.97A 43.68V 8.38A 36.4V 305W 15A
QJP300 1956x992x40
(mm)
20.3kg 8.85A 43.56V 8.27A 36.3V 300W 15A
QJP295 1956x992x40
(mm)
20.3kg 8.72A 43.44V 8.15A 36.2V 295W 15A
QJP290 1956x992x40
(mm)
20.3kg 8.61A 43.32V 8.04A 36.1V 290W 15A
QJP285 1956x992x40
(mm)
20.3kg 8.48A 43.2V 7.92A 36.0V 285W 15A
QJP280 1640x992x40
(mm)
18.2kg 9.71A 37.08V 9.07A 30.9V 280W 15A
QJP275 1640x992x40
(mm)
18.2kg 9.56A 36.96V 8.93A 30.8V 275W 15A
QJP270 1640x992x40
(mm)
18.3kg 9.41A 36.84V 8.8A 30.7V 270W 15A
QJP265 1640x992x40
(mm)
18.3kg 9.27A 36.72V 8.66A 30.6V 265W 15A
QJP260 1640x992x40
(mm)
18.3kg 9.13A 36.6V 8.53A 30.5V 260W 15A
QJP255 1640x992x40
(mm)
18.3kg 8.98A 36.48V 8.39A 30.4V 255W 15A
Model Module
Dimensions
Weigh
t
Isc Voc Imp Vm
p
Pmax Maximu
m series
Fuse
Raing
QJP250 1640x992x40
(mm)
18.3kg 8.83A 36.36V 8.26A 30.3
V
250W 15A
QJP245 1640x992x40
(mm)
18.3kg 8.68A 36.24V 8.12A 30.2
V
245W 15A
QJP240 1640x992x40
(mm)
18.3kg 8.54A 36.12V 7.98A 30.1
V
240W 15A
QJP235 1640x992x40
(mm)
18.3kg 8.39A 36V 7.84A 30.0
V
235W 15A
QJP230 1640x992x40
(mm)
18.3kg 8.24A 35.88V 7.7A 29.9
V
230W 15A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
19
QJ
QJP225 1640x992x40
(mm)
18.3kg 8.08A 35.76V 7.56A 29.8
V
225W 15A
QJP220 1325*992*40
(mm)
14.5kg 9.53A 29.64V 8.91 A 24.7
V
220W 15A
QJP215 1325*992*40
(mm)
14.5kg 9.36A 29.52V 8.74 A 24.6
V
215W 15A
QJP210 1325*992*40
(mm)
14.5kg 9.18A 29.4 V 8.58 A 24.5
V
210W 15A
QJP205 1325*992*40
(mm)
14.5kg 8.99A 29.28V 8.41 A 24.4
V
205W 15A
QJP200 1325*992*40
(mm)
14.5kg 8.81A 29.16V 8.23 A 24.3
V
200W 15A
QJP195 1325*992*40
(mm)
14.5kg 8.62A 29.04V 8.06 A 24.2
V
195W 15A
QJP190 1325*992*40
(mm)
14.5kg 8.44A 28.92V 7.89A 24.1
V
190W 15A
QJP165 1480*675*40
(mm)
11.5kg 9.49A 22.32V 8.87A 18.6
V
165W 15A
QJP160 1480*675*40
(mm)
11.5kg 9.26A 22. 2V 8.65A 18.5
V
160W 15A
QJP155 1480*675*40
(mm)
11.5kg 9.02A 22.08V 8.43A 18.4
V
155W 15A
QJP150 1480*675*40
(mm)
11.5kg 8.78A 21.96V 8.2A 18.3
V
150W 15A
QJP145 1480*675*40
(mm)
11.5kg 8.53A 21.84V 7.97A 18.2
V
145W 15A
QJP140 1480*675*40
(mm)
11.5kg 8.28A 21.72V 7.74A 18.1
V
140W 15A
QJP110 1008*675*40
(mm)
7.9kg 9.49A 14.88V 8.87A 12.4
V
110W 15A
QJP105 1008*675*40
(mm)
7.9kg 9.14A 14.76V 8.54A 12.3
V
105W 15A
QJP100 1008*675*40
(mm)
7.9kg 8.78A 14.64V 8.2A 12.2
V
100W 15A
QJP95 1008*675*40
(mm)
7.9kg 8.41A 14.52V 7.86A 12.1
V
95W 15A
QJP90 850*675*40
(mm)
6.96kg 9.36A 12.36V 8.74A 10.3
V
90W 15A
QJP85 850*675*40
(mm)
6.96kg 8.92A 12.24V 8.34A 10.2
V
85W 15A
QJP80 850*675*40
(mm)
6.96kg 8.48A 12.12V 7.93A 10.1
V
80W 15A
QJP75 690*675*40 5.86kg 9.67A 9.96V 9.04A 8.3 75W 15A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
20
QJ
(mm) V
QJP70 690*675*40
(mm)
5.86kg 9.14A 9.84V 8.54A 8.2
V
70W 15A
QJP65 690*675*40
(mm)
5.86kg 9.72A 8.6V 8.03A 8.1
V
65W 15A
QJP55 535*675*40
(mm)
4.72kg 9.49A 7.44V 8.87A 6.2
V
55W 15A
QJP50 535*675*40
(mm)
4.72kg 8.78A 7.32V 8.2A 6.1
V
50W 15A
QJP45 535*675*40
(mm)
4.72kg 8.03A 7.2V 7.5A 6.0
V
45W 15A
QJP35 376*675*40
(mm)
3.66kg 8.92A 5.04V 8.34A 4.2
V
35W 15A
QJP30 376*675*40
(mm)
3.66kg 7.83A 4.92V 7.32A 4.1
V
30W 15A
QJP25 535*356*40
(mm)
2.91kg 8.63A 3.72V 8.07A 3.1
V
25W 15A
QJP20 535*356*40
(mm)
2.91kg 7.14A 3.6V 6.67A 3.0
V
20W 15A
QJP10 220*356*40
(mm)
1.6kg 10.3A 1.25V 9.62A 1.04
V
10W 15A
QJM355 1956*992*40
(mm)
20.2kg 10.3A 44.4V 9.59A 37V 355W 15A
QJM350 1956*992*40
(mm)
20.2kg 10.15
A
44.28V 9.49A 36.9
V
350W 15A
QJM345 1956*992*40
(mm)
20.2kg 10.03
A
44.16V 9.38A 36.8
V
345W 15A
QJM340 1956*992*40
(mm)
20.2kg 9.92A 44.04V 9.27A 36.7
V
340W 15A
QJM335 1956*992*40
(mm)
20.2kg 9.79A 43.92V 9.16A 36.6
V
335W 15A
QJM330 1956*992*40
(mm)
20.2kg 9.68A 43.8V 9.04A 36.5
V
330W 15A
QJM325 1956*992*40
(mm)
20.2kg 9.56A 43.68V 8.93A 36.4
V
325W 15A
QJM320 1956*992*40
(mm)
20.2kg 9.44A 43.56V 8.82A 36.3
V
320W 15A
QJM315 1956*992*40
(mm)
20.2kg 9.32A 43.44V 8.71A 36.2
V
315W 15A
QJM310 1956*992*40
(mm)
20.2kg 9.19A 43.32V 8.59A 36.1
V
310W 15A
QJM305 1956*992*40
(mm)
20.2kg 9.07A 43. 2V 8.48A 36.0
V
305W 15A
QJM295 1640*992*40 18.1kg 10.22 37.08V 9.55A 30.9 295W 15A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
21
QJ
(mm) A V
QJM290 1640*992*40
(mm)
18.1kg 10.08
A
36.96V 9.42A 30.8
V
290W 15A
QJM285 1640*992*40
(mm)
18.1kg 9.93A 36.84V 9.28A 30.7
V
285W 15A
QJM280 1640*992*40
(mm)
18.1kg 9.79A 36.72V 9.15A 30.6
V
280W 15A
QJM275 1640*992*40
(mm)
18.1kg 9.65A 36.6V 9.02A 30.5
V
275W 15A
QJM270 1640*992*40
(mm)
18.1kg 9.51A 36.48V 8.89A 30.4
V
270W 15A
QJM265 1640*992*40
(mm)
18.1kg 9.36A 36.36V 8.75A 30.3
V
265W 15A
QJM260 1640*992*40
(mm)
18.1kg 9.22A 36.24V 8.61A 30.2
V
260W 15A
QJM255 1640*992*40
(mm)
18.1kg 9.07A 36.12V 8.48A 30.1
V
255W 15A
QJM250 1580x1066x5
0(mm)
21kg 5.81A 57.8V 5.19A 48.2
V
250W 10A
QJM245 1580x1066x5
0(mm)
21kg 5.71A 57.7V 5.10A 48.1
V
245W 10A
QJM240 1580x1066x5
0(mm)
21kg 5.61A 57.6V 5.01A 48.0
V
240W 10A
QJM235 1325*992*40
(mm)
14.4kg 10.18
A
29.64V 9.52A 24.7
V
235W 15A
QJM230 1325*992*40
(mm)
14.4kg 10.01
A
29.52V 9.35A 24.6
V
230W 15A
QJM225 1325*992*40
(mm)
14.4kg 9.83A 29.4V 9.19A 24.5
V
225W 15A
QJM220 1325*992*40
(mm)
14.4kg 9.65A 29.28V 9.02A 24.4
V
220W 15A
QJM215 1325*992*40
(mm)
14.4kg 9.47A 29.16V 8.85A 24.3
V
215W 15A
QJM210 1325*992*40
(mm)
14.4kg 9.29A 29.04V 8.68A 24.2
V
210W 15A
QJM205 1325*992*40
(mm)
14.4kg 9.11A 28.92V 8.51A 24.1
V
205W 15A
QJM200 1325*992*40
(mm)
14.4kg 8.92A 28.8V 8.34A 24
V
200W 15A
QJM195 1580x808x50
(mm)
15.5kg 6.01A 43.6V 5.37A 36.4
V
195W 10A
QJM190 1580x808x50
(mm)
15.5kg 5.86A 43.5V 5.23A 36.3
V
190W 10A
QJM185 1580x808x50 15.5kg 5.72A 43.4V 5.11A 36.2 185W 10A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
22
QJ
(mm) V
QJM180 1580x808x50
(mm)
15.5kg 5.59A 43.3V 4.99A 36.1
V
180W 10A
QJM175 1480*675*40
(mm)
11.4kg 10.13
A
22.2V 9.46A 18.5
V
175W 15A
QJM170 1480*675*40
(mm)
11.4kg 9.89A 22.08V 9.24A 18.4
V
170W 15A
QJM165 1480*675*40
(mm)
11.4kg 9.65A 21.96V 9.02A 18.3
V
165W 15A
QJM160 1480*675*40
(mm)
11.4kg 9.41A 21.84V 8.8A 18.2
V
160W 15A
QJM155 1480*675*40
(mm)
11.4kg 9.17A 21.72V 8.57A 18.1
V
155W 15A
QJM130 1074x808x50
(mm))
11kg 5.96A 29.3V 5.32A 24.4
V
130W 10A
QJM125 1074x808x50
(mm))
11kg 5.79A 29.0V 5.17A 24.2
V
125W 10A
QJM120 1074x808x50
(mm))
11kg 5.60A 28.8V 5.01A 24.0
V
120W 10A
QJM115 1008*675*40
(mm))
7.8kg 9.93A 14.88V 9.28A 12.4
V
115W 15A
QJM110 1008*675*40
(mm))
7.8kg 9.58A 14.76V 8.95A 12.3
V
110W 15A
QJM105 1008*675*40
(mm))
7.8kg 9.21A 14.64V 8.61A 12.2
V
105W 15A
QJM100 1008*675*40
(mm))
7.8kg 8.85A 14.52V 8.27A 12.1
V
100W 15A
QJM95 850*675*40
(mm))
6.9kg 9.87A 12.36V 9.23A 10.3
V
95W 15A
QJM90 850*675*40
(mm))
6.9kg 9.45A 12.24V 8.83A 10.2
V
90W 15A
QJM85 850*675*40
(mm))
6.9kg 9.01A 12.12V 8.42A 10.1
V
85W 15A
QJM80 850*675*40
(mm))
6.9kg 8.56A 12V 8A 10
V
80W 15A
QJM75 690*675*40
(mm))
5.8kg 9.67A 9.96V 9.04A 8.3
V
75W 15A
QJM70 690*675*40
(mm))
5.8kg 9.14A 9.84V 8.54A 8.2
V
70W 15A
QJM65 690*675*40
(mm))
5.8kg 8.59A 9.72V 8.03A 8.1
V
65W 15A
QJM55 535*675*40
(mm))
4.65kg 9.49A 7.44V 8.87A 6.2
V
55W 15A
QJM50 535*675*40 4.65kg 8.78A 7.32V 8.2A 6.1 50W 15A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
23
QJ
(mm)) V
QJM35 376*675*40
(mm))
3.6kg 8.92A 5.04V 8.34A 4.2
V
35W 15A
QJM30 376*675*40
(mm))
3.6kg 7.83A 4.92V 7.32A 4.1
V
30W 15A
QJM25 535*356*40
(mm))
2.85kg 8.63A 3.72V 8.06A 3.1
V
25W 15A
QJM10 220*356*40
(mm))
1.55kg 9.73A 1.32V 9.09A 1.1
V
10W 15A
QJM260-12
5
1580x1066x5
0(mm)
21kg 6.00A 58.2V 5.36A 48.5
V
260W 10A
QJM255-12
5
1580x1066x5
0(mm)
21kg 5.91A 58.0V 5.28A 48.3
V
255W 10A
QJM235-12
5
1580x1066x5
0(mm)
21kg 5.49A 57.4V 4.91A 47.9
V
235W 10A
QJM230-12
5
1580x1066x5
0(mm)
21kg 5.39A 57.3V 4.81A 47.8
V
230W 10A
QJM225-12
5
1580x1066x5
0(mm)
21kg 5.28A 57.2V 4.72A 47.7
V
225W 10A
QJM220-12
5
1580x1066x5
0(mm)
21kg 5.17A 57.0V 4.63A 47.5
V
220W 10A
QJM175-12
5
1580x808x50
(mm)
15.5kg 5.45A 43.1V 4.87A 35.9
V
175W 10A
QJM170-12
5
1580x808x50
(mm)
15.5kg 5.35A 42.7V 4.78A 35.6
V
170W 10A
QJM165-12
5
1580x808x50
(mm)
15.5kg 5.22A 42.5V 4.66A 35.4
V
165W 10A
QJM115-12
5
1074x808x50
(mm))
11kg 5.41A 28.8V 4.83A 23.8
V
115W 10A
QJM110-12
5
1074x808x50
(mm)
11kg 5.24A 28.2V 4.68A 23.5
V
110W 10A
QJM95-125 1200x552x50
(mm)
7.8kg 5.94A 21.5V 5.31A 17.9
V
95W 10A
QJM90-125 1200x552x50
(mm)
7.8kg 5.72A 21.1V 5.11A 17.6
V
90W 10A
QJM85-125 1200x552x50
(mm)
7.8kg 5.48A 20.9V 4.89A 17.4
V
85W 10A
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
24
QJ
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
25
QJ
Mounting Using Clamps on Long Edge of Module
QJ modules recommend to be mounted using clamps designed for solar modules as
shown in Figures 3.
A module should be attached on a mount or support structure rail by metal clamps.
The metal clamp should fulfill the following specifications:
Size: not less than 1.5”(38mm)width
Thickness: not less than 0.12”(3mm)
Material: Aluminum alloy
Recommendation of bolt torque range: 16N.m to 25N.m.
It is always recommmendable to position the clamps at the location of the holes in the
module’s frame.
Recommendation of clamps position range:Figure 4 for reference.
The Modules clamps must not contact the front glass or deform the frame in any
way.Avoid shading effects from the Modules clamps.Drainage holes on the Modules frame
must not be closed or obscured by the clamps.
Figure 5 to Figure 14 is just used for the 60 cells modules and the dimension is
1640*992*40mm.
The details of Part 1and Part 11 in from Figure 6 to Figure 14 is reference to Figure 6
For Figure 7 and Figure8,the PV modules are designed for a maximum fo 2400Pa wind
load.
For from Figure 9to Figure 14,the PV modules are designed for a maximium of 2400Pa
Wind load and 5400Pa withstand heavy accumulations of snow and ice.
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
26
QJ
QJ SOLAR
CIXI CITY RIXING ELECTRONICS CO.,LTD
Jietang Industrial Park,Tianyuan Town,Cixi City,Zhejiang Province,China
WWW.QJSOLAR.COM Email: [email protected] Tel: +86 13586844751 Fax: +86 574 63456148
27
QJ