+ All Categories
Home > Documents > INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting...

INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting...

Date post: 24-Sep-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
140
CONTENTS NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 8 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 GAS HEATING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 GAS FURNACE OPERATING INSTRUCTIONS. . . 68 MILLENNIUM SEQUENCE OF OPERATION . . . . . 70 TROUBLESHOOTING A MILLENNIUM SIMPLICITY CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 THE MILLENNIUM SIMPLICITY CONTROL . . . . . . 96 SIMPLICITY PROGRAMMING OPTIONS . . . . . . . 106 SETTABLE SYSTEM PARAMETERS. . . . . . . . . . 106 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 See the following pages for a complete Table of Contents. NOTES, CAUTIONS AND WARNINGS Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING . Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. INSTALLATION MANUAL CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT. SAVE THIS MANUAL MILLENNIUM™ ROOFTOP 102777-YIM-B-0105 MODELS: Y22 Y23 Y24
Transcript
Page 1: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

CONTENTSNOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 6GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 8INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9GAS HEATING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63GAS FURNACE OPERATING INSTRUCTIONS. . . 68MILLENNIUM SEQUENCE OF OPERATION . . . . . 70TROUBLESHOOTING A MILLENNIUM SIMPLICITY CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95THE MILLENNIUM SIMPLICITY CONTROL. . . . . . 96SIMPLICITY PROGRAMMING OPTIONS . . . . . . . 106SETTABLE SYSTEM PARAMETERS. . . . . . . . . . 106SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

See the following pages for a complete Table of Contents.

NOTES, CAUTIONS AND WARNINGS

Installer should pay particular attention to the words: NOTE,CAUTION, and WARNING. Notes are intended to clarify ormake the installation easier. Cautions are given to preventequipment damage. Warnings are given to alert installerthat personal injury and/or equipment damage may result ifinstallation procedure is not handled properly.

INSTALLATION MANUAL

CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT.

SAVE THIS MANUAL

MILLENNIUM™ ROOFTOP

102777-YIM-B-0105

MODELS: Y22

Y23

Y24

Page 2: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

2 Unitary Products Group

TABLE OF CONTENTSNOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 8

NOTES, CAUTIONS AND WARNINGS. . . . . . . . . . . . . . . 8GAS FIRED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

WHAT TO DO IF YOU SMELL GAS. . . . . . . . . . . . . . . . 8ALL MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9LIMITATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9LOCATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9RIGGING AND HANDLING . . . . . . . . . . . . . . . . . . . . . . . 12CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13AIR HOODS FOR FIXED OUTSIDE AIR(UNITS WITHOUT ECONOMIZER). . . . . . . . . . . . . . . . . 13AIR HOODS FOR ECONOMIZER . . . . . . . . . . . . . . . . . . 13AIR HOODS FOR EXHAUST AIR . . . . . . . . . . . . . . . . . . 13CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . 13SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14COMPRESSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14THERMOSTAT (CONSTANT VOLUME UNITS) . . . . . . . 14SPACE SENSOR (VARIABLE AIR VOLUME UNITS). . . 14POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . 15

POWER WIRING DETAIL. . . . . . . . . . . . . . . . . . . . . . . 15ERV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

GAS HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16GAS CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16VENT AND COMBUSTION AIR. . . . . . . . . . . . . . . . . . . . 17

233 & 466 MBH HEAT . . . . . . . . . . . . . . . . . . . . . . . . . 17699 MBH HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

ELECTRIC HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18HOT WATER HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

PIPING CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . 19STEAM HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

PIPING CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . 20STATIC PRESSURE CONTROL PLASTIC TUBING . . . 20EXHAUST STATIC PRESSURE . . . . . . . . . . . . . . . . . . . 20CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS . . . . . . . . . . . . . 46

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63COMPRESSOR ROTATION . . . . . . . . . . . . . . . . . . . . . . 63SUPPLY AIR FAN INSTRUCTIONS . . . . . . . . . . . . . . . . 63

CHECK BLOWER BEARING SET SCREWS . . . . . . . . 63CHECKING SUPPLY AIR CFM . . . . . . . . . . . . . . . . . . 63FAN ROTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63BELT TENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63AIR BALANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

CHECKING AIR QUANTITY. . . . . . . . . . . . . . . . . . . . . 63SUPPLY AIR DRIVE ADJUSTMENT . . . . . . . . . . . . . . 65

SYSTEM SETPOINTS. . . . . . . . . . . . . . . . . . . . . . . . . . . 65CONSTANT VOLUME AND VARIABLE AIR VOLUME: 65

GAS FURNACE OPERATINGINSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

TO LIGHT THE MAIN BURNERS . . . . . . . . . . . . . . . . . . 68TO SHUT DOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68POST-START CHECKLIST (GAS) . . . . . . . . . . . . . . . . . 68MANIFOLD GAS PRESSURE ADJUSTMENT . . . . . . . . 68BURNER INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . 69ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . . 69CHECKING GAS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . 69

NATURAL GAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69ELECTRIC HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . 70COOLING OPERATING INSTRUCTIONS . . . . . . . . . . . 70

COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70INTERNAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . 70CONDENSER FANS . . . . . . . . . . . . . . . . . . . . . . . . . . 70

MILLENNIUM SEQUENCE OF OPERATION . . . . . . . . . . 70OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70RUN SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71UNIT CONTROLS SEQUENCE . . . . . . . . . . . . . . . . . . . 71VARIABLE AIR VOLUME UNIT (VFD & IGV) . . . . . . . . . 73

OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73OCCUPIED / UNOCCUPIED / MORNING WARM-UP . . 73

OCCUPIED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73UNOCCUPIED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73MORNING WARM-UP [MWUP] . . . . . . . . . . . . . . . . . . 74

UNIT CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74HEAD PRESSURE CONTROL . . . . . . . . . . . . . . . . . . . . 77

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77SEQUENCE OF OPERATION - FOR HEADPRESSURE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . 77INTELLI-START. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

LEAD LAG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77DEVICES AND RULES . . . . . . . . . . . . . . . . . . . . . . . . . . 77

AIR PROVING SWITCH . . . . . . . . . . . . . . . . . . . . . . . . 78FAN DELAYS: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

COMFORT VENTILATION MODE . . . . . . . . . . . . . . . . . 78ECONOMIZER CONTROL DURINGCOMFORT VENTILATION . . . . . . . . . . . . . . . . . . . . . . 79STAGING CONTROL DURING COMFORTVENTILATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

HYDRONIC HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80COOLING LOCKOUT ON OAT. . . . . . . . . . . . . . . . . . . . 80WATER COIL FREEZE STAT (FSI) . . . . . . . . . . . . . . . . 80CV OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80THERMOSTAT OPERATION FOR COOLINGWITH Y1, Y2, Y3 AND Y4 INPUTS . . . . . . . . . . . . . . . . . 80

GROUPING COMPRESSORS INTO STAGES . . . . . . 81ECONOMIZER MODE . . . . . . . . . . . . . . . . . . . . . . . . . 81

OPERATION FOR HEATING WITH W1, W2, AND

Page 3: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 3

W3 INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81SUPPLY FAN OFF DELAY. . . . . . . . . . . . . . . . . . . . . . 81HEAT STAGE DELAYS . . . . . . . . . . . . . . . . . . . . . . . . 81THERMOSTAT OPERATION WITH HYDRONIC HEAT 81

SENSOR OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . 81TYPES OF SPACE SENSORS . . . . . . . . . . . . . . . . . . . . 81

SUPPLY FAN CONTROL WHEN USING AZONE SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82SUPPLY FAN OFF DELAY. . . . . . . . . . . . . . . . . . . . . . 82CONTROL OF COMPRESSORS WHEN USINGA ZONE SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82HEATING OPERATION WITH THE SENSOR OPTION 82COOLING OPERATION WITH THE SENSOR OPTION 82

VAV OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83VAV OPERATION WITH A THERMOSTAT . . . . . . . . . 83VAV OPERATION WITH A ZONE SENSOR . . . . . . . . 83STANDALONE VAV OPERATION . . . . . . . . . . . . . . . . 83SUPPLY FAN OFF DELAY. . . . . . . . . . . . . . . . . . . . . . 83OCCUPIED HEATING WITH A THERMOSTAT. . . . . . 83UNOCCUPIED HEATING WITH A THERMOSTAT . . . 84OCCUPIED COOLING WITH A THERMOSTAT . . . . . 84UNOCCUPIED COOLING WITH A THERMOSTAT. . . 84OCCUPIED HEATING WITH A SPACE SENSOR. . . . 84UNOCCUPIED HEATING WITH A SPACE SENSOR . 84OCCUPIED COOLING WITH A SPACE SENSOR . . . 84UNOCCUPIED COOLING WITH A SPACE SENSOR . 84UNOCCUPIED HEATING IN STANDALONEOPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85OCCUPIED COOLING IN STANDALONEOPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

SUPPLY DUCT PRESSURE CONTROL ALGORITHM . 85MORNING WARM UP / VAV OCCUPIED HEATINGCONTROL ALGORITHM. . . . . . . . . . . . . . . . . . . . . . . . . 85

STARTING MORNING WARM UP. . . . . . . . . . . . . . . . 85MORNING WARM UP / VAV OCCUPIED HEATING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85UNOCCUPIED VAV HEATING / COOLING CONTROL ALGORITHM WITH A SPACE SENSOR . . . . . . . . . . . 86OCCUPIED VAV HEATING / COOLING CONTROLALGORITHM WITH A SPACE SENSOR . . . . . . . . . . . 86

CONTROLLING EXCESSIVE SAT (SUPPLYAIR TEMPERATURE) . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

SAT CONTROL CONFIGURATION . . . . . . . . . . . . . . . 87SAT CONTROL FOR COOLING . . . . . . . . . . . . . . . . . 87ECONOMIZER LOADING OPERATION DURINGAN EXCESSIVE SAT FOR COOLING: . . . . . . . . . . . . 87CV ECONOMIZER OPERATION . . . . . . . . . . . . . . . . . 87

SAT SETPOINTS USED DURING COOLINGWITH ECONOMIZER OPERATION . . . . . . . . . . . . . . . . 87DEMAND VENTILATION. . . . . . . . . . . . . . . . . . . . . . . . . 90EXHAUST OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 91

TWO-POSITION CONTROL (NONMODULATING POWER EXHAUST) . . . . . . . . . . . . . . 91PROPORTIONAL CONTROL (FAN WITH MODULATING EXHAUST AIR DAMPER (EAD) CONTROLLED FROM

BUILDING STATIC PRESSURE). . . . . . . . . . . . . . . . . 91PROPORTIONAL CONTROL WITH VFD FAN . . . . . . 92TWO-POSITION CONTROL (POWER EXHAUSTWITH BAROMETRIC RELIEF, CONTROLLEDFROM BUILDING STATIC PRESSURE) . . . . . . . . . . . 92ERV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

SCHEDULING OPERATION. . . . . . . . . . . . . . . . . . . . . . 92COMPRESSOR STATUS MONITORING. . . . . . . . . . . . 92

TROUBLESHOOTING A MILLENNIUM SIMPLICITY CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

STATUS LED CHART. . . . . . . . . . . . . . . . . . . . . . . . . . . 95FAILURE MODES AND DEFAULT OPERATION. . . . . . 95

ERROR HISTORIES . . . . . . . . . . . . . . . . . . . . . . . . . . 95SENSOR FAILURES AND DEFAULT OPERATION . . . 95

SAT SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95RAT SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95OAT SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95OUTSIDE AIR RELATIVE HUMIDITY SENSOR . . . . . 95RETURN AIR RELATIVE HUMIDITY SENSOR. . . . . . 95SPACE TEMPERATURE SENSOR. . . . . . . . . . . . . . . 96BUILDING PRESSURE SENSOR . . . . . . . . . . . . . . . . 96DUCT STATIC PRESSURE SENSOR. . . . . . . . . . . . . 96IAQ SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

SYSTEM ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96HEATING SAT FAILURE . . . . . . . . . . . . . . . . . . . . . . . 96COOLING SAT FAILURE. . . . . . . . . . . . . . . . . . . . . . . 96SUPPLY FAN FAILURE. . . . . . . . . . . . . . . . . . . . . . . . 96COMPRESSOR SAFETY CHAIN TRIP . . . . . . . . . . . . 96DIRTY FILTER ALARM . . . . . . . . . . . . . . . . . . . . . . . . 96HIGH DUCT STATIC ALARM . . . . . . . . . . . . . . . . . . . 96HOT WATER COIL FREEZE ALARM . . . . . . . . . . . . . 96

THE MILLENNIUM SIMPLICITY CONTROL . . . . . . . . . . 96INTRODUCTION AND OVERVIEW . . . . . . . . . . . . . . . . 96

DIAGNOSTICS VIA LED . . . . . . . . . . . . . . . . . . . . . . . 97ERROR HISTORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

DIGITAL LINGO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98THE PI ALGORITHM . . . . . . . . . . . . . . . . . . . . . . . . . . 98

ANALOG TO DIGITAL CONVERTER. . . . . . . . . . . . . . . 98SOFTWARE TERMINOLOGY . . . . . . . . . . . . . . . . . . . 98

COMMUNICATIONS BUS . . . . . . . . . . . . . . . . . . . . . . . 99OPTIONAL MODLINC TRANSLATOR . . . . . . . . . . . . . . 99

OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99COMPONENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . 99

THE SIMPLICITY CONTROLLER . . . . . . . . . . . . . . . . 99WIRING AND TERMINATION, COMMUNICATIONS 100COMMUNICATION ADDRESS:. . . . . . . . . . . . . . . . . 100ACRONYMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100ANALOG INPUTS (AI): . . . . . . . . . . . . . . . . . . . . . . . 101BINARY INPUTS (BI): . . . . . . . . . . . . . . . . . . . . . . . . 102OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102BINARY OUTPUTS (BO) . . . . . . . . . . . . . . . . . . . . . . 103H1-3 - HEAT STAGES 1 TO 3 [OPTIONAL] . . . . . . . 103

SIMPLICITY PROGRAMMING OPTIONS . . . . . . . . . . . 106

Page 4: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

4 Unitary Products Group

INTERACTING THROUGH THE MILLENNIUMSIMPLICITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

SET THE CLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106PARAMETER SETTING . . . . . . . . . . . . . . . . . . . . . . . 106

INITIAL STARTUP OPTIONS . . . . . . . . . . . . . . . . . . . . 106METRIC OPERATION (ENGLISH) . . . . . . . . . . . . . . . . 106

SETTABLE SYSTEM PARAMETERS . . . . . . . . . . . . . . . 106SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . 114COMPRESSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114MOTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

INDOOR BLOWER MOTORS. . . . . . . . . . . . . . . . . . . 114POWER EXHAUST OR RETURN AIR FAN MOTORS 114CONDENSER FAN MOTORS . . . . . . . . . . . . . . . . . . 114DRAFT MOTOR (GAS FURNACE). . . . . . . . . . . . . . . 114

GAS FURNACE SAFETY FEATURES . . . . . . . . . . . . . 131COMBUSTION AIR PROVING . . . . . . . . . . . . . . . . . . 131ROLLOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131NORMAL MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . 131

FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131MOTORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131FAN DRIVES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132OUTDOOR COIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

GAS BURNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132TO CLEAN BURNERS . . . . . . . . . . . . . . . . . . . . . . . . 132COMBUSTION AIR DISCHARGE. . . . . . . . . . . . . . . . 132CLEANING FLUE PASSAGES AND HEATING ELE-MENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

SECURE OWNERS APPROVAL. . . . . . . . . . . . . . . . . . 133

LIST OF FIGURESFig. # Pg. #

1 COMPONENT LOCATION. . . . . . . . . . . . . . . . . . . . . . . 72 TYPICAL RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . . 114 RECOMMENDED DRAIN PIPING . . . . . . . . . . . . . . . . 145 TYPICAL THERMOSTAT WIRING . . . . . . . . . . . . . . . . 146 TYPICAL GAS PIPING CONNECTION . . . . . . . . . . . . 167 VENT AND COMBUSTION AIR HOODS . . . . . . . . . . . 178 699 MBH HEAT VENT . . . . . . . . . . . . . . . . . . . . . . . . . 179 FLUE EXTENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1710 CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1811 HOT WATER PIPING CROSS-SECTION. . . . . . . . . . . 1912 STEAM PIPING CROSS-SECTION . . . . . . . . . . . . . . . 1913 BOTTOM SUPPLY AND RETURN . . . . . . . . . . . . . . . . 3914 END RETURN, BOTTOM SUPPLY . . . . . . . . . . . . . . . 4015 BOTTOM RETURN, FRONT & REAR SUPPLY . . . . . . 4116 END RETURN, FRONT & REAR SUPPLY. . . . . . . . . . 4217 FIELD INSTALLED DISCONNECT . . . . . . . . . . . . . . . . 4318 PARTIAL ROOF CURB MODEL 1RC0455P . . . . . . . . 4419 FULL ROOF CURB MODEL 1RC0455F. . . . . . . . . . . . 4520 ALTITUDE/TEMPERATURE CONVERSION

FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

21 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . . 5022 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . . 5323 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . . 5624 POWER EXHAUST - ONE FORWARD CURVE

FAN - 25 TONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6025 POWER EXHAUST - TWO FORWARD CURVED

FANS - 30 & 40 TONS . . . . . . . . . . . . . . . . . . . . . . . . . 6226 BELT TENSION ADJUSTMENT. . . . . . . . . . . . . . . . . . 6327 TYPICAL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . . 6928 TYPICAL FLAME APPEARANCE . . . . . . . . . . . . . . . . 7029 COMFORT VENTILATION ECONOMIZER

CONTROL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7830 SAT CONTROL BAND . . . . . . . . . . . . . . . . . . . . . . . . . 8531 SIMPLICITY CONTROLLER . . . . . . . . . . . . . . . . . . . . 9732 SIMPLICITY CONTROLS PUSH BUTTONS . . . . . . . . 9733 ANALOG TO DIGITAL CONVERTER . . . . . . . . . . . . . 9834 VFD CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . 10235 SEQUENCE OF SETTING THE SET POINTS . . . . . 10936 HOT WATER COIL - 25 & 30 TON, 1 ROW,

AT 10 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11837 HOT WATER COIL - 25 & 30 TON, 1 ROW,

AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11838 HOT WATER COIL - 25 & 30 TON, 1 ROW,

AT 30 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11939 HOT WATER COIL - 25 & 30 TON, 1 ROW,

AT 40 GPM 11940 HOT WATER COIL - 25 & 30 TON, 2 ROW,

AT 60 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12041 HOT WATER COIL - 25 & 30 TON, 2 ROW,

AT 80 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12042 HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM . 12143 HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM . 12144 HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM . 12245 HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM . 12246 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM . 12347 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM . 12348 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM . 12449 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM . 12450 STEAM COIL - 25 & 30 TON (1 ROW). . . . . . . . . . . . 12551 STEAM COIL - 40 TON (1 ROW) . . . . . . . . . . . . . . . . 12552 TYPICAL CONTROL WIRING . . . . . . . . . . . . . . . . . . 12653 LEGEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12754 TYPICAL 25 TON POWER WIRING . . . . . . . . . . . . . 12855 TYPICAL 30/40 TON POWER WIRING . . . . . . . . . . . 12956 TYPICAL GAS HEAT WIRING . . . . . . . . . . . . . . . . . . 13057 TYPICAL FLUE BAFFLE . . . . . . . . . . . . . . . . . . . . . . 13358 25 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . 13459 30 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . 13560 40 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . 13661 PRESSURE DROP DRY EVAPORATOR

COIL VS SUPPLY AIR CFM - 25 TON . . . . . . . . . . . . 13762 PRESSURE DROP DRY EVAPORATOR

COIL VS SUPPLY AIR CFM - 30 & 40 TON . . . . . . . 138

Page 5: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 5

LIST OF TABLES

Tbl. # Pg. #

1 COOLING & ELECTRICAL APPLICATION . . . . . . . . . . 92 COOLING & ELEC. APP. LIMITATIONS . . . . . . . . . . . . 93 GAS APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . 104 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 SUPPLY FAN MOTOR VFD WEIGHTS. . . . . . . . . . . . 116 EXHAUST FAN MOTOR VFD WEIGHTS . . . . . . . . . . 117 UNIT CORNERWEIGHT . . . . . . . . . . . . . . . . . . . . . . . 128 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 129 CONTROL WIRE SIZES . . . . . . . . . . . . . . . . . . . . . . . 1410 PIPE SIZES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1611 GENERAL PHYSICAL DATA . . . . . . . . . . . . . . . . . . . 2112 REFIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . 2213 ELECTRICAL DATA BASIC UNIT - 25 TON . . . . . . . . 2214 ELECTRICAL DATA BASIC UNIT - 30 TON . . . . . . . . 2315 ELECTRICAL DATA BASIC UNIT - 40 TON . . . . . . . . 2316 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC

HEAT - 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2417 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC

HEAT - 30 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2518 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC

HEAT - 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2619 ELECTRICAL DATA BASIC UNIT WITH POWER EX-

HAUST - 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2720 ELECTRICAL DATA BASIC UNIT WITH POWER EX-

HAUST - 30 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2821 ELECTRICAL DATA BASIC UNIT WITH POWER EX-

HAUST - 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2922 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST

& ELECTRIC HEAT - 25 TON . . . . . . . . . . . . . . . . . . . 3023 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST

& ELECTRIC HEAT - 30 TON . . . . . . . . . . . . . . . . . . . 3324 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST

& ELECTRIC HEAT - 40 TON . . . . . . . . . . . . . . . . . . . 3625 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 4626 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . 4827 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . 5128 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . 5429 COMPONENT STATIC RESISTANCE . . . . . . . . . . . . 5730 SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . . . 5831 EXHAUST FAN DRIVE DATA . . . . . . . . . . . . . . . . . . . 5832 POWER EXHAUST - ONE FORWARD CURVED

FAN 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5933 POWER EXHAUST - TWO FORWARD CURVED

FANS - 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Tbl. # Pg. #

34 BELT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . 6435 BLOWER SPEED RATE OF CHANGE . . . . . . . . . . . . 6536 25 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 6637 30 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 6638 40 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 6739 DRIVE ADJUSTMENT FOR POWER EXHAUST -

25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6740 DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 &

40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6841 GAS RATE - CUBIC FEET PER HOUR . . . . . . . . . . . 6942 COOLING STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7143 COMPRESSOR MINIMUM OFF TIMES . . . . . . . . . . . 8144 WEEKLY SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . 8645 HOLIDAY SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . 8646 ALARM DEFAULT CODES . . . . . . . . . . . . . . . . . . . . . 9347 STATUS LED CHART . . . . . . . . . . . . . . . . . . . . . . . . . 9548 ACRONYMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10049 INPUT SIGNAL TO Y1 ACTUATOR POSITION . . . . 10250 SIMPLICITY CONTROL INPUTS . . . . . . . . . . . . . . . 10351 SIMPLICITY CONTROL OUTPUTS . . . . . . . . . . . . . 10552 SETTABLE SYSTEM PARAMETERS. . . . . . . . . . . . 11253 SYSTEM MOISTURE INDICATOR . . . . . . . . . . . . . . 11454 STEAM COIL (1 ROW, 25 & 30 TON). . . . . . . . . . . . 11555 STEAM COIL (1 ROW, 40 TON) . . . . . . . . . . . . . . . . 11556 STATIC RESISTANCE STEAM COIL (25 & 30 TON) 11557 STATIC RESISTANCE STEAM COIL (40 TON) . . . . 11558 HOT WATER COIL (1 ROW 25 & 30 TON) . . . . . . . 11559 HOT WATER COIL (1 ROW, 40 TON) . . . . . . . . . . . 11660 WATER PRESSURE DROP (1 ROW, 25 &

30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11661 WATER PRESSURE DROP (1 ROW, 40 TONS) . . . 11662 HOT WATER COIL (2 ROW, 25 & 30 TON) . . . . . . . 11663 WATER PRESSURE DROP (2 ROW, 25 &

30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11764 WATER PRESSURE DROP (2 ROW, 40 TON) . . . . 11765 STATIC RESISTANCE HOT WATER COIL

(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11766 STATIC RESISTANCE HOT WATER COIL

(40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11767 INDOOR BLOWER BEARING LUBRICATION

SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

Page 6: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

6 Unitary Products Group

NOMENCLATURE

Page 7: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 7

FIGURE 1 - COMPONENT LOCATION

FILTER ACCESS

EVAPORATOR COIL

AND DRAINPAN ACCESS

POWER & CONTROL WIRING

COMPRESSOR ACCESS

HEAT SECTION

POWER EXHAUST ACCESS

FILTER ACCESS

EVAPORATOR COIL

AND DRAINPAN ACCESS

HEAT SECTION

SUPPLY BLOWER & MOTOR

FILTER DRIERS

RIGHT

SIDE

LEFT SIDE

FRONT

REAR

REAR

Page 8: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

8 Unitary Products Group

GENERAL

YORK Model Y22/Y23/Y24 units are single package coolingonly or cooling with gas, electric, hot water or steam heatingdesigned for outdoor installation on a rooftop and for non-res-idential use.

The units are completely assembled on rigid, permanentlyattached base rails. All piping, refrigerant charge, and electri-cal wiring is factory installed and tested. The units requireelectric power, gas, steam, or hot water connections and ductconnections. Gas fired units also require installation of a fluegas outlet hood.

SAFETY CONSIDERATIONS

NOTES, CAUTIONS AND WARNINGS

Installer should pay particular attention to the words: NOTE,CAUTION, and WARNING. Notes are intended to clarify ormake the installation easier. Cautions are given to preventequipment damage. Warnings are given to alert installer thatpersonal injury and/or equipment damage may result if instal-lation procedure is not handled properly.

GAS FIRED MODELS

DO NOT store or use gasoline or other flammable vapors andliquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance. Do not touch any electricalswitch. Do not use any phone in your building. Immediatelycall your gas supplier from a neighbor’s phone. Follow thegas supplier’s instructions. If you cannot reach your gas sup-plier, call the fire department.

ALL MODELS

Installation and servicing of air conditioning equipment canbe hazardous due to system pressure and electrical compo-nents. Only trained and qualified service personnel shouldinstall, repair or service air conditioning equipment.

Untrained personnel can perform basic maintenance func-tions of cleaning coils and filters and replacing filters. All otheroperations should be performed by trained service personnel.When working on air conditioning equipment, observe pre-cautions in the literature, tags and labels attached to the unitand other safety precautions that may apply.

Follow all safety codes, including ANSI Z223.1-Latest Edi-tion: wear safety glasses and work gloves; use quenchingcloth for unbrazing operations; have fire extinguisher avail-able for all brazing operations.

INSPECTION

As soon as a unit is received, it should be inspected for possi-ble damage during transit. If damage is evident, the extent ofdamage should be noted on the carrier’s freight bill. A sepa-rate request for inspection by the carrier’s agent should bemade in writing.

The furnace and its individual shut-off valve mustbe disconnected from the gas supply piping sys-tem during any pressure testing of that system attest pressures in excess of 0.5 psig. Pressuresgreater than 0.5 will cause gas valve damageresulting in a hazardous condition. If gas valve issubjected to a pressure greater than 0.5 psig, itmust be replaced. The furnace must be isolatedfrom the gas supply piping system by closing itsindividual manual shut-off valve during any pres-sure testing of that system at test pressures equalto or less than 0.5 psig.

This Furnace is not to be used for temporary heat-ing of buildings or structures under construction.

Before performing service or maintenance opera-tions on unit, turn off main power switch to unit.Electrical shock could cause personal injury.

Improper installation, adjustment, alteration, ser-vice or maintenance can cause injury or propertydamage. Refer to this manual. For assistance oradditional information consult a qualified installer,service agency or the gas supplier.

Page 9: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 9

REFERENCE

Additional information is available in the following referenceforms:

• 036-21091-004 - Technical Guide• TBD - Unit Replacement Parts List (25, 30 & 40 Tons)

APPROVALS

Designed certified by CGA, ETL, CETL as follows:

1. For use as a forced air furnace with cooling unit (gas heat models).

2. For outdoor installation only.

3. For installation on combustible material and may be installed directly on combustible flooring or Class A, Class B or Class C roof covering materials.

4. For use with natural gas (convertible to LP with kit).

Not suitable for use with conventional venting systems.

INSTALLATION

LIMITATIONS

The installation of this unit must conform to local buildingcodes, or in the absence of local codes, with ANSI Z223.1Natural Fuel Gas Code and /or CAN/CGA B149 installationcodes.

In U.S.A.:

1. National Electrical Code ANSI/NFPA No. 70-Latest Edi-tion.

2. National Fuel Gas Code Z223.1-Latest Edition.

3. Gas-Fired Central Furnace Standard ANSI Z21.47-Lat-est Edition.

4. Local gas utility requirements.

Refer to Table 1 for Cooling and Electrical Application Dataand to Table 2 for Gas Heat Application Data.

After installation, gas fired units must be adjusted to obtain atemperature rise within the range specified on the unit ratingplate.

If components are to be added to a unit to meet local codes,they are to be installed at the contractor's and/or the cus-tomer's expense.

Size of unit for proposed installation should be based on heatloss / heat gain calculation made according to the methods ofthe Air Conditioning Contractors of America (ACCA).

LOCATION

Use the following guidelines to select a suitable location forthese units:

1. Unit is designed for outdoor installation only.

2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.

3. Suitable for roof mount on curb.

4. Roof structures must be able to support the weight of the unit and its accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.

5. Maintain level tolerance to 3/4 inches across width and 2 inches along length.

TABLE 1: COOLING & ELECTRICAL APPLICATION

UNIT POWER SUPPLY

VOLTAGE VARIATIONS

MIN. VOLTS MAX VOLTS

575-3-60 540 630

208/230-3-60 187 252

460-3-60 432 504

TABLE 2: COOLING & ELEC. APP. LIMITATIONS

LIMITATIONSMODEL

Y22 Y23 Y24

Supply Air CFM (min./max)

6,000-12,5000

6,000-15,000

8,000-20,000

Entering Wet Bulb Temp (F°) (min./max) 57/75 57/75 57/75

Ambient Temp 40/120 40/120 40/120

Min. Air Temperature on Gas Fired Heat Exchangers (°F)

Aluminized 25 25 25

Stainless 0 0 0

Page 10: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

10 Unitary Products Group

TABLE 3: GAS APPLICATION DATA

INPUT CAPACITY (MBH)

AVAILABLE ON

MODELS

GAS RATE1

(FT.3/HR.)

TEMP. RISE °FAT FULL INPUT2 30 TO 2,000 FEET ABOVE

SEA LEVEL3,000 FEET ABOVE

SEA LEVEL44,000 FEET ABOVE

SEA LEVEL4

MAX. MIN. MAX. MIN. MAX. MIN. MIN. MAX.

233 233 205 205 196 196 Y22, Y23, Y24 217 5 35

466 233 410 205 392 196 Y22, Y23, Y24 434 15 45

6995 233 615 205 587 196 Y24 650 20 50

1. Based on maximum input and 1075 Btu/Ft.32. The air flow must be adjusted to obtain a temperature rise within the range shown.3. On VAV units, individual room damper boxes must go full open in heating mode to ensure airflow falls within temperature rise

range.4. For operation at elevations above 2,000 feet and, in the absence of specific recommendations from local authority having jurisdic-

tion, equipment ratings shall be reduced at the rate of 4% for each 1,000 feet above sea level.5. Minimum heating CFM for 699 MBH input heat is 11,700 CFM.

If a unit is to be installed on a roof curb other thana YORK roof curb, gasketing must be applied to allsurfaces that come in contact with the unit under-side.

If a unit is to be installed on an angle iron frame itis recommended that it be sized to allow the bot-tom rail to overhang to facilitate installation of con-densate drains (see Fig. 4).

FIGURE 2 - TYPICAL RIGGING

CABLES

SPREADER BARS(3 PLACES)

20"

A

B

C

UNITUNIT

WEIGHT(LB)

LIFTING LUG DIMENSIONS

A B C

25 TON

30 TON

40 TON

SEE NOTE 5

SEE NOTE 5

SEE NOTE 5

8' 4"

8' 4"

8' 4" 6' 9"

6' 9"

6' 9"

2' 3"

2' 3"

2' 3"

RIGGING:

1) RIG WITH 6 CABLES, THREE SPREADER BARS - 95" ACROSS WIDTH AND SPREADER BARS OF LENGTH EQUAL TO "A + B".

2) CENTER OF GRAVITY INCLUDES ECONOMIZER, POWER EXHAUST AND INLET GUIDE VANES.

3) CAUTION: ALL PANELS MUST BE SECURED IN PLACE WHEN THE UNIT IS LIFTED.

4) CAUTION: THE CONDENSER COIL SHOULD BE PROTECTED FROM DAMAGE BY THE RIGGING CABLES WITH PLYWOOD OR OTHER SUITABLE MATERIALS.

5) REFER TO INSTALLATION INSTRUCTIONS.

NOTICE TO RIGGERS

Page 11: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 11

NOTE: If the Millennium is VAV with ERV, add the weight of an exhaust VFD - it will be in the unit.

.

TABLE 4: UNIT WEIGHTSCOMPONENT 25 TON 30 TON 40 TON

Basic Unit 4350 4550 4950Gas Heat

233 MBH 180 180 180466 MBH 320 320 320700 MBH - - 450

Electric Heat40KW 40 40 4080KW 105 105 105

108KW 110 110 110Hot Water Heat

1 Row Coil 70 70 702 Row Coil 85 85 85

Steam Heat1 Row Coil 85 85 85

BlowerForward Curve Fan (Std Fan) 0 0 0

FC IGV 155 155 175Air Foil Fan 135 135 155

AF IGV 155 155 180Motor - Supply Fan

7.5hp 110 - -10hp 145 145 14515hp 200 200 20020hp 240 240 24025hp - 300 300

Supply Fan Motor VFD See Table 5Refrigeration

Hi Cap. Evap. Coil - 50 15T-Coat Evap. 32 30 40T-Coat cond. 32 30 40

Hot Gas Bypass 10 10 10Low Ambient Head Pressure Control

208-230/380/460 5 5 5575 25 25 25

Filters6" Rigid 70 70 70

Exhaust1

1. If ERV and Supply Fan VAV are selected, add the weight of an Exhaust VFD, Table 5.

Exhaust TypeBarometric 45 65 65Modulated 140 275 275

Exhaust Motor5hp 80 80 80

7.5hp 110 110 11010hp 145 145 14515hp 200 200 200

Exhaust Motor VFD See Table 6Economizer

Std. Econ. 235 235 235Econ. w/ERV 50 50 50

ControlDisconnect 15 15 15110V outlet 55 55 55Optilogic 20 20 20

Roof CurbPartial Curb 415 415 415

Full Curb 615 615 615

TABLE 5: SUPPLY FAN MOTOR VFD WEIGHTS

Supply Fan Motor VFD 230V 460V 575V

W/O Bypass

7.5hp 60 25 30

10hp 60 25 30

15hp 75 50 60

20hp 75 50 60

25hp 115 50 60

W/Bypass

7.5hp 155 90 120

10hp 155 90 120

15hp 185 140 155

20hp 185 140 155

25hp 255 140 155

TABLE 6: EXHAUST FAN MOTOR VFD WEIGHTS

Exhaust Fan Motor 230V 460V 575V

W/O Bypass

5hp 15 10 20

7.5hp 50 15 20

10hp 50 15 20

15hp 65 40 50

25hp 255 140 155

FIGURE 3 - CENTER OF GRAVITY1

1. Refer to Tables 7 and 8 for A, B, C, D and X and Y data respectively.

All panels must be secured in place when the unit islifted.The condenser coils should be protected from dam-age by the rigging cables with plywood or other suit-able material.An adhesive backed cover is provided over the out-side of the combustion air inlet opening on gas firedunits to prevent moisture from entering the unitwhich could cause damage to electrical compo-nents. Allow this closure label to remain in placeuntil the combustion air hood is to be installed (Referto Figures 7, 8, & 9).

RIGHT SIDE

C�E�N�T�E�R��O�F��G�R�A�V�I�T�Y�

C�O�N�D�E�N�S�E�R�C�O�I�L��E�N�D�

LEFT SIDE

X�

Y�

8�3�"�

2�4�0�"�

A�

B�

C�

D�

�����

Page 12: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

12 Unitary Products Group

RIGGING AND HANDLING

This unit is not designed to be handled with a fork-truck.

Exercise care when moving the unit. Do not remove anypackaging until the unit is near the place of installation. Rigthe unit by attaching chain or cable slings to the holes pro-vided in lifting lugs. Spreaders MUST be used across the topof the unit. Refer to Figure 2.

• Rig with six cables and spread with four 95-inch spread-ers across width and two spreaders of length equal to A + B.

• Refer to Tables 4 and 7 for unit weight.

• Center of gravity includes economizer, exhaust or return air fan and inlet guide vanes (Refer to Table 8).

NOTES: Basic Unit = cooling only, 10hp FC fan.+ Econ = +235lb+ Heat = single stage gas, 180 lb+ Power Exhaust = modulating 7.5hp

CLEARANCES

All units require certain clearances for proper operation andservice. Installer must make provisions for adequate combus-tion and ventilation air in accordance with section 5.3, Air forCombustion and Ventilation of the National Fuel Gas CodeANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149installation codes-Latest Edition and/or applicable provisionsof the local building codes. Refer to Figure 10 for clearancesrequired for combustible construction, servicing, and properunit operation.

TABLE 7: UNIT CORNERWEIGHT

UNIT DESCRIPTION

25 TON 30 TON 40 TON

A B C D A B C D A B C D

Basic Unit 1033 1033 1215 1215 1079 1053 1269 1294 1131 1131 1417 1417

Basic Unit With Economizer 1112 1112 1253 1253 1185 1157 1280 1308 1205 1205 1460 1460

Basic Unit With Economizer and

Gas or Electric Heat1162 1162 1293 1293 1209 1155 1346 1400 1255 1224 1500 1531

Basic Unit With Economizer and

Gas or Electric Heat and Power Exhaust

1284 1284 1296 1296 1359 1298 1389 1449 1416 1384 1532 1563

TABLE 8: UNIT CENTER OF GRAVITY

MODEL25 TON 30 TON 40 TON

X Y X Y X Y

Basic Unit 99” 46” 98” 45” 93” 46"

Basic Unit With Econ. 110” 46” 108” 45” 97” 46"

Basic Unit With Econ. & Gas or

Elect. Heat, Steam or Hot Water Heat

104” 45” 102” 44” 96” 45"

Basic Unit With Econ. & Gas or Elect. Heat, &

Power Exhaust

118” 45” 112” 44” 108” 45"

(COOLING OPERATION) Do not permit overhang-ing structures or shrubs to obstruct condenser airdischarge outlet, combustion air inlet or vent out-lets.

Page 13: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 13

DUCTWORK

Ductwork should be designed and sized according to themethods in Manual Q of the Air Conditioning Contractors ofAmerica (ACCA).

A closed return duct system should be used. This will not pre-clude use of economizers or outdoor fresh air intake. Thesupply and return air duct connections at the unit should bemade with flexible joints to minimize noise.

When the unit is equipped with power exhaust fans or returnair fan the return duct should have a 90 elbow before openingto the building space to abate noise.

The supply and return air duct systems should be designedfor the CFM and static pressure requirements of the job. Theyshould NOT be sized to match the dimensions of the ductconnections on the unit.

If the unit is equipped with hot water or steam heat then thesupply air direction will be down only.

AIR HOODS FOR FIXED OUTSIDE AIR(UNITS WITHOUT ECONOMIZER)

These hoods are factory installed. The dampers may beadjusted by loosening the thumb screw, turning the lever tothe desired position, and retightening the thumb screw.

AIR HOODS FOR ECONOMIZER

There are (3) economizer outside air intake hoods providedwith the unit. The hood on the end of the unit is factorymounted. The (2) front and rear hoods are made operationalper the following instructions.

Remove the screws holding the economizer hood shippingcovers in place. Discard covers.

Rotate the hoods out (each hood is hinged in the lower cor-ner). Secure the hoods with screws along the top and sides.

Apply a bead of RTV sealer along the edge of both hoodsand each pivot joint to prevent water leakage.

Seal any unused screw holes with RTV or by replacing thescrew.

AIR HOODS FOR EXHAUST AIR

When furnished, these hoods and dampers are factoryinstalled.

CONDENSATE DRAIN

There is one condensate drain connection. Trap the connec-tion per Figure 4. The trap and drain lines should be pro-tected from freezing.

Plumbing must conform to local codes. Use a sealing com-pound on male pipe threads. Install condensate drain linesfrom the 1-1/2 inch NPT female connections on the unit to anopen drain.

(GAS HEATING OPERATION)

Excessive exposure to contaminated combustionair will result in safety and performance relatedproblems. To maintain combustion air quality, therecommended source of combustion air is the out-door air supply.

The outdoor air supplied for combustion should befree from contaminants due to chemical exposurethat may be present from the following sources:

• Commercial buildings • Indoor pools • Laundry rooms • Hobby or craft rooms • Chemical storage areas

The following substances should be avoided tomaintain outdoor combustion air quality:

• Permanent wave solutions • Chlorinated waxes and cleaners • Chlorine based swimming pool cleaners • Water softening chemicals • De-icing salts or chemicals • Carbon tetrachloride • Halogen type refrigerants • Cleaning solvents (such as perchloroethylene) • Printing inks, paint removers, varnishes, etc. • Hydrochloric acid • Cements and glues • Antistatic fabric softeners for clothes dryers • Masonry acid washing materials

Page 14: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

14 Unitary Products Group

SERVICE ACCESS

Access to all serviceable components is provided by the fol-lowing hinged doors:

• Furnace compartment

• Supply Air Fan compartment Evaporator Coil compart-ment (three doors)

• Filter compartment economizer compartment (two doors)

• Power Exhaust compartment (two doors)

• Main control panels (one door)

Refer to Figure 1 for location of these access panels.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted and ready for operation.

FILTERS

Throwaway or rigid filters are supplied with each unit. Filtersmust always be installed ahead of evaporator coil and mustbe kept clean or replaced with same size and type. Dirty fil-ters will reduce the capacity of the unit and will result infrosted coils or safety shutdown. Required filter sizes areshown in Table 11. The unit should not be operated withoutfilters properly installed.

THERMOSTAT (CONSTANT VOLUME UNITS)

The thermostat, if used, should be located on an inside wallapproximately 56 inches above the floor where it will not besubject to drafts, sun exposure or heat from electrical fixturesor appliances. Follow manufacturer's instructions enclosedwith sensor for general installation procedure (See Figure 5).Refer to Table 9 for control wire sizing and maximum length.

SPACE SENSOR (VARIABLE AIR VOLUME UNITS)

The space sensor, if used, should be located on an insidewall approximately 56 inch above the floor where it will not besubject to drafts, sun exposure or heat from electrical fixturesor appliances. Follow manufacturer's instructions enclosedwith sensor for general installation procedure.

FIGURE 4 - RECOMMENDED DRAIN PIPING

Make sure that all screws and panel latches arereplaced and properly positioned on the unit tomaintain an air-tight seal.

DO NOT loosen compressor mounting bolts.

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � �

� � � � � � � � � �

� � � � � � � � � � � � � � �� � � � � � � � � � � � �

� � � � � � � �

� � � �� � � �� �

� � � � � � � � � � �

� � � � � � �

FIGURE 5 - TYPICAL THERMOSTAT WIRING

TABLE 9: CONTROL WIRE SIZES

WIRE SIZE MAXIMUM LENGTH

20 AWG 100 Feet

18 AWG 150 Feet

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� �

� �

� �

� �

� �

� �

� �

� � � � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � � � � � �

� � � � � �

� � �

� � �

� � � � � � � � �

� � � � � � � � � �

� � � � � � � � � �

Page 15: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 15

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of NationalElectrical Code (NEC) ANSI / NFPA 70-Latest Edition and / orlocal ordinances. The unit must be electrically grounded inaccordance with the NEC and / or local codes. Voltage toler-ances which must be maintained at the compressor terminalsduring starting and running conditions are indicated on theunit Rating Plate and Table 1.

The internal wiring harnesses furnished with this unit are anintegral part of the design certified unit. Field alteration tocomply with electrical codes should not be required. If any ofthe wire supplied with the unit must be replaced, replacementwire must be of the type shown on the wiring diagram and thesame minimum gauge as the replaced wire.

Power supply to the unit must be NEC Class 1 and mustcomply with all applicable codes. A disconnect switch mustbe provided (factory option available). The switch must beseparate from all other circuits. Wire entry at knockout open-ings requires conduit fittings to comply with NEC and/or LocalCodes. Refer to Figures 13, 14, 15, and 16 for installationlocation of openings.

If installing a field mounted disconnect on the unit, refer toFigure 17 for the recommended mounting location. Unit-strutTM or equivalent rails should be mounted as shown toprovide structure for mounting. The location of the railsshould be adjusted to fit the disconnect within the dimensionsshown. Conduit run from the disconnect to the power entrylocation in the baserail should be routed so that it does notinterfere with the doors of the unit access panels.

NOTE: Since not all local codes allow the mounting of a dis-connect on the unit, please confirm compliance withlocal code before mounting a disconnect on the unit.

Electrical wiring must be sized properly to carry the load.Each unit must be wired with a separate branch circuit feddirectly from the meter panel and properly fused.

Refer to Figure 5 for typical field wiring and to the appropriateunit wiring diagram mounted inside control doors for controlcircuit and power wiring information.

POWER WIRING DETAIL

Units are factory wired for the voltage shown on the unitnameplate. The main power block requires copper wires.Refer to Electrical Data Tables 13 through 24 to size powerwiring, fuses and disconnect switch. All field supplied wiring,fuses and disconnects must comply with applicable NECcodes.

Power wiring is brought into the unit through the side of thebaserail or the bottom of the unit/control box inside the curb.The baserail has a 2-1/2” diameter hole for field wiring and a3-5/8” hole is provided for a through-the-curb connection. Aremovable patch plate covers both the openings.

ERV

The ERV [Energy Recovery Ventilation] is a separate air han-dler that attaches to the exhaust end of the 25-40T Millen-nium packaged rooftop unit. The ERV is shipped separatelyand assembled to the Millennium at the jobsite. An 'ERV' Mil-lennium is shipped with an end configuration and electrichookups designed to mate with the ERV. This option is avail-able only with the Simplicity control, and no other powerexhaust option can be supplied if an ERV is selected.

The ERV incorporates a rotating heat exchange wheel and apair of exhaust blowers. It exhausts return air through thewheel, capturing the thermal energy of the exiting hot or coldair as it passes. As the wheel rotates, the incoming airstream,pulled through by the supply fan, regains that energy.

The Millennium ERV has a terminal block and mating con-nectors to simplify hooking up the two systems. The controlsof both units are factory set to interact properly. Power for theERV blower motors and controls is provided through the Mil-lennium unit. The Millennium /ERV dataplate informationincludes the ERV electrical load.

The Millennium Simplicity control has parameters for theERV; ref. the parameter list. When economizer and ERVoptions are selected on the same unit, the Simplicity controland the ERV have specific connections and internal rules forthat operation.

Also refer to the ERV Installation Instructions packaged withthe ERV.

Use care to avoid damage when drilling holes forthe disconnect mounting.

When connecting electrical power and control wir-ing to the unit, waterproof connectors MUST BEUSED so that water or moisture cannot be drawninto the unit during normal operation. The abovewaterproofing conditions will also apply wheninstalling a field-supplied disconnect switch.

Waterproof connections MUST be used to ensurethat water cannot penetrate the roof or roof curb.

Page 16: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

16 Unitary Products Group

GAS HEATING

GAS PIPING

Proper sizing of gas piping depends on the cubic feet perhour of gas flow required, specific gravity of the gas and thelength of run. National Fuel Gas Code Z223.1-Latest Editionshould be followed in all cases unless superseded by localcodes or gas company requirements. Refer to Table 10.

The heating value of the gas may differ with locality. Thevalue should be checked with the local gas utility.

NOTE: There may be a local gas utility requirement specify-ing a minimum diameter for gas piping. All unitsrequire a 1-1/4 inch pipe connection at the entrancefitting. Line should not be sized smaller than theentrance fitting size.

GAS CONNECTION

The gas supply line should be routed within the space andpenetrate the roof at the gas inlet connection of the unit.Refer to Fig. 13 -- 16 to locate the access opening. Typicalsupply piping arrangements are shown in Figure 5.

Gas piping recommendations:

1. A drip leg and a ground joint union must be installed in the gas piping.

2. When required by local codes, a manual shut-off valve will have to be installed outside of the unit.

3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only.

4. All piping should be cleaned of dirt and scale by ham-mering on the outside of the pipe and blowing out the loose particles. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air.

5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under Limitations. After the gas connections have been com-pleted, open the main shutoff valve admitting normal gas pressure to the mains. Check all joints for leaks with

On VAV units with gas fired furnace, ALL INDIVID-UAL ROOM DAMPER BOXES MUST BE CON-TROLLED FULL OPEN DURING HEATINGOPERATION TO ENSURE PROPER AIRFLOWOVER THE FURNACE. A control contact betweenD1 and D2 on TB3 is provided for the damper boxinterlock. This contact is normally open, thus isclosed during heating operation.

TABLE 10: PIPE SIZES

LENGTH IN FEET

NOMINAL IRON PIPE, SIZE

1-1/4 IN.1

1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas.

1-1/2 IN.1 2 IN.1

10 1,050 1,600 3,050

20 730 1,100 2,100

30 590 890 1,650

40 - 760 1,450

50 - - 1,270

60 - - 1,150

70 - - 1,050

80 - - 990

FIGURE 6 - TYPICAL GAS PIPING CONNECTION

Natural gas may contain some propane. Propane,being an excellent solvent, will quickly dissolvewhite lead or most standard commercial com-pounds. Therefore, a special pipe dope must beapplied when wrought iron or steel pipe is used.Shellac base compounds such as Gaskolac orStalastic, and compounds such as Rectorseal #5,Clyde's or John Crane may be used.

Page 17: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 17

soap solution or other material suitable for the purpose. NEVER USE A FLAME

6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system dur-ing any pressure testing of that system at test pressures in excess of 0.5 psig.

7. A 1/8 inch N.P.T. plugged tapping, accessible for test gage connection, must be installed immediately upstream of the gas supply connection to the furnace.

VENT AND COMBUSTION AIR

NOTE: All the hoods and hardware are shipped within theevaporator section. Each hood must be properlyattached to the furnace doors to assure properoperation and compliance with CSA/ETL safety cer-tification. (Refer to Figure 7 and 8)

The products of combustion are discharged horizontallythrough hooded openings in the gas heat access doors.

233 & 466 MBH HEAT

(Figure 7)

1. Remove the shipping covers that are attached to the heat section door covering the flue outlets.

2. Locate the flue which is shipped in the evaporator sec-tion.

3. Place the flue over the flue outlet with the diverter angles facing up toward the top of the unit and attach with screws provided.

4. Refer to the Gas Furnace Operation Instruction in the Start-up Section of this manual for further instructions.

699 MBH HEAT

(Figure 8)

1. Remove the shipping covers that are attached to the heat section door covering the flue outlets.

2. Locate the flue duct extensions and flue which are shipped between the evaporator and filter section.

Disconnect gas piping from unit when leak testingat pressures greater than 0.5 psig. Pressuresgreater than 0.5 psig will cause gas valve damageresulting in a hazardous condition. If gas valve issubjected to pressure greater than 0.5 psig, it mustbe replaced.

FIGURE 7 - VENT AND COMBUSTION AIR HOODS

� � � � � � � � � � � � � � �

� � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � �

� � � � � � � � � � � � �

� � � � � � � � � � � � � � � � �

� � � � � � � � � � � � � �

FIGURE 8 - 699 MBH HEAT VENT

FIGURE 9 - FLUE EXTENSION

� � � � � � � �

� � � � � �

� � � � � �

� � �

� � � � � � � � � � � � �

� � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � �

Page 18: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

18 Unitary Products Group

3. Place the flue extension (Figure 9) on the flue duct of each furnace section and attach with screws provided.

4. Place the flue in position with the diverter angles facing up toward the top of the unit and attach with screws pro-vided.

5. Place the wind shield over the louvers on the right side of the burner access door and attach with screws provided.

6. Refer to the Gas Furnace Operation Instructions in the Start-up Section of this manual for further information.

ELECTRIC HEAT

Units with electric heat are fully wired and operational whenshipped. Constant volume units are designed for two equalsteps of capacity for 80 and 108 kWH heat; 40 kW heat is onestep only. VAV units are one full step at full heat capacity.

HOT WATER HEAT

The YORK Millennium units (25, 30, and 40 Ton sizes) can befurnished with a YORK hot water coil as the heat source. Oneor two row coil units will be factory installed in the heatingsection.

NOTE: The hot water control valve will not be provided. Theinstaller will need to purchase a hot water controlvalve, to connect the hot water piping and powerwiring at the job site for the hot water heat section tobe operational.

NOTE: For all hot water coils the entering water tempera-ture should not exceed 200°F.

The hot water coil is located downstream of the supply air fanand just above the supply air opening in the bottom of theunit.

Refer to Tables 58 through 66 and Figures 36 through 49 forflow rate and capacity.

FIGURE 10 - CLEARANCES

60"REAR

60"FRONT

60"ENDS

10'

60"ENDS

REQUIRED CLEARANCES

LEFTRIGHTREARFRONTTOP

60"60"60"60"10'

* Right is the side with access to the Electrical / Gas Controls.* is the side with the Condenser Coils

NOTE: DONOT use the unit roof to support any type ofstructure or bracing.

Front

DO NOT use hot water coils as steam coils underany circumstances.

All piping, control valves, and wiring that is fieldinstalled must be properly insulated and conformto all local and national codes.

Page 19: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 19

PIPING CONNECTIONS

The hot water pipping must enter the unit through the floor ofthe heat section compartment. The access doors to the com-partment are gasketed so the compartment can be sealed.However, as added protection for water leakage into thespace, the piping access holes should be sealed with a heatresistant mastic Figure 11 shows the location of the compart-ment and piping connections.

STEAM HEAT

The YORK Millennium units (25, 30 and 40 Ton sizes) can befurnished with a YORK single row steam coil. YORK steamcoils are a factory installed option.

There are no provisions in the coil or controlsequence to prevent freezing of condensate. Thecontrol valve, piping and field installed wiring con-nections are particularly vulnerable because theyare installed in the vestibule outside of the condi-tioned air stream. The installing party will beresponsible for properly insulating and installingpower and control wiring, to the actuator and pip-ing.

In one row hot water coil systems DO NOT exceeda 40 gallons per minute flow rate.

In two row hot water coil systems Do Not exceed a80 gallons per minute flow rate

Condensate will freeze on the control valve andpiping if they are not properly insulated. Insulatingthe control valve and piping is the responsibility ofthe installing party.

Piping access holes should be sealed with a heatresistant mastic to prevent damage to equipment.

DO NOT use tin based solder. Brazing with tinbased solder could cause equipment damage orpossible injury to tenets of the structure that isbeing conditioned.

FIGURE 11 - HOT WATER PIPING CROSS-SEC-TION

FIGURE 12 - STEAM PIPING CROSS-SECTION

� � � � � � � �� � �

� � � � � � � � � � �

� � � � � ! "� � � � � � � ! "

� �

� � # # !

$ � � $ !

� � � # !

� � � $ $ !

� % !

� # � $ !

$ $ � � # !

� � � � � � � �� � � � � � � � � �

� � � � � � � � � � �

� � � � � � �� � � � � �

� � �� � �

� � � � � � � � � � �

� � � � � � � � � & � ! "

� �

� � # # !

$ � � $ !

� % !

� # � $ ! � � � � � ! "

$ !

' !

� � � � � � � �� � � � � � � � � �

$ $ � � # !

� � � � � � � �

� � � � � � �� � � � � �

Page 20: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

20 Unitary Products Group

NOTE: The steam control valve, power and control wiring tothe actuator of the valve is the responsibility of theinstalling party.

PIPING CONNECTIONS

Refer to Tables 54 through 57 and Figures 50 and 51 for flowrate and capacity.

The steam piping must enter the unit through the floor of theheat section compartment. The access doors to the compart-ment are gasketed so the compartment can be sealed. How-ever, as added protection for condensate leakage into thespace, the piping access holes should be sealed with a heatresistant mastic. The following figure illustrates the location ofthe compartment and piping connections.

STATIC PRESSURE CONTROL PLASTIC TUBING

On units with inlet guide vanes (IGV's) and variable fre-quency drives on the supply blower and/or power exhaustfans, pressure sensing tubing must be field supplied andinstalled from differential pressure switches or transducers tothe locations in the building or ductwork where a constantpressure is desired, and to the atmosphere.

The supply air discharge static pressure switch or transduceris located in the blower compartment on the heat section par-tition panel. Plastic tubing (1/4") must be run from the highpressure tap of the transducer to a static pressure tap (fieldsupplied) in the supply duct located at a point where constantpressure is desired. Tubing must also be run between the lowpressure tap of the transducer to atmospheric pressure.

EXHAUST STATIC PRESSURE

If a modulating power exhaust is installed, there will be abuilding pressure sensor (BPS) in the control box directlybelow the Millennium Simplicity. This ± .25 0-5VDC trans-ducer sends a building pressure signal to the control. A sens-ing tube must be installed from a representative location inthe building to the HI power of the transducer.

Changing the adjustment is done to the building pressureparameter in the control.

All piping and control valves, and wiring that isfield installed must be properly insulated and con-form to all local and national codes.

There are no provisions in the coil or controlsequence to prevent freezing of condensate. Thecontrol valve, piping and field installed wiring con-nections are particularly vulnerable because theyare installed in the vestibule outside of the condi-tioned air stream. The installing party will beresponsible for properly insulating and installingpower and control wiring, to the actuator and pip-ing.

DO NOT use steam coils as hot water coils underany circumstances.

In steam coil systems, the steam pressure shallnot exceed 15 PSI.

Piping access holes should be sealed with a heatresistant mastic to prevent damage to equipment.

DO NOT use tin based solder. Brazing with tinbased solder could cause equipment damage orpossible injury to tenets of the structure that isbeing conditioned.

Do not run plastic tubes in the supply or return airducts as air movement could cause erroneoussensing. If tubes penetrate bottom of unit be sureopenings are sealed against air and water leak-age.

Page 21: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 21

TABLE 11: GENERAL PHYSICAL DATA UNIT SIZE 25 TON 30 TON 40 TONUnit EER 10.0 9.5 9.5

Compressor DataNumber/Size 2 x 13 Ton 3 x 10 Ton 4 x 10 Ton

Type Scroll Scroll ScrollUnit Capacity Steps 50%, 100% 33%, 67%, 100% 25%, 50%, 75%, 100%

Indoor Fan and DriveNumber / Type 1 / FC 1 / FC 1 / FC

Diameter x Width (inches) 22 x20 22 x 20 25 x 22HP Range 7.5 - 20 10 - 25 10 - 25

CFM Range (full load) 6,000 - 12,500 6,000 - 15,000 8,000 - 18,000ESP Range 0.2” - 4.0” 0.2" - 4.0” 0.2" - 4.0"

Exhaust FanNumber/Size/Type 1/FC 2/FC 2/FC

HP Range (single motor) 5 - 10 7.5 - 15 7.5 - 15CFM 3,000 - 9,000 4,000 - 18,000 4,000 - 18,000

Standard Evaporator CoilSize (sq. ft.) 26.0 26.0 30.4Rows/FPI 3 / 13 3 / 16 4 / 13

High Capacity Evaporator CoilSize (sq. ft.) 26.0 26.0 30.4Rows/FPI 3/13 4 / 16 4 / 16

Condenser CoilSize (sq. ft.) 52.0 48.8 65.0Rows/FPI 2/16 2 /16 2 /16

Condenser FansQuantity / Diameter (inches) 4 / 24 3 / 24 4 / 24

Nominal CFM 4,600 6,800 6,800Motor HP 3 / 4 1.0 1.0

Electric HeatkW Range 40 - 108 40 - 108 40 - 108

40 kW Capacity Steps 1 1 180 and 108 kW Capacity Steps (CV/VAV) 2 / 1 2 / 1 2 / 1

Natural Gas Heat233 MBH Capacity Steps (CV/VAV) 1 / 1 1 / 1 1 / 1466 MBH Capacity Steps (CV/VAV) 2 / 1 2 / 1 2 / 1699 MBH Capacity Steps (CV/VAV) - 2 / 1 3 / 1

Hot Water CoilSize (inches) 22.5” X 65” 22.5" X 65" 22.5" X 65"

Capacity 25 Ton 30 Ton 40 TonSteam Coil

Size (inches) 21" X 65"Type Steam Coil

Filters 2" Hi. Eff. TA Number / Size 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25

Face Area (sq. Ft.) 30.4 30.4 30.4Filters 2" Pleated, 65%

Number / Size 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25Face Area (sq. Ft.) 30.4 30.4 30.4

Filters 65% Rigid w/ 2" TA PrefiltersNumber / Size 4 / 16 x 25 & 6 / 20 x 25 4 /16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25

Face Area (sq. Ft.) 30.4 30.4 30.4Filters 95% Rigid w/ 2" TA Prefilters

Number / Size 4 / 16 x 25 / 6 / 20 x 25 4 / 16 x 25 / 6 / 20 x 25 4 / 16 x 25 / 6 / 20 x 25Face Area (sq. Ft.) 30.4 30.4 30.4

Page 22: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

22 Unitary Products Group

TABLE 12: REFIGERANT CHARGE

UNIT (TONS) MODEL TYPE FACTORY/ FIELD CHARGED

CHARGE

SYS #1 SYS #2 SYS #3 SYS #4

25 wo/HGBP R22 Factory 27 lb. / 0 oz. 26lb / 0oz - -

30 wo/HGBP R22 Factory 13 lb. / 4 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. -

25 w/HGBP R22 Factory 27 lb. / 8 oz. 26 lb. / 0oz - -

30 w/HGBP R22 Factory 14 lb. / 0 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. -

40 wo/HGBP R22 Factory 15 lb. / 5 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz.

40 w/HGBP R22 Factory 15 lb. / 13 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz.

30 wo/HGBP R22 Factory 14 lb. / 6 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -

30 w/HGBP R22 Factory 15 lb. / 2 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -

TABLE 13: ELECTRICAL DATA BASIC UNIT - 25 TON

VOLTAGE

COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT

QTY. RLA LRA QTY FLA HP FLA MCA MAX OVERCURRENT PROTECTION DEVICE

208-3-60 2 45.7 350 4 7.6 ea.

7.5 24.2 157 200

10 30.8 164 200

15 46.2 180 225

20 59.4 196 250

230-3-60 2 45.7 350 4 6.9 ea.

7.5 22.0 152 175

10 28.0 158 200

15 42.0 172 200

20 54.0 187 225

460-3-60 2 24.3 158 4 3.5 ea.

7.5 11.0 80 100

10 14.0 83 100

15 21.0 90 110

20 27.0 96 110

575-3-60 2 19.3 125 4 3.0 ea.

7.5 9.0 64 80

10 11.0 66 80

15 17.0 72 90

20 22.0 78 100

Page 23: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 23

TABLE 14: ELECTRICAL DATA BASIC UNIT - 30 TON

VOLTAGE

COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT

QTY. RLA LRA QTY. FLA TOTAL HP FLA MCA MAX. OVERCURRENT PROTECTION DEVICE

208-3-60 3 38.5 228 3 4.0 ea. 12.0

10 30.8 168 200

15 46.2 185 225

20 59.4 202 250

25 74.8 221 250

230-3-60 3 38.5 255 3 3.6 ea. 10.8

10 28 164 200

15 42 179 200

20 54 194 225

25 68 211 250

460-3-60 3 18.8 127 3 2.2 ea. 6.6

10 14 81 90

15 21 88 100

20 27 96 110

25 34 104 125

575-3-60 3 15.7 100 3 1.4 ea. 4.2

10 11 66 80

15 17 73 80

20 22 79 100

25 27 85 110

TABLE 15: ELECTRICAL DATA BASIC UNIT - 40 TON

VOLTAGE

COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT OVERCURRENT PROTECTION DEVICE

QTY. RLA LRA QTY. FLA TOTAL HP FLA MCA MAX. OVERCURRENT PROTECTION DEVICE

208-3-60 4 38.5 228 4 4.0 ea. 12.0

10 30.8 210 225

15 46.2 228 250

20 59.4 244 300

25 74.8 264 300

230-3-60 4 38.5 255 4 3.6 ea. 14.4

10 28 206 225

15 42 221 250

20 54 236 250

25 68 253 300

460-3-60 4 18.8 127 4 2.2 ea. 8.8

10 14 101 110

15 21 109 125

20 27 116 125

25 34 125 150

575-3-60 4 15.7 100 4 1.4 ea. 5.6

10 11 83 90

15 17 90 100

20 22 96 110

25 27 102 125

Page 24: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

24 Unitary Products Group

TABLE 16: ELECTRICAL DATA BASIC UNIT WITH ELECTRIC HEAT - 25 TON

VOLTAGEELECTRIC HEAT SUPPLY AIR MOTOR BASIC UNIT W/ ELECTRIC HEAT

NOMINAL KW APPLIED KW HP FLA MCA MAX OVERCURRENT PROTECTION DEVICE

208-3-60

40 30

7.5 24.2 157 20010 30.8 164 20015 46.2 180 22520 59.4 196 250

80 60.1

7.5 24.2 197 22510 30.8 205 22515 46.2 225 25020 59.4 241 300

230-3-60

40 40

7.5 22.0 152 17510 28.0 158 20015 42.0 172 20020 54.0 187 225

80 80

7.5 22.0 212 25010 28.0 219 25015 42.0 237 25020 54.0 252 300

460-3-60

40 40

7.5 11.0 80 10010 14.0 83 10015 21.0 90 11020 27.0 96 110

80 80

7.5 11.0 106 12510 14.0 110 12515 21.0 118 12520 27.0 126 150

108 108

7.5 11.0 138 15010 14.0 142 17515 21.0 151 17520 27.0 158 175

575-3-60

40 40

7.5 9.0 64 8010 11.0 66 8015 17.0 72 9020 22.0 78 100

80 80

7.5 9.0 92 11010 11.0 94 11015 17.0 102 11020 22.0 108 125

108 108

7.5 9.0 120 15010 11.0 122 15015 17.0 130 15020 22.0 136 150

Page 25: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 25

TABLE 17: ELECTRICAL DATA BASIC UNIT WITH ELECTRIC HEAT - 30 TON

VOLTAGEELECTRIC HEAT SUPPLY AIR MOTOR BASIC UNIT WITH ELECTRIC HEAT

NOMINAL KW APPLIED KW HP FLA MCA MAX OVERCURRENT PROTECTION DEVICE

208-3-60

40 30

10 30.8 210 22515 46.2 228 25020 59.4 244 30025 74.8 264 300

80 60.1

10 30.8 210 22515 46.2 228 25020 59.4 244 30025 74.8 264 300

230-3-60

40 40

10 28 206 22515 42 221 25020 54 236 25025 68 253 300

80 80

10 28 227 25015 42 245 25020 54 260 30025 68 277 300

460-3-60

40 40

10 14 101 11015 21 109 12520 27 116 12525 34 125 150

80 80

10 14 114 12515 21 122 12520 27 130 15025 34 139 150

108 108

10 14 147 17515 21 156 17520 27 164 17525 34 172 200

575-3-60

40 40

10 11 83 9015 17 90 10020 22 96 11025 27 102 125

80 80

10 11 94 11015 17 102 11020 22 108 12525 27 114 125

108 108

10 11 122 15015 17 130 15020 22 136 15025 27 142 150

Page 26: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

26 Unitary Products Group

TABLE 18: ELECTRICAL DATA BASIC UNIT WITH ELECTRIC HEAT - 40 TON

VOLTAGE

ELECTRICHEAT

SUPPLYAIR

MOTOR

BASIC UNIT WITHELECTRIC HEAT

NOMINAL KW APPLIED KW HP FLA MCA MAX. OVERCURRENTPROTECTION DEVICE

208-3-60

40 30

10 30.8 210 22515 46.2 228 25020 59.4 244 30025 74.8 264 300

80 60.1

10 30.8 210 22515 46.2 228 25020 59.4 244 30025 74.8 264 300

230-3-60

40 40

10 28.0 206 22515 42.0 221 25020 54.0 236 25025 68.0 253 300

80 80

10 28.0 227 25015 42.0 245 25020 54.0 260 30025 68.0 277 300

460-3-60

40 40

10 14.0 101 11015 21.0 109 12520 27.0 116 12525 34.0 125 150

80 80

10 14.0 114 12515 21.0 122 12520 27.0 130 15025 34.0 139 150

108 108

10 14.0 147 17515 21.0 156 17520 27.0 164 17525 34.0 172 200

575-3-60

40 40

10 11.0 83 9015 17.0 90 10020 22.0 96 11025 27.0 102 125

80 80

10 11.0 94 11015 17.0 102 11020 22.0 108 12525 27.0 114 125

108 108

10 11.0 122 15015 17.0 130 15020 22.0 136 15025 27.0 142 150

Page 27: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 27

TABLE 19: ELECTRICAL DATA BASIC UNIT WITH POWER EXHAUST - 25 TON

VOLTAGE

SUPPLY AIR MOTOR EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT W/ EXHAUST FAN

HP HP FLA MCA MAX OVERCURRENT PROTECTION DEVICE

208-3-60

7.55 16.7 174 200

7.5 24.2 182 22510 (5 x 2) 30.8 188 225

105 16.7 181 225

7.5 24.2 188 22510 (5 x 2) 30.8 195 225

155 16.7 196 225

7.5 24.2 204 22510 (5 x 2) 30.8 210 250

205 16.7 213 250

7.5 24.2 220 25010 (5 x 2) 30.8 227 250

230-3-60

7.55 15.2 168 200

7.5 22.0 174 20010 (5 x 2) 28.0 180 225

105 15.2 174 200

7.5 22.0 180 22510 (5 x 2) 28.0 186 225

155 15.2 188 225

7.5 22.0 194 22510 (5 x 2) 28.0 200 225

205 15.2 202 250

7.5 22.0 209 25010 (5 x 2) 28.0 215 250

460-3-60

7.55 7.6 87 110

7.5 11.0 91 11010 (5 x 2) 14.0 94 110

105 7.6 90 110

7.5 11.0 94 11010 (5 x 2) 14.0 97 110

155 7.6 97 110

7.5 11.0 101 11010 (5 x 2) 14.0 104 125

205 7.6 104 125

7.5 11.0 107 12510 (5 x 2) 14.0 110 125

575-3-60

7.55 6.1 71 80

7.5 9.0 74 9010 (5 x 2) 11.0 76 90

105 6.1 73 90

7.5 9.0 76 9010 (5 x 2) 11.0 78 90

155 6.1 79 90

7.5 9.0 82 10010 (5 x 2) 11.0 84 100

205 6.1 84 100

7.5 9.0 87 10010 (5 x 2) 11.0 89 110

Page 28: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

28 Unitary Products Group

TABLE 20: ELECTRICAL DATA BASIC UNIT WITH POWER EXHAUST - 30 TON

VOLTAGESUPPLY AIR MOTOR EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN

HP HP FLA MCA MAX. OVERCURRENT PROTECTION DEVICE

208-3-60

107.5 24.2 192 225

10 (5 x 2) 30.8 199 22515 (7.5 x 2) 46.2 216 250

157.5 24.2 209 250

10 (5 x 2) 30.8 216 25015 (7.5 x 2) 46.2 231 250

207.5 24.2 226 250

10 (5 x 2) 30.8 233 25015 (7.5 x 2) 46.2 248 300

257.5 24.2 245 300

10 (5 x 2) 30.8 252 30015 (7.5 x 2) 46.2 267 300

230-3-60

107.5 22.0 186 200

10 (5 x 2) 28.0 192 22515 (7.5 x 2) 42.0 207 225

157.5 22.0 201 225

10 (5 x 2) 28.0 207 22515 (7.5 x 2) 42.0 221 250

207.5 22.0 216 250

10 (5 x 2) 28.0 222 25015 (7.5 x 2) 42.0 236 250

257.5 22.0 233 300

10 (5 x 2) 28.0 239 30015 (7.5 x 2) 42.0 253 300

460-3-60

107.5 11.0 92 110

10 (5 x 2) 14.0 95 11015 (7.5 x 2) 21.0 102 110

157.5 11.0 99 110

10 (5 x 2) 14.0 102 11015 (7.5 x 2) 21.0 109 125

207.5 11.0 107 125

10 (5 x 2) 14.0 110 12515 (7.5 x 2) 21.0 117 125

257.5 11.0 115 125

10 (5 x 2) 14.0 118 15015 (7.5 x 2) 21.0 125 150

575-3-60

107.5 9.0 75 90

10 (5 x 2) 11.0 77 9015 (7.5 x 2) 17.0 84 100

157.5 9.0 82 90

10 (5 x 2) 11.0 84 10015 (7.5 x 2) 17.0 90 100

207.5 9.0 88 100

10 (5 x 2) 11.0 90 11015 (7.5 x 2) 17.0 96 110

257.5 9.0 94 110

10 (5 x 2) 11.0 96 11015 (7.5 x 2) 17.0 102 125

Page 29: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 29

TABLE 21: ELECTRICAL DATA BASIC UNIT WITH POWER EXHAUST - 40 TON

VOLTAGESUPPLY AIR MOTOR EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN

HP HP FLA MCA MAX. OVERCURRENT PROTECTION DEVICE (MOPD)

208-3-60

107.5 24.2 235 250

10 (5 x 2) 30.8 241 25015 (7.5 x 2) 46.2 259 300

157.5 24.2 252 300

10 (5 x 2) 30.8 259 30015 (7.5 x 2) 46.2 274 300

207.5 24.2 268 300

10 (5 x 2) 30.8 275 30015 (7.5 x 2) 46.2 290 300

257.5 24.2 288 350

10 (5 x 2) 30.8 294 35015 (7.5 x 2) 46.2 310 350

230-3-60

107.5 22 228 250

10 (5 x 2) 28 234 25015 (7.5 x 2) 42 249 250

157.5 22 243 250

10 (5 x 2) 28 249 25015 (7.5 x 2) 42 263 300

207.5 22 258 300

10 (5 x 2) 28 264 30015 (7.5 x 2) 42 278 300

257.5 22 275 300

10 (5 x 2) 28 281 30015 (7.5 x 2) 42 295 350

460-3-60

107.5 11 112 125

10 (5 x 2) 14 115 12515 (7.5 x 2) 21 123 125

157.5 11 120 125

10 (5 x 2) 14 123 12515 (7.5 x 2) 21 130 150

207.5 11 127 150

10 (5 x 2) 14 130 15015 (7.5 x 2) 21 137 150

257.5 11 136 150

10 (5 x 2) 14 139 15015 (7.5 x 2) 21 146 175

575-3-60

107.5 9 92 100

10 (5 x 2) 11 94 11015 (7.5 x 2) 17 101 110

157.5 9 99 110

10 (5 x 2) 11 101 11015 (7.5 x 2) 17 107 110

207.5 9 105 125

10 (5 x 2) 11 107 12515 (7.5 x 2) 17 113 125

257.5 9 111 125

10 (5 x 2) 11 113 12515 (7.5 x 2) 17 119 125

Page 30: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

30 Unitary Products Group

TABLE 22: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 25 TON

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV

FAN MOTOR(S) BASIC UNIT W/ EXHAUST FAN

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION DEVICE

208-3-60

40 30

7.55 16.7 174 200

7.5 24.2 182 22510 (5 x 2) 30.8 188 225

105 16.7 181 225

7.5 24.2 188 22510 (5 x 2) 30.8 195 225

155 16.7 196 225

7.5 24.2 204 22510 (5 x 2) 30.8 210 250

205 16.7 213 250

7.5 24.2 220 25010 (5 x 2) 30.8 227 250

80 60.1

7.55 16.7 218 225

7.5 24.2 227 25010 (5 x 2) 30.8 236 250

105 16.7 226 250

7.5 24.2 236 25010 (5 x 2) 30.8 244 250

155 16.7 245 250

7.5 24.2 255 30010 (5 x 2) 30.8 263 300

205 16.7 262 300

7.5 24.2 271 30010 (5 x 2) 30.8 280 300

230-3-60

40 40

7.55 15.2 168 200

7.5 22.0 174 20010 (5 x 2) 28.0 180 225

105 15.2 174 200

7.5 22.0 180 22510 (5 x 2) 28.0 186 225

155 15.2 188 225

7.5 22.0 195 22510 (5 x 2) 28.0 203 225

205 15.2 202 250

7.5 22.0 210 25010 (5 x 2) 28.0 218 250

80 80

7.55 15.2 231 250

7.5 22.0 239 25010 (5 x 2) 28.0 247 250

105 15.2 238 250

7.5 22.0 247 25010 (5 x 2) 28.0 254 300

155 15.2 256 300

7.5 22.0 264 30010 (5 x 2) 28.0 272 300

205 15.2 271 300

7.5 22.0 279 30010 (5 x 2) 28.0 287 300

Page 31: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 31

460-3-60

40 30

7.55 7.6 87 110

7.5 11.0 91 11010 (5 x 2) 14.0 94 110

105 7.6 90 110

7.5 11.0 94 11010 (5 x 2) 14.0 97 110

155 7.6 97 110

7.5 11.0 101 11010 (5 x 2) 14.0 104 125

205 7.6 104 125

7.5 11.0 107 12510 (5 x 2) 14.0 110 125

80 80

7.55 7.6 115 125

7.5 11.0 120 12510 (5 x 2) 14.0 123 125

105 7.6 119 125

7.5 11.0 123 12510 (5 x 2) 14.0 127 150

155 7.6 128 150

7.5 11.0 132 15010 (5 x 2) 14.0 136 150

205 7.6 135 150

7.5 11.0 140 15010 (5 x 2) 14.0 143 150

108 108

7.55 7.6 148 175

7.5 11.0 152 17510 (5 x 2) 14.0 156 175

105 7.6 151 175

7.5 11.0 156 17510 (5 x 2) 14.0 159 175

155 7.6 160 175

7.5 11.0 164 17510 (5 x 2) 14.0 168 175

205 7.6 168 175

7.5 11.0 172 17510 (5 x 2) 14.0 176 200

TABLE 22: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 25 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV

FAN MOTOR(S) BASIC UNIT W/ EXHAUST FAN

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION DEVICE

Page 32: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

32 Unitary Products Group

575-3-60

40 40

7.55 6.1 71 80

7.5 9.0 74 9010 (5 x 2) 11.0 76 90

105 6.1 73 90

7.5 9.0 76 9010 (5 x 2) 11.0 79 90

155 6.1 79 90

7.5 9.0 83 10010 (5 x 2) 11.0 85 100

205 6.1 85 100

7.5 9.0 89 10010 (5 x 2) 11.0 91 110

80 80

7.55 6.1 99 110

7.5 9.0 103 11010 (5 x 2) 11.0 105 110

105 6.1 102 110

7.5 9.0 105 11010 (5 x 2) 11.0 108 110

155 6.1 109 110

7.5 9.0 113 12510 (5 x 2) 11.0 115 125

205 6.1 115 125

7.5 9.0 119 12510 (5 x 2) 11.0 122 125

108 108

7.55 6.1 127 150

7.5 9.0 131 15010 (5 x 2) 11.0 133 150

105 6.1 130 150

7.5 9.0 133 15010 (5 x 2) 11.0 136 150

155 6.1 137 150

7.5 9.0 141 15010 (5 x 2) 11.0 143 150

205 6.1 144 150

7.5 9.0 147 15010 (5 x 2) 11.0 150 175

TABLE 22: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 25 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV

FAN MOTOR(S) BASIC UNIT W/ EXHAUST FAN

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION DEVICE

Page 33: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 33

TABLE 23: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 30 TON

VOLTAGEELECTRIC HEAT SUPPLY

AIR MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

208-3-60

40 30

107.5 24.2 192 225

10 (5 x 2) 30.8 199 22515(7.5 x 2) 46.2 216 250

157.5 24.2 209 250

10 (5 x 2) 30.8 216 25015(7.5 x 2) 46.2 231 250

207.5 24.2 226 250

10 (5 x 2) 30.8 233 25015(7.5 x 2) 46.2 248 300

257.5 24.2 245 300

10 (5 x 2) 30.8 252 30015(7.5 x 2) 46.2 267 300

80 60.1

107.5 24.2 236 250

10 (5 x 2) 30.8 244 25015(7.5 x 2) 46.2 263 300

157.5 24.2 255 300

10 (5 x 2) 30.8 263 30015(7.5 x 2) 46.2 282 300

207.5 24.2 271 300

10 (5 x 2) 30.8 280 30015(7.5 x 2) 46.2 299 300

257.5 24.2 291 350

10 (5 x 2) 30.8 299 35015(7.5 x 2) 46.2 318 350

230-3-60

40 40

107.5 22 186 200

10 (5 x 2) 28 192 22515(7.5 x 2) 42 208 225

157.5 22 201 225

10 (5 x 2) 28 208 22515(7.5 x 2) 42 225 250

207.5 22 216 250

10 (5 x 2) 28 223 25015(7.5 x 2) 42 240 250

257.5 22 233 300

10 (5 x 2) 28 240 30015(7.5 x 2) 42 258 300

80 80

107.5 22 255 300

10 (5 x 2) 28 262 30015(7.5 x 2) 42 280 300

157.5 22 272 300

10 (5 x 2) 28 280 30015(7.5 x 2) 42 297 300

207.5 22 287 300

10 (5 x 2) 28 295 30015(7.5 x 2) 42 312 350

257.5 22 305 350

10 (5 x 2) 28 312 35015(7.5 x 2) 42 330 350

Page 34: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

34 Unitary Products Group

460-3-60

40 40

107.5 11 92 110

10 (5 x 2) 14 95 11015(7.5 x 2) 21 104 110

157.5 11 100 110

10 (5 x 2) 14 104 11015(7.5 x 2) 21 113 125

207.5 11 108 125

10 (5 x 2) 14 111 12515(7.5 x 2) 21 120 125

257.5 11 116 125

10 (5 x 2) 14 120 15015(7.5 x 2) 21 129 150

80 80

107.5 11 127 150

10 (5 x 2) 14 131 15015(7.5 x 2) 21 140 150

157.5 11 136 150

10 (5 x 2) 14 140 15015(7.5 x 2) 21 149 150

207.5 11 144 150

10 (5 x 2) 14 147 15015(7.5 x 2) 21 156 175

257.5 11 152 175

10 (5 x 2) 14 156 17515(7.5 x 2) 21 165 175

108 108

107.5 11 161 175

10 (5 x 2) 14 165 17515(7.5 x 2) 21 174 175

157.5 11 170 175

10 (5 x 2) 14 174 17515(7.5 x 2) 21 182 200

207.5 11 177 200

10 (5 x 2) 14 181 20015(7.5 x 2) 21 190 200

257.5 11 186 200

10 (5 x 2) 14 190 20015(7.5 x 2) 21 199 225

TABLE 23: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 30 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY

AIR MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

Page 35: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 35

575-3-60

40 40

107.5 9 75 90

10 (5 x 2) 11 78 9015(7.5 x 2) 17 85 100

157.5 9 83 90

10 (5 x 2) 11 85 10015(7.5 x 2) 17 93 100

207.5 9 89 100

10 (5 x 2) 11 91 11015(7.5 x 2) 17 99 110

257.5 9 95 110

10 (5 x 2) 11 98 11015(7.5 x 2) 17 105 125

80 80

107.5 9 105 110

10 (5 x 2) 11 108 11015(7.5 x 2) 17 115 125

157.5 9 113 125

10 (5 x 2) 11 115 12515(7.5 x 2) 17 123 125

207.5 9 119 125

10 (5 x 2) 11 122 12515(7.5 x 2) 17 129 150

257.5 9 125 150

10 (5 x 2) 11 128 15015(7.5 x 2) 17 135 150

108 108

107.5 9 133 150

10 (5 x 2) 11 136 15015(7.5 x 2) 17 143 150

157.5 9 141 150

10 (5 x 2) 11 143 15015(7.5 x 2) 17 151 175

207.5 9 147 150

10 (5 x 2) 11 150 15015(7.5 x 2) 17 157 175

257.5 9 153 175

10 (5 x 2) 11 156 17515(7.5 x 2) 17 163 175

TABLE 23: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 30 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY

AIR MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

Page 36: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

36 Unitary Products Group

TABLE 24: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 40 TON

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

208-3-60

40 30

107.5 24.2 235 250

10 (5 x 2) 30.8 241 25015(7.5 x 2) 46.2 259 300

157.5 24.2 252 300

10 (5 x 2) 30.8 259 30015(7.5 x 2) 46.2 274 300

207.5 24.2 268 300

10 (5 x 2) 30.8 275 30015(7.5 x 2) 46.2 290 300

257.5 24.2 288 350

10 (5 x 2) 30.8 294 35015(7.5 x 2) 46.2 310 350

80 60.1

107.5 24.2 236 250

10 (5 x 2) 30.8 244 25015(7.5 x 2) 46.2 263 300

157.5 24.2 255 300

10 (5 x 2) 30.8 263 30015(7.5 x 2) 46.2 282 300

207.5 24.2 271 300

10 (5 x 2) 30.8 280 30015(7.5 x 2) 46.2 299 350

257.5 24.0 291 350

10 (5 x 2) 30.8 299 35015(7.5 x 2) 46.2 318 350

230-3-60

40 40

107.5 22 228 250

10 (5 x 2) 28 234 25015(7.5 x 2) 42 249 250

157.5 22 243 250

10 (5 x 2) 28 249 25015(7.5 x 2) 42 263 300

207.5 22 258 300

10 (5 x 2) 28 267 30015(7.5 x 2) 42 278 300

257.5 22 275 300

10 (5 x 2) 28 281 30015(7.5 x 2) 42 295 350

80 80

107.5 22 255 300

10 (5 x 2) 28 262 30015(7.5 x 2) 42 280 300

157.5 22 272 300

10 (5 x 2) 28 280 30015(7.5 x 2) 42 297 300

207.5 22 287 300

10 (5 x 2) 28 295 30015(7.5 x 2) 42 312 350

257.5 22 305 350

10 (5 x 2) 28 312 35015(7.5 x 2) 42 330 350

Page 37: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 37

460-3-60

40 40

107.5 11 112 125

10 (5 x 2) 14 115 12515(7.5 x 2) 21 123 125

157.5 11 120 125

10 (5 x 2) 14 123 12515(7.5 x 2) 21 130 150

207.5 11 127 150

10 (5 x 2) 14 130 15015(7.5 x 2) 21 137 150

257.5 11 136 150

10 (5 x 2) 14 139 15015(7.5 x 2) 21 146 175

80 80

107.5 11 127 150

10 (5 x 2) 14 131 15015(7.5 x 2) 21 140 150

157.5 11 136 150

10 (5 x 2) 14 140 15015(7.5 x 2) 21 149 150

207.5 11 144 150

10 (5 x 2) 14 147 15015(7.5 x 2) 21 156 175

257.5 11 152 175

10 (5 x 2) 14 156 17515(7.5 x 2) 21 165 175

108 108

107.5 11 161 175

10 (5 x 2) 14 165 17515(7.5 x 2) 21 174 175

157.5 11 170 175

10 (5 x 2) 14 174 17515(7.5 x 2) 21 182 200

207.5 11 177 200

10 (5 x 2) 14 181 20015(7.5 x 2) 21 190 200

257.5 11 186 200

10 (5 x 2) 14 190 20015(7.5 x 2) 21 199 225

TABLE 24: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 40 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

Page 38: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

38 Unitary Products Group

575-3-60

40 40

107.5 9 92 100

10 (5 x 2) 11 94 11015(7.5 x 2) 17 101 110

157.5 9 99 110

10 (5 x 2) 11 101 11015(7.5 x 2) 17 107 110

207.5 9 105 125

10 (5 x 2) 11 107 12515(7.5 x 2) 17 113 125

257.5 9 111 125

10 (5 x 2) 11 113 12515(7.5 x 2) 17 119 125

80 80

107.5 9 105 110

10 (5 x 2) 11 108 11015(7.5 x 2) 17 115 125

157.5 9 113 125

10 (5 x 2) 11 115 12515(7.5 x 2) 17 123 125

207.5 9 119 125

10 (5 x 2) 11 122 12515(7.5 x 2) 17 129 150

257.5 9 125 150

10 (5 x 2) 11 128 15015(7.5 x 2) 17 135 150

108 108

107.5 9 133 150

10 (5 x 2) 11 136 15015(7.5 x 2) 17 143 150

157.5 9 141 150

10 (5 x 2) 11 143 15015(7.5 x 2) 17 151 175

207.5 9 147 150

10 (5 x 2) 11 150 15015(7.5 x 2) 17 157 175

257.5 9 153 175

10 (5 x 2) 11 156 17515(7.5 x 2) 17 163 175

TABLE 24: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 40 TON (Continued)

VOLTAGEELECTRIC HEAT SUPPLY AIR

MOTOREXHAUST OR ERV FAN

MOTOR(S)BASIC UNIT WITH EXHAUST FAN

AND ELECTRIC HEAT

NOMINAL KW APPLIED KW HP HP FLA MCA MAX. OVERCURRENT

PROTECTION

Page 39: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 39

FIGURE 13 - BOTTOM SUPPLY AND RETURN

88.7"

CL

CL240"

38.59"83"

4.5"

4.5"

64"

92"

80.93"

SEE�

DETAIL�

A

26"

4.5"

15.89"

71.61"

127.5"

100.10"

128.50"

SEE

DETAIL�

CSEE

DETAIL�

B

OPEN

1-5/8" FPT FLANGED

FITTING

1-1/2" FPT

3.625"

6.46"

12"

1-1/4" FPT

10-1/4"

3-1/16"

1-1/4" FPT

3-5/8"

6.46"3-1/16"

MIN

14"MIN

12"MIN

BASE RAIL

BASE RAIL

DETAIL A(DRAIN CONNECTION)

DETAIL B DETAIL C(ELECTRICAL CONNECTION) (GAS CONNECTION,

THROUGH CURB)

NOTE: Hole must be drilled�

at job site.

4-5/8"

4-5/8"

FOR COOLING ONLY AND ALL HEATING APPLICATIONS

SUPPLY AIR

RETURN AIR

����

����

����

���

����

���

����

���

����

���

�� ��

�� ��

Page 40: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

40 Unitary Products Group

FIGURE 14 - END RETURN, BOTTOM SUPPLY

RETURN AIR

SUPPLY AIR

240"

64"

92"

80.93"SEE

DETAIL

A

100.10"

128.50"

SEEDETAIL

B

75.6"

OPEN

7-7/8"

8.15"76-3/824.9"

6.25"

26"

4.5"

15.89"

71.61"

SEEDETAIL

C

4-5/8"

1-1/2" FPT

3.625"

6.46"

12"

1-1/4" FPT

10-1/4"

3-1/16"

3-5/8"

6.46"3-1/16"

MIN

14"MIN

12"MIN

2-1/2"

NOTE:�

FACTORY INSTALLED POWER�

EXHAUST CANNOT BE ORDERED�

WITH END RETURN.

CL88.7"

4-5/8"

DETAIL A(DRAIN CONNECTION)

DETAIL B DETAIL C(ELECTRICAL CONNECTION) (GAS CONNECTION

THROUGH CURB)FOR COOLING ONLY AND ALL HEATING APPLICATIONS

NOTE: Hole must be drilled

at job site.

FIELD SUPPLIED

BASE RAIL

BASE RAIL

����

����� ��

���� ���� ��

�� ��

�����

��

���� ��

����

Page 41: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 41

FIGURE 15 - BOTTOM RETURN, FRONT & REAR SUPPLY

FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS�

REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS

BASE RAIL

DETAIL A�

(DRAIN CONNECTION)

DETAIL B�

(ELECTRICAL CONNECTION)

BASE RAIL

DETAIL C�

(GAS CONNECTION�

THROUGH CURB)�

FIELD SUPPLIED

4-5/8"

4-5/8"

RETURN AIR

SUPPLY AIR

240"

38.59"83"

4.5"

4.5"

64"

92"

80.93"SEE�

DETAIL�

A

100.10"

128.50"

SEE�

DETAIL�

C

SEE

DETAIL�

B

26"

55"

75.6"

OPEN

8.15"

3.625"

6.46"

12"MIN

1-1/2" FPT

12"

1-1/4" FPT

10-1/4"

3-1/16"

2-1/2"

3-5/8"

6.46"

NOTE: Hole must be drilled�at job site.

3-1/16"

MIN

14"MIN

FRONT

FRONT

FRONT

REAR

REAR

LEFT SIDE

LEFT SIDE

REAR

RIGHT SIDE

RIGHT

SIDE

Page 42: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

42 Unitary Products Group

FIGURE 16 - END RETURN, FRONT & REAR SUPPLY

FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS

REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS

RETURN AIR

SUPPLY AIR

240"

64"

92"

80.93"SEE�

DETAIL�

A

100.10"

128.50"

SEE�

DETAIL

C

SEE�

DETAIL�

B

26"

55"

75.6"

OPEN

7-7/8"

8.15"24.9"

6.25"

1-1/2" FPT

3.625"

6.46"

12"

1-1/4" FPT

10-1/4"

3-1/16"

2-1/2"

3-5/8"

6.46"

NOTE: Hole must be drilledat job site.

3-1/16"

MIN

14"MIN

12"MIN

76-3/8

BASE RAIL

BASE RAIL

DETAIL A�

(DRAIN CONNECTION)

DETAIL B�

(ELECTRICAL CONNECTION)

DETAIL C�

(GAS CONNECTION�

THROUGH CURB)�

FIELD SUPPLIED

26"

55"

4-5/8"

4-5/8"

�����

���

�����

���

��

���

��

���

���

���

���

�� ��

�� ��

Page 43: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 43

FIGURE 17 - FIELD INSTALLED DISCONNECT

31"MAXIMUM

DRILL & BOLT

THROUGH UNIT

SHEET METAL

(4 PLACES)

34"*

6-1/2"

MINIMUM

MAXIMUM DOOR SWING

OF HEAT SECTION

DOOR WHEN OPEN

UNISTRUT

1-5/8" W x 7/8" H

OR EQUIVALENT

TM

47"

*34 INCHES IS THE MINIMUM LENGTH REQUIRED TOMOUNT TO THE FOUR POINTS SHOWN. THE RAILS CANBE EXTENDED TO MOUNT A TALLER DISCONNECTSWITCH, BUT THESE FOUR POINTS SHOULD BE USEDTO MOUNTTHE RAILS TO THE UNIT.

Page 44: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

44 Unitary Products Group

FIGURE 18 - PARTIAL ROOF CURB MODEL 1RC0455P

! " � # #

! $ � # #

" ! � % & & % � # & � ' � # #

� " % � # #

( � # #

� � # #

� ( � # #

$ � � ' �

� � � " &

� � �� � �

� � � � � �

� � � � �� � �

� � � � � �

� � � � � � � � � � � � ) � � � � �

� � � � � � � � ) �

� � � � � ( �� � � � �

� ( � � � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � � �

� � ( � # # �

� � � � � � ! � ( � !

� � � � � � � � � � � � � � � � � � � � �

� � � � �

� � � � �

� � � � �

� � � � �

� � � � �

� � �

) * + , - . / 0 ) � 1 2 3� 4 0 . 3 5 . 0 4

6 3 3 . � � 3 . - ,� 0 * 3 � � / 3 5 3 "

� � � � � � � � �� � � �

� � ( � � � � � � � � � � � � � � � � � �� � ( � � � � � � � � � � � � � � � � � � � � �

� � � 7 � � 4 0 . 3 5 . � / ) * + , - . / 0 ) � 8 / . 6 � - � * 6 3 3 . � 9 3 . - ,) 0 * 3 � : / 3 5 3 � 8 6 3 ) � / ) * . - , , / ) 2 � - � / ) . 3 4 ) - , , ; � / ) * + , - . 3 11 + 5 . � 8 0 4 < �

� ; : / 5 - , � ) * + , - . / 0 )

� � � � � � � � � � � � � � � � � � � � �

Page 45: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 45

FIGURE 19 - FULL ROOF CURB MODEL 1RC0455F

� � � � � � � � � � � � ) � � � � �

� � � � � � � � ) �

� � � � � ( �� � � � �

� ( � � � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � � �

� � ( � # # �

! " � # #

! $ � # #

" ! � % &

� ' � # #

� " % � # #

� � # #

$ � � ' �

� � � " &

� � �� � �

� � � � � �

� � � � �� � �

� � � � � �

� ( � # #

$ " � " #

� " � $ ' � " � $ $ � " � $ $" � # #

� � # #

� � � # #� � $ � % #

� � # #

� � � � � � � � � � � � � � � � � � � � �

� � � � �

� � � � �

� � � � �

� � � � �

� � � � �

� � �

Page 46: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

46 Unitary Products Group

CFM, STATIC PRESSURE, AND POWER - ALTI-TUDE AND TEMPERATURE CORRECTIONS

The information below should be used to assist in applicationof product when being applied at altitudes at or exceeding1000 feet above sea level.

The air flow rates listed in the standard blower performancetables are based on standard air at sea level. As the altitudeor temperature increases, the density of air decreases. In

order to use the indoor blower tables for high altitude applica-tions, certain corrections are necessary.

A centrifugal fan is a "constant volume" device. This meansthat, if the rpm remains constant, the CFM delivered is thesame regardless of the density of the air. However, since theair at high altitude is less dense, less static pressure will begenerated and less power will be required than a similarapplication at sea level. Air density correction factors areshown in Table 25 and Figure 20.

The examples below will assist in determining the airflow per-formance of the product at altitude.

Example 1: What are the corrected CFM, static pressure,and BHP at an elevation of 5,000 ft. if the blower performancedata is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: At an elevation of 5,000 ft the indoor blower will stilldeliver 6,000 CFM if the rpm is unchanged. However, Table25 must be used to determine the static pressure and BHP.Since no temperature data is given, we will assume an airtemperature of 70°F. Table 25 shows the correction factor tobe 0.832.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC

Corrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is todeliver 6,000 CFM at a static pressure of 1.5". Use the unit

blower tables to select the blower speed and the BHPrequirement.

Solution: As in the example above, no temperature informa-tion is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft.The first step is to convert this static pressure to equivalentsea level conditions.

Sea level static pressure = 1.5 / .832 = 1.80"

Enter the blower table at 6000 sCFM and static pressure of1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Suppose that the corresponding BHP listed in the table is 3.2.This value must be corrected for elevation.

BHP at 5,000 ft = 3.2 x .832 = 2.66

TABLE 25: ALTITUDE CORRECTION FACTORS

AIR TEMP ALTITUDE (FEET)

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 1000040 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.72950 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.71560 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.70170 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.68880 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.67690 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663

100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

Page 47: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 47

FIGURE 20 - ALTITUDE/TEMPERATURE CONVERSION FACTOR

������������� ���� ���������� � ����

�����

�����

�����

�����

�����

�����

�� � �� �� �� �� ���

��������� ����

�������� �����

�� �����

���� ��

����

����

���

����

����

����

����

������

����

Page 48: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

48 Unitary Products Group

TABLE 26: FAN PERFORMANCE - 25 TON1 2

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

0.2 0.4 0.6 0.8 1.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

4000 - - 342 0.59 404 0.82 456 1.08 506 1.35

5000 306 0.62 362 0.83 415 1.08 465 1.36 512 1.66

6000 337 0.93 387 1.17 433 1.43 478 1.72 521 2.04

7000 370 1.34 415 1.60 456 1.88 497 2.20 535 2.54

8000 408 1.88 446 2.17 484 2.49 520 2.80 555 3.15

9000 444 2.56 480 2.86 514 3.21 547 3.58 579 3.96

10000 481 3.40 514 3.76 545 4.11 576 4.47 606 4.83

11000 520 4.38 550 4.74 579 5.12 608 5.54 635 5.97

12000 557 5.55 585 5.96 612 6.37 638 6.78 664 7.19

13000 596 6.90 622 7.32 647 7.76 671 8.22 696 8.69

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

1.2 1.4 1.6 1.8 2.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

4000 549 1.63 591 1.93 628 2.23 663 2.55 698 2.86

5000 555 1.97 597 2.31 634 2.66 670 3.00 705 3.38

6000 562 2.39 602 2.74 638 3.11 674 3.52 709 3.92

7000 573 2.88 610 3.27 645 3.68 679 4.09 713 4.50

8000 591 3.55 624 3.95 657 4.35 689 4.76 720 5.19

9000 611 4.34 642 4.72 673 5.12 703 5.59 732 6.06

10000 634 5.23 663 5.68 692 6.13 719 6.58 747 7.03

11000 662 6.39 689 6.82 715 7.25 741 7.70 766 8.21

12000 690 7.62 714 8.10 739 8.59 763 9.07 787 9.55

13000 720 9.15 743 9.61 766 10.09 789 10.65 811 11.20

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

2.2 2.4 2.6 2.8 3.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

4000 728 3.19 757 3.53 787 3.87 814 4.21 839 4.55

5000 736 3.75 767 4.13 798 4.50 825 4.88 851 5.28

6000 740 4.32 772 4.73 803 5.14 830 5.58 858 6.03

7000 744 4.92 775 5.37 805 5.84 833 6.31 861 6.78

8000 751 5.67 781 6.15 810 6.63 837 7.11 865 7.60

9000 760 6.53 789 7.00 817 7.48 843 8.01 870 8.55

10000 774 7.48 801 8.01 826 8.54 852 9.07 878 9.60

11000 792 8.72 817 9.24 841 9.75 865 10.30 890 10.90

12000 811 10.05 834 10.63 857 11.21 880 11.79 903 12.38

13000 833 11.76 855 12.32 877 12.87 899 13.43 921 13.99

Page 49: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 49

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

3.2 3.4 3.6 3.8 4.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

4000 864 4.90 890 5.26 913 5.64 935 6.01 957 6.39

5000 878 5.69 904 6.10 927 6.51 950 6.92 973 7.33

6000 885 6.47 911 6.91 935 7.36 959 7.82 983 8.29

7000 889 7.25 914 7.74 939 8.24 964 8.75 988 9.25

8000 892 8.13 918 8.66 942 9.18 967 9.71 992 10.26

9000 897 9.09 921 9.63 946 10.18 970 10.78 995 11.37

10000 903 10.15 927 10.76 951 11.36 975 11.97 999 12.57

11000 913 11.50 936 12.10 959 12.70 983 13.30 1005 13.90

12000 926 12.96 948 13.54 970 14.12 992 14.70 1013 15.33

13000 942 14.55 963 15.12 984 15.79 1005 16.45 1025 17.11

1. Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-sity and 0 degree elevation.

2. Refer to Tables 29, 56, and 65 for component additions and deductions to fan performance tables.3. BHP does not include drive losses. Multiply BHP by 1.05 for drive losses.

TABLE 26: FAN PERFORMANCE - 25 TON1 2 (Continued)

Page 50: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

50 Unitary Products Group

FIGURE 21 - FAN PERFORMANCE - 25 TON

Page 51: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 51

TABLE 27: FAN PERFORMANCE - 30 TON 1 2

AIRFLOW (CFM)

Available External Static Pressure (IWG)

0.2 0.4 0.6 0.8 1.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

6000 321 0.9 373 1.1 422 1.5 469 1.8 513 2.17000 357 1.3 404 1.6 447 1.9 490 2.2 529 2.68000 398 1.8 437 2.1 477 2.5 515 2.9 551 3.39000 436 2.5 473 2.8 509 3.2 543 3.6 577 4.0

10000 477 3.2 511 3.7 543 4.1 575 4.5 606 5.011000 519 4.2 549 4.7 579 5.1 609 5.6 637 6.112000 560 5.4 589 5.9 617 6.4 643 6.9 670 7.413000 603 6.8 629 7.3 654 7.8 680 8.4 705 8.914000 645 8.4 669 8.9 694 9.5 718 10.0 741 10.715000 688 10.2 711 10.8 733 11.5 755.6 12.1 778 12.7

AIRFLOW (CFM)

Available External Static Pressure (IWG)

1.2 1.4 1.6 1.8 2.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

6000 554 2.4 596 2.8 632 3.2 668 3.5 703 3.97000 568 3.0 607 3.4 642 3.8 676 4.2 710 4.68000 587 3.7 622 4.1 655 4.5 689 5.0 720 5.49000 610 4.5 642 4.9 673 5.4 704 5.9 734 6.4

10000 636 5.5 666 6.0 695 6.5 723 7.0 751 7.511000 665 6.6 693 7.1 720 7.6 746 8.2 773 8.812000 697 7.9 722 8.5 747 9.1 772 9.6 797 10.213000 729 9.5 753 10.0 777 10.7 801 11.3 824 11.914000 764 11.3 787 11.9 809 12.6 831 13.2 853 13.815000 800 13.3 821 13.9 842 14.6 863 15.2 884 15.9

AIRFLOW (CFM)

Available External Static Pressure (IWG)

2.2 2.4 2.6 2.8 3.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

6000 734 4.3 765 4.7 796 5.1 824 5.5 850 6.07000 741 5.0 772 5.5 803 6.0 830 6.4 858 6.98000 750 5.9 781 6.4 810 6.9 837 7.4 865 7.99000 763 6.9 792 7.4 820 7.9 847 8.5 873 9.0

10000 779 8.0 807 8.6 833 9.1 859 9.7 885 10.311000 799 9.3 824 9.9 849 10.5 874 11.1 899 11.712000 821 10.8 845 11.5 869 12.1 893 12.7 916 13.413000 847 12.6 869 13.2 892 13.9 914 14.5 936 15.114000 874 14.5 896 15.1 917 15.8 938 16.5 959 17.215000 904 16.6 924 17.4 944 18.1 964 18.8 984 19.5

Page 52: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

52 Unitary Products Group

AIRFLOW (CFM)

Available External Static Pressure (IWG)

3.2 3.4 3.6 3.8 4.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

6000 877 6.4 904 6.8 928 7.3 951 7.7 975 8.27000 885 7.3 911 7.8 935 8.3 959 8.8 984 9.28000 892 8.4 917 8.9 942 9.4 966 9.9 991 10.49000 900 9.5 925 10.1 949 10.6 974 11.2 998 11.8

10000 910 10.9 934 11.5 958 12.1 982 12.7 1006 13.311000 923 12.4 946 13.0 970 13.6 993 14.2 1015 14.812000 939 14.0 961 14.6 984 15.3 1006 16.0 1028 16.713000 958 15.8 980 16.5 1001 17.2 1022 17.9 1043 18.614000 980 17.9 1001 18.7 1021 19.4 1040 20.1 1060 20.815000 1004 20.2 1023 21.0 1043 21.8 1062 22.5 1081 23.3

1. Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-sity and 0 degree elevation.

2. Refer to Tables 29, 56, and 65 for component additions and deductions to fan performance tables.3. BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.

TABLE 27: FAN PERFORMANCE - 30 TON 1 2 (Continued)

Page 53: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 53

FIGURE 22 - FAN PERFORMANCE - 30 TON

Page 54: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

54 Unitary Products Group

TABLE 28: FAN PERFORMANCE - 40 TON1 2

AIRFLOW (CFM)

Available External Static Pressure (IWG)

0.2 0.4 0.6 0.8 1.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

8000 304 1.3 348 1.7 393 2.1 431 2.5 469 2.99000 329 1.8 371 2.2 411 2.6 448 3.0 484 3.5

10000 356 2.3 396 2.7 432 3.2 467 3.7 502 4.211000 385 2.9 421 3.4 454 3.9 488 4.5 519 5.012000 414 3.7 446 4.3 479 4.8 510 5.4 539 5.913000 442 4.6 473 5.2 504 5.8 532 6.4 560 7.014000 472 5.7 502 6.3 529 6.9 556 7.6 583 8.215000 503 6.9 529 7.6 555 8.2 581 8.9 607 9.616000 532 8.3 557 9.0 583 9.7 607 10.4 631 11.217000 562 9.9 587 10.6 611 11.4 633 12.1 656 12.918000 593 11.7 616 12.5 638 13.2 660 14.0 682 14.7

AIRFLOW (CFM)

Available External Static Pressure (IWG)

1.2 1.4 1.6 1.8 2.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

8000 506 3.3 537 3.8 569 4.2 601 4.7 627 5.29000 518 4.0 549 4.4 581 4.9 610 5.5 637 6.0

10000 532 4.7 563 5.2 594 5.8 621 6.3 648 6.811000 549 5.5 579 6.1 608 6.7 634 7.2 661 7.812000 568 6.5 596 7.1 623 7.7 649 8.3 675 9.013000 588 7.6 614 8.2 640 8.9 665 9.5 690 10.214000 609 8.9 634 9.5 658 10.2 683 10.9 707 11.615000 631 10.3 655 11.0 679 11.7 702 12.5 724 13.216000 654 11.9 677 12.6 700 13.4 722 14.1 743 14.917000 678 13.6 701 14.4 722 15.2 742 16.0 763 16.818000 703 15.6 724 16.4 744 17.2 764 18.1 785 18.9

AIRFLOW (CFM)

Available External Static Pressure (IWG)

2.2 2.4 2.6 2.8 3.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

8000 654 5.7 681 6.2 706 6.7 729 7.2 752 7.79000 664 6.5 691 7.0 715 7.6 738 8.1 761 8.7

10000 675 7.4 701 8.0 725 8.6 748 9.1 771 9.711000 687 8.4 712 9.0 735 9.7 758 10.3 781 10.912000 700 9.6 723 10.2 747 10.9 770 11.6 793 12.313000 714 10.9 737 11.6 760 12.3 782 13.0 805 13.714000 729 12.4 752 13.1 774 13.8 796 14.5 817 15.215000 746 13.9 768 14.7 790 15.4 811 16.2 831 17.016000 764 15.7 786 16.5 807 17.3 826 18.1 846 18.917000 784 17.6 805 18.5 824 19.3 843 20.1 863 21.018000 805 19.7 824 20.6 843 21.5 862 22.4 881 23.3

Page 55: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 55

AIRFLOW (CFM)

Available External Static Pressure (IWG)

3.2 3.4 3.6 3.8 4.0

RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3 RPM BHP3

8000 774 8.3 797 8.8 817 9.4 837 9.9 857 10.59000 784 9.3 806 9.8 826 10.4 846 11.0 866 11.6

10000 794 10.3 815 11.0 836 11.6 856 12.3 876 12.911000 804 11.6 824 12.2 845 12.9 865 13.6 886 14.212000 814 12.9 835 13.6 855 14.3 876 15.0 896 15.713000 825 14.4 846 15.1 866 15.8 886 16.6 906 17.314000 837 16.0 858 16.8 878 17.5 898 18.3 917 19.115000 851 17.8 871 18.6 891 19.4 910 20.2 928 21.016000 866 19.7 886 20.5 905 21.4 923 22.2 941 23.117000 882 21.9 901 22.7 919 23.6 937 24.5 - -18000 900 24.2 - - - - - - - -

1. Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-sity and 0 degree elevation.

2. Refer to Tables 29, 57 and 66 for component additions and deductions to fan performance tables.3. BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.

TABLE 28: FAN PERFORMANCE - 40 TON1 2 (Continued)

Page 56: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

56 Unitary Products Group

FIGURE 23 - FAN PERFORMANCE - 40 TON

Page 57: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 57

TABLE 29: COMPONENT STATIC RESISTANCE1 2

COMPONENT COIL LOSSES

CFM

6,000 8,000 10,000 12,000 14,000 16,000 18,000

Std. 25 Ton, Dry -0.06 -0.08 -0.10 -0.13 - - -

Std. 25 Ton, Wet Baseline Baseline Baseline Baseline Baseline Baseline Baseline

Std. 30 Ton, Dry -0.045 -0.075 -0.112 -0.157 -0.207 -0.264 -0.326

Std. 30 Ton, Wet Baseline Baseline Baseline Baseline Baseline Baseline Baseline

Hi Cap 30 Ton, Dry -0.019 -0.035 -0.052 -0.073 -0.098 -0.124 -0.155

Hi Cap 30 Ton, Wet 0.042 0.069 0.103 0.142 0.186 0.236 0.290

Std. 40 Ton, Dry -0.030 -0.051 -0.076 -0.106 -0.140 -0.177 -0.219

Std. 40 Ton, Wet Baseline Baseline Baseline Baseline Baseline Baseline Baseline

Hi Cap 40 Ton, Dry -0.020 -0.033 -0.050 -0.069 -0.092 -0.116 -0.144

Hi Cap 40 Ton, Wet 0.023 0.038 0.057 0.079 0.105 0.133 0.164

Filter Losses

2” TA or HI Eff. Baseline Baseline Baseline Baseline Baseline Baseline Baseline

Rigid 6”, 65% 0.048 0.080 0.119 0.165 0.217 0.274 0.338

Rigid 6”, 95% 0.189 0.308 0.448 0.609 0.790 0.988 1.205

IGV Losses

30 Ton 0.048 0.085 0.132 0.190 0.259 0.338 0.428

40 Ton 0.027 0.049 0.076 0.110 0.149 0.195 0.246

Gas Heat

233 MBH Heat 0.106 0.141 0.177 0.212 0.247 0.283 0.318

466 MBH Heat 0.212 0.283 0.353 0.424 0.495 0.566 0.636

699 MBH Heat 0.318 0.423 0.531 0.636 0.741 0.849 0.954

Electric Heat 0.050 0.100 0.150 0.310 0.430 0.530 0.680

Economizer* 0.063 0.104 0.153 0.210 0.276 0.349 0.429

Power Exhaust* 0.046 0.081 0.127 0.182 0.248 0.324 0.410

1. Baseline losses based on system/cabinet effects, wet standard coil and 2-inch throwaway filters at 70°F, 0 degree elevation with standard air.

2. See Tables 56, 57, 65, and 66 for steam and hot water coil static resistance.

Page 58: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

58 Unitary Products Group

TABLE 30: SUPPLY FAN MOTOR AND DRIVE DATA

ModelBlower

RPM Range

Motor Motor Pulley Blower Pulley Belts

HP FrameSize

MotorEfficiency

(Std. Motor)

MotorEfficiency(Ultra HiEff Opt)

Pitch Dia(Inches)

Bore(Inches)

Pitch Dia(Inches)

Bore(Inches) Designation Qty

25 Ton

567 7.5 213T 88.5 91.7 4.5 1-3/8 13.9 2-3/16 BX56 2

692 10 215T 89.5 91 5.5 1-3/8 13.9 2-3/16 BX56 2

793 15 254T 91 91.7 6.3 1-5/8 13.9 2-3/16 BX56 2

894 20 256T 91 93 7.1 1-5/8 13.9 2-3/16 BX56 2

30 Ton

617 10 215T 89.5 91 4.9 1-3/8 13.9 2-3/16 BX56 2

743 15 254T 91 91.7 5.9 1-5/8 13.9 2-3/16 BX56 2

844 20 256T 91 93 6.7 1-5/8 13.7 2-3/16 5VX610 2

919 25 284T 91.7 93.6 7.1 1-7/8 13.7 2-3/16 5VX610 2

40 Ton

567 10 215T 89.5 91 4.5 1-3/8 13.9 2-7/16 BX67 2

642 15 254T 91 91.7 5.1 1-5/8 13.7 2-7/16 5VX710 2

717 20 256T 91 93 5.7 1-5/8 13.7 2-7/16 5VX710 2

768 25 284T 91.7 93.6 6.1 1-7/8 13.7 2-7/16 5VX710 2

TABLE 31: EXHAUST FAN DRIVE DATA

ModelBlower

RPMRange

Motor Motor Pulley Blower Pulley Belts

HP FrameSize

Motor Eff(Std.

Motor)

MotorEff (Hi

Eff opt)

Pitch Dia(Inches)

Bore(Inches)

Pitch Dia(Inches)

Bore(Inches) Designation Qty

25 Ton

732 5 213T 87.5 89.5 4.9 1-3/8 11.3 2-3/16 BX63 2

827 7.5 215T 88.5 91.7 5.5 1-3/8 11.3 2-3/16 BX63 2

955 10 215T 89.5 91 6.3 1-5/8 11.3 2-3/16 BX63 2

30 Ton

852 7.5 213T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2

976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2

1069 15 254T 85.7 89.5 6.9 1-3/8 11.3 1-11/16 B65 2

40 Ton

852 7.5 184T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2

976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2

1069 15 254T 85.7 89.5 6.5 1-3/8 11.3 1-11/16 B65 2

Page 59: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 59

TABLE 32: POWER EXHAUST - ONE FORWARD CURVED FAN 25 TON1

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

0.2 0.4 0.6 0.8 1.0

RPM BHP2 RPM BHP2 RPM BHP2 RPM BHP2 RPM BHP2

2000 --- --- --- --- 524 0.32 609 0.42 685 0.54

3000 --- --- 450 0.41 531 0.51 605 0.64 672 0.77

4000 442 0.63 496 0.74 562 0.87 626 1.00 687 1.16

5000 524 1.15 566 1.29 609 1.43 663 1.58 717 1.74

6000 612 1.84 646 2.08 679 2.25 717 2.43 762 2.60

7000 703 2.86 731 3.16 759 3.37 787 3.57 820 3.78

8000 791 3.63 821 4.09 844 4.54 868 4.99 892 5.23

9000 877 5.53 911 5.88 932 6.22 953 6.57 974 6.92

10000 967 8.02 1004 8.34 1022 8.66 1041 8.98 1059 9.30

AIRFLOW CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IWG)

1.2 1.4 1.6 1.8 2.0

RPM BHP2 RPM BHP2 RPM BHP2 RPM BHP2 RPM BHP2

2000 754 0.66 819 0.78 878 0.90 933 1.03 986 1.16

3000 736 0.92 797 1.08 854 1.24 909 1.41 961 1.58

4000 743 1.32 799 1.47 850 1.66 900 1.84 948 2.04

5000 768 1.90 818 2.08 865 2.28 911 2.48 955 2.68

6000 806 2.78 850 2.95 895 3.17 937 3.40 978 3.62

7000 857 3.98 895 4.19 933 4.39 972 4.60 1010 4.80

8000 921 5.47 953 5.71 985 5.95 1018 6.19 1052 6.43

9000 995 7.27 1020 7.59 1048 7.86 1075 8.13 1103 8.39

10000 1077 9.62 1096 9.94 - - - - - -

1. Fan performance is based on system/cabinet effects and backdraft damper effects at standard air density and 0° elevation.2. BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.

Page 60: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

60 Unitary Products Group

FIGURE 24 - POWER EXHAUST - ONE FORWARD CURVE FAN - 25 TONS

Power Exhaust 25 Ton

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0

CFM (x1000)

Tot

al S

tatic

Pre

ssur

e (I

WG

)

300400

500

600

700800

900

1000

1100

1200

1300

1400

1500

1600

5 BHP

7.5 BHP

10 BHP

Page 61: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 61

TABLE 33: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON1

AIRFLOW (CFM)

Available External Static Pressure (IWG)

0.2 0.4 .06 0.8 1.0

RPM BHP2 3 RPM BHP2 3 RPM BHP2 3 RPM BHP2 3 RPM BHP2 3

4000 363 0.3 468 0.5 560 0.7 641 0.9 716 1.1

5000 402 0.5 494 0.7 576 1.0 652 1.2 722 1.4

6000 445 0.8 527 1.0 602 1.3 670 1.6 735 1.9

7000 494 1.2 565 1.5 633 1.7 697 2.0 757 2.4

8000 544 1.7 609 2.0 670 2.3 729 2.6 784 3.0

9000 597 2.3 654 2.7 711 3.0 765 3.3 817 3.7

10000 651 3.1 703 3.5 754 3.8 805 4.2 853 4.6

11000 705 4.1 753 4.5 801 4.9 847 5.3 893 5.7

12000 761 5.2 805 5.6 849 6.0 893 6.5 934 6.9

13000 817 6.6 858 7.0 899 7.4 939 7.9 979 8.4

14000 874 8.1 912 8.6 950 9.1 988 9.5 1025 10.0

15000 932 9.9 967 10.4 1002 11.0 1037 11.5 1072 12.0

16000 989 12.0 1022 12.6 1055 13.1 1088 13.6

AIRFLOW (CFM)

Available External Static Pressure (IWG)

1.2 1.4 1.6 1.8 2

RPM BHP2 3 RPM BHP2 3 RPM BHP2 3 RPM BHP2 3 RPM BHP2 3

4000 783 1.4 844 1.6 903 1.8 956 2.1 1008 2.3

5000 788 1.7 848 2.0 906 2.3 959 2.5 1011 2.8

6000 798 2.1 855 2.5 911 2.8 963 3.1 1014 3.4

7000 814 2.7 869 3.0 922 3.3 972 3.7 1021 4.0

8000 837 3.3 889 3.7 938 4.0 987 4.4 1033 4.8

9000 866 4.1 915 4.5 961 4.9 1007 5.3 1050 5.7

10000 900 5.0 945 5.4 989 5.9 1032 6.3 1073 6.8

11000 936 6.1 979 6.6 1020 7.0 1061 7.5 1101 7.9

12000 976 7.4 1016 7.9 1055 8.3 1094 8.8 1131 9.3

13000 1018 8.9 1055 9.4 1093 9.9 1129 10.4 1165 11.0

14000 1061 10.6 1098 11.1 1133 11.7 1167 12.3 1202 12.8

15000 1107 12.6 1141 13.1 1175 13.7 1208 14.2 1240 14.8

1. Fan performance is based on system/cabinet effects and backdraft damper effects at standard air density and 0° elevation.2. BHP includes the sum of both exhaust fan blowers.3. BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.

Page 62: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

62 Unitary Products Group

FIGURE 25 - POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TONS

Page 63: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 63

START-UP COMPRESSOR ROTATION

Check for proper compressor rotation (See page 114 forsymptoms of reverse compressor operations). Millenniumunits are properly phased at the factory. If the blower, con-denser fan, or compressor, rotate in the wrong direction atstart-up, the electrical connection to the unit is misphased.Change the incoming line connection phasing to obtainproper rotation.

SUPPLY AIR FAN INSTRUCTIONS

CHECK BLOWER BEARING SET SCREWS

• The bearing set screws on the supply air blower are properly torqued before shipment. However, in transit they may loosen. Prior to start up they should be rechecked. The set screws are 3/8" and the torque range is 200 - 215 in.-lbs.

NOTE: If a unit is equipped with exhaust fans, those bear-ing set screws should also be rechecked. The setscrews are 1/4 inch and the torque range is 70 - 87in.-lbs.

CHECKING SUPPLY AIR CFM

The RPM of the supply air blower will depend on the requiredCFM, the static pressure resistances of the unit components(Tables 29, 56, 57, 65, and 66) and the static pressure resis-tances of both the supply and the return air duct systems.With this information, the RPM for the supply air blower canbe determined from the blower performance data in Tables26, 27, and 28. See Table 30 for pulley and drive informationfor the fixed pitch pulleys supplied on the unit.

The supply air CFM must be within the limitations shown inTable 2.

NOTE: If unit is equipped with power exhaust fans or returnair fan see Tables 32 and 33 for fan performanceand for pulley and drive information see Table 31.

FAN ROTATION

Check for proper supply air blower rotation. If fans are rotat-ing backwards the line voltage to unit point of power connec-tion is misphased (see Compressor Rotation above.)

NOTE: If unit is equipped with power exhaust fans or returnair fan also check them for proper rotation.

BELT TENSION

The tension on the belt should be adjusted as shown in Fig-ure 26 and Table 34.

NOTE: If unit is equipped with power exhaust fans or returnair fan check belt tension and adjust as necessary.

AIR BALANCE

Start the supply air blower motor. Adjust the resistances inboth the supply and the return air duct systems to balancethe air distribution throughout the conditioned space. The jobspecifications may require that this balancing be done bysomeone other than the equipment installer.

CHECKING AIR QUANTITY

Scroll compressors require proper rotation to oper-ate correctly. Units are properly phased at the fac-tory. DO NOT change the internal wiring to makethe blower, condenser fans or compressor rotatecorrectly.

FIGURE 26 - BELT TENSION ADJUSTMENT

On VAV and VFD units be certain all IGV’s on VAVunit are full open, VFD drive is set to maximumoutput, exhaust dampers are closed and individualspace damper boxes are full open.

VFD units with bypass must not have the bypassactivated unless all individual space dampers arefull open.

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � = � � � � � � � � � � � � �� � � � 0 0 * 3 ) � > 0 + 4 � ? 0 , . * � 6 0 , 1 / ) 2 � 9 0 . 0 4 � ? - * 3 � . 0 � 5 6 - ) ) 3 , *� � � � 1 @ + * . � ? 3 , . � ? ; � � . + 4 ) / ) 2 � ) + . * � ! � ! � * 3 3 � 1 3 . - / , � ! � ! " �� � � � * / ) 2 � - � ? 3 , . � . 3 ) * / 0 ) � 5 6 3 5 < 3 4 A � - : : , ; � - � : 3 4 : 3 ) 1 / 5 + , - 4 � > 0 4 5 3� � � � . 0 � 0 ) 3 � ? 3 , . � - . � . 6 3 � 9 / 1 : 0 / ) . � 0 > � . 6 3 � * : - ) � - * � * 6 0 8 ) � � � 6 3 � 1 3 > , 3 5 . / 0 )� � � � > 0 4 5 3 � * 6 0 + , 1 � ? 3 � - : : , / 3 1 � + ) . / , � - � * : 3 5 / > / 5 � 1 3 > , 3 5 . / 0 ) � 1 / * . - ) 5 3� � � � 0 > � � & % � ! � : 3 4 � / ) 5 6 � 0 > � * : - ) � , 3 ) 2 . 6 � / * � 0 ? . - / ) 3 1 �� � � � 0 � 1 3 . 3 4 9 / ) 3 � . 6 3 � 1 3 > , 3 5 . / 0 ) � 1 / * . - ) 5 3 � > 4 0 9 � ) 0 4 9 - , � : 0 * / . / 0 ) A� � � � + * 3 � - � * . 4 - / 2 6 . � 3 1 2 3 � > 4 0 9 � * 6 3 - B 3 � . 0 � * 6 3 - B 3 � - * � - � 4 3 > 3 4 3 ) 5 3 � , / ) 3 �� � � � � * 3 � . 6 3 � 4 3 5 0 9 9 3 ) 1 3 1 � 1 3 > , 3 5 . / 0 ) � > 0 4 5 3 � : 3 4 � � 3 , . � � 1 @ + * . 9 3 ) . � � - ? , 3 �

# � � � > . 3 4 � - 1 @ + * . / ) 2 A � 4 3 . / 2 6 . 3 ) � ? 0 , . * � 6 0 , 1 / ) 2 � 9 0 . 0 4 � ? - * 3 � . 0 � 5 6 - ) ) 3 , �

� 3 ) * / 0 ) � ) 3 8 � ? 3 , . * � - . � . 6 3 � 9 - C / 9 + 9 � 1 3 > , 3 5 . / 0 ) � > 0 4 5 34 3 5 0 9 9 3 ) 1 3 1 � � � 6 3 5 < � . 6 3 � ? 3 , . � . 3 ) * / 0 ) � - . � , 3 - * . � . 8 0 � . / 9 3 *1 + 4 / ) 2 � . 6 3 � > / 4 * . � � � � 6 4 * � � 0 > � 0 : 3 4 - . / 0 ) � � � ) ; � 4 3 ( . 3 ) * / 0 ) / ) 2* 6 0 + , 1 � > - , , � ? 3 . 8 3 3 ) � . 6 3 � 9 / ) � � - ) 1 � 9 - C � � 1 3 > , 3 5 . / 0 ) � > 0 4 5 3 � B - , + 3 * �

! � !

� � � � � � � �

� � � � � ! � !

� � � � � � � � �

� � � � � � �� � � � � � � � � �

Page 64: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

64 Unitary Products Group

1. Remove the dot plugs from the two 5/16 inch holes in the blower motor and the filter access doors.

2. Insert at least 8 inch of 1/4 inch metal tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil.

3. Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pres-sure drop across a wet coil under field conditions would be inaccurate. To assure a dry coil, the compressors should be de-activated while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual CFM through the unit with clean 2 inch filters, can be determined from the curve in Figure 61 and 62.

After readings have been obtained, remove the tubes andreinstall the two 5/16 inch dot plugs.

NOTE: De-energize the compressors before taking any testmeasurements to assure a dry evaporator coil.

TABLE 34: BELT ADJUSTMENT

FAN MOTOR HORSE POWER 5 7.5 10 15 20 25

30 TON FORWARD CURVED SUPPLY FAN SIZE: 22 X 20

Belt Deflection Force (lbs) new belts - - 10.5 12.6 15.2 22.1

Belt Deflection Force (lbs) old belts - - 7.1 8.5 10.2 14.8

40 TON FORWARD CURVED SUPPLY FAN SIZE: 25 X 20

Belt Deflection Force (lbs) new belts - - 10.5 12.6 15.2 15.2

Belt Deflection Force (lbs) old belts - - 7.1 8.5 10.2 10.2

30 & 40 TON POWER EXHAUST FAN SIZE: (2) 15 X 15

Belt Deflection Force (lbs) new belts - 7.9 9.4 9.4 - -

Belt Deflection Force (lbs) old belts - 5.3 6.3 6.3 - -

25 TON FORWARD CURVE SUPPLY FAN SIZE: 22 X 20

New Belt - 10.5 10.5 12.6 15.2 -

Old Belt - 7.1 7.1 8.5 10.2 -

25 TON POWER EXHAUST

New Belt 10.5 10.5 12.6 - - -

Old Belt 7.1 7.1 8.5 - - -

Failure to properly adjust the total system air quan-tity can result in extensive blower damage.

Page 65: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 65

SUPPLY AIR DRIVE ADJUSTMENT

At unit start-up the measured CFM based on Figures 61 and62 may be higher or lower than the specified CFM. Toachieve the specified CFM, the speed of the drive may haveto be decreased or increased by changing the pitch diameter(PD) of the motor sheave as outlined below:

• (Specified CFM/Measured CFM) X PD of standard sheave = PD of new sheave.

Use the following tables and the PD calculated per the aboveequation to select a new motor sheave.

EXAMPLE

• A 30 ton unit was selected to deliver 12,000 CFM with a 20 HP motor and a 966 RPM drive, but the unit is only delivering 11,000 CFM per Table 33.

• Use the equation to determine the required PD for the new motor sheave (12,000 CFM/11,000 CFM X 6.9” = 7.53 inch).

• Use the 30 ton Table 37.To select a Browning 2B5V74 which will increase the speed of the unit’s drive and its supply air CFM 108.7%.

• New drive speed = 1.087 X 966 = 1,050 RPM

• New supply air = 1.087 X 11,000 = 11,957 CFM

• Re-use the existing belts and blower sheave.

.

New motor BHP = (speed increase) 3 X estimated motor BHPto original start-up with 11,000 CFM and 966 RPM = (1.087)3

X 13.5 BHP = 1.284 X 13.5 BHP = 17.3 BHP New motoramps = (speed increase)3 X measured motor amps at originalstart-up with 11,000 CFM and 966 RPM.

SYSTEM SETPOINTS

Constant Volume and Variable Air Volume:

Thermostat and space sensor offsets must be made externalto the unit. For internal settings, refer to the Settable Parame-ters Table 52. All parameters affecting the unit with that spe-cific set of options and for that specific application must bereviewed. In many cases, the default settings will be fine - butverify and fine tune where necessary.

Before making any blower speed changes reviewthe installation for any installation errors, leaks orundesirable systems effects that can result in lossof air flow.

Even small changes in blower speed can result insubstantial changes in static pressure and BHP.BHP or AMP draw of the blower motor willincrease (see table 35) by the cube ratio of theblower speed. Static pressure will increase by thesquare ratio of the blower speed. Tables 36, 37and 38 are for reference only. All blower speedchanges must be made by qualified personnel withstrict adherence to the fan laws.

TABLE 35: BLOWER SPEED RATE OF CHANGE

CHANGE IN RPM

CHANGE IN

CFM TSPBHP AND MOTOR AMPS

.90 .90 .81 .73

.93 .93 .86 .79

.95 .95 .90 .86

.98 .98 .95 .93

1.00 1.00 1.00 1.00

1.03 1.03 1.05 1.08

1.05 1.05 1.10 1.16

1.08 1.08 1.16 1.24

1.10 1.10 1.21 1.33

1.13 1.13 1.27 1.42

1.15 1.15 1.32 1.52

1.18 1.18 1.38 1.62

1.20 1.20 1.44 1.73

Page 66: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

66 Unitary Products Group

TABLE 36: 25 TON DRIVE ADJUSTMENT

7.5 HP Motor & 567 RPM Drive 10 HP Motor & 692 RPM Drive 15 HP Motor & 793 RPM Drive 20 HP Motor & 814 RPM Drive

%RPM& CFM

Req’d PD

Browning 2b5v_ _

%RPM& CFM

Req’d PD

Browning 2b5v_ _

%RPM& CFM

Req’d PD

Browning 2b5v_ _

%RPM & CFM

Req’d PD

Browning 2b5v_ _

- - - 81 4.2 42 83 5 50 85 5.8 58

- - - 85 4.4 44 87 5.2 52 88 6 60

- - - 88 4.6 46 90 5.4 54 91 6.2 62

- - - 92 4.8 48 95 5.7 57 94 6.4 64

- - - 96 5 50 97 5.8 58 97 6.6 66

100 4.2 42 100 5.2 52 100 6 60 100 6.8 68

105 4.4 44 104 5.4 54 103 6.2 62 103 7 70

110 4.6 46 108 5.6 56 107 6.4 64 109 7.4 74

114 4.8 48 112 5.8 58 110 6.6 66 118 8 80

119 5 50 115 6 60 113 6.8 68 126 8.6 86

124 5.2 52 119 6.2 62 117 7 70 - - -

129 5.4 54 123 6.4 64 123 7.4 74 - - -

TABLE 37: 30 TON DRIVE ADJUSTMENT

10 HP Motor & 617 RPM Drive 15 HP Motor & 743 RPM Drive 20 HP Motor & 856 RPM Drive “25 HP Motor & 933 RPM Drive”

%RPM& CFM

Req’d PD

Browning2B5V_ _

%RPM& CFM

Req’d PD

Browning2B5V_ _

%RPM& CFM

Req’d PD

Browning2B5V_ _

%RPM & CFM

Req’d PD

Browning2B5V_ _

- - - - - - 82 5.5 54 - - -- - - - - - 85 5.7 56 86 6.1 60- - - 86 4.8 48 88 5.9 58 89 6.3 62- - - 89 5 50 91 6.1 60 92 6.5 64

91 4.2 42 93 5.2 52 94 6.3 62 94 6.7 6696 4.4 44 96 5.4 54 97 6.5 64 97 6.9 68

100 4.6 46 100 5.6 56 100 6.7 66 100 7.1 70104 4.8 48 104 5.8 58 103 6.9 68 106 7.5 74109 5 50 107 6 60 106 7.1 70 114 8.1 80113 5.2 52 111 6.2 62 112 7.5 74 123 8.7 86117 5.4 54 114 6.4 64 121 8.1 80 - - -122 5.6 56 118 6.6 66 130 8.7 86 - - -126 5.8 58 121 6.8 68 - - - - - -

- - - 125 7 70 - - - - - -

Page 67: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 67

TABLE 38: 40 TON DRIVE ADJUSTMENT

10 HP Motor & 567 RPM Drive 15 HP Motor & 652 RPM Drive 20 HP Motor & 728 RPM Drive 25 HP Motor & 779 RPM Drive

%RPM & CFM

Req’d PD

Browning2B5V_ _

% RPM & CFM

Req’d PD

Browning2B5V_ _

%RPM & CFM

Req’d PD

Browning 2B5V_ _

%RPM & CFM

Req’d PD

Browning2B5V_ _

- - - - - - 82 4.7 46 84 5.1 50- - - - - - 86 4.9 48 87 5.3 52- - - 88 4.5 44 89 5.1 50 90 5.5 54- - - 92 4.7 46 93 5.3 52 83 5.7 56- - - 96 4.9 48 96 5.5 54 97 5.9 58

100 4.2 42 100 5.1 50 100 5.7 56 100 6.1 60105 4.4 44 104 5.3 52 104 5.9 58 103 6.3 62110 4.6 46 108 5.5 54 107 6.1 60 107 6.5 64114 4.8 48 112 5.7 56 111 6.3 62 110 6.7 66119 5 50 116 5.9 58 114 6.5 64 113 6.9 68124 5.2 52 120 6.1 60 118 6.7 66 116 7.1 70129 5.4 54 124 6.3 62 121 6.9 68 123 7.5 74

- - - 127 6.5 64 - - - - - -- - - 131 6.7 66 - - - - - -

TABLE 39: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON

5 HP Motor & 732 RPM Drive 7.5 HP Motor & 827 RPM Drive 10 HP Motor & 955 RPM Drive

%RPM& CFM

Req’dPD

Browning 2b5v_ _

%RPM& CFM

Req’dPD

Browning 2b5v_ _

%RPM& CFM Req’d PD Browning

2b5v_ _

100 4.9 46 92 5.1 48 93 5.9 56

104 5.1 48 96 5.3 50 97 6.1 58

109 5.3 50 100 5.5 52 100 6.3 60

113 5.5 52 104 5.7 54 103 6.5 62

117 5.7 54 108 5.9 56 107 6.7 64

122 5.9 56 112 6.1 58 110 6.9 66

Page 68: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

68 Unitary Products Group

GAS FURNACE OPERATINGINSTRUCTIONS

TO LIGHT THE MAIN BURNERS

1. Turn off electric power to unit.

2. Turn space temperature sensor to lowest setting.

3. Turn gas valve knobs to on position (Refer to Figure 27).

4. Turn on electric power to unit.

5. On Constant Volume units, set space setpoint to warmer or cooler as desired. (If sensor set point temperature is above room temperature, the main burners will ignite). If a second stage of heat is called for, the main burners for second stage heat will ignite for the second stage heat. For VAV units set morning warm-up thermostat far above the return air temperature and cycle the time clock OFF, then ON.

TO SHUT DOWN

1. Turn off electric power to unit.

2. Depress knob of gas valve while turning to off position. (Refer to Figure 27).

POST-START CHECKLIST (GAS)

After the entire control circuit has been energized and theheating section is operating, make the following checks:

1. Check for gas leaks in the unit piping as well as the sup-ply piping.

2. Check for correct manifold gas pressures. See Checking Gas Input.

3. Check the supply gas pressure. It must be within the lim-its shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the standby gas pressure exceed 13 inches, nor the operating pressure drop below 6 inches. If gas pressure is outside these limits, contact the local gas utility for corrective action.

MANIFOLD GAS PRESSURE ADJUSTMENT

Small adjustments to the gas flow may be made by turningthe pressure regulator adjusting screw on the automatic gasvalve. Refer to Figure 27.

Adjust as follows:

1. Remove the cap on the regulator. It's located next to the push-on electrical terminals.

2. To decrease the gas pressure, turn the adjusting screw counterclockwise.

3. To increase the gas pressure, turn the adjusting screw clockwise.

NOTE: The correct manifold pressure for each furnacemodule is 3.50 IWG 0.3.

TABLE 40: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON

7.5 HP Motor & 852 RPM Drive 10 HP Motor & 976 RPM Drive 15 HP Motor & 1069 RPM Drive

% RPM& CFM

REQ’DPD (in)

Browning2B5V_ _

% RPM& CFM

REQ’DPD (in)

Browning2B5V_ _

% RPM& CFM

REQ’DPD (in)

Browning2B5V_ _

96.4 5.3 52 93.7 5.9 58 94.2 6.5 64100.0 (Std.) 5.5 54 96.8 6.1 60 97.1 6.7 66103.6 5.7 56 100.0 (Std.) 6.3 62 100.0 (Std.) 6.9 68107.3 5.9 58 103.2 6.5 64 102.9 7.1 70110.9 6.1 60 106.3 6.7 66 108.7 7.5 74114.5 6.3 62 109.5 6.9 68 117.4 8.1 80

Each furnace module is equipped with an auto-matic re-ignition system. DO NOT attempt to man-ually light the burners.

Page 69: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 69

BURNER INSTRUCTIONS

To check or change burners, pilot or orifices, CLOSE MAINMANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWERTO THE UNIT.

1. Remove the screws holding either end of the manifold to the burner supports.

2. Open the union fitting in the gas supply line just upstream of the unit gas valves and downstream from the main manual shut-off valve.

3. Disconnect wiring to the gas valves and spark ignitors. Remove the manifold-burner gas valve assemblies by pulling back.

4. Remove the heat shield on top of the manifold support.

Burners are now accessible for service.

Reverse the above procedure to replace the assemblies.Make sure that burners are level and seat at the rear of thegas orifice.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise (or temperature difference between thereturn air and the heated air from the furnace) must lie withinthe range shown on the CGA/ETL rating plate and the data inTable 3.

After the temperature rise has been determined, the CFM canbe calculated as follows:

After about 20 minutes of operation, determine the furnacetemperature rise. Take readings of both the return air and theheated air in the ducts (about six feet from the furnace) wherethey will not be affected by radiant heat. Increase the blowerCFM to decrease the temperature rise; decrease the blowerCFM to increase the rise. Refer to Table 30 for supply airblower motor and drive data. Minimum allowable CFM is6,000 CFM. Limit will open below this rating.

CHECKING GAS INPUT

NATURAL GAS

1. Turn off all other gas appliances connected to the gas meter.

2. With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.

3. Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from Table 41.

If the actual input is not within 5% of the furnace rating (withallowance being made for the permissible range of the regu-lator setting), replace the orifice spuds with spuds of theproper size.

NOTE: To find the Btu input, multiply the number of cubicfeet of gas consumed per hour by the Btu content ofthe gas in your particular locality (contact your gascompany for this information - it varies widely fromcity to city).

FIGURE 27 - TYPICAL GAS VALVE

ManualShutoff

RegulatorCap

OutletPressureTap

TABLE 41: GAS RATE - CUBIC FEET PER HOUR

Seconds for One Rev.

Size of Test Dial

1/2 cu. Ft. 1 cu. Ft.

2 900 1800

4 450 900

6 300 600

8 225 450

10 180 360

CFM Btuh 0.8×1.08 F Degrees Temp Rise×--------------------------------------------------------------------------=

Page 70: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

70 Unitary Products Group

Example: By actual measurement, it takes 7 seconds for thehand on the one cubic foot dial to make a revolution with justa 570,000 Btuh furnace running. Read across to the columnin Table 24, headed 1 Cubic Foot where you will determinethat 525 cubic feet of gas per hour are consumed by the fur-nace at that rate. Multiply 525 x 1050 (the Btu rating of thegas obtained from the local gas company). The result of551,000 Btuh is within 5% of the 570,000 Btuh rating of thefurnace.

ELECTRIC HEATING

The electric furnace is operational as shipped from the fac-tory and does not receive any field adjustments.

COOLING OPERATING INSTRUCTIONS

COMPRESSOR

Compressors are factory mounted ready for operation (Seepage 63 Compressor Rotation).

OIL LEVEL - All compressors are factory charged with oil.Each compressor is equipped with an oil level sight glass.Check for proper oil level which is approximately to the centerof the sight glass. Recheck oil level at startup.

INTERNAL WIRING

Check all electrical connections in the unit control box;tighten as required.

CONDENSER FANS

Check for proper condenser fan rotation; clockwise facing theair discharge. If condenser fans are rotating backwards, linevoltage to unit single point power connection is misphased(See page 63 Compressor Rotation).

MILLENNIUM SEQUENCE OF OPERATION

OVERVIEW

The Millennium Simplicity control has comprehensive rulesets to respond to heat and cool calls, provide anti-shortcycleand other safeties, date / time clock, and other features mak-ing the programmable thermostat unnecessary. The Millen-nium Simplicity extends on the rules of the Synthesys digitalcontrol.

With an attached (optional) Room Sensor, the control pro-vides calls for heating and cooling and occupied override.The control determines when to start morning warm-up,mechanical cooling, or heat based on parameter settings inthe Millennium Simplicity control, its internal time clock,Occupied and holiday schedules, the deviation from the set-points, and the rate of temperature change.

A separate thermostat cannot determine if an output functionis available. For example, if the belts on the supply fan wereto break, the thermostat would still call for the fan to operateand, if space conditions require, call for heating or cooling.Logic in the control prevents undesired operation of heatingand cooling stages, with interlocks and minimum run times.Moreover, the control can report faults on its digital display oron a network to a monitoring system.

Control logic is designed such that airflow must be provenbefore any heating or cooling stage can operate. Mechanicalcooling is locked out below 40°Foutdoor ambient for all unitswithout head pressure control. The control provides voltageto energize the contactors for the supply fan, cooling stages,heating stages, and options such as the economizer andpower exhaust. The thermostat makes calls for cooling andheating; the Simplicity control is responsible for executing therules putting these calls into action and protecting the unitthrough appropriate safety devices. If the Millennium Simplic-ity senses low voltage, it will hold any call that energizes acontactor until the voltage is adequate. It will not alarm for lowvoltage, but will provide a flash code.

The control also energizes the supply fan and cooling stagesbased on external inputs from the thermostat:

• G - Supply Fan• Y1-1st Stage Cooling• Y2-2nd Stage Cooling• Y3-3rd Stage Cooling• Y4-4th Stage Cooling

FIGURE 28 - TYPICAL FLAME APPEARANCE

� � � � � � �� �

� � � � �

� � � � � � � � � � D � � � � � �

� � � � � � � � � � � � � � � � � � "

� � � � � � � � � � � � � � �

Page 71: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 71

Heating stages are controlled based on inputs:

• W1-1st Stage Heating• W2-2nd Stage Heating• W3-3rd Stage Heating

The economizer is enabled through settings in the controland operating conditions, or external BAS calls.

RUN SEQUENCE

The unit operates in one of three modes: Occupied, Unoccu-pied, and Recovery (Warm-up / Cool-down). The controlallows none, one, or two separate occupied / unoccupiedschedules for each day of the week, and twenty holidays. Inaddition to the programmed schedule, the space sensorallows a single key press to provide up to a 4-hour unoccu-pied override into the occupied mode.

OCCUPIED MODE: The supply fan operates continuously inthe Occupied and Recovery modes. The thermostat cyclescooling / heating to maintain the space temperature to theOccupied setpoints. Simplicity will enable optional econo-mizer and power exhaust features.

UNOCCUPIED MODE: The supply fan operates only withcooling / heating calls. The economizer is disabled during theunoccupied mode except when free cooling may be used tocondition the space. Cooling / heating stages are cycled tomaintain the space temperature to the Unoccupied setpoints.

RECOVERY MODE: A special unoccupied mode that allowstransition to occupied mode. The supply fan operates contin-uously and the economizer remains disabled. Instead ofmaintaining the unoccupied setpoints, the thermostat rampsthe space temperature toward the occupied setpoints. TheMillennium Simplicity control has an option for the control to“learn” how long it takes to get the building to the desiredtemperature, and adjust its start time to minimize the recov-ery time. Refer to the Intelli-Start section.

UNIT CONTROLS SEQUENCE

If the thermostat gives a call for G fan, W heating, or Y cool-ing, or the space sensor reading is not within the setpointrange; this is acted upon by unit control according to thesequence outlined below. A thermostat must not be con-nected anywhere but the appropriate labeled terminals.Direct control of compressors and heaters is not acceptable.

Abbreviations for various components correspond to thelabels on the wiring diagram.

1. On a call for the supply fan, voltage at terminal G is acted on by the control. If the supply fan overload is not tripped, voltage goes out from the FAN terminal on the control to either contactor 5M (Supply Fan Motor Starter) or relay FR (permission-to-run for the Variable Fre-

quency Drive). Power is applied to the airflow proving switch (APS). If the supply fan operates correctly (proper rotation), the pressure difference between the supply fan section and the heating section increases and APS closes to enable operation.

The air proving switch is monitored by the control 90 sec-onds after the fan is energized.

The control also monitors the supply fan overload. The overload circuit is wired directly to the control, not in series with the fan contactor. If the supply fan overload trips for longer than 5 seconds, the control will shut down the unit. If the trip clears within 15 minutes, the unit will log an error and resume operation. If the overload trips three times in two hours [or stays tripped longer than 15 minutes], the control will shut the unit down and report an alarm. In a VAV unit, the control will shut down the unit if the duct pressure shutdown setpoint is reached or exceeded.

2. Mechanical cooling stages have three monitoring cir-cuits: low pressure, high pressure, and internal [“mod-ule”] compressor overheat. They are connected to the control through the LPSx, HPSx, and C10, C20, etc., ter-minals. These allow the control to track specific error alarms, and let the control energize the next available compressor.

For units without optional head pressure control: If the outside air temperature rises above 50°F, the control enables all mechanical cooling stages. If the outside air temperature falls below 40°F and the unit does not have head pressure control, mechanical cooling stages are locked out.

For units with head pressure control: The first and second mechanical cooling stages are enabled when the ambient temperature rises above 10°F. When the ambi-ent temperature rises above 50°F, the third (on 30 and 40 ton) and fourth (40 ton only) stage mechanical cooling are enabled. If the outside air temperature falls below 40°F, mechanical cooling stages 3 and 4 (40 ton only) are locked out. If the outside air temperature falls below 0°F, all mechanical cooling stages are locked out. On units with optional heating, any call for heating engages

TABLE 42: COOLING STAGE

CALL ECONOMIZERMODE

MECHANICAL COOLING MODE

COOL 1 Economizer (N/A) Compressor 1

COOL 2 Compressor 1 Compressor 2

COOL 3 Compressor 2 Compressor 3

COOL4 Compressor 3 Compressor 4

Page 72: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

72 Unitary Products Group

the supply fan. Operation of heating is dependent upon the APS closure.

When all run rules are satisfied, cooling stages are avail-able. A call for first stage cooling, Y1, initiates the control rules for cooling. When the control is satisfied [tempera-ture, short cycling timing, safety circuits, etc.], it sends voltage out terminal C1 to contactor 1M for compressor 1. If compressor 1 is not available, the control will start compressor 2 via C2 / 2M.

In Occupied mode, the economizer is enabled [if installed and the parameter set in the control]; if free cooling is available, the economizer will energize in place of the first cooling stage.

A thermostat call for second stage cooling powers termi-nal Y2, third stage powers Y3 (30 and 40 ton) and fourth stage powers Y4 (40 ton only). These thermostat calls are entered into the control’s logic, and available cooling stages brought on to meet the demand.

NOTE: The economizer may function when all mechanicalcooling stages are locked out on low ambient.

3. When the control calls for Compressor 1 (25 ton), or Compressor 1 or 2 (30 and 40 ton), it will also call con-denser fan stage 1 through terminal CF1, powering the coil of contactor 6M (condenser fan 1). On 25 ton units, condenser fan 2 (contactor 7M) is brought on by PS5 if discharge pressure on compressor 1 exceeds 280 psi. Fan 2 drops out if discharge pressure drops below 180 psi; condenser fan 4 (contactor 8M) is brought on by PS6 monitoring discharge pressure on compressor 2.

4. A control call for Compressor 2 powers contactor 2M through terminal C2, and CF2 (fan 3) on 25 ton units. On 30 and 40 ton units, because fans 1 and 2 pull through coils for both circuit 1 and circuit 2, the coil of contactor 7M (condenser fan 2) is powered in turn through either of condenser fan cycling switches PS5 or PS6, which enables condenser fan 2 operation if the discharge pres-sure of Compressor 1 or Compressor 2 exceeds 280 psi.

5. 30 and 40 ton only: A call for Compressor 3 powers con-tactor 3M (contactor, compressor 3) from terminal C3. A call for Compressor 3 or 4 also powers terminal CF2, second stage condenser fans (contactor 8M, condenser fan 3, and also contactor 9M, condenser fan 4 - 40 ton only).

6. 40 Ton Only: A call for Compressor 4 powers the coil of contactor 4M from terminal C4.

7. Gas Heat Option, Stage 1: a W1 call locks out cooling and initiates the control logic for Heat 1. The supply fan is engaged, at full speed if VAV-equipped. Once APS (air proving switch) closes to acknowledge supply airflow, power is supplied from terminal H1, which engages Igni-tion Control 1 (IC1) at heat module terminal W/TH. 24V is supplied to IC1 at terminal R/24V, and to the overtemp limit switch LS1, which opens only with excessive heat

exchanger temperature, on each gas heat module. That switch is monitored by connecting each limit switch to the LIM1, 2, or 3 terminal at the Simplicity board. IC1 closes contacts between terminals L1 and IND to engage Draft Motor 1. The 24V signal downstream from the overtemp limit switch goes through the vent motor air proving switch circuit to the PSW terminal on IC1.

With LS1 and PS1 closed, IC1 will attempt ignition. IC1 provides direct spark ignition with flame verification, and controls the GV1 gas valve through manual reset switch RS1 (rollout switch). If RS1 has tripped, GV1 is locked out and IC1 will electronically lockout after three failed ignition attempts. The Simplicity control monitors voltage to the gas valves through terminals GV1-3.

When the W1 call is canceled, power is removed from IC1 terminal TH, which directs IC1 to close GV1. As long as APS continues to prove supply fan airflow, IC1 remains powered and keeps the L1 to IND contacts closed for 45 {60??} seconds to maintain the operation of Draft Motor 1 for a postpurge of the heat exchanger.

8. Gas Heat Option, Stages 2 and 3: the Millennium Sim-plicity responds to W2 and W3 similarly to W1, if the unit is equipped with second and third heat modules.

9. Electric Heat Option: the Millennium Simplicity control allows staging electric heat. On units with the Electric Heat Option, a call for heat (W1) will initiate the main supply fan. When the Simplicity control is satisfied by the APS, it will complete the circuit to the first stage of elec-tric heat by energizing terminal H1. If additional heat is required, H2 will energize the second stage of electric heat [if the unit is so equipped], and H3 the third stage [if the unit is so equipped].

All electric heat modules have an auto-reset primary limit, monitored by the control, and non-restartable back-up limits. Dirty filters, broken belts, fan motor burn-out or running this unit below 6,000 CFM will cause the limit to trip on the auto-reset primary limit. In addition to the pri-mary limit, back-up limits may trip under these condi-tions. The backup limits are one-trip devices and will have to be replaced should they trip.

When a call for heat has been satisfied, the highest stage running will be de-energized until all are de-ener-gized.

10. Hot Water Heat Option: the unit will send a 2-10 VDC signal to drive a hot water valve.

Disconnect all power supplies before checking orservicing the electric heat section.

Page 73: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 73

11. Economizer Option: the control directly controls the posi-tion of the outside air / return air dampers through a 2-10 VDC signal from terminal ECO to ACT1 (economizer actuator). The economizer is enabled only in Occupied or Recovery mode, and after supply fan operation has been verified (APS closed). When the supply fan is pow-ered and there is no Y1 call or if free cooling is unavail-able, the control opens the economizer dampers to the minimum position setting.

The actuator maximum opening speed is 150 seconds to full open; the control moves the actuator at the rate of two seconds for each one % it is opening, so full open from closed would take 200 seconds. At entry to Occu-pied mode, the economizer is typically opening from 0 to a minimum setting of 20%, which would take about 40 seconds. In Unoccupied mode, the economizer will close to 0%.

With a Y1 call when the outside air is appropriate for free cooling (see below), free cooling is used for first stage cooling. The control modulates the economizer dampers to maintain a SAT setpoint plus or minus one degree.

The control uses one of three methods to determine when free cooling is available. The method used is determined by the unit options, which function as listed below.

Dry Bulb: the control relies on the RAT, OAT, and SAT readings, connected to those terminals on the control. Free cooling will be available until the outdoor tempera-ture rises above the indicated temperature range. Free cooling is disabled when the outdoor temperature rises above the temperature range and cannot be enabled until the outdoor temperature falls below the indicated temperature range.

Single Enthalpy: The Outdoor Air Humidity Sensor is connected to terminal OAH. When the outdoor enthalpy is below the setpoint, free cooling is available.

Dual Enthalpy (Comparative/Differential Enthalpy): Both the Outdoor Air Humidity [OAH] and the Return Air Humidity [RAH] sensors are connected to the control. When the outdoor air enthalpy is less than the return air enthalpy, free cooling is available. The control will dis-able free cooling and force mechanical cooling when the outside air temperature exceeds setpoints.

12. Power Exhaust Option with Modulating Dampers: The power exhaust controls are enabled in Occupied or Recovery mode when the APS is satisfied. The building pressure is sampled by a tube provided and installed by the customer at a location in the building, connected to the high pressure port of the pressure transducer BPS. BPS provides a 0-5 VDC signal to the control, which compares the reading to the pressure setpoint to control the exhaust dampers. The exhaust damper vanes are modulated by ACT2, from a signal from terminal EXD+. The exhaust motor is energized by voltage at terminal

EXH to contactor 10M when the dampers are driven above the ON setpoint for damper open %.

The exhaust motor is powered OFF when the vanes reach the OFF % point set in control parameters. When the power exhaust is disabled, ACT2's spring return closes the exhaust dampers and 10M opens to shut down the exhaust fans.

13. Power Exhaust Option with Variable Frequency Drive: The power exhaust controls are powered through EXH / 10M with a call for the supply fan. Once powered, the BPS sensor (Building Pressure sensor) sends a signal to terminal 53 of the VFD. The damper vanes are gravity-closed; motor speed is continuously variable. See sepa-rate document for details on power exhaust VFD opera-tion.

14. Non-modulating Power Exhaust Option: The power exhaust motor is energized by EXH / 10M based on the position of the Economizer damper settings in the control parameters. Minimum run time is 10 seconds; minimum off time is 60 seconds. The outlet pressure of the power exhaust fan forces the barometric relief dampers open; gravity closes the dampers when the exhaust fan is off.

VARIABLE AIR VOLUME UNIT (VFD & IGV)

OVERVIEW

The VAV units operate in one of three modes: Occupied,Unoccupied, and Recovery. The unit operational mode isdetermined by the status of the internal clock and the internalschedules.

OCCUPIED / UNOCCUPIED / MORNING WARM-UP

OCCUPIED

In Occupied mode, all installed options enabled by theparameter settings are available. The supply fan is operated[controlled to the duct pressure setpoint if a VAV], optionalunit heating is available at full capacity, the optional powerexhaust system is enabled, the economizer outside air damp-ers go to their minimum position or open for free cooling. Thisoperation continues until the unit enters Unoccupied mode.When the control sees an Occupied override button pushfrom the thermostat or space sensor, it will go to Occupiedmode for the length of time set in the parameters, up to fourhours. If the unit is in Space Sensor operation, the fan willoperate at full speed [controlled to the duct pressure setpointif a VAV].

A VAV standalone unit will run MWUP the first hour of theOCC override signal, then go to Occupied. The supply fan willrun continuously.

UNOCCUPIED

In Unoccupied mode, the economizer goes to full closed; thesupply fan will only operate if there is a call for heating or

Page 74: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

74 Unitary Products Group

cooling [controlled to the duct pressure setpoint if a VAV]. Ifheating is required, all installed stages will be energized.

MORNING WARM-UP [MWUP]

The unit enters a morning warm-up mode going in to the firstOccupied period of the control’s internal daily schedule. Inthis mode, the supply fan is operated at full volume, optionalunit heating is engaged at full capacity if needed, the optionalpower exhaust system is enabled, the economizer outside airdampers close (return air dampers open), cooling is disabled,and voltage is provided at H1 to signal the remote VAV boxesto open. This operation continues until the return air tempera-ture exceeds the adjustable setpoint of the Morning Warm-upbulb thermostat (MWUP).

The parameter for MWUP must be turned on. Without Intelli-Start, MWUP will start one hour ahead of Occupied. Coolingwill not start until the Occupied mode starts. In MWUP, thecontrol will operate the fan and energize heat after monitoringRAT five minutes after going into MWUP, or if RAT goes twodegrees below the MWUP setpoint.

UNIT CONTROLS

1. The control reviews parameters, the unit clock, and occupied / Holiday schedules to select the appropriate mode. In Occupied mode, the unit will look at inputs enabled by parameter settings. It will default to second-ary inputs if necessary.

When the unit is running in Occupied mode, the duct pressure controller, if that option is installed, is activated; the optional power exhaust system is activated, power is applied to the airflow proving switch (APS), and to the supply fan motor contactor (5M) to engage the supply fan. If the supply fan operates correctly (proper rotation) the pressure difference between the supply fan section and the heating section increases and APS closes to enable operation. The control waits 75 [90??] seconds for the fan to reach equilibrium, then looks at the APS.

For units without optional head pressure control: If the outside air temperature rises above 50°F the control enables all mechanical cooling stages. If the outside air temperature falls below 40°F, then all mechanical cooling stages are locked out.

For units with head pressure control: Enable third and fourth (40 Ton only) stage mechanical cooling when the ambient temperature rises above 50°F. If the outside air temperature falls below 40°F, mechanical cooling stages 3 and 4 (40 Ton only) are locked out. Enable first and second stage mechanical cooling when the ambient tem-perature rises above 10°F. If the outside air temperature falls below 0°F, all mechanical cooling stages are locked out.

2. While the return air temperature remains below the set-point of MWUP (Morning Warm-up), engage the unit heat (optional) at full capacity.

For Inlet Guide Vane VAV: terminal VFD provides a 10VDC signal for the actuator, thus forcing the inlet guide vane dampers to fully open during the warm-up cycle. Terminal H1, heat stage 1, is used to signal the remote VAV boxes to open. In this warm-up mode, VAV and the economizer (optional) are disabled, so cooling is disabled and the optional economizer outside air damp-ers are closed.

3. When the return air temperature climbs above the MWUP setpoint, heating is disabled, VAV and the econo-mizer are enabled.

4. A call for first stage cooling initiates the cooling sequence. The optional economizer is enabled, and drives the damper to the minimum open position. If free cooling is available, dampers open to satisfy setpoints. If there is no economizer, the control powers terminal C1 to energize compressor 1.

The control provides a minimum of 30 seconds between each cooling stage call [see Lead-Lag], a 4 minute mini-

The bypass VFD is a standard Variable FrequencyDrive packaged with a further set of contactorsWhen bypass mode is activated, contactors routepower around the VFD, connecting the indoor fanmotor direct to supply voltage. At this point themotor will go to full RPM regardless of the ductpressure signal, because the VFD is out of theloop, and there is a potential for over pressuringthe ducts.

The air balancer must set maximum duct static /CFM to stay within a static pressure that the duct-work of that installation can tolerate when themotor is at full RPM, considering that the VAVboxes, if they are part of the system, may not befull open.

If the duct system includes VAV boxes, they mustbe driven open in Bypass mode in the same man-ner as going to heat mode. The drive indicatesbeing in “bypass” mode with normally open con-tacts wired to terminal block 1, position 5 and 6across Danfoss relay M3 [refer to drawings sup-plied by Danfoss, packed with the unit].

Voltage sufficient to signal the boxes to open mustbe wired through this contact. This is a field-installconnection.

Page 75: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 75

mum ON time for each cooling stage and a 5 minute min-imum OFF time for each cooling stage.

5. A call for Compressor 1 powers the high pressure safety switch (HPS1), the low pressure switch (LPS1), the coil of contactor 6M (condenser fan 1), and the coil of con-tactor 7M (contactor, condenser fan 2) through con-denser fan cycling switch PS5 (PS5 disables condenser fan 2 operation based upon the discharge pressure of the Compressor 1). If the system pressures are within HPS1 (high refrigerant pressure) and LPS1 (low refriger-ant pressure) switch settings and the solid state com-pressor motor protector (Compressor Module No. 1) is not tripped, contactor 1M is engaged to start scroll Com-pressor 1.

6. A call for Compressor 2 powers contactor 2M (contactor, compressor 2) if HPS2, LPS2 (high and low refrigerant pressure) and Compressor Module 2 (compressor motor protector) contacts are closed.

7. 30 and 40 ton only: A call for Compressor 3 powers the coils of contactors 8M (contactor, condenser fan 3) and 9M (contactor, condenser fan 4 - 40 ton only). If HPS3, LPS3 (high and low refrigerant pressure) and Compres-sor Module 3 contacts are closed, power is applied to the coil of Contactor 3M, which starts compressor 3.

8. 40 Ton Only: A call for Compressor 4 powers the coils of contactor 4M if HPS4, LPS4 (high and low refrigerant pressure) and Compressor Module 4 contacts are closed.

9. When the internal time clock matches the setting in the holiday and daily schedules, the unit enters Unoccupied mode. The control disables the supply fan, the optional power exhaust, cooling, heating, and the economizer. The optional outside air dampers are closed with the optional inlet guide vanes.

10. When the space temperature falls below the heating set-point, the control powers contactor 5M from terminal FAN to engage the supply fan motor. If the supply fan operates correctly (proper rotation) the pressure differ-ence between the heating section and the supply fan section increases and APS closes to enable heating operation. If heat safeties are satisfied, the VAV speed signal (VFD or Inlet Guide Vanes) goes to maximum flow [the customer-installed connection will drive the VAV boxes to full open]. The control engages unit heat (optional) at full capacity. Until heat is energized, duct pressure control is activated. The optional power exhaust system is activated.

In heat mode, cooling is disabled and the optional econ-omizer outside air dampers are closed. This operation is maintained until the space temperature rises above the heating setpoint or Occupied mode is engaged.

11. Gas Heat Option, Stage 1: A call for heat engages Igni-tion Control 1 (IC1-terminal TH) from Simplicity terminal H1. Once APS (supply air proving switch) closes to

acknowledge supply airflow and the LIM1-3 safeties are satisfied, IC1 is powered. IC1 closes contacts between terminals L1 and IND to engage Draft Motor 1. The IC1 monitors PSW (draft fan air proving switch) and LS1 (heat limit switch, which opens only with excessive heat exchanger temperature). When the safeties are satisfied, IC1 will attempt ignition. IC1 provides direct spark igni-tion with flame verification and controls the GV1 gas valve through manual reset switch RS1 (rollout switch). If RS1 has tripped, GV1 is locked out and IC1 will electron-ically lockout after 3 failed ignition attempts. The Simplic-ity control also monitors the voltage going to the gas valve at terminals GV1-3.

When the W1 call is canceled, power is removed from IC1 terminal TH, which directs IC1 to close GV1. As long as APS continues to prove supply fan airflow, IC1 remains powered and keeps the L1 to IND contacts closed for 45 seconds to maintain the operation of Draft Motor 1 for a post-purge of the heat exchanger.

12. Gas Heat Option, Stages 2 and 3: These follow the same rules as Stage 1. Separate terminals and safety monitor circuits are wired to each installed heat stage. For gas heat, there is a separate overtemperature limit switch for each heat module.

13. Electric Heat Option: A call for heat stages electric heat on. Electric heat is available as 40kW [one stage], 80kW [two stages], or 108kW [three stages]. There is one over-heat limit for electric heat, regardless of the number of stages - contrasted with gas heat, which has individual over-heat limits on each module.

On units with the Electric Heat Option, a call for heat (W1) will initiate the main blower. The blower will pro-duce static in the supply and the Air Proving Switch (APS) contacts will close. The control recognizes closure of the APS and energizes the H1 terminal to complete the circuit to the first stage of electric heat.

In Occupied mode, if additional heat is required, the W2 signal will energize the second stage of electric heat through terminal H2; W3 / H3 function similarly. When the W2 call for heat has been satisfied, W2 will be de-energized and will in turn de-energize H2 second stage heat. As the call heat (W1) has been satisfied, W1 will be de-energized. If the unit is in Unoccupied mode, the fan will shut off and the APS will open. For units in space sensor control, the Simplicity will stage on heat as required to maintain space sensor temp, or SAT temp if the space sensor signal is lost.

All electric heat modules have an auto-reset primary limit and non-restartable back-up limits. Dirty filters, broken belts, fan motor burn-out or running this unit below 6,000 CFM will cause the limit to trip on the auto-reset primary limit. In addition to the primary limit, back-up limits may trip under these conditions. The back-up limits are one-trip devices and will have to be replaced should they trip.

Page 76: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

76 Unitary Products Group

14. When the space temperature rises above the Unoccu-pied cooling setpoint, the control enables optional duct pressure control and optional power exhaust system; power is applied to the airflow proving switch (APS) and to the coil of starter 5M to engage the supply fan motor. If the supply fan operates correctly (proper rotation) the pressure difference between the heating section and the supply fan section increases and APS closes to allow mechanical cooling operation. The unit operates as though it were in the Occupied mode (see above) until the space temperature falls below the cooling setpoint or Occupied mode is engaged.

15. Duct Pressure Control - Inlet Guide Vane Option: The duct pressure controls are powered with a call for the supply fan. Once powered, the pressure transducer DPS provides a voltage signal input to the Simplicity control. The control calculates a 2-10VDC signal to the inlet guide vane actuator.

16. Duct Pressure Control - VFD (Variable Frequency Drive) Option: The duct pressure controls are powered with a call for the supply fan. Once powered, the VFD responds to a VDC control signal from the DPS (Duct Pressure transducer). In the heating mode the VDC, DPS pressure signal forces the fan to full volume. VAV boxes should be tied to the H1 terminal to signal the boxes to full open.

17. Electronic Economizer Option: The control directly controls the position of the outside air / return air damp-ers through a 2-10 VDC signal to ACT1 (economizer actuator). The economizer is powered only after supply fan operation has been verified (APS closed) and the unit is in Occupied or Recovery mode. When the control is not powered or is in Unoccupied mode, the outside air dampers spring return closed. When in Occupied or Recovery mode and there is no Y1 call or if free cooling is unavailable, the Simplicity control opens the econo-mizer dampers to the minimum position setting made in the parameters.

With a Y1 call where the outside air is appropriate for free cooling (see below), the control modulates the vanes for free cooling in place of first stage cooling. (Please see the compressor staging chart above.) The control modulates the economizer dampers to maintain a Mixed Air Temperature (Return Air / Outside Air Mixture, sensed between the filters and the DX coil) between 50°F and 55°F (adjustable between 40°F and 65°F).

The Simplicity control uses one of three methods to determine when free cooling is available. The method used is determined by the option selection.

Dry Bulb: The control refers to input from the OAT, and will allow free cooling when the outdoor temperature falls below the Economizer First Stage temperature setpoint. Free cooling will be available until the outdoor tempera-ture rises above the temperature setpoint.

Single Enthalpy: the control will consider, along with outside temperature, outside air humidity [OAH sensor; parameter must be set to ON] in enabling free cooling. The outside air enthalpy setpoint parameter [BTU per pound] must also be set.

Dual Enthalpy (Comparative/Differential Enthalpy): Both the Outdoor Air Enthalpy and the Return Air Enthalpy [RAH sensor, option parameter must be set to ON] are connected to the control. The setpoint when the outdoor air enthalpy is less than the return air enthalpy, free cooling is available. The rules in the control will lock out free cooling and force mechanical cooling when the outside air temperature exceeds setpoints.

18. Power Exhaust Option with Modulating Dampers: The power exhaust controls are enabled in Occupied mode. The building pressure sensor [BSP] provides a signal to the control. The exhaust dampers are modu-lated by a 2-10VDC signal from the control, proportional to the pressure sensed, to the damper actuator. When the actuator opens the damper more than the parameter “Exhaust Damper Position for Exhaust Fan to Turn ON” setting, the Simplicity control powers the 10M starter to engage the power exhaust fan motor. When the dampers reach the ”Exhaust Damper Position for Exhaust Fan to Turn OFF” setting, the control turns the motor off. When the power exhaust is disabled, the control closes the exhaust dampers.

19. Non-Modulating Power Exhaust Option: The power exhaust controls are enabled by the Simplicity control. The control powers the exhaust fan motor by monitoring the position of the economizer damper vanes [“Econo-mizer Damper Setting for Exhaust Fan to Turn ON [OFF]”]. The outlet pressure of the power exhaust fan forces the barometric relief dampers open. Exhaust Fan operation is continued until the economizer reaches the % set in the parameter Gravity closes the barometric relief dampers when the exhaust fans are off.

20. Power Exhaust Option with Variable Frequency Drive (VFD): The power exhaust controls are enabled through the Simplicity control. The variable frequency drive is controlled by a signal from the control, based on the Building Pressure sensor (BPS), located in the control box, which translates the building pressure signal to a VDC signal. Fine tuning is accomplished by setting parameters in the VFD [ref: separate instruction].

NOTE: Modulated exhaust: Pressure-tap tubing must berun from an appropriate location in the building tothe "high" port on the BPS transducer. Dampers onthe VFD power exhaust are gravity-closed and arenot modulated. The BPS signal is proportional withthe difference between outside ambient pressureand building pressure. The VFD is set for a mini-mum speed of 33% and a maximum of 100%. TheVFD parameters are factory set, specific for eachcontrol system, and are detailed on a sticker by thedrive. The drive manual is shipped with the unit.

Page 77: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 77

NOTE: For smoke purge, etc., special connections: forstandard controls, consult a controls specialistfamiliar with your local codes.

HEAD PRESSURE CONTROL

DESCRIPTION

The head pressure control option controls the speed of con-denser fan 1 for low ambient mechanical cooling operation ofsystems 1 and 2. This option functions independently of theSimplicity control.

The option includes two pressure transducers and a variablefrequency drive. The pressure transducers are connected tothe discharge line of system 1 and 2. The VFD modulates tothe higher signal; if either system 1 or 2 exceeds 280 psi, asecondary mechanical switch close to turn on fan 2. Typicallythe modulated fan will slow down; if both systems drop below180 psi, fan 2 drops out.

System 3 on a 30 ton and system 3 and 4 on a 40 ton arelocked out below 45°F ambient.

NOTE: Altering the factory settings could result in poor con-trol or operation of the system.

No special motor is required on three-phase systems; singlephase systems will use three phase motors on fan 1. Thevariable Frequency Drive is pre programmed at the factory.

SEQUENCE OF OPERATION - FOR HEAD PRES-SURE CONTROL

A call for the first stage cooling powers the 6M contactorenergizing the variable frequency drive. The drive will ramp tothe pre programmed minimum speed of 20 Hertz immediatelyupon start up. As the discharge pressure on system 1 or 2compressor rises, the transducer output signal to the variablefrequency drive rises. The drive will increase the speed ofcondenser 1 fan, maintaining a setpoint of 240 PSI.

The scroll compressor produces a rapid rise in dischargepressure upon start up. This usually will result in full speedoperation of condenser fan 1. After the discharge pressurehas settled out, the speed of condenser 1 may decreaseespecially during times when the ambient temperature isbelow 80°F. After the 1 system has stabilized and compressor

2 is energized, the speed of condenser Fan 1 will increase tocompensate for the discharge pressure rise. Typically, sincefan 2 will run at full speed, fan 1 will slow down when fan 2energizes.

As the ambient temperature drips below 40°F the 1 con-denser fan will slow to the minimum speed. The circuit 2 con-denser fan will disengage when the discharge pressure dropsbelow 180 PSIG as the ambient temperature falls. The dis-charge pressure of system 1 and/or 2 will increase when con-denser fan 2 stops, consequently causing an increase in thespeed of condenser fan 1.

The Millennium Simplicity control includes a terminal SD forthe user to wire a signal to shut down, and a Purge terminalto signal the unit to shut off heat or mechanical cooling, openthe economizer and exhaust dampers, and run the exhaustfan [depending on which options are installed on the unit].

INTELLI-START

If Intelli-Start is enabled the control will use that calculation todetermine when to start Morning Warm-Up. If the Intelli-Startoption is not enabled, the control will start Morning Warm-Upone hour before Occupancy.

When Intelli-Start is enabled, the control will attempt torecover the building to the Occupied Setpoint by the time theOccupied period begins. On the first day when the controlhas nothing stored for recovery, it will go “Occupied” twohours before the Occupied period. The control will store thebeginning demand and track the time it takes to reach theOccupied Setpoint. When the Occupied setpoint is reached,the control will store how long it took, and use that warm-upability to calculate the period needed the next time it runs.The control will store the recovery value separately for Heat-ing and Cooling. Unoccupied Recovery will only run on thefirst Occupied period of the day. It will always be operating onthe previous day’s performance. The Economizer will beused if free cooling is available.

Millennium Simplicity will accommodate inputs for water coilfreeze stat, SA sensor, ODA sensor, Space sensor, andRoom sensor, Building pressure sensor, Duct pressure sen-sor, Demand ventilation, RA humidity, OD humidity, RS485communications.

LEAD LAG

When this option is set ON, the unit will equalize run time oncompressors [except for compressor 1 if the head pressurecontrol option or hot gas bypass is installed].

DEVICES AND RULES

This chapter describes the many control modes of operationfor Simplicity. Because of the narrative and detailed descrip-tions contained in this section, you should only scan thischapter and become familiar with the primary topics. Then,

All power exhaust options require that the cus-tomer provide tubing connections to the trans-ducer from a representative location in thebuilding; modulating-vane and VFD exhausts willopen full / power on in Purge mode

Page 78: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

78 Unitary Products Group

use this chapter as a reference whenever a more detailedunderstanding of a particular mode is needed.

You should keep in mind that, especially with digital controls,interlocking between control modes is common and easilyachieved. Also, by the very nature of digital control program-ming, many simultaneous rules can be implemented becausethey generally require only software programming and verylittle peripheral hardware. This reduces the costs associatedwith manufacturing and servicing equipment with this level ofinteracting features - but you can’t see the status of inter-locked rules as you can with discreet relays.

Several control modes will override other modes of operation.

For example, The Demand Ventilation (or, Indoor Air Quality)control may override Comfort Ventilation / Economizer controland drive the OA dampers above the established minimumposition. The Excessive SAT control will override all tempera-ture control modes, Economizer mode, and compressor oper-ation as well. If you suspect that a problem exists with theeconomizer, or the compressors are locked out when noalarms are set, verify that one of the control modes is notoverriding the normal mode of operation or the operation youmight expect to see. Another important example is the AirProving Switch interlocking mode. If the Air Proving Switchalarms on a VAV unit, the unit will refer to the duct pressuresensor; if duct pressure is present, the control will assumethe fan is working even though the APS is not.

If the fan status [APS] fails, and the duct pressure switch of aVAV unit sees no duct pressure, all controlling algorithms andoperations, and outputs (except hydronic heat) will cease andthe control will shut down all outputs.

AIR PROVING SWITCH

When the control starts the supply fan, it waits 90 seconds tocheck for closure of the Air Proving Switch (APS). If the APSdoes not close, the control will turn off all outputs except Fanand the VFD speed signal, flag an alarm, and flash an alarmon the display. If it is a VAV unit, the control will look to theduct pressure signal; if it is above .05”, the control will flag abad APS and continue operation.

It will retry the Fan output every 30 minutes for three retries. Ifafter three retries it still cannot qualify the Fan, it will Alarmand lock all heating and cooling operation out. If the switchcloses after an alarm has been flagged, the control willresume normal operation and clear the active alarm.

After the control has turned off the fan, it will wait 90 secondsand verify that the switch opens. If the switch does not openafter 90 seconds, the control will flag a failed switch and flashthe alarm. On the next startup, the control will stage up equip-ment normally.

This switch-closed failure mode of the Air Proving Switch canonly be detected with the Supply Fan off. It is important to

detect because it effectively disables the fan failure alarmchecking while fan is running, described in the paragraphsabove. Those checks would always pass as the switch wouldremain closed. In networked applications, the error flag isreadable by the network. The alarm will automatically resetafter the problem that caused it has been corrected.

When the control is running the fan and the APS has alreadybeen proven, and then it opens, the control will wait 2 sec-onds before shutting down heating, cooling, and locking out.It will alarm and retry as if it happened during start-up.

FAN DELAYS:

There are separate Fan ON and OFF delay periods for heat-ing and cooling, to reduce the momentary change in SAT.

COMFORT VENTILATION MODE

Comfort Ventilation is a control mode that uses the econo-mizer to modulate SAT. Where possible, the economizer willmodulate the outside / return air mix to keep SAT within theupper and lower Comfort Ventilation setpoints. The controlwill modulate the economizer, and energize cooling or heat-ing if necessary, to keep SAT within the Comfort Ventilationsetpoints, even though space temperature may be satisfied.

For example, minimum economizer position can take SAT outof the Comfort Ventilation range, requiring heat or coolingthat the thermostat isn’t calling for. The result of comfort ven-tilation control is less variation of SAT, and fewer on-off cyclesof mechanical cooling or heating. If turning off a cooling stageraises SAT above the upper setpoint, but leaving it runningwill take SAT below the lower setpoint - then the compressoris left on, and warmer outside air is brought in to raise SAT tothe lower setpoint to keep a compressor from cycling off.Similarly, if leaving a heat stage on will raise SAT above theUpper setpoint, the control will leave heat on and modulatecooler outside air into the mix.

FIGURE 29 - COMFORT VENTILATION ECONO-MIZER CONTROL

High Supply Air Setpoint

Economizer Control Setpoint

(Middle of SAT Control Band)

Low Supply Air Setpoint

SAT Control Band

(Gray Area)

Page 79: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 79

The Comfort Ventilation temperature-band minimum width isfive degrees. Comfort Ventilation high and low setpoints willbe within the Cooling Upper and Heating Lower setpoints.

Without using the Comfort Ventilation mode where available,when the space temperature control loop is satisfied (zerodemand), all cooling and/or heating stages would be turnedoff and the SAT would be allowed to float until the space tem-perature control loop again generates a call for cooling orheating. The supply fan may be kept on during the “satisfied”periods, or may be turned off, depending on thermostat set-tings, or “Fan ON mode with the Sensor” option setting.

If Comfort Ventilation is selected, it will take priority over sup-ply fan control and keep it running during the “satisfied” peri-ods, when there is no call for heating or cooling. The ComfortVentilation mode is used to optionally replace the uncon-trolled, floating SAT situation during the “satisfied” periodswith a “loose” SAT control in a fairly wide temperature band(between specified Comfort Ventilation Upper Setpoint andComfort Ventilation Lower Setpoint). This may require someadditional energy, but improves space comfort (e.g. instead ofbringing a very hot and humid ventilation / outdoor air intospace during the “satisfied” periods, the ventilation air tem-perature is “trimmed” to be within the specified SAT controlband).

Comfort Ventilation mode terminates when there is a call forheating or cooling from the space temperature control.

• Comfort Ventilation can be used only on units equipped with an Economizer.

• Comfort Ventilation only operates in an Occupied mode.

• “Comfort Ventilation Mode” must be set to ON (default setting is OFF).

The modulating range of the economizer dampers are limitedby a specified Economizer Minimum Position and by a speci-fied Comfort Ventilation Maximum Economizer Setpoints.

The Economizer capability to control SAT may be further lim-ited in case the Demand Ventilation Operation is enabled andoverrides the economizer to a more-open position in order tosatisfy space IAQ requirements. The values of “Comfort Ven-tilation Upper Setpoint” and “Comfort Ventilation Lower Set-point” would typically be set such that they are centeredaround an expected return air temperature. The bandbetween the two setpoints should be set wide enough so thatSAT changes due to staging / destaging compressors, orheating stages, can be compensated for by the economizercontrol such that staging / destaging is minimized. Also, awider band minimizes use of additional energy during unit’s“satisfied” periods.

ECONOMIZER CONTROL DURING COMFORT VENTILA-TION

Economizer control uses a Proportional-Integral control algo-rithm that maintains SAT within the specified SAT band by

modulating the economizer dampers. The PI algorithm set-point is calculated as a midpoint between the programmed"Comfort Ventilation Upper Setpoint" and "Comfort VentilationLower Setpoint". As the controller uses outside air to maintainthe SAT at the setpoint, it must be capable of self-configura-tion for Direct, or Reverse action, depending on the relation-ship of the OAT to the specified SAT control band:

• If the OAT is below the specified SAT band low setpoint ("Comfort Ventilation Lower Setpoint"), the action is Direct Acting. In this case, the economizer control can lower the SAT temperature just by opening the econo-mizer damper and using more outdoor air. However, if the economizer algorithm can not prevent the SAT from dropping below the bottom control band limit by closing the economizer damper to its programmed minimum position, one or more heating stages may need to be turned on. Similarly, if the economizer algorithm can not prevent the SAT from increasing above the top control band limit, one or more compressors may need to be turned on.

• If the OAT is above the specified SAT band high setpoint ("Comfort Ventilation Upper Setpoint"), the action is Reverse Acting. In this case, the economizer control can increase the SAT temperature just by opening the econ-omizer damper and using more outdoor air. However, if the economizer algorithm can not prevent the SAT from increasing above the top control band limit by closing the economizer damper to its programmed minimum posi-tion, one or more compressors may need to be turned on. Similarly, if the economizer algorithm can not prevent the SAT from dropping below the bottom control band limit by opening the economizer damper, one or more heating stages may need to be turned on.

• If the OAT is within the SAT control band, i.e. between the programmed "Comfort Ventilation Upper Setpoint" and "Comfort Ventilation Lower Setpoint", the econo-mizer damper is driven to the fully open position. In this case, no other control action needs to be taken to main-tain the SAT within the specified control band.

STAGING CONTROL DURING COMFORT VENTILATION

The economizer control alone may not be able to maintainthe SAT within the specified control band. A separate stagingcontrol algorithm supplements the economizer control andwill stage heating, or mechanical cooling as necessary. If theSAT increases above the "Comfort Ventilation Upper Set-point" for more than 5 minutes, the control will destage aheating stage (if any heating stages running), or add a com-pressor. The control will repeat this process every 5 minutesuntil the SAT gets back to within the control band.

If the SAT drops below the "Comfort Ventilation Low SupplyAir Setpoint" for more than 5 minutes, the control will destagea compressor (if any compressors running), or add a heatingstage. The control will repeat this every 5 minutes until theSAT gets back to within the control band. As the heating

Page 80: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

80 Unitary Products Group

stages, or compressors are staged up, or destaged, theeconomizer controls continues using the economizer damperto "trim" the effect of the staging and to maintain the SAT asnear the middle of the SAT control band as possible.

If the unit is using hydronic heat, the control modulates thewater valve to maintain SAT at the programmed "ComfortVentilation Low Supply Air Setpoint". At this setpoint, thehydronic heat control does not conflict with the economizercontrol, and will prevent SAT from dropping outside of thespecified control band when the economizer can no longermaintain the SAT at its middle-of-the-band setpoint.

HYDRONIC HEAT

The Hydronic Heat option requires locating a SAT sensordownstream of the heating coil.

During hydronic heating, the SAT control to the selected“Hydronic Heat First Stage SAT setpoint”, or “Hydronic HeatSecond Stage SAT Setpoint” is performed using a Propor-tional / Integral control algorithm. The control algorithmincludes special provisions (sometimes referred to as a“bumpless transfer” feature) that allow it to resume control ofSAT as fast as possible when it is re-activated during the ON/ OFF cycling of the unit (cycling between a satisfied and aheating state under control of a zone thermostat, or zonesensor). In its OFF-state, the control algorithm continuesmonitoring the SAT and performs calculations necessary toset its output, that controls the hot water valve, to have thesame value on starting the ON-cycle as it had when it wentinto the OFF-cycle (in spite of some decrease in the SAT dur-ing the OFF-cycle).

The “bumpless transfer” feature of the hydronic heat controlalgorithm essentially acts similar to a “memory” that holds thealgorithm output during the OFF-cycles. This “memory” isreset only on unit shutdown. The effect of this “memory” canbe observed on the action of the hot water valve. After unitstartup (during the first ON-cycle of the hydronic heat), thereis no “memorized” output value and the valve moves rela-tively slowly into a control position required to maintain theSAT setpoint. On subsequent ON cycles, the valve movesinto a control position much faster as dictated by the outputvalue stored in control algorithm “memory”.

COOLING LOCKOUT ON OAT

This is the Outside Air Temperature Setpoint that the controluses to lock out mechanical cooling when the OAT is belowthis setpoint. There is a one-degree hysteresis on each sideof the setpoint. Adjustable from 0°F to 100°F, the default is45°F.

The change to 0°F applies only to compressors # 1 and # 2when head pressure control is installed. Cooling Lockout onOAT may occur while the control is in an Economizer modeand there is a demand for compressors.

WATER COIL FREEZE STAT (FSI)

This option is used only on rooftop units with hydronic heat(Hydronic heat option is turned ON). When the FSI terminalsees 24 VAC, the control will open the Hot Water valve to100%. The control will continue to drive the valve to 100%until five minutes after the switch has closed. If the control isoperating the Fan, it will close the Economizer fully until thefreeze condition is over. If the fan is off and the RAT dropsbelow 40°F, the Hot Water Valve will turn on 100%. This con-trol sequence takes place regardless of the supply fan status(it is expected to be used/ needed mostly in situations whenthe supply fan is not running). A Hot Water Coil Freeze Alarmis generated. The alarm is written to the Error History Buffer.In networked applications, the alarm flag is readable by thenetwork.

After the valve override sequence described above is com-pleted, the valve will revert to normal operation and the alarmis automatically reset. The same sequence is repeated everytime the Hot Water Coil Freeze Switch opens (infinite retries).

CV OPERATION

The paragraphs below identify control modes of CV operationand provide an overview of control methods in all modes. Themodes include Occupied and Unoccupied Heating and Cool-ing, and differ depending on the method used to control zonetemperature (thermostat, or a space sensor). The heating vs.cooling modes are entered under control of the thermostat,or, in case of space sensor, control algorithm detecting zonecooling or heating demand. The "occupied" vs. "unoccupied"modes are controlled by an internal time clock. If a thermostatis connected in addition to the space sensor, it takes priorityover the space sensor.

THERMOSTAT OPERATION FOR COOLING WITH Y1, Y2, Y3 AND Y4 INPUTS

When connected to a thermostat, the Millennium Simplicitycontrol will apply internal rules to specific G, Y1, W1, etc.,requests for fan, cooling, or heating; other inputs such asSAT, economizer availability, etc., will be considered beforeacting on the thermostat request.

When stage outputs are de-energized, and when the fourtime delay settings in "Fan ON Delay for Heat, OFF for heat,ON for Cooling, and OFF for Cooling" are made, the Fan out-put will continue for the set time even if the G input becomesinactive along with Y1 and Y2. If G does not terminate, thecontroller will continue to operate the Fan.

A Minimum Run Time of up to ten minutes applies to all com-pressors. There is a built-in five-minute ASCD cycle when-ever a compressor is destaged. The minimum run time isnecessary to ensure that the oil in the refrigerant circuit circu-lates back to the compressor. A minimum ASCD delay of fiveminutes (nominal) applies any time compressor operation is

Page 81: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 81

started other than destaging. The actual minimum off timesfor individual compressors differ by 10 seconds in order toprevent compressors from turning on simultaneously duringcertain control mode transfers:

GROUPING COMPRESSORS INTO STAGES

In space sensor operation in CV mode: On two compressorunits, compressor one is first stage and compressor two issecond stage. On three compressor units, compressors oneand two are first stage and compressor three is secondstage. On four compressor units, compressors one and twoare first stage and compressors three and four are secondstage. There is a five-minute delay (cooling interstage delay)between stage-one and stage-two operation

Otherwise the system treats each compressor as a stage.

ECONOMIZER MODE

In CV cooling with a thermostat and when free cooling isavailable ("economizer suitable"), the SAT controlled by theeconomizer control algorithm (see section Economizer Oper-ation later in this manual) and the thermostat determines (by1st and 2nd stage calls) the active economizer SAT setpoint.When the thermostat is satisfied (Y1=OFF, Y2=OFF), thenthe unit either shuts down (in case G=OFF) after the specifiedsupply fan overrun time, or only the supply fan continues tooperate (in case G=ON). The operation of the thermostat's Gsignal is determined by the thermostat's fan mode switch

NOTE: During Economizer operation using "EconomizerFirst Stage Setpoint" for SAT control, one or morecompressors may be running in addition to econo-mizer damper partially, or fully open to provide freecooling. The number of compressors running willmainly depend on outdoor air temperature. There-fore, when the thermostat is satisfied and shutsdown the cooling, it may be turning off more thanone compressor (after compressor minimum runtime expires). This is acceptable and is notexpected to occur frequently. See the section onComfort Ventilation. If the outdoor air condition issuch that more than one compressor is needed inaddition to free cooling, the Economizer mode islikely to terminate and the unit will switch over tomechanical cooling only.

OPERATION FOR HEATING WITH W1, W2, AND W3 INPUTS

W1, W2, and W3 inputs are available on the Millennium Sim-plicity board.

SUPPLY FAN OFF DELAY

When the Wx thermostat signal is de-energized, the fan out-put will continue until the SAT drops below 100°F with a 5°Fdifferential to prevent fan cycling, i.e. the fan will go off whenthe SAT drops below 95°F. This control sequence will be ineffect even if G becomes inactive along with Wx. If G doesnot terminate, the Fan will continue to operate. The parame-ter “Turn Off Continuous Fan Operation When Starting Heat”can be set to the customer’s preference.

HEAT STAGE DELAYS

Three minute Minimum Run Time and two minutes minimumoff time applies to all heat stages.

THERMOSTAT OPERATION WITH HYDRONIC HEAT

The zone thermostat makes a selection between satisfiedstate (W1, W2, and W3 off), heating using a programmed"Hydronic Heat 1st Stage SAT Setpoint" (W1 is on, W2 is off),or heating using a programmed "Hydronic Heat 2nd StageSAT Setpoint" (both W1 and W2 are on). During heating, theSAT control to the selected SAT setpoint is performed using aPI algorithm.

SENSOR OPERATION

Typically, only a thermostat, or only a space sensor would beinstalled. However, there are cases where both could exist.One such case is servicing or troubleshooting the unit. A ser-vice person will typically hardwire the thermostat inputs tocheck the equipment operation even if the unit is using aspace sensor. The thermostat input will have priority over theSpace Sensor. A unit using a space sensor will switch to athermostat control strategy automatically if a thermostat inputis detected and switch back if the thermostat is no longerdetected.

TYPES OF SPACE SENSORS

No Sensor- The system will internally detect the presenceof space sensors.

Sensor with Unoccupied Override Button - This Sen-sor has a Thermistor and an Override button that shorts theSensor when pushed. If the Override button is pushed theunit will go into the Unoccupied Override mode for the Unoc-cupied Override Time (note that the control must not recog-nize the short as a sensor failure). Once the UnoccupiedOverride mode is initiated, it will continue until the pro-grammed Unoccupied Override Time Limit is reached.

TABLE 43: COMPRESSOR MINIMUM OFF TIMES

COMPRESSOR MIN. OFF TIME

#1 4 min. 40 sec

#2 4 min. 50 sec

#3 5 min. 00 sec

#4 5 min. 10 sec

Page 82: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

82 Unitary Products Group

Sensor with Space Setpoint Adjust - This Sensor hasa slider potentiometer on it that represents (as a default) +/-3°F adjustment to the Space Setpoint. The Space SetpointOffset option. If the unit appears to be controlling at a higheror lower temperature than the setpoint, check the Space Set-point Adjust slider.

SUPPLY FAN CONTROL WHEN USING A ZONE SENSOR

In the Occupied mode, setting of the parameter "Fan ONmode with the Sensor Option" will determine if the SupplyFan is ON continuously, or is in "Auto" mode (i.e. cycles withthe heating/ cooling cycles). In Unoccupied mode, the fan isalways in the Auto mode.

SUPPLY FAN OFF DELAY

Uses minimum off time.

CONTROL OF COMPRESSORS WHEN USING A ZONE SENSOR

A Minimum run time of one to ten minutes [default = three]applies to all compressors. The minimum run time is neces-sary to ensure that the oil in the refrigerant circuit circulatesback to the compressor.

The Anti Short Cycle delay of five minutes OFF applies anytime compressor operation is terminated. Compressors areturned ON and OFF individually during CV operation with azone sensor, where the cooling control algorithm is imple-mented in the controller (rather than in a thermostat).

The stage groups are applicable only for control of compres-sors with external signals, such as from a thermostat.

There is a minimum 30 second delay between compressorswhen bringing on multiple compressors.

HEATING OPERATION WITH THE SENSOR OPTION

The space temperature is controlled to a programmed Unoc-cupied Heating Setpoint, or to a programmed Occupied Heat-ing Setpoint, as determined by the internal schedule and thestate of the Occupied Input (if this input is ON during a sched-uled unoccupied time, the unit goes to Occupied Overridemode).

The control will use as many as three stages of heat, depend-ing on what heat option is are installed.

A zone heating demand of -1.5°F will generate a request forfirst stage heat.

A zone heating demand of -2.0°F will generate a request forsecond stage heat.

A zone heating demand of -2.5°F will generate a request forthird stage heat. There is a three minute minimum off delayand a thirty second delay between stages.

When the zone temperature is -0.1°F, or less below the zonesetpoint for at least 1 minute, the transition to a satisfied stateoccurs, the heating stops and the supply fan either continuesrunning, or is turned off after SAT drops below 100°F. Thesupply fan control in the satisfied state and in the occupiedmode is determined by setting of the programmable parame-ter "Fan ON Mode with the Sensor Option". In the unoccupiedmode, the fan is always turned off when the zone is satisfied.

During heating, the SAT control to the selected SAT setpointis performed using a PI algorithm. Two minute Minimum RunTime and Anti Short Cycle delays applies to all heat stages.There is also a delay of at least one minute between turningon heating stages.

COOLING OPERATION WITH THE SENSOR OPTION

The control will operate as a two-stage unit.

On two compressor units, compressor one is first stage andcompressor two is second stage.

On three compressor units, compressors one and two arefirst stage and compressor three is second stage.

On four compressor units, compressors one and two are firststage and compressors three and four are second stage.

The control uses a minimum 30-second compressor delaybetween compressors when bringing on a stage with multiplecompressors.

A zone cooling demand 1.5° makes a call for first stage cool-ing.

A zone cooling demand 2.0° makes a call for second stagecooling.

If the unit has a demand greater than 1.5° but less than 2.0°,the control will turn on the first compressor of stage one andload a 5-minute timer. If after 5 minutes the Space tempera-ture is not moving toward the Setpoint, the control will turn onthe second compressor of stage one, if available, and wait 5minutes. The control will continue operating first stage untilthe Space temperature reaches the Setpoint and then it willturn off the stage one compressor. If after 5 minutes theSpace temperature is not moving toward the Setpoint, thecontrol will turn on the first compressor of stage two and wait5 minutes. The control will continue to turn on compressorsusing the 5-minute trending timer until the Space Tempera-ture begins to move toward the Setpoint. The control will turnoff all the second stage compressors with a 30-second delaybetween them when the demand reaches .5°F. The controlwill continue operating first stage until the Space temperaturereaches the Setpoint and then it will turn off the entire stageone compressor.

If the unit starts with a demand greater than 2.0°F, the controlwill stage up first stage and wait 5 minutes. The control will

Page 83: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 83

continue operating first stage until the Space temperaturereaches the Setpoint and then it will turn off all the stage onecompressors with a 30 second delay between them. If after 5minutes the Space temperature is not moving toward the Set-point the control will turn on the first compressor of stage twoand wait 5 minutes. The control will continue to turn on com-pressors until the Space Temperature begins to move towardthe Setpoint using the 5 minute trending method. The controlwill turn off all the second stage compressors when thedemand reaches .5°F with a 30 second delay between them.The control will continue operating first stage until the Spacetemperature reaches the Setpoint and then it will turn off theentire stage one using a 30 second delay between compres-sors if more than one is on.

VAV OPERATION

The paragraphs below identifies control modes of VAV opera-tion and provides an overview of control methods in allmodes. The modes include Occupied and Unoccupied Heat-ing and Cooling and differ depending on the method used tocontrol zone temperature (thermostat, or a space sensor).The heating vs. cooling modes are entered under control ofthe thermostat, or, in case of space sensor, by control algo-rithm detecting zone cooling, or heating demand. The "occu-pied" vs. "unoccupied" modes are controlled by the internal"Occupied/unoccupied" clock and the tables. If a thermostatis connected in addition to the space sensor, it takes priorityover the space sensor.

VAV OPERATION WITH A THERMOSTAT

The thermostat is placed in a selected, representative zone ofa VAV system and is used to reset SAT and cycle the VAVunit in cooling and to control heating. It is expected that thethermostat provide Yx outputs to control cooling and Wx out-put to control heating. The thermostat is expected to providean output to control occupied/unoccupied mode (a contactclosure that supplies in the occupied mode 24 VAC to the"OCC" Input).

As the thermostat has a capability to turn off the unit in occu-pied cooling mode, it is important to place it in a zone that isrepresentative of the remaining zones, or in a zone with thehighest occupied cooling demand.

The VAV zones are controlled by their own zone thermostatsto a temperature setpoint set independently of the setpointsof the "system control" thermostat; the setting of the occupiedcooling setpoint on the "system control" thermostat should atleast roughly correlate to the zone temperature setpoint. Forexample, the occupied cooling setpoint may be set at, orbelow the lowest zone temperature setpoint selectable on thezone thermostat. The setpoint setting should prevent a possi-bility of cooling turned off while other zone(s) in the systemstill have a cooling demand.

VAV OPERATION WITH A ZONE SENSOR

The Space Sensor is placed in a selected, representativezone of a VAV system. It is used to reset SAT in cooling andto control occupied heating based on comparison of zonetemperature to a programmed "VAV SAT Reset Setpoint".However, since the zone is controlled by its own zone ther-mostat to a temperature setpoint set independently of theVAV SAT Reset Setpoint, the setting of the VAV SAT ResetSetpoint should at least roughly correlate to the zone temper-ature setpoint.

For example, the VAV SAT Reset Setpoint may be set at, orbelow the lowest zone temperature setpoint selectable on thezone thermostat, in order to prevent a possibility of insuffi-cient cooling while other zone(s) in the system still have ahigh cooling demand. In unoccupied modes, the Space Sen-sor controls the unit based on unoccupied heating and cool-ing setpoints programmed in the unit controller.

The use of a Space Sensor is enabled by setting a program-mable parameter "VAV Operation with Thermostat". Whenthe Space Sensor is enabled, the control self-configures to aVAV operation with a Space Sensor if the sensor is available,and to a Return Air Temperature operation if the sensor is notavailable.

STANDALONE VAV OPERATION

In standalone operation the control unit receives an occu-pied/unoccupied command from an external source (such asa contact closure on the space sensor input). In occupiedcooling mode, it controls to the Low SAT setpoint. In unoccu-pied mode, the unit shuts down. In unoccupied mode, anexternal (network) command may be provided to start aMorning Warm-up cycle. The MWU cycle (if enabled) will alsostart upon a transition from Unoccupied to Occupied mode.

SUPPLY FAN OFF DELAY

Uses fan off delay.

OCCUPIED HEATING WITH A THERMOSTAT

When the unit enters the Occupied mode heating is startedby the thermostat turning ON its W1 output. In the Occupiedmode the thermostat will control to its occupied heating set-point. The thermostat's occupied heating setpoint should beset well below the zone thermostat's cooling setpoint, to rep-resent a heating setpoint typical for all system zones.

In VAV heating, full heating (all heating stages ON) occurswhen W1=ON, and no heating (all heating stages OFF)occurs when W1=OFF (note that in this case, the control willuse all available heating stages, regardless of setting of theprogrammable parameter "Heat Stages").

Page 84: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

84 Unitary Products Group

The supply fan operates at 100% during heating. Dependingon the control setting, the fan will cycle On/Off with the W1output, or will remain On. On startup, the fan speed is rampedup, or the inlet vanes ramped open (a "soft start").

During occupied heating, the economizer damper remains atminimum position and all VAV boxes are fully open - box heatrelays are energized from Heat output of the controller. IfHydronic heat option is used, the Heat output of the controlleris also actuated during heating, the SAT is controlled to the2nd stage hydronic heat setpoint.

UNOCCUPIED HEATING WITH A THERMOSTAT

This operation is identical to the Occupied heating, exceptthe unit mode is in Unoccupied mode from the internal controlOccupied/Unoccupied table. The economizer damperremains fully closed in the unoccupied mode.

OCCUPIED COOLING WITH A THERMOSTAT

In this mode, the control uses a thermostat for cooling andfan operation. The thermostat's occupied cooling setpointshould be set below the zone thermostat's lowest adjustablecooling setpoint, to prevent a possibility of cooling turned offwhile other zone(s) in the system still have a cooling demand.

UNOCCUPIED COOLING WITH A THERMOSTAT

This operation is identical to the Occupied cooling, exceptwhen operating in the unoccupied mode the control is pro-grammed to control to its unoccupied cooling setpoint and theeconomizer damper min. position is set to 0%, however thedamper may modulate open if outdoor air can be used forfree cooling (economizer operation).

OCCUPIED HEATING WITH A SPACE SENSOR

The Space Sensor is placed in a selected, representativezone of the VAV system, in addition to the zone thermostat, orsensor used to control the zone's VAV box. The heating con-trol algorithm is enabled whenever the zone temperaturedrops 2°F or more below a programmed "VAV SAT Reset Set-point ", and disabled whenever the zone temperature is 1.5°F,or less below a programmed “VAV SAT Reset Setpoint". The"VAV SAT Reset Setpoint" would typically be set at, or belowthe lowest zone temperature setpoint selectable on the zonethermostat.

The supply fan is controlled to 100% during occupied heatingand cycles OFF when the heating control algorithm is satis-fied if there is no other call for the fan. On startup, the fanspeed is ramped up, or the inlet vanes ramped open (a "softstart").

When a call for heating (W1 or W2=ON) occurs, the econo-mizer damper remains at its programmed minimum positionand all VAV boxes go fully open - box heat relays are ener-gized from Heat output of the controller.

If Hydronic heat option is used, the Heat output of the control-ler is also actuated during heating and the SAT is controlledto the 2nd stage hydronic heat setpoint.

UNOCCUPIED HEATING WITH A SPACE SENSOR

When this mode is enabled and the unit enters the unoccu-pied mode, the unit will control heating by comparing thezone temperature to a programmed "Unoccupied HeatingSetpoint". The Space Sensor should be placed in a selected,representative zone of the VAV system, in addition to thezone thermostat, or sensor used to control the zone's VAVbox.

Full heating (all heating stages ON) occurs when the SpaceSensor algorithm requests heating, no heating (all heatingstages OFF) when the Space Sensor algorithm is satisfied(note that in this case, the control will use all available heat-ing stages, regardless of setting of the programmable param-eter "Heat Stages").

The supply fan is controlled to 100% during unoccupied heat-ing and cycles OFF when the Space Sensor control algorithmis satisfied if there is no other call for the fan. On startup, thefan speed is ramped up, or the inlet vanes ramped open (a"soft start").

During unoccupied heating, the economizer damper is fullyclosed and all VAV boxes go fully open - box heat relays areenergized from Heat output of the controller.

OCCUPIED COOLING WITH A SPACE SENSOR

This mode is entered when the control sees a Space Sensorsignal and enters the "occupied" mode. The Space Sensorrequests cooling (to a programmed High, or Low SAT set-point) whenever the zone temperature increases by a speci-fied amount above a programmed "VAV SAT Rest Setpoint".The Space Sensor should be placed in a selected, represen-tative zone of the VAV system, in addition to the zone thermo-stat, or sensor used to control the zone's VAV box.

The "VAV SAT Reset Setpoint" would typically be set at, orbelow the lowest zone temperature setpoint selectable on thezone thermostat, in order to prevent a possibility of insuffi-cient cooling while other zone(s) in the system still have ahigh cooling demand.

The supply fan, economizer, VAV boxes operate within theirnormal control rules.

UNOCCUPIED COOLING WITH A SPACE SENSOR

In this mode, the Space Sensor requests cooling based oncomparing the zone temperature to a programmed "Unoccu-pied Cooling Setpoint". When the Space Sensor control algo-rithm requests cooling, the unit runs cooling controlled to aprogrammed High SAT setpoint ("VAV Upper Cooling SATSetpoint"), or to a programmed Low SAT Setpoint ("VAVUpper Cooling SAT Setpoint"), as determined by comparison

Page 85: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 85

of zone temperature to a programmed "VAV SAT Reset Set-point". The "VAV SAT Reset Setpoint" would typically be setwell below the "Unoccupied Cooling Setpoint", causing theunoccupied cooling to typically use a Low SAT Setpoint.

There are two different SAT control algorithms, one usedwhen free cooling is available (economizer operation) and theother one for mechanical cooling only. These two SAT controlalgorithms are described in the “Occupied Cooling in Standa-lone Operation” section below. Since the economizer is notactive in Unoccupied mode, this will be restricted to mechani-cal cooling.

UNOCCUPIED HEATING IN STANDALONE OPERATION

Unoccupied heating is never used in standalone operation.

OCCUPIED COOLING IN STANDALONE OPERATION

The unit controls cooling to a programmed Low SAT setpoint("VAV Lower Cooling SAT Setpoint") during the occupiedmode. There are two different SAT control algorithms, oneused when free cooling is available (economizer operation)and the other one for mechanical cooling only. First, whenfree cooling is available ("economizer suitable"), the SAT con-trol algorithm is as described in the Economizer Operationsection later in this document, except the programmed Econ-omizer First Stage Setpoint and Economizer Second StageSetpoint are replaced by the programmed VAV Upper CoolingSAT Setpoint and VAV Lower Cooling SAT Setpoint.

When free cooling is not available, the SAT control is per-formed by the following control algorithm: Minimum compres-sor off times (ASCD) of 5 minutes and minimum on times ofone to ten minutes [default is three] are maintained and thecycling rate of the compressors will not exceed maximum 6cycles/hour. The SAT is controlled in a ±5°F band around theactive SAT setpoint. A compressor is allowed to turn on only ifthe current SAT minus the Predicted SAT Drop is more than5°F.

SUPPLY DUCT PRESSURE CONTROL ALGORITHM

The Supply Duct pressure is controlled to a specified setpoint(see paragraph Duct Pressure Setpoint, section Option Oper-ation earlier in this document). An appropriate closed loopcontrol PI algorithm is used to control the supply duct staticpressure by modulating Inlet Guide Vanes, or the supply fanVFD.

MORNING WARM UP / VAV OCCUPIED HEATING CONTROL ALGORITHM

STARTING MORNING WARM UP

Non-networked systems: The MWU (Morning Warm Up)option is enabled by setting the option parameter and estab-lishing a start and end Occupied time period in the control’sOccupied 1 weekly schedule.

MWU (Morning Warm Up) is initiated upon all transitions fromUnoccupied to Occupied mode. The system clock is used toidentify, for the Morning Warm Up, a 1 hour period beforeactual occupancy begins (also see Intelli-Start). If the MWUoption is disabled, the occupancies should be scheduled attheir regular time.

An Occupied Override signal will initiate a warm up of up totwo hours (the setpoint value of the Unoccupied OverrideTime Period). It is important to note that the unit is still operat-ing in an Unoccupied mode for the first hour after the occu-pied Override input is turned on. Reference the Weekly andHoliday Schedule, Tables 44 and 45.

MORNING WARM UP / VAV OCCUPIED HEATING FUNC-TION

Morning Warm Up controls the RAT to a preprogrammedMorning Warm Up RAT Setpoint. An appropriate closed loopcontrol algorithm is used to control heat stages to accomplishthis. The algorithm uses a dead band (i.e. control RATbetween the MWU RAT Setpoint and two degrees below thesetpoint).

FIGURE 30 - SAT CONTROL BAND

Stage Up If SAT is Above Setpoint

By + 5.00F, or More, For 5 Minutes

Active SAT Setpoint

Stage Down If SAT is Above Setpoint

By - 5.00F, or More, For 5 Minutes

- 5.00F

+ 5.00F

Page 86: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

86 Unitary Products Group

Holiday Schedule

• If the Start Time is programmed to zero, the default is all day.

• The Number of Days will be programmed from 0-99.

• The Start Date is programmed by Month-Day-Year.

• When the Start Date is 00-00-0000, that Holiday is ignored.

• When the Time is 00:00, the Time is equal to 12:00 a.m., the beginning of the day.

Full heating (all stages) is ON when RAT drops 2°F below thesetpoint, heating is OFF when RAT is at, or above the set-point. (Note that in this case, the control will use all availableheating stages, regardless of setting of the programmableparameter "Heat Stages"). Before energizing heat for Morn-ing Warm Up the control will start the Fan and operate it for 5minutes. The Economizer will stay closed and the Fan willcontinue to run during the Morning Warm Up. The MorningWarm Up will terminate when the Occupied period begins.

If the RAT setpoint is achieved before the MWU periodexpires, Unoccupied cooling is permitted. If further heating isneeded during the Occupied period, it is controlled by a VAVOccupied Heating algorithm (if enabled and if a Space Sen-sor is used), or by a space thermostat.

The same algorithm is also used for VAV Occupied Heating(see also paragraph "VAV Occupied heating" in "Option Oper-ation" section earlier in this document). In this case, the VAVOccupied Heating control algorithm is activated under thecontrol of the Space Sensor (whenever the zone temperaturesensed by the Space Sensor drops 2°F or more below a pro-grammed "VAV SAT Reset Setpoint"). Once activated, theOccupied Heating control algorithm controls RAT betweenthe MWU RAT Setpoint and two degrees below the setpointand cycles the fan the same way as the MWU algorithm.

The specified Max Morning Warm Up Time is not used to limitthe duration of VAV Occupied Heating. During heating forMorning Warm Up, or for VAV Occupied heating function, theVAV boxes controls will receive an override signal to open theVAV box damper. This is accomplished by wiring the VAVheat relay for the VAV boxes to open, and energizing it fromHeat output of the controller. Note that as the first stage ofheat cycles on / off, the VAV box heat relay will cycle with it.

UNOCCUPIED VAV HEATING / COOLING CONTROL ALGORITHM WITH A SPACE SENSOR

In the unoccupied mode, the Space Sensor will compare thetemperature in a selected VAV zone to the programmedUnoccupied Heating and Cooling setpoints and request heat-ing or cooling using the following control algorithm:

OCCUPIED VAV HEATING / COOLING CONTROL ALGO-RITHM WITH A SPACE SENSOR

In the occupied mode, the control will compare the tempera-ture in a selected VAV zone to the programmed "VAV SATReset Setpoint" and request heating or cooling using the fol-lowing control algorithm: The transition from cooling to occu-pied heating occurs at 2°F below the "VAV SAT ResetSetpoint". There is no "satisfied", or "idle" state of the unitbetween cooling and occupied heating.

The above algorithm only requests occupied cooling andselects a SAT occupied cooling setpoint, or requests occupiedheating at a programmed "Morning Warm Up RAT Setpoint".

Once requested by this Space Sensor algorithm, the coolingis controlled by the SAT control algorithm described in para-graph "SAT Control Algorithm in VAV Cooling" earlier in this

TABLE 44: WEEKLY SCHEDULE

Times Mon Tues Wed Thu Fri Sat Sun

Occupied 1 00:00 00:00 00:00 00:00 00:00 00:00 00:00

Unoccupied 1 00:00 00:00 00:00 00:00 00:00 00:00 00:00

Occupied 2 00:00 00:00 00:00 00:00 00:00 00:00 00:00

Unoccupied 2 00:00 00:00 00:00 00:00 00:00 00:00 00:00

TABLE 45: HOLIDAY SCHEDULE

Holiday Number Start Month Start Dayof Month Start Time Number

of Days

Holiday 1 00 00 00:00 00

Holiday 2 00 00 00:00 00

Holiday 3 00 00 00:00 00

Holiday 4 00 00 00:00 00

Holiday 5 00 00 00:00 00

Holiday 6 00 00 00:00 00

Holiday 7 00 00 00:00 00

Holiday 8 00 00 00:00 00

Holiday 9 00 00 00:00 00

Holiday 10 00 00 00:00 00

Holiday 11 00 00 00:00 00

Holiday 12 00 00 00:00 00

Holiday 13 00 00 00:00 00

Holiday 14 00 00 00:00 00

Holiday 15 00 00 00:00 00

Holiday 16 00 00 00:00 00

Holiday 17 00 00 00:00 00

Holiday 18 00 00 00:00 00

Holiday 19 00 00 00:00 00

Holiday 20 00 00 00:00 00

Page 87: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 87

section [not to be found by that name...]. Once requested bythis Space Sensor algorithm, the occupied heating is con-trolled by the RAT control algorithm described in paragraph"Morning Warm Up / VAV Occupied Heating Control Algo-rithm" earlier in this section.

CONTROLLING EXCESSIVE SAT (SUPPLY AIR TEMPERATURE)

This is required in cooling operation in order to prevent a dan-ger of "slugging" and damage to the DX compressors. Roof-top units do not use accumulators on compressor intake, andliquid refrigerant could enter the intake of a compressor incase of a low heat transfer on the evaporator coil. In heatingoperation, the Excessive SAT control is not used.

SAT CONTROL CONFIGURATION

SAT control for cooling is configurable to enable or disable(on/off). The default setting for cooling is ON. The user is notnormally expected to turn this mode OFF, but the possibility ofturning it OFF is provided mainly for troubleshooting purposes.

SAT CONTROL FOR COOLING

This control has priority over any other zone temperature orSAT control and is used at all times, during CV as well asVAV operation. The Excessive SAT Control state is enteredany time the SAT drops below the trip point of a compressor(as the trip points are programmed in an ascendingsequence, the compressor that trips will always be the high-est- numbered one).

While in this state, the control will continue monitoring theSAT and turning off compressors any time the SAT dropsbelow the respective trip point. There is a 2 minute time delaybetween compressor trips in cases when the SAT dropsbelow trip points of multiple compressors. This assures thatmultiple compressors will not be turned off simultaneously.

ECONOMIZER LOADING OPERATION DURING AN EXCESSIVE SAT FOR COOLING:

CV ECONOMIZER OPERATION

Economizer dampers allow mixing of outdoor and return air.The dampers are coupled and controlled with a single actua-tor such that when the Outdoor Air damper is fully closed, theReturn Air damper is fully open (and vice versa). The positionof the Economizer dampers is controlled based on:

• Energy considerations (“free cooling”)• Ventilation considerations (minimum Outdoor Air damper

position and Demand Ventilation)• Space static pressure considerations (minimum Outdoor

Air damper position).

Economizer dampers are also controlled in certain situationsto perform ”economizer loading” - which minimizes SAT tem-perature swings resulting from turning cooling, or heatingstages on / off. This function is separate from normal econo-mizer operation, and is separately described at the end of thissection.

When is the Economizer operation used?

If the rooftop unit is equipped with an economizer (and thatoption is selected), and free cooling is available (“economizersuitable”), then the Economizer Operation as specified in thissection will be used in the following operation modes:

CV cooling with thermostat, or zone temperature sensor con-trol (note that in the zone sensor mode, the compressor stag-ing algorithm defined in this Economizer section will replacethe zone sensor based control described in Sensor Operationin CV Operation section, earlier in this document).

Minimum Ventilation Position setting

The minimum position setting represents the minimum open-ing of the outdoor air damper (% open). This setting will bemaintained any time the unit is in Occupied mode. The mini-mum position setting will be determined by an “EconomizerMin Position” programmable parameter set by a Palm Pilot.The minimum position setting will be ignored during the Unoc-cupied mode. During the Unoccupied mode, the minimumposition is 0% (the Economizer may not remain closed duringthe Unoccupied mode, in case the temperature control to anunoccupied setpoint can use Outside Air for free cooling).

Minimum Position during Heating and Occupied Mode

During heating while in Occupied mode, the economizer willbe at its programmed minimum position.

Minimum Position during Cooling and Occupied Mode

During cooling while in Occupied Mode, the economizer maybe at its programmed minimum or may be modulatedbetween its minimum position and 100% open position by theeconomizer control.

SAT SETPOINTS USED DURING COOLING WITH ECONOMIZER OPERATION

As long as the Economizer Operation is enabled and “freecooling” is available, the economizer will be controlled (with,or without any compressors running) to maintain the followingSAT setpoints: In CV cooling mode:

• With a call for first stage cooling, a programmed Econo-mizer First Stage Setpoint. This setpoint is programma-ble in the range of 40°F to 65°F, default setting is 55°F.

• With a call for second stage cooling, a programmed Econ-omizer Second Stage Setpoint. This setpoint is program-mable in the range of 40°F to 65°F, default setting is 50°F.

Criteria for Economizer Suitable decision Sensor avail-ability:

There are three different methods of deciding whether theeconomizer is suitable:

• Differential enthalpy (highest preference from energy viewpoint)

• Outside enthalpy (middle preference) and• Outside temperature method (lowest preference)

Page 88: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

88 Unitary Products Group

The choice of a method with highest preference is automatic(“self-configuration”) based on availability of appropriate sen-sors. If a sensor fails/ goes unreliable, a fault is indicated and,again, the next highest preference method will be automati-cally selected (“fault tolerance”).

There are two ON/OFF programmable parameters related tothe choice of an economizer method:

• “OAH Sensor Enable”• “RAH Sensor Enable”

These parameters are set to reflect the installed sensors thatcan be used by the “self-configuration” feature and controlsensor failure alarms.

The OAH sensor, if available, allows use of Outside Enthalpymethod for deciding on free cooling availability.

The RAH sensor, if available in addition to the OAH sensor,allows use of Differential Enthalpy method for deciding onfree cooling availability.

See paragraphs OAH Sensor Enable and RAH SensorEnable in Settable Parameters, Table 52 in this document.

If the selected method is using an enthalpy, the enthalpy iscalculated in the controller from sensed temperature andhumidity of the respective air stream.

Differential Enthalpy Method: is set by parameter and usedonly when sensors for Outdoor Air temperature, Outdoor Airhumidity, Return Air temperature and Return Air humidity areall installed and reliable.

Outside Enthalpy Method: will be configured by setting ONthe parameter for the Outdoor Humidity Sensor [OAH], andwill be the default if the unit defined as Differential Enthalpycannot read the Return Air Humidity sensor.

Outside Temperature Method: will be self-configured andused only when differential enthalpy or outside enthalpymethods are not available, and sensor for Outside Air tem-perature is installed and reliable.

Economizer is suitable when OAT is less than SAT setpoint +10°F. Use a 2°F differential on both sides of this limit. As theSAT setpoint value, use only one of the programmed 1st or2nd stage economizer setpoints (depending on what coolingstage is called), not any “transient” setpoints that may betemporarily used during process of staging. Note that this ruledoes not reflect any consideration of geographical locationand weather conditions, but rather reflects the averageexpected SAT temperature drop obtained from DX coolingstages, i.e. the highest outdoor air temperature that the DXcooling can still reliably reduce to the SAT setpoint

Outside Enthalpy Method: Economizer is suitable when OAEnthalpy is less than Outside Enthalpy number AND OAT isless than SAT setpoint + 10°F: Use a 2°F and 1 BTU/LB dif-ferentials respectively on both sides of these limits. TheEnthalpy number is a programmed parameter (range 22-40BTU/LB, default 30 BTU/LB. The Enthalpy Number can beviewed as the maximum outdoor air enthalpy with which the

outside air can still be considered suitable for DX cooling, or,in comparison to the Differential Enthalpy Method describedbelow, as a “best guess” on actual return air enthalpy (whichin this method is not being sensed). The temperature limitreflects the average expected SAT temperature dropobtained from DX cooling stages.

Differential Enthalpy Method: Economizer is suitable whenOA Enthalpy is less than the RA Enthalpy AND OAT is lessthan SAT setpoint plus 10°F (+/- 2° and 1 BTU/LB): Use a 2°Fand 1 BTU/LB differentials respectively on both sides of theselimits. This is similar to the Outside Enthalpy method, exceptinstead of a programmed Enthalpy Number, an actuallysensed return air enthalpy is used.

SAT Control with Economizer

If the economizer is “suitable” (free cooling is available) andcooling is required (the unit is not in satisfied state), the algo-rithm will be active and modulate economizer position inorder to control SAT to the active SAT setpoint. If the econo-mizer is not suitable, the algorithm is deactivated and theeconomizer is placed at its programmed minimum position.The economizer control algorithm will typically be cycledON/OFF several times an hour (will be activated and deacti-vated) under control of a zone thermostat, or a zone sensor.A zone control algorithm will activate the economizer algo-rithm when cooling is required, and will switch between Econ-omizer 1st and 2nd stage SAT setpoints, and will deactivatethe economizer algorithm when the zone is satisfied.

The PI algorithm is direct acting. This economizer controlalgorithm is always active during economizer operation (aslong as economizer is “suitable”) and will control SAT to anactive (1st or 2nd stage) Economizer setpoint. This meansthat this control loop not only modulates the Outside Airdamper open to add free cooling and decrease mixed airtemperature to maintain SAT at setpoint, but, when DX cool-ing is running, also may modulate the Outside Air damperclosed to increase mixed air temperature (use more returnair) and thus add load on the DX coil to maintain SAT at set-point (“economizer loading”). This represents a trade-offbetween energy and compressor cycling.

Control of compressors with Economizer

Compressors are turned ON / OFF individually, regardless ofgrouping them into “stages”. The stage groups are used onlyfor control of compressors with external signals, such as froma thermostat.

Turning ON of compressor #1:

Never operate compression if the Economizer can maintainthe SAT setpoint with free cooling. If no compressors are on,and the economizer controller is saturated High (i.e. theeconomizer is 100% open and can no longer maintain theSAT setpoint by just free cooling),

• Temporarily override SAT setpoint to increase it by 5°F• When the SAT is within 0.5°F of this temporary setpoint,

turn on compressor #1• Resume SAT control at active setpoint

Page 89: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 89

This is done in order to read and store the SAT temperaturedifferential (drop) due to turning on compressor #1, whileassuring that turning it on will not drop the SAT below com-pressor #1 trip point (where the Excessive SAT control wouldturn it off again). The same staging sequence is used for theremaining compressors (see below). Note that the standard 5minute delay before monitoring SAT after a compressor isturned on, or off, applies here also.

Turning on compressors #2 through #4:

If the economizer controller is saturated High (i.e. the econo-mizer is 100% open while one or more compressors are run-ning and the control can no longer maintain the active SATsetpoint requested by the zone control),

• Temporarily override SAT setpoint to increase it by 5°F• When the SAT is within 0.5°F of this temporary setpoint,

turn on the next compressor• Resume SAT control at active setpoint

NOTE: The pre-staging SAT increase must be done ”proactively”, by a temporary override of the active SATsetpoint, rather than by allowing the SAT to “drift” upby 5°F out of control. The time it would take for theSAT to “drift” up could be fairly long, mostly depen-dent on the outdoor air temperature change and inthe meantime, the zone temperature may go out ofcontrol as the additional needed cooling is not beingdelivered.

NOTE: The standard 5 minute delay before monitoring SATafter a compressor is turned on, or off, and thechecking against a stored, predicted SAT tempera-ture drop, applies here also.

Turning compressors off:

A highest numbered running compressor is turned off whenthe economizer controller is saturated Low.

This method of turning compressor off is considered betterthan using the Excessive SAT Control - turning a compressorOFF only if SAT reaches its specified trip point. If that methodwas used and the Excessive SAT Control was not selected,there would be no means for turning compressors off.

NOTE: The compressors also will be turned off in CV sys-tems with zone thermostat, or zone sensor tempera-ture control, when the zone temperature control issatisfied. For the case of zone sensor, the compres-sor destaging is described in section “CV Opera-tion”, paragraph “Control Algorithm for Cooling withthe Sensor Option, with Economizer”. For the caseof zone thermostat, the compressor destaging isdescribed in section “CV Operation”, paragraph“Thermostat Operation for Cooling with Y1 and Y2inputs”, subparagraph “Economizer Mode”.

Compressor control when exiting Cooling Lockout onOAT:

A situation may arise when in Economizer Mode and one ormore compressors are required in addition to full availablefree cooling in order to maintain the SAT setpoint, but CoolingLockout on OAT prevents the compressors use. This situationmay arise when the SAT setpoint is set very close to, or evenbelow the temperature set for Cooling Lockout on OAT - a rel-atively unusual case. If the OAT then increases above thelockout setting while the call for several compressors exists,the compressors will turn on with a delay between compres-sors.

Economizer Loading Option

This is a programmable option. The user has the ability toturn this function off. It is automatically disabled if the unitdoes not use an economizer. The on/off programming choiceis common to both cooling and heating. The default setting isON. This programmable “Economizer Loading” function isused only outside the normal Economizer operation.

During the Economizer operation, the “Loading” function isalways used and is an integral part of the Economizer controlalgorithm.

Economizer loading option in cooling:

In cooling, this function causes changes in mixed air temper-ature (as modulated by the economizer dampers) in order tochange SAT and keep it at SAT setpoint when only compres-sor #1 is running. This makes a trade-off between energy andcompressor cycling and minimizes cycling of compressor #1.The loading is done by the same type of control algorithm (PI)as used in the normal Economizer operation.

The algorithm will be activated to do this function in followingconditions:

• Economizer is “not suitable” (i.e. we are not in a normal Economizer mode)

• The programmable option “Economizer Loading to Con-trol SAT” is ON

• Only compressor #1 is running

The PI control algorithm in this case has a capability to auto-matically change from direct to reverse acting in response todifference between OAT and RAT. When OAT is less thanRAT, the algorithm is direct acting, for OAT & RAT, the algo-rithm changes to reverse acting. This way, the ”loading” of theDX coil is correctly done with return, or outdoor air, as appro-priate, and there is no need to activate this “loading” functiononly at higher outdoor air temperatures (e.g. OAT > 60°F).

The algorithm controls SAT to its specified setpoint (whenapplicable, e.g. in VAV operation), or, in control modes whereno SAT setpoint is specified (such as in Excessive SAT con-trol state in cooling), to a fixed temperature deadband of 50°Fto 55°F.

Page 90: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

90 Unitary Products Group

NOTE: As opposed to the PI algorithm used in economizercontrol, the PI algorithm used here for economizerloading function does not need to utilize the Highsaturation state for any additional control functions.Therefore no complications arise when switchingbetween direct and reverse acting modes.

Economizer loading option in heating:

In heating, this function uses additional outside air (as modu-lated by the economizer dampers) in order to decrease SATwhen only the first stage of heating is running and keep theSAT below the programmed ”Economizer Loading Setpoint inHeating”. This prevents heating stage from cycling on itsinternal temperature limit safety switch (which is typically setabout 10°F above the Economizer Loading Setpoint). A needfor economizer loading arises in Communicating Zoning Sys-tem applications (“VVT” systems) using supply air bypasswhen heating load in the zones is low and a large amount ofhot supply air is bypassed back into return and mixed air tem-perature is very high. Economizer loading may also beneeded when supply air flow across the heat exchanger islower than expected (e.g. wrong setting of fan speed,plugged air filters). A secondary benefit of economizer load-ing is an improvement in comfort as the supply air tempera-ture is more stable and cycling of the unit is minimized.

The economizer loading option in heating is not implementedin VAV applications as these do not use supply air bypassand (in case of using a zone thermostat) run all heatingstages during heating (economizer loading applies to only the1st heating stage).

The economizer loading minimizes cycling of heating stage#1 and makes a trade-off between energy and the benefitsdescribed above.

The Economizer Loading in heating option requires a SATsensor that can sense SAT in heating mode (a sensor placeddownstream of the heating stages). Such a sensor is pro-vided only as a field-installed accessory, on units equippedwith heating stages. The SAT sensor that is factory-installedcan be used for cooling mode only. If a field-installed sensoris added, it will replace the factory-installed one and will thenbe usable for both heating and cooling modes.

The loading is done by the similar control algorithm as usedin the normal economizer operation. The algorithm is acti-vated to do this function in following conditions:

• Heating mode• The programmable option “Economizer Loading to Con-

trol SAT” is ON• Only heating stage #1 is running

The PI control algorithm in this case has a capability to auto-matically change from direct to reverse acting in response todifference between OAT and RAT. When OAT is less thanRAT the algorithm is direct acting, when OAT is greater thanRAT the algorithm is reverse acting.

This way, the “loading” of the heating stage is correctly donewith return, or outdoor air, as appropriate, and there is noneed to activate this ”loading” function only in some specificrange of outdoor air temperatures (e.g. OAT > programmedfirst heating stage trip point minus 50°F).

NOTE: In this case, the provision for direct vs. reverse act-ing switching is not essential feature of the controlalgorithm and the algorithm could be implementedas direct acting only in order to simplify implementa-tion and save code space. The situation when econ-omizer loading in heating is required while OATgreater than RAT is unlikely and if it should occur,the difference between OAT and RAT is negligible incomparison to the SAT control setpoint. The Econo-mizer Loading function in heating controls SAT to afixed temperature deadband of programmed “Econ-omizer Loading Setpoint in Heating” and 5°F belowthis setpoint (the setpoint is programmable between100°F - 195°F, default is 160°F).

In units that use hydronic heat, the Economizer Loading func-tion may be enabled in order to be used for cooling (the on/offprogramming choice for this function is common to both cool-ing and heating). In this case, it is important to ensure that theprogrammed value of the “Economizer Loading Setpoint inHeating” is set higher than the value of “Hydronic Heat FirstStage Setpoint”. That, in normal conditions, assures that theEconomizer Loading function in heating is effectively disabledand the economizer is closed to its minimum position duringheating.

VAV

When is the Economizer operation used? If the rooftop unit isequipped with an economizer and free cooling is availablethen the Economizer Operation as specified in this section isused in the following operation modes:

VAV cooling (except the programmed Economizer First StageSetpoint and Economizer Second Stage Setpoint arereplaced by the programmed VAV Upper Cooling SAT Set-point and VAV Lower Cooling SAT Setpoint)

DEMAND VENTILATION

Demand Ventilation Operation control mode is self-configur-ing for the use of an Indoor Air Quality (IAQ) sensor - it willautomatically detect that an IAQ sensor is connected and useit any time the IAQ sensor input indicates an IAQ level of 200ppm, or higher.

NOTE: Due to the self-configuration operation, an error dueto IAQ sensor failure can be indicated only in casethe IAQ sensor fails during normal controller opera-tion. If the IAQ sensor fails, or is removed / discon-nected during a power-off condition (e.g. duringservicing of the unit while the control is not pow-ered), the control will, on power up, self configurewithout the IAQ sensor and no error indication isprovided.

Page 91: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 91

When the IAQ sensor is detected as available, the control willuse the Demand Ventilation Setpoint to control the IAQ levelsin the building by modulating the Economizer more open.

The Demand Ventilation will operate in units equipped with anEconomizer (Economizer option is turned ON) any time thecontrol is in Occupied mode. The Demand Ventilation Opera-tion is applicable in heating, or cooling mode, and will modu-late the Economizer damper more open, if necessary, from itsprogrammed minimum position (in heating, or in coolingwhen economizer is not "suitable"), or from its modulatedposition determined as defined in the Economizer Operationsection (in cooling, when economizer is "suitable").

An appropriate control algorithm is used to accomplish thiscontrol. Preferably, this algorithm is a "step-and-wait" type,with the step size calculated as a function of offset betweenthe Demand Ventilation Setpoint and the current IAQ level,and with a fixed "wait", or sampling time. This algorithm isactivated whenever the IAQ level exceeds the setpoint andwill override the economizer position more open, as needed,up to a pre programmed Maximum Economizer Position forDemand Ventilation. The algorithm is deactivated, and theprevious, normal mode of economizer position controlresumed when the IAQ level becomes 50 ppm lower than thesetpoint.

The programmed "Maximum Economizer Position forDemand Ventilation" is used to minimize the possibility thatthe Demand Ventilation may open the Economizer dampertoo much, such that at fairly high OA temperatures, evencombined cooling output of all compressors would not pro-vide sufficient cooling (as a rule of thumb, all compressorscombined achieve approx. 20°F SAT decrease). Similarly, atfairly low OA temperatures, the combined output of all heat-ing stages may not be able to provide sufficient heating. ThisEconomizer max. position limit is simpler to implement than aclosed loop SAT low-limit control that would operate with aprogrammed high-limit for cooling and a programmed lowlimit for heating.

NOTE: An added measure of protection against excessiveSAT during Demand Ventilation Operation is pro-vided by Supply Air Alarm Setpoint for Cooling andSupply Air Alarm Setpoint for Heating, and the con-trol function associated with these setpoints (seethe respective paragraphs in the Option Operationsection earlier in this document).

EXHAUST OPERATION

Building static pressure is controlled through one of threemethods. One method incorporates a fixed speed fan that iscontrolled from the position of the Economizer dampers. Asecond method uses proportional control that modulates theexhaust damper and operates the fan based on the positionof the dampers. A third method uses a variable speed fancontrol that looks at building static pressure. All are depen-dent on the supply fan being ON.

TWO-POSITION CONTROL (NON MODULATING POWER EXHAUST)

This mode is a fixed speed, ON/OFF Power exhaust fan, witha barometric relief damper, controlled from position of theEconomizer damper. The Power Exhaust and the Econo-mizer options must be ON.

This mode is a fixed speed, ON/OFF Power exhaust fan, witha barometric relief damper, controlled from position of theEconomizer damper. The Power Exhaust and the Econo-mizer options must be ON.

The Exhaust Fan (EF) is controlled with a relay output of thecontroller and "slaved" to the Economizer damper positionvalue.

The EF relay is energized whenever the Supply Fan is run-ning and the Economizer (Outdoor Air Damper) is com-manded open more than the programmed EconomizerDamper Position for Exhaust Fan to turn ON.

The EF will be de-energized when supply fan is off or whenthe OAD opening is less than the EF Turn OFF set point or10% open, whichever is greater. Default Setpoint settings forthe EF to turn ON at Economizer 60% open, turn OFF atEconomizer 20% open. The EF has a minimum run time of10 seconds and a minimum off time of 60 seconds.

PROPORTIONAL CONTROL (FAN WITH MODULATING EXHAUST AIR DAMPER (EAD) CONTROLLED FROM BUILDING STATIC PRESSURE)

In this mode the Power Exhaust, Modulating Exhaust, Econo-mizer and Building Pressure Sensor Enable options must beON and the Supply Fan must be running. The EAD actuatoris modulated to maintain building static pressure to a pro-grammed Building Pressure Setpoint. An appropriate closedloop control algorithm is used to accomplish this control.

The control will modulate from full closed to full open over a2-minute period. The proportional band is from 0.015 in w.g.(3.7 Pa) below the Building Pressure Setpoint to 0.015-in.w.g. (3.7 Pa) above the set point.

The control algorithm is disabled and exhaust air dampercommanded closed whenever the supply fan is off. Buildingpressure is sensed with a -0.250 to +0.250 in. w.g. (-31 to +31 Pa) 0 - 5V output pressure differential transducer. Thetransducer senses the building pressure as referenced to anappropriate reference point outside the building. Transduceroutput signal is filtered (e.g. time averaged over 15 secondperiod) to compensate for wind gusts.

The Exhaust Fan (EF) is controlled with a relay output of thecontroller and "slaved" to the Exhaust Air Damper position.The EF relay is energized whenever the Supply fan is runningand the EAD is open more than the programmed ExhaustDamper Position for Exhaust Fan to turn ON. The EF relay is

Page 92: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

92 Unitary Products Group

de-energized when Supply fan is off or when the EAD open-ing is less than the programmed Exhaust Damper Position forExhaust Fan to turn OFF, or 10% open, whichever is greater.The minimum run time is 10 seconds and minimum off time is60 seconds. (Non-adjustable). Default Setpoint settings arefor the EF to turn ON at Exhaust Air Damper 80% open andturn OFF at Exhaust Air Damper 20% open. The BuildingPressure Setpoint default is 0.100" w.g.

PROPORTIONAL CONTROL WITH VFD FAN

This is similar to the proportional EAD option, except that thedamper signal is used to control motor speed using a variablefrequency drive.

TWO-POSITION CONTROL (POWER EXHAUST WITH BAROMETRIC RELIEF, CONTROLLED FROM BUILDING STATIC PRESSURE)

In this mode the Power Exhaust, Economizer and BuildingPressure Sensor Enable options must be ON. The ExhaustFan (EF) is controlled with a relay output of the controller. TheEF relay is energized whenever Supply fan is running andbuilding static pressure is above a programmed Building Pres-sure Setpoint + 0.015 “ w.g. (3.7 Pa). The EF relay is de-ener-gized when supply fan is off, or when building static pressure isless than a programmed Building Pressure Setpoint - 0.015”w.g. (3.7 Pa). The minimum run time is 10 seconds and mini-mum off time 60 seconds (Non-adjustable). With this type ofcontrol, the Power Exhaust fan cycle, as its operation directlyinfluences the building static pressure that controls it. Thecycling rate is limited by these minimum ON and OFF time set-tings. The Building Pressure Setpoint default is 0.100" w.g.

ERV

During operation, the ERV [Energy Recovery Ventilation]exhausts return air from the building, but it is not a 'powerexhaust'; the system is NOT controlled by building pressure.If building pressure control is required, it must be done byother means - standalone power exhaust, or power exhaustin another unit serving the same space.

The ERV forces high volume fresh air exchange, but capturesthe heat energy of the outgoing air and transfers it to theincoming stream. ERV blower operation is NOT modulated toa pressure setting; there is no building pressure transducer inthe system. The unit's supply fan pulls air through the inletside of the ERV wheel.

Ducting and demand will vary from one installation to another.Adjusting the unit to achieve fresh air requirements and'exhaust-neutral' air flow must be done by the installer, usingthe manual dampers in the unit.

If the unit is variable air volume, the ERV exhaust motors willbe controlled by a variable frequency drive in the Millennium,using the same signal voltage that modulates supply air,either by inlet guide vane or variable frequency drive. This isdone to keep supply and exhaust air flow in balance.

The exhaust blowers in the ERV use the power and controlhardware that otherwise would run the power exhaust. TheEXH output from the Simplicity runs the ERV motors; if theunit is VAV, the EXD+/- terminals provide the ERV variablefrequency drive speed signal.

Where a unit has both ERV and an economizer, the ERV willstop wheel rotation when the economizer dampers open farenough to trigger the user-settable switch in the damper actu-ator. If free cooling is available, the heat exchange wheeldoes not need to rotate; the wheel will cycle on schedule tokeep the air passages blown clean.

Also refer to the ERV Installation Instructions packaged withthe ERV.

SCHEDULING OPERATION

The Millennium Simplicity refers to its clock and internal cal-endar.

COMPRESSOR STATUS MONITORING

Compressor status is monitored using three separate 24 VACcircuits.

Monitoring: low pressure, high pressure, and compressormodules.

The corresponding compressor status is monitored. If any ofthe three safeties is in error, the trip is noted in the alarm his-tory and the next available compressor will be used ifneeded.

The Low Refrigerant Pressure Switch is Normally Open,pressure closed. When the compressor is off and refrigerantpressure equalized, the switch under normal conditions isexpected to be closed. However, in cold ambient operation, itmay stay open and close only after the compressor starts up.

If an error is detected for a compressor, that compressor’soutput is turned off (note that the controller executes theapplication code once every 32ms, with a 30 second startupdelay and 5 second minimum error time on low pressure. Thecontrol then declares a "Compressor Locked Out on [ ] Trip"alarm. The alarm is written to the Error History Buffer.

NOTE: The compressor lockout works as an override of theoutput of the staging algorithm for cooling control.For example, the cooling control may ask for com-pressor #2 that is locked out, and as this requestdoes not generate additional cooling, will ask for thenext compressor, #3, to satisfy the cooling demand.If, after 10 minutes, the requested compressor #2does start up, the cooling output now may beexceeding demand, and the control will turn offcompressor #3, etc.

Page 93: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 93

TABLE 46: ALARM DEFAULT CODES

Code Cause

1 Compressor number one locked out on High Pressure Control

2 Compressor number two locked out on High Pressure Control

3 Compressor number three locked out on High Pressure Control

4 Compressor number four locked out on High Pressure Control

5 Compressor number one locked out on Low Pressure Control

6 Compressor number two locked out on Low Pressure Control

7 Compressor number three locked out on Low Pressure Control

8 Compressor number four locked out on Low Pressure Control

9 Compressor number one locked out on excessive motor trips

10 Compressor number two locked out on excessive motor trips

11 Compressor number three locked out on excessive motor trips

12 Compressor number four locked out on excessive motor trips

13 First stage heating is locked out due to excessive Limit Switch Trips

14 Second stage heating is locked out due to excessive Limit Switch Trips

15 Third stage heating is locked out due to excessive Limit Switch Trips

16First stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the control is not calling for this stage of heating

17Second stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the control is not calling for this stage of heating

18Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the control is not calling for this stage of heating

19 Space Temperature Sensor has failed open or shorted

20 Supply Air Temperature Sensor has failed open or shorted

21 Return Air Temperature Sensor has failed open or shorted

22 Outside Air Temperature Sensor has failed open or shorted

23 Dirty Filter Switch has tripped

24 Unit has locked out on the APS. Air Pressure Switch.

25 The APS is stuck closed.

26 A microelectronics failure has occurred and the control is operating on defaults

27 A microelectronics failure has occurred and the control is down due to a fatal fault.

28 The control is locked out due to Fan Overload Trips

29 Outside Humidity Sensor is out of Range

Page 94: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

94 Unitary Products Group

30 Return Air Humidity Sensor is out of Range

31 IAQ Sensor is out of Range

32 Real Time Clock cannot be read and has a hardware failure

33 Space Temperature Offset is greater than 20K Ohms

34 CV/VAV input is out of range and the unit is locked out

35 Unit is locked out due to low voltage on the 24 VAC supply

36 Smoke Purge

37 Duct Static has Exceeded Limit

38 Supply Air Temperature Cooling

39 Supply Air Temperature Heating

40 Economizer Minimum Position

41 Space Temperature

TABLE 46: ALARM DEFAULT CODES (Continued)

Code Cause

Page 95: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 95

TROUBLESHOOTING A MILLENNIUM SIM-PLICITY CONTROL

STATUS LED CHART

The Status LED mounted on the controller PC board will flashspecified flash patterns to indicate rooftop unit status. SeeTable 47.

Flash Times:

• Off: The power is Off, or the control has failed• On 250ms Off 250ms: The Control is operating but an

Alarm is active.• (The Number of the Alarm will be displayed on the char-

acter display.)• On one second, Off one second: This will be the "Heat

Beat"; The Control is operating normally with no Alarms.• On Steady: The Control has Failed• Two flashes On, then two seconds Off: The Control is

waiting for an ASCD Timer to finish.

FAILURE MODES AND DEFAULT OPERATION

ERROR HISTORIES

Error data storage: The control will store the latest five errorsin a FIFO manner in EEPROM, for later display. It will storestatus information ("active" vs. "inactive") for all error types toprovide for situations when an error snapshot is triggered bymultiple errors occurring at the same time. As the control col-lects errors, it will overwrite the oldest error after the historybuffer becomes full.

Errors that are entered into the error history buffer:

• Compressor locked out on safety chain trip• Supply fan failure• Heating SAT failure• Cooling SAT failure• SAT,RAT,OAT,IAQ, ST, or RH failure• Duct static or Bldg. Pressure sensor failure• Dirty Filter alarm• High duct static alarm• Hot Water Coil Freeze alarm• External alarm input• Bad Air Proving Switch

SENSOR FAILURES AND DEFAULT OPERATION

A failure of SAT RAT, OAT, IAQ, Space Temperature, or anoutside or return air Relative Humidity sensor will generate acommon error. A failure of the Duct Static or Building Pres-sure sensor will generate another common error. The errorswill be indicated by a Status LED (see Status LED Chart ear-lier in this chapter). The errors will be written to the Error His-tory Buffer. In networked application, the error flag will bereadable by the network. The error indication of a sensor fail-ure will continue until the problem is corrected and will auto-matically terminate when the sensor is again detected asreliable. If the unit is shut down as a result of a sensor failure,the alarm must be reset (after the sensor problem has beencorrected) by resetting the controller (power cycle, or resetcommand issued by the Palm Pilot Configuration Tool).

SAT SENSOR

CV operation: If the SAT sensor fails, the Economizer,excessive SAT control and predicted SAT drop checking willbe disabled. The Control will then continue a "limp along"operation under zone thermostat, or zone sensor control. ForVAV operation the unit will be shut down.

RAT SENSOR

If the RAT sensor fails, Morning Warm Up mode and VAVOccupied Heating are disabled. For Economizer Loadingfunction, the control will default to estimated RAT of 75°F (forthis function only).

OAT SENSOR

Units without Economizer: If there is no Economizer, thecontrol will lockout Cooling on an OAT sensor failure. This isbecause the controller can not determine when cooling needsto be locked out at low OAT to prevent damage to compres-sors. Heating operation will continue normally.

Units with Economizer: All Economizer Operation will bedisabled. This is because OAT sensor is the most essentialsensor in determining availability of free cooling. Even if theunit is equipped with Outside RH sensor and controller couldcalculate Outdoor Enthalpy, the OAT sensor is still essentialin that calculation. The Economizer will only modulate to theMinimum Position when the Fan is operating and the controlis Occupied.

OUTSIDE AIR RELATIVE HUMIDITY SENSOR

If the OAH sensor fails, the control will only use the OAT sen-sor to decide if Free Cooling is available. The control will self-configure to Outside Temperature Method (see also Econo-mizer Operation section earlier in this document).

RETURN AIR RELATIVE HUMIDITY SENSOR

The control will self-configure to Outside Enthalpy Operation.

TABLE 47: STATUS LED CHARTFlash Codes Decription

On Steady Control Failure

1 Flash (Not Applicable)

2 Flashes Control waiting ASCD

OFF No Power or Control Failure

Page 96: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

96 Unitary Products Group

SPACE TEMPERATURE SENSOR

CV operation with a zone sensor: When this sensor failsthe control will see if it has a RAT sensor. If it has a RAT sen-sor, the control will use it as a backup and continue tempera-ture control to the active space temperature setpoint. If thereis no RAT Sensor, the control will shut down all outputs. If thedetected sensor failure is a short circuit, the error can bedeclared only if the short persists for several minutes, in orderto distinguish a sensor failure from a short caused by some-body pushing on Unoccupied Override button.

VAV operation: If the space temperature sensor fails, thecontrol will continue normal function, only SAT reset fromspace temperature will be disabled.

BUILDING PRESSURE SENSOR

If this sensor fails, the Power Exhaust control will default tooperate as a two position Power Exhaust. The PowerExhaust Fan will be controlled as a fixed speed, ON/OFFPower exhaust fan, controlled from position of the Econo-mizer damper. If the unit is equipped with a ModulatingExhaust Air Damper, this damper will be closed.

DUCT STATIC PRESSURE SENSOR

If this sensor fails, all outputs are turned off and the unit isshut down.

IAQ SENSOR

If the IAQ sensor fails, Demand Ventilation mode is de-acti-vated.

SYSTEM ERRORS

HEATING SAT FAILURE

In Heating mode and all stages of heating energized, the SATmust drive above the Supply Air Alarm Setpoint for Heatingwithin ten minutes or this SAT failure error will be activated.The error will be written to the Error History Buffer. In net-worked application, the error flag will be readable by the net-work.

COOLING SAT FAILURE

In Cooling mode and all stages of compression are ener-gized, the SAT must drive below the Supply Air Alarm Set-point for Cooling within ten minutes or this SAT failure errorwill be activated. The error will be written to the Error HistoryBuffer.. In networked application, the error flag will be read-able by the network.

SUPPLY FAN FAILURE

The conditions under which this failure is declared, and thefollow-up actions of the control when this error occurs aredescribed in a paragraph on Air Proving Switch Operationearlier in this document. The error will be written to the Error

History Buffer. In networked application, the error flag will bereadable by the network.

COMPRESSOR SAFETY CHAIN TRIP

The conditions under which this failure is declared, and thefollow-up actions of the control when this error occurs aredescribed in a paragraph on Compressor Status Monitoringearlier in this document. The error will be written to the ErrorHistory Buffer. In networked application, the error flag will bereadable by the network.

DIRTY FILTER ALARM

The conditions under which this failure is declared, and thefollow-up actions of the control when this error occurs aredescribed in a paragraph on Dirty Filter Switch (DFS) optionearlier in this document. The error will be written to the ErrorHistory Buffer. In networked application, the error flag will bereadable by the network.

HIGH DUCT STATIC ALARM

The conditions under which this failure is declared, and thefollow-up actions of the control when this error occurs aredescribed in a paragraph on Duct Static High Limit Setpointoption earlier in this document. The error will be written to theError History Buffer. In networked application, the error flagwill be readable by the network.

HOT WATER COIL FREEZE ALARM

The conditions under which this failure is declared, and thefollow-up actions of the control when this error occurs aredescribed in a paragraph on FSI (Hot Water Freeze Protec-tion) option earlier in this document. The error will be writtento the Error History Buffer. In networked application, the errorflag will be readable by the network.

THE MILLENNIUM SIMPLICITY CONTROL

INTRODUCTION AND OVERVIEW

Welcome to the new Millennium Simplicity control, a digitalcontrol system designed specifically for the Millennium 25 to40 Ton single package rooftop unit. The Simplicity is composedof 72 monitored and controlled input and output points. Thecontrol logic of the Simplicity extends on the rules built in to theSynthesys control, and provides character displays in additionto LED flashes to display information to the technician.

The Simplicity digital control performs all of the control andmonitoring functions that were originally done by separatediscrete relays, controls, and interlocking hardware. Thisreduces manufacturing, service, and maintenance costs. TheSimplicity digital controller includes sophisticated control ofthe individual components of the HVAC cooling/heating unit,and has built-in rules that protect those components and opti-mize the control to its environment. The cooling and heating

Page 97: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 97

modes are protected against frequent cycling, slugging, mul-tiple restarts, etc.

One result is that the system may not immediately respondas you expect. For example, internal digital timers may delaythe start of a compressor even though the thermostat calls forcooling. The control may be in the middle of a timingsequence; without the observer knowing what has alreadyhappened and the status of current inputs, the system maytake action not expected by the tech.

In the Simplicity control, there are:• a list of user-selected option settings and setpoints

recorded within the control;

• inputs monitored by the Simplicity;

• specific fixed rules and timings built in to the control

• outputs to compressors, heat, economizers, and other options.

The Simplicity has a real-time clock function, with minimum often hours ‘Time-of-day retention’ with unit power off.

The Millennium Simplicity control is resistor-configured forConstant Volume (CV) units or Variable Air Volume (VAV)units. The option settings for a specific option configurationwill be made as part of unit test at the factory; however, ifthere is doubt about how a unit is responding in the field,check the option setting for the unexplained action.

If connected to a network, the control requests an address bya press of the Address/Down button.

DIAGNOSTICS VIA LED

There is an LED on the board that shows the status of thecontrol and alarms (see Status LED Table). There are twocharacter displays, one 2-digit and one 4-digit, to indicatedetails of run conditions and alarms (see Alarms Table in theTrouble Shooting section of this manual).

When the Alarm / Change Data button (See Figure 2 Simplic-ity Controller Push Buttons) is pushed and released one timewithin five seconds, it will re-enunciate the last five alarms onthe Display.

When this button is pushed and released two times within fiveseconds, it will clear all stored alarms.

The error details for most conditions are stored in summary inthe Simplicity Control and can be accessed by the digital dis-play, personal computer interface, or Palm Pilot (Some inter-faces still in development).

Diagnosing requires patience because of internal timings.Normal observable conditions are the same - contactor 1Mpulled in, compressor 1 running - but the control does notidentify what it has just done or is about to do. The Simplicitycontrol will take action according to its internal rules eventhough action requests come from smart thermostats. A callfor cooling, for example, will be compared with supply airtemperature before energizing a cooling stage.

ERROR HISTORY

The Simplicity control stores up to 5 of the most recentalarms in a First In, First Out (FIFO) manner. As the controlcollects alarms, it will overwrite the oldest alarm after the his-tory buffer becomes full.

Some system errors will initiate a controlling response as wellas being stored in the error memory buffer. See the “Trouble-shooting” chapter in this manual for a detailed description ofhow controller errors are handled.

Data items stored for maintenance / run history, in addition toAlarms:

• Accumulated run times for each compressor and heat stage

FIGURE 31 -SIMPLICITY CONTROLLER

FIGURE 32 -SIMPLICITY CONTROLS PUSH BUTTONS

Program

Alarms / Change Data Address / Down

Test / Reset / Up

Page 98: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

98 Unitary Products Group

• Unit model number• Unit serial number• Unit Name

DIGITAL LINGO

This training manual is intended to help you with the commis-sioning process by illustrating the use of tools like the con-trol’s digital input and software engineered specifically forstarting up and servicing a Millennium rooftop unit.

You should become familiar with some common terminologyand lingo used in the digital controls industry. [If you are famil-iar with the Synthesys controller, the logic of the Simplicity willbe familiar territory.]

If this is your first exposure to the world of digital controls youmay experience a lot of new terms, acronyms and technicallingo commonly used in the controls industry. For example,the Simplicity input and output hardware points are describedas analog, relating to a continuous scale of value readingssuch as a temperature sensor ranging from -400F to 1600Frange, or binary, meaning 2-states, either on or off, open orclosed, true or false, one or zero. The term “digital” alsomeans two states and its use is often interchanged with“binary”. These points may be either factory- or field-set.

THE PI ALGORITHM

Another common “digital controls” term is the PI algorithm orProportional-Integral control loop. The PI algorithm is a con-tinuously updated math calculation that the controller uses tomodulate an analog output point. For example, a variablespeed drive uses a PI loop to maintain a desired setpoint (inthis case, a duct static pressure value). The algorithm takesinto account several parameters to calculate the output. ThePI loop needs parameters such as the proportional operatingbandwidth, integral time constant, deadband, desired set-point value, sensed input value(s), start up ramp time, initialstart value, maximum output control value, a status point toinitiate the control action (i.e. a fan ON status), Direct orReverse Controlling Action, and several other parameters tocalculate a simple 0 to 100% analog output control. The PIalgorithm is also called a PI loop because it “loops” the outputback to the input (feedback) and determines a new outputvalue based on the “error” or difference between the setpointvalue and the sensed input value, and how that differencerelates proportionally to the 0 to 100% output value. Time isthe ”integral” constant that is factored in to increase ordecrease the controlling output action depending on how longthe sensed value remains away from its desired setpoint.

Fortunately, you do not have to determine all of these param-eters since they are pre-programmed at the factory. You needonly to set a desired setpoint and ensure that the inputs andoutputs are properly wired and working. This is referred to ascommissioning a system.

ANALOG TO DIGITAL CONVERTER

Computers can only understand a simple binary language.Remember, “binary” means two states - ON or OFF. Analog(continuous) values of voltages, currents, and resistances aresupplied by sensors and transducers to the control. Thesevalues must be converted in to a binary code so that the com-puter can understand them. This conversion process is per-formed through a combination of hardware and software. Forexample, the 0-5VDC analog value from a static pressuretransducer is divided into thousands of steps with a binarycoded number, often called “counts”, assigned to each step.

SOFTWARE TERMINOLOGY

A digital controller handles its control functions through soft-ware programming rather than with interlocking hardware andwiring. The software then becomes key to how controlledfunctions are handled. Software is a set of statements(referred to as the “program”) that define the function of thecontroller’s internal microprocessor computer.

Software procedurally tells the computer the sequence andorder of tasks that need to be performed using a languagethat the computer can understand.

Software is stored in a computer’s memory. There are severaltypes of memory in a computer. Each type has a specificfunction to perform.

EPROM - This is “nonvolatile” memory, meaning it will not beerased on a power loss. This memory is usually programmedprior to assembly of the controller. Since this memory is notchanged during normal operation of the Simplicity control,only basic operation instructions are stored in this type ofmemory.

FIGURE 33 -ANALOG TO DIGITAL CONVERTER

BINARY NUMBER EQUIVALENT

0 1 2 3 4 5 6 7------------- n

Page 99: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 99

EEPROM (Double “E” Prom) - Is also non-volatile, but thistype of memory requires a special process to be written to.This memory can be written to and changed by the micropro-cessor. This is the type of memory that the control program isstored in the Simplicity control.

ROM - Read Only Memory is non-volatile but can not be writ-ten to. This memory is programmed only once before the con-troller is assembled. ROM contains instructions specifically forthe internal microprocessor computer in the controller.

FIRMWARE - “Firmware” is software, program instructions orapplications, but stored in EPROM or ROM memory.

RAM - Random Access Memory is a volatile memory. It will beerased when a power fail occurs. This memory is used as akind of “scratch pad” for the controller. Temporary instructionsand information such as an output controlling action like drivingthe economizer dampers open is stored here. When a powerloss occurs or if the controller is sent a manual reset using acontrol push button, this memory is cleared and initialized.

Other filtered inputs include temperature and humidity sen-sors. You should be aware of this filtering effect because itwill appear the controller is not acting as fast as you maythink it should. In reality, it is acting and controlling on thesetime-averaged and weighted values.

FAULT TOLERANCE - Fault Tolerance of the Simplicity con-trol involves two issues: Hardware fault tolerance deals spe-cifically with the electrical characteristics of the controller -how much over voltage or power surge the controller canwithstand before damage occurs, and whether internal com-parisons are verifying that the control is calculating and com-municating properly. Software fault tolerance in thistechnology consists of comparing results to previous valuesand to reasonable values.

COMMUNICATIONS BUS

Networked communications may also be new to you. Itrelates to connecting several Millennium rooftop units to anetwork that can be monitored and controlled remotely fromnetwork computer workstations. You will find this typically onlarge installations where central control, monitoring, andenergy management issues become a critical factor in oper-ating a large complex such as a manufacturing facility.

The Simplicity Control has the ability to be networked into alarger system using the MODBUS communication protocol. Acommunication protocol is simply a set of rules that deter-mine how two systems communicate with each other oversome medium such as a pair of wires, phone line, radiowaves, etc. The transmission medium may also be called agateway, pathway, or bus. An “open” protocol such as MOD-BUS is a publicly published set of rules that any equipmentmanufacturer can use to network into another manufacturersequipment.

OPTIONAL ModLINC TRANSLATOR

Overview

The ModLINC translator operates as a Modbus® Client pro-viding an interface between a BACnet® control system anddevices that communicate using the Modbus® RTU protocol.The ModLINC is preconfigured to provide an interface toYORK UPG products equipped with an Intelli-Comfort or Sim-plicity-Elite controller and allows monitoring and control by anISN ConneXsys or third-party BACnet® Building AutomationSystem (BAS).

The ModLINC communicates using the Modbus® RTU proto-col on one port and BACnet® MS/TP, which is the protocolused by ISN ConneXsys devices, on the other port. By pro-viding different communication protocols on the two ports,data can be retrieved from and provided to two different sys-tems.

The ModLINC mounts inside the control panel of the UPGunit and utilizes 24 VAC power from the unit's control trans-former. One port is connected to the UPG controller. Theother port must be connected to the ISN ConneXsys/BAC-net® network.

The ModLINC translator is preconfigured to obtain opera-tional data points from the controller and expose them on anISN ConneXsys/BACnet® network. The data can be trans-ferred to any network device, including an ISN ConneXsysOWS.

"The ModLINC device is primary a control offered and config-ured by York's ESG (Engineering Systems Group). Thedevice is designed to tie into and function with the ISN Con-neXsys system. The device can be used with other BACnet®MS/TP systems, but a qualified controls contractor must beinvolved. UPG cannot support the ModLINC device beyondits hardware functionality and cannot guarantee functionalitywith the ISN or other third party BAS device."

Please refer to the ModLINC Installation/Application manualPart Number 126367-UIM-A-0305.

COMPONENT DESCRIPTION

This section describes the main components of MillenniumSimplicity control. These components consist primarily ofcontrollers, hardware to handle signal input and control out-put and the Tstat interface terminals.

THE SIMPLICITY CONTROLLER

Simplicity is a proprietary, microprocessor-based controller foruse in HVAC applications. The controller provides monitoringand control for either VAV or CAV for a total of 22 outputs.

Page 100: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

100 Unitary Products Group

WIRING AND TERMINATION, COMMUNICATIONS

Most connections to the Simplicity Control are by wiring har-nesses. There are also screw terminal connections for ther-mostat inputs and for communications via an RS-485 port.

COMMUNICATION ADDRESS:

The communication address button (lower right of the dis-play) is used to identify a Millennium rooftop unit to a network,and “capture” the next available network address for that unit.Millenniums can be networked together for centralized moni-toring and control. Much like we need a unique street addressin our homes so we can receive our postal mail or emergencyservices, these units also need a unique address so the cen-tral Facilities Management System (FMS) can “talk” to eachunit individually. The Simplicity board has the model andserial number of the specific unit and has a memory space fora customer name to be applied. So the entire identification fora specific unit available to the network could be, for example,Y2AC04M3KDGABA, NCNM123456, SOUTH OFFICE.

The one-time commands to Override ASCD timers and/or tostart Run Test can be issued by the Test/Reset/Up pushbut-ton. When this button is pushed and released within five sec-onds, the control will zero all ASCD’s for one cycle.

ACRONYMS

A number of acronyms are used throughout this training man-ual. These are specific to the Simplicity control. They are alsoused in the Technical Guide and Installation and Operationmanuals. Acronyms are used to refer to input and outputhardware points and software parameters such as timingdelays and setpoints.

The acronyms used throughout this training manual are listedin the Acronym Table 48. They are described in much moredetail below.

INPUTS

There are two types of hardwired input points on the Simplic-ity control: Analog and Binary. These may be sensors, feed-back, or adjustable setpoints. Typical analog inputs [AI]

TABLE 48: ACRONYMSINPUTS DESCRIPTION

APS Air Proving SwitchIAQ Air Quality (CO2 Sensor)

BAS Economizer Passes BAS economizer command through to Economizer output

BPS Building Pressure SensorC1O-C4O Compressor Status

DF Dirty Filter StatusDPS Duct Pressure SensorFSI Hot Water Coil Freeze InputG Thermostat input for Fan

GV1-3 Monitors gas valve actuation call

HPS1-4 High pressure switch monitored forcompressor discharge

LPS1-4 Low pressure switch monitored for compres-sor suction

Lim 1-3 Over-temperature limit switch from heat stages

OAT Outside Air TemperatureOCC Building Occupied StatusPurge Building Purge input

RAT Return Air TemperatureSAT Supply Air TemperatureSD System Shutdown Connector

OAH Outside Air EnthalpyRAH Return Air EnthalpySSA Setpoint AdjustST Space Temperature

W1, 2, 3 Heating Stages from TstatY1,2 3, 4 Cooling Stages from Tstat

PUSHBUTTONS DESCRIPTIONTest/Reset / 'Up 'Test / control reset / Data value incrementAddress / 'Down 'Change data / Data value decrement

Alarms / Advance data Show alarms / go to next data pointProgram Go to program mode

Real Time Clock Incorporated on the boardOUTPUTS DESCRIPTION

Status LED Flash to indicate alarm, otherwise'heartbeat'

Digital displays One 2-character and one 4-characterC1-C4 Cooling Outputs 1 through 4CF1, 2 Cond Fan Bank 1, 2ECO Economizer damper outputEXH Exhaust Fan relay output

EXD Exhaust Air Damper / Exhaust VFD Signal Output

Fan Supply Fan relay output [contactor orpermission relay]

H1, 2, 3 Heating Stages 1, 2, and 3 outputHGR Hot gas reheat [future]HWV Hot Water Valve output VFD Supply Fan IGV or VFD Signal Output

X Alarm signalMiscellaneous Description

AI Analog InputAO Analog OutputBI Binary Input same asBO Binary OutputCAV Constant Air VolumeVAV Variable Air VolumeVFD Variable Frequency DriveIGV Inlet Guide VaneIAQ Indoor Air QualityPI Proportional-Integral Control

ASCD Anti Short Cycle Timer (Compressor)

TABLE 48: ACRONYMS (Continued)

Page 101: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 101

include Space Temperature (ST), Supply and Return Air Tem-peratures (SAT, RAT), and Building Pressure Sensor (BPS).The binary inputs (BI) on the Millennium Simplicity use a drycontact input to determine the status of a monitored point.Typical BI points are Fan Status (APS), Filter Status (DFS),and Compressor Status (HPS1-4, LPS1-4, C1O-4O).

ANALOG INPUTS (AI):

Analog inputs require parameters that define the input’s char-acteristics. Attributes of an AI include the linear range, alarmlimits, alarm differential, change of state (COS) enable, andfilter weight. The input values may be overridden by a exter-nal system command or by using the input buttons on theSimplicity board. This is useful to override current conditionsto test certain control functions or modes.

BAS - Economizer override; if this option is enabled, anexternal BAS system will control the economizer 2-10 VDCsignal through this pair of terminals.

ST - Space Temperature sensor is a field installed sensor(PN: 025-38928-000 - w/ Override Button). The sequence ofcontrol for space temperature is different depending onwhether the system is a VAV or CAV. See chapter onSequence of Operation for a detailed description of the STcontrol modes.

SSA - Space Temperature Adjust is field installed. It is a slideadjustment located on a space sensor (PN: 025-38927-000)with a slide bar potentiometer. It is used to offset the spacetemperature setpoint. This slide-bar is a 10K ohm potentiom-eter. The programmable range for the Setpoint adjust is +/-5°F. For example, if the Space Temperature setpoint is set to74°F, the SSA is programmed to +/- 3°F and the SSA isadjusted fully to the + position, the new controlling space set-point will be 78°F.

OAT - The outside air temperature sensor (PN: 031-01916-000A) is a factory-installed 10 K NTC sensor. Its linear rang-ing is from -50°F to 250°F.

OAH - Outside Air Humidity (PN: 031-09127-000-A) is a fac-tory-installed sensor manufactured by MAMAO. The OAHsensor, installed only with enthalpy economizer, provides a 0-10 VDC signal to the controller over a range of 0 to 100% rel-ative humidity. This input is used for the economizer calcula-tion to determine whether free cooling is available and toswitch between minimum outside air and using outside air asthe first stage of cooling.

SAT - Supply Air Temperature sensor (PN: 031-01915-000A)is a factory-installed -50°F to 250°F, 10 K NTC sensor.

RAT - Return Air Temperature sensor (PN: 031-01917-000A)is a factory-installed -50°F to 250°F, 10 K NTC sensor.

RAH - Return Air Humidity (PN: 031-09127-000-A) is a fac-tory-installed sensor manufactured by MAMAO, installed only

with dual enthalpy economizer. The control will calculate thereturn air enthalpy using the relative humidity and return tem-perature inputs.

LOW VOLTAGE DETECTION - This input monitors the 24VAC for low voltage conditions. The input has two thresholds,one at 16 VAC and one at 19.2 VAC. If the control needs toturn on a contactor, it will look to see if the voltage isabove19.2 VAC before it will turn it on. If the voltage is notabove 19.2 VAC, it will hold off the contactor and flash theappropriate flash code. This flash code is not an alarm. If thecontrol already has contactors pulled in, it will monitor thevoltage and drop the contactors and shut down if the voltagedrops below 16 VAC and flash the appropriate flash code.

REMOTE - the control will use 0-10 VDC from third-partyBAS to control SAT setpoints. Thermostat inputs override if inconflict with Remote Control voltage input.

SPC TEMP - offset value from the space sensor offset poten-tiometer.

CV/VAV - resistive value across terminals, to determinewhich supply fan rules the control will follow.

Demand Ventilation / IAQ - Indoor Air Quality. The IAQexpects a 0-10 VDC signal to the control from a field suppliedand installed Carbon Dioxide (CO2) sensor. Indoor air qualityis monitored for adequate ventilation. In Demand VentilationMode, as the CO2 levels in the building rise above the pro-grammed setpoint, more fresh air must be brought in. Theeconomizer is therefore adjusted to a more open position asnecessary. The linear ranging for IAQ sensor input is from 0to 10,000 ppm. The Demand Ventilation setpoint is adjustablefrom 0 to 2000 ppm and is set at the factory at 1000 ppm.

DPS - Duct Pressure Sensor is monitored by a factory-installed 0-5 VDC transducer (PN: 031-01209-000A). Thehigh-pressure port sensing tube is installed in the field. Thesense tube should be located approximately two thirds of theway down the duct plenum. To prevent an unstable signaldue to air turbulence, there should be no obstructions, turnsor VAV terminal boxes up or down-stream of the sense tubelocation for at least 6 to 10 times the diameter of the duct.The sensor is located in the control box just below the Millen-nium Simplicity control.

BPS - The Building Pressure Sensor (PN: 031-01262-000A)is a factory-installed Johnson Controls DPT-2640-522 trans-ducer that provides a 0 to 5 VDC signal to the controller overa range from -0.25”WC to +0.25”WC. The transducer islocated in the control box just below the Millennium Simplicitycontrol. The sense tubes are field installed with the outsidepressure being sensed external to the unit. To avoid anerratic pressure reading, the building pressure sense tubeshould be mounted in an area away from the return air grill,discharge diffusers, doors and windows.

Page 102: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

102 Unitary Products Group

BINARY INPUTS (BI):

APS - Supply Fan status is monitored by an Air Proving Sta-tus switch (PN: 024-27557-000A) installed at the factory. TheAPS monitors the difference in pressure between the suctionand discharge of the fan.

C1O through C4O - These four binary inputs report the statusof the Compressors 1 through 4 overload modules.

FOVR - Monitoring loop through the supply fan overloadmodule.

HPS1-4, LPS1-4 - The refrigerant high pressure (HP) and lowpressure (LP) safety switches, are independently monitoredby the Millennium Simplicity. If any switch opens, the controlvoltage from the control binary output is interrupted and thestatus is monitored by the control.

G, OCC, P - These signals represent Fan (G), Building Occu-pancy (OCC), and Building Purge (P) calls from the thermo-stat. If a thermostat is installed on the system, these inputsare connected to the thermostat interface board just as arethe cooling/heating calls. These inputs are connected throughthe Tstat Interface board directly to the respective binaryinputs of the Controller. These signals are, however, eachloaded with a resistor to maintain voltage levels and to pre-vent “floating” of signals. Thermostat wiring is typically notshielded and may have induced voltages that could causeerrant signal readings by the controller.

FILT - Dirty Filter switch [customer supplied, field installed onfactory-provided harness connections] input to provide a filterstatus to the control. The control will alarm only after 24V hasbeen sensed for ten minutes.

GV1-3 - Monitoring that voltage is being supplied to gasvalves on optional heat stages.

LIM1-3 - Overtemperature inputs from optional heat stages.

FSI - Freeze Stat is a customer installed temperature switchon the FSI input to the controller to tell the control that a tem-perature has occurred that risks the hot water or steam coil.

Y1-4, W1-3 - If a thermostat is installed on the system, theseinputs will take priority over software programmed setpointsand limits.

SD - This terminal set allows attachment of an external shut-down NC contact. 24VAC power is supplied to the board atSD2; a factory installed jumper passes that power to terminalR to power the Simplicity Elite board. If an external shutdownsignal is required at a particular installation, remove thejumper and connect the NC shutdown circuit between SD1and R.

OUTPUTS

Analog Outputs (AO) - Analog outputs provide a 2-10 VDCsignal to operate controlled devices. The Simplicity is cur-rently configured to use only 2-10 VDC outputs to the Vari-able Frequency Drive, Inlet Guide Vane, EconomizerDamper, Power Exhaust Dampers or VFD, and Heating watervalves. Since these outputs are analog, they are continuousbetween 2 and 10 Volts and are proportional to the 0 to 100%drive position of the device.

ECO - Economizer Actuator - The modulating Economizeruses a Belimo AF24-SR.9 spring-return actuator (PN: 025-30869-000A). This actuator uses a 2-10 VDC signal to drivethe dampers open. The actuator drives 95 degree rotation.Note the chart below for a correlation between the input drivesignal at terminal 3 (Y1) of the Belimo actuator and the corre-sponding output drive position of the damper:

VFD - Inlet Guide Vane or VFD. The Inlet Guide Vane usesa Belimo GM24-SR spring-return actuator. This actuator usesthe 2-10 VDC signal from VFD+/- terminals to drive thedampers open. The actuator drives 95 degree rotation. Notethe chart below for a correlation between the input drive sig-nal at terminal 3 (Y1) and the corresponding output driveposition of the guide vane. If the unit has a factory-installedVariable Frequency Drive, the 2 to 10 VDC signal is wiredfrom VFD+/- output directly to the VFD’s signal input termi-nals to control fan motor speed.

TABLE 49:INPUT SIGNAL TO Y1 ACTUATOR POSITION

Input Signal to Y1 Actuator Position10 VDC 90 degrees

9 788 677 566 455 334 223 112 00 -5

8VDC over a 90 degree Span = 11.25 degrees/VDC

FIGURE 34 - VFD CONTROL WIRING

VFDFR

FRFan

VFD +

VFD -

Simplicity12

18

53

55

P13-1

P14-1

P14-2

Wht

Blk

TB2

Page 103: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 103

EXD - Power Exhaust Damper Vane or VFD - PowerExhaust Damper Actuator is a BELIMO AF24-3-S 24VAC. Ituses a full open/ Full Closed scheme and operates a 95degree rotation. If VFD Power Exhaust is configured, thesame signal controls the exhaust fan motor drive frequency.

HWV - Heating Water Valve - Customer supplied andinstalled, connect to factory-provided harness.

BINARY OUTPUTS (BO)

FAN - Fan Start/Stop Relay, VFD “permission” relay FR

H1-3 - HEAT STAGES 1 TO 3 [OPTIONAL]

C1 through C4 - Cooling Stages 1 through 4

CF1 & CF2 - Condenser Fan Banks 1 and 2

X - Controller Alarm is field-wired from the thermostat inter-face board to signify a controller alarm has occurred.

TABLE 50: SIMPLICITY CONTROL INPUTSName Range Resolution Precision Description

Y1 18 - 30 VAC On - Off +/- .5 VAC Request for the first stage of Cooling (24 VAC sense) Tstat Screw Terminal

Y2 18 - 30 VAC On - Off +/- .5 VAC Request for the second stage of Cooling (24 VAC sense) Tstat Screw Terminal

Y3 18 - 30 VAC On - Off +/- .5 VAC Request for the third stage of Cooling (24 VAC sense) Tstat Screw Terminal

Y4 18 - 30 VAC On - Off +/- .5 VAC Request for the fourth stage of Cooling (24 VAC sense) Tstat Screw Terminal

W1 18 - 30 VAC On - Off +/- .5 VAC Request for the first Stage of Heating (24 VAC sense) Tstat Screw Terminal

W2 18 - 30 VAC On - Off +/- .5 VAC Request for the second Stage of Heating (24 VAC sense) Tstat Screw Terminal

W3 18 - 30 VAC On - Off +/- .5 VAC Request for the third Stage of Heating (24 VAC sense) Tstat Screw Terminal

G 18 - 30 VAC On - Off +/- .5 VAC Request for the Fan (24 VAC sense) Tstat Screw Terminal

R 18 - 30 VAC - - These terminals are a ¼' Female Faston and a Thermostat Screw terminal connected to the power supply of the board.

C Earth Ground - - These terminals are a ¼' Faston and a Thermostat Screw termi-nal.

OCC 18 - 30 VAC On - Off +/- .5 VAC Occupied input (24 VAC sense) Tstat Screw Terminal

SD 18 - 30 VAC - +/- .5 VAC Shut Down input Tstat Screw Terminal

Purge 18 - 30 VAC On - Off +/- .5 VAC Building Purge input (24 VAC sense) Tstat Screw Terminal

BAS Economizer 2 - 10 VDC Not Read by micro - Input that routes to the Economizer output Two Tstat Screw Ter-

minals +&-

HPS1 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 1 (24 VAC sense)

HPS2 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 2 (24 VAC sense)

HPS3 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 3 (24 VAC sense)

HPS4 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 4 (24 VAC sense)

LPS1 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 1 (24 VAC sense)

LPS2 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 2 (24 VAC sense)

LPS3 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 3 (24 VAC sense)

LPS4 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 4 (24 VAC sense)

Limit Switch 1 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 1

Limit Switch 2 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 2

Limit Switch 3 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 3

GV1 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 1

GV2 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 2

GV3 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 3

Test / Reset / Up ON - Off ON - Off - Test / Reset Button and Increment Data Input

Address / Down ON - Off ON - Off - Address Button and Decrement Data Input

Alarms / Advance Data ON - Off ON - Off - Alarm Button and Advance Data Input

Page 104: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

104 Unitary Products Group

Program ON - Off ON - Off - Program Button Input

Real Time Clock

24 hours, 365 Days including Leap year and

Daylight Savings Time

Seconds - Real Time Clock Chip

Water Coil Freeze Stat (FSI) 18 - 30 VAC On - Off +/- .5 VAC Hot Water Freeze Stat (24 VAC sense) two ¼ Fastons

Supply Air Temp Sensor (SAT) -40° - +180° F .1° F

-40° - 180°F +/- 2°F across

rangeThis is a 10KΩ type 3 Thermistor

Outside Air Temp Sensor (OAT) -40° - +180° F .1° F

-40° - 180°F +/- 2°F across

rangeThis is a 10KΩ type 3 Thermistor

Space TempSensor (ST) 32° - 100° F .1° F .5° F This is a 10KΩ type 3 Thermistor

Return Air Temp Sensor (RAT) -40° - +180° F .1° F

-40° - 180°F +/- 2 °F across

rangeThis is a 10KΩ type 3 Thermistor

Space Setpoint Off-set (SSA) 0 - 20 KΩ 1 KΩ + and - 250 Ω

3 position Mini Screw Terminal shared with Space Temp The common terminal in the center is common for both the Space Temp and Setpoint Offset.

Building Pressure Sensor (BPS)

0 - 5 VDC-.25 - +.25 "WC .001 "WC .005 "WC

1% Across range 0 - 5 volt input

Duct Pressure Sen-sor (DPS)

0 - 5 VDC0 - 5 "WC .01 "WC .05 "WC 1%

across range 0 - 5 volt input

Compressor 1 Over-load (C1O) 18 - 30 VAC On - Off +/- .5 VAC Compressor number 1 Overload (24 VAC sense)

Compressor 2 Over-load (C2O) 18 - 30 VAC On - Off +/- .5 VAC Compressor number 2 Overload (24 VAC sense)

Compressor 3 Over-load (C3O) 18 - 30 VAC On - Off +/- .5 VAC Compressor number 3 Overload (24 VAC sense)

Compressor 4 Over-load (C4O) 18 - 30 VAC On - Off +/- .5 VAC Compressor number 4 Overload (24 VAC sense)

APS (APS) 18 - 30 VAC On - Off +/- .5 VAC Air Proving Switch (24 VAC sense)

Fan Overload (FOVR) 18 - 30 VAC On - Off +/- .5 VAC Fan Overload Switch (24 VAC sense)

CV / VAV Input 0 - 20 KΩ 1Ω + / - 5 Ω Resistive Input 0 - 5.5K = CV 10K - 20K = VAV

Demand Ventilation Input

0 - 10 VDC 0 - 2000 PPM of

CO21 PPM 20 PPM

1% Across Range 0 - 10 volt input

Remote Control 0 - 10 VDC .05 VDC 0.01 0 - 10 VDC Screw terminal two position Small screw terminal

Dirty Filter Switch (FILT) 18 - 30 VAC On - Off +/- .5 VAC This is the Dirty Filter Switch (24 VAC sense)

Low Voltage Detec-tion 12 - 35 VAC .1 VAC .5 VAC This input monitors the 24 VAC for Low Voltage Detection

Return AirHumidity (RAH)

0 - 5 VDC0 - 100% RH .05 VDC1% RH .1 VDC

2% Across RangeScaleable 0 - 10 volts Screw terminal two position Small screw terminal

Outside AirHumidity (OAH)

0 - 5 VDC0 - 100% RH .05 VDC1% RH .1 VDC

2% Across RangeScaleable 0 - 10 volts Screw terminal two position Small screw terminal

Comm Port 128 nodes See Communica-tions - Asynchronous Serial Port (RS485) three position Small screw

terminal

24 VAC - Class 1 18 - 30 VAC - - ¼'' quick connect for power to the contactors through the Relays.

TABLE 50: SIMPLICITY CONTROL INPUTS (Continued)Name Range Resolution Precision Description

Page 105: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 105

TABLE 51: SIMPLICITY CONTROL OUTPUTSName Range Resolution Precision Description

LED On - Off - - Status LED

Display 7 segment W/ Decimal Point 6 "Seven Segment LED /W decimal point"

H1 Class 1 Relay Contacts - - Heat 1 contactor output (Relay Contacts - 24 VAC/120 VAC)

H2 Class 1 Relay Contacts - - Heat 2 contactor output (Relay Contacts - 24 VAC/120 VAC)

H3 Class 1 Relay Contacts - - Heat 3 contactor output (Relay Contacts - 24 VAC/120 VAC)

C1 Class 1 Relay Contacts - - Compressor number one contactor output (Relay Contacts - 24

VAC/120 VAC)

C2 Class 1 Relay Contacts - - Compressor number two contactor output (Relay Contacts - 24

VAC/120 VAC)

C3 Class 1 Relay Contacts - - Compressor number three contactor output (Relay Contacts - 24

VAC/120 VAC)

C4 Class 1 Relay Contacts - - Compressor number four contactor output (Relay Contacts - 24

VAC/120 VAC)

CF1 Class 1 Relay Contacts - - Condenser Fan contactor output (Relay Contacts - 24 VAC/120

VAC)

CF2 Class 1 Relay Contacts - - Condenser Fan contactor output (Relay Contacts - 24 VAC/120

VAC)

Fan Class 1 Relay Contacts - - Fan contactor output (Relay Contacts - 24 VAC/120 VAC)

Exhaust Fan (EXH) Class 1 Relay Contacts - - Exhaust Fan contactor output (Relay Contacts - 24 VAC/120

VAC)

Supply Fan VFD 2 - 10 VDC - - This is a 2 - 10 volt output capable of 10 ma

Exhaust Fan Damper (EXD) 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma

Hot Water Valve (HWV) 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma

Hot Gas Reheat 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma

Economizer (ECO) 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma

X 24VDC - - This is a 24VDC output for Alarms

Page 106: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

106 Unitary Products Group

SIMPLICITY PROGRAMMING OPTIONSThe paragraphs below provide a definition of, and specify thefunction related to, each of the parameters that are field-adjustable using the interfaces available. The Millennium Unitis shipped from the factory with the necessary options pre-programmed as indicated by the model nomenclature. It isalways a good practice, though, to verify that the correctparameters are properly configured for the unit you are com-missioning. You can find a complete list of field-adjustableparameters in the “Settable System Parameters”.

For a description of the parameters, see the Settable Sys-tem Parameters below and Table 52.

INTERACTING THROUGH THE MILLENNIUM SIM-PLICITY

SET THE CLOCK

• Power up the unit.• Press the Program button [upper left].• Press the Test/Up button [upper right]. Hold it in and it

will step through the parameters, or push in to advance one parameter at a time. Advance to parameter 63, Hours.

• Press Change [lower left] Press Up [upper right] or Down [lower right] to the correct hour [24 hour time].

• Press Change to enter the new value.• Press Up to get to parameter 64, Minutes.• Press Change.• Press Up or Down to get to the correct minute value.

Press Change to enter the new value.• If you are done changing parameters, press Program to

exit the program mode.

PARAMETER SETTING

The buttons allow the operator to go to a specific parameterand to view and change the data in that parameter.

• To enter the parameter setting mode, press the Pro-gram button. The control will display the current parameter number in the two-digit display, and the present value of that parameter in the four-digit dis-play.

• To change to another parameter, press the /Up or /Down button to move to the address of the desired parameter. The present value of that parameter will display.

• To change the data, press the /Change button. The value will flash. While it is flashing, press the /Up or /Down button to increase or decrease the value.

• When the desired new value is showing, press the /Change Data button again to tell the control to store the new value. You can verify that the new value is in place when the value stops flashing.

• To exit Program mode, press the Program button again.

INITIAL STARTUP OPTIONS

Commissioning a new Millennium installation requires somefield adjustments to the Simplicity control program. Most ofthese adjustments simply involve setting up the various set-points that are specific to your customer’s needs (i.e. buildingpressure) or enabling some extended options that are inte-grated into the Simplicity control. Also, if there are fieldchanges, i.e. a modulating power exhaust option, the controlconfiguration will need to be modified for the new option.

METRIC OPERATION (ENGLISH)

The factory default for this option is OFF. The metric (SI) con-versions are part of the controller software; when the Metricparameter is selected, temperature setpoints and readingswill convert to Centigrade (°C).

SETTABLE SYSTEM PARAMETERS The following headings list each parameter’s name and itsdefault setting. The control is set at the factory for the optionsof the specific unit; if a replacement control is being installed,the entire parameter set must be matched to the unit. Thenumber in (parentheses) is the value of a parameter in an un-configured control.

Compressors - (2) - This tells the control the number of com-pressors available. The Factory Default [the value in anunconfigured replacement control] is 2 and can be adjustedfrom 1 to 4.

Heat Stages - (2) - This tells the control the number of heat-ing stages available. This parameter may be set from 0 to 3.The default setting is 2 stages of heat.

Hydronic Heat - (OFF) - This tells the control that a HotWater Coil is installed. If the control is going to modulate theHot Water Valve it will also turn on the Heat One output. Thisis to energize the VAV heat relay for the VAV boxes. Thedefault is OFF for this option. If this parameter is enabled,remember to set the Hydronic Heat First and Second StageSetpoints and the Economizer Loading Setpoint found in the”Simplicity Setpoints”.

Stage 1 Hydronic Heat SAT Setpoint - (120°F) - When theHydronic Heat option is enabled, the control will maintain thisSAT setpoint for a call for first stage Heating, by modulatingthe Hot Water Valve. This is the reset temperature whenoperating a VAV unit in the Heating mode. The reset rangefor SAT setpoint is from 80°F to 180°F with 120°F shipped asthe default.

Hydronic Heat Reverse Actuated Valve - (OFF) - This set-ting is to allow convenient use of reverse acting water valves;setting this parameter to (ON) will change the signal to 2VDC= open, 10 VDC = closed.

Page 107: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 107

SAT Control for Cooling - (ON) - This tells the control if it isgoing to do excessive SAT monitoring and tripping or not, forCooling. The SAT should be maintained in an acceptablerange in order to achieve reliable compressor operation. Thecompressor trip limits are user adjustable between 40°F and65°F in one degree increments. The default cooling trip limitsare 50°F for stages 2-4, and 45°F for stage 1. When the SATdrops below the trip limit for each respective compressor, thatcompressor is locked out and a 5 minute ASCD is initiated forthat compressor. If this option is enabled, remember to setthe compressor cooling limits for low limit trip.

Power Exhaust - (ON) - This tells the control if it has thePower Exhaust option installed.

Economizer Damper Position for Exhaust Fan to turn ON(Non-Modulating PE Only) - (60%) - This tells the controlthe Economizer Damper position to turn on the Exhaust Fan.This value is based on the 0%-100% output drive signal fromthe controller to the economizer damper actuator.

Economizer Damper Position for Exhaust Fan to turnOFF (Non-Modulating PE only) - (20%) - This tells the con-trol the Economizer Damper position to turn off the ExhaustFan. This value is based on the 0%-100% output drive signalfrom the controller to the economizer damper actuator.

Modulating Exhaust - (OFF) - This tells the control if thePower Exhaust is Modulating or not. A modulating exhaustwill be equipped with a Building Pressure Sensor [BPS]. ANon-Modulating exhaust will look to the economizer damperposition to energize the EXD output. If the sensor gets dis-connected, or fails, an alarm is set. The alarm can be turnedoff by correcting the sensor problem (or; by turning off thisoption). The control is not in this case self-configuring. It willnot automatically use the Building Pressure Sensor if thesensor is connected.

Exhaust VFD Installed - (OFF) - If the unit has a VFD, theEXD output will be enabled when the supply fan is ON.

Exhaust Damper Position For The Exhaust Fan To TurnOn (Modulating Only) - (80%) - This tells the control theExhaust Damper position at which to turn on the ExhaustFan. This value is based on the 0%-100% output drive signalfrom the controller to the damper actuator.

Exhaust Damper Position For Exhaust Fan To Turn Off(Modulating Only) - (20%) - This tells the control theExhaust Damper position to turn off the Exhaust Fan. Thisvalue is based on the 0%-100% output drive signal from thecontroller to the damper actuator.

Building Pressure Setpoint - (+0.100”WG) - This is thepressure setpoint the control will maintain when operating aPower Exhaust. The Building Pressure Setpoint is adjustablefrom -0.200”WG to +0.200”WG. The factory programmeddefault is +0.100”WC. This setpoint is used when the exhaustcontrol is implemented as Proportional Control (with a Modu-

lating Exhaust Air Damper or VFD controlled from buildingstatic pressure), or as a Two-position Control using buildingstatic (Power Exhaust Fan controlled on-off from buildingstatic pressure).

Economizer - (ON) - This tells the control that there is anEconomizer Installed.

Economizer Min Position - (20%) - This tells the controlwhat the minimum outdoor damper position will be for theOccupied mode. Adjustable from 0-100%, the EconomizerMinimum Position default is 20%.

Economizer First Stage Setpoint - (55°F) - This tells thecontrol what Supply Air Temperature to maintain for a call forfirst stage of cooling. This is used only during Constant Vol-ume cooling mode with Economizer operation. The setpointis set at 55°F with an adjustable range from 40°F to 65°F.

Economizer Second Stage Setpoint - (50°F) - This tells thecontrol what Supply Air Temperature to maintain for a call forsecond stage of cooling. This is used only during ConstantVolume cooling mode with Economizer operation. This set-point is set at 50°F with a range from 40°F to 65°F.

Outside Air Humidity (OAH) Sensor Enable - (OFF) - Thissetting tells the control that it is expected to use Outside AirEnthalpy (calculated from Outside Air Temperature and Out-side Air Relative Humidity sensed values) to decide if OutsideAir can be used for cooling.

The control is self-configuring to the best available decisionstrategy for free cooling availability. For example, if it detectsthat OAT and OAH and RAT and RAH sensors are all con-nected and reliable, will self-configure for Differential Enthalpyoperation. If one of the return air sensors should fail, the con-trol will reconfigure for Outside Enthalpy operation, etc.

If the OAH Sensor Enable option is turned ON, it means thatthe Outside Enthalpy Operation, or better decision strategy, isexpected (and supported by installed sensors). If the appro-priate sensors are not installed, or one of them failed, a sen-sor failure alarm is set. The alarm can be turned off by turningoff the OAH Sensor Enable option. Thus, the option setting isused to reflect the desired operation and mainly to controlsensor failure alarms.

The option setting can be viewed as specifying that (the self-configured economizer decision strategy has to be at leastthis, or better, otherwise an alarm is set). If the option is OFF,the control still may self configure to Outside Enthalpy Opera-tion, or even to Differential Enthalpy Operation (if all neededsensors are available), but this option setting will allow alsothe decision strategy based on only OAT (in case other sen-sors fail, or are not installed) without setting an alarm.

Outside Air Enthalpy Setpoint - (27 BTU/LB) - This tells thecontrol an outside air enthalpy limit. Below this limit, outsideair is available for cooling. See enthalpy chart. This parame-

Page 108: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

108 Unitary Products Group

ter uses a one BTU/LB hysteresis on each side of the limit.The limit is preset to 27 BTU/ LB with an adjustable rangefrom 10 to 50 BTU/LB.

Return Air Humidity (RAH) Sensor enable - (OFF) - Thistells the control that it will compare Outside Air Enthalpy (cal-culated from Outside Air Temperature and Outside Air Rela-tive Humidity sensed values) and Return Air Enthalpy(calculated from Return Air Temperature and Return Air Rela-tive Humidity sensed values). The control will use the airstream with the lower enthalpy for cooling.

The control is self-configuring to the best available decisionstrategy for free cooling availability. For example, if it detectsthat OAT and OAH and RAT and RAH sensors are all con-nected and reliable, will self-configure for DifferentialEnthalpy operation. If one of the return air sensors should fail,the control will stop using rules that involve RAH and set analarm.

If the RAH Sensor Enable option is turned ON (and sup-ported by installed sensors), Differential Enthalpy Operationcan be enabled. If the appropriate sensors are not installed,or one of them failed, a sensor failure alarm is set. The RAHalarm can be turned off by turning off the RAH Sensor Enableoption. Thus, the option setting is used to reflect the desiredoperation and mainly to control sensor failure alarms.

Economizer Loading to Control SAT - (ON) - This tells thecontrol if it is going to use Economizer Loading to controlexcessive SAT [supplying warmer outside air to keep SATfrom going too low]. This parameter is only applicable outsidethe normal Economizer operation. During the Economizeroperation, the loading function is always performed and is anintegral part of the control algorithm.

Duct Static Setpoint - (1.5”WG) - This parameter is applica-ble only to VAV mode of operation. This is the pressure set-point that the control will maintain when operating the fan in aVAV unit. This setpoint is adjustable between 0”WG and5”WG with the default set to 1.5”WG.

Duct Static High Limit Setpoint - (4.5”WG) - This parame-ter is applicable only to VAV mode of operation. This tells thecontrol at what Static Pressure to shut down the unit due to aFan control failure. This setpoint is to insure that we don'tcontinue to operate the Fan with an Inlet Guide Vane or VFDproblem that could cause the ductwork to fail from duct pres-sure. When the Static Pressure reaches this setpoint(4.5”WG default), the control will drive the supply fan controloutput to zero. If the static pressure does decrease below the“Duct Static High Limit Setpoint” within 3 seconds afterdecreasing the supply fan control output to zero, the controlwill resume normal operation. If there is no change in staticpressure after 3 seconds, the control will generate a HighDuct Static alarm, shut down all the outputs including the Fanand shut down the unit. The alarm is written to the Error His-tory Buffer and will trigger storing a snapshot of Points

Screen data along with a date and time stamp. In networkedapplications, the alarm flag is readable by the network. Thisparameter can be adjusted from 0”WG to 5”WG with the fac-tory default set to 4.5”WG.

The customer must be aware of the duct pressure designlimit, and what the duct pressure sensor will be reading whenthe peak pressure is reached [the pressure pickup tube maynot have been located at the place of highest pressure in thesystem].

The alarm must be reset (after the problem that caused thealarm is corrected) by resetting the controller by turningpower to the unit off and back on, or by reset commandissued by an external connection.

Morning Warm Up - Is inferred from the entries in Occu-pied/Unoccupied

Occupied - (from settings in Weekly Schedule and Holi-day Schedule Tables 44 and 45.) - See discussion inSequence of Operation.

Unoccupied - (from settings in Weekly Schedule and Hol-iday Schedule Tables 44 and 45.) - See discussion inSequence of Operation.

VAV High Temperature SAT Setpoint for Cooling - (60°F) -The control will maintain this SAT when operating in VAVmode with a thermostat that is calling for first stage cooling.This parameter may be adjusted from 40°F to 70°F with 60°Fset as the default value.

VAV Low Temperature SAT Setpoint for Cooling - (55°F) -The control will maintain this SAT when operating in VAVmode with a thermostat that is calling for second stagecooling. This parameter may also be adjusted from 40°F to70°F with 55°F set as the default value.

VAV SAT Reset Setpoint - (72°F) - This parameter is usedonly in VAV mode with a Space Sensor. The control willswitch from the VAV Lower Cooling SAT Setpoint to the VAVUpper Cooling SAT Setpoint when this Space TemperatureSetpoint minus 0.5°F is reached. The control will switch fromHigh setpoint back to Low setpoint when the space tempera-ture gets 2°F above this setpoint. This is SAT reset based onSpace Temperature. The reset occurs in both Occupied andUnoccupied modes and may be adjusted from 40°F to 85°F.The factory default is 72°F.

VAV Occupied Heating - (OFF) - This option applies in VAVmode with a Space Sensor and does not affect VAV Occu-pied heating if requested by a thermostat. When this option istoggled on, a VAV unit is able to operate heating in the occu-pied mode as long as it is operating with a Space Sensor. Ifthe Space Temperature drops to 2°F below the VAV SATReset Setpoint the control will read the RAT. If the RAT isbelow the Morning Warm Up RAT Setpoint the unit will enter

Page 109: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 109

the Occupied Heating mode. Operation is the same as Morn-ing Warm Up. This parameter is factory set to OFF.

Comfort Ventilation Mode - (OFF) - Comfort Ventilation is aSAT control mode that controls SAT during “satisfied” periodsin a fairly wide temperature band, using mostly Outside Air,and also cooling and heating stages as necessary. It is avail-able only on the Constant Volume unit.

To enable Comfort Ventilation, the programmable parameter“Comfort Ventilation Mode” must be set to ON (default settingis OFF).

For a detailed explanation of Comfort Ventilation, refer to theSequence of Operation in this manual.

Comfort Ventilation High Supply Air Setpoint - (80°F) -This is the High Limit Setpoint for the Comfort Ventilationmode. For a stable operation of Comfort Ventilation function,the High Supply Air Setpoint should be set 10.0°F or moreabove the Low Setpoint.

Comfort Ventilation Low Supply Air Setpoint - (70°F) -This is the Low Limit Setpoint for the Comfort Ventilationmode. For a stable operation of Comfort Ventilation function,the Low Supply Air Setpoint should be set 10.0°F or morebelow the High Setpoint.

Dirty Filter Switch - (OFF) - This tells the control that a DirtyFilter Switch is connected to it. The control will wait for tenminutes after the switch has closed before declaring a DirtyFilter Alarm. The alarm is written to the Error History Buffer. Innetworked applications, the error flag is readable by the net-work. The alarm will automatically reset when the error condi-tion is corrected.

The default is OFF.

Heating Lockout on OAT - (75°F) - This is the Outside AirTemperature Setpoint that the control will use to lock outHeating when the OAT is above this setpoint. There is a one-degree hysteresis on each side of the setpoint. This parame-ter is adjustable between 0°F and 100°F with the default setto 75°F.

Heating Lockout on OAT affects only staged heating, it doesnot affect hydronic heat. If the heating is energized when OATreaches this setpoint, the Status LED will indicate the lockoutcondition immediately, but the control will finish the heatingmode and then lock out the heating.

Note that a Heating Lockout on OAT may occur while the con-trol is in a heating mode and there is a demand for heating.

If the OAT then decreases below the lockout setting while thecall for several heat stages exists, the heat stages will turn onsimultaneously. This is considered acceptable as this situa-tion is not expected to occur frequently.

Cooling Lockout on OAT - (45°F) - This is the Outside AirTemperature Setpoint that the control uses to lock out Cool-ing when the OAT is below this setpoint. Adjustable from 0°Fto 100°F, the default is 45°F.

Unoccupied Heating Setpoint - (60°F) - This value is theUnoccupied Heating Setpoint. It is used in both CV and VAVmode of operation (in VAV, it controls Unoccupied heatingwith a Space Sensor).

The control will attempt to correct wrong temperature overlapsettings; for example, if a change is made that would putOccupied Heating above Occupied Cooling, the OccupiedCooling setting will change to stay above the heating set-point.

Occupied Heating Setpoint - (68°F) - This value is theOccupied Heating Setpoint. It is used only in CV mode ofoperation. Its relationship to the related setpoints is asdefined in the Unoccupied Heating Setpoint paragraphabove.

Unoccupied Cooling Setpoint - (85°F) - This value is theUnoccupied Cooling Setpoint. It is used in both CV and VAVmode of operation (in VAV, it controls Unoccupied coolingwith a Space Sensor).

Occupied Cooling Setpoint - (72°F) - This value is theOccupied Cooling Setpoint. It is used only in CV mode ofoperation. Its relationship to the related setpoints is asdefined in the Unoccupied Heating Setpoint paragraphabove.

[Input] FSI (Hot Water Freeze Protection) - (OFF) - Thisoption is used only on rooftop units with hydronic heat(Hydronic Heat Option is turned ON). Freeze protectionshould always be placed on units that use hydronic heating.When the control senses 24VAC, the control will turn on theHot Water valve to 100%. The control will continue to drivethe valve at 100% until five minutes after the switch hasopened. Then the valve will revert to normal operation. If thecontrol is operating the Fan, it will close the Economizer fullyuntil the freeze condition is over. If the fan is off and the RATdrops below 40°F, the Hot Water Valve will turn on 100%.

FIGURE 35 -SEQUENCE OF SETTING THE SET POINTS

UnOcc.

Htg.

Occ.

Htg.

UnOcc.

Clg.Occ.

Clg.

Page 110: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

110 Unitary Products Group

Supply AirTemp (SAT) Alarm Setpoint for Cooling - (0°F) -If the SAT does not drive below this setpoint when all stagesof compression are operating and 10 minutes has elapsedsince the last compressor was energized, the control willdeclare a Cooling SAT Failure Alarm.

The alarm is written to the Error History Buffer. In networkedapplications, the alarm flag is readable by the network.

The alarm will reset automatically if the SAT does decreasebelow the setpoint (the alarm condition no longer exists), orwhen a compressor is turned off (the control does not requestall compressors operate). The SAT Alarm Setpoint for Cool-ing can be adjusted from 50°F - 80°F. If the value is set to 0°F(default) this feature is disabled.

Before the control declares an error, it will read the OAT andthe Economizer position. If the OAT is more than 20°Fwarmer than the setpoint and the Economizer is open morethan 20%, the control will close the Economizer for 10 min-utes and then read the SAT. If the SAT falls below the set-point, the control will declare an Economizer MinimumPosition alarm. The control will keep the Economizer closedand finish the Cooling mode. After the Cooling mode hasbeen satisfied, the control will move the Economizer back tothe minimum position.

Supply Air Temp (SAT) Alarm Setpoint for Heating - (0°F) -The SAT must drive above this setpoint when all stages ofheating are operating and 10 minutes has elapsed since thelast stage was energized. If this does not happen, the controlwill declare a Heating SAT Failure Alarm. The alarm is writtento the Error History Buffer. In networked applications, the alarmflag is readable by the network. The alarm will reset automati-cally if the SAT does increase above the setpoint (the alarmcondition no longer exists), or when a heating stage is turnedoff (the control does not request all heat stages to operate).

The SAT Alarm Setpoint for Cooling can be adjusted from70°F - 120°F. If the value is set to 0°F (default) this feature isdisabled.

Before the control declares an error, it will read the OAT andthe Economizer position. If the OAT is more than 20°F colderthan the setpoint and the Economizer is open more than20%, the control will close the Economizer for 10 minutes andthen read the SAT. If the SAT rises above the setpoint, thecontrol will declare an Economizer Minimum Position alarm.The control will keep the Economizer closed and finish theHeating mode. After the Heating mode has been satisfied,the control will move the Economizer back to the minimumposition.

Unoccupied Override Time Period - (60 min) - The Unoc-cupied Override Time Limit function will determine how longthe unit will operate in the Unoccupied Override mode whenthe Override button is pressed on the Space Sensor.

Once the Unoccupied Override mode is initiated, it will con-tinue until the programmed Unoccupied Override Time Limitis reached. The Override mode can not be cancelled by, forexample, a change of state of the Occupied input to ON(occupied) and then back to OFF (unoccupied).

This parameter is adjustable from 0 to 240 minutes. Thedefault is 60 minutes.

Fan Delays (ON) & (OFF) - Any time the control starts acompressor it will load the Fan On Delay for Cool with theprogrammed value. Any time the control turns off all the com-pressors it will load the Fan Off Delay for Cool with the pro-grammed value.

When the control turns on a gas heat stage, it will begin mon-itoring the gas valve and load the Fan On Delay For Heat withthe programmed value when it senses gas valve voltage.

When the thermostat terminates the call for W1 the controlwill turn off H1 output and load the Fan Off Delay for Heatwith the programmed value.

After the control has turned on heat, it will start monitoring theGas Valve. If at any time the Gas Valve (24 VAC) is notpresent for five minutes while H1 is on, the control will flag anAlarm. Anytime GV1/H1 goes off during the fan on delay, thecontrol will force the fan on, for the fan off delay period. Thecontrol will wait for GV1 to be on at least 15 seconds beforeforcing the fan on. If GV1 has been on for at least 15 sec-onds, and then goes away before the Fan On Delay has fin-ished, the fan will turn on anyway far a length of time equal tothe Fan Off Delay period.

If the control senses this input along with a Y signal, it will notturn on the compressors and it will run the Heating mode.Heating takes priority.

Fan ON Mode with the Sensor Option - (ON) - When thisoption is turned ON, the supply fan will continue runningwhen the zone sensor based temperature control is satisfied.This option applies only in systems using a zone sensor andonly in Occupied mode. With this option turned OFF, or inUnoccupied mode, the fan will go off when the zone sensorbased temperature control is satisfied and will go on onlywhen there is a call for heating or cooling. Turning this optionON is an equivalent of selecting fan ON (rather than AUTO)in systems with a thermostat. In a thermostat system, the fancontrol follows the thermostat's G signal. In sensor systemsand in the Occupied mode, the fan control follows the FanON Mode option.

Space Sensor Enable - (OFF) (INTERNALLY SET) - Thecontrol will use this input if it detects the device.

RAT Sensor Enable - (OFF) (INTERNALLY SET) - The con-trol will use this input if it detects the device.

Page 111: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 111

Demand Ventilation (ON) - Setting this parameter on tellsthe control to expect a signal from a 0-10VDC CO2 sensor.The default setting for CO2 is 1,000 ppm.

Demand Ventilation Setpoint - (1000 ppm) - This Setpointis the maximum Indoor Air Quality (IAQ) level that the controlwill allow. It is adjustable from 700 ppm to 1500 ppm.

IAQ Sensor Range - (5,000 ppm) - This tells the controlwhat the full range is for a specific IAQ sensor. It can bechanged from 0 to 10,000 ppm.

Cooling Mode Enable (ON) - This tells the control if it hasCooling Available (Mode Switch). If this option is turned off,cooling operation is disabled. Note that this parameter doesnot affect cooling operation in Comfort Ventilation mode.

Heating Mode Enable - (ON) - This tells the control if it hasHeating Available (Mode Switch). If this option is turned off,heating operation is disabled. Note that this parameter doesnot affect heating operation in Comfort Ventilation mode.

Space Setpoint Offset - (3°F) - The Space Setpoint Offset isthe +/- value the control will use to offset the Space Setpointwhen the slidebar Space Sensor is used. For example, if theSpace Setpoint Offset value is set to 3.0°F, shifting the slide-bar all the way in minus direction will decrease the SpaceSetpoint by 3.0°F and shifting it all the way in plus directionwill increase the Space Setpoint by 3.0°F. It is adjustable from0°F to 5°F.

ASCD Override - This is not an option parameter but rather aone-time command issued by pressing the Test / Reset / Upbutton pressed and released within five seconds; the ASCD’swill be set to zero for one cycle.

Run Test (Commissioning Test) - This is not an optionparameter but rather a one-time command, activated by set-ting parameter 1 ON.

When the Run Test command is issued, the control will shutthe unit down if it is running and then start a Run testsequence:

1. Turn on the Fan and then turn on all the compressors, one at a time, with a 15-second delay between them. Condenser fan #1 turns on with compressor #1, con-denser fan #2 turns on with compressor #2. After the last compressor has been turned on, the control will run the compressors for the programmed minimum run time and then turn them all off. Condenser fans are also turned off.

2. The control will then turn on the Heat stages, one at a time, with a 15 second delay between them. The control will run each Heat stage for three minutes and then turn all the Heat off.

3. The control will then open the Economizer to the 100% open position and wait five minutes before closing it to the Minimum Position. When the economizer is at 100%, the exhaust damper will be open to 100% and the exhaust fan runs for 5 minutes, then shuts down.

4. During this Run Test operation the control will read all the installed sensors and verify that their readings are good. If any error is detected the control will display the appro-priate error. During the Run Test, the supply fan contin-ues to be monitored via the Air Proving Switch, and a fan failure will cause a unit shutdown.

After the control is finished with the Run Test the normal oper-ation will resume. This command is a good method to use toensure the control is operating and all input and output pointsare functional.

Page 112: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

112 Unitary Products Group

TABLE 52: SETTABLE SYSTEM PARAMETERSADDRESS FUNCTION UNIT RANGE DEFAULT YOUR SETTINGS

1 Run test ON-OFF OFF

2 Fan on delay-Heating Sec 0-30 30

3 Fan off delay-Heating Sec 0-255 60

4 Fan on delay-Cooling Sec 0-30 0

5 Fan off delay-Cooling Sec 0-255 30

6 Factory setting - - 1 Do not change

7 Suspend Cont Fan when starting Heating ON-OFF OFF

8 Factory setting - ON-OFF 0 Do not change

9 Unoccupied Override Time Period Minutes 0-240 60

10 Occupied Cooling Setpoint Degrees 45-99 72

11 Occupied Heating Setpoint Degrees 45-99 68

12 Unoccupied Cooling Setpoint Degrees 45-99 85

13 Unoccupied Heating Setpoint Degrees 45-99 60

14 SAT Control-Cooling ON-OFF ON-OFF ON

15 Cooling SAT Control Setpoint Degrees 40-65 50

16 SAT Control for Heating ON-OFF ON-OFF ON

17 Heating SAT Control Setpoint Degrees 100-180 135

18 Hydronic Heating ON-OFF ON-OFF OFF

19 First Stage Hydronic Heating SAT Setpoint Degrees 80-180 120

20 Second Stage Hydronic Heating SAT Setpoint Degrees 80-180 150

21 Hydronic Heating Reverse Actuated Valve ON-OFF ON-OFF OFF

22 Remote Control ON-OFF ON-OFF OFF

23 VAV Upper Cooling SAT Degrees 40-70 60

24 VAV Lower Cooling SAT Degrees 40-70 55

25 VAV SAT Reset Setpoint Degrees 40-85 72

26 VAV Occupied Setpoing ON-OFF ON-OFF OFF

27 VAV Occupied Heating Degrees 40-85 68

28 VAV Stand Alone Operation ON-OFF ON-OFF ON

29 Morning Warm-Up RAT Degrees 50-85 70

30 Duct Static Setpoint " H2O 0 – 5” 1.5”

31 Building Pressure Setpoint " H2O neg .25 to .25 .1”

32 Economizer ON-OFF ON-OFF ON

33 Economizer First Stage Degrees 40-65 55

34 Economizer Second Stage Degrees 40-65 50

35 Economizer Minimum Position Percent 0 to 100% 20

36 Outside Air Humidity Sensor ON-OFF ON-OFF OFF

37 Economizer Outside Air Enthalpy Setpoint BTUs Per Pound Oct-50 27

38 Return Air Humidity Sensor ON-OFF ON-OFF OFF

39 Economizer OAT Enable Degrees 40-80 55

Page 113: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 113

40 Demand Ventilation ON-OFF ON-OFF OFF

41 IAQ Sensor Range PPM 0-5000 2000

42 Demand Ventilation Setpoint PPM 0-5000 1000

43 Power Exhaust ON-OFF ON-OFF ON

44 Modulating Exhaust ON-OFF ON-OFF OFF

45 Exhaust VFD Installed ON-OFF ON-OFF OFF

46 Exhaust Damper Position for Exhaust Fan to Turn On (Modulating Only) % Of Damper Position 0-100 80%

47 Exhaust Damper Position for Exhaust Fan to Turn Off (Modulating Only) % Of Damper Position 0-100 20%

48Economizer Damper Position for

Exhaust Fan to Turn On (Non-Modu-lating Only)

% Of Damper Position 0-100 60%

49Economizer Damper Position for

Exhaust Fan to Turn Off (Non-Modu-lating Only)

Percent of Economizer Position 0-100% 20%

50 APS Data Open-Closed Open-Closed Open

51 Dirty Filter Switch ON-OFF ON-OFF OFF

52 Dirty Filter Switch Data Open-Closed Open-Closed Open

53 Cooling Mode Enable ON-OFF ON-OFF ON

54 Heating Mode Enable ON-OFF ON-OFF ON

55 Fan On Mode with the Sensor Option ON-OFF ON-OFF ON

56 Space Setpoint Offset Degrees -5 to 5 0 degrees

57 Metric Operation ON-OFF ON-OFF OFF

58 BAS Economizer ON-OFF ON-OFF OFF

59 Year Year 00-99 4

60 Month Month Number 1

61 Day of Month Day Number 1

62 Day of Week Day Number 1

63 Hour Hour 0-23 0

64 Minute Minutes 0-59 0

65 SAT (Supply Air Temp) Degrees -40 to 180 Read Only Read Only

66 RAT (Return Air Temp) Degrees -40 to 180 Read Only Read Only

67 OAT (Outside Air Temp) Degrees -40 to 180 Read Only Read Only

68 ST (Space Temp) Degrees -40 to 180 Read Only Read Only

69 OAH (Outside Air Hum) %RH 0 to 100% Read Only Read Only

70 RAH (Return Air Hum) %RH 0 to 100% Read Only Read Only

71 Occupied Input Enable ON-OFF ON-OFF OFF

72 Alarm Array

These values represent the last 5 alarm codes in memory. 72 is latest & 76 oldest.

Read Only Read Only

73 Alarm Array Read Only Read Only

74 Alarm Array Read Only Read Only

75 Alarm Array Read Only Read Only

76 Alarm Array Read Only Read Only

77 CV/VAV Mode Read Only Flag CV=0 VAV=1 Read Only Read Only

78 Hot Gas Reheat ON-OFF ON-OFF OFF

TABLE 52: SETTABLE SYSTEM PARAMETERS (Continued)ADDRESS FUNCTION UNIT RANGE DEFAULT YOUR SETTINGS

Page 114: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

114 Unitary Products Group

NOTES:For On/Off functions, 1 is ON and 0 is OFFRead only items are readings from sensors which only change as the measured condition changes.

SERVICE

REFRIGERATION SYSTEM

CHARGE: Each system is fully factory charged with R-22.The correct charge appears on the unit nameplate.

Thermal Expansion Valves: The 30 ton unit has 3 and the 40ton unit has 4 independent refrigeration systems. TheseTXVs are set to maintain 15°F superheat leaving the evapo-rator coil. The superheat on each valve is adjustable, how-ever, adjustments should only be made if absolutelynecessary.

MOISTURE/LIQUID SIGHT GLASS: Each system has amoisture/liquid sight glass. These are located on the liquidlines in the condenser section.

A clear flow of liquid indicates the unit is properly charged.Any bubbles indicates the system is undercharged or non-condensables may exist. Corrective action should be taken.

A change in color of the moisture indicator shows the approx-imate moisture content of the system in parts per million. Ifmoisture is indicated, corrective action should be taken.

FILTER DRIER: Each system is equipped with a filter drier.The drier should be replaced whenever moisture is indicatedin the system.

COMPRESSORS

Each compressor is inherently protected from over currentand over temperature. High and low pressure switches areinstalled on the discharge and suction lines respectively forhigh and low pressure protection. Scroll compressors operatein only one direction. If the compressor is experiencing lowamperage draw, similar discharge and suction pressure orincreased noise level, it is operating in reverse. Switch twoline voltage connections to correct (See Compressor Rotationpage 63).

MOTORS

INDOOR BLOWER MOTORS

All indoor blower motors are non-inherently protected threephase motors. Overcurrent protection is provided by a man-ual reset starter/overload relay and short circuit protection isprovided by fuses.

POWER EXHAUST OR RETURN AIR FAN MOTORS

All motors are non-inherently protected three phase motors.Overcurrent protection is provided by a manual resetstarter/overload relay and short circuit protection is providedby fuses.

CONDENSER FAN MOTORS

All condenser fan motors are inherently protected threephase motors. Short circuit protection is provided by fuses.

DRAFT MOTOR (GAS FURNACE)

All draft motors are line voltage, inherently protected, singlephase PSC motors. Short circuit protection is provided byfuses.

79 Hot Gas Bypass ON-OFF ON-OFF OFF

80 Duct Static Reading Inches Water 0 to 5.0” Read Only Read Only

81 Building Pressure Reading Inches Water 0 to 5.0” Read Only Read Only

82 Number Of Compressors Number 1 to 4 Factory Set

83 Number Of Heating Stages Number 1 to 3

TABLE 52: SETTABLE SYSTEM PARAMETERS (Continued)ADDRESS FUNCTION UNIT RANGE DEFAULT YOUR SETTINGS

TABLE 53: SYSTEM MOISTURE INDICATOR

INDICATOR COLOR 75° 100° 125°

Green (Dry) Below 30 Below 45 Below 60

Chartreuse 30 - 90 45 - 130 60 - 180

Yellow (Wet) Above 90 Above 130 Above 180

Page 115: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 115

TABLE 54: STEAM COIL (1 ROW, 25 & 30 TON)1

1. Based on 60°F entering air temperature, 2.00” maxi-mum air pressure drop across the coil.

CFMCapacity (MBH) at Steam Pressure (PSI)

2 6 10 15

6000 194.1 207.9 219.8 232.6

8000 221.1 236.9 250.4 265.0

10000 243.2 260.5 275.4 291.4

12000 261.9 280.6 296.6 313.9

15000 285.6 306.0 323.5 342.4

TABLE 55: STEAM COIL (1 ROW, 40 TON)1

1. Based on 60°F entering air temperature, 2.00” maxi-mum air pressure drop across the coil.

CFMCapacity (MBH) at Steam Pressure (PSI)

2 6 10 15

8000 221.1 236.9 250.4 265.0

11000 252.9 271.0 286.4 303.1

14000 278.2 298.0 315.0 333.4

17000 299.4 320.7 339.0 358.8

20000 317.6 340.2 359.6 380.6

TABLE 56: STATIC RESISTANCE STEAM COIL (25 & 30 TON)

CFM 6000 8000 10000 12000 15000

Air Pressure Drop 0.11 0.18 0.26 0.36 0.54

TABLE 57: STATIC RESISTANCE STEAM COIL (40 TON)

CFM 8000 11000 14000 17000 20000

Air Pressure Drop 0.18 0.31 0.48 0.67 0.88

TABLE 58: HOT WATER COIL (1 ROW 25 & 30 TON)1

1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.

GPM CFM

Capacity (MBH) at Entering Water Temperature

140 °F 160 °F 180 °F 200 °F

10

6000 91.4 115.3 139.3 163.6

8000 102 128.8 155.8 182.9

10000 110.4 139.5 168.8 198.4

12000 117.3 148.4 179.6 211.2

15000 125.9 159.2 192.9 226.9

20

6000 103 129.4 156 182.7

8000 116.8 147 177.2 207.7

10000 128.2 161.3 194.7 228.2

12000 137.8 173.6 209.5 245.6

15000 150 189 228.2 267.8

30

6000 107.6 135 162.5 190.1

8000 122.8 154.3 185.8 217.5

10000 135.5 170.3 205.1 240.2

12000 146.4 184 221.8 259.7

15000 160.3 201.6 243 284.8

40

6000 110.1 138 166 194.1

8000 126.1 158.2 190.5 222.8

10000 139.6 175.2 210.9 246.8

12000 151.2 189.8 228.5 267.5

15000 166.1 208.6 251.3 294.1

Page 116: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

116 Unitary Products Group

TABLE 59: HOT WATER COIL (1 ROW, 40 TON)1

1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.

GPM CFM

Capacity (MBH) at Entering Water Temperature

140 °F 160 °F 180 °F 200 °F

10

8000 102 128.8 155.8 182.9

11000 114 144.1 174.4 205.1

14000 123.2 155.9 188.8 222.1

17000 130.6 165.4 200.4 235.8

20000 136.8 173.3 210.1 247.3

20

8000 116.8 147 177.2 207.7

11000 133.2 167.7 202.3 237.2

14000 146.2 184.2 222.4 260.8

17000 157 197.9 239 280.5

20000 166.2 209.6 253.2 297.3

30

8000 122.8 154.3 185.8 217.5

11000 141.2 177.4 213.8 250.3

14000 155.9 196.1 236.4 276.9

17000 168.3 211.8 255.4 299.3

20000 179.1 225.3 271.8 318.6

40

8000 126.1 158.2 190.5 222.8

11000 145.6 182.7 220 257.5

14000 161.4 202.6 244.1 285.8

17000 174.7 219.5 264.5 309.7

20000 186.3 234.2 282.3 330.6

TABLE 60: WATER PRESSURE DROP (1 ROW, 25 & 30 TON)

GPM 10 20 30 40

Water Pressure

Drop0.9 3.0 6.0 10.0

TABLE 61: WATER PRESSURE DROP (1 ROW, 40 TONS)

GPM 10 20 30 40

Water Pressure

Drop0.9 3.0 6.0 10.0

TABLE 62: HOT WATER COIL (2 ROW, 25 & 30 TON)1

1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.

GPM CFM

Capacity (MBH) at Entering Water Temperature

140 °F 160 °F 180 °F 200 °F

20

6000 177.5 223.8 270.4 317.3

8000 203.8 257.2 311.1 365.5

10000 224.8 284.1 343.9 404.2

12000 242.2 306.4 371.1 436.4

15000 263.6 333.8 404.6 476.1

40

6000 198.1 248.9 300.0 351.3

8000 232.2 292.0 352.2 412.7

10000 260.7 328.1 395.9 464.1

12000 285.0 359.0 433.4 508.3

15000 316.0 398.4 481.3 564.8

60

6000 206.1 258.7 311.4 364.2

8000 243.6 305.9 368.4 431.1

10000 275.3 345.9 416.8 488.0

12000 302.9 380.7 458.9 537.6

15000 338.4 425.7 513.4 601.7

80

6000 210.5 263.9 317.4 371.1

8000 249.8 313.3 377.1 441.1

10000 283.3 355.6 428.2 501.0

12000 312.7 392.7 473.0 553.6

15000 351.0 440.9 531.3 622.1

Page 117: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 117

NOTE: Water pressure drop numbers are based on 60°Fentering air temperature, 2.00” maximum air pres-sure drop across the hot water coil(s). ARI certifiedratings at covering other conditions are availableupon request. Hot water coils are approved for usewith glycol (rates available upon request.

TABLE 63: WATER PRESSURE DROP (2 ROW, 25 & 30 TON)

GPM 20 40 60 80

Water Pressure

Drop0.9 3.0 6.0 10.0

TABLE 64: WATER PRESSURE DROP (2 ROW, 40 TON)

GPM 20 40 60 80

Water Pressure

Drop0.9 3.0 6.0 10.0

TABLE 65: STATIC RESISTANCE HOT WATER COIL (25 & 30 TON)

CFM 6000 8000 10000 15000

Air Pressure Drop 1 Row 0.07 0.11 0.16 0.32

Air Pressure Drop 2 Row 0.14 0.23 0.33 0.65

TABLE 66: STATIC RESISTANCE HOT WATER COIL (40 TON)

CFM 8000 11000 14000 20000

Air Pressure Drop 1 Row 0.11 0.19 0.29 0.52

Air Pressure Drop 2 Row 0.23 0.39 0.58 1.06

Page 118: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

118 Unitary Products Group

FIGURE 36 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPM

8 0 .0

9 0 .0

1 0 0 .0

1 1 0 .0

1 2 0 .0

1 3 0 .0

1 4 0 .0

1 5 0 .0

1 6 0 .0

1 7 0 .0

1 8 0 .0

1 9 0 .0

2 0 0 .0

2 1 0 .0

2 2 0 .0

2 3 0 .0

6 0 0 0 7 0 0 0 8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 ° F1 6 0 ° F1 8 0 ° F2 0 0 ° F

FIGURE 37 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 20 GPM

9 0 .0

1 0 0 .0

1 1 0 .0

1 2 0 .0

1 3 0 .0

1 4 0 .0

1 5 0 .0

1 6 0 .0

1 7 0 .0

1 8 0 .0

1 9 0 .0

2 0 0 .0

2 1 0 .0

2 2 0 .0

2 3 0 .0

2 4 0 .0

2 5 0 .0

2 6 0 .0

2 7 0 .0

6 0 0 0 7 0 0 0 8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 119: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 119

FIGURE 38 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPM

1 0 0 .0

1 1 0 .0

1 2 0 .0

1 3 0 .0

1 4 0 .0

1 5 0 .0

1 6 0 .0

1 7 0 .0

1 8 0 .0

1 9 0 .0

2 0 0 .0

2 1 0 .0

2 2 0 .0

2 3 0 .0

2 4 0 .0

2 5 0 .0

2 6 0 .0

2 7 0 .0

2 8 0 .0

2 9 0 .0

6 0 0 0 7 0 0 0 8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 ° F1 6 0 ° F1 8 0 ° F2 0 0 ° F

FIGURE 39 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 40 GPM

180.0

200.0

220.0

240.0

260.0

280.0

300.0

320.0

340.0

360.0

380.0

400.0

420.0

440.0

460.0

480.0

500.0

520.0

540.0

560.0

580.0

6000 7000 8000 9000 10000 11000 12000 13000 14000 15000

F L O W R AT E (C F M )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

Page 120: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

120 Unitary Products Group

FIGURE 40 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPM

190 .0

210 .0

230 .0

250 .0

270 .0

290 .0

310 .0

330 .0

350 .0

370 .0

390 .0

410 .0

430 .0

450 .0

470 .0

490 .0

510 .0

530 .0

550 .0

570 .0

590 .0

610 .0

60 00 7000 8 000 9000 1 0000 110 00 1200 0 130 00 1400 0 15 000

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

FIGURE 41 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 80 GPM

2 0 0 .0

2 2 0 .0

2 4 0 .0

2 6 0 .0

2 8 0 .0

3 0 0 .0

3 2 0 .0

3 4 0 .0

3 6 0 .0

3 8 0 .0

4 0 0 .0

4 2 0 .0

4 4 0 .0

4 6 0 .0

4 8 0 .0

5 0 0 .0

5 2 0 .0

5 4 0 .0

5 6 0 .0

5 8 0 .0

6 0 0 .0

6 2 0 .0

6 4 0 .0

6 0 0 0 7 0 0 0 8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 121: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 121

FIGURE 42 - HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM

90 .0

100 .0

110 .0

120 .0

130 .0

140 .0

150 .0

160 .0

170 .0

180 .0

190 .0

200 .0

210 .0

220 .0

230 .0

240 .0

250 .0

8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000

F L O W R AT E (C F M )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

FIGURE 43 - HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM

1 0 0 .0

1 1 0 .0

1 2 0 .0

1 3 0 .0

1 4 0 .0

1 5 0 .0

1 6 0 .0

1 7 0 .0

1 8 0 .0

1 9 0 .0

2 0 0 .0

2 1 0 .0

2 2 0 .0

2 3 0 .0

2 4 0 .0

2 5 0 .0

2 6 0 .0

2 7 0 .0

2 8 0 .0

2 9 0 .0

3 0 0 .0

8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0 1 6 0 0 0 1 7 0 0 0 1 8 0 0 0 1 9 0 0 0 2 0 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 122: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

122 Unitary Products Group

FIGURE 44 - HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM

110.0

120.0

130.0

140.0

150.0

160.0

170.0

180.0

190.0

200.0

210.0

220.0

230.0

240.0

250.0

260.0

270.0

280.0

290.0

300.0

310.0

320.0

8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000

FLOW RATE (CFM )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

FIGURE 45 - HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM

1 2 0 .0

1 3 0 .0

1 4 0 .0

1 5 0 .0

1 6 0 .0

1 7 0 .0

1 8 0 .0

1 9 0 .0

2 0 0 .0

2 1 0 .0

2 2 0 .0

2 3 0 .0

2 4 0 .0

2 5 0 .0

2 6 0 .0

2 7 0 .0

2 8 0 .0

2 9 0 .0

3 0 0 .0

3 1 0 .0

3 2 0 .0

3 3 0 .0

3 4 0 .0

8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0 1 6 0 0 0 1 7 0 0 0 1 8 0 0 0 1 9 0 0 0 2 0 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 123: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 123

FIGURE 46 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM

FIGURE 47 - HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM

190.0

210.0

230.0

250.0

270.0

290.0

310.0

330.0

350.0

370.0

390.0

410.0

430.0

450.0

470.0

490.0

510.0

530.0

8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000

F LO W R AT E (C FM )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

2 1 0 .0

2 3 0 .0

2 5 0 .0

2 7 0 .0

2 9 0 .0

3 1 0 .0

3 3 0 .0

3 5 0 .0

3 7 0 .0

3 9 0 .0

4 1 0 .0

4 3 0 .0

4 5 0 .0

4 7 0 .0

4 9 0 .0

5 1 0 .0

5 3 0 .0

5 5 0 .0

5 7 0 .0

5 9 0 .0

6 1 0 .0

6 3 0 .0

6 5 0 .0

8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0 1 6 0 0 0 1 7 0 0 0 1 8 0 0 0 1 9 0 0 0 2 0 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 124: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

124 Unitary Products Group

FIGURE 48 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM

220.0240.0260.0280.0300.0320.0340.0

360.0380.0400.0420.0440.0460.0480.0500.0520.0540.0560.0580.0600.0620.0640.0660.0680.0700.0

8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000

FLOW RATE (CFM )

CA

PAC

ITY

(MB

H)

140 °F160 °F180 °F200 °F

FIGURE 49 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM

2 3 0 .02 5 0 .02 7 0 .02 9 0 .03 1 0 .03 3 0 .03 5 0 .03 7 0 .03 9 0 .04 1 0 .04 3 0 .04 5 0 .04 7 0 .04 9 0 .05 1 0 .05 3 0 .05 5 0 .05 7 0 .05 9 0 .06 1 0 .06 3 0 .06 5 0 .06 7 0 .06 9 0 .07 1 0 .07 3 0 .0

8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0 1 6 0 0 0 1 7 0 0 0 1 8 0 0 0 1 9 0 0 0 2 0 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

1 4 0 °F1 6 0 °F1 8 0 °F2 0 0 °F

Page 125: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 125

FIGURE 50 - STEAM COIL - 25 & 30 TON (1 ROW)

1 8 0

1 9 0

2 0 0

2 1 0

2 2 0

2 3 0

2 4 0

2 5 0

2 6 0

2 7 0

2 8 0

2 9 0

3 0 0

3 1 0

3 2 0

3 3 0

3 4 0

3 5 0

6 0 0 0 7 0 0 0 8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

2 p s i6 p s i1 0 p s i1 5 p s i

FIGURE 51 - STEAM COIL - 40 TON (1 ROW)

2 1 0

2 2 0

2 3 0

2 4 0

2 5 0

2 6 0

2 7 0

2 8 0

2 9 0

3 0 0

3 1 0

3 2 0

3 3 0

3 4 0

3 5 0

3 6 0

3 7 0

3 8 0

3 9 0

8 0 0 0 9 0 0 0 1 0 0 0 0 1 1 0 0 0 1 2 0 0 0 1 3 0 0 0 1 4 0 0 0 1 5 0 0 0 1 6 0 0 0 1 7 0 0 0 1 8 0 0 0 1 9 0 0 0 2 0 0 0 0

F L O W R A T E (C F M )

CA

PAC

ITY

(MB

H)

2 p s i6 p s i1 0 p s i1 5 p s i

Page 126: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

126 Unitary Products Group

FIGURE 52 - TYPICAL CONTROL WIRING

Page 127: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 127

FIGURE 53 - LEGEND

Page 128: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

128 Unitary Products Group

FIGURE 54 - TYPICAL 25 TON POWER WIRING

Page 129: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 129

FIGURE 55 - TYPICAL 30/40 TON POWER WIRING

Page 130: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

130 Unitary Products Group

FIGURE 56 - TYPICAL GAS HEAT WIRING

Page 131: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 131

GAS FURNACE SAFETY FEATURES

COMBUSTION AIR PROVING

Combustion air proving is provided by a pressure switch. Asthe motor approaches full speed, this switch closes beforeany other circuit or gas component can be energized.

ROLLOUT

Rollout protection is provided by a switch mounted on theheat shield of each furnace module. The switch senses anyflame or excessive heat in the burner compartment. Whenthe switch opens, the furnace module is immediately lockedout until there is a break in power to the specific furnace mod-ule and the manual itch is reset. Note that only the modulewith the open rollout switch will be locked out, the remainingmodules will continue to operate although all should beinspected.

A trip of the rollout switch likely indicates a flue restriction, anopening in the flue passageway, defective pressure switch ora loose combustion blower wheel. Corrective action shouldbe taken accordingly.

MAINTENANCE

NORMAL MAINTENANCE

Periodic maintenance normally consists of changing or clean-ing filters and (under some conditions) cleaning the mainburners.

FILTERS

Inspect once a month. Replace disposable or clean perma-nent type as necessary. The dimensional size of the replace-ment filter must be the same as the replaced filter (Refer toTable 11).

MOTORS

Outdoor fan motors are permanently lubricated and requireno maintenance. Lubrication, if desired, is to be performed bya qualified service agency.

Ventor motors are factory lubricated for an estimated 10-yearlife.

Indoor Fan Motors - The indoor blower motor features ball-bearings that do not require periodic lubrication. Periodiclubrication of the motor bearings can extend the life but isoptional.

To go to bypass mode, the bypass VFD as installed in thisunit must be switched by hand on the front of the bypassenclosure in the fan cabinet of the rooftop unit. It does notautomatically go to bypass mode if the drive fails.

The switches on the front of the bypass box control its runmode. For normal running:

• The ON/OFF rotary power switch must be in the ON position.

• The BYPASS/OFF/DRIVE switch S1 should be in the DRIVE position.

• The HAND/STOP/AUTO switch S2 should be in the AUTO position, so that the unit control will properly run the fan and control the speed.

• The TEST/NORMAL switch S3 should be in the NOR-MAL position.

If the drive fails:

• Switch the BYPASS/OFF/DRIVE switch to BYPASS. If there is a call for the fan, it will go to full speed.

• If there are VAV boxes, connect them to the circuit at TB1/6 and they will be driven open in bypass mode.

Prior to any of the following maintenance proce-dures, shut off all power to the unit. Failure to doso could cause personal injury.

Label all wires prior to disconnection when servic-ing controls. Wiring errors can cause improper anddangerous operation. Verify proper operation afterservicing.

Damage can occur if the bearings are over lubri-cated. Use grease sparingly.

Perform all maintenance operations on the blowermotor with power disconnected from the unit. Donot attempt to lubricate bearings with the unit inoperation.

Page 132: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

132 Unitary Products Group

On an annual basis, check the motor for accumulations ofdust, etc. That may block the cooling slots in the motor shell.Check for loose, damaged or misaligned drive components.Check that all mounting bolts are tight. Replace defectiveparts as required.

If desired, every three years remove both pipe plugs at eachend shell and clean out any hardened grease or foreign mat-ter. Replace one plug on each end with a clean grease fitting.Using a low pressure grease gun, pump grease (ChevronSRI-2 or equivalent) into the bearing cavity until new greaseshows at the open port. Do not over-lubricate. Run the motorfor ten minutes until excess grease is purged from the cavity.Replace the plugs.

FAN DRIVES

Units are supplied with fan shaft bearings that do not requiremaintenance but may be relubricated per Table 67.

Lubricate with a premium quality NLGI 2 grade multi-purposeroller bearing grease having corrosion inhibitors, anti-oxidantadditives and mechanical stability for high speed operation.The grease should also have a minimum base oil viscosity of500 SUS at 100°F. Do not use a heavy, long fibered grease.

The presents of dirt, moisture or chemical fumes around thebearings requires more frequent lubrication.

Fill bearings with lubricant prior to extended shutdown or stor-age. Rotate the shaft monthly during idle periods.

Avoid excessive grease purging from seals during lubrication,this reduces the life of the bearing.

OUTDOOR COIL

Dirt should not be allowed to accumulate on the outdoor coilsurface or other parts in the air circuit. Cleaning should be asoften as necessary to keep coil clean. Use a brush, vacuumcleaner attachment, or other suitable means. If water is used

to clean coil, be sure power to the unit is shut off prior tocleaning.

NOTE: Exercise care when cleaning the coil so that the coilfins are not damaged.

Do not permit the hot condenser air discharge to beobstructed by overhanging structures or shrubs.

GAS BURNER

Periodically (at least annually at the beginning of each heat-ing season) make a visual check of the main burner flame. Ifnecessary, adjust main burner primary air shutters to give adistinct, sharp blue flame as explained under BURNERINSTRUCTIONS.

TO CLEAN BURNERS

Remove them from the furnace as explained in BURNERINSTRUCTIONS. Clean burners with hot water applied alongtop of the burner.

COMBUSTION AIR DISCHARGE

Visually inspect discharge outlet periodically to make surethat the buildup of soot and dirt is not excessive. If necessary,clean to maintain adequate combustion air discharge.

CLEANING FLUE PASSAGES AND HEATING ELEMENTS

With proper combustion adjustment, the heating element of agas fired furnace will seldom need cleaning. If the elementshould become sooted, it can be cleaned as follows:

1. Remove the burner assembly as outlined in BURNER INSTRUCTIONS.

2. Remove the screws holding the top of the flue collector box. Carefully remove the top of the flue collector box. The draft wheel, housing, and draft motor can remain assembled to the flue box top, if cleaning of these com-ponents is not required.

3. This will provide access to flue baffles, then remove the flue baffles from the tube interiors. To remove, the flue baffles, remove the stainless steel screws from the vest panel. Refer to Figure 57.

4. Using a wire brush on a flexible wand, brush out the inside of each heat exchanger from the burner inlet and flue outlet ends.

5. Brush out the inside of the flue collector box, and the flue baffles.

6. Run the wire brush down the vent hoods from the flue collector end.

7. If soot build-up is particularly bad, remove the vent motor and clean the wheels and housings. Run the wire brush

TABLE 67: INDOOR BLOWER BEARING LUBRICATION SCHEDULE

Shaft Size (Inches)

Operating Speed (RPM)

500 1000 1500 2000

Relubrication Cycle (Months)

1-1/16 - 1-7/16 6 6 6 6

1-1/2 - 1-3/4 6 6 6 4

1-7/8 - 2-3/16 6 6 4 4

2 -1/4 - 3 6 4 4 2

Page 133: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 133

down the flue extension at the outlet of the vent hous-ings.

8. After brushing is complete, blow all brushed areas with air or nitrogen. Vacuum as needed.

9. Replace parts in the order they were moved in steps 1 to 4.

10. Assure that all seams on the vent side of the combustion systems are air tight. Apply a high temperature (+500°F) sealing compound where needed (Dow Corning, Silastic 736, Loctite Superflex 596 or equivalent).

The restrictor plate must also be sealed to furnace tube sheet.

SECURE OWNERS APPROVAL

When the system is functioning properly, secure the owner’sapproval. Show him the location of all disconnect switchesand the room temperature sensors. Teach him how to startand stop the unit and how to adjust the temperature settingswithin the limitations of the system.

FIGURE 57 - TYPICAL FLUE BAFFLE

��� ���

����������

���������

�������������������������������������� ������������� ��� ��� ������! ��������������"�� ������ ������ �� ������� ������� ��� �������� ��������#

$�%�&��'$�(�

��'�)� ���!���

Page 134: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

134 Unitary Products Group

FIGURE 58 - 25 TON CHARGING CURVE

���

���

���

���

���

���

���

���

���

���

���

��

��

��

��

��

��

�� ��������� ����� ���

����

���

����

���

��������� ����� ���

������������������

Page 135: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 135

FIGURE 59 - 30 TON CHARGING CURVE

����

��

��

� �

���

��

��

����

��

����

��

�����

�����

��

��

��

���

��

��

��

����

��

����

����

����

���

���

���

���

���

���

���

���

���

���

���

���

� ������������������ ��

Page 136: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

136 Unitary Products Group

FIGURE 60 - 40 TON CHARGING CURVE

����

��

��

� �

���

���

����

��

����

��

�����

�����

��

��

��

���

��

��

��

����

��

����

����

����

���

���

���

���

���

���

���

� ������������������ ��

Page 137: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 137

FIGURE 61 - PRESSURE DROP DRY EVAPORATOR COIL VS SUPPLY AIR CFM - 25 TON

2

3

4

5

6

7

8

9

10

11

12

13

14

0.050 0.1 0.15 0.2 0.25 0.3 0.35

25TONS3ROWS

������������ ������

����� �� ���� ��� ����

����� �� ���� ������ � ��� ���������� ����

�� � ���� ��� ��

Page 138: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

138 Unitary Products Group

FIGURE 62 - PRESSURE DROP DRY EVAPORATOR COIL VS SUPPLY AIR CFM - 30 & 40 TON

Page 139: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

102777-YIM-B-0105

Unitary Products Group 139

Page 140: INSTALLATION MILLENNIUM™ ROOFTOP MANUAL · 102777-yim-b-0105 4 unitary products group interacting through the millennium simplicity. . . . . . . . . . . . . . . . . . . . . . .

Subject to change without notice. Printed in U.S.A. 102777-YIM-B-0105Copyright © by Unitary Products Group 2005. All rights reserved. Supersedes: 102777-YIM-A-0704/035-16682-001-A-0704

Unitary 5005 NormanProducts York OKGroup Drive 73069


Recommended