+ All Categories
Home > Documents > IVEN - Unical AG€¦ · AND DIMENSIONS..... pag. 5 1.1 Technical features ... pag. 5 1.2...

IVEN - Unical AG€¦ · AND DIMENSIONS..... pag. 5 1.1 Technical features ... pag. 5 1.2...

Date post: 23-Oct-2020
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
36
00331967 - 1 a edition - 02/2004 IVEN 04 UK RTN 24 - RTFS 24 - RTFS 28 CTN 24 F - CTFS 24 F - CTFS 28 F INSTALLATION USE AND MAINTENANCE
Transcript
  • 00331967 - 1a edition - 02/2004

    IVEN 04

    UK

    RTN 24 - RTFS 24 - RTFS 28

    CTN 24 F - CTFS 24 F - CTFS 28 F

    INSTALLATION USE

    AND MAINTENANCE

  • 2

    General infoIMPORTANT

    This INSTRUCTION MANUAL, which is an integral and indispensable part of the product, must be handed over to the user by the plumbers andmust be kept in a safe place for future reference. The manual must be handed over with the boiler should it be sold or transferred.

    This boiler must be used for the purposes for which it has been designed. Any other use shall be considered incorrect and thereforedangerous.

    The boiler must be installed in compliance with applicable laws and standards and according to the manufacturer’s instructions given in thismanual. Incorrect installation may cause injury to persons and/or animals and damage to property. The manufacturer shall not be held liable for anysuch injury and/or damage.

    Damage and/or injury caused by incorrect installation or use and/or damage and/or injury due to non-observance of the manufacturer’s instructionsshall relieve UNICAL from any and all contractual and extracontractual liability.

    Before installing the boiler, check that the technical data corresponds to requirements for its correct use in the system.

    Check that the boiler is intact and that it has not been damaged during transport and handling. Do not install equipment which is patently damagedand/or faulty.

    Do not obstruct the air suction and/or heat dissipation grates.

    Only original accessories must be used for all boilers supplied with optionals or kits (including electrical ones).

    Dispose of the packaging with care as all the materials can be recycled. The packaging must therefore be sent to specific waste managementsites.

    Keep the packaging out of the reach of children as it may represent a choking and suffocation hazard.

    In the event of failure and/or faulty functioning, switch off the boiler. Do not attempt to make repairs: contact qualified technicians.

    Original parts must be used for all repairs to the boiler.

    Non-observance of the above requirement may jeopardize the safety of the boilers and expose people, animals and property to danger.

    To guarantee efficiency and correct functioning of the equipment it is legally binding to service the boilers once a year according to theschedule indicated in the relative section of this manual.

    In the event of long periods of inactivity of the boiler, disconnect it from the power mains and close the gas tap (Warning! In this case the boiler’selectronic anti-freeze function will not be operative).

    Should there be a risk of freezing, add anti-freeze: it is not advisable to empty the system as this may result in damage; use specific anti-freezeproducts suitable for multi-metal heating systems.

    N.B.For boilers which use gaseous fuel, if you smell gas:- do not turn on or off electrical switches and do not turn on electrical appliances;- do not ignite flames and do not smoke;- close the main gas tap;- open doors and windows;- contact a Service Centre, qualified installer or the gas supply company.

    Never use flames to detect gas leaks.

    WARNING

    This boiler has been built for installation in the country indicated on the technical data plate: installation in any other country may be a sourceof danger for people, animals and property.

    Read the warranty conditions and clauses on the warranty certificate attached to the boiler with care.

    ‘’WATER TREATMENT IN C.H. SYSTEM FOR CIVIL USE’’NOTE FOR INSTALLER AND USER

    1) The frequency of the cleaning of the D.H.W. heat exchanger is related to the hardness of the feeding water.

    2) With a water hardness higher than 28°f (16°d) the use of antiscaling devices, whose choice will be made on the base of water characteristics, issuggested.

    3) To increase the resistance to the scaling, a D.H.W. temperature adjustment very close to that one of the actual use, is suggested.

    4) The adoption of a modulating room thermostat reduces the scaling danger.

    5) We advise you to verify the state of cleaness of the D.H.W. heat exchanger at the end of the first year and subsequently every two years.

  • 3

    General info

    DATA PLATE

    ®

    2H

    2E

    3+

    3B/P

    3P

    G20

    G20

    G30/G31

    G30 - 31

    G31

    20 - 25

    20

    28-30/37

    30 - 50

    37 - 50

    mbar

    mbar

    mbar

    mbar

    mbar

    IT ES IEPT GRTR HRCZ SKHUSIGBCN RU ROLV EE LT

    II 2H3+II 2H3+II 2H3B/PII 2H3PII 2HS 3B/PII 2E3PII 2H3P I 2H I 2H

    20 ; 28-30/37 mbar20 ; 28-30/37 mbar20 ; 50 mbar18 ; 50 mbar25 ; 30 mbar20 ; 50 mbar20 ; 37 mbar20 mbar20 mbar

    /

    1

    2

    3 4 5

    6 7 8

    9

    12

    15

    17

    19

    20

    18

    16

    10

    13

    11

    14

    21

    1 = P.I.N. code

    2 = Boiler type (only for condensing boiler)

    3 = (S.N°) Serial Nr.

    4 = Manufacture Date

    5 = Model

    6 = Appliance type

    7 = Elettrical supply

    8 = Maximum absorbed power - Insulation

    protection

    9 = (Pn) Nominal Output

    10 = (Pcond) Condensing Nominal Output

    (only for condensing boiler)

    11 = (D) Specific flow rate EN 625

    12 = (Qn) Nominal heat input

    13 = (Qnw) Nominal heat input for D.H.W.

    system if there are different out puts

    between the C.H. and D.H.W. circuits

    14 = (NOx) NOx Class

    15 = (PMS) Max pressure C.H. system

    16 = (T max) Max Temperature C.H. system

    17 = (PMW) Max pressure D.H.W. system

    18 = (T max) Temperature D.H.W. system

    19 = Adjusted for gas type X

    20 = Country of destination, Gas category,

    Supply pressure

    21 = EN standards applicable to the boiler

    type

    GAS VALVE LABEL

    ��������

    TranslationWhile connecting gas inlet pipe of the boiler to the

    pipe coming from gas network, it is MANDATORY to

    insert a TIGHT GASKET, whose dimensions and material

    must be adequate. Connection is NOT suitable for

    hemp, teflon strip or similar materials

  • 4

    General info

    1

    2

    3

    For your own safety, observe these safety instructions.:

    PLEASE NOTE:User tip for the optimum utilisationand setting of the control(s) plususeful information.

    WARNING

    from risk of electric shock.

    WARNING

    Identifies potentially dangerous

    situations.

    TECHNICAL FEATURESAND DIMENSIONS .......................................................... pag. 51.1 Technical features ................................................................... pag. 5

    1.2 Dimensions .............................................................................. pag. 5

    1.3 Hydraulic circuits ..................................................................... pag. 6

    1.4 Technical data ......................................................................... pag. 8

    1.5 Main characteristics ................................................................ pag. 8

    DIRECTIONS FORINSTALLERS ......................................................................... pag. 92.1 Installations rules .................................................................... pag. 9

    2.2 Installation ............................................................................... pag. 9

    2.2.1 Packing ....................................................................... pag. 9

    2.2.2 Positioning the boiler .................................................. pag. 10

    2.2.3 Assembling the boiler ................................................. pag. 11

    2.2.4 Ventilation ................................................................... pag. 11

    2.2.5 Flue gas discharge system ........................................ pag. 11

    2.2.6 Discharge and suction pipe configuration .................. pag. 13

    2.2.7 Positioning of terminals for type C boilers .................. pag. 14

    2.2.8 Smoke evacuation Ø80 air suction flange .................. pag. 15

    2.2.9 Discharge of flue gas into coaxial ducts with a

    diameter of 100/60 mm (Type A accessories) ........... pag. 16

    2.2.10 Flue gas discharge and air suction with separate

    pipes with 80 mm diameter ........................................ pag. 17

    2.2.11 Measurements of combustion efficiency ................... pag. 16

    2.2.12 Connection to the gas mains ...................................... pag. 20

    2.2.13 Hydraulic connection .................................................. pag. 20

    2.2.14 Arrangement for a D.H.W. tank................................... pag. 22

    2.2.15 Electrical connection .................................................. pag. 23

    2.3 Wiring diagram ......................................................................... pag. 24

    2.3.1 Pratical connection diagram ....................................... pag. 24

    2.3.2 Jumper location .......................................................... pag. 25

    2.4 Filling the system .................................................................... pag. 25

    2.5 Starting the boiler .................................................................... pag. 25

    2.6 Adjusting the burner ................................................................ pag. 26

    2.7 Modification of other gases ..................................................... pag. 27

    2.8 Adjustement of the output to ch system's needs ................... pag. 29

    2.9 Finding chart and corrective actions ...................................... pag. 29

    2.10 Failure code ............................................................................. pag. 31

    USERS' INSTRUCTION ............................................... pag. 323.1 Control panel ........................................................................... pag. 32

    3.2 Switching on/off ....................................................................... pag. 33

    3.3 Antifrost protection .................................................................. pag. 34

    3.4 Important suggestion and notes ............................................. pag. 34

  • 5

    Installation info

    1 TECHNICAL FEATURES AND DIMENSIONS

    fig. 1

    1.2 - DIMENSION

    A

    ��� ���

    ���

    1.1 - TECHNICAL FEATURES

    IVEN 04 is a wall hung gas boiler with built-in

    atmospheric gas burner; it is available in the

    following versions:

    24 with 24 kW output;

    28 with 28 kW output;

    C with instantaneous D.H.W. production;

    R- for heating only;

    TN with natural draught open chamber;

    TFS with forced draught room sealed com

    bustion chamber;

    All versions have electronic ignition.

    Models in the IVEN 04 series are the following:

    IVEN 04 CTN 24 F open boiler, with electronic

    ignition and instantaneous D.H.W. production;

    IVEN 04 RTN 24 F open boiler, with electronic

    ignition, for heating only;

    IVEN 04 CTFS 24 F forced draught room sea-

    led boiler, with electronic ignition and instan-

    taneous D.H.W. production;

    IVEN 04 RTFS 24 F forced draught room sea-

    led boiler, with electronic ignition for heating

    only;

    IVEN 04 CTFS 28 F forced draught room sea-

    led boiler with electronic ignition and instanta-

    neous D.H.W production;

    IVEN 04 RTFS 28 F forced draught room sea-

    led boiler with electronic ignition for heating

    only;

    IVEN 04 is supplied with all control and sa-

    fety features according to the latest laws in

    force.

    The main technical features of the IVEN 04

    boilers are summarised below.

    • Bithermal, copper, high performance heat

    exchanger;

    • Electronic ignition;

    • Electronic flame modulation;

    • Minimum output control;

    • Electronic control of ignition ramp;

    • Anti-freeze function;

    • Pump anti-jamming function;

    • Pump over run function;

    • High limit thermostat (95°C);

    • Three-speed circulating pump;

    • Expansion vessel;

    • Automatic air vent;

    • C.H. system water filling valve except Fren-

    ch, Belgium and England version) ;

    • Safety pressure switch for low water level;

    • Priority flow switch for D.H.W.;

    • Tap water flow rate restrictor set at 10 li-

    tres/min, for 24 kW boilers (brown) and 12

    l/min, for 28 kW boilers (pink)

    Note: This 10 (12) l/min flow rate

    is guaranteed with a upstream

    pressure of 2 bar. If the upstream

    pressure is much higher than 2

    bar, then it is possible to reduce the flow

    rate to 10 (12) l/min by rotating clock-wise

    the screw ‘’A’’. On the contrary, if the up-

    stream pressure is lower than 2 bar it is

    possible to reach the flow rate of 10 (12) l/

    min by rotating counter clock-wise the

    screw ‘’A’’. If, also in this case the flow

    rate of 10 (12) l/min is not reacheable then

    the flow restrictor can be removed from its

    seat.

    • Control panel with IP 44 insulation protec-

    tion

    • Temperature and pressure gauge;

    • Warning light for: presence of power, re-

    quest for heating, burner in operation, lock

    out;

    • ON-OFF switch;

    • D.H.W. temperature selector (35/57°C) forIVEN 04 CTN 24 F-CTFS 24 F-CTFS 28 F+ antifrost position;

    (25/57°C) for IVEN 04 RTN 24 - RTFS 24 -

    set off only if arranged with storarage tank

    • C.H. temperature selector (45/78°C) + sum-

    mer/winter position.

    • Reset button;

    • Chimney sweeper button

    • Mounting jig

    • Mounting frame with valves (opt.)

    • Flue gas antispillage thermostat 75°C(IVEN 04 TN)

  • 6

    Installation info

    1.3 - HYDRAULIC CIRCUIT

    fig. 3

    IVEN 04 CTN 24 F

    IVEN 04 CTFS 24 F - IVEN 04 CTFS 28 F

    fig. 2

    12 13

    5

    6

    89

    10

    14

    15

    17

    4

    7

    19

    18

    20

    3

    1

    2

    21

    9

    11

    16

    ���� �

    ���� �

    3

    19

    4

    7

    6

    8

    9

    13

    14

    15

    18

    16

    17

    5

    20

    2223

    12

    11

    21

    24

    8

    1

    2

    10

    1 Heating circuit safety valve2 Minimum water pressure switch3 Filling valve (except French, Belgium

    and England version)4 D.H.W. temperature sensor5 Gas valve6 Expansion vessel7 Burner nozzles8 Expansion vessel filling valve9 Ignition electrode10 Bithermal heat exchanger11 H.L. thermostat12 Flue gas manifold/down-draught

    dverter13 Flue gas anti-spillage thermostat14 Ionisation electrode15 C.H. temperature sensor16 Automatic air vent17 Circulating pump18 D.H.W. flow restrictor 10-12 l/min19 Flow switch20 Cold water filter21 By-pass

    M C.H. system flowC D.H.W. outletG Gas inletF D.C.W. inletR C.H. system return

    1 Heating circuit safety valve

    2 Minimum water pressure switch

    3 D.H.W. temperature sensor

    4 Expansion vessel

    5 Gas valve

    6 Burner nozzles

    7 Expansion vessel filling valve

    8 Ignition electrode

    9 Bithermal heat exchanger

    10 H.L. thermostat

    11 Room sealed combustion chamber

    12 Flue gas extractor fan

    13 Air/flue coaxial duct

    14 Micro-switch on flue gas pressure

    switch

    15 Flue gas pressure switch

    16 Ionisation electrode

    17 Heating temperature sensor

    18 Automatic air vent

    19 Circulating pump

    20 Filling valve (except French, Belgium

    and England version)

    21 D.H.W. flow restrictor 10-12 l/min

    22 D.H.W. Flow switch

    23 Cold water filter

    24 By-pass

    M C.H. system flow

    C D.H.W. outlet

    G Gas inlet

    F D.C.W. inlet

    R C.H. system return

  • 7

    General info

    ���

    ���

    fig. 5

    IVEN 04 RTFS 24 - IVEN 04 RTFS 28

    fig. 4

    183

    6

    5

    7

    8

    11

    1213

    14

    15

    16

    4

    19

    10

    9

    9 10

    4

    3

    6

    7

    8 11

    12

    13

    14

    15

    16

    5

    17

    20

    11

    15

    1

    2

    1

    2

    17

    IVEN 04 RTN 241 Heating circuit safety valve2 Minimum water pressure switch3 Expansion vessel4 Gas valve5 Burner nozzles6 Expansion vessel filling valve7 Ionisation electrode8 Heat exchanger9 Flue gas manifold/down-draught

    diverter10 Flue gas anti-spillage thermostat11 Ignition electrode12 H.L. thermostat13 C.H. temperature sensor14 Automatic air vent15 Circulating pump16 Filling valve (except French,

    Belgium and England version)17 By-pass

    M C.H. system flowG Gas inletR C.H. system return

    1 Heating circuit safety valve2 Low water level pressure switch

    3 Expansion vessel

    4 Gas valve

    5 Burner nozzles6 Expansion vessel filling valve7 Ionisation electrode

    8 Heat exchanger

    9 Room sealed combustion chamber

    10 Flue gas extractor fan

    11 Air/flue coaxial duct

    12 Micro-switch on flue gas pressure

    switch

    13 Flue gas pressure switch

    14 H.L. thermostat

    15 Ignition electrode

    16 Heating temperature sensor

    17 Automatic air vent

    18 Circulating pump19 Filling valve (except French,

    Belgium and England version)20 By-pass

    M C.H. system flowG Gas inletR C.H. system return

  • 8

    General info

    Warning:If the boilers are used in low tem-

    perature heating system (ex. floor hea-

    ting)

    it is necessary to use a mixing valve to

    avoid condensation phenomena.

    l/min

    bar

    bar

    l

    °C

    °C

    l

    bar

    l

    l

    bar

    bar

    l/min.

    l/min.

    l/min.

    l/min.

    l/min.

    l/min.

    l/min.

    °C

    V-Hz

    A (F)

    W

    IP

    kg

    kW

    kW

    %

    %

    %

    %

    n.

    %

    %

    %

    °C

    g/s

    %

    %

    mg/kWh

    %

    %

    RTN 2423,8810,0790,1189,7688,5387,3292,690,22,6 - 2,591,818-20113,82,4-5,319729,8 - 7,40,486

    RTFS 2423,949,9590,3489,7688,6087,14293,387,91,88-2,96112,513,64-14,3867,73,0-7,4157212,1-6,70,295

    CTN 24 F23,8810,0790,1189,7688,5387,3292,690,22,6 - 2,591,818-20113,82,4-5,319729,8 - 7,40,486

    CTFS 24 F23,949,9590,3489,7688,6087,14293,387,91,88-2,96112,513,64-14,3867,73,0-7,4157212,1-6,70,295

    RTFS 2827,459,8090,0189,8887,4387,32293,286,81,76-3,1987,717,5-17,660,862,65-7,9163213,2-6,80,256

    RTN 24 II2H3+7,20,533,5814581183,9----------

    230/50470X4D37

    CTN 24 F II2H3+7,20,533,5814581183,92,50,5611,5107,68,69,7811,413,6935 - 57230/50470X4D37

    CTFS 24 F II2H3+7,370,533,5814581183,92,50,5611,5107,68,589,8011,4413,7335 - 57230/504130X4D37

    RTFS 24 II2H3+7,370,533,5814581183,9-----------230/504130X4D37

    RTFS 28 II2H3+7,020,533,5814581183,9-----------230/504130X4D37

    IVEN 04

    CTFS 28 F II2H3+7,020,533,5814581183,92,50,5612,5128,749,8411,2413,1115,74 35 - 57230/504130X4D37

    CTFS 28 F27,459,8090,0189,8887,4387,32293,286,81,76-3,1987,717,5-17,660,862,65-7,9163213,2-6,80,256

    1.4 - OPERATING DATA

    Nominal output

    Minimum output

    Actual water efficiency at full load (100%)

    Min. required water efficiency at full load (100%)

    Actual water efficiency at part load (30%)

    Min. required water efficiency at part load (30%)

    Stars No. off (According EEC Directive 92/42)

    Combustion efficiency at nominal load (100%)

    Combustion efficiency at part load (30%)

    Stand-by losses (min.-max.)

    (*)Flue gas temperature (min. - max.)

    Flue gas mass flow rate (min. - max)

    Excess of air l

    CO2

    NOX (value according EN 297/A3 + EN 483)

    NOX class

    Flue losses with burner in operation (min.-max)

    Flue losses with burner off

    For the following data: Nozzle - Burner pressure - Diaphragm (where applicable) - Inputs - Gas consumptions refer to pagraph SUITABILITY TO USEOTHER GASES.

    Appliance category

    Min. water flow rate in CH circuit (Dt 20 K)

    Min. pressure in CH circuit

    Max. pressure in CH circuit

    Water content primary circuit

    Max. oper. temperature in CH mode

    Min. oper. temperature in CH mode

    Total capacity of expansion vessel

    C.H. expansion vessel pre-loading

    Max. water content CH circuit (calc. x max. T°of 82°C)

    Min. water flow rate in D.H.W. circuit

    Min. DHW. pressure

    Max. DHW. pressure

    DHW specific flow rate (Dt 30 K)

    Flow restrictor

    DHW production in continuous operation with Dt 45 K

    DHW production in continuous operation with Dt 40 K

    DHW production in continuous operation with Dt 35 K

    DHW production in continuous operation with Dt 30 K*

    DHW production in continuous operation with Dt 25 K*

    DHW Temperature range

    Electrical supply

    Supply fuse

    Maximun absorbed power

    Insulation protection

    Net weight

    1.5 - GENERAL FEATURES

    (*) mixed

  • 9

    Installation info

    fig. 6

    2.2.1 - PACKING

    IVEN 04 24 F is delivered completely assem-

    bled and packed in a strong cardboard box.

    Once the boiler has been unpacked check that

    it is intact.

    2DIRECTIONS FORINSTALLER

    2.1 - DIRECTIONS FOR

    INSTALLER

    IVEN 04 is a gas boiler which must beinstalled in accordance with the latest re-gulations or rules in force. For the boilercategory, which changes according to thedestination country, see page 4.

    NOTE:Observe the corresponding technical rulesand the building supervisory and statutoryregulations of the country of final use wheninstalling and operating the system.

    Always ensure that an appropriatelyspecialised company is entrusted withinstallation, gas supply and flue gasconnection, commissioning and powersupply connection, as well as all servicingand repair work.Work on gas conduits and fittings mustonly be carried out by a registered serviceprovider.The system must be cleaned and servicedonce a year. This includes an inspection

    900

    495

    390

    Keep the packaging material

    (cardboard box, plastic strips,

    plastic bag, etc.) out of the rea-

    ch of children as it represents

    a choking and suffocation ha-

    zard.

    In addition to the boiler packaging contains:

    - a bag with:

    - installation, use and maintenance

    handbook,

    - warranty card

    - template for fixing the boiler to the wall,

    - 2 dowels with screws hook to fix the boiler

    to the wall,

    - Only for models TFS, a diaphragm for flue

    gas outlet

    UNICAL refuses all liability forinjury to persons and animals

    or damage to property resul-

    ting from non-observance ofthe above.

    of the entire system to see if it is in fullworking order.Defects and faults must be eliminatedimmediately.Please note that we can accept no liabilitywhatsoever for loss or injury resulting fromunauthorised adjustment or manipulationof the system’s control or regulatingdevices.

    2.2 - INSTALLATION

  • 10

    Installation info

    fig. 7

    2.2.2 - POSITIONING THE BOILER

    Every boiler is supplied with special “MOUN-

    TING JIG” with which the pipes for connec-

    tion to the system, D.H.W. and gas can be

    positioned when the hydraulic system is being

    laid out and before the boiler is installed.

    This MOUNTING JIG, comprising a sheet of

    strong paper which must be fixed to the wall

    chosen for the installation of the boiler, gives

    all the indications needed to make the holes

    in the wall using two screws with expanding

    dowels.

    Use the lower part of the MOUNTING JIG to

    mark the exact point of the connection of the

    gas supply, cold water supply pipe, D.H.W.

    outlet, C.H. flow and return.

    When choosing the position of the boiler:

    - refer to the indications given in the section

    “Flue gas evacuation system “.

    - leave a clearance of 50 mm on each side

    of the boiler to facilitate maintenance ope-

    rations.

    - check that the wall is suitable.

    - avoid fixing the boiler to thin partitions.

    - avoid installing the boiler above applian-

    ces which might affect operation when in

    use (cookers which produce greasy ste-

    am, washing machines, etc.)

    - avoid installing natural draught boilers in

    corrosive or very dusty atmospheres such

    as hairdressers’, laundrettes, etc. as the

    life of the boiler components could be si-

    gnificantly shortened.

    LM = C.H. system

    flow

    C = D.H.W.outlet

    G = Gas

    F = Cold waterinlet

    R = C.H. system

    return

    S = Safety valvedischarge

    Ø L mm

    = 3/4'' 144

    = 1/2'' 144

    = 3/4'' 153,5

    = 1/2'' 144

    = 3/4'' 144

    = 195,5

    For IVEN 04 TFSSince the temperature of the wall

    on which the boiler is installed

    and the temperature on the sur-

    face of the coaxial duct do not

    IVEN 04 TNMaintain distance of at least 200mm on the sides with wall whichhave inflammable materials. CONNECTION POSITION SEEN FROM ABOVE

    MOUNTING JIGS FOR BOILER CONNECTIONS

    increase, in normal operating conditions, more

    than 60 K, it is not necessary to keep a mini-

    mum distance from inflammable walls.

    For boilers with dual suction and exhaust ducts,

    place insulating material between the wall and

    the pipe in the case of inflammable walls and

    wall crossings.

    �����

    �����

    ���

    � � � � �

    ����������

    ������������

    ���������������

    85 85

  • 11

    Installation info

    2.2.3 - ASSEMBLING THE BOILER

    Before connecting the boiler to the D.H.W. andheating system pipes, carefully clean the pi-pes to remove all traces of metal resulting fromprocessing and welding operations as well asany oil and grease which could damage theboiler or jeopardize its operation. To install the boiler:

    - Fix with tape the paper template to the wall- make two Ø 12 holes in the wall and insert

    the hooks;- position the junction points for the connec-

    tion of the gas supply pipe, cold water sup-ply pipe, D.H.W. outlet, CH flow and returnin the positions shown by the template. ;

    - fit the boiler onto the support hooks;

    Do not use solvents whichcould damage the componen-ts.

    Unical refuses all liability forinjury to persons and animals ordamage to property resultingfrom non-observance of the abo-ve.

    - connect the boiler to the gas pipe, dome-stic cold and hot water pipes, CH flow andreturn pipes.

    - connect to electrical supply

    2.2.4 - VENTILATION

    The boiler must be installed in a suitable roomaccording to the rules in force and particular-

    ly:

    NATURAL DRAUGHT OPEN FLUE BOILERS

    (TYPE B11bs INSTALLATION and VMC)

    The boliers IVEN 04 CTN 24 F, IVEN 04 RTN

    24, are open flue boilers and are foreseen forchimney connection: the air for combustion is

    taken directly from the room in which it is in-

    stalled.The room can have both a direct ventilation

    (i.e. with ventilation openings facing outwar-ds) or an indirect ventilation (i.e. with ventila-

    tion openings facing an adjacent room) provi-ded that the following requirements are com-

    plied with:

    Direct ventilation:- The room has to have a ventilation ope-

    ning of, at least,6 cm² /kW of installed input (see input ta-

    ble on par. 2.7) and, in no case, lower than

    100 cm² and made directly onto an exter-nal wall.

    - The opening has to be as close as possi-ble to the floor.

    - It should not be possible to close it and itshould be protected with a grate not redu-

    cing its usefull ventilation section.

    - A correct ventilation can be optained alsothrough the addition of more openings, pro-

    vided the addition of the different sectionsis not less than that really needed.

    must have a vertical section with a length

    more than twice the diameter, before get-

    ting into the chimney.

    2.2.5 - FLUE GAS DISCHARGESYSTEM

    NATURAL DRAUGHT OPEN FLUE BOILERS

    Connection to the chimney

    A good chimney is very important for the cor-

    rect functioning of the boiler; it must therefore

    conform with the following requirements:

    - it must be made from waterproof material

    and be resistant at the temperature of the

    flue gas and relative condensate;

    - it must have sufficient mechanical stren-

    gth and low thermal conductivity;

    - it must be perfectly sealed to prevent co-

    oling due to parasite air inlets;

    - it must be as vertical as possible and the

    end section must have a chimney cap

    which guarantees efficient and constant

    evacuation of the combustion products;

    - the chimney must have a diameter not

    smaller than that of the boiler’s draught di-

    verter; for chimneys with a square or

    rectangular section, the internal section

    must be 10% larger than the section of the

    connection duct to the draught diverter.

    - starting from the draught diverter, the duct

    - In case it is not possible to make a venti-

    lation opening close to the floor, it will benecessary to increase its usefull section

    of at least 50%.

    - If an open fire is present in the same roomit needs an indipendent air supply, othe-

    rwise the installation of a type B applianceis not permitted.

    - If in the room there are other devices whi-ch need air for their operation (e.g. a wall

    exhauster) the section of the ventilation

    opening has to be the properly sized.

    Indirect ventilationIn case it is not possible to make a room ven-

    tilation opening on an external wall, it is pos-

    sible to have an indirect ventilation, suctingthe air from an adjacent room, making an ope-

    ning in the lowest part of a door.This solution is possible only if:

    - The adjacent room is not a bed room- The adjacent room is not a common part

    of the building and is not a room with fire

    danger (e.g. a fuel deposit, a garage, etc..)

    FORCED DRAUGHT ROOM SEALED BOI-LER(TYPE C12 - C32 - C42 - C52 - C62 - C82)The IVEN 04 CTFS 24 F - IVEN 04 RTFS 24 -

    IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 are

    forced draught, room sealed boilers; so they

    do not need particular ventilation openings for

    the combustion air, in the room in which theyare installed.

    FORCED DRAUGHT, OPEN FLUE BOILER

    (TYPE B22)If the IVEN 04 CTFS 24 F - IVEN 04 RTFS 24

    - IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 are

    installed in a room according to the chimney

    configuration on type B22, the same ventila-tion requirements established in paragraphs

    Direct ventilation and Indirect ventilationapply.

  • 12

    Installation info

    fig. 8

    2 Ø min.

    Pendenzamin. 3%

    Ø

    1,5

    m m

    in.

    2 Ø 1 m max.

    1,5

    m m

    in.

    2 Ø

    Ø

    Pendenzamin. 3%

    1 m max.

    2 Ø min.

    > 3

    Ø>

    3 Ø

    fig. 9

    210Ø 130

    200

    Direct emission into the atmosphere

    Natural draught boilers can discharge combu-

    stion products directly into the atmosphere

    using a duct, which goes through the outside

    walls of the building, connected to a flue

    exhaust terminal.

    The exhaust duct must also comply with the

    following requirements:

    - the sub-horizontal part inside the building

    must be as short as possible (no more than

    1 m);

    - for boilers with vertical discharge, such as

    boilers IVEN 04 CTN 24 F, IVEN 04 RTN24, there must be no more than 2 directionchanges;

    - it must receive the discharge from a single

    boiler;

    - the part going through the wall must be

    protected by a sheath duct; the part of the

    sheath duct facing the inside of the buil-

    ding must be sealed and the part facing

    outwards must be open;

    - the final section, on which the draught ter-

    minal will be fixed, must protrude from the

    wall of the building for a length of at least

    twice the diameter of the duct;

    - the draught terminal must overlap the con-

    nection to the boiler by at least 1.5 m (see

    fig. 8).

    DIMENSIONALS FOR CONNECTING FLUE GAS DUCTWARNING:

    The boiler is fitted with an automatic safety

    reset device as protection against spillage of

    combustion products inside the building.

    If this device is activated the boiler will cut off

    and a fault will be indicated by the lockout

    (warning light G) fig. 35.After the cooling down of the smoke thermo-

    stat it will be possible to restart the boiler by

    pressing the reset button L fig. 35.

    It is absolutely forbidden to

    by-pass the smoke thermo-stat.

    If the boiler cuts off regularly, itis necessary to ask a technician for a check

    of the flue gas exhaust duct. This duct may

    be obstructed or may be unsuitable for the

    discharge of flue gas into the atmosphere.

    UNICAL refuses all liability fordamage caused as a result of in-

    correct installation, use, modifica-

    tion of the boilers or for non-observance of

    the instructions provided by the manufacturer

    or applicable installation regulations

  • 13

    Installation info

    2.2.6 - SMOKE DISCARGE ANDAIR SUCTION DUCTCONFIGURATIONC12, C32, C42, C52, C62,C82 - B22

    typeC12

    typeC32

    typeC52

    type C82

    typeC62

    typeC42

    SEPARATEtype B22

    C12 Boiler designed for connection to hori-zontal exhaust and suction terminals

    directly into the atmosphere

    using coaxial or dual ducts. The distan-

    ce between the air intake duct and the

    flue gas outlet duct must be at least

    250 mm and both end sections must

    be located within a 500 mm square.

    C32 Boiler designed for connection to verti-cal discharge and suction outlets directly

    into the atmosphere

    using coaxial or dual ducts. The distan-

    ce between the air intake duct and the

    flue gas outlet duct must be at least

    250 mm and both end sections must

    be located within a 500 mm square.

    C42 Boiler designed for connection to col-

    lective chimneys including two ducts,

    one for the suction of com-

    bustion air and the other for the exhaust

    of the combustion products,

    through coaxial or dual ducts.

    The chimney must comply with rele-

    vant applicable law provisions.

    C52 Boiler with separate combustion air

    suction and combustion product

    exhaust ducts.

    These ducts can discharge into are-

    as with different pressure.

    The dual ducts must not be located

    on two opposite walls.

    C62 Boiler that has to be connected to a

    system of air supply and smoke of ap-

    proved type and sold apart.

    C82 Boiler designed for connection to an airsupply terminal and fitted to an indivi-

    dual or shared chimney.

    The chimney must comply with rele-vant applicable law provisions.

    B22 Boiler designed for connection to anexternal flue gas evacuation duct, with

    the air for combustion taken from the

    room in which the boiler is installed.

    For this type of installation the boiler

    house follows the same installation re-

    quirements used for the open type boi-

    lers.

    Note: type B22

    is not approved by

    Turkish market.

  • 14

    Installation info

    fig. 10

    Pursuant to the directives of regulations in

    force, discharge of forced draught boilers can

    2.2.7 - POSITIONING OF TERMINALS FOR TYPE ‘’C’’BOILERS

    either take place through the roof or directly

    outwards the room they are installed in. The

    following distances shall be considered for

    terminals proper positioning:

    POSITIONING OF TERMINALS FOR "FORCED DRAUGHT" BOILERS

    Min.

    POSITIONING OF THE TERMINAL distances in mm.

    Under a window A 600

    Under a ventilation opening B 600

    Under a gutter C 300

    Under a balcony (1) D 300

    From an adjancent window E 400

    From an adjacent ventilation opening F 600

    From vertical or horizontal air pipes or drains (2) G 300

    From an external corner of the building H 300

    From an internal corner of the building I 300

    From the ground or from another floor L 2500

    Between two vertical terminals M 1500

    Between two horizontal terminals N 1000

    From a facing front surface without opening or teminals within a radius

    of 3 mt. from smoke outlet point O 2000

    As above, but with openings or terminals within a radius of 3 mt. from

    smoke outlet point P 3000

    NOTES

    (1) Terminals below a practicable balcony shall be arranged in such a way as to assure that the total run of smokes, from their outlet from

    terminal up to outlet from balcony external perimeter, including the height of protection baluster, if any, is not less than 2 m.

    (2) Distances of not less than 500 mm shall be adopted in placing the terminals, due to the proximity to materials subject to the action of

    products of combustion such as plastic gutters or waterspouts, wooden jetties, etc.) unless adequate screeening measures are taken for

    the said materials.

    FLUE TERMINAL POSITIONING

  • 15

    Installation info

    2.2.8 - SMOKE EVACUATION Ø 80WITH AIR SUCTIONFLANGE - Type B22(see par. 2.2.6)

    Note: For evacuation system with 80 mm dia.

    and a lenght between 0.5 m and 4 m, it

    is necessary to introduce a diaphragm

    of 44 mm dia. supplied with the boiler in

    the plastic bag, into the fun outlet adap-

    tor (see fig. 11).

    The maximum allowed length for a smo-

    ke pipe of Ø80 mm dia. is 20 m (for

    IVEN 04 RTFS 24 e IVEN 04 CTFS 24

    F) and 25 m (for IVEN 04 RTFS 24 e

    IVEN 04 CTFS 28 F), included a wide

    radium curve and one smoke terminal.

    For this type of installation the chim-

    ney has to serve just one boiler, i.e. the

    boiler must have its indipendent smo-

    ke duct.fig. 11

    fig. 12

    DiaphragmØ 44 mm

    Fitting of the diaphragm Ø44

    WARNING:

    For the installation where there

    is a freezing risk it is dia. sug-

    gested to insulate the smoke

    duct 80 mm on all its length,

    both in case it discharges from a vertical wall

    or in a chimney.

  • 16

    Installation info

    2.2.9 - DISCHARGE OF FLUEGAS INTOCOAXIAL DUCTSØ 100/60 mm

    Type C12The minimum length of horizontal co-axial

    ducts is 0.5 metres. The maximum allowablelength of horizontal co-axial ducts is 3 me-tres; for each additional bend the maximumallowable length must be reduced by 1 metre.

    Moreover, the duct must have a downward dip

    of 1% towards the outlet point to prevent rain

    water from getting into the duct.

    Type C32The minimum length of vertical coaxial ducts

    is 0.5 metres. The maximum allowable lengthof vertical coaxial ducts is 4 metres exclu-ding the stack (Ø80/125); for each additional

    bend the maximum allowable length must be

    reduced by 1 metre.

    The diaphragm Ø 44 supplied with the boi-

    ler must be inserted in the flue gas exhaust

    pipe as shown in figure 13, for installa-

    tions with horizontal coaxial pipe up to 1

    m and with vertical coaxial pipe up to 2 m.

    fig. 13

    VERTICAL FLUE DUCT WITH

    COAXIAL DUCT Ø 80/125

    Tipo C32

    The minimum length of vertical co-axial ducts

    is 1,2 metres. The maximum allowable lengthof vertical coaxial ducts is 6 metres exclu-ding the stack (Ø80/125); for each additional

    bend the maximum allowable length must be

    reduced by 1 metre.

    The diaphragm Ø44 supplied with the boi-

    ler must be inserted in the flue gas exhaust

    pipe, as shown in figure 14, for installa-tions with a coaxial pipe up to 2,5 m.

    fig. 14

    Diaframma Ø 44 mm

    Ø 60/100

    Ø 80/125

    Ø 80/125

    Ø 80/125

    Rubber foamgasket

    Up

    to

    2 m

    Up to

    1 m

    Up

    to

    2,5

    m

    Rubber foamgasket

    DiaphragmØ 44

    DiaphragmØ 44

  • 17

    Installation info

    fig. 15

    245

    100

    95

    2.2.10 - FLUE GAS DISCHARGEAND AIR SUCTION WITHDUAL DUCTS WITH 80 mmDIAMETER

    NB: The maximum allowable pressure loss,

    irrespective of the type of installation, must

    not exceed 50 Pa (for per IVEN 04 RTFS 24 /

    CTFS 24 F) and 60 Pa (for IVEN 04 RTFS 28

    / CTFS 28 F)

    For all installations with a pressure loss of the

    ducts not exceeding 20 Pa, the diaphragm

    supplied with the boiler must be installed insi-

    de the flue gas outlet pipe (see fig. 16).

    WARNING! In case the flue duct

    has to cross walls or floors, or if

    it is easily reachable, it is ne-

    cessary to foresee a convenient

    insulation of such a duct. The

    flue duct, during the operation

    of the boiler can reach tempera-

    tures higher than 120°C.

    fig. 16

    DIMENSIONS FOR CONNECTING TO COAXIAL FLUE GAS DUCTS

    Up to ∆∆∆∆∆ P = 20 Pa

    Rubber foamgasket

    Diaphragm

    Ø 44

    IMPORTANT

    Flue gas pressure switch operation

    The boiler is fitted with a device control-ling flue gas pressure.This device shuts down the boiler in the

    event of a malfunction.

    This situation is not indicated by the emer-gency light.The safety device needs to be reset by

    switching OFF and ON.

  • 18

    Installation info

    fig. 17

    fig. 18

    _> 5

    00

    Example N.1

    Hmin. = 150 mm

    CONFIGURAZIONI RELATIVE ALLE TUBA-

    ZIONI SIA DI SCARICO CHE DI ASPIRAZIO-

    NE Ø 80

    DIMENSIONS FOR CONNECTING THE AIR INTAKE AND THE FLUE GAS DISCHARGEWITH DUAL DUCTS

    Example N.1 (fig. 18)

    Primary air suction from perimeter wall and

    flue gas discharge on roof.

    Maximum allowable pressure loss:50 Pa (IVEN 04 TFS 24)60 Pa (IVEN 04 TFS 28)

    85 85

    245

    Ø 80

    85

    160

    245

    8585

    85 85

  • 19

    Installation info

    CALCULATION OF PRESSURE LOSSESFOR DISCHARGE AND SUCTION DUCTS

    Bear in mind the following parameters when

    calculating pressure losses:

    - for each metre of duct with Ø 80 (both

    suction and discharge) the pressure loss

    is 2 Pa;

    - for each 90° Ø 80 (R=D) bend with long

    radius, the pressure loss is 2 Pa;

    - for each 90° Ø 80 (R=½ D) bend with

    short radius, the pressure loss is 6 Pa insuction and 8 Pa in discharge;

    - for the Ø 80 L = 0.5 m horizontal air inlet

    terminal, the pressure loss is 3 Pa;

    - for the Ø 80 L = 0.6 m horizontal

    discharge end section, the pressure loss

    is 5 Pa;

    - 2 short radius 90° Ø 80 curves + 1

    adapter Ø 80, the pressure loss is 14

    Pa.

    fig. 20

    fig. 19

    2.2.11- MEASUREMENTS OFCOMBUSTION EFFICIENCY

    Ducts Ø 80 type B22 (C)

    Coaxial ducts (A)

    Dual ducts Ø 80 (B)

    To determine combustion efficiency the fol-

    lowing measurements must be made:

    - the combustion air temperature measured

    in hole 2 (see fig. 20).

    - the flue gas temperature and CO2 % mea-

    sured in hole 1 (see fig. 20).

    Make these measurements with the boiler

    running in a steady state condition.

    135

    45

    C

    Sondaanalizzatore

    2

    1

    25

    0 m

    in.

    Sondaanalizzatore

    NB: These values refer to di-

    scharges through original UNI-

    CAL non-flexible and smooth

    ducts.

    Example of check using wide radius

    bends:

    - 2 Ø 80 long radius 90° bends + 1 adapter

    Ø 80

    (14 Pa)

    - (TFS 28) 17 mt duct Ø 80 x 2 =

    (34 Pa)

    - (TFS 24) 12 mt duct Ø 80 x 2 =

    (24 Pa)

    - 2 90° Ø 80 long radius bends x 4 =

    8 Pa

    - horizontal Ø 80 air inlet terminal =

    3 Pa

    - horizontal Ø 80 terminal =

    5 Pa

    Tot. pressure loss (TFS 28) = 60 Pa

    Tot. pressure loss (TFS 24) = 50 Pa

    1

    2 Sondaanalizzatore

    Sondaanalizzatore

    Fumi

    Aria

    A

    Example N.2 (fig. 19)Primary air suction from perimeter wall and

    flue gas discharge from the same outside pe-

    rimeter wall.

    Maximum allowable pressure loss:

    50 Pa (IVEN 04 TFS 24)60 Pa (IVEN 04 TFS 28)

    Example N.2

    Aria

    Sonda

    analizzatore

    1

    Fumi

    B

    2

  • 20

    Installation info

    2.2.12 - CONNECTION TO THE GASMAINS

    The supply pipe must have a section which is

    the same as or greater than the one used in

    the boiler.

    Comply with the applicable local installation

    requirements which shall be considered as

    having been incorporated in full in this ma-

    nual.

    Before opening the internal gas supply system;

    i.e. before connecting the gas meter, all seals

    must be checked.

    If any part of the system is concealed the seals

    must be checked before the pipes are cove-

    red.

    The seal test must be conducted using air or

    nitrogen at a pressure of at least 100 mbar.

    The commissioning of the boiler also inclu-

    des the following operations and checks:

    - Opening of the gas gate valve and venting

    2.2.13 - HYDRAULIC CONNECTION

    Before installing the boiler we recommend that

    the system be cleaned to remove any impuri-

    ties which could originate from components

    and which could risk damaging the circulating

    pump and heat exchanger.

    Note: The use of solvents could damage

    the components of the heating cir-

    cuit.

    PRELIMINARY OPERATIONS:

    Act on the coupled spring (located in the lower

    part) and remove the two screws (located in

    the upper part) in order to remove the casing.

    fig. 21

    of the air contained in the piping and ap-

    pliances, proceding appliance by applian-

    ce

    - Check, with the gate valve of all the ap-

    pliance Off, that there are no gas leaks.

    During the 2nd quarter of a hour from the

    beginning of the test no pressure reduc-

    tion is to be detected on the gas pressure

    Move the control panel in the high position for

    the hydraulic connection. Remove the three

    screws "A" fixing the panel and then placethe panel in correspondence to the low holes

    "B" and fix the panel.

    After having carried out the connections, re-

    store the panel's normal position.

    HEATING

    The heating flow and return must be connected

    to the relevant ¾” connections of the boiler Mand R (see fig. 7).When determining the size of the heating cir-

    cuit pipes it is essential to bear in mind the

    pressure losses induced by radiators, any ther-

    mostatic valves, radiator cut-off valves and

    the configuration of the system.

    In the boiler, onto a bass group positioned,

    between the flow and return an automatic by-

    pass device is fitted (about a differential val-

    ve with a flow rate of about 150 l/h) which gua- fig. 22A

    B

    C

    D

    To OPEN the

    By-pass

    rotate the screw

    anti-clockwise

    To CLOSE the

    By-pass

    rotate thescrewclockwise

    Note:The control panel can be mo-

    ved in two positions beyond the nor-

    mal position ‘’D’’, that is to say highand low position, in order to make

    the maintenance operations easy.

    rantees always minimum flow rate throught

    the heat exchanger, also in the case, for in-

    stance, that all the thermostatic valves fitted

    on the radiators, are closed. It is possible to

    adjust the by-pass by acting onto the adju-

    sting screw (see fig. 21)

    We recommend that the discharge of the sa-

    fety valve mounted in the boiler be conveyed

    into the sewer.

    If this precaution is not taken, activation of

    the safety valve may result in flooding of the

    room where the boiler is installed.

    UNICAL shall not be held responsible for da-

    mage caused by non-observance of this tech-

    nical precaution.

    D.H.W.

    Outlet and inlet of D.H.W. must be connected

    to the relevant ½” connections of the boiler Cand F (see fig. 7).

    The hardness of the supply water affects the

    frequency of the cleaning of the heat exchan-

    ger.

    gauge. If gas leaks have to be found, use

    only water soap solution or any other spe-

    cific gas leak detector which can be avai-

    lable on the market. Never look for gas le-

    aks using a nacked flame.

    While connecting gas inlet pipe of the boiler to the pipe coming fromgas network, it is MANDATORY to insert a TIGHT GASKET, whosedimensions and material must be adequate. Connection is NOT sui-table for hemp, teflon strip or similar materials�����������

  • 21

    Installation info

    fig. 23

    IVEN 04 RTN 24 - IVEN 04 RTFS 24

    IVEN 04 CTN 24 F - IVEN 04 CTFS 24 F

    IVEN 04 CTFS 28 F - IVEN 04 RTFS 28

    6,26,05,85,65,45,25,04,84,64,44,24,03,83,63,43,23,02,82,62,42,22,01,81,61,41,21,00,80,60,40,2

    00 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

    V1V2

    V3

    6,26,05,85,65,45,25,04,84,64,44,24,03,83,63,43,23,02,82,62,42,22,01,81,61,41,21,00,80,60,40,2

    00 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

    V1V2

    V3

    6,26,05,85,65,45,25,04,84,64,44,24,03,83,63,43,23,02,82,62,42,22,01,81,61,41,21,00,80,60,40,2

    00 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

    V1V2 V3

    DIAGRAM FLOW RATE/MANOMETRIC HEAD AVAILABLE FOR THE CH SYSTEM

    Ma

    no

    me

    tric

    He

    ad

    av

    ail

    ab

    le in

    mW

    .G.

    Flow rate Q (l/h)

    Note: The boiler is delivered with the by-pass in OPEN position.= By-Pass CLOSED - - - - - - - - = By-Pass OPEN

    Ma

    no

    me

    tric

    He

    ad

    av

    ail

    ab

    le in

    mW

    .G.

    Flow rate Q (l/h)

    Ma

    no

    me

    tric

    He

    ad

    av

    ail

    ab

    le in

    mW

    .G.

    Flow rate Q (l/h)

  • 22

    Installation info

    WARNINGDepending on the hardness ofthe supply water, it is impor-tant to assess the convenien-ce of installing a domesticdevice to dose water treat-ment products which can beused to treat the drinking wa-ter.It is always advisable to treat

    the water if the supply water has

    a hardness value of more than

    28°f.

    As far as concerns the positio-

    ning size of the "E" stirrup, you

    have to consider the template

    in the figure 7 (size 730.5 mm -

    optional kit).

    2.2.14 - ARRANGEMENTS FOR AD.H.W. TANK (for boiler typesproviding only heating)

    This Kit permits an only heating boiler (type

    IVEN 04 RTN 24, RTFS 24 or RTFS 28.) to

    produce sanitary warm water (through the use

    of an external D.H.W. tank).

    PRELIMINARY OPERATIONS

    Act on the coupled spring (located in the lower

    part) and remove the two screws (located in

    the upper part) in order to remove the shell.

    In order to install such a kit, you have to move

    the control panel in the lower position. Then

    unloose the three fixing screws "A" two on

    the side and one on the back of the panel bo-

    ard, and place the panel in correspondence to

    the upper holes "C" and fix the panel.

    If the boiler is already installed, go on with the

    emptying of the boiler

    - Relate for the discharge connection of the

    safety valve a plastic pipe with hose adap-

    ter, whose length can

    reach a drain.

    - Remove the components from 1 to 6 of fig.

    25/A and assemble the components from

    1 to 6 contained in the kit and shown in the

    fig. 25 B; also remove the minimum pres-

    sure switch from the C.H. flow group and

    place it on manifold of the diverting valve.

    - Connect electrically the connector from the

    panel board to the actuator of the diverting

    valve. See detail "F"

    fig. 25.

    - Connect the cable of the D.H.W. sensor

    from the panel board (colour BLUE -

    BROWN, see detail "G") to the cable of

    the D.H.W.sensor kept in the kit (which has

    to be placed in the sheath of the external

    D.H.W. tank) through two terminals provi-

    ded with the kit.

    fig. 24

    E

    fig. 25

    � �

    A

    B

    F

    G

    E

    INSTALLATION WITH PRE-PIPING KIT

    (OPTIONAL 00360808)

    ARRANGEMENTS FOR A CONNECTION TO AN EXTERNAL D.H.W. TANK

    COMPONENTS TO BE REMOVED

    1 - SAFETY VALVE

    2 - NIPPLE

    3 - FLOW PIPE

    4 - CLOSING CAP

    6 - MINIMUM PRESSURE SWITCH

    COMPONENTS TO BE ADDED

    1 - ELECTRIC DIVERTING VALVE

    2 - ACTUATOR

    3 - FLOW PIPE TO D.H.W. TANK

    4 - RETURN PIPE FROM D.H.W. TANK

    5 - FLOW PIPE TO DIVERTING VALVE

    6 - MINIMUM PRESSURE WITCH

  • 23

    Installation info

    � �

    2.2.15 - ELECTICAL CONNECTIONS

    The electrical connections of Logamax are

    shown in the clause ‘’WIRING DIAGRAMS’’

    (par. 2.3 - pag. 24)

    The boiler must be connected to

    the mains supply at

    230 V - 50 Hz. This connection isto be perfectly done, as foreseen

    by the IEC and local rules and must be ear-

    thed.

    This fundamental requirement for safety pur-

    poses must be checked; in case of doubt,

    ask for a professionally qualified technician

    to check the electrical system.

    UNICAL disclaims all liability for damage orinjury caused by failure to earth the system

    properly.

    Gas, domestic water and central heatingpipes are not suitable for earthing purpo-ses.The boiler is supplied with 1.5 m long

    3x0,75mm² cord.

    A double pole switch with a distance between

    the contacts higher than 3 mm, must be in-

    stalled upstream the boiler to enable all main-

    tenance operations to be carried out safely.

    Access to the electrical terminal strip

    - WARNING! Switch off the electrical sup-

    ply

    - Remove the casing.

    - Remove the four screws (A) and the cover

    (B) in order to get access to the connec-

    tions area.

    Replacement of the feeding cord

    Should the feeding cord be replaced, you have

    to use the original cable code 00610308.

    - Approach the feeding connector Y2.

    - Introduce the feeding cord through the ex-

    tractable cable clamp.

    - Extract the connector Y2 and proceed with

    the connections according to the positions

    and to the colours. The female faston of

    the earth wire must be introduced in the

    male faston GND1.

    Connection of the ON/OFF room thermo-stat (RT)- Approach the connector Y1.

    - Remove the existing jumper and connect,

    on its place the room thermostat cable,

    passing it through one of the cable clam-

    ps avaible.

    Connection of the room modulating ther-mostat (OT)- Approach the connector Y1.

    - Connect the room thermostat cable, pas-

    sing it through one of the cable clamps

    avaible.

    - The modulating chronothermostat is to be

    connected exactly to the same terminal of

    the ON/OFF room thermostat; in this case

    the jumper JP2 has to be changed of posi-

    tion (see. par 2.3.2).

    For a multi-zones temperature control it is not

    possible to install the modulating chronother-

    most.

    Example: At 25°C, the nominal resistance is 10067 OhmAt 90°C, the nominal resistance is 920 Ohm

    Relation between the temperature (°C) and nominal resistance (Ohm)of the heating sensor SR and D.H.W. sensor SS

    TABLE OF RESISTANCE VALUES AS A FUNCTION OF THE TEMPERATUREOF THE HEATING SENSOR (SR) AND D.H.W. SENSOR (SS)

    T°C 0 1 2 3 4 5 6 7 8 9

    0 32755 31137 29607 28161 26795 25502 24278 23121 22025 2098710 20003 19072 18189 17351 16557 15803 15088 14410 13765 1315320 12571 12019 11493 10994 10519 10067 9636 9227 8837 846630 8112 7775 7454 7147 6855 6577 6311 6057 5815 558440 5363 5152 4951 4758 4574 4398 4230 4069 3915 376850 3627 3491 3362 3238 3119 3006 2897 2792 2692 259660 2504 2415 2330 2249 2171 2096 2023 1954 1888 182470 1762 1703 1646 1592 1539 1488 1440 1393 1348 130480 1263 1222 1183 1146 1110 1075 1042 1010 979 94990 920 892 865 839 814 790 766 744 722 701

  • 24

    Installation info

    fig. 26

    2.3 WIRING DIAGRAM

    2.3.1 ACTUAL WIRING DIAGRAM

    LE

    GE

    ND

    A

    A1...A

    8=

    Connecto

    rs

    Y1

    =R

    oom

    therm

    osta

    t 2

    4 V

    connecto

    r

    Y2

    =E

    lectr

    ical s

    upply

    connecto

    r

    IG=

    ON

    /OF

    F s

    witch

    TA=

    Room

    therm

    osta

    t (o

    ptional)

    VG

    =G

    as v

    alv

    e

    E. R

    IV=

    Ionis

    ation e

    lectr

    ode

    E. A

    CC

    =Ig

    nitio

    n e

    lectr

    ode

    V=

    Fan (only

    for T

    FS

    )

    PV

    =F

    an p

    ressure

    sw

    itch (only

    for T

    FS

    )

    TL

    =H

    .L. T

    herm

    osta

    t

    TF

    =F

    lue-g

    as s

    pill

    age therm

    osta

    t

    (only

    for T

    N)

    P=

    Circula

    ting p

    um

    p

    DK

    =M

    inim

    um

    wate

    r pre

    ssure

    sw

    itch

    SR

    =C

    .H. s

    ensor

    FL

    =R

    ota

    ry flo

    w s

    witch (only

    for C

    TN

    -CT

    FS

    )

    SS

    =D

    .H.W

    . sensor (only

    for C

    TN

    -CT

    FS

    )

    SS

    *=

    D.H

    .W. sensor (o

    nly

    for boile

    r w

    ith e

    xte

    rnal D

    .H.W

    .

    tank)

    MV

    D=

    Moto

    r 3 w

    ay v

    alv

    e (optional f

    or only

    heating b

    oile

    r).

    �����

    �����

    �����

    ����

    ���

    ���

    ���

    ���

    �����

    �����

    ���

    �����

    ��

    ������

    ���

    ����

    ���

    ����

    �������

    ���

    ����

    ����

    ��

    ������

    ���

    ����

    �����

    ���������������

    �����������������

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ���

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    � ���

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ����������

    ������

    ������������

    ��

    ���������������

    ��

    ��

    ��

    ��

    ��

    ��

    ����

    ��

    ����

    ���

    �������

    ���

    ���

    �����

    ���������

    ���

    ������

    ����

    ���

    ���

    ��

    ��

    ��

    ��

    ��

    ����

    ���

    �����

    ��

    ����

    � �

    ��

    ������

    ����

    ������������

    ��

    ��

    ��

    �������

    ���

    �����

    �����

    ��

    �����

    � ���

    ���

    ��

    ��

    ��

    � ���

    ���

    ����������

    ��������

    �������

    ����������

    �����������

    ����

    ��

    ��

    !

    ��

    "

    !

    �� ��

    ��

    ��! ��

    ��

    !�

    ���

    !

    ��

    ���

    ��

    �� !��

    ��

    !

    ��

    "�

    ���

    ���

    ���

    ���

    ���

    ���

    ���

    ���

    �����

    !����

    ��

    ��

    ��

    ��

    ��

    ��

    ��

    ���

    �!

    ������

    �������

    �����

    ���

    ���

    ����

    �����

    �!

    �#$��

    � ��

    �����

    ��

    �����

    ������������� ���

    ���������

    ����

    ��

    ������

    ��

    ����

    �����

    ����

    ���

    ���

    ���

    ����

    ����

    ���

    ����

    ������

    �������

    ���

    �����

    ����������

    ���������������

    ���������������

    �������������

    �����������

    ����

    ����������������

  • 25

    Installation info

    ���

    ���

    ���

    ���

    ���

    ���� �

    2.4 - FILLING THESYSTEM

    EAfter completing all the connections of the

    system the heating circuit can be filled.

    This filling operation must be performed with

    care as follows:- open the air vents of the radiators and che-

    ck that the automatic air vent in the boiler

    is works properly;

    - gradually open the water tap and check

    operation of any automatic air vents instal-

    led in the system;

    - close the air vents on the radiators as soon

    as water comes out;

    - use the pressure gauge on the boiler to

    check that the pressure has reached the

    value of 0.8/1bar;

    - close the water inlet tap and then release

    the air again through the radiator air vents;

    - after switching on the boiler and after the

    system has reached the correct tempera-

    ture, stop the pump and repeat the air re-

    lief operations;

    - let the system cool down and then adjust

    the water pressure to 0.8/1 bar.

    WARNING

    The minimum water pressure

    switch does not give electrical

    fig. 27

    2.3.2 - JUMPER LOCATION

    They are placed on the modulation card and

    their purpose is to settle basic operational fun-

    ctions.

    In order to get access to the jumper:

    - WARNING! switch off electrical supply.- Remove the casing.

    - Remove the four screws (A) and the cover(B) in order to get access to the connec-tions area.

    JP1: For nat. gas boilers, the jumper is onNAT.For LPG boilers, the jumper is on LPG.

    JP2: SETTLEMET OF THE CHRONOTHER-MOSTAT TYPE

    For modulating chronothermostat the jumper

    is on OTFor ON / OFF thermostat (delivery condition)the jumper is in RT.

    FILLING TAP

    impulse to the burner to ignite when the pres-

    sure is lower than 0.4 bar. The pressure of the

    water in the C.H. system must not be lower

    than 0.8/1bar; if this value is lower use the

    water filling tap on the boiler to adjust the pres-

    sure.

    This must be performed when the system is

    cold. Use the temperature and pressure gau-

    ge on the boiler to read the pressure value of

    the circuit.

    NB: After a given period of inactivity and

    without electrical supply the pump could be

    blocked.

    Before switching on the boiler it is important

    to restart the pump as follows: loosen the pro-

    tection screw in the centre of the pump motor,

    insert a screwdriver in the hole and then ma-

    nually rotate the pump shaft clockwise.

    Once the pump has been restarted tighten the

    protection screw and check that there are no

    water leaks.

    WARNINGOnce the protection screw has been removed

    a little water may leak out. Before replacing

    the casing of the boiler dry any wet surfaces.

    2.5 - STARTING THE BOILER

    PRELIMINARY CHECKS

    Before starting the boiler check that:

    - the boiler installation has been made in

    accordance with all the applicable regula-

    tions concerning water and gas installation,

    smoke evacuation and electrical installa-

    tion

    - the flue gas exhaust duct and its terminal

    are installed correctly: when the boiler is

    switched on there must be no leakageof any combustion products from anyseals;

    - the supply voltage of the boiler is 230 V-

    50 Hz;

    - the system is correctly filled with water

    (pressure at the gauge 0.8/1 bar);

    - any gate valves taps of the system are

    open;

    - the mains gas corresponds to that with

    which the boiler has been calibrated: othe-

    rwise, convert the boiler to use the gas

    available (see section: “MODIFICATION

    FOR OTHER GASES “): this operation

    must be performed by qualified techni-cians;

    - the gas supply tap is open;

    - there are no gas leaks;

    - the external mains switch is on;

    - the boiler’s safety valve is not locked;

    - there are no water leaks.

    SWITCHING ON AND OFF

    To switch on and off the boiler follow the indi-

    cations in the “Users’ Instructions”.

  • 26

    Adjustment info

    fig. 28

    A

    fig. 31

    D

    fig. 30

    fig. 29

    B

    1 2 3

    1 2 3

    Pressure testnipple ''D''downstreamgas valve

    Plug of max pressureadjust screew

    Maximum pressureadjust screw ''B''

    Pressuretest nippleupstreamgas valve

    2.6 ADJUSTING THE

    BURNER

    All the instructions below are for the exclusi-

    ve use of qualified technicians.All the boilers leave the factory calibrated and

    tested.

    If it is necessary to change the calibration fol-

    lowing changes in the type of gas or adapta-

    tion to the supply network conditions, it is

    necessary to recalibrate the gas valve.

    To correctly regulate the gas valve, follow the

    steps below:

    1) Maximum output adjustment- check the value of the supply pressure (see

    table NOZZLES - PRESSURES);

    - Unloose the screw ''D'' on the pressure testnipple downstream the gas valve (fig. 30)

    and connect a pressure gauge as shown

    in figure 30;

    - set the ''B'' knob (onto the panel board) tomax. position (fig.35);

    - check that the room thermostat contact

    TA is closed;

    - Switch on the power supply to the boiler

    and depress the ''chimney sweeper'' switch

    ''H fig. 35'' on the panel board: in this way

    the boiler will operate at maximum output;

    - when the burner is ignited, check that the

    “MAXIMUM” pressure value corresponds

    to that indicated on the table “NOZZLES -

    PRESSURES”: if it does not, correct it by

    removing the screw plug “A” (fig. 28) and

    by turning screw “B” (fig. 29) CLOCKWISE

    to increase, and ANTICLOCKWISE to de-

    crease

    2) Minimum output adjustment

    - Depress a second time the ''chimney swee-

    per'' switch ''H fig. 35'' on the panel board:

    in this way the boiler will operate at mini-

    mum output;

    - when the burner is ignited, check the “MI-

    NIMUM” pressure value corresponds to that

    indicated in the table “NOZZLES - PRES-

    SURES ”;

    - correct the value, if necessary, turning the

    MIN GAS potentiometer 2 on the PCBusing a screwdriver (see fig.31).

    3) Completion of the basic adjustement- check the minimum and maximum pres-

    sure values of the gas valve;

    - if necessary make any fine adjustments

    - Disactivate the ''chimney sweeper'' func-

    tion switching Off and On again through

    the ‘’A’’ switch fig. 35.- Remove the plastic pipe from pressure test

    nipple and close the inner screw;

    - Using a soapy solution check for gas

    leaks.

    PRESSURE TESTNIPPLE

    CLOCKWISEANTI-CLOCKWISE CLOCKWISE

    ANTI-CLOCKWISECLOCKWISE

    ANTI-CLOCKWISE

  • 27

    Adjustment info

    fig. 32

    fig. 33

    ���

    ���

    ���

    ���

    ���

    1

    IVEN 04 CTN 24 F - IVEN 04 RTN 24

    Gas

    consump-

    tion

    max.

    Natural gas

    Propan

    Butan

    10,07 - 23,88

    10,07 - 23,88

    10,07 - 23,88

    11,5 - 26,5

    11,5 - 26,5

    11,5 - 26,5

    20

    37

    28-30

    14

    14

    14

    -

    -

    -

    IVEN 04 CTFS 24 F - IVEN 04 RTFS 24

    9,95 - 23,94

    9,95 - 23,94

    9,95 - 23,94

    11,5 - 26,5

    11,5 - 26,5

    11,5 - 26,5

    20

    37

    28-30

    14

    14

    14

    -

    -

    -

    IVEN 04 CTFS 28 F - IVEN 04 RTFS 28

    9,8 - 27,45

    9,8 - 27,45

    9,8 - 27,45

    11,5 - 30,5

    11,5 - 30,5

    11,5 - 30,5

    20

    37

    28-30

    14

    14

    14

    -

    -

    -

    Natural gas

    Propan

    Butan

    Natural gas

    Propan

    Butan

    1,25

    0,75

    0,75

    2,1

    6,4

    4,6

    11,0

    32,1

    25,8

    1,22 m³/h

    0,89 kg/h

    0,91 kg/h

    2,80 m³/h

    2,06 kg/h

    2,09 kg/h

    1,25

    0,75

    0,75

    2,0

    6,2

    4,8

    10,8

    35,3

    27,1

    1,22 m³/h

    0,89 kg/h

    0,91 kg/h

    2,80 m³/h

    2,06 kg/h

    2,09 kg/h

    1,25

    0,78

    0,78

    2,1

    4,4

    3,7

    13,8

    35,5

    27,4

    1,23 m³/h

    0,89 kg/h

    0,91 kg/h

    3,24 m³/h

    2,37 kg/h

    2,40 kg/h

    JP1: For nat. gas boilers, the jumper is

    on NAT.

    For LPG boilers, the jumper is on

    LPG.

    2.7 - MODIFICATION FOR

    OTHER GASES

    The boilers are manufactured for the type of

    gas specifically required upon order.

    Any subsequent conversion must be perfor-

    med by qualified technicians who will use the

    kits supplied by Unical and perform the con-version and required adjustments for correct

    preparation of the boiler for use.

    To convert the boiler from one type of gas to

    another proceed as follows:

    for conversion from natural gas to LPG- remove the main burner;

    - disassemble injectors “1” (fig. 32) of themain burner and replace them with those

    with a diameter corresponding to the new

    type of gas (see table “INJECTORS -

    PRESSURES”);

    - reassemble the main burner;

    - position the jumper on the modulation PCB

    in the panel board as shown in fig. 33

    - remove plug ‘’A’’ (fig.28) on the gas valve

    and fully tighten max pressure adjustment

    screws ‘’B’’ (fig.29)

    - check the pressure value upstream the gas

    valve (see table “INJECTORS - PRESSU-

    RES”) and adjust the pressure of the bur-

    ner as indicated in section “ADJUSTING

    THE BURNER”

    - check that the burner is functioning pro-

    perly;

    - check that there are no gas leaks.

    - tighten the plug ”A” (fig.28) of the max

    pressure adjustment screw

    - when the conversion is completed, fill in

    label supplied with the kit with the informa-

    tion required and stick it onto the boiler

    alongside the data plate.

    for conversion from LPG to natural gas- remove the main burner;

    - disassemble injectors “1” (fig. 32) of themain burner and replace them with those

    with a diameter corresponding to the new

    type of gas (see table “INJECTORS -

    PRESSURES”);

    - reassemble the main burner;

    - position the jumper on the modulation PCB

    in the panel board as shown in figure 33;

    - remove plug ‘’A’’ (fig.28) on the gas valve- check the pressure value upstream the gas

    valve (see table “INJECTORS - PRESSU-

    RES”) and adjust the burber pressure as

    indicated in section “ADJUSTING THE

    BURNER”;

    - check that the burner is functioning pro-

    perly;

    - check that there are no gas leaks.

    - tighten the plug “A” (fig.28) of the max

    pressure adjustment screw;

    - when the conversion is completed, fill in

    label supplied with the kit with the informa-

    tion required and stick it onto the boiler

    alongside the data plate.

    Nominal

    Output

    (kW)

    Nominal

    input

    (kW)

    Supply

    pressure

    (mbar)

    Ø

    Diaphragme

    (mm)min.

    (mbar)max

    (mbar)

    Ø

    Nozzles

    (mm)

    Gas

    consump-

    tion

    min.

    The pressures at the burner indicated in the following table must be checked after the boiler has been operating for 3 minutes.TABLE NOZZLES - PRESSION - DIAPHRAGME - CONSUMPTION

    Tipe of

    gasNo. of

    Nozzles

    Burner pressure

    Gas

    consump-

    tion

    max.

    Nominal

    Output

    (kW)

    Nominal

    input

    (kW)

    Supply

    pressure

    (mbar)

    Ø

    Diaphragme

    (mm)min.

    (mbar)max

    (mbar)

    Ø

    Nozzles

    (mm)

    Gas

    consump-

    tion

    min.

    Tipe of

    gasNo. of

    Nozzles

    Burner pressure

    Gas

    consump-

    tion

    max.

    Nominal

    Output

    (kW)

    Nominal

    input

    (kW)

    Supply

    pressure

    (mbar)

    Ø

    Diaphragme

    (mm)min.

    (mbar)max

    (mbar)

    Ø

    Nozzles

    (mm)

    Gas

    consump-

    tion

    min.

    Tipe of

    gasNo. of

    Nozzles

    Burner pressure

  • 28

    Adjustment info

    fig. 34

    IVEN 04 CTN 24 F - IVEN 04 RTN 24 (A)

    IVEN 04 CTFS 24 F - IVEN 04 RTFS 24 (B)

    IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 (C)

    ��� � � � � � � � �� �� �� �� ���

    ��

    ��

    ��

    ��

    ��

    ���

    ����

    ��� ����

    � � �� �� �� �� �� �� ��

    ��� ���

    � �� �� �� �� ��� �� ��

    � ����

    ��

    ��

    ���

    �������������������������

    ����������������

    ����������������

    ��

    ������

    ��

    � � � � � � � � ! �� �� �� �� ���

    ��

    ��

    ��

    ��

    ����

    ���

    � � �� �� �� ��

    �� ����

    � �� �� �� �� �� ���

    ����

    �������������������������

    ����������������

    ����������������

    ��� � � � � � � � ! �� �� �� �� ���

    ��

    ��

    ��

    ��

    ��

    ����

    �� ���

    � � �� �� �� �� �� ��

    ��� ����

    � �� �� �� �� �� �� ���

    ���������������������

    ����������������

    ����������������

    ������

    ��

    2.8 ADJUSTEMENT OF

    THE OUTPUT TO

    THE C.H. SYSTEM'S

    NEEDS

    Connect the pressure gauge to the burner as

    previously shown in fig. 30, switch on the boi-

    ler in heating mode and proceed as follows:

    - Wait about 50 sec. to allow the burner pres-

    sure to reach the standard operating va-

    lue.

    - Check the pressure value and through the

    diagrams of fig. 34 estimate if the boiler

    output is correct for heating needs.

    - If not, act on the adjuster ''1 CH-POWER''(fig. 31) on the panel board and turn it to

    reach the desired value (clockwise to in-crease, or anticlockwise to reduce thepressure).

    - Then establish the pressure value corre-

    sponding to the required output.

    Example:

    Assuming that the heating system which is

    using a IVEN CTN 24 F boiler has a total ab-

    sorption of 17 kW. Using the graph ‘’A’’ in fi-

    gure 34 it is possible to determine the burner

    pressure, which will be:

    - 6,18 mbar if the boiler runs on natural gas

    - 20,5 mbar if the boiler runs on propan gas.

    - 16,3 mbar if the boiler runs on butan gas.

    Acting on potentiometer 1 - CH POWER set

    the pressure resulting from the diagram.

    GAS PRESSURE BURNER DIAGRAM CORRESPONDING TOTHE SYSTEMS OUTPUT

  • 29

    Service info

    2.9 FINDING CHART AND CORRECTIVE ACTIONS

    In the table of faults and corrective actions, we intend to give some technical informations related to the solution of faults wich can happen

    during the operation or the putting into operation.

    SOLUTIONS

    a) Replace the transformer

    b) Reconnect or replace the ignition leads

    c) Replace the electrode(s)

    d) Replace the electronic PCB

    a) Open the gas shut-off valve

    b) Plug the pluginto the gas train

    c) Adjust the pot.meter nr. 3 in a clock wise

    direction to increase in anticlockwise di-

    rection to decrease the gas quantity du-

    ring ignition.

    d) Replace the gas train

    a) Reconnect or replace the cable

    b) Replace the electrode

    c) Reposition the electrode

    d) Check the burner input at minimum rate

    e) Replace the electronic PCB

    a) Check the chimney and the combustion air

    intake grates

    b) Check the temperature sensor and ascer-

    tain that the pump is not blocked

    a) Check the good operation of the air pres-

    sure switch and replace if necessary..

    b) Reconnect or replace the silicone pipes.

    c) Check all the air/smoke ducts, clean or

    replace if necessary.

    d) Replace the fan.

    e) Replace the electronic PCB

    POSSIBLE CAUSES

    a) The ignition transformer is faulty

    b) The ignition leads are interrupted or discon-

    nected

    c) The ignition electrodes have the insulator

    broken or are in short circuit with earth

    d) The electronic board is faulty

    a) The gas shut-off valve is closed

    b) The plug to the gas train is not connected

    c) the soft light is incorrectly adjusted

    d) The gas train is faulty

    a) The detection electrode cable is faulty or not

    connected

    b) The detection electrode is broken inside the

    insulator (if only the insulator is broken does

    not matter)

    c) The detection electrode is in short circuit with

    earth

    d) The input at the minimum rate is not enough

    e) The PCB does not detected the flame

    a)* The chimney draught is not correct

    b) The H.L. thermostat has cut in.

    An over heating of the heat exchanger oc-

    currend.

    a)* The flue gas pressure switch is faulty.

    b)* The silicon pipes are disconnected or bro-

    ken.

    c)* There is insufficient combustion air suction

    or flue gas discharge.

    d)* The fan does not work.

    e)* The PCB is faulty

    BOILERS STATUS

    The boiler is in lock-out position and the red

    light G is on.

    INCONVENIENT:

    The burner does not ignite because there

    is no spark at the ignition electrodes

    After the removal of the fault’s cause press

    the reset button on the control panel to resto-

    re

    The boiler is in lock-out position and the red

    light G is on.

    INCONVENIENT:

    The burner does not ignite even if there isthe spark at the ignition electrode

    After the removal of the fault’s cause press

    the reset button on the control panel to resto-

    re

    The boiler is in lock-out position and the red

    light G is on.

    INCONVENIENT:

    The burner ignites for a few seconds andthen goes out

    After the removal of the fault’s cause press

    the reset button on the control panel to resto-

    re

    The boiler is in lock-out position and the red

    light G is on.

    INCONVENIENT:

    The boilers does not try to make the igni-tion procedure because:- The smoke thermostat has cut the cir-

    cuit (only for boilers Logamax U014 - Lo-

    gamax U014 K - Logamax U014 VMC - Lo-gamax U014 K VMC)- The H.L. thermostat has cut the circuit

    After the removal of the fault’s cause press

    the reset button L on the control panel to

    restore

    The boiler is in permanent lock-out.

    The red light G in on and the green light F isblinking

    INCONVENIENTS: The smoke pressureswitch did not give the permission for theburner ignition

    Reset from this status can be done by

    swtching OFF and ON the main switch A

    * These conditions are detected as ignition failure (vedi 2.10.3)

  • 30

    Service info

    1. Adjustment of maximumoutput in heating modeIt allows to adapt the boiler ou-

    tput to the actual C.H. needs by

    adjusting the burner pressure:

    By rotating the trimmer 1

    clockwise the pressure increases;

    By rotating anticlockwise the

    pressure decreases.

    2. Adjustment of the

    modulation currentAllows to adjust the minimum gas

    pressure

    THIS ADJUSTEMENTS MUSTBE CARRIED OUT SOLELY BYTRAINED TECHNICIANS

    To accede to the trimmer it is necessary to

    dismantle the electrical panel

    The uncontrolled adjustment of the pot.meter can jeopardize the correct opera-tion of the boiler

    WARNING The adjustments of the pot. meter 1-2-3 arecarried out by the constructor.

    3. Adjustment of the softlight

    Allows to adjust the burner

    pressure at the ignition time.

    1

    2

    3

    SOLUTIONS

    a) Check the status of the system

    b) Check the pump.

    a) Heat the boiler inside until the temperatu-re exceeds 2°C.

    b) Replace D.H.W. sensor.

    c) Reconnect or replace it.

    d) Set the correct pressure value.

    e) Reconnect it.

    f) Replace it.

    a) Check the D.H.W. system.

    b) Reconnect or replace it.

    c) Reconnect it.

    d) Replace it.

    POSSIBLE CAUSES

    a) Water does not circulate in the heating sy-stem. Pipes are blocked, the thermostatic val-ves are closed or the system gate valves areclosed.

    b) The circulation pump is blocked or is faulty

    a) The boiler may be frozen. (2.10.7)

    b) The D.H.W. sensor is faulty. (2.10.6)

    c) One or both temperature sensors are discon-nected or faulty. (2.10.5 or 2.10.6)

    d) There is insufficient water pressure in theC.H. system (2.10.2)

    e) The minimum water pressure switch isdisconnected.

    f) The The minimum water switch is faulty.

    a) There are insufficient pressure or flow rate inthe D.H.W. system.

    b) The flow switch sensor is disconnected orfaulty.

    c) The flow switch is disconnected.

    d) The flow switch is faulty.

    BOILERS STATUS

    The boilers is in permanent lock-out. The redlight G is off

    INCONVENIENT:The heating sensor detects a temperaturehigher than 81°C

    The reset is automatically done after the re-moval of the fault’s cause.

    The boiler is in permanent lock-out. The redlight G is off

    INCONVENIENTS:a) - The heating sensor detects atemperatur lower than 2°C

    b) - The D.H.W. sensor detects a tempera-tur higher than 62°C

    c) - The PCB does not detected the pre-sence of either or both temperature sen-sor

    d) - e) - f) The minimum water pressureswitch does not give the burner the per-mission to ignite.

    The boiler does not operate in D.H.W. mode

    INCONVENIENT:The D.H.W. flow switch does not operate

    * These conditions are detected as error codes (see 2.10.2 - 2.10.5 - 2.10.6 - 2.10.7)

  • 31

    Service info

    2.10 FAILURE CODES

    In case of failure the burner is automatically switched off, and the

    cobination of different LEDs on the panel board (E.F.G. see fig. 34)

    show the fault code.

    Each fault is characterised by a priority level: if different failures

    are detected at the same time, the code of the highest priority one

    is shown.

    The following failure codes are recognised:

    2.10.1 - LOCKOUT (priority 7)

    Description:

    Lockout of the flame control due to H.L. thermostat or smoke

    thermostat cut-off or loss of flame signal.

    2.10.2 - LACK OF WATER (priority 6)

    Description:

    Insufficient water pressure: intervention of minimum water pressu-

    re switch.

    2.10.3 - IGNITION FAILURE (priority 5)

    Description:

    No flame has been detected within 20" from the start of the ignition

    procedure and the burner control lockout has not intervened.

    2.10.4 - WRONG FLAME DETECTION (priority 4)Description:

    False flame has been detected at ignition start-up

    2.10.5 - CH TEMPERATURE SENSOR (priority 3)Description:

    CH sensor interruption or short circuit.

    2.10.6 - DHW TEMPERATURE SENSOR (priority 2)Description:

    DHW sensor interruption or short circuit. This failure is not de-

    tected if DHW mode is disabled.

    2.10.7 - FROST (priority 1)

    Description:

    Freezing of the heat exchanger is detected if CH sensor < 2°C;

    ignition in inhibited until CH sensor reaches 5°C.

    WARNING:

    If within the end of the ignition there is no flame detection the

    boiler goes into permanent lockout.

    To reset it will be necessary to push the reset button.

    � � �

    � � �

    � � �

    � � �

    � � �

    � � �

    � � �

    LED Status


Recommended