Installation, Operation and Maintenance Manual MAN-10-04-100-0720-EN Rev. 2 October 2019 Keystone EPI2 Logic Board Firmware Upgrade Programmer ICD-U64 Procedure
Transcript
  • Installation, Operation and Maintenance Manual MAN-10-04-100-0720-EN Rev. 2

    October 2019

    Keystone EPI2Logic Board Firmware Upgrade Programmer ICD-U64 Procedure

  • I

    Installation, Operation and Maintenance Manual MAN-10-04-100-0720-EN Rev. 2

    Table of ContentsOctober 2019

    Table of Contents

    Table of Contents

    Section 1: Firmware Upgrade 1.1 Tools ............................................................................................................. 11.2 ICD-U64 Programmer Preparation ................................................................ 31.3 Firmware Update .......................................................................................... 41.4 Firmware Upload ........................................................................................... 41.5 Actuator Settings Checklist ......................................................................... 16

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    Section 1: Firmware Upgrade This procedure details how to program firmware on the logic board for the EPI2 Actuator using the ICD-U64 Programmer.

    1.1 Tools

    WARNINGInstallation, configuration, commissioning, maintenance, and repairs must be performed by approved and qualified personnel only.

    NOTICECertain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of "safe use", installation, and maintenance. These special instructions are in addition to and may override the standard installation procedures. Special instructions are listed by approval type.

    To update the firmware of EPI2 actuators, the following tools are necessary:

    • PC with program CSSLOAD-CCS Programmer Control Software installed (Figure 1). This software can be downloaded from: http://www.ccsinfo.com/content.php?page=ccsloadsw

    • PC with USB Drivers for all CSS programmers/debuggers

    • Firmware “F02_63_125_v3_11.X.production”, for models E006, E013 or latest revision

    • Firmware “F02_250_500_v4_12.X.production”, for models E025, E051, E091, E171 or latest revision

    • The Universal programmer ICD-U64 (Figure 2)

    • Logic Board or Actuator

    • Cable from the ICD-U64 to the processor card firmware programming connector part number: VA001-692-15

    Figure 1

    1

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    Figure 2 ICD-U64 CCS Programmer

    Figure 3 EPI2 Logic Board

    Table 1. Programming Connector Pinout

    Signal ICD-U64 Pinout EPI2 Logic Board J15Real Time Debugging Pin 1

    ICSP Clock Pin 2 Pin 5ICSP Data Pin 3 Pin 4

    GND Ground Pin 4 Pin 3VDD Power Pin 5 Pin 2

    MCLR Pin 6 Pin 1

    2

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    1.2 ICD-U64 Programmer Preparation

    The ICD-U64 Programmer has an internal jumper to select multiple options to power the target board (actuator logic board).

    1. ICD-U64 programmer internal jumper selecting 5V

    This configuration allows the ICD-64 Programmer to provide power to the logic board. This configuration can be used to program the logic board as standalone board or to program the logic board while installed in the actuator. The firmware upgrade of the logic board should be successful regardless if the logic board is powered from the actuator power supply or ICD-U64 programmer.

    2. ICD-U64 no jumper

    The ICD-U64 internal jumper is not present or was set to no power the target board. It's not possible to upgrade firmware in the logic board as a standalone board since no power is being supplied to the target board. If the logic board is installed in the actuator, the actuator requires to be powered on to have a successful firmware upgrade. Note that a new programming tool will likely have this no voltage setting.

    3. ICD-U64 programmer internal jumper selecting 3.3V

    This option must not be selected, it is not applicable for the EPI2 Actuator.

    3

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    1.3 Firmware Update

    After downloading the new firmware, the actuator settings will return to their default values. As such, the settings in place prior to the firmware download will need to be set again. For this reason, be sure to store the actuator settings (e.g. opening speed, closing speed, % opening torque, % closing torque). Refer to Section 6.2 (Local Configuration of the EPI2) in the actuator IOM for details. To be clear, all settings will be returned to the factory default values, it is necessary to reset the open/close travel limits; also, the motor will default to the smallest size.

    If not correctly reset the unit will alarm in open torque.

    OM1 settings are not required to be reset because they are unaffected by the processor card firmware flash.

    1.4 Firmware Upload

    This procedure is based on the CCS Inc. CCSLOAD ICD-U64 programming tool- This tool can power the microprocessor from the USB port of the PC, using the 5V setting and also from the actuator, using the actuators power source. The microprocessor to be flashed is referred to as the “target”. Take care that the target is only powered from one source, not both.

    In some field installations is difficult to remove power from the actuator, this procedure provides instructions in how to download firmware without removing the power from the actuator, therefore instructions in the procedure must be followed to avoid any damage to the actuator or any personal injury.

    1. It is necessary to identify the position of the jumper inside the ICD-U64 programmer before downloading firmware as indicated in step 1.2.

    2. To program the logic board as standalone board, connect the ICD-U64 programmer as shown in the picture and proceed in step 9.

    4

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    3. To program the logic board as part of an actuator with no OM1 board present, carefully connect the ICD-U64 programmer as shown in the pictures and proceed in step 9.

    Figure 4

    4. To program the logic board as part of an actuator with an OM1 board present, and the actuator is powered ON.

    CAUTIONAccessing the electronics compartment while the actuator is in service exposes the technician to lethal voltage and possibly from more than one source.

    Set the OM1 switch SW4 in ON position, it will prevent the actuator from stroking during firmware download, and it will allow to maintain the actuator in the last position requested by the 4-20mA or the 0-10V loop control.

    Switch SW4 inON position

    5

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    5. Note the position then remove the yellow position indicator to allow the OM1 board to be slightly moved to the side and have access to the programming connector found in the actuator logic board.

    6. Carefully remove the 4 screws that are holding the OM1 board. If the actuator is in vertical position, there is a risk of dropping the screws inside the actuator. Dropping the screws inside the actuator could cause a short circuit if the screws drop in the power board, or a damage of the gears if the screws drop in the gears section.

    OM1 board screws

    6

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    7. Once all the screws have been removed, carefully place an insulator material underneath the OM1 board to protect the board from the metal spacers contacting the circuit board shorting the board or I/O's to ground. Place the OM1 board slightly to the front to allow access to the programming connector in the actuator logic board.

    Insulator

    Programming connector

    7

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    8. Carefully connect the ICD-U64 programmer. Make sure no to touch any electrical contact.

    Programming cable

    9. Double click on CCSLOAD icon (Figure 1) to open programmer application (Figure 5).

    Figure 5

    8

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    10. Select Device.

    Figure 6

    11. Verify the correct firmware for the size and model of the actuator.

    Table 2.

    Actuator Size Firmware063/E006 F02_63_125_v3_11.X.production.hex125/E013 F02_63_125_v3_11.X.production.hex250/E025 F02_250_500_v4_12.X.production.hex500/E051 F02_250_500_v4_12.X.production.hex

    1000/E091 F02_250_500_v4_12.X.production.hex2000/E171 F02_250_500_v4_12.X.production.hex

    9

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    Figure 7

    12. Load the *.hex file to the CCS Device Programmer.

    Figure 8

    10

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    13. Verify in the left window (File) of the CCS Device Programmer Screen shows the correct Target Chip as the right window (Target Chip). If the Target Chip field is empty, close the application and reopen, the Target Chip will be populated once the correct file name is loaded.

    Figure 9

    11

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    14. Erase chip. Verify the entire chip is erased without errors.

    Figure 10

    12

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    15. Verify that the chip is blank.

    Figure 11

    13

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    16. Write to chip. Verify that the programming is complete and without errors. The programming is now finished. The programming should take less than 30 seconds. Remove the programing cable.

    Figure 12

    17. If no OM1 board is present, proceed with step 22.

    18. Carefully remove the insulator material from underneath the OM1 board that protected the board from the metal spacers.

    19. Place the 4 screws back to the OM1 board. If the actuator is in vertical position, there is a risk of dropping the screws inside the actuator. Dropping the screws inside the actuator could cause a short circuit if the screws drop in the power board, or a damage of the gears if the screws drop in the gears section. Carefully replace the yellow position indicator, ensuring the indicator fingers properly engage the position sensor.

    20. Set the actuator parameters as per the IOM Manual section 6.2 Local configuration of the EPI2 and section 1.5 Actuator Settings Checklist of this document. This is critical for proper operation on the actuator.

    14

    Section 1: Firmware Upgrade

  • October 2019

    Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2

    Firmware Upgrade

    21. Return the switch SW4 to the OFF position- the actuator will immediately start stroking if the new position request is different from the position before programming the actuator.

    Switch SW4 in OFF position

    22. Fill the label with the date, firmware version and technician initials, then place the label on top of the motor.

    23. Place the label indicating the firmware upgrade outside the actuator.

    24. Refit the electronics enclosure cover actuator and verify correct operation.

    15

    Section 1: Firmware Upgrade

  • Installation and Maintenance InstructionsMAN-10-04-100-0720-EN Rev. 2 October 2019

    Firmware Upgrade

    1.5 Actuator Settings Checklist

    The actuator settings will be returned to default values after a firmware upgrade. To ensure the proper operation of the actuator the settings must be configured as referred in the IOM Manual paragraph 6.2, Local Configuration of the EPI2 and 6.2.1 EPI2 default general configuration. The OM1 board settings are not affected by the firmware upgrade and it is not necessary to perform any setting changes if the OM1 is configured properly for the application.

    Collect the actuator technical information

    Date

    Technician Name

    Model

    Size

    Serial Number

    Firmware Version

    External Label ID

    Access actuator per Instructions

    Upload Firmware

    Place internal label on the motor

    Verify Actuator Settings

    Set motor parameter

    Set Close limit

    Set Open limit

    Set L/S close by position or torque

    Set L/S open by position or torque

    Closing speed

    Opening speed

    % Closing torque

    % Opening torque

    Direction CW/CCW

    Actuator Size/Motor setup

    Blinker / Local Selector

    Heater

    Inversion colors LED of local control

    Place external label on the actuator

    Stroke actuator open and close a minimum of 3 times, to verify proper cycling and indication

    Replace electronics compartment carefully, noting the indicator/window alignment.

    16

    Section 1: Firmware Upgrade

  • For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at [email protected]

    World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:

    NORTH & SOUTH AMERICA 19200 Northwest FreewayHouston TX 77065USAT +1 281 477 4100

    Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105BrazilT +55 15 3413 8888

    ASIA PACIFIC

    No. 9 Gul Road#01-02 Singapore 629361T +65 6777 8211

    No. 1 Lai Yuan RoadWuqing Development AreaTianjin 301700P. R. ChinaT +86 22 8212 3300

    MIDDLE EAST & AFRICA P. O. Box 17033Jebel Ali Free ZoneDubaiT +971 4 811 8100

    P. O. Box 10305Jubail 31961Saudi ArabiaT +966 3 340 8650

    24 Angus CrescentLongmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5South AfricaT +27 11 451 3700

    EUROPE

    Holland Fasor 6Székesfehérvár 8000HungaryT +36 22 53 09 50

    Strada Biffi 16529017 Fiorenzuola d’Arda (PC)ItalyT +39 0523 944 411

    www.emerson.com

    ©2019 Emerson. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are property of their respective owners. The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.