For Technical Support: www.panduit.com/resources/install_maintain.asp Page 1 of 2 INSTALLATION INSTRUCTIONS © Panduit Corp. 2015 PN307K ** Denotes color. 1" (25.4mm) 1 {Not to scale} DO NOT BEND CABLE! “TOP” CGJT 8 Note: Bending the cable may cause conductors to become unsecured and termination to fail. Keep cable straight. Verify conductors are visible and secured in place. Mini-Com TX5e and TX6 PLUS UTP Jack Modules Part Numbers: CJ5E88T**, CJD5E88T**, CJ688TP**, CJD688TP**, KJ688TP** 2 T568B T568A A B Wiring sequence 3 1 3 2 4 4 T568B T568A 3 2 4 1 6 8 7 5 5 T568B T568A 6 8 7 5 Follow order carefully so wires overlap properly in the next step. ! 9 10 6 T568B T568A Blue/white wire should overlap and be parallel to green wire as shown. Blue/white wire should overlap and be parallel to orange wire as shown. 9 10 ! ! CWST 7 T568B T568A Ensure conductors are secure in slots before cutting flush with cap.
Transcript

For Technical Support: www.panduit.com/resources/install_maintain.aspPage 1 of 2

INSTALLATION INSTRUCTIONS © Panduit Corp. 2015 PN307K

** Denotes color.

1"(25.4mm)

1

{Not to scale}

DO NOT BEND CABLE!

“TOP”

CGJT

8 Note: Bending the cable may cause conductors to become unsecured and termination to fail.

Keep cable straight. Verify conductors are visible and secured in place.

Mini-Com TX5e and TX6 PLUSUTP Jack Modules

Part Numbers: CJ5E88T**, CJD5E88T**, CJ688TP**, CJD688TP**, KJ688TP**

2 T568B T568A

A

B

Wiring sequence

3

13

24

4 T568B T568A

3

24

1

6

8

75

5 T568B T568A

6

8

75

Follow order carefully so wires overlap properly in the next step.

!

9

10

6 T568B T568A

Blue/white wire should overlap and be parallel to green wire as shown.

Blue/white wire should overlap and be parallel toorange wireas shown.

9

10

! !

CWST

7

T568B

T568A

Ensure conductors are secure in slots before cutting flush with cap.

E-mail:[email protected]

Phone: 866-405-6654

For Instructions in Local Languagesand Technical Support:

www.panduit.com/resources/install_maintain.asp

Page 2 of 2

INSTALLATION INSTRUCTIONS © Panduit Corp. 2015 PN307K

www.panduit.com

87654321

7 8

4 65 3

2 1

87654321

7 8

4 65 3

2 1

Wiring Sequences

T568A1 8

Pin #’s

T568B

Notes:

1. For specified performance, follow ANSI/NECA/BICSI-568-2006 installation guidelines.

2. Jack modules can terminate PVC or Plenum rated 22-24 AWG solid or stranded IWC cable with insulated conductor outside diameter ranging between 0.035 inch (0.88mm) and 0.048 inch (1.2mm).

3. Jack modules may be re-terminated a minimum of 10 times.4. For technical and performance information, consult Panduit Technical

Support.

As with all Wiring Accessories, the following statements apply:

1. Never install communications wiring during a lightning storm.2. Never install communications wiring in wet locations unless the jack is

specifically designed for use in wet locations.3. Never touch uninsulated communications wiring or terminals unless the

communication line has been disconnected at the network interface.4. Use caution when installing or modifying communication wiring.

2

TERMINATION CAP REMOVAL

1 3

4 5

JACK MODULE INSTALLATION / REMOVAL

12

2

3

Mini-Com style jack modules Keystone style jack modules

1

1

2

23

INSTALL REMOVEINSTALL REMOVEDepress latch on module

For Technical Support: www.panduit.com/resources/install_maintain.aspPage 1 of 1

INSTALLATION INSTRUCTIONS © Panduit Corp. 2015 PN580A

1

1"(25.4mm)

{Not to scale}

Termination for Right Hand Lay Cable

2 T568B T568A

A

B

Wiring sequence

4 T568B T568A

1

2

4

32

14

3

3

8

6

75

5 T568B T568A

8

6

75

Follow order carefully so wires overlap properly in the next step.

!

9

10

6 T568B T568A

Green/white wire should overlap and be parallel to blue wire as shown.

Orange/white wire should overlap and be parallel toblue wireas shown.

9

10

! !

DO NOT BEND CABLE!

“TOP”

CGJT

8 Note: Bending the cable may cause conductors to become unsecured and termination to fail.

Keep cable straight. Verify conductors are visible and secured in place.

CWST

7

T568B

T568A

Ensure conductors are secure in slots before cutting flush with cap.


Recommended