+ All Categories
Home > Documents > MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal...

MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal...

Date post: 22-Mar-2018
Category:
Upload: vanliem
View: 223 times
Download: 7 times
Share this document with a friend
16
MV Air Insulated Metal Enclosed Switchgears Nature is Our Most Valuable Partner Rated Voltage : 12 kV - 38.5 kV Rated Current : 400 A - 1250 A Short Circuit Current : 16 kA - 25 kA Standard IEC 62271-200
Transcript
Page 1: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

MV Air InsulatedMetal EnclosedSwitchgears

Nature isOur Most

Valuable Partner

Rated Voltage : 12 kV - 38.5 kVRated Current : 400 A - 1250 AShort Circuit Current : 16 kA - 25 kA

Standard IEC 62271-200

Page 2: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

MV Air InsulatedMetal EnclosedSwitchgears

Page 3: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

Some of other main products are; MV-HV CTs, VTs, Fuses, and Lighting Fixtures. All of ourproducts have type test reports from CESI (Italy), KEMA (Holland), IPH (Germany) and ICMET (Romania). By developing its own technology considering quality importance, Elimsan became one of

transmission and distribution systems. Since last 29 years, more than 100.000 units of these equipments had beenmanufactured and distributed over all Turkey and world. They are all under operation satisfactorily since their assembly Elimsan has a very large land more than 550.000 sqm and 50.000 sqm closed facilities. All of our equipments are manufactured with CNC controlled workbenches under the ISO 9001 Quality Management System and ISO 14001 Environmental Management System. Our products are tested in our accredited High Voltage Laboratories according to ISO 17025 standards.

Since the establishment date, Elimsan always produces advanced technology along the Turkey’sdevelopment process; represents our country successfully, challenges in competitive international market conditions. Its products are preferred on wide geographical areas from Australia to Estonia, from Far East to South America. In the year of 2008 Elimsan has signed a partnership agreement with Saudi Cable which is on of the

Elimsan is a creative, innovated and dynamic company. We respect and pay much attention to communicate and interact with our clients; and meeting each customer’s needs is our number one priority.

3

Brief History Of Company; Elimsan

for manufacturing electrical switchgears and switching devices.

ELIMSAN is a specialist company in the electrical switchgears production for the range 7,2 kV – 525 kV. We have a very big capacity for the production of SF6 Gas and Vacuum Circuit Breakers (10000 pcs./year), Metal Enclosed Switchgears (3000 panels/year), Metal Clad Switchgears (1500 panels / year), High Voltage-Disconnectors (3000 units / year).

Page 4: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

4

Elimsan TG21-XX designation covers medium voltage cubicles or prefabricated systems with SF6 or vacuum

switchgears TG21-XX type suitable for:

Small substations for private usersMV- LV public distribution substationsMedium voltage metering substationsNetwork substations and industrial applicationsMotor control centers with vacuum contactors

These switchgears permit carry out all the functions that could be presented, so much in the networks of electrical energy distribution and transformer centers.

Operations of development, such as to break in no-load of the ring networks or radial networks.Disconnecting with earthing of the active parts, to effect periodic maintenance.Protection of power transformers for overloads and short circuits.Troubleshooting in cables and monitoring the phases conformity before making of cloosed- loops.

STANDARTS The switchgears have been developed and tested according to the following procedures:

IEC 62271-200. A.C. Metal-Enclosed Switchgear and ControlgearIEC 62271-100. High-voltage circuit breakersIEC 60265-1. High-voltage switchesIEC 60420. High-voltage alternating current switch-fuse combinations.IEC 62271-102. High-voltage disconnector and earthing switchs.

PROTECTION DEGREELoad Break Switch : IP68Busbar Compartment : IP3XBetween Compartment : IP3XMechanisms : IP3XCable Compartment : IP3X

Switchgear in service:

Being in service with the switch closed, to access to the interior of the switchgear, it’s necessary to accomplish the following operations:

Open the switch.Verify the absence of tension in the cables by means of the neon lamps of voltage indicators. Close the earthing-switch.Open the door.

Switchgear out of service: To open the door previously earthing switch must be closed. In this position:

The switch can not be closed.The earthing switch can not be opened.

Page 5: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

EXAMPLE 1

Distribution feeder with measuring and protection

Exist a double interlock:

Among the Load Break Switch and the earthing switchAmong the Load Break Switch, the earthing switch and the door.

To accomplish the measure in cables will can be get, by a wiling action, realising the interlocks using an

This equipment prevents closing of the door and, before closing it have to be removed, remaining the interlocks in its initial position.

To prevent that someone could operate the switchgear, while are effected the measurements in the cables, exits a safety device that prevents the introduction of the operating lever.

Limited overall dimensions:The switchboards can be installed in small rooms and be leaned against the wall. All the operations are carried out at the front of the switchboard.

Service continuity:The segregations of the various compartments allow to operate when switchboard alive to re-placecomponents such as fuses, relays, cable terminals, etc.

Safety:Suitables mechanical and key locks, guarantee the safety of personel, prevent-ing from any possibility of wrong operations. The metal segregations between the bus-bar compartment and the instruments compartment, prevents accidental contacts with medium voltage components. The switchboard is provided with grounding of the whole structure and components.

Inspection and maintenance:Inspection of the equipment is facilitated by porthole placed on the unit door and the maintenance is simple by the easy access to equipment with open door.

Construction characteristics and painting:The structural steelwork is made of bent and bolted sheet plate, painting with electrostatic powder colour RAL7032.

5

Page 6: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

6

The busbar insulating supports are integral with the switchgear (switch or disconnector)

The busbars consist of:Aluminium or copper bar for 400A and 630A

conventional crew/spring washer attachment. The connection screw is covered by a stress cap.

The front access is elosed by a bolted plate with a yellow warning plate.

EXAMPLE 2 EXAMPLE 3Customer Measurement and Distrubution CenterTransformer Protection System

Load Break Switch cubicles and off-load disconnector cubicles: The lower part of the switch and of the

clips.Transformer protection cubicles: Connection is made at the fuse lower supports.Circuit Breaker cubicles: connection is made on a support lug mounted on the capacitor dividers.

The reduced depth of the cubicles results in the last phase being within arm reach, and this greatly facilitates cable installation.For easier work, a stud enables the operator to hook up the cable end clip during the connection operation.

EARTHING SWITCHESIn generally Elimsan switchboards have two simultaneously operated earthing switches. The station earth bar is situated on the cubicle top. The station is connected to earth by means of a contact stud on the forward part of the side partition.

The lower part of cubicles houses standardized for fuses. During fuses changing the operator’s safety is ensured by two earthing switches.

Capacitor bank protection:

Page 7: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

7

Circuit Breaker Compartment

Motor protection:Within the limit of 3 starting per hour, each of a duration of 10 seconds and with Id/ln < 6 (Id = starting current and In = motor rated current), use fuses with a rated current immediately superior to 3 times the motor rated current.

Safety is a constructional feature at the switchboards. During the internal arc fault the gases are directed intothe rear vent, thus preserving the safety of the operator standing in front of the cubicle.

Tests have demonstrated the absence of dangerous distortions or projections of elements in way of the station front panel.

DISCONNECTOR MONITORINGThe disconnector control is shown on the mimic diagram by the position of a rod directly coupled to the control shaft carrying the contacts without any intermediate linkage. This provides a fail safe indication of the position (open or closed) of the switch.

VOLTAGE MONITORINGVoltage presence or absence is shown by means of neon indicator lights connected to the capacitor dividers

possible to check the phase sequence of two adjacent panels in a fail safe way, as shown on the sketch opposite.

Correct phase sequence: Presence lights on. Test light off.

Incorrect phase sequence: Presence lights dimming. Test light on.No voltage condition without test light. Light off.

Checking that cables which are not live is of major importance prior to closing the earthing switch.Hence the feature of the neon lamp which is a fail safe system to indicate live cables.

OPTIONAL ACCESSORIESShunt opening releaseGearmotor for spring chargingAuxiliary contactsAdditional key locks

Digital protective relaysIndicating metering insturmentsCurrent transformersVoltage transformers

Disconnector and Earthing Switch Control Panel

DATA DEFINING THE SWITCHBOARD

Single-line diagramLayout of the switchboard, relative position of the vairous unitsRated and service voltageFrequencyShort-circuit current at service voltageRated currentSupply voltage for auxiliary servicesInstallation ambientSwitchboard accessories

Page 8: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

8

TYPES DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12

TG21-01 X X

TG21-02 X X X X X X

TG21-02V X X X X X X

TG21-03 X X X X

TG21-04 X X X X

TG21-04V -NECTOR X X X X

TG21-05 X X X X X

TG21-05V X X X X X

TG21-07 X X X X X

TG21-11 X X X X

TG21-13 X X X X X

TG21-14 X X X X

TG21-15 X X X

TG21-16 X X X X X

TG21-17 X X

TG21-18 X

TG21-19 X X

TG21-22 X X

TG21-27 X X X X X X X

TG21-27V X X X X X X X

1 Disconnector Switch

2 Load Break Switch

3 SF6 Circuit Breaker

4 Vacuum Circuit Breaker

5 Current Transformer

6 Voltage Transformer

7 Protection relay

8 Capacitive Voltage Divider

9 Fuses with 3P Tripping

10 Fuses without 3P Tripping

11 Earthing Switch

12 Bushing Insulator

Page 9: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

9

General 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated voltage 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated withstand voltage 50-60 Hz. 1min. 28 kV 38 kV 50 kV 70 kV 80 kV

Rated withstand voltage across isolating distance 50-60 Hz 1min 32 kV 45 kV 60 kV 80 kV 95 kV

Rated impulse withstand voltage 1.2 / 50µs 75 kV 95 kV 125 kV 170 kV 180 kV

Rated impulse withstand voltage across isolatingdistance 1,2 / 50µs 85 kV 110 kV 145 kV 195 kV 195 kV

Rated current of transformer feeder 400/630/1250A 400/630/1250A 400/630/1250A 400/630/1250A 400/630/1250A

Atmosphere conditions -5/+50 C° -5/+50 C° -5/+50 C° -5/+50 C° -5/+50 C°

Load Break Switch 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated mainly active load breaking current 400 A 400/630 A 400/630 A 400/630 A 400/630 A

Rated closed-loop breaking current 400 A 400/630 A 400/630 A 400/630 A 400/630 A

Rated cable-charging breaking current 25 A 25 A 25 A 25 A 25 A

Rated no-load transformer breaking current 10(16) A 10(16) A 10(16) A 10(16) A 10(16) A

Rated short-circuit making current (peak) 40 kA 40/50 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA

Rated short-time current 1s (rms) 16 kA 16/20 kA 16/20/25 kA 16/20/25 kA 16/20/25 kA

switch 20 C° 0.5 Bar 0.5 Bar 0.5 Bar 0.5 Bar 0.5 Bar

Earthing Switch 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Rated short-time current, 1s (rms) 16 kA 16/20 kA 16/20/25 kA 16/20/25 kA 16/20/25 kA

Rated short-circuit making current (peak) 40/50 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA 40/50/63 kA

Fuses (Striker fuse units according IEC 60282) 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Dimensions (Medium Type) 292 mm 442 mm 442 mm 537 mm 537 mm

Maximum power dissipate value 75 W 75 W 75 W 75 W 75 W

Main Dimensions 12 kV 17.5 kV 24 kV 36 kV 38,5 kV

Height (mm) 1950 1950 1950 2250 2250

Wide (mm) 750/500/375 750/500/376 900/500 1150/1000/750 1150/1000/750

Depth (mm) 1000 1000 1000 1400 1400

Page 10: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

10

Page 11: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

11

Page 12: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

12

Elimsan Medium VoltageCircuit Breaker

Elimsan Voltage Detector Systems

Elimsan Medium Voltage Fuses

Elimsan Medium Voltage Voltage Transformers

Elimsan Medium Voltage Current Transformers

Elimsan Medium Voltage Earthing Switches

Page 13: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

13

LEGEND

Page 14: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

14

EQUIPMENT VOLTAGE POWER CONTACTQUANTITY

Motor 24,48,110,VDC 340 W

4NO + 4NC,6NO + 6NC 8NO + 8NC

Tripping Coil 24,48,110,VDC 80 VA

Closing Coil 24,48,110,VDC 80 VA

Auxiliary Switch 10 A -220VAC

TG21-13-36 Metering With Load Break Switch

TG21-01-36 Incoming and OutgoingWith Load Break Switch

TG21-02-36 TransformerProtection With CB and CT

TG21-14-24 TransformerProtection with LBS

TG21-01-24 Incoming and OutgoingWith Load Break Switch

TG21-02-24 TransformerProtection With CB and CT

Page 15: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

TG21-XX Metal Enclosed cubicles are produced according to the latest standards and norms as the following.

TG21-XX Metal Enclosed cubicles have been designed to meet the requirements of international standards (IEC), and validated by type tests, caried out by independent laboratories. These independent laboratories are as follows:

IEC 62271-100IEC 62271-102 IEC 62271-200IEC 60265-1IEC 60420

The following routine test are carried out before the

switchgear are submitted to customer.

15

Page 16: MV Air Insulated Metal Enclosed Switchgearsencoenergy.com.vn/admin/webroot/upload/image/files/Metal Enclosed... · MV Air Insulated Metal Enclosed Switchgears Nature is Our Most ...

Not

e : E

limsa

n’s

polic

y is

con

tinuo

us d

evel

opm

ent a

nd im

prov

emen

t. Th

eref

ore

the

right

is re

serv

ed to

sup

ply

prod

ucts

whi

ch m

ay d

iffer

in d

etai

l fro

m th

ose

desc

ribed

and

illu

stra

ted

in th

is p

ublic

atio

n.

Elimsan Switchgear Equipmentand Electromechanics Industryand Trade, Inc.

Tel : 90 262 375 23 60Fax : 90 262 375 23 [email protected]@elimsangroup.comwww.elimsangroup.com


Recommended