Today s technology involves sensitive electronic equipment which you depend upon for systems reliability. Your valuable electronic systems will experience unpredictable and potentially destructive power quality conditions such as lightning and transients which cost your business maintenance time, equipment replacement and customer dissatisfaction. Our I2R ICP Series features our proprietary silicon avalanche suppressor diode (SASD) technology for effective safeguarding and maximized performance of your systems. In addition, it provides remote status monitoring and plug-in modules. Your success demands a superior protection solution provided by Transtector Systems. Telecom Power Systems Communications Hubs, Nodes Digital Loop Carries Cabinets/Load Centers Din Rail Mounts Solar & Turbine
Transcript

Today s̓ technology involves sensitive electronic equipment which you depend upon for systems reliability. Your valuable electronic systems will experience unpredictable and potentially destructive power quality conditions such as lightning and transients which cost your business maintenance time, equipment replacement and customer dissatisfaction. Our I2R ICP Series features our proprietary silicon avalanche suppressor diode (SASD) technology for effective safeguarding and maximized performance of your systems. In addition, it provides remote status monitoring and plug-in modules. Your success demands a superior protection solution provided by Transtector Systems.

• Telecom Power Systems

• Communications Hubs, Nodes

• Digital Loop Carries

• Cabinets/Load Centers

• Din Rail Mounts

• Solar & Turbine

208.772.8515 800.882.9110 FAX 208.762.613310701 N. Airport Road, Hayden, ID 83835

www.transtector.com [email protected]

An ISO 9001:2000 and 14001 Certified Company

Configurations

1452-011 Rev.B

Features• 100% silicon suppression

• Plug-in suppression modules with status indicators

• Designed to standard 35mm DIN Rail profile and compact footprint

• Mountable without DIN Rail

• Remote status monitoring capability

• UL and CSA approved and designed to meet IEC specifications

I2 R IC

P Se

ries -

DC

* Voltage protection level determined at 6kV 500A.

Nominal Service

Protection Levels*

Current Ratings

Part Number

12V 24V 48V

36V 58V 90V

2kA 2kA 2kA

1101-624 1101-625 1101-626

Operating Temperature

Response Time (Max.)

-30 º C to +65 º C

<5 Nanoseconds

Dimensions2.6”H X 1.09”W X 2.64”L6.6 cm X 2.8 cm X 6.7 cm

WarrantyFive (5) year unconditional warrantyTen (10) year manufacturer warranty

I2R ICP Series - For IEEE Locations A and B Per C62.41-19911. Warning! Disconnect power upstream from the device when wiring to avoid potential shock hazard. Unit must be installed within an enclosure. It is recommended that a 15 or 20A current limiting fuse be installed in series with each I2R ICP. Example Bussmann KTK 15 or KTK 20.

2. Mounting the I2R ICP Series2.1 35 mm DIN Rail Mount (see Figure 3)2.2 Screw Mount (see Figure 4)

3. Wiring the I2R ICP Series: Unplug Suppressor Module frombase. Install 4-14 AWG into base per Figure 1 or 2 keepingleads as short as possible.

4. Insert Suppressor Module into Base Unit.

5. Optional Wiring for Remote Status Indication (see Figure 4)*5.1 Use test plug included in packaging.*5.2 Wire with respect to opposite rail as indicated by voltage potential in Figure 4.5.3 Maximum continuous current for remote status not to exceed .5A.

6. Turn power on. LED illumination indicates power is supplied and suppression is enabled.WARNING!!! REMOTE STATUS CONTACT IS ENERGIZED. LIVEELECTRICAL POWER EVEN WITHOUT LED ILLUMINATION.

InstallationMOUNTING OPTION

Figure 1Base Unit

������

������

L

Common

DC

Figure 1

+

-

Low Voltage VAC

Figure 2

I R ICP2

I R ICP2

REMOTE STATUS

Typical Application

Figure 4Suppressor Module

Remote StatusIndication Plug

Remote LampIndicator

On = ProtectedVoltage PotentialOutput Plug Included

Single Phase Wiring Diagrams

Multiple Unit Wiring Diagrams


Recommended