    REFERENCE GUIDE

    NPU Unit

    Mains decoupling relay

    Installation and Operation Instructions

    Software version 2.0

  • 7/28/2019 NPU 2.0 Reference Guide

    2/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 2

    1. Contents

    1. Contents..................................................................................................................................................22. Technical Specification ...........................................................................................................................3

    NPU Technical Specification.......................................................................................................................4NPU Mechanical Design .............................................................................................................................5

    3. Installation...............................................................................................................................................6Power Supply ..............................................................................................................................................6Analog Inputs ..............................................................................................................................................6Output Relays..............................................................................................................................................6The NPU Unit Wiring Diagram ....................................................................................................................7

    Connection NPU Unit to phase-to-neutral voltage..................................................................................7Connection NPU Unit to phase-to-phase voltage...................................................................................8

    4. Function ..................................................................................................................................................9Protection types...........................................................................................................................................9Overvoltage protection............................................................................................................................9

    Undervoltage protection..........................................................................................................................9Overfrequency protection........................................................................................................................9Underfrequency protection....................................................................................................................10Voltage asymmetry protection ..............................................................................................................10Vector shift supervision.........................................................................................................................10

    Phase sequence supervision ....................................................................................................................11Frequency measurement ..........................................................................................................................11Internal watchdog......................................................................................................................................11Output Relays............................................................................................................................................11Example: Evaluation of under voltage protection, B3=0...........................................................................14Vector Shift Protection...............................................................................................................................15

    5. Settings .................................................................................................................................................17Buttons ......................................................................................................................................................17Display and LEDs......................................................................................................................................17Parameters settings ..................................................................................................................................17

    6. Displayed Quantities and Parameters ..................................................................................................18Set A:.........................................................................................................................................................18

    Default setting .......................................................................................................................................19Set B:.........................................................................................................................................................20

    Default setting .......................................................................................................................................217. Order codes ..........................................................................................................................................22

  • 7/28/2019 NPU 2.0 Reference Guide

    3/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 3

    2. Technical Specification

    The NPU unit is designed for 3-phase mains protection. The operator can switch on/off availableprotections or adjust limits and time delays for each protection. The operator can also select one of twofunctions of output relays.Rated voltages are 100, 230, 400, 480 VAC selected by order - see order codes. Measuring voltagefrequency range is from 44 up to 68 Hz.NPU power supply voltage can be in the range 90 250 VAC or 16 110 VDC selected by order - seeorder codes.

    NPU offers following protections:

    Over frequency protection f>, f>> Under frequency protection f> Under voltage protection U

  • 7/28/2019 NPU 2.0 Reference Guide

    4/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 4

    NPU Technical Specif ication

    Parameter Specification

    Dimensions 75 x 100 x 115 mm

    Power supply

    NPU FUV/YYY/230VAC

    NPU FUV/YYY/24VDC

    90 250 VAC

    16 110 VDC

    Power consumption c. 3 W

    Insulation 4 kV

    Elmg. Interference immunity According to IEC 50082-2

    Elmg. Interference According to IEC 55022

    Temperature range -20 +70C

    Protection IP20

    Rated voltage 100, 230, 400, 480 VAC (by the order)

    Maximal voltage range Rated + 30 %

    Rated frequency 50 / 60 Hz

    Maximal frequency range 44 68 Hz

    Accuracy of frequency measuring 0,2% from rated value (from 10% of rated voltage value)

    Accuracy of voltage measuring 1% from rated value at rated frequency 10% and 25C

    1,5% over whole temperature range

    Signal relay contacts

    - max. switched voltage / current

    - max. switched power

    - rated voltage / current

    - minimum load

    - lifetime

    250 V / 4 A

    resistive load: 1000 VA AC, 200 W DC

    inductive load: 500VA AC, 25W DC

    resistive load: 250V / 4A AC

    200V/0,1A DC, 24V 4A DC

    inductive load: 250V / 2A AC

    200V/0,1A DC, 24V 3A DC

    1W / 1VA at Umin > 10V

    1x105 cycles

    Overvoltage category Class. III

    Time delay accuracy 0.2% +030ms

  • 7/28/2019 NPU 2.0 Reference Guide

    5/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 5

    NPU Mechanical DesignThe NPU is packaged in a plastic box for assembly on a mounting plate TS 35 (DIN rail 35 mm).NPU could be also mounted with two screws M4 (with span 60mm) to a mounting board. For thisalternative it is necessary to take out and turn clamp on the rare side of the box.

    NPU has four operating push-buttons. The SET button (for settings) can be protected with cover (fixed bywire with two seals). The NPU has an LED display (four digits) and 10 LEDs for indication. Dimensions areon the figure.

    115

    ,0

    75,

    0

    100,0

    Set

    NPU PWRERR

    L1 U U Uf

    L2

    L3

  • 7/28/2019 NPU 2.0 Reference Guide

    6/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 6

    3. Installation

    Power Supply

    There are two power supplies available for NPU units see also chapter 7 Order codes:NPU FUV/YYY/230VAC power supply is in range 90 250 VACNPU FUV/YYY/24VDC power supply is in range 16 110 VDCPower supply polarity is not important in the case of DC power. The terminal PE is only as an anti-interference terminal.

    Analog Inputs

    The rated voltage (100, 230, 400, 480 VAC) is selected by order. Terminals are designed for connection ofeither phase-to-phase or phase-to-neutral voltage measurement. For connection see wiring diagram.

    Output Relays

    See wiring diagram. Relays on figure are without supply voltage (failure situation)

  • 7/28/2019 NPU 2.0 Reference Guide

    7/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 7

    The NPU Unit Wiring Diagram

    Connection NPU Unit to phase-to-neutral voltage

    11 14 12 21 24 22 31 34 32 41 44 42 A1 PE A2

    2L1 3L11L1 2L2 3L21L2 2L3 3L31L3

    POWER SUPPLYSWITCHED CONTACTSOF SIGNAL RELAYS

    CONNECTION NPU UNIT TO PHASE-TO-NEUTRAL VOLTAGE

  • 7/28/2019 NPU 2.0 Reference Guide

    8/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 8

    Connection NPU Unit to phase-to-phase voltage

    11 14 12 21 24 22 31 34 32 41 44 42 A1 PE A2

    POWER SUPPLYSWITCHED CONTACTSOF SIGNAL RELAYS

    CONNECTION NPU UNIT TO PHASE-TO-PHASE VOLTAGE

    L1L2L3PE

    2L1 3L11L1 2L2 3L21L2 2L3 3L31L3

  • 7/28/2019 NPU 2.0 Reference Guide

    9/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 9

    4. Function

    Protection types

    Overvoltage protectionThe protection responds to raising the voltage above set threshold with its own delay (see the descriptionbelow and the Set A table on page 18 as well). Limits can be set for any phase extra. By setting zerovalue the protection is switched off. See the correspondings parameters:

    The first stage of overvoltage threshold:

    Overvoltage limit 1 L1 A15Overvoltage limit 1 L2 A16

    Overvoltage limit 1 L3 A17Overvoltage delay 1 A18

    The second stage of overvoltage threshold:

    Overvoltage limit 2 L1 A19Overvoltage limit 2 L2 A20Overvoltage limit 2 L3 A21Overvoltage delay 2 A22

    Undervoltage protection

    The protection responds to voltage drop under set threshold with its own delay (see the description belowand the Set A table on page 18 as well). Limits can be set for any phase extra. By setting zero value theprotection is switched off.

    The first stage of undervoltage threshold:

    Undervoltage limit 1 L1 A23Undervoltage limit 1 L2 A24Undervoltage limit 1 L3 A25Undervoltage delay 1 A26

    The second stage of undervoltage threshold:

    Undervoltage limit 2 L1 A27

    Undervoltage limit 2 L2 A28Undervoltage limit 2 L3 A29Undervoltage delay 2 A30

    Overfrequency protectionThe protection responds to raising frequency above set threshold with its own delay (see the descriptionbelow and the Set A table on page 18 as well). Limit is common for all three phases. By setting zero valuethe protection is switched off.

  • 7/28/2019 NPU 2.0 Reference Guide

    10/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 10

    The first stage of overfrequency threshold:

    Overfrequency limit 1 A7Overfrequency delay 1 A8

    The second s tage of overfrequency threshold:Overfrequency limit 2 A9Overfrequency delay 2 A10

    Underfrequency protectionThe protection responds to fall frequency under set threshold with its own delay (see the description belowand the Set A table on page 18 as well). Limit is common for all three phases. By setting zero value theprotection is switched off.

    The first stage of underfrequency threshold:

    Underfrequency limit 1 A11

    Underfrequency delay 1 A12

    The second stage of underfrequency threshold:

    Underfrequency limit 2 A13Underfrequency delay 2 A14

    Voltage asymmetry protectionThe protection responds to raising of the voltage difference between any two phases above set thresholdwith its own delay (see the description below and the Set A table on page 18 as well). By setting zerovalue the protection is switched off.

    Voltage asymetry limit A31Voltage asymetry delay A32

    Vector shift supervisionThe protection responds to voltage vector shift (e.g. this can be caused by jump loading generator). Nodelay it is possible to adjust. By setting zero value the protection is switched off. The vector shiftsupervision delay (see the description below and the Set A table on page 18 as well) can be set from 0 sto 99.98 s (skip factor 20 ms) only at power supply switch on. It could be used when connecting ofasynchronous generators to the mains.

    Vector shift limit A33Vector shift evaluation delay on voltage connection A34

    Note:When NPU unit cooperates with the Inteli ComAps controller, wire the relay output of vector shiftprotection to the circuit breaker to open the circuit breaker directly and then wire the relay output to the BI:Ext MF relay of the controller.

  • 7/28/2019 NPU 2.0 Reference Guide

    11/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 11

    Phase sequence supervision

    Phase sequence supervision checks the right sequence. The angle has to be at interval (120 30)among voltage vectors. The right phase sequence is L1L2L3. The LEDs L1, L2 and L3 are red flashingat incorrect phase sequence. If the voltage is too small (approx.

  • 7/28/2019 NPU 2.0 Reference Guide

    12/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 12

    The RE2 relay opens immediately when Vector shift protection is activated. RE2 closes back after the timegiven by parameterB5. The relay doesnt open (doesnt indicate a new failure) until all active failures aregone. LED ERR copies the state ofRE2.In example on the following drawing there are theA26, A30 - Under voltage delays.

    Relay RE3:The relay RE3 opens at any failure with delay given by active protection (see the Set A table on page 18as well):

    Overfrequency delay 1 A8Overfrequency delay 2 A10Underfrequency delay 1 A12Underfrequency delay 2 A14Overvoltage delay 1 A18Overvoltage delay 2 A22

    Undervoltage delay 1 A26Undervoltage delay 2 A30Voltage asymetry delay A32

    The RE3 relay opens immediately when Vector shift protection is activated. RE3 stays opened until anyfailure is active and closes back immediately when no failure is active or with delay B6 in the case of vectorshift protection.In example on the following drawing it is Under voltage delayA26, A30.

    Relay RE4:The relay RE4 opens at any failure with delay given by active protection (see the Set A table on page 18as well):

    Overfrequency delay 1 A8Overfrequency delay 2 A10Underfrequency delay 1 A12Underfrequency delay 2 A14Overvoltage delay 1 A18Overvoltage delay 2 A22Undervoltage delay 1 A26Undervoltage delay 2 A30Voltage asymetry delay A32

    The RE4 relay opens immediately when Vector shift protection is activated. RE4 closes after the time givenby parameterB4. The relay operates similar as RE2, but indicates any new failure.This feature is available from software version 1.5 (see parameterB11 to find your software version).In example on the following drawing it is Under voltage delayA26, A30.

  • 7/28/2019 NPU 2.0 Reference Guide

    13/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 13

    MODE 2 - funct ion of relays corresponds to certain protections (B3=1)

    Relay RE1:

    The RE1 relayopens at Undervoltage, Overvoltage or Voltage asymetry failure with delay given by (see

    the Set A table as well):

    Overvoltage delay 1 A18Overvoltage delay 2 A22Undervoltage delay 1 A26Undervoltage delay 2 A30Voltage asymetry delay A32

    The RE1 relay will close back after the period of the failure + the period of the timerB4.

    Note: When the failure has gone the relay stays open till the "additional" timer period will elapse and then

    the relay will close back.

    Relay RE2:The RE2 relayopens at Underfrequency or Overfrequency failure with delay given by (see the Set A tableon page 18 as well):

    Overfrequency delay 1 A8Overfrequency delay 2 A10Underfrequency delay 1 A12Underfrequency delay 2 A14

    The RE2 relay will close back after the period of the failure + the period of the timerB5.

    Relay RE3:The RE3 relayopens at Vector shift failure immediately.

    The RE3 relay will close back after the period of the failure + the period of the timerB6.

    There is a dead time for Vector shift sensing after a voltage measurement input connection during a timegiven by the A34 delay

    Relay RE4:The RE4 relayopens at both incorrect phase sequence or NPUs internal failure immediately.The RE4 relay will close back after the period of the failure.

    Note: If there is no power supply, all relays are opened.

  • 7/28/2019 NPU 2.0 Reference Guide

    14/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 14

    Example: Evaluation of under voltage protection, B3=0

    t[s]

    U[V]

    A15

    A18

  • 7/28/2019 NPU 2.0 Reference Guide

    15/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 15

    Vector Shift Protection

    The vector shift protection protects synchronous generator in parallel operation in case of mains failure byvery fast opening the coupling breaker. Automatic mains reclosing for synchronous generator is verydangerous. The mains voltage returning after 300 ms can meet the generator in asynchronous mode.

    There are two main applications for vector protection:1. parallel mode only (no island mode)The vector protection controls the generator circuit breaker.2. parallel and island modeThe vector protection controls the mains circuit breaker.The NPU detects mains failure within 30 ms. The total time of disconnection is shorter than 100 msincluding disconnecting time of the circuit breaker.The requirement for generator disconnection comes on power change of more than 15% - 20%. Slowchanges of frequency (e.g. governor commands) dont activate the protection.

    Measuring principleWhen a synchronous alternator is loaded, the rotor displacement angle is build between the terminalvoltage (mains voltage) g and the synchronous electromotive force e. Therefore a voltage difference

    U is built between e and g. The rotor displacement angle between stator and rotor is depending onmechanical moving torque of the generator shaft. The mechanical shaft power is balanced with theelectrical feeder mains power and therefore the synchronous speed keeps constant.

    In case of mains failure or auto reclosing the generator suddenly feeds a very high consumer load. The

    rotor displacement angle is decreased repeatedly and the voltage vector g changes its direction to g.

    MainsUe Ug Z

    l1 l2U

    Generator Mains/Load

    Ue

    Ug

    In parallel with the mains

    MainsUe U g Z

    l 1

    U

    Generator Load

    Ue

    UgU

    g

    At mains fai lure

  • 7/28/2019 NPU 2.0 Reference Guide

    16/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 16

    As shown in the timing diagram the voltage jumps to an other value and the phase position changes. Thisprocedure is named phase or vector surge. NPU continuously measures the cycles, starting each zero upward slope. The time cycle is internally compared to the quartz table reference time. In case of vectorsurge the zero up ward is delayed and the device trips instantaneously. The trip angle andconsequently the sensitivity of the vector surge detection is adjustable.

    Measuring principle

  • 7/28/2019 NPU 2.0 Reference Guide

    17/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 17

    5. Settings

    Buttons

    Parameters and quantities are divided into two sets. For transfer from one set to the other press MODEbutton for 5 seconds. See tables for these sets. Items (parameters and quantities) in tables are in the samesequence as on display.If the SET button is available (the SET button can be protected with panel fixed by two seals), parameterscan be adjusted by pressing ofSET button.

    For transfer between items use (up arrow) or(down arrow).

    Display and LEDs

    Parameters or measured quantities are displayed on four digits display.The display switches on after pressing any button and switches off after the time given by B2. If B2 is 0,than the display never switches off. The display switch off also aborts unfinished parameter settings.The green LED PWR indicates power supply.Three-color LEDs L1, L2, L3 indicate the phase that corresponds to the data on display (yellow color) or toa failure LED (red color).

    Three-color LEDs f, f, U, U,U, U, indicate failure type (red color) or data on display (yellow color).The three-color LED ERR follows either relay RE2 (red color id. RE2 is open, switches off if RE2 is closed)when B3=0 or each relay when B3=1. The LED ERR follows also NPU internal error (red flashing).Notes:

    If any LED shines or flashes red the failure is indicated. The failure indication has always priority to anotherindications.

    The LEDs L1, L2, L3, f, f, U, U,U, U, shine red immediately after failure (without delay). If RE2relay opens LEDs starts red flashing. The LED flashing is finished by pressing any button or the time givenby B2. Failures are not indicated by red LED flashing ifB2 is zero.

    Parameters settings

    Press the SET button and the first digit starts flashing. The flashing digit can be changed by pressing (+1)and (-1) buttons. The next digit is selected by pressing MODE button.If the required parameter value is displayed press the SET button again and the new value is stored. If anew value is out of allowed range the NPU sets it to proximate value.

    Caution: a new value is applied immediately.

  • 7/28/2019 NPU 2.0 Reference Guide

    18/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 18

    6. Displayed Quantit ies and ParametersSet A:

    No. Quantity(parameter)

    Front panelsignals

    Characterson display

    Limits Step Unit

    A1 Frequency in L1, L2, L3 Green L1,L2,L3 0,01 [Hz]

    A2 Voltage L1 Green L1 1 [V]

    A3 Voltage L2 Green L2 1 [V]

    A4 Voltage L3 Green L3 1 [V]

    A5 Max. phase asymmetry 1 [V]

    A6 Max. vector shift in L1, L2, L3 Yellow L1 0,1 []

    A7

    A8Overfrequency limit 1

    Overfrequency delay 1

    Green f

    Yellow f

    0;4565

    099,98

    0,1

    0,02

    [Hz]

    [s]

    A9

    A10Overfrequency limit 2

    Overfrequency delay 2

    Green f

    Yellow f

    0;4565

    099,98

    0,1

    0,02

    [Hz]

    [s]

    A11

    A12

    Underfrequency limit 1

    Underfrequency delay 1

    Green f

    Yellow f

    0;4565

    099,98

    0,1

    0,02

    [Hz]

    [s]

    A13

    A14

    Underfrequency limit 2

    Underfrequency delay 2

    Green f

    Yellow f

    0;4565

    099,98

    0,1

    0,02

    [Hz]

    [s]

    A15

    A16

    A17

    A18

    Overvoltage limit 1 L1

    Overvoltage limit 1 L2

    Overvoltage limit 1 L3

    Overvoltage delay 1

    Green L1, U

    Green L2, U

    Green L3, U

    Yellow U

    0999

    0999

    0999

    099,98

    1

    1

    1

    0,02

    [V]

    [V]

    [V]

    [s]

    A19

    A20

    A21

    A22

    Overvoltage limit 2 L1

    Overvoltage limit 2 L2

    Overvoltage limit 2 L3

    Overvoltage delay 2

    Green L1, U

    Green L2, U

    Green L3, U

    Yellow U

    0999

    0999

    0999

    099,98

    1

    1

    1

    0,02

    [V]

    [V]

    [V]

    [s]

    A23

    A24

    A25

    A26

    Undervoltage limit 1 L1

    Undervoltage limit 1 L2

    Undervoltage limit 1 L3

    Undervoltage delay 1

    Green L1, U

    Green L2, U

    Green L3, U

    Yellow U

    0999

    0999

    0999

    099,98

    1

    1

    1

    0,02

    [V]

    [V]

    [V]

    [s]

    A27

    A28

    A29

    A30

    Undervoltage limit 2 L1

    Undervoltage limit 2 L2

    Undervoltage limit 2 L3

    Undervoltage delay 2

    Green L1, U

    Green L2, U

    Green L3, U

    Yellow U

    0999

    0999

    0999

    099,98

    1

    1

    1

    0,02

    [V]

    [V]

    [V]

    [s]

    A31

    A32

    Voltage asymmetry limit

    Asymmetry delay

    Green U

    Yellow U

    0999

    099,98

    1

    0,02

    [V]

    [s]

  • 7/28/2019 NPU 2.0 Reference Guide

    19/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 19

    A33

    A34

    Vector shift limit

    Vector shift evaluation delay onvoltage connection

    Green U

    Yellow U

    050

    099,98

    1

    0,02

    []

    [s]

    Default setting

    No. Quantity (parameter) Rated voltage100V 230V 400V 480V

    A1 Frequency in L1, L2, L3A2 Voltage L1A3 Voltage L2A4 Voltage L3A5 Max. phase asymmetry

    A6 Max. vector shift in L1, L2, L3A7, A9A8, A10

    Overfrequency limitOverfrequency delay

    52 (62) Hz2,5 s

    52 (62)Hz2,5 s

    52 (62) Hz2,5 s

    52 (62) Hz2,5 s

    A9, A13A10, A14

    Underfrequency limitUnderfrequency delay

    48 (58) Hz2,5 s

    48 (58) Hz2,5 s

    48 (58) Hz2,5 s

    48 (58) Hz2,5 s

    A11, A19A12, A20A13, A21A14, A22

    Overvoltage limit L1Overvoltage limit L2Overvoltage limit L3Overvoltage delay

    110 V110 V110 V2,5 s

    253 V253 V253 V2,5 s

    440 V440 V440 V2,5 s

    528 V528 V528 V2,5 s

    A15, A27A16, A28A17, A29A18, A30

    Undervoltage limit L1Undervoltage limit L2Undervoltage limit L3Undervoltage delay

    85 V85 V85 V2,5 s

    196 V196 V196 V2,5 s

    340 V340 V340 V2,5 s

    432 V432 V432 V2,5 s

    A31A32

    Voltage asymmetry limitAsymmetry delay

    15 V2,5 s

    30 V2,5 s

    60 V2,5 s

    60 V2,5 s

    A33A34

    Vector shift limitVector shift evaluation delay onvoltage connection

    202,5 s

    202,5 s

    202,5 s

    202,5 s

  • 7/28/2019 NPU 2.0 Reference Guide

    20/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 20

    Set B:

    No. Quantity

    (parameter)

    Front panel

    signals

    Characters

    on displayLimits Step Unit

    B1 Failure time signaling(red LEDs flashing time)

    Flashing greenL1,L2

    09999 1 [min]

    B2 Display switch off time Flashing green

    L1, L309999 1 [min]

    B3 Function of the output relays RE1 RE4

    Flash. yellow

    L1, L2, L301 1

    B4 When B3=0:Relay RE1, RE4 switch off time;

    When B3=1:Relay RE1 switch off time after

    failure

    Flash. yellow

    L1, L2099,98 0,02 [s]

    B5 When B3=0:Relay RE2 switch off time

    When B3=1:Relay RE2 switch off time afterfailure

    Flash. yellow

    L1, L3099,98 0,02 [s]

    B6 When B3=0 or B3=1:Relay RE3 switch off time aftervector shift protection

    Flash. yellow

    U099,98 0,02 [s]

    B7 Max. vector shift in L1, L2, L3 (frommanual reset)

    Yellow

    L1, L2, L3

    00 []

    B8 Angle between L1 and L2 Yellow L1, L2 1 []

    B9 Angle between L2 and L3 Yellow L2, L3 1 []

    B10 Display and LEDs brightness 09 1

    B11 Software release

    B12 Display and LEDs test All LEDsyellow

    (no failure)

    ERR red

    Time delays are set with step 0.02 s (without relay drop out time - c. 0.01 s has to be added).The Max. vector shift (A6) is the highest measured value between data recovery on display.The Max. vector shift (B7) is the highest measured value between manual resets. This could be used for along-term monitoring of the grids vector shifts. Reset ofB7: Set zero like in the other parameters.Setting zero bold typed parameters switches off the appropriate protection.Exception: B2 set to zero makes the display shining continuously.

  • 7/28/2019 NPU 2.0 Reference Guide

    21/22

  • 7/28/2019 NPU 2.0 Reference Guide

    22/22

    NPU, SW Version 2.0, ComAp, July 2008NPU-2.0.PDF 22

    7. Order codes

    NPU - FUV / YYY / ZZZ

    YYY measurement range: 100 / 230 / 400 / 480 VACZZZ power supply range: 230VAC / 24VDC

    Order code

    Frequency

    protection

    Voltage

    protection

    Voltage

    asymmetry

    protection

    Vectorshift

    supervision

    Rated

    voltage

    Power

    supply

    voltage

    NPU-FUV/100/230VACNPU-FUV/100/24VDC

    Yes Yes Yes Yes

    100V 230VAC24VDC

    NPU-FUV/230/230VACNPU-FUV/230/24VDC

    Yes Yes Yes Yes

    230V 230VAC24VDC

    NPU-FUV/400/230VACNPU-FUV/400/24VDC

    Yes Yes Yes Yes

    480V 230VAC24VDC

    NPU-FUV/480/230VACNPU-FUV/480/24VDC

    Yes Yes Yes Yes

    480V 230VAC24VDC


Recommended