Asset: P.S. 130 - QUEENS, 200-01 42 AVENUE, New York, 11361
Inspection Id Inspection Type Time In Last Edited
SA : Q130 Architectural - Senior 2018-12-13 8:05 AM 2019-06-05 5:29 PM
AA : Q130 Architectural - Associate 2018-12-13 8:39 AM 2018-12-27 2:57 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Michelle Contratti
Organization P.S. 130 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback Assistant Principal Kathy Specchia, speaking on behalf of thePrincipal, had the following comments: 1. Student Toilet Rooms arenot appropriate for the age of the students. 2. There are not enoughStudent Toilet Rooms for the number of students attending the school.3. The Teachers Lounge does not have enough outlets or power forschool components.
Principal Name (Site Coordinator) Tabitha Judge
Organization P.S. 993 - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Was not present
Fireman Brian Steiger
Building Square Footage 64000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B+SB
Comments on the Number of Classrooms 27
Comments on the Year Built 1925
Student Population 473
Staff Population 152
Weather Fair
Facade Photo
Corner of 42nd Avenue and Francis LewisBoulevard - Northeast
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 1 of 43
Main Entrance Photo
Facade A - 42nd Avenue
Roof Photo
Roof 1 - Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited steel structure repairs at Basement level.
Year: 2017
Systems: Exterior Modernization Project including new Roofing,Flashing, Parapets, Coping, Cornice, Roof Barrier;Exterior Masonry repointing and repairs at Bulkheads andChimneys; Foundation Walls repairs and Waterproofing;Vault Slab and Walls repairs and Waterproofing; limitedExterior Doors replacement
Year: 2016
Systems: Structural repairs to Stair (Exit 5/1st Floor)
Year: 2015
Systems: Windows and Exterior Guards replacement
Year: 2009
Systems: HC Toilet upgrades at 1st Floor
Year: 2007
Systems: New HC Ramp at Facade F
Year: 2006
Systems: Parapets replacement; limited Exterior Masonryrepointing; Areaway Gratings replacement
Year: 2001
Systems: Complete Exterior Doors replacement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 2 of 43
Year: 1998
Have there been any New Building Additions? Yes
Comments on New Building Additions 1965 (+8,200sf)
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes
Boys and Girls or Unisex accessible toilets exist on the 1st floor? Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria Basement Yes No Not on Accessible Route Yes No
Classrooms 1st Floor Yes Yes
Computer Rooms Room 306 Yes No Not on Accessible Route
Gymnasium No
Library No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 3 of 43
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Main Office Room 106 (P.S. 993) Yes Yes
Room 213 (P.S. 130) Yes No Not on Accessible Route
Multi-purpose Room 1st Floor Yes Yes Yes No
3rd Floor Yes No Not on Accessible Route No No
Nurse's Room Room 109 Yes Yes
Room 317 Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) 1st Floor Yes Yes
Toilet Rooms (Girls) 1st Floor (Unisex) Yes Yes
Toilet Rooms (Staff) 1st Floor Yes Yes
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW6
Instance Condition 3 - Fair
Instance Quantity 6
Instance Quantity Uom EACH
Deficiency AREAWAY SLAB: CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 4 of 43
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW3
Violations No violations recorded.
Deficiency AREAWAY GRATINGS: MINOR RUSTING
Roof Plan reference
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 5 of 43
Question Response
EXTERIOR
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency CAST STONE: CRACKED/BROKEN PIECES
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 6 of 43
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 9
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade J
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 26,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 26,000
Instance Quantity Uom S.F.
Deficiency TERRA COTTA: CHIPPED/SPALLED/BROKEN PIECES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 7 of 43
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 8 of 43
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BRICK: MAJOR / THRU CRACKS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 9 of 43
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade G
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 10 of 43
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 4,350
Replacement Uom C.F.
InspectedInstance on All Roofs
Instance Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 11 of 43
Question Response
EXTERIOR
PARAPETS
Instance Quantity 4,350
Instance Quantity Uom C.F.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 19,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: Roof 1
Instance Condition 1 - Good
Instance Quantity 12,400
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2016
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on IRMA: Roofs 2 and 3
Instance Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 12 of 43
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Instance Quantity 6,600
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2016
Source of Installation Custodial Staff
Deficiency IRMA: FLASHING: PITCH POCKET- POOR CONDITION
Roof Plan reference
Deficiency Quantity 12
Quantity Uom EACH
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 3
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 3 - Fair
Deficiency DETERIORATED
Roof Plan reference
Deficiency Quantity 1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 13 of 43
Question Response
EXTERIOR
ROOF
Roofing
ROOFING DRAINS
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 14 of 43
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 15 of 43
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
RAILINGS Inspected
Condition 3 - Fair
Deficiency DAMAGED
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 16 of 43
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency RUST - MINOR
Roof Plan reference
Deficiency Quantity 80
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 17 of 43
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade J
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: CRACKS, SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 18 of 43
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 7,500
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 19 of 43
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum, Other
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 7,100
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Other: Facades A and C
Instance Condition 2 - Between Good and Fair
Instance Quantity 400
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MAJOR RUSTING
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 20 of 43
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Purpose of Action LEVEL 5
Deficiency Photo1
Mower Storage Room
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING
Deficiency Location/Instance 1st Floor
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Stair H
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 21 of 43
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS Inspected
Boiler Room (mower storage room similar)
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Basement
Deficiency Quantity 60
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 22 of 43
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room (2 locations)
Violations No violations recorded.
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Room B04 (Sub-Basement)
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 23 of 43
Question Response
INTERIOR
CAFETERIA
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Room 105
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 105
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Exit Vestibule 7
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 24 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Exit Vestibule 7
Violations 35271616K
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 121
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 121
Violations No violations recorded.
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Room 105
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 25 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 105
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Exit Vestibule 5, Corridor near Room 104
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule 5
Violations No violations recorded.
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 317
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 26 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Room 317
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Room 122/123
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 122/123
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Room 115, Exit Vestibule 6
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 115
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 106 Corridor near Room 106
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 27 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Deficiency Photo1
Room 106
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Lobby Near Exit 6
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Lobby Near Exit 6
Violations No violations recorded.
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Room 105
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 28 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Corridor near Room 105
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance Room 101
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 101
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 121 Corridor near Room 101
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 121
Violations No violations recorded.
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 105, 112
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 29 of 43
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Corridor near Room 112
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Exit Vestibule
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule
Violations No violations recorded.
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 30 of 43
Question Response
INTERIOR
KITCHEN
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Does not Exist
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 1st Floor
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor
Does not ExistInstance on 3rd Floor
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near the Entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 31 of 43
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Floor Finish
Deficiency Photo1
Near the Entrance
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 1st Floor
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
Does not ExistInstance on 3rd Floor
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair C-D/1 Exit Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 32 of 43
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Photo1
Stair C-D/1 Exit Vestibule
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Stair G/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair G/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Stair H/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 33 of 43
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Stair H/1
Violations 35271616K
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Stair H/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Stair H/1
Violations 35271616K
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Inside Room 317
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 34 of 43
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Deficiency Photo1
Inside Room 317
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Basement Cafeteria
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement Cafeteria
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 113/114, 212
Deficiency Quantity 2
Quantity Uom EACH
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 35 of 43
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 212
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 4 - Between Fair and Poor
Deficiency BROKEN/MISSING
Deficiency Location/Instance Inside Room 121
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 121
Violations No violations recorded.
Deficiency RUST - MAJOR
Deficiency Location/Instance Room 118
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 36 of 43
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Deficiency Photo1
Room 118
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 208, 318
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 208
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency FENCING MISSING
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 37 of 43
Question Response
SITE
CONTAINERIZATION
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED COVER
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 38 of 43
Question Response
SITE
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance 42nd Avenue
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
42nd Avenue
Violations No violations recorded.
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance 42nd Avenue
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
42nd Avenue
Violations No violations recorded.
Deficiency CHAIN LINK: RUST - MAJOR
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 39 of 43
Question Response
SITE
FENCES
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 201st Street, 42nd Avenue
Deficiency Quantity 280
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
201st Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Exit to 201st Street
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 40 of 43
Question Response
SITE
PAVING
Student Non-Use
Concrete
Deficiency Photo1
Exit to 201st Street
Violations No violations recorded.
Pavers Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Rear of School
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear of School
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 41 of 43
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Francis Lewis Boulevard, 42nd Avenue, 201st Street
Deficiency Quantity 525
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Francis Lewis Boulevard
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 42 of 43
Question Response
SITE
RETAINING WALLS
Deficiency Photo1
Francis Lewis Boulevard
Violations No violations recorded.
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q130
PB/A&W Print Date: 6/21/2019Page 43 of 43