+ All Categories
Home > Documents > Optimal Example Inspection, 1313 Mockingbird Ln.pdf

Optimal Example Inspection, 1313 Mockingbird Ln.pdf

Date post: 15-Sep-2015
Category:
Upload: ashleigh-oliver
View: 225 times
Download: 2 times
Share this document with a friend
20
Optimal Home Inspection Optimal Home Inspection P.O. Box 5282 Bella Vista, Arkansas 72714 (479) 366-5032 1313 Mockingbird Ln. Bella Vista, AR 72715
Transcript
  • Optimal Home Inspection

    Optimal Home InspectionP.O. Box 5282Bella Vista, Arkansas 72714(479) 366-5032

    1313 Mockingbird Ln. Bella Vista, AR 72715

  • Table of Contents Scope of work 2Definitions 3General Information 3Grounds 4Exterior 6Garage 7Roof 7Interior 8Appliances 8Electrical 9Structure 10Basement 11Crawl Space 11Air Conditioning 12Heating System 13Plumbing 14Attic 16Summary 17

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 1 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Scope of work Optimal Home Inspection follows the ASHI Standards of Practice in conjunction with the AHIB Standards of Practice. We inspect readily accessible systems and components of homes as listed below. Items and issues exempt from the inspection will be listed in the disclaimer prior to each category. Inspected systems and components are as follows; Structural system: structural components, including foundation and framing where accessible. Describe; foundation type and methods used to inspect crawl space. Floor structure, wall structure, and ceiling structure. Roof structure and methods used to inspect attic. Exterior: Exterior wall covering, flashing and trim. All exterior doors. Attached decks, balconies, stoops, steps, porches, and associated railings. Eaves, soffits, and fascias where accessible from ground level. Vegetation, grading, surface drainage, and retaining walls where likely to adversely affect building. Describe; exterior wall covering. Roof System: Roof covering, drainage, flashings, skylights, chimneys, and penetrations. Describe; roof covering and method of inspection. Plumbing System: Interior water supply and distribution including fixtures and faucets. Drain, waste, and vent systems including all fixtures. Water heating equipment. Vent systems, flues, and chimneys. Fuel storage and distribution systems. Drainage sumps, sump pumps, and related piping. Describe; water supply, drain, waste, vent piping materials. Water heating equipment including energy source. Location of main water and fuel shut-off valves. Electrical system: Service drop, service entrance conductors, cables, and raceways. Service equipment and main disconnects. Service grounding. Interior components of service panels and sub-panels. Conductors and overcurrent protection devices. Representative number of lighting fixtures, switches, receptacles, and GFCIs. Describe; Amperage and voltage rating of service. Location of main disconnect and sub-panels. Wiring methods. Report; presence of solid conductor aluminum branch circuit wiring and absence of smoke detectors. Heating System: Installed heating equipment, vent systems, flues, and chimneys. Describe; Energy source, heating method by distinguishing characteristics. Air Conditioning System: Installed centrall and through-wall cooling equipment. Describe; Energy source, cooling method by distinguishing characteristics. Interior: Walls, ceilings, and floors. Steps, stairways, and railings. Countertops and representative number of installed cabinets. Representative number of doors and windows. Garage doors and garage door operators. Insulation and Ventilation: Insulation and vapor retarders in unfinished spaces. Ventilation of attics and foundation areas. Mechanical ventilation systems. Describe; Insulation and vapor retarders in unfinished spaces. Absence of insulation in unfinished spaces at conditioned surfaces. Fire places and solid fuel burning appliances: System components, vent systems, flues, and chimneys. Describe; Fireplaces and solid fuel burning appliances, and chimneys. General Limitations: Inspections are not technically exhaustive and will not identify concealed conditions or latent defects. General Exclusions: Inspector is not required to determine any of the following: Condition of systems or components which are not readily accessible. Remaining life of any system or component. Strength, adequacy, effectiveness, or efficiency of any system or component. Causes of any condition or deficiency. Methods, materials, or costs of corrections. Future conditions including, but not limited to, failure of systems and components. Suitability of the property for any specialized use. Compliance with regulatory requirements (codes, regulations, laws, ordinances, etc.). Market value of property or marketability. Advisability of purchase of property. Presence of potentially hazardous plants or animals including, but not limited to, wood-destroying organisms or diseases harmful to humans. Presence of any environmental hazards including, but not limited to, toxins, carcinogens, noise, and contaminants in soil, water, and air. Effectiveness of any system installed or methods utilized to control or remove suspected hazardous substances. Operating costs of systems or components. Acoustical properties of any system or component. Inspector is not required to offer, or perform: Any act or service contrary to law. Engineering services. Work in any trade or any professional service other than home inspection. Warranties or guarantees of any kind. Inspector is not required to operate: Any system or component which is shut down or otherwise inoperable. Any system or component

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 2 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Scope of work (Continued)which does not respond to normal operating controls. Shut-off valves. Inspector is not required to enter: Any area which will, in the opinion of the inspector, likely be dangerous to inspector, other persons, or damage the property or its systems or components. Under-floor crawl spaces or attics which are not readily accessible. Inspector is not required to inspect: Underground items including but not limited to, underground storage tanks or other underground indications of their presence, whether abandoned or active. Systems or components which are not installed. Decorative items. Systems or components located in areas that are not readily accessible. Detached structures other than garages and carports. Common elements or common areas in multi-unit housing, such as condominium properties or cooperative housing. Inspector is not required to: Perform any procedure or operation which will, in the opinion of the inspector, likely be dangerous to the inspector or other persons, or damage the property or its system or components. Move suspended ceiling tiles, personal property, furniture, equipment, plants, soil, snow, ice, or debris. Dismantle any system or component beyond what is necessary for operational inspection.

    DefinitionsNOTE: All definitions listed below refer to the property or item listed as inspected on this report at the time of inspection

    Acceptable Functional with no obvious signs of defect. Not Present Item not present or not found. Not Inspected Item was unable to be inspected for safety reasons or due to lack of power, inaccessible, or disconnected at time

    of inspection. Marginal Item is not fully functional and requires repair or servicing. Safety Issue Item is a safety issue and should be repaired or adjusted by a certified professional Defective Item needs immediate repair or replacement. It is unable to perform its intended function.

    General InformationProperty Information

    Property Address 1313 Mockingbird Ln. City Bella Vista State Arkansas Zip 72715 Contact Name Doe, Jon Phone 555-1212

    Client Information Client Name Doe, Jon Client Address 1313 Mockingbird Ln. City Bella Vista State Arkansas Zip 72715 Phone 555-1212 E-Mail [email protected]

    Inspection Company Inspector Name Jeromy Overman Company Name Optimal Home Inspection Address P.O. Box 5282 City Bella Vista State Arkansas Zip 72714 Phone (479) 366-5032 AHIB License # HI-1725 E-Mail [email protected] File Number 61515-1313 Amount Received $250.00

    Conditions

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 3 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • General Information (Continued)Others Present Home Owner Property Occupied Occupied Estimated Age 46 yrs. Entrance Faces Southwest Inspection Date 06/15/2015 Start Time 1:00 p.m. End Time 4:00 p.m. Electric On Yes Gas/Oil On Yes Water On Yes Temperature 82 Weather Thunderstorm Soil Conditions Wet Space Below Grade Crawl Space Building Type Single family Garage Carport Sewage Disposal Septic How Verified Multiple Listing Service Water Source City How Verified Multiple Listing Service Additions/Modifications None

    Grounds Not part of inspection process: Fences, outbuildings, recreational facilities, seawalls, break-walls, and docks. Geological, geotechnical, or hydrological conditions. Erosion control and earth stabilization measures

    1. Acceptable, Marginal Driveway: Concrete - Concrete pitted and chipped with minor cracking. Pitting is uniform and seems age/ weather related. Minor settlement cracks, with no signs of spread or uplift. Cracking is most likely due to settlement and does not seem on going. Heaves in concrete are possible trip hazard. Upheaval occurs at both ends where the driveway meets the concrete pad under the Porte-cochere and is a uniform 1/2 inch high for width of pad. Driveway is in overall acceptable condition, with the exception of offset area under Porte-cochere. A qualified contractor is recommended to evaluate and estimate repairs.

    1/2 Inch Heave at Porte-cochere

    Minor Settlement Crack

    Pitting is Uniform due to Weather and Age

    2. Acceptable Walks: Concrete

    Tile Step and Porch

    3. Acceptable Steps: Tile

    4. Acceptable Porch: Tile

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 4 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Grounds (Continued)5. Safety Issue Deck: Treated wood, Stained wood - The basement deck built to close to grade, unable to

    inspect the underside. Baluster openings too wide, should be no more than 4 inches apart. This is considered a safety hazard. Some components showing signs of weathering and should be replaced. A qualified contractor is recommended to evaluate and estimate repairs.

    Balusters Spaced More than 4 Inches

    Apart

    Not Enough Clearance for Inspection

    Decking Components Showing Signs of Rot.

    Hand Rail Less than 34 Inches in Height

    6. Safety Issue Railings: Wood - Hand rails should be between 34-38 inches in height. A qualified contractor is recommended to evaluate and estimate repairs.

    Hand Rail Less than 34 Inches High

    No Balusters Present

    7. Safety Issue Stairs (Exterior) Wood - Hand rails should be between 34-38 inches in height. Balusters should be spaced no more than 4 inches apart and should be installed vertically. A qualified contractor is recommended to evaluate and estimate repairs.

    Tree Limbs Overhanging Roof

    8. Acceptable, Marginal Vegetation: Trees, Shrubs, Shrubs/Weeds - Tree limbs over hang the roof and should be cut back. All vegetation should be kept a minimum of 1 foot from structure.

    9. Acceptable Retaining Walls: Block 10. Acceptable Grading: Steep slope - Drains away from foundation well. However there seems to be an

    erosion issue, due to the steep grade, that should be monitored to avoid issues in the future. 11. Acceptable Swale: Adequate slope and depth for drainage

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 5 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Exterior Not part of inspection process: Shutters, screens, awnings, and similar seasonal accessories.

    Northeast, Northwest, Southeast, Southwest Exterior Surface

    Patches to Sidings

    1. Acceptable Type: Wood - Signs of repair to siding.

    2. Acceptable Trim: Wood

    Signs of Weathering

    3. Marginal Fascia: Wood - Early signs of weathering evident. A qualified contractor is recommended to evaluate and estimate repairs.

    4. Marginal Soffits: Plywood - Moisture stains, paint peeling, wood rot. A certified professional should be contacted for further evaluation. Paint Peeling and Signs of Wood Rot

    Paint Peeling and Signs of Wood Rot

    5. Acceptable Flashing: Aluminum 6. Acceptable Entry Doors: Metal 7. Acceptable Patio Door: Vinyl sliding 8. Marginal Windows: Metal - Seals showing signs of weathering. Could lead to drafts and energy loss.

    Front window in master is hard to open, needs an adjustment. Fixed windows in living area are fogging due to failed seals. A certified professional should be contacted for further evaluation.

    9. Acceptable Storm Windows: None 10. Acceptable, Marginal Window Screens: Metal - Windows on left side of the house are missing screens. 11. Acceptable Basement Windows: Aluminum double hung

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 6 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Garage1. Type of Structure: Porte-Cochere Car Spaces: 1 2. Acceptable Ceiling: Paint 3. Acceptable Walls: Exterior grade materials - Porte-Cochere is a type of car port and as such uses the

    exterior of house as walls 4. Acceptable Floor/Foundation: Poured concrete

    Roof Not part of inspection process: Antennae, interiors of flues or chimneys which are not readily accessible, and other installed accessories.

    Main Roof Surface 1. Method of Inspection: On roof

    Roof Over Porte-cochere and Front of House

    Roof Over Master Bath/Bedroom and Kitchen

    Roof Over 2nd / 3rd Bedroom and 2nd Bath

    Moss Growing on Shingles

    2. Acceptable, Marginal Material: Asphalt shingle - Moss growing on shingles. This can trap moisture and lead to premature failure. Recommend a certified professional be contacted to clean and treat the roof. Spongy areas noted, some sheathing may need replacing the next time the roof is re-shingled.

    3. Type: Gable 4. Approximate Age: 5-10 yrs 5. Acceptable Flashing: Aluminum 6. Acceptable Valleys: None 7. Acceptable Skylights: None 8. Acceptable, Marginal Plumbing Vents: PVC - Plumbing boots nailed on bottom flanges. This is not a

    recommended building practice as exposed fasteners can lead to water intrusion. Roof should be monitored for signs of water intrusion. If intrusion is noted contact a certified professional for further evaluation.

    Bottom Flange of Plumbing Boot Nailed

    Bottom Flange of Plumbing Boot Nailed

    Roof Water Control 9. Acceptable Gutters: None

    10. Acceptable Downspouts: None 11. Acceptable Leader/Extension: None

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 7 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Interior Not part of inspection process: Paint, wallpaper, and other finish treatments. Carpeting. Window treatments. Central vacuum systems.

    General Interior 1. Acceptable Closets: Large - All closets have built in wooden organizers.

    Seperation at Ceiling / Wall Joint Can be a Sign of Truss Uplift

    2. Acceptable, Marginal Ceilings: Texture paint - Evidence of possible truss uplift in 3rd bedroom. Possibly due to insufficient insulation in attic, see attic notes. Monitor for further movement, if movement continues contact a certified professional for further evaluation.

    3. Acceptable Walls: Paint and paneling, Paint and tile - Paneling through entire house with exception of bathrooms. Bathrooms are gypsum and tile.

    4. Acceptable Floors: Tile, Laminates - Bathrooms and kitchen are tile, the rest of house is wood laminate. 5. Acceptable Doors: Hollow wood 6. Acceptable HVAC Source: Heating system register

    Kitchen 7. Acceptable Kitchen Cabinets: Wood 8. Acceptable Kitchen Counter Tops: Formica

    Bathroom 9. Acceptable Bathroom Cabinets: Composite and wood

    10. Acceptable Bathroom Counter Tops: Corian 11. Acceptable Ventilation: None - Bathroom ventilation not common during the era the house was built. Lack

    of ventilation can cause excessive moisture build up and could lead to issues down the road. Monitor for excessive moisture, if noted contact a licensed contractor to for further evaluation.

    12. Acceptable Smoke Detector Location Bedrooms, Living area, Mechanical room - Battery operated smoke detectors through out home. Recommend regular testing and battery replacement.

    13. Acceptable Carbon Monoxide Detector Location Living Room - Battery Operated

    Appliances Not part of inspection process: Household appliances that are not installed.

    Kitchen 1. Acceptable Cooking Appliances: General Electric 2. Acceptable Ventilator: Whirlpool 3. Acceptable Disposal: None 4. Acceptable Dishwasher: Whirlpool 5. Air Gap Present? Yes 6. Acceptable Refrigerator: Fisher & Paykel

    Crack in Door

    7. Acceptable Microwave: Whirlpool - Door has crack in body.

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 8 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Appliances (Continued)Other Appliances

    Dryer Exhaust Terminates Within 4 Feet of A/C Fan Unit

    8. Acceptable, Marginal Dryer Vent: Metal flex - Needs cleaning. Terminates within 4 feet of air conditioning fan. This can lead to lint build up on A/C fan coils reducing the life span of unit. Termination should be directed to move lint away from A/C unit.

    Electrical Not part of inspection process: Remote control devices unless the device is the only control device. Alarm systems and components. Low voltage wiring, systems, and components. Ancillary wiring, systems, and components not a part of the primary electrical power distribution system. Measure amperage, voltage, or impedance.

    1. Acceptable Service Entrance: Above Ground From Mast - Boot at roof penetration has been sealed with a caulk and flange has been nailed at bottom. This is not a recommended building practice as it can lead to water intrusion. A certified professional should be contacted for further evaluation.

    Conduit Boot has been Caulked and Bottom

    Flange has been Nailed

    2. Service Size Amps: 100 Volts: 110-240 VAC 3. Acceptable Service: Copper

    4. Acceptable Ground: Rod in ground only 5. Acceptable 120 VAC Branch Circuits: Copper 6. Acceptable 240 VAC Branch Circuits: Copper 7. Acceptable Aluminum Wiring: Not present 8. Acceptable Conductor Type: Romex 9. Acceptable Interior Lighting: 110 VAC

    10. Acceptable 120 VAC Outlets: Grounded 11. Acceptable 240 VAC Outlets: 3-pole 4-wire grounded Second bedroom closet Electric Panel 12. Acceptable, Marginal, Safety Issue Manufacturer: Cutler-Hammer - Panels should not be

    located in closets or wet areas as they constitute safety hazards. Evaluation by a licensed electrician is recommended

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 9 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Electrical (Continued)13. Maximum Capacity: 125 Amps

    14. Acceptable Main Breaker Size: 100 Amps 15. Acceptable Breakers: Copper 16. Not Present AFCI: N/A 17. Acceptable GFCI: At GFCI receptacles only 18. Is the panel bonded? Yes 19. Acceptable Door Bell: Hard wired 20. Acceptable Smoke Detectors: Battery operated with light 21. Acceptable Exterior Lighting: Surface mounted lamps front and rear 22. Acceptable Exterior Electric Outlets: 110 VAC

    Structure Inspection does not provide engineering service or architectural service. Inspection does not offer opinions as to adequacy of structural system or component.

    1. Acceptable Structure Type: Wood frame 2. Acceptable Foundation: Block

    3. Acceptable Differential Movement: No movement or displacement noted 4. Acceptable Beams: Bonded wood

    5. Acceptable Bearing Walls: Frame 6. Acceptable Joists/Trusses: 2x8 7. Acceptable Piers/Posts: Block piers and posts 8. Acceptable Floor/Slab: Composite wood or plywood 9. Acceptable Stairs (Interior): Exterior only

    10. Acceptable Subfloor: Plywood

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 10 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Basement1. Acceptable Ceiling: Exposed framing, Suspended ceiling

    2. Acceptable Walls: Concrete blocks, Paint and paneling, Exposed framing

    3. Acceptable Floors: Poured and sealed concrete

    4. Acceptable Ventilation: Windows, Vents 5. Acceptable Insulation: Batting 6. Acceptable Vapor Barrier: Paper 7. Acceptable Moisture Location: None noted

    Crawl Space Not part of inspection process: Disturb vapor barrier for inspection purposes. Air quality.

    1. Method of Inspection: In the crawl space

    2. Acceptable Access: Wood door 3. Acceptable Moisture Penetration: No moisture present at time of inspection 4. Acceptable Moisture Barrier: plastic over soil, sealed to walls and columns

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 11 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Crawl Space (Continued)5. Acceptable Ventilation: Vents, Windows - Vents sealed, this is a conditioned space.

    6. Acceptable Insulation: Fiberglass

    7. Acceptable Vapor Barrier: plastic over soil, sealed to walls and columns

    Air Conditioning Not part of inspection process: Electronic air filter. Determine cooling sypply adequacy or distribution balance.

    Main, left side of house AC System 1. Acceptable A/C System Operation: Appears serviceable, Functional 2. Acceptable Condensate Removal: PVC 3. Acceptable Exterior Unit: Pad mounted

    4. Manufacturer: Carrier 5. Model Number: 38CKC042310 Serial Number: 3398E29185 6. Area Served: Whole building Approximate Age: 10+ yrs 7. Fuel Type: 220-240 VAC Temperature Differential: 18 8. Type: Central A/C Capacity: 1.5 Ton 9. Acceptable Visible Coil: Aluminum

    10. Acceptable Refrigerant Lines: Serviceable condition 11. Acceptable Electrical Disconnect: Breaker disconnect 12. Acceptable Exposed Ductwork: Metal 13. Acceptable Blower Fan/Filters: Direct drive with disposable filter

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 12 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Heating System Not part of inspection process: Interiors of flues or chimneys which are not readily accessible. Heat exchanger, humidifier or dehumidifier. Electronic air filter. Solar spacce heating system. Determine heat supply adequacy or distribution balance.

    Main, Crawl Space Heating System 1. Acceptable Heating System Operation: Adequate, Appears functional

    2. Manufacturer: Lennox

    3. Model Number: G51MP-48C-090-07 Serial Number: 5909J06987 4. Type: Forced air Capacity: 88,000 BTUHR 5. Area Served: Whole building Approximate Age: 6 yrs 6. Fuel Type: Propane gas

    7. Acceptable Heat Exchanger: 4 Burner 8. Unable to Inspect: 50%

    9. Acceptable Blower Fan/Filter: Direct drive with disposable filter 10. Acceptable Distribution: Metal duct

    11. Acceptable Circulator: N/A 12. Acceptable Draft Control: Automatic 13. Acceptable Flue Pipe: PVC 14. Acceptable Controls: Limit switch 15. Acceptable Devices: Temp gauge 16. Acceptable Humidifier: N/A 17. Acceptable Thermostats: Individual, Programmable - Located on left wall of main living space.

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 13 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Heating System (Continued)18. Acceptable Fuel Tank: Propane tank

    19. Tank Location: Rear yard 20. Suspected Asbestos: No

    Plumbing Not part of inspection process: Clothes washing machine connections. Interiors of flues or chimneys which are not readily accessible. Wells, well pumps, or water storage related equipment. Water conditioning systems. Solar water heating systems. Fire and lawn sprinkler systems. Private waste disposal systems. Determine; whether water supply and waste disposal systems are public or private. Quantity or quality of water supply. Operate safety valves or shut-off valves.

    Interior 1. Acceptable Service Line: Copper 2. Acceptable Main Water Shutoff: Front of house, Crawl space - City shutoff located at

    front left of property, just left of the power pole. House shut off located in crawl space front left corner.

    3. Acceptable Water Lines: Copper 4. Acceptable Vent Pipes: PVC 5. Acceptable Basement Floor Drain: None noted 6. Acceptable Drain Pipes: Cast iron, PVC

    7. Acceptable Service Caps: Accessible 8. Acceptable Kitchen Sink: fiberglass 9. Acceptable Bathroom Sink/Basin: Porcelain coated

    10. Acceptable Faucets/Traps: Stainless steel faucets w/ PVC traps 11. Acceptable Plumbing/Fixtures: PVC 12. Acceptable Tub/Surround: Fiberglass tub and ceramic tile surround 13. Acceptable Toilets: American Standard Utility Closet Water Heater

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 14 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Plumbing (Continued)14. Acceptable Water Heater Operation: Adequate - Doors to utility closet do not provide

    proper ventilation for combustion air. Recommend replacing doors with louvered doors to allow for proper air flow.

    15. Manufacturer: Whirlpool 16. Model Number: BFG1F404S3PV Serial Number: 0851T407768 17. Type: Propane Capacity: 40 Gal. 18. Approximate Age: 9 yrs Area Served: Whole building 19. Acceptable Flue Pipe: Double wall

    20. Acceptable TPRV and Drain Tube: PVC

    Exterior West, East Exterior Surface 21. Acceptable Type: Block 22. Acceptable Hose Bibs: Gate 23. Acceptable Exterior Surface Drain: Surface drain

    Gas Service 24. Acceptable Gas Service Line: Cast iron, Insulflex

    Laundry Area 25. Acceptable Washer Hose Bib: Gate valves 26. Acceptable Washer Drain: Wall mounted drain

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 15 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Attic Not part of inspection process: Accessing areas that would require disturbing of insulation, or where there is not a suitable walking surface. Air quality.

    None Attic 1. Method of Inspection: No Access 2. Acceptable Unable to Inspect: 100% - No access door due to the low roof pitch and vaulted ceiling in main

    living area. Attic access is only necessary when there is at least 30 inches of head room above the opening, there is not enough head room to allow for a proper attic access in this house.

    3. Acceptable Roof Framing: Rafter 4. Acceptable Sheathing: Unknown 5. Acceptable Ventilation: Soffit vents - Recommend additional ventilation be installed. A ridge vent could help

    ventilation of the attic space. A qualified roofing contractor is recommended to evaluate and estimate repairs.

    6. Acceptable Insulation: Unknown - Lack of access made it impossible to determine insulation type, if any. Signs of truss uplift in back bedroom may indicate need for more insulation. A certified professional should be contacted for further evaluation.

    7. Acceptable Insulation Depth: Unknown - No access 8. Acceptable Vapor Barrier: Unknown - No access 9. Acceptable Moisture Penetration: Unknown - No access. There are no signs of moisture penetration on

    interior ceilings. 10. Acceptable Bathroom Fan Venting: None

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 16 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Marginal SummaryThis summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read the complete report.

    Grounds 1. Driveway: Concrete - Concrete pitted and chipped with minor cracking. Pitting is uniform and seems age/

    weather related. Minor settlement cracks, with no signs of spread or uplift. Cracking is most likely due to settlement and does not seem on going. Heaves in concrete are possible trip hazard. Upheaval occurs at both ends where the driveway meets the concrete pad under the Porte-cochere and is a uniform 1/2 inch high for width of pad. Driveway is in overall acceptable condition, with the exception of offset area under Porte-cochere. A qualified contractor is recommended to evaluate and estimate repairs.

    1/2 Inch Heave at Porte-cochere

    Minor Settlement Crack

    Pitting is Uniform due to Weather and Age

    Tree Limbs Overhanging Roof

    2. Vegetation: Trees, Shrubs, Shrubs/Weeds - Tree limbs over hang the roof and should be cut back. All vegetation should be kept a minimum of 1 foot from structure.

    Exterior

    Signs of Weathering

    3. Fascia: Wood - Early signs of weathering evident. A qualified contractor is recommended to evaluate and estimate repairs.

    4. Soffits: Plywood - Moisture stains, paint peeling, wood rot. A certified professional should be contacted for further evaluation. Paint Peeling and Signs of Wood Rot

    Paint Peeling and Signs of Wood Rot

    5. Windows: Metal - Seals showing signs of weathering. Could lead to drafts and energy loss. Front window in master is hard to open, needs an adjustment. Fixed windows in living area are fogging due to failed seals. A certified professional should be contacted for further evaluation.

    6. Window Screens: Metal - Windows on left side of the house are missing screens.

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 17 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Marginal Summary (Continued)Roof

    Moss Growing on Shingles

    7. Main Roof Surface Material: Asphalt shingle - Moss growing on shingles. This can trap moisture and lead to premature failure. Recommend a certified professional be contacted to clean and treat the roof. Spongy areas noted, some sheathing may need replacing the next time the roof is re-shingled.

    8. Plumbing Vents: PVC - Plumbing boots nailed on bottom flanges. This is not a recommended building practice as exposed fasteners can lead to water intrusion. Roof should be monitored for signs of water intrusion. If intrusion is noted contact a certified professional for further evaluation.

    Bottom Flange of Plumbing Boot Nailed

    Bottom Flange of Plumbing Boot Nailed

    Interior

    Seperation at Ceiling / Wall Joint Can be a Sign of Truss Uplift

    9. Ceilings: Texture paint - Evidence of possible truss uplift in 3rd bedroom. Possibly due to insufficient insulation in attic, see attic notes. Monitor for further movement, if movement continues contact a certified professional for further evaluation.

    Appliances Dryer Exhaust

    Terminates Within 4 Feet of A/C Fan Unit

    10. Dryer Vent: Metal flex - Needs cleaning. Terminates within 4 feet of air conditioning fan. This can lead to lint build up on A/C fan coils reducing the life span of unit. Termination should be directed to move lint away from A/C unit.

    Electrical 11. Second bedroom closet Electric Panel Manufacturer: Cutler-Hammer - Panels should

    not be located in closets or wet areas as they constitute safety hazards. Evaluation by a licensed electrician is recommended

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 18 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.

  • Safety Issue Summary

    Grounds 1. Deck: Treated wood, Stained wood - The basement deck built to close to grade, unable to inspect the

    underside. Baluster openings too wide, should be no more than 4 inches apart. This is considered a safety hazard. Some components showing signs of weathering and should be replaced. A qualified contractor is recommended to evaluate and estimate repairs.

    Balusters Spaced More than 4 Inches

    Apart

    Not Enough Clearance for Inspection

    Decking Components Showing Signs of Rot.

    Hand Rail Less than 34 Inches in Height

    2. Railings: Wood - Hand rails should be between 34-38 inches in height. A qualified contractor is recommended to evaluate and estimate repairs.

    Hand Rail Less than 34 Inches High

    No Balusters Present

    3. Stairs (Exterior) Wood - Hand rails should be between 34-38 inches in height. Balusters should be spaced no more than 4 inches apart and should be installed vertically. A qualified contractor is recommended to evaluate and estimate repairs.

    Electrical 4. Second bedroom closet Electric Panel Manufacturer: Cutler-Hammer - Panels should

    not be located in closets or wet areas as they constitute safety hazards. Evaluation by a licensed electrician is recommended

    Optimal Home Inspection16:02 June 17, 2015 Doe, Jon

    1313 Mockingbird Ln.Page 19 of 19

    Palm-Tech Inspector, Copyright 1998-2015, PDmB, Inc.


Recommended