OUTSULATION ® MD SYSTEM ® An Exterior Wall Insulation and Finish System with Engineered Moisture Drainage That Incorporates Continuous Insulation and An Air-Water-Resistive Barrier Outsulation MD System Installation Details DS167
Transcript
Page 1: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

OUTSULATION® MD SYSTEM® An Exterior Wall Insulation and Finish System with

Engineered Moisture Drainage That Incorporates

Continuous Insulation and An Air-Water-Resistive Barrier

Outsulation MD System

Installation Details

DS167

Page 2: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

NOTE

DETAIL

TABLE OF CONTENTS

DETAIL

Outsulation® MD System®

OUTSULATION MD SYSTEM OMD 0.0.01BUILDING FACADE OMD 0.0.02DRYVIT VENT ASSEMBLY™ OMD 0.0.03INSULATION BOARD OMD 0.0.04INSULATION BOARD LAYOUT OMD 0.0.05AWRB APPLICATION OMD 0.0.06OPENING PREPARATION- OMD 0.0.07 AQUAFLASH® SYSTEM OPTIONOPENING PREPARATION- OMD 0.0.08 BACKSTOP® NT™ OPTIONOPENING FLASHING INTEGRATION OMD 0.0.09INSIDE/OUTSIDE CORNERS OMD 0.0.10OUTSIDE CORNER - HIGH IMPACT OMD 0.0.11GRADE TERMINATION OMD 0.0.12TERMINATION AT CONCRETE CURB OMD 0.0.13TERMINATION AT OMD 0.0.14 ADA COMPLIANT SIDEWALKEPS PREPARATION AT OMD 0.0.15 WALL PENETRATIONSSTOREFRONT WINDOW SILL - JAMB OMD 0.0.16STOREFRONT WINDOW HEAD OMD 0.0.17TERMINATION AT OMD 0.0.18 WOOD FRAMED DECKTERMINATION AT OMD 0.0.19 WATERPROOF DECKPREPARATION AT PARAPET/ OMD 0.0.20 WALL INTERSECTIONTERMINATION ATPARAPET - OMD 0.0.21 CAP FLASHINGTERMINATION AT FLAT ROOF - OMD 0.0.22 SOLID SUBSTRATETERMINATION AT SLOPED ROOF OMD 0.0.23VERTICAL WALL/ SUSPENDED OMD 0.0.24 SOFFIT TRANSITIONTRANSITION AT SOFFIT/ OMD 0.0.25 FASCIA INTERSECTIONFASCIA/ UNINSULATED SOFFIT OMD 0.0.26 TRANSITIONTERMINATION AT OMD 0.0.27 UNINSULATED SOFFIT VENTHORIZONTAL JOINT AT SLIP TRACK OMD 0.0.28HORIZONTAL JOINT - OMD 0.0.29 SUBSTRATE CHANGEHORIZONTAL TERMINATION OMD 0.0.30 AT STONE VENEER

HORIZONTAL TERMINATION OMD 0.0.31 AT LAP SIDINGVERTICAL EXPANSION JOINT- OMD 0.0.32 EIFSTHROUGH-WALL EXPANSION JOINT OMD 0.0.33VERTICAL EXPANSION JOINT - OMD 0.0.34 FLUSH AND RECESSED OPTIONSVERTICAL EXPANSION JOINT - OMD 0.0.35 DOUBLE SEAL OPTIONVERTICAL TERMINATION OMD 0.0.36 AT STONE VENEERPENETRATIONS OMD 0.0.37SIGN ATTACHMENT OMD 0.0.38AESTHETIC REVEALS OMD 0.0.39RECESSED GRAPHICS OMD 0.0.40PROJECTING GRAPHICS OMD 0.0.41

DRYVIT MAKES NO REPRESENTATION REGARDINGCONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDINGCODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,OR PROJECT LOCATIONS. ALL COMPONENTS INDICATEDIN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BEDESIGNED, DETAILED, AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER, ORCONTRACTOR TO BE IN CONFORMANCE WITH MODELCODES, ARCHITECTURAL, AND ENGINEERINGREQUIREMENTS PERTAINING TO SPECIFIC BUILDINGPROJECTS.

DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, ORWORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMSOR PRODUCTS.

THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THEOUTSULATION MD LIMITED COMMERCIAL WARRANTY.CONTACT DRYVIT FOR A FULL AND COMPLETE COPY OFTHE WARRANTY.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 3: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

OMD 0.0.01

NORMAL IMPACT

HIGH IMPACT

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

FRAMING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

EPS INSULATION BOARD

APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

FRAMING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT VENT ASSEMBLY

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

DRYVIT VENT TRACKDRYVIT BASE COAT

DRYVIT PANZER® REINFORCING MESH

Outsulation® MD System® Outsulation MD SystemNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ OR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 4: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

12" (305 MM) DRYVIT CLOSURE BLOCKS

DRYVIT STARTER STRIP

DRYVIT VENT TRACK™ (SEE NOTE 1)

DRYVIT VENT ASSEMBLY™

DRYVIT TRACK™ (NO VENT HOLES)OVER 6" (152 MM) DRYVIT STARTERSTRIP™

FLOORLINE EXPANSION JOINT(WHEN SPECIFIED)

DRYVIT CLOSURE BLOCKS

OMD 0.0.02

Outsulation® MD System® Building FacadeNOTE:1. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 5: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

12" (305 MM)

3/4"(19 MM)

5 5/8" (143 MM)

8" (203 MM)

2"(51 MM)

6" (152 MM)

OMD 0.0.03

Outsulation® MD System® Dryvit Vent Assembly™

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 6: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

2"(51 MM) MIN.

2'-0"(610 MM)

1/4" X 1" (6.4 MM X 25 MM) TYP. VERTICALDRAINAGE GROOVE

1/4" X 1/2" (6.4 MM X 12.7 MM)VERTICAL DRAINAGE GROOVEAT BOARD EDGES

4'-0" (1.2 M)

12"(305 MM) TYP.

OMD 0.0.04

Outsulation® MD System® Insulation Board

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 7: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

BY OTHERS

OUTSULATION MD SYSTEM

APPROVED SUBSTRATE

VERTICAL DRAINAGE GROOVES

FRAMING

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™

2'-0"(610 MM)

0'-6"(152 MM)

EPS INSULATION BOARD

DRYVIT STARTER STRIP™

Insulation Board Layout

OMD 0.0.05

Outsulation® MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 8: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

OMD 0.0.06

Outsulation® MD System® AWRB ApplicationNOTE:1. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER DETAILS, REFER TODRYVIT PUBLICATION DS840.

DRYVIT BACKSTOP® NT™ - TEXTURE

APPROVED SUBSTRATE

FRAMING

DRYVIT BACKSTOP NT - TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT AIR/WATER - RESISTIVEBARRIER COATING

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 9: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

STEP #1 STEP #2

STEP #4STEP #3

INSTALL DIAGONAL STRIP OF DRYVITAQUAFLASH MESH AT CORNERSAND EMBED IN AQUAFLASH LIQUID(SEE NOTES 1, 3 AND 4)

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 1 AND 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 6)

INSTALL DRYVIT AQUAFLASHSYSTEM AT HEADS(SEE NOTES 1 AND 4)

INSTALL DRYVIT AQUAFLASHSYSTEM AT JAMBS(SEE NOTES 1 AND 3)

OMD 0.0.07

Outsulation® MD System® AquaFlash® System Option NOTE:1. DRYVIT AQUAFLASH SHALL EXTEND TOINTERIOR FACE OF OPENING.

2. REFER TO HEAD, SILL AND JAMB DETAILSFOR FLASHING INTEGRATION.

3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.

5. AQUAFLASH SYSTEM CONSISTS OFAQUAFLASH MESH AND AQUAFLASH LIQUID.

6. FOR ADDITIONAL AIR/WATER- RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

Opening Preparation -

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 10: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

STEP #1 STEP #2

APPLY DRYVIT GRID TAPE™(SEE NOTES 1 AND 2)

TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)

6" (152 MM)MIN. (typ)

STEP #3

4" (102 MM) MIN.

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 2, 3 AND 5)

STEP #4

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING APPLIED TOFACE OF WALL (SEE NOTE 6)

Opening Preparation -Backstop® NT™ Option

OMD 0.0.08

Outsulation® MD System®NOTE:1. APPLY DRYVIT GRID TAPE ON HEAD, JAMB, ANDCORNERS OF OPENINGS AND SHEATHING JOINTS.

2. TROWEL APPLY DRYVIT BACKSTOP NT-TEXTUREOVER THE DRYVIT GRID TAPE ALL THE WAY TOINSIDE FACE OF OPENING. ALL VOIDS MUST BEFILLED; MULTIPLE PASSES MAY BE REQUIRED. ASAN OPTION, DRYVIT GRID TAPE AND DRYVITBACKSTOP NT-TEXTURE MAY ALSO BE APPLIED ATTHE SILL PRIOR TO DRYVIT AQUAFLASH SYSTEMOR FLASHING TAPE APPLICATION.

3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM AT SILL, INCLUDING CORNER SPLICES.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTS ANDPROJECT DOCUMENTS.

5. REFER TO HEAD, SILL, AND JAMB DETAILS FORFLASHING INTEGRATION.

6. FOR ADDITIONAL AIR/WATER- RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 11: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

STEP #1

REFER TO OMD 0.0.07 & OMD 0.0.08 FORPREPARATION OF OPENING PRIOR TOFLASHING INSTALLATION

STEP #2 STEP #3

REFER TO OMD 0.0.16 FORJAMB DETAIL

INSTALL WINDOW UNIT ANDASSOCIATED FLASHINGS ANDAPPLY DRYVIT AQUAFLASHSYSTEM OVER VERTICAL LEG OFFLASHING (SEE NOTES 1 AND 2)

APPLY DRYVIT AQUAFLASH®SYSTEM SPLICES LAPPING OVERLIP OF SILL PAN FLASHING.(SEE NOTES 1 AND 2)

OMD 0.0.09

Outsulation® MD System® Opening Flashing IntegrationNOTE:1. REFER TO OMD 0.0.16 FORINTEGRATION OF FLASHING.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER DETAILS, REFER TODRYVIT PUBLICATION DS840.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 12: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

8"(203 MM) MIN.

MUST OVERLAP 8" (203 MM) MIN.

SEE NOTE 3

MUST OVERLAP8" (203 MM) MIN.

(SEE NOTES 2, 3 AND 4)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

8"(203 MM)

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

EPS INSULATION

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT BACKSTOP NT-TEXTUREOVER DRYVIT GRID TAPE

DRYVIT BASE COAT

OMD 0.0.10

Outsulation® MD System® Inside/Outside CornersNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DOUBLE WRAP OUTSIDE CORNERSWITH REINFORCING MESH OR USECORNER MESH™.

3. DO NOT LAP REINFORCING MESHWITHIN 8" (203 MM) OF A CORNER.

4. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 13: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

8"(203 MM) MIN.

DRYVIT FINISH

DRYVIT BACKSTOP® NT-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT PANZER®REINFORCING MESH

DRYVIT STANDARD MESH ORSTANDARD PLUS REINFORCINGMESH OVERLAP MIN. 8" (203 MM)AT CORNER

EPS INSULATION

DRYVIT CORNER MESH™

8" (203 MM) MIN.

DRYVIT BASE COAT

DRYVIT BASE COAT

OMD 0.0.11

Outsulation® MD System® Outside Corner - High ImpactNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 14: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

8"(203 MM) MIN.

2'-0"(610 MM) MAX.(SEE NOTE 2)

OUTSULATION MDSYSTEM

BY OTHERS

DRYVIT AIR/ WATER-RESISTIVE BARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

APPROVED SUBSTRATE

EPS INSULATION

DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM(SEE NOTE 4)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

SLOPE GRADE AWAYFROM FOUNDATION WALL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BACKSTOP® NT™- TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT VENT ASSEMBLY™™

DRYVIT VENT TRACK™(SEE NOTE 3 & 5)

DRYVIT FINISH

DRYVIT BASE COAT

OMD 0.0.12

Outsulation® MD System® Grade TerminationNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 2'-0" (610 MM)DIMENSION IS EXCEEDED.

3. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™, OR DRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE, MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM.

5. LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 15: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE OUTSULATION MDSYSTEM

DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT

GRID TAPE™ (SEE NOTE 4)

DRYVIT VENT ASSEMBLY™

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT STARTER STRIP™

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE LAPPED OVERVERTICAL LEG OF DRYVIT VENTTRACK (SEE NOTES 2, 3, AND 4)

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 5)

DRYVIT COMPATIBLE SEALANT,(SEE NOTE 5)

DRYVIT BASE COAT

DRYVIT VENT TRACK™ (SEE NOTES 2 AND 3)

Section A-A

VENT ASSEMBLY LOCATION

CLOSED CELL BACKER ROD,BY OTHERS

SEALANT MATERIAL, BY OTHERS(SEE NOTE 5)

A

A

OMD 0.0.13

Outsulation® MD System® Termination At Concrete CurbNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.

3. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OR BACKSTOP NT-TEXTURE OVER GRID TAPE.

5. SEALANT SHALL TURN IN AT DRYVITVENT ASSEMBLY LOCATIONS (SEESECTION A-A) TO ALLOW FOR DRAINAGE.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 16: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

OUTSULATION MD SYSTEM

BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE APPLIED IN VERTICALNOTCHED TROWEL CONFIGURATION TOBACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

3/4" (19 MM) MIN. (SEE NOTE 4)

DRYVIT VENT ASSEMBLY™

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 7)

DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

METAL PROTECTION SHEET,BY OTHERS

ADA COMPLIANT SIDEWALK SLOPEDAWAY FOR POSITIVE DRAINAGE

2" (51 MM) MAX.OVERLAP

FULLY ADHERED FOUNDATIONWATERPROOFING MEMBRANE,

BY OTHERSCOMPRESSIBLE FILLER BOARD,BY OTHERS

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™ LAPPED OVER VERTICAL LEG OFDRYVIT VENT TRACK™ (SEE NOTES 5, 6 AND 7)

DRYVIT BASE COAT

DRYVIT VENT TRACK(SEE NOTES 5 AND 6)

OMD 0.0.14

Outsulation® MD System® Termination At ADA Compliant SidewalkNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. USE OF THIS DETAIL IS LIMITED TOSLAB-ON-GRADE APPLICATIONS.

3. INCORPORATE MEASURES TO PROTECTSTRUCTURE FROM MOISTURE INTRUSION,DAMPNESS, AND FROST HEAVE.

4. TO PREVENT DEBRIS ACCUMULATION IT ISRECOMMENDED TO TERMINATE SYSTEM2" (51MM) ABOVE SIDEWALK.

5. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.

6. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

7. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF AQUAFLASHSYSTEM OR BACKSTOP NT-TEXTURE OVERGRID TAPE.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 17: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

EPS INSULATION(SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DETAIL REINFORCING MESH9 1/2" (241 MM) X 12" (305 MM) (TYP.)(SEE NOTE 3)

OMD 0.0.15

Outsulation® MD System® EPS Preparation At Wall PenetrationsNOTE:1. LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITH CORNERS OFPENETRATION.

2. APPLY A PIECE OF 9 1/2" (241 MM) X 12" (305 MM)DETAIL REINFORCING MESH DIAGONALLY ATEACH CORNER.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 18: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

DRYVIT ADHESIVE INVERTICAL NOTCHED

TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

2 1/2"(64 MM) MIN.

1/2" (12.7 MM)

SILL PAN FLASHINGDETAIL

AIR SEAL PER MANUFACTURER'SREQUIREMENTS, BY OTHERS

DRYVIT COMPATIBLESEALANT, BY OTHERS

WRAP DRYVIT DETAILMESH® 2" (51 MM) MIN.

AT BACKSIDE OF EPS(SEE NOTE 5)

CONTINUOUS FLASHING, BYOTHERS, TURN UP 1/2" (12.7 MM) MIN.AT JAMBS - SEE DETAIL BELOW

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT,BY OTHERS (SEE NOTE 4)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2 & 3)

DRYVIT CLOSURE BLOCKDRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVITAIR/WATER-RESISTIVE

BARRIER COATING

WRAP DRYVIT DETAIL MESH®2" (51 MM) MIN. AT BACKSIDE OF EPS

SLOPED SHIM ASREQUIRED, BY OTHERS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGDRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TO RECEIVESEALANT

DRYVIT BASE COAT

EPS INSULATION BOARD

SEAL PER WINDOW MANUFACTURERREQUIREMENTS, BY OTHERS

OMD 0.0.16

Outsulation® MD System® Storefront Window Sill - JambNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.

3. DRYVIT BACKSTOP® NT-TEXTURE OVER DRYVITGRID TAPE™ IS AN ALTERNATIVE OPTION AT JAMBAND HEAD CONDITION PER DETAIL OMD 0.0.08.

4. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

5. EDGE WRAPPING METHOD IS ACCEPTABLE ATSILL AND JAMB IN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLY EMBEDDED INDRYVIT BASE COAT AT EPS EDGE AND MUSTEXTEND ONTO SUBSTRATE 2" (51 MM) MIN.

3/4" (19 MM) MIN.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 19: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

OUTSULATION MDSYSTEM

BY OTHERS

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 2)

DRYVIT AQUAFLASH SYSTEMOVER CONTINUOUS FLASHINGWITH END DAMS (SEE NOTE 2)

AIR SEAL PERMANUFACTURER'S

REQUIREMENTS,BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT FINISH

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT AQUAFLASH® SYSTEM, ORDRYVIT BACKSTOP® NT-TEXTURE OVER

GRID TAPE, OVER VERTICAL LEG OFDRYVIT TRACK (SEE NOTES 2 & 4)

DRYVIT TRACK

DRYVIT STARTER STRIP™

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

SEALANT AND FLASHING, BY OTHERS

DRYVIT BASE COAT

OMD 0.0.17

Outsulation® MD System® Storefront Window HeadNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

4. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 20: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

2" (51 MM) MIN.

FLASHING NO. 2, BY OTHERS

FLASHING NO. 3, BY OTHERS

1" (25 MM) MIN.

2-1/2" (64 MM) MIN.

DRYVIT COMPATIBLESEALANT, BY OTHERS

FLASHING NO. 1,BY OTHERS

DECK BOARD

END JOIST

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TORECEIVE SEALANT

2" (51 MM) MIN.

DRYVIT COMPATIBLESEALANT WITH BOND

BREAKER, BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT BASE COATEPS INSULATION BOARD

DRYVIT VENT ASSEMBLY™

DRYVIT AQUAFLASH® SYSTEM OVERCONTINUOUS FLASHING (NOTE 2)

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)DRYVIT VENT TRACK™(SEE NOTES 4 & 5)

DRYVIT BASE COAT

OMD 0.0.18

Outsulation® MD System® Termination at Wood Framed DeckNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DETAIL DOES NOT APPLY TOCANTILEVERED DECKS. CANTILEVEREDDECKS REQUIRE JOB SPECIFICFLASHING DETAILS.

4. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

5. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 21: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

APPROVED SUBSTRATE

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

FRAMING

SLOPE CONCRETE DECK SURFACEAWAY FROM VERTICAL WALL

2"(51 MM) MIN.

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

COMPATIBLE WATERPROOFDECK COATING, BY OTHERS

CANT STRIP, BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 4)

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™(SEE NOTES 2 & 3)

DRYVIT BASE COAT

OMD 0.0.19

Outsulation® MD System® Termination at Waterproof DeckNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

3. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™, OR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 22: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

APPROVED SUBSTRATE

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

FLASHING SLEEVE,BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 1)

8"(203 MM)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 1)

STEP #1 STEP #2

STEP #3

6"(152 MM)

6"(152 MM)

OMD 0.0.20

Outsulation® MD System® Preparation At Parapet/ Wall IntersectionNOTE:1. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 23: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

ROOFASSEMBLY

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

FRAMING,BY OTHERS

2 1/2" (64 MM) MIN.

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

APPROVED SUBSTRATE

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)(SEE NOTE 3)

DRYVIT COMPATIBLE SEALANT,BY OTHERS

DRYVIT FINISH

DRYVIT BASE COAT

OMD 0.0.21

Outsulation® MD System® Termination At Parapet - Cap FlashingNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE.

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)

METAL CAP FLASHING,BY OTHERS

ROOF ASSEMBLY, BY OTHERS

DRYVIT CLOSURE BLOCK

3. EDGE WRAPPING METHOD ISACCEPTABLE IN LIEU OF BACK WRAPPING.DRYVIT REINFORCING MESH MUST BEFULLY EMBEDDED IN DRYVIT BASE COATAT INSULATION BOARD EDGE AND EXTENDONTO SUBSTRATE 2" (51 MM).

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 24: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT VENT ASSEMBLY™

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)DRYVIT VENT TRACK™(SEE NOTES 3 & 4)

ROOF FLASHING ANDCOUNTER FLASHING,

BY OTHERS

DRYVIT COMPATIBLE SEALANT, BYOTHERS (SEE NOTE 5)

8"(203 MM) MIN.

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

ROOF ASSEMBLY,BY OTHERS

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TO

RECEIVE SEALANT

DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER

ROD, BY OTHERS (SEE NOTE 5)

3/4" (19 MM) MIN.

OMD 0.0.22

Outsulation® MD System® Termination At Flat Roof - Solid SubstrateNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

4. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.

5. DETAIL OMD 0.0.13 SECTION A-A FORSEALANT JOINT CONFIGURATION.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 25: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

2"(51 MM)

MIN.

3/4"(19 MM)

MIN.

110

100

ROOF DIVERTER(NOTE 2)

12"(305 MM)

6"(152 MM)

6"(152 MM)

FRAMINGAPPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

ROOF STEP FLASHING, BY OTHERS

ROOFING SHINGLES

ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

GUTTER SYSTEM SLOPEDAWAY FROM WALL

ROOF DIVERTER FLASHING, BY OTHERS(SEE NOTE 2)

DRYVIT FINISH

EPS INSULATION BOARDDRYVIT BASE COATDRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEMOVER FLASHING (SEE NOTE 8)

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™(SEE NOTES 5 & 6)

DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID

TAPE™ (SEE NOTE 8)

OMD 0.0.23

Outsulation® MD System® Termination at Sloped RoofNOTE:1. EXTEND DIVERTER FLASHING (KICKOUT) AMINIMUM OF 1" (25 MM) BEYOND FACE OF THESYSTEM.

2. ROOF DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN. 24 GAGEWITH WATER TIGHT SEAMS.

3. EXTEND ROOFING UNDERLAYMENT 5" (127 MM)UP VERTICAL WALL BEHIND METAL FLASHING.

4. FOR ADDITIONAL SLOPED ROOF DETAILS,REFER TO DRYVIT PUBLICATION DS106.

5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

6. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.

7. METAL FLASHINGS ARE 10" (254 MM) X 2" (51 MM)LONGER THAN THE EXPOSED PORTION OF THEROOFING SHINGLE AND ARE BENT IN HALFTO ALLOW FOR TWO 5" (127 MM) LEGS. ALTHOUGHNOT SHOWN, METAL FLASHINGS ARE STEPFLASHED (INTERWOVEN) WITH ROOFINGSHINGLES.

8. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 26: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT ADHESIVE

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 4)

APPROVED SUBSTRATE

FRAMING

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 2 & 3)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 5)

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,

BY OTHERS (SEE NOTE 2 & 3)

DRYVIT BASE COAT

DRYVIT CLOSURE BLOCK

APPROVED SUBSTRATE

EPS INSULATION BOARD(SEE NOTE 6)

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION TO BACK OF EPS

OMD 0.0.24

Outsulation® MD System® Vertical Wall/Suspended Soffit TransitionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DRAWINGS.

2. SEALANT JOINT IS REQUIRED FORSUSPENDED SOFFITS. OPTIONAL FORRIGIDLY FRAMED.

3. DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT.

4. DRYVIT AIR/WATER-RESISTIVE BARRIERIS REQUIRED OVER VERTICAL SUBSTRATES.APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESSREQUIRED AS PART OF A CONTINUOUS AIRBARRIER SYSTEM.

5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

6. GROOVED BOARD AND FLAT STOCK EPSARE ACCEPTABLE FOR USE IN HORIZONTALSOFFIT CONDITION.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 27: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

FRAMING

APPROVED SUBSTRATE

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 6)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT FINISH

DRYVIT ADHESIVE APPLIEDTO BACK OF EPS

DRYVIT DETAIL MESH®

DRIP GROOVE

DRYVIT DETAIL MESH®

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™ -TEXTURE OVER DRYVIT GRIDTAPE™ (SEE NOTE 4)

DRYVIT VENT TRACK™(SEE NOTES 2 AND 3)

DRYVIT VENT ASSEMBLY™

DRYVIT BACKSTOP NT- TEXTUREOVER DRYVIT GRID TAPE

DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD(SEE NOTE 5)

OMD 0.0.25

Outsulation® MD System® Transition At Soffit/Fascia IntersectionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

3. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OFAQUAFLASH SYSTEM OR BACKSTOP NT™-TEXTURE OVER GRID TAPE.

5. GROOVED BOARD AND FLAT STOCK EPSARE ACCEPTABLE FOR USE INHORIZONTAL SOFFIT CONDITION.

6. DRYVIT AIR/WATER RESISTIVE BARRIERIS REQUIRED OVER VERTICALSUBSTRATES. APPLICATION OVERHORIZONTAL SOFFIT SUBSTRATE ISOPTIONAL UNLESS REQUIRED AS PART OFA CONTINOUS AIR BARRIER SYSTEM.

1"(25 MM) MIN.

2-1/2"(64 MM) MIN.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 28: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS 2" (51 MM) MIN.

DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™ -TEXTURE OVER DRYVIT GRIDTAPE™ (SEE NOTE 4)DRYVIT VENT TRACK™(SEE NOTES 5 & 6)

DRYVIT VENT ASSEMBLY™

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

CASING BEAD, BY OTHERS

DRYVIT BASE COAT

FRAMING

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

OMD 0.0.26

Outsulation® MD System® Fascia/Uninsulated Soffit TransitionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. SOFFITS WITHOUT EPS INSULATIONREQUIRE EXPANSION JOINTS EVERY20 FT (6.1 M).

3. REFER TO DRYVIT PUBLICATION DS173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF AQUAFLASH SYSTEM.

5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

6. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 29: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

FRAMING, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT BASE COAT

SOFFIT VENT, BY OTHERS

DRYVIT FINISH

OMD 0.0.27

Outsulation® MD System® Termination at Uninsulated Soffit VentNOTE:1. CONTROL JOINTS ARE RECOMMENDEDEVERY 20 FT (6.1 M).

2. REFER TO DRYVIT PUBLICATION DS173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.

3. SEAL ALL BUTT JOINTS, INTERSECTIONS,AND ENDS OF VENTS WITH COMPATIBLESEALANT.

4. SEE DRYVIT PUBLICATION DS842 FORADDITIONAL DIRECT APPLIED DETAILS.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 30: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

A

DRYVIT AQUAFLASHSYSTEM

(SEE NOTE 7)

SLIP TYPECONNECTION

Section A-A

SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE AT VENTASSEMBLY ONLY (SEE NOTES 5 AND 8)

VENT ASSEMBLY LOCATION

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 7)CLOSED CELL BACKER ROD,

BY OTHERS

SEALANT MATERIAL, BY OTHERS

OMD 0.0.28

Outsulation® MD System® Horizontal Joint at Slip TrackNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.

2. EXPANSION JOINT IN THE OUTSULATION MD SYSTEM ISNECESSARY WHERE SIGNIFICANT DIFFERENTIALMOVEMENT IS EXPECTED AT FLOOR LINES.

3. LIGHTLY SAND SURFACE OF DRYVIT VENT TRACK TOMAXIMIZE ADHESION.

4. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF BREAK IN SHEATHING.

5. SEALANT SHALL NOT BE IN DIRECT CONTACT WITHASPHALTIC ADHESIVE ON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITH POLYETHYLENE TAPEOR BACKER ROD.

6. SLOT IN DRYVIT VENT TRACK MUST BE POSITIONED OVERDRYVIT VENT ASSEMBLY.

7. DRYVIT FLASHING TAPE SURFACE CONDITIONER ANDDRYVIT FLASHING TAPEMAY BE USED IN LIEU OF DRYVIT AQUAFLASH SYSTEM.

8. SEALANT SHALL TURN IN AT DRYVIT VENT ASSEMBLYLOCATIONS TO ALLOW FOR DRAINAGE. SEE SECTION A-A.

CLOSED CELL BACKERROD, BY OTHERS

(SEE NOTE 4)

DRYVIT VENT TRACK™(SEE NOTES 3 & 6)

DRYVIT VENT ASSEMBLY™

DRYVIT DEMANDIT® OR COLOR PRIME™ ONSURFACES TO RECEIVE SEALANT

SLOPE SURFACE OUTSIDE OF SEALANT1:5 MIN. OUTWARD TO DRAIN

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)

EPS INSULATION BOARD

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

APPROVED SUBSTRATE

A3/4"

(19 MM) MIN.

DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 5)

DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 7)

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS(SEE NOTES 4, 5, AND 8)

DRYVIT CLOSURE BLOCK

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 31: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

DRYVIT VENT ASSEMBLY™™

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

SLOPE SURFACE OUTSIDE OF SEALANT1:5 MIN. OUTWARD TO DRAIN

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)

EPS INSULATION BOARD

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGDRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

APPROVED SUBSTRATE

A

A3/4"

(19 MM) MIN.

Section A-A

SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTES 3 AND 6)

VENT ASSEMBLY LOCATION

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)CLOSED CELL BACKER ROD,BY OTHERS

SEALANT MATERIAL, BY OTHERS

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 5)

DRYVIT COMPATIBLE SEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS (SEE NOTES 3 AND 6)

DRYVIT VENT TRACK™ (SEE NOTES 2 & 4)

WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)

DRYVIT CLOSURE BLOCK

DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 3)

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)

OMD 0.0.29

Outsulation® MD System® Horizontal Joint - Substrate ChangeNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

3. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

4. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.

5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.

6. SEALANT SHALL TURN IN AT DRYVIT VENTASSEMBLY LOCATIONS TO ALLOW FORDRAINAGE. SEE SECTION A-A.

DRYVIT STARTER STRIP™

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 32: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

SEALANT WITH BOND BREAKER, BY OTHERS

FRAMINGAPPROVED SUBSTRATE

PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT FINISHDRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVE BARRIERCOATING (SEE NOTE 3)

3/4"(19 MM)

MIN.

DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 2)

CONTINUOUS FLASHING, BY OTHERS

STONE VENEER SYSTEM,BY OTHERS

DRYVIT VENT ASSEMBLY™

DRYVIT VENT TRACK™ (SEE NOTES 4 & 5)

DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 6)

DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

Section A-A

SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTE 6)

VENT ASSEMBLY LOCATION

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

CLOSED CELL BACKER ROD,BY OTHERS

SEALANT MATERIAL, BY OTHERS

A

A

OMD 0.0.30

Outsulation® MD System® Horizontal Termination at Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVIT AIR/WATER-RESISTIVE BARRIER COATING BENEATHCLADDINGS OTHER THAN DRYVIT EIFS,REFER TO DRYVIT PUBLICATION DS840.

4. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.

5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.

6. SEALANT SHALL TURN IN AT DRYVIT VENTASSEMBLY LOCATIONS TO ALLOW FORDRAINAGE. SEE SECTION A-A.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 33: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

FRAMING

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

SEALANT WITH BOND BREAKER,BY OTHERS

LAP SIDING, BY OTHERS

CONTINUOUS FLASHING,BY OTHERS

3/4"(19 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT FINISH

DRYVIT BASE COATDRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 3)

DRYVIT AQUAFLASH® SYSTEM ORBACKSTOP® NT™-TEXTURE OVERDRYVIT GRID TAPE™ (SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT VENT TRACK™(SEE NOTES 4 & 5)

DRYVIT BASE COAT

SEALANT WITH BOND BREAKER,BY OTHERS

DRYVIT VENT ASSEMBLY™

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 6)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

Section A-A

SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTE 6)

VENT ASSEMBLY LOCATIONDRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

CLOSED CELL BACKER ROD,BY OTHERS

SEALANT MATERIAL, BY OTHERS

A

A

OMD 0.0.31

Outsulation® MD System® Horizontal Termination at Lap SidingNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER- RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THANDRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

4. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.

5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.

6. SEALANT SHALL TURN IN AT DRYVITVENT ASSEMBLY LOCATIONS TO ALLOWFOR DRAINAGE. SEE SECTION A-A.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 34: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

3/4" (19 MM) MIN.

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

2

OMD 0.0.32

Outsulation® MD System® Vertical Expansion Joint - EIFSNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EIFS EXPANSION JOINTS ARE REQUIREDIN CONTINUOUS ELEVATIONS ATINTERVALS NOT EXCEEDING 75 FT (23 M).

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 35: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

FRAMING

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

OPTIONAL SECONDARY SEAL, BY OTHERS

DRYVIT DEMANDIT OR COLOR PRIME ONSURFACES TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

DRYVIT DETAIL MESH WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

OPTIONAL SECONDARY SEAL, BY OTHERS

CLOSED CELL BACKER ROD, BY OTHERS (SEE NOTE 4)DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

3/4" (19 MM) MIN.

3/4" (19 MM) MIN.

FRAMING

APPROVED SUBSTRATE

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT BASE COAT

APPROVED SUBSTRATE

OMD 0.0.33

Outsulation® MD System® Through-Wall Expansion JointNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

4. LOCATE EXTERNAL SEALANT JOINTWITHIN 2" (51 MM) OF SUBSTRATE JOINT.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 36: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

FRAMING

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

DRYVIT BACKSTOP® NT™ - TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

FLUSH OPTION

RECESSED OPTION

3/4" (19 MM) MIN.

3/4" (19 MM) MIN.

APPROVED SUBSTRATE

OMD 0.0.34

Outsulation® MD System® Vertical Expansion Joint - Flush and Recessed OptionsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 37: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

©Dryvit Systems, Inc.Issued: 10/2016

3/4" (19 MM) MIN.

REAR SEAL

FACE SEAL

VENT

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)

REAR SEAL

FACE SEAL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

VENT

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

FRAMING

DRYVIT BACKSTOP® NT™ - TEXTUREOVER DRYVIT GRID TAPE™

APPROVED SUBSTRATE

OMD 0.0.35

Outsulation® MD System® Vertical Expansion Joint - Double Seal OptionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Page 38: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

3/4" (19 MM) MIN.

FRAMINGAPPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

BEDDING COAT AND STONEVENEER SYSTEM, BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 2)DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

EPS INSULATION BOARD

DRYVIT REINFORCING MESHEMBEDDED IN BASE COAT

PAPER BACKED EXPANDEDMETAL LATH, BY OTHERS

ANGLE STOP FOR STONEVENEER SYSTEM, BY OTHERS

DRYVIT BASE COAT

OMD 0.0.36

Outsulation® MD System® Vertical Termination At Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIERCOATING BENEATH CLADDINGS OTHERTHAN DRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 39: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

3/4"(19 MM)

MIN.

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

SECONDARY SEAL, BY OTHERS

FRAMING

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT DEMANDIT OR COLOR PRIMEON SURFACES TO RECEIVE SEALANT

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

DRYVIT BASE COAT

OMD 0.0.37

Outsulation® MD System® PenetrationsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 40: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

1/2" (12.7 MM) MIN.

FRAMING

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT FINISH

SCREW/BOLT ATTACHMENT TO BUILDINGFRAMING/BLOCKING, BY OTHERS

NEOPRENE WASHER, BY OTHERSSIGN FIXTURE, BY OTHERS

DRYVIT COMPATIBLE SEALANT AND BONDBREAKER TAPE, BY OTHERS (SEE NOTE 2)NON-CORROSIVE PIPE SLEEVE, BYOTHERS, SET IN SEALANT

BLOCKING, SECURED TO FRAMING

DRYVIT BASE COAT

OMD 0.0.38

Outsulation® MD System® Sign AttachmentNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. PERIMETER OF PIPE SLEEVE ISCAULKED TO PREVENT WATER ENTRYINTO WALL.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 41: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

2" (51 MM) MIN.

DRYVIT DETAIL MESH® EMBEDDED IN DRYVIT BASECOAT. OVERLAP REINFORCING MESH 2 1/2" (64 MM)

DRYVIT BASE COAT

OMD 0.0.39

Outsulation® MD System® Aesthetic RevealsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SLOPE BOTTOM EDGE OF REVEAL FORPOSITIVE DRAINAGE.

2 1/2" (64 MM)

2 1/2" (64 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 42: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

BY OTHERS

2" (51 MM) MIN.

OUTSULATION MDSYSTEM

OVERLAP 2 1/2" (64 MM)

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

DRYVIT BASE COAT

OMD 0.0.40

Outsulation® MD System® Recessed Graphics

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 43: OUTSULATION MD SYSTEM - Dryvit · outsulation® md system® outsulation md system omd 0.0.01 building facade omd 0.0.02 dryvit vent assembly™ omd 0.0.03 insulation board omd 0.0.04

NOTE:1. MAXIMUM THICKNESS OF EPS BUILTOUT SHAPES SHALL NOT EXCEED13" (330 MM) AT ANY POINT MEASUREDFROM THE SUBSTRATE.

BY OTHERS

OUTSULATION MDSYSTEM

OVERLAP MESH2 1/2" (64 MM)

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT ADHESIVE

EPS SHAPE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT BASE COAT

OMD 0.0.41

Outsulation® MD System® Projecting Graphics

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.