+ All Categories
Home > Documents > P74x_EN_M_H54

P74x_EN_M_H54

Date post: 07-Nov-2014
Category:
Upload: elkhalfi
View: 32 times
Download: 0 times
Share this document with a friend
Popular Tags:
490
MiCOM P741, P742, P743 P74x/EN M/H54 © 2012. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. GRID Technical Manual Differential Busbar Protection Relay Platform Hardware Version: J and K Platform Software Version: 33 Publication Reference: P74x/EN M/H54
Transcript
Page 1: P74x_EN_M_H54

MiCOM P741, P742, P743

P74x/EN M/H54 © 2012. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice.

GRID

Technical Manual

Differential Busbar Protection Relay

Platform Hardware Version: J and K Platform Software Version: 33 Publication Reference: P74x/EN M/H54

Page 2: P74x_EN_M_H54
Page 3: P74x_EN_M_H54

CONTENTS

Update Documentation P74x/EN AD/xxx

Section 1 Introduction P74x/EN IT/H54

Section 2 Technical Data P74x/EN TD/H54

Section 3 Getting Started P74x/EN GS/H54

Section 4 Settings P74x/EN ST/H54

Section 5 Operation P74x/EN OP/H54

Section 6 Application Notes P74x/EN AP/H54

Section 7 Programmable Logic P74x/EN PL/H54

Section 8 Measurements and Recording P74x/EN MR/H54

Section 9 Firmware Design P74x/EN FD/H54

Section 10 Commissioning P74x/EN CM/H54

Section 11 Maintenance P74x/EN MT/H54

Section 12 Troubleshooting P74x/EN TS/H54

Section 13 SCADA Communications P74x/EN SC/H54

Section 14 Symbols and Glossary P74x/EN SG/H54

Section 15 Installation P74x/EN IN/H54

Section 16 Firmware and Service Manual Version History P74x/EN VH/H54

TD

N/A

IT

ST

GS

OP

AP

PL

MR

FD

CM

VH

TS

SC

SG

IN

MT

Page 4: P74x_EN_M_H54
Page 5: P74x_EN_M_H54

Safety Section Pxxx/EN SS/G11

SAFETY SECTION

Page 6: P74x_EN_M_H54

Pxxx/EN SS/G11 Safety Section

Page 7: P74x_EN_M_H54

Safety Section Pxxx/EN SS/G11

(SS) - 1

CONTENTS

1. INTRODUCTION 3

2. HEALTH AND SAFETY 3

3. SYMBOLS AND LABELS ON THE EQUIPMENT 4

3.1 Symbols 4

3.2 Labels 4

4. INSTALLING, COMMISSIONING AND SERVICING 4

5. DE-COMMISSIONING AND DISPOSAL 7

6. TECHNICAL SPECIFICATIONS FOR SAFETY 7

6.1 Protective fuse rating 7

6.2 Protective class 7

6.3 Installation category 7

6.4 Environment 7

Page 8: P74x_EN_M_H54

Pxxx/EN SS/G11 Safety Section (SS) - 2

Page 9: P74x_EN_M_H54

Safety Section Pxxx/EN SS/G11

(SS) - 3

STANDARD SAFETY STATEMENTS FOR ALSTOM GRID EQUIPMENT

1. INTRODUCTION This Safety Section and the relevant equipment documentation provide full information on safe handling, commissioning and testing of this equipment. This Safety Section also includes reference to typical equipment label markings.

The technical data in this Safety Section is typical only, see the technical data section of the relevant equipment documentation for data specific to a particular equipment.

Before carrying out any work on the equipment the user should be familiar with the contents of this Safety Section and the ratings on the equipment’s rating label.

Reference should be made to the external connection diagram before the equipment is installed, commissioned or serviced.

Language specific, self-adhesive User Interface labels are provided in a bag for some equipment.

2. HEALTH AND SAFETY The information in the Safety Section of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition.

It is assumed that everyone who will be associated with the equipment will be familiar with the contents of this Safety Section, or the Safety Guide (SFTY/4L M).

When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and also cause personal injury or physical damage.

Before working in the terminal strip area, the equipment must be isolated.

Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

• Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected;

• Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it;

• Are trained in the care and use of safety apparatus in accordance with safety engineering practices;

• Are trained in emergency procedures (first aid).

The equipment documentation gives instructions for its installation, commissioning, and operation. However, the manuals cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Alstom Grid technical sales office and request the necessary information.

Page 10: P74x_EN_M_H54

Pxxx/EN SS/G11 Safety Section (SS) - 4

3. SYMBOLS AND LABELS ON THE EQUIPMENT For safety reasons the following symbols which may be used on the equipment or referred to in the equipment documentation, should be understood before it is installed or commissioned.

3.1 Symbols

Caution: refer to equipment documentation

Caution: risk of electric shock

Protective Conductor (*Earth) terminal

Functional/Protective Conductor (*Earth) terminal.

Note: This symbol may also be used for a Protective Conductor (Earth) Terminal if that terminal is part of a terminal block or sub-assembly e.g. power supply.

*NOTE: THE TERM EARTH USED THROUGHOUT THIS TECHNICAL MANUAL IS THE DIRECT EQUIVALENT OF THE NORTH AMERICAN TERM GROUND.

3.2 Labels

See Safety Guide (SFTY/4L M) for typical equipment labeling information.

4. INSTALLING, COMMISSIONING AND SERVICING

Equipment connections

Personnel undertaking installation, commissioning or servicing work for this equipment should be aware of the correct working procedures to ensure safety.

The equipment documentation should be consulted before installing, commissioning, or servicing the equipment.

Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated.

The clamping screws of all terminal block connectors, for field wiring, using M4 screws shall be tightened to a nominal torque of 1.3 Nm.

Equipment intended for rack or panel mounting is for use on a flat surface of a Type 1 enclosure, as defined by Underwriters Laboratories (UL).

Any disassembly of the equipment may expose parts at hazardous voltage, also electronic parts may be damaged if suitable electrostatic voltage discharge (ESD) precautions are not taken.

If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards.

Voltage and current connections shall be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety.

Watchdog (self-monitoring) contacts are provided in numerical relays to indicate the health of the device. Alstom Grid strongly recommends that these contacts are hardwired into the substation's automation system, for alarm purposes.

Page 11: P74x_EN_M_H54

Safety Section Pxxx/EN SS/G11

(SS) - 5

To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used.

The equipment must be connected in accordance with the appropriate connection diagram.

Protection Class I Equipment

- Before energizing the equipment it must be earthed using the protective conductor terminal, if provided, or the appropriate termination of the supply plug in the case of plug connected equipment.

- The protective conductor (earth) connection must not be removed since the protection against electric shock provided by the equipment would be lost.

- When the protective (earth) conductor terminal (PCT) is also used to terminate cable screens, etc., it is essential that the integrity of the protective (earth) conductor is checked after the addition or removal of such functional earth connections. For M4 stud PCTs the integrity of the protective (earth) connections should be ensured by use of a locknut or similar.

The recommended minimum protective conductor (earth) wire size is 2.5 mm² (3.3 mm² for North America) unless otherwise stated in the technical data section of the equipment documentation, or otherwise required by local or country wiring regulations.

The protective conductor (earth) connection must be low-inductance and as short as possible.

All connections to the equipment must have a defined potential. Connections that are pre-wired, but not used, should preferably be grounded when binary inputs and output relays are isolated. When binary inputs and output relays are connected to common potential, the pre-wired but unused connections should be connected to the common potential of the grouped connections.

Before energizing the equipment, the following should be checked:

- Voltage rating/polarity (rating label/equipment documentation);

- CT circuit rating (rating label) and integrity of connections;

- Protective fuse rating;

- Integrity of the protective conductor (earth) connection (where applicable);

- Voltage and current rating of external wiring, applicable to the application.

Accidental touching of exposed terminals

If working in an area of restricted space, such as a cubicle, where there is a risk of electric shock due to accidental touching of terminals which do not comply with IP20 rating, then a suitable protective barrier should be provided.

Equipment use

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Removal of the equipment front panel/cover

Removal of the equipment front panel/cover may expose hazardous live parts, which must not be touched until the electrical power is removed.

UL and CSA/CUL Listed or Recognized equipment

To maintain UL and CSA/CUL Listing/Recognized status for North America the equipment should be installed using UL or CSA Listed or Recognized parts for the following items: connection cables, protective fuses/fuseholders or circuit breakers, insulation crimp terminals and replacement internal battery, as specified in the equipment documentation.

Page 12: P74x_EN_M_H54

Pxxx/EN SS/G11 Safety Section (SS) - 6

For external protective fuses a UL or CSA Listed fuse shall be used. The Listed type shall be a Class J time delay fuse, with a maximum current rating of 15 A and a minimum d.c. rating of 250 Vd.c., for example type AJT15. Where UL or CSA Listing of the equipment is not required, a high rupture capacity (HRC) fuse type with a maximum current rating of 16 Amps and a minimum d.c. rating of 250 Vd.c. may be used, for example Red Spot type NIT or TIA.

Equipment operating conditions

The equipment should be operated within the specified electrical and environmental limits.

Current transformer circuits

Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to personnel and could damage insulation. Generally, for safety, the secondary of the line CT must be shorted before opening any connections to it.

For most equipment with ring-terminal connections, the threaded terminal block for current transformer termination has automatic CT shorting on removal of the module. Therefore external shorting of the CTs may not be required, the equipment documentation should be checked to see if this applies.

For equipment with pin-terminal connections, the threaded terminal block for current transformer termination does NOT have automatic CT shorting on removal of the module.

External resistors, including voltage dependent resistors (VDRs)

Where external resistors, including voltage dependent resistors (VDRs), are fitted to the equipment, these may present a risk of electric shock or burns, if touched.

Battery replacement

Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity to avoid possible damage to the equipment, buildings and persons.

Insulation and dielectric strength testing

Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.

Insertion of modules and pcb cards

Modules and PCB cards must not be inserted into or withdrawn from the equipment whilst it is energized, since this may result in damage.

Insertion and withdrawal of extender cards

Extender cards are available for some equipment. If an extender card is used, this should not be inserted or withdrawn from the equipment whilst it is energized. This is to avoid possible shock or damage hazards. Hazardous live voltages may be accessible on the extender card.

External test blocks and test plugs

Great care should be taken when using external test blocks and test plugs such as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be accessible when using these. *CT shorting links must be in place before the insertion or removal of MMLB test plugs, to avoid potentially lethal voltages.

*Note: When a MiCOM P992 Test Plug is inserted into the MiCOM P991 Test Block, the secondaries of the line CTs are automatically shorted, making them safe.

Fiber optic communication

Where fiber optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

Page 13: P74x_EN_M_H54

Safety Section Pxxx/EN SS/G11

(SS) - 7

Cleaning

The equipment may be cleaned using a lint free cloth dampened with clean water, when no connections are energized. Contact fingers of test plugs are normally protected by petroleum jelly, which should not be removed.

5. DE-COMMISSIONING AND DISPOSAL

De-commissioning The supply input (auxiliary) for the equipment may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the equipment (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to de-commissioning.

Disposal It is recommended that incineration and disposal to water courses is avoided. The equipment should be disposed of in a safe manner. Any equipment containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of the equipment.

6. TECHNICAL SPECIFICATIONS FOR SAFETY Unless otherwise stated in the equipment technical manual, the following data is applicable.

6.1 Protective fuse rating

The recommended maximum rating of the external protective fuse for equipments is 16A, high rupture capacity (HRC) Red Spot type NIT, or TIA, or equivalent. The protective fuse should be located as close to the unit as possible.

CAUTION - CTs must NOT be fused since open circuiting them may produce lethal hazardous voltages.

6.2 Protective class

IEC 60255-27: 2005 Class I (unless otherwise specified in the equipment EN 60255-27: 2005 documentation). This equipment requires a protective conductor (earth) connection to ensure user safety.

6.3 Installation category

IEC 60255-27: 2005 Installation category III (Overvoltage Category III):

EN 60255-27: 2005 Distribution level, fixed installation.

Equipment in this category is qualification tested at 5 kV peak, 1.2/50 µs, 500 Ω, 0.5 J, between all supply circuits and earth and also between independent circuits.

6.4 Environment

The equipment is intended for indoor installation and use only. If it is required for use in an outdoor environment then it must be mounted in a specific cabinet of housing which will enable it to meet the requirements of IEC 60529 with the classification of degree of protection IP54 (dust and splashing water protected).

Pollution Degree - Pollution Degree 2 Compliance is demonstrated by reference to Altitude - Operation up to 2000m safety standards.

IEC 60255-27:2005 EN 60255-27: 2005

Page 14: P74x_EN_M_H54

Pxxx/EN SS/G11 Safety Section (SS) - 8

BLANK PAGE

Page 15: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

IT

INTRODUCTION

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 16: P74x_EN_M_H54

P74x/EN IT/H54 Introduction

MiCOM P741, P742, P743

Page 17: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

(IT) 1-1

IT

CONTENTS

1. MiCOM DOCUMENTATION STRUCTURE 3 2. INTRODUCTION TO MiCOM 5 3. PRODUCT SCOPE 6

3.1 Functional overview 6

3.2 Ordering options 8

FIGURES

Figure 1: Functional diagram 7

Page 18: P74x_EN_M_H54

P74x/EN IT/H54 Introduction (IT) 1-2

MiCOM P741, P742, P743

IT

BLANK PAGE

Page 19: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

(IT) 1-3

IT

1. MiCOM DOCUMENTATION STRUCTURE The manual provides a functional and technical description of the MiCOM protection relay and a comprehensive set of instructions for the relay’s use and application.

The section contents are summarized below:

P74x/EN IT Introduction

A guide to the MiCOM range of relays and the documentation structure. General safety aspects of handling Electronic Equipment is discussed with particular reference to relay safety symbols. Also a general functional overview of the relay and brief application summary is given.

P74x/EN TD Technical Data

Technical data including setting ranges, accuracy limits, recommended operating conditions, ratings and performance data. Compliance with norms and international standards is quoted where appropriate.

P74x/EN GS Getting Started

A guide to the different user interfaces of the protection relay describing how to start using it. This section provides detailed information regarding the communication interfaces of the relay, including a detailed description of how to access the settings database stored within the relay.

P74x/EN ST Settings

List of all relay settings, including ranges, step sizes and defaults, together with a brief explanation of each setting.

P74x/EN OP Operation

A comprehensive and detailed functional description of all protection and non-protection functions.

P74x/EN AP Application Notes

This section includes a description of common power system applications of the relay, calculation of suitable settings, some typical worked examples, and how to apply the settings to the relay.

P74x/EN PL Programmable Logic

Overview of the programmable scheme logic and a description of each logical node. This section includes the factory default (PSL) and an explanation of typical applications.

P74x/EN MR Measurements and Recording

Detailed description of the relays recording and measurements functions including the configuration of the event and disturbance recorder and measurement functions.

P74x/EN FD Firmware Design

Overview of the operation of the relay’s hardware and software. This section includes information on the self-checking features and diagnostics of the relay.

P74x/EN CM Commissioning

Instructions on how to commission the relay, comprising checks on the calibration and functionality of the relay.

P74x/EN MT Maintenance

A general maintenance policy for the relay is outlined.

P74x/EN TS Troubleshooting

Advice on how to recognize failure modes and the recommended course of action. Includes guidance on whom within Alstom Grid to contact for advice.

Page 20: P74x_EN_M_H54

P74x/EN IT/H54 Introduction (IT) 1-4

MiCOM P741, P742, P743

IT

P74x/EN SC SCADA Communications

This section provides an overview regarding the SCADA communication interfaces of the relay. Detailed protocol mappings, semantics, profiles and interoperability tables are not provided within this manual. Separate documents are available per protocol, available for download from our website.

P74x/EN SG Symbols and Glossary

List of common technical abbreviations found within the product documentation.

P74x/EN IN Installation

Recommendations on unpacking, handling, inspection and storage of the relay. A guide to the mechanical and electrical installation of the relay is provided, incorporating earthing recommendations. All external wiring connections to the relay are indicated.

P74x/EN VH Firmware and Service Manual Version History

History of all hardware and software releases for the product.

Page 21: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

(IT) 1-5

IT

2. INTRODUCTION TO MiCOM MiCOM is a comprehensive solution capable of meeting all electricity supply requirements. It comprises a range of components, systems and services from Alstom Grid.

Central to the MiCOM concept is flexibility.

MiCOM provides the ability to define an application solution and, through extensive communication capabilities, integrate it with your power supply control system.

The components within MiCOM are:

− P range protection relays;

− C range control products;

− M range measurement products for accurate metering and monitoring;

− S range versatile PC support and substation control packages.

MiCOM products include extensive facilities for recording information on the state and behaviour of the power system using disturbance and fault records. They can also provide measurements of the system at regular intervals to a control centre enabling remote monitoring and control to take place.

For up-to-date information on any MiCOM product, visit our website:

www.alstom.com/grid

Page 22: P74x_EN_M_H54

P74x/EN IT/H54 Introduction (IT) 1-6

MiCOM P741, P742, P743

IT

3. PRODUCT SCOPE The MiCOM P74x differential busbar protection relays have been designed for the protection of a wide range of substation busbars from distribution to transmission voltage levels. The relays include a comprehensive range of non-protection features to aid with system diagnosis and fault analysis. The P74x offers integral biased differential busbar, breaker failure, dead zone, overcurrent and earth-fault protection and is suitable for application on solidly grounded, impedance grounded, Petersen coil grounded and isolated systems. The relays are especially suitable where a complete scheme solution is required.

The scheme comprises of three relays:

The MiCOM P741 (Central Unit)

The MiCOM P742 and P743 (Peripheral Units)

Which, together with the topology configuration software and the dynamic synoptic monitoring tool, allow full flexibility for all configurations.

3.1 Functional overview

The P74x Busbar protection contains a wide variety of protection functions. The protection features are summarized below:

PROTECTION FUNCTIONS OVERVIEW P741 P742 P743

87BB / P Phase segregated biased current differential high speed busbar protection • - -

87CZ / P Check Zone segregated biased phase current differential high speed busbar protection

• - -

87BB / N Sensitive earth fault bias current controlled busbar protection • - -

87 CZ/ N Check Zone segregated biased earth current controlled busbar protection • - -

50 / 51 / P Phase overcurrent protection (2 stages) - • •

50 / 51 / N Earth overcurrent protection (2 stages) - • •

50ST Dead zone protection (short zone between CTs and open CBs) - • •

CTS Current transformer supervision • • •

50BF Breaker failure protection (LBB) • • •

ISL Isolator discrepancy alarm - • •

Fibre optic signalling channel • • •

Digital inputs 8 16 24

Output relays 8 8 16

Virtual Digital inputs (via fibre communication) 16 16 16

Virtual Output relays (via fibre communication) 16 16 16

Front communication port (RS232) • • •

Rear communication port (Kbus/EIA(RS)485) • • •

Rear communication port (Ethernet) * Option - Option

Time synchronisation port (IRIG-B) * Option - -

Function keys 10 - 10

Programmable tri-colour LEDs 18 - 18

• Refer to the data sheet for model selection

Page 23: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

(IT) 1-7

IT

The P74x supports the following relay management functions in addition to the functions illustrated above.

• Trip circuit and coil supervision

• 4 Alternative setting groups

• Programmable function keys (P741 and P743)

• Control inputs

• Programmable scheme logic

• Programmable allocation of digital inputs and outputs

• Sequence of event recording

• Comprehensive disturbance recording (waveform capture)

• Fully customizable menu texts

• Multi-level password protection

• Power-up diagnostics and continuous self-monitoring of relay

Application overview

X

/

/

/ /

Fault records

Measurements

PSL

Local Communication

Remote comm. port

Busbar protection scheme Peripheral Unit P742 / P743

LEDsBinaryInput / output

Self monitoring

50/51/P

50/51/N

Disturbance Record

Fibre optic signaling channel

50BF50ST CTS

Fault records

Measurements

PSL

Local Communication

Remote comm. port

Busbar protection scheme Central Unit P741

LEDsBinaryInput / output

Self monitoring

87BB/ P

87BB/ N

87CZ / N

87CZ / P

Disturbance Record

Fibre optic signaling channel

50BF CTS

ISL

FIGURE 1: FUNCTIONAL DIAGRAM

Page 24: P74x_EN_M_H54

P74x/EN IT/H54 Introduction (IT) 1-8

MiCOM P741, P742, P743

IT

3.2 Ordering options

Information Required with Order

Relay Type (Busbar Protection Relay) P741 Auxiliary Voltage Rating 24 – 48V dc only 48 – 125V dc (30 – 110V ac) 110 – 250V dc (100 – 240V ac)

1 2 3

Communication Boards

1 communication board (1 to 4 Peripheral Unit) 2 communication board (to 8 Peripheral Unit) 3 communication board (to 12 Peripheral Unit) 4 communication board (to 16 Peripheral Unit) 5 communication board (to 20 Peripheral Unit) 6 communication board (to 24 Peripheral Unit) 7 communication board ( to 28 Peripheral Unit)

1 2 3 4 5 6 7

Hardware options

Nothing IRIG-B only

1 2

Product Specific

Fixed A

Protocol Options

K-Bus/Courier IEC60870-5-103 (Via KITZ274)

1 1

Mounting

Panel Mounting M

Language

Multilingual – English, French, German, Spanish Multilingual – English, French, German, Russian

0 5

Software Version

Unless specified the latest version will be delivered * *

Settings File

Default Customer Specific

0 1

Hardware Suffix

Original K

Page 25: P74x_EN_M_H54

Introduction P74x/EN IT/H54 MiCOM P741, P742, P743

(IT) 1-9

IT

Relay Type (Busbar Protection Relay) P742 Auxiliary Voltage Rating 24 – 48V dc only 48 – 125V dc (30 – 110V ac) 110 – 250V dc (100 – 240V ac)

1 2 3

Hardware options

Without CT input With CT input

0 1

Communication options

Nothing 1

Product Specific

Fixed A

Protocol Options

K-Bus/Courier IEC60870-5-103 (Via KITZ274)

1 1

Mounting

Panel Mounting M

Language

Multilingual – English, French, German, Spanish Multilingual – English, French, German, Russian

0 5

Software Version

Unless specified the latest version will be delivered * *

Settings File

Default Customer Specific

0 1

Hardware Suffix

Original J

Page 26: P74x_EN_M_H54

P74x/EN IT/H54 Introduction (IT) 1-10

MiCOM P741, P742, P743

IT

Relay Type (Busbar Protection Relay) P743 Auxiliary Voltage Rating 24 – 48V dc only 48 – 125V dc (30 – 110V ac) 110 – 250V dc (100 – 240V ac)

1 2 3

Hardware options

Without CT input With CT input

0 1

Communication options

Nothing 1

Product Specific

Fixed A

Protocol Options

K-Bus/Courier IEC60870-5-103 (Via KITZ274)

1 1

Mounting

Panel Mounting M

Language

Multilingual – English, French, German, Spanish Multilingual – English, French, German, Russian

0 5

Software Version

Unless specified the latest version will be delivered * *

Settings File

Default Customer Specific

0 1

Hardware Suffix

Original K

Page 27: P74x_EN_M_H54

Technical Data P74x/EN TD/H54 MiCOM P741, P742, P743

TD

TECHNICAL DATA

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 28: P74x_EN_M_H54

P74x/EN TD/H54 Technical Data

MiCOM P741, P742, P743

Page 29: P74x_EN_M_H54

Technical Data P74x/EN TD/H54 MiCOM P741, P742, P743

(TD) 2-3

TD

Technical Data

Mechanical Specification Design Modular MiCOM Px40 platform relay: P741: Size 16“ case (80TE) P742: Size 8“ case (40TE) P743: Size 12“ case (60TE) Mounting is front of panel flush mounting.

Enclosure Protection Per IEC 60529: 1989 IP 52 Protection (front panel) against dust and dripping water, IPx2 except P741 – Protected against vertically falling drops of water with the product in 4 fixed positions of 15° tilt with a flow rate of 3mm/minute for 2.5 minutes.

Weight P741 with 7 comm. boards 7.4 kg with 1 comm. board 6.2 kg P742 7.5 kg P743 9.2 kg

Terminals AC Current and Voltage Measuring Inputs P742 and P743 only Located on heavy duty (black) terminal block: Threaded M4 terminals, for ring lug connection. CT inputs have integral safety shorting, upon removal of the terminal block. General Input/Output Terminals For power supply, opto inputs, output contacts and COM1 rear communications. Located on general purpose (grey) blocks: Threaded M4 terminals, for ring lug connection. Case Protective Earth Connection Two rear stud connections (2 P741, 1 P742/3), threaded M4. Must be earthed (grounded) using the protective (earth) conductor for safety, minimum wire size 2.5mm2. Front Port Serial PC Interface EIA RS232 DTE, 9 pin D-type female connector. Courier protocol for interface to MiCOM S1 software. *PEB rated Maximum cable length 15 m. Front Download/Monitor Port EIA RS232, 25 pin D-type female connector. For firmware downloads. *PEB rated circuit. Rear Communications Port K-Bus/EIA (RS)485 signal levels, two wire Connections located on general purpose block, M4 screw.

For screened twisted pair cable, multidrop, 1000 m max. Courier protocol *SELV rated circuit Optional Rear IRIG-B Interface P741 only (P742 & P743 synchronized by the P741) BNC plug *SELV rated circuit 50 ohm coaxial cable. Optical Fiber Connection BFOC 2.5 (ST®) interface for multi-mode glass fibre type 62.5/125 μm, as per IEC 874-10, 850 nm short-haul fibres, one Tx and one Rx. Optical budget: 5.6 dB Data rate:2.5 Mbits Max Length: 1000 m *PEB = Protective equipotential bonded *SELV = Safety/Separated extra low voltage Both PEB and SELV circuits are safe to touch after a single fault condition.

Ratings AC Measuring Inputs Nominal frequency: 50 and 60 Hz (settable) Operating range: 45 to 65 Hz Phase rotation: ABC or ACB AC Current Nominal current (In): 1 and 5 A dual rated. (1A and 5A inputs use different transformer tap connections, check correct terminals are wired). Nominal burden per phase

1 A: <0.04VA at rated current Impedance per phase

1 A: <40mΩ over 0 - 30In Nominal burden per phase

5 A: <0.01VA at rated current Impedance per phase

1 A: <8mΩ over 0 - 30In Thermal withstand: continuous 4 In for 10 s: 30 In for 1 s; 100 In Linear to 64 In (non-offset AC current).

Page 30: P74x_EN_M_H54

P74x/EN TD/H54 Technical Data (TD) 2-4

MiCOM P741, P742, P743

TD

Power supply Auxiliary Voltage (Vx) Three ordering options: (i) Vx: 24 to 48 Vdc (ii) Vx: 48 to 110 Vdc,

and 30 to 100 Vac (rms.) (iii) Vx: 110 to 250 Vdc,

and 100 to 240 Vac (rms.). Operating Range (i) 19 to 65 V (dc only for this variant) (ii) 37 to 150 V(dc), 24 to 110 V (ac) (iii) 87 to 300 V(dc), 80 to 265 V (ac). With a tolerable ac ripple of up to 12 % for a dc supply, per IEC 60255-11: 1979. Nominal Burden Quiescent burden:

P741: 37 to 41 W P742: 16 to 23 W P743: 22 to 32 W

Additions for energised binary inputs/outputs: Per opto input: 0.09 W…(24 to 54 V), 0.12 W...(110/125 V), 0.19 W...(220/250 V). Per energised output relay: 0.13 W Power-up Time Time to power up < 30 s. Power Supply Interruption Per IEC 60255-11: 1979 The relay will withstand a 20ms interruption in

the DC auxiliary supply, without de-energising.

Per IEC 61000-4-11: 1994 The relay will withstand a 20ms interruption in

an AC auxiliary supply, without de-energising.

Note: the use of a E124 extends these limits Battery Backup Front panel mounted Type ½ AA, 3.6 V Field Voltage Output Regulated 48 Vdc Current limited at 112 mA maximum output Digital (“Opto”) Inputs Universal opto inputs with programmable voltage thresholds. May be energised from the 48 V field voltage, or the external battery supply. Rated nominal voltage: 24 to 250 Vdc Operating range: 19 to 265 Vdc Withstand: 300 Vdc. Nominal pick-up and reset thresholds: Pick-up: approx. 70 % of battery nominal set, Reset: approx. 66 % of battery nominal set. Recognition time: 7 ms

Output Contacts Standard Contacts General purpose relay outputs for signalling, tripping and alarming: Rated voltage: 300 V Continuous current: 10 A Short-duration current: 30 A for 3 s Making capacity: 250 A for 30 ms Breaking capacity: DC: 50 W resistive DC: 62.5 W inductive (L/R = 50 ms) AC: 2500 VA resistive (cos φ = unity) AC: 2500VA inductive (cos φ = 0.7) Response to command: < 5 ms Durability: Loaded contact: 10 000 operations minimum, Unloaded contact: 100 000 operations minimum. Watchdog Contacts Non-programmable contacts for relay healthy/relay fail indication: Breaking capacity: DC: 30 W resistive DC: 15 W inductive (L/R = 40 ms) AC: 375 VA inductive (cos φ = 0.7) IRIG-B Interface External clock synchronisation per IRIG standard 200-98, format B. Input impedance 6 kΩ at 1000 Hz Modulation ratio: 3:1 to 6:1 Input signal, peak-peak: 200 mV to 20 V

Environmental Conditions Ambient Temperature Range Per IEC 60255-6: 1988 Operating temperature range: -25 °C to +55 °C (or -13 °F to +131 °F). Storage and transit: -40 °C to +70 °C (or -28 °F to +158 °F). Ambient Humidity Range Per IEC 60068-2-3: 1969:

56 days at 93 % relative humidity and +40 °C

Per IEC 60068-2-30: 1980: Damp heat cyclic, six (12 + 12) hour cycles, 93 % RH, +25 to +55 °C

Page 31: P74x_EN_M_H54

Technical Data P74x/EN TD/H54 MiCOM P741, P742, P743

(TD) 2-5

TD

Type Tests Insulation Per IEC 60255-5: 2000,

Insulation resistance > 100 MΩ at 500 Vdc (Using only electronic/brushless insulation tester).

Creepage Distances and Clearances Per IEC 60255-27:2005

Pollution degree 3, Overvoltage category III, Impulse test voltage 5 kV.

High Voltage (Dielectric) Withstand (EIA RS232 ports excepted). Per IEC 60255-27:2005, 2 kV rms. AC, 1 min.

Between all case terminals connected together, and the case earth. Also, between all terminals of independent circuits. 1 kV rms. AC for 1 minute, across open watchdog contacts. 1 kV rms. AC for 1 minute, across open contacts of changeover output relays.

(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed 1994):

1.5 kV rms. AC for 1 minute, across open contacts of changeover output relays.

Impulse Voltage Withstand Test Per IEC 60255-27: 2005

Front time: 1.2 µs, Time to half-value: 50 µs,

Peak value: 5 kV, 0.5 J Between all terminals, and all terminals and case earth.

Electromagnetic Compatibility (EMC) 1 MHz Burst High Frequency Disturbance Test Per IEC 60255-22-1: 1988, Class III,

Common-mode test voltage: 2.5 kV, Differential test voltage: 1.0 kV,

Test duration: 2 s, Source impedance: 200 Ω (EIA RS232 ports excepted). Immunity to Electrostatic Discharge Per IEC 60255-22-2: 1996, Class 4, 15 kV discharge in air to user interface, display, and exposed metalwork. Per IEC 60255-22-2: 1996, Class 3, 8 kV discharge in air to all communication ports. 6 kV point contact discharge to any part of the front of the product.

Electrical Fast Transient or Burst Requirements Per IEC 60255-22-4: 2002. Test severity Class III and IV:

Amplitude: 2 kV, burst frequency 5 kHz (Class III), Amplitude: 4 kV, burst frequency 2.5 kHz (Class IV).

Applied directly to auxiliary supply, and applied to all other inputs. (EIA RS232 ports excepted). Surge Withstand Capability Per IEEE/ANSI C37.90.1: 2002:

4 kV fast transient and 2.5 kV oscillatory applied directly across each output contact, optically isolated input, and power supply circuit.

Surge Immunity Test (EIA RS232 ports excepted). Per IEC 61000-4-5: 2002 Level 4,

Time to half-value: 1.2 / 50 µs, Amplitude: 4 kV between all groups and case earth, Amplitude: 2 kV between terminals of each group.

Immunity to Radiated Electromagnetic Energy Per IEC 60255-22-3: 2000, Class III:

Test field strength, frequency band 80 to 1000 MHz: 10 V/m,

Test using AM: 1 kHz / 80%, Spot tests at 80, 160, 450, 900 MHz Per IEEE/ANSI C37.90.2: 1995:

25 MHz to 1000 MHz, zero and 100% square wave modulated.

Field strength of 35 V/m. Radiated Immunity from Digital Communications Per EN61000-4-3: 2002, Level 4:

Test field strength, frequency band 800 to 960 MHz, and 1.4 to 2.0 GHz:

30 V/m, Test using AM: 1 kHz / 80%. Radiated Immunity from Digital Radio Telephones Per ENV 50204: 1995 10 V/m, 900 MHz and 1.89 GHz. Immunity to Conducted Disturbances Induced by Radio Frequency Fields Per IEC 61000-4-6: 1996, Level 3,

Disturbing test voltage: 10 V

Page 32: P74x_EN_M_H54

P74x/EN TD/H54 Technical Data (TD) 2-6

MiCOM P741, P742, P743

TD

Power Frequency Magnetic Field Immunity Per IEC 61000-4-8: 1994, Level 5,

100 A/m applied continuously, 1000 A/m applied for 3 s.

Per IEC 61000-4-9: 1993, Level 5, 1000 A/m applied in all planes.

Per IEC 61000-4-10: 1993, Level 5, 100 A/m applied in all planes at 100 kHz/1 MHz with a burst duration of 2 s.

Conducted Emissions Per EN 55022: 1998:

0.15 – 0.5 MHz, 79 dBμV (quasi peak) 66 dBμV (average) 0.5 – 30 MHz, 73 dBμV (quasi peak) 60 dBμV (average).

Radiated Emissions Per EN 55022: 1998:

30 – 230 MHz, 40 dBμV/m at 10 m measurement distance 230 MHz – 1 GHz, 47 dBμV/m at 10 m measurement distance.

EU Directives EMC Compliance Per 89/336/EEC:

Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route. Product Specific Standards were used to establish conformity:

EN50263: 2000 Product Safety Per 73/23/EEC: Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: IEC 60255-27:2005 EN 60255-5:2001.

Mechanical Robustness Vibration Test Per IEC 60255-21-1: 1996 Response Class 2 Endurance Class 2 Shock and Bump Per IEC 60255-21-2: 1995 Shock response Class 2 Shock withstand Class 1 Bump Class 1 Seismic Test Per IEC 60255-21-3: 1995 Class 2

Page 33: P74x_EN_M_H54

Technical Data P74x/EN TD/H54 MiCOM P741, P742, P743

(TD) 2-7

TD

Protection Functions Busbar trip (including trip relay closing time): 11 ms (min) 13 ms (typical)

Performance Data

Three phase overcurrent protection All quoted operating times include the closure of the trip output contact. Accuracy Pick-up: Setting ±5 % Drop-off: 0.95 x Setting ±5 % Min. trip level of IDMT elements:

1.05 x Setting ±5 % IDMT shape: ±5 % or 40 ms whichever is

greater (under reference conditions)* IEEE reset: ±5 % or 40 ms whichever is

greater DT operation: ±2 % or 50 ms whichever is

greater DT reset: Setting ±5 % Characteristic

UK curves: IEC 60255-3 … 1998 US curves: IEEE C37.112 … 1996

Dead Zone Protection Accuracy Pick-up: Setting ± 5% Drop-off: >0.95 x Setting Min. trip level: 1.05 x Setting ± 5%

Earth Fault Protection Accuracy Pick-up: Setting ± 5% Drop-off: >0.85 x Setting Min. trip level of IDMT elements: 1.05 x Setting ± 5% IDMT characteristic shape: ± 5 % or 40 ms

whichever is greater (under reference conditions)*

IEEE reset: ±10 % or 40 ms whichever is greater

DT operation: ±2 % or 50 ms whichever is greater

DT reset: ± 5% or 50 ms whichever is greater Repeatability: 7.5 %

Transient overreach and overshoot Accuracy Additional tolerance due to increasing X/R ratios: ± 5% over the X/R ratio of 1 to 90 Overshoot of overcurrent elements: < 40 ms

Programmable scheme logic Accuracy Output conditioner timer: Setting ±2 % or 50 ms whichever is greater Dwell conditioner timer: Setting ±2 % or 50 ms whichever is greater Pulse conditioner timer: Setting ±2 % or 50 ms whichever is greater

Measurements Accuracy Phase current: ±1.0 % of reading Phase local current: ±1.0 % of reading

or ±(f-fn)/fn % Phase remote current: ±1.0 % of reading

or ±(f-fn)/fn % Phase differential current: ±5.0 % Bias current: ±5.0 % Frequency: ±1 %

Disturbance records Accuracy Waveshape : Comparable with applied

quantities Magnitude and relative phases: ±5 % of

applied quantities Duration: ±2 % Trigger position: ±2 %

(minimum trigger 100 ms)

Reference conditions Ambient temperature: 20 °C

Frequency Tracking Range 45 to 65 Hz

Breaker failure Accuracy Reset time = 25 ms from: start to [(TBF2 or TBF4) - 30ms] Reset time = 15 ms from: [(TBF2 or TBF4) - 30ms] to [TBF2 or TBF4] ±2 % or 10 ms whichever is greater Thresholds: settings ±5 % Step 5 ms

Page 34: P74x_EN_M_H54

P74x/EN TD/H54 Technical Data (TD) 2-8

MiCOM P741, P742, P743

TD

Settings, Measurements and Records List

Settings List

Global Settings (System Data): Language: English/French/German/Spanish Frequency: 50/60 Hz

Common conventional ratios (CU) Primary basis current (virtual) Ibp: 1000A

Current transformers (PU) Phase CT Primary: 1...30.000 A Phase CT Secondary In: 1 A or 5 A

Phase Fault elements (CU) Phase current slope adjustment

k2: 0.20...0.90 Phase differential current threshold

ID>2: 50 A... 30 kA Check Zone slope adjustment kCZ: 0.00...

0.90 Check Zone differential current threshold

IDCZ >2: 50 A... 30 kA Circuitry fault slope adjustment

ID>1: 10...500 A Circuitry fault threshold

k1: 0.00...0.50 Circuitry fault alarm timer

ID>1 tCF: 0.1... 600.0 s

Sensitive earth fault Option for high neutral impedance:

Disabled/Enabled Threshold for sensitive Earth fault with flowing

current control: IbiasPh>Cur.: 50 A... 30 kA

Residual current slope adjustment kN2: 0.00...0.90

Residual differential current threshold: IDN>2: 10 A... 30 kA

Residual Check Zone current slope adjustment kNCZ: 0.00...0.90

Residual Check Zone differential current threshold: IDNCZ>2: 10 A... 30 kA

Circuitry fault slope adjustment kN1: 0.00...0.50

Circuitry fault threshold: IDN>1: 10...500 A

Circuitry fault alarm timer IDN>1 tCF: 0.1... 600.0 s

Current transformer and feeder characteristics Class: 5P (IEC185) X (BS3958) TPX (IEC 44-6) TPY (IEC 44-6) TPZ (IEC 44-6) Min. Knee point voltage (BS 3958):

Vk: 20 V - 5 kV Rated Burden (IEC 44-6): S: 5 … 200 (step 5) Rated Resistive Burden (IEC 44-6): rRB: data calculated from rated burden Rated short-circuit current factor:

Kscc: 10...50 (step 5) Secondary resistance (Ω): RCT: 0.1 ... 50.0 Ω External loop resistance Eff. Burden (Ω):

RB: 0.1 ... 200.0 Ω External loop resistance

Eff. Burden VA (Data calculated from Eff. Burden Ohm)

Blocking of 87BB on phase-phase feeder fault for external ph-ph fault detection - (>1.5 max ph-ph fault current infeed) with Ultra high speed detection <1 ms: I>BB: 0.25... 20 xIn

Blocking of 87BB on earth/feeder fault (external earth fault detection) - (>1.5 max earth fault current infeed. Ultra high speed detection required <1 ms): IN>BB: 0.25... 30 kA

Supervision of I0 calculation: Kce: 0.01 ... 1.00 I0 error alarm time delay: Tce: 0.0 … 10.0 s

Dead Zone protection (PU) Phase threshold:

I>DZ: 0.05...4.00 xIn Time delay: 0.00…100.00 s Disabled/Enabled Neutral threshold:

IN>DZ: 0.05...4.00 xIn Time delay: 0.00…100.00 s

Breaker failure protection (PU) Caution: the following current set values are expressed in multiple of the local CT’s nominal rated current inp (primary) or ins (secondary). Breaker Failure 1ST phase O/C threshold

(dead pole detection for 50BF): I<: 0.05 ... 1.00 xIn

Confirmation I>: Disabled/Enabled 2nd phase O/C threshold:

I>: 0.05...4.00 xIn Confirmation IN>: Disabled/Enabled 2nd residual O/C threshold:

IN>: 0.05...4.00 xIn

Page 35: P74x_EN_M_H54

Technical Data P74x/EN TD/H54 MiCOM P741, P742, P743

(TD) 2-9

TD

Timers for 50BF internal tripping CB fail 1 timer:

tBF1: 0.00...10.00 s CB fail 2 timer:

tBF2: 0.00...10.00 s Timers for 50BF external tripping (orders from 21 or 87Tetc…) CB fail 1 timer:

TBF3: 0.00...10.00 s CB fail 2 timer:

TBF4: 0.00...10.00 s

Overcurrent Protection (PU) Phase Fault Protection (50/51) 3 phase Overcurrent Function Status I>1:

0. Disabled 1. DT 2. IEC S Inverse 3. IEC V Inverse 4. IEC E Inverse 5. UK LT Inverse 6. IEEE M Inverse 7. IEEE V Inverse 8. IEEE E Inverse 9. US Inverse 10. US ST Inverse

Current Set if “function status” ≠0 I>1: 0.10...32.00 xIn

Time delay if “function status” =1 I>1: 0.00...100.00 xIn

TMS if 2≤ ”function status” ≤5 I>1: 0.025...1.200 xIn (step 0.025)

Time dial if “function status” ≥6 I>1: 0.5...15.0 xIn

Reset Char. if “function status”≥6 I>1:

0. DT 1. Inverse

tReset if 2≤ ”function status” ≤5 OR if “Reset Char.” =1 AND “function status” ≥6

I>1: 0.0...100.0 xIn 3 phase Overcurrent threshold function status I>2:

0. Disabled 1. Blocking 87BB 2. High set I>2 3. Both

Current Set I>2: 0.10... 32.00 xIn

Time Delay if “function status” =1 I>2: 0.00...100.00 s

Earth Fault Protection (50N/51N) Residual Overcurrent Function Status IN>1: Disabled

11. DT 12. IEC S Inverse 13. IEC V Inverse 14. IEC E Inverse 15. UK LT Inverse 16. IEEE M Inverse 17. IEEE V Inverse 18. IEEE E Inverse 19. US Inverse 20. US ST Inverse

Current Set if “function status” ≠0 IN >1: 0.10...32.00 xIn

Time delay if “function status” =1 IN >1: 0.00...100.00 xIn

TMS if 2≤ ”function status” ≤5 IN >1: 0.025...1.200 xIn (step 0.025)

Time dial if “function status” ≥6 IN >1: 0.5...15.0 xIn

Reset Char. if “function status” ≥6 IN >1:

2. DT 3. Inverse

tReset if 2≤ ”function status” ≤5 OR if “Reset Char.” =1 AND “function status” ≥6 IN >1: 0.0...100.0

Residual Overcurrent threshold function status IN >2:

4. Disabled 5. Blocking 87BB 6. High set I>2 7. Both

Current Set IN >2: 0.10...32.00 xIn

Time Delay if “function status” =1 IN >2: 0.00...100.00 s

CB Control (PU) Prot Trip Pulse: 0.05...2.00 s Trip Latched: Disabled/Enabled Rest Trip Latch: Yes/No CB Control by: Disabled/Enabled Man Close Pulse: 0.1...5.0 s Man Trip Pulse: 0.1...5.0 s Man Close Delay: 0... 60 s

Date and Time IRIG-B Sync: Disabled/Enabled Battery Alarm: Disabled/Enabled

Configuration Setting Group: Select via Menu Select via Opto Active Settings: Group 1/2/3/4 Setting Group 1: Disabled/Enabled Setting Group 2: Disabled/Enabled Setting Group 3: Disabled/Enabled Setting Group 4: Disabled/Enabled

Page 36: P74x_EN_M_H54

P74x/EN TD/H54 Technical Data (TD) 2-10

MiCOM P741, P742, P743

TD

CU Only Diff Busbar Prot: Disabled/Enabled PU Only Dead Zone Prot: Disabled/Enabled CB Fail & I>: Disabled/Enabled BB Trip Confirm: Disabled/Enabled Overcurrent Prot: Disabled/Enabled Earth Fault Prot: Disabled/Enabled CU & PU Setting Values: Primary/Secondary LCD Contrast: (Factory pre-set)

Fault Recorder Records for the last 5 faults Central Unit: Active Setting group Faulty phase Protection started/operated (87BB, 50BF,

Dead Zone…) Fault occurrence time and duration Check Zone values (Diff. & Bias for A, B, C, N) Faulty zone(s) Topology prior the fault occurrence Peripheral Unit: Active setting group Indication of the tripped phases Protection started/operated (87BB, 50BF,

Dead Zone…) Relay Trip Time and duration Relay Trip Time Faulty phase currents (A, B, C, N)

Event Recorder Records for the last 512 events

Oscillography (Disturbance Recorder) Central Unit: Duration: Fixed value 1.2 s Trigger Position: 0.000 ...50.000s (step 0.200) Analogue Channel 1: (up to 8): Digital Input 1: (up to 32): Peripheral Unit: Duration: Settable from 0.1 to 10.5 s Trigger Position: 0.000 ...50.000s (step 0.200) Trigger Mode: Single/Extended Analogue Channel 1: (up to 8): Digital Input 1: (up to 32): Selected binary channel assignment from any

DDB status point within the relay (opto input, output contact, alarms, starts, trips, controls, logic…).

Sampling frequency: 600Hz

Communications RP1 Protocol: Courier RP1 Address (courier) 6…34 Inactivity Timer: 1…30 minutes RP1 Port Config: (Courier): K Bus / EIA485 (RS485) RP1 Comms Mode (EIA485 (RS485)): IEC60870 FT1.2 Frame IEC60870 10-Bit FrameRP1 Baud Rate

(EIA485 (RS485)): 9600/19200/38400 bits/s

COMMISSION TESTS Monitor Bit 1(up to 8):: Binary function link strings, selecting which

DDB signals have their status visible in the Commissioning menu, for test purposes

Test Mode: (CU) Enabled or Disabled 87BB trip blocked but 50BF (back trip) enable

per zone 87BB and 50BF trip blocked per zone All the protections (87BB, Dead Zone, General

50BF, Local 50BF, O/C) disabled 87BB disable but 50BF (back trip) enable for

all zones Test Mode: (PU) Enabled or Disabled 50BF Blocked Overhaul Test Pattern: Configuration of which output contacts are to

be energised when the contact test is applied.

Static Test Mode: Disabled/Enabled Opto input voltage range: 24-27 V 30-34 V 48-54 V 110-125 V 220-250 V Custom Opto Input 1

(up to # = max. opto no. fitted) Custom options allow independent thresholds

to be set per opto, from the same range as above

Filter Control:

Opto Input Labels Opto Input 1 up to: 8 for P741

16 for P742 24 for P743

User defined text string to describe the function of the particular opto input.

Outputs Labels Relay 1 up to: 8 for P741 & P742

16 for P743 User defined text string to describe the

function of the particular relay output contact.

Page 37: P74x_EN_M_H54

Getting Started P74x/EN GS/H54 MiCOM P741, P742, P743

GS

GETTING STARTED

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 38: P74x_EN_M_H54

P74x/EN GS/H54 Getting Started

MiCOM P741, P742, P743

Page 39: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-1

GS

CONTENTS

1. GETTING STARTED 3

1.1 User interfaces and menu structure 3

1.2 Introduction to the relay 3

1.2.1 Front panel 3

1.2.2 Relay rear panel 9

1.3 Relay connection and power-up 11

1.4 Introduction to the user interfaces and settings options 12

1.5 Menu structure 13

1.5.1 Protection settings 13

1.5.2 Disturbance recorder settings 13

1.5.3 Control and support settings 14

1.6 Password protection 14

1.7 Relay configuration 15

1.8 Front panel user interface (keypad and LCD) 15

1.8.1 Default display and menu time-out 16

1.8.2 Menu navigation and setting browsing 16

1.8.3 Hotkey menu navigation 16

1.8.4 Password entry 18

1.8.5 Reading and clearing of alarm messages and fault records 18

1.8.6 Setting changes 19

1.9 Front communication port user interface 19

1.9.1 Front courier port 21

1.10 MiCOM S1 relay communications basics 21

1.10.1 PC requirements 21

1.10.2 Connecting to the P74x relay using MiCOM S1 22

1.10.3 Open communication link with relay 23

1.10.4 Off-line use of MiCOM S1 25

Appendix – Relay Menu Map (Default) 27

Page 40: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-2

MiCOM P741, P742, P743

GS

FIGURES

FIGURE 1: RELAY FRONT VIEW (EXAMPLE FOR MiCOM P742 – 40 TE) 3 FIGURE 2: RELAY FRONT VIEW (EXAMPLE FOR MiCOM P743 – 60 TE) 4 FIGURE 3: P742 RELAY REAR VIEW 40TE 9 FIGURE 4: P743 RELAY REAR VIEW 60TE 10 FIGURE 5: P741 RELAY REAR VIEW 80TE 10 FIGURE 6: MENU STRUCTURE 13 FIGURE 7: FRONT PANEL USER INTERFACE 15 FIGURE 8: HOTKEY MENU NAVIGATION 17 FIGURE 9: FRONT PORT CONNECTION 19 FIGURE 10: PC – RELAY SIGNAL CONNECTION 20 FIGURE 11: COMMUNICATION SET-UP SCREEN 24

Page 41: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-3

GS

1. GETTING STARTED

1.1 User interfaces and menu structure

The settings and functions of the MiCOM protection relay can be accessed both from the front panel keypad and LCD, and via the front and rear communication ports. Information on each of these methods is given in this section to describe how to start using the relay.

1.2 Introduction to the relay

1.2.1 Front panel

The front panel of the relay is shown in Figure 1a (P742) or 1b (P741 or P743), with the hinged covers at the top and bottom of the relay shown open. Extra physical protection for the front panel can be provided by an optional transparent front cover. With the cover in place read only access to the user interface is possible. Removal of the cover does not compromise the environmental withstand capability of the product, but allows access to the relay settings. When full access to the relay keypad is required, for editing the settings, the transparent cover can be unclipped and removed when the top and bottom covers are open. If the lower cover is secured with a wire seal, this will need to be removed. Using the side flanges of the transparent cover, pull the bottom edge away from the relay front panel until it is clear of the seal tab. The cover can then be moved vertically down to release the two fixing lugs from their recesses in the front panel.

User programable

function LEDs

TRIP

ALARM

OUT OF SERVICE

HEALTHY

= CLEAR

= READ

= ENTER

SER N o

DIAG N o

Z n

Vx

Vn

V

V

1/5 A 50/60 Hz

SK 1 SK 2

Serial N° and *, V RatingsI Top cover

Fixed

function

LEDs

Bottom

cover

Battery compartment Front comms port Download/monitor port

Keypad

LCD

P0103ENb

FIGURE 1: RELAY FRONT VIEW (EXAMPLE FOR MiCOM P742 – 40 TE)

The front panel of the relay includes the following, as indicated in Figure 1a:

• a 16-character by 3-line alphanumeric liquid crystal display (LCD).

• a 9-key keypad comprising 4 arrow keys ( , , and ), an enter key ( ), a clear key ( ), a read key ( ) and 2 hot keys ( ).

• 12 LEDs; 4 fixed function LEDs on the left hand side of the front panel and 8 programmable function LEDs on the right hand side.

Under the top hinged cover:

• the relay serial number, and the relay’s current and voltage rating information*.

Page 42: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-4

MiCOM P741, P742, P743

GS

Under the bottom hinged cover:

• battery compartment to hold the 1/2 AA size battery which is used for memory back-up for the real time clock, event, fault and disturbance records.

• a 9-pin female D-type front port for communication with a PC locally to the relay (up to 15m distance) via an RS232 serial data connection.

• a 25-pin female D-type port providing internal signal monitoring and high speed local downloading of software and language text via a parallel data connection.

P0103ENe

FIGURE 2: RELAY FRONT VIEW (EXAMPLE FOR MiCOM P743 – 60 TE)

The front panel of the relay includes the following, as indicated in Figure 1:

− a 16-character by 3-line alphanumeric liquid crystal display (LCD)

− a 19-key keypad comprising 4 arrow keys ( , , and ), an enter key ( ), a clear key ( ), a read key ( ), 2 hot keys ( ) and 10 ( − ) programmable function keys

− Function key functionality:

− The relay front panel features control pushbutton switches with programmable LEDs that facilitate local control. Factory default settings associate specific relay functions with these 10 direct-action pushbuttons and LEDs e.g. reset indications. Using programmable scheme logic, the user can readily change the default direct-action pushbutton functions and LED indications to fit specific control and operational needs.

Hotkey functionality:When the functionality is disabled:

− SCROLL

Starts scrolling through the various default displays.

− STOP

Stops scrolling the default display.

When the functionality is disabled:

− For control of setting groups, control inputs and circuit breaker operation

− 22 LEDs; 4 fixed function LEDs, 8 tri-colour programmable function LEDs on the left hand side of the front panel and 10 tri-colour programmable function LEDs on the right hand side associated with the function keys

Page 43: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-5

GS

− Under the top hinged cover:

− The relay serial number, and the relay’s current and voltage rating information

− Under the bottom hinged cover:

− Battery compartment to hold the 1/2 AA size battery which is used for memory back-up for the real time clock, event, fault and disturbance records

− A 9-pin female D-type front port for communication with a PC locally to the relay (up to 15m distance) via an EIA(RS)232 serial data connection

− A 25-pin female D-type port providing internal signal monitoring and high speed local downloading of software and language text via a parallel data connection

1.2.1.1 LED indications

Fixed Function

The 4 fixed function LEDs on the left-hand side of the front panel are used to indicate the following conditions:

Trip (Red) indicates that the relay has issued a trip signal. It is reset when the associated fault record is cleared from the front display.

Alarm (Yellow) flashes to indicate that the relay has registered an alarm. This may be triggered by a fault, event or maintenance record. The LED will flash until the alarms have been accepted (read), after which the LED will change to constant illumination, and will extinguish, when the alarms have been cleared.

Out of service (Yellow) indicates that the relay’s protection is unavailable or a test mode is selected.

Healthy (Green) indicates that the relay is in correct working order, and should be on at all times. It will be extinguished if the relay’s self-test facilities indicate that there is an error with the relay’s hardware or software. The state of the healthy LED is reflected by the watchdog contact at the back of the relay.

To improve the visibility of the settings via the front panel, the LCD contrast can be adjusted using the “LCD Contrast” setting in the CONFIGURATION column. This should only be necessary in very hot or cold ambient temperatures.

Programmable LEDs

All the programmable LEDs are tri-colour and can be programmed to indicate RED, YELLOW or GREEN depending on the requirements. The 8 programmable LEDs on the left are suitable for programming alarm indications and the default indications and functions are indicated in the table below. The 10 programmable LEDs physically associated with the function keys, are used to indicate the status of the associated pushbutton’s function and the default indications are shown below:

Page 44: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-6

MiCOM P741, P742, P743

GS

The default mappings for each of the programmable LEDs are as shown in the following table:

Central Unit P741:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1

LED1 Red

LED1 Yellow

LED1 Green

Yes

87BB fault on phase A

Not used

Not used

2

LED2 Red

LED2 Yellow

LED2 Green

Yes

87BB fault on phase B

Not used

Not used

3

LED3 Red

LED3 Yellow

LED3 Green

Yes

87BB fault on phase C

Not used

Not used

4

LED4 Red

LED4 Yellow

LED4 Green

Yes

50BF Trip Zone 1

87BB & 50BF Trip Zone 1

87BB Trip Zone 1

5

LED5 Red

LED5 Yellow

LED5 Green

Yes

50BF Trip Zone 2

87BB & 50BF Trip Zone 2

87BB Trip Zone 2

6

LED6 Red

LED6 Yellow

LED6 Green

No

Zone 1 blocked by itself

Zone 1 blocked by Check Zone

Zone 1 protected

7

LED7 Red

LED7 Yellow

LED7 Green

No

Zone 2 blocked by itself

Zone 2 blocked by Check Zone

Zone 2 protected

8

LED8 Red

LED8 Yellow

LED8 Green

No

Fiber communication Error

Fiber communication to change

Fiber communication healthy

9

FnKey LED1 Red

FnKey LED1 Yellow

FnKey LED1 Green

No

Zone or CZ circuitry fault block.

Zone or CZ circuitry fault alarm

No Zone or CZ circuitry fault

10

FnKey LED2 Red

FnKey LED2 Yellow

FnKey LED2 Green

No

Zone or CZ PU error fault block.

Zone or CZ PU error fault alarm

No Zone or CZ PU error fault

11

FnKey LED3 Red

FnKey LED3 Yellow

FnKey LED3 Green

No

All protections Disabled

Not used

All protections Not Disabled

12

FnKey LED4 Red

FnKey LED4 Yellow

FnKey LED4 Green

No

Zone 1: 87BB & 50BF blocked

Zone 1: 50BF blocked

Zone 1: protected

Page 45: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-7

GS

LED Number LED Input Connection/Text Latched P74x LED Function Indication

13

FnKey LED5 Red

FnKey LED5 Yellow

FnKey LED5 Green

No

Zone 2: 87BB & 50BF blocked

Zone 2: 50BF blocked

Zone 2: protected

14

FnKey LED6 Red

FnKey LED6 Yellow

FnKey LED6 Green

No

Not used

Not used

Reset CU Indications

15

FnKey LED7 Red

FnKey LED7 Yellow

FnKey LED7 Green

No

Not used

Not used

Reset CU & PU Indications

16

FnKey LED8 Red

FnKey LED8 Yellow

FnKey LED8 Green

No

Not used

Not used

Reset PU Trip Latch

17

FnKey LED9 Red

FnKey LED9 Yellow

FnKey LED9 Green

No

Not used

Not used

Manual DR trigger

18

FnKey LED10 Red

FnKey LED10 Yellow

FnKey LED10 Green

No

Not used

Dead Zone fault

Not used

Peripheral Unit P742:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1 LED 1 Red No Isolator 1 Closed

2 LED 2 Red No Isolator 2 Closed

3 LED 3 Red No Isolator 3 Closed

4 LED 4 Red Yes Trip on CU 50BF backtrip order

5 LED 5 Red Yes Trip on CU 87BB trip order

6 LED 6 Red Yes Dead Zone fault

7 LED 7 Red No Circuit Breaker out of service

8 LED 8 Red No Fiber communication Error

Page 46: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-8

MiCOM P741, P742, P743

GS

Peripheral Unit P743:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1

LED1 Red

LED1 Yellow

LED1 Green

No

Isolator 1 Closed

Isolator 1 Status Alarm

Isolator 1 Open

2

LED2 Red

LED2 Yellow

LED2 Green

No

Isolator 2 Closed

Isolator 2 Status Alarm

Isolator 2 Open

3

LED3 Red

LED3 Yellow

LED3 Green

No

Isolator 3 Closed

Isolator 3 Status Alarm

Isolator 3 Open

4

LED4 Red

LED4 Yellow

LED4 Green

Yes

Trip on CU 50BF backtrip order

Not used

Not used

5

LED5 Red

LED5 Yellow

LED5 Green

Yes

Trip on CU 87BB trip order

Not used

Not used

6

LED6 Red

LED6 Yellow

LED6 Green

Yes

Dead Zone fault

Not used

Not used

7

LED7 Red

LED7 Yellow

LED7 Green

No

Circuit Breaker out of service

Not used

Circuit Breaker healthy

8

LED8 Red

LED8 Yellow

LED8 Green

No

Fiber communication Error

Fiber communication to change

Fiber communication healthy

9

FnKey LED1 Red

FnKey LED1 Yellow

FnKey LED1 Green

No

Not used

Not used

Reset PU Indications

10

FnKey LED2 Red

FnKey LED2 Yellow

FnKey LED2 Green

No

Not used

Not used

Reset PU Trip Latch

11

FnKey LED3 Red

FnKey LED3 Yellow

FnKey LED3 Green

No Not used

12

FnKey LED4 Red

FnKey LED4 Yellow

FnKey LED4 Green

No

Not used

Mode 50BF disabled

Mode normal

13

FnKey LED5 Red

FnKey LED5 Yellow

FnKey LED5 Green

No

Mode overhaul

Not used

Mode normal

Page 47: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-9

GS

LED Number LED Input Connection/Text Latched P74x LED Function Indication

14

FnKey LED6 Red

FnKey LED6 Yellow

FnKey LED6 Green

No Not used

15

FnKey LED7 Red

FnKey LED7 Yellow

FnKey LED7 Green

No Not used

16

FnKey LED8 Red

FnKey LED8 Yellow

FnKey LED8 Green

No Not used

17

FnKey LED9 Red

FnKey LED9 Yellow

FnKey LED9 Green

No Not used

18

FnKey LED10 Red

FnKey LED10 Yellow

FnKey LED10 Green

No Not used

1.2.2 Relay rear panel

The rear panel of the relay is shown in Figures 2/3/4. All current signals, digital logic input signals and output contacts are connected at the rear of the relay. Also connected at the rear is the twisted pair wiring for the rear RS485 communication port; the IRIG-B time synchronising input is optional in the P741.

COPROCESSOR BOARD(Connexion to CU via optical fibre)

COPROCESSOR BOARD(Connexion to CU via optical fibre)

POWER SUPPLYPOWER SUPPLY

ANALOG INPUT MODULEANALOG INPUT MODULE

16 LOGICAL INPUTS16 LOGICAL INPUTS

8 LOGICAL OUTPUTS8 LOGICAL OUTPUTS

16 17 2418

13 14

10 11

7 8

23

22

15

12

219

4 5

1 2

A

20

19

6

3

B C D

2

EF

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

P3710ENa

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

22 2

FIGURE 3: P742 RELAY REAR VIEW 40TE

Page 48: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-10

MiCOM P741, P742, P743

GS 16 17 18 24

13 14

10 11

7 8

15 23

12 22

9 21

A

4 5

1 2

6 20

3 19

B C D E F G

POWER SUPPLYANALOG INPUT

24 LOGICAL INPUTS 16 LOGICAL OUTPUTS

J

P3711ENb

COPROCESSOR BOARD(connexion to CU via optic fibre)

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

CH1

TX

RX

TX

CH2 RX

H

TX

ACTIVITY

LINK

RX

SK6

00.0

2.84

.9F.

FF.

9000

.02.

84.9

F.F

F.90

20

14

80

98

VxW

ork

sR

Win

dR

iver

R

OPTIONAL BOARD

FIGURE 4: P743 RELAY REAR VIEW 60TE

1 TO 7 COMMUNICATION BOARDS

OPTIONAL BOARD

CO-PROCESSOR BOARD

POWER SUPPLY MODULE

P3712ENc

LOGICAL OUTPUT CONTACT BOARD

LOGICAL INPUT CONTACT BOARD

A GB C D E F HJ K

TX

RX

SK6

LINK

ACTIVITY

00.0

2.84

.9F.

FF.

90

R

20148098

xWorks

IRIG-B12x

WindRiverRRXCH1

RXCH2

TX

L

TX

M N

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

FIGURE 5: P741 RELAY REAR VIEW 80TE

Refer to the wiring diagram in ‘Installation Chapter’ (P74x/EN IN) for complete connection details.

Page 49: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-11

GS

1.3 Relay connection and power-up

Before powering-up the relay, confirm that the relay power supply voltage and nominal ac signal magnitudes are appropriate for your application. The relay serial number, and the relay’s current and voltage rating, power rating information can be viewed under the top hinged cover. The relay is available in the following auxiliary voltage versions and these are specified in the table below:

Nominal Ranges Operative dc Range

Operative ac Range

24 - 48V dc 19 to 65V -

48 - 110V dc (30 - 100V ac rms) ** 37 to 150V 24 to 110V

110 - 250V dc (100 - 240V ac rms) ** 87 to 300V 80 to 265V

** rated for ac or dc operation

Please note that the label does not specify the logic input ratings. The P74x relays are fitted with universal opto isolated logic inputs that can be programmed for the nominal battery voltage of the circuit of which they are a part. See ‘Universal Opto input’ in the Firmware section for more information on logic input specifications. Please note that the opto inputs have a maximum input voltage rating of 300V dc at any setting.

Once the ratings have been verified for the application, connect external power capable of delivering the power requirements specified on the label to perform the relay familiarization procedures. Figure 2 and 3 indicates the location of the power supply terminals but please refer to the wiring diagrams in the Installation section for complete installation details ensuring that the correct polarities are observed in the case of dc supply.

Page 50: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-12

MiCOM P741, P742, P743

GS

1.4 Introduction to the user interfaces and settings options

The relay has three user interfaces:

− The front panel user interface via the LCD and keypad

− The front port which supports Courier communication

− The rear port which supports one protocol: Courier. (IEC 60870-5-103 is converted from Courier using a KITZ274).

The measurement information and relay settings that can be accessed from the three interfaces are summarized in Table 1.

Keypad/ LCD Courier IEC870-5-

103

Display & modification of all settings • •

Digital I/O signal status • • •

Display/extraction of measurements • • •

Display/extraction of fault records • •

Extraction of disturbance records • •

Programmable scheme logic settings •

Reset of fault & alarm records • • •

Clear event & fault records • •

Time synchronization • •

Control commands • • •

Table 1

Page 51: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-13

GS

1.5 Menu structure

The relay’s menu is arranged in a tabular structure. Each setting in the menu is referred to as a cell, and each cell in the menu may be accessed by reference to a row and column address. The settings are arranged so that each column contains related settings, for example all of the disturbance recorder settings are contained within the same column. As shown in Figure 4, the top row of each column contains the heading that describes the settings contained within that column. Movement between the columns of the menu can only be made at the column heading level. A complete list of all of the menu settings is given in the Menu Content Map at the end of this section.

Column

data

settings

Column header

Control & support Group 1 Group 4

Up to 4 protection setting groups

System data View recordsDIFF

BUSBAR PROT

BUSBAR

OPTION

P0106ENb

INPUTS

LABELS

OUTPUT

LABELS

DIFF

BUSBAR PROT

BUSBAR

OPTIONINPUTS

LABELS

OUTPUT

LABELS

FIGURE 6: MENU STRUCTURE

All of the settings in the menu fall into one of three categories; protection settings, disturbance recorder settings, or control and support (C&S) settings. One of two different methods is used to change a setting depending on which category the setting falls into. Control and support settings are stored and used by the relay immediately after they are entered. For either protection settings or disturbance recorder settings, the relay stores the new setting values in a temporary ‘scratchpad’. It activates all the new settings together, but only after it has been confirmed that the new settings are to be adopted. This technique is employed to provide extra security, and so that several setting changes that are made within a group of protection settings will all take effect at the same time.

1.5.1 Protection settings

The protection settings include the following items:

− Protection element settings

− Scheme logic settings

There are four groups of protection settings, with each group containing the same setting cells. One group of protection settings is selected as the active group, and is used by the protection elements.

1.5.2 Disturbance recorder settings

The disturbance recorder settings include the record duration and trigger position, selection of analogue and digital signals to record, and the signal sources that trigger the recording.

Page 52: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-14

MiCOM P741, P742, P743

GS

1.5.3 Control and support settings

The control and support settings include:

− Relay configuration settings

− Open/close circuit breaker

− CT & VT ratio settings

− Reset LEDs

− Active protection setting group

− Password & language settings

− Communications settings

− Measurement settings

− Event & fault record settings

− User interface settings

− Commissioning settings

1.6 Password protection

The menu structure contains three levels of access. The level of access that is enabled determines which of the relay’s settings can be changed and is controlled by entry of two different passwords. The levels of access are summarized in Table 2.

Access level Operations enabled

Level 0 No password required

Read access to all settings, alarms, event records and fault records

Level 1 Password 1 or 2 required

As level 0 plus: Control commands, e.g. Circuit breaker open/close (when available). Reset of fault and alarm conditions. Reset LEDs. Clearing of event and fault records.

Level 2 Password 2 required

As level 1 plus: All other settings

Table 2

Each of the two passwords is 4 characters of upper case text. The factory default for both passwords is AAAA. Each password is user-changeable once it has been correctly entered. Entry of the password is achieved either by a prompt when a setting change is attempted, or by moving to the ‘Password’ cell in the ‘System data’ column of the menu. The level of access is independently enabled for each interface, that is to say if level 2 access is enabled for the rear communication port, the front panel access will remain at level 0 unless the relevant password is entered at the front panel. The access level enabled by the password entry will time-out independently for each interface after a period of inactivity and revert to the default level. If the passwords are lost an emergency password can be supplied - contact Alstom Grid with the relay’s serial number. The current level of access enabled for an interface can be determined by examining the 'Access level' cell in the 'System data' column, the access level for the front panel User Interface (UI), can also be found as one of the default display options.

Page 53: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-15

GS

The relay is supplied with a default access level of 2, such that no password is required to change any of the relay settings. It is also possible to set the default menu access level to either level 0 or level 1, preventing write access to the relay settings without the correct password. The default menu access level is set in the ‘Password control’ cell which is found in the ‘System data’ column of the menu (note that this setting can only be changed when level 2 access is enabled).

1.7 Relay configuration

The relay is a multi-function device that supports numerous different protection, control and communication features. In order to simplify the setting of the relay, there is a configuration settings column which can be used to enable or disable many of the functions of the relay. The settings associated with any function that is disabled are made invisible, i.e. they are not shown in the menu. To disable a function change the relevant cell in the ‘Configuration’ column from ‘Enabled’ to ‘Disabled’.

The configuration column controls which of the four protection settings groups is selected as active through the ‘Active settings’ cell. A protection setting group can also be disabled in the configuration column, provided it is not the present active group. Similarly, a disabled setting group cannot be set as the active group.

1.8 Front panel user interface (keypad and LCD)

When the keypad is exposed it provides full access to the menu options of the relay, with the information displayed on the LCD.

The , , and keys which are used for menu navigation and setting value changes include an auto-repeat function that comes into operation if any of these keys are held continually pressed. This can be used to speed up both setting value changes and menu navigation; the longer the key is held depressed, the faster the rate of change or movement becomes.

!"

#$

%

!"

#$

&'

!"

()%&*$

#++,-(

FIGURE 7: FRONT PANEL USER INTERFACE

Page 54: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-16

MiCOM P741, P742, P743

GS

1.8.1 Default display and menu time-out

The front panel menu has a default display, the contents of which can be selected from the following options in the ‘default display’ cell of the ‘Measure’t. setup’ column:

− Date and time

− Relay description (user defined)

− Plant reference (user defined)

− Check zone bias currents (A, B, C)

− Check zone differential currents (A, B, C)

From the default display it is also possible to view the other default display options using the and keys. However, if there is no keypad activity for the 15 minute timeout period,

the default display will revert to that selected by the setting and the LCD backlight will turn off. If this happens any setting changes that have not been confirmed will be lost and the original setting values maintained.

Whenever there is an uncleared alarm present in the relay (e.g. fault record, protection alarm, control alarm etc.) the default display will be replaced by:

Alarms/Faults Present

Entry to the menu structure of the relay is made from the default display and is not affected if the display is showing the ‘Alarms/Faults present’ message.

1.8.2 Menu navigation and setting browsing

The menu can be browsed using the four arrow keys, following the structure shown in Figure 5. Thus, starting at the default display the key will display the first column heading. To select the required column heading use the and keys. The setting data contained in the column can then be viewed by using the and keys. It is possible to return to the column header either by holding the [up arrow symbol] key down or by a single press of the clear key . It is only possible to move across columns at the column heading level. To return to the default display, press the key or the clear key from any of the column headings. It is not possible to go straight to the default display from within one of the column cells using the auto-repeat facility of the key, as the auto-repeat will stop at the column heading. To move to the default display, the key must be released and pressed again.

1.8.3 Hotkey menu navigation

The hotkey menu can be browsed using the two keys directly below the LCD. These are known as direct access keys. The direct access keys perform the function that is displayed directly above them on the LCD. Thus, to access the hotkey menu from the default display the direct access key below the “HOTKEY” text must be pressed. Once in the hotkey menu the ⇐ and ⇒ keys can be used to scroll between the available options and the direct access keys can be used to control the function currently displayed. If neither the ⇐ or ⇒ keys are pressed with 20 seconds of entering a hotkey sub menu, the relay will revert to the default display. The clear key will also act to return to the default menu from any page of the hotkey menu. The layout of a typical page of the hotkey menu is described below:

• The top line shows the contents of the previous and next cells for easy menu navigation

• The centre line shows the function

• The bottom line shows the options assigned to the direct access keys

The functions available in the hotkey menu are listed below:

Page 55: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-17

GS

1.8.3.1 Setting group selection

The user can either scroll using <<NXT GRP>> through the available setting groups or <<SELECT>> the setting group that is currently displayed.

When the SELECT button is pressed a screen confirming the current setting group is displayed for 2 seconds before the user is prompted with the <<NXT GRP>> or <<SELECT>> options again. The user can exit the sub menu by using the left and right arrow keys.

For more information on setting group selection refer to “Changing setting group” section in the Operation section (P74x/EN OP).

1.8.3.2 Control inputs – user assignable functions

The number of control inputs (user assignable functions – USR ASS) represented in the hotkey menu is user configurable in the “CTRL I/P CONFIG” column. The chosen inputs can be SET/RESET using the hotkey menu.

For more information refer to the “Control Inputs” section in the Operation section (P74x/EN OP).

1.8.3.3 Hotkey menu navigation

HO T KEY MENU

EXIT

Description

MiCOM P741

HO TKEY

<USER 32 STG GP>

SETTING GROUP 1

SELECT

<MENU USER 01>

NXT GRP

CONTROL INPUT 1

ON

<STG GP USER 02>

EXIT

CONTROL INPUT 32

ON

<USER 31 MENU>

EXIT

SETTING GROUP 2

SELECT

<MENU USER 01>

NXT GRP

SETTING GROUP 2

SELECTED

<MENU USER 01>

CONTROL INPUT 1

ON

<MENU USER 02>

CONTROL INPUT 1

EXIT

<MENU USER 02>

OFF

Confirmationscreen

displayed for2 seconds

Confirmationscreendisplayed for2 seconds

Default Display

NOTE : <<EXIT>> K ey returnsthe user to the HotkeyMenu Screen

P3915ENa

FIGURE 8: HOTKEY MENU NAVIGATION

Page 56: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-18

MiCOM P741, P742, P743

GS

1.8.4 Password entry

When entry of a password is required the following prompt will appear:

Enter password **** Level 1

Note: The password required to edit the setting is the prompt as shown above.

A flashing cursor will indicate which character field of the password may be changed. Press the and keys to vary each character between A and Z. To move between the character fields of the password, use the and keys. The password is confirmed by pressing the enter key . The display will revert to ‘Enter Password’ if an incorrect password is entered. At this point a message will be displayed indicating whether a correct password has been entered and if so what level of access has been unlocked. If this level is sufficient to edit the selected setting then the display will return to the setting page to allow the edit to continue. If the correct level of password has not been entered then the password prompt page will be returned to. To escape from this prompt press the clear key . Alternatively, the password can be entered using the ‘Password’ cell of the ‘System data’ column.

For the front panel user interface the password protected access will revert to the default access level after a keypad inactivity time-out of 15 minutes. It is possible to manually reset the password protection to the default level by moving to the ‘Password’ menu cell in the ‘System data’ column and pressing the clear key instead of entering a password.

1.8.5 Reading and clearing of alarm messages and fault records

The presence of one or more alarm messages will be indicated by the default display and by the yellow alarm LED flashing. The alarm messages can either be self-resetting or latched, in which case they must be cleared manually. To view the alarm messages press the read key . When all alarms have been viewed, but not cleared, the alarm LED will change from flashing to constant illumination and the latest fault record will be displayed (if there is one). To scroll through the pages of this use the key. When all pages of the fault record have been viewed, the following prompt will appear:

Press clear to reset alarms

To clear all alarm messages press ; to return to the alarms/faults present display and leave the alarms uncleared, press . Depending on the password configuration settings, it may be necessary to enter a password before the alarm messages can be cleared (see section on password entry). When the alarms have been cleared the yellow alarm LED will extinguish, as will the red trip LED if it was illuminated following a trip.

Alternatively it is possible to accelerate the procedure, once the alarm viewer has been entered using the key, the key can be pressed, and this will move the display straight to the fault record. Pressing again will move straight to the alarm reset prompt where pressing once more will clear all alarms.

Page 57: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-19

GS

1.8.6 Setting changes

To change the value of a setting, first navigate the menu to display the relevant cell. To change the cell value press the enter key , which will bring up a flashing cursor on the LCD to indicate that the value can be changed. This will only happen if the appropriate password has been entered, otherwise the prompt to enter a password will appear. The setting value can then be changed by pressing the or keys. If the setting to be changed is a binary value or a text string, the required bit or character to be changed must first be selected using the and keys. When the desired new value has been reached it is confirmed as the new setting value by pressing . Alternatively, the new value will be discarded either if the clear button is pressed or if the menu time-out occurs.

For protection group settings and disturbance recorder settings, the changes must be confirmed before they are used by the relay. To do this, when all required changes have been entered, return to the column heading level and press the key. Prior to returning to the default display the following prompt will be given:

Update settings? Enter or clear

Pressing will result in the new settings being adopted, pressing will cause the relay to discard the newly entered values. It should be noted that, the setting values will also be discarded if the menu time out occurs before the setting changes have been confirmed. Control and support settings will be updated immediately after they are entered, without the ‘Update settings?’ prompt.

1.9 Front communication port user interface

The front communication port is provided by a 9-pin female D-type connector located under the bottom hinged cover. It provides EIA(RS)232 serial data communication and is intended for use with a PC locally to the relay (up to 15m distance) as shown in Figure 7. This port supports the Courier communication protocol only. Courier is the communication language developed by Alstom Grid to allow communication with its range of protection relays. The front port is particularly designed for use with the relay settings program MiCOM S1 that is a Windows 98, Windows NT4.0, Windows 2000 or Windows XP based software package.

!

#++.-(/

FIGURE 9: FRONT PORT CONNECTION

Page 58: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-20

MiCOM P741, P742, P743

GS

The relay is a Data Communication Equipment (DCE) device. Thus the pin connections of the relay’s 9-pin front port are as follows:

Pin no. 2 Tx Transmit data

Pin no. 3 Rx Receive data

Pin no. 5 0V Zero volts common

None of the other pins are connected in the relay. The relay should be connected to the serial port of a PC, usually called COM1 or COM2. PCs are normally Data Terminal Equipment (DTE) devices which have a serial port pin connection as below (if in doubt check your PC manual):

25 Way 9 Way

Pin no. 2 3 2 Rx Receive data

Pin no. 3 2 3 Tx Transmit data

Pin no. 5 7 5 0V Zero volts common

For successful data communication, the Tx pin on the relay must be connected to the Rx pin on the PC, and the Rx pin on the relay must be connected to the Tx pin on the PC, as shown in Figure 7. Therefore, providing that the PC is a DTE with pin connections as given above, a ‘straight through’ serial connector is required, i.e. one that connects pin 2 to pin 2, pin 3 to pin 3, and pin 5 to pin 5. Note that a common cause of difficulty with serial data communication is connecting Tx to Tx and Rx to Rx. This could happen if a ‘cross-over’ serial connector is used, i.e. one that connects pin 2 to pin 3, and pin 3 to pin 2, or if the PC has the same pin configuration as the relay.

FIGURE 10: PC – RELAY SIGNAL CONNECTION

Having made the physical connection from the relay to the PC, the PC’s communication settings must be configured to match those of the relay. The relay’s communication settings for the front port are fixed as shown in the table below:

Protocol Courier

Baud rate 19,200 bits/s

Courier address 1

Message format 11 bit - 1 start bit, 8 data bits, 1 parity bit (even parity), 1 stop bit

The inactivity timer for the front port is set at 15 minutes. This controls how long the relay will maintain its level of password access on the front port. If no messages are received on the front port for 15 minutes then any password access level that has been enabled will be revoked.

Page 59: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-21

GS

1.9.1 Front courier port

The front EIA(RS)2321 9 pin port supports the Courier protocol for one to one communication. It is designed for use during installation and commissioning/maintenance and is not suitable for permanent connection. Since this interface will not be used to link the relay to a substation communication system, some of the features of Courier are not implemented. These are as follows:

Automatic Extraction of Event Records:

− Courier Status byte does not support the Event flag

− Send Event/Accept Event commands are not implemented

Automatic Extraction of Disturbance Records:

− Courier Status byte does not support the Disturbance flag

Busy Response Layer:

− Courier Status byte does not support the Busy flag, the only response to a request will be the final data

Fixed Address:

− The address of the front courier port is always 1, the Change Device address command is not supported.

Fixed Baud Rate:

− 19200 bps

It should be noted that although automatic extraction of event and disturbance records is not supported it is possible to manually access this data via the front port.

1.10 MiCOM S1 relay communications basics

The front port is particularly designed for use with the relay settings program MiCOM S1 that is a Windows 98, Windows NT4.0, Windows 2000 or Windows XP based software package. MiCOM S1 is the universal MiCOM IED Support Software and provides users a direct and convenient access to all stored data in any MiCOM IED using the EIA(RS)232 front communication port.

MiCOM S1 provides full access to:

• MiCOM Px20, Px30, Px40 relays

• MiCOM Mx20 measurements units

1.10.1 PC requirements

The following minimum requirements must be met for the MiCOM S1 software to properly work on a PC.

• IBM computer or 100% compatible,

• WindowsTM 98 or NT 4.0 (Not WindowsTM 95)

• Pentium II 300 Mhz minimum,

• Screen VGA 256 colours minimum,

• Resolution 640 x 400 minimum (1024 x 768 recommended),

• 48Mb RAM minimum,

• 500Mb free on computer hard-disk.

1 This port is actually compliant to EIA(RS)574; the 9-pin version of EIA(RS)232, see www.tiaonline.org.

Page 60: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-22

MiCOM P741, P742, P743

GS

1.10.2 Connecting to the P74x relay using MiCOM S1

Before starting, verify that the EIA(RS)232 serial cable is properly connected to the EIA(RS)232 port on the front panel of the relay. Please follow the instructions in section 1.9 to ensure a proper connection is made between the PC and the relay before attempting to communicate with the relay.

This section is intended as a quick start guide to using MiCOM S1 and assumes you have a copy of MiCOM S1 installed on your PC. Please refer to the MiCOM S1 User Manual for more detailed information.

To start MiCOM S1, click on the icon:

In the "Programs" menu, select "MiCOM S1" then "MiCOM S1 Start-up".

WARNING: CLICKING ON "UNINSTALL MiCOM S1", WILL UNINSTALL MiCOM S1, AND ALL DATA AND RECORDS USED IN MiCOM S1.

You access the MiCOM S1 launcher screen.

The MiCOM S1 launcher is the software that gives access to the different application programs:

• MiCOM S1 for MiCOM M/Px20 IEDs

• MiCOM S1 for MiCOM Px30 IEDs

• MiCOM S1 for MiCOM Px40 IEDs

• MiCOM S1 disturbance application

To access these different programs, use the blue arrows,

Page 61: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-23

GS

Click on the desired type of access

and click on the required MiCOM Px40 series

1.10.3 Open communication link with relay

To open the communications link from S1 to the P74x relay the following procedure must be followed:

First the communication setup must be adjusted if necessary. In the "Device" menu, select "Communications Setup…"

Page 62: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-24

MiCOM P741, P742, P743

GS

This brings up the following screen:

FIGURE 11: COMMUNICATION SET-UP SCREEN

When the communications setup is correct the link with the relay can be initialized. In the "Device" menu, select "Open Connection…"

This brings up a prompt for the address of the relay to be interrogated (for front port access, the relay address is:

“6” for P741

“7” for the first Peripheral Unit (P742 or P743), “8” for the next one and so on.

When this has been entered a prompt for the password appears.

Page 63: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-25

GS

When these have been entered satisfactorily the relay is then able to communicate with MiCOM S1. When a communication link has been established between the PC and a MiCOM IED, both are said to be online. Data and information can be directly transferred from and to the IED using the menu available under the “DEVICE” menu.

For further instruction on how to extract, download and modify settings files, please refer to the MiCOM S1 User Manual.

1.10.4 Off-line use of MiCOM S1

As well as being used for the on-line editing of settings, MiCOM S1 can also be used as an off-line tool to prepare settings without access to the relay. In order to open a default setting file for modification, in the “File” menu, select “New” and then “Settings File…”

This brings up a prompt for the relay model type where you can select the correct relay for your application:

Page 64: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-26

MiCOM P741, P742, P743

GS

Clicking on OK will open the default file and you can start to edit settings. For further instruction on how to extract, download and modify settings files, please refer to the MiCOM S1 User Manual.

Page 65: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-27

GS

Appendix – P741 Relay Menu Map (Default)

Note: This menu map is annotated with the factory default settings.

SYSTEM DATA

Language Select Event* IA Diff CZ Z01 : IA diff Current Node 1 Current Node 1

English [0…511] 0 0 A 0 A 00000000 0000000000000000

Password Select Fault* IB Diff CZ Z01 : IB diff *: If existing *: If existing

**** [0…4] 0 0 A 0 A

Description Select Maint* IC Diff CZ Z01 : IC diff Current Node 2 * Current Node 2 *

MiCOM P741 [0…4] 0 0 A 0 A 00000000 0000000000000000

Plant Reference Reset Indication IN Diff CZ Z01 : IN diff Current Node 3 * Current Node 3 *

MiCOM No 0 A 0 A 00000000 0000000000000000

Model Number *: If existing IA Bias CZ Z01 : IA bias Current Node 4 * Current Node 4 *

0 A 0 A 00000000 0000000000000000

Serial Number IB Bias CZ Z01 : IB bias Current Node 5 * Current Node 5 *

0 A 0 A 00000000 0000000000000000

Frequency IC Bias CZ Z01 : IC bias Current Node 6 * Current Node 6 *

50 0 A 0 A 00000000 0000000000000000

Comms Level IN Bias CZ Z01 : IN bias Current Node 7 * Current Node 7 *

2 0 A 0 A 00000000 0000000000000000

Relay Address Current Node 8 * Current Node 8 *

6 00000000 0000000000000000

Plant Status

0000000000000000 *: If existing

Control Status Z02 : IA diff *

0000000000000000 0 A

Active Group Z02 : IB diff *

1 0 A

Software Ref. 1 Z02 : IC diff *

Ref. Number 0 A

Opto I/P Status Z02 : IN diff *

00000000 0 A

Relay O/P Status Z02 : IA bias *

00000000 0 A

Alarm Status 1 Z02 : IB bias *

0000000000000000 0 A

Alarm Status 1 Z02 : IC bias *

0000000000000000 0 A

Alarm Status 2 Z02 : IN bias *

0000000000000000 0 A

Alarm Status 3 Etc…

0000000000000000

Z08 : IA diff *

Access Level 0 A

2

Z08 : IB diff *

Password Control 0 A

2

Z08 : IC diff *

Password Level 1 0 A

****

Z08 : IN diff *

Password Level 2 0 A

****

Z08 : IA bias *

0 A

Z08 : IB bias *

0 A

TOPOLOGY 2VIEW RECORDS MEASUREMENTS 1 MEASUREMENTS 2 TOPOLOGY 1

Z08 : IC bias *

0 A

Z08 : IN bias *

0 A

Page 66: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-28

MiCOM P741, P742, P743

GS

CONFIGURATION

PU in service Date Restore Defaults Clear Events

05 Jan 2006 No Operation No

PU connected Time Setting Group Clear Faults

0000000000000000 12:00:00 Select via Menu No

PU topo valid IRIG-B Sync Active Settings Clear Maint

0000000000000000 Disabled Group 1 No

Reset Circt Flt Battery Status Save Changes Alarm Event

No Healthy No Operation Enabled

Reset PU Error Battery Alarm Copy From Relay O/P Event

No Enabled Group 1 Enabled

Circuitry Fault* Copy To Opto Input Event

00000000 No Operation Enabled

Circ Fault Phase* Setting Group 1 General Event

Enabled Enabled

PU Error Locked* Setting Group 2 Fault Rec Event

00000000 Disabled Enabled

87BB Monitoring* Setting Group 3 Maint Rec Event

00000000 Disabled Enabled

87BB&50BF Disabl* Setting Group 4 Protection Event

00000000 Disabled Enabled

*: If existing Busbar option DDB 31 - 0 DDB 607 - 576

Invisible

Diff Busbar Prot DDB 63 - 32 DDB 639 - 608

Enabled

Input Labels DDB 95 - 64 DDB 671 - 640

Visible

Output Labels DDB 127 - 96 DDB 607 - 576

Visible

Record Control DDB 159 - 128 DDB 639 - 608

Visible

Disturb Recorder DDB 191 - 160 DDB 671 - 640

Visible

Measure't Setup DDB 223 - 192 DDB 703 - 672

Visible

Comms Settings DDB 255 - 224 DDB 735 - 704

Invisible

Commission Tests DDB 287 - 256 DDB 767 - 736

Visible

Setting Values DDB 319 - 288 DDB 799 - 768

Primary

Control Inputs DDB 351 - 320 DDB 831 - 800

Visible

Control I/P Config DDB 383 - 352 DDB 863 - 832

Visible

Control I/P Labels DDB 415 - 384 DDB 895 - 864

Visible

Direct Access DDB 447 - 416 DDB 927 - 896

Enabled

Function key DDB 479 - 448 DDB 959 - 928

Visible

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

PU CONF & STATUS DATE AND TIME

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

0000000000000000

RECORD CONTROL

(When Visible)

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

LCD Contrast DDB 511 - 480 DDB 991 - 960

11

DDB 543 - 512 DDB 1022 - 992

DDB 575 - 544 Clear Dist Recs

No

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

Page 67: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-29

GS

Duration Default Display RP1 Protocol Opto I/P Status Global Nominal V

1,200 s Idiff CZ Courier 00000000 48/54V

Trigger Position Local Values RP1 Address Relay O/P Status If Custom selected:

33,34 % Primary 00000000

Trigger Mode Remote Values RP1 InactivTimer Test Port Status Opto Input 1

Single Primary 15 mins 00000000 48/54V

Analog Channel 1 RP1 Card Status Monitor Bit 1 Opto Input 2

IA diff K Bus OK Relay Label 01 48/54V

Analog Channel 2 RP1 Port Config Monitor Bit 2 Opto Input 3

IB diff K Bus Relay Label 02 48/54V

Analog Channel 3 If RS485: Monitor Bit 3 Opto Input 4

IC diff Relay Label 03 48/54V

Analog Channel 4 RP1 Comms Mode Monitor Bit 4

IN diff Relay Label 04

Analog Channel 5 RP1 Baud Rate Monitor Bit 5

IA bias 19200 Relay Label 05

Analog Channel 6 Monitor Bit 6 Opto Input 8

IB bias Relay Label 06 48/54V

Analog Channel 7 Monitor Bit 7

IC bias Relay Label 07

Analog Channel 8 Monitor Bit 8

IN bias Relay Label 08

Digital Input 1 Digital Input 18 Test Mode

Circt Flt Lck z1 Trip 87BB zone 2 Disabled

Digital Input 2 Digital Input 19 Test LEDs

Circt Flt Lck z2 PU Error Lck z1 No Operation

Digital Input 3 Digital Input 20 Red LED Status

87BB Blocked PU Error Lck z2 0000000000000000

Digital Input 4 Digital Input 21 Green LED Status

Ext Start DR Unused 0000000000000000

Digital Input 5 Digital Input 22 If Test Mode in:

Earth Fault Unused Out Of Service

Digital Input 6 Digital Input 23 Test Pattern

Fault Check zone Unused 00000000

Digital Input 7 Digital Input 24 Contact Test

Fault phase A Unused No operation

Digital Input 8 Digital Input 25 87BB Monitoring

Fault phase B Unused 00000000

Digital Input 9 Digital Input 26 87BB & 50BF Disabl

Fault phase C Unused 00000000

Digital Input 10 Digital Input 27 87BB Trip Pattern

Flt 87BB zone 1 Unused 00000000

Digital Input 11 Digital Input 28 87BB Trip Order

Flt 87BB zone 2 Unused No operation

Digital Input 12 Digital Input 29

Manual Start DR Unused

Digital Input 13 Digital Input 30

Topo/Set Changed Unused

Digital Input 14 Digital Input 31

Trip Manual zone Unused

IEC60870 FT1.2

6

OPTO CONFIGDISTURB RECORDER

(When Visible)

MEASURE'T SETUP

(When Visible)

COMMUNICATIONS

(If set visible)

COMMISSION TESTS

(When Visible)

Repeat as above for

Opto Input

5 - 8

Digital Input 15 Digital Input 32

Trip 50BF zone 1 Unused

Digital Input 16 Manual Trigger

Trip 50BF zone 2 No

Digital Input 17 Zone To Record

Trip 87BB zone 1 10000000

Page 68: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-30

MiCOM P741, P742, P743

GS

CONTROL INPUTS

(When Visible)

CTRL I/P CONFIG

(When Visible)

FUNCTION KEYS

(When Visible)CTRL I/P LABELS

Ctrl I/P Status Hotkey Enabled Fn Key Status Control Input 1

0000000000000000 1111111111111111 0000000000 Control Input 1

Control Input 1 Control Input 1 Control Input 15 Fn Key 1 Control Input 2

No Operation Latched Latched Unlocked Control Input 2

Control Input 2 Ctrl Command 1 Ctrl Command 15 Fn Key 1 Mode Control Input 3

No Operation Set/Reset Set/Reset Normal Control Input 3

Control Input 3 Control Input 2 Control Input 16 Fn Key 1 Label Control Input 4

No Operation Latched Latched Function Key 1 Control Input 4

Control Input 4 Ctrl Command 2 Ctrl Command 16 Fn Key 2 Control Input 5

No Operation Set/Reset Set/Reset Unlocked Control Input 5

Repeat as above Control Input 3 Control Input 17 Fn Key 2 Mode Control Input 6

Latched Latched Normal Control Input 6

Ctrl Command 3 Ctrl Command 17 Fn Key 2 Label Control Input 7

Set/Reset Set/Reset Function Key 2 Control Input 7

Control Input 32 Control Input 4 Control Input 18 Fn Key 3 Control Input 8

No Operation Latched Latched Unlocked Control Input 8

Ctrl Command 4 Ctrl Command 18 Fn Key 3 Mode Control Input 9

Set/Reset Set/Reset Normal Control Input 9

Control Input 5 Control Input 19 Fn Key 3 Label Control Input 10

Latched Latched Function Key 3 Control Input 10

Ctrl Command 5 Ctrl Command 19 Fn Key 4 Control Input 11

Set/Reset Set/Reset Unlocked Control Input 11

Control Input 6 Control Input 20 Fn Key 4 Mode Control Input 12

Latched Latched Normal Control Input 12

Ctrl Command 6 Ctrl Command 20 Fn Key 4 Label * Continue as

Set/Reset Set/Reset Function Key 4

Control Input 7 Control Input 21 Fn Key 5

Latched Latched Unlocked

Ctrl Command 7 Ctrl Command 21 Fn Key 5 Mode Control Input 32

Set/Reset Set/Reset Normal Control Input 32

Control Input 8 Control Input 22 Fn Key 5 Label

Latched Latched Function Key 5

Ctrl Command 8 Ctrl Command 22 Fn Key 6

Set/Reset Set/Reset Unlocked

Control Input 9 Control Input 23 Fn Key 6 Mode

Latched Latched Normal

Ctrl Command 9 Ctrl Command 23 Fn Key 6 Label

Set/Reset Set/Reset Function Key 6

Control Input 10 Control Input 24 Fn Key 7

Latched Latched Unlocked

Ctrl Command 10 Ctrl Command 24 Fn Key 7 Mode

Set/Reset Set/Reset Normal

Control Input 11 Control Input 25 Fn Key 7 Label

Latched Latched Function Key 7

Ctrl Command 11 Ctrl Command 25 Fn Key 8

Set/Reset Set/Reset Unlocked

Control Input 12 Control Input 26 Fn Key 8 Mode

Latched Latched Normal

Ctrl Command 12 Ctrl Command 26 Fn Key 8 Label

Set/Reset Set/Reset Function Key 8

Control Input 13 Fn Key 9 Fn Key 10

Latched Unlocked Unlocked

Ctrl Command 13 Control Input 32 Fn Key 9 Mode Fn Key 10 Mode

Set/Reset Latched Normal Normal

Control Input 14 Ctrl Command 32 Fn Key 9 Label Fn Key 10 Label

Latched Set/Reset Function Key 9 Function Key 10

Ctrl Command 14

Set/Reset

Page 69: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-31

GS

Idem Group 2,3 & 4

if setPSL DATA

Diff Phase Fault CZ Circ Flt Mode Opto Input 1 Relay 1 Grp 1 PSL Ref

Group 1 Alarm & No Block Opto Label 01 Relay Label 01 Reference

CZ Parameters Zx Circ Flt Mode Opto Input 2 Relay 2 JJ Month AAAA

Group 1 Blocking Latched Opto Label 01 Relay Label 02 HH:MM:SS:mmm

2

Phase Slope kCZ Circ. Blok Mode Opto Input 3 Relay 3 Grp 1 PSL ID

30.00 % 3phase Blocking Opto Label 03 Relay Label 03 1061683974

IDCZ>2 Current CZ PU ERR.Mode Opto Input 4 Relay 4 Grp 2 PSL Ref

1.200 kA Alarm & No Block Opto Label 04 Relay Label 04 Reference

Zone Parameters Zx PU ERR.Mode Opto Input 5 Relay 5 same for

Group 1 Blocking Latched Opto Label 05 Relay Label 05 Groupe 3 & 4

Phase Slope k2 PU Error Timer Opto Input 6 Relay 6

60.00 % 5.000 s Opto Label 06 Relay Label 06

ID>2 Current If Self Reset selected: Opto Input 7 Relay 7

1.000 kA Opto Label 07 Relay Label 07

Common Cicuitry tReset Opto Input 8 Relay 8

Group 1 5.000 s Opto Label 08 Relay Label 08

ID>1 Current PU Error tReset

100 A 5.000 s

Phase Slope k1

10.00 %

ID>1 Alarm Timer

5.000 s

Diff Phase Fault

Disabled

If Enabled:

Diff Phase Fault

Enabled

IBiasPh> Cur.

2.000 kA

CZ Parameters

Group 1

Earth Slope kCZ

10.00 %

IDNCZ>2 Current

1.200 kA

Zone Parameters

Group 1

Earth Slope kN2

10.00 %

IDN>2 Current

1000 A

Common

Group 1

IDN>1 Current

100 A

Earth Slope kN1

5.000 %

IDN>1 Alarm Timer

5.000 s

OUTPUT LABELS

GROUP 1 (Visible)

DIFF BUSBAR PROT

GROUP 1

BUSBAR OPTION

GROUP 1

INPUT LABELS

GROUP 1 (Visible)

Page 70: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-32

MiCOM P741, P742, P743

GS

Appendix – P742 Relay Menu Map (Default)

Note: This menu map is annotated with the factory default settings.

SYSTEM DATA

Language Select Event* IA Magnitude Link CT / zone Min Trip Pulse Date

English [0…511] 0 0.000 A 00000000 200.0 ms 05 Jan 2006

Password Select Fault* IA Phase Angle Zx: IA Diff Trip Latched Time

**** [0…4] 0 0.000 ° 0 A Disabled 12:00:00

Description Select Maint* IB Magnitude Zx: IB Diff CB Control by Battery Status

MiCOM P742 [0…4] 0 0.000 A 0 A Healthy

Plant Reference Reset Indication IB Phase Angle Zx: IC Diff If not: Battery Alarm

MiCOM No 0.000 ° 0 A Enabled

Model Number *: If existing IC Magnitude Zx: IN Diff Man Close Pulse

0.000 A 0 A 500.0 ms

Serial Number IC Phase Angle Zx: IA Bias Man Trip Pulse

0.000 ° 0 A 500.0 ms

Frequency IN Magnitude Zx: IB Bias Man Close Delay

50 0.000 A 0 A 10.00 s

Comms Level IN Phase Angle Zx: IC Bias Reset Trip Latch

2 0.000 ° 0 A No

Relay Address IN Derived Magn Zx: IN Bias

255 0.000 A 0 A

Plant Status IN Derived Angle x = 1 to 8 if existing

0000000000000000 0.000 °

Control Status I1 Magnitude

0000000000000000 0.000 A

Active Group I2 Magnitude

1 0.000 A

Software Ref. 1 I0 Magnitude

Ref. Number 0.000 A

Opto I/P Status Frequency

0000000000000000 50 Hz

Relay O/P Status

00000000

Alarm Status 1

0000000000000000

Alarm Status 1

0000000000000000

Alarm Status 2

0000000000000000

Alarm Status 3

0000000000000000

Access Level

2

Password Control

2

Password Level 1

****

Password Level 2

****

Disabled

DATE AND TIMEVIEW RECORDS MEASUREMENTS 1 TOPOLOGY 1 CB CONTROL

Page 71: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-33

GS

CONFIGURATION

Restore Defaults Phase CT Primary Clear Events Duration

No Operation 1.000 kA No 1,200 s

Setting Group Phase CT Sec'y Clear Faults Trigger Position Digital Input 6

Select via Menu 1.000 A No 33,34 % CBF Int Backtrip

Active Settings RBPh / RBN Clear Maint DDB 415 - 384 Trigger Mode Input 6 Trigger

Group 1 1.000 No Extended Trigger L/H

Save Changes Power Parameters Alarm Event DDB 447 - 416 Analog Channel 1 Digital Input 7

No Operation Enabled IA CBF Ext Backtrip

Copy From Standard Input Relay O/P Event DDB 479 - 448 Analog Channel 2 Input 7 Trigger

Group 1 British Standard Enabled IB Trigger L/H

Copy To Knee Voltage Vk Opto Input Event DDB 511 - 480 Analog Channel 3 Digital Input 8

No Operation 500.0 V Enabled IC Dead Zone Fault

Setting Group 1 RCT Sec'y General Event DDB 543 - 512 Analog Channel 4 Input 8 Trigger

Enabled 500,0 m_ Enabled IN Trigger L/H

Setting Group 2 Eff. Burden Ohm Fault Rec Event DDB 575 - 544 Analog Channel 5 Digital Input 9

Disabled 500,0 m_ Enabled Unassigned Ext. CB Fail

Setting Group 3 If IEC: Maint Rec Event DDB 607 - 576 Analog Channel 6 Input 9 Trigger

Disabled Enabled Unassigned Trigger L/H

Setting Group 4 Rated Burden VA Protection Event DDB 639 - 608 Analog Channel 7 Digital Input 10

Disabled 25.00 VA Enabled Unassigned Ext. 3 ph Trip

Dead Zone Prot Rated Burden Ohm DDB 31 - 0 DDB 671 - 640 Analog Channel 8 Input 10 Trigger

Disabled 25.00 _ Unassigned Trigger L/H

BB Trip Confirm KSCC DDB 63 - 32 DDB 703 - 672 Digital Input 1 Digital Input 11

Disabled 10 Field Volt Fail Internal Trip

Overcurrent Prot RCT Sec'y DDB 95 - 64 DDB 735 - 704 Input 1 Trigger Input 11 Trigger

Disabled 500,0 m_ No Trigger Trigger L/H

Earth Fault Prot Eff. Burden Ohm DDB 127 - 96 DDB 767 - 736 Digital Input 2 Digital Input 12

Disabled 500,0 m_ Any Trip Q1 Closed

CB Fail & I< Eff. Burden VA DDB 159 - 128 DDB 799 - 768 Input 2 Trigger Input 12 Trigger

Enabled 500,0 mVA Trigger L/H No Trigger

Input Labels DDB 191 - 160 DDB 831 - 800 Digital Input 3 Digital Input 13

Visible CB Closed Q2 Closed

Output Labels DDB 223 - 192 DDB 863 - 832 Input 3 Trigger Input 13 Trigger

Visible No Trigger No Trigger

CT & VT Ratios DDB 255 - 224 DDB 895 - 864 Digital Input 4 Digital Input 14

Visible CB Fail Alarm Q3 Closed

Record Control DDB 287 - 256 DDB 927 - 896 Input 4 Trigger Input 14 Trigger

Visible No Trigger No Trigger

Disturb Recorder DDB 319 - 288 DDB 959 - 928 Digital Input 5 Digital Input 15

Visible CB not available Man. Trip zone

Measure't Setup DDB 351 - 320 DDB 991 - 960 Input 5 Trigger Input 15 Trigger

Visible No Trigger Trigger L/H

Comms Settings DDB 383 - 352 DDB 1022 - 992

Invisible

Commission Tests Clear Dist Recs

Visible

Setting Values

Primary

Control Inputs

Visible

CT AND VT RATIOSRECORD CONTROL

(When Visible)

DISTURB RECORDER

(When Visible)

111111111111111

111111111111111

111111111111111

No

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

Control I/P Config

Visible

Control I/P Labels

Visible

Direct Access

Enabled

LCD Contrast

11

Page 72: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-34

MiCOM P741, P742, P743

GS

Default Display RP1 Protocol Opto I/P Status Global Nominal V

IA - AB - IC Courier 0000000000000000 48/54V

Digital Input 16 Digital Input 26 Local Values RP1 Address Relay O/P Status If Custom selected:

Relay Label 01 Unused Primary 00000000

Input 16 Trigger Input 26 Trigger Remote Values RP1 InactivTimer Test Port Status Opto Input 1

No Trigger No Trigger Primary 15 mins 00000000 48/54V

Digital Input 17 Digital Input 27 RP1 Card Status LED Staus Opto Input 2

Relay Label 02 Unused K Bus OK 00000000 48/54V

Input 17 Trigger Input 27 Trigger RP1 Port Config Monitor Bit 1 Opto Input 3

No Trigger No Trigger K Bus Relay Label 01 48/54V

Digital Input 18 Digital Input 28 If RS485: Monitor Bit 2 Opto Input 4

Relay Label 03 Unused Relay Label 02 48/54V

Input 18 Trigger Input 28 Trigger RP1 Comms Mode Monitor Bit 3

No Trigger No Trigger Relay Label 03

Digital Input 19 Digital Input 29 RP1 Baud Rate Monitor Bit 4

Saturation ph A Unused 19200 Relay Label 04

Input 19 Trigger Input 29 Trigger Monitor Bit 5 Opto Input 16

No Trigger No Trigger Relay Label 05 48/54V

Digital Input 20 Digital Input 30 Monitor Bit 6

Saturation ph B Unused Relay Label 06

Input 20 Trigger Input 30 Trigger Monitor Bit 7

No Trigger No Trigger Relay Label 07

Digital Input 21 Digital Input 31 Monitor Bit 8

Saturation ph C Unused Relay Label 08

Input 21 Trigger Input 31 Trigger Test Mode

No Trigger No Trigger Disabled

Digital Input 22 Digital Input 32 Test LEDs

Trip 50BF (CU) Unused No Operation

Input 22 Trigger Input 32 Trigger Position Pattern

Trigger L/H No Trigger 0000000

Digital Input 23 If Test Mode enabled:

Trip 87BB

Input 23 Trigger Test Pattern

Trigger L/H 00000000

Digital Input 24 Contact Test

Unused No operation

Input 24 Trigger

No Trigger

Digital Input 25

Unused

Input 25 Trigger

No Trigger

COMMISSION TESTS

(When Visible)OPTO CONFIG

6

Repeat as above for

Opto Input

5 - 16

MEASURE'T SETUP

(When Visible)

IEC60870 FT1.2

COMMUNICATIONS

(If set visible)

Page 73: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-35

GS

Ctrl I/P Status Hotkey Enabled Control Input 1 I>BB Current Set

0000000000000000 1.200 kA

Control Input 1 Control Input 1 Control Input 12 Control Input 2 IN>BB Current Set

No Operation Latched Latched 200.0 A

Control Input 2 Ctrl Command 1 Ctrl Command 12 Control Input 3

No Operation Set/Reset Set/Reset

Control Input 3 Control Input 2 Control Input 13 Control Input 23 Control Input 4

No Operation Latched Latched Latched

Control Input 4 Ctrl Command 2 Ctrl Command 13 Ctrl Command 23 Control Input 5

No Operation Set/Reset Set/Reset Set/Reset Control Input 5

Control Input 3 Control Input 14 Control Input 24 Control Input 6

Latched Latched Latched

Ctrl Command 3 Ctrl Command 14 Ctrl Command 24 Control Input 7

Set/Reset Set/Reset Set/Reset Control Input 7

Control Input 32 Control Input 4 Control Input 15 Control Input 25 Control Input 8

No Operation Latched Latched Latched Control Input 8

Ctrl Command 4 Ctrl Command 15 Ctrl Command 25 Control Input 9

Set/Reset Set/Reset Set/Reset Control Input 9

Control Input 5 Control Input 16 Control Input 26 Control Input 10

Latched Latched Latched Control Input 10

Ctrl Command 5 Ctrl Command 16 Ctrl Command 26 Control Input 11

Set/Reset Set/Reset Set/Reset Control Input 11

Control Input 6 Control Input 17 Control Input 27 Control Input 12

Latched Latched Latched Control Input 12

Ctrl Command 6 Ctrl Command 17 Ctrl Command 27 Control Input 13

Set/Reset Set/Reset Set/Reset Control Input 13

Control Input 7 Control Input 18 Control Input 28 Control Input 14

Latched Latched Latched Control Input 14

Ctrl Command 7 Ctrl Command 18 Ctrl Command 28 Control Input 15

Set/Reset Set/Reset Set/Reset Control Input 15

Control Input 8 Control Input 19 Control Input 29 Control Input 16

Latched Latched Latched Control Input 16

Ctrl Command 8 Ctrl Command 19 Ctrl Command 29 Control Input 17

Set/Reset Set/Reset Set/Reset Control Input 17

Control Input 9 Control Input 20 Control Input 30 Control Input 18

Latched Latched Latched Control Input 18

Ctrl Command 9 Ctrl Command 20 Ctrl Command 30 Control Input 19

Set/Reset Set/Reset Set/Reset Control Input 19

Control Input 10 Control Input 21 Control Input 31 Control Input 20

Latched Latched Latched Control Input 20

Ctrl Command 10 Ctrl Command 21 Ctrl Command 31

Set/Reset Set/Reset Set/Reset

Control Input 11 Control Input 22 Control Input 32

Latched Latched Latched

Ctrl Command 11 Ctrl Command 22 Ctrl Command 32 Control Input 32

Set/Reset Set/Reset Set/Reset Control Input 32

BB TRIP CONFIRM

GROUP 1 (If set)

CONTROL INPUTS

(When Visible)

CTRL I/P CONFIG

(When Visible)CTRL I/P LABELS

1111111111111111 Control Input 1

Control Input 3

Control Input 4

Control Input 2

Repeat as above for

Control Input

5 - 31

Control Input 6

* Continue as above up

to Control input 32

Page 74: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-36

MiCOM P741, P742, P743

GS

I>DZ Current Set I>1 Function IN>1 Function Control By IO SUPERVISION Opto Input 1

1.200 A Disabled Disabled I< GROUP 1 Opto Label 01

I>DZ Time Delay I>2 Function IN>2 Function I< Current Set Error Factor Kce Opto Input 2

1.000 s Disabled Disabled 50.00 A 40.00 % Opto Label 02

IN>DZ Cur. Set If I>1 IEC x Inverse: If IN>1 IEC x Inverse: I> Status Alarm Delay Tce Opto Input 3

Disabled Disabled 5.000 s Opto Label 03

If Enabled: I>1 Current Set IN>1 Current Set If Enabled: Opto Input 4

3.000 kA 300.0 A Opto Label 04

IN>DZ Cur. Set I>1 TMS IN>1 TMS I> Current Set Opto Input 5

1.200 A 1.000 s 1.000 s 1.2 Opto Label 05

IN>DZ Time Delay I>1 tReset IN>1 tReset IN> Current Set Opto Input 6

1.000 s 0 s 0 s 0.2 Opto Label 06

If I>2 Blocking 87BB: If IN>2 Blocking 87BB: Internal Trip Opto Input 7

GROUP 1 Opto Label 07

I>2 Current Set IN>2 Current Set CB Fail Timer 1 Opto Input 8

20.00 kA 20.00 kA 50.00 ms Opto Label 08

If I>2 High Set I>2: If IN>2 High Set I>2: CB Fail Timer 2 Opto Input 9

200.00 ms Opto Label 09

I>2 Current Set IN>2 Current Set External Trip Opto Input 10

20.00 kA 20.00 kA GROUP 1 Opto Label 10

I>2 Time delay IN>2 Time delay CB Fail Timer 3 Opto Input 11

1.000 s 1.000 s 50.00 ms Opto Label 11

If I>2 Both: If IN>2 Both: CB Fail Timer 4 Opto Input 12

200.00 ms Opto Label 12

I>2 Current Set IN>2 Current Set If Contol By 52a: Opto Input 13

20.00 kA 20.00 kA Opto Label 13

I>2 Time delay IN>2 Time delay Internal Trip Opto Input 14

1.000 s 1.000 s GROUP 1 Opto Label 14

CB Fail Timer 1 Opto Input 15

50.00 ms Opto Label 15

CB Fail Timer 2 Opto Input 16

200.00 ms Opto Label 16

External Trip

GROUP 1

CB Fail Timer 3

50.00 ms

CB Fail Timer 4

200.00 ms

DEAD ZONE PROT

GROUP 1 (If set)

EARTH FAULT

GROUP 1 (If set)

OVERCURRENT

GROUP 1 (If set)

CB FAIL

GROUP 1

INPUT LABELS

GROUP 1 (Visible)

SUPERVISION

GROUP 1

Page 75: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-37

GS

Idem Group 2,3 & 4

PSL DATA

Relay 1 Grp 1 PSL Ref

Relay Label 01 Reference

Relay 2 JJ Month AAAA

Relay Label 02 HH:MM:SS:mmm

Relay 3 Grp 1 PSL ID

Relay Label 03 1061683974

Relay 4 Grp 2 PSL Ref

Relay Label 04 Reference

Relay 5 same for

Relay Label 05 Groupe 3 & 4

Relay 6

Relay Label 06

Relay 7

Relay Label 07

Relay 8

Relay Label 08

OUTPUT LABELS

GROUP 1 (Visible)

Page 76: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-38

MiCOM P741, P742, P743

GS

Appendix – P743 Relay Menu Map (Default)

Note: This menu map is annotated with the factory default settings.

SYSTEM DATA

Language Select Event* IA Magnitude Link CT / zone Min Trip Pulse Date

English [0…511] 0 0.000 A 00000000 200.0 ms 05 Jan 2006

Password Select Fault* IA Phase Angle Zx: IA Diff Trip Latched Time

**** [0…4] 0 0.000 ° 0 A Disabled 12:00:00

Description Select Maint* IB Magnitude Zx: IB Diff CB Control by Battery Status

MiCOM P743 [0…4] 0 0.000 A 0 A Healthy

Plant Reference Reset Indication IB Phase Angle Zx: IC Diff If not: Battery Alarm

MiCOM No 0.000 ° 0 A Enabled

Model Number *: If existing IC Magnitude Zx: IN Diff Man Close Pulse

0.000 A 0 A 500.0 ms

Serial Number IC Phase Angle Zx: IA Bias Man Trip Pulse

0.000 ° 0 A 500.0 ms

Frequency IN Magnitude Zx: IB Bias Man Close Delay

50 0.000 A 0 A 10.00 s

Comms Level IN Phase Angle Zx: IC Bias Reset Trip Latch

2 0.000 ° 0 A No

Relay Address IN Derived Magn Zx: IN Bias

255 0.000 A 0 A

Plant Status IN Derived Angle x = 1 to 8 if existing

0000000000000000 0.000 °

Control Status I1 Magnitude

0000000000000000 0.000 A

Active Group I2 Magnitude

1 0.000 A

Software Ref. 1 I0 Magnitude

Ref. Number 0.000 A

Opto I/P Status Frequency

0000000000000000 50 Hz

Relay O/P Status

0000000000000000

Alarm Status 1

0000000000000000

Alarm Status 1

0000000000000000

Alarm Status 2

0000000000000000

Alarm Status 3

0000000000000000

Access Level

2

Password Control

2

Password Level 1

****

Password Level 2

****

VIEW RECORDS MEASUREMENTS 1 TOPOLOGY 1 CB CONTROL

Disabled

DATE AND TIME

Page 77: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-39

GS

CONFIGURATION

Restore Defaults Phase CT Primary Clear Events Duration

No Operation 1.000 kA No 1,200 s

Setting Group Phase CT Sec'y Clear Faults Trigger Position Digital Input 6

Select via Menu 1.000 A No 33,34 % CBF Int Backtrip

Active Settings RBPh / RBN Clear Maint DDB 415 - 384 Trigger Mode Input 6 Trigger

Group 1 1.000 No ########### Extended Trigger L/H

Save Changes Power Parameters Alarm Event DDB 447 - 416 Analog Channel 1 Digital Input 7

No Operation Enabled IA CBF Ext Backtrip

Copy From Standard Input Relay O/P Event DDB 479 - 448 Analog Channel 2 Input 7 Trigger

Group 1 British Standard Enabled IB Trigger L/H

Copy To Knee Voltage Vk Opto Input Event DDB 511 - 480 Analog Channel 3 Digital Input 8

No Operation 500.0 V Enabled IC Dead Zone Fault

Setting Group 1 RCT Sec'y General Event DDB 543 - 512 Analog Channel 4 Input 8 Trigger

Enabled 500,0 m_ Enabled IN Trigger L/H

Setting Group 2 Eff. Burden Ohm Fault Rec Event DDB 575 - 544 Analog Channel 5 Digital Input 9

Disabled 500,0 m_ Enabled Unassigned Ext. CB Fail

Setting Group 3 If IEC: Maint Rec Event DDB 607 - 576 Analog Channel 6 Input 9 Trigger

Disabled Enabled Unassigned Trigger L/H

Setting Group 4 Rated Burden VA Protection Event DDB 639 - 608 Analog Channel 7 Digital Input 10

Disabled 25.00 VA Enabled Unassigned Ext. 3 ph Trip

Dead Zone Prot Rated Burden Ohm DDB 31 - 0 DDB 671 - 640 Analog Channel 8 Input 10 Trigger

Disabled 25.00 _ Unassigned Trigger L/H

BB Trip Confirm KSCC DDB 63 - 32 DDB 703 - 672 Digital Input 1 Digital Input 11

Disabled 10 Field Volt Fail Internal Trip

Overcurrent Prot RCT Sec'y DDB 95 - 64 DDB 735 - 704 Input 1 Trigger Input 11 Trigger

Disabled 500,0 m_ No Trigger Trigger L/H

Earth Fault Prot Eff. Burden Ohm DDB 127 - 96 DDB 767 - 736 Digital Input 2 Digital Input 12

Disabled 500,0 m_ Any Trip Q1 Closed

CB Fail & I< Eff. Burden VA DDB 159 - 128 DDB 799 - 768 Input 2 Trigger Input 12 Trigger

Enabled 500,0 mVA Trigger L/H No Trigger

Input Labels DDB 191 - 160 DDB 831 - 800 Digital Input 3 Digital Input 13

Visible CB Closed Q2 Closed

Output Labels DDB 223 - 192 DDB 863 - 832 Input 3 Trigger Input 13 Trigger

Visible No Trigger No Trigger

CT & VT Ratios DDB 255 - 224 DDB 895 - 864 Digital Input 4 Digital Input 14

Visible CB Fail Alarm Q3 Closed

Record Control DDB 287 - 256 DDB 927 - 896 Input 4 Trigger Input 14 Trigger

Visible No Trigger No Trigger

Disturb Recorder DDB 319 - 288 DDB 959 - 928 Digital Input 5 Digital Input 15

Visible CB not available Man. Trip zone

Measure't Setup DDB 351 - 320 DDB 991 - 960 Input 5 Trigger Input 15 Trigger

Visible No Trigger Trigger L/H

Comms Settings DDB 383 - 352 DDB 1022 - 992

Invisible

Commission Tests Clear Dist Recs

Visible

Setting Values

Primary

Control Inputs Direct Access

Visible Enabled

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

CT AND VT RATIOS

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

No

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

RECORD CONTROL

(When Visible)

DISTURB RECORDER

(When Visible)

111111111111111

111111111111111

111111111111111

111111111111111111111111111111

111111111111111

111111111111111

111111111111111

111111111111111

Control I/P Config Function key

Visible Visible

Control I/P Labels LCD Contrast

Visible 11

Page 78: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-40

MiCOM P741, P742, P743

GS

Default Display RP1 Protocol Opto I/P Status Global Nominal V

IA - AB - IC Courier 0000000000000000 48/54V

Digital Input 16 Digital Input 26 Local Values RP1 Address Relay O/P Status If Custom selected:

Relay Label 01 Unused Primary 0000000000000000

Input 16 Trigger Input 26 Trigger Remote Values RP1 InactivTimer Test Port Status Opto Input 1

No Trigger No Trigger Primary 15 mins 00000000 48/54V

Digital Input 17 Digital Input 27 RP1 Card Status Monitor Bit 1 Opto Input 2

Relay Label 02 Unused K Bus OK Relay Label 01 48/54V

Input 17 Trigger Input 27 Trigger RP1 Port Config Monitor Bit 2 Opto Input 3

No Trigger No Trigger K Bus Relay Label 02 48/54V

Digital Input 18 Digital Input 28 If RS485: Monitor Bit 3 Opto Input 4

Relay Label 03 Unused Relay Label 03 48/54V

Input 18 Trigger Input 28 Trigger RP1 Comms Mode Monitor Bit 4

No Trigger No Trigger Relay Label 04

Digital Input 19 Digital Input 29 RP1 Baud Rate Monitor Bit 5

Saturation ph A Unused 19200 Relay Label 05

Input 19 Trigger Input 29 Trigger Monitor Bit 6 Opto Input 24

No Trigger No Trigger Relay Label 06 48/54V

Digital Input 20 Digital Input 30 Monitor Bit 7

Saturation ph B Unused Relay Label 07

Input 20 Trigger Input 30 Trigger Monitor Bit 8

No Trigger No Trigger Relay Label 08

Digital Input 21 Digital Input 31 Test Mode

Saturation ph C Unused Disabled

Input 21 Trigger Input 31 Trigger Test LEDs

No Trigger No Trigger No Operation

Digital Input 22 Digital Input 32 Position Pattern

Trip 50BF (CU) Unused 0000000

Input 22 Trigger Input 32 Trigger Red LED Status

Trigger L/H No Trigger 0000000000000000

Digital Input 23 Green LED Status

Trip 87BB 0000000000000000

Input 23 Trigger If Test Mode enabled:

Trigger L/H

Digital Input 24 Test Pattern

Unused 00000000

Input 24 Trigger Contact Test

No Trigger No operation

Digital Input 25

Unused

Input 25 Trigger

No Trigger

IEC60870 FT1.2 Repeat as above for

Opto Input

5 - 24

6

COMMUNICATIONS

(If set visible)

MEASURE'T SETUP

(When Visible)

COMMISSION TESTS

(When Visible)OPTO CONFIG

Page 79: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-41

GS

Ctrl I/P Status Hotkey Enabled Fn Key Status

0000000000000000 0000000000

Control Input 1 Control Input 1 Control Input 12 Fn Key 1

No Operation Latched Latched Unlocked

Control Input 2 Ctrl Command 1 Ctrl Command 12 Fn Key 1 Mode

No Operation Set/Reset Set/Reset Normal

Control Input 3 Control Input 2 Control Input 13 Control Input 23 Fn Key 1 Label

No Operation Latched Latched Latched Function Key 1

Control Input 4 Ctrl Command 2 Ctrl Command 13 Ctrl Command 23 Fn Key 2

No Operation Set/Reset Set/Reset Set/Reset Unlocked

Control Input 3 Control Input 14 Control Input 24 Fn Key 2 Mode

Latched Latched Latched Normal

Ctrl Command 3 Ctrl Command 14 Ctrl Command 24 Fn Key 2 Label

Set/Reset Set/Reset Set/Reset Function Key 2

Control Input 32 Control Input 4 Control Input 15 Control Input 25 Fn Key 3

No Operation Latched Latched Latched Unlocked

Ctrl Command 4 Ctrl Command 15 Ctrl Command 25 Fn Key 3 Mode

Set/Reset Set/Reset Set/Reset Normal

Control Input 5 Control Input 16 Control Input 26 Fn Key 3 Label

Latched Latched Latched Function Key 3

Ctrl Command 5 Ctrl Command 16 Ctrl Command 26 Fn Key 4

Set/Reset Set/Reset Set/Reset Unlocked

Control Input 6 Control Input 17 Control Input 27 Fn Key 4 Mode

Latched Latched Latched Normal

Ctrl Command 6 Ctrl Command 17 Ctrl Command 27 Fn Key 4 Label

Set/Reset Set/Reset Set/Reset Function Key 4

Control Input 7 Control Input 18 Control Input 28 Fn Key 5

Latched Latched Latched Unlocked

Ctrl Command 7 Ctrl Command 18 Ctrl Command 28 Fn Key 5 Mode

Set/Reset Set/Reset Set/Reset Normal

Control Input 8 Control Input 19 Control Input 29 Fn Key 5 Label Fn Key 8 Mode

Latched Latched Latched Function Key 5 Normal

Ctrl Command 8 Ctrl Command 19 Ctrl Command 29 Fn Key 6 Fn Key 8 Label

Set/Reset Set/Reset Set/Reset Unlocked Function Key 8

Control Input 9 Control Input 20 Control Input 30 Fn Key 6 Mode Fn Key 9

Latched Latched Latched Normal Unlocked

Ctrl Command 9 Ctrl Command 20 Ctrl Command 30 Fn Key 6 Label Fn Key 9 Mode

Set/Reset Set/Reset Set/Reset Function Key 6 Normal

Control Input 10 Control Input 21 Control Input 31 Fn Key 7 Fn Key 9 Label

Latched Latched Latched Unlocked Function Key 9

Ctrl Command 10 Ctrl Command 21 Ctrl Command 31 Fn Key 7 Mode Fn Key 10

Set/Reset Set/Reset Set/Reset Normal Unlocked

Control Input 11 Control Input 22 Control Input 32 Fn Key 7 Label Fn Key 10 Mode

Latched Latched Latched Function Key 7 Normal

Ctrl Command 11 Ctrl Command 22 Ctrl Command 32 Fn Key 8 Fn Key 10 Label

Set/Reset Set/Reset Set/Reset Unlocked Function Key 10

Repeat as above for

Control Input

5 - 31

1111111111111111

FUNCTION KEYS

(When Visible)

CTRL I/P CONFIG

(When Visible)

CONTROL INPUTS

(When Visible)

Page 80: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-42

MiCOM P741, P742, P743

GS

Control Input 1 I>BB Current Set I>DZ Current Set I>1 Function IN>1 Function Control By

1.200 kA 1.200 A Disabled Disabled I<

Control Input 2 IN>BB Current Set I>DZ Time Delay I>2 Function IN>2 Function I< Current Set

200.0 A 1.000 s Disabled Disabled 50.00 A

Control Input 3 IN>DZ Cur. Set If I>1 IEC x Inverse: If IN>1 IEC x Inverse: I> Status

Disabled Disabled

Control Input 4 If Enabled: I>1 Current Set IN>1 Current Set If Enabled:

3.000 kA 300.0 A

Control Input 5 IN>DZ Cur. Set I>1 TMS IN>1 TMS I> Current Set

Control Input 5 1.200 A 1.000 s 1.000 s 1.2

Control Input 6 IN>DZ Time Delay I>1 tReset IN>1 tReset IN> Current Set

1.000 s 0 s 0 s 0.2

Control Input 7 If I>2 Blocking 87BB: If IN>2 Blocking 87BB: Internal Trip

Control Input 7 GROUP 1

Control Input 8 I>2 Current Set IN>2 Current Set CB Fail Timer 1

Control Input 8 20.00 kA 20.00 kA 50.00 ms

Control Input 9 If I>2 High Set I>2: If IN>2 High Set I>2: CB Fail Timer 2

Control Input 9 200.00 ms

Control Input 10 I>2 Current Set IN>2 Current Set External Trip

Control Input 10 20.00 kA 20.00 kA GROUP 1

Control Input 11 I>2 Time delay IN>2 Time delay CB Fail Timer 3

Control Input 11 1.000 s 1.000 s 50.00 ms

Control Input 12 If I>2 Both: If IN>2 Both: CB Fail Timer 4

Control Input 12 200.00 ms

Control Input 13 I>2 Current Set IN>2 Current Set If Contol By 52a:

Control Input 13 20.00 kA 20.00 kA

Control Input 14 I>2 Time delay IN>2 Time delay Internal Trip

Control Input 14 1.000 s 1.000 s GROUP 1

Control Input 15 CB Fail Timer 1

Control Input 15 50.00 ms

Control Input 16 CB Fail Timer 2

Control Input 16 200.00 ms

Control Input 17 External Trip

Control Input 17 GROUP 1

Control Input 18 CB Fail Timer 3

Control Input 18 50.00 ms

Control Input 19 CB Fail Timer 4

Control Input 19 200.00 ms

Control Input 20

Control Input 20

Control Input 3

Control Input 4

Control Input 6

Control Input 1

Control Input 2

BB TRIP CONFIRM

GROUP 1 (If set)

DEAD ZONE PROT

GROUP 1 (If set)

EARTH FAULT

GROUP 1 (If set)CTRL I/P LABELS

CB FAIL

GROUP 1

OVERCURRENT

GROUP 1 (If set)

Control Input 32

Control Input 32

* Continue as above up

to Control input 32

Page 81: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

MiCOM P741, P742, P743

(GS) 3-43

GS

Idem Group 2,3 & 4

PSL DATA

IO SUPERVISION Opto Input 1 Relay 1 Grp 1 PSL Ref

GROUP 1 Opto Label 01 Relay Label 01 Reference

Error Factor Kce Opto Input 2 Relay 2 JJ Month AAAA

40.00 % Opto Label 02 Relay Label 02 HH:MM:SS:mmm

Alarm Delay Tce Opto Input 3 Relay 3 Grp 1 PSL ID

5.000 s Opto Label 03 Relay Label 03 1061683974

RP1 Card Status Opto Input 4 Relay 4 Grp 2 PSL Ref

K Bus OK Opto Label 04 Relay Label 04 Reference

RP1 Port Config Opto Input 5 Relay 5 same for

K Bus Opto Label 05 Relay Label 05 Groupe 3 & 4

* see Note 3

Opto Input 6 Relay 6

Opto Label 06 Relay Label 06

Opto Input 7 Relay 7

Opto Label 07 Relay Label 07

Opto Input 8 Relay 8

Opto Label 08 Relay Label 08

Opto Input 9 Relay 9

Opto Label 09 Relay Label 09

Opto Input 10 Relay 10

Opto Label 10 Relay Label 10

Opto Input 11 Relay 11

Opto Label 11 Relay Label 11

Opto Input 12 Relay 12

Opto Label 12 Relay Label 12

Opto Input 13 Relay 13

Opto Label 13 Relay Label 13

Opto Input 14 Relay 14

Opto Label 14 Relay Label 14

Opto Input 15 Relay 15

Opto Label 15 Relay Label 15

Opto Input 16 Relay 16

Opto Label 16 Relay Label 16

Opto Input 17

Opto Label 17

Opto Input 18

Opto Label 18

Opto Input 19

Opto Label 19

Opto Input 20

Opto Label 20

Opto Input 21

Opto Label 21

Opto Input 22

Opto Label 22

Opto Input 23

Opto Label 23

Opto Input 24

Opto Label 24

INPUT LABELS

GROUP 1 (Visible)

SUPERVISION

GROUP 1

OUTPUT LABELS

GROUP 1 (Visible)

Page 82: P74x_EN_M_H54

Getting Started P74x/EN GS/H54

(GS) 3-44

MiCOM P741, P742, P743

GS

BLANK PAGE

Page 83: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

ST

SETTINGS

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 84: P74x_EN_M_H54

P74x/EN ST/H54 Getting Started

MiCOM P741, P742, P743

Page 85: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-1

ST

CONTENTS

1. SETTINGS 3

1.1 Relay settings configuration 3

1.1.1 The configuration column for the P741 Central Unit 3

1.1.2 The configuration column for the P742 Peripheral Unit 6

1.1.3 The configuration column for the P743 Peripheral Unit 8

1.1.4 Default settings restore 10

1.2 Protection settings 10

1.2.1 Central Unit P741 10

1.2.2 Peripheral Units P742 or P743 12

1.2.3 Non-Directional Earth Fault Overcurrent Protection and External Fault Detection by High-Set Overcurrent 14

1.2.4 Circuit breaker fail and undercurrent function 15

1.2.5 Supervision CTS 16

1.3 Control and support settings 16

1.3.1 System data 17

1.3.2 Circuit breaker control 22

1.3.3 Date and time 22

1.3.4 CT ratios 23

1.3.5 Record control 24

1.3.6 Measurements 25

1.3.7 Communications 25

1.3.8 Commissioning tests 26

1.3.9 Peripheral Unit P742 28

1.3.10 Peripheral Unit P743 30

1.3.11 Opto configuration 32

1.3.12 Control input configuration 33

1.3.13 Function keys 34

1.3.14 Control input labels 35

Page 86: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-2

MiCOM P741, P742, P743

ST

1.4 Disturbance recorder settings 35

1.4.1 Central Unit P741 35

1.4.2 Peripheral Unit P742 or P743 37

Page 87: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-3

ST

1. SETTINGS The P74x must be configured to the system and application by means of appropriate settings. The sequence in which the settings are listed and described in this chapter will be the protection setting, control and configuration settings and the disturbance recorder settings (see section P74x/EN GS for the detailed relay menu maps). The relay is supplied with a factory-set configuration of default settings.

1.1 Relay settings configuration

The relay is a multi-function device that supports numerous different protection, control and communication features. In order to simplify the setting of the relay, there is a configuration settings column which can be used to enable or disable many of the functions of the relay. The settings associated with any function that is disabled are made invisible; i.e. they are not shown in the menu. To disable a function change the relevant cell in the ‘Configuration’ column from ‘Enabled’ to ‘Disabled’.

The configuration column controls which of the four protection settings groups is selected as active through the ‘Active settings’ cell. A protection setting group can also be disabled in the configuration column, provided it is not the present active group. Similarly, a disabled setting group cannot be set as the active group.

The column also allows all of the setting values in one group of protection settings to be copied to another group.

To do this firstly set the ‘Copy from’ cell to the protection setting group to be copied, then set the ‘copy to’ cell to the protection group where the copy is to be placed. The copied settings are initially placed in the temporary scratchpad, and will only be used by the relay following confirmation.

1.1.1 The configuration column for the P741 Central Unit

Menu Text Default Setting Available Settings

Restore Defaults No Operation

No Operation All Settings Setting Group 1 Setting Group 2 Setting Group 3 Setting Group 4

Setting to restore a setting group to factory default settings.

Setting Group Select via Menu Select via Menu Select via Optos

Allows setting group changes to be initiated via Opto Input or via Menu.

Active Settings Group 1 Group 1, Group 2, Group 3, Group 4

Selects the active setting group.

Save Changes No Operation No Operation, Save, Abort

Saves all relay settings.

Copy from Group 1 Group 1, 2, 3 or 4

Allows displayed settings to be copied from a selected setting group.

Copy to No Operation No Operation Group 1, 2, 3 or 4

Allows displayed settings to be copied to a selected setting group (ready to paste).

Setting Group 1 Enabled Enabled or Disabled

If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting (paste).

Page 88: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-4

MiCOM P741, P742, P743

ST

Menu Text Default Setting Available Settings

Setting Group 2 (as above) Disabled Enabled or Disabled

Setting Group 3 (as above) Disabled Enabled or Disabled

Setting Group 4 (as above) Disabled Enabled or Disabled

Busbar Option Invisible Visible / Invisible Sets the Busbar Option menu visible further on in the relay settings menu.

Diff Busbar Prot Enabled Enabled or Disabled

To enable (activate) or disable (turn off) the Differential Busbar Protection function. ANSI 87BB.

Input Labels Visible Invisible or Visible

Sets the Input Labels menu visible further on in the relay settings menu.

Output Labels Visible Invisible or Visible

Sets the Output Labels menu visible further on in the relay settings menu.

Recorder Control Visible Invisible or Visible

Sets the Record Control menu visible further on in the relay settings menu.

Disturb. Recorder Visible Invisible or Visible

Sets the Disturbance Recorder menu visible further on in the relay settings menu.

Measure't. Set-up Visible Invisible or Visible

Sets the Measurement Setup menu visible further on in the relay settings menu.

Comms. Settings Invisible Invisible or Visible

Sets the Communications Settings menu visible further on in the relay settings menu. These are the settings associated with the 1st and 2nd rear communications ports.

Commission Tests Visible Invisible or Visible

Sets the Commissioning Tests menu visible further on in the relay settings menu.

Setting Values Primary Primary or Secondary

This affects all protection settings that are dependent upon CT and VT ratios.

Control Inputs Visible Invisible or Visible

Activates the Control Input status and operation menu further on in the relay setting menu.

Ctrl I/P Config. Visible Invisible or Visible

Sets the Control Input Configuration menu visible further on in the relay setting menu.

Ctrl I/P Labels Visible Invisible or Visible

Sets the Control Input Labels menu visible further on in the relay setting menu.

Direct Access Enabled Enabled/Disabled/Hotkey only/CB Cntrl. only

Defines what CB control direct access is allowed. Enabled implies control via menu, hotkeys etc.

Function Key Visible Invisible or Visible

Sets the Function Key menu visible further on in the relay setting menu.

LCD Contrast 11 0…31

Sets the LCD contrast.

Page 89: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-5

ST

In the central unit an additional configuration column “PU Conf & Status” is present to configure the hardware to the software topology.

MENU TEXT Default Setting Available Settings

PU CONF & STATUS

PU in service 0000000000000000

00000000000

0 or 1

List of the PUs in service.

For example a topology scheme may define 12 PU:

5 PU for current phase and 7 PU for future.

This would be set to: 1111100000000000000000000000

PU connected 0000000000000000

00000000000

Live values

List of the PUs connected and synchronized with the CU. After reboot the CU waits for the list of connected PUs to equal the PUs in service before enabling the busbar protection.

If there is a discrepancy the CU will not start and the scheme will be locked.

PU topo valid 0000000000000000

00000000000

Live values

List of PUs with valid topology data. After rebooting the CU checks the topology configuration on all PUs and reports the result in this cell.

If there is a discrepancy the central unit will not start and the scheme will be locked.

Reset Circt Flt No Yes or No

After a circuitry fault has been detected, the user can accept and clear the error, using the command from this cell. The command will be rejected if the fault is still present.

Circuitry Fault 00000000 Live values

List of the zones blocked by a circuitry fault

Circ Fault Phase Phase A or B or C or N

Faulty phase that blocks by a circuitry fault the zone

Reset PU Error No Yes or No

After a PU communication error has been detected, the user can accept and clear the error, using the command from this cell. The command will NOT be rejected if the fault is still present.

PU Error Locked 00000000 Live values

List of the zones blocked for PU communication error

87BB monitoring 00000000 Live values

List of the zones on which the 87BB protection is blocked

87BB&50BF disabl 00000000 Live values

List of the zones on which the 87BB AND 50BF protection are blocked

Page 90: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-6

MiCOM P741, P742, P743

ST

1.1.2 The configuration column for the P742 Peripheral Unit

MENU TEXT Default Setting Available Settings

CONFIGURATION

Restore Defaults No Operation No Operation All Settings Setting Group 1 Setting Group 2 Setting Group 3 Setting Group 4

Setting to restore a setting group to factory default settings.

Setting Group Select via Menu Select via Menu Select via Optos

Allows setting group changes to be initiated via Opto Input or via Menu.

Active Settings Group 1 Group 1 Group 2 Group 3 Group 4

Selects the active setting group.

Save Changes No Operation No Operation (Save Abort)

Saves all relay settings.

Copy From Group 1 Group 1 Group 2 Group 3 Group 4

Allows displayed settings to be copied from a selected setting group.

Copy to No Operation No Operation Group 1 Group 2 Group 3 Group 4

Allows displayed settings to be copied to a selected setting group (ready to paste).

Setting Group 1 Enabled Enabled/Disabled

If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting (paste).

Setting Group 2 Disabled Enabled/Disabled

Setting Group 3 Disabled Enabled/Disabled

Setting Group 4 Disabled Enabled/Disabled

Dead Zone Prot Enabled Enabled/Disabled

To enable (activate) or disable (turn off) the Dead Zone Protection function. BB Trip Confirm Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Busbar Trip order confirmation on an overcurrent function to allow to trip the breaker. ANSI .

Overcurrent Prot Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Phase Overcurrent Protection function. Earth Fault Prot Disabled Enabled/Disabled

Page 91: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-7

ST

MENU TEXT Default Setting Available Settings

CONFIGURATION

To enable (activate) or disable (turn off) the Earth Overcurrent Protection function. ANSI 50N/51N.

CB Fail & I< Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection functions. ANSI 50BF.

Input Labels Visible Visible/Invisible

Sets the Input Labels menu visible further on in the relay settings menu.

Output Labels Visible Visible/Invisible

Sets the Output Labels menu visible further on in the relay settings menu.

CT & VT Ratios Visible Visible/Invisible

Sets the Current & Voltage Transformer Ratios menu visible further on in the relay settings menu.

Recorder Control Visible Visible/Invisible

Sets the Record Control menu visible further on in the relay settings menu.

Disturb Recorder Visible Visible/Invisible

Sets the Disturbance Recorder menu visible further on in the relay settings menu.

Measure't Setup Visible Visible/Invisible

Sets the Measurement Setup menu visible further on in the relay settings menu.

Comms Settings Invisible Visible/Invisible

Sets the Communications Settings menu visible further on in the relay settings menu.

Commission Tests Visible Visible/Invisible

Sets the Commissioning Tests menu visible further on in the relay settings menu.

Setting Values Secondary Primary/Secondary

This affects all protection settings that are dependent upon CT and VT ratios.

Control Inputs Visible Visible/Invisible

Activates the Control Input status and operation menu further on in the relay setting menu.

Ctrl I/P Config Visible Visible/Invisible

Sets the Control Input Configuration menu visible further on in the relay setting menu.

Ctrl I/P Labels Visible Visible/Invisible

Sets the Control Input Labels menu visible further on in the relay setting menu.

Direct Access Enabled Enabled / Disabled

Defines what CB control direct access is allowed. Enabled implies control via menu, hotkeys etc.

LCD Contrast 11 0…31

Sets the LCD contrast.

Page 92: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-8

MiCOM P741, P742, P743

ST

1.1.3 The configuration column for the P743 Peripheral Unit

MENU TEXT Default Setting Available Settings

CONFIGURATION

Restore Defaults No Operation No Operation All Settings Setting Group 1 Setting Group 2 Setting Group 3 Setting Group 4

Setting to restore a setting group to factory default settings.

Setting Group Select via Menu Select via Menu Select via Optos

Allows setting group changes to be initiated via Opto Input or via Menu. Active Settings Group 1 Group 1

Group 2 Group 3 Group 4

Selects the active setting group. Save Changes No Operation No Operation

Save Abort

Saves all relay settings. Copy From Group 1 Group 1

Group 2 Group 3 Group 4

Allows displayed settings to be copied from a selected setting group. Copy to No Operation No Operation

Group 1 Group 2 Group 3 Group 4

Allows displayed settings to be copied to a selected setting group (ready to paste). Setting Group 1 Enabled Enabled/Disabled

If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting (paste).

Setting Group 2 Disabled Enabled/Disabled

Setting Group 3 Disabled Enabled/Disabled

Setting Group 4 Disabled Enabled/Disabled

Dead Zone Prot Enabled Enabled/Disabled

To enable (activate) or disable (turn off) the Dead Zone Protection function. BB Trip Confirm Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Busbar Trip order confirmation on an overcurrent function to allow to trip the breaker.

Overcurrent Prot Disabled Enabled/Disabled To enable (activate) or disable (turn off) the Phase Overcurrent Protection function. ANSI 50P/51.

Page 93: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-9

ST

MENU TEXT Default Setting Available Settings

CONFIGURATION

Earth Fault Prot Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Earth Overcurrent Protection function. ANSI 50N/51N.

CB Fail & I< Disabled Enabled/Disabled

To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection functions. ANSI 50BF.

Input Labels Visible Visible/Invisible

Sets the Input Labels menu visible further on in the relay settings menu.

Output Labels Visible Visible/Invisible

Sets the Output Labels menu visible further on in the relay settings menu.

CT & VT Ratios Visible Visible/Invisible

Sets the Current & Voltage Transformer Ratios menu visible further on in the relay settings menu.

Recorder Control Visible Visible/Invisible

Sets the Record Control menu visible further on in the relay settings menu.

Disturb Recorder Visible Visible/Invisible

Sets the Disturbance Recorder menu visible further on in the relay settings menu.

Measure't Setup Visible Visible/Invisible

Sets the Measurement Setup menu visible further on in the relay settings menu.

Comms Settings Invisible Visible/Invisible

Sets the Communications Settings menu visible further on in the relay settings menu.

Commission Tests Visible Visible/Invisible

Sets the Commissioning Tests menu visible further on in the relay settings menu.

Setting Values Secondary Primary/Secondary

This affects all protection settings that are dependent upon CT and VT ratios.

Control Inputs Visible Visible/Invisible

Activates the Control Input status and operation menu further on in the relay setting menu.

Ctrl I/P Config Visible Visible/Invisible

Sets the Control Input Configuration menu visible further on in the relay setting menu.

Ctrl I/P Labels Visible Visible/Invisible

Sets the Control Input Labels menu visible further on in the relay setting menu.

Direct Access Enabled Enabled / Disabled

Defines what CB control direct access is allowed. Enabled implies control via menu, hotkeys etc.

Function Key Visible Invisible or Visible

Sets the Function Key menu visible further on in the relay setting menu.

LCD Contrast 11 0…31

Sets the LCD contrast.

The aim of the configuration column is to allow general configuration from a single point in the menu. Items that are disabled or made invisible do not appear in the main relay menu.

Page 94: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-10

MiCOM P741, P742, P743

ST

1.1.4 Default settings restore

To restore the default values to the settings in any protection settings group, set the ‘restore defaults’ cell to the relevant group number. Alternatively it is possible to set the ‘restore defaults’ cell to ‘all settings’ to restore the default values to all of the relay’s settings, not just the protection groups’ settings. The default settings will initially be placed in the scratchpad and will only be used by the relay after they have been confirmed. Note that restoring defaults to all settings includes the rear communication port settings, which may result in communication via the rear port being disrupted if the new (default) settings do not match those of the master station.

1.2 Protection settings

The protection settings include all the following items that become active once enabled in the configuration column of the relay menu database:

− Protection element settings.

− Scheme logic settings.

There are four groups of protection settings, with each group containing the same setting cells. One group of protection settings is selected as the active group, and is used by the protection elements. The settings for group 1 are shown. The settings are discussed in the same order in which they are displayed in the menu.

1.2.1 Central Unit P741

1.2.1.1 Differential Protection Configuration

Differential Elements 87BB

The differential element has independent settings for phase and earth (sensitive) faults, which are used for all zones and the check zone.

Setting Range Menu Text Default Setting

Min. Max. Step Size

DIFF BUSBAR PROT

Diff Check zone Phase Fault

Phase slope kCZ 30% 0% 90% 1%

Slope angle setting for the check zone biased differential element.

IDCZ>2 Current 1200 A 50 A 30.000 A 10 A

Setting that determines the minimum differential operating current for the check zone biased differential element

Diff Phase Fault

Phase slope k2 60% 20% 90% 1%

Slope angle setting for all discriminating zone biased differential elements

ID>2 Current 1000 A 50 A 30.000 A 10 A

Setting that determines the minimum differential operating current for all the discriminating zone biased differential elements

Phase slope k1 10% 0% 50% 1%

Slope angle setting for the phase circuitry fault monitoring characteristic.

ID>1 Current 100 A 10 A 500 A 10 A

Setting for the phase circuitry fault monitoring characteristic for the minimum pickup

ID>1 Alarm Timer 5.0s 0.0s 600.0s 0.1s

Setting for the operating time delay of the phase circuitry fault monitoring

Page 95: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-11

ST

1.2.1.2 Sensitive earth fault element

The sensitive earth fault element is included for high impedance earthed systems and has bias current control to guarantee stability under external faults or when there are significant errors in the measurement CTs. The element is usually disabled for effectively earthed systems with low impedance or solid earthing.

Setting Range Menu Text Default Setting

Min. Max. Step Size

Diff Earth Fault

Diff Earth Fault Disabled Enabled/Disabled

IBiasPh>Cur. 2000 A 50 A 30.000 A 10 A

Setting that determines the Earth fault element blocking characteristic

Diff Check zone Earth Fault

Earth Slope kNCZ 10% 0% 90% 1%

Slope angle setting for the check zone biased differential Earth element.

IDNCZ>2 Current 1200 A 10 A 30.000 A 10 A

Setting that determines the minimum differential operating current for the check zone biased differential Earth element

Diff Zone Earth Fault

Earth Slope kN2 10% 0% 90% 1%

Slope angle setting for all discriminating zone biased differential Earth elements

IDN>2 Current 1000 A 10 A 30.000 A 10 A

Setting that determines the minimum differential operating current for all the discriminating zone biased differential Earth elements

Phase slope kN1 10% 0% 50% 1%

Slope angle setting for the Neutral circuitry fault monitoring characteristic.

IDN>1 Current 100 A 10 A 500 A 10 A

Setting for the Neutral circuitry fault monitoring characteristic for the minimum pickup

IDN>1 Alarm Timer 5.0s 0.0s 600.0s 0.1s

Setting for the Neutral circuitry fault monitoring minimum pickup timer

Page 96: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-12

MiCOM P741, P742, P743

ST

1.2.2 Peripheral Units P742 or P743

1.2.2.1 Busbar Trip Confirmation (87BB) or Central Breaker Fail BackTrip Confirmation (50BF)

The peripheral units can be enabled to control the trip command issue by the central unit (87BB or 50BF) if a local fault threshold, either phase or earth (i.e. I>BB or IN>BB), is exceeded.

This criterion provides additional scheme stability. Should the command proceed, and a trip be issued to the circuit breaker this element can confirm the evolution of a circuit breaker failure condition. If the element is still operated after a set time delay a breaker failure condition must exist.

Setting Range Menu Text Default Setting

Min. Max. Step Size

BB Trip Confirm

I>BB Current Set 1.20*In 0.05*In 4.00*In 0.01*In

Setting for the minimum pickup phase fault element trip authorization

IN>BB Current 0.20*In 0.05*In 4.00*In 0.01*In

Setting for the minimum pickup Earth fault element trip authorization

Note: In is the CT nominal current.

1.2.2.2 Dead Zone configuration

Setting Range Menu Text Default Setting

Min. Max. Step Size

Dead Zone Prot

I>DZ Current Set 1.20*In 0.05*In 4.00*In 0.01*In

Setting for the tripping characteristic for the minimum pickup phase dead zone element

I>DZ Time Delay 1.00 s 0.00 s 100.00 s 0.01 s

Setting for the minimum pickup phase dead zone element timer

IN>DZ Current Set 1.20*In 0.05*In 4.00*In 0.01*In

Setting for the tripping characteristic for the minimum pickup neutral dead zone element

IN>DZ Time Delay 1.00 s 0.00 s 100.00 s 0.01 s

Setting for the minimum pickup neutral dead zone element timer

Page 97: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-13

ST

1.2.2.3 Non-directional Phase overcurrrent protection

The overcurrent protection included in the P742 or P743 relay provides two stages non-directional three-phase overcurrent protection with independent time delay characteristics. All overcurrent settings apply to all three phases but are independent for each of the four stages. The first stage of overcurrent protection has time-delayed characteristics which are selectable between inverse definite minimum time (IDMT), or definite time (DT). The second stage has definite time characteristics only.

Setting Range Menu Text Default Setting

Min. Max. Step Size

BB TRIP CONFIRM

BACKUP OVERCURRENT

I>1 Function Disabled Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse

Setting for the tripping characteristic for the first stage overcurrent element.

I>1 Current Set 3.00*In 0.10* In 32.00* In 0.01* In

Pick-up setting for first stage overcurrent element.

I>1 Time Delay 1.00s 0.00s 100.00s 0.01s

Setting for the time-delay for the definite time setting if selected for first stage element.

I>1 TMS 1.000 0.025 1.200 0.025

Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.

I>1 Time Dial 7.0 0.5 15.0 0.1

Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves.

I>1 Reset Char DT DT/Inverse

Setting to determine the type of reset/release characteristic of the IEEE/US curves.

I>1tReset 0.0 0.0 100.0 0.1

Setting that determines the reset/release time for definite time reset characteristic.

I>2 Function Disabled Disabled

Blocking 87BB

High Set I>2

Both

Setting to enable or disable the second stage overcurrent element.

I>2 Current Set 20.00* In 0.10* In 32.00* In 0.01* In

Pick-up setting for second stage overcurrent element.

I>2 Time Delay 1.00s 0.00s 10.00s 0.01s

Setting for the operating time-delay for second stage overcurrent element.

Page 98: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-14

MiCOM P741, P742, P743

ST

1.2.3 Non-Directional Earth Fault Overcurrent Protection and External Fault Detection by High-Set Overcurrent

The P742 and P743 relays include extra or backup non-directional earth fault protection. The earth fault element has two stages of protection. The earth fault element needs to be co-ordinated with any other protection elements on the system, in order to provide discriminative fault clearance. The inverse time characteristics available for the earth fault protection, are the same as those for the Overcurrent element.

Note: Ιn is the CT nominal current.

Setting Range Menu Text Default Setting

Min. Max. Step Size

OVERCURRENT

O/C EARTH FAULT

ΙN>1 Function Disabled Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse

Setting for the tripping characteristic for the first stage earth fault element.

ΙN>1 Current Set 0.30*Ιn 0.10*Ιn 32.00*Ιn 0.01*Ιn

Pick-up setting for the first stage earth fault element.

ΙN>1 Time Delay 1.00s 0.00s 100.00s 0.01s

Time-delay setting for the first stage definite time element.

ΙN>1 TMS 1.000 0.025 1.200 0.025

Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.

ΙN>1 Time Dial 7.0 0.5 15.0 0.1

Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves.

ΙN>1 Reset Char DT DT/Inverse

Setting to determine the type of reset/release characteristic of the IEEE/US curves.

ΙN>1tReset 0.0 0.0 100.0 0.1

Setting to determine the reset/release time for definite time reset characteristic.

ΙN>2 Function Disabled Disabled/Blocking 87BB/High Set I>2/Both

Setting to enable or disable the second stage definite time element. If the function is disabled, then all associated settings with the exception of this setting, are hidden.

ΙN>2 Current Set 20.00* Ιn 0.10*Ιn 32.00* Ιn 0.01* Ιn

Pick-up setting for the second stage earth fault element.

ΙN>2 Time Delay 1.00s 0.00s 10.00s 0.01s

Setting for the operating time delay for the second stage earth fault element.

Page 99: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-15

ST

1.2.4 Circuit breaker fail and undercurrent function

This function consists of two-stage circuit breaker fail functions that can be initiated by:

• Internal protection element initiation.

• External protection element initiation.

For current-based protection, the reset condition is based on undercurrent operation to determine that the CB has opened. For the non-current based protection, the reset criteria may be selected by means of a setting for determining a CB Failure condition.

It is common practice to use low set undercurrent elements in protection relays to indicate that circuit breaker poles have interrupted the fault or load current, as required.

Setting Range Menu Text Default Setting

Min. Max. Step Size

CB FAIL

Control by I< I<

52a

both

Setting which determines the elements that will reset the circuit breaker fail time protection function.

Both means that 52a and current criteria have to indicate open to reset the CB fail.

I< Current Set 0.05*In 0.05*In 4.00*In 0.01*In

Setting that determines the circuit breaker fail timer reset current for overcurrent based protection circuit breaker fail initiation.

I> Status Disabled Enabled/Disabled

I> Current Set 1.2*In 0.05*In 4.00*In 0.01*In

IN> Current Set 0.2*In 0.05*In 4.00*In 0.01*In

Internal trip Initiated by a Central Unit trip order

CB Fail Timer 1 0.05 s 0.00 s 10.00 s 0.01 s

Setting for the circuit breaker fail timer stage 1 for which the initiating condition must be valid.

CB Fail Timer 2 0.20 s 0.00 s 10.00 s 0.01 s

Setting to enable or disable the second stage of the circuit breaker function.

External trip Initiated by an external trip order or integrated overcurrent

CB Fail Timer 3 0.05 s 0.00 s 10.00 s 0.01 s

Setting for the circuit breaker fail timer stage 1 for which the initiating condition must be valid.

CB Fail Timer 4 0.20 s 0.00 s 10.00 s 0.01 s

Setting to enable or disable the second stage of the circuit breaker function.

Page 100: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-16

MiCOM P741, P742, P743

ST

1.2.5 Supervision CTS

The CT supervision feature operates on detection of derived zero sequence current.

Setting Range Menu Text Default Setting

Min. Max. Step Size

SUPERVISION GROUP 1

SUPERVISION ELEMENTS

ΙO Supervision Sub-heading

Error Factor KCE 0.40 0.01 1 0.01

Setting for the supervision characteristic for the slope

Alarm Delay TCE 5.0 s 0.0 s 10.0 s 0.1 s

Setting that determines the operating time-delay of the element upon detection of a current transformer supervision condition.

1.3 Control and support settings

The control and support settings are part of the main menu and are used to configure the relays global configuration. It includes submenu settings as below and is discussed in more detail below:

− Relay function configuration settings

− CT & VT ratio settings

− Reset LEDs

− Active protection setting group

− Password & language settings

− Circuit breaker control

− Communications settings

− Measurement settings

− Event & fault record settings

− User interface settings

− Commissioning settings

Page 101: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-17

ST

1.3.1 System data

1.3.1.1 Central Unit P741

This menu provides information for the device and general status of the P741 relay.

Setting Range Menu Text Default Setting

Min. Max. Step Size

Language English

The default language used by the device. Selectable as English, French, German, Russian, Spanish.

Password ****

Device default password.

Description MiCOM P741

16 character relay description. Can be edited.

Plant Reference MiCOM

Associated plant description and can be edited.

Model Number P741??????????K

Relay model number. This display cannot be altered.

Serial Number 6 digits + 1 letter

Relay model number. This display cannot be altered.

Frequency 50 Hz 10Hz

Relay set frequency. Settable between 50 and 60Hz

Comms. Level 2

Displays the conformance of the relay to the Courier Level 2 comms.

Relay Address 255 6 6 1

Fixed front and first rear port relay address.

Plant Status 0000000000000000

Displays the circuit breaker plant status for up to 8 circuit breakers. The P741 relay does not support any circuit breaker. Not used

Control Status 0000000000000000

Not used.

Active Group 1

Displays the active settings group.

Software Ref. 1

Displays the relay software version including protocol and relay model.

Opto I/P Status 00000000

Duplicate. Displays the status of opto inputs.

Relay O/P Status 00000000

Duplicate. Displays the status of output relays.

Alarm Status 1 00000000000000000000000000000000

32 bits field give status of first 32 alarms.

Page 102: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-18

MiCOM P741, P742, P743

ST

Alarm Status 2 00000000

Next 32 alarm status defined.

Alarm Status 3 00000000

Next 32 alarm status defined. Assigned specifically for platform alarms.

Access Level 00000000000000000000000000000000

Displays the current access level.

Level 0 - No password required - Read access to all settings, alarms, event records and fault records

Level 1 - Password 1 or 2 required - As level 0 plus: Control commands, e.g. circuit breaker open/close

Reset of fault and alarm conditions, Reset LEDs Clearing of event and fault records

Level 2 - Password 2 required - As level 1 plus: All other settings

Password Control 00000000000000000000000000000000

Sets the menu access level for the relay. This setting can only be changed when level 2 access is enabled.

Password Level 1 00000000000000000000000000000000

Allows user to change password level 1.

Password Level 2 2

Allows user to change password level 2.

1.3.1.2 Peripheral Unit P742

Setting Range Menu Text Default Setting

Min. Max. Step Size

Language English

The default language used by the device. Selectable as English, French, German, Russian, Spanish.

Password ****

Device default password.

Sys. Fn. Links 0 1

Setting to allow the fixed function trip LED to be self resetting.

Description MiCOM P742

16 character relay description. Can be edited.

Plant Reference MiCOM

Associated plant description and can be edited.

Model Number P742??????????J

Relay model number. This display cannot be altered.

Serial Number 6 digits + 1 letter

Relay model number. This display cannot be altered.

Frequency 50 Hz 10Hz

Relay set frequency. Settable between 50 and 60Hz

Page 103: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-19

ST

Comms. Level 2

Displays the conformance of the relay to the Courier Level 2 comms.

Relay Address 255 7 34 1

Sets the front and first rear port relay address from 7.

Plant Status 0000000000000000

Displays the circuit breaker plant status for up to 8 circuit breakers. The P74x relay supports only a single circuit breaker configuration.

Control Status 0000000000000000

Not used.

Active Group 1

Displays the active settings group.

CB Trip/Close No Operation No Operation/ Trip/Close

Supports trip and close commands if enabled in the Circuit Breaker Control menu.

Software Ref. 1

Displays the relay software version including protocol and relay model.

Opto I/P Status 0000000000000000

Duplicate. Displays the status of opto inputs.

Relay O/P Status 00000000

Duplicate. Displays the status of output relays.

Alarm Status 1 00000000000000000000000000000000

Duplicate of Alarm Status 1 above.

Alarm Status 2 0000000000000000

Next 32 alarm status defined.

Alarm Status 3 00000000

Next 32 alarm status defined. Assigned specifically for platform alarms.

Access Level 00000000000000000000000000000000

Displays the current access level.

Level 0 - No password required - Read access to all settings, alarms, event records and fault records

Level 1 - Password 1 or 2 required - As level 0 plus: Control commands, e.g. circuit breaker open/close

Reset of fault and alarm conditions, Reset LEDs Clearing of event and fault records

Level 2 - Password 2 required - As level 1 plus: All other settings

Password Control 00000000000000000000000000000000

Sets the menu access level for the relay. This setting can only be changed when level 2 access is enabled.

Password Level 1 00000000000000000000000000000000

Allows user to change password level 1.

Password Level 2 2

Allows user to change password level 2.

Page 104: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-20

MiCOM P741, P742, P743

ST

1.3.1.3 Peripheral Unit P743

Setting Range Menu Text Default Setting

Min. Max. Step Size

Language English

The default language used by the device. Selectable as English, French, German, Russian, Spanish.

Password ****

Device default password.

Sys. Fn. Links 0 1

Setting to allow the fixed function trip LED to be self resetting.

Description MiCOM P743

16 character relay description. Can be edited.

Plant Reference MiCOM

Associated plant description and can be edited.

Model Number P743??????????K

Relay model number. This display cannot be altered.

Serial Number 6 digits + 1 letter

Relay model number. This display cannot be altered.

Frequency 50 Hz 10Hz

Relay set frequency. Settable between 50 and 60Hz

Comms. Level 2

Displays the conformance of the relay to the Courier Level 2 comms.

Relay Address 255 7 34 1

Sets the front and first rear port relay address from 7.

Plant Status 0000000000000000

Displays the circuit breaker plant status for up to 8 circuit breakers. The P74x relay supports only a single circuit breaker configuration.

Control Status 0000000000000000

Not used.

Active Group 1

Displays the active settings group.

CB Trip/Close No Operation No Operation/ Trip/Close

Supports trip and close commands if enabled in the Circuit Breaker Control menu.

Software Ref. 1

Displays the relay software version including protocol and relay model.

Opto I/P Status 000000000000000000000000

Duplicate. Displays the status of opto inputs.

Relay O/P Status 0000000000000000

Duplicate. Displays the status of output relays.

Page 105: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-21

ST

Setting Range Menu Text Default Setting

Min. Max. Step Size

Alarm Status 1 00000000000000000000000000000000

Duplicate of Alarm Status 1 above.

Alarm Status 2 00000000000000000000000000000000

Next 32 alarm status defined.

Alarm Status 3 00000000000000000000000000000000

Next 32 alarm status defined. Assigned specifically for platform alarms.

Access Level 2

Displays the current access level.

Level 0 - No password required - Read access to all settings, alarms, event records and fault records

Level 1 - Password 1 or 2 required - As level 0 plus: Control commands, e.g. circuit breaker open/close

Reset of fault and alarm conditions, Reset LEDs Clearing of event and fault records

Level 2 - Password 2 required - As level 1 plus: All other settings

Password Control 2 0 2 1

Sets the menu access level for the relay. This setting can only be changed when level 2 access is enabled.

Password Level 1 ****

Allows user to change password level 1.

Password Level 2 ****

Allows user to change password level 2.

Page 106: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-22

MiCOM P741, P742, P743

ST

1.3.2 Circuit breaker control

The relay includes the following options for control of a single circuit breaker:

• Local tripping and closing, via the relay menu (or hotkeys)

• Local tripping and closing, via opto-isolated inputs or hotkeys (or function keys)

• Remote tripping and closing, using the relay communications

Setting Range Menu Text Default Setting

Min. Max. Step Size

CB CONTROL

Prot Trip Pulse 0.20s 0.05s 2.00s 0.01s

Defines the duration of the trip pulse.

Trip Latched Disabled Enabled, Disabled

Reset Trip Latch No Yes, No

Latch of the trip pulse.

CB control by Disabled Disabled, Local, Remote, Local + Remote, Opto, Opto + local, Opto + Remote, Opto + Remote + local

This Setting selects the type of circuit breaker control that be used in the logic

Man Close Pulse 0.50s 0.10s 10.00s 0.01s

Defines the duration of the close pulse.

Man Trip Pulse 0.50s 0.10s 5.00s 0.01s

Defines the duration of the trip pulse.

Man Close Delay 10.00s 0.01s 600.00s 0.01s

This defines the delay time before the close pulse is executed.

1.3.3 Date and time

Displays the date and time as well as the battery condition.

Setting Range Menu Text Default Setting

Min. Max. Step Size

Date/Time Data

Displays the relay’s current date and time.

IRIG-B Sync. Disabled Disabled or Enabled

Enable IRIG-B time synchronization.

IRIG-B Status Data Card not fitted/Card failed/ Signal healthy/No signal

Displays the status of IRIG-B.

Battery Status Data

Displays whether the battery is healthy or not.

Battery Alarm Enabled Disabled or Enabled

Setting that determines whether an unhealthy relay battery condition is alarmed or not.

Page 107: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-23

ST

1.3.4 CT ratios

Setting Range Menu Text Default Setting

Min. Max. Step Size

Phase CT Primary 1.000A 1A 30kA 1

Sets the phase Current Transformer input primary current rating.

Phase CT Sec’y 1.000A 1 5 4

Sets the phase Current Transformer input secondary current rating.

RBPh / RBN 1 0.5 10 0.1

Sets the ratio between the phase lead burden and the neutral lead burden.

Power Parameters

BRITISH STANDARD Knee voltage Vk

250/In V 100/In V 5000/In V 10/In V

Sets the Current Transformer knee point voltage when the British standard has been chosen.

IEC Rated Burden VA

25 VA 5 VA 100 VA 1 VA

Sets the Current Transformer power when the IEC standard has been chosen.

IEC Rated Burden Ohm (calculated value)

25 / In2 Ω 5 / In

2 Ω 100 / In2 Ω 1 / In

2 Ω

Calculated value from the Rated Burden set in VA

IEC Rated short-circuit factor Kscc

10 10 50 5

Sets the Current Transformer accuracy limit factor when the IEC standard has been chosen.

Secondary RCT 0.5 Ω 0.1 Ω 50.0 Ω 0.1 Ω

Sets the Current Transformer secondary resistance.

Eff Burden Ohm 25 / In2 Ω 1 / In

2 Ω 200 / In2 Ω 1 / In

2 Ω

Sets the lead burden when the British standard has been chosen.

Eff Burden VA (calculated value)

25.00 VA 0.10 VA 200.00 VA 0.01 VA

Calculated value from the Rated Burden set in Ohm

Page 108: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-24

MiCOM P741, P742, P743

ST

1.3.5 Record control

It is possible to disable the reporting of events from all interfaces that supports setting changes. The settings that control the various types of events are in the Record Control column. The effect of setting each to disabled is as follows:

Menu Text Default Setting Available Settings

Clear Event No No or Yes

Selecting “Yes” will cause the existing event log to be cleared and an event will be generated indicating that the events have been erased.

Clear Faults No No or Yes

Selecting “Yes” will cause the existing fault records to be erased from the relay.

Clear Maint. No No or Yes

Selecting “Yes” will cause the existing maintenance records to be erased from the relay.

Alarm Event Enabled Enabled or Disabled

Disabling this setting means that all the occurrences that produce an alarm will result in no event being generated.

Relay O/P Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any change in logic input state.

Opto Input Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any change in logic input state.

General Event Enabled Enabled or Disabled

Disabling this setting means that no General Events will be generated

Fault Rec. Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any fault that produces a fault record

Maint. Rec. Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any occurrence that produces a maintenance record.

Protection Event Enabled Enabled or Disabled

Disabling this setting means that any operation of protection elements will not be logged as an event.

DDB 31 - 0 11111111111111111111111111111111

Displays the status of DDB signals 0 – 31.

DDB 1022 - 992 11111111111111111111111111111111

Displays the status of DDB signals 992 – 1022 for the P743.

Page 109: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-25

ST

1.3.6 Measurements

1.3.6.1 Central Unit P741

Menu Text Default Settings Available settings

MEASUREMENT SETUP

Default Display Description Description / Plant Reference / Idiff CZ / Ibias CZ / Date and Time

This setting can be used to select the default display from a range of options, note that it is also possible to view the other default displays whilst at the default level using the and

keys. However once the 15 minute timeout elapses the default display will revert to that selected by this setting.

Local Values Primary Primary/Secondary

This setting controls whether measured values via the front panel user interface and the front courier port are displayed as primary or secondary quantities.

Remote Values Primary Primary/Secondary

This setting controls whether measured values via the rear communication port are displayed as primary or secondary quantities.

1.3.6.2 Peripheral Unit P742 and P743

Menu Text Default Settings Available settings

MEASUREMENT SETUP

Default Display Description Description / Plant Reference / IA-IB-IC/ Date and Time

This setting can be used to select the default display from a range of options, note that it is also possible to view the other default displays whilst at the default level using the and

keys. However once the 15 min timeout elapses the default display will revert to that selected by this setting.

Local Values Primary Primary/Secondary

This setting controls whether measured values via the front panel user interface and the front courier port are displayed as primary or secondary quantities.

Remote Values Primary Primary/Secondary

This setting controls whether measured values via the rear communication port are displayed as primary or secondary quantities.

1.3.7 Communications

The communications settings apply to the rear communications port. Further details are given in the SCADA communications section (P74x/EN SC).

These settings are available in the menu ‘Communications’ column and are displayed.

Page 110: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-26

MiCOM P741, P742, P743

ST

1.3.7.1 Communications settings for courier protocol

1.3.7.1.1 Central Unit P741

Setting Range Menu Text Default Setting

Min. Max. Step Size

COMMUNICATIONS

RP1 Protocol Courier

Indicates the communications protocol that will be used on the rear communications port.

RP1 Remote Address 6 6 6 0

This cell sets the unique address for the relay such that only one relay is accessed by master station software.

RP1 Inactivity Timer 15 min. 1 min. 30 min. 1 min.

This cell controls how long the relay will wait without receiving any messages on the rear port before it reverts to its default state, including resetting any password access that was enabled.

1.3.7.1.2 Peripheral Unit P742 and P743

Setting Range

Menu Text Default Setting Min. Max.

Step Size

COMMUNICATIONS

RP1 Protocol Courier

Indicates the communications protocol that will be used on the rear communications port.

RP1 Remote Address 255 7 34 1

This cell sets the unique address for the relay such that only one relay is accessed by master station software. There is a single address for front port and first rear port, a modification of this cell will affect the cell [SYSTEM DATA: Relay Address]

RP1 Inactivity Timer 15 min. 1 min. 30 min. 1 min.

This cell controls how long the relay will wait without receiving any messages on the rear port before it reverts to its default state, including resetting any password access that was enabled.

1.3.8 Commissioning tests

To help minimising the time required to test MiCOM relays the relay provides several test facilities under the ‘COMMISSION TESTS’ menu heading.

There are menu cells which allow the status of the opto-isolated inputs, output relay contacts, internal digital data bus (DDB) signals and user-programmable LEDs to be monitored. Additionally there are cells to test the operation of the output contacts, user-programmable LEDs.

1.3.8.1 Central Unit P741

Menu Text Default Setting Available Settings

COMMISSION TESTS

Opto I/P Status 00000000

This menu cell displays the status of the relay’s opto-isolated inputs as a binary string, a ‘1’ indicating an energized opto-isolated input and a ‘0’ a de-energized one

Relay O/P Status 00000000

Page 111: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-27

ST

Menu Text Default Setting Available Settings

This menu cell displays the status of the digital data bus (DDB) signals that result in energisation of the output relays as a binary string, a ‘1’ indicating an operated state and ‘0’ a non-operated state.

When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test Port Status 00000000

This menu cell displays the status of the eight digital data bus (DDB) signals that have been allocated in the ‘Monitor Bit’ cells.

Monitor Bit 1 Relay Label 01

0 to 1022 See PSL section for details of digital data bus signals

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Monitor Bit 8 Relay Label 08 0 to 1022

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Test Mode Disabled Disabled/Out Of Service

The Test Mode menu cell is used to allow secondary injection testing to be performed on a Peripheral Unit relay without operation of the connected zone. It also enables a facility to directly test the output contacts by applying menu controlled test signals. To select test mode the Test Mode menu cell should be set to ‘Out of Service’, which takes the relay out of service. It also causes an alarm condition to be recorded and the yellow ‘Out of Service’ LED to illuminate and an alarm message ‘Out of Service’ is given. The 87BB and 50BF protections are in service as long as the cells ‘87BB Monitoring’ and ‘87BB & 50BF disabl’ are equal to 0. Once testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to service.

Test Pattern 00000000 0 = Not Operated 1 = Operated

This cell is used to select the output relay contacts that will be tested when the ‘Contact Test’ cell is set to ‘Apply Test’.

Contact Test No Operation No Operation, Apply Test, Remove Test

When the ‘Apply Test’ command in this cell is issued the contacts set for operation (set to ‘1’) in the ‘Test Pattern’ cell change state. After the test has been applied the command text on the LCD will change to ‘No Operation’ and the contacts will remain in the Test State until reset issuing the ‘Remove Test’ command. The command text on the LCD will again revert to ‘No Operation’ after the ‘Remove Test’ command has been issued.

Note: When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test LEDs No Operation No Operation Apply Test

When the ‘Apply Test’ command in this cell is issued the eighteen user-programmable LEDs will illuminate for approximately 2 seconds before they extinguish and the command text on the LCD reverts to ‘No Operation’.

87BB Monitoring All bits set to 0 Each bit represents 1 zone

0 = In Service 1 = 87BB blocked

Page 112: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-28

MiCOM P741, P742, P743

ST

Menu Text Default Setting Available Settings

This cell is used to select the zone on which the 87BB protection will be disabled.

87BB & 50BF disabl All bits set to 0 Each bit represents 1 zone

0 = In Service 1 = 87BB and 50BF blocked

This cell is used to select the zone on which the 87BB AND 50BF protections will be disabled.

BB Trip Pattern 00000000 0 = In Service 1 = Out of Service

This cell is used to select the zone that will be tested when the ‘BB Trip Command’ cell is set to ‘Apply Test’.

BB Trip Command No Operation No Operation Apply Test Remove Test

When the ‘Apply Test’ command in this cell is issued the Central Unit sends the trip orders for the zone(s) set for operation (set to ‘1’) in the ‘BB Trip Pattern’ cell change state. After the test has been applied the command text on the LCD will change to ‘No Operation’ and the trip command will remain in the Test State until reset issuing the ‘Remove Test’ command. The command text on the LCD will again revert to ‘No Operation’ after the ‘Remove Test’ command has been issued.

Red LED Status 000000000000000000

This cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated with the Red LED input active when accessing the relay from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.

Green LED Status 000000000000000000

This cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated with the Green LED input active when accessing the relay from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.

DDB 31 - 0 11111111111111111111111111111111

Displays the status of DDB signals 0 – 31.

DDB 1022 - 992 11111111111111111111111111111111

Displays the status of DDB signals 992 – 1022.

1.3.9 Peripheral Unit P742

Menu Text Default Setting Available Settings

COMMISSION TESTS

Opto I/P Status 0000000000000000

This menu cell displays the status of the relay’s opto-isolated inputs as a binary string, a ‘1’ indicating an energized opto-isolated input and a ‘0’ a de-energized one

Relay O/P Status 00000000

This menu cell displays the status of the digital data bus (DDB) signals that result in energisation of the output relays as a binary string, a ‘1’ indicating an operated state and ‘0’ a non-operated state.

When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test Port Status 00000000

This menu cell displays the status of the eight digital data bus (DDB) signals that have been allocated in the ‘Monitor Bit’ cells.

Page 113: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-29

ST

Menu Text Default Setting Available Settings

Monitor Bit 1 Relay Label 01

0 to 1022 See PSL section for details of digital data bus signals

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Monitor Bit 8 Relay Label 08 0 to 1022

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Test Mode Disabled Disabled /

50BF Disabled / Overhaul

The Test Mode menu cell is used to ease the maintenance of an other feeder relay or to allow secondary injection testing to be performed on the relay without operation of the connected zone. It also enables a facility to directly test the output contacts by applying menu controlled test signals. To select a test mode the Test Mode menu cell should be set to ‘50BF Disabled’, which blocks the breaker failure function or to ‘Overhaul’ which allow the complete test of the relay. It also causes an alarm condition to be recorded and the yellow ‘Out of Service’ LED to illuminate and an alarm message ‘50BF Disabled’ or ‘Overhaul’ is given. Once testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to service.

Test Pattern 0000000000000000 0 = Not Operated 1 = Operated

This cell is used to select the output relay contacts that will be tested when the ‘Contact Test’ cell is set to ‘Apply Test’.

Contact Test No Operation No Operation, Apply Test, Remove Test

When the ‘Apply Test’ command in this cell is issued the contacts set for operation (set to ‘1’) in the ‘Test Pattern’ cell change state. After the test has been applied the command text on the LCD will change to ‘No Operation’ and the contacts will remain in the Test State until reset issuing the ‘Remove Test’ command. The command text on the LCD will again revert to ‘No Operation’ after the ‘Remove Test’ command has been issued.

Note: When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test LEDs No Operation No Operation Apply Test

When the ‘Apply Test’ command in this cell is issued the eighteen user-programmable LEDs will illuminate for approximately 2 seconds before they extinguish and the command text on the LCD reverts to ‘No Operation’.

Position Pattern 0000000 0 = To Force Opened 1 = To Force Closed

This cell is used to select the forced position of the isolators and the circuit breaker when the ‘Test Mode’ is ‘Overhaul’. The advised position is Opened for all the isolators and the circuit breaker, the position closed should be used only for the isolators connected to a transfer bus.

DDB 31 - 0 11111111111111111111111111111111

Displays the status of DDB signals 0 – 31.

DDB 1022 - 992 11111111111111111111111111111111

Displays the status of DDB signals 992 – 1022 for the P742.

Page 114: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-30

MiCOM P741, P742, P743

ST

1.3.10 Peripheral Unit P743

Menu Text Default Setting Available Settings

COMMISSION TESTS

Opto I/P Status 000000000000000000000000

This menu cell displays the status of the relay’s opto-isolated inputs as a binary string, a ‘1’ indicating an energized opto-isolated input and a ‘0’ a de-energized one

Relay O/P Status 0000000000000000

This menu cell displays the status of the digital data bus (DDB) signals that result in energisation of the output relays as a binary string, a ‘1’ indicating an operated state and ‘0’ a non-operated state.

When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test Port Status 00000000

This menu cell displays the status of the eight digital data bus (DDB) signals that have been allocated in the ‘Monitor Bit’ cells.

Monitor Bit 1 Relay Label 01

0 to 1022 See PSL section for details of digital data bus signals

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Monitor Bit 8 Relay Label 08 0 to 1022

The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or via the monitor/download port.

Test Mode Disabled Disabled /

50BF Disabled / Overhaul

The Test Mode menu cell is used to ease the maintenance of an other feeder relay or to allow secondary injection testing to be performed on the relay without operation of the connected zone. It also enables a facility to directly test the output contacts by applying menu controlled test signals. To select a test mode the Test Mode menu cell should be set to ‘50BF Disabled’, which blocks the breaker failure function or to ‘Overhaul’ which allow the complete test of the relay. It also causes an alarm condition to be recorded and the yellow ‘Out of Service’ LED to illuminate and an alarm message ‘50BF Disabled’ or ‘Overhaul’ is given. Once testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to service.

Test Pattern 0000000000000000 0 = Not Operated 1 = Operated

This cell is used to select the output relay contacts that will be tested when the ‘Contact Test’ cell is set to ‘Apply Test’.

Page 115: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-31

ST

Contact Test No Operation No Operation, Apply Test, Remove Test

When the ‘Apply Test’ command in this cell is issued the contacts set for operation (set to ‘1’) in the ‘Test Pattern’ cell change state. After the test has been applied the command text on the LCD will change to ‘No Operation’ and the contacts will remain in the Test State until reset issuing the ‘Remove Test’ command. The command text on the LCD will again revert to ‘No Operation’ after the ‘Remove Test’ command has been issued.

Note: When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.

Test LEDs No Operation No Operation Apply Test

When the ‘Apply Test’ command in this cell is issued the eighteen user-programmable LEDs will illuminate for approximately 2 seconds before they extinguish and the command text on the LCD reverts to ‘No Operation’.

Position Pattern 0000000 0 = To Force Opened 1 = To Force Closed

This cell is used to select the forced position of the isolators and the circuit breaker when the ‘Test Mode’ is ‘Overhaul’. The advised position is Opened for all the isolators and the circuit breaker, the position closed should be used only for the isolators connected to a transfer bus.

Red LED Status 000000000000000000

This cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated with the Red LED input active when accessing the relay from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.

Green LED Status 000000000000000000

This cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated with the Green LED input active when accessing the relay from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.

DDB 31 - 0 11111111111111111111111111111111

Displays the status of DDB signals 0 – 31.

DDB 1022 - 992 11111111111111111111111111111111

Displays the status of DDB signals 992 – 1022.

Page 116: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-32

MiCOM P741, P742, P743

ST

1.3.11 Opto configuration

1.3.11.1 Central Unit P741

Setting Range Menu Text Default Setting

Min. Max. Step Size

OPTO CONFIG.

Global Nominal V 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V, Custom

Sets the nominal battery voltage for all opto inputs by selecting one of the five standard ratings in the Global Nominal V settings. If Custom is selected then each opto input can individually be set to a nominal voltage value.

Opto Input 1 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

Opto Input 2 - 8 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

1.3.11.2 Peripheral Unit P742

Setting Range Menu Text Default Setting

Min. Max. Step Size

OPTO CONFIG.

Global Nominal V 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V, Custom

Sets the nominal battery voltage for all opto inputs by selecting one of the five standard ratings in the Global Nominal V settings. If Custom is selected then each opto input can individually be set to a nominal voltage value.

Opto Input 1 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

Opto Input 2 - 16 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

Page 117: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-33

ST

1.3.11.3 Peripheral Unit P743

Setting Range Menu Text Default Setting

Min. Max. Step Size

OPTO CONFIG.

Global Nominal V 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V, Custom

Sets the nominal battery voltage for all opto inputs by selecting one of the five standard ratings in the Global Nominal V settings. If Custom is selected then each opto input can individually be set to a nominal voltage value.

Opto Input 1 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

Opto Input 2 - 24 24/27V 24/27V, 30/34V, 48/54V, 110/125V, 220/250V

Each opto input can individually be set to a nominal voltage value if custom is selected for the global setting.

1.3.12 Control input configuration

The control inputs function as software switches that can be set or reset either locally or remotely. These inputs can be used to trigger any function that they are connected to as part of the PSL.

Menu Text Default Setting Setting Range Step Size

CTRL I/P CONFIG.

Hotkey Enabled 11111111111111111111111111111111

Setting to allow the control inputs to be individually assigned to the “Hotkey” menu by setting ‘1’ in the appropriate bit in the “Hotkey Enabled” cell. The hotkey menu allows the control inputs to be set, reset or pulsed without the need to enter the “CONTROL INPUTS” column

Control Input 1 Latched Latched, Pulsed

Configures the control inputs as either ‘latched’ or ‘pulsed’. A latched control input will remain in the set state until a reset command is given, either by the menu or the serial communications. A pulsed control input, however, will remain energized for 10ms after the set command is given and will then reset automatically (i.e. no reset command required) .

Ctrl Command 1 Set/Reset Set/Reset, In/Out, Enabled/Disabled, On/Off

Allows the SET / RESET text, displayed in the hotkey menu, to be changed to something more suitable for the application of an individual control input, such as “ON / OFF”, “IN / OUT” etc.

Control Input 2 to 32 Latched Latched, Pulsed

Configures the control inputs as either ‘latched’ or ‘pulsed’.

Ctrl Command 2 to 32 Set/Reset Set/Reset, In/Out, Enabled/Disabled,

On/Off

Allows the SET / RESET text, displayed in the hotkey menu, to be changed to something more suitable for the application of an individual control input, such as “ON / OFF”, “IN / OUT” etc.

Page 118: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-34

MiCOM P741, P742, P743

ST

1.3.13 Function keys

Available in the Central Unit P741 and the Peripheral Unit P743

Setting Range Menu Text Default Setting

Min. Max. Step Size

FUNCTION KEYS

Fn. Key Status 0000000000

Displays the status of each function key.

Fn. Key 1 Status Unlocked Disabled, Locked, Unlock

Setting to activate function key. The ‘Lock’ setting allows a function key output that is set to toggle mode to be locked in its current active state.

Fn. Key 1 Mode Toggled Toggled, Normal

Sets the function key in toggle or normal mode. In ‘Toggle’ mode, a single key press will set/latch the function key output as ‘high’ or ‘low’ in programmable scheme logic. This feature can be used to enable/disable relay functions. In the ‘Normal’ mode the function key output will remain ‘high’ as long as key is pressed.

Fn. Key 1 Label Function Key 1

Allows the text of the function key to be changed to something more suitable for the application.

Fn. Key 2 to 10 Status Unlocked Disabled, Locked, Unlock

Setting to activate function key. The ‘Lock’ setting allows a function key output that is set to toggle mode to be locked in its current active position.

Fn. Key 2 to 10 Mode Toggled Toggled, Normal

Sets the function key in toggle or normal mode. In ‘Toggle’ mode, a single key press will set/latch the function key output as ‘high’ or ‘low’ in programmable scheme logic. This feature can be used to enable/disable relay functions. In the ‘Normal’ mode the function key output will remain ‘high’ as long as key is pressed.

Fn. Key 2 to 10 Label Function Key 2 to 10

Allows the text of the function key to be changed to something more suitable for the application.

Page 119: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-35

ST

1.3.14 Control input labels

Menu Text Default Setting Setting Range Step Size

CTRL I/P LABELS

Control Input 1 Control Input 1 16 Character Text

Setting to change the text associated with each individual control input. This text will be displayed when a control input is accessed by the hotkey menu, or it can be displayed in the programmable scheme logic.

Control Input 2 to 32 Control Input 2 to 32 16 Character Text

Setting to change the text associated with each individual control input. This text will be displayed when a control input is accessed by the hotkey menu, or it can be displayed in the programmable scheme logic.

1.4 Disturbance recorder settings

The disturbance recorder settings include the record duration and trigger position, selection of analog and digital signals to record, and the signal sources that trigger the recording.

1.4.1 Central Unit P741

Setting Range Menu Text Default Setting

Min. Max. Step Size

DISTURB. RECORDER

Duration 1.2 s 1.2 s 1.2 s 0.0 s

This sets the overall recording time.

Trigger Position 33.3% 0.0% 100.0% 33.3%

This sets the trigger point as a percentage of the duration. For example, the default settings show that the overall recording time is set to 1.2s with the trigger point being at 33.3% of this, giving 0.4 s pre-fault and 0.8 s post fault recording times.

Trigger Mode Single Single

Because set to single mode, if a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger.

Analog. Channel 1 IA diff Non settable

The Phase A differential calculated current is assigned to this channel.

Analog. Channel 2 IB diff As above

The Phase B differential calculated current is assigned to this channel.

Analog. Channel 3 IC diff As above

The Phase C differential calculated current is assigned to this channel.

Analog. Channel 4 IN diff As above

The Neutral differential calculated current is assigned to this channel.

Analog. Channel 5 IA bias As above

The Phase A bias calculated current is assigned to this channel.

Analog. Channel 6 IB bias As above

The Phase B bias calculated current is assigned to this channel.

Analog. Channel 7 IC bias As above

The Phase C bias calculated current is assigned to this channel.

Page 120: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-36

MiCOM P741, P742, P743

ST

Setting Range Menu Text Default Setting

Min. Max. Step Size

Analog. Channel 8 IN bias As above

The Neutral bias calculated current is assigned to this channel.

Digital Inputs 1 Circt Flt Lck z1 Any O/P Contacts or Any Opto Inputs or Internal Digital Signals

The Circuitry fault blocks zone 1 digital channel is assigned to this channel.

Digital Inputs 2 Circt Flt Lck z2 As above

The Circuitry fault blocks zone 2 digital channel is assigned to this channel.

Digital Inputs 3 87BB Blocked As above

The digital 87BB Blocked channel is assigned to this channel.

Digital Inputs 4 Ext Start DR As above

The External start of the disturbance recorder digital channel is assigned to this channel.

Digital Inputs 5 Earth Fault As above

The Earth fault digital channel is assigned to this channel.

Digital Inputs 6 Fault Check zone As above

The Fault Check zone digital channel is assigned to this channel.

Digital Inputs 7 Fault phase A As above

The Fault phase A digital channel is assigned to this channel.

Digital Inputs 8 Fault phase B As above

The Fault phase B digital channel is assigned to this channel.

Digital Inputs 9 Fault phase C As above

The Fault phase C digital channel is assigned to this channel.

Digital Inputs 10 Flt 87BB zone 1 As above

The Fault 87BB zone 1 digital channel is assigned to this channel.

Digital Inputs 11 Flt 87BB zone 2 As above

The Fault 87BB zone 2 digital channel is assigned to this channel.

Digital Inputs 12 Manual Start DR As above

The Manual start of the disturbance recorder digital channel is assigned to this channel.

Digital Inputs 13 Topo/Set Changed As above

The Topology or setting changed digital channel is assigned to this channel.

Digital Inputs 14 Trip Manual zone As above

The Manual trip of the zone digital channel is assigned to this channel.

Digital Inputs 15 Trip 50BF zone 1 As above

The Trip 50BF zone 1 digital channel is assigned to this channel.

Digital Inputs 16 Trip 50BF zone 2 As above

The Trip 50BF zone 2 digital channel is assigned to this channel.

Digital Inputs 17 Trip 87BB zone 1 As above

The Trip 87BB zone 1 digital channel is assigned to this channel.

Digital Inputs 18 Trip 87BB zone 2 As above

The Trip 87BB zone 2 digital channel is assigned to this channel.

Page 121: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-37

ST

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 19 PU Error Lck z1 As above

The PU error blocks zone 1 digital channel is assigned to this channel.

Digital Inputs 20 PU Error Lck z2 As above

The PU error blocks zone 2 digital channel is assigned to this channel.

Digital Inputs 21 to 32 Unused As above

The digital channels may be mapped to any of the opto isolated inputs or output contacts, in addition to a number of internal relay digital signals, such as protection starts, LEDs etc.

Manual Trigger No Yes or No

Command to trigger the disturbance recorder. The differential and bias currents recorded depend of the following settings Zone to record.

Zone to record Zone 1 Zone 1 to zone 8

Any one of the 8 zones can be recorded upon a manual triggering. If 2 or more zones are selected, the check zone will be recorded

1.4.2 Peripheral Unit P742 or P743

Setting Range

Menu Text Default Setting Min. Max.

Step Size

DISTURB. RECORDER

Duration 1.2 s 1.2 s 10.5 s 0.01 s

This sets the overall recording time.

Trigger Position 33.3% 0.0% 100.0% 0.1%

This sets the trigger point as a percentage of the duration. For example, the default settings show that the overall recording time is set to 1.2s with the trigger point being at 33.3% of this, giving 0.4 s pre-fault and 0.8 s post fault recording times.

Trigger Mode Extended Single or Extended

If set to single mode, if a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger. However, if this has been set to "Extended", the post trigger timer will be reset to zero, thereby extending the recording time.

Analog. Channel 1 IA Non settable

The Phase A analogue current input is assigned to this channel.

Analog. Channel 2 IB As above

The Phase B analogue current input is assigned to this channel.

Analog. Channel 3 IC As above

The Phase C analogue current input is assigned to this channel.

Analog. Channel 4 IN As above

The Neutral analogue current input is assigned to this channel.

Digital Inputs 1 Field Volt Fail Any O/P Contacts or Any Opto Inputs or Internal Digital Signals

The Mains field voltage has failed digital channel is assigned to this channel.

Input 1 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Page 122: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-38

MiCOM P741, P742, P743

ST

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 2 Any Trip As above

The Any Trip digital channel is assigned to this channel.

Input 2 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 3 CB Closed As above

The CB Closed digital channel is assigned to this channel.

Input 3 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 4 CB Fail Alarm As above

The CB Fail Alarm digital channel is assigned to this channel.

Input 4 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 5 CB not available As above

The CB not available digital channel is assigned to this channel.

Input 5 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 6 CBF Int Backtrip As above

The CB Failure Internal Backtrip order digital channel is assigned to this channel.

Input 6 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 7 CBF Ext Backtrip As above

The CB Failure External Backtrip order digital channel is assigned to this channel.

Input 7 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 8 Dead Zone Fault As above

The Dead Zone Fault digital channel is assigned to this channel.

Input 8 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 9 Ext. CB Fail As above

The External CB Fail digital channel is assigned to this channel.

Input 9 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 10 Ext. 3 ph Trip As above

The Ext. 3 phase Trip digital channel is assigned to this channel.

Input 10 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 11 Internal Trip As above

The Internal Trip digital channel is assigned to this channel.

Page 123: P74x_EN_M_H54

Settings P74x/EN ST/H54 MiCOM P741, P742, P743

(ST) 4-39

ST

Setting Range

Menu Text Default Setting Min. Max.

Step Size

Input 11 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 12 Q1 Closed As above

The Isolator 1 closed digital channel is assigned to this channel.

Input 12 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 13 Q2 Closed As above

The Isolator 2 closed digital channel is assigned to this channel.

Input 13 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 14 Q3 Closed As above

The Isolator 3 closed digital channel is assigned to this channel.

Input 14 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 15 Man. Trip zone As above

The Manual Trip of the zone digital channel is assigned to this channel.

Input 15 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 16 Relay Label 01 As above

The Relay Label 01 digital channel is assigned to this channel.

Input 16 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 17 Relay Label 02 As above

The Relay Label 02 digital channel is assigned to this channel.

Input 17 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 18 Relay Label 03 As above

The Relay Label 03 digital channel is assigned to this channel.

Input 18 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 19 Saturation ph A As above

The Saturation phase A digital channel is assigned to this channel.

Input 19 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 20 Saturation ph B As above

The Saturation phase B digital channel is assigned to this channel.

Input 20 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Page 124: P74x_EN_M_H54

P74x/EN ST/H54 Settings

(ST) 4-40

MiCOM P741, P742, P743

ST

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 21 Saturation ph C As above

The Saturation phase C digital channel is assigned to this channel.

Input 21 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 22 Trip 50BF (CU) As above

The Trip 50BF from the CU digital channel is assigned to this channel.

Input 22 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 23 Trip 87BB As above

The Trip 87BB digital channel is assigned to this channel.

Input 23 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 24 to 32 Unused As above

The digital channels may be mapped to any of the opto isolated inputs or output contacts, in addition to a number of internal relay digital signals, such as protection starts, LEDs etc.

Page 125: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

OP

OPERATION

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 126: P74x_EN_M_H54

P74x/EN OP/H54 Operation

MiCOM P741, P742, P743

Page 127: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-1

OP

CONTENTS

1. OPERATION OF INDIVIDUAL PROTECTION FUNCTIONS 3

1.1 Busbar Biased Current Differential Protection 3 1.1.1 Operating principle 3 1.1.2 Application of Kirchoffs law 3 1.2 Central Unit 5 1.2.1 Bias Characteristic and Differential current setting 5 1.2.2 Scheme supervision by "check zone” element 5 1.2.3 Scheme Earth characteristic element 6 1.2.4 Threshold coherency. 7 1.2.5 Signal Quality 8 1.2.6 Tripping Criteria 8 1.2.7 Current Circuit Supervision 9 1.3 Peripheral Unit 9 1.3.1 Dead Zone protection (DZ) 9 1.3.2 Stub protection 9 1.3.3 Circuit Breaker Fail (CBF) 9 1.4 Three Phase Overcurrent Protection 19 1.5 Earth Fault Protection 20 1.5.1 EF time delay characteristics 20 1.5.2 External Fault Detection by High-Set Overcurrent or Earth Fault Element 20 1.5.3 Supervision 20

1.5.4 Zero Sequence Current (ΙO) Supervision. 20

2. CURRENT TRANSFORMERS 22

2.1 CT Saturation detection 22

3. ISOLATOR AND CIRCUIT BREAKER FUNCTION 26

3.1 Isolator State Monitoring Features 26 3.2 Circuit Breaker State Monitoring Features 26 3.3 Circuit Breaker Control 28

4. OPERATION OF NON PROTECTION FUNCTIONS 29

4.1 Programmable scheme logic 29 4.1.1 Level settings 29 4.1.2 Accuracy 29

5. COMMUNICATIONS BETWEEN PU AND CU 30

5.1 Communications link 30

Page 128: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-2

MiCOM P741, P742, P743

OP

5.2 Direct optical fibre link, 850nm multi-mode fibre 30 5.3 Optical budgets 31 5.3.1 Main operating features 31 5.4 Trip LED logic 31 5.5 Function keys 32 5.5.1 CB control using hotkeys 32 5.5.2 CB control using function keys 33 5.6 Setting groups selection 34 5.7 Control inputs 34

FIGURES

FIGURE 1: DIFFERENTIAL BUSBAR PROTECTION PRINCIPLE 3 FIGURE 2: P74x SCHEME CHARACTERISTIC 5 FIGURE 3: SENSITIVE EARTH FAULT CHARACTERISTIC 6 FIGURE 4: SENSITIVE EARTH FAULT BLOCKING CHARACTERISTIC 7 FIGURE 5: CB FAIL ELEMENT LOGIC – PRINCIPLE OF RESET TIME CONTROL 11 FIGURE 6: CB ELEMENT LOGIC 12 FIGURE 7: CB FAIL LOGIC 14 FIGURE 8: CB FAIL LOGIC (DDB INPUTS & OUTPUTS) 15 FIGURE 9: CB FAIL ELEMENT LOGIC – INTERNALLY INITIATED 15 FIGURE 10: CIRCUIT BREAKER FAILURE LOGIC 16 FIGURE 11: EXAMPLES 17 FIGURE 12: CB FAIL ELEMENT LOGIC – EXTERNALLY INITIATED 17 FIGURE 13: CURRENT VARIATION 22 FIGURE 14: CURRENT VARIATION CRITERIA 22 FIGURE 15: DETERMINATION OF SIGNAL QUALITY IN PERIPHERAL UNIT 23 FIGURE 16: DETERMINATION OF SIGNAL QUALITY IN THE PERIPHERAL UNIT 23 FIGURE 17: CT SATURATION RESET 24 FIGURE 18: CT SATURATION 24 FIGURE 19: DETERMINATION OF SIGNAL QUALITY IN THE PERIPHERAL UNIT 25 FIGURE 20: CT LOCATION 25 FIGURE 21: REMOTE CONTROL OF CIRCUIT BREAKER 28 FIGURE 22: MODULE INTERCONNECTION 30 FIGURE 23: TRIP LED LOGIC DIAGRAM 31 FIGURE 24: CB CONTROL HOTKEY MENU 33 FIGURE 25: CB CONTROL VIA FUNCTION KEYS DEFAULT PSL 33

Page 129: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-3

OP

1. OPERATION OF INDIVIDUAL PROTECTION FUNCTIONS The following sections detail the individual protection functions.

Note however that not all the protection functions listed below are applicable to every relay.

1.1 Busbar Biased Current Differential Protection

The primary protection element of the P74x scheme is phase segregated biased current differential protection. The technique used is purely numerical and uses nodal analysis throughout the scheme, on a per zone and per scheme basis. The analysis is carried out in the central unit therefore communication between the central unit and all peripheral units is essential. This is achieved via a direct optical connection utilising a 2.5 Mbits/sec data rate.

1.1.1 Operating principle

The basic operating principle of the differential protection is based on the application of Kirchhoff’s law. This compares the amount of current entering and leaving the protected zone and the check zone. Under normal operation, the amount of current flowing into the area and the check zone concerned is equal in to the amount of the current flowing out of the area. Therefore the currents cancel out. In contrast, when a fault occurs the differential current that arises is equal to the derived fault current.

xIi1

S1

xIi2

S2

xIi3

S3

xIo1

xIo2

xIo3

Io4x

xSΣIi ΣIo

xImport Export

Substation Simplified Scheme

Ii = | ΣIin |

Io = | ΣIon|

Ibias = Ii + Io

Idiff = Ii - Io

P3766ENa

FIGURE 1: DIFFERENTIAL BUSBAR PROTECTION PRINCIPLE

1.1.2 Application of Kirchoffs law

Several methods of summation can be used for a differential protection scheme:

• Vector sum

• Instantaneous sum

The algorithms applied in MiCOM P74x use the instantaneous sum method (on samples). This method has the advantage of cancelling the harmonic and DC components of external origin in the calculation and in particular under transformer inrush conditions.

The other advantage of using an instantaneous sum lies in the speed of decision, which in turn is dictated by the sampling frequency.

Differential currents may also be generated under external fault conditions due to CT error. To provide stability for through fault conditions the relay adopts a biasing technique, which

Page 130: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-4

MiCOM P741, P742, P743

OP

effectively raises the setting of the relay in proportion to the through fault current thereby preventing relay maloperation.

The bias current is the scalar sum of the currents in the protected zone and for the check zone. Each of these calculations is done on a per phase basis for each node and then summated.

1.1.2.1 Bias Characteristic and Differential current

The operation of the busbar differential protection is based on the application of an algorithm having a biased characteristic, (Figure 2) in which a comparison is made between the differential current and a bias or restraining current. A trip is only permitted if this differential current exceeds the set slope of the bias characteristic. This characteristic is intended to guarantee the stability of protection during external faults where the scheme has current transformers with differing characteristics, likely to provide differing performance.

The algorithm operands are as follows:

Differential Current

idiff(t) = Σ i

Bias or Restraining current

ibias(t) = Σ i

Slope of the bias characteristic

kx

Tripping permitted by bias element for:

idiffx(t) > kx x ibias(t)

The main differential current element of MiCOM P74x will only be able to operate if the differential current reaches a threshold IDx>2. In general, this setting will be adjusted above the normal full load current.

1.1.2.2 Scheme supervision by "check zone” element

The use of a "check zone" element is based on the principle that in the event of a fault on one of the substation busbars, the differential current measured in the faulty zone will be equal to that measured in the entire scheme.

One of the most frequent causes of maloperation of differential busbar protection schemes is an error in the actual position of an isolator or CB in the substation to that replicated in the scheme (auxiliary contacts discrepancy). This would produce a differential current in one or more current nodes. However, if an element monitors only the currents "entering" and "leaving" the substation, the resultant will remain negligible in the absence of a fault, and the error will lie with the zone’s assumption of the plant position at this particular point in time.

Page 131: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-5

OP

1.2 Central Unit

1.2.1 Bias Characteristic and Differential current setting

Figure 2 shows the characteristics of the P74x scheme phase differential element.

FIGURE 2: P74x SCHEME CHARACTERISTIC

The Phase characteristic is determined from the following protection settings:

• Area above the ID>2 High-set zone differential current threshold setting and the set slope of the bias characteristic (k2 × Ibias) (k2 is the percentage bias setting (“slope”) for the zone)

Note: The origin of the bias characteristic slope is 0.

When an external fault condition causes CT saturation, a differential current is apparent and is equal to the current of the saturated CT. The measured differential current may be determined as an internal fault and initiate an unwanted trip of the bus bar. In order to avoid a risk of tripping under these circumstances, MiCOM P74x uses an ultra fast innovative algorithm based on the prediction of the next samples and the calculation of the image of the flux of the HV CT core. This signal-processing algorithm makes it possible to block a trip sample within a window of 1,7 ms. A timer ‘Block Duration’ of 150 ms is used to block the differential element in case of CT saturation detection.

1.2.2 Scheme supervision by "check zone” element

For security, the P74x scheme will only trip a particular busbar zone if that zone differential element AND the check zone element are in agreement to trip.

The principal advantage of this element is total insensitivity to topological discrepancies. Under such circumstances the "check zone" element will see two currents with equal amplitude but of opposite sign in adjacent zones.

The Check Zone characteristic is determined from the following protection settings:

• Area above the IDCZ>2 High-set check zone differential current threshold setting and the set slope of the bias characteristic (kCZ × Ibias) (kCZ is the percentage bias setting (“slope”) for the Check Zone)

Note: The origin of the bias characteristic slope is 0.

Page 132: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-6

MiCOM P741, P742, P743

OP

The check zone is the sum of all the current nodes entering and leaving the substation (feeders).

Scheme differential current = sum of all differential current feeder nodes:

idiff(t) CZ = Σ idiff

The Check Zone will operate as the Zone element.

1.2.3 Scheme Earth characteristic element

The Earth characteristic is determined from the following protection settings:

IDN>2 High-set zone differential current threshold setting which crosses the set slope of the bias characteristic (k × Ibias)

IDNCZ>2 High-set check zone differential current threshold setting which crosses the set slope of the bias characteristic (kCZ × Ibias)

KN2 Percentage bias setting (“slope”) for the zone

kNCZ Percentage bias setting (“slope”) for the check zone

The current control and blocking matrix is shown in figure 3

FIGURE 3: SENSITIVE EARTH FAULT CHARACTERISTIC

This element is automatically enabled/disabled via the load (flowing) current. The point at which the sensitive earth fault protection is enabled/disabled (IbiasPh>Cur.) is settable in the range. This threshold is usually set to be equal to the minimum phase to phase short circuit current.

Under earth fault conditions the risk of CT saturation is minimal and therefore the slope of the characteristic can be set low, however, should the fault evolve to a phase fault, it is important that the normal characteristic be restored.

Page 133: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-7

OP

FIGURE 4: SENSITIVE EARTH FAULT BLOCKING CHARACTERISTIC

For an external phase fault the SDEF protection will be disabled by the blocking command as long as the 'IbiasPh>Cur.' threshold remains exceeded.

It can be seen that for an internal phase to phase fault the bias current will be sufficient to enable the SDEF blocking order. The SDEF protection is then blocked and no trip issued from this element irrespective of SDEF setting thresholds being exceeded. As the main phase differential protection is always active, it is able to react to the fault and issue a trip command accordingly.

For an external phase to phase fault the SDEF will be disabled via the blocking order.

The sensitive differential earth fault protection is delayed by 20ms to prevent any maloperation during CT saturation condition.

Important note: SDEF should only be used when all the CTs are of the same standard

1.2.4 Threshold coherency.

The measuring elements have several level detectors for differential current. Upon starting, the protection reacts to any setting inconsistency in the detection of these levels' specific order.

The differential protection is blocked until the thresholds [ID>1and ID>2] and [IDN>1and IDN>2] are set in the correct sequence.

The thresholds must be set so that:

(ID>1) (ID>2) , (ID>1) (IDCZ>2) and (IDN>1) (IDN>2), (IDN>1) (IDNCZ>2)

Page 134: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-8

MiCOM P741, P742, P743

OP

Table below shows operation depending on the thresholds' status.

ID>1 k1.Ibias ID>2 Status Operation

0 0 0 Normal No operation

1 0 0 Normal No operation

0 1 0 Normal No operation

1 0 1 External fault or circuitry fault

External fault with CT saturation or block circuitry fault alarm after tCF

1 1 0 Circuitry fault Block and circuitry fault alarm after tCF

1 1 1 Internal fault Trip

TABLE 1: OPERATION CONDITIONS

1.2.5 Signal Quality

An additional check is carried out to confirm that the signals used to determine the previous criteria are satisfactory.

This includes checking for CT saturation conditions (information from peripheral unit, refer to Section 2.1), that no plant discrepancies exist (via check zone as discussed earlier), and that a change (increase or loss) in current flow has been detected by at least two peripheral units (∆I detection). The latter condition is used, as internal or external faults will cause a change in levels in at least two circuits whereas, a CT fail only affect a single circuit’s level (faulty CT).

Note: This condition is used only when there is no dead bus condition.

When a trip is issued for a bus zone by the central unit a signal is sent to all peripheral units associated (or not) with the faulted bus zone. The peripheral units associated with the faulted zone can carry out a further local confirmation via local Overcurrent protection, I>BB or IN>BB, before allowing a trip to take place.

1.2.6 Tripping Criteria

Before a trip signal is issued 4 trip criterions at the top level, i.e. the Central Unit, and 1 (optional) at the local level, i.e. the Peripheral Units, must be met.

These criterions are:

Top level (Central Unit)

Instantaneous criteria:

• Bias characteristic ( Idiff > (ID>2)) and Differential current setting are exceeded (Idiff> k2 Ibias) for the zone for 2 consecutive samples

• Bias characteristic ( Idiff > (IDCZ>2)) and Differential current setting are exceeded (Idiff> kCZ Ibias) for the check zone for 2 consecutive samples

• No CT saturation

• Signal quality (CT supervision, , AD converter, etc…)

Delayed criteria:

• Bias characteristic ( Idiff > (ID>2)) and Differential current setting are exceeded (Idiff> k2 Ibias) for the zone for at least 1 sample

• Bias characteristic ( Idiff > (IDCZ>2)) and Differential current setting are exceeded (Idiff> kCZ Ibias) for the check zone for at least 1 sample

• Bias characteristic ( Idiff > (ID>2)) and Differential current setting are not exceeded (Idiff> k2 Ibias) for the zone for at least 1 sample in the 4 following samples

Page 135: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-9

OP

• Bias characteristic ( Idiff > (IDCZ>2)) and Differential current setting are not exceeded (Idiff> kCZ Ibias) for the check zone for at least 1 sample in the 4 following samples

• Bias characteristic ( Idiff > (ID>2)) and Differential current setting are exceeded (Idiff> k2 Ibias) for the zone for all the 7 following samples

• Bias characteristic ( Idiff > (IDCZ>2)) and Differential current setting are exceeded (Idiff> kCZ Ibias) for the check zone for all the 7 following samples

• Signal quality (CT supervision, , AD converter, etc…)

Local Level (Peripheral Unit)

• Local confirmation by an instantaneous Overcurrent element (enabled/disabled) (I>BB or IN>BB)

1.2.7 Current Circuit Supervision

During normal operation the differential current in the scheme should be zero or negligible. Any anomaly is detected via a given threshold ID>1.

A biased differential element is used to supervise the current circuit. A differential current will result if the secondary circuit of a CT becomes open circuited, short circuited; the amplitude of this current is proportional to the load current flowing in the circuit monitored by the faulty current circuit.

The setting is chosen to be as low as possible (minimum suggested setting is 2% of the biggest CT primary winding) but also allow for standing differential current for example due to CT mismatch and varying magnetising current losses. 5 to 20% is a typical application range.

The element is typically time delayed for 5 seconds (set greater than the maximum clearance time of an external fault). Instead the time delay allows the relevant protection element (which should be substantially faster) to clear the fault instead i.e. ID>2 in the case of an internal phase fault.

1.3 Peripheral Unit

1.3.1 Dead Zone protection (DZ)

On a feeder, if the isolators or the breaker is open, a dead zone (or end zone) is said to exist between the open element and the CT. The P74x peripheral units can protect this zone with the Dead Zone protection. This is a simple time delayed overcurrent and earth fault element which is only active when a dead zone is identified in the local topology.

1.3.2 Stub protection

When a one and half breaker scheme is protected by a MiCOM P74x, the stub protection can be done using a simple time delayed overcurrent element in each PU. The activation of this protection has to be set in the PSL and activated when all the associated isolators are open.

In the main setting group (usually 1), there is no overcurrent protection, in the next setting group (usually 2) this overcurrent is enabled (on top of the same setting as in the main setting group).

The setting group will be changed from “main” to “next” in the PSL.

1.3.3 Circuit Breaker Fail (CBF)

The detailed logic of the circuit breaker failure element follows.

Page 136: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-10

MiCOM P741, P742, P743

OP

1.3.3.1 Distributed Tripping, Control and Indication Elements (Peripheral Units)

As the P74x scheme has been designed for use as either a centralised or distributed scheme, the hardware corresponds to one circuit breaker and can accommodate 1 or 2 trip coils:

• 1 main trip coil • 1 back-up trip coil

Furthermore these can be either 3 single-phase trip coils or 1 three-phase trip coil. These can be combined for example 3 single-phase trip coils on the main system and 1 three-phase trip coil for the back-up system.

Note: - The backtrip order (coming from the Central Unit) is always given to the relay 1, 2 and 3 even if the CBF is disabled in the Peripheral Units. - The retrip has to be done using the PSL.

1.3.3.2 Circuit Breaker Fail Reset Criteria

1.3.3.2.1 Overcurrent Criterion

One of the most common causes of busbar mal-tripping is error introduced in the back tripping of adjacent sections. To prevent such an error it is possible to condition the operation of 50BF protection only when there is presence of a significant current i.e. a short-circuit on the concerned feeder. This confirmation is provided by the I> threshold which is set by default at 1.2 times the nominal rated current of the CT and/or by the threshold setting of residual current IN> set by default to 0.2 times the rated current.

1.3.3.2.2 Undercurrent reset Criterion

The criterion normally used for the detection of a circuit breaker pole opening is the disappearance of the current i.e. undercurrent element. This function is generally preferred above other elements due to its very fast response time. In P74x this method of detection is utilised and has the threshold I<.

See figure 6, part for phase A.

Note: The same algorithm is used for the other phases.

This Undercurrent elements have an I< threshold, which is used to supervise that each circuit breaker has opened correctly, when commanded to do so. By use of the I< threshold, it is possible to ensure that all load and fault current has been ruptured, ensuring that no arcing remains across the circuit breaker primary contacts. Optionally, the user can decide to include 52a supervision in the breaker fail logic (see chapters 1.3.3.2.3 and 1.3.3.2.4). The first function is to compare the current sample to the I< threshold and check for the following sequence:

• positive value of the current • no current (below the threshold) • negative value of the current • no current (below the threshold) • positive value of the current • …

The output signal is pl(t), it changes between 0 and 1.

Page 137: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-11

OP

To maintain the current criterion active while the signal crosses zero, there is a drop-off timer associated with the pl(t) signal. The latching duration is variable in order to take all cases into account:

• Just after the initiation of the CB fail signal, the waveform can include a DC component, and the time between two successive zero crossings can thus reach one period. Therefore, the resetting time is equal to the period plus a margin of 3ms (23ms at 50Hz, 20ms at 60Hz).

• For the last 30ms before the end of the stage 2 timer, the DC component should have disappeared so that the time between two successive zero crossings should be close to one half-period. Moreover it is important to detect the opening of the circuit breaker quickly because the end of the back trip timer is near. The drop-off duration is therefore equal to one half period + 3ms (13ms at 50Hz, 11.3ms at 60Hz).

Tn1

pl (t)

PL

Tn1

pl (t)

PL

P0303ENa

Excitation with zero crossing signal:

Excitation without zero crossing signal:

a

I< 0

&

0

Tbf3

0

Tbf4-

Tbf3 &Tn1

TpAExternal single pole

tripping signal from

distance protection

Pl(

t)IA

PL

I>BB confirmation

52a status

TpABC

To

general

tripping

Short reset time control by

instantaneous recheck at tBF4 expiry

To local

retrip

>1

&

&

>1PLP

l(t)

0

0

0

0

tBF2-30ms

tFB4-30ms

Pulse Tn1

=(T)+3ms

Pulse Tn1

=(T/2)+3ms

1

7

Internal three pole

tripping signal from 87BB

Details of TN1 Control

P0304ENa

FIGURE 5: CB FAIL ELEMENT LOGIC – PRINCIPLE OF RESET TIME CONTROL

Page 138: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-12

MiCOM P741, P742, P743

OP

FIGURE 6: CB ELEMENT LOGIC

Principle of the undercurrent function.

Instantaneous current measurements are taken for both the positive and negative half cycles, ensuring immunity to DC offset waveforms, and CT current ring-down.

The two horizontal dotted lines are instantaneous thresholds, fixed in proportion to the user's I< setting. The instantaneous threshold is at 70 percent of the I< fundamental RMS setting. As any current rises above the dotted line instantaneous threshold, this rising measurement triggers a pulse timer to declare that current is flowing. The duration of the pulse is one full cycle plus 3ms (T+3ms). It does not matter whether the magnitude of the current stays above the dotted line further, as the detector is effectively edge-triggered. Current flow has been declared based on this half cycle, and not until the current falls below the detector setting is the edge-trigger ready to declare an output again. Whilst current is flowing, on the rise of current in each half-cycle the pulse timer is retriggered. This sequential retriggering ensures that current is detected.

The detection of breaker opening is made upon one of two scenarios:

(1) The current falls below the instantaneous detection threshold, and does not rise again before the pulse timer expires; or

(2) A CT current ringdown does not change sign, and remains in one polarity sense up until the timer expires.

Note The pulse timer length is variable, and adapts according to the anticipated proportion of DC current offset that may be present in the measured waveform. The pulse timer initially is fixed at one cycle plus 3ms, as described previously, as upon fault inception the DC offset could be appreciable. Near the end of the breaker fail time, the pulse length is shortened to half a power cycle plus 3ms (T/2 + 3ms). The presumption is that the DC offset in real fault current has decayed, and that the shorter time is all that is required. The pulse length is commuted 30ms before expiry of the tBF2 timer (for internally-initiated CBF) and 30ms before expiry of the tBF4 timer (for externally-initiated CBF). The reduced pulse length means faster resetting of the current detector.

Page 139: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-13

OP

1.3.3.2.3 Logic reset Criterion

This is for instances where circuits may carry a very low level of load, or even may operate unloaded from time to time. Where 52a contact (CB closed) supervision is set, the relay looks only for 52a resetting to stop the breaker fail timers.

This criterion is based on checking the state of the circuit breaker auxiliary contacts. i.e. to see if the 52a contact is open for open circuit breaker conditions. In the P74x protection system, this detection method is used with the '52a' threshold.

1.3.3.2.4 Logic AND Current reset Criterion

This is for instances where circuits may carry a very low level of load, or even may operate unloaded from time to time. Where 52a contact (CB closed) supervision is set, the relay looks for I< undercurrent, and 52a resetting to stop the breaker fail timers.

This criterion relies on verifying the disappearance of the current AND of the state of the CB auxiliary contacts. In the P74x protection system, this detection method is used with the 'I< AND 52a' threshold.

1.3.3.2.5 Processing a Circuit Breaker Failure Condition

Due to the nature of the busbar protection, the substation topology can manage the system under circuit breaker failure conditions (50BF).

There are several options for circuit breaker failure protection installations. Generally these depend on the substation construction and wiring:

• Internally initiated CBF i.e. Initiation from the differential element, 87BB trip issued by the Central Unit

• Externally initiated, for example by the feeder protection, but using the busbar protection’s integral 50BF protection to execute tripping procedure

• Separate 50BF protection to the busbar protection (such as a MiCOM P821)

The breaker failure logic uses fast acting undercurrent elements to provide the required current check. These elements reset within 15ms, thereby allowing the use of the P74x relay at all voltage levels.

Since the Overcurrent element within the peripheral units may also be used in blocking schemes to provide back-up protection, it is possible to reset the Overcurrent start signals after the breaker fail time delay has elapsed. This ensures that the upstream back-up protection can be maintained by removal of the blocking signal. This would also ensure that the possible risk of re-trip on re-closure of the circuit breaker is minimised.

CB Trip 3 ph:

• Triphase Circuit Breaker Trip from CU (Init 50BF TBF1 / TBF2), Logical OR of 87BB, 50BF, Manual Trip Zone X

CB Trip phase A:

• Phase A Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of O/C Protection, External Trip A, External Trip 3ph

CB Trip phase B:

• Phase B Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of O/C Protection, External Trip A, External Trip 3ph

CB Trip phase C:

• Phase C Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of O/C Protection, External Trip A, External Trip 3ph

Note: The CB fail alarm is raised as soon as tBF1 or tBF2 or tBF3 or tBF4 has been reached (Logical OR of the signals 8, 9, 10, 11, 12, 13 in the following figure).

Page 140: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-14

MiCOM P741, P742, P743

OP 52a

Phase

A

I<

A

I<

B

I<

C

0

Tn1

0

Tn1

0

Tn1

& & &Ext

ern

altr

ipsi

gnalfr

om

peri

phera

lunit

(21

,8

7T,

etc

….)

TpA T

pB T

pC

0 0 0

0 0 0

TBF3

Retr

iptim

edela

y

IBIA IC

0

250m

s

I>

a

I>

b c

0

Tn2

0

Tn2

0

=1

IBIA IC

& & &

& & &

=1

=1

=1

=1

CB

FAIL

ALA

RM

CB

FAIL

ALA

RM

BB/F

FBusb

ar

Trip

on

feeder

fault

=1

=1

=1

TBF1

0&

TBF2-T

BF1

0&

0

250m

s

=1

&

52a

Phase

B

52a

Phase

C

Trip

sig

nalto

localC

BB

us

Couple

r

from

Busbar

pro

tection

3phases

Trip

(TpA

BC

)

IN>

N

0

Tn2

Tn2

IN

TBF3

TBF3

TBF3

=1

=1

TBF4

Back

trip

tim

edela

y

TBF4-

TBF3

TBF4-

TBF3

TBF4-

TBF3

Dead

pole

dete

ctio

n

I>

Fault

Dete

ctio

n

52

aEnable

I,IN

>Retr

ip&

back

trip

confirm

ation

I,IN

>Retr

ip&

back

trip

confirm

ation

TBF1

Back

trip

tim

edela

yT

BF2

Back

trip

tim

edela

y

Re

trip

Phase

AFeeder

Fault

Re

trip

Phase

BFeeder

Fault

Retr

ipPhase

CFeeder

Fault

Busb

ar2

Trip

on

Busb

ar1

Fault

Loca

lre

trip

on

Busb

ar

Fault

1 2 3 4 5 6 7

8 9 10

11

P3738E

Na12

13

FIGURE 7: CB FAIL LOGIC

Page 141: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-15

OP

P3739ENa

>1

>1

>1

DDB Ext. CB Fail

DDB O/C Protection

DDB Ext. 3ph Trip

DDB External Trip A

DDB External Trip B

DDB External Trip C

1

2

3

>1

>1

>1

DDB CB Aux. 3ph (52a)

DDB CB Aux. A (52a)

DDB CB Aux. B (52a)

DDB CB Aux. C (52a)

4

5

6

7Trip signal from CU

8

12

13

>1

DDB CBF Int Backtrip

DDB CBF Ext Backtrip

DDB Int Retrip 3ph

9

10

11

DDB Ext. Retrip ph A

DDB Ext. Retrip ph B

DDB Ext. Retrip ph C

DDB BF Trip RequestTrip signal towards CU

CB FailLogic

(See Fig 9)

FIGURE 8: CB FAIL LOGIC (DDB INPUTS & OUTPUTS)

1.3.3.2.6 Internally Initiated CBF i.e.

Tripping from the Differential Element 87BB issued by the Central Unit

When a tripping order is generated by the busbar protection (87BB or 50BF) but not executed due to a circuit breaker failure condition, the following circuit breakers are required to be tripped instead:

All the circuit breakers in the adjacent busbar zone if the faulty circuit breaker is that of a bus coupler or bus section.

Optional: The remote end circuit breaker if the faulty circuit breaker is that of a feeder (line or transformer). This intertripping is done via PSL and may not be required on feeders, which may be serviced automatically via the distance or other line protection.

The tripping order from the busbar protection is referenced as TpABC, it is always three-phase and initiates timers tBF1 and tBF2. The first timer is associated with the local re-trip function while the second timer is associated with the conveyance of the signal to the central unit for tripping of the adjacent zone in the cases of bus coupler/bus section circuit breaker failure.

1.3.3.2.6.1 Description of the Logic for Internally Initiated CBF

Local overcurrent element 87BB confirmation

I<Dead pole detection threshold

I> (note 2)

Local overcurrent element CBF confirmation

&

& &tBF1

tBF2-tBF1 &

BBx

LocalRetrip

LocalCircuitBreaker

TpABC: Tripping signal from 87BB

Note 1: Signal to CU for back-trip (including adjacent zone(s) if failed CB is bus section or bus coupler circuit breaker

Back trip(Note 1)

I>BB (note 2)

Trip signalfrom CU

Main busbar protection trip signal

Note 2: I>BB and I> could be enabled or disabled (scheme shown is with the 2 functions enhanced)

P3771ENa

FIGURE 9: CB FAIL ELEMENT LOGIC – INTERNALLY INITIATED

Page 142: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-16

MiCOM P741, P742, P743

OP

1.3.3.2.6.2 Initial Trip

A trip signal is issued by the central unit and then confirmed by the local peripheral unit. If the (optional) threshold for the local Overcurrent protection setting for busbar protection (I>BB) is exceeded then the local circuit breaker trip coil is energised and subsequently the local circuit breaker is tripped.

1.3.3.2.6.3 Re-Trip after time tBF1

The peripheral unit’s dead pole detection threshold (I<) and external protection initiation (I>) trigger the first breaker failure timer (tBF1). This signal in turn is passed through an AND gate with the signal from the local Overcurrent protection for busbar protection (I>BB) (if a circuit breaker failure condition has evolved this will still be present) and a re-trip command is issued. Re-trip output contacts should be assigned using the PSL editor (including in default PSL settings).

1.3.3.2.6.4 Back-Trip after time tBF2

A signal from the first circuit breaker timer triggers the second breaker failure timer (tBF2). This in turn is passed through an AND gate with the signal from the local overcurrent protection for busbar protection (I>BB), if a circuit breaker failure condition has persisted this will still be present, and a general bus-zone back-trip signal issued via the central unit.

In summary tBF1 is used for re-trip and tBF2 for general bus zone back-trip

Because the busbar protection scheme uses the substation topology, during circuit breaker failure conditions, circuit breaker operations are executed according to on the current state of the system. It is therefore of paramount importance that should an internally initiated scheme be implemented, the circuit breaker tripping order, must be thoroughly defined within the scheme topology to guarantee correct scheme operation.

OtherProtection

P3758ENa

BB1

Trip Order (1)

PU

50BF

PU

50BF

CU 87BB

PU

50BF

CB

Failed

(2)

Main Trip

or Retrip

Back Trip

CB Fail signal (3) Back Trip Order (4)

BB2

FIGURE 10: CIRCUIT BREAKER FAILURE LOGIC

Page 143: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-17

OP

Z1

P3740ENa

PU

PU

PU

PU PU PU PU

PU PU

PU PU

PU PU

PU PU PU

Z2

Z3 Z4

Remote Substation

CBA

Fault in Z2 CB failed:

Back trip Z2 to Z1

and A

Z1

P3741ENa

PU

PU

PU

PU PU PU PU

PU PU

PU PU

PU PU

PU PU PU

Z2

Z3 Z4

Remote Substation

CBB

Fault in Z3 CB failed:

Back trip to remote end

and B

FIGURE 11: EXAMPLES

1.3.3.2.7 Externally Initiated 50BF

I<Dead pole detection threshold

I>Local oversurrent element CBF confirmation

& &tBF3

tBF4-tBF3 &

BBx

LocalRetrip(Note 2)

LocalCircuitBreaker

TpA, TpB or TpC: Tripping signal from external protection

Note 1: Signal to CU for back-trip (including adjacent zone(s) if failed CB is bus section or bus coupler circuit breakerNote 2: Optional, refer to section 3.3.2.1Note 3: I> could be enable or disable

Back trip(Note 1)

ExternalProtectionInitiation

P3772ENa

FIGURE 12: CB FAIL ELEMENT LOGIC – EXTERNALLY INITIATED

Page 144: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-18

MiCOM P741, P742, P743

OP

Taking into account the relationship between the busbar protection and the circuit breaker failure protection certain operators prefer an integrated solution where the breaker failure may be initiated by external protection but executed in the busbar scheme. Tripping is then worked out in the section or zone.

On an overhead line for example the external commands may be generated by the distance protection (21). Generally these commands are on a per phase basis and therefore the tripping commands must be to. In the diagrams these signals are labelled TpA, TpB, TpC (Tripping pole A, B or C).

The logic is similar to that for internally initiated CB fail protection but utilises tBf3 for re-trip and tBF4 for back-trip functions.

1.3.3.2.8 Local re-trip after time tBf3

This re-trip command can be applied via either the main or back up trip coil. It is possible to choose between the 3 following modes:

• Local re-trip activated/deactivated via PSL. The relay used for this function can use the same fixed logic for the busbar protection or other independent relays.

• A re-trip can be applied after a time tBF3. This is typically set at 50ms when a single phase trip and re-trip is used. This prevents loss of phase selectivity by allowing the main protection trip to execute via the main CB trip coil before re-trip command is executed by the back-up CB trip coil.

• Single or three phase re-trip is possible. If the feeder protection executes single-phase tripping, the three-phase re-trip must be carried out in time tBF3 and this must be adjusted to have a value higher than the normal operation time of the circuit breaker. Typical setting under this condition is 150ms.

1.3.3.2.8.1 General zone trip after time tBF4

When both the local trip and re-trip have failed, the countdown continues with a second timer adjusted to have a value of tBF4 - tBF3. The end of this time thus corresponds to total time tBF4, beyond which a persistent circuit breaker failure condition is declared.

Information is then relayed to the Central unit for routing to the other peripheral units, and the associated circuit breakers, in the adjacent zone(s) for a general three-phase back-trip.

1.3.3.2.9 CB Fail alarm

The CB Fail alarm is raised on any timer reached (tBF1 or tBF2 or tBF3 or tBF4)

1.3.3.2.10 Separate external 50BF protection to the busbar protection

This is the most common solution utilising conventional wiring. The 50BF relay is completely independent of all others. When a circuit breaker failure condition occurs the external protection trips all adjacent circuit breakers as defined in the separate scheme (DDB Ext. CB fail).

In view of the connection between the functions of the busbar protection and the circuit breaker failure protection some operators prefer one of the more integrated system solutions previously mentioned.

Page 145: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-19

OP

1.4 Three Phase Overcurrent Protection

1.4.1.1 Inverse Time (IDMT) Characteristic

IDMT characteristics are selectable from a choice of four IEC/UK and five IEEE/US curves as shown in the table below.

The IEC/UK IDMT curves conform to the following formula:

( ) ⎟⎠

⎞⎜⎝

⎛+×=

−α LK

Tt1IsI

The IEEE/US IDMT curves conform to the following formula:

( ) ⎟⎠

⎞⎜⎝

⎛+×=

−α LK

7TD

t1IsI

Where: t = Operation time K = Constant Ι = Measured current ΙS = Current threshold setting α = Constant L = ANSI/IEEE constant (zero for IEC/UK curves) T = Time Multiplier Setting for IEC/UK curves TD = Time Dial Setting for IEEE/US curves

IDMT Curve description Standard K Constant α Constant L Constant

Standard Inverse IEC 0.14 0.02 0

Very Inverse IEC 13.5 1 0

Extremely Inverse IEC 80 2 0

Long Time Inverse UK 120 1 0

Moderately Inverse IEEE 0.0515 0.02 0.114

Very Inverse IEEE 19.61 2 0.491

Extremely Inverse IEEE 28.2 2 0.1217

Inverse US-C08 5.95 2 0.18

Short Time Inverse US-C02 0.02394 0.02 0.01694

1.4.1.2 Reset Characteristics

For all IEC/UK curves, the reset characteristic is definite time only.

For all IEEE/US curves, the reset characteristic can be selected as either inverse curve or definite time.

The definite time can be set (as defined in IEC) to zero. Range 0 to 100 seconds in steps of 0.01 seconds.

The Inverse Reset characteristics are dependent upon the selected IEEE/US IDMT curve as shown in the table below.

Page 146: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-20

MiCOM P741, P742, P743

OP

All inverse reset curves conform to the following formula:

( ) ⎟⎟⎠

⎞⎜⎜⎝

−×⎟

⎠⎞

⎜⎝⎛= αIsI1

tr7TD

tReset

Where: tReset = Reset time tr = Constant Ι = Measured current ΙS = Current threshold setting α = Cconstant TD = Time Dial Setting (Same setting as that employed by IDMT curve)

IEEE/US IDMT Curve description Standard tr Constant α Constant

Moderately Inverse IEEE 4.85 2

Very Inverse IEEE 21.6 2

Extremely Inverse IEEE 29.1 2

Inverse US-C08 5.95 2

Short Time Inverse US-C02 2.261 2

Inverse Reset Characteristics

1.5 Earth Fault Protection

1.5.1 EF time delay characteristics

The earth-fault measuring elements for EF and SEF are followed by an independently selectable time delay. These time delays are identical to those of the Phase Overcurrent time delay. The reset time delay is the same as the Phase overcurrent reset time.

1.5.2 External Fault Detection by High-Set Overcurrent or Earth Fault Element

An ultra high-speed detection is carried out by each of the peripheral units (P742 and P743) and can generate a blocking signal from the moment of the first sample at 0.42 ms.

In this scenario de-saturation may not occur until after the scheme has eliminated the saturation condition for the external fault.

This function can be activated independently for phase faults (Ι>2) and for Earth Faults (ΙN>2).

1.5.3 Supervision

1.5.4 Zero Sequence Current (ΙO) Supervision.

The four current inputs (A, B, C, N) to the peripheral units are used to verify that the calculated zero sequence current is within the correct range for CT supervision purposes. This then provides continuous supervision of the relay's measuring chain (internal CTs, ADC, etc…).

The residual current 3Ιo is derived from the three phases Ιa + Ιb + Ιc and compared to the measured value of ΙN from the neutral CT input.

|3ΙO - ΙN |

During an earth fault the two values should be the same and the sum should therefore be equal to zero or below the threshold (CTS ΙN> Set) and the CT supervision alarm will not be issued.

If a CT becomes short-circuited, a difference between the derived and measured value will appear, i.e. a CT problem has been detected and after a user settable time delay (CTS Time delay) the alarm will be issued.

Page 147: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-21

OP

This calculation is then compared to a further criterion to verify and monitor CT connections and associated current circuits.

|3ΙO - ΙN |> 0.05 Ιn + KCE x (|Ιa| + |Ιb| + |Ιc| + |ΙN| )

(Where KCE is a calculation error coefficient and In is the nominal current)

The calculation error coefficient in the above formula is set between 0.01 and 1 thereby allowing for small discrepancies and preventing false blocking of the differential elements whilst the constant value of 0.05 In provides stability under no load or low load conditions.

Main causes for alarms from zero sequence current calculations are:-

• Commissioning with load current – detection of connection errors (input inverted/rated current incorrect)

• Maintenance with load current – By pass of analogue input, when a separate neutral CT is made available.

• Failure of an analogue channel – e.g. A/D converter failure

Once detected the alarm will be issued after a user settable time delay (Alarm Delay TCE).

Because the peripheral units sample at 2400Hz discrepancies between the measured and derived values are identified and responded to very quickly. If any anomalies arise for either of the above calculations the differential elements associated with the faulty peripheral unit are instantaneously blocked. The blocking signal remains in place for 10ms with an alarm signal sent after the time delay. The time delay is usually set above the time required to trip under fault conditions.

Page 148: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-22

MiCOM P741, P742, P743

OP

2. CURRENT TRANSFORMERS

2.1 CT Saturation detection

Innovative methods are used to detect CT saturation in the P74x. The values associated with the CT saturation algorithms are entered into the Peripheral Unit’s CT ratio menu column and are used to define the CT’s characteristic. The algorithms for CT saturation detection are executed in the peripheral units.

The first algorithm to be examined is the detection of variation of current.

The PU calculates the derived current and compares it to the magnitude of the waveform. With 2400Hz sampling, maximum variation between 2 successive samples of sinusoidal current can not exceed 14% of the previous period's magnitude.

FIGURE 13: CURRENT VARIATION

The magnitude of the current is the maximum value of the current measure during the last period with a minimum of 50% of nominal current. A variation is detected is derived current exceed 20% of this magnitude.

This instantaneous value is maintained 150ms for the first variation then 50ms for the next ones, as shown as figure 17.

FIGURE 14: CURRENT VARIATION CRITERIA

Page 149: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-23

OP

The second algorithm, by integration of the secondary current, presumes of maximum flux in the HV CT core.

The flux calculation starts when the first variation of current is detected, then if the calculated flux reached 20% of the maximum flux, a CT saturation is presumed as shown in figure 18.

FIGURE 15: DETERMINATION OF SIGNAL QUALITY IN PERIPHERAL UNIT

CT saturation detection starts at the first variation of current detected and stop if there is no variation during 100ms.

The third algorithm blocks the occurrence of saturation for as long as the current increases during the first half-cycle.

Blocking starts upon detection of the first current variation. Then, as soon as the current is reversed, CT saturation is permitted as shown below in Figure 16.

FIGURE 16: DETERMINATION OF SIGNAL QUALITY IN THE PERIPHERAL UNIT

Page 150: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-24

MiCOM P741, P742, P743

OP

CT saturation is detected after a variation of current, detection of a presumption of maximum flux and current reversal, as shown figure 4. When CT saturation appears, a blocking order is sent to the CU to block all zones (the check zone is blocked).

FIGURE 17: CT SATURATION RESET

FIGURE 18: CT SATURATION

Page 151: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-25

OP

P3774ENa

FIGURE 19: DETERMINATION OF SIGNAL QUALITY IN THE PERIPHERAL UNIT

CT Location

There are no restriction imposed as to the location of current transformers within the system, however, when the topological model is created, the position and orientation of the current transformers must be defined correctly to ensure the correct operation of the protection.

A suggested current transformer location is to position the current transformer for the busbar protection, line side of the circuit breaker whilst the line protection current transformers are positioned busbar side of the circuit breaker. This then covers the largest possible busbar zone providing an overlap with the line protection therefore eliminating any possible blind spots. This is shown in Figure below.

P3775ENa

FIGURE 20: CT LOCATION

Page 152: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-26

MiCOM P741, P742, P743

OP

3. ISOLATOR AND CIRCUIT BREAKER FUNCTION

3.1 Isolator State Monitoring Features

MiCOM relays can be set to monitor normally open (89A) and normally closed (89B) auxiliary contacts of the isolators. Under healthy conditions, these contacts will be in opposite states. Should both sets of contacts be open, this would indicate one of the following conditions:

• Auxiliary contacts / wiring defective

• Isolator is defective

• Isolator is in isolated position

Should both sets of contacts be closed, only one of the following two conditions would apply:

• Auxiliary contacts / wiring defective

• Isolator is defective

A normally open / normally closed output contact has to be assigned to this function via the programmable scheme logic (PSL). The time delay is set to avoid unwanted operation during normal switching duties. If any of the above conditions exist, an alarm will be issued after the time delay set in the PSL.

In the PSL Qx must be used following the two options:

• 89A or 89B

• Both 89A and 89B

If both 89A and 89B are used then status information will be available and in addition a discrepancy alarm will be possible. 89A and 89B inputs are assigned to relay opto-isolated inputs via the PSL.

3.2 Circuit Breaker State Monitoring Features

MiCOM relays can be set to monitor normally open (52A) and normally closed (52B) auxiliary contacts of the circuit breaker. Under healthy conditions, these contacts will be in opposite states. Should both sets of contacts be open, this would indicate one of the following conditions:

• Auxiliary contacts / wiring defective

• Circuit Breaker (CB) is defective

• CB is in isolated position

Should both sets of contacts be closed, only one of the following two conditions would apply:

• Auxiliary contacts / wiring defective

• Circuit Breaker (CB) is defective

If any of the above conditions exist, an alarm will be issued after a 200ms time delay. A normally open / normally closed output contact can be assigned to this function via the programmable scheme logic (PSL). The time delay is set to avoid unwanted operation during normal switching duties.

In the PSL CB AUX could be used or not, following the four options:

• None

• Both 52A and 52B (triphase - 2 optos)

• Both 52A and 52B (per phase - 6 optos)

No CB status available directly affects any function within the relay that requires this signal, for example CB control, Topology for buscoupler, etc.

Page 153: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-27

OP

If both 52A and 52B are used then status information will be available and in addition a discrepancy alarm will be possible, according to the following table. 52A and 52B inputs are assigned to relay opto-isolated inputs via the PSL.

Auxiliary Contact Position CB State Detected Action

52A 52B

Open Closed Breaker Open Circuit breaker healthy

Closed Open Breaker Closed Circuit breaker healthy

Closed Closed CB Failure Alarm raised if the condition persists for longer than 150ms

Open Open State Unknown Alarm raised if the condition persists for longer than 150ms

In the bus sections and bus couplers, the position used in the topology algorithm is open when the ‘CB State Detected’ is ‘Breaker Open’. In all others cases, the position closed will be used to calculate the topology. CB auxiliary contacts and Manual CB closed command are definitely required for all bus-sections and bus-couplers.

They are not definitely required for feeders, but if the information is supplied to the scheme, better operation is possible:

• Dead Zone fault, the CB position is required (send remote trip order to the other end of the line).

• CB supervision.

In that case the best is to provide the Manual CB closing order.

No specific auxiliary contacts are required but ideally one 52a and one 52b should be available.

The faster these contacts operate (following real CB operation) the better it is.

During operation of the CB, when 52a=52b=0 or 52a=52b=1, the CB is considered as closed.

In the PSL:

If 52a is per pole, 52b should be per pole;

If 52a is 3phase, 52b should be 3phase too.

INTERMEDIATE POSITION

HV CONTACT

AUXILIARY CONTACT a0

AUXILIARY CONTACT b0

AUXILIARY CONTACT bc

AUXILIARY CONTACT ac

CONTACT CLOSED

CONTACT OPEN

Page 154: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-28

MiCOM P741, P742, P743

OP

3.3 Circuit Breaker Control

The relay includes the following options for control of a single circuit breaker:

Local tripping and closing, via the relay menu

Local tripping and closing, via relay opto-isolated inputs

It is recommended that separate relay output contacts are allocated for remote circuit breaker control and protection tripping. This enables the control outputs to be selected via a local/remote selector switch as shown below. Where this feature is not required the same output contact(s) can be used for both protection and remote tripping.

Close

Trip0close

LocalRemote

Trip

Protectiontrip

Remote controltrip

Remotecontrolclose

+ve

ve

FIGURE 21: REMOTE CONTROL OF CIRCUIT BREAKER

The following table is taken from the relay menu and shows the available settings and commands associated with circuit breaker control.

A manual trip will be permitted provided that the circuit breaker is initially closed. Likewise, a close command can only be issued if the CB is initially open. To confirm these states it will be necessary to use the breaker 52A and/or 52B contacts via PSL. If no CB auxiliary contacts are available no CB control (manual or auto) will be possible.

Once a CB Close command is initiated the output contact can be set to operate following a user defined time delay (‘Man Close Delay’). This would give personnel time to move away from the circuit breaker following the close command. This time delay will apply to all manual CB Close commands.

The length of the trip or close control pulse can be set via the ‘Man Trip Pulse’ and ‘Man Close Pulse’ settings respectively. These should be set long enough to ensure the breaker has completed its open or close cycle before the pulse has elapsed.

Note: The manual close commands for each user interface are found in the System Data column of the menu.

If an attempt to close the breaker is being made, and a protection trip signal is generated, the protection trip command overrides the close command.

If the CB fails to respond to the control command (indicated by no change in the state of CB Status inputs) a ‘CB Fail Trip Control’ or ‘CB Fail Close Control’ alarm will be generated after the relevant trip or close pulses have expired. These alarms can be viewed on the relay LCD display or can be assigned to operate output contacts for annunciation using the relays programmable scheme logic (PSL).

Page 155: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-29

OP

4. OPERATION OF NON PROTECTION FUNCTIONS

4.1 Programmable scheme logic

4.1.1 Level settings

Name Range Step Size

Time delay t 0-14400000ms 1ms

4.1.2 Accuracy

Output conditioner timer Setting ±2% or 50ms whichever is greater

Dwell conditioner timer Setting ±2% or 50ms whichever is greater

Pulse conditioner timer Setting ±2% or 50ms whichever is greater

Page 156: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-30

MiCOM P741, P742, P743

OP

5. COMMUNICATIONS BETWEEN PU AND CU The P74x scheme can be either centralised in one cubicle or distributed in cubicles housing other protection depending on the availability of space. Either way the peripheral units still need to communicate with the central unit and vice versa. Each central unit has up to 7 communication boards each accommodating inputs from 4 peripheral units. Thus each central unit can accommodate up to 28 peripheral units.

5.1 Communications link

The following communication media is used for the communication channel within the P74x scheme. The data rate is 2.5 Mbits/sec.

5.2 Direct optical fibre link, 850nm multi-mode fibre

The units are connected directly using two 850nm multi-mode optical fibres for each signalling channel. Multi-mode fibre type 62.5/125μm is suitable and standard BFOC/2.5 type fibre optic connectors are used. These are commonly known as “ST” connectors (“ST” is a registered trademark of AT&T).

FIGURE 22: MODULE INTERCONNECTION

This is typically suitable for connection up to 1km.

Page 157: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-31

OP

5.3 Optical budgets

When using fibre optics as a method of communication the type of fibre used and the distance between devices needs to be considered. The following table shows the optical budgets of the communications interface.

Parameter 850nm Multi mode

Min. transmit output level (average power) -19.8dBm

Receiver sensitivity (average power)

-25.4dBm

Optical budget 5.6dB

Less safety margin (3dB) 2.6dB 3dB

Typical cable loss 2.6dB/km

Max. transmission distance 1km

TABLE 2: OPTICAL BUDGET

The total optical budget is given by transmitter output level minus the receiver sensitivity and will indicate the total allowable losses that can be tolerated between devices. A safety margin of 3dB is also included in the above table. This allows for degradation of the fibre as a result of ageing and any losses in cable joints. The remainder of the losses will come from the fibre itself. The figures given are typical only and should only be used as a guide.

5.3.1 Main operating features

5.3.1.1 Operation modes

5.4 Trip LED logic

The trip LED can be reset when the flags for the last fault are displayed or via dedicated ddbs. The flags are displayed automatically after a trip occurs, or can be selected in the fault record menu. The reset of trip LED and the fault records is performed by pressing the key once the fault record has been read.

FIGURE 23: TRIP LED LOGIC DIAGRAM

Page 158: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-32

MiCOM P741, P742, P743

OP

5.5 Function keys

The P741 and P743 relays offer users 10 function keys for programming any operator control functionality such as auto-reclose ON/OFF, earth fault1 ON/OFF etc. via PSL. Each function key has an associated programmable tri-colour LED that can be programmed to give the desired indication on function key activation.

These function keys can be used to trigger any function that they are connected to as part of the PSL. The function key commands can be found in the ‘Function Keys’ menu (see Settings section, P74x/EN ST). In the ‘Fn. Key Status’ menu cell there is a 10 bit word which represent the 10 function key commands and their status can be read from this 10 bit word.

In the programmable scheme logic editor 10 function key signals, which can be set to a logic 1 or On state, as described above, are available to perform control functions defined by the user.

The “Function Keys” column has ‘Fn. Key n Mode’ cell which allows the user to configure the function key as either ‘Toggled’ or ‘Normal’. In the ‘Toggle’ mode the function key DDB signal output will remain in the set state until a reset command is given, by activating the function key on the next key press. In the ‘Normal’ mode, the function key DDB signal will remain energized for as long as the function key is pressed and will then reset automatically. A minimum pulse duration can be programmed for a function key by adding a minimum pulse timer to the function key DDB output signal.

The “Fn. Key n Status” cell is used to enable/unlock or disable the function key signals in PSL. The ‘Lock’ setting has been specifically provided to allow the locking of a function key thus preventing further activation of the key on consequent key presses. This allows function keys that are set to ‘Toggled’ mode and their DDB signal active ‘high’, to be locked in their active state thus preventing any further key presses from deactivating the associated function. Locking a function key that is set to the “Normal” mode causes the associated DDB signals to be permanently off. This safety feature prevents any inadvertent function key presses from activating or deactivating critical relay functions.

The “Fn. Key Labels” cell makes it possible to change the text associated with each individual function key. This text will be displayed when a function key is accessed in the function key menu, or it can be displayed in the PSL.

The status of the function keys is stored in battery backed memory. In the event that the auxiliary supply is interrupted the status of all the function keys will be recorded. Following the restoration of the auxiliary supply the status of the function keys, prior to supply failure, will be reinstated. If the battery is missing or flat the function key DDB signals will set to logic 0 once the auxiliary supply is restored. Please also note the relay will only recognize a single function key press at a time and that a minimum key press duration of approximately 200msec. is required before the key press is recognized in PSL. This deglitching feature avoids accidental double presses.

5.5.1 CB control using hotkeys

In the Peripheral Units, the hotkeys allow direct access to the manual trip and close commands without the need to enter the SYSTEM DATA column. Hotkeys supplement the direct access possible via the function keys described in section 5.5. Red or green colour coding can be applied when used in CB control applications.

IF <<TRIP>> or <<CLOSE>> is selected the user is prompted to confirm the execution of the relevant command. If a trip is executed a screen with the CB status will be displayed once the command has been completed. If a close is executed a screen with a timing bar will appear while the command is being executed. This screen has the option to cancel or restart the close procedure. The timer used is taken from the manual close delay timer setting in the CB Control menu. When the command has been executed, a screen confirming the present status of the circuit breaker is displayed. The user is then prompted to select the next appropriate command or exit – this will return to the default relay screen.

If no keys are pressed for a period of 25 seconds while waiting for the command confirmation, the relay will revert to showing the CB Status. If no key presses are made for a period of 25 seconds while displaying the CB status screen, the relay will revert to the default relay screen. Figure 57 shows the hotkey menu associated with CB control functionality.

Page 159: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-33

OP

To avoid accidental operation of the trip and close functionality, the hotkey CB control commands will be disabled for 10 seconds after exiting the hotkey menu.

!" #$!%

&

!'#( $)

'"*%)

++,

FIGURE 24: CB CONTROL HOTKEY MENU

5.5.2 CB control using function keys

In the P743, the function keys allow direct control of the circuit breaker if programmed to do this in PSL. local tripping and closing, via relay opto-isolated inputs must be set in the “CB Control” menu ‘CB control by’ cell to enable this functionality. All CB manual control settings and conditions will apply for manual tripping and closing via function keys.

The following default logic can be programmed to activate this feature:

FIGURE 25: CB CONTROL VIA FUNCTION KEYS DEFAULT PSL

Function key 2 and function key 3 are both enabled and set to ‘Normal’ Mode and the associated DDB signals ‘DDB 677’ and ‘DDB 678’ will be active high ‘1’ on key press.

The following DDB signal must be mapped to the relevant function key:

Man. Trip CB – Initiate manual circuit breaker trip

Man. Close CB – Initiate manual circuit breaker close

The programmable function key LED’s have been mapped such that the LED’s will indicate yellow whilst the keys are activated.

Page 160: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-34

MiCOM P741, P742, P743

OP

5.6 Setting groups selection

The setting groups can be changed either via opto inputs, via a menu selection, via the hotkey menu or via function keys. In the Configuration column if 'Setting Group - select via optos' is selected then any opto input or function key can be programmed in PSL to select the setting group as shown in the table below. If 'Setting Group - select via menu' is selected then in the Configuration column the 'Active Settings - Group1/2/3/4' can be used to select the setting group.

The setting group can be changed via the hotkey menu providing ‘Setting Group select via menu’ is chosen.

5.7 Control inputs

The control inputs function as software switches that can be set or reset either locally or remotely. These inputs can be used to trigger any function that they are connected to as part of the PSL. There are three setting columns associated with the control inputs that are: “CONTROL INPUTS”, “CTRL. I/P CONFIG.” and “CTRL. I/P LABELS”. The function of these columns is described below:

Menu Text Default Setting Setting Range Step Size

CONTROL INPUTS

Ctrl I/P Status 00000000000000000000000000000000

Control Input 1 No Operation No Operation, Set, Reset

Control Input 2 to 32 No Operation No Operation, Set, Reset

The Control Input commands can be found in the ‘Control Input’ menu. In the ‘Ctrl. Ι/P status’ menu cell there is a 32 bit word which represent the 32 control input commands. The status of the 32 control inputs can be read from this 32-bit word. The 32 control inputs can also be set and reset from this cell by setting a 1 to set or 0 to reset a particular control input. Alternatively, each of the 32 Control Inputs can be set and reset using the individual menu setting cells ‘Control Input 1, 2, 3’ etc. The Control Inputs are available through the relay menu as described above and also via the rear communications.

In the programmable scheme logic editor 32 Control Input signals, DDB 800 – 831, which can be set to a logic 1 or On state, as described above, are available to perform control functions defined by the user.

Menu Text Default Setting Setting Range Step Size

CTRL. I/P CONFIG.

Hotkey Enabled 11111111111111111111111111111111

Control Input 1 Latched Latched, Pulsed

Ctrl Command 1 SET/RESET SET/RESET, IN/OUT, ENABLED/DISABLED, ON/OFF

Control Input 2 to 32 Latched Latched, Pulsed

Ctrl Command 2 to 32 SET/RESET SET/RESET, IN/OUT, ENABLED/DISABLED, ON/OFF

Menu Text Default Setting Setting Range Step Size

CTRL. I/P LABELS

Control Input 1 Control Input 1 16 character text

Control Input 2 to 32 Control Input 2 to 32 16 character text

Page 161: P74x_EN_M_H54

Operation P74x/EN OP/H54 MiCOM P741, P742, P743

(OP) 5-35

OP

The “CTRL. I/P CONFIG.” column has several functions one of which allows the user to configure the control inputs as either ‘latched’ or ‘pulsed’. A latched control input will remain in the set state until a reset command is given, either by the menu or the serial communications. A pulsed control input, however, will remain energized for 10ms after the set command is given and will then reset automatically (i.e. no reset command required).

In addition to the latched/pulsed option this column also allows the control inputs to be individually assigned to the “Hotkey” menu by setting ‘1’ in the appropriate bit in the “Hotkey Enabled” cell. The hotkey menu allows the control inputs to be set, reset or pulsed without the need to enter the “CONTROL INPUTS” column. The “Ctrl. Command” cell also allows the SET/RESET text, displayed in the hotkey menu, to be changed to something more suitable for the application of an individual control input, such as “ON/OFF”, “IN/OUT” etc.

The “CTRL. I/P LABELS” column makes it possible to change the text associated with each individual control input. This text will be displayed when a control input is accessed by the hotkey menu, or it can be displayed in the PSL.

Note: With the exception of pulsed operation, the status of the control inputs is stored in battery backed memory. In the event that the auxiliary supply is interrupted the status of all the inputs will be recorded. Following the restoration of the auxiliary supply the status of the control inputs, prior to supply failure, will be reinstated. If the battery is missing or flat the control inputs will set to logic 0 once the auxiliary supply is restored.

Page 162: P74x_EN_M_H54

P74x/EN OP/H54 Operation (OP) 5-36

MiCOM P741, P742, P743

OP

BLANK PAGE

Page 163: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

AP

APPLICATION NOTES

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 164: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes

MiCOM P741, P742, P743

Page 165: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-1

AP

CONTENTS

1. INTRODUCTION 5

1.1 Protection of Substation Busbars 5

2. APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS 6

2.1 Central Unit 7

2.1.1 Setting guidelines 7

2.2 Peripheral Unit 11

2.2.1 Dead Zone protection (DZ) 11

2.2.2 Stub protection 11

2.2.3 Circuit Breaker Fail (CBF) 11

2.2.4 External Fault Detection by High-Set Overcurrent or Earth Fault Element 12

2.2.5 Setting guidelines 13

3. CURRENT TRANSFORMERS 14 4. CIRCUIT BREAKER FUNCTION 15

4.1 Circuit breaker state monitoring 15

4.2 Trip relays and Trip Circuit Supervision 15

4.2.1 TCS scheme 1 15

4.2.2 Scheme 1 PSL 16

4.2.3 TCS scheme 2 17

4.2.4 Scheme 2 PSL 17

4.2.5 TCS scheme 3 18

4.2.6 Scheme 3 PSL 18

5. ISOLATION AND REDUCED FUNCTION MODE 19

5.1 Normal mode 19

5.2 Peripheral Units (P742 and P743) 19

5.2.1 CB Failure Protection (50BF) disabled 19

5.2.2 Overhaul 20

Page 166: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-2

MiCOM P741, P742, P743

AP

5.3 Central processing unit (P741) 22

5.3.1 Busbar protection (87BB) Blocked 22

5.3.2 87BB Blocked & 50BF disabled 22

5.4 System operation under failed communications situation 22

5.5 Waiting Configuration 22

6. TOPOLOGY 23

6.1 Topology Configuration Tool 23

6.2 Nodal Assignment 24

6.3 Topology Communication 25

6.4 Topology data 25

6.5 Topology processing 26

6.5.1 CTs on one side of bus coupler, CB closes before status acquisition. 26

6.5.2 CTs on both sides of bus coupler, CB closes before status acquisition. 27

6.5.3 CTs on one side of bus coupler, CB closed and fault evolves between CT and CB (even for switch onto fault). 28

6.5.4 CTs on both sides of coupler, CB closed and fault evolves between CT and CB. 30

7. UNDERTAKING A NUMERICAL DIFFERENTIAL BUSBAR PROTECTION PROJECT 32

7.1 Check list 32

7.2 General Substation information 33

7.3 Short Circuit Levels 33

7.4 Switchgear 34

7.5 Cubicle specifications 34

7.6 Substation Architecture 35

8. STANDARD CONFIGURATIONS 36 9. APPLICATION OF NON PROTECTION FUNCTIONS 46

9.1 Function keys 47

Page 167: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-3

AP

10. CT REQUIREMENTS 48

10.1 Notation 48

10.2 87BB Phase CT Requirements 48

10.2.1 Feeders connected to sources of significant power (i.e. lines and generators) 48

10.2.2 Out of service feeders or those with low power contribution (low infeed) 48

10.2.3 CT Specification according to IEC 185, 44-6 and BS 3938 (British Standard) 49

10.3 87BB Sensitive Differential Earth Fault CT Requirements 50

10.4 Support of IEEE C Class CTs 50

11. AUXILIARY SUPPLY FUSE RATING 52

Page 168: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-4

MiCOM P741, P742, P743

AP

BLANK PAGE

Page 169: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-5

AP

1. INTRODUCTION Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label.

1.1 Protection of Substation Busbars

The busbars in a substation are possibly one of the most critical elements in a power system. If a fault is not cleared or isolated quickly, not only could substantial damage to the busbars and primary plant result, but also a substantial loss of supply to all consumers who depend upon the substation for their electricity. It is therefore essential that the protection associated with them provide reliable, fast and discriminative operation.

As with any power system the continuity of supply is of the utmost importance, however, faults that occur on substation busbars are rarely transient but more usually of a permanent nature. Circuit breakers should, therefore, be tripped and not subject to any auto-reclosure.

The busbar protection must also remain stable for faults that occur outside of the protected zone as these faults will usually be cleared by external protection devices. In the case of a circuit breaker failure, it may be necessary to open all of the adjacent circuit breakers, this can be achieved by issuing a backtrip to the busbar protection. Security and stability are key requirements of a busbar protection scheme. Should the busbar protection maloperate under such conditions substantial loss of supply could result unnecessarily.

Many different busbar configurations exist. A typical arrangement is a double busbar substation with a transfer bar. The positioning of the primary plant can also vary and also needs to be considered which in turn introduces endless variations, all of which have to be able to be accommodated within the busbar protection scheme.

Backup protection is also an important feature of any protection scheme. In the event of equipment failure, such as signalling equipment or switchgear for example it is necessary to provide alternative forms of fault clearance. It is desirable to provide backup protection, which can operate with minimum time delay and yet discriminate with other protection elsewhere on the system.

Page 170: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-6

MiCOM P741, P742, P743

AP

2. APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS The following sections detail individual protection functions in addition to where and how they may be applied. Each section provides some worked examples on how the settings are applied to the relay There are three modules that make up the P74x scheme.

The P741 is the Central Unit (CU), whilst the P742 and P743 are both variants of the Peripheral Unit (PU).

The central unit co-ordinates the scheme, receiving signals from all the peripheral units associated with the protected busbar(s) and acting on these signals, initiating a bus zone protection trip when necessary.

One peripheral unit is associated with each CT location, usually one per incomer/feeder and one or two for each bus coupler/bus section depending on the number of CTs (1 or 2). The peripheral units acquire the analogue signals from the associated CT and the binary signals from the auxiliary contacts of the primary plant (CB and isolator(s)). The peripheral units also incorporate the main circuit breaker failure logic together with backup protection. The difference between the P742 and P743 is the amount of I/O, the number and type of LEDs and the function keys that each can accommodate. The P743 allows for increased I/O (useful in multiple bar applications or where single pole breakers and a transfer bar are employed), tricolour LEDs, function keys and Ethernet board slot. The main features of the P74x scheme are summarised below:

• Current differential busbar protection – Phase segregated biased differential protection (sometimes referred to as low impedance type)

• Provides the main protection element for the scheme. This protection provides high-speed discriminative protection for all fault types

• Sensitive differential earth fault protection – provided for high impedance earthed systems and incorporates bias current control to guarantee stability under external faults

• Circuit breaker failure protection – two stage breaker fail logic that can be initiated internally or externally.

• Dead Zone protection – phase and neutral.

• Non-directional phase fault over current protection – provides two stage backup protection

• Non-directional earth fault protection – provides two stage backup protection

• Low Burden – Allows the protection to be installed in series with other equipment on a common CT secondary

• Accommodates different CT classes, ratios and manufacturer

Page 171: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-7

AP

2.1 Central Unit

Busbar Biased Current Differential Protection

2.1.1 Setting guidelines

2.1.1.1 87BB Phase CU settings (Solid Earthed Network Schemes)

An Excel spreadsheet tool called “Idiff_Ibias“ is available on request to assure a reliable setting choice:

Page 172: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-8

MiCOM P741, P742, P743

AP

2.1.1.1.1 Sub-station features

Only 6 values have to be known:

1. Minimum load current in a feeder

2. Maximum load current in a feeder

3. Maximum load current in a bus

4. Biggest CT primary winding

5. Minimum short-circuit value (phase to phase) in a bus

6. Number of independent bars

2.1.1.1.2 “Idiff_Ibias” Setting calculation spreadsheet

Enter in the Idiff_Ibias spreadsheet the 5 values here above listed and you’ll be able to choose the 7 values hereafter listed.

2.1.1.1.3 Differential Busbar Protection

1. ID>1 (from 5 A to 500 A (primary value)) as high as possible

2. Slope k1 (ID>1) (from 0% to 50%), recommendation is 10%

3. ID>2 (from 50 A to 50000 A (primary value)) as low as possible, whilst ensuring the single CT failure will not cause tripping under maximum load conditions

4. Slope k2 (ID>2) (from 20% to 90%), recommendation is generally 65%

5. IDCZ>2 (from 50 A to 50000 A (primary value)) as low as possible

6. Slope kCZ (IDCZ>2) (from 0% to 90%), recommendation is generally 30%

7. ID>1 Alarm Timer (from 0 to 100 s) shall be greater than the longest protection time (such as line, overcurrent, etc…)

2.1.1.2 87BB CU Settings (Compensated Earthed Network Schemes)

2.1.1.2.1 Sub-station features

Only 4 values have to be known:

1. Maximum load current in a feeder

2. Minimum phase to phase fault current (Ph-Ph min.) in a bus

3. Maximum single phase steady state faulty current (Ph-N Max.) in a bus

4. Number of independent bars

2.1.1.2.2 Differential Busbar Protection

9 values have to be chosen:

1. ID>1 (from 5 A to 500 A (primary value)), recommendation equal to 1,2 x (Ph-N Max.)

2. Slope k1 (ID>1) (from 0% to 50%), recommendation is 10%.

3. ID>1 Alarm Timer (from 0 to 100 s) shall be greater than the longest Busbar protection time

4. Slope k2 (from 20% to 90%) but recommendation 65%.

5. ID>2 (from 50 A to 50000 A (primary value)), recommendation is:

6. Lower than 0,8 x (Ph-Ph min) and Higher than 1,2 x Iload Max and if possible equal to 6 x (ID>1).

7. Slope kCZ (from 0% to 90%) but recommendation 30%.

8. IDCZ>2 (from 50 A to 50000 A (primary value)), recommendation is:

9. Lower than 0,8 x (Ph-Ph min) and Higher than 1,2 x Iload Max and if possible equal to 6 x (ID>1).

Page 173: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-9

AP

2.1.1.3 87BB SDEF CU Settings (High Impedance Earthed Schemes Only)

An Excel spreadsheet tool called “Idiff_Ibias_SDEF_HighImp “ is available on request to assure a reliable setting choice:

Page 174: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-10

MiCOM P741, P742, P743

AP

2.1.1.3.1 Sub-station features

8 values have to be known:

1. Number of independent bus

2. Minimum load current in a feeder

3. Maximum load current in a feeder

4. Maximum load current in a bus

5. Biggest CT primary winding

6. Minimum phase to phase short-circuit value in a bus

7. Minimum phase to ground short-circuit value in a bus

8. Maximum phase to ground short-circuit value in a bus

2.1.1.3.2 “Idiff_Ibias_SDEF_HighImp” Setting calculation spreadsheet

Enter in the Idiff_Ibias_SDEF spreadsheet the 8 values here above listed and you’ll be able to choose the 9 values hereafter listed.

2.1.1.3.3 SDEF Busbar Protection

15 values have to be entered:

1. ID>1 (from 5 A to 500 A (primary value)) as high as possible

2. Slope k1 (ID>1) (from 0% to 50%), recommendation is 5%.

3. ID>2 (from 50 A to 50000 A (primary value))

4. Slope k2 (ID>2) (from 20% to 90%), recommendation is 65%.

5. IDCZ>2 (from 50 A to 50000 A (primary value)) as low as possible

6. Slope kCZ (IDCZ>2) (from 0% to 90%), recommendation is 30%.

7. ID>1 Alarm Timer (from 0 to 100 s) shall be greater than the longest protection time (such as line, overcurrent, etc…)

8. Current IbiasPh> Cur. (from 50 A to 50000 A (primary value)) as low as possible

9. IDN>1 (from 5 A to 500 A (primary value)), recommendation is equal to ID>1

10. Slope kN1 (IDN>1) (from 0% to 50%), recommendation is 5%.

11. IDN>2 (from 50 A to 50000 A (primary value)) as high as possible

12. Slope kN2 (IDN>2) (from 0% to 50%), recommendation is over 30%.

13. IDNCZ>2 (from 50 A to 50000 A (primary value)) as high as possible

14. Slope kNCZ (IDNCZ>2) (from 0% to 50%), recommendation is 10%.

15. IDN>1 Alarm Timer (from 0 to 100 s) recommendation = ID>1 Alarm Timer

Page 175: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-11

AP

2.2 Peripheral Unit

2.2.1 Dead Zone protection (DZ)

On a feeder, if the isolators or the breaker is open, a dead zone (or end zone) is said to exist between the open element and the CT. The P74x peripheral units can protect this zone with the Dead Zone protection. This is a simple time delayed overcurrent and earth fault element which is only active when a dead zone is identified in the local topology.

2.2.1.1 Setting guidelines

For each PU connected to a Feeder Circuit Breaker (not on bus couplers or bus sections)

For the phase:

• I>DZ must be below 80% of the minimum Dead Zone fault level (and if possible bigger than the maximum load).

• I>DZ Time delay must be at least 50ms if the CB status positions are used (any value otherwise)

For the Neutral (if used):

• IN>DZ must be below 80% of the minimum Dead Zone earth fault.

• IN>DZ Time delay must be at least 50ms if the CB status positions are used (any value otherwise)

2.2.2 Stub protection

When a one and half breaker scheme is protected by a MiCOM P74x, the stub protection can be done using a simple time delayed overcurrent element in each PU.

The activation of this protection has to be set in the PSL and activated when all the associated isolators are open.

In the main setting group (usually 1), there is no overcurrent protection, in the next setting group (usually 2) this overcurrent is enabled (on top of the same setting as in the main setting group).

The setting group will be changed from “main” to “next” in the PSL.

2.2.2.1 Setting guidelines

For each PU:

• I>1 must be below 80% of the minimum Stub fault level (and if possible bigger than the maximum load).

• The time delay can be any value.

2.2.3 Circuit Breaker Fail (CBF)

2.2.3.1 Setting guidelines

Typical timer settings to use are as follows:

CB fail reset mechanism tBF time delay Typical delay for 2 cycle circuit breaker

CB open CB auxiliary contacts opening/ closing time (max.) + error in tBF timer + safety margin

50 + 10 + 50 = 110 ms

Undercurrent elements CB interrupting time + undercurrent element (max.) + safety margin operating time

50 + 15 + 20 = 85 ms

Page 176: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-12

MiCOM P741, P742, P743

AP

The examples above consider direct tripping of a 2-cycle circuit breaker. Note that where auxiliary tripping relays are used, an additional 10-15ms must be added to allow for trip relay operation.

The phase undercurrent settings (Ι<) must be set less than load current, to ensure that Ι< operation indicates that the circuit breaker pole is open. A typical setting for overhead line or cable circuits is 20% Ιn, with 5% Ιn common for generator circuit breaker CBF.

2.2.4 External Fault Detection by High-Set Overcurrent or Earth Fault Element

There are feeders where, the short-circuit power is sufficiently low in relation to that of the busbar or external faults that the CT would saturate for an external fault within 2ms. These feeders are mainly transformer feeders where the short circuit reactance poses significant limitations, or weak outfeeders. Thus, knowing the feeder’s maximum possible contribution to the busbar fault current, it is easy to infer that exceeding this value will indicate an external fault. In these cases it is just the presence of a high current that will indicate an external fault.

In this case, CT saturation could occur very quickly. The P74x scheme may detect a fault, but a saturation condition is immediately detected and inhibits tripping.

An ultra high-speed detection is carried out by each of the peripheral units (P742 and P743) and can generate a blocking signal from the moment of the first sample at 0.42 ms.

In this scenario de-saturation may not occur until after the scheme has eliminated the saturation condition for the external fault.

This function can be activated independently for phase faults (Ι>2) and for earth faults (ΙN>2).

2.2.4.1 Application Example

3000/5A 3000/5A

3000/5A

1500/5AI>2 enabledIN>2 enabledI>2 enabledIN>2 enabled

I>2 enabledIN>2 enabledBlocking orderto 87BB element

150/5A25VA5P10

150/5A25VA5P10

ph-ph <300Aph-N 0A

TR11115/13,8K25 MVAX = 12%

ph-ph 30 000Aph-N 7 500A

TR12115/13,8K25 MVAX = 12%

Example of use of high speed detectorsI>2 and/or IN>2 to block the 87BB

element before CT saturation

P3770ENa

FIGURE 1: TRANSFORMER FEEDER EXAMPLE

An example where this facility is required and where there is a high risk of CT saturation, is shown in the above example.

Page 177: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-13

AP

The problem lies in the transformer feeder circuits TR11 and TR12 both 25 MVA 115/13.8kV rated and with a reactance of 12%. Both feeders are equipped with 150/5 A CTs. (If rating is 25 MVA I=125A @115 kV). Maximum busbar short circuit current is 30kA phase to phase and 7.5kA phase to earth.

The contribution of each transformer feeder under internal fault conditions is as follows:

1. Maximum of 1045A i.e. full load current x 1/X%, assuming infinite 13.8kV bar (which is unrealistic).

2. 0 A for phase to earth faults.

When an external fault occurs on one of these transformer feeders, the fault MVA will be the same as that for an internal fault but the feeder will be subjected to an excessively high overcurrent condition as compared to normal load conditions at rated current.

In the example shown, under the external fault condition, the short-circuit phase to phase current is 200 times the primary rated current. Taking into account the CT and initial flux estimated at 80% of that at full load, saturation will be detected at 10 times In, where In is the CT nominal current – in this case in primary values (150 A x 10 = 1500 A)

With Ιsaturation = 1500 A and Ιshort-circuit = 30000 A = 20 x Ιsaturation.

If the assumption is taken that there is no remnant flux, saturation will be detected 1.4 ms after the appearance of the fault at which time the current will have reached 0.4 times the maximum value i.e. 1200 A.

Conclusion: An ultra fast Overcurrent detector in the P742 and P743 when used on HV/MV transformer feeders makes it possible to pre-empt CT saturation and establish an external fault condition. The setting used for this detection is Ι>2 for phase faults and ΙN>2 for earth faults.

In this example a setting of 1305 A can be used for both phase and earth faults.

2.2.5 Setting guidelines

A spreadsheet tool called “FastExtThreshold” is available on request.

This feature has to be used when the CT does not meet the CT requirements and if the maximum feeder contribution is far less than the maximum external fault.

For each PU connected to a Circuit Breaker

2.2.5.1 CT features:

Only 5 values have to be known and entered:

1. Phase CT Primary current given by the manufacturer.

2. Phase CT secondary current (1 or 5 A) given by the manufacturer.

3. CT secondary resistance given by the manufacturer.

4. Secondary burdens to be measured.

5. Knee point Voltage (or Rated Burden and KSCC) given by the manufacturer.

2.2.5.2 Sub-station features

1. Maximum feeder load

2. Feeder contribution to internal fault

2.2.5.3 Please use FastExtThreshold Setting calculation spreadsheet

Put for I>2 the recommended value.

Page 178: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-14

MiCOM P741, P742, P743

AP

3. CURRENT TRANSFORMERS It is important that the CT settings are entered in full as these are required to calculate additional parameters for use in the saturation detection algorithms that run within the peripheral units .

A P74x scheme can accommodate different CT ratios throughout the protected zone, the maximum difference being 40. In other words, the maximum ratio between the smallest primary CT winding and the biggest primary CT winding is 40. This mix must, therefore, be accounted for by the scheme and this is achieved by using the primary currents sent by the Peripheral Units to the central unit that undertakes scheme calculations.

In the P741, a common virtual current transformer of 1000/1 A is used to convert to secondary values.

Page 179: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-15

AP

4. CIRCUIT BREAKER FUNCTION

4.1 Circuit breaker state monitoring

An operator at a remote location requires a reliable indication of the state of the switchgear. Without an indication that each circuit breaker is either open or closed, the operator has insufficient information to decide on switching operations. The relay incorporates circuit breaker state monitoring, giving an indication of the position of the circuit breaker, or, if the state is unknown, an alarm is raised.

4.2 Trip relays and Trip Circuit Supervision

Relays contacts 1, 2, and 3 of every PU are used for tripping signals from busbar protection, overcurrent protection and back-trip breaker failure. Even if these relay contacts 1, 2, and 3 are not used in the PSL, they are closed if there is a trip command from these functions listed above. However these relays can be affected in PSL for additional functions (breaker-failure retrip for example).

The dwell time of these three contacts is controlled by the [CB CONTROL, Prot Trip Pulse] setting and ensures that a minimum tripping duration is always applied.

The trip circuit, in most protective schemes, extends beyond the relay enclosure and passes through components such as fuses, links, relay contacts, auxiliary switches and other terminal boards. This complex arrangement, coupled with the importance of the trip circuit, has led to dedicated schemes for its supervision.

Several trip circuit supervision schemes with various features can be produced with the P74x range. Although there are no dedicated settings for TCS, in the P74x, the following schemes can be produced using the programmable scheme logic (PSL). A user alarm is used in the PSL to issue an alarm message on the relay front display. If necessary, the user alarm can be re-named using the menu text editor to indicate that there is a fault with the trip circuit.

4.2.1 TCS scheme 1

4.2.1.1 Scheme description

P2228ENa

Optional

FIGURE 2: TCS SCHEME 1

This scheme provides supervision of the trip coil with the breaker open or closed, however, pre-closing supervision is not provided. This scheme is also incompatible with latched trip contacts, as a latched contact will short out the opto for greater than the recommended DDO timer setting of 400ms. If breaker status monitoring is required a further 1 or 2 opto inputs must be used. Note: a 52a CB auxiliary contact follows the CB position and a 52b contact is the opposite.

When the breaker is closed, supervision current passes through the opto input, blocking diode and trip coil. When the breaker is open current still flows through the opto input and into the trip coil via the 52b auxiliary contact. Hence, no supervision of the trip path is provided whilst the breaker is open. Any fault in the trip path will only be detected on CB closing, after a 400ms delay.

Page 180: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-16

MiCOM P741, P742, P743

AP

Resistor R1 is an optional resistor that can be fitted to prevent maloperation of the circuit breaker if the opto input is inadvertently shorted, by limiting the current to <60mA. The resistor should not be fitted for auxiliary voltage ranges of 30/34 volts or less, as satisfactory operation can no longer be guaranteed. The table below shows the appropriate resistor value and voltage setting (OPTO CONFIG. menu) for this scheme.

This TCS scheme will function correctly even without resistor R1, since the opto input automatically limits the supervision current to less that 10mA. However, if the opto is accidentally shorted the circuit breaker may trip.

Auxiliary Voltage (Vx) Resistor R1 (ohms) Opto Voltage Setting with R1 Fitted

24/27 - -

30/34 - -

48/54 1.2k 24/27

110/250 2.5k 48/54

220/250 5.0k 110/125

Note: When R1 is not fitted the opto voltage setting must be set equal to supply voltage of the supervision circuit.

TABLE 1: SCHEME 1 OPTIONAL R1 OPTO INPUT RESISTOR VALUES

4.2.2 Scheme 1 PSL

Figure 2 shows the scheme logic diagram for the TCS scheme 1. Any of the available opto inputs can be used to indicate whether or not the trip circuit is healthy. The delay on drop off timer operates as soon as the opto is energized, but will take 400ms to drop off/reset in the event of a trip circuit failure. The 400ms delay prevents a false alarm due to voltage dips caused by faults in other circuits or during normal tripping operation when the opto input is shorted by a self-reset trip contact. When the timer is operated the NC (normally closed) output relay opens and the LED and user alarms are reset.

The 50ms delay on pick-up timer prevents false LED and user alarm indications during the relay power up time, following an auxiliary supply interruption.

!"

#$%&

''"!

FIGURE 3: PSL FOR TCS SCHEMES 1 AND 3

Page 181: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-17

AP

4.2.3 TCS scheme 2

4.2.3.1 Scheme description

Optional

Optional

P2230ENa

FIGURE 4: TCS SCHEME 2

Much like scheme 1, this scheme provides supervision of the trip coil with the breaker open or closed and also does not provide pre-closing supervision. However, using two opto inputs allows the relay to correctly monitor the circuit breaker status since they are connected in series with the CB auxiliary contacts. This is achieved by assigning Opto A to the 52a contact and Opto B to the 52b contact. Provided the “Circuit Breaker Status” is set to “52a and 52b” (CB CONTROL column) the relay will correctly monitor the status of the breaker. This scheme is also fully compatible with latched contacts as the supervision current will be maintained through the 52b contact when the trip contact is closed.

When the breaker is closed, supervision current passes through opto input A and the trip coil. When the breaker is open current flows through opto input B and the trip coil. As with scheme 1, no supervision of the trip path is provided whilst the breaker is open. Any fault in the trip path will only be detected on CB closing, after a 400ms delay.

As with scheme 1, optional resistors R1 and R2 can be added to prevent tripping of the CB if either opto is shorted. The resistor values of R1 and R2 are equal and can be set the same as R1 in scheme 1.

4.2.4 Scheme 2 PSL

The PSL for this scheme (Figure 4) is practically the same as that of scheme 1. The main difference being that both opto inputs must be off before a trip circuit fail alarm is given.

%

(

(%)* "+,

-

!"

#

#$%&

'"! '

(%)* "+.,

-/0.

FIGURE 5: PSL FOR TCS SCHEME 2

Page 182: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-18

MiCOM P741, P742, P743

AP

4.2.5 TCS scheme 3

4.2.5.1 Scheme description

P2231ENa

FIGURE 6: TCS SCHEME 3

Scheme 3 is designed to provide supervision of the trip coil with the breaker open or closed, but unlike schemes 1 and 2, it also provides pre-closing supervision. Since only one opto input is used, this scheme is not compatible with latched trip contacts. If circuit breaker status monitoring is required a further 1 or 2 opto inputs must be used.

When the breaker is closed, supervision current passes through the opto input, resistor R2 and the trip coil. When the breaker is open current flows through the opto input, resistors R1 and R2 (in parallel), resistor R3 and the trip coil. Unlike schemes 1 and 2, supervision current is maintained through the trip path with the breaker in either state, thus giving pre-closing supervision.

As with schemes 1 and 2, resistors R1 and R2 are used to prevent false tripping, if the opto-input is accidentally shorted. However, unlike the other two schemes, this scheme is dependent upon the position and value of these resistors. Removing them would result in incomplete trip circuit monitoring. The table below shows the resistor values and voltage settings required for satisfactory operation.

Auxiliary Voltage (Vx)

Resistor R1 & R2 (ohms) Resistor R3 (ohms) Opto Voltage

Setting

24/27 - - -

30/34 - - -

48/54 1.2k 0.6k 24/27

110/250 2.5k 1.2k 48/54

220/250 5.0k 2.5k 110/125

Note: Scheme 3 is not compatible with auxiliary supply voltages of 30/34 volts and below.

TABLE 2: SCHEME 3 OPTIONAL R1, R2 & R3 OPTO INPUT RESISTOR VALUES

4.2.6 Scheme 3 PSL

The PSL for scheme 3 is identical to that of scheme 1 (see Figure 2).

Page 183: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-19

AP

5. ISOLATION AND REDUCED FUNCTION MODE The scheme permits maintenance on the busbar and, or busbar protection whilst maintaining some form of protection if possible. Two maintenance mode levels in the Central Unit and two maintenance mode levels in the Peripheral Units allow this to be possible. A command to one or more of the affected units will then force the scheme to a selected (reduced) operating mode. The levels are as follow.

5.1 Normal mode

Central Unit: Normal mode

Currents,Topology,

50BF Back-trip...

Feeder In Service

BayProtection

Peripheral Unit

Trips

50/51DZ- Etc... 50BF

P0707ENb

5.2 Peripheral Units (P742 and P743)

Two levels of command can be applied selectively to each peripheral unit.

5.2.1 CB Failure Protection (50BF) disabled

In this mode, all tripping information from external relay are not taken into account. The topology algorithm forwards the feeder positions to the central unit as normal. As the peripheral unit continues to monitor the analogue values the central unit will maintain a balanced condition with the remainder of the system still in normal operation. However, the CB failure backtrip information will not be sent to the Central Unit. The local protections (Dead Zone, Overcurrent, Earth Fault) are still enabled and the PU is able to retrip the breaker. However, the Peripheral Unit is able to react to a fault condition by creating a CB fail condition and back tripping the zone(s) if the CU sends a trip order (87BB or 50BF backtrip), to clear a genuine fault).

Page 184: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-20

MiCOM P741, P742, P743

AP

To test other protection relays such as Distance, Feeder...

50BF

Feeder In Service

Primary current flowing

Central Unit: Normal mode

Trips

50/51DZ- Etc...

50BF

Currents, Topology

Isolation to beexternaly done

P0708ENb

To test other protection relays such as Distance, Feeder...

50BF

Feeder In Service

Primary current flowing

Central Unit: Normal mode

Trips

50/51DZ- Etc...

50BF50BF

Currents, Topology

Isolation to beexternaly done

P0708ENb

FIGURE 7: PU – 50BF DISABLED

5.2.2 Overhaul

* The status positions can be forced closed.If so a busbar trip could occur if the CU is not in maintenance mode.

Feeder Out of Service

Both isolators and CB forced

Open*No primary

current

50BF

Central Unit: Normal mode

Currents, Topology

No Trips

To test the PU

50/51DZ- Etc... 50BF

P0709ENb

* The status positions can be forced closed.If so a busbar trip could occur if the CU is not in maintenance mode.

Feeder Out of Service

Both isolators and CB forced

Open*No primary

current

50BF50BF

Central Unit: Normal mode

Currents, Topology

No Trips

To test the PU

50/51DZ- Etc... 50BF

P0709ENb

FIGURE 8: PU – OVERHAUL

In this mode the feeder is totally disconnected from the system because all the isolators are open but all information is passed back to the central unit for inclusion in zone calculations and hence the protection scheme. Hence the central unit can keep the zone elements in service as the contribution of this feeder will be zero. (The CT is still used by the Check Zone element)

Whilst in this mode the peripheral unit can be tested locally for example secondary injections tests can be carried out.(The system is stable because during the current injection there is a differential current in the CZ but not in the Zone)

Page 185: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-21

AP

No 87 BB trip order

to relevant CB ’s

Feeder In Service

At least one isolator and

the CB closed

CU: 87BB&50BF blocked

Currents, Topology

NO Trips

To test the PU & CU

50/51DZ- Etc... 50BF

Isolation to beexternaly done

P0710ENb

No 87 BB trip order

to relevant CB ’s

Feeder In Service

At least one isolator and

the CB closed

CU: 87BB&50BF blocked

Currents, Topology

NO Trips

To test the PU & CU

50/51DZ- Etc... 50BF

Isolation to beexternaly done

P0710ENb

21-50BF ...

Response of the Differential Elements

Example 1 of forced scheme =

Feeder connectedto BB2

I load

BB1

BB2

Z1, Id 1=-i load

Z2, Id 2=+i load

Total Zone , Σ Id = 0

+ i load+ i load

Example 2 of forcedscheme = Feeder

disconnected

Z1, Id 1=-i load

End Z, Id =+i load

Total Zone , Σ Id = 0

Examplescheme:Feeder

connected to BB1

No statusindication

to PU

P0711ENb

21-50BF ...

Response of the Differential Elements

Example 1 of forced scheme =

Feeder connectedto BB2

I load

BB1

BB2

Z1, Id 1=-i load

Z2, Id 2=+i load

Total Zone , Σ Id = 0

+ i load+ i load

Example 2 of forcedscheme = Feeder

disconnected

Z1, Id 1=-i load

End Z, Id =+i load

Total Zone , Σ Id = 0

Examplescheme:Feeder

connected to BB1

No statusindication

to PU

P0711ENb

FIGURE 9 FORCING PLANT POSITION STATE

Under certain conditions it may be desirable to force the positions of the primary plant to enable scheme testing to be carried out, for example during commissioning.

In the first example the forced scheme theoretically connects the feeder to busbar 2, whilst in practice it is connected to busbar 1. Zone 1 will see a differential current equal to –iload whilst zone 2 will see a differential current equal to +iload this will give a check zone equal to zero.

In the second example the forced scheme theoretically totally disconnects the feeder. An end zone or extra node, is created by the topology in order to fully replicate the scheme. This lies between the feeder CT and the circuit breaker.

However, it must be remembered that in practice the feeder is still connected to busbar 1. Zone 1 will see a differential current equal to –iload. This extra node will see a differential current equal to +iload and which when included in the check zone will give a result equal to zero.

If done, to avoid any maloperation, the Central Unit must be in 87BB blocking mode while performing these forcings

Page 186: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-22

MiCOM P741, P742, P743

AP

5.3 Central processing unit (P741)

A central instruction for a reduced operation mode of the busbar protection on two levels can be applied selectively zone by zone.

5.3.1 Busbar protection (87BB) Blocked

The busbar protection is monitored only (not protected by 87BB) (i.e. all BB protection trips are inhibited and measurements are enabled). All other protection remains in service and trips can still be issued for genuine CBF conditions.

5.3.2 87BB Blocked & 50BF disabled

In this mode, both the busbar and circuit breaker fail conditions are monitored but all trips are inhibited.

Additionally, all protection functions are disabled when the system is awaiting configuration downloads (topology is missing).

5.4 System operation under failed communications situation

With each start or reboot of the CU, all the zones are set to 87BB and 50BF disabled mode as described above. They will remain in this mode until all peripheral units are recognised as being in service and synchronised. (PU CONF & STATUS/PU in service).

If a PU that was considered to be out of service but suddenly communicates with the CU, the CU automatically places all zones to a waiting system configuration mode while waiting for an input from the user to either assign the PU in service or disconnect additional PUs.

During operation, if the communication with a PU is broken during a very short time, the zone connected to the CT of the non-communicating PU is temporarily suspended. If the communication is restored, the differential protection is restored for the zone. On the other hand, if the break in communications persists longer than permitted as given by the PU Error Timer, the zone protection is suspended.

If the PU error self-reset mode is disabled, for the reinstatement of the zone the user must intervene:

• If communication is restored the user must reset the alarm by the same command to reset PU Error (PU CONF & STATUS -> Reset PU Error)

If the PU error self-reset mode is enabled, the reinstatement of the zone will be automatically done after the set timer delay

On the PU, an alarm will indicate loss of communication with the CU.

On the CU, an alarm will indicate that one or more PUs are no longer synchronised.

In the PU CONF & STATUS column, it is possible to view the list of synchronised PU (PU connected) after having altered the list of PU in service (PU in service).

If at the time of the initial start-up, the topology of the substation was implemented including futures (for example 15 PU including 6 extensions) it is possible to boot the system only activating the existing 9 PUs in the cell PU in service. When the futures 6 PUs are connected, it will be sufficient to connect them and indicate that they are now in service in the CU menu columns.

5.5 Waiting Configuration

Alarm “Config error” occurs when the configuration is incorrect:

• Topology download in relay does not correspond to this relay address (be careful to erase topology by sending a default setting file)

• For CU: check the coherency of threshold: [IDCZ>2] > [ID>1] and [ID>2] > [ID>1] and [IDNCZ>2] > [IDN>1] and [IDN>2] > [IDN>1]

Page 187: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-23

AP

6. TOPOLOGY The topological analysis of the state of the substation in real time is one of the primary factors of the reliability of numerical differential busbar protection. Thus in the case of a power system fault, this analysis determines the sections of the substation concerned with the fault and only takes those sections out of service. The algorithms available for topological analysis make this level of discrimination possible and it is these algorithms that are utilized in the P74x scheme.

6.1 Topology Configuration Tool

For the P74x scheme the system topology is determined by replication of the circuit, i.e. the connections between the various pieces of plant on the system, via a graphical interface. This topological replication is carried out from a single line diagram of the system, which is used to recreate the system using the topology configuration software. This is carried out by Alstom Grid personnel at an authorised Alstom Grid competence centre or by the customer for extensions after having successfully completed the dedicated training.

In that case, we’ll be very pleased to provide the installation code that is required to install the MiCOM P74x configuration tools (during installation, it will be required to enter this code).

It should be considered that use of the P74x Scheme Editor and Synoptic without appropriate training and careful consideration can be extremely hazardous. To remind you of this, every time the tools are launched the following “pop-up” message will be displayed:

FIGURE 10: P74x SCHEME EDITOR

Page 188: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-24

MiCOM P741, P742, P743

AP

FIGURE 11: P74x SYNOPTIC

The topology configuration tool uses standard symbols for creating the system model by simply dragging and dropping in the configuration screen.

Bar

Link

Node

Current Transformer Feeder

Circuit Breaker (CB) Isolator

FIGURE 12: TOPOLOGY CONFIGURATOR OBJECTS

The switchgear/busbars are then labelled and assigned to relevant peripheral units.

When the topology has been fully defined it is compiled and then downloaded to each PU and the CU.

6.2 Nodal Assignment

Four files are created from the topological model. The first identifies each piece of primary plant such as circuit breakers, isolators, current transformer (CT), bus section and feeders. The second file identifies the connections between each piece of primary plant and the third calculates the topological nodal assignment thus making it possible to link to each peripheral unit with associated primary plant of the system. The fourth file will be used by the Dynamic Synoptic software to visualise in real time the substation.

Algorithms search to determine the electrical topology. These operate in real time in the P74x scheme. They start with the information obtained regarding the state of the primary plant. A state table is created and associated with each device. According to the algorithm, this state table gathers the data related to the physical states of the primary plant taken by the unit.

The results of these algorithms are then subjects of a further algorithm, developed from operational research. This algorithm identifies commonality between nodes and merges nodes where appropriate. The new node includes all common nodes.

The principal characteristics of this algorithm mean that the scheme has the following benefits:

• Adaptability to various substation configurations

• Permanent identification of current nodes

• Permanent identification of physical links for each zone

• Reference to the neighbouring circuit breakers for each point of the circuit

Page 189: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-25

AP

• These algorithms offer flexibility to the operator not met in non-numeric conventional systems.

• The global substation topology is updated every 16ms.

The above improve the overall function and discrimination of the protection scheme and therefore reliability of the network.

6.3 Topology Communication

The peripheral units relay the information regarding their associated topological model to the central unit. The central unit gathers the information from all attached peripheral units and calculates the topological scheme for these as well as carrying out the calculations for the system topology.

6.4 Topology data

Topology results are displayed in Central Unit and locally in Peripheral Units and can be visualised in real time using the Dynamic Synoptic software.

For the Central Unit, zones included in each current node are displayed in Topology 1 column and current transformer (or Peripheral Unit) included in each current node are displayed in Topology 2 column.

2 bars with 1 CT coupling example:

Node 1 = Zone 1; Node 2 = Zone 2

If the two zones are shunt by a feeder switches:

Node 1 = Zone 1 and Zone 2; Node 2 is then removed

2 bars with 2 CT coupling example:

Node 1 = Zone 1; Node 2 = Zone 2

A Node 3 is created when the coupling breaker is closed.

For the Peripheral Unit, link between current transformer and zones are displayed in Topology column.

2 bars with 1 CT coupling example:

• The feeder PUs connected to Zone 1 are connected to Node 1

• The feeder PUs connected to Zone 2 are connected to Node 2 (if existing)

• The coupling PU is connected to the both nodes when the breaker is closed and to none when the breaker is open

2 bars with 2 CT coupling example:

• The feeder PUs connected to Zone 1 are connected to Node 1

• The feeder PUs connected to Zone 2 are connected to Node 2 (if existing)

• The coupling PUs are connected to Node 3 and the appropriate node when the breaker is closed and to none when the breaker is open

The bias and differential currents for the connected zone are displayed.

Note: If the topology scheme is equipped with a transfer bus outside the protection zone, this link is never reported in Topology column because the current transformer is connected to the feeder.

Page 190: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-26

MiCOM P741, P742, P743

AP

6.5 Topology processing

The following scenarios demonstrate how the dynamic topology processing accommodates anomalies and discrepancies in the scheme.

6.5.1 CTs on one side of bus coupler, CB closes before status acquisition.

BB1 BB2IExtFault through CB

CB CLOSEDbut auxiliary

contact OPEN

CT removedfrom Zone 1

Zone 1 Zone 2

IdiffZ1= - iExtFault IdiffZ2 = + iExtFault

1 CT coupler and CB Closes on to external fault before Status Acquisition

Check zone Idiff = Σ idifffeeder = i7 + i8 + i10 + i11 = [- IExtFault ] + [IExtFault ] = 0

i7

i8

i11

i10

P0701ENb

BB1 BB2IExtFault through CB

CB CLOSEDbut auxiliary

contact OPEN

CT removedfrom Zone 1

Zone 1 Zone 2

IdiffZ1= - iExtFault IdiffZ2 = + iExtFault

1 CT coupler and CB Closes on to external fault before Status Acquisition

Check zone Idiff = Σ idifffeeder = i7 + i8 + i10 + i11 = [- IExtFault ] + [IExtFault ] = 0

i7

i8

i11

i10

P0701ENb

FIGURE 13: CT’S ON ONE SIDE OF BUS COUPLER, CB CLOSES BEFORE STATUS ACQUISITION

As the CB has closed but the status has not yet been refreshed the topology still believes the CB to be open.

Treating this as an open bus coupler circuit breaker the topology algorithm will have extended Zone 1(with the area located between the CT and the circuit breaker). This then fully replicates the scheme up to the open bus coupler CB on both sides.

If the circuit breaker was open no load current would flow through the circuit breaker. The differential current in the two main zones would equal zero, as the current flowing into the zones would still equal the current flowing out.

However, if the circuit breaker is actually closed, the external fault current will flow through the circuit breaker. The differential current in main zone 1 and in main zone 2 will be equal in magnitude but opposite in sign. (±fault)

When the check zone element is calculated, the differential currents seen in zone 1 and 2, which result from the discrepancy in the plant status, can be seen to be cancelled out.

Zone 1 Idiff = I7+ I8= idiffZ1 = -ifault > (ID>2 + k2 x IBias)

Zone 2 Idiff = I10+ I11=idiffZ2 = +ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11=(-ifault) + (+ifault) = ∅

Again the system retains its stability for discrepancies in plant status (even for switch onto fault).

Page 191: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-27

AP

6.5.2 CTs on both sides of bus coupler, CB closes before status acquisition.

Check zone Idiff = Σ idifffeeder = i7 + i8 + i10 + i11 = [- iExtFault ] + [ iExtFault ] = 0

BB1 BB2IExtFault through CB

CB CLOSEDbut auxiliary

contact OPEN

CT removedfrom Zone 1

CT removedfrom Zone2

Zone 1 Zone 2

IdiffZ1= - iExtFault IdiffZ2 = + iExtFault

2 CT Coupler and CB Closes on to external fault before Status Acquisition

i8

i7

i10

i11

P0702ENb

FIGURE 14: CT’S ON BOTH SIDES OF BUS COUPLER, CB CLOSES BEFORE STATUS ACQUISITION

As the CB has closed but the status has not yet been refreshed the topology still believes the CB to be open.

Treating this as an open bus coupler the topology algorithm will have extended the two zones with the areas located between the CTs and the circuit breaker. These then fully replicate the scheme up to the open bus coupler CB on both sides.

If the circuit breaker was open no load current would flow through the circuit breaker. The differential current in the two main zones would equal zero, as the current flowing into the zones would still equal the current flowing out.

However, if the circuit breaker is actually closed, the external fault current will flow through the circuit breaker. The differential current in the two main zones will be equal in magnitude but opposite in sign. (±ifault)

When the check zone element is calculated, the differential currents seen in the two main zones, which result from the discrepancy in the plant status and which are taken into account for the check zone calculation, can be seen to be cancelled out.

Zone 1 Idiff = I7+ I8= idiffZ1 = -ifault > (ID>2 + k2 x IBias)

Zone 2 Idiff = I10+ I11=idiffZ2 = +ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11=(-ifault) + (+ifault) = ∅

Hence, the system retains its stability even when there are discrepancies in plant status.

Page 192: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-28

MiCOM P741, P742, P743

AP

6.5.3 CTs on one side of bus coupler, CB closed and fault evolves between CT and CB (even for switch onto fault).

BB1 BB2Zone 1 Zone 2

1 CT Coupler with CB closed - Fault clearance - Stage 1

IdiffZ1= 0 IdiffZ2= Ifault

Check zone Idiff = Σ idifffeeder = i7 + i8 + i10 + i11 = 0 + iFault

i8

i9i7

i10

i11

P0703ENb

FIGURE 15: CT’S ON ONE SIDE OF BUS COUPLER, CB CLOSED AND FAULT OCCURS BETWEEN THE CB & THE CT

Treating this as a closed bus section circuit breaker the topology algorithm will have extended the limits of the main zones to the bus coupler CT. This then fully replicates the scheme.

Under normal operating conditions when the circuit breaker is closed load current would flow through the circuit breaker and differential current in the two main zones would equal zero, as the current flowing into the zones would still equal the current flowing out.

However, if a fault occurs between the CT and the circuit breaker, the current will flow from zone 1 into zone 2 which feeds the fault. The differential current in main zone 1 will still equal zero, as the current flowing into the zone 1 will still equal the current flowing out, but the differential current measured in zone 2 will be equal to that of the fault current.

In this case zone 2 would operate as will the check zone element.

Zone 1 Idiff = I7+ I8+ I9= idiffZ1 = 0

Zone 2 Idiff = I9+ I10+ I11=idiffZ2 = ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11= idiffZ2 = ifault > (IDCZ>2 + kCZ x IBias)

Page 193: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-29

AP

However, when zone 2 trips the fault will still be present. The topology then analyses the remainder of the system as follows.

Zone 1 Zone 2

1 CT Coupler with CB closed - Fault clearance - Stage 2(zone 2 tripped but fault still present.)

Check zone Idiff = Σ idiff = i7 + i8 + i10 + i11 = iFault

IdiffZ1= Ifault IdiffZ2= 0

i8

i7

i10

I11CT removedfrom Zone 1

P0704ENb

Zone 1 Zone 2

1 CT Coupler with CB closed - Fault clearance - Stage 2(zone 2 tripped but fault still present.)

Check zone Idiff = Σ idiff = i7 + i8 + i10 + i11 = iFault

IdiffZ1= Ifault IdiffZ2= 0

i8

i7

i10

I11CT removedfrom Zone 1

P0704ENb

FIGURE 16: ZONE 2 TRIPPED, FAULT STILL PRESENT

Treating this as an open bus coupler circuit breaker as before the topology algorithm will have extended zone 1 with the area located between the CT and the circuit breaker. This then fully replicates the scheme up to the open bus coupler CB. Remember that in this example zone 2’s limit extended up to the circuit breaker but this zone has been tripped already.

The circuit breaker is now open and the fault current would flow to feed the fault. The differential current in the main zone 2 would equal zero, as the current is flowing into zone 1 whereas the current measured will be equal to the fault current ifault.

Zone 2 Idiff = I10+ I11= idiffZ2 = 0

Zone 1 Idiff = I7+ I8=idiffZ1 = ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11=idiffZ1 = ifault > (IDCZ>2 + kCZ x IBias)

Hence, the system reacts to the continuing presence of the fault and trips the zone 1 as the check zone Idiff > (IDCZ>2 + kCZ x IBias) and the zone Idiff > (ID>2 + k2 x IBias).

In this example it can be seen that the opposite zone is tripped first but the dynamic topology reacts to the changed scheme and subsequently trips the adjacent main zone.

Page 194: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-30

MiCOM P741, P742, P743

AP

6.5.4 CTs on both sides of coupler, CB closed and fault evolves between CT and CB.

VZ

Zone 1 Zone 2BB1 BB2

IdiffZ1= 0 IdiffZ2 = 0

2 CT Coupler with the CB Closed and Fault between a CT and the CBIdiffZ3 = IFault

Check zone Idiff = Σ idiff = i7 + i8 + i10 + i11 = iFault

i8

i7

i10

i11

P0705ENb

VZ

Zone 1 Zone 2BB1 BB2

IdiffZ1= 0 IdiffZ2 = 0

2 CT Coupler with the CB Closed and Fault between a CT and the CBIdiffZ3 = IFault

Check zone Idiff = Σ idiff = i7 + i8 + i10 + i11 = iFault

i8

i7

i10

i11

P0705ENb

FIGURE 17: CT’ ON BOTH SIDES OF BUS COUPLER, CB CLOSED FAULT OCCURS BETWEEN A CT & THE CB

Treating this as a closed bus section circuit breaker the topology algorithm will have created a virtual zone that surrounds the circuit breaker with the bus coupler CTs as its limits called zone 3 in the event report and measurements. This then fully replicates the scheme.

Under normal operating conditions when the circuit breaker is closed load current would flow through the circuit breaker and hence the virtual zone. The differential current in the two main zones would equal zero, as the current flowing into the zones would still equal the current flowing out. This is also the case for the virtual zone around the bus coupler.

However, if a fault was to occur in the virtual zone, current would flow into the virtual zone and feed the fault. The differential current in the two main zones will still equal zero, as the current flowing into the zone(s) will still equal the current flowing out, but the differential current measured in the virtual zone will be equal to that of the fault current.

The main zones would not operate but the virtual zone or zone 3, which surrounds the bus coupler and has limits at the bus coupler CTs would operate. When the check zone element is calculated, the differential current seen in the virtual zone or zone 3, which results from the presence of the fault in the coupler, will confirm the presence of a fault and initiate either (1) a simultaneous trip of both main zones or (2) a step by step trip of, first the coupler then, once the topology has been refreshed, the faulty zone 1 (longer fault clearance: around 60 ms + 2 x opening time of the breakers).

(1) Hence, the system reacts to a fault occurring between the CT and the CB simultaneously tripping both adjacent zones.

Zone 1 Idiff = I7+ I8+ I9=idiffZ1 = 0

Zone 2 Idiff = I10+ I11+ I12= idiffZ2 = 0

Zone 3 Idiff = I9+ I12= idiffZ2 = ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11=idiffZ3 = ifault

Page 195: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-31

AP

(2) The bus coupler can operate first for a fault in the virtual zone or zone 3 and then the faulty zone 1, zone 2 will remain in service. For such operation a special topology scheme should be used.

First:

Zone 1 Idiff = I7+ I8+ I9=idiffZ1 = 0

Zone 2 Idiff = I10+ I11+ I12= idiffZ2 = 0

Zone 3 Idiff = I9+ I12= idiffZ2 = ifault > (ID>2 + k2 x IBias)

Check zone Idiff = I7+ I8+ I10+ I11= idiffZ3 = ifault > (IDCZ>2 + kCZ x IBias)

After the coupling breaker has been tripped:

Zone 1 Idiff = I7+ I8=idiffZ1 = ifault > (ID>2 + k2 x IBias)

Zone 2 Idiff = I10+ I11= idiffZ2 = 0

Check zone Idiff = I7+ I8+ I10+ I11= idiffZ1 = ifault > (IDCZ>2 + kCZ x IBias)

Note 1: As the topology algorithm scheme updates every 16ms. The longest time to updates the topology after Isolator auxiliary contacts change state is 33ms.

Note 2: For the Differential Busbar protection, the status positions of the Breakers are not taken into account.

Page 196: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-32

MiCOM P741, P742, P743

AP

7. UNDERTAKING A NUMERICAL DIFFERENTIAL BUSBAR PROTECTION PROJECT This Engineering must be done by a P74x Competency Centre

The substation construction will influence the protection scheme installed. It is advisable that a scheme evaluation is conducted as soon as possible, preferably at the same time as the definition of the equipment specification.

7.1 Check list

The following steps must be performed:

Engineering phase:

1. Check the CT compliance (using VkTest.xls & Rct_Approx.xls)

2. Design the Junction schemes (using AUTOCAD (or equivalent))

3. Create the material definition and the wiring plans (distributed or centralised version)

4. Create the wiring diagram (distributed version)

5. Label the relay Inputs & Outputs (using MiCOM S1 Setting (per Group))

6. Calculate the Central Unit settings (using Idiff_Ibias_xxx.xls & P74x setting guide)

7. Calculate the different Peripheral Units settings (transformer, coupler, line, etc…)

8. Draw the topology line diagram (using Scheme Editor and Topology Tips)

9. Create the topology files (using Synoptic Editor and Topology Tips)

10. Merge the parameter files with the topology files (using P74x File Merger)

11. Merge the testing parameter files with the topology files (using P74x File Merger)

12. Create the CU PSL file (using MiCOM S1 & Tips)

13. Create the PU PSL files (using MiCOM S1 & Tips)

14. Print out the front panel Labels (CU & PUs) (using P74x_Stickers.xls)

15. Write up the test specification

16. Write up the insulation test specification (centralised version)

After Reception of the relays & KITZ(s): Testing phase:

1. Stick the labels on the front of the CU & PUs

2. Mount the relays in the (or a) cubicle

3. Wire them to the Substation Simulation Box(es)

4. Put the right addresses into the relays (CU = 06, PU from 07)

Page 197: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-33

AP

5. Put the right addresses into the KITZs (using comms.xls)

6. Download the complete setting files into the relays (using MiCOM S1)

7. Download the setting files into the KITZs (using comms.xls)

8. Download the PSL files into the relays (using MiCOM S1)

9. Test the PSLs & Analogue inputs (using a Inputs / Outputs and current generator)

10. Put the default Substation Testing Box relay settings (using MiCOM S1)

11. Test the Topology according to the test specification

12. Test the communication links (KITZ) (using Master (courier))

13. Perform the FAT with the customer

14. Put the project relay settings (using MiCOM S1)

Commissioning phase:

1. Check the inputs / outputs

2. Check CT connections (per phase (A, then B, then C))

3. Add Rb & Rbph/Rbn CT parameters in the Pus (using RBurden_b.xls)

4. Check the measurements and the tripping slopes (see documentation)

7.2 General Substation information

Only a few system parameters are required and it is vital that these are included.

• Number of feeders, bus couplers, bus sections

• Positions of bus sections

• Positions of switchgear plant i.e. circuit breakers, isolators

• Positions of CTs (including the polarity (P1/P2 – S1/S2))

• Planned future extensions with circuit breaker, isolator and current transformer (CT)

• Type of electrical network earthing (Solid, High impedance or compensated)

7.3 Short Circuit Levels

Maximum external fault current (phase to phase and phase to ground faults)

• Solid:

- Minimum two phase busbar fault current

- Minimum load current on the smallest feeder

- Maximum load current on the biggest feeder or coupler

- Optional: Maximum three phase busbar fault current

Page 198: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-34

MiCOM P741, P742, P743

AP

• Compensated:

- Minimum two phase busbar fault current

- Maximum single-phase steady state busbar fault current

- Maximum load current on the biggest feeder

- Optional: Maximum three phase busbar fault current

• With impedance:

- Minimum two phase busbar fault current

- Minimum single phase to earth busbar fault current

- Minimum load current on the smallest feeder

- Maximum load current on the biggest feeder

- Optional: Maximum three phase busbar fault current

Maximum substation short-circuit withstand time

7.4 Switchgear

• Nominal CT ratio

• Highest nominal primary current (CT In Max)

• Lowest nominal primary current (CT In Min)

• CT Knee point voltage (Vk) for each CT

• CT secondary resistance (RCT) for each CT

• Length and cross section of the conductors between each CT and the peripheral unit. (In the absence of precise information, an estimate taken from the lowest CT ratio will suffice).

• Auxiliary contacts of disconnecting switches and tripping orders for circuit breaker failure (irrespective of the how the CB fail scheme is to be implemented i.e. internally or externally initiated).

7.5 Cubicle specifications

• Cubicle specification is contract specific.

• However, Alstom Grid propose the following:

• Single cubicle: 800x800x2000

• Double cubicle: 1600x800x2000

• Model: Schroff type Proline

• Colour: RAL 7032

1 P741 and P742:

Page 199: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-35

AP

15 P742 P742 16

13 P742 P742 14 1 P742 P742 2 17 P742 P742 18

1 P742 P742 2 15 P742 P742 16 3 P742 P742 4 19 P742 P742 20

3 P742 P742 4 17 P742 P742 18 5 P742 P742 6 21 P742 P742 22

5 P742 P742 6 19 P742 P742 20 7 P742 P742 8 23 P742 P742 24

7 P742 P742 8 21 P742 P742 22 9 P742 P742 10 25 P742 P742 26

9 P742 P742 10 23 P742 P742 24 11 P742 P742 12 27 P742 P742 28

11 P742 P742 12 25 P742 P742 26 13 P742 P742 14

1 P741 and 1 P741 and12 P742 14 P742 14 P742 14 P742

FIXED FRAME

P741

P741

First Cubicle: Additional cubicle: First Cubicle: Additional cubicle:

REVOLVING DOOR REVOLVING DOOR FIXED FRAME

FIGURE 18: 1 P741 AND P742 WITH P99X TEST BLOCK

P99x P743 8

P99x P743 7 P99x P743 1 P99x P743 9

P99x P743 1 P99x P743 8 P99x P743 2 P99x P743 10

P99x P743 2 P99x P743 9 P99x P743 3 P99x P743 11

P99x P743 3 P99x P743 10 P99x P743 4 P99x P743 12

P99x P743 4 P99x P743 11 P99x P743 5 P99x P743 13

P99x P743 5 P99x P743 12 P99x P743 6 P99x P743 14

P99x P743 6 P99x P743 13 P99x P743 7 P99x P743 15

1 P741 and 1 P741 and6 P743 & 6 P99x 7 P743 & 7 P99x 7 P743 & 7 P99x 8 P743 & 8 P99x

FIXED FRAME

P741

P741

REVOLVING DOOR REVOLVING DOOR FIXED FRAME

First Cubicle: Additional cubicle: First Cubicle: Additional cubicle:

FIGURE 19: 1 P741 AND P743 WITH (OR WITHOUT) P99X TEST BLOCK

7.6 Substation Architecture

Due to the flexibility of the differential busbar protection there is an infinite number of busbar configurations that can be accommodated via the topology. Each may have very different architecture and, therefore, vary in complexity.

You will find in the following pages topology examples of layouts most frequently encountered. For each example, the number of central units and peripheral units necessary to protect the busbars is specified.

Generally, the elements of the protection architecture will be identified in a similar manner to the principal parts of the substation e.g. by the letters A and B.

Note: A cubicle needs to be considered for a centralised solution whereas if the peripheral units are distributed and the scheme is distributed there is no requirement for a dedicated cubicle.

In both cases, and before any delivery, the topology will be thoroughly tested on appropriate test platforms the scheme is engineered by an Alstom Grid competency centre).

Page 200: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-36

MiCOM P741, P742, P743

AP

8. STANDARD CONFIGURATIONS The following information relates only to the more common standard schemes. For further information on the accommodation of other busbar configurations consult your Alstom Grid representative.

The main rule to calculate the minimum number of Peripheral Unit to use is:

1 Peripheral Unit per CT.

P3782ENa

FIGURE 20: SINGLE BUSBAR APPLICATION WITH BUS SECTION ISOLATOR

The above example shows a single busbar with a bus section isolator. It is split into two zones. There are n feeders connected to the busbar. This configuration requires 1 central unit and n peripheral units (the additional peripheral unit being for the bus section isolator is optional). The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3783ENa

FIGURE 21: SINGLE BUSBAR APPLICATION WITH BUS SECTION CIRCUIT BREAKER

The above example shows a single busbar with a bus section circuit breaker. It is split into two zones. There are n feeders connected to the busbar. The bus section circuit breaker has CTs on either side.

Page 201: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-37

AP

This configuration requires 1 central unit and n + 2 peripheral units (the additional peripheral units being for the bus section CTs). The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

It is recommended that the CTs for feeder protection are sited such as to overlap with the CTs defining the limits of each busbar protection zone.

P3784ENa

FIGURE 22: BREAKER AND A HALF SCHEME

The above example shows a breaker and a half scheme. The recommended solution is to have two separate schemes. There are n feeders connected to each busbar. Each scheme will require 1 central unit and n peripheral units. An other solution is to use only one central unit and 2 x n peripheral units. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3785ENa

FIGURE 23: DOUBLE BUSBAR APPLICATION WITH BUS COUPLER

The above example shows a double busbar with a bus coupler. It is split into two zones. There are n feeders connected to the busbar. The bus coupler circuit breaker can have either a single CT (solution 1) on one side or CTs on both sides (solution 2).

Page 202: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-38

MiCOM P741, P742, P743

AP

This configuration requires 1 central unit and n + 1 peripheral units for solution 1 or n + 2 peripheral units for solution 2. (The additional peripheral units being for the bus coupler CTs). The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3786ENa

FIGURE 24: TRADITIONAL DOUBLE BUSBAR APPLICATION WITH BUS COUPLER AND BUS SECTION

The above example shows a double busbar with both a bus section and a bus coupler. It is split into four zones. There are n feeders connected to the busbar. The bus coupler and bus section circuit breakers can have either a single CT (solution 1 and 2) on one side or CTs on both sides (solution 1a or 2a). This configuration requires 1 central unit and n plus the following number of peripheral units. The total number of peripheral units required allows for a peripheral unit for the bus section isolator on the upper bar.

Solution Solution A1 CT on BC & 1 CT on BS

Solution B2 CT on BC & 2 CT on BS

Solution C 1 CT on BC & 2 CT on BS

Solution D2 CT on BC & 1 CT on BS

Solution 1

Solution 1a

Solution 2

Solution 2a

Number of peripheral units required

n + 2 n + 4 n + 3 n + 3

If a second bus coupler is added i.e. one bus coupler either side of the bus section

Using solution 1 for the 2nd coupler

Using solution 1a for the 2nd coupler

Number of peripheral units required

n + 3 n + 6 n + 4 n + 5

TABLE 3: NUMBER OF REQUIRED PU’S FOR FIGURE 42

Page 203: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-39

AP

The additional peripheral unit being for the bus section isolator is optional.

The number of additional peripheral units being dependant on the number of bus section/bus coupler CTs. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3787ENa

FIGURE 25: DOUBLE BUSBAR APPLICATION WITH BUS COUPLER AND BUS SECTION

WITH ADDITIONAL BUS SECTION ISOLATORS

The above example shows a double busbar with both a bus section and a bus coupler. The bus section also has additional bus section isolators and allows for bus section bypass. The scheme is split into four zones. There are n feeders connected to the busbar. The bus coupler and bus section circuit breakers can have either a single CT (solution 1 and 2) on one side or CTs on both sides (solution 1a or 2a). This configuration requires 1 central unit and n plus the following number of peripheral units. The total number of peripheral units required allow for a peripheral unit for the bus section isolators.

Solution Solution A1 CT on BC & 1 CT on BS

Solution B2 CT on BC & 2 CT on BS

Solution C 1 CT on BC & 2 CT on BS

Solution D2 CT on BC & 1 CT on BS

Solution 1 Solution 1a Solution 2 Solution 2a Number of peripheral units required

n + 2 n + 4 n + 3 n + 3

If a second bus coupler is added i.e. one bus coupler either side of the bus section Using solution 1 for the 2nd coupler

Using solution 1a for the 2nd coupler

Number of peripheral units required

n + 3 n + 6 n + 4 n + 5

TABLE 4: NUMBER OF REQUIRED PU’S FOR FIGURE 43

Page 204: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-40

MiCOM P741, P742, P743

AP

The additional peripheral unit being for the bus section isolators is optional.

The number of additional peripheral units being dependant on the number of bus section/bus coupler CTs. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3788ENa

FIGURE 26: DOUBLE BUSBAR APPLICATION WITH BUS COUPLER AND DOUBLE BUS SECTION CIRCUIT BREAKER ARRANGEMENT

The above example shows a double busbar with both a bus section and a bus coupler. There are circuit breakers on both the upper and lower bars. The scheme is split into four zones. There are n feeders connected to the busbar. The bus coupler and bus section circuit breakers can have either a single CT (solution 1 and 2) on one side or CTs on both sides (solution 1a or 2a). This configuration requires 1 central unit and n plus the following number of peripheral units. The total number of peripheral units required allows for a peripheral unit for the bus section isolator on the upper bar.

Solution Solution A1 CT on BC & 1 CT on each BS

Solution B2 CT on BC & 2 CT on each BS

Solution C 1 CT on BC & 2 CT on each BS

Solution D2 CT on BC & 1 CT on each BS

Solution 1

Solution 1a

Solution 2

Solution 2a

Number of peripheral units required

n + 3 n + 6 n + 5 n + 4

If a second bus coupler is added i.e. one bus coupler either side of the bus section

Using solution 1 for the 2nd coupler

Using solution 1a for the 2nd coupler

Number of peripheral units required

n + 4 n + 8 n + 6 n + 6

TABLE 5: NUMBER OF REQUIRED PU’S FOR FIGURE 44

Page 205: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-41

AP

The number of additional peripheral units being dependant on the number of bus section/bus coupler CTs. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3789ENa

FIGURE 27: DOUBLE BUSBAR APPLICATION WITH A BUS COUPLER. THE TRANSFER BUSBAR IS NOT INCLUDED

IN THE PROTECTION ZONE.

The above example shows a double busbar with a bus coupler and a transfer busbar. As the transfer busbar is on the line side of all the feeder CTs, it is not included in the protected zone it can be considered similarly to figure 45, an additional peripheral unit must be included for the transfer bay.

It is split into two zones. There are n feeders connected to the busbar. The bus coupler circuit breaker can have either a single CT (solution 1) on one side or CTs on both sides (solution 2). This configuration requires 1 central unit and n + 2 peripheral units for solution 1 or n + 3 peripheral units for solution 2. (The additional peripheral units being for the bus coupler CTs and the transfer bay). The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3790ENa

FIGURE 28: DOUBLE BUSBAR APPLICATION WITH A BUS COUPLER. THE TRANSFER BUSBAR IS INCLUDED IN THE PROTECTION ZONE.

Page 206: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-42

MiCOM P741, P742, P743

AP

The above example shows a double busbar with a bus coupler and a transfer busbar. The transfer busbar is on the bus side of all the feeder CTs, it is included in the protected zone. It can be considered similarly to figure 43, where an additional peripheral unit has been included for the transfer bay. The only difference being the positioning of the CTs and therefore the protection.

Again it is split into two zones. With an additional zone for the transfer bay, there are n feeders connected to the busbar. The bus coupler circuit breaker can have either a single CT (solution 1) on one side or CTs on both sides (solution 2). This configuration requires 1 central unit and n + 2 peripheral units for solution 1 or n + 3 peripheral units for solution 2. (The additional peripheral units being for the bus coupler CTs and the transfer bay). The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3791ENa

FIGURE 29: TRIPLE BUSBAR APPLICATION WITH BUS COUPLER AND BUS SECTION

The above example shows a triple busbar with both a bus section and a bus coupler. The bus section also has additional bus section isolators and allows for bus section bypass. The scheme is split into six zones. There are n feeders connected to the busbar. The bus coupler and bus section circuit breakers can have either a single CT (solution 1 and 2) on one side or CTs on both sides (solution 1a or 2a). This configuration requires 1 central unit and n plus the following number of peripheral units. The total number of peripheral units required allows for a peripheral unit for the bus section isolators.

Page 207: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-43

AP

Solution Solution A1 CT on BC & 1 CT on BS

Solution B2 CT on BC & 2 CT on BS

Solution C 1 CT on BC & 2 CT on BS

Solution D2 CT on BC & 1 CT on BS

Solution 1

Solution 1a

Solution 2

Solution 2a

Number of peripheral units required

n + 2 n + 4 n + 3 n + 3

If a second bus coupler is added i.e. one bus coupler either side of the bus section

Using solution 1 for the 2nd coupler

Using solution 1a for the 2nd coupler

Number of peripheral units required

n + 3 n + 6 n + 4 n + 5

TABLE 6: NUMBER OF REQUIRED PU’S FOR FIGURE 47

The additional peripheral unit being for the bus section isolators is optional.

The number of additional peripheral units being dependant on the number of bus section/bus coupler CTs. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

P3792ENa

FIGURE 30: DOUBLE BUS BAR WITH TWO CIRCUIT BREAKERS PER FEEDER

Page 208: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-44

MiCOM P741, P742, P743

AP

The above example shows a double busbar with two circuit breakers on each feeder. The scheme is split into two zones. There are n feeders connected to the busbar. This configuration should require 1 central unit and 2 x n peripheral units but only n Peripheral Units can be used. In each bay the two peripheral units should share the CT, and each circuit breaker should be assigned to a separate peripheral unit but when one Peripheral Unit is used per feeder, the trip order is connected to the two breakers.

P3793ENa

FIGURE 31: MESH CORNER

The above example shows a mesh corner arrangement. The scheme is split into four zones. This configuration requires 1 central unit and 12 peripheral units.

P3794ENa

FIGURE 32: SIX MAIN BUS FOR S/S CB BUS-SECTIONS AND CB BY-PASS

Page 209: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-45

AP

The above example shows a six busbar arrangement with both a bus section and a bus coupler. It is also possible to include bypass facilities. The scheme is split into six zones. There are n feeders connected to the busbar. The bus coupler, bus section and bypass circuit breakers can have either a single CT (solution 1, 2 and 3) on one side or CTs on both sides (solution 1A, 2A and 3A).

This configuration requires 1 central unit and n plus the following number of peripheral units.

Solution Solution A1 CT on BC & 1 CT on each BS

Solution B2 CT on BC & 2 CT on each BS

Solution C 1 CT on BC & 2 CT on each BS

Solution D2 CT on BC & 1 CT on each BS

Solution 1

Solution 1a

Solution 2

Solution 2a

Number of peripheral units required

n + 4 n + 8 n + 7 n + 5

If bypass facilities are to be included

Using solution 3

Using solution 3a

Number of peripheral units required

n + 5 n + 10 n + 8 n + 8

If a second bus coupler is added i.e. one bus coupler either side of the bus section and no bypass facilities

Using solution 1 for the 2nd coupler

Using solution 1a for the 2nd coupler

Number of peripheral units required

n + 5 n + 10 n + 8 n + 7

If a second bus coupler is added i.e. one bus coupler either side of the bus section and bypass facilities are included

Using solution 3

Using solution 3a

Number of peripheral units required

n + 6 n + 12 n + 9 n + 10

TABLE 7: NUMBER OF REQUIRED PU’S FOR FIGURE 50

The number of additional peripheral units being dependant on the number of bus section/bus coupler CTs. The type of peripheral unit used for each bay will depend on the i/o requirements of the bay in question.

Page 210: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-46

MiCOM P741, P742, P743

AP

9. APPLICATION OF NON PROTECTION FUNCTIONS The non-protection features for the scheme are summarised below:

• Scheme can be centralised/distributed – if space is not available to locate the busbar protection centrally it is possible to decentralise the scheme and locate the units within other protection cubicles.

• Local, zone and scheme measurements – various measurements are available locally via the relay LCD or remotely via the serial communication link

• Event, fault and disturbance recording – Comprehensive post fault analysis available via event lists, disturbance records and fault records which can be accessed locally via the relay LCD or remotely via the serial communication link (PU -> CU)

• Real time clock/time synchronisation – Time synchronisation available via IRIG-B input (option in Central Unit that synchronises the PUs)

• Four settings groups – Independent remotely selectable setting groups to allow for customer specific applications

• CB and isolator state monitoring – indication of the circuit breaker/isolator position via the auxiliary contacts, scheme acts accordingly should discrepancy conditions be detected

• CB control – available locally via the HMI

• Commissioning test facilities

• Continuous self monitoring – extensive self checking routines to ensure maximum reliability

• Communications supervision – detects communication failure between units and enables remedial action to be taken e.g. switch to communication independent backup protection locally and disregard feeder at a zone level

• Graphical programmable scheme logic – allowing user defined protection and control logic to be tailored to the specific application

Page 211: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-47

AP

9.1 Function keys

The following default PSL logic illustrates the programming of function keys to enable/disable the commissioning mode functionality.

FIGURE 33: COMMISSIONING MODE DEFAULT PSL

Note: Energizing two inputs to an LED conditioner creates a YELLOW illumination.

Function Keys 4 and 5 are set to ‘Toggle’ mode and on activation of the key, the commissioning mode will be in service as long as the function has been enabled in the “Configuration” menu. The associated LED will indicate the state of the protection function in service as GREEN and YELLOW for the 50BF disable mode and RED for the Overhaul mode.

Page 212: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-48

MiCOM P741, P742, P743

AP

10. CT REQUIREMENTS

10.1 Notation

IF max fault maximum fault current (same for all feeders) in A

IF max int cont

maximum contribution from a feeder to an internal fault (depends on the feeder) in A

Inp CT primary rated current

In nominal secondary current (1A or 5A)

RCT CT secondary winding Resistance in Ohms

RB Total external load resistance in Ohms

Vk CT knee point voltage in Volts

SVA Nominal output in VA

KSSC Short-circuit current coefficient (generally 20)

General recommendations for the specification of protection CTs use common rules of engineering which are not directly related to a particular protection.

10.2 87BB Phase CT Requirements

10.2.1 Feeders connected to sources of significant power (i.e. lines and generators)

The primary rated current is specified above a 1/20th of the maximum contribution of the feeder to internal faults.

i.e. Inp = IF max int/20

e.g. A power line likely to import electricity at 20 kA gives rated primary current Inp as 1000 A.

This recommendation is used for the majority of line or transformer protection applications.

The CT must be sized so as not to saturate during internal faults:

For each CT, IFeederMax = maximum contribution of the feeder to an internal fault (could be different for each feeder):

Vk > IFeederMax * (RCT + RB)

Note: This specification is valid for internal faults.

10.2.2 Out of service feeders or those with low power contribution (low infeed)

Because of CT construction, thermal behaviour, and electrodynamics the CT primary rated current cannot be as low as required compared to the maximum fault current. In the case of a CT with primary bushings and not wound there is not a precise limit but a practical one. The primary rated current could not be lower than the 1/200th of the maximum short-circuit current crossing the CT at the time of an external fault

i.e. Inp = IF max /200

This is possible using the fast overcurrent detection I>2 to distinguish between an internal or external fault in case of CT saturation below than 2 ms

e.g. For a substation whose maximum short-circuit current would be 30 kA, the CTs on the least powerful feeders are to be specified for a rated primary current Inp = 150 A, even if the normal consumption of the feeder is much lower than this value (Substation transformer feeder)

Page 213: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-49

AP

10.2.3 CT Specification according to IEC 185, 44-6 and BS 3938 (British Standard)

1. Class X according to British Standard: Minimum knee point voltage for saturation

Vk min = 0.5 x secondary IF max x (RCT + RB)

Note: This specification is valid for external faults.

The recommended specification makes it possible to guarantee a time to saturation greater than 1.4 ms with a remnant flux of 80 % of maximum flux (class X or TPX). This provides a sufficient margin of security for CT saturation detection, which operates in less than 2 ms.

2. Class 5P to IEC 185. Conversion of class X (BS) with the 5P equivalent (IEC)

3. Class TPX and TPY according to IEC 44-6. IEC defines a composite error as a percentage of a multiple of the rated current (IN) on a definite load SVA.

e.g. CT 1000/5 A – 50VA 5P 20 [CT Inp / InA – SVA Accuracy P Kscc]

This definition indicates that the composite error must be lower than 5%, for a primary current of 20Inp when the external load is equal to 2 ohms (50VA to In). If secondary resistance, RCT, is known it is easy to calculate the magnetising EMF developed with the fault current (20In). Actually if the error is 5% (= 5A) with this EMF, the point of operation is beyond the knee point voltage for saturation. By convention one admits that the knee point voltage, Vk, is 80% of this value. For a conversion between a class 5P (IEC) and a class X (BS) CT one uses the relation:

Vk=0.8 X [(SVA x Kssc)/In + (RCT x Kssc x In) ]

SVA = (In x Vk/0.8 Kssc) – RCT x In2

In particular cases, calculation could reveal values too low to correspond to industrial standards. In this case the minima will be: SVA min = 10 VA 5P 20 which correspond to a knee point voltage of approximately Vkmin = 70 V at 5A or 350V at 1A. Class TPY would permit lower values of power, (demagnetisation air-gap). Taking into account the weak requirements of class X or TPX one can keep specifications common.

For accuracy, class X or class 5P current transformers (CTs) are strongly recommended. The knee point voltage of the CTs should comply with the minimum requirements of the formulae shown below.

Vk ≥ k (RCT + RB)

Where:

Vk = Required knee point voltage

k = Dimensioning factor

RCT = CT secondary resistance

RL = Circuit resistance from CT to relay

RB = Burden resistance

k is a constant depending on:

If = Maximum value of through fault current for stability (multiple of In)

X/R = Primary system X/R ratio (for the P74x system, X/R up to 80)

The following CT requirement can be developed for the P74x scheme

Vk > 0.5 x (secondary If max) x (RCT + RB)

With RB = 2 RL

Page 214: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-50

MiCOM P741, P742, P743

AP

10.3 87BB Sensitive Differential Earth Fault CT Requirements

The Sensitive Differential Earth Fault (SDEF) shall be enabled only on High Impedance Earthed Networks.

To enable the SDEF the CTs have to comply with the additional following requirement:

Vk min = 1.5 x X/R x In x (RCT + RB)

Note: If the X/R is lower than 20, chose 20 as X/R.

Where:

Vk = Required knee point voltage

X/R = Primary system X/R ratio (for the P74x system, X/R up to 80)

In = nominal secondary current (1A or 5A)

RCT = CT secondary resistance

RB = Burden resistance (with RB = 2 RL)

10.4 Support of IEEE C Class CTs

MiCOM Px40 series protection is compatible with ANSI/IEEE current transformers as specified in the IEEE C57.13 standard. The applicable class for protection is class “C”, which specifies a non air-gapped core. The CT design is identical to IEC class P, or British Standard class X, but the rating is specified differently. The following table allows C57.13 ratings to be translated into an IEC/BS knee point voltage

IEEE C57.13 – “C” Classification (volts)

C50 C100 C200 C400 C800 CT Ratio RCT (ohm)

Vk Vk Vk Vk Vk

100/5 0.04 56.5 109 214 424 844

200/5 0.8 60.5 113 218 428 848

400/5 0.16 68.5 121 226 436 856

800/5 0.32 84.5 137 242 452 872

1000/5 0.4 92.5 145 250 460 880

1500/5 0.6 112.5 165 270 480 900

2000/5 0.8 132.5 185 290 500 920

3000/5 1.2 172.5 225 330 540 960

TABLE 8: IEC/BS KNEE POINT VOLTAGE VK OFFERED BY “C” CLASS CTS

Assumptions:

1. For 5A CTs, the typical resistance is 0.0004 ohm secondary per primary turn (for 1A CTs, the typical resistance is 0.0025 ohm secondary per primary turn)

2. IEC/BS knee is typically 5% higher than ANSI/IEEE knee

Page 215: P74x_EN_M_H54

Application Notes P74x/EN AP/H54 MiCOM P741, P742, P743

(AP) 6-51

AP

Given:

1. IEC/BS knee is specified as an internal EMF, whereas the “C” class voltage is specified at the CT output terminals. To convert from ANSI/IEEE to IEC/BS requires the voltage drop across the CTs secondary winding resistance to be added.

2. IEEE CTs are always rated at 5A secondary

3. The rated dynamic current output of a “C” class CT (Kssc) is always 20 x In

Vk = (C x 1.05) + (In. RCT. Kssc)

Where:

Vk = Equivalent IEC or BS knee point voltage

C = C Rating

In = 5A

RCT = CT secondary winding resistance

Kssc = 20 times

Page 216: P74x_EN_M_H54

P74x/EN AP/H54 Application Notes (AP) 6-52

MiCOM P741, P742, P743

AP

11. AUXILIARY SUPPLY FUSE RATING In the Safety section of this manual, the maximum allowable fuse rating of 16A is quoted. To allow time grading with fuses upstream, a lower fuselink current rating is often preferable. Use of standard ratings of between 6A and 16A is recommended. Low voltage fuselinks, rated at 250V minimum and compliant with IEC60269-2 general application type gG are acceptable, with high rupturing capacity. This gives equivalent characteristics to HRC "red spot" fuses type NIT/TIA often specified historically.

The table below recommends advisory limits on relays connected per fused spur. This applies to MiCOM Px40 series devices with hardware suffix C and higher, as these have inrush current limitation on switch-on, to conserve the fuse-link.

Maximum Number of MiCOM Px40 Relays Recommended Per Fuse

Battery Nominal Voltage 6A 10A Fuse 15 or 16A Fuse Fuse Rating > 16A

24 to 54V 2 4 6 Not permitted

60 to 125V 4 8 12 Not permitted

138 to 250V 6 10 16 Not permitted

Alternatively, miniature circuit breakers (MCB) may be used to protect the auxiliary supply circuits.

Page 217: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

PL PROGRAMMABLE LOGIC

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 218: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

MiCOM P741, P742, P743

Page 219: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-1

PL

CONTENTS

1. PROGRAMMABLE LOGIC 3

1.1 Overview 3

1.2 MiCOM S1 Px40 PSL editor 3

1.3 How to use MiCOM Px40 PSL editor 4

1.4 Warnings 4

1.5 Toolbar and commands 5

1.5.1 Standard tools 5

1.5.2 Alignment tools 5

1.5.3 Drawing Tools 5

1.5.4 Nudge tools 5

1.5.5 Rotation tools 5

1.5.6 Structure tools 5

1.5.7 Zoom and pan tools 5

1.5.8 Logic symbols 5

1.6 PSL logic signals properties 7

1.6.1 Link properties 7

1.6.2 Opto signal properties 7

1.6.3 Input signal properties 8

1.6.4 Output signal properties 8

1.6.5 GOOSE input signal properties 8

1.6.6 GOOSE output signal properties 8

1.6.7 Control in signal properties 9

1.6.8 Function key properties 9

1.6.9 Fault recorder trigger properties 9

1.6.10 LED signal properties 9

1.6.11 Contact signal properties 9

Page 220: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-2

MiCOM P741, P742, P743

PL

1.6.12 LED conditioner properties 10

1.6.13 Contact conditioner properties 10

1.6.14 Timer properties 11

1.6.15 Gate properties 11

1.7 Description of P741 logic nodes 13

1.7.1 Sorted by DDB number: 13

1.7.2 Sorted by DDB name: 17

1.8 Description of P742 logic nodes 21

1.8.1 Sorted by DDB number: 21

1.8.2 Sorted by DDB name: 25

1.9 Description of P743 logic nodes 30

1.9.1 Sorted by DDB number: 30

1.9.2 Sorted by DDB name: 35

1.10 Factory default programmable scheme logic 40

1.11 Logic input mapping 40

1.12 Relay output contact mapping 42

1.13 Function key input mapping 43

1.14 Programmable LED output mapping 44

1.15 Fault recorder start mapping 48

1.16 PSL DATA column 48

MiCOM P741 PROGRAMMABLE SCHEME LOGIC 49

MiCOM P742 PROGRAMMABLE SCHEME LOGIC 53

MiCOM P743 PROGRAMMABLE SCHEME LOGIC 57

Page 221: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-3

PL

1. PROGRAMMABLE LOGIC

1.1 Overview

The purpose of the programmable scheme logic (PSL) is to allow the relay user to configure an individual protection scheme to suit their own particular application. This is achieved through the use of programmable logic gates and delay timers.

The input to the PSL is any combination of the status of opto inputs. It is also used to assign the mapping of functions to the opto inputs and output contacts, the outputs of the protection elements, e.g. protection starts and trips, and the outputs of the fixed protection scheme logic. The fixed scheme logic provides the relay’s standard protection schemes. The PSL itself consists of software logic gates and timers. The logic gates can be programmed to perform a range of different logic functions and can accept any number of inputs. The timers are used either to create a programmable delay, and/or to condition the logic outputs, e.g. to create a pulse of fixed duration on the output regardless of the length of the pulse on the input. The outputs of the PSL are the LEDs on the front panel of the relay and the output contacts at the rear.

The execution of the PSL logic is event driven; the logic is processed whenever any of its inputs change, for example as a result of a change in one of the digital input signals or a trip output from a protection element. Also, only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This reduces the amount of processing time that is used by the PSL; even with large, complex PSL schemes the relay trip time will not lengthen.

This system provides flexibility for the user to create their own scheme logic design. However, it also means that the PSL can be configured into a very complex system, hence setting of the PSL is implemented through the PC support package MiCOM S1.

1.2 MiCOM S1 Px40 PSL editor

To access the Px40 PSL Editor Menu click on

The PSL Editor module enables you to connect to any MiCOM device front port, retrieve and edit its Programmable Scheme Logic files and send the modified file back to a MiCOM Px40 device.

Page 222: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-4

MiCOM P741, P742, P743

PL

1.3 How to use MiCOM Px40 PSL editor

With the MiCOM Px40 PSL Module you can:

• Start a new PSL diagram

• Extract a PSL file from a MiCOM Px40 IED

• Open a diagram from a PSL file

• Add logic components to a PSL file

• Move components in a PSL file

• Edit link of a PSL file

• Add link to a PSL file

• Highlight path in a PSL file

• Use a conditioner output to control logic

• Download PSL file to a MiCOM Px40 IED

• Print PSL files

For a detailed discussion on how to use these functions, please refer to MiCOM S1 Users Manual.

1.4 Warnings

Before the scheme is sent to the relay checks are done. Various warning messages may be displayed as a result of these checks.

The Editor first reads in the model number of the connected relay, and then compares it with the stored model number. A "wildcard" comparison is employed. If a model mismatch occurs then a warning will be generated before sending commences. Both the stored model number and that read-in from the relay are displayed along with the warning; the onus is on you to decide if the settings to be sent are compatible with the connected relay. Wrongly ignoring the warning could lead to undesired behaviour in the relay.

If there are any potential problems of an obvious nature then a list will be generated. The types of potential problems that the program attempts to detect are:

• One or more gates, LED signals, contact signals, and/or timers have their outputs linked directly back to their inputs. An erroneous link of this sort could lock up the relay, or cause other more subtle problems to arise.

• Inputs to Trigger (ITT) exceeds the number of inputs. A programmable gate has its ITT value set to greater than the number of actual inputs; the gate can never activate. Note that there is no lower ITT value check. A 0-value does not generate a warning.

• Too many gates. There is a theoretical upper limit of 256 gates in a scheme, but the practical limit is determined by the complexity of the logic. In practice the scheme would have to be very complex, and this error is unlikely to occur.

• Too many links. There is no fixed upper limit to the number of links in a scheme. However, as with the maximum number of gates, the practical limit is determined by the complexity of the logic. In practice the scheme would have to be very complex, and this error is unlikely to occur.

Page 223: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-5

PL

1.5 Toolbar and commands

There are a number of toolbars available for easy navigation and editing of PSL.

1.5.1 Standard tools

• For file management and printing.

1.5.2 Alignment tools

• To snap logic elements into horizontally or vertically aligned groupings.

1.5.3 Drawing Tools

• To add text comments and other annotations, for easier reading of PSL schemes.

1.5.4 Nudge tools

• To move logic elements.

1.5.5 Rotation tools

• Tools to spin, mirror and flip.

1.5.6 Structure tools

• To change the stacking order of logic components.

1.5.7 Zoom and pan tools

• For scaling the displayed screen size, viewing the entire PSL, or zooming to a selection.

1.5.8 Logic symbols

This toolbar provides icons to place each type of logic element into the scheme diagram. Not all elements are available in all devices. Icons will only be displayed for those elements available in the selected device.

Link

Create a link between two logic symbols.

Page 224: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-6

MiCOM P741, P742, P743

PL

Opto Signal

Create an opto signal.

Input Signal

Create an input signal.

Output Signal

Create an output signal.

GOOSE In

Create an input signal to logic to receive a UCA2.0 GOOSE message transmitted from another IED. GOOSE Out

Create an output signal from logic to transmit a UCA2.0 GOOSE message to another IED.

Control In

Create an input signal to logic that can be operated from an external command.

Function Key

Create a function key input signal.

Trigger Signal

Create a fault record trigger.

LED Signal

Create an LED input signal that repeats the status of tri-colour LED.

Contact Signal

Create a contact signal.

LED Conditioner

Create an LED conditioner.

Contact Conditioner

Create a contact conditioner.

Timer

Create a timer.

AND Gate

Create an AND Gate.

OR Gate

Create an OR Gate.

Programmable Gate

Create a programmable gate.

Page 225: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-7

PL

1.6 PSL logic signals properties

The logic signal toolbar is used for the selection of logic signals.

Performing a right-mouse click on any logic signal will open a context sensitive menu and one of the options for certain logic elements is the Properties… command. Selecting the Properties option will open a Component Properties window, the format of which will vary according to the logic signal selected.

Properties of each logic signal, including the Component Properties windows, are shown in the following sub-sections:

Signal properties menu

The Signals List tab is used for the selection of logic signals.

The signals listed will be appropriate to the type of logic symbol being added to the diagram. They will be of one of the following types:

1.6.1 Link properties

Links form the logical link between the output of a signal, gate or condition and the input to any element.

Any link that is connected to the input of a gate can be inverted via its properties window. An inverted link is indicated with a “bubble” on the input to the gate. It is not possible to invert a link that is not connected to the input of a gate.

Rules for Linking Symbols

Links can only be started from the output of a signal, gate, or conditioner, and can only be ended on an input to any element.

Since signals can only be either an input or an output then the concept is somewhat different. In order to follow the convention adopted for gates and conditioners, input signals are connected from the left and output signals to the right. The Editor will automatically enforce this convention.

A link attempt will be refused where one or more rules would otherwise be broken. A link will be refused for the following reasons:

• An attempt to connect to a signal that is already driven. The cause of the refusal may not be obvious, since the signal symbol may appear elsewhere in the diagram. Use “Highlight a Path” to find the other signal.

• An attempt is made to repeat a link between two symbols. The cause of the refusal may not be obvious, since the existing link may be represented elsewhere in the diagram.

1.6.2 Opto signal properties

Opto Signal

Each opto input can be selected and used for programming in PSL. Activation of the opto input will drive an associated DDB signal.

For example activating opto input L1 will assert DDB 032 in the PSL.

Page 226: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-8

MiCOM P741, P742, P743

PL

1.6.3 Input signal properties

Input Signal

Relay logic functions provide logic output signals that can be used for programming in PSL. Depending on the relay functionality, operation of an active relay function will drive an associated DDB signal in PSL.

For example DDB 261 will be asserted in the PSL should the active earth fault 1, stage 1 protection operate/trip.

1.6.4 Output signal properties

Output Signal

Relay logic functions provide logic input signals that can be used for programming in PSL. Depending on the relay functionality, activation of the output signal will drive an associated DDB signal in PSL and cause an associated response to the relay function

For example, if DDB 216 is asserted in the PSL, it will block the sensitive earth function stage 1 timer.

1.6.5 GOOSE input signal properties

GOOSE In

The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic (see S1 users manual) by means of 32 Virtual inputs. The Virtual Inputs can be used in much the same way as the Opto Input signals.

The logic that drives each of the Virtual Inputs is contained within the relay’s GOOSE Scheme Logic file. It is possible to map any number of bit-pairs, from any enrolled device, using logic gates onto a Virtual Input (see S1 Users manual for more details).

For example DDB 832 will be asserted in PSL should virtual input 1 and its associated bit pair operate.

1.6.6 GOOSE output signal properties

GOOSE Out

The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic by means of 32 Virtual outputs.

It is possible to map virtual outputs to bit-pairs for transmitting to any enrolled devices (see S1 Users manual for more details).

For example if DDB 865 is asserted in PSL, Virtual Output 32 and its associated bit-pair mappings will operate.

Page 227: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-9

PL

1.6.7 Control in signal properties

Control In

There are 32 control inputs which can be activated via the relay menu, ‘hotkeys’ or via rear communications. Depending on the programmed setting i.e. latched or pulsed, an associated DDB signal will be activated in PSL when a control input is operated.

For example operate control input 1 to assert DDB 800 in the PSL.

1.6.8 Function key properties

Function Key

Each function key can be selected and used for programming in PSL. Activation of the function key will drive an associated DDB signal and the DDB signal will remain active depending on the programmed setting i.e. toggled or normal. Toggled mode means the DDB signal will remain latched or unlatched on key press and normal means the DDB will only be active for the duration of the key press.

For example operate function key 1 to assert DDB 712 in the PSL.

1.6.9 Fault recorder trigger properties

Fault Record Trigger

The fault recording facility can be activated, by driving the fault recorder trigger DDB signal.

For example assert DDB 144 to activate the fault recording in the PSL.

1.6.10 LED signal properties

LED

All programmable LEDs will drive associated DDB signal when the LED is activated.

For example DDB 652 will be asserted when LED 7 is activated.

1.6.11 Contact signal properties

Contact Signal

All relay output contacts will drive associated DDB signal when the output contact is activated.

For example DDB 009 will be asserted when output R10 is activated.

Page 228: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-10

MiCOM P741, P742, P743

PL

1.6.12 LED conditioner properties

LED Conditioner

1. Select the LED name from the list (only shown when inserting a new symbol).

2. Configure the LED output to be Red, Yellow or Green.

Configure a Green LED by driving the Green DDB input.

Configure a RED LED by driving the RED DDB input.

Configure a Yellow LED by driving the RED and GREEN DDB inputs simultaneously.

3. Configure the LED output to be latching or non-latching.

1.6.13 Contact conditioner properties

Each contact can be conditioned with an associated timer that can be selected for pick up, drop off, dwell, pulse, pick-up/drop-off, straight-through, or latching operation. “Straight-through” means it is not conditioned in any way whereas “latching” is used to create a sealed-in or lockout type function.

1. Select the contact name from the Contact Name list (only shown when inserting a new symbol).

2. Choose the conditioner type required in the Mode tick list.

Page 229: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-11

PL

3. Set the Pick-up Time (in milliseconds), if required.

4. Set the Drop-off Time (in milliseconds), if required.

1.6.14 Timer properties

Each timer can be selected for pick up, drop off, dwell, pulse or pick-up/drop-off operation.

1. Choose the operation mode from the Timer Mode tick list.

2. Set the Pick-up Time (in milliseconds), if required.

3. Set the Drop-off Time (in milliseconds), if required.

1.6.15 Gate properties

A Gate may be an AND, OR, or programmable gate.

An AND gate requires that all inputs are TRUE for the output to be TRUE.

An OR gate requires that one or more input is TRUE for the output to be TRUE.

A Programmable gate requires that the number of inputs that are TRUE is equal to or

greater than its ‘Inputs to Trigger’ setting for the output to be TRUE.

Page 230: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-12

MiCOM P741, P742, P743

PL

1. Select the Gate type AND, OR, or Programmable.

2. Set the number of inputs to trigger when Programmable is selected.

3. Select if the output of the gate should be inverted using the Invert Output check box. An inverted output is indicated with a "bubble" on the gate output.

Page 231: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-13

PL

1.7 Description of P741 logic nodes

1.7.1 Sorted by DDB number:

DDB No.

English Text Source Description

0 Relay Label 01 RELAY Output Conditioner Output Relay 01 7 Relay Label 08 RELAY Output Conditioner Output Relay 08

64 Opto Label 01 OPTO Opto Input Opto Input 1 71 Opto Label 08 OPTO Opto Input Opto Input 8

104 Sett Grp Bit LSB PSL Output Signal

PSL Setting Group Selector X1 (low bit) SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

105 Sett Grp Bit MSB PSL Output Signal

PSL Input signal Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

106 To Reset CircFlt PSL Output Signal

PSL To Reset the Circuitry Fault

107 Ext Start DR PSL Output Signal

PSL Starting Disturbance Recorder

108 To Block 87BB PSL Output Signal

PSL To Block 87BB phase & Earth algorithms

109 Reset Indication PSL Output Signal

PSL Reset all indications (Led and relays latched in PSL) that includes the Led Alarm

110 To Reset PU err PSL Output Signal

PSL To reset PU error

111 All Prot Blocked PSL Output Signal

PSL (Commissioning) To disable all the protections (CU & PU)

112 CU->PU Signal 01

PSL Output Signal

PSL Virtual Signal 01 from the CU to all the PUs via the fibre optic

127 CU->PU Signal 16

PSL Output Signal

PSL Virtual Signal 16 from the CU to all the PUs via the fibre optic

135 Fibre Com Error PSL Input Signal Scheme Integrity Communication error to at least 1 PU 136 User Alarm 1 PSL Output

Signal PSL Triggers User Alarm 1 message to be alarmed on LCD

display (self-resetting) 143 User Alarm 8 PSL Output

Signal PSL Triggers User Alarm 8 message to be alarmed on LCD

display (self-resetting) 144 PU Error Lck z8 PSL Input Signal Scheme Integrity PU error blocking of zone 8 151 PU Error Lck z1 PSL Input Signal Scheme Integrity PU error blocking of zone 1 152 PU Error Alm z8 PSL Input Signal Scheme Integrity PU error alarm in zone 8 159 PU Error Alm z1 PSL Input Signal Scheme Integrity PU error alarm in zone 1 160 Circt Flt Lck z8 PSL Input Signal 87BB Busbar

Protection Circuitry fault blocking of zone 8

167 Circt Flt Lck z1 PSL Input Signal 87BB Busbar Protection

Circuitry fault blocking of zone 1

168 Circt Flt Alm z8 PSL Input Signal 87BB Busbar Protection

Circuitry fault alarm in zone 8

175 Circt Flt Alm z1 PSL Input Signal 87BB Busbar Protection

Circuitry fault alarm in zone 1

176 Flt 87BB Zone 8 PSL Input Signal 87BB Busbar Protection

Differential fault current in zone 8

183 Flt 87BB Zone 1 PSL Input Signal 87BB Busbar Protection

Differential fault current in zone 1

184 Trip 87BB Zone 8 PSL Input Signal 87BB Busbar Protection

Busbar trip of zone 8

191 Trip 87BB Zone 1 PSL Input Signal 87BB Busbar Protection

Busbar trip of zone 1

192 Man.Trip Zone 8 PSL Input Signal Commissioning Manual trip of zone 8 199 Man.Trip Zone 1 PSL Input Signal Commissioning Manual trip of zone 1 200 Trip 50BF Zone 8 PSL Input Signal 50BF Backtrip

protection Breaker failure trip (50BF) of zone 8

207 Trip 50BF Zone 1 PSL Input Signal 50BF Backtrip protection

Breaker failure trip (50BF) of zone 1

208 INP block SEF z8 PSL Output Signal

PSL (87BB SEF Busbar Protection)

87BB SEF protection algorithm blocking of zone 8 opto input

215 INP block SEF z1 PSL Output Signal

PSL (87BB SEF Busbar Protection)

87BB SEF protection algorithm blocking of zone 1 opto input

Page 232: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-14

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

216 Ext Trip 50BF z8 PSL Output Signal

PSL (50BF Backtrip protection)

External Breaker failure trip order (50BF) of zone 8 opto input

223 Ext Trip 50BF z1 PSL Output Signal

PSL (50BF Backtrip protection)

External Breaker failure trip order (50BF) of zone 1 opto input

224 INP Lck Lev.1 z8 PSL Output Signal

PSL (Commissioning) Maintenance Mode 1 (87BB monitoring) of zone 8 opto input

231 INP Lck Lev.1 z1 PSL Output Signal

PSL (Commissioning) Maintenance Mode 1 (87BB monitoring) of zone 1 opto input

232 INP Lck Lev.2 z8 PSL Output Signal

PSL (Commissioning) Maintenance Mode 2 (50BF & 87BB blocked) of zone 8 opto input

239 INP Lck Lev.2 z1 PSL Output Signal

PSL (Commissioning) Maintenance Mode 2 (50BF & 87BB blocked) of zone 1 opto input

240 Lck Lev.1 Zone 8 PSL Input Signal Scheme Integrity Commissioning mode 1: 50BF disabled in zone 8 247 Lck Lev.1 Zone 1 PSL Input Signal Scheme Integrity Commissioning mode 1: 50BF disabled in zone 1 248 Lck Lev.2 Zone 8 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled in

zone 8 255 Lck Lev.2 Zone 1 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled in

zone 1 256 Trip 87BB PSL Input Signal 87BB Busbar

Protection Busbar trip order (87BB) Logical OR of DDB 184 to 191

257 Trip 87BB Locked PSL Input Signal Scheme Integrity Busbar trip order blocked by commissioning mode or Circuitry fault

258 Trip Manual zone PSL Input Signal Commissioning Manual Trip Order Logical OR of DDB 192 to 199 259 Trip 50BF PSL Input Signal 50BF Backtrip

protection Breaker fail trip order (50BF) Logical OR of DDB 200 to 207

260 Trip 50BF Locked PSL Input Signal Scheme Integrity Breaker fail trip order blocked by commissioning mode or Circuitry fault

261 Ext Trip 50BF PSL Input Signal 50BF Backtrip protection

50BF backtrip request by opto input Logical OR of DDB 216 to 223

262 Fault phase A PSL Input Signal 87BB Busbar Protection

Differential fault current in phase A

263 Fault phase B PSL Input Signal 87BB Busbar Protection

Differential fault current in phase B

264 Fault phase C PSL Input Signal 87BB Busbar Protection

Differential fault current in phase C

265 Earth Fault PSL Input Signal 87BB Busbar Protection

Differential sensitive earth fault current

266 Circt Flt Alm Zx PSL Input Signal Scheme Integrity Circuitry fault Alarm on 1 or several zones Logical OR of DDB 168 to 175

267 Alm Lck Level 1 PSL Input Signal Scheme Integrity Commissioning mode 1: 87BB monitoring Logical OR of DDB 224 to 231

268 Alm Lck Level 2 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled Logical OR of DDB 232 to 239

269 Config. valid PSL Input Signal Scheme Integrity Valid Setting configuration 270 Topology valid PSL Input Signal Scheme Integrity Valid Topology file 272 Fibre Com Worn PSL Input Signal Relay Integrity Warning: fibre communication to be changed 275 Fault Check Zone PSL Input Signal 87BB Busbar

Protection Differential fault detected by the Check Zone

276 Circt Flt ph A PSL Input Signal Scheme Integrity Circuitry fault in phase A 277 Circt Flt ph B PSL Input Signal Scheme Integrity Circuitry fault in phase B 278 Circt Flt ph C PSL Input Signal Scheme Integrity Circuitry fault in phase C 279 Circt Flt Earth PSL Input Signal Scheme Integrity Circuitry fault on the neutral 280 Circt Flt Lck Zx PSL Input Signal Scheme Integrity Circuitry fault blocking Zone x

Logical OR of DDB 160 to 239 281 PU Error Alm Zx PSL Input Signal Scheme Integrity PU error Alarm in Zone x

Logical OR of DDB 152 to 159 282 PU Error Lock Zx PSL Input Signal Scheme Integrity PU error blocking Zone x

Logical OR of DDB 144 to 151 283 SEF Blocked PSL Input Signal 87BB SEF Busbar

Protection 87BB SEF blocked by opto input Logical OR of DDB 208 to 215

284 Circt Flt Alm CZ PSL Input Signal Scheme Integrity Circuitry fault on the Check Zone 285 Circt Flt Lck CZ PSL Input Signal Scheme Integrity Circuitry fault blocking the Check Zone 286 PU Error Alm CZ PSL Input Signal Scheme Integrity PU error Alarm in the Check Zone 287 PU Error Lock CZ PSL Input Signal Scheme Integrity PU error blocking the Check Zone 288 Err Chan 1 Com

A PSL Input Signal Relay Integrity PU communication error: channel 1 board A

Page 233: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-15

PL

DDB No.

English Text Source Description

289 Err Chan 2 Com A

PSL Input Signal Relay Integrity PU communication error: channel 2 board A

290 Err Chan 3 Com A

PSL Input Signal Relay Integrity PU communication error: channel 3 board A

291 Err Chan 4 Com A

PSL Input Signal Relay Integrity PU communication error: channel 4 board A

312 Err Chan 1 Com G

PSL Input Signal Relay Integrity PU communication error: channel 1 board G

313 Err Chan 2 Com G

PSL Input Signal Relay Integrity PU communication error: channel 2 board G

314 Err Chan 3 Com G

PSL Input Signal Relay Integrity PU communication error: channel 3 board G

315 Err Chan 4 Com G

PSL Input Signal Relay Integrity PU communication error: channel 4 board G

324 PU Adr 34 error PSL Input Signal Scheme Integrity Error: several PUs with address 34 351 PU Adr 07 error PSL Input Signal Scheme Integrity Error: several PUs with address 7 355 Minor Err COM1 PSL Input Signal Relay Integrity Minor error in communication board A 356 Minor Err COM2 PSL Input Signal Relay Integrity Minor error in communication board B 357 Minor Err COM3 PSL Input Signal Relay Integrity Minor error in communication board C 358 Minor Err COM4 PSL Input Signal Relay Integrity Minor error in communication board D 359 Minor Err COM5 PSL Input Signal Relay Integrity Minor error in communication board E 360 Minor Err COM6 PSL Input Signal Relay Integrity Minor error in communication board F 361 Minor Err COM7 PSL Input Signal Relay Integrity Minor error in communication board G 364 Operating Mode1 PSL Input Signal Scheme Integrity For Expert Only 365 Operating Mode2 PSL Input Signal Scheme Integrity For Expert Only 366 87BB InstantTrip PSL Input Signal 87BB Busbar

Protection 87BB Trip after fault detection on 2 successive samples. Function disabled during CT saturation.

367 87BB DelayedTrip PSL Input Signal 87BB Busbar Protection

87BB Trip after fault detection on 2 successive half periods. Function to be able to trip on internal fault with CT saturation.

368 PU->CU Signal 01

PSL Input Signal PSL Virtual Signal 01 from any PU to the CU via the fibre optic

383 PU->CU Signal 16

PSL Input Signal PSL Virtual Signal 16 from any PU to the CU via the fibre optic

385 87BB Enabled PSL Input Signal 87BB Busbar Protection

Busbar protection enable

386 87BBN Enabled PSL Input Signal 87BB SEF Busbar Protection

Busbar earth enable

387 Circ Flt Reset PSL Input Signal Commissioning Reset circuitry fault alarm and / or blocking 388 Topo/Set

Changed PSL Input Signal Group Selection Change on topology or configuration

389 Manual Start DR PSL Input Signal Commissioning Disturbance recorder - Manual start 390 PU Topo invalid PSL Input Signal Scheme Integrity Topology file error for one or several PU 391 PU Error Reset PSL Input Signal Scheme Integrity Reset PU Error alarm and / or blocking 392 87BB Blocked PSL Input Signal Scheme Integrity 87BB phase and earth algorithms blocked by opto

input 398 General Alarm PSL Input Signal Scheme Integrity General alarm 468 Fault_REC_TRIG FRT PSL Trigger for the Fault Recorder 469 Battery Fail PSL Input Signal Relay Integrity Front panel Battery Failure 470 Field Volt Fail PSL Input Signal Relay Integrity 48V Field Voltage Failure 471 Comm2 H/W FAIL PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 472 GOOSE IED

Absent PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 473 NIC Not Fitted PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 474 NIC No Response PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 475 NIC Fatal Error PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 476 NIC Soft. Reload PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) 477 Bad TCP/IP Cfg. PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented)

Page 234: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-16

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

478 Bad OSI Config. PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

479 NIC Link Fail PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

480 NIC SW Mis-Match

PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

481 IP Addr Conflict PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

482 IM Loopback PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

483 IM Message Fail PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

484 IM Data CD Fail PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

485 IM Channel Fail PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

486 Backup Setting PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

544 GOOSE VIP 1 GOOSEIN GOOSE Input Command

GOOSE Input 1 Not Used Allows binary signals that are mapped to virtual inputs to interface into PSL (reserved for future use when IEC61850 implemented)

575 GOOSE VIP 32 GOOSEIN GOOSE Input Command

GOOSE Input 1 Not Used Allows binary signals that are mapped to virtual inputs to interface into PSL (reserved for future use when IEC61850 implemented)

576 GOOSE OUT 1 GOOSEOUT PSL GOOSE Output 1 Not Used Allows user to control a binary signal which can be mapped via SCADA protocol output to other devices (reserved for future use when IEC61850 implemented)

583 GOOSE OUT 8 GOOSEOUT PSL GOOSE Output 8 Not Used Allows user to control a binary signal which can be mapped via SCADA protocol output to other devices (reserved for future use when IEC61850 implemented)

584 InterMiCOM in 1 INTERIN InterMiCOM Not Used 591 InterMiCOM in 8 INTERIN InterMiCOM Not Used 592 InterMiCOM out 1 INTEROUT InterMiCOM Not Used 599 InterMiCOM out 8 INTEROUT InterMiCOM Not Used 608 Control Input 1 CONTROL Control Input

Command Control Input 1 - for SCADA and menu commands into PSL

639 Control Input 32 CONTROL Control Input Command

Control Input 32 - for SCADA and menu commands into PSL

640 LED 1 Red TRI_LED PSL (LED) Programmable LED 1 Red is energized 641 LED 1 Grn TRI_LED PSL (LED) Programmable LED 1 Green is energized 654 LED 8 Red TRI_LED PSL (LED) Programmable LED 8 Red is energized 655 LED 8 Grn TRI_LED PSL (LED) Programmable LED 8 Green is energized 656 FnKey LED 1 Red TRI_LED PSL (LED) Programmable Function Key LED 1 Red is energized 657 FnKey LED 1 Grn TRI_LED PSL (LED) Programmable Function Key LED 1 Green is

energized 674 FnKey LED 10

Red TRI_LED PSL (LED) Programmable Function Key LED 10 Red is energized

675 FnKey LED 10 Grn

TRI_LED PSL (LED) Programmable Function Key LED 10 Green is energized

676 Function Key 1 FUNCTION_KEY PSL (Function Key) Function Key 1 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

685 Function Key 10 FUNCTION_KEY PSL (Function Key) Function Key 10 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

700 Relay condit 01 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 707 Relay condit 08 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 764 LED 1 Red Condit TRI_LED_CON Output Conditioner Assignment of input signal to drive output LED 1Red 765 LED 1 Grn Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 1Green.

To drive LED1 Yellow DDB 764 and DDB 765 must be driven at the same time

Page 235: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-17

PL

DDB No.

English Text Source Description

778 LED 8 Red Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8Red 779 LED 8 Grn Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8 Green.

To drive LED8 Yellow DDB 778 and DDB 779 must be active at the same time

780 FnKey LED 1 Red TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 1 Red. This LED is associated with Function Key 1

781 FnKey LED 1 Grn TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 1 Green. This LED is associated with Function Key 1. To drive function key LED, yellow DDB 692 and DDB 693 must be active at the same time

797 FnKey LED 9 Grn TRI_LED_CON Output Conditioner 798 FnKey LED 10

Red TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED

10 Red. This LED is associated with Function Key 10

799 FnKey LED 10 Grn

TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Green. This LED is associated with Function Key 10. To drive function key LED1 yellow, DDB 710 and DDB 711 must be active at the same time

923 Int. Node 923 Can be created automatically by the PSL 1022 Int. Node 1022 Can be created automatically by the PSL

1.7.2 Sorted by DDB name:

English Text DDB No.

Source Description

87BB Blocked 392 PSL Input Signal Scheme Integrity 87BB Blocked by opto input 87BB DelayedTrip 367 PSL Input Signal 87BB Busbar

Protection 87BB Trip after fault detection on 2 successive half periods. Function to be able to trip on internal fault with CT saturation.

87BB Enabled 385 PSL Input Signal 87BB Busbar Protection

Busbar protection enable

87BB InstantTrip 366 PSL Input Signal 87BB Busbar Protection

87BB Trip after fault detection on 2 successive samples. Function disabled during CT saturation.

87BBN Enabled 386 PSL Input Signal 87BB SEF Busbar Protection

Busbar earth enable

All Prot Blocked 111 PSL Output Signal PSL (Commissioning) To disable all the protections (CU & PU) Alm Lck Level 1 267 PSL Input Signal Scheme Integrity Commissioning mode 1: 87BB monitoring

Logical OR of DDB 224 to 231 Alm Lck Level 2 268 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled

Logical OR of DDB 232 to 239 Backup Setting 486 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) Bad OSI Config. 478 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) Bad TCP/IP Cfg. 477 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) Battery Fail 469 PSL Input Signal Relay Integrity Front panel Battery Failure Circ Flt Reset 387 PSL Input Signal Commissioning Reset circuitry fault alarm and / or blocking Circt Flt Alm CZ 284 PSL Input Signal Scheme Integrity Circuitry fault on the Check Zone Circt Flt Alm z1 175 PSL Input Signal 87BB Busbar Protection Circuitry fault alarm in zone 1 Circt Flt Alm z8 168 PSL Input Signal 87BB Busbar

Protection Circuitry fault alarm in zone 8

Circt Flt Alm Zx 266 PSL Input Signal Scheme Integrity Circuitry fault Alarm on 1 or several zones Logical OR of DDB 168 to 175

Circt Flt Earth 279 PSL Input Signal Scheme Integrity Circuitry fault on the neutral Circt Flt Lck CZ 285 PSL Input Signal Scheme Integrity Circuitry fault blocking the Check Zone Circt Flt Lck z1 167 PSL Input Signal 87BB Busbar

Protection Circuitry fault blocking of zone 1

Circt Flt Lck z8 160 PSL Input Signal 87BB Busbar Protection

Circuitry fault blocking of zone 8

Circt Flt Lck Zx 280 PSL Input Signal Scheme Integrity Circuitry fault blocking Zone x Logical OR of DDB 160 to 239

Circt Flt ph A 276 PSL Input Signal Scheme Integrity Circuitry fault in phase A Circt Flt ph B 277 PSL Input Signal Scheme Integrity Circuitry fault in phase B Circt Flt ph C 278 PSL Input Signal Scheme Integrity Circuitry fault in phase C Comm2 H/W FAIL 471 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented)

Page 236: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-18

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

Config. valid 269 PSL Input Signal Scheme Integrity Valid Setting configuration Control Input 1 608 CONTROL Control Input

Command Control Input 1 - for SCADA and menu commands into PSL

Control Input 32 639 CONTROL Control Input Command

Control Input 32 - for SCADA and menu commands into PSL

CU->PU Signal 01

112 PSL Output Signal

PSL Virtual Signal 01 from the CU to all the PUs via the fibre optic

CU->PU Signal 16

127 PSL Output Signal

PSL Virtual Signal 16 from the CU to all the PUs via the fibre optic

Earth Fault 265 PSL Input Signal 87BB Busbar Protection

Differential sensitive earth fault current

Err Chan 1 Com A

288 PSL Input Signal Relay Integrity PU communication error: channel 1 board A

Err Chan 1 Com G

312 PSL Input Signal Relay Integrity PU communication error: channel 1 board G

Err Chan 2 Com A

289 PSL Input Signal Relay Integrity PU communication error: channel 2 board A

Err Chan 2 Com G

313 PSL Input Signal Relay Integrity PU communication error: channel 2 board G

Err Chan 3 Com A

290 PSL Input Signal Relay Integrity PU communication error: channel 3 board A

Err Chan 3 Com G

314 PSL Input Signal Relay Integrity PU communication error: channel 3 board G

Err Chan 4 Com A

291 PSL Input Signal Relay Integrity PU communication error: channel 4 board A

Err Chan 4 Com G

315 PSL Input Signal Relay Integrity PU communication error: channel 4 board G

Ext Start DR 107 PSL Output Signal

PSL Starting Disturbance Recorder

Ext Trip 50BF 261 PSL Input Signal 50BF Backtrip protection

50BF backtrip request by opto input Logical OR of DDB 216 to 223

Ext Trip 50BF z1 223 PSL Output Signal

PSL (50BF Backtrip protection)

External Breaker failure trip order (50BF) of zone 1 opto input

Ext Trip 50BF z8 216 PSL Output Signal

PSL (50BF Backtrip protection)

External Breaker failure trip order (50BF) of zone 8 opto input

Fault Check Zone 275 PSL Input Signal 87BB Busbar Protection

Differential fault detected by the Check Zone

Fault phase A 262 PSL Input Signal 87BB Busbar Protection

Differential fault current in phase A

Fault phase B 263 PSL Input Signal 87BB Busbar Protection

Differential fault current in phase B

Fault phase C 264 PSL Input Signal 87BB Busbar Protection

Differential fault current in phase C

Fault_REC_TRIG 468 FRT PSL Trigger for the Fault Recorder Fibre Com Error 135 PSL Input Signal Scheme Integrity Communication error to at least 1 PU Fibre Com Worn 272 PSL Input Signal Relay Integrity Warning: fibre communication to be changed Field Volt Fail 470 PSL Input Signal Relay Integrity 48V Field Voltage Failure Flt 87BB Zone 1 183 PSL Input Signal 87BB Busbar

Protection Differential fault current in zone 1

Flt 87BB Zone 8 176 PSL Input Signal 87BB Busbar Protection

Differential fault current in zone 8

FnKey LED 1 Grn 657 TRI_LED PSL (LED) Programmable Function Key LED 1 Green is energized

FnKey LED 1 Grn 781 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 1 Green. This LED is associated with Function Key 1. To drive function key LED, yellow DDB 692 and DDB 693 must be active at the same time

FnKey LED 1 Red 656 TRI_LED PSL (LED) Programmable Function Key LED 1 Red is energized FnKey LED 1 Red 780 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED

1 Red. This LED is associated with Function Key 1

FnKey LED 10 Grn

675 TRI_LED PSL (LED) Programmable Function Key LED 10 Green is energized

FnKey LED 10 Grn

799 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Green. This LED is associated with Function Key 10. To drive function key LED1 yellow, DDB 710 and DDB 711 must be active at the same time

FnKey LED 10 Red

674 TRI_LED PSL (LED) Programmable Function Key LED 10 Red is energized

Page 237: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-19

PL

English Text DDB No.

Source Description

FnKey LED 10 Red

798 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Red. This LED is associated with Function Key 10

Function Key 1 676 FUNCTION_KEY PSL (Function Key) Function Key 1 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

Function Key 10 685 FUNCTION_KEY PSL (Function Key) Function Key 10 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

General Alarm 398 PSL Input Signal Scheme Integrity General alarm GOOSE IED Absent

472 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

GOOSE OUT 1 576 GOOSEOUT PSL GOOSE Output 1 Not Used Allows user to control a binary signal which can be mapped via SCADA protocol output to other devices (reserved for future use when IEC61850 implemented)

GOOSE OUT 8 583 GOOSEOUT PSL GOOSE Output 8 Not Used Allows user to control a binary signal which can be mapped via SCADA protocol output to other devices (reserved for future use when IEC61850 implemented)

GOOSE VIP 1 544 GOOSEIN GOOSE Input Command

GOOSE Input 1 Not Used Allows binary signals that are mapped to virtual inputs to interface into PSL (reserved for future use when IEC61850 implemented)

GOOSE VIP 32 575 GOOSEIN GOOSE Input Command

GOOSE Input 1 Not Used Allows binary signals that are mapped to virtual inputs to interface into PSL (reserved for future use when IEC61850 implemented)

IM Channel Fail 485 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

IM Data CD Fail 484 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

IM Loopback 482 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

IM Message Fail 483 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

INP block SEF z1 215 PSL Output Signal

PSL (87BB SEF Busbar Protection)

87BB SEF protection blocking of zone 1 opto input

INP block SEF z8 208 PSL Output Signal

PSL (87BB SEF Busbar Protection)

87BB SEF protection blocking of zone 8 opto input

INP Lck Lev.1 z1 231 PSL Output Signal

PSL (Commissioning) Maintenance Mode 1 (87BB monitoring) of zone 1 opto input

INP Lck Lev.1 z8 224 PSL Output Signal

PSL (Commissioning) Maintenance Mode 1 (87BB monitoring) of zone 8 opto input

INP Lck Lev.2 z1 239 PSL Output Signal

PSL (Commissioning) Maintenance Mode 2 (50BF & 87BB blocked) of zone 1 opto input

INP Lck Lev.2 z8 232 PSL Output Signal

PSL (Commissioning) Maintenance Mode 2 (50BF & 87BB blocked) of zone 8 opto input

Int. Node 1022 1022 Can be created automatically by the PSL Int. Node 923 923 Can be created automatically by the PSL InterMiCOM in 1 584 INTERIN InterMiCOM Not Used InterMiCOM in 8 591 INTERIN InterMiCOM Not Used InterMiCOM out 1 592 INTEROUT InterMiCOM Not Used InterMiCOM out 8 599 INTEROUT InterMiCOM Not Used IP Addr Conflict 481 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) Lck Lev.1 Zone 1 247 PSL Input Signal Scheme Integrity Commissioning mode 1: 50BF disabled in zone 1 Lck Lev.1 Zone 8 240 PSL Input Signal Scheme Integrity Commissioning mode 1: 50BF disabled in zone 8 Lck Lev.2 Zone 1 255 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled in

zone 1 Lck Lev.2 Zone 8 248 PSL Input Signal Scheme Integrity Commissioning mode 2: 87BB & 50BF disabled in

zone 8 LED 1 Grn 641 TRI_LED PSL (LED) Programmable LED 1 Green is energized LED 1 Grn Condit 765 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 1Green.

To drive LED1 Yellow DDB 764 and DDB 765 must be driven at the same time

LED 1 Red 640 TRI_LED PSL (LED) Programmable LED 1 Red is energized LED 1 Red Condit 764 TRI_LED_CON Output Conditioner Assignment of input signal to drive output LED 1Red LED 8 Grn 655 TRI_LED PSL (LED) Programmable LED 8 Green is energized

Page 238: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-20

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

LED 8 Grn Condit 779 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8 Green. To drive LED8 Yellow DDB 778 and DDB 779 must be active at the same time

LED 8 Red 654 TRI_LED PSL (LED) Programmable LED 8 Red is energized LED 8 Red Condit 778 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8Red Man.Trip Zone 1 199 PSL Input Signal Commissioning Manual trip of zone 1 Man.Trip Zone 8 192 PSL Input Signal Commissioning Manual trip of zone 8 Manual Start DR 389 PSL Input Signal Commissioning Disturbance recorder - Manual start Minor Err COM1 355 PSL Input Signal Relay Integrity Minor error in communication board A Minor Err COM2 356 PSL Input Signal Relay Integrity Minor error in communication board B Minor Err COM3 357 PSL Input Signal Relay Integrity Minor error in communication board C Minor Err COM4 358 PSL Input Signal Relay Integrity Minor error in communication board D Minor Err COM5 359 PSL Input Signal Relay Integrity Minor error in communication board E Minor Err COM6 360 PSL Input Signal Relay Integrity Minor error in communication board F Minor Err COM7 361 PSL Input Signal Relay Integrity Minor error in communication board G NIC Fatal Error 475 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) NIC Link Fail 479 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) NIC No Response 474 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) NIC Not Fitted 473 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) NIC Soft. Reload 476 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850

implemented) NIC SW Mis-Match

480 PSL Input Signal IEC 61850 Not Used (reserved for future use when IEC61850 implemented)

Operating Mode1 364 PSL Input Signal Scheme Integrity For Expert Only Operating Mode2 365 PSL Input Signal Scheme Integrity For Expert Only Opto Label 01 64 OPTO Opto Input Opto Input 1 Opto Label 08 71 OPTO Opto Input Opto Input 8 PU Adr 07 error 351 PSL Input Signal Scheme Integrity Error: several PUs with address 7 PU Adr 34 error 324 PSL Input Signal Scheme Integrity Error: several PUs with address 34 PU Error Alm CZ 286 PSL Input Signal Scheme Integrity PU error Alarm in the Check Zone PU Error Alm z1 159 PSL Input Signal Scheme Integrity PU error alarm in zone 1 PU Error Alm z8 152 PSL Input Signal Scheme Integrity PU error alarm in zone 8 PU Error Alm Zx 281 PSL Input Signal Scheme Integrity PU error Alarm in Zone x

Logical OR of DDB 152 to 159 PU Error Lck z1 151 PSL Input Signal Scheme Integrity PU error blocking of zone 1 PU Error Lck z8 144 PSL Input Signal Scheme Integrity PU error blocking of zone 8 PU Error Lock CZ 287 PSL Input Signal Scheme Integrity PU error blocking the Check Zone PU Error Lock Zx 282 PSL Input Signal Scheme Integrity PU error blocking Zone x

Logical OR of DDB 144 to 151 PU Error Reset 391 PSL Input Signal Scheme Integrity Reset PU Error alarm and / or blocking PU Topo invalid 390 PSL Input Signal Scheme Integrity Topology file error for one or several PU PU->CU Signal 01

368 PSL Input Signal PSL Virtual Signal 01 from any PU to the CU via the fibre optic

PU->CU Signal 16

383 PSL Input Signal PSL Virtual Signal 16 from any PU to the CU via the fibre optic

Relay condit 01 700 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner Relay condit 08 707 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner Relay Label 01 0 RELAY Output Conditioner Output Relay 01 Relay Label 08 7 RELAY Output Conditioner Output Relay 08 Reset Indication 109 PSL Output

Signal PSL Reset all indications (Led and relays latched in PSL)

that includes the Led Alarm SEF Blocked 283 PSL Input Signal 87BB SEF Busbar

Protection 87BB SEF blocked by opto input Logical OR of DDB 208 to 215

Sett Grp Bit LSB 104 PSL Output Signal

PSL Setting Group Selector X1 (low bit) SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

Sett Grp Bit MSB 105 PSL Output Signal

PSL Input signal Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

Timer in 436 436 TIMERIN PSL Timer Input Timer in 451 451 TIMERIN PSL Timer Input Timer out 467 467 TIMEROUT Timer Output

Page 239: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-21

PL

English Text DDB No.

Source Description

To Block 87BB 108 PSL Output Signal

PSL To Block 87BB phase & Earth

To Reset CircFlt 106 PSL Output Signal

PSL To Reset the Circuitry Fault

To Reset PU err 110 PSL Output Signal

PSL To reset PU error

Topo/Set Changed

388 PSL Input Signal Group Selection Change on topology or configuration

Topology valid 270 PSL Input Signal Scheme Integrity Valid Topology file Trip 50BF 259 PSL Input Signal 50BF Backtrip

protection Breaker fail trip order (50BF) Logical OR of DDB 200 to 207

Trip 50BF Locked 260 PSL Input Signal Scheme Integrity Breaker fail trip order blocked by commissioning mode or Circuitry fault

Trip 50BF Zone 1 207 PSL Input Signal 50BF Backtrip protection

Breaker failure trip (50BF) of zone 1

Trip 50BF Zone 8 200 PSL Input Signal 50BF Backtrip protection

Breaker failure trip (50BF) of zone 8

Trip 87BB 256 PSL Input Signal 87BB Busbar Protection

Busbar trip order (87BB) Logical OR of DDB 184 to 191

Trip 87BB Locked 257 PSL Input Signal Scheme Integrity Busbar trip order blocked by commissioning mode or Circuitry fault

Trip 87BB Zone 1 191 PSL Input Signal 87BB Busbar Protection

Busbar trip of zone 1

Trip 87BB Zone 8 184 PSL Input Signal 87BB Busbar Protection

Busbar trip of zone 8

Trip Manual zone 258 PSL Input Signal Commissioning Manual Trip Order Logical OR of DDB 192 to 199 User Alarm 1 136 PSL Output Signal PSL Triggers User Alarm 1 message to be alarmed on LCD

display (self-resetting)

User Alarm 8 143 PSL Output Signal PSL Triggers User Alarm 8 message to be alarmed on LCD display (self-resetting)

1.8 Description of P742 logic nodes

1.8.1 Sorted by DDB number:

DDB No.

English Text Source Description

0 Relay Label 01 RELAY Output Conditioner Output Relay 01 - All trips (FSL) but not retrip 1 Relay Label 02 RELAY Output Conditioner Output Relay 02 - All trips (FSL) but not retrip 2 Relay Label 03 RELAY Output Conditioner Output Relay 03 - All trips (FSL) but not retrip 3 Relay Label 04 RELAY Output Conditioner Output Relay 04 7 Relay Label 08 RELAY Output Conditioner Output Relay 08

64 Opto Label 01 OPTO Opto Input Opto Input 1 79 Opto Label 16 OPTO Opto Input Opto Input 16 96 LED 1 LED Led Conditioner Red LED 1

103 LED 8 LED Led Conditioner Red LED 8 104 Q1 Aux. (89b) PSL Output

Signal PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the

isolator 1 105 Q1 Aux. (89a) PSL Output

Signal PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the

isolator 1 114 Q6 Aux. (89b) PSL Output

Signal PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the

isolator 6 115 Q6 Aux. (89a) PSL Output

Signal PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the

isolator 6 116 Ext. 3 ph Trip PSL Output

Signal PSL (50BF protection)

External 3 phase Trip Allows external protection to initiate breaker fail (if enabled)

117 External Trip A PSL Output Signal

PSL (50BF protection)

External 3 phase A Trip Allows external protection to initiate breaker fail (if enabled)

118 External Trip B PSL Output Signal

PSL (50BF protection)

External 3 phase B Trip Allows external protection to initiate breaker fail (if enabled)

119 External Trip C PSL Output Signal

PSL (50BF protection)

External 3 phase C Trip Allows external protection to initiate breaker fail (if enabled)

120 Man.CB Close Cmd

PSL Output Signal

PSL Manual/operator Circuit Breaker trip command

Page 240: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-22

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

121 CB not available PSL Output Signal

PSL Circuit Breaker is not available to trip

122 Ext. CB Fail PSL Output Signal

PSL (50BF Backtrip protection)

50BF Backtrip order from an other protection

123 CB Aux. 3ph(52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (3 phase)

124 CB Aux. 3ph(52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (3 phase)

125 CB Aux. A (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase A)

126 CB Aux. A (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase A)

127 CB Aux. B (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase B)

128 CB Aux. B (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase B)

129 CB Aux. C (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase C)

130 CB Aux. C (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase C)

131 Reset Trip latch PSL Output Signal

PSL (Commissioning)

Reset Latched Relays

132 Sett Grp Bit LSB PSL Output Signal

PSL Setting Group Selector X1 (low bit) SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

133 Sett Grp Bit MSB PSL Output Signal

PSL Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

134 Reset All values PSL Output Signal

PSL (Commissioning)

Not used

135 Reset Indication PSL Output Signal

PSL (Commissioning)

Reset all indications (Led and relays latched in PSL) that includes the Led Alarm

136 User Alarm 1 PSL Output Signal

PSL Triggers User Alarm 1 message to be alarmed on LCD display (self-resetting)

142 User Alarm 7 PSL Output Signal

PSL Triggers User Alarm 7 message to be alarmed on LCD display (self-resetting)

143 Aux Volt Superv PSL Output Signal

PSL (Scheme Integrity)

Triggers User Alarm 8 message to be alarmed on LCD display (self-resetting)

144 PU->CU Signal 01 PSL Output Signal

PSL Virtual Signal 01 from the PU to the CU via the fibre optic

159 PU->CU Signal 16 PSL Output Signal

PSL Virtual Signal 16 from the PU to the CU via the fibre optic

160 Man.Close Q1 Cmd

PSL Output Signal

PSL Manual/operator Isolator 1 (switch) closing command

165 Man.Close Q6 Cmd

PSL Output Signal

PSL Manual/operator Isolator 6 (switch) closing command

166 Man. Close CB PSL Output Signal

PSL Circuit Breaker closing order (CB Control)

167 Man. Trip CB PSL Output Signal

PSL Circuit Breaker tripping order (CB Control)

168 Ext. Retrip Ph A PSL Input Signal 50BF Protection Retrip of phase A due to an external trip initiation of this phase (at tBF3)

169 Ext. Retrip Ph B PSL Input Signal 50BF Protection Retrip of phase B due to an external trip initiation of this phase (at tBF3)

170 Ext. Retrip Ph C PSL Input Signal 50BF Protection Retrip of phase C due to an external trip initiation of this phase (at tBF3)

171 Int. Retrip 3 ph PSL Input Signal 50BF Protection Retrip triphase due to a 87BB trip initiation (at tBF1) 172 CBF Int Backtrip PSL Input Signal 50BF Backtrip

Protection Backtrip triphase due to a 87BB trip initiation (at tBF2)

173 CBF Ext Backtrip PSL Input Signal 50BF Backtrip Protection

Backtrip triphase due to an external trip initiation (at tBF4)

174 CB Fail Alarm PSL Input Signal 50BF Protection Circuit Breaker Fail Alarm Logical OR of DDB 168 to 173

176 I>1 Start A PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start A 177 I>1 Start B PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start B 178 I>1 Start C PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start C 179 IN>1 Start PSL Input Signal Earth Fault 1st Stage Earth Fault Start

Page 241: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-23

PL

DDB No.

English Text Source Description

180 I>1 Trip PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Trip 3 phase 181 IN>1 Trip PSL Input Signal Earth Fault 1st Stage Earth Fault Trip 182 I>2 Start A PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start A 183 I>2 Start B PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start B 184 I>2 Start C PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start C 185 IN>2 Start PSL Input Signal Earth Fault 2nd Stage Earth Fault Start 186 I>2 Trip PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Trip 3 phase 187 IN>2 Trip PSL Input Signal Earth Fault 2nd Stage Earth Fault Trip 192 CU->PU Signal 01 PSL Input Signal PSL Virtual Signal 01 from the CU to the PU via the fibre

optic 207 CU->PU Signal 16 PSL Input Signal PSL Virtual Signal 16 from the CU to the PU via the fibre

optic 208 Zone 8 Off PSL Input Signal CU Information Zone 8 in commissioning mode or blocked

by a Circuitry fault or a PU error 215 Zone 1 Off PSL Input Signal CU Information Zone 1 in commissioning mode or blocked

by a Circuitry fault or a PU error 216 Trip Zone 8 PSL Input Signal CU Information Trip of Zone 8 (87BB, 50BF or manual) 223 Trip Zone 1 PSL Input Signal CU Information Trip of Zone 1 (87BB, 50BF or manual) 224 I>BB Start A PSL Input Signal Phase Overcurrent Local overcurrent phase A Trip confirmation for 87BB or

50BF (CU) trip order 225 I>BB Start B PSL Input Signal Phase Overcurrent Local overcurrent phase B Trip confirmation for 87BB or

50BF (CU) trip order 226 I>BB Start C PSL Input Signal Phase Overcurrent Local overcurrent phase C Trip confirmation for 87BB

or 50BF (CU) trip order 227 IN>BB Start PSL Input Signal Earth Fault Local overcurrent Trip confirmation for the neutral 228 I>BB Block Ph A PSL Input Signal Phase Overcurrent Local overcurrent phase A to block the 87BB on

external fault 229 I>BB Block Ph B PSL Input Signal Phase Overcurrent Local overcurrent phase B to block the 87BB on

external fault 230 I>BB Block Ph C PSL Input Signal Phase Overcurrent Local overcurrent phase C to block the 87BB on

external fault 231 IN>BB Block PSL Input Signal Earth Fault Local overcurrent earth to block the 87BB on external

fault 232 Saturation ph A PSL Input Signal Saturation Saturation on phase A 233 Saturation ph B PSL Input Signal Saturation Saturation on phase B 234 Saturation ph C PSL Input Signal Saturation Saturation on phase C 235 Current Overflow PSL Input Signal Saturation Fibre optic Maximum primary current encoding

exceeded 236 Max Flux ph A PSL Input Signal Saturation Maximum flux reached in the phase A CT 237 Max Flux ph B PSL Input Signal Saturation Maximum flux reached in the phase B CT 238 Max Flux ph C PSL Input Signal Saturation Maximum flux reached in the phase C CT 239 Alarm

OffsetABCN PSL Input Signal Saturation Offset current read by the Analog board Phase A, B, C

or N 240 Predict err ph A PSL Input Signal Saturation Variation error phase A (derived current) 241 Predict err ph B PSL Input Signal Saturation Variation error phase B (derived current) 242 Predict err ph C PSL Input Signal Saturation Variation error phase C (derived current) 244 Sat ADC ph A PSL Input Signal Saturation Analog to Digital Converter of phase A current

saturated 245 Sat ADC ph B PSL Input Signal Saturation Analog to Digital Converter of phase B current

saturated 246 Sat ADC ph C PSL Input Signal Saturation Analog to Digital Converter of phase C current

saturated 247 Sat ADC Neutral PSL Input Signal Saturation Analog to Digital Converter of the neutral current

saturated 248 Delta IA PSL Input Signal Saturation Variation detected on phase A 249 Delta IB PSL Input Signal Saturation Variation detected on phase B 250 Delta IC PSL Input Signal Saturation Variation detected on phase C 251 Delta IN PSL Input Signal Saturation Variation detected on the neutral 252 Fibre Com Error PSL Input Signal Relay Integrity Fibre communication to the CU error 253 Fibre Com Worn PSL Input Signal Relay Integrity Warning: fibre communication to be changed 254 Acq Error 3Io PSL Input Signal Relay Integrity Sample acquisition error: 3 x Io <> In 255 CT Fail Alarm PSL Input Signal Scheme Integrity Internal PU CT failure

Page 242: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-24

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

256 Internal Trip PSL Input Signal Local Protection Triphase Trip (87BB, 50BF(CU), I>, IN> or manual zone trip (CU)). Trip command directly applied to relay 1, 2, 3 (without PSL)

257 Trip 87BB PSL Input Signal 87BB Busbar Protection

Busbar trip order (87BB), general information common to all PUs, the PU can be connected to an healthy zone

258 Trip 87BB Locked PSL Input Signal Scheme Integrity Busbar trip order blocked by the CU commissioning mode or Circuitry fault

259 Trip 50BF (CU) PSL Input Signal 50BF Backtrip Protection

Breaker fail trip order (50BF), general information common to all PUs, the PU can be connected to an healthy zone

260 Man.Trip zone PSL Input Signal Commissioning Manual Trip Order of a zone, general information common to all PUs, the PU can be connected to an healthy zone

261 Dead Zone Fault PSL Input Signal Local Protection Fault in the dead zone 262 Dead Zone Phase PSL Input Signal Local Protection Fault in the dead zone on a phase 263 Dead Zone Earth PSL Input Signal Local Protection Fault in the dead zone on the neutral 264 Operating mode 1 PSL Input Signal Relay Integrity For Expert Only 265 Operating mode 2 PSL Input Signal Relay Integrity For Expert Only 266 Operating mode 3 PSL Input Signal Relay Integrity For Expert Only 267 Config. Valid PSL Input Signal Scheme Integrity Valid Setting configuration 268 Topology valid PSL Input Signal Scheme Integrity Valid Topology file 269 Topo/Set valid PSL Input Signal Scheme Integrity Wrong Topology address 270 All Prot Blocked PSL Input Signal Commissioning All the protections (CU & PU) disabled 288 I> Any Trip PSL Input Signal Phase Overcurrent Overcurrent Trip 289 CBAvailabToTrip PSL Input Signal Scheme Integrity Complement of ddb 297 290 BF Trip Request PSL Input Signal 50BF Protection External or internal Breaker failure trip order request

(50BF) Logical OR of DDB 122, 172 and 173 296 I> No Trip PSL Input Signal Phase Overcurrent Complement of ddb 288 297 CBNotAvailToTrip PSL Input Signal Scheme Integrity Logical OR of ddb 121 and 270 298 BFTripNoRequest PSL Input Signal 50BF Protection Complement of ddb 290 305 Ctrl CB Trip PSL Input Signal Manual Functionality Manual Trip Order of the Circuit Breaker 306 Ctrl CB Close PSL Input Signal Manual Functionality Manual closing order of the Circuit Breaker 307 PU Overhaul

mode PSL Input Signal Commissioning PU in overhaul mode

308 Alm 50BF Disable PSL Input Signal Commissioning PU in 50BF blocked mode Alarm 311 50BF Disabled PSL Output

Signal Commissioning To switch the PU in 50BF blocked mode

312 Overhaul Mode PSL Output Signal

Commissioning To switch the PU in overhaul mode

314 I>BB Enabled PSL Input Signal Local protection Overcurrent Local trip confirmation 315 Trip Rel Latched PSL Input Signal Local protection Trip Relays Latched 316 I>2 Block BB ON PSL Input Signal 87BB protection Fast external phase fault criterion to block the

connected zone enabled 317 IN>2 Block BB ON PSL Input Signal 87BB protection Fast external neutral fault criterion to block the

connected zone enabled 318 Reset Trip Relay PSL Input Signal Commissioning To reset the Trip relays 319 Topo/Set

Changed PSL Input Signal Commissioning Change on topology or configuration

320 Q1 Closed PSL Input Signal PSL Isolator 1 closed (not (Q1 Aux. (89b) AND Q1 Aux. (89a)))

321 Q1 Status Alarm PSL Output Signal

Scheme Integrity Isolator 1 discrepancy (Q1 Aux. (89b) = Q1 Aux. (89a) for too long

330 Q6 Closed PSL Input Signal PSL Isolator 6 closed (not (Q6 Aux. (89b) AND Q6 Aux. (89a)))

331 Q6 Status Alarm PSL Output Signal

Scheme Integrity Isolator 6 discrepancy (Q6 Aux. (89b) = Q6 Aux. (89a) for too long

332 CB Closed PSL Input Signal PSL Circuit Breaker closed (not (CB Aux. (52b) AND CB Aux. (52a)))

333 CB Healthy PSL Input Signal PSL Complement of ddb 121 336 Q1 Status Forced PSL Input Signal Commissioning Isolator 1 status position forced open (by default) or

closed 341 Q6 Status Forced PSL Input Signal Commissioning Isolator 6 status position forced open (by default) or

closed 342 CB Status Forced PSL Input Signal Commissioning CB status position forced open (by default) or closed

Page 243: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-25

PL

DDB No.

English Text Source Description

343 Forced Mode ON PSL Input Signal Commissioning When the forced positions of the CB and the Isolators are used (during commissioning test)

344 CB Aux. 52a PSL Input Signal CB Monitoring ddb 123 or Logical OR of ddb 125 and 127 and 129 345 CB Aux. 52b PSL Input Signal CB Monitoring ddb 124 or Logical AND of ddb 126 and 128 and 130 346 CB Trip 3 ph PSL Input Signal 50BF Protection Triphase Circuit Breaker Trip from CU (Init 50BF TBF1 /

TBF2), Logical OR of : 87BB, 50BF, Manual Trip Zone X

347 CB Trip phase A PSL Input Signal 50BF Protection Phase A Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip A, External Trip 3ph

348 CB Trip phase B PSL Input Signal 50BF Protection Phase B Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip B, External Trip 3ph

349 CB Trip phase C PSL Input Signal 50BF Protection Phase C Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip C, External Trip 3ph

351 General Alarm PSL Input Signal Relay Integrity General Alarm 352 CB Status Alarm PSL Input Signal Scheme Integrity Indication of discrepancy between the 52a and 52b

auxiliary contacts of the Circuit Breaker 353 Man CB Cls Fail PSL Input Signal Scheme Integrity Circuit Breaker Failed to Close

(after a manual/operator close command) 354 Man CB Trip Fail PSL Input Signal Scheme Integrity Circuit Breaker Failed to Trip

(after a manual/operator trip command) 355 Ctrl Cls in Prog PSL Input Signal Commissioning Control Close in Progress

The relay has been given an instruction to close the circuit breaker, but the Manual Close timer Delay has not yet finished timing out

356 Control Close PSL Input Signal Commissioning Control Close command to the circuit breaker. Operates for a manual close command (menu, SCADA)

357 Control Trip PSL Input Signal Commissioning Control Trip Operator trip instruction to the circuit breaker, via menu, or SCADA. (Does not operate for protection element trips)

358 Any Trip PSL Input Signal All Protections Any Trip (Logical OR of ddbs: 0, 1, 2, 168, 169, 170, 171, 256, 261)

428 LED Cond IN 1 LED_CON PSL Assignment of signal to drive LED 1 Red. 435 LED Cond IN 8 LED_CON PSL Assignment of signal to drive LED 8 Red. 436 Timer in 436 TIMERIN PSL Timer Input Input to Auxiliary Timer 1 451 Timer in 451 TIMERIN PSL Timer Input Input to Auxiliary Timer 16 452 Timer out 452 TIMEROUT Timer Output Output from Auxiliary Timer 1 467 Timer out 467 TIMEROUT Timer Output Output from Auxiliary Timer 16 468 Fault_REC_TRIG FRT PSL Trigger for the Fault Recorder 469 Battery Fail PSL Input

Signal Relay Integrity Front panel Battery Failure

470 Field Volt Fail PSL Input Signal

Relay Integrity 48V Field Voltage Failure

700 Relay condit 01 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 1 715 Relay condit 16 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 16 923 Int. Node 923 Can be created automatically by the PSL

1022 Int. Node 1022 Can be created automatically by the PSL

1.8.2 Sorted by DDB name:

English Text DDB No.

Source Description

50BF Disabled 311 PSL Output Signal

Commissioning To switch the PU in 50BF blocked mode

Acq Error 3Io 254 PSL Input Signal Relay Integrity Sample acquisition error: 3 x Io <> In Alarm OffsetABCN

239 PSL Input Signal Saturation Offset current read by the Analog board Phase A, B, C or N

All Prot Blocked 270 PSL Input Signal Commissioning All the protections (CU & PU) disabled Alm 50BF Disable 308 PSL Input Signal Commissioning PU in 50BF blocked mode Alarm Any Trip 358 PSL Input Signal All Protections Any Trip (Logical OR of ddbs:

0, 1, 2, 168, 169, 170, 171, 256, 261)

Page 244: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-26

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

Aux Volt Superv 143 PSL Output Signal

PSL (Scheme Integrity)

Triggers User Alarm 8 message to be alarmed on LCD display (self-resetting)

Battery Fail 469 PSL Input Signal Relay Integrity Front panel Battery Failure BF Trip Request 290 PSL Input Signal 50BF Protection External or internal Breaker failure trip order request

(50BF) Logical OR of DDB 122, 172 and 173 BFTripNoRequest 298 PSL Input Signal 50BF Protection Complement of ddb 290 CB Aux. 3ph(52a) 123 PSL Output

Signal PSL 52-A (CB closed) CB Auxiliary Input (3 phase)

CB Aux. 3ph(52b) 124 PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (3 phase)

CB Aux. 52a 344 PSL Input Signal CB Monitoring ddb 123 or Logical OR of ddb 125 and 127 and 129 CB Aux. 52b 345 PSL Input Signal CB Monitoring ddb 124 or Logical AND of ddb 126 and 128 and 130 CB Aux. A (52a) 125 PSL Output

Signal PSL 52-A (CB closed) CB Auxiliary Input (phase A)

CB Aux. A (52b) 126 PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase A)

CB Aux. B (52a) 127 PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase B)

CB Aux. B (52b) 128 PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase B)

CB Aux. C (52a) 129 PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase C)

CB Aux. C (52b) 130 PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase C)

CB Closed 332 PSL Input Signal PSL Circuit Breaker closed (not (CB Aux. (52b) AND CB Aux. (52a)))

CB Fail Alarm 174 PSL Input Signal 50BF Protection Circuit Breaker Fail Alarm Logical OR of DDB 168 to 173

CB Healthy 333 PSL Input Signal PSL Complement of ddb 121 CB not available 121 PSL Output

Signal PSL Circuit Breaker is not available to trip

CB Status Alarm 352 PSL Input Signal Scheme Integrity Indication of discrepancy between the 52a and 52b auxiliary contacts of the Circuit Breaker

CB Status Forced 342 PSL Input Signal Commissioning CB status position forced open (by default) or closed CB Trip 3 ph 346 PSL Input Signal 50BF Protection Triphase Circuit Breaker Trip from CU (Init 50BF TBF1 /

TBF2), Logical OR of : 87BB, 50BF, Manual Trip Zone X

CB Trip phase A 347 PSL Input Signal 50BF Protection Phase A Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip A, External Trip 3ph

CB Trip phase B 348 PSL Input Signal 50BF Protection Phase B Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip B, External Trip 3ph

CB Trip phase C 349 PSL Input Signal 50BF Protection Phase C Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip C, External Trip 3ph

CBAvailabToTrip 289 PSL Input Signal Scheme Integrity Complement of ddb 297 CBF Ext Backtrip 173 PSL Input Signal 50BF Backtrip

Protection Backtrip triphase due to an external trip initiation (at tBF4)

CBF Int Backtrip 172 PSL Input Signal 50BF Backtrip Protection

Backtrip triphase due to a 87BB trip initiation (at tBF2)

CBNotAvailToTrip 297 PSL Input Signal Scheme Integrity Logical OR of ddb 121 and 270 Config. Valid 267 PSL Input Signal Scheme Integrity Valid Setting configuration Control Close 356 PSL Input Signal Commissioning Control Close command to the circuit breaker.

Operates for a manual close command (menu, SCADA)

Control Trip 357 PSL Input Signal Commissioning Control Trip Operator trip instruction to the circuit breaker, via menu, or SCADA. (Does not operate for protection element trips)

CT Fail Alarm 255 PSL Input Signal Scheme Integrity Internal PU CT failure Ctrl CB Close 306 PSL Input Signal Manual Functionality Manual closing order of the Circuit Breaker Ctrl CB Trip 305 PSL Input Signal Manual Functionality Manual Trip Order of the Circuit Breaker Ctrl Cls in Prog 355 PSL Input Signal Commissioning Control Close in Progress

The relay has been given an instruction to close the circuit breaker, but the Manual Close timer Delay has not yet finished timing out

CU->PU Signal 01 192 PSL Input Signal PSL Virtual Signal 01 from the CU to the PU via the fibre optic

Page 245: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-27

PL

English Text DDB No.

Source Description

CU->PU Signal 16 207 PSL Input Signal PSL Virtual Signal 16 from the CU to the PU via the fibre optic

Current Overflow 235 PSL Input Signal Saturation Fibre optic Maximum primary current encoding exceeded

Dead Zone Earth 263 PSL Input Signal Local Protection Fault in the dead zone on the neutral Dead Zone Fault 261 PSL Input Signal Local Protection Fault in the dead zone Dead Zone Phase 262 PSL Input Signal Local Protection Fault in the dead zone on a phase Delta IA 248 PSL Input Signal Saturation Variation detected on phase A Delta IB 249 PSL Input Signal Saturation Variation detected on phase B Delta IC 250 PSL Input Signal Saturation Variation detected on phase C Delta IN 251 PSL Input Signal Saturation Variation detected on the neutral Ext. 3 ph Trip 116 PSL Output

Signal PSL (50BF protection)

External 3 phase Trip Allows external protection to initiate breaker fail (if enabled)

Ext. CB Fail 122 PSL Output Signal

PSL (50BF Backtrip protection)

50BF Backtrip order from an other protection

Ext. Retrip Ph A 168 PSL Input Signal 50BF Protection Retrip of phase A due to an external trip initiation of this phase (at tBF3)

Ext. Retrip Ph B 169 PSL Input Signal 50BF Protection Retrip of phase B due to an external trip initiation of this phase (at tBF3)

Ext. Retrip Ph C 170 PSL Input Signal 50BF Protection Retrip of phase C due to an external trip initiation of this phase (at tBF3)

External Trip A 117 PSL Output Signal

PSL (50BF protection)

External 3 phase A Trip Allows external protection to initiate breaker fail (if enabled)

External Trip B 118 PSL Output Signal

PSL (50BF protection)

External 3 phase B Trip Allows external protection to initiate breaker fail (if enabled)

External Trip C 119 PSL Output Signal

PSL (50BF protection)

External 3 phase C Trip Allows external protection to initiate breaker fail (if enabled)

Fault_REC_TRIG 468 FRT PSL Trigger for the Fault Recorder Fibre Com Error 252 PSL Input

Signal Relay Integrity Fibre communication to the CU error

Fibre Com Worn 253 PSL Input Signal Relay Integrity Warning: fibre communication to be changed Field Volt Fail 470 PSL Input Signal Relay Integrity 48V Field Voltage Failure Forced Mode ON 343 PSL Input Signal Commissioning When the forced positions of the CB and the Isolators

are used (during commissioning test) General Alarm 351 PSL Input Signal Relay Integrity General Alarm I> Any Trip 288 PSL Input Signal Phase Overcurrent Overcurrent Trip I> No Trip 296 PSL Input Signal Phase Overcurrent Complement of ddb 288 I>1 Start A 176 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start A I>1 Start B 177 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start B I>1 Start C 178 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start C I>1 Trip 180 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Trip 3 phase I>2 Block BB ON 316 PSL Input Signal 87BB protection Fast external phase fault criterion to block the

connected zone enabled I>2 Start A 182 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start A I>2 Start B 183 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start B I>2 Start C 184 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start C I>2 Trip 186 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Trip 3 phase I>BB Block Ph A 228 PSL Input Signal Phase Overcurrent Local overcurrent phase A to block the 87BB on

external fault I>BB Block Ph B 229 PSL Input Signal Phase Overcurrent Local overcurrent phase B to block the 87BB on

external fault I>BB Block Ph C 230 PSL Input Signal Phase Overcurrent Local overcurrent phase C to block the 87BB on

external fault I>BB Enabled 314 PSL Input Signal Local protection Overcurrent Local trip confirmation I>BB Start A 224 PSL Input Signal Phase Overcurrent Local overcurrent phase A Trip confirmation for 87BB or

50BF (CU) trip order I>BB Start B 225 PSL Input Signal Phase Overcurrent Local overcurrent phase B Trip confirmation for 87BB or

50BF (CU) trip order I>BB Start C 226 PSL Input Signal Phase Overcurrent Local overcurrent phase C Trip confirmation for 87BB

or 50BF (CU) trip order IN>1 Start 179 PSL Input Signal Earth Fault 1st Stage Earth Fault Start

Page 246: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-28

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

IN>1 Trip 181 PSL Input Signal Earth Fault 1st Stage Earth Fault Trip IN>2 Block BB ON 317 PSL Input Signal 87BB protection Fast external neutral fault criterion to block the

connected zone enabled IN>2 Start 185 PSL Input Signal Earth Fault 2nd Stage Earth Fault Start IN>2 Trip 187 PSL Input Signal Earth Fault 2nd Stage Earth Fault Trip IN>BB Block 231 PSL Input Signal Earth Fault Local overcurrent earth to block the 87BB on external

fault IN>BB Start 227 PSL Input Signal Earth Fault Local overcurrent Trip confirmation for the neutral Int. Node 1022 1022 Can be created automatically by the PSL Int. Node 923 923 Can be created automatically by the PSL Int. Retrip 3 ph 171 PSL Input Signal 50BF Protection Retrip triphase due to a 87BB trip initiation (at tBF1) Internal Trip 256 PSL Input Signal Local Protection Triphase Trip (87BB, 50BF(CU), I>, IN> or manual zone

trip (CU)). Trip command directly applied to relay 1, 2, 3 (without PSL)

LED 1 96 LED Led Conditioner Red LED 1 LED 8 103 LED Led Conditioner Red LED 8 LED Cond IN 1 428 LED_CON PSL Assignment of signal to drive LED 1 Red. LED Cond IN 8 435 LED_CON PSL Assignment of signal to drive LED 8 Red. Man CB Cls Fail 353 PSL Input Signal Scheme Integrity Circuit Breaker Failed to Close

(after a manual/operator close command) Man CB Trip Fail 354 PSL Input Signal Scheme Integrity Circuit Breaker Failed to Trip

(after a manual/operator trip command) Man. Close CB 166 PSL Output

Signal PSL Circuit Breaker closing order (CB Control)

Man. Trip CB 167 PSL Output Signal

PSL (Commissioning)

Circuit Breaker tripping order (CB Control)

Man.CB Close Cmd

120 PSL Output Signal

PSL Manual/operator Circuit Breaker trip command

Man.Close Q1 Cmd

160 PSL Output Signal

PSL Manual/operator Isolator 1 (switch) closing command

Man.Close Q6 Cmd

165 PSL Output Signal

PSL Manual/operator Isolator 6 (switch) closing command

Man.Trip zone 260 PSL Input Signal Commissioning Manual Trip Order of a zone, general information common to all PUs, the PU can be connected to an healthy zone

Max Flux ph A 236 PSL Input Signal Saturation Maximum flux reached in the phase A CT Max Flux ph B 237 PSL Input Signal Saturation Maximum flux reached in the phase B CT Max Flux ph C 238 PSL Input Signal Saturation Maximum flux reached in the phase C CT Operating mode 1 264 PSL Input Signal Relay Integrity For Expert Only Operating mode 2 265 PSL Input Signal Relay Integrity For Expert Only Operating mode 3 266 PSL Input Signal Relay Integrity For Expert Only Opto Label 01 64 OPTO Opto Input Opto Input 1 Opto Label 16 79 OPTO Opto Input Opto Input 16 Overhaul Mode 312 PSL Output

Signal Commissioning To switch the PU in overhaul mode

Predict err ph A 240 PSL Input Signal Saturation Variation error phase A (derived current) Predict err ph B 241 PSL Input Signal Saturation Variation error phase B (derived current) Predict err ph C 242 PSL Input Signal Saturation Variation error phase C (derived current) PU Overhaul mode

307 PSL Input Signal Commissioning PU in overhaul mode

PU->CU Signal 01 144 PSL Output Signal

PSL Virtual Signal 01 from the PU to the CU via the fibre optic

PU->CU Signal 16 159 PSL Output Signal

PSL Virtual Signal 16 from the PU to the CU via the fibre optic

Q1 Aux. (89a) 105 PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 1

Q1 Aux. (89b) 104 PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 1

Q1 Closed 320 PSL Input Signal PSL Isolator 1 closed (not (Q1 Aux. (89b) AND Q1 Aux. (89a)))

Q1 Status Alarm 321 PSL Output Signal

Scheme Integrity Isolator 1 discrepancy (Q1 Aux. (89b) = Q1 Aux. (89a) for too long

Q1 Status Forced 336 PSL Input Signal Commissioning Isolator 1 status position forced open (by default) or closed

Page 247: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-29

PL

English Text DDB No.

Source Description

Q6 Aux. (89a) 115 PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 6

Q6 Aux. (89b) 114 PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 6

Q6 Closed 330 PSL Input Signal PSL Isolator 6 closed (not (Q6 Aux. (89b) AND Q6 Aux. (89a)))

Q6 Status Alarm 331 PSL Output Signal

Scheme Integrity Isolator 6 discrepancy (Q6 Aux. (89b) = Q6 Aux. (89a) for too long

Q6 Status Forced 341 PSL Input Signal Commissioning Isolator 6 status position forced open (by default) or closed

Relay condit 01 700 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 1 Relay condit 16 715 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 16 Relay Label 01 0 RELAY Output Conditioner Output Relay 01 - All trips (FSL) but not retrip Relay Label 02 1 RELAY Output Conditioner Output Relay 02 - All trips (FSL) but not retrip Relay Label 03 2 RELAY Output Conditioner Output Relay 03 - All trips (FSL) but not retrip Relay Label 04 3 RELAY Output Conditioner Output Relay 04 Relay Label 08 7 RELAY Output Conditioner Output Relay 08 Reset All values 134 PSL Output

Signal PSL (Commissioning)

Not used

Reset Indication 135 PSL Output Signal

PSL (Commissioning)

Reset all indications (Led and relays latched in PSL) that includes the Led Alarm

Reset Trip latch 131 PSL Output Signal

PSL (Commissioning)

Reset Latched Relays

Reset Trip Relay 318 PSL Input Signal Commissioning To reset the Trip relays Sat ADC Neutral 247 PSL Input Signal Saturation Analog to Digital Converter of the neutral current

saturated Sat ADC ph A 244 PSL Input Signal Saturation Analog to Digital Converter of phase A current

saturated Sat ADC ph B 245 PSL Input Signal Saturation Analog to Digital Converter of phase B current

saturated Sat ADC ph C 246 PSL Input Signal Saturation Analog to Digital Converter of phase C current

saturated Saturation ph A 232 PSL Input Signal Saturation Saturation on phase A Saturation ph B 233 PSL Input Signal Saturation Saturation on phase B Saturation ph C 234 PSL Input Signal Saturation Saturation on phase C Sett Grp Bit LSB 132 PSL Output

Signal PSL Setting Group Selector X1 (low bit)

SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

Sett Grp Bit MSB 133 PSL Output Signal

PSL Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

Timer in 436 436 TIMERIN PSL Timer Input Input to Auxiliary Timer 1 Timer in 451 451 TIMERIN PSL Timer Input Input to Auxiliary Timer 16 Timer out 452 452 TIMEROUT Timer Output Output from Auxiliary Timer 1 Timer out 467 467 TIMEROUT Timer Output Output from Auxiliary Timer 16 Topo/Set Changed

319 PSL Input Signal

Commissioning Change on topology or configuration

Topo/Set valid 269 PSL Input Signal Scheme Integrity Wrong Topology address Topology valid 268 PSL Input Signal Scheme Integrity Valid Topology file Trip 50BF (CU) 259 PSL Input Signal 50BF Backtrip

Protection Breaker fail trip order (50BF), general information common to all PUs, the PU can be connected to an healthy zone

Trip 87BB 257 PSL Input Signal 87BB Busbar Protection

Busbar trip order (87BB), general information common to all PU, the PUs can be connected to an healthy zone

Trip 87BB Locked 258 PSL Input Signal Scheme Integrity Busbar trip order blocked by the CU commissioning mode or Circuitry fault

Trip Rel Latched 315 PSL Input Signal Local protection Trip Relays Latched Trip Zone 1 223 PSL Input Signal CU Information Trip of Zone 1 (87BB, 50BF or manual) Trip Zone 8 216 PSL Input Signal CU Information Trip of Zone 8 (87BB, 50BF or manual) User Alarm 1 136 PSL Output

Signal PSL Triggers User Alarm 1 message to be alarmed on LCD

display (self-resetting)

User Alarm 7 142 PSL Output Signal

PSL Triggers User Alarm 7 message to be alarmed on LCD display (self-resetting)

Page 248: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-30

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

Zone 1 Off 215 PSL Input Signal CU Information Zone 1 in commissioning mode or blocked by a Circuitry fault or a PU error

Zone 8 Off 208 PSL Input Signal CU Information Zone 8 in commissioning mode or blocked by a Circuitry fault or a PU error

1.9 Description of P743 logic nodes

1.9.1 Sorted by DDB number:

DDB No.

English Text Source Description

0 Relay Label 01 RELAY Output Conditioner Output Relay 01 - All trips (FSL) but not retrip 1 Relay Label 02 RELAY Output Conditioner Output Relay 02 - All trips (FSL) but not retrip 2 Relay Label 03 RELAY Output Conditioner Output Relay 03 - All trips (FSL) but not retrip 3 Relay Label 04 RELAY Output Conditioner Output Relay 04

15 Relay Label 16 RELAY Output Conditioner Output Relay 16 64 Opto Label 01 OPTO Opto Input Opto Input 1 87 Opto Label 24 OPTO Opto Input Opto Input 24

104 Q1 Aux. (89b) PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 1

105 Q1 Aux. (89a) PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 1

114 Q6 Aux. (89b) PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 6

115 Q6 Aux. (89a) PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 6

116 Ext. 3 ph Trip PSL Output Signal

PSL (50BF protection)

External 3 phase Trip Allows external protection to initiate breaker fail (if enabled)

117 External Trip A PSL Output Signal

PSL (50BF protection)

External 3 phase A Trip Allows external protection to initiate breaker fail (if enabled)

118 External Trip B PSL Output Signal

PSL (50BF protection)

External 3 phase B Trip Allows external protection to initiate breaker fail (if enabled)

119 External Trip C PSL Output Signal

PSL (50BF protection)

External 3 phase C Trip Allows external protection to initiate breaker fail (if enabled)

120 Man.CB Close Cmd

PSL Output Signal

PSL Manual/operator Circuit Breaker trip command opto input

121 CB not available PSL Output Signal

PSL Circuit Breaker is not available to trip

122 Ext. CB Fail PSL Output Signal

PSL (50BF Backtrip protection)

50BF Backtrip order from an other protection

123 CB Aux. 3ph(52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (3 phase)

124 CB Aux. 3ph(52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (3 phase)

125 CB Aux. A (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase A)

126 CB Aux. A (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase A)

127 CB Aux. B (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase B)

128 CB Aux. B (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase B)

129 CB Aux. C (52a) PSL Output Signal

PSL 52-A (CB closed) CB Auxiliary Input (phase C)

130 CB Aux. C (52b) PSL Output Signal

PSL 52-B (CB open) CB Auxiliary Input (Phase C)

131 Reset Trip latch PSL Output Signal

PSL (Commissioning)

Reset Latched Relays

132 Sett Grp Bit LSB PSL Output Signal

PSL Setting Group Selector X1 (low bit) SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

Page 249: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-31

PL

DDB No.

English Text Source Description

133 Sett Grp Bit MSB PSL Output Signal

PSL Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

134 Reset All values PSL Output Signal

PSL (Commissioning)

Not used

135 Reset Indication PSL Output Signal

PSL (Commissioning)

Reset all indications (Led and relays latched in PSL) that includes the Led Alarm

136 User Alarm 1 PSL Output Signal

PSL Triggers User Alarm 1 message to be alarmed on LCD display (self-resetting)

142 User Alarm 7 PSL Output Signal

PSL Triggers User Alarm 7 message to be alarmed on LCD display (self-resetting)

143 Aux Volt Superv PSL Output Signal

PSL (Scheme Integrity)

Triggers User Alarm 8 message to be alarmed on LCD display (self-resetting)

144 PU->CU Signal 01 PSL Output Signal

PSL Virtual Signal 01 from the PU to the CU via the fibre optic

159 PU->CU Signal 16 PSL Output Signal

PSL Virtual Signal 16 from the PU to the CU via the fibre optic

160 Man.Close Q1 Cmd

PSL Output Signal

PSL Manual/operator Isolator 1 (switch) closing command

165 Man.Close Q6 Cmd

PSL Output Signal

PSL Manual/operator Isolator 6 (switch) closing command

166 Man. Close CB PSL Output Signal

PSL Circuit Breaker closing order (CB Control)

167 Man. Trip CB PSL Output Signal

PSL Circuit Breaker tripping order (CB Control)

168 Ext. Retrip Ph A PSL Input Signal 50BF Protection Retrip of phase A due to an external trip initiation of this phase (at tBF3)

169 Ext. Retrip Ph B PSL Input Signal 50BF Protection Retrip of phase B due to an external trip initiation of this phase (at tBF3)

170 Ext. Retrip Ph C PSL Input Signal 50BF Protection Retrip of phase C due to an external trip initiation of this phase (at tBF3)

171 Int. Retrip 3 ph PSL Input Signal 50BF Protection Retrip triphase due to a 87BB trip initiation (at tBF1) 172 CBF Int Backtrip PSL Input Signal 50BF Backtrip

Protection Backtrip triphase due to a 87BB trip initiation (at tBF2)

173 CBF Ext Backtrip PSL Input Signal 50BF Backtrip Protection

Backtrip triphase due to an external trip initiation (at tBF4)

174 CB Fail Alarm PSL Input Signal 50BF Protection Circuit Breaker Fail Alarm Logical OR of DDB 168 to 173

176 I>1 Start A PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start A 177 I>1 Start B PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start B 178 I>1 Start C PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start C 179 IN>1 Start PSL Input Signal Earth Fault 1st Stage Earth Fault Start 180 I>1 Trip PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Trip 3 phase 181 IN>1 Trip PSL Input Signal Earth Fault 1st Stage Earth Fault Trip 182 I>2 Start A PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start A 183 I>2 Start B PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start B 184 I>2 Start C PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start C 185 IN>2 Start PSL Input Signal Earth Fault 2nd Stage Earth Fault Start 186 I>2 Trip PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Trip 3 phase 187 IN>2 Trip PSL Input Signal Earth Fault 2nd Stage Earth Fault Trip 192 CU->PU Signal 01 PSL Input Signal PSL Virtual Signal 01 from the CU to the PU via the fibre

optic 207 CU->PU Signal 16 PSL Input Signal PSL Virtual Signal 16 from the CU to the PU via the fibre

optic 208 Zone 8 Off PSL Input Signal CU Information Zone 8 in commissioning mode or blocked

by a Circuitry fault or a PU error 215 Zone 1 Off PSL Input Signal CU Information Zone 1 in commissioning mode or blocked

by a Circuitry fault or a PU error 216 Trip Zone 8 PSL Input Signal CU Information Trip of Zone 8 (87BB, 50BF or manual) 223 Trip Zone 1 PSL Input Signal CU Information Trip of Zone 1 (87BB, 50BF or manual) 224 I>BB Start A PSL Input Signal Phase Overcurrent Local overcurrent phase A Trip confirmation for 87BB

or 50BF (CU) trip order 225 I>BB Start B PSL Input Signal Phase Overcurrent Local overcurrent phase B Trip confirmation for 87BB

or 50BF (CU) trip order

Page 250: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-32

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

226 I>BB Start C PSL Input Signal Phase Overcurrent Local overcurrent phase C Trip confirmation for 87BB or 50BF (CU) trip order

227 IN>BB Start PSL Input Signal Earth Fault Local overcurrent Trip confirmation for the neutral 228 I>BB Block Ph A PSL Input Signal Phase Overcurrent Local overcurrent phase A to block the 87BB on

external fault 229 I>BB Block Ph B PSL Input Signal Phase Overcurrent Local overcurrent phase B to block the 87BB on

external fault 230 I>BB Block Ph C PSL Input Signal Phase Overcurrent Local overcurrent phase C to block the 87BB on

external fault 231 IN>BB Block PSL Input Signal Earth Fault Local overcurrent earth to block the 87BB on external

fault 232 Saturation ph A PSL Input Signal Saturation Saturation on phase A 233 Saturation ph B PSL Input Signal Saturation Saturation on phase B 234 Saturation ph C PSL Input Signal Saturation Saturation on phase C 235 Current Overflow PSL Input Signal Saturation Fibre optic Maximum primary current encoding

exceeded 236 Max Flux ph A PSL Input Signal Saturation Maximum flux reached in the phase A CT 237 Max Flux ph B PSL Input Signal Saturation Maximum flux reached in the phase B CT 238 Max Flux ph C PSL Input Signal Saturation Maximum flux reached in the phase C CT 239 Alarm

OffsetABCN PSL Input Signal Saturation Offset current read by the Analog board Phase A, B, C

or N 240 Predict err ph A PSL Input Signal Saturation Variation error phase A (derived current) 241 Predict err ph B PSL Input Signal Saturation Variation error phase B (derived current) 242 Predict err ph C PSL Input Signal Saturation Variation error phase C (derived current) 244 Sat ADC ph A PSL Input Signal Saturation Analog to Digital Converter of phase A current

saturated 245 Sat ADC ph B PSL Input Signal Saturation Analog to Digital Converter of phase B current

saturated 246 Sat ADC ph C PSL Input Signal Saturation Analog to Digital Converter of phase C current

saturated 247 Sat ADC Neutral PSL Input Signal Saturation Analog to Digital Converter of the neutral current

saturated 248 Delta IA PSL Input Signal Saturation Variation detected on phase A 249 Delta IB PSL Input Signal Saturation Variation detected on phase B 250 Delta IC PSL Input Signal Saturation Variation detected on phase C 251 Delta IN PSL Input Signal Saturation Variation detected on the neutral 252 Fibre Com Error PSL Input Signal Relay Integrity Fibre communication to the CU error 253 Fibre Com Worn PSL Input Signal Relay Integrity Warning: fibre communication to be changed 254 Acq Error 3Io PSL Input Signal Relay Integrity Sample acquisition error: 3 x Io <> In 255 CT Fail Alarm PSL Input Signal Scheme Integrity Internal PU CT failure 256 Internal Trip PSL Input Signal Local Protection Triphase Trip (87BB, 50BF(CU), I>, IN> or manual

zone trip (CU)). Trip command directly applied to relay 1, 2, 3 (without PSL)

257 Trip 87BB PSL Input Signal 87BB Busbar Protection

Busbar trip order (87BB), general information common to all PUs, the PU can be connected to an healthy zone

258 Trip 87BB Locked PSL Input Signal Scheme Integrity Busbar trip order blocked by the CU commissioning mode or Circuitry fault

259 Trip 50BF (CU) PSL Input Signal 50BF Backtrip Protection

Breaker fail trip order (50BF), general information common to all PUs, the PU can be connected to an healthy zone

260 Man.Trip zone PSL Input Signal Commissioning Manual Trip Order of a zone, general information common to all PUs, the PU can be connected to an healthy zone

261 Dead Zone Fault PSL Input Signal Local Protection Fault in the dead zone 262 Dead Zone Phase PSL Input Signal Local Protection Fault in the dead zone on a phase 263 Dead Zone Earth PSL Input Signal Local Protection Fault in the dead zone on the neutral 264 Operating mode 1 PSL Input Signal Relay Integrity For Expert Only 265 Operating mode 2 PSL Input Signal Relay Integrity For Expert Only 266 Operating mode 3 PSL Input Signal Relay Integrity For Expert Only 267 Config. Valid PSL Input Signal Scheme Integrity Valid Setting configuration 268 Topology valid PSL Input Signal Scheme Integrity Valid Topology file 269 Topo/Set valid PSL Input Signal Scheme Integrity Wrong Topology address 270 All Prot Blocked PSL Input Signal Commissioning All the protections (CU & PU) disabled

Page 251: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-33

PL

DDB No.

English Text Source Description

288 I> Any Trip PSL Input Signal Phase Overcurrent Overcurrent Trip 289 CBAvailabToTrip PSL Input Signal Scheme Integrity Circuit Breaker Healthy (Can Trip) 290 BF Trip Request PSL Input Signal 50BF Protection External or internal Breaker failure trip order request

(50BF) Logical OR of DDB 122, 172 and 173 296 I> No Trip PSL Input Signal Phase Overcurrent Complement of ddb 288 297 CBNotAvailToTrip PSL Input Signal Scheme Integrity Logical OR of ddb 121 and 270 298 BFTripNoRequest PSL Input Signal 50BF Protection Complement of ddb 290 305 Ctrl CB Trip PSL Input Signal Manual Functionality Manual Trip Order of the Circuit Breaker 306 Ctrl CB Close PSL Input Signal Manual Functionality Manual closing order of the Circuit Breaker 307 PU Overhaul

mode PSL Input Signal Commissioning PU in overhaul mode

308 Alm 50BF Disable PSL Input Signal Commissioning PU in 50BF blocked mode Alarm 311 50BF Disabled PSL Output

Signal Commissioning To switch the PU in 50BF blocked mode

312 Overhaul Mode PSL Output Signal

Commissioning To switch the PU in overhaul mode

314 I>BB Enabled PSL Input Signal Local protection Overcurrent Local trip confirmation 315 Trip Rel Latched PSL Input Signal Local protection Trip Relays Latched 316 I>2 Block BB ON PSL Input Signal Local protection Fast external phase fault criterion to block the

connected zone enabled 317 IN>2 Block BB ON PSL Input Signal Local protection Fast external neutral fault criterion to block the

connected zone enabled 318 Reset Trip Relay PSL Input Signal Commissioning To reset the Trip relays 319 Topo/Set

Changed PSL Input Signal Commissioning Change on topology or configuration

320 Q1 Closed PSL Input Signal PSL Isolator 1 closed (not (Q1 Aux. (89b) AND Q1 Aux. (89a)))

321 Q1 Status Alarm PSL Output Signal

Scheme Integrity Isolator 1 discrepancy (Q1 Aux. (89b) = Q1 Aux. (89a) for too long

330 Q6 Closed PSL Input Signal PSL Isolator 6 closed (not (Q6 Aux. (89b) AND Q6 Aux. (89a)))

331 Q6 Status Alarm PSL Output Signal

Scheme Integrity Isolator 6 discrepancy (Q6 Aux. (89b) = Q6 Aux. (89a) for too long

332 CB Closed PSL Input Signal PSL Circuit Breaker closed (not (CB Aux. (52b) AND CB Aux. (52a)))

333 CB Healthy PSL Input Signal PSL Complement of ddb 121 336 Q1 Status Forced PSL Input Signal Commissioning Isolator 1 status position forced open (by default) or

closed 341 Q6 Status Forced PSL Input Signal Commissioning Isolator 6 status position forced open (by default) or

closed 342 CB Status Forced PSL Input Signal Commissioning CB status position forced open (by default) or closed 343 Forced Mode ON PSL Input Signal Commissioning When the forced positions of the CB and the Isolators

are used (during commissioning test) 344 CB Aux. 52a PSL Input Signal CB Monitoring ddb 123 or Logical OR of ddb 125 and 127 and 129 345 CB Aux. 52b PSL Input Signal CB Monitoring ddb 124 or Logical AND of ddb 126 and 128 and 130 346 CB Trip 3 ph PSL Input Signal 50BF Protection Triphase Circuit Breaker Trip from CU (Init 50BF TBF1

/ TBF2), Logical OR of : 87BB, 50BF, Manual Trip Zone X

347 CB Trip phase A PSL Input Signal 50BF Protection Phase A Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip A, External Trip 3ph

348 CB Trip phase B PSL Input Signal 50BF Protection Phase B Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip B, External Trip 3ph

349 CB Trip phase C PSL Input Signal 50BF Protection Phase C Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip C, External Trip 3ph

351 General Alarm PSL Input Signal Relay Integrity General Alarm 352 CB Status Alarm PSL Input Signal Scheme Integrity Indication of discrepancy between the 52a and 52b

auxiliary contacts of the Circuit Breaker 353 Man CB Cls Fail PSL Input Signal Scheme Integrity Circuit Breaker Failed to Close

(after a manual/operator close command) 354 Man CB Trip Fail PSL Input Signal Scheme Integrity Circuit Breaker Failed to Trip

(after a manual/operator trip command) 355 Ctrl Cls in Prog PSL Input Signal Commissioning Control Close in Progress

The relay has been given an instruction to close the circuit breaker, but the Manual Close timer Delay has not yet finished timing out

Page 252: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-34

MiCOM P741, P742, P743

PL

DDB No.

English Text Source Description

356 Control Close PSL Input Signal Commissioning Control Close command to the circuit breaker. Operates for a manual close command (menu, SCADA)

357 Control Trip PSL Input Signal Commissioning Control Trip Operator trip instruction to the circuit breaker, via menu, or SCADA. (Does not operate for protection element trips)

358 Any Trip PSL Input Signal All Protections Any Trip (Logical OR of ddbs: 0, 1, 2, 168, 169, 170, 171, 256, 261)

436 Timer in 436 TIMERIN PSL Timer Input Input to Auxiliary Timer 1 451 Timer in 451 TIMERIN PSL Timer Input Input to Auxiliary Timer 16 452 Timer out 452 TIMEROUT Timer Output Output from Auxiliary Timer 1 467 Timer out 467 TIMEROUT Timer Output Output from Auxiliary Timer 16 468 Fault_REC_TRIG FRT PSL Trigger for the Fault Recorder 469 Battery Fail PSL Input Signal Relay Integrity Front panel Battery Failure 470 Field Volt Fail PSL Input Signal Relay Integrity 48V Field Voltage Failure 608 Control Input 1 CONTROL Control Input

Command Control Input 1 - for SCADA and menu commands into PSL

639 Control Input 32 CONTROL Control Input Command

Control Input 32 - for SCADA and menu commands into PSL

640 LED 1 Red TRI_LED PSL (LED) Programmable LED 1 Red is energized 641 LED 1 Grn TRI_LED PSL (LED) Programmable LED 1 Green is energized 654 LED 8 Red TRI_LED PSL (LED) Programmable LED 8 Red is energized 655 LED 8 Grn TRI_LED PSL (LED) Programmable LED 8 Green is energized 656 FnKey LED 1 Red TRI_LED PSL (LED) Programmable Function Key LED 1 Red is energized 657 FnKey LED 1 Grn TRI_LED PSL (LED) Programmable Function Key LED 1 Green is

energized 674 FnKey LED 10

Red TRI_LED PSL (LED) Programmable Function Key LED 10 Red is energized

675 FnKey LED 10 Grn

TRI_LED PSL (LED) Programmable Function Key LED 10 Green is energized

676 Function Key 1 FUNCTION_KEY PSL (Function Key) Function Key 1 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

685 Function Key 10 FUNCTION_KEY PSL (Function Key) Function Key 10 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

700 Relay condit 01 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 715 Relay condit 16 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner 764 LED 1 Red Condit TRI_LED_CON Output Conditioner Assignment of input signal to drive output LED 1Red 765 LED 1 Grn Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 1Green.

To drive LED1 Yellow DDB 764 and DDB 765 must be driven at the same time

778 LED 8 Red Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8Red 779 LED 8 Grn Condit TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8 Green.

To drive LED8 Yellow DDB 778 and DDB 779 must be active at the same time

780 FnKey LED 1 Red TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 1 Red. This LED is associated with Function Key 1

781 FnKey LED 1 Grn TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 1 Green. This LED is associated with Function Key 1. To drive function key LED, yellow DDB 692 and DDB 693 must be active at the same time

798 FnKey LED 10 Red

TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Red. This LED is associated with Function Key 10

799 FnKey LED 10 Grn

TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Green. This LED is associated with Function Key 10. To drive function key LED1 yellow, DDB 710 and DDB 711 must be active at the same time

923 Int. Node 923 Can be created automatically by the PSL 1022 Int. Node 1022 Can be created automatically by the PSL

Page 253: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-35

PL

1.9.2 Sorted by DDB name:

English Text DDB No.

Source Description

50BF Disabled 311 PSL Output Signal

Commissioning To switch the PU in 50BF blocked mode

Acq Error 3Io 254 PSL Input Signal Relay Integrity Sample acquisition error: 3 x Io <> In Alarm OffsetABCN

239 PSL Input Signal Saturation Offset current read by the Analog board Phase A, B, C or N

All Prot Blocked 270 PSL Input Signal Commissioning All the protections (CU & PU) disabled Alm 50BF Disable 308 PSL Input Signal Commissioning PU in 50BF blocked mode Alarm Any Trip 358 PSL Input Signal All Protections Any Trip (Logical OR of ddbs:

0, 1, 2, 168, 169, 170, 171, 256, 261) Aux Volt Superv 143 PSL Output

Signal PSL (Scheme Integrity)

Triggers User Alarm 8 message to be alarmed on LCD display (self-resetting)

Battery Fail 469 PSL Input Signal Relay Integrity Front panel Battery Failure BF Trip Request 290 PSL Input Signal 50BF Protection External or internal Breaker failure trip order request

(50BF) Logical OR of DDB 122, 172 and 173 BFTripNoRequest 298 PSL Input Signal 50BF Protection Complement of ddb 290 CB Aux. 3ph(52a) 123 PSL Output

Signal PSL 52-A (CB closed)

CB Auxiliary Input (3 phase) CB Aux. 3ph(52b) 124 PSL Output

Signal PSL 52-B (CB open)

CB Auxiliary Input (3 phase) CB Aux. 52a 344 PSL Input Signal CB Monitoring ddb 123 or Logical OR of ddb 125 and 127 and 129 CB Aux. 52b 345 PSL Input Signal CB Monitoring ddb 124 or Logical AND of ddb 126 and 128 and 130 CB Aux. A (52a) 125 PSL Output

Signal PSL 52-A (CB closed)

CB Auxiliary Input (phase A) CB Aux. A (52b) 126 PSL Output

Signal PSL 52-B (CB open)

CB Auxiliary Input (Phase A) CB Aux. B (52a) 127 PSL Output

Signal PSL 52-A (CB closed)

CB Auxiliary Input (phase B) CB Aux. B (52b) 128 PSL Output

Signal PSL 52-B (CB open)

CB Auxiliary Input (Phase B) CB Aux. C (52a) 129 PSL Output

Signal PSL 52-A (CB closed)

CB Auxiliary Input (phase C) CB Aux. C (52b) 130 PSL Output

Signal PSL 52-B (CB open)

CB Auxiliary Input (Phase C) CB Closed 332 PSL Input Signal PSL Circuit Breaker closed (not (CB Aux. (52b) AND CB

Aux. (52a))) CB Fail Alarm 174 PSL Input Signal 50BF Protection Circuit Breaker Fail Alarm

Logical OR of DDB 168 to 173 CB Healthy 333 PSL Input Signal PSL Complement of ddb 121 CB not available 121 PSL Output

Signal PSL Circuit Breaker is not available to trip

CB Status Alarm 352 PSL Input Signal Scheme Integrity Indication of discrepancy between the 52a and 52b auxiliary contacts of the Circuit Breaker

CB Status Forced 342 PSL Input Signal Commissioning CB status position forced open (by default) or closed CB Trip 3 ph 346 PSL Input Signal 50BF Protection Triphase Circuit Breaker Trip from CU (Init 50BF TBF1

/ TBF2), Logical OR of : 87BB, 50BF, Manual Trip Zone X

CB Trip phase A 347 PSL Input Signal 50BF Protection Phase A Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip A, External Trip 3ph

CB Trip phase B 348 PSL Input Signal 50BF Protection Phase B Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip B, External Trip 3ph

CB Trip phase C 349 PSL Input Signal 50BF Protection Phase C Circuit Breaker Trip (Init 50BF TBF3 / TBF4), Logical OR of : O/C Protection, External Trip C, External Trip 3ph

CBAvailabToTrip 289 PSL Input Signal Scheme Integrity Circuit Breaker Healthy (Can Trip) CBF Ext Backtrip 173 PSL Input Signal 50BF Backtrip

Protection Backtrip triphase due to an external trip initiation (at tBF4)

CBF Int Backtrip 172 PSL Input Signal 50BF Backtrip Protection

Backtrip triphase due to a 87BB trip initiation (at tBF2)

CBNotAvailToTrip 297 PSL Input Signal Scheme Integrity Logical OR of ddb 121 and 270 Config. Valid 267 PSL Input Signal Scheme Integrity Valid Setting configuration

Page 254: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-36

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

Control Close 356 PSL Input Signal Commissioning Control Close command to the circuit breaker. Operates for a manual close command (menu, SCADA)

Control Input 1 608 CONTROL Control Input Command

Control Input 1 - for SCADA and menu commands into PSL

Control Input 32 639 CONTROL Control Input Command

Control Input 32 - for SCADA and menu commands into PSL

Control Trip 357 PSL Input Signal Commissioning Control Trip Operator trip instruction to the circuit breaker, via menu, or SCADA. (Does not operate for protection element trips)

CT Fail Alarm 255 PSL Input Signal Scheme Integrity Internal PU CT failure Ctrl CB Close 306 PSL Input Signal Manual Functionality Manual closing order of the Circuit Breaker Ctrl CB Trip 305 PSL Input Signal Manual Functionality Manual Trip Order of the Circuit Breaker Ctrl Cls in Prog 355 PSL Input Signal Commissioning Control Close in Progress

The relay has been given an instruction to close the circuit breaker, but the Manual Close timer Delay has not yet finished timing out

CU->PU Signal 01 192 PSL Input Signal PSL Virtual Signal 01 from the CU to the PU via the fibre optic

CU->PU Signal 16 207 PSL Input Signal PSL Virtual Signal 16 from the CU to the PU via the fibre optic

Current Overflow 235 PSL Input Signal Saturation Fibre optic Maximum primary current encoding exceeded

Dead Zone Earth 263 PSL Input Signal Local Protection Fault in the dead zone on the neutral Dead Zone Fault 261 PSL Input Signal Local Protection Fault in the dead zone Dead Zone Phase 262 PSL Input Signal Local Protection Fault in the dead zone on a phase Delta IA 248 PSL Input Signal Saturation Variation detected on phase A Delta IB 249 PSL Input Signal Saturation Variation detected on phase B Delta IC 250 PSL Input Signal Saturation Variation detected on phase C Delta IN 251 PSL Input Signal Saturation Variation detected on the neutral Ext. 3 ph Trip 116 PSL Output

Signal PSL (50BF protection)

External 3 phase Trip Allows external protection to initiate breaker fail (if enabled)

Ext. CB Fail 122 PSL Output Signal

PSL (50BF Backtrip protection)

50BF Backtrip order from an other protection

Ext. Retrip Ph A 168 PSL Input Signal 50BF Protection Retrip of phase A due to an external trip initiation of this phase (at tBF3)

Ext. Retrip Ph B 169 PSL Input Signal 50BF Protection Retrip of phase B due to an external trip initiation of this phase (at tBF3)

Ext. Retrip Ph C 170 PSL Input Signal 50BF Protection Retrip of phase C due to an external trip initiation of this phase (at tBF3)

External Trip A 117 PSL Output Signal

PSL (50BF protection)

External 3 phase A Trip Allows external protection to initiate breaker fail (if enabled)

External Trip B 118 PSL Output Signal

PSL (50BF protection)

External 3 phase B Trip Allows external protection to initiate breaker fail (if enabled)

External Trip C 119 PSL Output Signal

PSL (50BF protection)

External 3 phase C Trip Allows external protection to initiate breaker fail (if enabled)

Fault_REC_TRIG 468 FRT PSL Trigger for the Fault Recorder Fibre Com Error 252 PSL Input Signal Relay Integrity Fibre communication to the CU error Fibre Com Worn 253 PSL Input Signal Relay Integrity Warning: fibre communication to be changed Field Volt Fail 470 PSL Input Signal Relay Integrity 48V Field Voltage Failure FnKey LED 1 Grn 657 TRI_LED PSL (LED) Programmable Function Key LED 1 Green is

energized FnKey LED 1 Grn 781 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED

1 Green. This LED is associated with Function Key 1. To drive function key LED, yellow DDB 692 and DDB 693 must be active at the same time

FnKey LED 1 Red 656 TRI_LED PSL (LED) Programmable Function Key LED 1 Red is energized FnKey LED 1 Red 780 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED

1 Red. This LED is associated with Function Key 1

FnKey LED 10 Grn

675 TRI_LED PSL (LED) Programmable Function Key LED 10 Green is energized

Page 255: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-37

PL

English Text DDB No.

Source Description

FnKey LED 10 Grn

799 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Green. This LED is associated with Function Key 10. To drive function key LED1 yellow, DDB 710 and DDB 711 must be active at the same time

FnKey LED 10 Red

674 TRI_LED PSL (LED) Programmable Function Key LED 10 Red is energized

FnKey LED 10 Red

798 TRI_LED_CON Output Conditioner Assignment of signal to drive output Function Key LED 10 Red. This LED is associated with Function Key 10

Forced Mode ON 343 PSL Input Signal Commissioning When the forced positions of the CB and the Isolators are used (during commissioning test)

Function Key 1 676 FUNCTION_KEY PSL (Function Key) Function Key 1 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

Function Key 10 685 FUNCTION_KEY PSL (Function Key) Function Key 10 is activated. In ‘Normal’ mode it is high on key press and in ‘Toggle’ mode remains high/low on single key press

General Alarm 351 PSL Input Signal Relay Integrity General Alarm I> Any Trip 288 PSL Input Signal Phase Overcurrent Overcurrent Trip I> No Trip 296 PSL Input Signal Phase Overcurrent Complement of ddb 288 I>1 Start A 176 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start A I>1 Start B 177 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start B I>1 Start C 178 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Start C I>1 Trip 180 PSL Input Signal Phase Overcurrent 1st Stage Overcurrent Trip 3 phase I>2 Block BB ON 316 PSL Input Signal Local protection Fast external phase fault criterion to block the

connected zone enabled I>2 Start A 182 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start A I>2 Start B 183 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start B I>2 Start C 184 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Start C I>2 Trip 186 PSL Input Signal Phase Overcurrent 2nd Stage Overcurrent Trip 3 phase I>BB Block Ph A 228 PSL Input Signal Phase Overcurrent Local overcurrent phase A to block the 87BB on

external fault I>BB Block Ph B 229 PSL Input Signal Phase Overcurrent Local overcurrent phase B to block the 87BB on

external fault I>BB Block Ph C 230 PSL Input Signal Phase Overcurrent Local overcurrent phase C to block the 87BB on

external fault I>BB Enabled 314 PSL Input Signal Local protection Overcurrent Local trip confirmation I>BB Start A 224 PSL Input Signal Phase Overcurrent Local overcurrent phase A Trip confirmation for 87BB

or 50BF (CU) trip order I>BB Start B 225 PSL Input Signal Phase Overcurrent Local overcurrent phase B Trip confirmation for 87BB

or 50BF (CU) trip order I>BB Start C 226 PSL Input Signal Phase Overcurrent Local overcurrent phase C Trip confirmation for 87BB

or 50BF (CU) trip order IN>1 Start 179 PSL Input Signal Earth Fault 1st Stage Earth Fault Start IN>1 Trip 181 PSL Input Signal Earth Fault 1st Stage Earth Fault Trip IN>2 Block BB ON 317 PSL Input Signal Local protection Fast external neutral fault criterion to block the

connected zone enabled IN>2 Start 185 PSL Input Signal Earth Fault 2nd Stage Earth Fault Start IN>2 Trip 187 PSL Input Signal Earth Fault 2nd Stage Earth Fault Trip IN>BB Block 231 PSL Input Signal Earth Fault Local overcurrent earth to block the 87BB on external

fault IN>BB Start 227 PSL Input Signal Earth Fault Local overcurrent Trip confirmation for the neutral Int. Node 1022 1022 Can be created automatically by the PSL Int. Node 923 923 Can be created automatically by the PSL Int. Retrip 3 ph 171 PSL Input Signal 50BF Protection Retrip triphase due to a 87BB trip initiation (at tBF1) Internal Trip 256 PSL Input Signal Local Protection Triphase Trip (87BB, 50BF(CU), I>, IN> or manual

zone trip (CU)). Trip command directly applied to relay 1, 2, 3 (without PSL)

LED 1 Grn 641 TRI_LED PSL (LED) Programmable LED 1 Green is energized LED 1 Grn Condit 765 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 1Green.

To drive LED1 Yellow DDB 764 and DDB 765 must be driven at the same time

LED 1 Red 640 TRI_LED PSL (LED) Programmable LED 1 Red is energized LED 1 Red Condit 764 TRI_LED_CON Output Conditioner Assignment of input signal to drive output LED 1Red

Page 256: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-38

MiCOM P741, P742, P743

PL

English Text DDB No.

Source Description

LED 8 Grn 655 TRI_LED PSL (LED) Programmable LED 8 Green is energized LED 8 Grn Condit 779 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8 Green.

To drive LED8 Yellow DDB 778 and DDB 779 must be active at the same time

LED 8 Red 654 TRI_LED PSL (LED) Programmable LED 8 Red is energized LED 8 Red Condit 778 TRI_LED_CON Output Conditioner Assignment of signal to drive output LED 8Red Man CB Cls Fail 353 PSL Input Signal Scheme Integrity Circuit Breaker Failed to Close

(after a manual/operator close command) Man CB Trip Fail 354 PSL Input Signal Scheme Integrity Circuit Breaker Failed to Trip

(after a manual/operator trip command) Man. Close CB 166 PSL Output

Signal PSL Circuit Breaker closing order (CB Control)

Man. Trip CB 167 PSL Output Signal

PSL (Commissioning)

Circuit Breaker tripping order (CB Control)

Man.CB Close Cmd

120 PSL Output Signal

PSL Manual/operator Circuit Breaker trip command opto input

Man.Close Q1 Cmd

160 PSL Output Signal

PSL Manual/operator Isolator 1 (switch) closing command

Man.Close Q6 Cmd

165 PSL Output Signal

PSL Manual/operator Isolator 6 (switch) closing command

Man.Trip zone 260 PSL Input Signal Commissioning Manual Trip Order of a zone, general information common to all PUs, the PU can be connected to an healthy zone

Max Flux ph A 236 PSL Input Signal Saturation Maximum flux reached in the phase A CT Max Flux ph B 237 PSL Input Signal Saturation Maximum flux reached in the phase B CT Max Flux ph C 238 PSL Input Signal Saturation Maximum flux reached in the phase C CT Operating mode 1 264 PSL Input Signal Relay Integrity For Expert Only Operating mode 2 265 PSL Input Signal Relay Integrity For Expert Only Operating mode 3 266 PSL Input Signal Relay Integrity For Expert Only Opto Label 01 64 OPTO Opto Input Opto Input 1 Opto Label 24 87 OPTO Opto Input Opto Input 24 Overhaul Mode 312 PSL Output

Signal Commissioning To switch the PU in overhaul mode

Predict err ph A 240 PSL Input Signal Saturation Variation error phase A (derived current) Predict err ph B 241 PSL Input Signal Saturation Variation error phase B (derived current) Predict err ph C 242 PSL Input Signal Saturation Variation error phase C (derived current) PU Overhaul mode

307 PSL Input Signal Commissioning PU in overhaul mode

PU->CU Signal 01 144 PSL Output Signal

PSL Virtual Signal 01 from the PU to the CU via the fibre optic

PU->CU Signal 16 159 PSL Output Signal

PSL Virtual Signal 16 from the PU to the CU via the fibre optic

Q1 Aux. (89a) 105 PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 1

Q1 Aux. (89b) 104 PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 1

Q1 Closed 320 PSL Input Signal PSL Isolator 1 closed (not (Q1 Aux. (89b) AND Q1 Aux. (89a)))

Q1 Status Alarm 321 PSL Output Signal

Scheme Integrity Isolator 1 discrepancy (Q1 Aux. (89b) = Q1 Aux. (89a) for too long

Q1 Status Forced 336 PSL Input Signal Commissioning Isolator 1 status position forced open (by default) or closed

Q6 Aux. (89a) 115 PSL Output Signal

PSL 89-A (Isolator closed) Auxiliary Input (3 phase) of the isolator 6

Q6 Aux. (89b) 114 PSL Output Signal

PSL 89-B (Isolator open) Auxiliary Input (3 phase) of the isolator 6

Q6 Closed 330 PSL Input Signal PSL Isolator 6 closed (not (Q6 Aux. (89b) AND Q6 Aux. (89a)))

Q6 Status Alarm 331 PSL Output Signal

Scheme Integrity Isolator 6 discrepancy (Q6 Aux. (89b) = Q6 Aux. (89a) for too long

Q6 Status Forced 341 PSL Input Signal Commissioning Isolator 6 status position forced open (by default) or closed

Relay condit 01 700 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner Relay condit 16 715 OUTPUT_CON Output Conditioner Input to Relay Output Conditioner Relay Label 01 0 RELAY Output Conditioner Output Relay 01 - All trips (FSL) but not retrip Relay Label 02 1 RELAY Output Conditioner Output Relay 02 - All trips (FSL) but not retrip

Page 257: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-39

PL

English Text DDB No.

Source Description

Relay Label 03 2 RELAY Output Conditioner Output Relay 03 - All trips (FSL) but not retrip Relay Label 04 3 RELAY Output Conditioner Output Relay 04 Relay Label 16 15 RELAY Output Conditioner Output Relay 16 Reset All values 134 PSL Output

Signal PSL (Commissioning)

Not used

Reset Indication 135 PSL Output Signal

PSL (Commissioning)

Reset all indications (Led and relays latched in PSL) that includes the Led Alarm

Reset Trip latch 131 PSL Output Signal

PSL (Commissioning)

Reset Latched Relays

Reset Trip Relay 318 PSL Input Signal Commissioning To reset the Trip relays Sat ADC Neutral 247 PSL Input Signal Saturation Analog to Digital Converter of the neutral current

saturated Sat ADC ph A 244 PSL Input Signal Saturation Analog to Digital Converter of phase A current

saturated Sat ADC ph B 245 PSL Input Signal Saturation Analog to Digital Converter of phase B current

saturated Sat ADC ph C 246 PSL Input Signal Saturation Analog to Digital Converter of phase C current

saturated Saturation ph A 232 PSL Input Signal Saturation Saturation on phase A Saturation ph B 233 PSL Input Signal Saturation Saturation on phase B Saturation ph C 234 PSL Input Signal Saturation Saturation on phase C Sett Grp Bit LSB 132 PSL Output

Signal PSL Setting Group Selector X1 (low bit)

SG1 is active DDB 104=0 & DDB 105=0 SG2 is active DDB 104=1 & DDB 105=0

Sett Grp Bit MSB 133 PSL Output Signal

PSL Setting Group Selector 1X (high bit) SG3 is active DDB 104=0 & DDB 105=1 SG4 is active DDB 104=1 & DDB 105=1

Timer in 436 436 TIMERIN PSL Timer Input Input to Auxiliary Timer 1 Timer in 451 451 TIMERIN PSL Timer Input Input to Auxiliary Timer 16 Timer out 452 452 TIMEROUT Timer Output Output from Auxiliary Timer 1 Timer out 467 467 TIMEROUT Timer Output Output from Auxiliary Timer 16 Topo/Set Changed

319 PSL Input Signal Commissioning Change on topology or configuration

Topo/Set valid 269 PSL Input Signal Scheme Integrity Wrong Topology address Topology valid 268 PSL Input Signal Scheme Integrity Valid Topology file Trip 50BF (CU) 259 PSL Input Signal 50BF Backtrip

Protection Breaker fail trip order (50BF), general information common to all PUs, the PU can be connected to an healthy zone

Trip 87BB 257 PSL Input Signal 87BB Busbar Protection

Busbar trip order (87BB), general information common to all PU, the PUs can be connected to an healthy zone

Trip 87BB Locked 258 PSL Input Signal Scheme Integrity Busbar trip order blocked by the CU commissioning mode or Circuitry fault

Trip Rel Latched 315 PSL Input Signal Local protection Trip Relays Latched Trip Zone 1 223 PSL Input Signal CU Information Trip of Zone 1 (87BB, 50BF or manual) Trip Zone 8 216 PSL Input Signal CU Information Trip of Zone 8 (87BB, 50BF or manual) User Alarm 1 136 PSL Output

Signal PSL Triggers User Alarm 1 message to be alarmed on LCD

display (self-resetting)

User Alarm 7 142 PSL Output Signal

PSL Triggers User Alarm 7 message to be alarmed on LCD display (self-resetting)

Zone 1 Off 215 PSL Input Signal CU Information Zone 1 in commissioning mode or blocked by a Circuitry fault or a PU error

Zone 8 Off 208 PSL Input Signal CU Information Zone 8 in commissioning mode or blocked by a Circuitry fault or a PU error

Page 258: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-40

MiCOM P741, P742, P743

PL

1.10 Factory default programmable scheme logic

The following section details the default settings of the PSL.

The P74x models are as follows:

Model Logic Inputs Relay Outputs

P741xxxAxxxxxxK 8 8

P742xxxAxxxxxxJ 16 8

P743xxxAxxxxxxK 24 16

1.11 Logic input mapping

The default mappings for each of the opto-isolated inputs are as shown in the following table:

Central Unit P741:

Opto-Input Number P74x Relay Text Function

1 Input Label 01 Disable 87BB on zone 1 & zone 2

2 Input Label 02 Disable 87BB & 50BF on zone 1 & zone 2

3 Input Label 03 Disable 87BB & 50BF on zone 1

4 Input Label 04 Disable 87BB & 50BF on zone 2

5 Input Label 05 Not Mapped

6 Input Label 06 Not Mapped

7 Input Label 07 Not Mapped

8 Input Label 08 Block all protections (CU & PU) Peripheral Unit P742:

Opto-Input Number P74x Relay Text Function

1 Input Label 01 Reset Indication

2 Input Label 02 Reset Trip Latch

3 Input Label 03 Isolator 1 closed auxiliary contact (89a)

4 Input Label 04 Isolator 1 open auxiliary contact (89b)

5 Input Label 05 Isolator 2 closed auxiliary contact (89a)

6 Input Label 06 Isolator 2 open auxiliary contact (89b)

7 Input Label 07 Circuit Breaker closed auxiliary contact (52a)

8 Input Label 08 Circuit Breaker open auxiliary contact (52b)

9 Input Label 09 Isolator 3 closed auxiliary contact (89a)

10 Input Label 10 Isolator 3 open auxiliary contact (89b)

11 Input Label 11 Mode 50BF disabled

12 Input Label 12 External 3 phase trip initiation

13 Input Label 13 CB not available

14 Input Label 14 External circuit breaker failure

15 Input Label 15 Manual CB close command

16 Input Label 16 Mode Overhaul

Page 259: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-41

PL

Peripheral Unit P743:

Opto-Input Number P74x Relay Text Function

1 Input Label 01 Reset Indication

2 Input Label 02 Reset Trip Latch

3 Input Label 03 Isolator 1 closed auxiliary contact (89a)

4 Input Label 04 Isolator 1 open auxiliary contact (89b)

5 Input Label 05 Isolator 2 closed auxiliary contact (89a)

6 Input Label 06 Isolator 2 open auxiliary contact (89b)

7 Input Label 07 Circuit Breaker closed auxiliary contact (52a)

8 Input Label 08 Circuit Breaker open auxiliary contact (52b)

9 Input Label 09 Isolator 3 closed auxiliary contact (89a)

10 Input Label 10 Isolator 3 open auxiliary contact (89b)

11 Input Label 11 Mode 50BF disabled

12 Input Label 12 External 3 phase trip initiation

13 Input Label 13 CB not available

14 Input Label 14 External circuit breaker failure

15 Input Label 15 Manual CB close command

16 Input Label 16 Mode Overhaul

17 Input Label 17 External single phase A trip initiation

18 Input Label 18 External single phase B trip initiation

19 Input Label 19 External single phase C trip initiation

20 Input Label 20 Not Mapped

21 Input Label 21 Not Mapped

22 Input Label 22 Not Mapped

23 Input Label 23 Not Mapped

24 Input Label 24 Not Mapped

Page 260: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-42

MiCOM P741, P742, P743

PL

1.12 Relay output contact mapping

The default mappings for each of the relay output contacts are as shown in the following table:

Central Unit P741:

Relay Contact Number

P74x Relay Text P74x Relay Conditioner Function

1 Relay Label 01 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

2 Relay Label 02 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

3 Relay Label 03 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

4 Relay Label 04 Pick-up 0/0 Trip zone 1

5 Relay Label 05 Pick-up 0/0 Trip zone 2

6 Relay Label 06 Pick-up 0/0 Circuit fault or PU error

7 Relay Label 07 Pick-up 0/0 Zone 1 or zone 2 blocked

8 Relay Label 08 Pick-up 0/0 Check Zone fault

Peripheral Unit P742:

Relay Contact Number

P74x Relay Text P74x Relay Conditioner Function

1 Relay Label 01 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

2 Relay Label 02 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

3 Relay Label 03 Pick-up 0/0 Trip 87BB or 50BF backtrip or overcurrent / earth fault trip (fixed)

4 Relay Label 04 Pick-up 0/0 Circuit Breaker failure

5 Relay Label 05 Pick-up 0/0 Circuit Breaker failure or out of service

6 Relay Label 06 Pick-up 0/0 Circuit Breaker failure retrip

7 Relay Label 07 Pick-up 0/0 Trip or Dead Zone Fault

8 Relay Label 08 Pick-up 0/0 Circuit Breaker or Isolator status alarm

Page 261: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-43

PL

Peripheral Unit P743:

Relay Contact Number

P74x Relay Text P74x Relay Conditioner Function

1 Relay Label 01 Pick-up 0/0 Trip 87BB or 50BF backtrip (fixed)

2 Relay Label 02 Pick-up 0/0 Trip 87BB or 50BF backtrip (fixed)

3 Relay Label 03 Pick-up 0/0 Trip 87BB or 50BF backtrip (fixed)

4 Relay Label 04 Pick-up 0/0 Circuit Breaker failure

5 Relay Label 05 Pick-up 0/0 Circuit Breaker failure or out of service

6 Relay Label 06 Pick-up 0/0 Circuit Breaker failure retrip

7 Relay Label 07 Pick-up 0/0 Trip or Dead Zone Fault

8 Relay Label 08 Pick-up 0/0 Circuit Breaker or Isolator status alarm

9 Relay Label 09 Pick-up 0/0 Circuit Breaker failure retrip phase A

10 Relay Label 10 Pick-up 0/0 Circuit Breaker failure retrip phase B

11 Relay Label 11 Pick-up 0/0 Circuit Breaker failure retrip phase C

12 Relay Label 12 Pick-up 0/0 Not Mapped

13 Relay Label 13 Pick-up 0/0 Not Mapped

14 Relay Label 14 Pick-up 0/0 Not Mapped

15 Relay Label 15 Pick-up 0/0 Not Mapped

16 Relay Label 16 Pick-up 0/0 Not Mapped

Note: It is essential that Relay 1, 2 and 3 are used for tripping purposes as this output is directly driven in the fixed logic to obtain the typical 13 ms tripping time.

A fault record can be generated by connecting one or a number of contacts to the “Fault Record Trigger” in PSL. It is recommended that the triggering contact be ‘self reset’ and not a latching. If a latching contact were chosen the fault record would not be generated until the contact had fully reset.

1.13 Function key input mapping

The default mappings for each of the function key inputs are as shown in the following table:

Central Unit P741:

LED Number Text Setting Function

1 FnKey 1 Normal To reset Zone or CZ circuitry fault

2 FnKey 2 Normal To reset Zone or CZ PU error fault

3 FnKey 3 Normal To Disable All protections (CU & PU)

4 FnKey 4 Toggled To block in Zone 1: 87BB & 50BF

5 FnKey 5 Toggled To block in Zone 2: 87BB & 50BF

6 FnKey 6 Normal To reset CU Indications

7 FnKey 7 Normal To reset CU & PU Indications

8 FnKey 8 Normal To reset PU Trip Latch

9 FnKey 9 Normal To trigger the Manual DR

10 FnKey 10 Not Used Not used

Page 262: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-44

MiCOM P741, P742, P743

PL

Peripheral Unit P743:

LED Number Text Setting Function

1 FnKey 1 Normal To reset the Latches

2 FnKey 2 Normal To reset the Trip Latch

3 FnKey 3 Not Used Not used

4 FnKey 4 Toggled To select the 50BF Disable mode

5 FnKey 5 Toggled To select the Overhaul mode

6 FnKey 6 Not Used Not used

7 FnKey 7 Not Used Not used

8 FnKey 8 Not Used Not used

9 FnKey 9 Not Used Not used

10 FnKey 10 Not Used Not used

1.14 Programmable LED output mapping

The default mappings for each of the programmable LEDs are as shown in the following table:

Central Unit P741:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1

LED1 Red

LED1 Yellow

LED1 Green

Yes

87BB fault on phase A

Not used

Not used

2

LED2 Red

LED2 Yellow

LED2 Green

Yes

87BB fault on phase B

Not used

Not used

3

LED3 Red

LED3 Yellow

LED3 Green

Yes

87BB fault on phase C

Not used

Not used

4

LED4 Red

LED4 Yellow

LED4 Green

Yes

50BF Trip Zone 1

87BB & 50BF Trip Zone 1

87BB Trip Zone 1

5

LED5 Red

LED5 Yellow

LED5 Green

Yes

50BF Trip Zone 2

87BB & 50BF Trip Zone 2

87BB Trip Zone 2

6

LED6 Red

LED6 Yellow

LED6 Green

No

Zone 1 blocked by itself

Zone 1 blocked by Check Zone

Zone 1 protected

7

LED7 Red

LED7 Yellow

LED7 Green

No

Zone 2 blocked by itself

Zone 2 blocked by Check Zone

Zone 2 protected

Page 263: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-45

PL

LED Number LED Input Connection/Text Latched P74x LED Function Indication

8

LED8 Red

LED8 Yellow

LED8 Green

No

Fiber communication Error

Fiber communication to change

Fiber communication healthy

9

FnKey LED1 Red

FnKey LED1 Yellow

FnKey LED1 Green

No

Zone or CZ circuitry fault block.

Zone or CZ circuitry fault alarm

No Zone or CZ circuitry fault

10

FnKey LED2 Red

FnKey LED2 Yellow

FnKey LED2 Green

No

Zone or CZ PU error fault block.

Zone or CZ PU error fault alarm

No Zone or CZ PU error fault

11

FnKey LED3 Red

FnKey LED3 Yellow

FnKey LED3 Green

No

All protections Disabled

Not used

All protections Not Disabled

12

FnKey LED4 Red

FnKey LED4 Yellow

FnKey LED4 Green

No

Zone 1: 87BB & 50BF blocked

Zone 1: 50BF blocked

Zone 1: protected

13

FnKey LED5 Red

FnKey LED5 Yellow

FnKey LED5 Green

No

Zone 2: 87BB & 50BF blocked

Zone 2: 50BF blocked

Zone 2: protected

14

FnKey LED6 Red

FnKey LED6 Yellow

FnKey LED6 Green

No

Not used

Not used

Reset CU Indications

15

FnKey LED7 Red

FnKey LED7 Yellow

FnKey LED7 Green

No

Not used

Not used

Reset CU & PU Indications

16

FnKey LED8 Red

FnKey LED8 Yellow

FnKey LED8 Green

No

Not used

Not used

Reset PU Trip Latch

17

FnKey LED9 Red

FnKey LED9 Yellow

FnKey LED9 Green

No

Not used

Not used

Manual DR trigger

18

FnKey LED10 Red

FnKey LED10 Yellow

FnKey LED10 Green

No

Not used

Dead Zone fault

Not used

Page 264: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-46

MiCOM P741, P742, P743

PL

Peripheral Unit P742:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1 LED 1 Red No Isolator 1 Closed

2 LED 2 Red No Isolator 2 Closed

3 LED 3 Red No Isolator 3 Closed

4 LED 4 Red Yes Trip on CU 50BF backtrip order

5 LED 5 Red Yes Trip on CU 87BB trip order

6 LED 6 Red Yes Dead Zone fault

7 LED 7 Red No Circuit Breaker out of service

8 LED 8 Red No Fiber communication Error

Peripheral Unit P743:

LED Number LED Input Connection/Text Latched P74x LED Function Indication

1

LED1 Red

LED1 Yellow

LED1 Green

No

Isolator 1 Closed

Isolator 1 Status Alarm

Isolator 1 Open

2

LED2 Red

LED2 Yellow

LED2 Green

No

Isolator 2 Closed

Isolator 2 Status Alarm

Isolator 2 Open

3

LED3 Red

LED3 Yellow

LED3 Green

No

Isolator 3 Closed

Isolator 3 Status Alarm

Isolator 3 Open

4

LED4 Red

LED4 Yellow

LED4 Green

Yes

Trip on CU 50BF backtrip order

Not used

Not used

5

LED5 Red

LED5 Yellow

LED5 Green

Yes

Trip on CU 87BB trip order

Not used

Not used

6

LED6 Red

LED6 Yellow

LED6 Green

Yes

Dead Zone fault

Not used

Not used

7

LED7 Red

LED7 Yellow

LED7 Green

No

Circuit Breaker out of service

Not used

Circuit Breaker healthy

8

LED8 Red

LED8 Yellow

LED8 Green

No

Fiber communication Error

Fiber communication to change

Fiber communication healthy

9

FnKey LED1 Red

FnKey LED1 Yellow

FnKey LED1 Green

No

Not used

Not used

Reset PU Indications

Page 265: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-47

PL

LED Number LED Input Connection/Text Latched P74x LED Function Indication

10

FnKey LED2 Red

FnKey LED2 Yellow

FnKey LED2 Green

No

Not used

Not used

Reset PU Trip Latch

11

FnKey LED3 Red

FnKey LED3 Yellow

FnKey LED3 Green

No Not used

12

FnKey LED4 Red

FnKey LED4 Yellow

FnKey LED4 Green

No

Not used

Mode 50BF disabled

Mode normal

13

FnKey LED5 Red

FnKey LED5 Yellow

FnKey LED5 Green

No

Mode overhaul

Not used

Mode normal

14

FnKey LED6 Red

FnKey LED6 Yellow

FnKey LED6 Green

No Not used

15

FnKey LED7 Red

FnKey LED7 Yellow

FnKey LED7 Green

No Not used

16

FnKey LED8 Red

FnKey LED8 Yellow

FnKey LED8 Green

No Not used

17

FnKey LED9 Red

FnKey LED9 Yellow

FnKey LED9 Green

No Not used

18

FnKey LED10 Red

FnKey LED10 Yellow

FnKey LED10 Green

No Not used

Page 266: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-48

MiCOM P741, P742, P743

PL

1.15 Fault recorder start mapping

The default mapping for the signal which initiates a fault record is as shown in the following table:

Central Unit (P741):

Initiating Signal Fault Trigger

Trip 87BB Initiate fault recording from main protection trip

Trip 50BF Initiate fault recording from main protection trip

Peripheral Unit (P742 and P743):

Initiating Signal Fault Trigger

Any Trip Initiate fault recording from main protection trip

Dead zone fault Initiate fault recording from main protection trip

1.16 PSL DATA column

The MiCOM P74x relay contains a PSL DATA column that can be used to track PSL modifications. A total of 12 cells are contained in the PSL DATA column, 3 for each setting group. The function for each cell is shown below:

Grp. PSL Ref.

When downloading a PSL to the relay, the user will be prompted to enter which group the PSL is for and a reference identifier. The first 32 characters of the reference ID will be displayed in this cell. The and keys can be used to scroll through 32 characters as only 16 can be displayed at any one time.

18 Nov 2002

08:59:32.047

This cell displays the date and time when the PSL was down loaded to the relay.

Grp. 1 PSL

ID - 2062813232

This is a unique number for the PSL that has been entered. Any change in the PSL will result in a different number being displayed.

Note: The above cells are repeated for each setting group.

Page 267: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-49

PL

MiCOM P741 PROGRAMMABLE SCHEME LOGIC

DDB #656Non - Latching

FnKey LED 1 Red

DDB #657FnKey LED 1 Grn

DDB #658Non - Latching

FnKey LED 2 Red

DDB #659FnKey LED 2 Grn

DDB #666Non - Latching

FnKey LED 6 Red

DDB #667FnKey LED 6 Grn

DDB #668Non - Latching

FnKey LED 7 Red

DDB #669FnKey LED 7 Grn

DDB #670Non - Latching

FnKey LED 8 Red

DDB #671FnKey LED 8 Grn

DDB #672Non - Latching

FnKey LED 9 Red

DDB #673FnKey LED 9 Grn

1

1

1

1

1

&

&

&

&

DDB #281PU Error Alm Zx

DDB #286PU Error Alm CZ

DDB #282PU Error Lock Zx

DDB #287PU Error Lock CZ

DDB #266Circt Flt Alm Zx

DDB #284Circt Flt Alm CZ

DDB #280Circt Flt Lck Zx

DDB #285Circt Flt Lck CZ

DDB #109Reset IndicationDDB #681

Function Key 6

DDB #682Function Key 7

DDB #682Function Key 7

DDB #112CU->PU Signal 01

DDB #683Function Key 8

DDB #113CU->PU Signal 02

DDB #682Function Key 7

DDB #684Function Key 9

DDB #676Function Key 1

DDB #676Function Key 1

DDB #677Function Key 2

DDB #677Function Key 2

DDB #684Function Key 9

DDB #107Ext Start DR

DDB #681Function Key 6

DDB #683Function Key 8

DDB #676Function Key 1

DDB #106To Reset CircFlt

DDB #677Function Key 2

DDB #110To Reset PU err

Circuitry fault

P741

PU error

Reset all indications

Reset Trip Relays on PU (if latched is enabled on PU)

Manual triggering of CU DR

Green = DR Manual Triggering

Green = Reset PU Trip Latch

Green = Reset CU&PU indications

Green = Reset CU indications

Reset for Zones / Check Zone

Zones or Check Zone:Red = BlockingYellow = Alarm onlyGreen = No Alarm

Reset for Zones / Check Zone

Zones or Check Zone:Red = BlockingYellow = Alarm onlyGreen = No Alarm

1/4

Page 268: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-50

MiCOM P741, P742, P743

PL

Dwell20

0

DDB #660Non - Latching

FnKey LED 3 Red

DDB #661FnKey LED 3 Grn

DDB #662Non - Latching

FnKey LED 4 Red

DDB #663FnKey LED 4 Grn

DDB #664Non - Latching

FnKey LED 5 Red

DDB #665FnKey LED 5 Grn

1

1

1

&

&

1

1

&

&

1

&

DDB #239INP Lck Lev .2 z1DDB #065

Opto Label 02

DDB #066Opto Label 03

DDB #238INP Lck Lev .2 z2DDB #065

Opto Label 02

DDB #067Opto Label 04

DDB #256Trip 87BB

DDB #259Trip 50BF

DDB #468Fault_REC_TRIG

DDB #068Opto Label 05

DDB #679Function Key 4

DDB #068Opto Label 05

DDB #680Function Key 5

DDB #231INP Lck Lev .1 z1

DDB #064Opto Label 01

DDB #230INP Lck Lev .1 z2

DDB #064Opto Label 01

DDB #111All Prot BlockedDDB #071

Opto Label 08

DDB #678Function Key 3

P741INPUTS

Zones 1 & 2 - 87BB Disabled

Maintenance Mode authorisation (if 0: Normal mode)

Zones 1 - 87BB Disabled TOGGLED in set

Zones 2 - 87BB Disabled TOGGLED in set

Zones 1 & 2 - 87BB & 50BF Disabled

Zone 1 - 87BB & 50BF Disabled

All Protections Disabled - CU and PU - TOGGLED in .set

Maintenance Mode authorisation (if 0: Normal mode)

Zones 1 & 2 - 87BB Disabled

Zone 2 - 87BB & 50BF Disabled

Zone 1:Red = 87BB BlockedYellow = 87BB & 50BF BlockedGreen = No Alarm

Zone 2:Red = 87BB BlockedYellow = 87BB & 50BF BlockedGreen = No Alarm

CU & PU protections:Red = BlockedGreen = Not blocked

87BB blocked

Zone 1

Zone 2

87BB & 50BF blocked

Zone 1

Zone 2

FAULT RECORDER

2/4

Page 269: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-51

PL

Pick-Up0

0

Relay Label 01DDB #000

Pick-Up0

0

Relay Label 02DDB #001

Pick-Up0

0

Relay Label 03DDB #002

Pick-Up0

0

Relay Label 04DDB #003

Pick-Up0

0

Relay Label 05DDB #004

Pick-Up0

0

Relay Label 06DDB #005

Pick-Up0

0

Relay Label 07DDB #006

Pick-Up0

0

Relay Label 08DDB #007

DDB #674Non - Latching

FnKey LED 10 Red

DDB #675FnKey LED 10 Grn

1

1

1

1

1

1

DDB #167Circt Flt Lck z1

DDB #247Lck Lev .1 Zone 1

DDB #255Lck Lev .2 Zone 1

DDB #190Trip 87BB Zone 2

DDB #198Man.Trip Zone 2

DDB #206Trip 50BF Zone 2

DDB #191Trip 87BB Zone 1

DDB #199Man.Trip Zone 1

DDB #207Trip 50BF Zone 1

DDB #280Circt Flt Lck Zx

DDB #282PU Error Lock Zx

DDB #285Circt Flt Lck CZ

DDB #287PU Error Lock CZ

DDB #166Circt Flt Lck z2

DDB #246Lck Lev .1 Zone 2

DDB #254Lck Lev .2 Zone 2

DDB #263Fault phase B

DDB #275Fault Check Zone

DDB #264Fault phase C

DDB #262Fault phase A

DDB #275Fault Check Zone

DDB #275Fault Check Zone

P741OUTPUTS

87BB Fault phase A

87BB Fault phase B

87BB Fault phase C

Trip zone 1

Trip zone 2

Circuitry faultorPU error bl ki

Zone 1 or 2 blocked

Check Zone Fault

Yellow = Check Zone Fault

3/4

Page 270: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-52

MiCOM P741, P742, P743

PL

DDB #640LatchingLED 1 Red

DDB #641LED 1 Grn

DDB #642LatchingLED 2 Red

DDB #643LED 2 Grn

DDB #644LatchingLED 3 Red

DDB #645LED 3 Grn

DDB #646LatchingLED 4 Red

DDB #647LED 4 Grn

DDB #648LatchingLED 5 Red

DDB #649LED 5 Grn

DDB #650Non - Latching

LED 6 Red

DDB #651LED 6 Grn

DDB #652Non - Latching

LED 7 Red

DDB #653LED 7 Grn

DDB #654Non - Latching

LED 8 Red

DDB #655LED 8 Grn

1

1

1

1

1

1

1

&

1

&

DDB #151PU Error Lck z1

DDB #167Circt Flt Lck z1

DDB #247Lck Lev .1 Zone 1

DDB #255Lck Lev .2 Zone 1

DDB #150PU Error Lck z2

DDB #166Circt Flt Lck z2

DDB #246Lck Lev .1 Zone 2

DDB #254Lck Lev .2 Zone 2

DDB #135Fibre Com Error

DDB #272Fibre Com Worn

DDB #135Fibre Com Error

DDB #272Fibre Com Worn

DDB #263Fault phase B

DDB #207Trip 50BF Zone 1

DDB #206Trip 50BF Zone 2

DDB #285Circt Flt Lck CZ

DDB #287PU Error Lock CZ

DDB #285Circt Flt Lck CZ

DDB #287PU Error Lock CZ

DDB #262Fault phase A

DDB #264Fault phase C

DDB #191Trip 87BB Zone 1

DDB #190Trip 87BB Zone 2

P741

87BB Fault phase A

LEFT-HAND LEDS

87BB Fault phase B

87BB Fault phase C

Trip zone 1:Red: 50BFYellow: BothGreen: 87BB

Trip zone 2:Red: 50BFYellow: BothGreen: 87BB

Zone 1:Red: Zone blockingYellow: Check Zone blocking Green: Protected

Zone 2:Red: Zone blockingYellow: Check Zone blocking Green: Protected

Fibre communicationRed: ErrorYellow: Change Green: Healthy

4/4

Page 271: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-53

PL

MiCOM P742 PROGRAMMABLE SCHEME LOGIC

1

1

1

1

DDB #135Reset Indication

DDB #064Opto Label 01

DDB #192CU->PU Signal 01

DDB #608Control Input 1

DDB #131Reset Trip latch

DDB #065Opto Label 02

DDB #193CU->PU Signal 02

DDB #609Control Input 2

DDB #071Opto Label 08

DDB #124CB Aux. 3ph(52b)

DDB #066Opto Label 03

DDB #105Q1 Aux. (89a)

DDB #075Opto Label 12

DDB #116Ext. 3 ph Trip

DDB #069Opto Label 06

DDB #106Q2 Aux. (89b)

DDB #078Opto Label 15

DDB #120Man.CB Close Cmd

DDB #072Opto Label 09

DDB #109Q3 Aux. (89a)

DDB #31150BF Disabled

DDB #074Opto Label 11

DDB #611Control Input 4

DDB #312Ov erhaul Mode

DDB #079Opto Label 16

DDB #612Control Input 5

DDB #067Opto Label 04

DDB #104Q1 Aux. (89b)

DDB #076Opto Label 13

DDB #121CB not av ailable

DDB #070Opto Label 07

DDB #123CB Aux. 3ph(52a)

DDB #073Opto Label 10

DDB #108Q3 Aux. (89b)

DDB #068Opto Label 05

DDB #107Q2 Aux. (89a)

DDB #077Opto Label 14

DDB #122Ext. CB Fail

P742

1/4

INPUTS

Reset all indications

Reset Trip Relays (if latched is enabled)

Isolator 1

External 3phase Trip order

External Back-trip order

Mode 50BF Disabled:- Local trip disabled- 50BF disabled- No backtrip sent to the CU- 87BB in service on this PU

Mode Overhaul:- PU 87BB protection Out Of Service- Position of isolator and CB are forced- Mode used to test local protection- Local trip enabled- No backtrip

Closed position

Open position

Open position

Open position

Open position

Closed position

Closed position

Closed position

CB Out Of Service

Manual CB Close Command

Isolator 2

Cicruit breaker

Isolator 3

Commissioning mode

Integrated CB Failure Protection

External CB Failure Protection

Commissioning mode

Page 272: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-54

MiCOM P741, P742, P743

PL

Pick-Up5000

0

Dwell20

0

Pick-Up5000

0

Pick-Up5000

0

&

11

1

&

11

&

11

1

DDB #066Opto Label 03

DDB #067Opto Label 04

DDB #066Opto Label 03

DDB #067Opto Label 04

DDB #261Dead Zone Fault

DDB #358Any Trip

DDB #068Opto Label 05

DDB #069Opto Label 06

DDB #068Opto Label 05

DDB #069Opto Label 06

DDB #072Opto Label 09

DDB #073Opto Label 10

DDB #072Opto Label 09

DDB #073Opto Label 10

DDB #352CB Status Alarm

DDB #321Q1 Status Alarm

DDB #468Fault_REC_TRIG

DDB #323Q2 Status Alarm

DDB #325Q3 Status Alarm

P742

2/4

Isolator 1

Isolator 2

Isolator 3

Status Alarm

Status Alarm

Status Alarm

Fault recorder

CB Status Alarm

Page 273: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-55

PL

DDB #096Non -

LatchingLED 1

DDB #097Non -

LatchingLED 2

DDB #098Non -

LatchingLED 3

DDB #099Latching LED 4

DDB #100Latching LED 5

DDB #101Latching LED 6

DDB #102Non -

LatchingLED 7

DDB #103Non -

LatchingLED 8

1

&

&

DDB #076Opto Label 13

DDB #174CB Fail Alarm

DDB #256Internal Trip

DDB #257Trip 87BB

DDB #256Internal Trip

DDB #259Trip 50BF (CU)

DDB #320Q1 Closed

DDB #324Q3 Closed

DDB #322Q2 Closed

DDB #261Dead Zone Fault

DDB #252Fibre Com Error

P742

3/4

LEFT-HAND LEDS

Isolator 1

Isolator 2

Red: Closed

Red: Closed

Isolator 3

Red: Closed

Trip information

Trip on 50BF CU backtrip order

Trip on 87BB CU trip order

Dead Zone Fault

Monitoring information

Red: CB Out Of Service

Red: Fibre Com Error

Page 274: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-56

MiCOM P741, P742, P743

PL

Pick-Up0

0

Relay Label 04DDB #003

Pick-Up0

0

Relay Label 05DDB #004

Pick-Up0

0

Relay Label 06DDB #005

Pick-Up0

0

Relay Label 07DDB #006

Pick-Up0

0

Relay Label 08DDB #007

1

1

1

DDB #076Opto Label 13

DDB #174CB Fail Alarm

DDB #168Ext. Retrip Ph A

DDB #169Ext. Retrip Ph B

DDB #170Ext. Retrip Ph C

DDB #171Int. Retrip 3 ph

DDB #256Internal Trip

DDB #261Dead Zone Fault

DDB #174CB Fail Alarm

P742OUTPUT RELAYS

Infomation to System

CB Fail

CB Fail - OutOfService

CB Fail - Retrip

Trip or dead zone

CB or isolator status alarm

Page 275: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-57

PL

MiCOM P743 PROGRAMMABLE SCHEME LOGIC

DDB #656Non - Latching

FnKey LED 1 Red

DDB #657FnKey LED 1 Grn

DDB #658Non - Latching

FnKey LED 2 Red

DDB #659FnKey LED 2 Grn

DDB #662Non - Latching

FnKey LED 4 Red

DDB #663FnKey LED 4 Grn

DDB #664Non - Latching

FnKey LED 5 Red

DDB #665FnKey LED 5 Grn

1

1

1

1

&

&

1

DDB #135Reset Indication

DDB #064Opto Label 01

DDB #192CU->PU Signal 01

DDB #608Control Input 1

DDB #676Function Key 1

DDB #065Opto Label 02

DDB #193CU->PU Signal 02

DDB #609Control Input 2

DDB #677Function Key 2

DDB #081Opto Label 18

DDB #118External Trip B

DDB #080Opto Label 17

DDB #117External Trip A

DDB #077Opto Label 14

DDB #122Ext. CB Fail

DDB #071Opto Label 08

DDB #124CB Aux. 3ph(52b)

DDB #066Opto Label 03

DDB #105Q1 Aux. (89a)

DDB #073Opto Label 10

DDB #108Q3 Aux. (89b)

DDB #068Opto Label 05

DDB #107Q2 Aux. (89a)

DDB #074Opto Label 11

DDB #611Control Input 4

DDB #679Function Key 4

DDB #312Ov erhaul Mode

DDB #079Opto Label 16

DDB #612Control Input 5

DDB #680Function Key 5

DDB #075Opto Label 12

DDB #116Ext. 3 ph Trip

DDB #082Opto Label 19

DDB #119External Trip C

DDB #131Reset Trip latch

DDB #067Opto Label 04

DDB #104Q1 Aux. (89b)

DDB #076Opto Label 13

DDB #121CB not av ailable

DDB #070Opto Label 07

DDB #123CB Aux. 3ph(52a)

DDB #069Opto Label 06

DDB #106Q2 Aux. (89b)

DDB #078Opto Label 15

DDB #120Man.CB Close Cmd

DDB #072Opto Label 09

DDB #109Q3 Aux. (89a)

DDB #31150BF Disabled

External Trip Phase A order

External Trip Phase B order

External Trip Phase C order

External 3phase Trip order

Green: Reset indication

Green: Reset Trip Latch

Mode 50BF Disabled:- Local trip disabled- 50BF disabled- No backtrip- 87BB in service on this

Mode Overhaul:- PU 87BB protection Out Of Service - Position of isolator and CB are forced - Mode used to test local protection - Local trip enabled - No backtrip

Closed position

Open position

Closed position

Open position

Closed position

Open position

Closed position

Open position

CB Out Of Service

Manual CB Close Command

External Back-trip order

P743INPUTS

Reset all indications

Reset Trip Relays (if latched is enabled)

Isolator 1

Isolator 2

Cicruit breaker

Isolator 3

External CB Failure Protection

Integrated CB Failure Protection

Commissioning mode

FK 4 & FK 5 TOGGLED in .set

Page 276: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-58

MiCOM P741, P742, P743

PL

Dwell20

0

Pick-Up5000

0

Pick-Up5000

0

Pick-Up5000

0

1

&

11

&

11

&

11

1

DDB #261Dead Zone Fault

DDB #358Any Trip

DDB #066Opto Label 03

DDB #067Opto Label 04

DDB #066Opto Label 03

DDB #067Opto Label 04

DDB #068Opto Label 05

DDB #069Opto Label 06

DDB #068Opto Label 05

DDB #069Opto Label 06

DDB #072Opto Label 09

DDB #073Opto Label 10

DDB #072Opto Label 09

DDB #073Opto Label 10

DDB #352CB Status Alarm

DDB #323Q2 Status Alarm

DDB #468Fault_REC_TRIG

DDB #321Q1 Status Alarm

DDB #325Q3 Status Alarm

P743

2/4

Isolator 1

Isolator 2

Isolator 3

Fault recorder

Status Alarm

Status Alarm

Status Alarm

CB Status Alarm

Page 277: P74x_EN_M_H54

Programmable Logic P74x/EN PL/H54 MiCOM P741, P742, P743

(PL) 7-59

PL

DDB #640Non - Latching

LED 1 Red

DDB #641LED 1 Grn

DDB #642Non - Latching

LED 2 Red

DDB #643LED 2 Grn

DDB #644Non - Latching

LED 3 Red

DDB #645LED 3 Grn

DDB #646LatchingLED 4 Red

DDB #647LED 4 Grn

DDB #648LatchingLED 5 Red

DDB #649LED 5 Grn

DDB #650LatchingLED 6 Red

DDB #651LED 6 Grn

DDB #652Non - Latching

LED 7 Red

DDB #653LED 7 Grn

DDB #654Non - Latching

LED 8 Red

DDB #655LED 8 Grn

1

&

1

1

1

1

1

1

&

&

1

1

DDB #076Opto Label 13

DDB #174CB Fail Alarm

DDB #256Internal Trip

DDB #257Trip 87BB

DDB #320Q1 Closed

DDB #320Q1 Closed

DDB #322Q2 Closed

DDB #322Q2 Closed

DDB #324Q3 Closed

DDB #324Q3 Closed

DDB #256Internal Trip

DDB #259Trip 50BF (CU)

DDB #252Fibre Com Error

DDB #253Fibre Com Worn

DDB #252Fibre Com Error

DDB #253Fibre Com Worn

DDB #261Dead Zone Fault

P743

3/4

LEFT-HAND LEDS

Isolator 1

Isolator 2

Red: ClosedYellow: Status AlarmGreen: Open

Red: ClosedYellow: Status AlarmGreen: Open

Red: ClosedYellow: Status AlarmGreen: Open

Red: Trip on 50BF CU backtrip order

Red: Trip on 87BB CU trip order

Red: Dead Zone Fault

Red: CB Out Of ServiceGreen: CB Healthy

Fibre comRed: ErrorYellow: ChangeGreen: Healthy

Monitoring information

Trip information

Isolator 3

Page 278: P74x_EN_M_H54

P74x/EN PL/H54 Programmable Logic

(PL) 7-60

MiCOM P741, P742, P743

PL

Pick-Up0

0

Relay Label 04DDB #003

Pick-Up0

0

Relay Label 05DDB #004

Pick-Up0

0

Relay Label 06DDB #005

Pick-Up0

0

Relay Label 07DDB #006

Pick-Up0

0

Relay Label 08DDB #007

Pick-Up0

0

Relay Label 09DDB #008

Pick-Up0

0

Relay Label 10DDB #009

Pick-Up0

0

Relay Label 11DDB #010

1

1

1

DDB #076Opto Label 13

DDB #174CB Fail Alarm

DDB #168Ext. Retrip Ph A

DDB #169Ext. Retrip Ph B

DDB #170Ext. Retrip Ph C

DDB #171Int. Retrip 3 ph

DDB #256Internal Trip

DDB #261Dead Zone Fault

DDB #174CB Fail Alarm

DDB #170Ext. Retrip Ph C

DDB #168Ext. Retrip Ph A

DDB #169Ext. Retrip Ph B

P743

CB Fail

CB Fail - OutOfService

CB Fail - Retrip

Trip or dead zone

Retrip 2nd coil phase A

Retrip 2nd coil phase B

Retrip 2nd coil phase C

CB or isolator status alarm

Infomation to System

CB Fail Retrip on 2nd coil

OUTPUT RELAYS

Page 279: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

MRMEASUREMENTS AND RECORDING

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 280: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

MiCOM P741, P742, P743

Page 281: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-1

MR

CONTENTS

1. MEASUREMENTS AND RECORDING 3

1.1 Introduction 3

1.2 Event & fault records 3

1.2.1 Types of event 6

1.3 Central Unit (P741) 7

1.4 Peripheral Unit 7

1.4.2 Resetting of event/fault records 9

1.4.3 Viewing event records via MiCOM S1 support software 10

1.4.4 Event filtering 12

1.5 Disturbance recorder 13

1.5.1 Central Unit P741 13

1.5.2 Peripheral Unit P742 or P743 15

1.6 Measurements 18

1.6.1 Check Zone Phase Currents 19

1.6.2 Measured currents 19

1.6.3 Sequence voltages and currents 19

1.6.4 Settings 19

1.6.5 Measurement display quantities 20

1.7 Monitoring tools 21

1.7.1 MiCOM S1 21

1.7.2 Dynamic Synoptic 22

Page 282: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-2

MiCOM P741, P742, P743

MRBLANK PAGE

Page 283: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-3

MR

1. MEASUREMENTS AND RECORDING

1.1 Introduction

The P74x is equipped with integral measurements, event, fault and disturbance recording facilities suitable for analysis of complex system disturbances.

The relay is flexible enough to allow for the programming of these facilities to specific user application requirements and are discussed below.

1.2 Event & fault records

The relay records and time tags up to 512 events and stores them in non-volatile (battery backed up) memory. This enables the system operator to establish the sequence of events that occurred within the relay following a particular power system condition, switching sequence etc. When the available space is exhausted, the oldest event is automatically overwritten by the new one.

The real time clock within the relay provides the time tag to each event, to a resolution of 1ms.

The event records are available for viewing either via the front plate LCD or remotely, via the communications port.

Local viewing on the LCD is achieved in the menu column entitled "VIEW RECORDS". This column allows viewing of event, fault and maintenance records. Different columns exist in the Central unit and the Peripheral Unit.

The column for the Central Unit is shown below. The column displayed in the Peripheral Units is shown underneath.

VIEW RECORDS

LCD Reference Description

Select Event Setting range from 0 to 511. This selects the required event record from the possible 512 that may be stored. A value of 0 corresponds to the latest event and so on.

Time & Date Time & Date Stamp for the event given by the internal Real Time Clock.

Event Text Up to 16 Character description of the Event refer to following sections).

Event Value Up to 32 Bit Binary Flag or integer representative of the Event (refer to following sections).

Select Fault Setting range from 0 to 4. This selects the required fault record from the possible 5 that may be stored. A value of 0 corresponds to the latest fault and so on.

The following cells show all the fault flags, protection starts, protection trips, fault location, measurements etc. associated with the fault, i.e. the complete fault record.

Active Group Active group when fault recorder starts

Faulted Phase Phase initiating fault recorder starts

Start Elements Note relevant for CU

Trip Elements Trip 87BB zone x, Trip 87BB block zone x, Trip 50BF zone x, Trip 50BF block zone, Dead Zone signal, Manual trip zone.

Time Stamp Time and date of fault recorder start

Fault Alarms Yes, No

System Frequency 50.00 Hz, 60.00 Hz,

Page 284: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-4

MiCOM P741, P742, P743

MR

VIEW RECORDS

LCD Reference Description

Fault duration - if fault detected by differential protection => delay between first detection of differential current and disappearance of differential current

- if breaker failure order received from PU => delay between reception of order and disappearance of the current

IA diff Differential current of the check zone

IB diff Differential current of the check zone

IC diff Differential current of the check zone

IN diff Differential current of the check zone

IA bias Differential current of the check zone

IB bias Bias current of the check zone

IC bias Bias current of the check zone

IN bias Bias current of the check zone

Faulted Zone Zone where fault is detected

Scheme Topology Zone linked to current nodes (for the 8 nodes)

Scheme Topology CT linked to current nodes (for the 8 nodes)

Select Maint. Setting range from 0 to 9. This selects the required maintenance report from the possible 10 that may be stored. A value of 0 corresponds to the latest report and so on.

Maint. Text Up to 16 Character description of the occurrence (refer to following sections).

Maint. Type/Main Data These cells are numbers representative of the occurrence. They form a specific error code which should be quoted in any related correspondence to Report Data.

Reset Indication

Either Yes or No. This serves to reset the trip LED indications provided that the relevant protection element has reset, to reset all LED and relays latched in the PSL, and to reset the latched alarms.

Page 285: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-5

MR

For extraction from a remote source via communications, refer to the SCADA Communications section (P74x/EN CT), where the procedure is fully explained.

VIEW RECORDS

LCD Reference Description

Select Event Setting range from 0 to 511. This selects the required event record from the possible 512 that may be stored. A value of 0 corresponds to the latest event and so on.

Time & Date Time & Date Stamp for the event given by the internal Real Time Clock.

Event Text Up to 16 Character description of the Event refer to following sections).

Event Value Up to 32 Bit Binary Flag or integer representative of the Event (refer to following sections).

Select Fault Setting range from 0 to 4. This selects the required fault record from the possible 5 that may be stored. A value of 0 corresponds to the latest fault and so on.

The following cells show all the fault flags, protection starts, protection trips, fault location, measurements etc. associated with the fault, i.e. the complete fault record.

Active Group Active group when fault recorder starts

Faulted Phase Phase initiating fault recorder starts

Tripped Phase Phase tripped

Start Elements Start I>1, Start I>2, Start I>2BB, Start I>BB, Start IN>1, Start IN>2, Start IN>2BB, Start IN>BB

Trip Elements Trip I>1, Trip I>2, Trip IN>1, Trip IN>2, Trip 87BB, Trip CBFail tBF1, Trip CBFail tBF2, Trip CBFail tBF3, Trip CBFail tBF4, Trip 50BF (CU), Manual Trip zone, Trip 87BB block, Dead Zone Trip

Time Stamp Time and date of fault recorder start

Fault Alarms Yes, No

System Frequency 50.00 Hz, 60.00 Hz,

Relay Trip Time Delay between reception of signal and end of trip on PU

IA Feeder phase A current

IB Feeder phase B current

IC Feeder phase C current

IN Feeder phase N current

Select Maint. Setting range from 0 to 9. This selects the required maintenance report from the possible 10 that may be stored. A value of 0 corresponds to the latest report and so on.

Maint. Text Up to 16 Character description of the occurrence (refer to following sections).

Maint. Type/Main Data These cells are numbers representative of the occurrence. They form a specific error code which should be quoted in any related correspondence to Report Data.

Reset Indication

Either Yes or No. This serves to reset the trip LED indications provided that the relevant protection element has reset, to reset all LED and relays latched in the PSL, and to reset the latched alarms.

Page 286: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-6

MiCOM P741, P742, P743

MR

1.2.1 Types of event

An event may be a change of state of a control input or output relay, an alarm condition, setting change etc. The following sections show the various items that constitute an event:

1.2.1.1 Change of state of opto-isolated inputs

If one or more of the opto (logic) inputs has changed state since the last time that the protection algorithm ran, the new status is logged as an event. When this event is selected to be viewed on the LCD, three applicable cells will become visible as shown below:

Time & date of event

“LOGIC INPUTS #”

“Event Value 0101010101010101”

Where # = 1 or 2 depending upon which group of 16 opto inputs is selected. In the case of P74x relay, however, the value will always be “1” as it is impossible to have more than 16 opto inputs.

The Event Value is a 12, 16, 24 or 32-bit word showing the status of the opto inputs, where the least significant bit (extreme right) corresponds to opto input 1 etc. The same information is present if the event is extracted and viewed via PC.

1.2.1.2 Change of state of one or more output relay contacts

If one or more of the output relay contacts have changed state since the last time that the protection algorithm ran, then the new status is logged as an event. When this event is selected to be viewed on the LCD, three applicable cells will become visible as shown below:

Time & date of event

“OUTPUT CONTACTS #”

“Event Value 1010101010101010”

Where # = 1 or 2 depending upon which group of 16 output relays is selected. In the case of P74x relay, however, the value will always be “1” as it is impossible to have more than 16 output relays.

The Event Value is a 12, 16, 24 or 32 bit word showing the status of the output contacts, where the least significant bit (extreme right) corresponds to output contact 1 etc. The same information is present if the event is extracted and viewed via PC.

1.2.1.3 Relay alarm conditions

Any alarm conditions generated by the relays will also be logged as individual events. The following table shows examples of some of the alarm conditions and how they appear in the event list:

Alarm Condition Event Text Event Value

Battery Fail Battery Fail ON/OFF Bit position 0 in 32 bit field

Field Voltage Fail Field Volt Fail ON/OFF Bit position 1 in 32 bit field

The previous table shows the abbreviated description that is given to the various alarm conditions and also a corresponding value between 0 and 31. This value is appended to each alarm event in a similar way as for the input and output events previously described. It is used by the event extraction software, such as MiCOM S1, to identify the alarm and is therefore invisible if the event is viewed on the LCD. Either ON or OFF is shown after the description to signify whether the particular condition has become operated or has reset.

Page 287: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-7

MR

1.3 Central Unit (P741)

English Français Deutsch Español

Fibre Com Worn Com Fibre Usée LWL Komm. Warn. FibraCom UsadoFibre Com Error Com Fibre Erreur LWL Komm.ausfall Error FibraComCircuitry Fault Défaut Filerie MKUE ZE Id FallaCircuiteríaLocking Level 1 Consign Niv 1 Blockadestufe 1 Bloqueo Nivel 1 Locking Level 2 Consign Niv 2 Blockadestufe 2 Bloqueo Nivel 2 Config Error Erreur Config Konfig. Fehler Error Config User Alarm 1 Alarme Ut. 1 Warnmeldung 1 Alarma us. 1 User Alarm 2 Alarme Ut. 2 Warnmeldung 2 Alarma us. 2 User Alarm 3 Alarme Ut. 3 Warnmeldung 3 Alarma us. 3 User Alarm 4 Alarme Ut. 4 Warnmeldung 4 Alarma us. 4 User Alarm 5 Alarme Ut. 5 Warnmeldung 5 Alarma us. 5 User Alarm 6 Alarme Ut. 6 Warnmeldung 6 Alarma us. 6 User Alarm 7 Alarme Ut. 7 Warnmeldung 7 Alarma us. 7 User Alarm 8 Alarme Ut. 8 Warnmeldung 8 Alarma us. 8 General Alarm Alarme Générale allgemeine Warn. Alarma General

1.4 Peripheral Unit

English Français Deutsch Español

Breaker Failure Défaillance DJ LS-Versager Fallo Interrupt CT Fail IN Alarm.Défail. IR Stromw-Fehler IE Offset via ABCN Offset Chan ABCN Offset Voie ABCN Offset 3-pol.-N Offset Chan ABCNFibre Com Error Com Fibre Erreur LWL Komm.ausfall Error FibraCom Fibre Com Worn Com Fibre Usée LWL Komm. Warn. FibraCom UsadoDead Zone Fault Déf. Zone Morte Fehler Totzone FalloZona MuertaCircuitry Fault Défaut Filerie MKUE ZE FalloCircuiteríaCB Status Alarm Alarme état DJ LS-Statusalarm AlarmaEstado INTMan CB Cls Fail Déf.ferm.man.DJ Stoer. Man.EIN-K FalloCierMan INTMan CB Trip Fail Déf.ouver.man.DJ Stoer. Man.AUS-K FalloAperMan INTCurrent Overflow Débordement I STROM_UEBERLAUF Desbordado IConfig Error Erreur Config Konfig. Fehler Error Config. PU OutOfService PU Hors Service FE ausser Betr. PU Fuera de ServPU I/O Disabled PU E/S désact. FE E/A gesperrt PU E/S desactiv User Alarm 1 Alarme Ut. 1 Warnmeldung 1 Alarma us. 1 User Alarm 2 Alarme Ut. 2 Warnmeldung 2 Alarma us. 2 User Alarm 3 Alarme Ut. 3 Warnmeldung 3 Alarma us. 3 User Alarm 4 Alarme Ut. 4 Warnmeldung 4 Alarma us. 4 User Alarm 5 Alarme Ut. 5 Warnmeldung 5 Alarma us. 5 User Alarm 6 Alarme Ut. 6 Warnmeldung 6 Alarma us. 6 User Alarm 7 Alarme Ut. 7 Warnmeldung 7 Alarma us. 7 General Alarm Alarme Générale allgemeine Warn. Alarma General

1.4.1.1 Protection element starts and trips

Any operation of protection elements, (either a start or a trip condition) will be logged as an event record, consisting of a text string indicating the operated element and an event value. Again, this value is intended for use by the event extraction software, such as MiCOM S1, rather than for the user, and is therefore invisible when the event is viewed on the LCD.

Page 288: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-8

MiCOM P741, P742, P743

MR

1.4.1.2 General events

A number of events come under the heading of ‘General Events’ - an example is shown below:

Nature of Event Displayed Text in Event Record Displayed Value

Level 1 password modified, either from user interface, front or rear port.

PW1 modified UI, F, R or R2 0 UI=6, F=11, R=16, R2=38

A complete list of the ‘General Events’ is given in the Relay Menu Database (P74x/EN MD), which is a separate document, available for downloaded from our website.

1.4.1.3 Fault records

Each time a fault record is generated, an event is also created. The event simply states that a fault record was generated, with a corresponding time stamp.

Note that viewing of the actual fault record is carried out in the "Select Fault’" cell further down the "VIEW RECORDS" column, which is selectable from up to 5 records. These records consist of fault flags, fault location, fault measurements etc. Also note that the time stamp given in the fault record itself will be more accurate than the corresponding stamp given in the event record as the event is logged some time after the actual fault record is generated.

The fault record is triggered from the ‘Fault REC. TRIG.’ signal assigned in the default programmable scheme logic to any trip (87BB or 50BF trip in the P741). Note the fault measurements in the fault record are given at the time of the protection start. Also, the fault recorder does not stop recording until the reset of the ‘Fault REC. TRIG.’ signal in order to record all the protection flags during the fault.

It is recommended that the triggering contact be ‘self reset’ and not latching. If a latching contact were chosen the fault record would not be generated until the contact had fully reset.

1.4.1.4 Maintenance reports

Internal failures detected by the self-monitoring circuitry, such as watchdog failure, field voltage failure etc. are logged into a maintenance report. The maintenance report holds up to 10 such ‘events’ and is accessed from the "Select Report" cell at the bottom of the "VIEW RECORDS" column.

Each entry consists of a self explanatory text string and a ‘Type’ and ‘Data’ cell, which are explained in the menu extract at the beginning of this section.

Each time a Maintenance Report is generated, an event is also created. The event simply states that a report was generated, with a corresponding time stamp.

Page 289: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-9

MR

1.4.1.5 Setting changes

Changes to any setting within the relay are logged as an event. Two examples are shown in the following table:

Type of Setting Change Displayed Text in Event Record Displayed Value

Control/Support Setting C & S Changed 22

Group # Change Group # Changed #

Where # = 1 to 4

Note: Control/Support settings are communications, measurement, CT/VT ratio settings etc, which are not duplicated within the four setting groups. When any of these settings are changed, the event record is created simultaneously. However, changes to protection or disturbance recorder settings will only generate an event once the settings have been confirmed at the ‘setting trap’.

1.4.2 Resetting of event/fault records

If it is required to delete either the event, fault or maintenance reports, this may be done from within the "RECORD CONTROL" column.

Page 290: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-10

MiCOM P741, P742, P743

MR

1.4.3 Viewing event records via MiCOM S1 support software

When the event records are extracted and viewed on a PC they look slightly different than when viewed on the LCD.

The following shows a P741 example of how various events appear when displayed using MiCOM S1:

The following shows a P742 example of how various events appear when displayed using MiCOM S1:

Page 291: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-11

MR

As can be seen, the first line gives the description and time stamp for the event, whilst the additional information that is displayed below may be collapsed via the +/– symbol.

For further information regarding events and their specific meaning, refer to relay menu database document (P74x/EN MR). This is a standalone document not included in this manual.

Page 292: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-12

MiCOM P741, P742, P743

MR

1.4.4 Event filtering

It is possible to disable the reporting of events from all interfaces that supports setting changes. The settings that control the various types of events are in the record control column. The effect of setting each to disabled is as follows:

Menu Text Default Setting Available Settings

Clear Event No No or Yes

Selecting “Yes” will cause the existing event log to be cleared and an event will be generated indicating that the events have been erased.

Clear Faults No No or Yes

Selecting “Yes” will cause the existing fault records to be erased from the relay.

Clear Maint. No No or Yes

Selecting “Yes” will cause the existing maintenance records to be erased from the relay.

Alarm Event Enabled Enabled or Disabled

Disabling this setting means that all the occurrences that produce an alarm will result in no event being generated.

Relay O/P Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any change in logic input state.

Opto Input Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any change in logic input state.

General Event Enabled Enabled or Disabled

Disabling this setting means that no General Events will be generated

Fault Rec. Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any fault that produces a fault record

Maint. Rec. Event Enabled Enabled or Disabled

Disabling this setting means that no event will be generated for any occurrence that produces a maintenance record.

Protection Event Enabled Enabled or Disabled

Disabling this setting means that any operation of protection elements will not be logged as an event.

DDB 383 - 0 11111111111111111111111111111111

Displays the status of DDB signals 0 – 383.

DDB 1022 - 992 11111111111111111111111111111111

Displays the status of DDB signals 1022 – 992.

Note that some occurrences will result in more than one type of event, e.g. a battery failure will produce an alarm event and a maintenance record event.

If the Protection Event setting is enabled a further set of settings is revealed which allow the event generation by individual DDB signals to be enabled or disabled.

For further information regarding events and their specific meaning, refer to relay menu database document (P74x/EN MD).

Page 293: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-13

MR

1.5 Disturbance recorder

The integral disturbance recorder has an area of memory specifically set aside for record storage. The number of records that may be stored by the relay is dependent upon the selected recording duration. The relay can typically store a minimum of 50 records, each of 1.2 seconds duration in the CU and up to 10.5 seconds in a PU. Disturbance records continue to be recorded until the available memory is exhausted, at which time the oldest record(s) are overwritten to make space for the newest one.

The recorder stores actual samples that are taken at a rate of 12 samples per cycle in the Central Unit (CU) and in the Peripheral Units (PU).

Minimum delay between 2 disturbance records (in the CU) is 5s.

Each disturbance record consists of 8 analogue data channels in the CU and 4 analogue data channels in the Pus and 32 digital data channels. The relevant CT ratios for the analogue channels are also extracted to enable scaling to primary quantities.

The "DISTURBANCE RECORDER" menu columns are different for the Central Unit and the Peripheral Units as shown in the configuration columns below:

1.5.1 Central Unit P741

Setting Range Menu Text Default Setting

Min. Max. Step Size

DISTURB. RECORDER

Duration 1.2 s 1.2 s 1.2 s 0.0 s

This sets the overall recording time.

Trigger Position 33.3% 0.0% 100.0% 33.3%

This sets the trigger point as a percentage of the duration. For example, the default settings show that the overall recording time is set to 1.2s with the trigger point being at 33.3% of this, giving 0.4 s pre-fault and 0.8 s post fault recording times.

Trigger Mode Single Single

Because set to single mode, if a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger.

Analog. Channel 1 IA diff Non settable

The Phase A differential calculated current is assigned to this channel.

Analog. Channel 2 IB diff As above

The Phase B differential calculated current is assigned to this channel.

Analog. Channel 3 IC diff As above

The Phase C differential calculated current is assigned to this channel.

Analog. Channel 4 IN diff As above

The Neutral differential calculated current is assigned to this channel.

Analog. Channel 5 IA bias As above

The Phase A bias calculated current is assigned to this channel.

Analog. Channel 6 IB bias As above

The Phase B bias calculated current is assigned to this channel.

Analog. Channel 7 IC bias As above

The Phase C bias calculated current is assigned to this channel.

Analog. Channel 8 IN bias As above

The Neutral bias calculated current is assigned to this channel.

Page 294: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-14

MiCOM P741, P742, P743

MR

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 1 Circt Flt Lck z1 Any O/P Contacts or Any Opto Inputs or Internal Digital Signals

The Circuitry fault blocks zone 1 digital channel is assigned to this channel.

Digital Inputs 2 Circt Flt Lck z2 As above

The Circuitry fault blocks zone 2 digital channel is assigned to this channel.

Digital Inputs 3 87BB Blocked As above

The digital 87BB Blocked channel is assigned to this channel.

Digital Inputs 4 Ext Start DR As above

The External start of the disturbance recorder digital channel is assigned to this channel.

Digital Inputs 5 Earth Fault As above

The Earth fault digital channel is assigned to this channel.

Digital Inputs 6 Fault Check zone As above

The Fault Check zone digital channel is assigned to this channel.

Digital Inputs 7 Fault phase A As above

The Fault phase A digital channel is assigned to this channel.

Digital Inputs 8 Fault phase B As above

The Fault phase B digital channel is assigned to this channel.

Digital Inputs 9 Fault phase C As above

The Fault phase C digital channel is assigned to this channel.

Digital Inputs 10 Flt 87BB zone 1 As above

The Fault 87BB zone 1 digital channel is assigned to this channel.

Digital Inputs 11 Flt 87BB zone 2 As above

The Fault 87BB zone 2 digital channel is assigned to this channel.

Digital Inputs 12 Manual Start DR As above

The Manual start of the disturbance recorder digital channel is assigned to this channel.

Digital Inputs 13 Topo/Set Changed As above

The Topology or setting changed digital channel is assigned to this channel.

Digital Inputs 14 Trip Manual zone As above

The Manual trip of the zone digital channel is assigned to this channel.

Digital Inputs 15 Trip 50BF zone 1 As above

The Trip 50BF zone 1 digital channel is assigned to this channel.

Digital Inputs 16 Trip 50BF zone 2 As above

The Trip 50BF zone 2 digital channel is assigned to this channel.

Digital Inputs 17 Trip 87BB zone 1 As above

The Trip 87BB zone 1 digital channel is assigned to this channel.

Digital Inputs 18 Trip 87BB zone 2 As above

The Trip 87BB zone 2 digital channel is assigned to this channel.

Page 295: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-15

MR

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 19 PU Error Lck z1 As above

The PU error blocks zone 1 digital channel is assigned to this channel.

Digital Inputs 20 PU Error Lck z2 As above

The PU error blocks zone 2 digital channel is assigned to this channel.

Digital Inputs 21 to 32 Unused As above

The digital channels may be mapped to any of the opto isolated inputs or output contacts, in addition to a number of internal relay digital signals, such as protection starts, LEDs etc.

Manual Trigger No Yes or No

Command to trigger the disturbance recorder. The differential and bias currents recorded depend of the following settings Zone to record.

Zone to record Zone 1 Zone 1 to zone 8

Any one of the 8 zones can be recorded upon a manual triggering. If 2 or more zones are selected, the check zone will be recorded

1.5.2 Peripheral Unit P742 or P743

Setting Range Menu Text Default Setting

Min. Max. Step Size

DISTURB. RECORDER

Duration 1.2 s 1.2 s 10.5 s 0.01 s

This sets the overall recording time.

Trigger Position 33.3% 0.0% 100.0% 0.1%

This sets the trigger point as a percentage of the duration. For example, the default settings show that the overall recording time is set to 1.2s with the trigger point being at 33.3% of this, giving 0.4 s pre-fault and 0.8 s post fault recording times.

Trigger Mode Extended Single or Extended

If set to single mode, if a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger. However, if this has been set to "Extended", the post trigger timer will be reset to zero, thereby extending the recording time.

Analog. Channel 1 IA Non settable

The Phase A analogue current input is assigned to this channel.

Analog. Channel 2 IB As above

The Phase B analogue current input is assigned to this channel.

Analog. Channel 3 IC As above

The Phase C analogue current input is assigned to this channel.

Analog. Channel 4 IN As above

The Neutral analogue current input is assigned to this channel.

Digital Inputs 1 Field Volt Fail Any O/P Contacts or Any Opto Inputs or Internal Digital Signals

The Mains field voltage has failed digital channel is assigned to this channel.

Input 1 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Page 296: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-16

MiCOM P741, P742, P743

MR

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 2 Any Trip As above

The Any Trip digital channel is assigned to this channel.

Input 2 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 3 CB Closed As above

The CB Closed digital channel is assigned to this channel.

Input 3 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 4 CB Fail Alarm As above

The CB Fail Alarm digital channel is assigned to this channel.

Input 4 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 5 CB not available As above

The CB not available digital channel is assigned to this channel.

Input 5 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 6 CBF Int Backtrip As above

The CB Failure Internal Backtrip order digital channel is assigned to this channel.

Input 6 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 7 CBF Ext Backtrip As above

The CB Failure External Backtrip order digital channel is assigned to this channel.

Input 7 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 8 Dead Zone Fault As above

The Dead Zone Fault digital channel is assigned to this channel.

Input 8 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 9 Ext. CB Fail As above

The External CB Fail digital channel is assigned to this channel.

Input 9 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 10 Ext. 3 ph Trip As above

The Ext. 3 phase Trip digital channel is assigned to this channel.

Input 10 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 11 Internal Trip As above

The Internal Trip digital channel is assigned to this channel.

Page 297: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-17

MR

Setting Range Menu Text Default Setting

Min. Max. Step Size

Input 11 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 12 Q1 Closed As above

The Isolator 1 closed digital channel is assigned to this channel.

Input 12 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 13 Q2 Closed As above

The Isolator 2 closed digital channel is assigned to this channel.

Input 13 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 14 Q3 Closed As above

The Isolator 3 closed digital channel is assigned to this channel.

Input 14 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 15 Man. Trip zone As above

The Manual Trip of the zone digital channel is assigned to this channel.

Input 15 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 16 Relay Label 01 As above

The Relay Label 01 digital channel is assigned to this channel.

Input 16 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 17 Relay Label 02 As above

The Relay Label 02 digital channel is assigned to this channel.

Input 17 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 18 Relay Label 03 As above

The Relay Label 03 digital channel is assigned to this channel.

Input 18 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 19 Saturation ph A As above

The Saturation phase A digital channel is assigned to this channel.

Input 19 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 20 Saturation ph B As above

The Saturation phase B digital channel is assigned to this channel.

Input 20 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Page 298: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-18

MiCOM P741, P742, P743

MR

Setting Range Menu Text Default Setting

Min. Max. Step Size

Digital Inputs 21 Saturation ph C As above

The Saturation phase C digital channel is assigned to this channel.

Input 21 trigger No Trigger No Trigger, Trigger L/H, Trigger H/L

This digital channel will not trigger the Disturbance recorder.

Digital Inputs 22 Trip 50BF (CU) As above

The Trip 50BF from the CU digital channel is assigned to this channel.

Input 22 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 23 Trip 87BB As above

The Trip 87BB digital channel is assigned to this channel.

Input 23 trigger Trigger L/H No Trigger, Trigger L/H, Trigger H/L

This digital channel will trigger the Disturbance recorder when changing from ‘0’ to ‘1’.

Digital Inputs 24 to 32 Unused As above

The digital channels may be mapped to any of the opto isolated inputs or output contacts, in addition to a number of internal relay digital signals, such as protection starts, LEDs etc.

The pre and post fault recording times are set by a combination of the "Duration" and "Trigger Position" cells. "Duration" sets the overall recording time and the "Trigger Position" sets the trigger point as a percentage of the duration. For example, the default settings show that the overall recording time is set to 1.2s with the trigger point being at 33.3% of this, giving 0.4s pre-fault and 0.8s post fault recording times.

If a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger if the "Trigger Mode" has been set to "Single". However, if this has been set to "Extended", the post trigger timer will be reset to zero, thereby extending the recording time.

As can be seen from the menu, each of the analog channels is selectable from the available analog inputs to the relay. The digital channels may be mapped to any of the opto isolated inputs or output contacts, in addition to a number of internal relay digital signals, such as protection starts, LEDs etc. The complete list of these signals may be found by viewing the available settings in the relay menu or via a setting file in MiCOM S1. Any of the digital channels may be selected to trigger the disturbance recorder on either a low to high or a high to low transition, via the "Input Trigger" cell.

It is not possible to view the disturbance records locally via the LCD; they must be extracted using suitable software such as MiCOM S1. This process is fully explained in the SCADA Communications section (P74x/EN SC).

1.6 Measurements

The relay produces a variety of both directly measured and calculated system quantities. These measurement values are updated on a per second basis and can be viewed in the “Measurements” columns (up to three) of the relay or via MiCOM S1 Measurement viewer.

The P741 relay is able to measure and display the following quantities as summarized.

Page 299: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-19

MR

1.6.1 Check Zone Phase Currents

There are also measured values from the protection functions, which are also displayed under the measurement columns of the menu; these are described in the section on the relevant protection function.

The P742 and P743 relays are able to measure and display the following quantities as summarized.

− Phase Currents

There are also measured values from the protection functions, which are also displayed under the measurement columns of the menu; these are described in the section on the relevant protection function.

1.6.2 Measured currents

The P742 and P743 relays produce current values. They are produced directly from the DFT (Discrete Fourier Transform) used by the relay protection functions and present both magnitude and phase angle measurement.

1.6.3 Sequence voltages and currents

Sequence quantities are produced by the P742 and P743 relays from the measured Fourier values; these are displayed as magnitude and phase angle values.

1.6.4 Settings

1.6.4.1 Central Unit P741

The following settings under the heading measurement set-up can be used to configure the relay measurement function.

Menu Text Default Settings Available settings

MEASUREMENT SETUP

Default Display Description Description / Plant Reference / Idiff CZ / Ibias CZ / Date and Time

This setting can be used to select the default display from a range of options, note that it is also possible to view the other default displays whilst at the default level using the and

keys. However once the 15 minute timeout elapses the default display will revert to that selected by this setting.

Local Values Primary Primary/Secondary

This setting controls whether measured values via the front panel user interface and the front courier port are displayed as primary or secondary quantities.

Remote Values Primary Primary/Secondary

This setting controls whether measured values via the rear communication port are displayed as primary or secondary quantities.

Page 300: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-20

MiCOM P741, P742, P743

MR

1.6.4.2 Peripheral Unit P742 and P743

Menu Text Default Settings Available settings

MEASUREMENT SETUP

Default Display Description Description / Plant Reference / IA-IB-IC/ Date and Time

This setting can be used to select the default display from a range of options, note that it is also possible to view the other default displays whilst at the default level using the and

keys. However once the 15 minute timeout elapses the default display will revert to that selected by this setting.

Local Values Primary Primary/Secondary

This setting controls whether measured values via the front panel user interface and the front courier port are displayed as primary or secondary quantities.

Remote Values Primary Primary/Secondary

This setting controls whether measured values via the rear communication port are displayed as primary or secondary quantities.

1.6.5 Measurement display quantities

There are “Measurement” columns available in the relay for viewing of measurement quantities. These can also be viewed with MiCOM S1 (see MiCOM Px40 – Monitoring section of the MiCOM S1 User Manual) and are shown below:

Central Unit (P741):

MEASUREMENTS 1 MEASUREMENTS 2 TOPOLOGY 1 TOPOLOGY 2 IA Diff CZ Z01 : IA diff Current Node 1 Current Node 1 IB Diff CZ Z01 : IB diff *: If existing *: If existing IC Diff CZ Z01 : IC diff Current Node 2 Current Node 2 IN Diff CZ Z01 : IN diff Current Node 3 Current Node 3 IA Bias CZ Z01 : IA bias Current Node 4 Current Node 4 IB Bias CZ Z01 : IB bias Current Node 5 Current Node 5 IC Bias CZ Z01 : IC bias Current Node 6 Current Node 6 IN Bias CZ Z01 : IN bias Current Node 7 Current Node 7 *: If existing Current Node 8 Current Node 8 Z02 : IA diff Z02 : IB diff Z02 : IC diff Z02 : IN diff Z02 : IA bias Z02 : IB bias Z02 : IC bias Z02 : IN bias Etc… Z08 : IA diff Z08 : IB diff Z08 : IC diff Z08 : IN diff Z08 : IA bias Z08 : IB bias Z08 : IC bias Z08 : IN bias

Page 301: P74x_EN_M_H54

Measurements and Recording P74x/EN MR/H54 MiCOM P741, P742, P743

(MR) 8-21

MR

Peripheral Unit (P742 or P743):

MEASUREMENTS 1 TOPOLOGY 1 IA Magnitude Link CT / zone IA Phase Angle Zx: IA Diff IB Magnitude Zx: IB Diff IB Phase Angle Zx: IC Diff IC Magnitude Zx: IN Diff IC Phase Angle Zx: IA Bias IN Magnitude Zx: IB Bias IN Phase Angle Zx: IC Bias IN Derived Magn Zx: IN Bias IN Derived Angle I1 Magnitude I2 Magnitude I0 Magnitude Frequency

1.7 Monitoring tools

1.7.1 MiCOM S1

The embedded standard MiCOM S1 Software monitoring is designed for 8 zones substation. Consequently, if you open connection with P741 which protects 4 zones substation, there are error messages to inform you that cells corresponding to topology and measurements of zone 5 to 8 can not be displayed.

You can use the monitor tool even if this error message appears.

To remove an error message, you have to remove cells in the default file:

Open file celllist.txt with text editor (for example notepad). This file is located in directory Monitor in the path of MiCOM S1 install (default is c:\Programmes Files\ALSTOM\MiCOM S1\Monitor)

Go to line [P741], referring to documentation “Menu Database - P74x/EN GC”

Remove addresses of cell that you don’t want to display after the line /Measurement. For example, to remove cell [Topology 1, Current node 5], delete line 0405

Save file

Later, if you want to display a new zone, perform the reverse operation.

Page 302: P74x_EN_M_H54

P74x/EN MR/H54 Measurements and Recording

(MR) 8-22

MiCOM P741, P742, P743

MR

1.7.2 Dynamic Synoptic

A dedicated software monitoring tool has been developed which allows the user to display on a PC (desktop or laptop) the substation busbar scheme and monitor the status of the isolators, breakers and CTs as well as analogue measurements and digital values.

FIGURE 1: CONNECTED TO THE CENTRAL UNIT

FIGURE 2: CONNECTED TO A PERIPHERAL UNIT

Page 303: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

FD

FIRMWARE DESIGN

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 304: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

MiCOM P741, P742, P743

Page 305: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-1

FD

CONTENTS

1. FIRMWARE DESIGN 3

1.1 Relay system overview 3

1.1.1 Hardware overview 3

1.1.2 Software overview 6

1.2 Hardware modules 8

1.2.1 Processor board 8

1.2.2 Coprocessor board 8

1.2.3 Communication board 9

1.2.4 Internal communication buses 9

1.2.5 Input module 10

1.2.6 Power supply module (including output relays) 12

1.2.7 Ethernet board 13

1.2.8 Mechanical layout 13

1.3 Relay software 14

1.3.1 Real-time operating system 15

1.3.2 System services software 15

1.3.3 Communication software 16

1.3.4 Platform software 17

1.3.5 Protection and control software 18

1.3.6 Signal processing 18

1.4 Self testing & diagnostics 20

1.4.1 Start-up self-testing 20

1.4.2 Continuous self-testing 21

Page 306: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-2

MiCOM P741, P742, P743

FD

BLANK PAGE

Page 307: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-3

FD

1. FIRMWARE DESIGN

1.1 Relay system overview

1.1.1 Hardware overview

The relay hardware is based on a modular design whereby the relay is made up of an assemblage of several modules that are drawn from a standard range. Some modules are essential while others are optional depending on the user’s requirements.

The different modules that can be present in the relay are as follows:

1.1.1.1 Processor board (Main board)

The main board performs some functions for the relay (fixed and programmable scheme logic…) and controls the operation of modules which are on its interconnection bus within the relay. The main board also contains and controls the user interfaces (LCD, LEDs, keypad and communication interfaces).

1.1.1.2 Coprocessor board

In P742 and P743, the co-processor board controls the operation of I/O modules within the relay and manages the communication with the P741 relay.

In P741, the co-processor board controls the communication boards and manages the communication with others P741 of the system (if present).

1.1.1.3 Internal Communication board

Only present within P741 relay.

The communication board manages the communication with the P742 and P743 relays.

1.1.1.4 Analogue Input module

The Analogue input module is only present in P742 and P743 relays. The input module converts the information contained in the analogue or digital input signals into a format suitable for the co-processor board. The standard input module consists of two boards:

• a Current transformer board to provide electrical isolation

• a main input board which provides analogue to digital conversion and the isolated digital inputs.

1.1.1.5 Input and output boards

P741 P742 P743

Opto-inputs 8 x UNI(1) 16 x UNI(1) 24 x UNI(1)

Relay outputs 6 n/o and 2 c/o 6 n/o and 2 c/o 14 n/o and 2 c/o

Universal voltage range opto inputs n/o – normally open

c/o – change over

Page 308: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-4

MiCOM P741, P742, P743

FD

1.1.1.6 Power supply module

The power supply module provides a power supply to all of the other modules in the relay, at three different voltage levels. The power supply board also provides the EIA(RS)485 electrical connection for the rear communication port.

On a second board the power supply module contains:

• relays which provide the output contacts (P742 and P743),

• an auxiliary power supply (P741).

The power supply module also provides a 48V external field supply output to drive the opto isolated digital inputs (or the substation battery may be used to drive the optos).

1.1.1.7 IRIG-B board

This board, which is optional, can be used where an IRIG-B signal is available to provide an accurate time reference for the relays (P741, P742 and P743). IRIG-B board can only be used in P741 relay and is controlled by the main board.

All modules are connected by a parallel data and address bus which allows the processor board to send and receive information to and from the other modules, as required. There is also a separate serial data bus for conveying sample data from the input module to the coprocessor. Following figures show the modules of the relay and the flow of information between them. There are two independent buses. Through the first bus, the main board controls the coprocessor board and the IRIG-B board (optional, in P741). Through the second bus, the coprocessor board controls the input/output boards and input module in P742 and P743 relays, it controls the communication boards in P741 relay. So the coprocessor board is controlled by the first bus and controls the second bus. Functionally, electrically, mechanically both interconnection buses are very similar.

Universal

Opto

Board

Coprocessor

Board

Main board

Relay board

Relay

Power

Supply

n Communication

Boards

(n=1 to 7)

Auxiliary

Power Supply

(for Comm. Boards)

IRIG-B

Board

(Optional)

P3701ENb

Interconnexion buses

Interconnexion buses

ENTER

READ

=

=

CLEAR

OUT OF SERVICE

HEALTHY

=

TRIP

ALARM

FIGURE 1: MiCOM P741 ARCHITECTURE

Page 309: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-5

FD

Coprocessor

Board

Power

Supply

Relay

Board

P3702ENb

Interconnexion buses

Interconnexion buses

Universal

Opto

Board

P743

Only

P743

Only

P743

Only

Relay

Board

Free

Slot

ENTER

READ

=

=

CLEAR

OUT OF SERVICE

HEALTHY

=

TRIP

ALARM

Main Board

Universal

Opto

Board

Universal

Opto

Board

P743

Only

Analogue

Input

Module

FIGURE 2: MiCOM P742 & P743 ARCHITECTURE

1.1.1.8 Ethernet board (P741 and P743)

It provides network connectivity through either copper or fibre media at rates of 10Mb/s or 100Mb/s.

All modules are connected by a parallel data and address bus that allows the processor board to send and receive information to and from the other modules as required. There is also a separate serial data bus for conveying sample data from the input module to the processor. Figure 1 shows the modules of the relay and the flow of information between them.

In the P741 and P743, a dedicated slot is available to receive the future optional Ethernet board.

Note: It is possible to connect to the Ethernet network any of the P74x without the embedded Ethernet board using the RS485 to Ethernet converter MiCOM I4X (Courier protocol)

Page 310: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-6

MiCOM P741, P742, P743

FD

1.1.2 Software overview

The busbar protection is a distributed system composed of two different software: the first one is used in central unit (P741) and the second one in peripheral units (P742 & P743).

The software for the relay can be conceptually split into five elements; the real-time operating system, the system services software, the platform software, the communication software, and the protection and control software. These five elements are not distinguishable to the user, and are all processed. The distinction between the five parts of the software is made purely for the purpose of explanation here:

Control of interfaces to keypad,

LCD, LEDs, Front & Rear comm. ports

Data exchanged

between CU & PU:Sample data,

Logic inputs &

Outputs contacts

Measurements & event,

fault & disturbance records

Protection &

control settings

Protection & Control software

Platform software

Disturbance

recorder task

Programmable &

fixed scheme logic

Signal processing &

saturation detection

Protection

algorithms

Topology

algorithms

Front panel interface

(LCD & Keypad)

Local & remote

communications

interface - Courier

Event, Fault,

Disturbance,

Maintenance

record logging.

Settings

database

System services softwareCommunication software

Relay hardware

Curent samples

& signal quality ;

Trip order ;

Internal courrier com. ;

Date & time.

P3704ENa

FIGURE 3: SOFTWARE OVERVIEW

1.1.2.1 Real-time operating system

As explain in the hardware overview, each relay contains one main board and one coprocessor board. These two boards use two different operating system:

• For main board software: a real time operating system is used to provide a framework for the different parts of the relay’s software to operate within. To this end the software is split into tasks. The real-time operating system is responsible for scheduling the processing of these tasks such that they are carried out in the time available and in the desired order of priority.

• For coprocessor board software: a sequencer manages all the functions implemented on the coprocessor board. Each function is executed at fixed frequency; consequently the CPU load of the coprocessor is fixed and independent of the network’s frequency.

The real-time operating system is responsible for scheduling the processing of these tasks such that they are carried out in the time available and in the desired order of priority. The operating system is also responsible for the exchange of information between tasks, in the form of messages.

Page 311: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-7

FD

!"!

#$%&'(

)%

'*+(

,+-

'*.(

/)

012

012%

1

/%%

'"$%(3

)%$

33

%

4%

$%

'(

56!78

)%#3

%%*39

$%9

:)

:)

/3$33 #

2 ;1 /

*

#3%

/

FIGURE 4: RELAY MODULES AND INFORMATION FLOW

1.1.2.2 System services software

The system services software provides the low-level control of the relay hardware. For example, the system services software controls the boot of the relay’s software from the non-volatile flash EPROM memory at power-on, and provides driver software for the user interface via the LCD and keypad, and via the serial communication ports. The system services software provides an interface layer between the control of the relay’s hardware and the rest of the relay software.

1.1.2.3 Platform software

The platform software deals with the management of the relay settings, the user interfaces and logging of event, alarm, fault and maintenance records. All of the relay settings are stored in a database within the relay that provides direct compatibility with Courier communications. The platform software notifies the protection & control software of all settings changes and logs data as specified by the protection & control software.

Page 312: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-8

MiCOM P741, P742, P743

FD

1.1.2.4 Communication software

The communication software manages optical fibre communication between the central unit and the peripheral units. This includes the control of data exchanged transmitted and the synchronisation of peripheral units. With this object, the communication software interfaces with the sequencer used in coprocessors boards.

1.1.2.5 Protection & control software

The protection and control software performs the calculations for all of the protection algorithms of the relays. This includes digital signal processing such as Fourier filtering and ancillary tasks such as the measurements. The protection & control software interfaces with the platform software for settings changes and logging of records, and with the system services software for acquisition of sample data and access to output relays and digital opto-isolated inputs.

1.1.2.6 Disturbance recorder

The analogue values and logic signals are routed from the protection and control software to the disturbance recorder software. The platform software interfaces to the disturbance recorder to allow extraction of the stored records.

1.2 Hardware modules

The relay is based on a modular hardware design where each module performs a separate function within the relay operation. This section describes the functional operation of the various hardware modules.

1.2.1 Processor board

The relay is based around a TMS320VC33 floating point, 32-bit digital signal processor (DSP) operating at a clock frequency of 75MHz. This processor performs all of the calculations for the relay, including the protection functions, control of the data communication and user interfaces including the operation of the LCD, keypad and LEDs.

The processor board is located directly behind the relay’s front panel which allows the LCD, function keys and LEDs to be mounted on the processor board along with the front panel communication ports. These comprise the 9-pin D-connector for EIA(RS)232 serial communications (e.g. using MiCOM S1 and Courier communications) and the 25-pin D-connector relay test port for parallel communication. All serial communication is handled using a field programmable gate array (FPGA).

All serial communication is handled using a two-channel 85C30 serial communications controller (SCC).

The memory provided on the main processor board is split into two categories, volatile and non-volatile; the volatile memory is fast access SRAM which is used for the storage and execution of the processor software, and data storage as required during the processor’s calculations. The non-volatile memory is sub-divided into 2 groups; 4MB of flash memory for non-volatile storage of software code, present setting values, text, configuration data, latched data signals (from control inputs, function keys, LEDs, relay outputs) and 4MB of battery backed-up SRAM for the storage of disturbance, event, fault and maintenance record data.

1.2.2 Coprocessor board

The co-processor board is based around a TMS320VC5402, 16-bit digital signal processor (DSP) operating at a clock frequency of 100MHz.

The features of the co-processor board are:

• 128 K * 16 bits high speed memory for external code execution.

• 128 K * 16 bits high speed memory for data storage.

• Interface with first interconnection bus from main board.

• 4 K * 16 bits double access memory for communication with main board.

• Interface with second interconnection bus towards peripheral boards.

Page 313: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-9

FD

• Serial communication interface on optical fibre with 4 full duplex channels. The communication uses a synchronous protocol with a date rate of 2.5 Mbit/s. On the co-processor board only 2 of the 4 optical channels are provided.

On board DC-DC converter which gives 3.3V chip power supply from the interconnection bus 22V rail.

After power on, the main board loads the software in coprocessor board via double access memory. When software starts, the microprocessor configures the board. After this, optical communication can begin.

In P741 relay, coprocessor board controls 1 opto board, 1 relay board and up to 7 communication boards via its own interconnection bus.

In P742 and P743 relays, coprocessor board controls opto boards and relay boards via its own interconnection bus. Coprocessor board provides the sample synchronisation to input module and receives the samples from input module.

1.2.3 Communication board

The communication board looks like the coprocessor board. The Differences are:

• Four duplex optical channels are provided.

• The second interconnection bus is not provided. The communication board controls no board.

This board is only used within P741 relay. It performs the communication with the P742 and P743 relays.

Up to 7 communication boards can be interfaced within P741 relay. So up to 28 P742 or P743 relays can be interfaced from a P741 relay.

1.2.4 Internal communication buses

The relay has two internal interconnection buses:

• The first is controlled by the main board. Via its interconnection bus the main board controls the coprocessor board (P741, P742 & P743) and the IRIG-B board (P741 only).

• The second is controlled by the coprocessor board. Via its interconnection bus the coprocessor board controls relay boards (P741, P742 & P743), opto boards (P741, P742 & P743), input module (P742 & P743) and communication boards (P741).

These two interconnection buses are very similar. Both are based on a 64-way ribbon cable. The ribbon cable carries the data and address bus signals in addition to control signals and all power supply lines. Operation of the bus is driven by the main processor board that operates as a master while all other modules within the relay are slaves.

The DSP processor has a built-in serial port that is used to read the sample data from the serial bus. The serial bus is also carried on the 64-way ribbon cable.

The main part of the buses is a parallel link with 6 address lines for board selection, 16 data lines and control lines. On the main controlled bus, main board drive address and control lines. On the coprocessor controlled bus, coprocessor board drive address and control lines.

Other parts of the buses are:

• The sample serial link from input module to coprocessor board which loads analogue channel samples.

• Power supply which are directly wired between the two interconnection buses.

• Serial lines for rear RS485 communication which are also directly wired between the two interconnection buses. So in any way main board keeps control of the rear RS485 communication.

Page 314: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-10

MiCOM P741, P742, P743

FD

1.2.5 Input module

The input module provides the interface between the coprocessor board and the analogue and digital signals coming into the relay. The input module consists of two PCBs; the main input board and a transformer board.

The P742 and P743 provide four current inputs (3 phases and neutral).

P741 relay don’t use this board.

CT CT

Buffer

16-bit

ADC

Serial

interface

Sample

control

16:1

Multiplexer

Up to 4 current inputs

8 digital inputs

Serial sample

data bus

Trigger from

processor board

Calibration

E2 PROM

Parallel bus

Up to 4

Up to 4

Up to 4

Diffn

to

single

Diffn

to

single

Low

pass

filter

Low

pass

filter

Noise Filter

Threshold

Bus Interface

FIGURE 5: MAIN INPUT BOARD

Page 315: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-11

FD

1.2.5.1 Transformer board

The transformer board holds four voltage transformers (VTs) and four current transformers (CTs). The current inputs will accept either 1A or 5A nominal current (menu and wiring options) and the voltage inputs can be specified for either 110V or 440V nominal voltage (order option). The transformers are used both to step-down the currents and voltages to levels appropriate to the relay’s electronic circuitry and to provide effective isolation between the relay and the power system. The connection arrangements of both the current and voltage transformer secondaries provide differential input signals to the main input board to reduce noise.

1.2.5.2 Input board

The main input board is shown as a block diagram in Figure 2. It provides the circuitry for the digital input signals and the analogue-to-digital conversion for the analogue signals. Hence it takes the differential analogue signals from the CTs and VTs on the transformer board(s), converts these to digital samples and transmits the samples to the processor board via the serial data bus. On the input board the analogue signals are passed through an anti-alias filter before being multiplexed into a single analogue to digital converter chip. The A - D converter provides 16-bit resolution and a serial data stream output. The digital input signals are opto isolated on this board to prevent excessive voltages on these inputs causing damage to the relay's internal circuitry.

<

<

2671 /)

8

8

2

67=6

*

/1

+, ,,

-

">,$

%

+%

%%

-- -

)

%

)

%

)

%

)

%

:

:

:

:

+

!

56!.8

FIGURE 6: MAIN INPUT BOARD

The signal multiplexing arrangement provides for 16 analogue channels to be sampled. The P74x relay provides 5 current inputs and 4 voltage inputs. 3 spare channels are used to sample 3 different reference voltages for the purpose of continually checking the operation of the multiplexer and the accuracy of the A - D converter. The sample rate is maintained at 24 samples per cycle of the power waveform by a logic control circuit that is driven by the frequency tracking function on the main processor board. The calibration E2PROM holds the calibration coefficients that are used by the processor board to correct for any amplitude or phase errors introduced by the transformers and analogue circuitry.

The other function of the input board is to read the state of the signals present on the digital inputs and present this to the parallel data bus for processing. The input board holds 8 optical isolators for the connection of up to eight digital input signals. The opto-isolators are used with the digital signals for the same reason as the transformers with the analogue signals; to isolate the relay’s electronics from the power system environment. The input board provides some hardware filtering of the digital signals to remove unwanted noise before buffering the signals for reading on the parallel data bus.

Page 316: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-12

MiCOM P741, P742, P743

FD

1.2.5.3 Universal opto isolated logic inputs

The P741, P742 and P743 relays are fitted with universal opto isolated logic inputs that can be programmed for the nominal battery voltage of the circuit of which they are a part. i.e. thereby allowing different voltages for different circuits e.g. signalling, tripping. They nominally provide a Logic 1 or "ON" value for Voltages 80% of the set voltage and a Logic 0 or "OFF" value for the voltages 60% of the set voltage. This lower value eliminates fleeting pickups that may occur during a battery earth fault, when stray capacitance may present up to 50% of battery voltage across an input. Each input has filtering of 7ms. This renders the input immune to induced noise on the wiring: although this method is secure it can be slow.

In the Opto Config. menu the nominal battery voltage can be selected for all opto inputs by selecting one of the five standard ratings in the Global Nominal V settings. If Custom is selected then each opto input can individually be set to a nominal voltage value.

Setting Range Menu Text Default Setting

Min. Max. Step Size

OPTO CONFIG

Global Nominal V 24-27 24 - 27, 30 - 34, 48 - 54, 110 - 125, 220 - 250, Custom

Opto Input x 24-27 24 - 27, 30 - 34, 48 - 54, 110 - 125, 220 - 250

1.2.6 Power supply module (including output relays)

The power supply module contains two PCBs, one for the power supply unit itself and the other for the output relays (P742 and P743). The power supply board also contains the input and output hardware for the rear communication port which provides an EIA(RS)485 communication interface.

1.2.6.1 Power supply board (including EIA(RS)485 communication interface)

One of three different configurations of the power supply board can be fitted to the relay. This will be specified at the time of order and depends on the nature of the supply voltage that will be connected to the relay. The three options are shown in table 1 below:

Nominal dc Range Nominal ac Range

24/54 V DC only

48/125 V 30/100 Vrms

110/250 V 100/240 Vrms

Table 1: Power supply options

The outputs from all versions of the power supply module are used to provide isolated power supply rails to all of the other modules within the relay. Three voltage levels are used within the relay, 5.1V for all of the digital circuits, 16V for the analogue electronics, e.g. on the input board, and 22V for driving the output relay coils and for coprocessor and communication boards 3.3V power supply (through on board DC-DC converter).

All power supply voltages including the 0V ground line are distributed around the relay via the 64-way ribbon cables. One further voltage level is provided by the power supply board which is the field voltage of 48V. This is brought out to terminals on the back of the relay so that it can be used to drive the optically isolated digital inputs.

The two other functions provided by the power supply board are the RS485 communications interface and the watchdog contacts for the relay. The RS485 interface is used with the relay’s rear communication port to provide communication using K Bus Courier. The RS485 hardware supports half-duplex communication and provides optical isolation of the serial data being transmitted and received.

All internal communication of data from the power supply board is conducted via the output relay board which is connected to the parallel bus.

Page 317: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-13

FD

The watchdog facility provides two output relay contacts, one normally open and one normally closed that are driven by the processor board. These are provided to give an indication that the relay is in a healthy state.

The power supply board incorporates inrush current limiting. This limits the peak inrush current, during energisation, to approximately 10A.

1.2.6.2 Output relay board

The output relay board holds eight relays, six with normally open contacts and two with changeover contacts. The relays are driven from the 22V power supply line. The relays’ state is written to or read from using the parallel data bus.

1.2.6.3 Auxiliary power supply

In P741 the power supply module contains main power supply and an auxiliary power supply. The auxiliary power supply adds power on 22 V rail for the up to 7 communication boards within the relay.

The three input voltage options are the same as for main supply. The relay board is provided as an alone board.

1.2.6.4 IRIG-B board (in P741)

The IRIG-B board is an order option that can be fitted to provide an accurate timing reference for the relay. This can be used wherever an IRIG-B signal is available. The IRIG-B signal is connected to the board via a BNC connector on the back of the relay. The timing information is used to synchronize the relay’s internal real-time clock to an accuracy of 1ms. The internal clock is then used for the time tagging of the event, fault maintenance and disturbance records.

1.2.7 Ethernet board

The Ethernet board will only be available for IEC 61850 communication variant relays, supports network connections of the following type:

• 100BASE-TX

• 100BASE-FX

For all copper based network connections an RJ45 style connector is supported. 10Mb fibre network connections use an ST style connector while 100Mb connections use the SC style fibre connection.

An extra processor, a Motorola PPC, and memory block is fitted to the Ethernet card that is responsible for running all the network related functions such as TCP/IP/OSI as supplied by VxWorks and by Sisco inc.

In the P741 and P743, a dedicated slot is available to receive the future optional Ethernet board.

1.2.8 Mechanical layout

The case materials of the relay are constructed from pre-finished steel that has a conductive covering of aluminium and zinc. This provides good earthing at all joints giving a low impedance path to earth that is essential for performance in the presence of external noise. The boards and modules use a multi-point earthing strategy to improve the immunity to external noise and minimize the effect of circuit noise. Ground planes are used on boards to reduce impedance paths and spring clips are used to ground the module metalwork.

Heavy duty terminal blocks are used at the rear of the relay for the current and voltage signal connections. Medium duty terminal blocks are used for the digital logic input signals, the output relay contacts, the power supply and the rear communication port. A BNC connector is used for the optional IRIG-B signal. 9-pin and 25-pin female D-connectors are used at the front of the relay for data communication.

Page 318: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-14

MiCOM P741, P742, P743

FD

Inside the relay the PCBs plug into the connector blocks at the rear, and can be removed from the front of the relay only. The connector blocks to the relay’s CT inputs are provided with internal shorting links inside the relay which will automatically short the current transformer circuits before they are broken when the board is removed.

The front panel consists of a membrane keypad with tactile dome keys, an LCD and 12 LEDs mounted on an aluminium backing plate.

1.3 Relay software

The relay software was introduced in the overview of the relay at the start of this manual (P74x/EN FD). The software can be considered to be made up of five sections:

• The real-time operating system

• The system services software

• The communication software

• The platform software

• The protection & control software

This section describes in detail the latter two of these, the platform software and the protection & control software, which between them control the functional behaviour of the relay. The figure below shows the structure of the relay software.

56!+8

!

"#$

%

"

&!$'()*("+",(-

%

% $ #$

#! .%"

% " /

"

# "$

$ #!

FIGURE 7: RELAY SOFTWARE STRUCTURE

Page 319: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-15

FD

1.3.1 Real-time operating system

• Real-time operating system for main board: the real-time operating system is used to schedule the processing of the tasks to ensure that they are processed in the time available and in the desired order of priority. The operating system is also responsible in part for controlling the communication between the software tasks through the use of operating system messages.

• Sequencer for coprocessor and communication boards: the sequencer executed all functions at fixed frequency depending of the priority of the functions. The highest frequency, 2400Hz, is the frequency of sample acquisition, signal processing and trip decision. To start analogue acquisition at the same time on all peripheral units, the sequencers of all peripheral units and central unit are synchronized and control the analogue acquisition interfacing with system services software.

The software is split into tasks; the real-time operating system is used to schedule the processing of the tasks to ensure that they are processed in the time available and in the desired order of priority. The operating system is also responsible in part for controlling the communication between the software tasks through the use of operating system messages.

1.3.2 System services software

As shown in Figure 4, the system services software provides the interface between the relay’s hardware and the higher-level functionality of the platform software and the protection & control software. For example, the system services software provides drivers for items such as the LCD display, the keypad and the remote communication ports, and controls the boot of the processor and downloading of the processor code into SRAM from flash EPROM at power up.

Page 320: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-16

MiCOM P741, P742, P743

FD

1.3.3 Communication software

In accordance with sequencer used in coprocessor board, the communication software sends frames at fixed frequency equal to 2400Hz. Likewise the contents of the frames is independent of the frequency and of the status of the protections. The frames are split in fixed parts according to the priority of each application. For example trip order and current sample are respectively transmitted at 2400Hz and 1200Hz whereas the internal courier communication or date & time are exchange at low frequency.

PERIPHERAL UNIT

Coprocessor board

Saturation detection

algorithm

Signal processing & local confirmation

threshold for busbar protection

Fixed scheme

logic

Local Topology

Local and global

measurements

Main board

Event & fault

recording

Disturbance recorder

of peripheral unit

Overcurrent

protection

Logic of breaker

failure

Programmable

scheme logic

CENTRAL UNIT

Coprocessor &

communications boards

Sum of current for busbar protection

Fixed scheme

logic

Global

topology

Main board

Event & fault

recording

Disturbance recorder

of central unit

Programmable

scheme logic

OpticalFibre

PERIPHERAL UNIT

PERIPHERAL UNIT

PERIPHERAL UNIT

P3705ENa

FIGURE 8: MiCOM P74x SYSTEM OVERVIEW

Page 321: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-17

FD

1.3.4 Platform software

The platform software has three main functions:

• To control the logging of records that are generated by the protection software, including alarms and event, fault, and maintenance records.

• To store and maintain a database of all of the relay’s settings in non-volatile memory.

• To provide the internal interface between the settings database and each of the relay’s user interfaces, i.e. the front panel interface and the front and rear communication ports, using whichever communication protocol has been specified (Courier, MODBUS, IEC 60870-5-103, DNP3.0 or UCA2.0).

1.3.4.1 Record logging

The logging function is provided to store all alarms, events, faults and maintenance records. The records for all of these incidents are logged in battery backed-up SRAM in order to provide a non-volatile log of what has happened. The relay maintains four logs: one each for up to 32 alarms, 512 event records, 5 fault records and 5 maintenance records. The logs are maintained such that the oldest record is overwritten with the newest record. The logging function can be initiated from the protection software or the platform software is responsible for logging of a maintenance record in the event of a relay failure. This includes errors that have been detected by the platform software itself or error that are detected by either the system services or the protection software function. See also the section on supervision and diagnostics later in this document (P74x/EN FD).

1.3.4.2 Settings database

The settings database contains all of the settings and data for the relay, including the protection, disturbance recorder and control & support settings. The settings are maintained in non-volatile memory. The platform software’s management of the settings database includes the responsibility of ensuring that only one user interface modifies the settings of the database at any one time. This feature is employed to avoid conflict between different parts of the software during a setting change. For changes to protection settings and disturbance recorder settings, the platform software operates a ‘scratchpad’ in SRAM memory. This allows a number of setting changes to be applied to the protection elements, disturbance recorder and saved in the database in non-volatile memory. (See also the Introduction to this manual (P74x/EN IT) on the user interface). If a setting change affects the protection & control task, the database advises it of the new values.

1.3.4.3 Database interface

The other function of the platform software is to implement the relay’s internal interface between the database and each of the relay’s user interfaces. The database of settings and measurements must be accessible from all of the relay’s user interfaces to allow read and modify operations. The platform software presents the data in the appropriate format for each user interface.

Page 322: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-18

MiCOM P741, P742, P743

FD

1.3.5 Protection and control software

The protection and control software task is responsible for processing all of the protection elements and measurement functions of the relay. To achieve this it has to communicate with both the system services software and the platform software as well as organize its own operations. The protection software has the highest priority of any of the software tasks in the relay in order to provide the fastest possible protection response. The protection & control software has a supervisor task that controls the start-up of the task and deals with the exchange of messages between the task and the platform software.

1.3.5.1 Overview - protection and control scheduling

The figure 2 shows the parts of Alstom Grid software and their allocation on the different boards of the peripheral and central units.

The P74x relays contained two global protections, busbar protection and circuit breaker failure, and one local function, overcurrent protection. Overcurrent protection is implemented on peripheral unit and is totally independent of the central unit. On the contrary, busbar protection and circuit breaker failure are distributed between central unit and peripheral units. Local functions such as saturation detection algorithm, logic of circuit breaker failure and local confirmation threshold are performed on each peripheral unit. Sum of current, logic of differential protection and circuit breaker failure are processed on central unit.

1.3.5.2 Topology software

Topology algorithm determines dynamically the electric scheme of the substation from the auxiliary contact of circuit breaker and isolators. The results of local topology performed on peripheral unit are sending to central unit which determines global topology of the substation. At the end of process, central unit know the node of current and zone to trip according to the fault location.

1.3.6 Signal processing

The sampling frequency of analogue signal is fixed to 2400Hz apart from the electric network frequency.

To ensure that the frequency is identical on each PU, analogue acquisition is based on interruption signal from communication software. Central unit send frames on optical fibres in diffusion towards all peripheral units. So they received data at the same instant, this reception signal starts the acquisition of analogue signal.

The main signal processing algorithms are:

• Flux calculation and prediction algorithm to detect CT saturation

• Zero sequence supervision

• Detection of signal variation

• Local threshold to block busbar protection on external fault

All this information are transmitted to central unit with the sample of current, they represent signal quality. The sum of current is processed in central unit each 1200Hz but the signal processing is executed at 2400Hz on peripheral unit.

The protection and control calculates the Fourier components for the analogue signals. The Fourier components are calculated using a one-cycle, 48-sample Discrete Fourier Transform (DFT). The DFT is always calculated using the last cycle of samples from the 2-cycle buffer, i.e. the most recent data is used. The DFT used in this way extracts the power frequency fundamental component from the signal and produces the magnitude and phase angle of the fundamental in rectangular component format. The DFT provides an accurate measurement of the fundamental frequency component, and effective filtering of harmonic frequencies and noise.

Page 323: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-19

FD

This performance is achieved in conjunction with the relay-input module which provides hardware anti-alias filtering to attenuate frequencies above the half sample rate. The Fourier components of the input current signals are stored in memory so that they can be accessed by all of the protection elements’ algorithms. The samples from the input module are also used in an unprocessed form by the disturbance recorder for waveform recording and to calculate true rms values of current.

1.3.6.1 Programmable scheme logic

The purpose of the programmable scheme logic (PSL) is to allow the relay user to configure an individual protection scheme to suit their own particular application. This is achieved through the use of programmable logic gates and delay timers.

The input to the PSL is any combination of the status of the digital input signals from the opto-isolators on the input board, the outputs of the protection elements, e.g. protection starts and trips, control inputs, function keys and the outputs of the fixed protection scheme logic. The fixed scheme logic provides the relay’s standard protection schemes. The PSL itself consists of software logic gates and timers. The logic gates can be programmed to perform a range of different logic functions and can accept any number of inputs. The timers are used either to create a programmable delay, and/or to condition the logic outputs, e.g. to create a pulse of fixed duration on the output regardless of the length of the pulse on the input. The outputs of the PSL are the LEDs on the front panel of the relay and the output contacts at the rear.

The execution of the PSL logic is event driven; the logic is processed whenever any of its inputs change, for example as a result of a change in one of the digital input signals or a trip output from a protection element. Also, only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This reduces the amount of processing time that is used by the PSL. The protection and control software updates the logic delay timers and checks for a change in the PSL input signals every time it runs.

This system provides flexibility for the user to create their own scheme logic design. However, it also means that the PSL can be configured into a very complex system, and because of this setting of the PSL is implemented through the PC support package MiCOM S1.

1.3.6.2 Function key interface (P741 and P743)

The ten function keys interface directly into the PSL as digital input signals and are processed based on the PSL’s event driven execution. However, a change of state is only recognized when a key press is executed on average for longer than 200 ms. The time to register a change of state depends on whether the function key press is executed at the start or the end of a protection task cycle, with the additional hardware and software scan time included. A function key press can provide a latched (toggled mode) or output on key press only (normal mode) depending on how it is programmed and can be configured to individual protection scheme requirements. The latched state signal for each function key is written to non-volatile memory and read from non-volatile memory during relay power up thus allowing the function Key state to be reinstated after power-up should relay power be inadvertently lost.

1.3.6.3 Event and fault recording

A change in any digital input signal or protection element output signal causes an event record to be created. When this happens, the protection and control task sends a message to the supervisor task to indicate that an event is available to be processed and writes the event data to a fast buffer in SRAM which is controlled by the supervisor task. When the supervisor task receives either an event or fault record message, it instructs the platform software to create the appropriate log in battery backed-up SRAM. The operation of the record logging to battery backed-up SRAM is slower than the supervisor’s buffer. This means that the protection software is not delayed waiting for the records to be logged by the platform software. However, in the rare case when a large number of records to be logged are created in a short period of time, it is possible that some will be lost if the supervisor’s buffer is full before the platform software is able to create a new log in battery backed-up SRAM. If this occurs then an event is logged to indicate this loss of information.

Page 324: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-20

MiCOM P741, P742, P743

FD

1.3.6.4 Disturbance recorder

The disturbance recorder operates as a separate task from the protection and control task. It can record the waveforms for up to 8 analogue channels and the values of up to 32 digital signals. For peripheral unit the recording time is user selectable up to a maximum of 10 seconds and for central unit the record duration is fixed to 600ms. The disturbance recorder is supplied with data by the protection and control task once per cycle. The disturbance recorder collates the data that it receives into the required length disturbance record. It attempts to limit the demands it places on memory space by saving the analogue data in compressed format whenever possible. This is done by detecting changes in the analogue input signals and compressing the recording of the waveform when it is in a steady-state condition. The disturbance records can be extracted by MiCOM S1 that can also store the data in COMTRADE format, thus allowing the use of other packages to view the recorded data.

1.4 Self testing & diagnostics

The relay includes a number of self-monitoring functions to check the operation of its hardware and software when it is in service. These are included so that if an error or fault occurs within the relay’s hardware or software, the relay is able to detect and report the problem and attempt to resolve it by performing a re-boot. This involves the relay being out of service for a short period of time which is indicated by the ‘Healthy’ LED on the front of the relay being extinguished and the watchdog contact at the rear operating. If the restart fails to resolve the problem, then the relay will take itself permanently out of service. Again this will be indicated by the LED and watchdog contact.

If a problem is detected by the self-monitoring functions, the relay attempts to store a maintenance record in battery backed-up SRAM to allow the nature of the problem to be notified to the user.

The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is performed when the relay is booted-up, e.g. at power-on, and secondly a continuous self-checking operation which checks the operation of the relay’s critical functions whilst it is in service.

1.4.1 Start-up self-testing

The self-testing which is carried out when the relay is started takes a few seconds to complete, during which time the relay’s protection is unavailable. This is signalled by the ‘Healthy’ LED on the front of the relay which will illuminate when the relay has passed all of the tests and entered operation. If the testing detects a problem, the relay will remain out of service until it is manually restored to working order.

The operations that are performed at start-up are as follows:

1.4.1.1 System boot

The integrity of the flash memory is verified using a checksum before the program code and data stored in it is copied into SRAM to be used for execution by the processor. When the copy has been completed the data then held in SRAM is compared to that in the flash to ensure that the two are the same and that no errors have occurred in the transfer of data from flash to SRAM. The entry point of the software code in SRAM is then called which is the relay initialization code.

Page 325: P74x_EN_M_H54

Firmware Design P74x/EN FD/H54 MiCOM P741, P742, P743

(FD) 9-21

FD

1.4.1.2 Initialization software

The initialization process includes the operations of initializing the processor registers and interrupts, starting the watchdog timers (used by the hardware to determine whether the software is still running), starting the real-time operating system and creating and starting the supervisor task. In the course of the initialization process the relay checks:

• The status of the battery

• The integrity of the battery backed-up SRAM that is used to store event, fault and disturbance records

• The voltage level of the field voltage supply which is used to drive the opto-isolated inputs

• The operation of the LCD controller

• The watchdog operation

At the conclusion of the initialization software the supervisor task begins the process of starting the platform software.

1.4.1.3 Platform software initialization & monitoring

In starting the platform software, the relay checks the integrity of the data held in non-volatile memory with a checksum, the operation of the real-time clock, and the IRIG-B board if fitted. The final test that is made concerns the input and output of data; the presence and healthy condition of the input board is checked and the analogue data acquisition system is checked through sampling the reference voltage.

At the successful conclusion of all of these tests the relay is entered into service and the protection started-up.

1.4.2 Continuous self-testing

When the relay is in service, it continually checks the operation of the critical parts of its hardware and software. The checking is carried out by the system services software (see section on relay software earlier in this document (P74x/EN FD)) and the results reported to the platform software. The functions that are checked are as follows:

• The flash containing all program code setting values and language text is verified by a checksum

• The code and constant data held in SRAM is checked against the corresponding data in flash to check for data corruption

• The SRAM containing all data other than the code and constant data is verified with a checksum

• The battery status

• The level of the field voltage

• The integrity of the digital signal I/O data from the opto-isolated inputs and the relay contacts is checked by the data acquisition function every time it is executed. The operation of the analogue data acquisition system is continuously checked by the acquisition function every time it is executed, by means of sampling the reference voltages

• The operation of the IRIG-B board is checked, where it is fitted, by the software that reads the time and date from the board

• The operation of the Ethernet board is checked, where it is fitted, by the software on the main processor card. If the Ethernet board fails to respond an alarm is raised and the card is reset in an attempt to resolve the problem

Page 326: P74x_EN_M_H54

P74x/EN FD/H54 Firmware Design

(FD) 9-22

MiCOM P741, P742, P743

FD

In the unlikely event that one of the checks detects an error within the relay’s subsystems, the platform software is notified and it will attempt to log a maintenance record in battery backed-up SRAM. If the problem is with the battery status or the IRIG-B board, the relay will continue in operation. However, for problems detected in any other area the relay will initiate a shutdown and re-boot. This will result in a period of up to 5 seconds when the protection is unavailable, but the complete restart of the relay including all initializations should clear most problems that could occur. As described above, an integral part of the start-up procedure is a thorough diagnostic self-check. If this detects the same problem that caused the relay to restart, i.e. the restart has not cleared the problem, then the relay will take itself permanently out of service. This is indicated by the ‘Healthy’ LED on the front of the relay, which will extinguish, and the watchdog contact that will operate.

Page 327: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

CM

COMMISSIONING AND MAINTENANCE

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 328: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance

MiCOM P741, P742, P743

Page 329: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-1

CM

CONTENTS

1. INTRODUCTION 3 2. SETTING FAMILIARISATION 4 3. EQUIPMENT REQUIRED FOR COMMISSIONING 5

3.1 Minimum equipment required 5 3.2 Optional equipment 5

4. PRODUCT CHECKS 6

4.1 With the relay de-energised 6 4.1.1 Visual inspection 7 4.1.2 Current transformer shorting contacts 7 4.1.3 Insulation 9 4.1.4 External wiring 9 4.1.5 Watchdog contacts 10 4.1.6 Auxiliary supply 10 4.2 With the relay energised 11 4.2.1 Watchdog contacts 11 4.2.2 Date and time 11 4.2.3 Light Emitting Diodes (LED’s) 12 4.2.4 Field voltage supply 13 4.2.5 Input opto-isolators 13 4.2.6 Output relays 13 4.2.7 Current differential communications 14 4.2.8 Current inputs (P742, P743 only) 14

5. COMMISSIONING TEST MENU 16

5.1 Test mode 16 5.1.1 Test mode for PU 16 5.1.2 Test mode for CU 16 5.2 Busbar Monitoring (only in CU) 17 5.3 Busbar (BB) & Circuit Breaker Fail (CBF) Disable (only in CU) 17

6. SETTING CHECKS 18

6.1 Apply application-specific settings 18 6.2 How to measure the Burden Resistance (RB) 18 6.2.1 RBph / RBN is close to 1 19 6.2.2 RBPh / RBN is close to 3 20

Page 330: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-2

MiCOM P741, P742, P743

CM

6.3 Demonstrate Correct Relay Operation 20 6.3.1 Current Differential Bias Characteristic 20 6.3.2 Phase Overcurrent Protection (P742 and P743) 23 6.3.3 Breaker Failure Protection 25 6.4 Check Application Settings 27

7. END TO END TESTS 28 8. ON-LOAD CHECKS 29 9. FINAL CHECKS 30 10. COMMISSIONING TEST RECORD 31

10.1 Peripheral Units: P742/P743 31

11. SETTING RECORD 37

11.1 Central Unit: P741 37 11.2 Peripheral Units: P742/P743 44

Page 331: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-3

CM

1. INTRODUCTION The MiCOM P74x Busbar Differential Protection is fully numerical in their design, implementing all protection and non-protection functions in software. The relays employ a high degree of self-checking and, in the unlikely event of a failure, will give an alarm. As a result of this, the commissioning tests do not need to be as extensive as with non-numeric electronic or electromechanical relays.

To commission numerical relays, it is only necessary to verify that the hardware is functioning correctly and the application-specific software settings have been applied to the relay (PSL, topology, differential and breaker failure protection linked to the topology/PSL). It is considered unnecessary to test every function of the relay if the settings have been verified by one of the following methods:

− Extracting the settings applied to the relay using appropriate setting software (preferred method) such as MiCOM S1

− Via the operator interface.

Unless previously agreed to the contrary, the customer will be responsible for determining the application-specific settings to be applied to the relay and for testing of any scheme logic applied by external wiring and/or configuration of the relay’s internal programmable scheme logic.

Blank commissioning test and setting records are provided at the end of this chapter for completion as required.

As the relay’s menu language is user-selectable, it is acceptable for the Commissioning Engineer to change it to allow accurate testing as long as the menu is restored to the customer’s preferred language on completion.

To simplify the specifying of menu cell locations in these Commissioning Instructions, they will be given in the form [courier reference: COLUMN HEADING, Cell Text]. For example, the cell for selecting the menu language (first cell under the column heading) is located in the System Data column (column 00) so it would be given as [SYSTEM DATA, Language].

Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label.

Page 332: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-4

MiCOM P741, P742, P743

CM

2. SETTING FAMILIARISATION When commissioning a MiCOM P74x Busbar protection for the first time, sufficient time should be allowed to become familiar with the method by which the settings are applied.

The Introduction (P74x/EN IT) contains a detailed description of the menu structure of P74x relays.

With the secondary front cover in place all keys except the key are accessible. All menu cells can be read. LED’s and alarms can be reset. However, no protection or configuration settings can be changed, or fault and event records cleared.

Removing the secondary front cover allows access to all keys so that settings can be changed, LED’s and alarms reset, and fault and event records cleared. However, menu cells those have access levels higher than the default level will require the appropriate password to be entered before changes can be made.

Alternatively, if a portable PC is available together with suitable setting software (such as MiCOM S1), the menu can be viewed a page at a time to display a full column of data and text. This PC software also allows settings to be entered more easily, saved to a file on a digital medium for future reference or printed to produce a setting record. Refer to the PC software user manual for details. If the software is being used for the first time, allow sufficient time to become familiar with its operation.

Page 333: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-5

CM

3. EQUIPMENT REQUIRED FOR COMMISSIONING 3.1 Minimum equipment required

Overcurrent test set with interval timer

Multimeter with suitable ac current range, and ac and dc voltage ranges of 0 – 440V and 0 – 250V respectively

Continuity tester (if not included in the multimeter)

Optical power meter with sensitivity 0 to –50dBm (to measure the optical signal level)

Note: Modern test equipment may contain many of the above features in one unit.

3.2 Optional equipment

Multi-finger test plug type P992 (if test block type P991 installed) or MMLB (if using MMLG blocks)

An electronic or brushless insulation tester with a dc output not exceeding 500V (for insulation resistance testing when required). This equipment will be required only if the dielectric test has not been done during the manufacturing process.

A portable PC, with appropriate software (this enables the rear communications port to be tested, if this is to be used, and will also save considerable time during commissioning).

A printer (for printing a setting record from the portable PC).

Page 334: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-6

MiCOM P741, P742, P743

CM

4. PRODUCT CHECKS These product checks cover all aspects of the relay which should be checked to ensure that it has not been physically damaged prior to commissioning, is functioning correctly and all input quantity measurements are within the stated tolerances.

If the application-specific settings have been applied to the relay prior to commissioning, it is advisable to make a copy of the settings so as to allow their restoration later. This could be done by:

− Obtaining a setting file on a digital medium from the customer (this requires a portable PC with appropriate setting software for transferring the settings from the PC to the relay).

− Extracting the settings from the relay itself (this again requires a portable PC with appropriate setting software).

− Manually creating a setting record. This could be done using a copy of the setting record located at the end of this chapter to record the settings as the relay’s menu is sequentially stepped through via the front panel user interface.

If password protection is enabled and the customer has changed password 2 that prevents unauthorised changes to some of the settings, either the revised password 2 should be provided, or the customer should restore the original password prior to commencement of testing.

Note: In the event that the password has been lost, a recovery password can be obtained from Alstom Grid by quoting the serial number of the relay. The recovery password is unique to that relay and is unlikely to work on any other relay.

4.1 With the relay de-energised

The following group of tests should be carried out without the auxiliary supply being applied to the relay and with the trip circuit isolated.

The current and voltage transformer connections must be isolated from the relay for these checks. If a P991 test block is provided, the required isolation can easily be achieved by inserting test plug type P992 which effectively open circuits all wiring routed through the test block, except CT circuits which are automatically short circuited.

Before inserting the test plug, reference should be made to the scheme (wiring) diagram to ensure that this will not potentially cause damage or a safety hazard. CTs must be suitably short circuited on the MMLB test plug before inserting this into the MMLG test block, otherwise there is a danger of fatal electric shock and damage to the equipment. This is not required if using a MiCOM P991 test block and MiCOM P992 test plug, since CTs are automatically safety short circuited.

BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY SECTION/SAFETY GUIDE SFTY/4LM/C11 OR LATER ISSUE, THE TECHNICAL DATA SECTION AND THE RATINGS ON THE EQUIPMENT RATING LABEL.

If a test block is not provided, the voltage transformer supply to the relay should be isolated by means of the panel links or connecting blocks. The line current transformers should be short-circuited and disconnected from the relay terminals. Where means of isolating the auxiliary supply and trip circuit (e.g. isolation links, fuses, MCB, etc.) are provided, these should be used. If this is not possible, the wiring to these circuits will have to be disconnected and the exposed ends suitably terminated to prevent them from being a safety hazard.

Page 335: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-7

CM

4.1.1 Visual inspection

Carefully examine the relay to see that no physical damage has occurred since installation.

The rating information given under the top access cover on the front of the relay should be checked to ensure it is correct for the particular installation.

Ensure that the case earthing connections, bottom left-hand corner at the rear of the relay case, are used to connect the relay to a local earth bar using an adequate conductor.

4.1.2 Current transformer shorting contacts

If required, the current transformer shorting contacts can be checked to ensure that they close when the heavy duty terminal block (block reference B for P742 and A for P743 in Figure 1 and Figure 2) is disconnected from the current input PCB.

COPROCESSOR BOARD(Connexion to CU via optical fibre)

COPROCESSOR BOARD(Connexion to CU via optical fibre)

POWER SUPPLYPOWER SUPPLY

ANALOG INPUT MODULEANALOG INPUT MODULE

16 LOGICAL INPUTS16 LOGICAL INPUTS

8 LOGICAL OUTPUTS8 LOGICAL OUTPUTS

16 17 2418

13 14

10 11

7 8

23

22

15

12

219

4 5

1 2

A

20

19

6

3

B C D

2

EF

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

P3710ENa

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

18

17

15

12

13

11

16

14

9

7

5

10

8

3

1

6

4

22 2

CH1

TX

RX

TX

CH2 RX

FIGURE 1: REAR TERMINAL BLOCKS ON P742

Page 336: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-8

MiCOM P741, P742, P743

CM

16 17 18 24

13 14

10 11

7 8

15 23

12 22

9 21

A

4 5

1 2

6 20

3 19

B C D E F G

POWER SUPPLYANALOG INPUT

24 LOGICAL INPUTS 16 LOGICAL OUTPUTS

J

P3711ENb

COPROCESSOR BOARD(connexion to CU via optic fibre)

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

18

17

15

13

11

16

14

12

9

7

5

10

8

3

1

6

4

2

CH1

TX

RX

TX

CH2 RX

H

TX

ACTIVITY

LINK

RX

SK6

00.0

2.84

.9F.

FF.

9000

.02.

84.9

F.F

F.90

20

14

80

98

VxW

ork

sR

Win

dR

ive

rR

OPTIONAL BOARD

FIGURE 2: REAR TERMINAL BLOCKS ON P743

The heavy duty terminal block is fastened to the rear panel using four crosshead screws. These are located top and bottom between the first and second, and third and fourth, columns of terminals (see Figure 2).

Note: The use of a magnetic bladed screwdriver is recommended to minimise the risk of the screws being left in the terminal block or lost.

Pull the terminal block away from the rear of the case and check with a continuity tester that all the shorting switches being used are closed. Table 1 shows the terminals between which shorting contacts are fitted.

Current input Shorting contact between terminals

P742 P743

1A – common – 5A 1A – common – 5A

ΙA B3 – B2 – B1 A3 – A2 – A1

ΙB B6 – B5 – B4 A6 – A5 – A4

ΙC B9 – B8 – B7 A9 – A8 – A7

ΙN B12 – B11 – B10 A12 – A11 – A10

TABLE 1: CURRENT TRANSFORMER SHORTING CONTACT LOCATIONS.

Page 337: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-9

CM

P0299ENa

FIGURE 3: LOCATION OF SECURING SCREWS FOR HEAVY DUTY TERMINAL BLOCKS

4.1.3 Insulation

Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation.

Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester at a dc voltage not exceeding 500V. Terminals of the same circuits should be temporarily connected together.

The main groups of relay terminals are:

a) Current transformer circuits

b) Auxiliary voltage supply.

c) Field voltage output and opto-isolated control inputs.

d) Relay contacts.

e) Case earth.

The insulation resistance should be greater than 100MΩ at 500V.

On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the relay.

4.1.4 External wiring

Check that the external wiring is correct to the relevant relay diagram or scheme diagram. The relay diagram number appears on the rating label under the top access cover on the front of the relay. The corresponding connection diagram will have been supplied with the Alstom Grid order acknowledgement for the relay.

If a P991 test block is provided, the connections should be checked against the scheme (wiring) diagram. It is recommended that the supply connections are to the live side of the test block [coloured orange with the odd numbered terminals (1, 3, 5, 7 etc.). The auxiliary supply is normally routed via terminals 13 (supply positive) and 15 (supply negative), with terminals 14 and 16 connected to the relay’s positive and negative auxiliary supply terminals respectively. However, check the wiring against the schematic diagram for the installation to ensure compliance with the customer’s normal practice.

Page 338: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-10

MiCOM P741, P742, P743

CM

4.1.5 Watchdog contacts

Using a continuity tester, check that the watchdog contacts are in the states given in Table 2 for a de-energised relay.

Contact state Terminals

Relay de-energised Relay energised

L11 – L12

E11 – E12

G11 – G12

(P741)

(P742)

(P743)

Closed Open

L13 – L14

E13 – E14

G13 – G14

(P741)

(P742)

(P743)

Open Closed

TABLE 2: WATCHDOG CONTACT STATUS

4.1.6 Auxiliary supply

The P74x relay can be operated from either a dc only or an ac/dc auxiliary supply depending on the relay’s nominal supply rating. The incoming voltage must be within the operating range specified in Table 3.

Without energising the relay measure the auxiliary supply to ensure it is within the operating range.

Nominal supply rating DC [AC rms] DC operating range AC operating range

24 – 48V [–] 19 to 65V -

48 – 110V [30 – 100V] 37 to 150V 24 to 110V

110 – 250V [100 – 240V] 87 to 300V 80 to 265V

TABLE 3: OPERATIONAL RANGE OF AUXILIARY SUPPLY VX.

It should be noted that the P74x relay range can withstand an ac ripple of up to 12% of the upper rated voltage on the dc auxiliary supply.

Do not energise the relay or interface unit using the battery charger with the battery disconnected as this can irreparably damage the relay’s power supply circuitry.

Energise the relay only if the auxiliary supply is within the specified operating ranges. If a test block is provided, it may be necessary to link across the front of the test plug to connect the auxiliary supply to the relay.

Page 339: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-11

CM

4.2 With the relay energised

The following group of tests verifies that the relay hardware and software is functioning correctly and should be carried out with the auxiliary supply applied to the relay.

The current and voltage transformer connections must remain isolated from the relay for these checks. The trip circuit should also remain isolated to prevent accidental operation of the associated circuit breaker.

4.2.1 Watchdog contacts

Using a continuity tester, check the watchdog contacts are in the states given in Table 2 for an energised relay.

4.2.2 Date and time

Before setting the date and time, ensure that the factory-fitted battery isolation strip, that prevents battery drain during transportation and storage, has been removed. With the lower access cover open, presence of the battery isolation strip can be checked by a red tab protruding from the positive side of the battery compartment. Whilst lightly pressing the battery, to prevent it from falling out of the battery compartment, pull the red tab to remove the isolation strip.

The date and time should now be set to the correct values. The method of setting will depend on whether accuracy is being maintained via the optional Inter-Range Instrumentation Group standard B (IRIG-B) port on the rear of the P741 relay.

4.2.2.1 With an IRIG-B signal for Central Unit (P741) only

If a satellite time clock signal conforming to IRIG-B is provided and the P741 relay has the optional IRIG-B port fitted, the satellite clock equipment should be energised.

To allow the relay’s time and date to be maintained from an external IRIG-B source cell [DATE and TIME, IRIG-B Sync] must be set to ‘Enabled’.

Ensure the relay is receiving the IRIG-B signal by checking that cell [DATE and TIME, IRIG-B Status] reads ‘Active’.

Once the IRIG-B signal is active, adjust the time offset of the universal co-ordinated time (satellite clock time) on the satellite clock equipment so that local time is displayed.

Check the time, date and month are correct in cell [DATE and TIME, Date/Time]. The IRIG-B signal does not contain the current year so it will need to be set manually in this cell.

In the event of the auxiliary supply failing, with a battery fitted in the compartment behind the bottom access cover, the time and date will be maintained. Therefore, when the auxiliary supply is restored, the time and date will be correct and not need to be set again.

To test this, remove the IRIG-B signal, then remove the auxiliary supply from the relay. Leave the relay de-energised for approximately 30 seconds. On re-energisation, the time in cell [DATE and TIME, Date/Time] should be correct.

Reconnect the IRIG-B signal.

The P741 will synchronise all peripheral units (P742/P743) every 10s and during the powering on of the scheme.

Page 340: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-12

MiCOM P741, P742, P743

CM

4.2.2.2 Without an IRIG-B signal for Central Unit (P741) or Peripheral Unit (P742/P743)

If the time and date is not being maintained by an IRIG-B signal, ensure that cell [DATE and TIME, IRIG-B Sync] is set to ‘Disabled’.

Set the date and time to the correct local time and date using cell [DATE and TIME, Date/Time].

In the event of the auxiliary supply failing, with a battery fitted in the compartment behind the bottom access cover, the time and date will be maintained. Therefore when the auxiliary supply is restored the time and date will be correct and not need to be set again.

To test this, remove the auxiliary supply from the relay for approximately 30 seconds. On re-energisation, the time in cell [DATE and TIME, Date/Time] should be correct.

4.2.3 Light Emitting Diodes (LED’s)

On power up the green LED should have illuminated and stayed on indicating that the relay is healthy. The relay has non-volatile memory which remembers the state (on or off) of the alarm, trip and, if configured to latch, user-programmable LED indicators when the relay was last energised from an auxiliary supply. Therefore these indicators may also illuminate when the auxiliary supply is applied.

If any of these LED’s are on then they should be reset before proceeding with further testing. If the LED’s successfully reset (the LED goes out), there is no testing required for that LED because it is known to be operational.

Note: It is likely that alarms related to the communications channels will not reset at this stage.

4.2.3.1 Testing the alarm and out of service LED’s

The alarm and out of service LED’s can be tested using the COMMISSION TESTS menu column. Set cell [COMMISSION TESTS, Test Mode] to ’Out Of Service’ on the P741 or ‘50BF Disabled’ on the P742 / P743. Check that the out of service LED illuminates continuously and the alarm LED flashes.

It is not necessary to return cell [COMMISSION TESTS, Test Mode] to ‘Disabled’ at this stage because the test mode will be required for later tests.

4.2.3.2 Testing the Trip LED

The trip LED can be tested by initiating a manual circuit breaker trip from the relay. However, the trip LED will operate during the setting checks performed later. Therefore no further testing of the trip LED is required at this stage. Please note that the CB control function does not exist in the Central Unit (P741) as only the Peripheral Unit (P742/P743) may trip/close the local circuit breakers.

4.2.3.3 Testing the user-programmable LEDS

To test the user-programmable LED’s set cell [COMMISSION TESTS, Test LED’s] to ‘Apply Test’. Check that all the LED’s of the relay illuminate.

In the P741 and P743:

− The ‘Red LED Status’ cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated when accessing the relay from a remote location, a ‘1’ indicating a particular Red LED is lit.

− The ‘Green LED Status’ cell is an eighteen bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated when accessing the relay from a remote location, a ‘1’ indicating a particular Green LED is lit.

− If a ‘Red LED Status’ cell AND the same ‘Green LED Status’ cell are at ‘1’ the particular LED is lit Orange

− If a ‘Red LED Status’ cell AND the same ‘Green LED Status’ cell are at ‘0’ the particular LED is not lit.

Page 341: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-13

CM

In the P742:

− The ‘LED Status’ cell is an eight bit binary string that indicates which of the user-programmable LEDs on the relay are illuminated when accessing the relay from a remote location, a ‘1’ indicating a particular LED is lit and a ‘0’ not lit.

4.2.4 Field voltage supply

The relay generates a field voltage of nominally 48V dc that can be used to energise the opto-isolated inputs (alternatively the substation battery may be used).

Measure the field voltage across the terminals 7 and 9 on the terminal block given in Table 4. Check that the field voltage is within the range 40V to 60V when no load is connected and that the polarity is correct.

Repeat for terminals 8 and 10.

Terminals Supply rail

P741 P742 P743

+ve L7 & L8 E7 & E8 G7 & G8

–ve L9 & L10 E9 & E10 G9 & G10

TABLE 4: FIELD VOLTAGE TERMINALS

4.2.5 Input opto-isolators

This test checks that all the opto-isolated inputs on the relay are functioning correctly. The P741 relay has 8 opto-isolated inputs while the P742 relay has 16 opto-isolated inputs and P743 relays has 24 opto-isolated inputs.

The opto-isolated inputs should be energised one at a time, see external connection diagrams (P74x/EN CO) for terminal numbers. Ensuring correct polarity, connect the field supply voltage to the appropriate terminals for the input being tested.

Note: The opto-isolated inputs may be energised from an external dc auxiliary supply (e.g. the station battery) in some installations. Check that this is not the case before connecting the field voltage otherwise damage to the relay may result.

The status of each opto-isolated input can be viewed using either cell [SYSTEM DATA, Opto I/P Status] or [COMMISSION TESTS, Opto I/P Status], a ‘1’ indicating an energised input and a ‘0’ indicating a de-energised input. When each opto-isolated input is energised one of the characters on the bottom line of the display will change to indicate the new state of the inputs.

4.2.6 Output relays

This test checks that all the output relays are functioning correctly. The P741 and P742 relays have 8 output relays while P743 relay has 16 output relays.

See external Connection Diagrams Chapter (P74x/EN CO) for terminal numbers.

Ensure that the relay is still in test mode by viewing cell [COMMISSION TESTS, Test Mode] to ensure that it is set to ‘Blocked’.

The output relays should be energised one at a time. To select output relay 1 for testing, set cell [COMMISSION TESTS, Test Pattern] as appropriate.

Connect a continuity tester across the terminals corresponding to output relay 1 as given in external connection diagram (P74x/EN CO).

To operate the output relay set cell COMMISSION TESTS, Contact Test] to ‘Apply Test’. Operation will be confirmed by the continuity tester operating for a normally open contact and ceasing to operate for a normally closed contact. Measure the resistance of the contacts in the closed state.

Page 342: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-14

MiCOM P741, P742, P743

CM

Reset the output relay by setting cell [COMMISSION TESTS, Contact Test] to ‘Remove Test’.

Note: It should be ensured that thermal ratings of anything connected to the output relays during the contact test procedure is not exceeded by the associated output relay being operated for too long. It is therefore advised that the time between application and removal of contact test is kept to the minimum.

Repeat the test for relays 2 to 8 for P741 and P742 relays, 2 to 16 for P743 relay.

Return the relay to service by setting cell [COMMISSION TESTS, Test Mode] to ‘Disabled’.

4.2.7 Current differential communications

This test verifies that the P742 or P743 relay’s fibre optic communications ports used for communications to the P741 Central Unit, are operating correctly.

1 TO 7 COMMUNICATION BOARDS

OPTIONAL BOARD

CO-PROCESSOR BOARD

POWER SUPPLY MODULE

P3712ENc

LOGICAL OUTPUT CONTACT BOARD

LOGICAL INPUT CONTACT BOARD

A GB C D E F HJ K

TX

RX

SK6

LINK

ACTIVITY

00.0

2.84

.9F.

FF.

9000

.02.

84.9

F.F

F.90

R

20148098

xWorks

IRIG-B12x

WindRiverRRXCH1

RXCH2

TX

L

TX

M N

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

15

13

17

16

18

12

14

5

7

9

11

8

10

6

4

1

3

2

FIGURE 4: P741 REAR TERMINAL BLOCKS AND COMMUNICATION PORTS

When connecting or disconnecting optical fibres care should be taken not to look directly into the transmit port or end of the optical fibre.

From central unit, the cell [PU CONF & STATUS, PU connected] displayed the list of peripheral units connected to the central unit.

From peripheral unit, it is possible to check the communication with the central unit by disconnecting the optical fibre, an alarm “Fibre Com Error” should appear.

4.2.8 Current inputs (P742, P743 only)

This test verifies that the accuracy of current measurement is within the acceptable tolerances.

All relays will leave the factory set for operation at a system frequency of 50Hz. If operation at 60Hz is required then this must be set in cell [SYSTEM DATA, Frequency].

Apply current equal to the line current transformer secondary winding rating to each current transformer input of the corresponding rating in turn, see Table 1 or external connection diagram (P74x/EN CO) for appropriate terminal numbers, checking its magnitude using a multimeter. The corresponding reading can then be checked in the relay’s MEASUREMENTS 1 column and value displayed recorded.

Page 343: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-15

CM

The measured current values displayed on the relay LCD or a portable PC connected to the front communication port will either be in primary or secondary Amperes. If cell [MEASURE’T SETUP, Local Values] is set to ‘Primary’, the values displayed should be equal to the applied current multiplied by the corresponding current transformer ratio set in the ‘CT and VT RATIOS’ menu column (see Table 5). If cell [MEASURE’T SETUP, Local Values] is set to ‘Secondary’, the value displayed should be equal to the applied current.

The measurement accuracy of the relay is ±5%. However, an additional allowance must be made for the accuracy of the test equipment being used.

Cell in MEASUREMENTS 1 column (02)

Corresponding CT Ratio

(in ‘CT and VT RATIOS‘ column(0A) of menu)

[IA Magnitude] [IB Magnitude] [IC Magnitude] [IN Magnitude]

[Phase CT Primary]__ [Phase CT Secondary]

TABLE 5: CT RATIO SETTINGS

Page 344: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-16

MiCOM P741, P742, P743

CM

5. COMMISSIONING TEST MENU

5.1 Test mode

5.1.1 Test mode for PU

This cell is used to allow secondary injection testing to be performed on the relay, without operation of the trip relays, or commissioning of other relays in the same bay as the PU, without mal-operation of the breaker failure protection. It also enables the user to directly test the output contacts and the effect of plant position via the application of controlled tests signals .

Two test modes are available:

− In the ‘CB Failure Protection (50BF) disabled’ mode, all tripping information from external relay are not taken into account. The topology algorithm forwards the feeder positions to the central unit as normal. As the peripheral unit continues to monitor the analogue values the central unit will maintain a balanced condition with the remainder of the system still in normal operation. However, the CB failure backtrip information will not be sent to the Central Unit. The local protections (Dead Zone, Overcurrent, Earth Fault) are still enabled and the PU is able to retrip the breaker. However, the Peripheral Unit is able to react to a fault condition by creating a CB fail condition and back tripping the zone(s) if the CU sends a trip order (87BB or 50BF backtrip), to clear a genuine fault).

− In the ‘Overhaul’ mode, the feeder is totally disconnected from the system because all the isolators are open but all information is passed back to the central unit for inclusion in zone calculations and hence the protection scheme. Hence the central unit can keep the zone elements in service as the contribution of this feeder will be zero. (The CT is still used by the Check Zone element)

Whilst in this mode the peripheral unit can be tested locally for example secondary injections tests can be carried out.(The system is stable because during the current injection there is a differential current in the CZ but not in the Zone)

When a test mode is select, the relay is out of service causing an alarm condition to be recorded and the yellow ‘Out of Service’ LED to illuminate. Once testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to service.

5.1.2 Test mode for CU

This cell is used to allow commissioning of busbar and general breaker failure protection. It also enables a facility to directly test the output contacts by applying menu controlled tests signals. During the test mode, opto inputs and outputs contacts remain in last known state before the test mode is selected.

To select test mode this cell should be set to ‘Enabled’ which takes the relay out of service causing an alarm condition to be recorded and the yellow ‘Out of Service’ LED to illuminate. Once testing is complete the cell must be set back to ‘Disabled’ to restore the relay back to service.

WHEN THE ‘TEST MODE’ CELL IS SET TO ‘ENABLED’, THE RELAY SCHEME LOGIC DOES NOT DRIVE THE OUTPUT RELAYS AND HENCE THE CU WILL NOT TRIP THE ASSOCIATED CIRCUIT BREAKER IF A BUSBAR FAULT OCCURS (COMMISSIONING MODE 1 AND 2).

HOWEVER, THE COMMUNICATIONS CHANNELS WITH REMOTE RELAYS REMAIN ACTIVE, WHICH, IF SUITABLE PRECAUTIONS ARE NOT TAKEN, COULD LEAD TO THE REMOTE ENDS TRIPPING WHEN CURRENT TRANSFORMERS ARE ISOLATED OR INJECTION TESTS ARE PERFORMED.

Page 345: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-17

CM

5.2 Busbar Monitoring (only in CU)

The ‘BB monitoring’ cell is used to select the status of each zone. This cell has a binary string with one bit per zone which can be set to ‘1’ to disable busbar protection and ‘0’ to keep the zone in operating mode. When a zone is set to ‘1’, the current sum calculation remains active for monitoring but a trip order cannot be generated by the busbar protection, only from the breaker failure protection. Zones can be in busbar monitoring when others zones remain active.

5.3 Busbar (BB) & Circuit Breaker Fail (CBF) Disable (only in CU)

The ‘BB & CBF disable’ cell is used to select the status of each zone. This cell has a binary string with one bit per zone which can be set to ‘1’ to disable busbar & breaker failure protection and ‘0’ to maintain the zone in operating mode. When a zone is set to ‘1’, the current sum calculation remains active for monitoring but trip orders cannot be sent by either the busbar protection or the breaker failure protection. Zones can be in ' BB & CBF disable ' when others zones remain active.

Page 346: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-18

MiCOM P741, P742, P743

CM

6. SETTING CHECKS The setting checks ensure that all of the application-specific relay settings (i.e. both the relay’s function and programmable scheme logic settings), for the particular installation, have been correctly applied to the relay.

Note: The trip circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker.

6.1 Apply application-specific settings

There are two methods of applying the settings to the relay:

− Transferring them from a pre-prepared setting file to the relay using a portable PC running the appropriate software via the relay’s front EIA(RS)232 port, located under the bottom access cover. This method is preferred for transferring function settings as it is much faster and there is less margin for error. If the programmable scheme logic other than the default settings with which the relay is supplied is to be used then this is the only way of changing the settings. If a setting file has been created for the particular application and provided on a digital medium, this will further reduce the commissioning time and should always be the case where application-specific programmable scheme logic is to be applied to the relay.

− Enter them manually via the relay’s operator interface. This method is not suitable for changing the programmable scheme logic.

Note: It is essential that where the installation needs application-specific Programmable Scheme Logic, that the appropriate .psl file is downloaded (sent) to the relay, for each and every setting group that will be used. If the user fails to download the required .psl file to any setting group that may be brought into service, then factory default PSL will still be resident. This may have severe operational and safety consequences.

6.2 How to measure the Burden Resistance (RB)

P3747ENb

V

A

A

B

C

N

CTA

CTB

CTC

Short-circuit of the secondary

winding of the current transformer

(HV site)

P992 or MMLG

PU

IA

IB

IC

IN

Insertion of the test block to open current circuit

FIGURE 5: WIRING

Page 347: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-19

CM

1. Short-circuit the secondary winding of the HV current transformer (see above)

2. Open the wiring by inserting a test block

3. Connect the current testing circuit of the test block (phase + neutral).

4. Inject a current (1A recommended) and measure the voltage at the resistive circuit terminals.

5. An Excel tool is available in order to help calculate the values below accurately.

6. Calculate the load resistance RB per phase using the following equation:

RB = Umeasured / Iinjected

Repeat the above operation for each resistive circuit:

RAN between loads A and N

RBN between loads B and N

RCN between loads C and N

RAB between loads A et B

6.2.1 RBph / RBN is close to 1

P3900FRa

TCA

TC B

TCC

PU

IA

I B

I C

IN

RBA = (RAB + RAN - RBN) / 2

RBN = RAN - RBA

RBB = RAB - RBA

RBC = RCN – RBN

Page 348: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-20

MiCOM P741, P742, P743

CM

6.2.2 RBPh / RBN is close to 3

P3901ENa

CTA

CTB

CTC

PU

IA

IB

IC

IN

RBA = RAN / 2

RBB = RBN / 2

RBC = RCN / 2

RBN = (RBA + RBB + RBC) / 9

The highest of the 3 phase values must be multiplied by 1.25 (25% increase at a 75°C temperature) and set in cell [CT/TT Ratios, RB in ohms].

The highest of the 3 phase values (RBA, RBB, RBC) should be divided by the neutral resistance, RBN, and set in cell [CT/TT Ratios, RBPh / RBN].

Note : The use of the Excel spreadsheet tool called “LeadBurdenR” is strongly recommended to calculate these values.

6.3 Demonstrate Correct Relay Operation

The purpose of these tests is as follows:

− To determine that the primary protection function of the relay, current differential, can trip according to the correct application settings.

− To verify correct setting of any backup phase overcurrent protection.

− To verify correct assignment of the inputs, relays and trip contacts, by monitoring the response to a selection of fault injections.

6.3.1 Current Differential Bias Characteristic

To avoid spurious operation of any Overcurrent, earth fault or breaker fail elements, these should be disabled for the duration of the differential element tests. This is done in the relay’s CONFIGURATION column. Ensure that cells, [Overcurrent Prot], [Earth Fault Prot] and [CB Fail & I<] are all set to “Disabled”. Make a note of which elements need to be re-enabled after testing.

Page 349: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-21

CM

6.3.1.1 Connect the test circuit

The following tests require an injection test set, able to feed the relays with one or two currents variable in phase and magnitude.

If only one current is available:

As shown in figure 5bis, this method will be used for a distributed solution when only one peripheral unit is available.

AP741

Central

Unit

P742/3

Peripheral

Unit 1

FO Test

Box

I2

P3749ENa

FIGURE 6: CONNECTION FOR BIAS CHARACTERISTIC TESTING

i bias

I = I =diff 2A I

i (t)diff

Slope kCZ

P3750ENc

45°

A

I = I = I =bias diff 2x I

I = I =bias 2A I0

I = I =diff 2B IB Slo

pek2

I = I =bias 2B I

Injection

An increasing current I2 is injected into a phase (and neutral) of the PU1 which is used as differential and bias current.

Idiff = Ibias = I2

K2 : Zone percentage bias, Characteristic limit: Idiff = ID>2

KCZ : Check Zone percentage bias, Characteristic limit: Idiff = IDCZ>2

In this case, we increase I2 from 0 to A then B point until the differential element operates:

KCZ : Check Zone percentage bias, Characteristic limit: Idiff = IDCZ>2, point A

K2 : Zone percentage bias, Characteristic limit: Idiff = ID>2, point B

When we reach the point A the Central Unit LED 8 and relay 8 will operate and when we reach the point B the differential element will operate.

Note: ID>1 alarm timer will be set to 100s during the test.

Note: This test does not allow checking the slopes but only the thresholds.

Page 350: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-22

MiCOM P741, P742, P743

CM

If 2 currents are available:

This method will be preferred whenever possible.

Note: The 2 PUs can have different CT ratios. This must be taken into account when injecting at the CT secondary side.

A

A

P741

Central

Unit

P742/3

Peripheral

Unit 1

P742/3

Peripheral

Unit 2

FO

FO

Test

Box

I1

I2

P3748ENa

FIGURE 7: CONNECTION FOR BIAS CHARACTERISTIC TESTING – CENTRALISED SOLUTION

I = I + Ibias 21 = constanti bias

i (t)diff

Slope kCZ

P3759ENc

45°

Acz

0

I = =diff II - IA1 A2 Bcz

Slope

k2

Injections

Bz

Az

I = =diff II - IA1 A2

Note: The easiest way to test the thresholds is to inject an increasing slope for I1 and a decreasing slope for I2 .The Ibias = I1 + I2 is thus constant and ∆I = Idiff= I2 - I1is increasing.

IMPORTANT: FOR THE CHECK ZONE, THE IBIAS INCLUDES ALL THE SUBSTATION FEEDER CURRENTS.

To test the thresholds:

Ibias is fixed to a lowest value of ID>2/k2 and IDCZ>2/kCZ, the Az and Acz points will thus be ID>2 and IDCZ>2. So Ibias = I1 + I2 = fixed value (Points A)

To test the slopes:

Ibias is fixed to a value greater than ID>2/k2 and IDCZ>2/kCZ the Bz and Bcz points will thus be Ibias x k2 and Ibias x kCZ. So Ibias = I1 + I2 = fixed value (Points B)

When we reach the point Xcz the Central Unit LED 8 and relay 8 will operate and when we reach the point Xz the differential element will operate.

To calculate the slope k, k = (I1 – I2) / (I1 + I2)

Page 351: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-23

CM

The differential current will increase twice the value ∆I.

Note: ID>1 alarm timer will be set to 100s during the test.

Note : Whenever possible, inject 2 × ID>2. Alternatively, the minimum current must be higher than 1.7 × ID>2 at 60Hz and I.42 × ID>2 at 50Hz in order to ensure a 15ms tripping time

6.3.1.2 Slopes and thresholds

If a LED has been assigned in central or/and peripheral units to display the trip information, these may be used to indicate correct operation. If not, monitor option will need to be used – see the next paragraph.

On P741 go Central Unit GROUP1-->BUSBAR PROTECT and set ID>1 Alarm timer to 100s

On P742/3 go to COMMISSION TESTS column in the menu, scroll down and change cells [Monitor Bit 1] to [BUSBAR_TRIPPING]. Doing so, cell [Test Port Status] will appropriately set or reset the bits that now represent BUSBAR_TRIPPING (with the rightmost bit representing Busbar Trip. From now on you should monitor the indication of [Test Port Status]. Make a note of which elements need to be re-enabled or re-set after testing.

Test of ID>2:

ID>1 Alarm Timer should be set to 100s during testing.

Inject a I2 current smaller than ID>2 and slowly increase I2 until tripping.

Test of the operating time of the differential element:

Inject a I2 current greater than twice ID>2 threshold and measure the operating time of the differential element.

Test of ID>1:

ID>1 Alarm Timer should be set to 100ms.

Inject a I2 current smaller than ID>1 and slowly increase I2 until circuit fault appears (LED Alarm of LED circuitry fault).

Test of ID>1 Alarm Timer:

ID>1 Alarm Timer should be set to 5s.

Inject a I2 current greater than twice the ID>1 threshold and check that the Circuitry Fault Alarm is coming in 5s.

Note: Same tests can be applied for the Differential Sensitive Earth Fault Protection. Note: the Sensitive Differential Earth Fault (SDEF) is 20ms delayed and controlled by a settable threshold Ibias ph> to unblock/block the sensitive element depending of the restrain phase currents.

Important note: Check that if the SDEF is enabled, all the CTs are of the same standard

6.3.2 Phase Overcurrent Protection (P742 and P743)

If the overcurrent protection function is being used, both Ι>1 and I>2 elements should be tested.

To avoid spurious operation of any current differential, earth fault, breaker fail or CT supervision elements, these should be disabled for the duration of the overcurrent tests. This is done in the relay’s CONFIGURATION column. Make a note of which elements need to be re-enabled after testing.

Page 352: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-24

MiCOM P741, P742, P743

CM

6.3.2.1 Connect the test circuit

Determine which output relay has been selected to operate when an Ι>1 trip and an I>2 occur by viewing the relay’s programmable scheme logic.

The programmable scheme logic can only be changed using the appropriate software. If this software has not been available then the default output relay allocations will still be applicable.

If the trip outputs are phase-segregated (i.e. a different output relay allocated for each phase), the relay assigned for tripping on ‘A’ phase faults should be used.

If stage 1 is not mapped directly to an output relay in the programmable scheme logic, output relay 1,2 or 3 could be used for the test as it operates for trip condition (phase A, B and C).

The associated terminal numbers can be found from the external connection diagram (Chapter P74x/EN CO).

Connect the output relay so that its operation will trip the test set and stop the timer.

Connect the current output of the test set to the ‘A’ phase current transformer input of the relay.

Ensure that the timer will start when the current is applied to the relay.

6.3.2.1.1 Perform the test

Ensure that the timer is reset.

Apply a current of twice the setting in cell [GROUP 1 OVERCURRENT, Ι>1 Current Set] to the relay and note the time displayed when the timer stops.

Check that the red trip LED has illuminated.

6.3.2.1.2 Check the operating time

Check that the operating time recorded by the timer is within the range shown in Table 6.

Note: Except for the definite time characteristic, the operating times given in Table 6 are for a time multiplier or time dial setting of 1. Therefore, to obtain the operating time at other time multiplier or time dial settings, the time given in Table 6 must be multiplied by the setting of cell [GROUP 1 OVERCURRENT, Ι>1 TMS] for IEC and UK characteristics or cell [GROUP 1 OVERCURRENT, Time Dial] for IEEE and US characteristics.

In addition, for definite time and inverse characteristics there is an additional delay of up to 0.02 second and 0.08 second respectively that may need to be added to the relay’s acceptable range of operating times.

Page 353: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-25

CM

For all characteristics, allowance must be made for the accuracy of the test equipment being used.

Characteristic Operating time at twice current setting and time multiplier/time dial setting of 1.0

Nominal (seconds) Range (seconds)

DT [: Ι>1 Time Delay] setting Setting ±2%

IEC S Inverse 10.03 9.53 – 10.53

IEC V Inverse 13.50 12.83 – 14.18

IEC E Inverse 26.67 24.67 – 28.67

UK LT Inverse 120.00 114.00 – 126.00

IEEE M Inverse 0.64 0.61 – 0.67

IEEE V Inverse 1.42 1.35 – 1.50

IEEE E Inverse 1.46 1.39 – 1.54

US Inverse 0.46 0.44 – 0.49

US ST Inverse 0.26 0.25 – 0.28

TABLE 6: CHARACTERISTIC OPERATING TIMES FOR Ι>1

Re-perform the tests for the function I>2.

Upon completion of the tests any current differential, overcurrent, earth fault, breaker fail or supervision elements which were disabled for testing purposes must have their original settings restored in the CONFIGURATION column.

6.3.3 Breaker Failure Protection

6.3.3.1 Separate external 50BF protection to the busbar protection

P3751ENa

PU4 PU5

PU3

PU1 PU2

CB Fail

External Fault

For example as shown in the above figure, we simulate a CB fail in feeder 1 (PU1). Therefore, we energise the opto input “External CB Fail” of the PU1 and we check that the central unit issues a tripping order to PU2 and PU3.

Note: If the I>BB or IN>BB are enabled in menu “Busbar Trip Confirm” in Peripheral Unit, the CB fail trip command issued by the Central Unit will be confirmed by a measured phase currents or neutral currents greater than I>BB (Phase) or IN>BB (Earth).

For example: PU2 and PU3 will operate only if the phase currents > I>BB else the local trip will be not confirmed.

The trip of the backup phase overcurrent or earth fault overcurrent protection initiates, as described above, the timers tBF3 and tBF4.

Page 354: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-26

MiCOM P741, P742, P743

CM

6.3.3.2 External initiation of BF Protection

Pro

tective

Rela

ys

P742/3

Peripheral

Unit

Trip A, B, C

P3752ENa

Trip Command

To test the retrip:

As shown in the above figure, we initiate the opto inputs “External Trip A,B,C” and apply a current twice the I< threshold.

Check that the PU issue a retrip order after the settable time tBF3.

To test the backtrip:

Do the same tests as for retrip however apply a faulty current for more than tBF4 and check that the backtrip signal is sent to the CU.

Check that PU2 and PU3 connected to the bus-section 1 are tripped by the CU.

Note: If the I>BB or IN>BB are enabled in menu “Busbar Trip Confirm” in Peripheral Unit, the CB fail trip command issued by the Central Unit will be confirmed by a measured phase currents or neutral currents greater than I>BB (Phase) or IN>BB (Earth).

For example: PU2 and PU3 will operate only if the phase currents > I>BB else the local trip will be not confirmed.

CB unavailable:

P3753ENa

PU4 PU5

PU3

PU1 PU2

Zone 1 Zone 2

Apply an internal fault in zone 2 and energise the opto input of PU3 “CB unavailable” and check that both bus-section 1 tripped simultaneously.

Note: If the input “CB unavailable” is energised, the CB will be not tripped and is normally used only for bus-coupler.

Page 355: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-27

CM

6.3.3.3 Internal initiation Breaker Failure Protection

This Breaker failure Protection can be initiated only by a trip command issued by the Central Unit.

P3753ENa

PU4 PU5

PU3

PU1 PU2

Zone 1 Zone 2

Simulate a busbar fault on the bus-section 2.

Continue to apply fault current in the bus-coupler until the timer tBF1 elapsed.

Check that the retrip signal is given by PU3 and backtrip signal is sent after tBF2.

Check that the CU issued a trip command to both bus-sections (PU1, PU2 PU4 and PU5 should have operated).

6.4 Check Application Settings

The settings applied should be carefully checked against the required application-specific settings to ensure that they are correct, and have not been mistakenly altered during the injection test.

There are two methods of checking the settings:

− Extract the settings from the relay using a portable PC running the appropriate software via the front EIA(RS)232 port, located under the bottom access cover. Compare the settings transferred from the relay with the original written application-specific setting record. (For cases where the customer has only provided a printed copy of the required settings but a portable PC is available).

− Step through the settings using the relay’s operator interface and compare them with the original application-specific setting record.

Unless previously agreed to the contrary, the application-specific programmable scheme logic will not be checked as part of the commissioning tests.

Due to the versatility and possible complexity of the programmable scheme logic, it is beyond the scope of these commissioning instructions to detail suitable test procedures. Therefore, when programmable scheme logic tests must be performed, written tests which will satisfactorily demonstrate the correct operation of the application-specific scheme logic should be devised by the Engineer who created it. These should be provided to the Commissioning Engineer together with the digital medium containing the programmable scheme logic setting file.

Page 356: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-28

MiCOM P741, P742, P743

CM

7. END TO END TESTS Verify communications between Peripheral units (P742 or P743) and Central Unit (P741) - Advisable for distributed scheme.

The following communication checks confirm that the optical power at the transmit and receive ports of the Peripheral Units and the Central Unit are within the recommended operating limits.

Measure and record the optical signal strength received by the Peripheral Unit (P742 or P743) by disconnecting the optical fibre from the Channel 1 receive port and connecting it to an optical power meter. The mean level should be in the range − 16.8 dBm to −25.4dBm. If the mean level is outside of this range check the size and type of fibre being used.

When connecting or disconnecting optical fibres care should be taken not to look directly into the transmit port or end of the optical fibre.

Measure and record the optical power of the Channel 1 transmit port using the optical power meter and length of optical fibre. The mean value should be in the range –16.8dBm to –22.8dBm.

Ensure that all transmit (Tx) and receive (Rx) optical fibres between Peripheral Unit and Central Unit are reconnected, ensuring correct placement.

Reset any alarm indications and check that no further communications failure alarms are raised.

Page 357: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-29

CM

8. ON-LOAD CHECKS The objectives of the on-load checks are to:

− confirm the external wiring to the current inputs is correct.

− ensure the on-load differential current is well below the relay setting.

However, these checks can only be carried out if there are no restrictions preventing the energisation of the plant being protected and the other P74x relays in the group have been commissioned.

Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has been removed to allow testing.

If it has been necessary to disconnect any of the external wiring from the relay in order to perform any of the foregoing tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram.

Confirm current transformer wiring:

Measure the current transformer secondary values for each input using a multimeter connected in series with the corresponding relay current input.

Check that the current transformer polarities are correct.

Ensure the current flowing in the neutral circuit of the current transformers is negligible.

Compare the values of the secondary phase currents with the relay’s measured values, which can be found in the MEASUREMENTS 1 menu column.

Note: Under normal load conditions the earth fault function will measure little, if any, current. It is therefore necessary to simulate a phase to neutral fault. This can be achieved by temporarily disconnecting one or two of the line current transformer connections to the relay and shorting the terminals of these current transformer secondary windings.

If cell [MEASURE’T SETUP, Local Values] is set to ‘Secondary’, the currents displayed on the LCD or a portable PC connected to the front EIA(RS)232 communication port of the relay should be equal to the applied secondary current. The values should be within 5% of the applied secondary currents. However, an additional allowance must be made for the accuracy of the test equipment being used.

If cell [MEASURE’T SETUP, Local Values] is set to ‘Primary’, the currents displayed on the relay should be equal to the applied secondary current multiplied by the corresponding current transformer ratio set in ‘CT & VT RATIOS’ menu column (see Table 5). Again the values should be within 5% of the expected value, plus an additional allowance for the accuracy of the test equipment being used.

Note: If a single dedicated current transformer is used for the earth fault function, it is not possible to check the relay’s measured values.

Page 358: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-30

MiCOM P741, P742, P743

CM

9. FINAL CHECKS The tests are now complete.

Remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the relay in order to perform the wiring verification tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram.

Ensure that the relay has been restored to service by checking that cell [COMMISSION TESTS, Test Mode] is set to ‘Disabled’.

If the menu language has been changed to allow accurate testing it should be restored to the customer’s preferred language.

If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the cover so that the protection is put into service.

Ensure that all event records, fault records, disturbance records, alarms and LED’s have been reset before leaving the relay.

If applicable, replace the secondary front cover on the relay.

Page 359: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-31

CM

10. COMMISSIONING TEST RECORD 10.1 Peripheral Units: P742/P743

Date: Engineer:

Station: Circuit:

System Frequency:

Front Plate Information

Peripheral Unit Type P74_

Model number

Serial number

Rated current In

Auxiliary voltage Vx

Test Equipment Used

This section should be completed to allow future identification of protective devices that have been commissioned using equipment that is later found to be defective or incompatible but may not be detected during the commissioning procedure.

Overcurrent test set Model:

Serial No:

Optical power meter Model:

Serial No:

Insulation tester Model:

Serial No:

Setting software: Type:

Version:

Page 360: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-32

MiCOM P741, P742, P743

CM

*Delete as

appropriate

Have all relevant safety instructions been followed?

Yes/No*

4 Product Checks

4.1 With the relay de-energised

4.1.1 Visual inspection

Relay damaged? Yes/No*

Rating information correct for installation? Yes/No*

Case earth installed? Yes/No*

4.1.2 Current transformer shorting contacts close? Yes/No/Not checked*

4.1.3 Insulation resistance >100MΩ at 500V dc Yes/No/Not tested*

4.1.4 External Wiring

Wiring checked against diagram? Yes/No*

Test block connections checked? Yes/No/na*

4.1.5 Watchdog Contacts (auxiliary supply off)

Terminals 11 and 12 Contact closed? Yes/No*

Contact resistance ____Ω/Not measured*

Terminals 13 and 14 Contact open? Yes/No*

4.1.6 Measured auxiliary supply ______V ac/dc*

4.2 With the relay energised

4.2.1 Watchdog Contacts (auxiliary supply on)

Terminals 11 and 12 Contact open? Yes/No*

Terminals 13 and 14 Contact closed? Yes/No*

Contact resistance ____Ω/Not measured*

4.2.2 Date and time

Clock set to local time? Yes/No*

Time maintained when auxiliary supply removed? Yes/No*

4.2.3 Light emitting diodes

4.2.3.1 Alarm (yellow) LED working? Yes/No*

Out of service (yellow) LED working? Yes/No*

Page 361: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-33

CM

4.2.3.2 Trip (red) LED working? Yes/No*

4.2.3.3 All 8 programmable LED’s working? Yes/No*

4.2.4 Field supply voltage

Value measured between terminals 7 and 9 ______V dc

Value measured between terminals 8 and 10 ______V dc

4.2.5 Input opto-isolators

Opto input 2 working? Yes/No*

Opto input 3 working? Yes/No*

Opto input 4 working? Yes/No*

Opto input 5 working? Yes/No*

Opto input 6 working? Yes/No*

Opto input 7 working? Yes/No*

Opto input 8 working? Yes/No*

For P742 Opto input 9 working? Yes/No/na*

Opto input 10 working? Yes/No/na*

Opto input 11 working? Yes/No/na*

Opto input 12 working? Yes/No/na*

Opto input 13 working? Yes/No/na*

Opto input 14 working? Yes/No/na*

Opto input 15 working? Yes/No/na*

Opto input 16 working? Yes/No/na*

For P743 Opto input 17 working? Yes/No/na*

Opto input 18 working? Yes/No/na*

Opto input 19 working? Yes/No/na*

Opto input 20 working? Yes/No/na*

Opto input 21 working? Yes/No/na*

Opto input 22 working? Yes/No/na*

Opto input 23 working? Yes/No/na*

Opto input 24 working? Yes/No/na*

4.2.6 Output relays

Relay 1 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 2 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Page 362: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-34

MiCOM P741, P742, P743

CM

Relay 3 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 4 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 5 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 6 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 7 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 8 Working? Yes/No/na*

Contact resistance ____Ω/Not measured*

For P743 Relay 9 Working? Yes/No/na*

Contact resistance ____Ω/Not measured*

Relay 10 Working? Yes/No/na*

Contact resistance ____Ω/Not measured*

Relay 11 Working? Yes/No*

Contac t resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 12 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 13 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 14 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 15 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 16 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Page 363: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-35

CM

4.2.9 Current Inputs

Displayed Current Primary/Secondary*

Phase CT Ratio _______ /na*

Input CT Applied value Displayed value

ΙA _______A _______A

ΙB _______A _______A

ΙC _______A _______A

ΙN _______A _______A

5 Setting Checks

5.1 Application-specific function settings applied? Yes/No*

Application-specific programmable scheme logic settings applied?

Yes/No/na*

5.2.1.2 Current Differential lower slope pickup _________A

5.2.1.3 Current Differential upper slope pickup _________A

5.2.5 Protection function timing tested? Yes/No*

Applied current _________A

Expected operating time _________s

Measured operating time _________s

5.4 Application-specific function settings verified? Yes/No/na*

Application-specific programmable scheme logic tested?

Yes/No/na*

Signal strength received by P742/3

Channel 1 ______dBm/na*

Signal strength transmitted by 742/3

Channel 1 ______dBm/na*

Signal Strength within tolerance Yes/No/na*

Optical fibres reconnected?

Channel RX and TX Yes/No*

Alarms reset? Yes/No*

7 On-load Checks

Test wiring removed? Yes/No/na*

Disturbed customer wiring re-checked? Yes/No/na*

Page 364: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-36

MiCOM P741, P742, P743

CM

7.1 Confirm current transformer wiring

7.1.2 Current connections

CT wiring checked? Yes/No/na*

CT polarities correct? Yes/No*

Displayed current Primary/Secondary*

Phase CT ratio _______ /na*

Currents: Applied value Displayed value

ΙA _______A _______A

ΙB _______A _______A

ΙC _______A _______A

ΙN _______A/na* _______A/na*

7.3 Differential current checked? Yes/ No*

8 Final Checks

Test wiring removed? Yes/No/na*

Disturbed customer wiring re-checked? Yes/No/na*

Test mode disabled? Yes/No*

Circuit breaker operations counter reset? Yes/No/na*

Current counters reset? Yes/No/na*

Event records reset? Yes/No*

Fault records reset? Yes/No*

Disturbance records reset? Yes/No*

Alarms reset? Yes/No*

LED’s reset? Yes/No*

Secondary front cover replaced? Yes/No/na*

Commissioning Engineer: Customer Witness:

Date: Date:

Page 365: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-37

CM

11. SETTING RECORD 11.1 Central Unit: P741

Date: Engineer:

Station: Circuit:

System Frequency:

Front Plate Information

Central Unit type: P741

Model Number

Serial Number

Rated Current In

Auxiliary Voltage Vx

*Delete as appropriate

Setting Groups Used

Group 1 Yes/No*

Group 2 Yes/No*

Group 3 Yes/No*

Group 4 Yes/No*

800 SYSTEM DATA

Language English/Francais/Deutsch/Espanol*

Description

Plant Reference

Model Number

Serial Number

Frequency

Comms Level

Relay Address

Software Ref.1

Password Control

Password Level 1

Password Level 2

Page 366: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-38

MiCOM P741, P742, P743

CM

800 PU CONF & STATUS

PU in service 0000 0000 0000 0000 0000 0000

28 1

PU Connected 0000 0000 0000 0000 0000 0000

28 1

PU Topo valid 0000 0000 0000 0000 0000 0000

28 1

800 DATE AND TIME

IRIG-B Sync Disabled/Enabled*

IRIG-B Status Inactive/Active*

Battery Status Dead/Healthy*

Battery Alarm Disabled/Enabled*

800 CONFIGURATION

Setting Group Select via Menu/Select via Optos*

Active Settings Group 1/Group 2/Group 3/Group 4*

Setting Group 1 Disabled/Enabled*

Setting Group 2 Disabled/Enabled*

Setting Group 3 Disabled/Enabled*

Setting Group 4 Disabled/Enabled*

Input Labels Invisible/Visible*

Output Labels Invisible/Visible*

Recorder Control Invisible/Visible*

Disturb Recorder Invisible/Visible*

Measure’t Setup Invisible/Visible*

Commission Tests Invisible/Visible*

Setting Values Primary/Secondary*

0C00 DISTURB RECORDER

Duration

Trigger Position

Trigger Mode Single

Analogue Channel 1

Analogue Channel 2

Analogue Channel 3

Analogue Channel 4

Analogue Channel 5

Page 367: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-39

CM

Analogue Channel 6

Analogue Channel 7

Analogue Channel 8

Digital Input 1

Digital Input 2

Digital Input 3

Digital Input 4

Digital Input 5

Digital Input 6

Digital Input 7

Digital Input 8

Digital Input 9

Digital Input 10

Digital Input 11

Digital Input 12

Digital Input 13

Digital Input 14

Digital Input 15

Digital Input 16

Digital Input 17

Digital Input 18

Digital Input 19

Digital Input 20

Digital Input 21

Digital Input 22

Digital Input 23

Digital Input 24

Digital Input 25

Digital Input 26

Digital Input 27

Digital Input 28

Digital Input 29

Digital Input 30

Digital Input 31

Digital Input 32

Page 368: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-40

MiCOM P741, P742, P743

CM

0D00 MEASURE’T SETUP

Default Display

Local Values Primary/Secondary*

Remote Values Primary/Secondary*

Ibp Base Cur Pri

0E00 COMMUNICATIONS

RP1 Protocol Courier* IEC870-5-103*

MODBUS* DNP3.0*

RP1 Address

RP1 InactivTimer

RP1 Baud Rate 1200* 2400* 4800*

9600* 19200* 38400*

RP1 Parity Odd* Even* None*

RP1 Meas. Period

RP1 PhysicalLink EIA(RS)485* Fiber Optic*

RP1 Time Sync. Disabled* Enabled*

0F00 COMMISSION TESTS

Monitor Bit 1

Monitor Bit 2

Monitor Bit 3

Monitor Bit 4

Monitor Bit 5

Monitor Bit 6

Monitor Bit 7

Monitor Bit 8

Test Mode Disabled/Test Mode/Blocked*

Test Pattern

Page 369: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-41

CM

800 OPTOS SETUP

Global Level

Opto Input 1

Opto Input 2

Opto Input 3

Opto Input 4

Opto Input 5

Opto Input 6

Opto Input 7

Opto Input 8

B00 OUTPUT LABELS

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6

Relay 7

Relay 8

Page 370: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-42

MiCOM P741, P742, P743

CM

GROUP 1 PROTECTION SETTINGS

For Group 2,3 or 4 the first address figure must be respectively: 5 and 6, 7and 8 or 9 and A

800 DIFF BUSBAR PROT

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Phase Slope k2

ID>2 Current

Check Zone Slope kCZ

IDCZ>2 Current

Phase Slope k1

ID>1 Current

ID>1 Alarm Timer

Diff. Earth Fault Enabled/

Disabled

Ibias Ph> Cur.

Earth Slope k2N

IDN>2 Current

Earth Check Zone Slope k2N

IDNCZ>2 Current

Phase Slope kN1

IDN>1 Current

IDN>1 Alarm Tim

4A00 INPUT LABELS

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Opto Input 1

Opto Input 2

Opto Input 3

Opto Input 4

Opto Input 5

Opto Input 6

Opto Input 7

Opto Input 8

Page 371: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-43

CM

4B00 OUTPUT LABELS

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6

Relay 7

Relay 8

Virtual Relay 01

Virtual Relay 02

Virtual Relay 03

Virtual Relay 04

Virtual Relay 05

Virtual Relay 06

Virtual Relay 07

Virtual Relay 08

Virtual Relay 09

Virtual Relay 10

Virtual Relay 11

Virtual Relay 12

Virtual Relay 13

Virtual Relay 14

Virtual Relay 15

Virtual Relay 16

Commissioning Engineer: Customer Witness:

Date: Date:

Page 372: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-44

MiCOM P741, P742, P743

CM

11.2 Peripheral Units: P742/P743

Date: Engineer:

Station: Circuit:

System Frequency:

Front Plate Information

Peripheral Unit type: P742/P743 *

Model Number

Serial Number

Rated Current In

Auxiliary Voltage Vx

*Delete as appropriate

Setting Groups Used

Group 1 Yes/No*

Group 2 Yes/No*

Group 3 Yes/No*

Group 4 Yes/No*

800 SYSTEM DATA

Language English/Francais/Deutsch/Espanol*

Description

Plant Reference

Model Number

Serial Number

Frequency

Comms Level

Relay Address

Software Ref.1

Password Control

Password Level 1

Password Level 2

800 CB CONTROL

Trip Latched

Reset Trip Latch

CB Control By

Man. Close Pulse Time

Man. Trip Pulse Time

Man. Close Delay

Page 373: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-45

CM

801 DATE AND TIME

Battery Status Dead/Healthy*

Battery Alarm Disabled/Enabled*

0900 CONFIGURATION

Setting Group Select via Menu/Select via Optos*

Active Settings Group 1/Group 2/Group 3/Group 4*

Setting Group 1 Disabled/Enabled*

Setting Group 2 Disabled/Enabled*

Setting Group 3 Disabled/Enabled*

Setting Group 4 Disabled/Enabled*

BusBar Option Disabled/Enabled*

BusBar Prot. Disabled/Enabled*

Optos Setup

Dead Zone Prot. Disabled/Enabled*

Backup Phase O/C Disabled/Enabled*

Backup Earth O/C Disabled/Enabled*

CB Fail Disabled/Enabled*

Input Labels Invisible/Visible*

Output Labels Invisible/Visible*

CT & VT Ratios Invisible/Visible*

Recorder Control Invisible/Visible*

Disturb Recorder Invisible/Visible*

Measure’t Setup Invisible/Visible*

Commission Tests Invisible/Visible*

Setting Values Primary/Secondary*

0A00 CT AND VT RATIOS

Phase CT Primary

Phase CT Secondary

Standard Input BS/IEC

Knee Voltage Vk BS

Rated Burden VA IEC

KSCC IEC

RCT Sec'y

Eff. Burden

Page 374: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-46

MiCOM P741, P742, P743

CM

0C00 DISTURB RECORDER

Duration

Trigger Position

Trigger Mode Single/Extended*

Analogue Channel 1

Analogue Channel 2

Analogue Channel 3

Analogue Channel 4

Digital Input 1

Digital Input 2

Digital Input 3

Digital Input 4

Digital Input 5

Digital Input 6

Digital Input 7

Digital Input 8

Digital Input 9

Digital Input 10

Digital Input 11

Digital Input 12

Digital Input 13

Digital Input 14

Digital Input 15

Digital Input 16

P743 Digital Input 17

Digital Input 18

Digital Input 19

Digital Input 20

Digital Input 21

Digital Input 22

Digital Input 23

Digital Input 24

0D00 MEASURE’T SETUP

Default Display

Local Values Primary/Secondary*

Remote Values Primary/Secondary*

Page 375: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-47

CM

0E00 COMMUNICATIONS

RP1 Protocol Courier* IEC870-5-103*

MODBUS* DNP3.0*

RP1 Address

RP1 InactivTimer

RP1 Baud Rate 1200* 2400* 4800*

9600* 19200* 38400*

RP1 Parity Odd* Even* None*

RP1 Meas. Period

RP1 PhysicalLink EIA(RS)485* Fiber Optic*

RP1 Time Sync. Disabled* Enabled*

0F00 COMMISSION TESTS

Monitor Bit 1

Monitor Bit 2

Monitor Bit 3

Monitor Bit 4

Monitor Bit 5

Monitor Bit 6

Monitor Bit 7

Monitor Bit 8

Test Mode Disabled/Test Mode/Blocked*

Test Pattern

Page 376: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-48

MiCOM P741, P742, P743

CM

1100 OPTOS SETUP

Global Level

Opto Input 1

Opto Input 2

Opto Input 3

Opto Input 4

Opto Input 5

Opto Input 6

Opto Input 7

Opto Input 8

Opto Input 9

Opto Input 10

Opto Input 11

Opto Input 12

Opto Input 13

Opto Input 14

Opto Input 15

Opto Input 16

P743 Opto Input 17

Opto Input 18

Opto Input 19

Opto Input 20

Opto Input 21

Opto Input 22

Opto Input 23

Opto Input 24

GROUP 1 PROTECTION SETTINGS

For Group 2,3 or 4 the first address figure must be respectively: 5 and 6, 7and 8 or 9 and A

3000 BB TRIP CONFIRM

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

I>BB Current set

IN>BB Current

Page 377: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-49

CM

3500 BACKUP O/C PHASE

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Ι>1 Function

Ι>1 Current Set

Ι>1 Time Delay

Ι>1 TMS

Ι>1 Time Dial

Ι>1 Reset Char

Ι>1 tRESET

Ι>2 Function

Ι>2 Current Set

Ι>2 Time Delay

3800 O/C EARTH FAULT

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

ΙN>1 Function

ΙN>1 Current Set

ΙN>1 Time Delay

ΙN>1 TMS

ΙN>1 Time Dial

ΙN>1 Reset Char

ΙN>1 tRESET

ΙN>2 Function

ΙN>2 Current Set

ΙN>2 Time Delay

4500 CB FAIL & I<

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Control By

Ι< Current Set

CB Fail Timer 1

CB Fail Timer 2

CB Fail Timer 3

CB Fail Timer 4

Page 378: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-50

MiCOM P741, P742, P743

CM

4600 SUPERVISION

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Error Factor Kce

Alarm delay Tce

4A00 INPUT LABELS

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Opto Input 1

Opto Input 2

Opto Input 3

Opto Input 4

Opto Input 5

Opto Input 6

Opto Input 7

Opto Input 8

Opto Input 9

Opto Input 10

Opto Input 11

Opto Input 12

Opto Input 13

Opto Input 14

Opto Input 15

Opto Input 16

P743 Opto Input 17

Opto Input 18

Opto Input 19

Opto Input 20

Opto Input 21

Opto Input 22

Opto Input 23

Opto Input 24

Page 379: P74x_EN_M_H54

Commissioning and Maintenance P74x/EN CM/H54 MiCOM P741, P742, P743

(CM) 10-51

CM

4B00 OUTPUT LABELS

Group 1 Settings Group 1 Settings

Group 2 Settings

Group 3 Settings

Group 4 Settings

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6

Relay 7

Relay 8

P743 Relay 9

Relay 10

Relay 11

Relay 12

Relay 13

Relay 14

Relay 15

Relay 16

Virtual Relay 01

Virtual Relay 02

Virtual Relay 03

Virtual Relay 04

Virtual Relay 05

Virtual Relay 06

Virtual Relay 07

Virtual Relay 08

Virtual Relay 09

Virtual Relay 10

Virtual Relay 11

Virtual Relay 12

Virtual Relay 13

Virtual Relay 14

Virtual Relay 15

Virtual Relay 16

Commissioning Engineer: Customer Witness:

Date: Date:

Page 380: P74x_EN_M_H54

P74x/EN CM/H54 Commissioning and Maintenance (CM) 10-52

MiCOM P741, P742, P743

CM

BLANK PAGE

Page 381: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

MT

MAINTENANCE

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 382: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance

MiCOM P741, P742, P743

Page 383: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-1

MT

CONTENTS

1. MAINTENANCE 3

1.1 Maintenance period 3

1.2 Maintenance checks 3

1.2.1 Alarms 3

1.2.2 Opto-isolators 3

1.2.3 Output relays 3

1.2.4 Measurement accuracy 3

1.3 Method of repair 4

1.3.1 Replacing the complete relay 4

1.3.2 Replacing a PCB 5

1.4 Recalibration 18

1.4.1 P74x relay 18

1.5 Changing the relay battery 18

1.5.1 Instructions for replacing the battery. 18

1.5.2 Post modification tests 18

1.5.3 Battery disposal 18

1.6 Cleaning 19

Page 384: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-2

MiCOM P741, P742, P743

MT

BLANK PAGE

Page 385: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-3

MT

1. MAINTENANCE

1.1 Maintenance period

It is recommended that products supplied by Alstom Grid Information receive periodic monitoring after installation. As with all products some deterioration with time is inevitable. In view of the critical nature of protective relays and their infrequent operation, it is desirable to confirm that they are operating correctly at regular intervals.

Alstom Grid protective relays are designed for a life in excess of 20 years.

MiCOM P74x current differential relays are self-supervising and so require less maintenance than earlier designs of relay. Most problems will result in an alarm so that remedial action can be taken. However, some periodic tests should be done to ensure that the relay is functioning correctly and the external wiring is intact.

If a Preventative Maintenance Policy exists within the customer’s organisation then the recommended product checks should be included in the regular programme. Maintenance periods will depend on many factors, such as:

• operating environment

• accessibility of the site

• amount of available manpower

• importance of the installation in the power system

• consequences of failure

1.2 Maintenance checks

It is recommended that maintenance checks are performed locally (i.e. at the substation itself).

Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label

1.2.1 Alarms

The alarm status LED should first be checked to identify if any alarm conditions exist. If so, press the read key repeatedly to step through the alarms.

Clear the alarms to extinguish the LED.

1.2.2 Opto-isolators

The opto-isolated inputs can be checked to ensure that the relay responds to their energisation by repeating the commissioning test.

1.2.3 Output relays

The output relays can be checked to ensure that they operate by repeating the commissioning test.

1.2.4 Measurement accuracy

If the power system is energised, the values measured by the relay can be compared with known system values to check that they are in the approximate range that is expected. If they are then the analogue/digital conversion and calculations are being performed correctly by the relay.

Alternatively, the values measured by the relay can be checked against known values injected into the relay via the test block, if fitted, or injected directly into the relay terminals. These tests will prove the calibration accuracy is being maintained.

Page 386: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-4

MiCOM P741, P742, P743

MT

1.3 Method of repair

P741, P742, P743 relays

If the relay should develop a fault whilst in service, depending on the nature of the fault, the watchdog contacts will change state and an alarm condition will be flagged. Due to the extensive use of surface-mount components faulty PCBs should be replaced as it is not possible to perform repairs on damaged circuits. Thus either the complete relay or just the faulty PCB, identified by the in-built diagnostic software, can be replaced. Advice about identifying the faulty PCB can be found in the Problem Analysis.

The preferred method is to replace the complete relay as it ensures that the internal circuitry is protected against electrostatic discharge and physical damage at all times and overcomes the possibility of incompatibility between replacement PCBs. However, it may be difficult to remove an installed relay due to limited access in the back of the cubicle and rigidity of the scheme wiring.

Replacing PCBs can reduce transport costs but requires clean, dry conditions on site and higher skills from the person performing the repair. However, if the repair is not performed by an approved service centre, the warranty will be invalidated.

Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label

1.3.1 Replacing the complete relay

The case and rear terminal blocks have been designed to facilitate removal of the complete relay should replacement or repair become necessary without having to disconnect the scheme wiring.

Before working at the rear of the relay, isolate all voltage and current supplies to the relay.

Note: The MiCOM relay range has integral current transformer shorting switches which will close when the module containing the block is removed.

Disconnect the relay earth, IRIG-B (Central unit only) and fibre optic connections, as appropriate, from the rear of the relay.

Medium duty terminal blockHeavy duty terminal block

P0149ENa

FIGURE 1: LOCATION OF SECURING SCREWS FOR TERMINAL BLOCK

Note: The use of a magnetic bladed screwdriver is recommended to minimise the risk of the screws being left in the terminal block or lost

Page 387: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-5

MT

Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks away from their internal connectors.

Remove the screws used to fasten the relay to the panel, rack, etc. These are the screws with the larger diameter heads that are accessible when the access covers are fitted and open.

If the top and bottom access covers have been removed, do not remove the screws with the smaller diameter heads which are accessible. These screws secure the front panel to the relay.

Withdraw the relay carefully from the panel, rack, etc. because it will be heavy due to the internal transformers.

To reinstall the repaired or replacement relay, follow the above instructions in reverse, ensuring that each terminal block is relocated in the correct position and the case earth, IRIG-B (Central Unit only) and fibre optic connections are replaced. To facilitate easy identification of each terminal block, they are labelled alphabetically with ‘A’ on the left hand side when viewed from the rear.

Once reinstallation is complete the relay should be recommissioned using the instructions in sections 1 to 8 inclusive of this chapter.

1.3.2 Replacing a PCB

If the relay fails to operate correctly refer to the Problem Analysis chapter, to help determine which PCB has become faulty.

To replace any of the relay’s PCBs it is necessary to first remove the front panel.

Before removing the front panel to replace a PCB the auxiliary supply must be removed. It is also strongly recommended that the voltage and current transformer connections and trip circuit are isolated.

Open the top and bottom access covers. With size 60TE/80TE cases the access covers have two hinge-assistance T-pieces which clear the front panel moulding when the access covers are opened by more than 90°, thus allowing their removal.

If fitted, remove the transparent secondary front cover. A description of how to do this is given in the ‘Introduction’.

By applying outward pressure to the middle of the access covers, they can be bowed sufficiently so as to disengage the hinge lug allowing the access cover to be removed. The screws that fasten the front panel to the case are now accessible.

The size 40TE case has four crosshead screws fastening the front panel to the case, one in each corner, in recessed holes. The size 60TE/80TE case has an additional two screws, one midway along each of the top and bottom edges of the front plate. Undo and remove the screws.

Do not remove the screws with the larger diameter heads which are accessible when the access covers are fitted and open. These screws hold the relay in its mounting (panel or cubicle).

When the screws have been removed, the complete front panel can be pulled forward and separated from the metal case.

Caution should be observed at this stage because the front panel is connected to the rest of the relay circuitry by a 64-way ribbon cable.

Additionally, from here on, the internal circuitry of the relay is exposed and not protected against electrostatic discharges, dust ingress, etc. Therefore ESD precautions and clean working conditions should be maintained at all times.

The ribbon cable is fastened to the front panel using an IDC connector; a socket on the cable itself and a plug with locking latches on the front panel. Gently push the two locking latches outwards which will eject the connector socket slightly. Remove the socket from the plug to disconnect the front panel.

Page 388: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-6

MiCOM P741, P742, P743

MT

The PCBs within the relay are now accessible. Figures 8, 9 and 10 show the PCB locations for the Central Unit (P741) in a size 80 TE case, and for Peripheral Units either in a size 40 TE case (P742) or in a size 60 TE case (P743).

Note: The numbers above the case outline identify the guide slot reference for each printed circuit board. Each printed circuit board has a label stating the corresponding guide slot number to ensure correct re-location after removal. To serve as a reminder of the slot numbering there is a label on the rear of the front panel metallic screen.

ENSURE SWITCH POSITIONS ON REF5 ARE POSITIONED AS SHOWN

P3754ENc

SL

OT

3

SL

OT

1

SL

OT

2S

LO

T2

SL

OT

4

SL

OT

6

SL

OT

5

SL

OT

8

SL

OT

9

SL

OT

11

SL

OT

10

SL

OT

12

SL

OT

12

SL

OT

13

SL

OT

14

SL

OT

14

1 1

1

6

ON1

6

ON1

6

ON1

6

ON1

6

ON1

6

ON1

6

ON1

6

ON

REF DESCRIPTION MATERIAL

1 Assy Power Supply ZN0021 *

2 Assy Power Supply 2070583 *

3 Assy Opto Input ZN0017 012

4 Assy Relay Output ZN0019 001

5 Assy Comms 2070273 001

6 Assy IRIG-B ZN0007 *

7 Assy Coprocessor 2070273 003

FIGURE 2: P741 – PCB/MODULE LOCATIONS (VIEWED FROM FRONT)

Page 389: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-7

MT

SLO

T4

ON

6

1

SLO

T1

SLO

T2

SLO

T3

SLO

T5

SLO

T6

0

SER No.

1 1

1 3

6

2 29 23 24or

P3755ENa

REF DESCRIPTION MATERIAL

1 Assy Power Supply ZN0021 *

2 Assy Relay Output ZN0019 001

3 Assy Opto Input ZN0017 012

6 Assy Coprocessor 2070273 003

23 Assy Standard Input Module GN0010 074

24 Input Module (Univ. Inputs only) GN0010 089

29 Assembly Screen Plate GN0058 001

FIGURE 3: P742 – PCB/MODULE LOCATIONS (VIEWED FROM FRONT)

Page 390: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-8

MiCOM P741, P742, P743

MT

P3756ENa

111 1

29

67

29

1 2

23

24

7

6

332

SER No.SER No.

66

6

1 ON

or

SL

OT

2

SL

OT

1

SL

OT

4

SL

OT

3

SL

OT

8

SL

OT

6

SL

OT

7

SL

OT

5

SL

OT

9

SL

OT

10

FIT JUMPERS (REF 64) TO PL2 ON

PCB'S REF 2 AND 3 IN SLOT POSITIONS SHOWN.

40

REF DESCRIPTION MATERIAL

1 Assy Power Supply ZN0021 *

2 Assy Relay Output ZN0019 001

3 Assy Opto Input ZN0017 012

6 Assy Coprocessor 2070273 003

23 Assy Standard Input Module GN0010 074

24 Input Module (Univ. Inputs only) GN0010 089

29 Assembly Screen Plate GN0058 001

FIGURE 4: P743 – PCB/MODULE LOCATIONS (VIEWED FROM FRONT)

The 64-way ribbon cable to the front panel also provides the electrical connections between PCBs with the connections being via IDC connectors.

The slots inside the case to hold the PCBs securely in place each correspond to a rear terminal block. Looking from the front of the relay these terminal blocks are labelled from right to left.

Note: To ensure compatibility, always replace a faulty PCB with one of an identical part number.

Page 391: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-9

MT

1.3.2.1 Replacement of the main processor board

ESD precautions should be taken to avoid damage to the microprocessor based circuits.

The main processor board is located in the front panel, not within the case as with all the other PCBs. Place the front panel with the user interface face-down and remove the six screws from the metallic screen, as shown in Figure 5. Remove the metal plate.

There are two further screws, one each side of the rear of the battery compartment recess, that hold the main processor PCB in position. Remove these screws.

The user interface keypad is connected to the main processor board via a flex-strip ribbon cable. Carefully disconnect the ribbon cable at the PCB-mounted connector as it could easily be damaged by excessive twisting.

The front panel can then be re-assembled with a replacement PCB using the reverse procedure. Ensure that the ribbon cable is reconnected to the main processor board and all eight screws are re-fitted.

P3007ENa

FIGURE 5: FRONT PANEL ASSEMBLY

Refit the front panel using the reverse procedure to that given before. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

After replacement of the main processor board, all the settings required for the application will need to be re-entered. Therefore, it is useful if an electronic copy of the application-specific settings is available on a digital medium. Although this is not essential, it can reduce the time taken to re-enter the settings and hence the time the protection is out of service.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

Page 392: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-10

MiCOM P741, P742, P743

MT

1.3.2.2 Replacement of the IRIG-B board (Central Unit only)

Depending on the model number of the central unit (P741), the IRIG-B board may have connections for IRIG-B signals.

To replace a faulty board, disconnect all IRIG-B connections at the rear of the relay.

The board is secured in the case by two screws accessible from the rear of the relay, one at the top and another at the bottom, as shown in Figure 6. Remove these screws carefully as they are not captive in the rear panel of the relay.

Gently pull the IRIG-B board forward and out of the case.

To help identify that the correct board has been removed, Figure 7 illustrates the layout of the IRIG-B board with IRIG-B (ZN0007 001).

RX

RX

TX

15

13

17

14

16

18

6

8

10

12

9

11

7

CH2

CH1

IRIG-B

RX

TX

TX4

2

3

5

1

L M N

P3757ENa

FIGURE 6: LOCATION OF SECURING SCREWS FOR IRIG-B BOARD

P3009FRa

SERIAL No.

ZN0007 C

FIGURE 7: TYPICAL IRIG-B BOARD

Page 393: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-11

MT

Before fitting the replacement PCB check that the number on the round label adjacent to the front edge of the PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect write the correct slot number on the label.

The replacement PCB should be carefully slotted into the appropriate slot, ensuring that it is pushed fully back on to the rear terminal blocks and the securing screws are re-fitted.

Reconnect IRIG-B connection at the rear of the relay.

Refit the front panel using the reverse procedure to that given in section 1.3.2.1. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

1.3.2.3 Replacement of the input module

The input module comprises of two boards fastened together, the transformer board and the input board.

The module is secured in the case by two screws on its right-hand side, accessible from the front of the relay, as shown in Figure 8. Remove these screws carefully as they are not captive in the front plate of the module.

Input module

Handle

P3010ENa

FIGURE 8: LOCATION OF SECURING SCREWS FOR INPUT MODULE

On the right-hand side of the analogue input module there is a small metal tab which brings out a handle. Grasping this handle firmly, pull the module forward, away from the rear terminal blocks. A reasonable amount of force will be required to achieve this due to the friction between the contacts of two terminal blocks, one medium duty and one heavy duty.

Note: Care should be taken when withdrawing the input module as it will suddenly come loose once the friction of the terminal blocks has been overcome. This is particularly important with unmounted relays as the metal case will need to be held firmly whilst the module is withdrawn.

Remove the module from the case, taking care as it is heavy because it contains all the relay’s input voltage and current transformers.

Before fitting the replacement module check that the number on the round label adjacent to the front edge of the PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect write the correct slot number on the label.

Page 394: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-12

MiCOM P741, P742, P743

MT

The replacement module can be slotted in using the reverse procedure, ensuring that it is pushed fully back on to the rear terminal blocks. To help confirm that the module has been inserted fully there is a V-shaped cut-out in the bottom plate of the case that should be fully visible. Re-fit the securing screws.

Note: The transformer and input boards within the module are calibrated together with the calibration data being stored on the input board. Therefore it is recommended that the complete module is replaced to avoid on-site recalibration having to be performed.

Refit the front panel using the reverse procedure to that given in section. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

1.3.2.4 Replacement of the power supply board

The power supply board is fastened to a relay board to form the power supply module and is located on the extreme left-hand side of all MiCOM differential busbar relays.

Pull the power supply module forward, away from the rear terminal blocks and out of the case. A reasonable amount of force will be required to achieve this due to the friction between the contacts of the two medium duty terminal blocks.

The two boards are held together with push-fit nylon pillars and can be separated by pulling them apart. Care should be taken when separating the boards to avoid damaging the inter-board connectors located near the lower edge of the PCBs towards the front of the power supply module.

The power supply board is the one with two large electrolytic capacitors on it that protrude through the other board that forms the power supply module. To help identify that the correct board has been removed, Figure 9 illustrates the layout of the power supply board for all voltage ratings.

Before re-assembling the module with a replacement PCB check that the number on the round label adjacent to the front edge of the PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect write the correct slot number on the label.

Re-assemble the module with a replacement PCB ensuring the inter-board connectors are firmly pushed together and the four push-fit nylon pillars are securely located in their respective holes in each PCB.

P3011XXa

SERIAL No. ZN0001 D

FIGURE 9: TYPICAL POWER SUPPLY BOARD FOR P742 & P743

Page 395: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-13

MT

2070584 B

P3761ENa

FIGURE 10: ADDITIVE POWER SUPPLY BOARD FOR P741

Slot the power supply module back into the relay case, ensuring that it is pushed fully back on to the rear terminal blocks.

Refit the front panel using the reverse procedure to that given in section. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

Page 396: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-14

MiCOM P741, P742, P743

MT

1.3.2.5 Replacement of the relay board in the power supply module

Remove and replace the relay board in the power supply module as described in above.

The relay board is the one with holes cut in it to allow the transformer and two large electrolytic capacitors of the power supply board to protrude through. To help identify that the correct board has been removed, Figure 11 illustrates the layout of the relay board.

Before re-assembling the module with a replacement relay board check that the number on the round label adjacent to the front edge of the PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect write the correct slot number on the label.

Ensure the setting of the link (located above IDC connector) on the replacement relay board is the same as the one being replaced before replacing the module in the relay case.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

E2

SERIAL No.

ZN0019

F

P3762XXa

FIGURE 11: TYPICAL RELAY BOARD

Page 397: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-15

MT

1.3.2.6 Replacement of the opto and separate relay boards (P741, P742, & P743)

To remove either, gently pull the faulty PCB forward and out of the case.

If the relay board is being replaced, ensure the setting of the link (located above IDC connector) on the replacement relay board is the same as the one being replaced. To help identify that the correct board has been removed, Figure 12 illustrates the layout of the opto board.

Before fitting the replacement PCB check that the number on the round label adjacent to the front edge of the PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect write the correct slot number on the label.

The replacement PCB should be carefully slid into the appropriate slot, ensuring that it is pushed fully back on to the rear terminal blocks.

Refit the front panel using the reverse procedure to that given in section. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

E1

C1

SERIAL No.

1

ZN0017

E

P3760XXa

FIGURE 12: TYPICAL OPTO BOARD

Page 398: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-16

MiCOM P741, P742, P743

MT

1.3.2.7 Replacement of the Coprocessor board

Before replacing a faulty Coprocessor board, disconnect fibre optic cable connections at the rear of the relay.

The board is secured in the case by two screws accessible from the rear of the relay, one at the top and another at the bottom, as shown in Figure 13. Remove these screws carefully as they are not captive in the rear panel of the relay.

Using the small metal tab on the left hand side of the input module rotate handle used for extraction until it is in a horizontal orientation. This is necessary so that the two PCB connectors on the underside of the Coprocessor board PCB do not catch the handle as the PCB is extracted.

Gently pull the faulty Coprocessor board PCB forward and out of the case.

P3763XXa

FIGURE 13: TYPICAL COPROCESSOR BOARD

To help identify that the correct board has been replace, Figure 18 illustrates the layout of the Coprocessor board with dual fibre optic communications channels fitted. The Coprocessor board boards with a single communications channel (used in relays for two ended feeders where dual redundant communications channels are not required) use the same PCB layout but have fewer components fitted.

The replacement PCB should be carefully slid into the appropriate slot, ensuring that it is pushed fully back and the board securing screws are re-fitted.

Refit the fibre optic cable connections, ensuring that they are in the correct locations.

Refit the front panel using the reverse procedure to that given before. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

Page 399: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-17

MT

1.3.2.8 Replacement of the Comms board

Before replacing a faulty Comms board (Communication board between central and peripheral units), disconnect fibre optic cable connections at the rear of the relay.

The board is secured in the case by two screws accessible from the rear of the relay, one at the top and another at the bottom, as shown in Figure 14. Remove these screws carefully as they are not captive in the rear panel of the relay.

Using the small metal tab on the left hand side of the input module rotate handle used for extraction until it is in a horizontal orientation. This is necessary so that the two PCB connectors on the underside of the Comms board PCB do not catch the handle as the PCB is extracted.

Gently pull the faulty Comms board PCB forward and out of the case.

P3764XXa

FIGURE 14: TYPICAL COMMS BOARD

To help identify that the correct board has been removed, Figure 14 illustrates the layout of the Comms board with dual fibre optic communications channels fitted. The Comms board boards with a single communications channel (used in relays for two ended feeders where dual redundant communications channels are not required) use the same PCB layout but have fewer components fitted.

The replacement PCB should be carefully slid into the appropriate slot, ensuring that it is pushed fully back and the board securing screws are re-fitted.

Refit the fibre optic cable connections, ensuring that they are in the correct locations.

Refit the front panel using the reverse procedure to that given before. After refitting and closing the access covers on size 60TE/80TE cases, press at the location of the hinge-assistance T-pieces so that they click back into the front panel moulding.

Once the relay has been reassembled after repair, it should be recommissioned in accordance with the instructions in sections 1 to 8 inclusive of this chapter.

Page 400: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-18

MiCOM P741, P742, P743

MT

1.4 Recalibration

1.4.1 P74x relay

Recalibration is not required when a PCB is replaced unless it happens to be one of the boards in the input module, the replacement of either directly affects the calibration.

Although it is possible to carry out recalibration on site, this requires test equipment with suitable accuracy and a special calibration program to run on a PC. It is therefore recommended that the work is carried out by the manufacturer, or entrusted to an approved service centre.

1.5 Changing the relay battery

Each relay has a battery to maintain status data and the correct time when the auxiliary supply voltage fails. The data maintained includes event, fault and disturbance records and the thermal state at the time of failure.

This battery will periodically need changing, although an alarm will be given as part of the relay’s continuous self-monitoring in the event of a low battery condition.

If the battery-backed facilities are not required to be maintained during an interruption of the auxiliary supply, the steps below can be followed to remove the battery, but do not replace with a new battery.

Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label.

1.5.1 Instructions for replacing the battery.

Open the bottom access cover on the front of the relay.

Gently extract the battery from its socket. If necessary, use a small insulated screwdriver to prize the battery free.

Ensure that the metal terminals in the battery socket are free from corrosion, grease and dust.

The replacement battery should be removed from its packaging and placed into the battery holder, taking care to ensure that the polarity markings on the battery agree with those adjacent to the socket.

Note: Only use a type ½AA Lithium battery with a nominal voltage of 3.6V and safety approvals such as UL (Underwriters Laboratory), CSA (Canadian Standards Association) or VDE (Vereinigung Deutscher Elektrizitätswerke).

Ensure that the battery is securely held in its socket and that the battery terminals are making good contact with the metal terminals of the socket.

Close the bottom access cover.

1.5.2 Post modification tests

To ensure that the replacement battery will maintain the time and status data if the auxiliary supply fails, check cell [0806: DATE and TIME, Battery Status] reads ‘Healthy’.

Additionally, if further confirmation that the replacement battery is installed correctly is required, the commissioning test described in chapter, ‘Date and Time’, can be performed.

1.5.3 Battery disposal

The battery that has been removed should be disposed of in accordance with the disposal procedure for Lithium batteries in the country in which the relay is installed.

Page 401: P74x_EN_M_H54

Maintenance P74x/EN MT/H54 MiCOM P741, P742, P743

(MT) 11-19

MT

1.6 Cleaning

Before cleaning the equipment ensure that all ac and dc supplies, current transformer and voltage transformer connections are isolated to prevent any chance of an electric shock whilst cleaning.

The equipment may be cleaned using a lint-free cloth dampened with clean water. The use of detergents, solvents or abrasive cleaners is not recommended as they may damage the relay’s surface and leave a conductive residue.

Page 402: P74x_EN_M_H54

P74x/EN MT/H54 Maintenance (MT) 11-20

MiCOM P741, P742, P743

MT

BLANK PAGE .

Page 403: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

TS

TROUBLESHOOTING

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 404: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting

MiCOM P741, P742, P743

Page 405: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-1

TS

CONTENTS

1. INTRODUCTION 3 2. INITIAL PROBLEM IDENTIFICATION 4 3. POWER UP ERRORS 5 4. ERROR MESSAGE/CODE ON POWER-UP 6 5. OUT OF SERVICE LED ILLUMINATED ON POWER UP 8 6. ERROR CODE DURING OPERATION 9 7. MAL-OPERATION OF THE RELAY DURING TESTING 20

7.1 Failure of output contacts 20

7.2 Failure of opto-isolated inputs 20

7.3 Incorrect analog signals (P742 or P743) 21

7.4 PSL editor troubleshooting 21

7.4.1 Diagram reconstruction after recover from relay 21

7.4.2 PSL version check 21

8. REPAIR AND MODIFICATION PROCEDURE 22

Page 406: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-2

MiCOM P741, P742, P743

TS

BLANK PAGE

Page 407: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-3

TS

1. INTRODUCTION Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label

The purpose of this section of the service manual is to allow an error condition on the relay to be identified so that appropriate corrective action can be taken.

Should the relay have developed a fault, it should be possible in most cases to identify which relay module requires attention. The Maintenance section (P74x/EN MT), advises on the recommended method of repair where faulty modules need replacing. It is not possible to perform an on-site repair to a faulted module.

In cases where a faulty relay/module is being returned to the manufacturer or one of their approved service centres, completed copy of the Repair/Modification Return Authorization Form located at the end of this section should be included.

Page 408: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-4

MiCOM P741, P742, P743

TS

2. INITIAL PROBLEM IDENTIFICATION Consult the table below to find the description that best matches the problem experienced, then consult the section referenced to perform a more detailed analysis of the problem.

Symptom Refer To

Relay fails to power up Section 4

Relay powers up - but indicates error and halts during power-up sequence Section 5

Relay Powers up but Out of Service LED is illuminated Section 6

Error during normal operation Section 7

Mal-operation of the relay during testing Section 8

Table 1: Problem identification

Page 409: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-5

TS

3. POWER UP ERRORS If the relay does not appear to power up then the following procedure can be used to determine whether the fault is in the external wiring, auxiliary fuse, power supply module of the relay or the relay front panel.

Test Check Action

1

Measure auxiliary voltage on terminals 1 and 2; verify voltage level and polarity against rating the label on front.

Terminal 1 is –dc, 2 is +dc

If auxiliary voltage is present and correct, then proceed to test 2. Otherwise the wiring/fuses in auxiliary supply should be checked.

2

Do LEDs/and LCD backlight illuminate on power-up, also check the N/O watchdog contact for closing.

If they illuminate or the contact closes and no error code is displayed then error is probably in the main processor board (front panel). If they do not illuminate and the contact does not close then proceed to test 3.

3 Check Field voltage output (nominally 48V DC)

If field voltage is not present then the fault is probably in the relay power supply module.

Table 2: Failure of relay to power up

Page 410: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-6

MiCOM P741, P742, P743

TS

4. ERROR MESSAGE/CODE ON POWER-UP During the power-up sequence of the relay self-testing is performed as indicated by the messages displayed on the LCD. If an error is detected by the relay during these self-tests then an error message will be displayed and the power-up sequence will be halted. If the error occurs when the relay application software is executing then a maintenance record will be created and the relay will reboot.

Test Check Action

1

Is an error message or code permanently displayed during power up?

If relay locks up and displays an error code permanently then proceed to test 2. If the relay prompts for input by the user proceed to test 4. If the relay re-boots automatically then proceed to test 5

2

Record displayed error, then remove and re-apply relay auxiliary supply.

Record whether the same error code is displayed when the relay is rebooted. If no error code is displayed then contact the local service centre stating the error code and relay information. If the same code is displayed proceed to test 3.

Error code Identification

Following text messages (in English) will be displayed if a fundamental problem is detected preventing the system from booting:

Bus Fail – address lines

SRAM Fail – data lines

FLASH Fail format error

FLASH Fail checksum

Code Verify Fail

The following hex error codes relate to errors detected in specific relay modules:

These messages indicate that a problem has been detected on the main processor board of the relay (located in the front panel).

0c140005/0c0d0000 Input Module (inc. Opto-isolated inputs)

0c140006/0c0e0000 Output Relay Cards

3

Last 4 digits provide details on the actual error.

Other error codes relate to problems within the main processor board hardware or software. It will be necessary to contact Alstom Grid with details of the problem for a full analysis.

4

Relay displays message for corrupt settings and prompts for restoration of defaults to the affected settings.

The power up tests have detected corrupted relay settings, it is possible to restore defaults to allow the power-up to be completed. It will then be necessary to re-apply the application-specific settings.

Page 411: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-7

TS

Test Check Action

5

Relay resets on completion of power up - record error code displayed

Error 0x0E080000, programmable scheme logic error due to excessive execution time. Restore default settings by performing a power up with ⇐ and ⇒ keys depressed, confirm restoration of defaults at prompt using ↵ key. If relay powers up successfully, check programmable logic for feedback paths.

Other error codes will relate to software errors on the main processor board, contact Alstom Grid.

Table 3: Power-up self-test error

Page 412: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-8

MiCOM P741, P742, P743

TS

5. OUT OF SERVICE LED ILLUMINATED ON POWER UP

Test Check Action

1

Using the relay menu confirm whether the Commission Test/Test Mode setting is Enabled. Otherwise proceed to test 2.

If the setting is Enabled then disable the test mode and, verify that the Out of Service LED is extinguished.

2

Select and view the last maintenance record from the menu (in the View Records).

Check for H/W Verify Fail this indicates a discrepancy between the relay model number and the hardware; examine the “Maint. Data”, this indicates the causes of the failure using bit fields:

Bit Meaning

0 The application type field in the

model number does not match the software ID

1 The application field in the model

number does not match the software ID

2 The variant 1 field in the model

number does not match the software ID

3 The variant 2 field in the model

number does not match the software ID

4 The protocol field in the model

number does not match the software ID

5 The language field in the model

number does not match the software ID

6 The VT type field in the model number is incorrect (110V VTs fitted)

7 The VT type field in the model number is incorrect (440V VTs fitted)

8 The VT type field in the model number is incorrect (no VTs fitted)

Table 4: Out of service LED illuminated

Page 413: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-9

TS

6. ERROR CODE DURING OPERATION The relay performs continuous self-checking, if an error is detected then an error message will be displayed, a maintenance record will be logged and the relay will reset (after a 1.6 second delay). A permanent problem (for example due to a hardware fault) will generally be detected on the power up sequence, following which the relay will display an error code and halt. If the problem was transient in nature then the relay should reboot correctly and continue in operation. The nature of the detected fault can be determined by examination of the maintenance record logged.

There are also two cases where a maintenance record will be logged due to a detected error where the relay will not reset. These are detection of a failure of either the field voltage or the lithium battery, in these cases the failure is indicated by an alarm message, however the relay will continue to operate.

If the field voltage is detected to have failed (the voltage level has dropped below threshold), then a scheme logic signal is also set. This allows the scheme logic to be adapted in the case of this failure (for example if a blocking scheme is being used).

In the case of a battery failure it is possible to prevent the relay from issuing an alarm using the setting under the Date and Time section of the menu. This setting ‘Battery Alarm’ can be set to 'Disabled' to allow the relay to be used without a battery, without an alarm message being displayed.

Error codes (as reported by the relay via the front panel or in the Maintenance Records) can offer a considerable amount of information about the source of the error.

The Hex Code is reported on the front user interface of the relay immediately prior to a reboot sequence. If this code could not be observed, use the Maintenance Records section of the View Records column to display the corresponding Decimal Code.

Hex Code Decimal Code Meaning

0x0C140001 202637313 The serial driver failed to initialise properly. Check the serial port hardware on the power supply board and the main processor board.

0x0C140002 202637314 The LCD driver failed to initialise properly. Check the LCD on the main processor board.

0x0C140003 202637315 The Flash memory driver failed to initialise properly. Check the Flash memory on the main processor board.

0x0C140004 202637316 The date and time driver failed to initialise properly. Check the real-time clock and battery-backed SRAM on the main processor board.

0x0C140008 202637320 The database failed to initialise properly. Check the EEPROM on the main processor board.

0x0C140009 202637321 The database took too long to commit a change. Check the EEPROM on the main processor board.

0x0C14000A

(P741 only)

202637322 The IRIG-B driver failed to initialise properly. Check the IRIG-B interface hardware on the IRIG-B board.

0x0C160010 202768400 The continuous self-checks have found an error in the RAM bus. Check the RAM on the main processor board.

0x0C160011 202768401 The continuous self-checks have found an error in the RAM block. Check the RAM on the main processor board.

0x0C160012 202768402 The continuous self-checks have found an error in the Flash EPROM checksum. Check the Flash EPROM on the main processor board, and then try downloading a new program.

Page 414: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-10

MiCOM P741, P742, P743

TS

Hex Code Decimal Code Meaning

0x0C160013 202768403 The continuous self-checks have found an error in the code comparison. Check the Flash EPROM on the main processor board, and then try downloading a new program.

0x0C160014 202768404 The continuous self-checks have found an error in the battery backed SRAM. Check the battery, then the RAM on the main processor board.

0x0C160015 202768405 The continuous self-checks have found an error in the EEPROM. Check the EEPROM on the main processor board.

0x0C1600A0 202768544 The continuous self-checks have found an error on the acquisition board. Check the input board.

0x0C170016 202833942 Secondary initialisation tests detected a fast watchdog failure. Check the Flash EPROM on the main processor board.

0x0C170017 202833943 Secondary initialisation tests detected a battery backed SRAM failure. Check the battery backed SRAM on the main processor board.

0x0C170018 202833944 Secondary initialisation tests detected a bus reset test failure. Check the main processor board.

0x0C170019 202833945 Secondary initialisation tests detected a slow watchdog failure.

0x0E020000 235012096 Excessive number of gates in PSL. Restore defaults and download new PSL.

0x0E080000 235405312 PSL excessive execution time. Restore defaults and download new PSL.

Table 5: Error Codes

Other error codes relate to problems within the main processor board software. It will be necessary to contact Alstom Grid with details of the problem for a full analysis.

EXTENDED LIST:

Hexa Code Decimal code Problem Verify or modify

0x8110xxxx Software initialisation error Contact Call Centre 0x8111xxxx Software initialisation error Contact Call Centre 0x8112xxxx Software initialisation error Contact Call Centre 0x8113xxxx Software initialisation error Contact Call Centre 0x8114xxxx Software initialisation error Contact Call Centre 0x8115xxxx Software initialisation error Contact Call Centre 0x8116xxxx Software initialisation error Contact Call Centre 0x8117xxxx Incorrect model number Cortec code 0x8118xxxx Software initialisation error Contact Call Centre 0x8119xxxx Software initialisation error Contact Call Centre 0x811Axxxx Software initialisation error Contact Call Centre 0x811Bxxxx Software initialisation error Contact Call Centre 0x811Cxxxx Software initialisation error Contact Call Centre 0x811Dxxxx Software initialisation error Contact Call Centre 0x811Exxxx Software initialisation error Contact Call Centre 0x811Fxxxx Software initialisation error Contact Call Centre

Page 415: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-11

TS

Hexa Code Decimal code Problem Verify or modify

0x8220xxxx TASK PRO software error Contact Call Centre 0x8221xxxx TASK PRO software error Contact Call Centre 0x8222xxxx TASK PRO software error Contact Call Centre 0x8223xxxx TASK PRO software error Contact Call Centre 0x8224xxxx TASK PRO software error Contact Call Centre

0x8350xxxx TASK DIAL software error Contact Call Centre 0x8351xxxx TASK DIAL software error Contact Call Centre 0x8352xxxx TASK DIAL software error Contact Call Centre 0x8353xxxx TASK DIAL software error Contact Call Centre 0x8354xxxx Incorrect relay type Cortec code or the Coprocessor

board address 0x8355xxxx 2 reboots within 5 minutes have

lead to stop 0x8356xxxx TASK DIAL software error Contact Call Centre 0x8357xxxx TASK DIAL software error Contact Call Centre 0x8358xxxx TASK DIAL software error Contact Call Centre 0x8359xxxx Main to Coprocessor board double

access memory communication problem

Contact Call Centre

0x8360xxxx Main to Coprocessor board double access memory read error

Contact Call Centre

0x8361xxxx Main to Coprocessor communication problem

Coprocessor board address

0x8370xxxx Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x8371xxxx Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720000 2205286400 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720001 2205286401 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720002 2205286402 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720003 2205286403 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720004 2205286404 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720005 2205286405 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720006 2205286406 Boot - Main to Coprocessor board communication problem

Cortec or Coprocessor board or number of comms board

0x83720007 2205286407 Relay ON - Main to Coprocessor communication problem

Cortec or Coprocessor board or number of comms board

0x8373xxxx See list of CU_OPER_MAJOR to PU_OPER_MAJOR

0x8374xxxx See list of CU_OPER_PERIPH to PU_OPER_PERIPH

0x8375xxxx See list of CU_OPER_MAJOR to PU_OPER_MAJOR

0x8376xxxx See list of CU_OPER_PERIPH to PU_OPER_PERIPH

Page 416: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-12

MiCOM P741, P742, P743

TS

Hexa Code Decimal code Problem Verify or modify

0x8377xxxx TASK DIAL software error Contact Call Centre 0x8378xxxx See list of CU_INIT_MAJOR to

PU_INIT_MAJOR 0x8379xxxx See list of CU_INIT_PERIPH to

PU_INIT_PERIPH 0x837Axxxx TASK DIAL software error Contact Call Centre 0x837Bxxxx See list of CU_INIT_MAJOR to

PU_INIT_MAJOR 0x837Cxxxx See list of CU_INIT_PERIPH to

PU_INIT_PERIPH 0x837Dxxxx TASK DIAL software error Contact Call Centre 0x837Exxxx See list of CU_OPER_MAJOR to

PU_OPER_MAJOR 0x837Fxxxx See list of CU_OPER_PERIPH to

PU_OPER_PERIPH 0x8380xxxx TASK DIAL software error Contact Call Centre 0x83810001 2206269441 Boot - wrong number of comm.

board Cortec or Coprocessor board or number of comms board

0x83810002 2206269442 Boot - firmware downloading error Contact Call Centre 0x83810004 2206269444 Boot - firmware downloading error Contact Call Centre 0x83810008 2206269448 Boot - firmware downloading error Contact Call Centre 0x83810010 2206269456 Boot - firmware downloading error Contact Call Centre 0x83810020 2206269472 Boot - firmware downloading error Contact Call Centre 0x83810040 2206269504 Boot - firmware downloading error Contact Call Centre 0x83810080 2206269568 Boot - firmware downloading error Contact Call Centre 0x83810100 2206269696 Boot - firmware downloading error Contact Call Centre 0x83810200 2206269952 Boot - firmware downloading error Contact Call Centre 0x83810400 2206270464 Boot - firmware downloading error Contact Call Centre 0x83810800 2206271488 Boot - firmware downloading error Contact Call Centre 0x83811000 2206273536 Boot - firmware downloading error Contact Call Centre 0x83812000 2206277632 Boot - firmware downloading error Contact Call Centre 0x83814000 2206285824 Boot - firmware downloading error Contact Call Centre 0x83818000 2206302208 Boot - wrong number of comm.

board Cortec or Coprocessor board or number of comms board or relay 0 address or opto 0 address

0x8384xxxx See list of CU_OPER_MAJOR to PU_OPER_MAJOR

0x8385xxxx See list of CU_OPER_PERIPH to PU_OPER_PERIPH

0x8386xxxx TASK DIAL software error Contact Call Centre 0x8387xxxx See list of CU_OPER_MAJOR to

PU_OPER_MAJOR 0x8388xxxx See list of CU_OPER_PERIPH to

PU_OPER_PERIPH 0x8389xxxx TASK DIAL software error Contact Call Centre 0x838Axxxx See list of CU_OPER_MAJOR to

PU_OPER_MAJOR 0x838Bxxxx See list of CU_OPER_PERIPH to

PU_OPER_PERIPH 0x838Cxxxx TASK DIAL software error Contact Call Centre

0x84A0xxxx TASK PSLOG software error Contact Call Centre

Page 417: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-13

TS

Hexa Code Decimal code Problem Verify or modify

0x8530xxxx TASK SUP software error Contact Call Centre 0x8531xxxx TASK SUP software error Contact Call Centre 0x8532xxxx TASK SUP software error Contact Call Centre 0x8533xxxx TASK SUP software error Contact Call Centre 0x8534xxxx TASK SUP software error Contact Call Centre 0x8535xxxx TASK SUP software error Contact Call Centre 0x8536xxxx TASK SUP software error Contact Call Centre 0x8537xxxx TASK SUP software error Contact Call Centre 0x8538xxxx TASK SUP software error Contact Call Centre 0x8539xxxx TASK SUP software error Contact Call Centre 0x853Axxxx TASK SUP software error Contact Call Centre 0x853Bxxxx TASK SUP software error Contact Call Centre 0x853Cxxxx TASK SUP software error Contact Call Centre 0x853Dxxxx TASK SUP software error Contact Call Centre 0x853Exxxx TASK SUP software error Contact Call Centre 0x853Fxxxx TASK SUP software error Contact Call Centre 0x8540xxxx TASK SUP software error Contact Call Centre 0x8541xxxx TASK SUP software error Contact Call Centre 0x8542xxxx TASK SUP software error Contact Call Centre 0x86B0xxxx TASK CBF software error Contact Call Centre 0x86B1xxxx TASK CBF software error Contact Call Centre 0x86B2xxxx TASK CBF software error Contact Call Centre

P741 - INIT MODE CU_INIT_MAJOR

2000 System error Coprocessor firmware 4008 External autotest RAM Coprocessor 4010 Autotest interruptions Coprocessor 4018 Comm. board autotest Coprocessor 8001 Main to Coprocessor

communication Coprocessor or Main board

8002 Main to Coprocessor communication

Coprocessor or Main board

8003 Main to Coprocessor communication

Coprocessor or Main board

8004 Main to Coprocessor communication

Coprocessor or Main board

8005 Main to Coprocessor communication

Coprocessor or Main board

8006 Main to Coprocessor communication

Coprocessor or Main board

8007 Main to Coprocessor communication - no IT

Coprocessor address or Coprocessor or Main board

Logical OR See lines included in the logical OR See lines included CU_INIT_PERIPH

0081 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0082 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0083 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0084 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

Page 418: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-14

MiCOM P741, P742, P743

TS

Hexa Code Decimal code Problem Verify or modify

0085 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0086 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0087 Coprocessor to Comm. board 6 communication - no IT

Coprocessor or Comm. board 6 or Comm. board 6 address

0101 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0102 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0103 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0104 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0105 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0106 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0107 Coprocessor to Comm. board 5 communication - no IT

Coprocessor or Comm. board 5 or Comm. board 5 address

0201 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0202 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0203 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0204 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0205 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0206 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0207 Coprocessor to Comm. board 4 communication - no IT

Coprocessor or Comm. board 4 or Comm. board 4 address

0401 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0402 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0403 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0404 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0405 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0406 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0407 Coprocessor to Comm. board 3 communication - no IT

Coprocessor or Comm. board 3 or Comm. board 3 address

0801 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0802 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0803 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0804 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

Page 419: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-15

TS

Hexa Code Decimal code Problem Verify or modify

0805 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0806 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0807 Coprocessor to Comm. board 2 communication - no IT

Coprocessor or Comm. board 2 or Comm. board 2 address

1001 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1002 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1003 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1004 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1005 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1006 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1007 Coprocessor to Comm. board 1 communication - no IT

Coprocessor or Comm. board 1 or Comm. board 1 address

2001 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2002 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2003 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2004 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2005 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2006 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2007 Coprocessor to Comm. board 0 communication - no IT

Coprocessor or Comm. board 0 or Comm. board 0 address

3FC0 no IT Comm. board to Coprocessor board

Coprocessor or Com or ribbon cable

4008 Relay 1 board missing Relay 1 board or Relay 1 board address

4010 Relay 1 board writing error Relay 1 board 8008 Opto 1 board missing Opto 1 board or Opto 1 board

address 8010 Opto 1 board read error Opto 1 board

Logical OR See lines included in the logical OR See lines included Ex: 3006 = 2006 OR 1006

P741 -OPERATING MODE CU_OPER_MAJOR

04xx Topology autotest Coprocessor firmware 08xx Fixed Scheme Logic Autotest Coprocessor firmware 1100 Measurement or Topology autotest Coprocessor firmware 1200 Measurement or Topology autotest Coprocessor firmware 2000 System error Coprocessor firmware 4008 Data RAM autotest Coprocessor 4010 RAM program autotest Coprocessor 4018 Double access memory autotest Coprocessor

Page 420: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-16

MiCOM P741, P742, P743

TS

Hexa Code Decimal code Problem Verify or modify

8001 Main to Coprocessor communication

Coprocessor or Main board

8002 Main to Coprocessor communication

Coprocessor or Main board

8003 Main to Coprocessor communication

Coprocessor or Main board

8004 Main to Coprocessor communication

Coprocessor or Main board

8005 Main to Coprocessor communication

Coprocessor or Main board

8006 Main to Coprocessor communication

Coprocessor or Main board

8007 Main to Coprocessor communication - no IT

Coprocessor address or Coprocessor or Main board

Logical OR See lines included in the logical OR See lines included CU_OPER_PERIPH

0081 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0082 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0083 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0084 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0085 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0086 Coprocessor to Comm. board 6 communication

Coprocessor or Comm. board 6

0087 Coprocessor to Comm. board 6 communication - no IT

Coprocessor or Comm. board 6 or Comm. board 6 address

0101 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0102 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0103 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0104 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0105 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0106 Coprocessor to Comm. board 5 communication

Coprocessor or Comm. board 5

0107 Coprocessor to Comm. board 5 communication - no IT

Coprocessor or Comm. board 5 or Comm. board 5 address

0201 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0202 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0203 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0204 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0205 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

0206 Coprocessor to Comm. board 4 communication

Coprocessor or Comm. board 4

Page 421: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-17

TS

Hexa Code Decimal code Problem Verify or modify

0207 Coprocessor to Comm. board 4 communication - no IT

Coprocessor or Comm. board 4 or Comm. board 4 address

0401 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0402 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0403 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0404 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0405 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0406 Coprocessor to Comm. board 3 communication

Coprocessor or Comm. board 3

0407 Coprocessor to Comm. board 3 communication - no IT

Coprocessor or Comm. board 3 or Comm. board 3 address

0801 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0802 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0803 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0804 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0805 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0806 Coprocessor to Comm. board 2 communication

Coprocessor or Comm. board 2

0807 Coprocessor to Comm. board 2 communication - no IT

Coprocessor or Comm. board 2 or Comm. board 2 address

1001 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1002 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1003 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1004 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1005 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1006 Coprocessor to Comm. board 1 communication

Coprocessor or Comm. board 1

1007 Coprocessor to Comm. board 1 communication - no IT

Coprocessor or Comm. board 1 or Comm. board 1 address

2001 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2002 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2003 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2004 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2005 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

2006 Coprocessor to Comm. board 0 communication

Coprocessor or Comm. board 0

Page 422: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-18

MiCOM P741, P742, P743

TS

Hexa Code Decimal code Problem Verify or modify

2007 Coprocessor to Comm. board 0 communication - no IT

Coprocessor or Comm. board 0 or Comm. board 0 address

3FC0 no IT Comm. board to Coprocessor board

Coprocessor or Com or ribbon cable

4008 Relay 1 board missing Relay 1 board or Relay 1 board address

4010 Relay 1 board writing error Relay 1 board 8008 Opto 1 board missing Opto 1 board or Opto 1 board

address 8010 Opto 1 board read error Opto 1 board

Logical OR See lines included in the logical OR See lines included Ex: 3006 = 2006 OR 1006

P742 / P743 - INIT MODE PU_INIT_MAJOR

2000 System error Coprocessor firmware 4008 External autotest RAM Coprocessor 4010 Autotest interruptions Coprocessor 4018 Comm. board autotest Coprocessor 8001 Main to Coprocessor

communication Coprocessor or Main board

8002 Main to Coprocessor communication

Coprocessor or Main board

8003 Main to Coprocessor communication

Coprocessor or Main board

8004 Main to Coprocessor communication

Coprocessor or Main board

8005 Main to Coprocessor communication

Coprocessor or Main board

8006 Main to Coprocessor communication

Coprocessor or Main board

8007 Main to Coprocessor communication - no IT

Coprocessor address or Coprocessor or Main board

Logical OR See lines included in the logical OR See lines included PU_INIT_PERIPH

0200 Analogue module acquisition problem

Analogue module

0408 Relay 3 board missing Relay 3 board or Relay 3 board address

0410 Relay 3 board writing error Relay 3 board 0808 Opto 3 board missing Opto 3 board or Opto 3 board

address 0810 Opto 3 board read error Opto 3 board 1008 Relay 2 board missing Relay 2 board or Relay 2 board

address 1010 Relay 2 board writing error Relay 2 board 2008 Opto 2 board missing Opto 2 board or Opto 2 board

address 2010 Opto 2 board read error Opto 2 board 4008 Relay 1 board missing Relay 1 board or Relay 1 board

address 4010 Relay 1 board writing error Relay 1 board 8008 Opto 1 board missing Opto 1 board or Opto 1 board

address 8010 Opto 1 board read error Opto 1 board

Page 423: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-19

TS

Hexa Code Decimal code Problem Verify or modify

Logical OR See lines included in the logical OR See lines included

Ex: 5010 = 4010 OR 1010 P742 / P743 - OPERATING MODE

PU_OPER_MAJOR 04xx Topology autotest Coprocessor firmware 08xx Fixed Scheme Logic Autotest Coprocessor firmware 1100 Measurement or Topology autotest Coprocessor firmware 1200 Measurement or Topology autotest Coprocessor firmware 2000 System error Coprocessor firmware 4008 External autotest RAM Coprocessor 4010 Interruptions autotest Coprocessor 4018 Comm. board autotest Coprocessor 8001 Main to Coprocessor

communication Coprocessor or Main board

8002 Main to Coprocessor communication

Coprocessor or Main board

8003 Main to Coprocessor communication

Coprocessor or Main board

8004 Main to Coprocessor communication

Coprocessor or Main board

8005 Main to Coprocessor communication

Coprocessor or Main board

8006 Main to Coprocessor communication

Coprocessor or Main board

8007 Main to Coprocessor communication - no IT

Coprocessor address or Coprocessor or Main board

Logical OR See lines included in the logical OR See lines included PU_OPER_PERIPH

0200 Analogue module acquisition problem

Analogue module

0408 Relay 3 board missing Relay 3 board or Relay 3 board address

0410 Relay 3 board writing error Relay 3 board 0808 Opto 3 board missing Opto 3 board or Opto 3 board

address 0810 Opto 3 board read error Opto 3 board 1008 Relay 2 board missing Relay 2 board or Relay 2 board

address 1010 Relay 2 board writing error Relay 2 board 2008 Opto 2 board missing Opto 2 board or Opto 2 board

address 2010 Opto 2 board read error Opto 2 board 4008 Relay 1 board missing Relay 1 board or Relay 1 board

address 4010 Relay 1 board writing error Relay 1 board 8008 Opto 1 board missing Opto 1 board or Opto 1 board

address 8010 Opto 1 board read error Opto 1 board

Logical OR See lines included in the logical OR See lines included Ex: a010 = 2010 OR 8010

Page 424: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-20

MiCOM P741, P742, P743

TS

7. MAL-OPERATION OF THE RELAY DURING TESTING

7.1 Failure of output contacts

An apparent failure of the relay output contacts may be caused by the relay configuration; the following tests should be performed to identify the real cause of the failure. Note that the relay self-tests verify that the coil of the contact has been energized, an error will be displayed if there is a fault in the output relay board.

Test Check Action

1

Is the Out of Service LED illuminated?

Illumination of this LED may indicate that the relay is in test mode or that the protection has been disabled due to a hardware verify error (see Table 4).

2 Examine the Contact status in the Commissioning section of the menu.

If the relevant bits of the contact status are operated then proceed to test 4, if not proceed to test 3.

3

Verify by examination of the fault record or by using the test port whether the protection element is operating correctly.

If the protection element does not operate verify whether the test is being correctly applied.

If the protection element does operate then it will be necessary to check the programmable logic, to ensure that the mapping of the protection element to the contacts is correct.

4

Using the Commissioning/Test mode function apply a test pattern to the relevant relay output contacts and verify whether they operate (note the correct external connection diagram should be consulted). A continuity tester can be used at the rear of the relay for this purpose.

If the output relay does operate then the problem must be in the external wiring to the relay. If the output relay does not operate this could indicate a failure of the output relay contacts (note that the self-tests verify that the relay coil is being energized). Ensure that the closed resistance is not too high for the continuity tester to detect.

Table 6: Failure of output contacts

7.2 Failure of opto-isolated inputs

The opto-isolated inputs are mapped onto the relay internal signals using the programmable scheme logic. If an input does not appear to be recognized by the relay scheme logic the Commission Tests/Opto Status menu option can be used to verify whether the problem is in the opto-isolated input itself or the mapping of its signal to the scheme logic functions. If the opto-isolated input does appear to be read correctly then it will be necessary to examine its mapping within the programmable logic.

Ensure the voltage rating for the opto inputs has been configured correctly with applied voltage. If the opto-isolated input state is not being correctly read by the relay the applied signal should be tested. Verify the connections to the opto-isolated input using the correct wiring diagram. Next, using a voltmeter verify that 80% opto setting voltage is present on the terminals of the opto-isolated input in the energized state. If the signal is being correctly applied to the relay then the failure may be on the input card itself. Depending on which opto-isolated input has failed this may require replacement of either the complete analog input module (the board within this module cannot be individually replaced without re-calibration of the relay) or a separate opto board.

Page 425: P74x_EN_M_H54

Troubleshooting P74x/EN TS/H54 MiCOM P741, P742, P743

(TS) 12-21

TS

7.3 Incorrect analog signals (P742 or P743)

The measurements may be configured in primary or secondary to assist. If it is suspected that the analog quantities being measured by the relay are not correct then the measurement function of the relay can be used to verify the nature of the problem. The measured values displayed by the relay should be compared with the actual magnitudes at the relay terminals. Verify that the correct terminals are being used (in particular the dual rated CT inputs) and that the CT and VT ratios set on the relay are correct. The correct 120 degree displacement of the phase measurements should be used to confirm that the inputs have been correctly connected.

7.4 PSL editor troubleshooting

A failure to open a connection could be because of one or more of the following:

• The relay address is not valid (note: this address is always 1 for the front port)

• Password in not valid

• Communication Set-up - COM port, Baud rate, or Framing - is not correct

• Transaction values are not suitable for the relay and/or the type of connection

• Modem configuration is not valid. Changes may be necessary when using a modem

• The connection cable is not wired correctly or broken. See MiCOM S1 connection configurations

• The option switches on any KITZ101/102 this is in use may be incorrectly set

7.4.1 Diagram reconstruction after recover from relay

Although the extraction of a scheme from a relay is supported, the facility is provided as a way of recovering a scheme in the event that the original file is unobtainable.

The recovered scheme will be logically correct, but much of the original graphical information is lost. Many signals will be drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest path from A to B.

Any annotation added to the original diagram (titles, notes, etc.) are lost.

Sometimes a gate type may not be what was expected, e.g. a 1-input AND gate in the original scheme will appear as an OR gate when uploaded. Programmable gates with an inputs-to-trigger value of 1 will also appear as OR gates.

7.4.2 PSL version check

The PSL is saved with a version reference, time stamp and CRC check. This gives a visual check whether the default PSL is in place or whether a new application has been downloaded.

Page 426: P74x_EN_M_H54

P74x/EN TS/H54 Troubleshooting (TS) 12-22

MiCOM P741, P742, P743

TS

8. REPAIR AND MODIFICATION PROCEDURE Please follow these 5 steps to return an Automation product to us:

1. Get the Repair and Modification Authorization Form (RMA)

Find a copy of the RMA form at the end of this section.

To obtain an electronic version of the RMA form for e-mailing, please visit the

following URL: www.alstom.com/grid/productrepair

2. Fill in RMA form

Fill in only the white part of the form.

Please ensure that all fields marked (M) are completed such as:

Equipment model

Model No. and Serial No.

Description of failure or modification required (please be specific)

Value for customs (in case the product requires export)

Delivery and invoice addresses

Contact details

3. Send RMA form to your local contact

Find enclosed a list of local service contacts, worldwide.

4. Receive from local service contact, the information required to ship the product

Your local service contact will provide you with all the information:

Pricing details

RMA n°

Repair centre address

If required, an acceptance of the quote must be delivered before going to next stage.

5. Send the product to the repair centre

Address the shipment to the repair centre specified by your local contact

Ensure all items are protected by appropriate packaging: anti-static bag and foam

protection

Ensure a copy of the import invoice is attached with the unit being returned

Ensure a copy of the RMA form is attached with the unit being returned

E-mail or fax a copy of the import invoice and airway bill document to your local contact.

Page 427: P74x_EN_M_H54

Repair/Modification Return Authorization Form

FIELDS IN GREY TO BE FILLED IN BY Alstom Grid PERSONNEL ONLY

Reference RMA: Date:

Repair Center Address (for shipping)

Service Type

Retrofit

Warranty

Paid service

Under repair contract

Wrong supply

LSC PO No.:

Alstom Grid - Local Contact Details

Name:

Telephone No.:

Fax No.:

E-mail:

IDENTIFICATION OF UNIT

Fields marked (M) are mandatory, delays in return will occur if not completed.

Model No./Part No.: (M)

Manufacturer Reference: (M)

Serial No.: (M)

Software Version:

Quantity:

Site Name/Project:

Commissioning Date:

Under Warranty: Yes No

Additional Information:

Customer P.O (if paid):

FAULT INFORMATION

Type of Failure

Hardware fail

Mechanical fail/visible defect

Software fail

Other:

Fault Reproducibility

Fault persists after removing, checking on test bench

Fault persists after re-energization

Intermittent fault

Found Defective

During FAT/inspection

On receipt

During installation/commissioning

During operation

Other:

Page 428: P74x_EN_M_H54

Description of Failure Observed or Modification Required - Please be specific (M)

FOR REPAIRS ONLY

Would you like us to install an updated firmware version after repair? Yes No

CUSTOMS & INVOICING INFORMATION

Required to allow return of repaired items

Value for Customs (M)

Customer Invoice Address ((M) if paid)

Customer Return Delivery Address (full street address) (M)

Part shipment accepted Yes No

OR Full shipment required Yes No

Contact Name:

Telephone No.:

Fax No.:

E-mail:

Contact Name:

Telephone No.:

Fax No.:

E-mail:

REPAIR TERMS

1. Please ensure that a copy of the import invoice is attached with the returned unit, together with the airway bill document. Please fax/e-mail a copy of the appropriate documentation (M).

2. Please ensure the Purchase Order is released, for paid service, to allow the unit to be shipped.

3. Submission of equipment to Alstom Grid is deemed as authorization to repair and acceptance of quote.

4. Please ensure all items returned are marked as Returned for ‘Repair/Modification’ and protected by appropriate packaging (anti-static bag for each board and foam protection).

Page 429: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

SC

SCADA COMMUNICATIONS

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 430: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

MiCOM P741, P742, P743

Page 431: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-1

SC

CONTENTS

1. SCADA COMMUNICATIONS 3

1.1 Introduction 3

1.2 Rear port information and connection advice – EIA(RS)485 protocols 3

1.2.1 Rear communication port EIA(RS)485 interface 3

1.2.2 Courier communication 5

1.2.3 MODBUS communication (not available) 7

1.2.4 IEC60870-5 CS 103 communication 7

1.2.5 DNP3.0 communication (not available) 9

1.3 Second rear communication port (SK4) 9

1.4 Ethernet communication 9

2. COURIER INTERFACE 10

2.1 Courier protocol 10

2.2 Supported command set 10

2.3 Relay courier database 11

2.4 Setting changes 12

2.4.1 Setting transfer mode 12

2.5 Event extraction 12

2.5.1 Automatic event extraction 12

2.5.2 Event types 13

2.5.3 Event format 13

2.5.4 Manual event record extraction 13

2.6 Disturbance record extraction 14

2.7 Programmable scheme logic settings 14

Page 432: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-2

MiCOM P741, P742, P743

SC

FIGURES

FIGURE 1: EIA(RS)485 BUS CONNECTION ARRANGEMENTS 4 FIGURE 2: REMOTE COMMUNICATION CONNECTION ARRANGEMENTS 6 FIGURE 3: UP TO 8 ADDRESSES EXAMPLE 8 FIGURE 4: MORE THAN 8 ADDRESSES EXAMPLE 8 FIGURE 5: SECOND REAR PORT EIA(RS)232 EXAMPLE 9 FIGURE 6: ETHERNET CONNEXION EXAMPLE 9

Page 433: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-3

SC

1. SCADA COMMUNICATIONS

1.1 Introduction

This section outlines the remote communications interfaces of the MiCOM relay. The relay supports a choice of one of five protocols via the rear communication interface, selected via the model number when ordering. This is in addition to the front serial interface and 2nd rear communications port, which supports the Courier protocol only.

The rear EIA(RS)485 interface is isolated and is suitable for permanent connection whichever protocol is selected. The advantage of this type of connection is that up to 32 relays can be ‘daisy chained’ together using a simple twisted pair electrical connection.

It should be noted that the descriptions contained within this section do not aim to fully detail the protocol itself. The relevant documentation for the protocol should be referred to for this information. This section serves to describe the specific implementation of the protocol in the relay.

1.2 Rear port information and connection advice – EIA(RS)485 protocols

1.2.1 Rear communication port EIA(RS)485 interface

The rear EIA(RS)485 communication port is provided by a 3-terminal screw connector located on the back of the relay. See section P74x/EN IN for details of the connection terminals. The rear port provides K-Bus/EIA(RS)485 serial data communication and is intended for use with a permanently wired connection to a remote control centre. Of the three connections, two are for the signal connection, and the other is for the earth shield of the cable. When the K-Bus option is selected for the rear port, the two signal connections are not polarity conscious, however for MODBUS, IEC60870-5-103 and DNP3.0 care must be taken to observe the correct polarity.

The protocol provided by the relay is indicated in the relay menu in the ‘Communications’ column. Using the keypad and LCD, firstly check that the ‘Comms. settings’ cell in the ‘Configuration’ column is set to ‘Visible’, then move to the ‘Communications’ column. The first cell down the column shows the communication protocol being used by the rear port.

1.2.1.1 EIA(RS)485 bus

The EIA(RS)485 two-wire connection provides a half-duplex fully isolated serial connection to the product. The connection is polarized and whilst the product’s connection diagrams indicate the polarization of the connection terminals it should be borne in mind that there is no agreed definition of which terminal is which. If the master is unable to communicate with the product, and the communication parameters match, then it is possible that the two-wire connection is reversed.

1.2.1.2 Bus termination

The EIA(RS)485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end across the signal wires – see Figure 1. Some devices may be able to provide the bus terminating resistors by different connection or configuration arrangements, in which case separate external components will not be required. However, this product does not provide such a facility, so if it is located at the bus terminus then an external termination resistor will be required.

Page 434: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-4

MiCOM P741, P742, P743

SC

1.2.1.3 Bus connections & topologies

The EIA(RS)485 standard requires that each device be directly connected to the physical cable that is the communications bus. Stubs and tees are expressly forbidden, as are star topologies. Loop bus topologies are not part of the EIA(RS)485 standard and are forbidden by it.

Two-core screened cable is recommended. The specification of the cable will be dependent on the application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must not exceed 1000m. The screen must be continuous and connected to ground at one end, normally at the master connection point; it is important to avoid circulating currents, especially when the cable runs between buildings, for both safety and noise reasons.

This product does not provide a signal ground connection. If a signal ground connection is present in the bus cable then it must be ignored, although it must have continuity for the benefit of other devices connected to the bus. At no stage must the signal ground be connected to the cables screen or to the product’s chassis. This is for both safety and noise reasons.

1.2.1.4 Biasing

It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level has an indeterminate state because the bus is not being actively driven. This can occur when all the slaves are in receive mode and the master is slow to turn from receive mode to transmit mode. This may be because the master purposefully waits in receive mode, or even in a high impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss the first bits of the first character in the packet, which results in the slave rejecting the message and consequentially not responding. Symptoms of this are poor response times (due to retries), increasing message error counters, erratic communications, and even a complete failure to communicate.

Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There should only be one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias must be clean; otherwise noise will be injected. Note that some devices may (optionally) be able to provide the bus bias, in which case external components will not be required.

!

" #

FIGURE 1: EIA(RS)485 BUS CONNECTION ARRANGEMENTS

Page 435: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-5

SC

It is possible to use the products field voltage output (48V DC) to bias the bus using values of 2.2kΩ (½W) as bias resistors instead of the 180Ω resistors shown in the above diagram.

Note the following warnings apply:

• It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will result in an excessive bias voltage that may damage the devices connected to the bus.

• As the field voltage is much higher than that required, Alstom Grid cannot assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage.

• Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs) as this may cause noise to be passed to the communication network.

1.2.2 Courier communication

Courier works on a master/slave basis where the slave units contain information in the form of a database, and respond with information from the database when it is requested by a master unit.

The relay is a slave unit that is designed to be used with a Courier master unit such as MiCOM S1, MiCOM S10, PAS&T or a SCADA system.

To use the rear port to communicate with a PC-based master station using Courier, a KITZ K-Bus to EIA(RS)232 protocol converter is required. This unit is available from Alstom Grid. A typical connection arrangement is shown in Figure 2. For more detailed information on other possible connection arrangements refer to the manual for the Courier master station software and the manual for the KITZ protocol converter. Each spur of the K-Bus twisted pair wiring can be up to 1000m in length and have up to 32 relays connected to it.

Page 436: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-6

MiCOM P741, P742, P743

SC

P0109ENe

FIGURE 2: REMOTE COMMUNICATION CONNECTION ARRANGEMENTS

Having made the physical connection to the relay, the relay’s communication settings must be configured. To do this use the keypad and LCD user interface. In the relay menu firstly check that the ‘Comms. settings’ cell in the ‘Configuration’ column is set to ‘Visible’, then move to the ‘Communications’ column. Only two settings apply to the rear port using Courier, the relay’s address and the inactivity timer. Synchronous communication is used at a fixed baud rate of 64kbits/s.

Move down the ‘Communications’ column from the column heading to the first cell down which indicates the communication protocol:

Protocol Courier

The next cell down the column controls the address of the relay:

Remote address 1

Page 437: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-7

SC

Since up to 32 relays can be connected to one K-bus spur, as indicated in Figure 2, it is necessary for each relay to have a unique address so that messages from the master control station are accepted by one relay only. Courier uses an integer number between 0 and 254 for the relay address, which is set with this cell. It is important that no two relays have the same Courier address. The Courier address is then used by the master station to communicate with the relay. Default value of remote address is 255 and must be changed to 6 for the P741 or a value in the range of 7 to 34 for the P742 and P743.

The next cell down controls the inactivity timer:

Inactivity timer 10.00 min.

The inactivity timer controls how long the relay will wait without receiving any messages on the rear port before it reverts to its default state, including revoking any password access that was enabled. For the rear port this can be set between 1 and 30 minutes.

Note that protection and disturbance recorder settings that are modified using an on-line editor such as PAS&T must be confirmed with a write to the ‘Save changes’ cell of the ‘Configuration’ column. Off-line editors such as MiCOM S1 do not require this action for the setting changes to take effect.

1.2.3 MODBUS communication (not available)

MODBUS is a master/slave communication protocol, which can be used for network control. In a similar fashion to Courier, the system works by the master device initiating all actions and the slave devices, (the relays), responding to the master by supplying the requested data or by taking the requested action. MODBUS communication is achieved via a twisted pair EIA(RS)485 connection to the rear port and can be used over a distance of 1000m with up to 32 slave devices.

This protocol is not available.

1.2.4 IEC60870-5 CS 103 communication

The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform communication with protection equipment. The standard configuration for the IEC60870-5-103 protocol is to use a twisted pair EIA(RS)485 connection over distances up to 1000m. The relay operates as a slave in the system, responding to commands from a master station.

To use the IEC60870-5-103 communication, the relays have to be connected to a KITZ274.

A KITZ274 converter can manage up to 8 P74x relays with consecutive addresses.

Page 438: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-8

MiCOM P741, P742, P743

SC

CU Informations: Idiff & Ibias / Inputs / Outputs / Events /Disturbance records

MiCOM P741Central Unit

Peripheral UnitsMiCOM P743

&MiCOM P742

K-BUS/Courier

IEC60870-5-103Optical fibre

EIA(RS)485 / EIA(RS)232

P3796ENb

FIGURE 3: UP TO 8 ADDRESSES EXAMPLE

FIGURE 4: MORE THAN 8 ADDRESSES EXAMPLE

Page 439: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-9

SC

1.2.5 DNP3.0 communication (not available)

The DNP 3.0 protocol is defined and administered by the DNP User Group. Information about the user group, DNP 3.0 in general and protocol specifications can be found on their website: www.dnp.org

This protocol is not available.

1.3 Second rear communication port (SK4)

For relays with Courier or IEC60870-5-103 protocol on the first rear communications port there is the hardware option of a second rear communications port, which will run the Courier language. This will be provided with a KITZ201.

Idiff (A,B,C) + Ibias (A,B,C) + Inputs + Outputs + Events + Disturbance P741Add 6

CU & PU Local PCPort 2 RS 232

P743 Kbus/courier Port 3 Port 1 Kbus/courierAdd 7

Kitz201Add 2

P742Add 8,

IEC 103 / FibreKbus/courier Port 3 Port 1 or Vdew/IEC Master

Per PU connection: I (A,B,C) + Inputs + Outputs + Events + Disturbance Port 2IEC 103 / RS 485/RS

Kitz274Add 1

The KITZ201 can be used to communicate with upto 32 relays but it is prefarable to use 1 kitz201 per KITZ274 to not slow down the communication

P3797ENb

FIGURE 5: SECOND REAR PORT EIA(RS)232 EXAMPLE

Note: The KITZ201 redates the events

1.4 Ethernet communication

It is possible to communicate through an Ethernet network using an Alstom Grid I4XS4UE

P741

PC with MiCOM S1

P743RS485/courier Ethernet

I4XS4U

CU: Idiff (A,B,C) + Ibias (A,B,C) + Inputs + Outputs + Events + Disturbance

P742Per PU: I (A,B,C) + Inputs + Outputs + Events + Disturbance

All: Settings, PSL, events,

P742

P742

One I4XS4UE can connect up to 29 adresses (full P740 scheme) P3798ENb

FIGURE 6: ETHERNET CONNEXION EXAMPLE

Page 440: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-10

MiCOM P741, P742, P743

SC

2. COURIER INTERFACE

2.1 Courier protocol

K-Bus is based on EIA(RS)485 voltage levels with HDLC FM0 encoded synchronous signalling and its own frame format. The K-Bus twisted pair connection is unpolarized, whereas the EIA(RS)485 and EIA(RS)232 interfaces are polarized.

The EIA(RS)232 interface uses the IEC60870-5 FT1.2 frame format.

The relay supports an IEC60870-5 FT1.2 connection on the front-port. This is intended for temporary local connection and is not suitable for permanent connection. This interface uses a fixed baud rate, 11-bit frame, and a fixed device address.

The rear interface is used to provide a permanent connection for K-Bus and allows multi-drop connection. It should be noted that although K-Bus is based on EIA(RS)485 voltage levels it is a synchronous HDLC protocol using FM0 encoding. It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC60870-5 FT1.2 frames to K-Bus. Nor is it possible to connect K-Bus to an EIA(RS)485 computer port. A protocol converter, such as the KITZ101, should be employed for this purpose.

Alternatively for direct connections, the fibre optic converter card may be used to convert the rear EIA(RS)485 port into a fibre optic (ST) port.

2.2 Supported command set

The following Courier commands are supported by the relay:

Protocol Layer

Reset Remote Link

Poll Status

Poll Buffer*

Low Level Commands

Send Event*

Accept Event*

Send Block

Store Block Identifier

Store Block Footer

Menu Browsing

Get Column Headings

Get Column Text

Get Column Values

Get Strings

Get Text

Get Value

Get Column Setting Limits

Page 441: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-11

SC

Setting Changes

Enter Setting Mode

Preload Setting

Abort Setting

Execute Setting

Reset Menu Cell

Set Value

Control Commands

Select Setting Group

Change Device Address*

Set Real Time

Note: Commands indicated with a * are not supported via the front Courier port.

2.3 Relay courier database

The Courier database is a two dimensional structure with each cell in the database being referenced by a row and column address. Both the column and the row can take a range from 0 to 255. Addresses in the database are specified as hexadecimal values; e.g. 0A02 is column 0A (10 decimal) row 02. Associated settings/data will be part of the same column, row zero of the column contains a text string to identify the contents of the column, i.e. a column heading.

P74x/EN MD contains the complete database definition for the relay. For each cell location the following information is stated:

− Cell text

− Cell datatype

− Cell value

− Whether the cell is settable, if so

− Minimum value

− Maximum value

− Step size

− Password level required to allow setting changes

− String information (for Indexed String or Binary flag cells)

Page 442: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-12

MiCOM P741, P742, P743

SC

2.4 Setting changes

(See R6512, Courier User Guide - Chapter 9)

There are three categories of settings within the relay database:

− Control and support

− Disturbance recorder

− Protection settings group

Setting changes made to the control and support settings are implemented immediately and stored in non-volatile memory. Changes made to either the disturbance recorder settings or the protection settings groups are stored in a ‘scratchpad’ memory and are not immediately implemented by the relay.

To action setting changes stored in the scratchpad the save changes cell in the configuration column must be written to. This allows the changes to either be confirmed and stored in non-volatile memory, or the setting changes to be aborted.

2.4.1 Setting transfer mode

If it is necessary to transfer all of the relay settings to or from the relay a cell within the communication system data column can be used. This cell (location BF03) when set to 1 makes all of the relay settings visible. Any setting changes made, with the relay set in this mode, are stored in scratchpad memory (including control and support settings). When the value of BF03 is set back to 0 any setting changes are verified and stored in non-volatile memory.

2.5 Event extraction

Events can be extracted either automatically (rear port only) or manually (either Courier port). For automatic extraction all events are extracted in sequential order using the standard Courier event mechanism, this includes fault/maintenance data if appropriate. The manual approach allows the user to select events, faults, or maintenance data at random from the stored records.

2.5.1 Automatic event extraction

(See Chapter 7 Courier User Guide, publication R6512)

This method is intended for continuous extraction of event and fault information as it is produced. It is only supported via the rear Courier port.

When new event information is created the event bit is set within the status byte, this indicates to the master device that event information is available. The oldest, unextracted event can be extracted from the relay using the send event command. The relay will respond with the event data, which will be either a Courier Type 0 or Type 3 event. The Type 3 event is used for fault records and maintenance records.

Once an event has been extracted from the relay, the accept event can be used to confirm that the event has been successfully extracted. If all events have been extracted then the event bit will reset, if there are more events still to be extracted the next event can be accessed using the send event command as before.

Page 443: P74x_EN_M_H54

SCADA Communications P74x/EN SC/H54

MiCOM P741, P742, P743

(SC) 13-13

SC

2.5.2 Event types

Events will be created by the relay under the following circumstances:

− Change of state of output contact

− Change of state of opto input

− Protection element operation

− Alarm condition

− Setting change

− Password entered/timed-out

− Fault record (Type 3 Courier Event)

− Maintenance record (Type 3 Courier Event)

2.5.3 Event format

The send event command results in the following fields being returned by the relay:

− Cell reference

− Timestamp

− Cell text

− Cell value

The menu database, P74x/EN MD, contains a table of the events created by the relay and indicates how the contents of the above fields are interpreted. Fault records and maintenance records will return a Courier Type 3 event, which contains the above fields together with two additional fields:

− Event extraction column

− Event number

These events contain additional information that is extracted from the relay using the referenced extraction column. Row 01 of the extraction column contains a setting that allows the fault/maintenance record to be selected. This setting should be set to the event number value returned within the record; the extended data can be extracted from the relay by uploading the text and data from the column.

2.5.4 Manual event record extraction

Column 01 of the database can be used for manual viewing of event, fault, and maintenance records. The contents of this column will depend on the nature of the record selected. It is possible to select events by event number and to directly select a fault record or maintenance record by number.

Event Record Selection (Row 01) - This cell can be set to a value between 0 to 511 to select which of the 512 stored events is selected, 0 will select the most recent record; 511 the oldest stored record. For simple event records, (Type 0) cells 0102 to 0105 contain the event details. A single cell is used to represent each of the event fields. If the event selected is a fault or maintenance record (Type 3) then the remainder of the column will contain the additional information.

Fault Record Selection (Row 05) – This cell can be used to directly select a fault record using a value between 0 and 4 to select one of up to five stored fault records. (0 will be the most recent fault and 4 will be the oldest). The column will then contain the details of the fault record selected.

Page 444: P74x_EN_M_H54

P74x/EN SC/H54 SCADA Communications

(SC) 13-14

MiCOM P741, P742, P743

SC

Maintenance Record Selection (Row F0) – This cell can be used to select a maintenance record using a value between 0 and 4 and operates in a similar way to the fault record selection.

It should be noted that if this column is used to extract event information from the relay the number associated with a particular record will change when a new event or fault occurs.

2.6 Disturbance record extraction

Select Record Number (Row 01) - This cell can be used to select the record to be extracted. Record 0 will be the oldest unextracted record, already extracted older records will be assigned positive values, and negative values will be used for more recent records. To facilitate automatic extraction via the rear port the disturbance bit of the status byte is set by the relay whenever there are unextracted disturbance records.

Once a record has been selected, using the above cell, the time and date of the record can be read from cell 02. The disturbance record itself can be extracted using the block transfer mechanism from cell B00B.

As has been stated, the rear Courier port can be used to automatically extract disturbance records as they occur. This operates using the standard Courier mechanism defined in Chapter 8 of the Courier User Guide. The front Courier port does not support automatic extraction although disturbance record data can be extracted manually from this port.

2.7 Programmable scheme logic settings

The programmable scheme logic (PSL) settings can be uploaded from and downloaded to the relay using the block transfer mechanism.

The following cells are used to perform the extraction:

− B204 Domain: Used to select either PSL settings (Upload or download) or PSL configuration data (Upload only)

− B208 Sub-Domain: Used to select the Protection Setting Group to be uploaded/downloaded.

− B20C Version: Used on a download to check the compatibility of the file to be downloaded with the relay.

− B21C Transfer Mode: Used to set-up the transfer process.

− B120 Data Transfer Cell: Used to perform upload/download.

The programmable scheme logic settings can be uploaded and downloaded to and from the relay using this mechanism. If it is necessary to edit the settings MiCOM S1 must be used as the data format is compressed. MiCOM S1 also performs checks on the validity of the settings before they are downloaded to the relay.

Page 445: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

SG

SYMBOLS AND GLOSSARY

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 446: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

MiCOM P741, P742, P743

Page 447: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

(SG) 14-1

SG

Logic Symbols used

Symbols Explanation

< Less than: Used to indicate an “under” threshold, such as undercurrent (current dropout).

> Greater than: Used to indicate an “over” threshold, such as overcurrent (current overload).

& Logical “AND”: Used in logic diagrams to show an AND-gate function.

1 Logical “OR”: Used in logic diagrams to show an OR-gate function.

o A small circle on the input or output of a logic gate: Indicates a NOT (invert) function.

52a A circuit breaker closed auxiliary contact: The contact is in the same state as the breaker primary contacts.

52b A circuit breaker open auxiliary contact: The contact is in the opposite state to the breaker primary contacts.

89a An Isolator closed auxiliary contact: The contact is in the same state as the breaker primary contacts.

89b An Isolator open auxiliary contact: The contact is in the opposite state to the breaker primary contacts.

Σ “Sigma”: Used to indicate a summation, such as cumulative current interrupted.

τ “Tau”: Used to indicate a time constant, often associated with thermal characteristics.

BU Backup: Typically a back-up protection element.

C/O A changeover contact having normally closed and normally open connections: Often called a “form C” contact.

CB Circuit breaker.

CB Aux. Circuit breaker auxiliary contacts: Indication of the breaker open/closed status.

CBF Circuit breaker failure protection.

CT Current transformer.

CTRL. Abbreviation of “Control”: As used for the Control Inputs function.

CTS Current transformer supervision:

To detect CT input failure.

CU Abbreviation of “Central Unit” (P741)

CZ Abbreviation of “Check Zone”: Zone taking into account only the feeders.

DDB Digital data bus within the programmable scheme logic: A logic point that has a zero or 1 status. DDB signals are mapped in logic to customize the relay’s operation.

Dly Time delay.

Page 448: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

(SG) 14-2

MiCOM P741, P742, P743

SG

Symbols Explanation

DR Abbreviation of “Disturbance Record”

DT Abbreviation of “Definite Time”: An element which always responds with the same constant time delay on operation.

DZ Abbreviation of “Dead Zone”: Area between a CT and an open breaker or an open isolator.

E/F Earth fault: Directly equivalent to ground fault.

FLC Full load current: The nominal rated current for the circuit.

Flt. Abbreviation of “Fault”: Typically used to indicate faulted phase selection.

FN Function.

GN> Neutral over conductance protection element:

Real component of admittance calculation from neutral current and residual voltage.

Gnd. Abbreviation of “Ground”: Used in distance settings to identify settings that relate to ground (earth) faults.

GRP. Abbreviation of “Group”: Typically an alternative setting group.

I Current.

I∧ Current raised to a power: Such as when breaker statistics monitor the square of ruptured current squared (∧ power = 2).

I< An undercurrent element: Responds to current dropout.

I> An overcurrent element: Detects phase faults; Optionally used by the 50BF protection.

I>1 First stage of phase overcurrent protection: Could be labelled 51-1 in ANSI terminology.

I>2 Second stage of phase overcurrent protection: Could be labelled 51-2 in ANSI terminology.

I>3 Third stage of phase overcurrent protection: Could be labelled 51-3 in ANSI terminology.

I>4 Fourth stage of phase overcurrent protection: Could be labelled 51-4 in ANSI terminology.

I>BB Minimum pick-up phase threshold for the local trip order confirmation.

I>DZ Minimum pick-up phase threshold for the Dead Zone protection.

I0 Zero sequence current: Equals one third of the measured neutral/residual current.

I1 Positive sequence current.

I2 Negative sequence current.

IA Phase A current: Might be phase L1, red phase. or other, in customer terminology.

Page 449: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

(SG) 14-3

SG

Symbols Explanation

IB Phase B current: Might be phase L2, yellow phase. or other, in customer terminology.

IbiasPh> Cur.

SDEF blocking bias current threshold.

IC Phase C current: Might be phase L3, blue phase. or other, in customer terminology.

ID Abbreviation of “Identifier”: Often a label used to track a software version installed.

ID>1 Minimum pick-up phase circuitry fault threshold.

ID>2 Minimum pick-up differential phase element for all the zones.

IDCZ>2 Minimum pick-up differential phase element for the Check Zone.

IDMT Inverse definite minimum time: A characteristic whose trip time depends on the measured input (e.g. current) according to an inverse-time curve.

IDN>1 Minimum pick-up neutral circuitry fault threshold.

IDN>2 Minimum pick-up differential neutral element for all the zones.

IDNCZ>2 Minimum pick-up differential neutral element for the Check Zone.

IDZ Minimum pick-up differential neutral element for the Check Zone.

In The rated nominal current of the relay: Software selectable as 1 amp or 5 amps to match the line CT input.

IN Neutral current, or residual current: This results from an internal summation of the three measured phase currents.

IN> A neutral (residual) overcurrent element: Detects earth/ground faults.

IN>1 First stage of ground overcurrent protection: Could be labelled 51N-1 in ANSI terminology.

IN>2 Second stage of ground overcurrent protection: Could be labelled 51N-2 in ANSI terminology.

IN>BB Minimum pick-up neutral threshold for the local trip order confirmation.

IN>DZ Minimum pick-up neutral threshold for the Dead Zone protection.

Inh An inhibit signal.

ISEF> Sensitive earth fault overcurrent element.

Inst. An element with “instantaneous” operation: i.e. having no deliberate time delay.

I/O Abbreviation of “Inputs and Outputs”: Used in connection with the number of optocoupled inputs and output contacts within the relay.

I/P Abbreviation of “Input”.

K1 Slope of the phase circuitry fault function.

K2 Slope of the differential phase element for all the zones.

KCZ Slope of the differential phase element for the Check Zone.

KN1 Slope of the neutral circuitry fault function.

Page 450: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

(SG) 14-4

MiCOM P741, P742, P743

SG

Symbols Explanation

KN2 Slope of the differential neutral element for all the zones.

KNCZ Slope of the differential neutral element for the Check Zone.

KZN The residual compensation factor: Ensuring correct reach for ground distance elements.

LCD Liquid crystal display: The front-panel text display on the relay.

LD Abbreviation of “Level Detector”: An element responding to a current or voltage below its set threshold.

LED Light emitting diode: Red or green indicator on the relay front-panel.

MCB A “miniature circuit breaker”: Used instead of a fuse to protect VT secondary circuits.

N Indication of “Neutral” involvement in a fault: i.e. a ground (earth) fault.

N/A Not applicable.

N/C A normally closed or “break” contact: Often called a “form B” contact.

N/O A normally open or “make” contact: Often called a “form A” contact.

NPS Negative phase sequence.

NXT Abbreviation of “Next”: In connection with hotkey menu navigation.

O/P Abbreviation of “output”.

Opto An optocoupled logic input: Alternative terminology: binary input.

P1 Used in IEC terminology to identify the primary CT terminal polarity: Replace by a dot when using ANSI standards.

P2 Used in IEC terminology to identify the primary CT terminal polarity: The non-dot terminal.

PCB Printed circuit board.

Ph Abbreviation of “Phase”: Used in distance settings to identify settings that relate to phase-phase faults.

Pol Abbreviation of “Polarizing”: Typically the polarizing voltage used in making directional decisions.

PSL Programmable scheme logic: The part of the relay’s logic configuration that can be modified by the user, using the graphical editor within MiCOM S1 software.

PU Abbreviation of “Peripheral Unit” (P742 or P743)

Qx Isolator number x (from 1 to 6).

R A resistance.

RBN Lead burden for the neutral.

RBPh Lead burden for the phases.

Page 451: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

(SG) 14-5

SG

Symbols Explanation

RCT Current Transformer secondary resistance.

REF Restricted earth fault protection.

Rev. Indicates an element responding to a flow in the “reverse” direction.

RMS The equivalent a.c. current: Taking into account the fundamental, plus the equivalent heating effect of any harmonics. Abbreviation of “root mean square”.

RP Abbreviation of “Rear Port”: The communication ports on the rear of the relay.

Rx Abbreviation of “Receive”: Typically used to indicate a communication receive line/pin.

S1 Used in IEC terminology to identify the secondary CT terminal polarity: Replace by a dot when using ANSI standards.

S2 Used in IEC terminology to identify the secondary CT terminal polarity: The non-dot terminal.

SDEF Sensitive Differential Earth Fault Protection.

SEF Sensitive Earth Fault Protection.

T A time delay.

TCS Trip circuit supervision.

TD The time dial multiplier setting: Applied to inverse-time curves (ANSI/IEEE).

TE A standard for measuring the width of a relay case: One inch = 5TE units.

TMS The time multiplier setting applied to inverse-time curves (IEC).

Tx Abbreviation of “Transmit”: Typically used to indicate a communication transmit line/pin.

V Voltage.

Vk IEC knee point voltage of a current transformer.

Vn The rated nominal voltage of the relay: To match the line VT input.

VN Neutral voltage displacement or residual voltage.

VN>1 First stage of residual (neutral) overvoltage protection.

VN>2 Second stage of residual (neutral) overvoltage protection.

Vres. Neutral voltage displacement or residual voltage.

VT Voltage transformer.

VTS Voltage transformer supervision: To detect VT input failure.

Vx An auxiliary supply voltage: Typically the substation battery voltage used to power the relay.

Page 452: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

(SG) 14-6

MiCOM P741, P742, P743

SG

Logic Symbols not used

Symbols Explanation

BAR Block auto-reclose signal.

BN> Neutral over susceptance protection element:

Reactive component of admittance calculation from neutral current and residual voltage.

CLP Cold load pick-up.

CS Check synchronism.

DEF Directional earth fault protection: A directionalised ground fault aided scheme.

Df/dt Rate of change of frequency protection (ROCOF).

Fwd. Indicates an element responding to a flow in the “Forward” direction.

F> An overfrequency element:

Could be labelled 81O in ANSI terminology.

F< An underfrequency element:

Could be labelled 81U in ANSI terminology.

I2> Negative sequence overcurrent protection (NPS element).

I2pol Negative sequence polarizing current.

NVD Neutral voltage displacement: Equivalent to residual overvoltage protection.

PN> Wattmetric earth fault protection:

Calculated using residual voltage and current quantities.

R Gnd. A distance zone resistive reach setting: Used for ground (earth) faults.

RCA Abbreviation of “Relay Characteristic Angle”: The centre of the directional characteristic.

V< An undervoltage element.

V<1 First stage of undervoltage protection: Could be labelled 27-1 in ANSI terminology.

V<2 Second stage of undervoltage protection: Could be labelled 27-2 in ANSI terminology.

V> An overvoltage element.

V>1 First stage of overvoltage protection: Could be labelled 59-1 in ANSI terminology.

V>2 Second stage of overvoltage protection: Could be labelled 59-2 in ANSI terminology.

V0 Zero sequence voltage: Equals one third of the measured neutral/residual voltage.

V1 Positive sequence voltage.

V2 Negative sequence voltage.

V2pol Negative sequence polarizing voltage.

Page 453: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

(SG) 14-7

SG

Symbols Explanation

VA Phase A voltage: Might be phase L1, red phase. or other, in customer terminology.

VB Phase B voltage: Might be phase L2, yellow phase. or other, in customer terminology.

VC Phase C voltage: Might be phase L3, blue phase. or other, in customer terminology.

VCO Voltage controlled overcurrent element.

YN> Neutral overadmittance protection element: Non-directional neutral admittance protection calculated from neutral current and residual voltage.

Z0 Zero sequence impedance.

Z1 Positive sequence impedance.

Z2 Negative sequence impedance.

Page 454: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

(SG) 14-8

MiCOM P741, P742, P743

SG

Logic Timers

Logic Symbols Explanation Time Chart

Delay on pick-up timer, t

Delay on drop-off timer, t

Delay on pick-up/drop-off timer

Pulse timer

Pulse pick-up falling edge

Pulse pick-up raising edge

Latch

Page 455: P74x_EN_M_H54

Symbols and Glossary P74x/EN SG/H54

MiCOM P741, P742, P743

(SG) 14-9

SG

Logic Symbols Explanation Time Chart

Dwell timer

Straight (non latching): Hold value until input reset signal

Page 456: P74x_EN_M_H54

P74x/EN SG/H54 Symbols and Glossary

(SG) 14-10

MiCOM P741, P742, P743

SG

Logic Gates

!"

!"

!"

! "

! "

# $

!"

!"

!"

! "

! "

! "

%# $

# $

"&'(

"

! "

! "

! "

$)*+$,# $

),

!" ),

!" ),

!"

!"

!"

!"

! "

! "

! "

,# $

"

!-

,

,././

-

! -0 &%1

21%121%1

,3

21%1

%1 ..

"

!-

,"

!-

,

4 ,5,3

- ! -0 &%121%1

,3

21%1

%1 ..

21%1

- ! -0 &%121%1

21%1

Page 457: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

IN

INSTALLATION

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 458: P74x_EN_M_H54

P74x/EN IN/H54 Installation

MiCOM P741, P742, P743

Page 459: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-1

IN

CONTENTS

1. RECEIPT OF RELAYS 3 2. HANDLING OF ELECTRONIC EQUIPMENT 4 3. STORAGE 5 4. UNPACKING 6 5. RELAY MOUNTING 7

5.1 Rack mounting 8 5.2 Panel mounting 9

6. RELAY WIRING 10

6.1 Medium and heavy duty terminal block connections 10 6.2 RS485 port 10 6.3 IRIG-B connections (P741 only) 11 6.4 RS232 port 11 6.5 Download/monitor port 11 6.6 Earth connection 11

7. MiCOM P741 - CENTRAL UNIT 12 8. MiCOM P742 – PERIPHERAL UNIT 15 9. MiCOM P743 – PERIPHERAL UNIT 18 10. COMMUNICATION OPTIONS 21

Page 460: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-2

MiCOM P741, P742, P743

IN

BLANK PAGE

Page 461: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-3

IN

1. RECEIPT OF RELAYS Protective relays, although generally of robust construction, require careful treatment prior to installation on site. Upon receipt, relays should be examined immediately to ensure no external damage has been sustained in transit. If damage has been sustained, a claim should be made to the transport contractor and Alstom Grid should be promptly notified.

Relays that are supplied unmounted and not intended for immediate installation should be returned to their protective polythene bags and delivery carton. Section 3 of this chapter gives more information about the storage of relays.

Page 462: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-4

MiCOM P741, P742, P743

IN

2. HANDLING OF ELECTRONIC EQUIPMENT A person’s normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage which, although not always immediately apparent, will reduce the reliability of the circuit. This is particularly important to consider where the circuits use complementary metal oxide semiconductors (CMOS), as is the case with these relays.

The relay’s electronic circuits are protected from electrostatic discharge when housed in the case. Do not expose them to risk by removing the front panel or printed circuit boards unnecessarily.

Each printed circuit board incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to remove a printed circuit board, the following precautions should be taken to preserve the high reliability and long life for which the relay has been designed and manufactured.

1. Before removing a printed circuit board, ensure that you are at the same electrostatic potential as the equipment by touching the case.

2. Handle analogue input modules by the front panel, frame or edges of the circuit boards. Printed circuit boards should only be handled by their edges. Avoid touching the electronic components, printed circuit tracks or connectors.

3. Do not pass the module to another person without first ensuring you are both at the same electrostatic potential. Shaking hands achieves equipotential.

4. Place the module on an anti-static surface, or on a conducting surface which is at the same potential as yourself.

5. If it is necessary to store or transport printed circuit boards removed from the case, place them individually in electrically conducting anti-static bags.

In the unlikely event that you are making measurements on the internal electronic circuitry of a relay in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist straps should have a resistance to ground between 500kΩ to 10MΩ. If a wrist strap is not available you should maintain regular contact with the case to prevent a build-up of electrostatic potential. Instrumentation which may be used for making measurements should also be earthed to the case whenever possible.

More information on safe working procedures for all electronic equipment can be found in BS EN 100015: Part 1:1992. It is strongly recommended that detailed investigations on electronic circuitry or modification work should be carried out in a special handling area such as described in the aforementioned British Standard document.

Page 463: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-5

IN

3. STORAGE If relays are not to be installed immediately upon receipt, they should be stored in a place free from dust and moisture in their original cartons. Where de-humidifier bags have been included in the packing they should be retained. The action of the de-humidifier crystals will be impaired if the bag is exposed to ambient conditions and may be restored by gently heating the bag for about an hour prior to replacing it in the carton.

To prevent battery drain during transportation and storage a battery isolation strip is fitted during manufacture. With the lower access cover open, presence of the battery isolation strip can be checked by a red tab protruding from the positive side.

Care should be taken on subsequent unpacking that any dust which has collected on the carton does not fall inside. In locations of high humidity the carton and packing may become impregnated with moisture and the de-humidifier crystals will lose their efficiency.

Prior to installation, relays should be stored at a temperature of between –40˚C to +70˚C.

Page 464: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-6

MiCOM P741, P742, P743

IN

4. UNPACKING Care must be taken when unpacking and installing the relays so that none of the parts are damaged and additional components are not accidentally left in the packing or lost.

Note: With the lower access cover open, the red tab of the battery isolation strip will be seen protruding from the positive side of the battery compartment. Do not remove this strip because it prevents battery drain during transportation and storage and will be removed as part of the commissioning tests.

Relays must only be handled by skilled persons.

The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust and excessive vibration. This particularly applies to installations which are being carried out at the same time as construction work.

Page 465: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-7

IN

5. RELAY MOUNTING MiCOM relays are dispatched either individually or as part of a panel/rack assembly.

Individual relays are normally supplied with an outline diagram showing the dimensions for panel cut-outs and hole centres. This information can also be found in the product publication.

Secondary front covers can also be supplied as an option item to prevent unauthorised changing of settings and alarm status. They are available in sizes 40TE (GN0037 001) and 60TE (GN0038 001). Note that the 60TE cover also fits the 80TE case size of the relay.

The design of the relay is such that the fixing holes in the mounting flanges are only accessible when the access covers are open and hidden from sight when the covers are closed.

If a P991 or MMLG test block is to be included, it is recommended that, when viewed from the front, it is positioned on the right-hand side of the relay (or relays) with which it is associated. This minimises the wiring between the relay and test block, and allows the correct test block to be easily identified during commissioning and maintenance tests.

P0146XXb

FIGURE 1: LOCATION OF BATTERY ISOLATION STRIP

If it is necessary to test correct relay operation during the installation, the battery isolation strip can be removed but should be replaced if commissioning of the scheme is not imminent. This will prevent unnecessary battery drain during transportation to site and installation. The red tab of the isolation strip can be seen protruding from the positive side of the battery compartment when the lower access cover is open. To remove the isolation strip, pull the red tab whilst lightly pressing the battery to prevent it falling out of the compartment. When replacing the battery isolation strip, ensure that the strip is refitted as shown in Figure 1, i.e. with the strip behind the battery with the red tab protruding.

Page 466: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-8

MiCOM P741, P742, P743

IN

5.1 Rack mounting

MiCOM relays may be rack mounted using single tier rack frames (our part number FX0121 001), as illustrated in Figure 2. These frames have been designed to have dimensions in accordance with IEC60297 and are supplied pre-assembled ready to use. On a standard 483mm (19”) rack system this enables combinations of widths of case up to a total equivalent of size 80TE to be mounted side by side.

The two horizontal rails of the rack frame have holes drilled at approximately 26mm intervals and the relays are attached via their mounting flanges using M4 Taptite self-tapping screws with captive 3mm thick washers (also known as a SEMS unit). These fastenings are available in packs of 5 (our part number ZA0005 104).

Note: Conventional self-tapping screws, including those supplied for mounting MIDOS relays, have marginally larger heads which can damage the front cover moulding if used.

Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the tier.

P0147XXb

FIGURE 2: RACK MOUNTING OF RELAYS

Relays can be mechanically grouped into single tier (4U) or multi-tier arrangements by means of the rack frame. This enables schemes using products from the MiCOM and MiDOS product ranges to be pre-wired together prior to mounting.

Where the case size summation is less than 80TE on any tier, or space is to be left for installation of future relays, blanking plates may be used. These plates can also be used to mount ancillary components. Table 1 shows the sizes that can be ordered.

Further details on mounting MiDOS relays can be found in publication R7012, “MiDOS Parts Catalogue and Assembly Instructions”.

Case size summation Blanking plate part number

5TE GJ2128 001

10TE GJ2128 002

15TE GJ2128 003

20TE GJ2128 004

25TE GJ2128 005

30TE GJ2128 006

35TE GJ2128 007

40TE GJ2128 008

TABLE 1: BLANKING PLATES

Page 467: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-9

IN

5.2 Panel mounting

The relays can be flush mounted into panels using M4 SEMS Taptite self-tapping screws with captive 3mm thick washers (also known as a SEMS unit). These fastenings are available in packs of 5 (our part number ZA0005 104).

Note: Conventional self-tapping screws, including those supplied for mounting MIDOS relays, have marginally larger heads which can damage the front cover moulding if used.

Alternatively tapped holes can be used if the panel has a minimum thickness of 2.5mm.

For applications where relays need to be semi-projection or projection mounted, a range of collars are available.

Where several relays are to mounted in a single cut-out in the panel, it is advised that they are mechanically grouped together horizontally and/or vertically to form rigid assemblies prior to mounting in the panel.

Note: It is not advised that MiCOM relays are fastened using pop rivets as this will not allow the relay to be easily removed from the panel in the future if repair is necessary.

If it is required to mount a relay assembly on a panel complying to BS EN60529 IP52, it will be necessary to fit a metallic sealing strip between adjoining relays (Part no GN2044 001) and a sealing ring selected from Table 2 around the complete assembly.

Width Single tier Double tier

10TE GJ9018 002 GJ9018 018

15TE GJ9018 003 GJ9018 019

20TE GJ9018 004 GJ9018 020

25TE GJ9018 005 GJ9018 021

30TE GJ9018 006 GJ9018 022

35TE GJ9018 007 GJ9018 023

40TE GJ9018 008 GJ9018 024

45TE GJ9018 009 GJ9018 025

50TE GJ9018 010 GJ9018 026

55TE GJ9018 011 GJ9018 027

60TE GJ9018 012 GJ9018 028

65TE GJ9018 013 GJ9018 029

70TE GJ9018 014 GJ9018 030

75TE GJ9018 015 GJ9018 031

80TE GJ9018 016 GJ9018 032

TABLE 2: IP52 SEALING RINGS

Further details on mounting MiDOS relays can be found in publication R7012, “MiDOS Parts Catalogue and Assembly Instructions”.

Page 468: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-10

MiCOM P741, P742, P743

IN

6. RELAY WIRING Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label.”

6.1 Medium and heavy duty terminal block connections

Loose relays are supplied with sufficient M4 screws for making connections to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two ring terminals per relay terminal.

If required, Alstom Grid can supply M4 90° crimp ring terminals in three different sizes depending on wire size (see Table 3). Each type is available in bags of 100.

Part number Wire size Insulation colour

ZB9124 901 0.25 – 1.65mm2 (22 – 16AWG) Red

ZB9124 900 1.04 – 2.63mm2 (16 – 14AWG) Blue

ZB9124 904 2.53 – 6.64mm2 (12 – 10AWG) Uninsulated*

TABLE 3: M4 90° CRIMP RING TERMINALS

* To maintain the terminal block insulation requirements for safety, an insulating sleeve should be fitted over the ring terminal after crimping.

The following minimum wire sizes are recommended:

− Current Transformers 2.5mm2

− Auxiliary Supply, Vx 1.5mm2

− RS485 Port See separate section

− Other circuits 1.0mm2

Due to the limitations of the ring terminal, the maximum wire size that can be used for any of the medium or heavy duty terminals is 6.0mm2 using ring terminals that are not pre-insulated. Where it required to only use pre-insulated ring terminals, the maximum wire size that can be used is reduced to 2.63mm2 per ring terminal. If a larger wire size is required, two wires should be used in parallel, each terminated in a separate ring terminal at the relay.

The wire used for all connections to the medium and heavy duty terminal blocks, except the RS485 port, should have a minimum voltage rating of 300Vrms.

It is recommended that the auxiliary supply wiring should be protected by a 16A high rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits must never be fused. Other circuits should be appropriately fused to protect the wire used.

6.2 RS485 port

Connections to the RS485 port are made using ring terminals. It is recommended that a 2 core screened cable is used with a maximum total length of 1000m or 200nF total cable capacitance. A typical cable specification would be:

− Each core: 16/0.2mm copper conductors PVC insulated

− Nominal conductor area: 0.5mm2 per core

− Screen: Overall braid, PVC sheathed

Page 469: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-11

IN

6.3 IRIG-B connections (P741 only)

The IRIG-B input and BNC connector have a characteristic impedance of 50Ω. It is recommended that connections between the IRIG-B equipment and the relay are made using coaxial cable of type RG59LSF with a halogen free, fire retardant sheath.

6.4 RS232 port

Short term connections to the RS232 port, located behind the bottom access cover, can be made using a screened multi-core communication cable up to 15m long, or a total capacitance of 2500pF. The cable should be terminated at the relay end with a 9-way, metal shelled, D-type male plug.

6.5 Download/monitor port

Short term connections to the download/monitor port, located behind the bottom access cover, can be made using a screened 25-core communication cable up to 4m long. The cable should be terminated at the relay end with a 25-way, metal shelled, D-type male plug.

6.6 Earth connection

Every relay must be connected to the local earth bar using the M4 earth studs in the bottom left hand corner of the relay case. The minimum recommended wire size is 2.5mm2 and should have a ring terminal at the relay end. Due to the limitations of the ring terminal, the maximum wire size that can be used for any of the medium or heavy duty terminals is 6.0mm2 per wire. If a greater cross-sectional area is required, two parallel connected wires, each terminated in a separate ring terminal at the relay, or a metal earth bar could be used.

Note: To prevent any possibility of electrolytic action between brass or copper earth conductors and the rear panel of the relay, precautions should be taken to isolate them from one another. This could be achieved in a number of ways, including placing a nickel-plated or insulating washer between the conductor and the relay case, or using tinned ring terminals.

Before carrying out any work on the equipment, the user should be familiar with the contents of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section and the ratings on the equipment rating label.”

Page 470: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-12

MiCOM P741, P742, P743

IN

7. MiCOM P741 - CENTRAL UNIT TERM

INA

LBLO

CK

DETA

IL

EA

CH

TERM

INATIO

NA

CC

EPTS:-

12

2x

M4

RIN

GTERM

INA

LS

17

18

Connections

for

I/O

board

s

12

OFF

HO

LES

Dia

.3.4

FLU

SH

MO

UN

TIN

G

PA

NEL

CU

T-O

UT

DETA

IL.

142.4

5116.5

574.9

159.0

62.0

155.4

408.9

129.5

4.5

168.0

TERM

INA

LSC

REW

S:

M4

x7

BRA

SS

CH

EESE

HEA

DSC

REW

SW

ITH

MO

UN

TIN

GSC

REW

S:

M4

x12

SEM

UN

ITSTEEL

TH

REA

DFO

RM

ING

SC

REW

.

30.0

LO

CK

WA

SH

ERS

PRO

VID

ED

.

FRO

NT

VIE

WW

ITH

AC

CESS

CO

VERS

OPEN

406.9

413.2

177.0

SEC

ON

DA

RY

CO

VER

(WH

EN

FIT

TED

)

240.0

INC

L.W

IRIN

G

SID

EVIE

W

157.5

MA

X.

TYPE

OF

FIB

RE

OPTIC

CO

NN

EC

TO

R:

ST

P3713E

Nc

CH

1

TX

RX

TX

CH

2RX

CH

3RX

CH

4

TX

TX

RX

EA

CH

TERM

INATIO

NA

CC

EPTS:-

ST

CO

NN

EC

TO

R/

MU

LTI-

MO

DE

FIB

RE

Connections

for

com

munic

ation

board

s

VI V

SE

RN

o.

SE

RN

o.

DIA

GN

o.

DIA

GN

o.

SK

1S

K2

SK

3

50/6

0H

z50

/60

Hz

Vx n

V

An

V

TR

IP

=E

NT

ER

=E

NT

ER

OU

TO

FS

ER

VIC

EO

UT

OF

SE

RV

ICE

HE

ALT

HY

HE

ALT

HY

=R

EA

D=

RE

AD

=C

LE

AR

=C

LE

AR

AL

AR

M

4 5321

9 10

876

P7

41

SC

RA

PV

IEW

SC

RA

PV

IEW

SH

OW

ING

AC

CE

SS

SH

OW

ING

AC

CE

SS

CO

VE

RC

LO

SE

DC

OV

ER

CL

OS

ED

FIGURE 3: MiCOM P741 (80TE) – HARDWARE DESCRIPTION

Page 471: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-13

IN

1T

O7

CO

MM

UN

ICA

TIO

NB

OA

RD

S

OP

TIO

NA

LB

OA

RD

CO

-PR

OC

ES

SO

RB

OA

RD

PO

WE

RS

UP

PLY

MO

DU

LE

P3712E

Nc

LO

GIC

AL

OU

TP

UT

CO

NTA

CT

BO

AR

D

LO

GIC

AL

INP

UT

CO

NTA

CT

BO

AR

D

AG

BC

DE

FH

JK

TX

RX

SK

6

LIN

K

AC

TIV

ITY

00.02.84.9F.FF.90

R

20148098

xW

ork

s

IRIG

-B12x

IRIG

-B12x

Win

dR

iverR

RX

CH

1

RX

CH

2

TX

L

TX

MN

15

13

17

16

18

12

14

5 7 9 11

8 1064

1 3

2

15

13

17

16

18

12

14

5 7 9 11

8 1064

1 3

2

15

13

17

16

18

12

14

5 7 9 11

8 1064

1 3

2

FIGURE 4: MiCOM P741 (80TE) – REAR VIEW

Page 472: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-14

MiCOM P741, P742, P743

IN

P0538E

Nc

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

21

to24

PU

*21

to24

PU

*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

17

to20

PU

*17

to20

PU

*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

13

to16

PU

*13

to16

PU

*

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

9to

12

PU

*9

to12

PU

*

TX

2T

X2

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

Positio

nB

Positio

nB

5to

8P

U*

5to

8P

U*

1to

4P

U*

1to

4P

U*

Positio

nA

Positio

nA

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CU

RR

DIF

FC

UR

RD

IFF

TX

4T

X4

RX

4R

X4

RX

2

RX

3

TX

3

TX

2

RX

1

TX

1

RX

3

RX

4

TX

4

TX

3

RX

2

RX

2

RX

3

TX

3P

ositio

nF

Positio

nF

TX

2

TX

1

RX

1

RX

3

RX

4

TX

4

TX

3

RX

2

Positio

nE

Positio

nE

CO

NN

EC

TIO

N

OP

TO

5O

PT

O5

OP

TO

7O

PT

O7

OP

TO

6O

PT

O6

OP

TO

8O

PT

O8

OP

TO

4O

PT

O4

OP

TO

1O

PT

O1

OP

TO

2O

PT

O2

OP

TO

3O

PT

O3

CO

MM

ON

+

K8

+

RX

1

TX

1

K18

K17

+

K12

K16

K15

K14

K13

+ --

K11

K10

K9

+ --

Positio

nD

Positio

nD

RX

1

TX

1

TX

4

RX

4

RX

3

RX

1

RX

2

TX

3

TX

2

TX

1

RX

4

MiC

OM

P7

41

(PA

RT

)M

iCO

MP

74

1(P

AR

T)

K4

K6

K7

K5

+ -+ -

K2

K3

K1

+ --

RX

3

TX

4

TX

3P

ositio

nC

Positio

nC

TX

2

RX

2

RX

1

TX

1

AC

OR

DC

AC

OR

DC

V

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

9-W

AY

&2

5-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T9

-WA

Y&

25

-WA

YF

EM

AL

ED

-TY

PE

SO

CK

ET

2.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G1

0P

x4

00

12

.F

OR

CO

MM

SO

PT

ION

SS

EE

DR

AW

ING

10

Px4

00

1

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

AU

XS

UP

PLY

AU

XS

UP

PLY

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

48V

DC

FIE

LD

48V

DC

FIE

LD

NO

TE

1.

NO

TE

1.

x

EA

RT

H

*

-L9

-

CA

SE

L10

++ +L7

L8

L2

CO

MM

S

NO

TE

2N

OT

E2

MiC

OM

P7

41

(PA

RT

)M

iCO

MP

74

1(P

AR

T)

J1

J12

RE

LA

Y6

RE

LA

Y8

-L1

J18

RE

LA

Y7

J15

J16

J17

J13

J14

*

J7

RE

LA

Y5

RE

LA

Y4

J10

J11

J9

J8

RE

LA

Y2

RE

LA

Y3

RE

LA

Y1

J4

J5

J6

J2

J3

CO

NTA

CT

WA

TC

HD

OG

WA

TC

HD

OG

CO

NTA

CT

L11

L14

L12

L13

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

25

to28

PU

*25

to28

PU

*

CU

RR

DIF

FC

UR

RD

IFF

FIB

RE

OP

TIC

FIB

RE

OP

TIC

Positio

nG

Positio

nG

TX

4

RX

4

RX

3

RX

2

TX

3

TX

2

RX

1

TX

1

FIGURE 5: MiCOM P741 (80TE) – WIRING DESCRIPTION

Page 473: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-15

IN

8. MiCOM P742 – PERIPHERAL UNIT

20

0.0

24

0.0

INC

L.

WIR

ING

30

.0

15

7.5

MA

X.

SEC

ON

DA

RY

CO

VER

(WH

EN

FIT

TED

)

8O

FF

HO

LES

3.4

10

.35

18

1.3

23

.31

55

.4

15

9.0

16

8.0

20

2.0

17

7.0

20

6.0

4.5

EA

CH

TERM

INATIO

NA

CC

EPTS:-

2x

M4

RIN

GTERM

INA

LS

HEA

VY

DU

TY

FLU

SH

MO

UN

TIN

GPA

NEL

CU

T-O

UT

DETA

IL

TERM

INA

LBLO

CK

DETA

IL

AN

ALO

G&

I/O

BO

ARD

S

1

18

2

17

161

19

3 24

18

SID

EVIE

W

MO

UN

TIN

GSC

REW

S:

M4

x1

2SEM

UN

ITSTEEL

TH

REA

DFO

RM

ING

SC

REW

.

TERM

INA

LSC

REW

S:

M4

x6

STEEL

CO

MBIN

ATIO

NPA

NH

EA

DM

AC

HIN

ESC

REW

.

FRO

NT

VIE

WW

ITH

AC

CESS

CO

VERS

OPEN

MED

IUM

DU

TY

TYPE

OF

FIB

RE

OPTIC

CO

NN

EC

TO

R:

ST

4

P3

71

4E

Nc

CH

1

TX

RX

TX

CH

2RX

EA

CH

TERM

INATIO

NA

CC

EPTS:-

ST

CO

NN

EC

TO

R/

MU

LTI-

MO

DE

FIB

RE

TERM

INA

LBLO

CK

DETA

IL

CO

PRO

CESSO

RBO

ARD

SC

RA

PV

IEW

SH

OW

ING

AC

CE

SS

CO

VE

RC

LO

SE

D

P7

42

SE

RN

o.

DIA

GN

o.

VI Vx nn

50/6

0H

z

V

V

A

V

=R

EA

D

CLE

AR

=E

NT

ER

EN

TE

R=

TR

IP

OU

TO

FS

ER

VIC

E

HE

ALT

HY

ALA

RM

FIGURE 6: MiCOM P742 (40TE) – HARDWARE DESCRIPTION

Page 474: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-16

MiCOM P741, P742, P743

IN

CO

PR

OC

ES

SO

RB

OA

RD

(Co

nn

exio

nto

CU

via

op

tica

lfib

re)

CO

PR

OC

ES

SO

RB

OA

RD

(Co

nn

exio

nto

CU

via

op

tica

lfib

re)

PO

WE

RS

UP

PLY

PO

WE

RS

UP

PLY

AN

AL

OG

INP

UT

MO

DU

LE

AN

AL

OG

INP

UT

MO

DU

LE

16

LO

GIC

AL

INP

UT

S1

6L

OG

ICA

LIN

PU

TS

8LO

GIC

AL

OU

TPU

TS

8LO

GIC

AL

OU

TPU

TS

16

17

24

18

13

14

10

11

78

2322

1512

21

9

45

12

A

2019

63

BC

D

2

EF

18

17

15

12

1311

16

14

975

108

31

64

P3

71

0E

Na

18

17

15

12

1311

16

14

975

108

31

64

18

17

15

12

1311

16

14

975

108

31

64

18

17

15

12

1311

16

14

975

108

31

64

22

2

CH

1

TX

RX

TX

CH

2RX

FIGURE 7: MiCOM P742 (40TE) – REAR VIEW

Page 475: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-17

IN

P2

S2

S1

P1

CBA

(2)

AI

(2)

BI

(2)

CI

IN

NO

TE

2.

NO

TE

2.

C.T

.S

HO

RT

ING

LIN

KS

C.T

.S

HO

RT

ING

LIN

KS

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1A

CO

NN

EC

TE

DA

ND

AR

ET

YP

ICA

LO

NLY

.2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1A

CO

NN

EC

TE

DA

ND

AR

ET

YP

ICA

LO

NLY

.

9-W

AY

&2

5-W

AY

FE

MA

LE

D-T

YP

ES

OC

KE

T9

-WA

Y&

25

-WA

YF

EM

AL

ED

-TY

PE

SO

CK

ET

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

(b)

(a)

B1

B2

B3

MiC

OM

P742

(PA

RT

)M

iCO

MP

742

(PA

RT

)M

iCO

MP

742

(PA

RT

)M

iCO

MP

742

(PA

RT

)

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

*

RE

LA

Y8

RE

LA

Y7

CO

NTA

CT

CO

NTA

CT

TR

IPB

TR

IPB

TR

IPA

WA

TC

HD

OG

WA

TC

HD

OG

CO

NTA

CT

CO

NTA

CT

WA

TC

HD

OG

WA

TC

HD

OG

CO

MM

ON

CO

NN

EC

TIO

NC

ON

NE

CT

ION

+ - +- - +- +

PH

AS

ER

OTA

TIO

NP

HA

SE

RO

TA

TIO

N

A

CB

+-

C2

OP

TO

4O

PT

O4

OP

TO

1O

PT

O1

OP

TO

2O

PT

O2

OP

TO

3O

PT

O3

+-

A6

+

A4

A5

-- +

A1

A3

A2

+-

48V

DC

FIE

LD

48V

DC

FIE

LD

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

AU

XS

UP

PLY

AU

XS

UP

PLY

AC

OR

DC

AC

OR

DC

xV

DIR

EC

TIO

NO

FF

OR

WA

RD

CU

RR

EN

TF

LO

WD

IRE

CT

ION

OF

FO

RW

AR

DC

UR

RE

NT

FL

OW

C1

EA

RT

HC

AS

E

B4

B5

B6

B7

B8

B9

B10

B11

B12

TR

IPC

RE

LA

Y4

RE

LA

Y5

TX

1

RX

1

RX

2

TX

2

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

CU

RR

DIF

FC

UR

RD

IFF

OP

TO

11

OP

TO

11

OP

TO

10

OP

TO

10

OP

TO

14

OP

TO

14

OP

TO

13

OP

TO

13

OP

TO

12

OP

TO

12

OP

TO

16

OP

TO

16

OP

TO

15

OP

TO

15

OP

TO

9O

PT

O9

CO

NN

EC

TIO

NC

OM

MO

N

OP

TO

5O

PT

O5

OP

TO

8O

PT

O8

OP

TO

7O

PT

O7

OP

TO

6O

PT

O6

+ ++ ---+-

+-

C3

C4

+-

C6

C5

+-

C8

C7

+ -+ -+-

*

CO

MM

S

NO

TE

3N

OT

E3

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001.

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G10P

x4001.

RE

LA

Y6

RE

LA

Y6 P0

53

9E

Nc

E14

D18

D15

D16

D17

D14

D13

D11

D12

D10

D9

D1

D3

D4

D5

D6

D2

D7

D8

E13

E12

E12

E11

E10

E9

E7

E8

E1

E2

C1

8

C1

7

C15

C14

C1

3

C16

C11

C1

0

C12

C9

A12

A13

A14

A15

A18

A17

A16

A10

A11

A9

A7

A8

FIGURE 8: MiCOM P742 (40TE) – WIRING DESCRIPTION

Page 476: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-18

MiCOM P741, P742, P743

IN

9. MiCOM P743 – PERIPHERAL UNIT

TERM

INA

LSC

REW

S:

M4

x6

STEEL

CO

MBIN

ATIO

NPA

NH

EA

D

MO

UN

TIN

GSC

REW

S:

M4

x1

2SEM

UN

ITSTEEL

TH

REA

DFO

RM

ING

SC

REW

.

SID

EVIE

W

MA

CH

INE

SC

REW

.

FLU

SH

MO

UN

TIN

GPA

NEL

CU

T-O

UT

DETA

IL

FRO

NT

VIE

W

SEC

ON

DA

RY

CO

VER

(WH

EN

FIT

TED

)

24

0.0

INC

L.

WIR

ING

30

.0

15

7.5

MA

X.

12

OFF

HO

LES

15

9.0

16

8.0

10

.31

55

.41

29

.5

30

5.5

11

6.5

52

3.2

51

42

.45

30

3.5

17

7.0

30

9.6

4.5

TYPE

OF

FIB

RE

OPTIC

CO

NN

EC

TO

R:

ST

P3

71

5E

Nc

EA

CH

TERM

INATIO

NA

CC

EPTS:-

2x

M4

RIN

GTERM

INA

LS

HEA

VY

DU

TY

TERM

INA

LBLO

CK

DETA

IL

AN

ALO

G&

I/O

BO

ARD

S 1

18

2

17

161

19

3 24

18

MED

IUM

DU

TY

4C

H1

TX

RX

TX

CH

2RX

EA

CH

TERM

INATIO

NA

CC

EPTS:-

ST

CO

NN

EC

TO

R/

MU

LTI-

MO

DE

FIB

RE

TERM

INA

LBLO

CK

DETA

IL

CO

PRO

CESSO

RBO

ARD

P7

43

SH

OW

ING

AC

CE

SS

SH

OW

ING

AC

CE

SS

CO

VE

RC

LO

SE

DC

OV

ER

CL

OS

ED

SC

RA

PV

IEW

SC

RA

PV

IEW

=C

LE

AR

=C

LE

AR

=E

NT

ER

=E

NT

ER

HE

ALT

HY

=R

EA

D=

RE

AD

OU

TO

FS

ER

VIC

EO

UT

OF

SE

RV

ICE

ALA

RM

TR

IP

5431 2

10

986 7

SK

1S

K2

SE

RN

o.

SE

RN

o.

DIA

GN

o.

DIA

GN

o.

50/6

0H

z50

/60

Hz

VV

A

Vx

In

Vn

V

SK

3

FR

ON

TV

IEW

(WIT

HA

CC

ES

SC

OV

ER

SO

PE

N)

FR

ON

TV

IEW

(WIT

HA

CC

ES

SC

OV

ER

SO

PE

N)

FIGURE 9: MiCOM P743 (60TE) – HARDWARE DESCRIPTION

Page 477: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-19

IN

16

17

18

24

13

14

10

11

78

15

23

12

22

921

A

45

12

620

319

BC

DE

FG

PO

WE

RS

UP

PLY

AN

AL

OG

INP

UT

24

LO

GIC

AL

INP

UT

S16

LO

GIC

AL

OU

TP

UT

S

J

P3711E

Nb

CO

PR

OC

ES

SO

RB

OA

RD

(co

nn

exio

nto

CU

via

op

tic

fib

re)

18

17

15

1311

16

14

12

975

108

31

642

18

17

15

1311

16

14

12

975

108

31

642

18

17

15

1311

16

14

12

975

108

31

642

18

17

15

1311

16

14

12

975

108

31

642

18

17

15

1311

16

14

12

975

108

31

642

18

17

15

1311

16

14

12

975

108

31

642

CH

1

TX

RX

TX

CH

2RX

H

TXAC

TIV

ITY

LIN

K

RXSK

6

00.02.84.9F.FF.90

20148098

VxWorksR

WindRiverR

OP

TIO

NA

LB

OA

RD

FIGURE 10: MiCOM P743 (60TE) – REAR VIEW

Page 478: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-20

MiCOM P741, P742, P743

IN

(2)

AI

(2)

BI

(2)

CI

NO

TE

2.

NO

TE

2.

C.T

.S

HO

RT

ING

LIN

KS

C.T

.S

HO

RT

ING

LIN

KS

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1

AC

ON

NE

CT

ED

AN

DA

RE

TY

PIC

AL

ON

LY.

2.

C.T

.C

ON

NE

CT

ION

SA

RE

SH

OW

N1

AC

ON

NE

CT

ED

AN

DA

RE

TY

PIC

AL

ON

LY.

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

PIN

TE

RM

INA

L(P

.C.B

.T

YP

E)

(b)

(a)

NO

TE

S1.

NO

TE

S1.

CO

NN

EC

TIO

N

OP

TO

24

OP

TO

24

CO

MM

ON

OP

TO

23

OP

TO

23

OP

TO

22

OP

TO

22

OP

TO

21

OP

TO

21

OP

TO

20

OP

TO

20

OP

TO

19

OP

TO

19

OP

TO

18

OP

TO

18

5A

MiC

OM

P7

43

(PA

RT

)M

iCO

MP

74

3(P

AR

T)

MiC

OM

P7

43

(PA

RT

)M

iCO

MP

74

3(P

AR

T)

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

PO

WE

RS

UP

PLY

VE

RS

ION

24-4

8V

(NO

MIN

AL)

D.C

.O

NLY

*

- -++- +

*

EA

RT

HC

AS

E

OP

TO

9O

PT

O9

OP

TO

12

OP

TO

12

OP

TO

13

OP

TO

13

OP

TO

10

OP

TO

10

OP

TO

11

OP

TO

11

+ + +-+-+ ---+-+-+-

+ +-+-+ --

+

D15

D17

D16

D18

+-

D13

D12

D14

D11

+-+-

D10

D9

D8

D7

+-+-

D6

D5

D4

D3

+ +---

B15

OP

TO

8O

PT

O8

+-

B16

OP

TO

7O

PT

O7

+-

B14

+-+-

B18

B17

CO

NN

EC

TIO

NC

OM

MO

N

3.

FO

RC

OM

MS

OP

TIO

NS

SE

ED

RA

WIN

G1

0P

x4

00

13

.F

OR

CO

MM

SO

PT

ION

SS

EE

DR

AW

ING

10

Px4

00

1

CO

MM

SN

OT

E3

NO

TE

3

RE

LA

Y8

RE

LA

Y7

TR

IPB

TR

IPA

WA

TC

HD

OG

CO

NTA

CT

TR

IPC

RE

LA

Y4

RE

LA

Y5

RE

LA

Y6

WA

TC

HD

OG

CO

NTA

CT

F3

F14

F17

F16

F18

F15

F4

F5

F6

F8

F9

F7

F10

F12

F11

F13

G14

F1

F2

G13

G12

G11

TX

1

RX

1

RX

2

TX

2

G10

G9

G7

G8

G1

G2

48V

DC

FIE

LD

48V

DC

FIE

LD

VO

LTA

GE

OU

TV

OLTA

GE

OU

T

AU

XS

UP

PLY

AU

XS

UP

PLY

AC

OR

DC

AC

OR

DC

xV

FIB

RE

OP

TIC

FIB

RE

OP

TIC

CO

MM

UN

ICA

TIO

NC

OM

MU

NIC

AT

ION

CU

RR

DIF

FC

UR

RD

IFF

E12

E17

E18

E13

E15

E14

E16

E1

E7

E8

E10

E11

E9

E2

E3

E5

E4

E6

RE

LA

Y16

RE

LA

Y15

RE

LA

Y13

RE

LA

Y14

RE

LA

Y12

RE

LA

Y10

RE

LA

Y11

RE

LA

Y9

P2

S2

S1

P1

CBA

PH

AS

ER

OTA

TIO

NP

HA

SE

RO

TA

TIO

N

A

CB

DIR

EC

TIO

NO

FF

OR

WA

RD

CU

RR

EN

TF

LO

WD

IRE

CT

ION

OF

FO

RW

AR

DC

UR

RE

NT

FL

OW

1A

5A

1A

5A

1A

5A

A1

A2

A3

A4

A5

A6

A7

A8

A9

I N

1A

A11

A12

A10

OP

TO

3O

PT

O3

OP

TO

2O

PT

O2

OP

TO

1O

PT

O1

OP

TO

4O

PT

O4

B8

B7

B6

B5

B4

B3

B2

B1

B11

OP

TO

6O

PT

O6

B13

B12

OP

TO

5O

PT

O5

B10

B9

OP

TO

17

OP

TO

17

OP

TO

15

OP

TO

15

OP

TO

16

OP

TO

16

OP

TO

14

OP

TO

14

CO

NN

EC

TIO

NC

OM

MO

NC

17

C18

C16

C15

C14

C13

C12

C11

D2

D1

C10

C9

C4

C6

C7

C8

C5

C2

C3

C1

P0

54

0E

Nc

FIGURE 11: MiCOM P743 (60TE) – WIRING DESCRIPTION

Page 479: P74x_EN_M_H54

Installation P74x/EN IN/H54 MiCOM P741, P742, P743

(IN) 15-21

IN

10. COMMUNICATION OPTIONS

100

BA

SE-T

X10

BA

SE-T

/

7 8

100

BA

SE-F

XRX

10 B

ASE

-FL

TX

OR

RJ45 2 4 5 631

RX-

RX+

TX+

TX-

REA

R C

OM

MS

BO

ARD

6 8 9753 4

SK5 1 2

0V

4

(OPT

ION

AL)

IRIG

-B IN

PUT

97 85 64

SK4 2 31

987

N.C

.CTS

RTS

5 6

-0V

N.C

.DTR

#

T

XRX

B

N.C

.

T

XRX

A

-0V

N.C

.

EIA

232

321N

.C.

EIA

485

N.C

.

SK6

CO

MM

UN

ICA

TIO

N(O

PTIO

NA

L)

IRIG

-B IN

PUT

RX (OPT

ION

AL)

FIB

RE O

PTIC

TX

DO

WN

LOA

D

SK2

SK1

DO

WN

LOA

DTE

ST/

9

CTS

RTS

0VRX

7 864 5317 2-9

11,1

2,15

,13,

1419,1

8,22

,25

20,2

1,23

,24

0V

CON

NEC

TED

TX

1 2

NO

T

TO-T

7

COM

MA

ND

DO

-D7

ACK

NO

WLE

DG

E10 16

EXTE

RNA

LRE

SET

DA

TA R

EAD

Y

DA

TA

1

PORT

KB

US

EIA

485/

16 SCN

+18

-17

ETH

ERN

ET B

OA

RD

OR

IRIG

-B B

OA

RD

NO

TE:

FOR

TERM

INA

L B

LOC

K C

ON

NEC

TIO

N

REFE

R TO

REL

EVA

NT

EXTE

RNA

L C

ON

NEC

TIO

N D

IAG

RAM

.

RXD

TXD

N.C

.

N.C

.

N.C

.

RXD

TXD

DCD

DTR

#

N.C

.

SERI

AL

PORT

RTS#

N.C

.

N.C

.

SERI

AL

PORT

EIA

232

# PE

RMA

NEN

TLY

AC

TIV

E

N.C

.

SERI

AL

PORT

EIA

232

OR

IRIG

-B IN

PUT

(OPT

ION

AL)

Sht:

Nex

tSh

t:

Drg

No

:

Issu

e:Re

visi

on

:

Dat

e:

Dat

e:

Nam

e:

Ch

kd:

DO

NO

T SC

ALE

CAD

DA

TA 1

:1 D

IMEN

SIO

NS:

mm

Titl

e:

29/0

3/06

S.W

OO

TTO

N

IRIG

-B in

pu

t ad

ded

to

eth

ern

et c

om

ms.

CD

NR5

944.

10Px

4001

1 -

EXTE

RNA

L C

ON

NEC

TIO

N D

IAG

RAM

: CO

MM

S O

PTIO

NS

MIC

OM

Px4

0 PL

ATF

ORM

G

R PR

ICE

P06

94E

Na

Page 480: P74x_EN_M_H54

P74x/EN IN/H54 Installation (IN) 15-22

MiCOM P741, P742, P743

IN

Page 481: P74x_EN_M_H54

Firmware and Service Manual P74x/EN VH/H54Version History MiCOM P741, P742, P743

VH

FIRMWARE AND SERVICE MANUAL

VERSION HISTORY

Date: 2012 Hardware Suffix: J and K Software Version: 33 Connection Diagrams: 10P740xx (xx = 01 to 07)

Page 482: P74x_EN_M_H54

P74x/EN VH/H54 Firmware and Service Manual Version History

MiCOM P741, P742, P743

Page 483: P74x_EN_M_H54

Firm

ware and S

ervice Manual

P

74x/EN

VH/H

54 Version H

istory

M

iCO

M P

741, P742, P

743

(VH) 16-1

VH

Relay type: P74x …

Software Version

Major Minor

Hardware Suffix

Original Date of Issue Description of Changes S1

Compatibility Technical

Documentation

00 B Feb 2003 Original Issue

First release to production V2.07 P740/EN xx/D22

01 B Jun 2003 Update of default settings in the four languages

Note: All relays have been updated to issue 30 or 31 V2.07 P740/EN xx/D22

02 A1.8 B May 2004 Addition of Courier rear communications

Note: All relays have been updated to issue 30 or 31 V2.10 P740/EN xx/D22

03 A2.1 B May 2004 Check zone blocking during CT saturation

Note: All relays have been updated to issue 30 or 31

V2.10

Patch 03 P740/EN xx/D22

30 A2.2 B Feb 2005 Detection of current disappearance in faster CBF protection V2.10

Patch 30 P740/EN xx/D22

31 C3.4 J or K May 2006

Original Issue

P741 and P743 Evolution with extended User Interface (32 Controls Inputs, 10 Function Keys and 18 tricolour LEDs).

P742 Evolution with new User Interface (32 Controls Inputs).

Control Input status stored in FLASH memory

10 Maintenance Records instead of 5.

V2.12

Patch 31 P740/EN xx/E33

Page 484: P74x_EN_M_H54

P

74x/EN

VH/H

54

Firmw

are and Service M

anual

Version H

istory (VH

) 16-2

MiC

OM

P741, P

742, P743

VH

Relay type: P74x …

Software Version

Major Minor

Hardware Suffix

Original Date of Issue Description of Changes S1

Compatibility Technical

Documentation

31 C3.5 J or K Dec 2006

The Delta I criterion did not block the trip: The 87BB protection trips even if only one variation of current is detected.

Isolators were considered closed when a status alarm occured even when the auxiliary voltage supervision was used. The last position of the isolator is used.

Check zone and circuitry fault with bias characteristic

New mode for circuitry fault and PU error

Different Commissioning modes

V2.13 P740/EN xx/E33

32 C3.7 J or K Jan 2007

Spurious error codes does not appear any more during power up of the P741

The Ethernet board and the Coprocessor board are compatible

The thresholds ID>2, IDCZ>2 or IBiasph> can be set higher than 6kA

Display of MEASUREMENT 2 is MEASUREMENT 2 in Russian language.

V2.13

Patch 32 P740/EN xx/F44

Page 485: P74x_EN_M_H54

Firm

ware and S

ervice Manual

P

74x/EN

VH/H

54 Version H

istory

M

iCO

M P

741, P742, P

743

(VH) 16-3

VH

Relay type: P74x …

Software Version

Major Minor

Hardware Suffix

Original Date of Issue Description of Changes S1

Compatibility Technical

Documentation

33 C3.8 J or K Apr 2007

First events following power up are tagged with the right date & time

When using default PSL ,there is a DR after a 50BF backtrip through an opto input of the CU

The latched Function Key DDB signals are correct on relay power up

Uncompressed Disturbance Record Pre-trigger is calculated correctly

When using MiCOM S1 to connect to relay and then activate Settings group by right clicking on the group, relay does not reboot

If the time delay of the overcurrent protection in PU is set to 0ms, then the overcurrent protection does not mal-trip during its power on.

V2.13

Patch 33 P740/EN xx/G54

Page 486: P74x_EN_M_H54

P

74x/EN

VH/H

54

Firmw

are and Service M

anual

Version H

istory (VH

) 16-4

MiC

OM

P741, P

742, P743

VH

Relay Software Version

31 32 33

31

32

33

Set

ting

File

Sof

twar

e V

ersi

on

Page 487: P74x_EN_M_H54

Firm

ware and S

ervice Manual

P

74x/EN

VH/H

54 Version H

istory

M

iCO

M P

741, P742, P

743

(VH) 16-5

VH

Relay Software Version

31 32 33

31

32

33

PS

L Fi

le S

oftw

are

Ver

sion

Page 488: P74x_EN_M_H54

P

74x/EN

VH/H

54

Firmw

are and Service M

anual

Version H

istory (VH

) 16-6

MiC

OM

P741, P

742, P743

VH

Relay Software Version

31 32 33

31

32

33

Men

u Te

xt F

ile S

oftw

are

Vers

ion

Page 489: P74x_EN_M_H54
Page 490: P74x_EN_M_H54

PXXX Product Description

GRID

Alstom Grid © - ALSTOM 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. Alstom Grid Worldwide Contact Centre www.alstom.com/grid/contactcentre/ Tel: +44 (0) 1785 250 070 www.alstom.com


Recommended