< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 2 of 26
TABLE OF CONTENTS
Sl. No. Title
Sheet No.
1 Site conditions
3
2 Details of Power Source
3
3 Power Supply Distribution System
4
4 Protection - metering, - control
6
5 Substation design
14
6 Equipment design
15
7 Cabling system
20
8 Earthing system
21
9 Lighting system
21
10 Electrical heat tracing system
23
11. Electrical equipment for hazardous Areas 23
12. Statutory Approval 26
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 3 of 26
1.0 SITE CONDITIONS
A. Equipment Design Temperature ( IS 9676) : 42 Deg C
B. Soil Resistivity : As per soil investigation report
C. Minimum Temperature(for battery sizing) : 10 Deg C
D. Elevation above Mean Sea Level : Less than 1000m above mean
sea
level.
E. Relative Humidity : 95 %
F. Seismic Zone : As per IS – 1893
2.0 DETAILS OF POWER SOURCE -- HOLD
2.1 Grid Incomer
A. Name of grid substation : 132kV GIS Switchyard
B. Number of feeders : One no. direct from grid &
through step down trafo.
One no. through 33 kV
GIS switchgear (spare)
C. Length of feeder / conductor size : km/ ___mm2 (Later)
D. Voltage : 33 kV
Frequency : 50 Hz
E. Min/max fault level : kA / kA (Later)
F. Design fault level / BIL : kA / kV (Later)
G. System neutral earthing : Later
H. Minimum load p.f. stipulated by supply authority. : Later
2.2 CPP and its configuration
A. Number / type of captive generators : 02 Gas Turbines +01 Steam
Turbine
B. Generator rating/voltage/power factor : STG-17MW/ 11kV / 0.8 p.f.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 4 of 26
GTG-2x31.5MW / 11kV / 0.8 p.f.
C. Parallel operation with grid : Yes
D. Type of Neutral Earthing : N G T
2.3 Emergency generator
A. Number / type of emergency generator : 03 Nos / Diesel
1 no. for GTG/1 no. for STG
1 no. for each S/S (hold)
B. Generator rating : KVA (min.) - Later
415 V/ 0.8 pf
C. Starting : Auto / Manual
D. Short time paralleling with grid system : No
3.0 POWER SUPPLY DISTRIBUTION SYSTEM
3.1 Voltage and frequency variation.
The following maximum variations shall be considered for equipment:
A. AC System
Voltage : +10%
Frequency : +3 %
B. DC System (at system output terminals)
Electrical Control, Critical Lighting etc. : +10% / -15%
Instrumentation Power Supplies : +10%
3.2 A. Primary HV distribution voltage : 33kV, 50Hz
B. Secondary HV distribution voltage : 6.6kV , 50Hz
C. Primary HV distribution system neutral Earthing : Solidly earthed
D. Secondary HV distribution system neutral Earthing : Resistance earthed
E. Auto/Manual transfer at HV : At 6.6 kV
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 5 of 26
F. Auto/Manual transfer at MV with momentary : At 415V PCC and MCC
Paralleling
G. Continuous Parallel operation of Incomers
- HV (33 kV) : Yes
- HV (6.6 kV) : No
- MV (415V) : No
H. Load shedding : Yes
I. HV motor voltage (above 160 kW) : 6.6kV AC, 50Hz, 3 Ph.
J. MV motor voltage (0.18kW and up to 160kW) : 415V AC, 50Hz, 3 Ph.
K. Power factor improvement capacitors : Later
L. Battery chargers ( Incomer Supply) : 415 V AC, 50Hz, 3 Ph
M. UPS System ( Incomer Supply) : 415 V AC, 50Hz, 3 Ph.
N. AC Lighting/Power Panels and Auxiliary Boards : 415V AC, 50Hz, 3 Ph
O. Welding Receptacles : 415V AC, 50Hz, 3 Ph
P. Bulk loads like Process Heaters etc. : 415V AC, 50Hz, 3 Ph
Q. Normal Lighting/Emergency Lighting : 240V AC, 50Hz,Single Ph.
R. Motors rated below 0.18 kW : 240V AC, 50Hz, Single Ph.
S. Convenience outlets : 240V AC, 50Hz,Single Ph.
T. DC Motor(e.g. emergency lube oil pump motor, etc) : 110V DC
U. MOVs : 415V AC, 50Hz,3Ph
V. Space heater for panels : 240V AC, 50Hz,Single Ph
3.3 A. Normal Instrumentation power supply : Refer Instrumentation design
basis
B. Critical instrumentation power supply : Refer Instrumentation design
basis
C. Instrumentation Shutdown system power supply : Independent system
D. Switchgear control, protection and : 110V DC
Critical lighting power supply
E. Input power supply for Plant communication : 240 V, AC, 50 Hz
System with battery back up
F. Input power supply for Fire alarm system : 240 V AC, 50Hz
with battery backup
G. Power supply to SCADA : 110V DC
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 6 of 26
H Input power supply to Telephone system : 240V AC, 50Hz
With battery backup
4.0 PROTECTION - METERING – CONTROL
4.1 Control Philosophy
A. Protection Relays for Generator / Grid Incomers : On Switchgear Panel /
Control Relay Panel
B. Protection relays for HV switchgear : On Switchgear panel
C. HV Switchgear control : From switchgear / ECS /
From Generator Control and
Monitoring Panel
D. Numerical Protection/Control/Monitoring system for:
i) Grid Incomers : Yes
ii) HV Switchboard : Yes
iii) 415V PMCC/PCC : Yes
iv) 415V MCC : Yes
E. Microprocessor Based system for control interlocks :
And monitoring of Electrical power system
i) Human machine interface system- HMI : Yes
ii) Separate Operator Console : Yes
iii) Separate Engineering Console : Yes
iv) Data concentrator for each Substation : Yes -If relay or switchboard
makes are different (Separate
for HV and MV system)
v) Integration with higher level system : Yes
vi) Communication Protocol For Numerical : Yes
Relays
vii) Location of HMI : Later
viii) Common HMI for HV/MV system : Yes
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 7 of 26
F. Limiting Conditions for Motor Start up
(Starting current limitation or method of starting)
i) HV Motors :As per engineering specification
for motors (case specific for
motor rated beyond 1000kW)
ii) MV Motors :As per Engineering specification
for motors
iii) Method of motor starting
For HV Motors (upto motor 1000kW) : DOL
For HV Motors (Beyond motor 1000kW) : Auto Transformer / Soft start /
Dedicated transformer /
VVFD
For MV Motors (upto motor 160kW) : DOL
G. Type of power isolation for remote transformers located away from HV
substation
i) Push button in transformer bay for tripping : No
remote breaker
ii) Local isolating load break switch panel in : No
switchgear room
iii) Local isolating breaker panel in switchgear : Yes
4.2 Relay protection system
4.2.1 Protection devices for power distribution system shall be as indicated below (Figure
inside bracket refers to note below) √ Applicable
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 8 of 26
HV TRANSFORMER
FEEDER
OUTGOING
BREAKER
INCOMER RELAY DESCRIPTION RELAY
NUMBE R
(SECOND ARY
WINDING VOLTAGE > 3.3 kV
(SECOND ARY
WINDING VOLTAGE
≤ 0.433 kV)
HV
MOTOR
FEEDER
HV PLANT
FEEDER
MV
PCC/ PMCC
HV MV
PCC / PMCC
IDMTL over-current relay
51 √ √ - √ √ √(1) √
IDMTL earth-fault relay 51N √ (2) - - √ √ √ (1) √
51G backup earth-fault relay (secondary neutral)
51G
√ √ - - - - -
Motor protection relay with (50, 50N,46, 49, 50L/R,86,95).
99 - - √ -
√ (3) - -
Instantaneous restricted earth-fault relay (secondary side).
64R
-
X’mer bigger than
2 MVA
- - - - -
Instantaneous over-current relay
50 √ √ - - - - -
Instantaneous earth-fault relay
50N √ (4) √ - - - - -
Differential protection .relay
87 √ (5) - √ (6)
√ (7)
- - -
High speed tripping relay
86 √ √ √ √ √ √ √
Trip circuit supervision relay
95 √ √ √ √ - √ √ (8)
Transformer auxiliary relay
63 √ √ - - - - -
Under-voltage relay with timer .
27/2 - - - - -
√ (9) √ (9)
Check synchronizationrelay
25 - - - - -
√ (10) √ (10)
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 9 of 26
4.2.2 Minimum protection relays for Synchronous generator (GTG/STG), Generator
transformer, grid power supply incomer and Synchronous motors shall be as follows √
Applicable.
RELAY
DESCRIPTION
NEMA
CODE
GENERAT
OR
GENERATOR
TRANSFOR
MER
HV/EHV
INCOM
ER
HV/EHV
TRANSF
ORMER
SYN
MOTOR
Distance protection 21 √
Synchronous check 25 √ √
Under voltage with timer 27 √ √ √
Reverse power 32 √ √
Low power flow 37 √
Loss of excitatior 40 √ √
Negative sequence 46 √ √
Over current 50 √ √
Earth fault relay 50N √ √
Over current 51 √ √
Voltage restrained 51V √ √ √
Earth Fault back up 51G √ √ √
Over current E/F 51N √ √ √
Over voltage with timer 59 √ √
VT failure 60 √ √
Auxiliary relay for transformer -
63TX √ √
Transformer Restricted Earth Fault
64R. √ √
Stator back up earth fault 64G √
Rotor Earth fault 64R √ √
Directional 0/C 67 √
Directional E/F 67N √
Under frequency/df/dt 81 √ √ √
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 10 of 26
Tripping relay 86 √ √ √ √ √
Gen differential 87G √
Gen and Transformer differential
87GT √
Transformer differential 87T √
Feeder differential 87F √
Busbar differential and check
87B/87C
H √
Trip circuit supervision 95 √ √ √ √
Dead bus charging relay 98 √
Over fluxing 99 √
Note: In addition to the above protections Overall Differential Protection for Generator
and Generator transformer shall be provided.
Notes:-
1. In case of HV switchboards with parallel operation of incomers, following
additional relays shall be provided:
A. One set of 87B (bus differential) and 95 B (bus wire supervision) for each bus
section.
B. 67 and 67N (Directional IDMTL over current & earth fault) relays for the
incomers.
2. Instantaneous earth fault (50N) shall be provided only for transformer with delta
primary.
3. For motor feeders rated above 55 kW, 50 elements shall not be provided for
contactor controlled feeders.
4. Directional IDMTL earth fault (67N) shall be provided for transformer with star
primary.
5. For transformers rated 5 MVA and above.
6. For motors rated 1500 KW and above.
7. For critical/long feeders and plant feeders connected to main power generation
and distribution bus. A plant feeder implies outgoing feeders from one
switchboard to another switchboard of same voltage level.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 11 of 26
8. Trip circuit supervision relay 95 shall be provided as part of the numerical relay
for MV feeders wherever numerical relays are provided
9. Wherever auto-transfer feature is provided.
10. For switchgears where continuous or momentary paralleling of incomers is
envisaged, check Synchronizing relay shall be provided
11. 51G and 64R relays shall not be provided for input transformer of VFD system.
12. Bus tie feeders in HV switchboards shall be provided with. 51, 51N, 86 and 95
relays.
13. HV capacitor bank feeders shall be provided with 51, 51N, 59 (over voltage), 60
(neutral Displacement) 86 and 95 relays
14. The following feeders shall be provided with timers for delayed tripping on bus
under voltage while The under voltage relay shall be common for the bus
a. HV and MV capacitor feeders
b. HV and MV breaker controlled motor feeders
c. Contactor controlled motor feeders with DC control supply.
15. One no. DC supply supervision relay (80) shall be provided for each incoming
DC supply to the switchboard.
16. One set of bus differential relays (87B) and bus wire supervision relay (95 B) for
each bus section shall be provided for
a. HV switchboards connected directly to generation buses
b. Remote HV switchboards directly connected to main generation switchboard.
17 In case of numerical relays, all relays shall be comprehensive units including all
protection, metering and control unless other wise specified
18. Under voltage and over voltage along with associated timer shall be part of the
Numerical relays.
19. Auto changeover logic between Incomers and bus coupler shall be built in the
numerical relay.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 12 of 26
20. 2 Nos of 86 relays shall be considered for HV and MV motor rated more than
55KW
21. Breaker control switch shall be hardwired type.
22. Stand by earth fault relay 51G shall be provided in the incomer of switchboard
fed from transformers and transformer and switchboard located remotely.
23. Restricted earth fault relay 64R shall be provided in the incomer of switchboard
fed from transformers having secondary voltage greater than 3.3KV and
secondary winding star connected. .
24. 51V voltage controlled over current relay shall be provided considering the rating
of the outgoing feeders with respect to the Incomer rating generally this relay
shall be provided where primary current of outgoing feeders is exceeding 40% of
the CT primary current of the incomer.
25. 415V DG set rated up to 500KVA shall have 51V, 51G, 40, 46, 86, 95, 80
protections unless other wise agreed with the owner.
26. Generator rated above 500KVA shall be provided with protection 51V, 51G, 40,
46, 86, 95, 80, 64R as minimum. Additional protection shall be provided, which
merit the size and application of the generator in line with manufacturer /
package vendor’s recommendation and governing specifications / data sheets.
27. All relays upto PMCC level shall be numerical type.
4.3 The metering devices in EHV , HV and MV switchboards shall be as below:
Feeder Type A V Hz PF MW MWH Hour MVAR MVAH MVA.
-Run
EHV Incomer √ √ √ √ √ √ - √ √ √
EHV Bus Tie √ - - - - - - - - -
EHV Transformer √ - - - √ √ - - - -
EHV Bus PT - √ - - - - - - - -
HV Incomer √ √ √ √ √ (2) √ - √ (2) √ (2) √ (1,2)
HV Bus Tie √ - - - - - - - - - HV Transformer √ - - - √ √ - - - -
HV Bus PT - √ - - - - - - - - HV plant Feeder √ - - - - √ - - - -
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 13 of 26
HV Motor √ - - - - √ (kWh) √ - - - HV Capacitor √ √ - - - - - √ - - PCC/PMCC Incomer √ √ - √ - √ (kWh) - - - -
PCC/PMCC Bus Tie √ - - - - - - - - -
PCC Bus PT - √ - - - - - - - -
ACB Outgoing √ - - - - √ (kWh) - - - -
MV Motor (> 55 KW) √ - - - - - - - -
MCC/PDB/ASB Incomer
√ √ - - - - - - - -
MCCB/SFU Outgoing √ - - - - √ (kWh) - - - - (>= 250A)
LDB Incomer √ √ - - - √ (kWh) - - - -
DG Set - MV √ √ √ √ √ (KW) √ (kWh) √ - - -
4.4 Metering for generator and Generator transformer shall be according to the table
below. These shall, however, not be limiting.
Meter HV Generator Generator transformer
Ammeter 3nos √ √ Voltmeter with selector switch
√ √
MW meter √ √ MVAR meter √ MVA meter √ MWH meter √ √ MVARH meter √ Power factor √ √ Frequency meter √
NOTE: 1) MVA meter in Grid Incomers shall include maximum demand indication also.
2) MW, MVAR, MVA, MVAH meters shall be provided for only Grid Incomer
feeders.
3) Field ammeters are to be provided for all motors rated above 5.5kW.
4) All metering shall be part of numerical relay in case of electrical system
having numerical relays unless specifically analogue / digital meters asked
for.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 14 of 26
5.0 SUBSTATION DESIGN
5.1 HV/MV Substation
Main/HV MV MCC Room
Elevated with trays in cable cellar Yes Yes No
Elevated with internal trenches No Yes Yes
All top cable entry with trays below
ceiling
No No No
Pressurization against ingress of dust Yes(Note-2)
Yes(Note-2)
No(Note-2)
Air-conditioning for operator room,
UPS, Battery chargers, VFD, ECS,
SCADA and SS-71
Yes Yes No
Roof slab for
Power Transformer
Distribution transformer
Yes
Yes
Yes
Yes
-
HV capacitor bank Yes Yes -
Note: 1. For Main/HV Cables ,internal cable trenches in the cable cellar shall be
considered.
2. Except SS-71 all other substations / MCC room shall be pressurized.
5.2 Specific Equipment Locations
A. Batteries : Separate room in sub-station/control room
B. Battery charger : Air-Conditioned room in Substation /
Control Room
C. Thyristor Controlled Heater Panels/ : Air-conditioned room in Substation
VFD Panels
D. UPS System : Air-conditioned room in control
room /Substation
E. Operator station/SCADA/ECS : Separate Air conditioned room in
substation
F. Fire Alarm Panel : Air conditioned room in Control Room
G. Paging System Equipment : Air conditioned room in Control Room
H. Excitation & control panel : Air conditioned room in Substation
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 15 of 26
for syn. Motor
I. Annunciation panel : Operator room in substation
J. Control relays panel / RTCC panel : Air conditioned room in Substation
K. Lighting Transformer : Switchgear room
6.0 EQUIPMENT DESIGN
6.1 HV Switchboard
A. Execution : Draw out
B. Type : Air insulated
C. Bus bar : Single bus
D. Circuit breaker type : SF6 / Vacuum circuit Breaker
E. Motor Control : Breaker ( 840 kW & above)
Vacuum contactor ( less than 840 kW)
6.2 Current Transformer (CT)/ Potential Transformer (PT)
A. CT Secondary
- Protection : 1A
- Metering : 1A
B. PT Secondary : 110 V AC
Note : Separate CT shall be provided for differential and restricted earth fault
protection relay.
6.3 Transformers (Power / Distribution)
Main power transformer Later OLTC
Generator unit transformer Later Off-circuit
Intermediate power transformer Dyn 11 Off-circuit / OLTC
Dedicated ( e.g. for VFD) As Reqd Off-circuit
Distribution transformer
( =< 2000 KVA)
Dyn 11 Off-circuit
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 16 of 26
6.4 MV Switchboard
A. Executions
i. PCC / PMCC
Breaker panels : Draw out , Single front
Contactor feeders : Draw out , Single/ double front
ii. MCC : Draw out , Single/ double front
iii. PDB /ASB : Draw out, Single/ double front
iv. LDB : Draw out, Single/ double front
v. Motors
PMCC : Above 55 kW and up to 160kW
MCC : Up to and including 55 kW
vi. Type of switchboard for small package : Draw out , Single front, of approved
(AC system, pressurization system etc,) make
B. Motor Starter Type
i. Contactor and switch fuse with overload relay : Upto 22 kW
ii. Contactor, switch fuse and overload relay : Above 22kW Upto 55 kW
relay with CBCT for earth fault protection
iii. Air circuit breaker with motor : Above 55 kW Upto 160 kW
Protection relay
iv. CT for remote metering : Motor rated above 5.5kW
C. Medium Voltage Outgoing Feeder Type
i Switch fuse : Up to 100 A
ii Switch fuse with Contactor and CBCT : Above 100A and up to 400A
for earth fault protection
iii MCCB with Contactor and CBCT : 100A and up to 400A
for earth fault protection
iv MCCB : 250A and up to 400A
v Air circuit breaker with protection relay : Above 400A
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 17 of 26
D. Motor Controls : As per process requirement
i Auto / Manual switch : Control Room/ field / switchgear / control
panel
ii. Local/remote switch : Control Room/ field / switchgear / control
panel
iii. Normal / Standby switch : Control Room/ field / switchgear / control
panel
iv. Process interlock : DCS / PLC / Switchgear
v. Reacceleration equipment : DCS / PLC / Switchgear
vi Control supply for earth fault relay : 110V DC/240V AC
in contactor feeder
vii Control supply for contactor starter : 240V AC , By control transformer
viii Separate transformer for each bus section : Yes
6.5 Motors
Motors High voltage Medium voltage
Enclosure IP55 IP55
Insulation class F (Temp. Rise limited to B)
F (Temp. Rise limited to B)
Terminal box Phase insulated/ Phase separated/ Phase segregated
-
Anti-condensation heater Yes Above 30kW
Additional canopy (outdoor motors)
Yes Yes
FRP Material
Design voltage / frequency variation
± 10%, ±3% ± 10/%, ±3%
Combined voltage / frequency variation
± 10% Any combination of above
± 10% Any combination of above
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 18 of 26
6.6 UPS System
A. Redundancy : 100%
B. Type of redundancy : Dual Redundant type
C. Back-up time : 30 minutes
D. Inverter bypass transformer : Static /Servo Controlled
E. Bypass transfer control : Auto / Manual
F. Battery type : Ni-Cd
G. Separate fault diagnostic unit : Yes/No
H. Type of UPS : IGBT / Transistorized
I. Battery execution : Single upto 600 Ah.
Parallel bank above 600 Ah
J. Spare Margin : 20 %
K. Isolation Trafo at Input and Output : Yes
L. Battery : Single Battery bank with 1 x 100%
loading
6. 7 Communication System
A Plant Communication System : Yes
B. Telephone System : Yes
C. Interface of communication system with FA system. : Yes
D. Interface with PA and Telephone System : Yes
E. Battery type : Ni-Cd
F. Battery backup time for telephone system : 60 Minutes
G. Battery backup time for Plant communication System: 60 minutes
6.8 Fire Detection & Alarm System
A. Type : Analogue addressable
B. Name of building to be provided with detectors : Sub-station, control rooms
Major non-plant buildings
C. Type of manual call point : With telephone facility
D. Detection System : Break Glass / Smoke
and Temp. Detector.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 19 of 26
E. Battery back up time : 48 hrs
F. Qty of siren and location : Later
G. Power supply for siren : Uninterrupted
H. Siren range : Later
6.9 DC System
A. Battery type
i) Switchgear Protection, Control & critical lighting : Ni-Cd
ii) Instrumentation System, DC System : Ni-Cd
iii) Diesel Engine Starting : Lead Acid Type
iv) DC Motors : Later
v) Fire alarm system : Ni-Cd
vi) Plant communication system : Ni-Cd
vii) Telephone system : Ni-Cd
B. Battery back up time
i) Switchgear Protection & Control : 120 Minutes
ii) DC Motors : Later
iii) Instrumentation : 30 Minutes
6.10 MV /HV Variable Frequency Drive
i) Type of inverter : Current / Voltage
ii) Number of pulse : Minimum 12 Pulse
iii) By pass feature required : Yes
iv ) VFD rated output voltage : Later
6.11 Cables
The power and control cables shall have the following minimum cross sectional areas:
a) Medium voltage power cable : 16 mm2 (Al.)/ 2.5mm2 (Cu)
b) Control cables : 2.5 mm2 (Copper)
c) Lighting : 2.5 mm2 (Copper)
d) Communication system : 0.9 mm dia (Copper)
e) Fire alarm cables : 1.5 mm2 (Copper)
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 20 of 26
Note: 1) For lighting inside the buildings, minimum1.5 mm2 copper conductor, PVC
insulated wire shall be used in conduit system (for circuit and point
wiring), with proper colour coding. 2) All power cables upto 10 mm2 shall be copper. 3) Cable sizes are of equipment manufacturer indicative only and these
shall be finalised as per the communication of the equipment manufacturer
7.0 CABLING SYSTEM
7.1 Cable details
Design Criteria High Voltage 415 Volt
Loads located beyond 1km Cable Cable
Loads located 200-1000 m 1 -core cable/ 3-core cable
1-core cable/ 3 & 31/2-core cable
Loads located up to 200 m Cable Cable / Bus trunking
Load beyond 1kA rating Bus duct /1 core cable Bus duct /1 core cable
Recommended limiting size of multi-core cable (mm2)
300 300
Short-circuit withstand time (seconds)
0.3(Outgoing)/0.60 (Plant)/ 1.0 (Incomer)
N.A.
Insulation voltage grade Earthed for 33kV and Unearthed ( Rest)
Earthed
Type of cable insulation XLPE XLPE
Type of cable insulation during Later -
Fire survival (Resistant ) cable Fire pump Fire proof MOV Plant communication
No - -
No No No
Armoured cables inside the substation
Yes Yes
7.2 Cabling System
A. Process area : RCC trench
B. Offsite paved area : Above Ground cable tray on
sleeper/Overhead rack / RCC
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 21 of 26
trench
C. Offsite unpaved area : Above Ground cable tray (on
sleeper / Overhead rack) /
directly buried.
D Type of cable trays : Galvanized prefabricated
F. Road Crossings for underground cables : PVC Pipes / Cable culvert
G. Road Crossings for above ground cables : Overhead cable bridge/culvert
Note: Plant communication, fire alarm and telephone cables shall be laid in
overhead cable trays / instrumentation trenches as far possible. In case
these are not available, cable shall be laid along berm of the roads.
8.0 EARTHING SYSTEM
A. Earth electrode :GI Pipe B. Main earth loop material :GI strip
C. Substation earth loop :GI strip
D. Above Ground Earthing : Copper conductor PVC insulated cable
9.0 LIGHTING SYSTEM
9.1 Supply System
A. LDB at each substation : Yes
B Lighting transformer required : Yes
C. Lighting transformer voltage ratio : 415 / 415V
9.2 Control Philosophy
A. Outdoor Area : Auto / Manual
B. Street lighting : Auto / Manual
C. Outdoor process area : Auto / Manual
D. Process building : Auto / Manual / Centralized / Local
E. Auto control : Synchronous timer / Photocell
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 22 of 26
F. Lamp type for outdoor lighting :HPMV(Normal)/MLL(Emergency)
/Incandescent type for (critical
lighting)
G. ELCB at Incomer of lighting and Power Panels : Yes
H. Lighting switch ON/OFF push button at substation entry : Yes
9.3 AC Emergency Lighting
A. Name of process plants : Later
B. Name of buildings : Later
C. Power supply : From Emergency Generator
9.4 DC Critical Lighting for Escape
A. Name of process plants : Later
B. Name of buildings : Later
C. Power supply : 110 V DC
D. DC lighting for remote buildings : Form 110V DC System
9.5 Wiring Type
A. Process plant / Building / Shed : Armoured cable
B. Large service building : surface conduit
C. Buildings with false ceiling : cables/Surface conduit above
false ceiling
` D. Substation (Switchgear Room) : METSEC channel /
Concealed conduit
E. Substation (Cable Cellar) : Surface Conduit / Armoured
cable
F. Other buildings : Surface cable Armoured
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 23 of 26
9.6 Specific Lighting Requirements
A. Aviation lighting : Yes
B. Type of control gear for HPMV/HPSV lamps : Separate
C. Control gear box location : At accessible level
D. Type of flood light mast : High mast lighting. /Flood
Lights
10.0 ELECTRIC HEAT TRACING SYSTEM
A. System Design Basis. : Product classification / system
approach
.
11.0 ELECTRICAL EQUIPMENT FOR HAZARDOUS AREAS
11.1 The electrical equipment for hazardous areas shall be selected as per lS-.5571 and
petroleum rules. The minimum requirement is summarized below
Equipment ZONE-1 Gas Group
IIA, IIB
ZONE-1 Gas Group
II C
ZONE-2 Gas Group
IIA, IIB
ZONE-2 Gas
Group IIC
MV Motors Ex “d” Ex “d” Ex “e”
Ex “e”
HV Motors Ex “d” / Ex “p” (Refer note-2.9)
Ex “d” / Ex “p” (Refer note-2.9)
Ex “e”
Ex “e”
Push button station
Ex “d” Ex “d” Ex “d” Ex “d”
Motor Starters Ex “d” Ex “d” Ex “d” Ex “d” Plug & Socket Ex “d” Ex “d” Ex “d” Ex “d” Welding Receptacle
Ex “d” Ex “d” Ex “d” Ex “d”
Lighting Fixtures
Light fitting Ex “d” Ex “d” Ex”nR” / Ex”d”
Ex”nR” / Ex”d”
Control Gear Box
Ex “d” Ex “d” Ex”d” Ex”d”
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 24 of 26
Junction Boxes Ex “d” Ex “d” Ex – e /Ex -d
Ex – e /Ex -d
Hand Lamps Ex “d” Ex “d” Ex “d” Ex “d” Light fitting Ex “d” Ex “d” Ex “d” Ex “d”
Transformer Unit
Ex “d” Ex “d” Ex “d” Ex “d”
Plug & Socket Ex “d” Ex “d” Ex “d” Ex “d” Break Glass Unit (Fire Alarm System)
Ex “d” Ex “d” Ex “d” Ex “d”
Lighting panel / power panel
Ex “d” Ex “d” Ex “d” Ex “d”
Transformers Hermetically sealed with surface temperature not exceeding 200°C
Notes:
1.0 The electrical equipment for hazardous areas shall generally be suitable for gas
group llB and temp classification T3 as applicable to the selected type of
explosion protection. In case of hydrogen or hydrocarbon mixtures having
more than 30% hydrogen, the gas group to be considered shall be IIC.
2.0 As additional safety features, the following requirements for electrical
equipment shall be followed:
2.1 All electric motors for agitators/mixers and metering, pumps handling flammable
material shall be flameproof type irrespective of the area being classified as
zone-2 or zone-1
2.2 All electric motors ‘for vertical sump pumps handling flammable material shall
be flameproof type.
2.3 Irrespective of the area classification (whether zone-1 or zone-2), all lighting
fixtures within the storage areas shall be flameproof type.
2.4 Irrespective of the area classification (whether.zone-1 or zone-2), all motors
and lighting fittings within the pump house (station) near the offsite tank farm
and within the loading/unloading gantries shall be of flameproof type.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 25 of 26
2.5 All emergency/critical lighting fixtures and associated junction boxes in
hazardous areas (whether zone-1 and zone-2) shall be flameproof type.
2.6 Even though fired heaters in process units are not considered for area
classification, all electrical equipments associated with fired heaters in process
units shall as a minimum be suitable for installation in Zone-2 area.
2.7 Where air conditioning system is designed considering ammonia as refrigerant,
the room housing air conditioning equipment shall be adequately ventilated to
classify it as safe area for additional safety the following shall be considered
- 100% standby system for ventilation.
- Location of MCC/local panels in adjacent separate room Instrumentation
to be flameproof type or hermetically sealed.
-. AC plant room motors with type e’ protection.
- Lighting in AC plant room suitable for zone-2 area.
2.8 Process Compressor sheds in hazardous area shall be designed to allow
adequate ventilation to allow area classification as Zone-2. Lighting equipment
EOT crane etc in the shed shall be flameproof type. All other electrical
equipment shall be suitable for Zone-1 or Zone-2 area depending on extent of
hazard.
2.9 All motors for hazardous area Zone-1shall be flameproof type. Pressurized
motors may be provided in case flameproof motors for the required rating are
not available.
2.10 Motors fed from variable frequency drive in hazardous area application shall be
type tested as unit with the VFD panel in case of Ex(e) type of motors and
provision for tripping the motor in case temperature rise exceeds the permissible
limits shall be considered for flameproof motors as per relevant standards.
2.11 All 6.6kV motors in hazardous areas (whether zone-1 and zone-2) shall be
Ex”d” type. In specific cases where flameproof motors in required kW
rating and RPM is not available Ex"p" type motor may be acceptable.
< Security Level 2 >
HPCL, Visakh
DESIGN DATA-ELECTRICAL
ISSUED : 17/04/2009 / Rev E JOB NO. : 6261
TOYO ENGINEERING INDIA LTD.
DOC.No. A-6261-098-002 DHT PROJECT Page 26 of 26
2.12 For Zone II, gas Group IIA,IIB and IIC if the offered MV motor is Ex'e' type
then the Risk Assesment for motors according to IS 6381:2004 and
IEC:60079-7(2001) shall be done by the vendor without any implication in
price, Or otherwise Vendor can offer Ex" d ' type motor.
12.0 STATUTORY APPROVAL :-
Statutory Authority for electrical Installation : State Electrical Inspectorate /
Central Electrical Inspectorate
Statutory authority for hazardous area : CCOE