+ All Categories
Home > Documents > Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH...

Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH...

Date post: 10-Aug-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
27
09/10/2015 U.S. Nuclear Reeulatorv Commission Operations Center Event Renort Paop I Part 21 (PAR) Event# 51309. Rep Org: ROTORK CONTROLS Notification Date / Time: 08/11/2015 09:55 (EDT) Supplier: ROTORK CONTROLS Event Date / Time: 07/28/2015 (EDT) Last Modification: 09/10/2015 Region: 1 Docket #: City: ROCHESTER Agreement State: Yes County: License #: State: NY NRC Notified by: PATRICK SHAW Notifications: RAY POWELL Ri1DO HQ Ops Officer: MARK ABRAMOVITZ ANTHONY MASTERS R2DO Emergency Class: NON EMERGENCY ROBERT ORLIKOWSKI R30O 10 CFR Section: BOB HAGAR R4DO 21.21(a)(2) INTERIM EVAL OF DEVIATION PART 21/50.55 REACTORS EMAIL PART-21 NOTIFICATION - MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June 4, 2015, Rotork Controls Inc. opened a formal Part 21 [10 CFR 21.21] investigation into a self-identified anomaly relating to a basic micro switch - Pt No N69-921, description 'V12'. The anomaly is intermittent variation in electrical contact resistance and was first observed during the factory acceptance test of a Rotork safety related NA Range Electric Actuator; also referred to as an electric Valve Operator. "Rotork and the switch manufacturer are currently characterizing switch population contact resistance to establish whether an unsafe condition could exist as defined under 10 CFR 21. * ** UPDATE AT 0958 EDT ON 9/10/2015 FROM PATRICK SHAW TO MARK ABRAMOVITZ ** * The following report was received via e-mail: "Rotork has concluded the investigation and based on test data determine an unsafe condition can exist as defined under 10OCFR21. Testing has established .that a small percentage of the switches supplied against Rotork purchase order P0116932 may exhibit an open circuit condition when operated. A slightly larger percentage of the population may exhibit high contact resistance ranging from 0.5 Ohm to open circuit. The anomaly affects the normally open and normally closed contacts equally. Contact resistance anomalies are random, not permanent, and appear to be unaffected by accumulated cycles. Additionally when a switch is oPerated its electrical state remains constant until the next operation. "Probabilities have been established by resistance measurements and by dynamic testing using voltages
Transcript
Page 1: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

09/10/2015 U.S. Nuclear Reeulatorv Commission Operations Center Event Renort Paop I

Part 21 (PAR) Event# 51309.

Rep Org: ROTORK CONTROLS Notification Date / Time: 08/11/2015 09:55 (EDT)Supplier: ROTORK CONTROLS Event Date / Time: 07/28/2015 (EDT)

Last Modification: 09/10/2015

Region: 1 Docket #:City: ROCHESTER Agreement State: Yes

County: License #:

State: NY

NRC Notified by: PATRICK SHAW Notifications: RAY POWELL Ri1DO

HQ Ops Officer: MARK ABRAMOVITZ ANTHONY MASTERS R2DOEmergency Class: NON EMERGENCY ROBERT ORLIKOWSKI R30O

10 CFR Section: BOB HAGAR R4DO21.21(a)(2) INTERIM EVAL OF DEVIATION PART 21/50.55 REACTORS EMAIL

PART-21 NOTIFICATION - MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE

The following report was received via fax:

'On June 4, 2015, Rotork Controls Inc. opened a formal Part 21 [10 CFR 21.21] investigation into a self-identifiedanomaly relating to a basic micro switch - Pt No N69-921, description 'V12'. The anomaly is intermittent variationin electrical contact resistance and was first observed during the factory acceptance test of a Rotork safety relatedNA Range Electric Actuator; also referred to as an electric Valve Operator.

"Rotork and the switch manufacturer are currently characterizing switch population contact resistance to establishwhether an unsafe condition could exist as defined under 10 CFR 21.

* ** UPDATE AT 0958 EDT ON 9/10/2015 FROM PATRICK SHAW TO MARK ABRAMOVITZ ** *

The following report was received via e-mail:

"Rotork has concluded the investigation and based on test data determine an unsafe condition can exist asdefined under 10OCFR21. Testing has established .that a small percentage of the switches supplied against Rotorkpurchase order P0116932 may exhibit an open circuit condition when operated. A slightly larger percentage of thepopulation may exhibit high contact resistance ranging from 0.5 Ohm to open circuit. The anomaly affects thenormally open and normally closed contacts equally. Contact resistance anomalies are random, not permanent,and appear to be unaffected by accumulated cycles. Additionally when a switch is oPerated its electrical stateremains constant until the next operation.

"Probabilities have been established by resistance measurements and by dynamic testing using voltages

Page 2: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

09/10/2015 U.S. Nuclear Regulatory Commission Operations Center Event Report Page 2•representative of customer applications. The dynamic evaluation predicts an open circuit probability of 0.0008%per operation. To date, no switch failures have been reported from any customer sites. Below are listed all ordersprovided to customers containing V12 switches from the defect batch. Report ER791 provides full details ofRotork's technical investigation."

Notified the R1DO (Gray), R2DO (Shaeffer), R3DO (Pelke), R4DO (Drake), and Part-21 Group (via e-mail).

Page 3: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotor wCotro~s

Rotork Controls, Inc.

675 Mile Crossing Blvd.

Rochester, New York

14624

U.S. Nuclcar Regulatory Commission, tel: +1 585 247 2304Washington, DC 20555-0001 lax: +1 585 247 2308

www.rotork.comnFrom: Patrick A. Shaw, P.E if~ookcr

To: NRC Operations CenterDate: September 9(11, 2015

Subject: Rotork Controls Inc. Part 21 Notification, V12 safety related micro switch, Pt No N69-921

Dear Sir/Madame,

On June 4, 2015 Rotork Controls Inc. opened a formal Pt 2l investigation into a self-identified anomalyrelating to a Basic micro switch - Pt No N69-921, description "V12". The anomaly is intermittentvariation in electrical contact resistance and was first observed during a factory acceptance test of aRotork safety related NA range electric actuator; also referred to as an electric Valve Operator.

On July 28 2015 Rotork Controls Inc. wrote to the U.S.NRC requesting a 40 day extension to the 60day investigation period permitted under 10CFR2 1. The extension was granted and the investigationexpiration date was extended to September 12 th 2015:

Rotork have concluded the investigation and based on test data determine an unsafe condition can existas defined under I10CFR21. Testing has established that a small percentage of the switches suppliedagainst Rotork purchase order P0116932 may exhibit an open circuit condition when operated. Aslightly larger percentage of the population may exhibit high contact resistance ranging from 0.5 Ohmto open circuit. The anomaly affects the normally open and normally closed contacts equally. Contactresistance anomalies are random, not permanent, and appear to be unaffected by accumulated cycles.Additionally when a switch is operated its electrical state remains constant until the next operation.

Probabilities have been established by resistance measurements and by dynamic testing using voltagesrepresentative of customer applications. The dynamic evaluation predicts an open circuit probabilityof 0.0008% per operation. To date, no switch failures have been reported from any customer sites.Below are listed all orders provided to customers containing V12 switches from the defect batch.Report ER791 provides full details of Rotork's technical investigation.

Page 1 of 5

Page 4: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotornControls

Rotork Controls Inc. have provided ER791I so that U.S. Licensees may evaluate each application whercRotork equipment is affected by this Part 21 notification.

Below this letter is a summary pursuant to 10CFR Part 21 .21(d)(4), a list of all actuators & sparecomponents containing V12 switches from P0116932, and a copy of ER791.

Sincerely • /

Patrick A. Shaw, P.EwQuality Assurance ManagerTel (585) 770-1019Patrick.Shaw @ rotork.com

President

Page 2 of 5

Page 5: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwControls

Required informlation as per 10CFR Part 21.21(d)(4) follows:

(i) Name and address of the individual or individuals informing the Commission.

Patrick A. Shaw, P.E.Rotork Controls Inc,675 Mile Crossing Blvd,Rochester, New York14624

(ii) Identification of the facility, the activity, or the basic component supplied for such facilityor such activity within the United States which fails to comply or contains a defect.

Rotork part number N69-921I micro-switch V 12/3252 (RSI104) manufactured by JohnsonElectric (formerly Burgess) during 2013.Rotork Controls Limited P0116932

(iii) Identification of the firm constructing the facility or supplying the basic component whichfails to comply or contains a defect

Rotork Controls LtdBrassmill LaneBath, EnglandBAI 3JQ

(iv) Nature of the defect or failure to comply and the safety hazard which is created or couldbe created by such defect or failure to comply.

In 2013 Johnson Electric changed V12 micro-switches assembly locations. The first batch(P0116932) from the new location was found to contain small particles of plastic casematerial that are loose within the switch housing and may lodge on the contacts. Switchesmanufactured prior to 2013 are not affected and due to batch control traceability withinRotork, switches from the affected batch have been traced.The manufacturer's acceptance criteria for the switch contact resistance is less than 25milliohms. Contact resistance has been found to randomly vary between compliant (lessthan 25 milliohms) to non-compliant (greater than 25 milliohms to occasionally opencircuit).From a sample of 1613 switches, the manufacturer established a 0.11% probability that aswitch may exhibit an open circuit condition when operated. Rotork in-house testing withinactuators, using voltages representative of in-service levels, established a 0.0008%probability that a switch may exhibit an open circuit condition when operated. Loss ofcontinuity is random, not permanent, and low in probability. To date, no V12 switch in-service faults have been reported by the industry.

Page 3 of 5

Page 6: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwControls

(v) The date on which the information of such defect or failure to comply was obtained.

7"h September 2015

(vi) In the case of a basic component which contains a defect or fails to comply, the numberand location of these components in use at, supplied for, being supplied for, or may besupplied for, manufactured, or being manufactured for one or more facilities or activitiessubject to the regulations in this part.

.Row Quantity Serial Number Description Shipped

1 6 851470010101 90NA1 WD 2023VNO 3/12/15

2 18 B53470010301 7NA1E/IWN3 WD 2023VNO 1/28/14

3 12 B54087010101 30NAX1E WD 2023VNO 3/20/14

4 18 B54087010201 30NAX1E WD 2023VN0 3/20/145 12 854177040101 '14NA1E WD 2"021VNO 2/25/14

6 12 854330010101 14NA1E WD 2021VNO 4/25/14

7 NAlE/5E 12SW V12 AOP 5/14/14___ 120 B544440101 (QTY 10) _______

8 6 B544440401 NAlE/SE 65W V12 AOP 12/23/13

9 12 854727010101 14NAIE WD 2021VNO 4/25/14

10 12 854727010201 14NA1E WD 2021VN0 4/25/14

11 12 B54727020101 14NAIE WD 2021VNO 8/5/14

12 12 854727020201 14NA1E WD 2021VNO 8/5/14

13 NA1/5 SWITCH M ECH 3/14/1418 B548420101 (QITY 3)

14 12 856398010101 14NA1E WD 2021VNO 12/29/14

15 12 B56398010201 14NA1E WD 2021VNO 12/29/14

16 18 856515010101 11NAlE WD 2023VNO 12/29/14

17 18 B57239010101 16NA1E WD 2023VNO 3/12/15

18 18 857239010201 16NA1E WD 2023VNO 3/12/15

19 18 B57239010301 16NA1E WD 2023VNO 3/12/15

20 18 857239020101 90NA1E WD 2023VNO 2/9/15

21 MODID 14/16NA5 G/CASE 12/3/14___ 1 8576870101 MAINT KIT POST 78

22 12 013359010101 7NA1E/IWN3 WD 2024VNO 1/17/14

23 6 013385010101 7NA5E WD 2020VNO 12/11/13

24 12 013962010101 7NASE WD 2021VNO 6/4/14

25 12 013962010201 7NA5E WD 2021VNO 6/4/14

26 12 013962010301 7NA5E WD 2021VN0 5/4/14

439 Sum

Page 4 of 5

Page 7: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwControgs

(vii) The corrective act ion. which has beeni, is being, or will be taken; the name of the individual.or organization responsible for the action; and the length of lime that has been or will betaken to complete the action.

By this notification Rotork is notifying all utilities and listing affected customer orders.The manufacturer Johnson Electric has introduced cleanliness checks at applicable stagesof switch assembly. Rotork has already obtained replacement switches and further batchesarc now being manufactured.

(viii) Any advice related to the defect or failure to comply about the facility, activity, or basiccomponent that has been, is being, or will be given to purchasers or licensees.

U.S. Licensees with installed or in storage actuators, switch mechanisms or Add-On-Pak(AOP) spares modules containing VI2 switches identified in section (vi) should evaluatethe impact of a high contact resistance or occasionally open circuit condition on safetyrelated systems.

(ix) In th~e case of an early site permit, the entities to whom an early site permit was

transferred

Not Applicable

Page 5 of 5

Page 8: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorkRotork Controls Limited

Nuclear Engineering Report No.

Page 1 of 20

Approved by Engineering

Date: 9 th September 2015ER791 Issue 1

REVISION SHEETv

ORIGIN

DATE OF ISSUE

TITLE

Privang Jadav

09/09/2015Part 21 Investigation..Intermittent operation of V12 Micro-Switch N69-921

Prepared Checked Approved

Priyang Jadav Stuart Adam Kevin SweetProduct Engineer - Senior Engineer - Engineering Manager -

Nuclear Nuclear Nuclear

Issue No Date Revision By

1 09/09/15 Original PUJ

Page 9: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwRotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

CONTENTS

1. Summary ................................................................................................... 3

2. Deviation Description ..................................................................................... 3

3. Micro-Switch Function .................................................................................... 3

4. Review of Orders Affected................................................................................ 4

5. Root Cause Analysis ....................................................................................... 5

6. Johnson Electric Micro-Switch Testing .................................................................. 6

7. ERA Micro-Switch Testing ............................................................................... 10

8. Rotork In-House testing ................................................................................. 14

9. Conclusion ................................................................................................ 20

Page 10: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotork Pg3of2Rotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

1. Summary

This report documents work performed to support a Part 21 investigation opened by Rotork ControlsInc. ref. tracking number NCR164927. Measurements and tests were performed to establish the

operational reliability of a Rotork safety related micro-switch containing a manufacturing defect. Non-

compliant switches were identified from a batch of 4997 switches supplied to Rotork in 2013 againstpurchase order P0116932. The investigation has confirmed that the potential defect is only attributed

to the aforementioned 4997 switches and that switches orders prior to this are not affected.

1281 switches were supplied to customers prior to detecting the non-compliance. A percentage were

supplied to North American customers by Rotork Controls Inc. 3716 switches in stock at Rotork Ltd.

were returned to the supplier for analysis. From the 3716 switches, 1613 switches were tested by the

supplier, who established a 0.11% probability that a switch may exhibit loss of continuity whenoperated. However, in-house testing in actuators using voltages representative of in-service levels,establish a 0.0008% probability that a switch may exhibit loss of continuity when operated. Test data

indicate loss of continuity is random, not permanent, and low in probability. To date, no V12 switch

in-service faults have been reported by the industry.

2. Deviation Description

On June 4, 2015 Rotork Controls Inc. opened a formal Part 21 investigation into a self-identifiedanomaly relating to a Basic micro-switch - Part No. N69-921, description "V12". The anomaly isintermittent variation in electrical contact resistance and was first observed during the FactoryAcceptance Test of a Rotork Safety Related NA Range electric Actuator; also referred to as an electric

Valve Operator.

3. Micro-Switch Function

The micro-switch has four functions:

* Rotork actuators can be set to operate to a maximum torque level of opening or closing a

valve. When the torque sensing mechanism in the actuator registers this maximum torque,

the V12 micro-switch will be tripped to turn off the motor.

* Rotork actuators can also be set to operate to a maximum travel limit. The mechanism inside

the actuator will register when the maximum travel in the open or close direction is reached

and the V12 micro-switch will be tripped to turn off the motor.

*In the Add-on-Pak (AOP) the switch is intended for indication purposes but can also be used

for interlocks and permissives to start other equipment such as pumps and valves. AOPswitches can be set to trip at any point during valve travel. The AOP can also be used for torqueswitch bypass. If the circuit is "open" then the MOV could stop before achieving "end of

travel".

* Switches must be "closed" to initiate travel.

Page 11: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorweP eoRotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

4. Review of Orders Affected

The following are details of the switches affected:

* Order no. P0116932 was supplied to Rotork in 3 batches, Rotork Lot references LC009150,

LC009162 & LC009205.

* All switches supplied to customers are from LC009150.

* Suspect switches have date code 3513K to 4013K stamped at location shown below. Code

refers to week (35 to 40) and year (2013).

Figure 1: Location of date code on switch housing

Page 12: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotore PageS of 20Rotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

5. Root Cause Analysis

Defect: Intermittent and/or high contact resistance of the N69-921 V12 Micro-Switch.

Why - micro-switch did not function as intendedWhy - micro-switch contacts were open circuitWhy - microscopic plastic particles lodged between the contacts created an air gapWhy- the action of the switch plunger can potentially disturb plastic particles within the switch

housing and cause them to become lodged between the electrical contacts

Why - inadequate de-flash and cleaning prior to switch assembly

Following the moulding operation housings require de-flash and cleaning operations. In 2013, for

P0116932, these operations were transferred from the housing manufacturer to Johnson Electric. Aninvestigation by Rotork QA and Johnson Electric determined the intermittent switching was attributedto inadequate de-flashing and cleaning of the plastic housing at Johnson Electric. All switches supplied

against P0116932 are thus suspect. Microscopic plastic particles may randomly lodge between thecontacts and cause the resistance to exceed the Johnson Electric 25mf) acceptable limit, and possiblyloss of continuity.

Figure 2: Uncleaned flash inside of ho using

Figure 3: Plastic particles around the contact

Page 13: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwaeoRotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

6. Johnson Electric Micro-Switch Testing

1281 switches have been supplied against customer orders worldwide. The remaining stock of 3716switches from the defect batch was rejected back to the supplier for further analysis. The aims of

analysis were:

* To investigate whether a method could be established by which non-compliant switches can

be identified and segregated from compliant switches. Readings exceeding themanufacturer's 25m0 end-of-line acceptance criteria were classed as non-compliant.

* To determine whether high resistance or open circuit condition occurs on the normally open

(NO) contact, normally closed (NC) contact, or both.

* To determine whether the number of switch operations has an influence on contact

resistance.

* To collect data which can be used to calculate probability of switch failure i.e. open circuit

condition.

Test Method

* Each switch was operated 10 times. At each operation the NC and NO contact resistance was

recorded with a milliohm meter.(This gives 10 NC and 10 NO resistance readings)

* Test voltage = 9VDCTest current = 5mA

*The switch was then operated a further 50 times to check if the number of operations

influenced the contact resistance value. The NC and NO contact resistance was recorded at

every tenth operation.(This gives 5 NC and 5 NO resistance readings)

Total no. of operations per switch = 60Total no. of resistance readings per switch = 30

Test Results

Of the 3716 switches, 1520 were tested to above test method.1520 x 30 readings per switch = 45600 readings

A further 93 switches were operated only up to the point where high resistance/intermittentoperation was recorded. The total number of readings across the 93 switches were 911.

Total number of switches testedTotal recorded resistance readings

= 1520 +93 = 1613= 45600 +911 = 46511

Page 14: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorkRotork Controls Limited

Page 7 of 20

Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

Table 1 characterises the resistance test results from this data sample. The milliohm meter can registerreadings up to 2000 maximum. Readings over this limit are classed as open circuit. The column 'No.

of Readings' is presented graphically in Figure 4.

Resistance Range No. of No. of Readings as Cumulative FrequencyReadings % of Total above 25mC)

_____________Readings manufacturer acceptance0 < R < 25m0 46148 99.220% ___________

25 < R < l00mO 240 0.5216% 240100 < R < 200m0 30 0.065% 270200 < R < 300m0 27 0.058% 297300 <R•<400m0 4 0.009% 301

400 < R _< 500mO 5 0.011% 306500m0 < R < 10 1 0.002% 307

1 <R•<20 3 0.006% 310

2 <R <50 1 0.002% 311

5 <R _<2000 1 0.002% 3122000+ (Open Circuit) 51 0.110% 363

Table 1: Johnson Electric resistance test data

N69-921 SWITCH RESISTANCE POPULATIONData based on sample of 1613 switches from batch of 3716

400

350

300

250

-• 200

,,_15006 1o0

a2

U,N

VI0

46148 switch operations within manufacturing acceptance criteria (green)

0

363 switch operations outsidemanufacturing acceptance crteria (orange)

00

V V V 2 Uo, 0

50

0

Resistance Range

Figure 4: Johnson Electric resistance test data in graphicalf•orm

Page 15: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwRotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

The majority of non-compliant readings are < 500mO. In the range 50 < R < 200 there was one readingat value 21.90. The effect of this in a 48V, l0mA circuit and a 120V, 30mA circuit is calculated below:

V=IxR48 =0.0l0 xRR =48 /0.010 =48000

V=IxR120 = 0.030 x RR = 120 /0.030 =40000

If circuit resistance increased due to high switch contact resistance of 21.90:

4800 + 21.9 = 4821.9048 = L x 4821.90I = 48 / 4821.90 = 9.95mA

4000 + 21.9 = 4021.90120 = I x 4021.90I = 120 / 4021.90 = 29.84mA

The calculations above show that:* In a 48V, l0mA circuit, a contact resistance of 21.90 would reduce the current to 9.95mA.

* In a 120V, 30mA circuit, a contact resistance of 21.90 would reduce the current to 29.84mA.

The high resistance values captured thus have negligible effect on the circuit current in aboveexamples. The primary concern is thus the open circuit condition. Table 1 and Figure 4 show 46148compliant operations and 51 open circuit operations. The probability of a switch displaying an opencircuit condition is thus:

P(A) = 51 / 46511 = 0.0011 or 0.11% (operation based data)

Although Rotork are treating the whole batch of switches as suspect, Johnson Electric test data shows165 switches exceeded the 25m0 acceptance criteria. The probability of selecting a non-compliant

switch is thus:

P(B) = 165 / 1613 = 0.1023, or 10.23% (population based data)

Summary

Resistance testing demonstrates the occurrence of high resistance or open circuit condition is random.The anomaly occurs on the NO or NC contact, or both. Once the anomaly has occurred, correct switchoperation may revert on the next operation, or it may revert after a number of operations. Data showsno trend between the number of operations and the number of anomalies. Some switches displayedan anomaly on the first operation while others displayed an anomaly on the final (6 0th) operation.Most switches passed the resistance test. However, due to the random nature of the anomaly it ispossible that on the 6 1St operation an anomaly could occur. The segregation method cannot provideabsolute assurance.

Contact resistances in the order of tens of Ohms are considered to have negligible effect and mostanomalous readings were below this value. However, the utility must evaluate this point. The opencircuit condition is a concern. Test data based on resistance testing indicate a 0.11% probability peroperation that any switch may exhibit an open circuit condition.

Page 16: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorw ~o

Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

Resistance testing is performed at 9VDC. Rotork extended the investigation to establish whethersupply voltage level influenced switch operation reliability. ERA, an independent test laboratory,

performed the evaluation. The results are discussed in the next section.

Page 17: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorw Page 10of2

Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

7. ERA Micro-Switch Testing

5 switches that lost continuity during Johnson Electric test were sent to ERA to establish a voltage levelabove which the switches would operate reliably. The conjecture for testing was that switches in opencircuit condition have particles lodged between the contacts which create an air gap that may bebridged by the formation of an arc if the voltage potential is sufficiently high.

At ERA the open circuit condition could only be replicated on 2 of the 5 switches. On one switch a DCvoltage ramp was applied while in open circuit mode, and on the other an AC voltage ramp.

The other 3 switches, which had shown open circuit mode during Johnson Electric test, showed no

fault at ERA.

Test Method

* Similar to Johnson Electric test, the switches were operated 25 times. At each operation theNC and NO contact resistance was recorded with a milliohm meter.(This gives 25 NC and 25 NO resistance readings)

* Test voltage < 5VDCTest current < 10mA

* The switches were then operated a further 50 times. The NC and NO contact resistance was

recorded at every tenth operation.(This gives 5 NC and 5 NO resistance readings)

* During operations if loss of continuity was captured, the switch was kept in the fault modeand a voltage ramp applied.

For DC ramp test:Voltage representative of in-service levels = 48VDCCurrent representative of in-service levels = 10mARequired level of resistance during ramp = 48 / 0.010 = 48000

For AC ramp test:Voltage representative of in-service levelsCurrent representative of in-service levelsRequired level of resistance during ramp

= 120VAC= 30mA- 120 /0.030 = 40000

Page 18: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorl( Page 1of 2

Rotork Controls Limited Approved by Engineering

Date: 9th September 2015Nuclear Engineering Report No. ER791 Issue 1

DC Test Results

A contact resistance reading of 60k0 was captured on the NO contact. A voltage ramp up to 48VDCwas applied to the switch. The switch started to conduct at 15V, stopped conducting at 23V, andstarted to conduct again at 32V (Figure 5).

60kC2 Contact Resistance, 48VDC Ramp

55

50

C" 40

•, 30

10

15

10

14

13

12

11

10

9

8

6

4

3

0

0u

C)

2 5 9 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

Time (set) -- VO =(re!

Figure 5: Voltage ramp up to 48VDC when 60kD resistance was captured

On the next operation of the same switch, a contact resistance reading above 2M0 (milliohm meterlimit) was captured on the NO contact and a voltage ramp was again applied to the switch. This timethe switch started to conduct at 10V, stopped conducting at 32V, and started to conduct again whenthe voltage was further increased to 64VDC (Figure 6).

>2M0 Contact Resistance, 48VDC then to 64VDC Ramp

95 14

- 3

12

11

10

9

8

6

4

C

U

_iii I0 10 20 30 40 50 80 20 80 90 100 110 120 130

Time (set)140

-- VC -- Cjrren¶

Figure 6: Voltage ramp up to 48 VDC then increased to 64VDC, when >2MD resistance was captured

Page 19: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorl( ae1 of 20Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

AC Test Results

AC voltage tests were carried out on a different switch. A contact resistance reading above 2M0Q(milliohm meter limit) was captured on the NO contact. A voltage ramp up to 120VAC was applied tothe switch. The switch started to conduct at 104V (Figure 7). However, with the switch in the same

state, a subsequent ramp was applied (Figure 8) and the switch failed to conduct.

>2MC) Contact Resistance, 120VAC Ramp (1)

120

10

100

90

>i 70

• 60

> ,0

40

30

20

10

3432

30

28

26

24

2220 •"

E

18

1604

14

12

10

0 1 2 3 4 5 6 7 8 8 10 11 12 13 14 15 16 17 18Time (see) -- VAC -I-l •ren

Figure 7: First voltage ramp up to 120 VAC when >2Mf) resistance was captured

>2MC2 Contact Resistance, 120VAC Ramp (2)

130

120

110

1301

90

> 0

> 50

40

30

20

10

0

3432

30

28

26

24

2220 •"

E

12

10

8

6

4

2

0

0 1 2 3 4t 5 6 7 8 9 10 11 12 13 14 35 1615 I 16Time (sec) --~ -- urn

Figure 8: Second voltage romp up to 120 VAC when >2MC2 resistance was captured

Page 20: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotori ae1 of 2Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

Summary

Tests have revealed that when a voltage ramp is applied to a switch that is already in open circuitmode, the switch will not always operate reliably. A safe DC or AC operating voltage could thus not be

established.

However, when the voltage ramps were applied, the switch was static and fault condition already

established. It was thought that in dynamic operation, mechanical impact of the contacts and the heatfrom the arc may both act to clean the electrode contacts. Based on this the investigation was

extended to study the likelihood of an open circuit condition arising when switches are being used inan actuator at voltage levels representative of the application. The testing and results are discussed

in the next section.

Page 21: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorw Pae1 f2

Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

8. Rotork In-House testing

Rotork in-house tests were conducted to test suspect switches in the most representative manner ofhow they would be utilised in service. The reason for testing in a manner that represents theapplication is based on the hypothesis that mechanical impact of the contacts and the heat from the

arc may both act to clean the electrode contacts thus switch reliability in application may be betterthan Johnson Electric resistance measurements suggest.

A batch of switches including those that passed and those that were found non-compliant during tests

at Johnson Electric were called back to Rotork for further testing. Switches were assembled in theSwitch Mechanism, Figure 11, and Add-on-Pak (AOP), Figure 12, of 2 nuclear actuators.

The actuators completed a number of life tests to at least 4000 cycles Open-Close-Open. In betweeneach life test the switches in the Switch Mechanism and AOP were removed and replaced with moresuspect switches.

Page 22: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorwRotork Controls Limited

Nuclear Engineering Report No.

Page 15 of 20

Approved by Engineering

Date: 9 th September 2015ER791 Issue 1

Open auxiliaryswitch (OAS2)

Open auxiliary _____

switch (OAS1)

Open torque/limit -

switch (OTS)

AOP indication switches

IASi - IAS6

~Close auxiliaryswitch (CAS2)

~Close auxiliary

switch (CASi)

•----Close torque/limit

switch (CTS)

AOP indication switches

IAS7 - IA512

Figure 12: Photo of Add-on-Pack (AOP)

Page 23: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorI Page 1 of 20Rotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

Switches OTS and CTS were operated at 24VDC, 2.6mA average.Switches OAS1-2 and IASI-IAS6 were operated at 48VDC, 16.9mA average.Switches CAS1-2 and IAS7-IAS12 were operated at 120VAC, 12.5mA average.A reduced voltage life test was also completed using 38.8VDC, 13.7mA and 80VAC, 6.6mA.Voltages above 24VDC were applied through relays as illustrated in Figure 13.

•,POWER SUPPLY

V12 TEST •.jVMODULE:SWITCH I•- eod

Figure 13: Typical schematic showing V12 switch test

The operation of each switch was monitored during test. The data captured showed which switchesbehaved intermittently and when. The testing is summarised in Table 2.

A total of 84 different switches were tested during tests 1 - 9. Of these:* 28 were switches that showed no fault during Johnson Electric tests. These also showed no

fault during representative testing in an actuator.

* 51 were switches that intermittently exceeded 25m0 during Johnson Electric tests, having

readings in the range 26m03 to 2.8903.* 5 were switches that showed open circuit condition. This includes the 2 switches that were

used for DC and AC voltage ramp test at ERA. The 2 were used in Test 9 and no faults were

reported.

In Test 1, the AOP was fitted with switches that showed no fault during Johnson Electric tests. The

actuator completed 5537 cycles after which, in Test 2, all switches other than OTS and CTS werereplaced by more switches that showed no fault. In both Test 1 and 2 the switches that passed JohnsonElectric resistance test did not display open circuit behaviour during actuator operating life.

Between Test 3 - 7 the same actuator was used with the same switches. Switches OTS and CTS werethe same as Test 1 and 2. All other switches were those that showed high resistance during JohnsonElectric tests. The total actuator cycles in Tests 3 - 7 were 15686. The purpose of these tests was tosee what effect the voltage levels had on switch failure. In Test 3 there were 3 intermittent operationsrecorded and in Test 7 there were 4, both tests conducted at low voltage 38.8VDC and 80VAC (limitedby the minimum voltage capability of the relays). In Test 8 more high resistance switches were testedand there were 13 fault occurrences at nominal voltage 48VDC and 120VAC. These tests show thatthe fault can potentially occur at nominal and reduced voltage.

Page 24: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorl( ae1 of 2Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

OAS1-2 & CAS1-2 No. ofTest No f OS& IAS1-6 & IAS7- intermittent

Actuator actuator CTS testDecitoofesRef. test 12 test operations Decitoofes

cycles voltage voltage voltage recorded

IAS1-12 were switches thatshowed no fault duringJohnson Electric tests.

a 14NAIE 5537 24VDC 48VDC 120VAC 0 CS2adOS-switches were those thatshowed high resistance

during Johnson Electric

___________tests.

From Test 1, all butswitches OTS and CTS were

2 14NA1E 4000 24VDC 48VDC 12OVAC 0 replaced with those thatshowed no fault duringJohnson Electric test.From Test 2, all butswitches OTS and CTS were

3 replaced with those that3 1NA1 400 2V0 388VD 8OAC (See Note 1) showed high resistance

during Johnson Electric

__________ ________tests.

This test is a repeat of Test4 14NA1E 4000 24VDC 48VDC 120VAC 0 3 with same switches but

_________running at nominal voltage.This test is a repeat of Test

5 14NA1E 1913 24VDC 38.8VDC 80VAC 0 4 with same switches________running at reduced voltage.

This test is a repeat of Test6 14NA1E 4000 24VDC 48VDC 120VAC 0 5 with same switches

________running at nominal voltage.This test is a repeat of Test

7 14NA1E 1773 24VDC 38.8VDC 80VAC 4 6 with same switches

(SeeNot 2) running at reduced voltage.

From Test 7, all butswitches OTS and CTS were

13 replaced with those that8 14A1E 400 24DC 8VD 12VAC (See Note 3) showed high resistance

during Johnson Electric

tests.Switches IAS4-6 and lAS11-12 were those that showed"OFF" during Johnson

9 7NAIE 4000 24VDC 48VDC 120VAC 0 Elcrcts.Alohe

switches were those thatshowed high resistance.

Table 2: Summary of Rotork in-haouse switch testing with nuclear actuators

Page 25: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotor Page 18of2

Rotork Controls Limited Approved by Engineering

Date: 9 th September 2015Nuclear Engineering Report No. ER791 Issue 1

Note 1: Switch at OAS2 (at 38.8VDC) failed to close circuit during cycle 865.Switch at IAS8 (at 80VAC) failed to close circuit during cycle 28 and cycle 954.

Note 2: Switch at OAS2 (at 38.8VDC) failed to close circuit for 4 consecutive cycles from cycle

42.

Note 3: Switch at OAS2 (at 48VDC) failed to close circuit during the following cycles; 279, 280,

281, 283.Switch at IAS2 (at 48VDC) failed to close circuit during the following cycles; 276, 3647,

3651, 3655.Switch at IAS9 (at 120VAC) failed to close circuit during the following cycles; 6, 43, 45,

47, 158.

All switches that failed (Note 1 - 3) were those that were found to have intermittent high resistance.There were no failures of switches that had previously exhibited open circuit.

For the calculation of failure probability over actuator life only the first 4000 operations of each switch

are relevant. A switch operates once per actuator cycle. Based on Table 2, the total number of relevant

operations are:

Test 1 4000 operations of 18 switches.Test2 400 peraion of16 sitces. Demonstrates failure is random and the 25m£0

Test 3 4000 operations of 16 switches. tetdecsfu.

Test4 -7 Swich oeraionsfro tes 47 With Test 1 - 3 demonstrates that failure isare not included in the

probbilty alcuatinsrandom and not affected by accumulated cycles.

Test 8 4000 operations of 16 switches. Demonstrates failure is random and the 25mC)

Test 9 4000 operations of 18 switches. test detects fault.

Table 3: Relevant operations for calculation of switch failure probability

It should be noted that the switches used in representative testing were not randomly selected. Theselected switches were pre-identified as being compliant or non-compliant as per Johnson Electric

test.

Page 26: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorl( ae1 f2Rotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

Probability of a switch exhibiting open circuit in application is given by:P(C) = P(B) x P(D)

Where:P(B) = Probability of selecting a non-compliant switch i.e. >25m02. Calculated in section 6.P(D) = Probability of a non-compliant switch displaying open circuit when installed in an actuator

The probability of a non-compliant switch displaying open circuit, P(D), is determined using data from

Rotork in-actuator representative tests 3, 8, and 9. The total number of switch operations across thesethree tests are computed below and displayed in Table 3:

2(4000 x 16) + (4000 x 18) = 200,000 (total operations of tested switches classified non-compliant)

The total number of observed open circuit operations in these three tests are:

3 + 13 = 16 (see Table 2)

P(D) = (16 / 200,000) = 0.00008, or 0.008% (operation based data)

P(C) = 0.1023 x 0.00008 = 8 x 10.6, or 0.0008% (per switch operation)

In some applications when a valve is initially stroked two switches are required to function correctly,the torque/limit switch and the torque bypass switch. The probability that either of these goes open

circuit is:P(2 Switches) = 2 x P(B) = 0.0016%100 - 0.0016 = 99.998% probability of success

The probability that any one of the 18 switches in an actuator fitted with a switch mechanism and 12switch AOP could go open circuit is:P(18 Switches) = 18 x P(B) -0.0144%100 - 0.0144 = 99.986% probability of success

Summary

The probability P(C) of a switch displaying open circuit in application is considerably lower than the

probability P(A) of a switch displaying open circuit during Johnson Electric test. These result suggestthat switch operation is more reliable than resistance evaluation indicates, It also supports why no in-

service faults are reported by industry and why Rotork Controls Inc. eventually observed the anomaly

based on 100% resistance inspection of all V12 switches fitted to actuators.

Page 27: Part - 21 Notification - Micro Switch Intermittent ... · PART-21 NOTIFICATION -MICRO SWITCH INTERMITTENT VARIATION IN RESISTANCE The following report was received via fax: 'On June

rotorI(Pge2 of 2Rotork Controls Limited Approved by Engineering

Nuclear Engineering Report No. ER791 Issue 1 Date: 9 th September 2015

9. Conclusion

Testing indicates that occurrence of high resistance or open circuit condition is random with a lowprobability of a switch exhibiting an open circuit condition. Based on Johnson Electric testing of 1613switches, there is 0.11% probability that a switch may exhibit open circuit when operated. Rotork's in-

house tests show that in application there is a 0.0008% probability that a switch operation may exhibitopen circuit when operated.

Thermal & radiation effects could not be evaluated but are considered not pertinent given thecontamination nature. The housing material is qualified for high temperature and radiation levels thusthe material properties of contaminating particles are thought to be unaffected by these factors.To date there have been no in-service faults reported.

Rotork cannot evaluate application risk. Utilities must evaluate their in service switches and determine

if a high contact resistance or open circuit conditions could potentially affect safety related functions.


Recommended