n Current sensor n Universal input voltage: 24-240VAC and 24VDC n Choice of five AC current ranges: 351-1 0.1 to 1 Amp 351-2 – 0.2 to 2 Amps 351-5 0.5 to 5 Amps 351-8 – 0.8 to 8 Amps 351-16 – 1.6 to 16 Amps n Overcurrent sensing with 5% hysteresis when returning from fault condition n Adjustable time delay from 0.5 to 10 seconds eliminates nuisance tripping n Relay output form: SPDT – 8 Amps n Green LED indicates sensor is powered n Red LED indicates fault condition n Single-phase applications n DIN rail mounting n UL and CE approvals, RoHS compliant MODE OF OPERATION FEATURES SPECIFICATIONS When the sensed current increases above set point, the time delay starts. At the end of the delay the output is energized. When the current falls below set point, a 5% hysteresis occurs before relay transfers to NO condition. Hysteresis 10/15/08 Input terminals ............ A1–A2 Input voltage .............. 24–240VAC (AC 50/60Hz), 24VDC Input voltage tolerance ... -15% to +10% Power consumption (max) . . 1.5VA Current connection........ between B2–B1 Current ranges (AC) choose 1 of 5 .................. 351-1 0.1 to 1 Amp 351-2 0.2 to 2 Amps 351-5 0.5 to 5 Amps 351-8 0.8 to 8 Amps 351-16 1.6 to 16 Amps Permanent current (max).. 351-1 1 Amp 351-2 2 Amps 351-5 5 Amps 351-8 8 Amps 351-16 16 Amps Overload capacity (max) . . 100A/1ms Current adjustment by .... Potentiometer Time delay (adjustable) ... 0.5 to 10 seconds Setting accuracy........... 5% Repeatability .............. <1% Set point tolerance ........ 5% Hysteresis (fault to normal) . . . 5% Relay output form ......... SPDT Rated current .............. 8 Amps Switching capacity ........ 2500 VA/ AC, 240 W/ DC Output indicator .......... Red LED Operating temperature ... -20°C to +55°C Storage temperature ...... -30°C to +70°C Dielectric strength ........ 4 kV Operating position ........ any Mounting .................. DIN rail EN 60715 Protection degree ......... IP 40 from front panel Wire size (max) ............ 10AWG Standards ................. EN 60255-6, EN 61010-1, UL, CE, RoHS 315-655-8476 n www.peltectimers.com 351 CURRENT SENSOR 300 Series
Transcript
Page 1: Peltec Timers 351

n Current sensor n Universal input voltage: 24-240VAC and 24VDCn Choice of five AC current ranges:

351-1 – 0.1 to 1 Amp 351-2 – 0.2 to 2 Amps 351-5 – 0.5 to 5 Amps 351-8 – 0.8 to 8 Amps 351-16 – 1.6 to 16 Amps

n Overcurrent sensing with 5% hysteresis when returning from fault condition

n Adjustable time delay from 0.5 to 10 seconds eliminates nuisance tripping

n Relay output form: SPDT – 8 Ampsn Green LED indicates sensor is powered n Red LED indicates fault condition n Single-phase applications n DIN rail mountingn UL and CE approvals, RoHS compliant

mode of operAtion

feAtUreS

SpeCifiCAtionS

When the sensed current increases above set point, the time delay starts.

At the end of the delay the output is energized.

When the current falls below set point, a 5% hysteresis occurs before relay transfers to NO condition.

Hysteresis

10/15/08

input terminals . . . . . . . . . . . . A1–A2

input voltage . . . . . . . . . . . . . . 24–240VAC (AC 50/60Hz), 24VDC

input voltage tolerance . . . -15% to +10%

power consumption (max) . . 1.5VA

Current connection . . . . . . . . between B2–B1

Current ranges (AC) choose 1 of 5 . . . . . . . . . . . . . . . . . . 351-1 0.1 to 1 Amp

351-2 0.2 to 2 Amps 351-5 0.5 to 5 Amps 351-8 0.8 to 8 Amps 351-16 1.6 to 16 Amps

permanent current (max) . . 351-1 1 Amp 351-2 2 Amps 351-5 5 Amps 351-8 8 Amps 351-16 16 Amps

overload capacity (max) . . 100A/1ms

Current adjustment by . . . . Potentiometer

time delay (adjustable) . . . 0.5 to 10 seconds

Setting accuracy . . . . . . . . . . . 5%

repeatability . . . . . . . . . . . . . . <1%

Set point tolerance . . . . . . . . 5%

Hysteresis (fault to normal) . . . 5%

relay output form . . . . . . . . . SPDT

rated current . . . . . . . . . . . . . . 8 Amps

Switching capacity . . . . . . . . 2500 VA/ AC, 240 W/ DC

output indicator . . . . . . . . . . Red LED

operating temperature . . . -20°C to +55°C

Storage temperature . . . . . . -30°C to +70°C

dielectric strength . . . . . . . . 4 kV

operating position . . . . . . . . any

mounting . . . . . . . . . . . . . . . . . . DIN rail EN 60715

protection degree . . . . . . . . . IP 40 from front panel

Wire size (max) . . . . . . . . . . . . 10AWG

Standards . . . . . . . . . . . . . . . . . EN 60255-6, EN 61010-1, UL, CE, RoHS315-655-8476 n www.peltectimers.com

351CUrrent

SenSor

300 Series

Page 2: Peltec Timers 351

feAtUreS Wiring diAgrAm

2747 Route 20 East, Cazenovia, NY 13035315-655-8476 n www.peltectimers.com 10/15/08

A1 A2

B1 B2

15 18

16

L N

peltec351 CUrrent SenSor

InputVoltage

15

16 18 A2

B1 B2

A1

SensedCurrent

Current setting as % of rangeOvercurrent is indicated by relay transfer and red LED.

0.5

Imax[ % In]

102030

4050 60

708090

100

Time delay setting 0.5 to 10 seconds

Input terminals

Time delay

Current setting in %Output indicator

Output terminals15 18

A1 A2

B1 B2

16

Current sensing terminals (AC only)


Recommended