Date post: | 12-Jan-2016 |
Category: |
Documents |
Upload: | william-pope |
View: | 218 times |
Download: | 1 times |
Phoenix Convention Center • Phoenix, Arizona
Targeted E4 Re-Tuning at GSA Facilities
Integrated Energy
Low/No Cost Solutions through Building Automation System Control Technologies
August 13, 2015
Nick FernandezPacific Northwest National Laboratory
Linda Baschnagel, P.E.General Services Administration
Energy Exchange: Federal Sustainability for the Next Decade2
2007 - The Heartland Region (R6) began working with Pacific Northwest National Laboratory (PNNL)
Phase I - Energy Efficiency Expert Evaluations (E4)• E4 field audits provided training to identify low-cost and no-
cost energy efficiency measures (EEMs) to GSA Staff and operation and maintenance (O&M) contractors outlining improvements to the operational efficiency of buildings.
• 8 R6 GSA Building (4.7 million SF)• Classroom and field training for 110 GSA Staff and O&M
contractors• 160 recommendations (no-cost/low cost and small repairs)
Targeted E4: Project History
Energy Exchange: Federal Sustainability for the Next Decade3
In FY12, DOE funded an assessment to evaluate the impact of the 8 E4 audits.Results• Average savings at the 8 buildings: 6.4%• Only about 50% of the 160 recommendations implemented• Field auditing to identify a list of measures was not totally
effective– Staff did not make audit recommendations a priority– Limited experience by O&M with control systems to perform
implementations– Implementation weighted towards easy changes like scheduling, but
advanced control measures were left on the table.
Targeted E4: Project History
Energy Exchange: Federal Sustainability for the Next Decade4
Based on the results, the Heartland Region and PNNL revised the approach to achieve key EEM implementationPhase II – Targeted E4• Identify and implement control system measures.• Train the O&M staff on the control measures and use of BAS• Two site visits
– Initial visit to identify and implement measures– Second visit to verify functionality of implemented measures– Ongoing remote assistance by tele-conference and remote access to
BAS
• Nov 2011 -Targeted E4 model was tested in 4 buildings– Results – Energy savings range: 9% - 18%– Simple Payback approximately 1 year
Targeted E4: Project History
Energy Exchange: Federal Sustainability for the Next Decade5
The Targeted E4 model was expanded to 5 additional buildings in FY13 and FY14.• Two site visits were conducted over the 1 year assessment
period for each building– Initial visit identified and implemented measures– Second visit scheduled during the opposite season
• Identify and implement additional measures not looked at before– Opportunity for additional on-job-training for staff– Continued remote assistance by tele-conference and remote access to
BAS
The Targeted E4 model has been adopted by the Heartland Region as a standard practice and will be completed on 15 buildings by the end of FY15. (7.3 million SF)
Targeted E4: Project History
Energy Exchange: Federal Sustainability for the Next Decade6
Targeted E4: Project History
GSA Region 6: 15 Targeted E4 Buildings
Energy Exchange: Federal Sustainability for the Next Decade7
• Cooperation and engagement of the building staff and O&M is critical
• Ensure the staff/O&M understand and are comfortable with the implementations and know how make adjustments if necessary
• Training is more effective with hands-on experience• Proper scheduling of site visit is essential
Keys to Success
Energy Exchange: Federal Sustainability for the Next Decade8
• Regional Project Manager to assist with logistics before, during and after the site visits is a requirement for success
• Coordination of other work ongoing in the building• Leverage staff ideas for additional opportunities• Onsite support and remote monitoring are key• Continually monitoring of building performance a must
Keys to Success
Energy Exchange: Federal Sustainability for the Next Decade9
• Two site visits (minimum) – Site visits during heating and cooling season will result in more
complete analysis
• To date, Region 6 experience indicates the Monitoring and Re-tuning Plans included in each report are not being used for follow-up by the O&M– R6 has engaged spot monitoring building performance with the
assistance of a contract BAS Specialist and the planned hiring of a new Building Systems Analyst FTE
Further Improvements
Energy Exchange: Federal Sustainability for the Next Decade10
• Targeted E4 re-tuning helps to quickly identify, and then quickly implement no-cost/low-cost building retuning measures that produce immediate/measurable energy performance improvements
• Targeted E4 produced significantly better results than E4 approach• All buildings improved energy performance• Targeted E4s are sustainable and are showing an impact on the
improved regional energy performance• Targeted E4 re-tuning is a transferable, repeatable model • The R6 Regional Energy Team shared the Targeted E4 approach
and resulting successes with GSA Central Office and other Regions. The Targeted E4 model was expanded throughout GSA in FY14.
• PNNL is currently offering the model to other GSA Regions and federal agencies.
Results from Targeted E4 Implementation
Energy Exchange: Federal Sustainability for the Next Decade11
Targeted E4: Project History
• FY2011-2013: GSA Region 6 funded effort: 9 buildings total (Red)• FY2014: GSA Central Office funded effort: 18 buildings total (Blue)• FY2015: GSA Central Office funded effort: 17 buildings total (Green)
Energy Exchange: Federal Sustainability for the Next Decade12
Energy Saving Control Measures
• 341 total measures (59 unique measures) recommended at 39 buildings
AHU and OAHU Air Delivery
Static Pressure Reset
Supply Air Temperature Reset
Economizer Strategy
Preheat Coil Strategy
Outdoor AHU Discharge Temperature
Ventilation (minimum) air flow rate
Energy Exchange: Federal Sustainability for the Next Decade13
• 341 total measures (59 unique measures) recommended at 39 buildings
HVAC Scheduling
AHU Schedule Adjustment
Optimal StartOptimal Stop
Exhaust Fan Schedule/Coordination
Pump Staging and Scheduling
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade14
• 341 total measures (59 unique measures) recommended at 39 buildings
Zone Equip.,T-stat, and Air Distribution
Server Room Equipment Coordination
Thermostat Set points and Dead-bandsVAV box mode configuration
Minimum VAV airflow fraction
Night Setback
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade15
• 341 total measures (59 unique measures) recommended at 39 buildings
Ventilation, Infiltration and Heat Recovery
OAHU coil and wheel control
Minimum outdoor-air damper scheduling
Ventilation (minimum) air flow rate
Demand Control Ventilation
Building Pressurization Control
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade16
• 341 total measures (59 unique measures) recommended at 39 buildings
Chilled Water Plant
Control
Chilled Water Temperature ResetChilled Water Differential Pressure Reset
Condenser Water Temperature Reset
Chiller and coil lockouts
Chiller Staging
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade17
• 341 total measures (59 unique measures) recommended at 39 buildings
Heating Plant
Control
Hot Water Differential Pressure Reset
Hot Water Temperature Reset
Boiler LockoutsIsolation Valves
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade18
• 341 total measures (59 unique measures) recommended at 39 buildings
Lighting Schedules and De-lamping Other
Domestic Hot Water
Faulty ValvesSnowmelt
SensorCalibration
Pneumatic Compressor
Energy Saving Control Measures
Energy Exchange: Federal Sustainability for the Next Decade19
• 39 buildings analyzed• Average building: 14.4% total predicted savings(all measures)• Engineering estimates, TMY analysis, building energy models (BEMs)
Where are the Opportunities? Average Predicted Savings
4.02%
2.80%
0.10%
2.36%
1.29%
1.94%
1.48%
0.40%
AHU and OAHU Air Delivery
HVAC Scheduling
Lighting
Zone Equipment, Terminal Boxes, and Thermostats
Chilled Water Plant Control
Heating Plant Control
Ventilation, Infiltration and Heat Recovery
Other (DHW, Compressors, Sensors, and Actuators)
Energy Exchange: Federal Sustainability for the Next Decade20
• 27 buildings analyzed• Estimates based on predicted savings by measure, verification of measure
implementation, and monitoring of 12-month energy savings.
Most Impactful Measures: Estimated Share of Total Achieved Savings
15.1%
10.9%
10.3%
10.2%
5.4%5.3%4.
7%
4.0%
3.7%
2.7%
27.9%
SAT Reset
HWT Reset
HVAC Schedule Reductions
SP Reset
Minimum VAV Box Airflow Setpoints
Optimal Start
ChW Temp Reset
Night Setback
Economizer Strategy
Garage and Exhaust Fan Scheduling
Other
Energy Exchange: Federal Sustainability for the Next Decade21
Quantifying Energy Savings
0 2 4 6 8 10 12 14 16 18 20 220
50
100
150
200
250
300
350
Pre-E4 Weekdays Post-E4 WeekdaysPre-E4, Weekends Post-E4, Weekends
Hour of Day
Elec
tric
ity
(kW
)
• Using Interval metered-data whenever possible (most cases), monthly utility data when not possible• Data “cleaned” to remove meter outages and unreliable data.• Post-site visit data at each meter interval matched to average of pre-site visit data at same hour of day,
same day type (weekday/weekend) and similar OA temperature• Verification that savings patterns in interval meter data match savings in monthly utility data
Energy Exchange: Federal Sustainability for the Next Decade22
Verified Energy Savings
• 26 Buildings• Median Savings: 12.7% (9.7% electricity, 17.7% gas/steam)• Wide spectrum of heating meter savings• Electricity savings very commonly in 5-10% range.
Less than 0%
0 to 5% 5 to 10%
10 to 15%
15 to 20%
20 to 25%
25 to 30%
30 to 35%
35 to 40%
40 to 45%
45 to 50%
0
1
2
3
4
5
6
7
8
Overall Energy SavingsElectricity Sav-ingsGas/Steam Sav-ings
Energy Savings Range
Num
ber o
f Bui
ldin
gs
Energy Exchange: Federal Sustainability for the Next Decade23
Verified Energy Cost Savings
• Median Savings: $0.127 per square foot per year• 2/3 of buildings saved between 5 and 15 cents per square foot
per year
Less than 0%
$0 to $0.05/sf
$0.05 to $0.1/sf
$0.1 to $0.15/sf
$0.15 to $0.2/sf
$0.2 to $0.25/sf
$0.25 to $0.3/sf
$0.3 to $0.35/sf
$0.35 to $0.4/sf
$0.4 to $0.45/sf
$0.45 to $0.5/sf
$0.5 to $0.55/sf
0
1
2
3
4
5
6
7
Energy Savings Range
Num
ber o
f Bui
ldin
gs
Energy Exchange: Federal Sustainability for the Next Decade24
Persistence of Savings
• Four Buildings suitable for long-term analysis• In all 4 buildings, savings has not deviated substantially after
year 1.
0 1 2 3 4 50%
5%
10%
15%
20%
25%
30%
Region 6 Site 1Region 6 Site 2Region 6 Site 3Region 6 Site 4
Year After Re-Tuning Site Visit
Ener
gy S
avin
gs fr
om U
til-
ity D
ata
Anal
ysis
Energy Exchange: Federal Sustainability for the Next Decade25
Persistence of Savings
• PNNL Reports Savings based on an analysis of “ION” system sub-metered data using a 6-month monitoring period
• Validating with utility monthly data, corrected for weather, savings has increased slightly (on average) each year, relative to original ION-reported savings.
Year 1 (Utility Data)
Year 2 (Utility Data)
Year 3 (Utility Data)
0%1%2%3%4%5%6%7%8%9%
10%
+0.10%+1.00%
+2.33%
Savi
ngs I
ncre
ase
Rela
tive
to
Repo
rted
Sav
ings
Energy Exchange: Federal Sustainability for the Next Decade26
Factors that Promote Cost Effective Re-Tuning
• Building size matters! • We have consistently achieved simple payback periods under
2 years when buildings are over 100,000 sf.
10,000 100,000 1,000,0000
1
2
3
4
5
6
7
8
9
10
Building Square Footage
Estim
ated
Pro
ject
Sim
ple
Payb
ack
(Yea
rs)
Minimum expected payback time?
Energy Exchange: Federal Sustainability for the Next Decade27
Factors that Promote Cost Effective Re-Tuning
• Initial Energy Efficiency of building (using Energy Star score)• Energy Star scores a building relative to similar buildings in similar climate. 50 is average. 0
is worst building in cohort, 100 is best building in cohort– Not a strong correlation BUT…– For Energy Star scores 80 or below, 6/6 achieved >10% savings– For Energy Star scores above 80, 8/17 achieved <10% savings– Yet 3 buildings with initial scores over 90 saved between 18-25%
50 55 60 65 70 75 80 85 90 95 100-10.0%
-5.0%
0.0%
5.0%
10.0%
15.0%
20.0%
25.0%
30.0%
35.0%
R² = 0.0659432069281135
Initial Energy Star Score
Annu
al E
nerg
y Sa
ving
s
Energy Exchange: Federal Sustainability for the Next Decade28
Factors that Promote Cost Effective Re-Tuning
• Factors that we observe promote success– Presence of variable speed drives, especially on fans– Advanced controls (resets, Optimal Start, etc.) NOT already in place– Direct Digital Control (DDC) as opposed to pneumatic systems – Modern, updated Building Automation System– Dedicated Outdoor Air Systems with energy recovery (commonly lack
advanced controls for optimization)– Strong leaders within region who advocate for energy efficiency and/or have
mechanical and controls expertise• Region 6 (very strong support): 72/96 measures implemented (75%)• Other regions visited: 81/125 measures implemented (65%)
– Building property managers and O&M staff willing to experiment!
Phoenix Convention Center • Phoenix, Arizona
THANK YOU!! -- QUESTIONS?
Nick [email protected]
Linda [email protected]