+ All Categories
Home > Documents > Pompe de Caldura Bucla

Pompe de Caldura Bucla

Date post: 09-Jan-2016
Category:
Upload: auras177
View: 58 times
Download: 5 times
Share this document with a friend
Description:
Pompe de Caldura Bucla
96
7/17/2019 Pompe de Caldura Bucla http://slidepdf.com/reader/full/pompe-de-caldura-bucla 1/96 HydroBank ®  MS Compact, Single Stage ½ to 6 Tons – Horizontal and Vertical Water Source Heat Pumps PRODUCT CATALOG
Transcript
  • HydroBank MS Compact, Single Stage to 6 Tons Horizontal and Vertical

    Water Source Heat Pumps ProduCT CaTalog

  • 2 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    ContentsContents

    Contents

    Contents ...................................................................................................................................................2Introduction ...............................................................................................................................................3Nomenclature ...........................................................................................................................................4Horizontal Unit Features and Benefits .....................................................................................................5Vertical Unit Features and Benefits ..........................................................................................................7MS Product Features and Benefits ..........................................................................................................8MS Product Options ...............................................................................................................................10Controls ..................................................................................................................................................12Application and Design Considerations ................................................................................................14Horizontal Unit Installation......................................................................................................................22Vertical Unit Installation .........................................................................................................................24Unit Selection Procedures ......................................................................................................................26Operating Limits and Correction Factors ...............................................................................................28Horizontal Units ISO Performance Data ................................................................................................29Horizontal Units Capacity Data ..............................................................................................................30Horizontal Units Electrical Data ..............................................................................................................42Horizontal Units Blower Performance Data............................................................................................44Horizontal Units Physical Data ...............................................................................................................46Horizontal Units Dimensional Data .....................................................................................................47Vertical Units ISO Performance Data .....................................................................................................56Vertical Units Capacity Data ...................................................................................................................57Vertical Units Electrical Data ..................................................................................................................70Vertical Units Blower Performance Data ................................................................................................72Vertical Units Physical Data ...................................................................................................................74Vertical Units Dimensional Data .............................................................................................................75Wiring Diagrams .....................................................................................................................................79Field-Installed Accessories .....................................................................................................................87Engineering Specification .......................................................................................................................91

    Mammoth is a registered trademark of CES Group. CES Group 2014. All rights reserved throughout the world.

    Illustrations cover the general appearance of Mammoth products at the time of publication. We reserve the right to make changes in design and construction at anytime without notice.

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 3

    IntroductionIntroduction

    HydroBank MS: Your New Best Choice in Water Source Heat PumpsMammoth HydroBank water source heat pumps offer highly efficient and flexible solutions for your building environment. Our new MS model is no exception. Its designed specifically for developer, new construction and replacement markets where compact design and a low first cost are primary considerations.

    Cabinet dimensions make the HydroBank MS model one of the smallest in the industry and ideal for the replacement of existing water source heat pumps. eneral Description

    Reliable

    Ask anyone who owns a Mammoth water source heat pump system and the answer is the sametheyre built to last. We dont cut costs at the expense of perfor-mance, reliability and longevityits as simple as that.

    Efficient

    HydroBank MS units are designed with the latest heat transfer technology available in the industry. With Water Loop (WHLP) Energy Efficiency Ratios (EERs) of up to 14.9 with ECM motors, they surpass ASHRAE 90.1 requirements and are eligible for most utility rebates and tax incentive programs. Contact your local utility or visit www.dsireusa.org for details on tax incen-tives and utility rebates available in your area.

    About MammothMammoth is among the original manufacturers of water source heat pump systems, with expertise dating back to the 1970s. Recent innovations include units from 2 to 70 tons that provide both industry-leading high effi-ciency and superior IAQ for use in healthcare and other sensitive applications, or to maximize points for LEED certification.

    Mammoth units can be found in offices, schools, hos-pitals, nursing homes and other commercial buildings, as well as high-rise condominiums. Owners, engineers, and contractors have placed their trust in Mammoth water source heat pumps in thousands of installations worldwide.

    Mammoth is a CES Group brand. This extends Mam-moth product development and research capabilities with a wealth of additional engineering and application expertise. Mammoth products are offered through trained, local representatives. Our representatives are experienced engineers with knowledge of environmental conditions in your area to match the optimal HVAC solu-tion to your specific requirements.

  • 4 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    NomenclatureNomenclature

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

    M S H 1 0 1 9 D L S E S A C Y 1 0 1

    Digits 17-18: Cabinet Finish01 = Standard GalvanizedXX = Special

    Digit 16: Filtration1 = Standard 1" w 1" Throwaway2 = 4-Sided 2" w 1" Throwaway

    Digit 4: Design Series 3 = 4-Sided 2" w Merv81 = A Design 4 = 4-Sided 2" w Merv13

    X = Special

    006 = 6,000 036 = 36,000 Digit 15: Coil Coating009 = 9,000 040 = 40,000 (Vertical Only) C = E-Coat012 = 12,000 042 = 42,000 Y = None (standard)015 = 15,000 048 = 48,000 X = Special019 = 19,000 060 = 60,000024 = 24,000 070 = 70,000 Digit 14: Heat Exchanger030 = 30,000 C = Copper (standard)

    N = Cupro-NickelDigit 8: VoltageA = 115/60/1 F = 208-230/60/3 Digit 13: Blower MotorD = 208-230/60/1 G = 460/60/3 A = PSC (standard)E = 265-277/60/1 C = ECM - Constant Torque

    E = ECM - Constant CFMDigit 9: Return AirL = Left Digit 10: Discharge Air Digit 12: Application TypeR = Right T = Top S = Standard Range (standard)

    S = Straight G = Geothermal RangeE = End

    Digit 11: ControlsE = Stand-AloneB = BACnetL = LONMARKM = ModBusN = Metasys N2 by JCIX = Special

    MS = Standard Efficiency

    Digits 5-7: Nominal Capacity

    Digits 1-2: Model Type

    Digit 3: Cabinet TypeH = HorizontalV = Vertical

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 5

    Horizontal Unit Features and BenefitsHorizontal Unit Features and Benefits

    Compact Design Cabinet dimensions make the HydroBank MS one of the smallest horizontal units in the industry and ideal for the replacement of existing water source heat pumps. The 1/2 through 1 ton units have a vertical clearance of 11.5 inches.

    Durable, Quiet ConstructionHydroBank MS cabinets are constructed of heavy gage galvanized sheet metal for commercial gauge strength and corrosion resistance. Internal metal parts are also fabricated from galvanized steel.

    Standard cabinet insulation is acoustic-type half-inch, dual-density fiberglass. Half-inch closed-cell foam insu-lation is an option for high IAQ applications. The entire bottom panel is insulated with the same material to prevent condensation and reduce noise transmission.

    Units have an insulated divider panel between the air handling section and the compressor compartment to minimize the transmission of compressor noise, and to permit service testing without air bypass.

    Isolated Air Handling Section

  • 6 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Horizontal Unit Features and BenefitsEasy Mounting and HookupHydroBank units feature flush-mounted water fittings that eliminate the need for a backup wrench to tighten.Easy access to the electrical enclosure speeds hookup of power lines and controls. The corner post adjacent to the control box accepts a line-voltage conduit con-nection for fast electrical hookup. Factory-installed duct collars simplify duct connections.

    Horizontal units are easily attached to threaded hanging rods via factory-supplied, heavy-gauge steel brackets and vibration-isolating bushings. The brackets can be easily moved from end to side placement to accommo-date installation requirements.

    Flush-Mounted Fittings, Field-Adjustable Mounts

    Easy AccessHorizontal units have four access panels for the elec-trical control box, blower and compressor sections to allow service of all major components without removing the unit from the ceiling. All major electrical components, including transformer, relays, contactor(s) and circuit board, are located inside the control box for convenient electrical service access. Schrader valves are easily accessed for refrigerant charging or testing.

    Field-Convertible Blower Configuration

    Multiple ConfigurationsHorizontal units are configured for straight-through discharge as standard with an option for end discharge. Unit discharge can be easily field-converted to match the configuration of the unit being replaced.

    Left Hand Return End Discharge

    Condensate Drain

    Left Hand Return Straight Discharge

    Control Panel

    Control Panel

    Water Connections

    Water Connections

    Control Panel

    Control Panel

    Water Connections

    Water Connections

    Condensate Drain

    Right Hand Return End Discharge

    Right Hand Return Straight Discharge

    Horizontal Cabinet Configurations

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 7

    Vertical Unit Features and BenefitsVertical Unit Features and Benefits

    Durable, Quiet ConstructionHydroBank MS vertical-mounted cabinets are con-structed of heavy-gauge galvanized steel for commercial grade strength and corrosion resistance. Internal metal parts are also fabricated from galvanized steel.

    Standard cabinet insulation is acoustic-type half-inch, dual-density fiberglass. Half-inch closed-cell foam insu-lation is an option for high IAQ applications. Units have an insulated divider panel between the air handling sec-tion and the compressor compartment to minimize the transmission of compressor noise, and to permit service testing without air bypass.

    Easy Mounting and HookupHydroBank MS units feature flush-mounted water fittings that eliminate the need for a backup wrench to tighten. The corner post adjacent to the control box accepts a line-voltage conduit connection for fast electrical hookup. Low-voltage thermostat connections are con-veniently made terminal strips. Condensate lines are internally trapped. A flush-mounted condensate connec-tion outside the cabinet is provided on each unit.

    Multiple ConfigurationsVertical units are available in right-hand and left-hand return air configurations for maximum installation flexibility.

    Vertical Left Hand Return Air

    Control Panel

    Water Connections

    Vertical Right Hand Return

    Control Panel

    Water Connections

    Vertical Cabinet Configurations

    Ample access to the electrical enclosure and schrader valves for ease of service

    Floating compressor mass plate minimizes vibration transmission to the cabinet for quiet operation

    Heavy-gauge, galvanized steel cabinet for commer-cial grade strength and corrosion resistance

    Factory-installed duct collar for quick, easy supply duct connection

    Removable orifice ring helps facilitate motor replacement

    Flush-mounted water fittings eliminate the need for a backup wrench to tighten

  • 8 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    MS Product Features and BenefitsMS Product Features and Benefits

    Fast, Convenient Filter ReplacementEach unit includes a 1-inch throw-away filter in a factory-mounted filter bracket designed to accommo-date a return air duct connection. Filters are removed horizontally. Four-sided filter racks are available as an option for both vertical and horizontal units. See Four-Sided Filter Rack on page 11.

    Units are designed to accommodate high- efficiency filters like 2 Merv 8 and Merv 13.

    Easy Filter Replacement

    Quiet, Efficient Refrigeration SystemAll units feature a sealed refrigerant circuit including a hermetic compressor with overload protection, balance-port expansion valve, finned tube air-to-refrigerant heat exchanger, tube-in-tube water-to-refrigerant heat exchanger, refrigerant reversing valve and service ports.

    Floating Base Plate

    Compressors

    Compressors are high efficiency and designed for heat pump duty. They are internally spring isolated (if reciprocating type) for maximum sound attenuation. A 10 gauge steel mass plate under the compressor minimizes vibration transmission to the cabinet for quiet operation. High-density rubber isolators between the base plate and the unit base pan isolate both noise and vibration.

    The water-to-refrigerant heat exchanger is a coaxial coil with a convoluted copper inner tube and a steel outer tube. The convoluted tube has increased heat transfer surface area per unit length for greater performance. 90-10 cupro-nickel inner tubes are an option. It is rated for 600 psig on the refrigerant side and 400 psig on the water side. Optimum heat transfer is achieved with a counter-flow arrangement of water and refrigerant during condensing.

    Coaxial Water-To-Refrigerant Heat Exchanger

    The airside coil is a copper tube, aluminum finned type selected for high efficiency and is rated for 650 psig working pressure.

    Air Coil

    The reversing valve is pilot-operated, of the sliding piston type, with replaceable, encapsulated magnetic coils, ener-gized only during the cooling cycle.

    Reversing Valve

    Safety controls include high- and low-refrigerant pressure switches (loss of charge protection). A lockout relay built into the standard microprocessor board prevents the com-pressor from operating if any safety switch trips.

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 9

    MS Product Features and BenefitsQuiet, Easy-Access Air Handling SectionThe air handling section includes the blower wheel and housing, motor, discharge outlet and drain pan that is located under the air coil. Components are separated from the compressor section to limit noise transmission. The forward-curve, centrifugal blower wheel is dynami-cally balanced for minimum vibration. The drain pan is insulated from the unit casing to prevent sweating.

    A three-speed PSC fan motor is standard on all unit sizes. It is permanently lubricated and includes thermal overload protection.

    Permanently Lubricated PSC Motor

    The blower features a removable inlet ring to facilitate removal and servicing of the fan motor. For horizontal units, the blower assembly can be easily reconfigured in the field for side or straight discharge.

    Easy Motor Removal

    Extended Warranty OptionsExtended warranty options allow you to tailor your costs to the requirements of the job. Our standard warranty is for a period of 12 months from startup or 18 months from shipping (whichever occurs first). Extended 2nd thru 5th year warranty options are available to cover some or all components, based on your requirements, and with or without labor allowances. For more informa-tion see Warranty: on page 94.

    Factory Mounted Controls and Safety DevicesControls and safety devices are factory wired and mounted within the unit. They include a blower relay, compressor contactor, 24V transformer, reversing valve coil and a solid state lockout controller (HP-5). A remov-able terminal block makes controls hookup easy. For more information on the controller and included safety devices, see HP-5 Microprocessor Board on page 12.

    Electrical Panel - Horizontal Unit

    Electrical Panel - Vertical Unit

  • 10 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    MS Product OptionsMS Product Options

    HydroBank MS water source heat pumps offer numerous factory-installed options that can help mini-mize field labor and enhance system performance.

    Extended Range, Geothermal UnitsAn extended-range or low-temperature option is avail-able on all heat pump units to allow heating operation down to 25F and cooling operation down to 40F entering fluid temperature. The option includes a freeze-stat water sensor, an insulated coaxial heat exchanger and insulated refrigerant piping.

    Extended Range, Insulated Unit

    Cupro-Nickel Heat ExchangerCupro-nickel tubes on the inner tube of the water-to-refrigerant heat exchanger provide additional corrosion protection in applications using well or city water.

    Electronically Commutated Motors (ECM)Electronically Commutated Motors (ECM) offer a high level of efficiency at a variety of speeds, boosting the units EER. They are ideal in applications where high-efficiency filtration is required. The motor maintains the design airflow as filters load and the system static pressure increases. These constant-torque motors feature five pre-programmed torque settings that can be changed in the field to match design requirements. A soft-start, soft-stop feature reduces noise at unit startup and shutdown.

    Constant-Torque ECM Motor

    DDC ControllerA field-supplied DDC controller can be factory mounted and wired by Mammoth. This allows the engineer to specify a specific control manufacturer and achieve simple interface of the network system. See EPiC DDC Controls on page 13.

    FreezestatA freezestat is available to sense the leaving water temperature. If the leaving water falls below 32F, the freezestat will open the safety lockout circuit and shut down the compressor. This option is beneficial on well water and city water applications where water tempera-tures can drop during the heating season.

    Waterside Economizer CoilA waterside economizer coil option allows pre-cooling of the entering air to take advantage of cool loop water and to reduce compressor operation during cool weather. The kit includes a two-row water coil, 3-way diverting valve and an entering water thermostat to divert the water through the coil if the temperature is below set point.

    Waterside Economizer Coil Option - Horizontal Units

    Waterside Economizer Coil Option - Vertical Units

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 11

    MS Product OptionsHot Gas Bypass ControlHot gas bypass prevents frosting of the evaporator coil during low-load conditions by keeping the compressor more fully-loaded. Hot, high-pressure refrigerant gas is diverted to the low-pressure suction side to help stabi-lize the system balance point. This option includes a hot gas bypass valve.

    Hot Gas Bypass Option

    Hot Gas ReheatHot gas reheat is the ideal solution to prevent over-cooling of the occupied space when the unit is in dehu-midification mode. Hot gas is used to reheat saturated air coming off the cooling coil without using an external heat source. Hot gas reheat coils are available on all unit sizes.

    Hot Gas Reheat Option

    Sound PackageA sound package option includes thick, 1 lb. den-sity fiberglass insulation on the entire unit, as well as the addition of a heavy dampening material over the entire bottom panel for reduced radiated sound levels.

    Motorized Shutoff ValveTwo-way motorized control valves are ideal in systems that employ VFDs on the condenser water pumps. When the space temperature set point is satisfied, the unit shuts down and the valve closes. Pump power is thus greatly reduced at reduced flows, resulting in sig-nificant energy savings. A motorized valve is available to shut off the water flow through the unit when the com-pressor is off. The valve is a normally open, power-close type and will open in the event of power loss.

    Motorized Valve Option

    Four-Sided Filter RackA four-sided, 2-inch filter rack is available as a factory-installed option to accept high-efficiency filters such as Merv 8 or Merv 13. This option includes gaskets between the rack and the cabinet, and along the edge of the filter access door. The gaskets maintain the leakage rate below 4 CFM per square foot of filter area at 0.5 ESP. The filter door pivots open for easy filter removal and replacement.

    Four-Sided Filter Rack Option

    Dirty Filter SwitchA dirty filter switch informs the maintenance personnel to change filters. The switch senses the pressure drop across the filter.

  • 12 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    ControlsControls

    HP-5 Microprocessor Board The standard HP-5 microprocessor board provides the control interface between the room thermostat and the units compressors, reversing valves, fan, safety features and troubleshooting fault indicators. A remov-able terminal block makes controls hookup easy. For more information and a wiring diagram, see the HP-5 Operation and Maintenance Manual. For a copy of this document, contact your local Mammoth representative or visit www.mammoth-inc.com.

    Fixed 8-Pole Terminal Block (P2) Removable 8-Pole Terminal Block (P1)

    HP-5 Microprocessor Board

    HP-5 Features and Benefits

    Random start delays the startup of the unit 5 to 35 seconds after coming off from an unoccupied or shutdown cycle to prevent all of the units from start-ing at the same time.

    Condensate overflow protection stops compres-sor operation if the drain pan sensor detects mois-ture at the top of the pan to prevent overflow due to clogged or slow-draining condensate piping

    Compressor anti-short cycle protection prevents the compressor from being energized for 5 minutes after shutoff to limit compressor cycling and to ex-tend compressor life.

    Shutdown allows the units to be shutoff with no compressor or fan operation in the event of an emer-gency. Shutdown is activated from a two-wire signal.

    LED diagnostic display communicates the status of the unit to indicate normal operating mode, low voltage condition, high voltage condition, shutdown mode, high pressure/ low pressure switch fault, and condensate sensor.

    High and low voltage protection shuts off the unit in the event the supply voltage is too high or too low to protect the internal components from damage.

    Safety lockout prevents compressor operation if any of the following safety switches trip: high pres-sure/low pressure switch, condensate overflow pro-tection or optional freezestat. The unit can be reset from the wall thermostat or the main unit disconnect.

    Auto reset-allows the unit to automatically reset itself three times within a 100 minute period; two-minute startup delay at initial startup; and at loss of power.

    Fan interlock makes sure the fan is on when the compressor is on.

    Lockout alarm sends a signal to the thermostat to illuminate an LED and close a set of dry contacts if any of the safety switches trip or if the unit is in shutdown mode due to a remote signal or to high/low voltage. Auxiliary dry contacts (set of normally-open and normally-closed) are activated when the compressor is on to operate a motorized valve.

    When coupled with the proper thermostat the HP-5 board is also compatible with the following features:

    o Night setback allows heating operation at a lower set point to maintain a minimum space temperature, which is activated by a two-wire signal. The fan will cycle with the compressor.

    o Night setup allows cooling operation at a higher set point to maintain a maximum space temperature, which is activated by a two-wire signal. The fan will cycle with the compressor.

    o Override allows night setback or setup modes to be deactivated for 2 hours while the unit resumes operation at its daytime set points. Override operation is activated by a push button on the wall thermostat.

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 13

    ControlsEPiC DDC ControlsAs an option, Mammoth offers factory-programmed and unit-mounted EPiC DDC controllers for precise unit operation. They are factory programmed per the application, and have a 16-bit processor with 1MB Flash RAM and 4MB of battery-backed RAM.

    The control programs, hand-held human-machine interface (HMI) files and editable set-points are stored on Flash RAM at the time of download or upon manual archive initiation.

    In the event of a battery-backed memory loss, the program, HMI and archived set-points are refreshed from the archived data in Flash RAM. An on-board, battery-backed, real-time clock is included to allow for stand-alone operation scheduling.

    The controllers include LED indicators for power, run, processor error for each control output, Building Man-agement System (BMS) communication transmit, and BMS communication receive.

    EPiC controllers are capable of BMS network com-munication using either BACnet MSTP, Modbus RTU, or JCI N2 without an external gateway device from 9.6k to 76.8k Baud. They conform to BACnet Advanced Appli-cation Controller (B-ACC) Standard Device Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 9.

    EPiC controllers are also capable of BMS network com-munication using LonWorks (LonTalk) protocol with an optional LonCard to only include the required neuron chip. There are no requirements for LonCard programming.

    A sensor/HMI network port allows 5 remote-mounted wall sensors and an HMI to be connected at the same time.

    Wiring diagrams for these controllers are provided on pages 46 and 47.

    Inputs:

    Supply (discharge) air temperature sensor

    Entering source water temperature sensor

    Leaving source water temperature sensor

    Emergency shutdown dry contact

    Remote start/stop dry contact

    Compressor alarm dry contact

    Compressor lockout dry contact

    Dirty filter dry contact

    Fan proof dry contact

    A sensor/HMI networked, wall-mounted, room/space air temperature sensor (optional room/spare air temperature/humidity sensor).

    Digital Outputs:

    Supply Fan Start

    Compressor Start

    Reversing valve

    Common Alarm

    Analog Outputs (EPiC 583 Controller Only):

    Start and modulate a variable-capacity compressor

    Control an optional modulating heating source

    Control an optional reheat source

    For more control options, contact your Mammoth repre-sentative.

    EPiC 560 Controller

    EPiC 583 Controller with Analog Outputs

  • 14 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Application and Design Considerations Application and Design Considerations

    What is a water source heat pump? A water source heat pump (WSHP) is a self-contained, packaged cooling-and-heating unit with a reversible refrigeration cycle. The refrigeration circuit is comprised of a compressor, a refrigerant-to-air heat exchanger (air coil), a refrigerant-to-water heat exchanger, an expansion device (thermal expansion valve), and a reversing valve. See the figure below.

    Additionally, each water-source heat pump includes a blower to move air through the air-to-refrigerant heat exchanger, an air filter, unit-level controls, and possibly a few optional accessories depending on the application.

    Water source heat pump systems can provide more energy efficient operation than most other HVAC systems on the market today. Water loop (cooling tower/boiler) water source heat pump systems also offer low installation costs. Ground loop (geothermal) systems, though more expensive to install, due to the cost of the ground loop,

    provide exceptional efficiencies that usually recover the additional installation costs through lower energy costs.

    How A Water Source Heat Pump WorksThe refrigerant reversing valve is the key difference between a heat pump and a standard air conditioning system. It allows a single refrigerant-to-air heat exchanger to provide both cooled air and heated air to the conditioned space.

    In an air source heat pump system, a second refrig-erant-to-air heat exchanger is employed to remove heat from the refrigerant when the unit is in the cooling mode and to add heat to the system when the unit is in the heating mode. In a water source heat pump system, a refrigerant-to-water heat exchanger is employed for this purpose and the heat is transfered to a water loop.

    A detailed explanation of how this system works in both the cooling mode and the heating mode is provided on the next page.

    How a Water Source Heat Pump Works

    2

    Major Components

    Refrigerant-to-air heat exchangerCompressor

    Refrigerantto-water heat exchanger

    Reversing valve

    Thermal expansion

    valve

    Blower

    Controls

    Air Filter

    Water Source Heat Pump Components

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 15

    Application and Design Considerations Cooling Mode

    How a Water Source Heat Pump Works

    3

    Heat Pump in Cooling Mode

    Refrigerant-to-air heat exchanger

    Compressor

    Refrigerantto-water heat exchanger

    Reversing valve

    Thermal expansion

    valve

    Hot gas refrigerant

    Cool gas refrigerant

    Cold liquid refrigerant

    Warm liquid refrigerant

    Loop fluid

    Loop fluidCooled

    Air

    Blower

    In the cooling mode, hot, high-pressure refrigerant gas is pumped from the compressor (upper right in the figure below) to the reversing valve (center) which diverts it to the refrigerant-to-water heat exchanger (lower right). Heat is transferred from the refrigerant gas to the loop fluid and the refrigerant condenses into a warm liquid. The warm liquid refrigerant then flows through the thermal expansion valve which reduces its pressure and temperature. The cold liquid refrig-erant then flows to the refrigerant-to-air heat exchanger (upper left) where it changes state from a liquid to a gas. Heat is absorbed from the air during this state change, and the cooled air is blown into the conditioned space (lower left). The refrig-erant gas then flows back to the reversing valve, which diverts it to the compressor to repeat the cycle.

    Heating Mode

    How a Water Source Heat Pump Works

    4

    Heat Pump in Heating Mode

    Refrigerant-to-air heat exchanger

    Compressor

    Refrigerantto-water heat exchanger

    Reversing valve

    Thermal expansion

    valve

    Hot gas refrigerant

    Cool gas refrigerant

    Cold liquid refrigerant

    Loop fluid

    Loop fluidHeated

    Air

    Hot gas refrigerant

    Warm liquid refrigerant

    Cool gas refrigerant

    Blower

    In the heating mode, hot, high-pressure refrigerant gas is pumped from the compressor (upper right in the figure below) to the reversing valve (center). The reversing valve diverts it to to the refrigerant-to-air heat exchanger (upper left), where it changes state from a gas to a liquid. Heat is rejected to the air during this state change, and the heated air is blown into the conditioned space (lower left). The warm liquid refrigerant then flows through the thermal expansion valve which reduces its pres-sure and temperature. The cold liquid refrigerant then flows to the refrig-erant-to-water heat exchanger, where it changes state from a liquid to a gas. The refrig-erant absorbs heat from the loop fluid during the state change. The refrig-erant gas then flows back to the reversing valve, which diverts it to the compressor to repeat the cycle.

  • 16 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Application and Design Considerations Water Source Heat Pump SystemsIn a typical WSHP system, each office, classroom or other defined space within the building is equipped with its own water source heat pump. Each heat pump inde-pendently satisfies the heating or cooling requirements for that space, regardless of the requirements of any other space.

    Unlike conventional HVAC systems, this offers individual control and enhanced comfort in each conditioned space. Additional, dedicated outdoor air systems (DOAS) may be used to bring in outside air to meet fresh air requirements.

    All of the water source heat pumps in the building are connected to a common water distribution loop. In addition to the heat pumps, this water loop will typically include a cooling tower, a boiler, a primary pump, a standby pump and a loop water temperature controller. In a ground loop (geothermal) system, the cooling tower and/or the boiler may not be needed, depending on the size of the ground loop and the local climate.

    Water Loop (Boiler/Tower) SystemsWater loop systems, also called standard, conventional or boiler/tower systems, use a two pipe water circulating system to add, remove, or transfer rejected heat to other units throughout the building. A boiler/tower system uses a natural gas or electric boiler located in a mechanical equipment room to provide heat. A cooling tower is used to dissipate waste heat. This system typically has the lowest installed cost of the loop options.

    Boiler/Tower System

    Summer Cooling Mode

    In the summer cooling mode, the water source heat pumps cool the space and reject heat to the water loop. If the loop temperature rises above the tower set point, the heat added to the water loop is rejected to the atmo-sphere through the cooling tower. See the Boiler/Tower System - Summer Cooling Mode figure below.

    Winter Heating Mode

    In the winter heating mode, the heat pumps heat the space using heat from the water loop and from the heat pump compressors heat of compression. The heat removed from the water loop is replenished by the boiler or by the ground loop. See the Boiler/Tower System - Winter Heating Mode figure on the next page.

    Boiler / Tower System

    3

    Summer Operation

    3

    Coolingtower on

    Water pumps

    Heat pumps in cooling mode

    Water distribution loop

    Boiler off

    3-wayvalve

    90F[32C]

    3-wayvalve

    Boiler/Tower System - Summer Cooling Mode

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 17

    Application and Design Considerations

    Boiler / Tower System

    4

    Winter Operation

    4

    Coolingtower off

    Water pumps

    Heat pumps inheating model

    Water distribution loop

    Boiler on

    3-wayvalve

    60F[16C]

    3-wayvalve

    Boiler/Tower System - Winter Heating Mode

    Balanced Mode - A Major Advantage of Water Source Heat Pump Systems

    Most modern buildings have a net cooling requirement year round in the interior core, irrespective of the out-side temperature. This is due to internal heat gains from people, office equipment and lighting. When this is the case, heat pumps in the interior core reject heat to the common water loop year round. In the winter, this heat is absorbed by those units on the building perimeter that are in heating mode. See the Boiler/Tower System - Balanced Mode figure below.

    In effect, the system is moving energy around the building from where it is in excess to areas where it is needed. In many instances, the result is a balanced system where the heat generated in the interior space is sufficient to heat the perimeter space with neither the cooling tower nor the boiler operating. This is especially true during the spring or fall when the demand for heating or cooling is lower. This makes a water source heat pump system one of the most energy efficient systems on the market.

    Boiler / Tower System

    5

    Spring and Fall Operation

    5

    Coolingtower off

    Water pumps

    Heat pumps some in cooling mode,some in heating mode

    Water distribution loop

    Boiler off3-wayvalve

    3-wayvalve

    Boiler/Tower System - Balanced Mode

  • 18 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Application and Design Considerations Ground Loop (Geothermal) SystemsGround loop systems take advantage of the earths rela-tively constant temperature and use the ground, surface water or well water to absorb and eject heat from the water source heat pump fluid loop. During the summer, the heat pumps absorb heat from the building and store it in the ground. See the Geothermal System - Summer

    Cooling Mode figure below. During the winter, they absorb heat from the ground and transfer it into the building. See the Geothermal System - Winter Heating Mode figure below.

    During the fall and spring, some water source heat pumps are typically absorbing heat from the water loop while others are rejecting it.

    Ground Loop

    Geothermal (Ground Loop) System

    7

    Summer Operation

    7

    Water pumpsHeat pumps in cooling mode

    Water distribution loop

    Geothermal System - Summer Cooling Mode

    Ground Loop

    Geothermal (Ground Loop) System

    8

    Winter Operation

    8

    Water pumpsHeat pumps in heating mode

    Water distribution loop

    Geothermal System - Winter Heating Mode

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 19

    Application and Design Considerations Ground Loop System TypesIn a geothermal system, lengths of high-density poly-ethylene pipe are typically buried in the earth either in vertical bore holes or in horizontal trenches. Fluid from the distribution loop inside the building circulates through these pipes and either rejects heat to the earth or absorbs heat from it. Systems may also be config-ured to reject or absorb heat from ground water or a pond, lake or stream.

    Horizontal Closed-Loop Systems

    Horizontal closed-loop geothermal systems use a series of parallel loops installed in trenches approximately 5 feet below the ground. The piping may be installed using a four-pipe or a six-pipe design. This system is well suited for applications where physical space is available or where vertical bore drilling is prohibitive. Between 1,500 and 2,500 square feet of space per ton of cooling is required.

    Horizontal Closed-Loop System

    Vertical Closed-Loop Systems

    Vertical closed-loop geothermal systems are ideal for projects with minimum available space. Vertical bore holes are drilled 150 to 500 feet deep depending on building design considerations. Plastic polyethylene U-bend loops are inserted into the holes and are con-nected in a parallel, reverse-return arrangement to allow fluid to circulate evenly throughout the bore field. Depending on the design, loop temperatures range from 37F to 95F.

    Vertical Closed-Loop System

    Surface Water Closed-Loop Systems

    Surface water, closed loop geothermal systems use a polyethylene loop or plate-type heat exchangers installed directly in a lake or pond near the building. This is an extremely efficient and cost effective system. Care must be taken to ensure the body of water will meet building loads. Debris problems from flooding or the need for public access may limit the use of this application.

    Surface Water Closed-Loop System

  • 20 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Application and Design Considerations Open-Loop Well Water Systems

    Open-loop systems use ground water to remove or add heat to the water loop. They are typically used in regions where ground water is plentiful. Water is typi-cally extracted and discharged back to the aquifer. The major benefit is the constant well water temperature which provides very efficient operation at a relatively low installed cost. An isolation heat exchanger can be added to reduce maintenance costs and conserve water.

    This system usually has supply wells and return wells. Some states have requirements regarding the depth of return wells. Check local regulations. Water should be tested and strainers are typically required as poor water quality can increase heat exchanger scaling and suspended solids can lead to heat exchanger erosion.

    Open-Loop Well Water System

    Hybrid Geothermal SystemsIn a traditionally designed ground-source heat pump system, no cooling tower is necessary. In addition, if the heat pumps can satisfy all building heating require-ments, no boiler is necessary, saving initial cost and floor space. That being said, there are applications where the addition of a cooling tower or boiler to the system makes economic sense, since it can significantly reduce the size requirements for the ground loop field.

    Hybrid System for Southern Climates

    In southern climates with long, hot summers and mild winters, the size of the ground loop field required to eject heat to the ground can be reduced considerably by adding a cooling tower to the system. The cooling tower provides supplemental cooling to the system on hot summer days. See the Hybrid System with Cooling Tower figure below.

    Ground Loop

    Hybrid Geothermal Systems

    14

    With Cooling Tower for Southern Climates

    14

    Water pumpsHeat pumps in cooling mode

    Water distribution loop

    3-wayvalve

    Cooling tower supplements ground loopwhen cooling demand is high

    Hybrid System with Cooling Tower

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 21

    Application and Design Considerations Hybrid System for Northern Climates

    In northern climates with short summers and long, cold winters, the size of the ground loop field required to absorb heat from the ground can be reduced con-siderably by adding a boiler to the system. The boiler

    provides supplemental heating to the system on cold winter days. The ground loop must be bypassed during boiler operation. See the Hybrid System with Boiler figure below.

    Ground Loop

    Hybrid Geothermal Systems

    15

    With Boiler for Northern Climates

    15

    Water pumps

    Heat pumps in heating mode

    Water distribution loop

    3-wayvalve

    Boiler provides heat when demand is high; ground loop is bypassed

    Hybrid System with Boiler

  • 22 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Horizontal Unit InstallationHorizontal Unit Installation

    Mounting Horizontal units are typically suspended from the ceiling using four threaded rods (supplied by others). The rods should be attached to building structural members. See the Suggested Horizontal Unit Mounting figure below for a typical mounting configuration. The rods are fas-tened to each corner of the unit through factory-provided mounting brackets and rubber isolators. See the instal-lation and operation manual provided with the unit for detailed instructions.

    Do not locate units above noise-sensitive areas such as offices, meeting rooms, and classrooms. If possible, avoid locations above areas where there is considerable traffic as service time may be limited during occupied hours. Placing units above hallways is a typical location in schools to avoid potential noise problems, with supply and return air ducted to adjacent classrooms. Such locations may limit service time during school hours.

    Suggested Horizontal Unit Mounting

    Suggested Service ClearancesUnits should be positioned to provide clearance to per-form routine maintenance or service, including easy filter replacement. The figure to the right above shows sug-gested clearances. Any additional clearances would be beneficial, but are not always necessary. For information on filter sizes, see Table 8: Physical Data: Horizontal Units on page 46.

    The requirements on any specific unit may increase or decrease depending on factors such as electrical instal-lation codes. If return air is not ducted, it is important to provide enough clearance for adequate airflow.

    2 ft (61 cm)service access

    filter removal(width of filter)

    2 ft (61 cm)motor

    access end discharge

    2 ft (61 cm)motor access

    straight discharge

    Suggested Horizontal Unit Service Clearances

    PipingUnits are usually connected to the water loop supply and return piping using a reverse return arrangement. A flow control device is included to maintain proper water flow for each zone. A flexible, high-pressure hose should be used to connect the system piping to the unit to simplify installation and provide sound attenuation. One end of the hose should have a swivel fitting for removal of the unit for servicing.

    The system piping design should include supply and return shutoff valves to facilitate the removal of one unit for servicing or replacement while the system continues to operate. The return valve may be used for water flow balancing. It will typically have a memory stop to allow it to adjust to the proper position for the required flow upon reopening. Fixed flow valves can be used to replace the memory-type valve.

    Providing pressure and temperature ports allows mea-surement of these values during operation.

    Vented PVC Condensate Trap by Others

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 23

    Horizontal Unit InstallationCondensate Drain Piping A flush-mounted, female thread, condensate connec-tion is provided on the cabinet. See Horizontal Units Dimensional Data on page 47 for location and sizing. Condensate piping can be PVC, steel or copper. PVC typically eliminates the need to insulate the pipe to prevent sweating.

    A condensate trap that has a depth of at least 3 inches or 2.5 times the the expected negative static pressure of the unit must be provided. The condensate pipe run must slope down from the unit at least 1/8 inch per foot. The trap may be constructed of PVC, copper or steel. Piping should be vented. See Vented PVC Condensate Trap by Others on page 22 for an example. Refer to local codes for the correct condensate piping to drains.

    Ductwork and Sound Attenuation Horizontal, ceiling-mounted heat pumps virtually always have discharge ductwork attached to the unit. A collar is provided on the discharge to facilitate attachment to the ductwork. Ductwork should conform to industry standards as listed in the ASHRAE Systems Guide.

    Good design practice requires a flexible connector between the collar and transition to the main duct system. This connector attenuates sound from the unit, especially fan sound, and simplifies unit removal.

    Ductwork should be lined with an acoustic, thermal insulation that is a minimum of inch thick. For sensi-tive installations, use 1-inch insulation a minimum of five to 10 feet prior to each diffuser. For applications that are

    especially acoustically sensitive, consider an acoustic kit that includes additional unit lining and dampening mate-rial beneath the entire unit.

    Ducted returns may be used on horizontal units for acoustically sensitive applications. Return ducting should extend at least 12 inches from the coil before transitioning to provide even air distribution across the coil. A flexible connector should be used to connect the unit to the return ducting to attenuate unit sound levels and allow ease of unit removal. The filter section is sup-plied with a bracket to accommodate return ductwork.

    Changes in duct direction such as tees, elbows, and internal devices such as dampers that create airflow tur-bulence can increase acoustic problems. Minimize these items where possible. Placing a straight run of duct about the width between fittings will decrease turbulence and associated noise. Diffusers located in the bottom of a trunk duct pose acoustical problems. Volume control dampers should be placed well upstream of any air outlets.

    Applications that have a single duct discharge, such as hotels, should limit the velocity to a maximum of 600 fpm. These applications have a short run of discharge duct that must be fully lined with an elbow without turning vanes. Return air grilles should be located low on the sidewall and routed up to the ceiling plenum. An attenuator placed at the return opening will provide added acoustical protection.

    Flexible connectors

    Ductwork supported independently from unit

    Return air located away from unit fan

    Acoustic thermal lining

    Two 90 degree turns prior to intake

    ASHRAE AND SMACNA Suggested Supply and Return Air Ducting

  • 24 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Vertical Unit Installation Vertical Unit Installation

    LocationVertical units are intended for installation in a small mechanical room or closet. HydroBank MS unit design minimizes sound levels to allow installation adjacent to occupied spaces. The return may be ducted or non-ducted and is typically located ninety degrees to the closet door with access panels facing the door as shown in the figure below.

    Suggested Vertical Unit Mounting

    Suggested Service ClearancesLocate units for ease of filter and access panel removal. The closet door should extend past the end of the unit to allow for easy filter removal. A field-supplied line voltage disconnect is required for branch circuit protection.

    The figure to the right above shows minimum sug-gested clearances. Any additional clearances would be beneficial, but not always necessary. Units need to be accessed from the front for filter removal and for access to the electrical panel, blower motor, air coil and com-pressor compartment. For information on filter sizes, see Table 11: Physical Data: Vertical Units on page 74. The requirements on any specific unit may increase or be reduced depending on several factors such as maintenance requirements and mechanical or electrical installation codes. If return air is not ducted, enough clearance will be required to provide for adequate airflow.

    2 ft (61 cm)service access

    1 ft (31 cm) non-ductedunits for even air distributionacross coil

    filter removal(width of filter)

    Suggested Vertical Unit Service Clearances

    PipingUnits are usually connected to the water loop supply and return piping using a reverse return arrangement. A flow control device is included to maintain proper water flow for each zone. A flexible, high-pressure hose should be used to connect the system piping to the unit to simplify installation and provide sound attenuation. One end of the hose should have a swivel fitting for removal of the unit for servicing.

    The system piping design should include supply and return shutoff valves to facilitate the removal of one unit for servicing or replacement while the system continues to operate. The return valve may be used for water flow balancing. It will typically have a memory stop to allow it to adjust to the proper position for the required flow upon reopening. Fixed flow valves can be used to replace the memory-type valve.

    Providing pressure and temperature ports allows mea-surement of these values during operation.

    Vented PVC Drain Piping (Internally Trapped), Flexible Braided Hose Water Piping By Others

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 25

    Vertical Unit Installation Condensate Drain Piping Condensate lines on vertical units are internally trapped. A 3/4 FPT, flush-mounted, condensate drain connection is provided on the outside of the cabinet. Condensate piping can be PVC, steel or copper. PVC typically elimi-nates the need to insulate the pipe to prevent sweating. Piping should be vented. Refer to local codes for the correct condensate piping to drains.

    Ductwork and Sound Attenuation Vertical unit discharge ductwork should include a non-insulated transition from the unit connection to a flexible connector at the full duct size. It should also include a short run of duct and an elbow internally lined with insu-lation but without turning vanes. The main duct may tee into branch circuits with discharge diffusers. Ductwork should conform to industry standards as listed in the ASHRAE Systems Guide.

    Vertical unit return air is typically brought in through a grille in the closet door. The door should be located ninety degrees from the unit return to eliminate any line of sight. For non-ducted applications, a clearance in front of the unit of at least 12 is suggested to provide even air distribution across the air coil.

    Return air may also be brought in through a grille and ducted to the unit. This ductwork should be internally lined with acoustic insulation and include a flexible con-nector at the unit. Sound attenuation is particularly crit-ical at the unit return. Return ducting will likely increase the required width of the closet. The filter section on all units is supplied with a bracket to accommodate return ductwork.

    Ductwork should be lined with an acoustic, thermal insulation that is a minimum of inch thick. For sensi-tive installations, use 1-inch insulation a minimum of five to 10 feet prior to each diffuser. For applications that are especially acoustically sensitive, consider an acoustic kit that includes additional unit lining and dampening mate-rial beneath the entire unit.

    Changes in duct direction such as tees, elbows, and internal devices such as dampers that create airflow tur-bulence can increase acoustic problems. Minimize these items where possible. Placing a straight run of duct about the width between fittings will decrease turbulence and associated noise. Diffusers located in the bottom of a trunk duct pose acoustical problems. Volume control dampers should be placed well upstream of any air outlets.

    Flexible connectors

    Ductwork supported independently from unit

    Acoustic thermal lining

    Return air located away from unit fan

    Two 90 degree turns prior to intake

    ASHRAE AND SMACNA Suggested Supply and Return Air Ducting

  • 26 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Unit Selection ProceduresUnit Selection Procedures

    Mammoth HydroBank Select Software for Water Source Heat Pumps can be used to provide fast, accurate and complete selections of all water source heat pump products. It is recommended that you always use the HydroBank Select software to correctly match a unit to the actual zone loads and airflow requirements. This software is available from your local Mammoth repre-sentative.

    If situations prevent you from immediately accessing HydroBank Select software, use the catalog selection procedure below and confirm results with the selection software at a later date.

    Unit Selection Using Catalog DataDuring HVAC system design, a unit may need to be quickly selected or considered without the availability of the HydroBank Select Software. The following catalog selection procedures can quickly match a unit to the zone requirements.

    Boiler / Cooling Tower Application

    In this example we are using 80F dry bulb / 67F wet bulb entering air conditions for cooling and 70F entering air conditions for heating. Entering fluid tem-peratures for this Boiler / Tower application are 90F (32.2C) for cooling and 70F (21.1C) for heating. Existing zone load requirements are:

    Total Cooling Load = 33,600 BTUH Sensible Cooling Load = 25,300 BTUHTotal Heating Load = 26,100 BTUH Design Air Flow = 1,200 CFMEntering Air Temp - Cooling = 80F DB/67F WBEntering Air Temp - Heating = 70F DBEntering Fluid Temp - Cooling= 90FEntering Fluid Temp - Heating= 70FWater Flow (Based on Cooling) = 10.8 GPMCabinet configuration Horizontal

    First establish whether this application is commercial or multifamily. Commercial buildings are usually cooling dominant so the initial unit selection should match the cooling sensible load. If it is a multifamily application, you may need to match the heating requirement which, in some cases, could be the dominant load.

    Start by selecting a unit with approximately 36,000 BTUH of cooling. In this case the Mammoth horizontal MSH1036 (page 37) will supply the following capacities at 1200 CFM airflow and 10.8 GPM water flow:

    Zone requirement

    Catalog Capacity Values (MSH1036)

    Total Cooling Load = 33,600 BTUH 34,700 BTUHSensible Cooling Load = 25,300 BTUH 25,700 BTUHTotal Heating Load = 26,100 BTUH 44,300 BTUHDesign Air Flow = 1,200 CFM 1,200 CFMEntering Air Temp - Cooling =

    80F DB/67F WB

    80F DB/67F WB

    Entering Air Temp - Heating =

    70F DB 70F DB

    Entering Fluid Temp, Cooling=

    90F 90F

    Entering Fluid Temp, Heating=

    70F 70F

    Water Flow (Based on Cooling) =

    10.8 GPM 10.8 GPM

    Cabinet configuration: Horizontal Horizontal MSH1036

    Final Boiler / Tower zone selection = Mammoth MSH1036 Horizontal Cabinet

    Geothermal Ground Loop Application

    The following example illustrates the same zone in a geothermal application. Entering fluid temperatures for geothermal systems can be as high as 110F and as low as 20F. Design entering fluid temperatures for heating and cooling are to be determined by the design engineer and are usually based on location and /or ground temperatures. Typical design entering fluid tem-peratures are 90F for cooling (summer) and 40F for heating (winter). As a rule of thumb, the design entering fluid temperature for cooling is 10F below the maximum outdoor air temperature, and the design entering fluid temperature for heating is 40F above the minimum outdoor air temperature. Water flow rates are typically 2.5 to 3.0 GPM per ton and the use of antifreeze is recommended in most northern applications.

    Like the earlier Boiler / Tower example, we are using entering air temperatures of 80F dry bulb / 67F wet bulb entering air conditions for cooling and 70F entering air conditions for heating. It is determined that the highest entering water temperatures for the ground loop design will be 90F for cooling with expected entering water temperatures for heating at 35F.

    Antifreeze will be used in the loop field so capacity correction factors will be used and will be based on the type of antifreeze and concentration. The design air flow will be 95% of catalog data and will also require use of correction factors for final capacity output.

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 27

    Unit Selection ProceduresZone load requirements are:

    Total Cooling Load = 33,600 BTUH Sensible Cooling Load = 25,300 BTUHTotal Heating Load = 24,300 BTUH Design Air Flow = 1,140 CFMEntering Air Temp - Cooling = 80F DB/67F WBEntering Air Temp - Heating = 70F DBEntering Fluid Temp, Cooling = 90FEntering Fluid Temp, Heating = 35FWater Flow (Based on Cooling) = 10.8 GPMCabinet configuration Horizontal

    Start by selecting a unit with approximately 36,000 BTUH of cooling. In this case, the Mammoth horizontal MSH1036 (page 37) will supply the following capacities at 1200 CFM airflow and 10.8 GPM water flow. The heating capacity data (page 37) is 26,400 BTUH for 40F and 23,400 BTUH at 30F. The heating capacity at 35F is exactly between the two numbers and is 24,900 BTUH.

    Zone requirement

    Catalog capacity Values

    Total Cooling Load = 33,600 BTUH 34,700 BTUHSensible Cooling Load =

    25,300 BTUH 25,700 BTUH

    Total Heating Load = 24,300 BTUH 24,900 BTUHDesign Air Flow = 1,140 CFM 1,200 CFMEntering Air Temp - Cooling =

    80F DB/67F WB

    80F DB/67F WB

    Entering Air Temp - Heating =

    70F DB 70F DB

    Entering Fluid Temp, Cooling =

    90F 90F

    Entering Fluid Temp, Heating =

    35F 35F

    Water Flow (Based on Cooling) =

    10.8 GPM 10.8 GPM

    Cabinet configuration Horizontal Horizontal

    Next, determine reduced capacity based on the airflow and antifreeze correction factors available on 28 of this catalog. In this case the engineer is using 20% propylene glycol (with a sufficient inhibitor package) and airflow is 95% of catalog CFM.

    Glycol correction factor for 20% propylene glycol is:

    0.987 (Cooling and heating)

    Airflow correction factor for 1,140 CFM (95% of catalog) is:

    0.993 Total Cooling 0.974 Sensible Cooling 0.990 Heating

    Corrected Capacity = Capacity Table Data Air Flow Correction Antifreeze Correction

    Corrected Total Cooling =

    34,700 0.993 0.987 = 34,009 BTUH

    Corrected Sensible Cooling =

    25,700 0.974 0.987 = 24,706 BTUH

    Corrected Heating Capacity =

    24,900 0.99 0.987 = 24,330 BTUH

    Corrected CFM = 1,140 CFM

    Since the sensible cooling capacity is slightly less than the design load, judgment must be used to determine if the next larger capacity unit is necessary. Oversized equipment should be avoided to minimize the potential for humidity and comfort issues.Recommended selection = Mammoth MSH1036 Horizontal Cabinet

    Geothermal loop software programs are available to help determine the size of the loop field based on:

    Desired entering water temperatures for the system. These are usually the same temperatures that are used in this unit selection procedure.

    Specific loop field design criteria based on acreage available, loop field spacing, vertical bore depth, piping selected, flow rates, circulated heat transfer fluid, and local formation geology for the loop which produces specific min./max. loop temperatures for the unit selection.

  • 28 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Operating Limits and Correction FactorsOperating Limits and Correction Factors

    Table 1: Operating Limits: Water and Air Temperatures (F)Standard Range Low Temperature Geothermal

    Cooling Heating Cooling HeatingMinimum Water Temperature 50F 50F 40F 25FMaximum Water Temperature 110F 90F 110F 90FMinimum Ambient Air Temperature 50F 50F 50F 50FMaximum Ambient Air Temperature 110F 110F 110F 110FMinimum Entering Air Temperature 65F 40F 65F 40FMaximum Entering Air Temperature 100F 80F 100F 80F

    Table 2: Cooling Correction TableEnt Air WB

    FTotal Cooling

    CapacitySensible Cooling Capacity Multipliers - Entering DB F

    PowerHeat of

    Rejection65 70 75 80 80.6 85 90 9550 0.7633 * * * * * Condition Does Not Exist 1.0009 0.804755 0.8275 0.8356 * * * * * * * 1.0004 0.857760 0.9058 0.6384 0.8338 1.0288 * * * * * 1.0004 0.917265 0.9796 0.6348 0.8298 1.0250 1.0484 1.2198 * * 1.0000 0.9832

    66.2 1.0000 0.5870 0.7820 0.9766 1.0000 1.1717 * * 1.0000 1.000067 1.0138 0.5548 0.7497 0.9446 0.9681 1.1397 * * 1.0000 1.011470 1.0676 Operation

    Not Recommended0.6294 0.8238 0.8471 1.0186 1.2134 * 0.9996 1.0558

    75 1.1634 0.6217 0.6450 0.8160 1.0099 1.2044 0.9996 1.1349

    *Sensible capacity is equal to total capacity. ** AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of cooling - 80.6F DB/66.2F WB, and heating - 68F DB/59F WB.

    Table 3: Heating Correction TableEnt Air DB F Heating Capacity Heating Power Heat of Extraction

    45 1.0468 0.7762 1.118150 1.0417 0.8219 1.099655 1.0338 0.8693 1.077160 1.0230 0.9184 1.050765 1.0095 0.9687 1.020268 1.0000 1.0000 1.000070 0.9931 1.0212 0.985875 0.9739 1.0753 0.947380 0.9520 1.1311 0.9048

    Table 4: Air Flow Correction Table% of Rated Flow 85% 90% 95% 100% 105% 110% 115%

    CoolingTotal Cooling Capacity 0.9681 0.9795 0.9902 1.0000 1.0090 1.0171 1.0245

    Sensible Cooling 0.9126 0.9417 0.9710 1.0000 1.0289 1.0574 1.0858

    kW - Cooling 1.0004 1.0000 0.9996 1.0000 1.0004 1.0013 1.0026Total Heat of Rejection 0.9737 0.9831 0.9919 1.0000 1.0075 1.0144 1.0207

    HeatingTotal Heating Capacity 0.9731 0.9831 0.9920 1.0000 1.0069 1.0128 1.0178

    kW - Heating 1.0470 1.0296 1.0140 1.0000 0.9877 0.9772 0.9683Total Heat of Absorption 0.9536 0.9708 0.9863 1.0000 1.0120 1.0223 1.0309

    Table 5: Antifreeze Correction Table

    Total Sens kW Pres Drop Htg Cap kWPres Drop

    Water 1.000 1.000 1.000 1.000 1.000 1.000 1.000

    5% 0.998 0.998 1.002 1.003 0.993 0.998 1.040

    10% 0.996 0.996 1.003 1.005 0.987 0.996 1.080

    20% 0.991 0.991 1.006 1.014 0.973 0.992 1.160

    30% 0.965 0.965 1.023 1.023 0.917 0.974 1.225

    40% 0.955 0.955 1.030 1.030 0.890 0.965 1.324

    50% 0.943 0.943 1.038 1.038 0.865 0.956 1.419

    5% 0.995 0.995 1.003 1.006 0.989 0.997 1.070

    10% 0.991 0.991 1.006 1.012 0.979 0.994 1.140

    20% 0.982 0.982 1.012 1.020 0.958 0.987 1.285

    30% 0.950 0.950 1.033 1.033 0.854 0.953 1.433

    40% 0.937 0.937 1.042 1.042 0.813 0.939 1.614

    50% 0.922 0.922 1.053 1.053 0.770 0.923 1.816

    5% 0.998 0.998 1.002 1.003 0.981 0.994 1.140

    10% 0.996 0.996 1.004 1.006 0.963 0.989 1.220

    20% 0.990 0.990 1.007 1.018 0.931 0.979 1.330

    30% 0.947 0.947 1.035 1.035 0.856 0.953 1.383

    40% 0.930 0.930 1.047 1.047 0.815 0.939 1.523

    50% 0.911 0.911 1.060 1.060 0.779 0.926 1.639

    5% 0.997 0.997 1.002 1.004 0.989 0.997 1.070

    10% 0.994 0.994 1.005 1.009 0.965 0.980 1.115

    20% 0.986 0.986 1.010 1.020 0.924 0.968 1.190

    30% 0.951 0.951 1.032 1.032 0.895 0.966 1.235

    40% 0.936 0.936 1.043 1.043 0.863 0.955 1.323

    50% 0.920 0.920 1.055 1.055 0.833 0.945 1.399

    Heating: 30F, 1.1C

    Ethylene Glycol

    Propylene Glycol

    Ethanol

    Methanol

    Type % by Wgt

    Cooling: 90F, 32.2C

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 29

    Horizontal Units ISO Performance DataHorizontal Units ISO Performance Data

    Table 6: Horizontal Unit Certified Performance, PSC Motor*

    Unit Size CFM GPM

    Water Loop (Boiler/Tower) Ground Loop (Geothermal)

    Cooling Heating Cooling HeatingCapacity

    Btu/hrSensible

    Btu/hr KW EERCapacity

    Btu/hr KW COPCapacity

    Btu/hrSensible

    Btu/hr KW EERCapacity

    Btu/hr KW COP

    006

    Contact Factory009

    012

    015 500 4.0 14,100 11,200 1.05 13.4 15,800 1.05 4.4 14,800 11,200 0.97 15.2 10,100 0.95 3.1

    019 600 4.5 19,000 14,200 1.37 13.9 22,100 1.44 4.5 20,100 14,200 1.27 15.8 13,700 1.22 3.3

    024 800 6.0 22,600 18,200 1.74 13.0 26,500 1.77 4.4 23,700 18,200 1.57 15.1 16,500 1.51 3.2

    030 1000 7.0 28,100 22,600 2.15 13.1 32,000 2.18 4.3 30,000 22,600 1.95 15.4 21,500 1.91 3.3

    036 1200 9.0 35,500 28,000 2.50 14.2 36,500 2.43 4.4 37,600 28,000 2.34 16.1 24,900 2.21 3.3

    042 1400 10.5 40,800 32,200 3.04 13.4 44,000 2.93 4.4 42,500 32,200 2.78 15.3 29,000 2.58 3.3

    048 1600 12.0 48,000 37,200 3.40 14.1 54,500 3.63 4.4 50,500 37,200 3.20 15.8 34,500 3.06 3.3

    060 2000 15.0 59,000 46,100 4.50 13.1 69,500 4.74 4.3 60,500 46,100 4.12 14.7 47,000 4.30 3.2

    070 2200 18.0 67,000 53,000 4.93 13.6 77,000 5.25 4.3 69,000 53,000 4.48 15.4 53,000 4.85 3.2*AHRI/ISO 13256-1 certified capacity and efficiency. Cooling capacities are based on 80.6F db, 66.2F wb (27C) entering air temperature, 86F (30C) entering water temperature for Water Loop and 77F (25C) entering water temperature for Ground Loop. Heating capacities are based on 68F (20C) entering air temperature, 77F (25C) entering water temperature for Water Loop and 32F(0C) entering water temperature for Ground Loop.

    Table 7: Horizontal Unit Certified Performance, ECM Motor*

    Unit Size CFM GPM

    Water Loop (Boiler/Tower) Ground Loop (Geothermal)

    Cooling Heating Cooling HeatingCapacity

    Btu/hrSensible

    Btu/hr KW EERCapacity

    Btu/hr KW COPCapacity

    Btu/hrSensible

    Btu/hr KW EERCapacity

    Btu/hr KW COP

    015 500 4.0 14,300 11,500 1.01 14.2 15,400 1.00 4.5 14,900 11,800 0.93 16.1 9,700 0.86 3.3

    019 600 4.5 19,200 14,500 1.33 14.5 21,500 1.38 4.6 20,100 14,900 1.21 16.6 13,500 1.16 3.4

    024 800 6.0 23,000 18,800 1.65 14.0 25,700 1.66 4.6 24,000 19,200 1.51 15.9 16,200 1.41 3.4

    030 1000 7.0 28,600 23,400 2.04 14.1 31,100 2.06 4.4 29,800 23,900 1.88 15.9 19,600 1.76 3.3

    036 1200 9.0 35,900 28,800 2.41 14.9 35,600 2.34 4.5 37,500 29,400 2.23 16.9 22,500 2.00 3.3

    042 1400 10.5 41,300 33,100 2.95 14.0 43,000 2.82 4.5 43,100 33,900 2.74 15.8 27,300 2.43 3.3

    048 1600 12.0 48,500 38,200 3.31 14.7 53,000 3.44 4.5 50,800 39,200 3.04 16.7 33,500 2.93 3.4

    060 2000 15.0 60,000 48,000 4.28 14.0 67,600 4.49 4.4 62,700 49,200 3.97 15.8 43,100 3.87 3.3

    070 2200 18.0 68,000 54,700 4.73 14.4 75,100 5.03 4.4 71,000 56,000 4.39 16.2 47,700 4.32 3.2*AHRI/ISO 13256-1 certified capacity and efficiency. Cooling capacities are based on 80.6F db, 66.2F wb (27C) entering air temperature, 86F (30C) entering water temperature for Water Loop and 77F (25C) entering water temperature for Ground Loop. Heating capacities are based on 68F (20C) entering air temperature, 77F (25C) entering water temperature for Water Loop and 32F(0C) entering water temperature for Ground Loop.

  • 30 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Horizontal Units Capacity DataHorizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/71

    100

    Notes:(1) Shaded area is extended range; antifreeze required. (2) Ratings at 30F and 40F EWT are based on a 15% methanol antifreeze solution. (3) AHRI/ISO 13256-1 certified conditions are 80.6F DB/66.2F WB in cooling and 68F in heating. (4) Table does not include fan credit or water pump penalty power corrections required for AHRI/ISO standard performance ratings. (5) Data are based on full load operation. (6) Performance data are subject to change without notice. (7) Interpolation is permissible; extrapolation is not.(8) For performance data outside the EAT listed, refer to the Hydrobank Select Software Program.

    110

    90 90

    85 80

    80 70

    70 60

    60 50

    50 40

    40

    HydroBank MS Horizontal WSHP - Size 006 (PSC Motor) at Rated 250 CFM Air Flow

    Entering Water

    Temp. FGPM

    Water Pressure

    Drop Ft H2O

    Cooling Heating

    30

    Cons

    ult

    Facto

    ry

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 31

    Horizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/71

    100

    Notes:(1) Shaded area is extended range; antifreeze required. (2) Ratings at 30F and 40F EWT are based on a 15% methanol antifreeze solution. (3) AHRI/ISO 13256-1 certified conditions are 80.6F DB/66.2F WB in cooling and 68F in heating. (4) Table does not include fan credit or water pump penalty power corrections required for AHRI/ISO standard performance ratings. (5) Data are based on full load operation. (6) Performance data are subject to change without notice. (7) Interpolation is permissible; extrapolation is not.(8) For performance data outside the EAT listed, refer to the Hydrobank Select Software Program.

    110

    30

    90

    80

    70

    60

    50

    40

    HydroBank MS Horizontal WSHP - Size 009 (PSC Motor) at Rated 300 CFM Air Flow

    Entering Water

    Temp. FGPM

    Water Pressure

    Drop Ft H2O

    Cooling Heating

    80

    85

    90

    40

    50

    60

    70

    Cons

    ult

    Facto

    ry

  • 32 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Horizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/63 6080/67 7085/71 8075/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/7175/6380/6785/71

    40

    100

    Notes:(1) Shaded area is extended range; antifreeze required. (2) Ratings at 30F and 40F EWT are based on a 15% methanol antifreeze solution. (3) AHRI/ISO 13256-1 certified conditions are 80.6F DB/66.2F WB in cooling and 68F in heating. (4) Table does not include fan credit or water pump penalty power corrections required for AHRI/ISO standard performance ratings. (5) Data are based on full load operation. (6) Performance data are subject to change without notice. (7) Interpolation is permissible; extrapolation is not.(8) For performance data outside the EAT listed, refer to the Hydrobank Select Software Program.

    110

    30

    90

    80

    70

    60

    50

    40

    HydroBank MS Horizontal WSHP - Size 012 (PSC Motor) at Rated 400 CFM Air Flow

    Entering Water

    Temp. FGPM

    Water Pressure

    Drop Ft H2O

    Cooling Heating

    80

    85

    90

    50

    60

    70

    Cons

    ult

    Facto

    ry

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 33

    Horizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 16.1 11.3 18.5 0.71 22.8 60 9.9 6.9 0.89 3.380/67 17.3 11.7 19.7 0.71 24.5 70 9.7 6.4 0.97 2.985/71 18.6 12.1 21.0 0.71 26.3 80 9.3 5.7 1.05 2.675/63 16.4 11.5 18.7 0.68 24.1 60 10.2 7.2 0.90 3.380/67 17.6 11.9 19.9 0.68 25.9 70 9.9 6.6 0.98 3.085/71 18.9 12.3 21.2 0.68 27.8 80 9.6 5.9 1.06 2.675/63 16.6 11.6 18.9 0.67 24.8 60 10.3 7.3 0.90 3.480/67 17.8 12.0 20.1 0.67 26.6 70 10.1 6.7 0.98 3.085/71 19.2 12.4 21.4 0.67 28.6 80 9.7 6.0 1.07 2.775/63 15.6 11.1 18.3 0.81 19.3 60 11.2 8.1 0.92 3.680/67 16.7 11.5 19.4 0.81 20.7 70 10.9 7.5 1.00 3.285/71 17.9 11.9 20.7 0.81 22.3 80 10.5 6.8 1.09 2.875/63 15.9 11.2 18.5 0.77 20.5 60 11.5 8.4 0.93 3.680/67 17.0 11.6 19.7 0.77 22.0 70 11.2 7.8 1.01 3.385/71 18.3 12.0 20.9 0.77 23.6 80 10.8 7.0 1.10 2.975/63 16.1 11.3 18.7 0.76 21.1 60 11.7 8.5 0.93 3.780/67 17.2 11.7 19.8 0.76 22.6 70 11.4 7.9 1.02 3.385/71 18.5 12.1 21.1 0.76 24.3 80 10.9 7.1 1.11 2.975/63 14.8 10.7 17.9 0.91 16.3 60 13.4 10.0 0.97 4.080/67 15.9 11.2 19.0 0.91 17.5 70 13.0 9.3 1.06 3.685/71 17.1 11.5 20.2 0.91 18.8 80 12.5 8.5 1.16 3.275/63 15.1 10.9 18.1 0.87 17.3 60 13.7 10.4 0.98 4.180/67 16.2 11.3 19.2 0.87 18.6 70 13.3 9.7 1.07 3.685/71 17.4 11.7 20.4 0.87 20.0 80 12.8 8.8 1.17 3.275/63 15.3 11.0 18.2 0.86 17.9 60 13.9 10.5 0.99 4.180/67 16.4 11.4 19.4 0.86 19.2 70 13.5 9.8 1.08 3.785/71 17.6 11.8 20.6 0.86 20.6 80 13.0 9.0 1.18 3.275/63 14.0 10.4 17.5 1.01 13.9 60 14.7 11.3 1.01 4.380/67 15.1 10.8 18.5 1.01 14.9 70 14.3 10.6 1.10 3.885/71 16.2 11.2 19.7 1.01 16.1 80 13.8 9.7 1.20 3.475/63 14.3 10.5 17.6 0.97 14.8 60 15.2 11.7 1.02 4.480/67 15.4 10.9 18.7 0.97 15.9 70 14.7 10.9 1.11 3.985/71 16.5 11.3 19.8 0.97 17.1 80 14.1 10.0 1.21 3.475/63 14.5 10.6 17.8 0.95 15.2 60 15.3 11.9 1.02 4.480/67 15.6 11.0 18.8 0.95 16.4 70 14.9 11.1 1.11 3.985/71 16.7 11.4 20.0 0.95 17.6 80 14.3 10.2 1.22 3.575/63 13.3 10.1 17.0 1.11 11.9 60 16.1 12.6 1.04 4.580/67 14.2 10.5 18.0 1.11 12.8 70 15.7 11.8 1.13 4.085/71 15.3 10.9 19.1 1.11 13.8 80 15.0 10.8 1.24 3.675/63 13.5 10.2 17.2 1.07 12.7 60 16.6 13.0 1.05 4.680/67 14.5 10.6 18.2 1.07 13.6 70 16.1 12.2 1.15 4.185/71 15.6 11.0 19.2 1.07 14.6 80 15.5 11.2 1.25 3.675/63 13.7 10.2 17.3 1.05 13.1 60 16.8 13.2 1.05 4.780/67 14.7 10.7 18.3 1.05 14.0 70 16.3 12.4 1.15 4.285/71 15.8 11.1 19.4 1.05 15.1 80 15.7 11.4 1.25 3.775/63 12.8 9.9 16.8 1.16 11.0 60 17.5 13.8 1.07 4.880/67 13.8 10.3 17.8 1.16 11.9 70 17.0 13.0 1.17 4.385/71 14.8 10.7 18.8 1.16 12.7 80 16.3 12.0 1.28 3.875/63 13.1 10.0 16.9 1.11 11.8 60 18.0 14.3 1.08 4.980/67 14.1 10.4 17.9 1.11 12.6 70 17.5 13.5 1.18 4.385/71 15.1 10.8 18.9 1.11 13.6 80 16.8 12.4 1.29 3.875/63 13.3 10.1 17.0 1.09 12.1 60 18.2 14.5 1.09 4.980/67 14.3 10.5 18.0 1.09 13.0 70 17.7 13.7 1.19 4.485/71 15.3 10.9 19.0 1.09 14.0 80 17.0 12.6 1.29 3.975/63 12.4 9.7 16.6 1.21 10.2 60 18.9 15.1 1.10 5.080/67 13.4 10.1 17.5 1.21 11.0 70 18.3 14.2 1.20 4.585/71 14.4 10.5 18.5 1.21 11.8 80 17.6 13.1 1.31 3.975/63 12.7 9.8 16.7 1.16 10.9 60 19.4 15.6 1.11 5.180/67 13.6 10.2 17.6 1.16 11.7 70 18.9 14.7 1.22 4.585/71 14.6 10.6 18.6 1.16 12.6 80 18.1 13.6 1.33 4.075/63 12.8 9.9 16.7 1.14 11.2 60 19.7 15.9 1.12 5.280/67 13.8 10.3 17.7 1.14 12.1 70 19.1 14.9 1.22 4.685/71 14.8 10.7 18.7 1.14 13.0 80 18.4 13.8 1.33 4.075/63 11.6 9.3 16.1 1.32 8.880/67 12.4 9.7 16.9 1.32 9.485/71 13.4 10.1 17.9 1.32 10.275/63 11.8 9.4 16.1 1.26 9.480/67 12.7 9.9 17.0 1.26 10.185/71 13.6 10.2 17.9 1.26 10.875/63 12.0 9.5 16.2 1.24 9.780/67 12.9 9.9 17.1 1.24 10.485/71 13.8 10.3 18.0 1.24 11.275/63 10.7 9.0 15.5 1.42 7.580/67 11.5 9.4 16.3 1.42 8.185/71 12.4 9.8 17.2 1.42 8.775/63 10.9 9.1 15.6 1.36 8.080/67 11.7 9.5 16.4 1.36 8.685/71 12.6 9.9 17.3 1.36 9.375/63 11.1 9.1 15.6 1.33 8.380/67 11.9 9.5 16.4 1.33 8.985/71 12.8 9.9 17.3 1.33 9.6

    100

    2.8 9.1Notes:(1) Shaded area is extended range; antifreeze required. (2) Ratings at 30F and 40F EWT are based on a 15% methanol antifreeze solution. (3) AHRI/ISO 13256-1 certified conditions are 80.6F DB/66.2F WB in cooling and 68F in heating. (4) Table does not include fan credit or water pump penalty power corrections required for AHRI/ISO standard performance ratings. (5) Data are based on full load operation. (6) Performance data are subject to change without notice. (7) Interpolation is permissible; extrapolation is not.(8) For performance data outside the EAT listed, refer to the Hydrobank Select Software Program.

    4.0 16.1

    4.8 21.8

    110

    2.8 9.1

    4.0 16.1

    4.8 21.8

    304.0 18.6

    4.8 25.3

    904.0 16.1

    4.8

    804.0 16.1

    4.8 21.8

    2.8 9.1

    704.0 16.1

    4.8 21.8

    2.8 9.1

    604.0 16.1

    4.8 21.8

    2.8 9.1

    504.0 16.1

    4.8 21.8

    2.8 9.1

    404.0 16.1

    4.8 21.8

    2.8 9.1

    HydroBank MS Horizontal WSHP - Size 015 (PSC Motor) at Rated 500 CFM Air Flow

    Entering Water

    Temp. FGPM

    Water Pressure

    Drop Ft H2O

    Cooling Heating

    80

    85

    90

    21.8

    40

    2.8

    50

    60

    70

    2.8 9.1

    10.6

  • 34 Catalog MAMM-WSHP-PC-1MSA (October 2014)

    Horizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 21.7 14.6 24.8 0.92 23.6 60 13.8 9.6 1.22 3.380/67 23.2 15.1 26.4 0.92 25.3 70 13.4 8.8 1.34 2.985/71 25.0 15.6 28.1 0.92 27.2 80 12.9 7.9 1.46 2.675/63 22.1 14.8 25.1 0.88 25.1 60 14.2 10.0 1.23 3.480/67 23.7 15.3 26.7 0.88 26.9 70 13.8 9.2 1.35 3.085/71 25.5 15.8 28.5 0.88 28.9 80 13.3 8.2 1.47 2.675/63 22.4 15.0 25.3 0.87 25.8 60 14.4 10.1 1.24 3.480/67 24.0 15.5 27.0 0.87 27.7 70 14.0 9.3 1.36 3.085/71 25.8 15.9 28.7 0.87 29.8 80 13.4 8.4 1.48 2.775/63 20.9 14.3 24.5 1.05 19.9 60 15.6 11.3 1.27 3.680/67 22.5 14.8 26.1 1.05 21.3 70 15.2 10.4 1.39 3.285/71 24.1 15.2 27.7 1.05 22.9 80 14.6 9.4 1.51 2.875/63 21.4 14.5 24.8 1.01 21.2 60 16.1 11.7 1.28 3.780/67 22.9 15.0 26.4 1.01 22.7 70 15.6 10.8 1.40 3.385/71 24.6 15.4 28.1 1.01 24.4 80 15.0 9.8 1.53 2.975/63 21.6 14.6 25.0 0.99 21.8 60 16.3 11.9 1.28 3.780/67 23.2 15.1 26.6 0.99 23.4 70 15.8 11.0 1.41 3.385/71 24.9 15.5 28.3 0.99 25.1 80 15.2 9.9 1.54 2.975/63 20.0 13.8 24.0 1.20 16.7 60 18.6 14.0 1.35 4.080/67 21.4 14.3 25.5 1.19 17.9 70 18.1 13.0 1.47 3.685/71 23.0 14.7 27.1 1.19 19.2 80 17.3 11.8 1.61 3.275/63 20.4 14.0 24.3 1.14 17.8 60 19.1 14.5 1.36 4.180/67 21.9 14.5 25.8 1.14 19.1 70 18.6 13.5 1.49 3.785/71 23.5 14.9 27.4 1.14 20.5 80 17.9 12.3 1.63 3.275/63 20.6 14.1 24.4 1.12 18.4 60 19.4 14.7 1.37 4.280/67 22.1 14.6 26.0 1.12 19.7 70 18.8 13.7 1.50 3.785/71 23.8 15.1 27.6 1.12 21.2 80 18.1 12.5 1.64 3.275/63 18.9 13.3 23.5 1.34 14.2 60 20.5 15.8 1.39 4.380/67 20.3 13.8 24.9 1.34 15.2 70 20.0 14.7 1.53 3.885/71 21.8 14.3 26.4 1.34 16.3 80 19.2 13.5 1.67 3.475/63 19.3 13.5 23.7 1.28 15.1 60 21.2 16.4 1.41 4.480/67 20.7 14.0 25.1 1.28 16.2 70 20.6 15.3 1.54 3.985/71 22.3 14.4 26.6 1.28 17.4 80 19.7 14.0 1.69 3.475/63 19.6 13.6 23.8 1.25 15.6 60 21.4 16.6 1.41 4.480/67 21.0 14.1 25.3 1.25 16.8 70 20.8 15.5 1.55 3.985/71 22.5 14.6 26.8 1.25 18.0 80 20.0 14.2 1.69 3.575/63 17.9 12.8 22.9 1.48 12.1 60 22.5 17.6 1.44 4.680/67 19.2 13.3 24.2 1.48 13.0 70 21.8 16.5 1.58 4.185/71 20.6 13.8 25.6 1.48 14.0 80 21.0 15.1 1.72 3.675/63 18.2 13.0 23.0 1.41 12.9 60 23.2 18.2 1.45 4.780/67 19.6 13.5 24.4 1.41 13.9 70 22.5 17.1 1.59 4.185/71 21.0 14.0 25.8 1.41 14.9 80 21.6 15.6 1.74 3.675/63 18.5 13.1 23.2 1.38 13.3 60 23.5 18.5 1.46 4.780/67 19.8 13.6 24.5 1.38 14.3 70 22.8 17.3 1.60 4.285/71 21.3 14.1 26.0 1.38 15.4 80 21.9 15.9 1.75 3.775/63 17.3 12.6 22.6 1.55 11.2 60 24.4 19.4 1.48 4.880/67 18.6 13.1 23.9 1.55 12.0 70 23.7 18.2 1.63 4.385/71 20.0 13.5 25.3 1.55 12.9 80 22.8 16.7 1.78 3.775/63 17.7 12.8 22.7 1.48 12.0 60 25.2 20.1 1.50 4.980/67 19.0 13.2 24.0 1.48 12.9 70 24.5 18.8 1.65 4.485/71 20.4 13.7 25.4 1.48 13.8 80 23.5 17.3 1.80 3.875/63 17.9 12.9 22.8 1.45 12.3 60 25.5 20.3 1.51 5.080/67 19.2 13.3 24.2 1.45 13.3 70 24.8 19.1 1.65 4.485/71 20.6 13.8 25.6 1.45 14.2 80 23.8 17.6 1.81 3.875/63 16.8 12.4 22.3 1.62 10.4 60 26.4 21.2 1.53 5.180/67 18.0 12.8 23.5 1.62 11.1 70 25.6 19.9 1.68 4.585/71 19.3 13.3 24.9 1.62 12.0 80 24.6 18.3 1.84 3.975/63 17.1 12.5 22.4 1.54 11.1 60 27.2 21.9 1.55 5.180/67 18.4 13.0 23.6 1.54 11.9 70 26.4 20.6 1.70 4.685/71 19.7 13.4 25.0 1.54 12.8 80 25.3 19.0 1.86 4.075/63 17.3 12.6 22.5 1.51 11.4 60 27.5 22.2 1.55 5.280/67 18.6 13.1 23.8 1.51 12.3 70 26.7 20.9 1.71 4.685/71 20.0 13.5 25.1 1.51 13.2 80 25.7 19.3 1.87 4.075/63 15.6 11.9 21.6 1.76 8.980/67 16.8 12.3 22.8 1.76 9.585/71 18.0 12.8 24.0 1.76 10.375/63 16.0 12.0 21.7 1.68 9.580/67 17.1 12.5 22.9 1.68 10.285/71 18.4 12.9 24.1 1.68 11.075/63 16.2 12.1 21.8 1.65 9.880/67 17.4 12.6 23.0 1.65 10.585/71 18.6 13.0 24.2 1.64 11.375/63 14.5 11.3 20.9 1.90 7.680/67 15.5 11.8 22.0 1.90 8.285/71 16.7 12.3 23.2 1.90 8.875/63 14.8 11.5 20.9 1.81 8.280/67 15.9 12.0 22.0 1.81 8.885/71 17.0 12.4 23.2 1.81 9.475/63 14.9 11.6 21.0 1.78 8.480/67 16.1 12.0 22.1 1.78 9.085/71 17.2 12.5 23.3 1.78 9.7

    100

    3.1 4.6Notes:(1) Shaded area is extended range; antifreeze required. (2) Ratings at 30F and 40F EWT are based on a 15% methanol antifreeze solution. (3) AHRI/ISO 13256-1 certified conditions are 80.6F DB/66.2F WB in cooling and 68F in heating. (4) Table does not include fan credit or water pump penalty power corrections required for AHRI/ISO standard performance ratings. (5) Data are based on full load operation. (6) Performance data are subject to change without notice. (7) Interpolation is permissible; extrapolation is not.(8) For performance data outside the EAT listed, refer to the Hydrobank Select Software Program.

    4.5 8.3

    5.4 11.3

    110

    3.1 4.6

    4.5 8.3

    5.4 11.3

    304.5 9.7

    5.4 13.1

    904.5 8.3

    5.4

    804.5 8.3

    5.4 11.3

    3.1 4.6

    704.5 8.3

    5.4 11.3

    3.1 4.6

    604.5 8.3

    5.4 11.3

    3.1 4.6

    504.5 8.3

    5.4 11.3

    3.1 4.6

    404.5 8.3

    5.4 11.3

    3.1 4.6

    HydroBank MS Horizontal WSHP - Size 019 (PSC Motor) at Rated 600 CFM Air Flow

    Entering Water

    Temp. FGPM

    Water Pressure

    Drop Ft H2O

    Cooling Heating

    80

    85

    90

    11.3

    40

    3.1

    50

    60

    70

    3.1 4.6

    5.4

  • Catalog MAMM-WSHP-PC-1MSA (October 2014) 35

    Horizontal Units Capacity Data

    Entering Air Temp.

    (db/wb) F

    Total Capacity MBTUH

    Sensible Capacity MBTUH

    Heat of Rejection MBTUH

    Power Input kW EER

    Entering Fluid

    Temp. F

    Entering Air

    Temp. F

    Total Capacity MBTUH

    Heat of Absorption

    MBTUH

    Power Input kW

    COP

    75/63 25.8 18.3 29.7 1.15 22.4 60 16.6 11.6 1.48 3.380/67 27.7 19.0 31.6 1.15 24.1 70 16.1 10.6 1.61 2.985/71 29.8 19.7 33.7 1.15 25.8 80 15.5 9.5 1.75 2.675/63 26.3 18.6 30.1 1.11 23.8 60 17.1 12.0 1.49 3.480/67 28.3 19.3 32.0 1.11 25.5 70 16.6 11.0 1.63 3.085/71 30.3 19.9 34.1 1.11 27.4 80 15.9 9.9 1.77 2.675/63 26.7 18.7 30.4 1.09 24.4 60 17.3 12.2 1.50 3.480/67 28.6 19.4 32.3 1.09 26.3 70 16.8 11.2 1.63 3.085/71 30.7 20.1 34.4 1.09 28.2 80 16.1 10.1 1.78 2.775/63 25.0 18.0 29.4 1.32 18.9 60 18.8 13.5 1.53 3.680/67 26.8 18.6 31.3 1.32 20.3 70 18.2 12.5 1.67 3.285/71 28.8 19.3 33.3 1.32 21.8 80 17.5 11.3 1.82 2.875/63 25.4 18.2 29.8 1.27 20.1 60 19.3 14.0 1.54 3.780/67 27.3 18.9 31.6 1.26 21.6 70 18.8 13.0 1.69 3.385/71 29.3 19.5 33.7 1.26 23.2 80 18.0 11.8 1.84 2.975/63 25.8 18.3 30.0 1.24 20.7 60 19.5 14.2 1.55 3.780/67 27.7 19.0 31.9 1.24 22.2 70 19.0 13.2 1.69 3.385/71 29.7 19.6 33.9 1.24 23.9 80 18.2 11.9 1.85 2.975/63 23.8 17.4 28.8 1.49 16.0 60 22.3 16.8 1.62 4.080/67 25.5 18.1 30.6 1.49 17.1 70 21.7 15.7 1.77 3.685/71 27.4 18.7 32.5 1.49 18.4 80 20.8 14.2 1.94 3.275/63 24.2 17.6 29.1 1.43 17.0 60 23.0 17.4 1.64 4.180/67 26.0 18.3 30.9 1.43 18.2 70 22.3 16.2 1.79 3.685/71 28.0 19.0 32.8 1.43 19.6 80 21.4 14.8 1.96 3.275/63 24.5 17.8 29.3 1.40 17.5 60 23.3 17.6 1.65 4.180/67 26.4 18.4 31.1 1.40 18.8 70 22.6 16.5 1.80 3.785/71 28.3 19.1 33.1 1.40 20.2 80 21.7 15.0 1.96 3.275/63 22.5 16.9 28.2 1.66 13.6 60 24.7 18.9 1.68 4.380/67 24.2 17.6 29.9 1.66 14.6 70 24.0 17.7 1.83 3.885/71 26.0 18.2 31.7 1.66 15.7 80 23.0 16.2 2.00 3.475/63 23.0 17.1 28.4 1.59 14.5 60 25.4 19.6 1.69 4.480/67 24.7 17.8 30.1 1.59 15.5 70 24.7 18.3 1.85 3.985/71 26.5 18.4 31.9 1.59 16.7 80 23.7 16.8 2.02 3.475/63 23.3 17.2 28.6 1.56 14.9 60 25.7 19.9 1.70 4.480/67 25.0 17.9 30.3 1.56 1


Recommended