5
MTU 16V4000 DS2560 Power Module Certifications and standards 50 Hz: 1,914 - 2,560 kVA/400V 60 Hz: 1,807 - 2,321 kWe/480V Emissions Fuel optimized Generator set is designed and manufactured in facilities certi�ed to standards ISO 9001:2008 and ISO 14001:2004 Container Designed and manufactured as special purpose container for the use as generator set container, including CSC certification Performance assurance certi�cation (PAC) Generator set tested to ISO 8528-5 for transient response Verified product design, quality and performance integrity All container systems are prototype and factory tested G3 Power rating Permissible average power output during 24 hours of operation is approved up to 85% for standby rated unit Permissible average power output during 24 hours of operation is approved up to 75% for prime rated unit Permissible average power output during 24 hours of operation is approved up to 100% (110%) for continuous rated unit Optional equipment shown. Standard equipment may vary.
Transcript
Page 1: Power Module MTU 16V4000 DS2560 · 2019-10-28 · 1 Fuel density = 0.84 Kg/L 2 Air 3density = 1.184 kg/m3 (0.0739 lbm/ft) 3 For 60 Hz standby rated power Application data Engine Manufacturer

MTU 16V4000 DS2560Power Module

Certificationsandstandards

50 Hz: 1,914 - 2,560 kVA/400V60 Hz: 1,807 - 2,321 kWe/480V

Emissions— Fueloptimized

Generator set is designed and manufactured in facilities certi� ed to standards ISO 9001:2008 and ISO 14001:2004

Container— Designedandmanufacturedasspecialpurposecontainerfortheuseasgeneratorsetcontainer,includingCSCcertification

Performance assurance certi� cation (PAC)— GeneratorsettestedtoISO8528-5fortransientresponse— Verifiedproductdesign,qualityandperformanceintegrity— AllcontainersystemsareprototypeandfactorytestedG3

Power rating— Permissibleaveragepoweroutputduring24hoursofoperationisapprovedupto85%forstandbyratedunit

— Permissibleaveragepoweroutputduring24hoursofoperationisapprovedupto75%forprimeratedunit

— Permissibleaveragepoweroutputduring24hoursofoperationisapprovedupto100%(110%)forcontinuousratedunit

Optionalequipmentshown.Standardequipmentmayvary.

Page 2: Power Module MTU 16V4000 DS2560 · 2019-10-28 · 1 Fuel density = 0.84 Kg/L 2 Air 3density = 1.184 kg/m3 (0.0739 lbm/ft) 3 For 60 Hz standby rated power Application data Engine Manufacturer

1 Fueldensity=0.84Kg/L

2 Airdensity=1.184kg/m3(0.0739lbm/ft3)

3 For60Hzstandbyratedpower

Applicationdata

EngineManufacturer MTU Model 16V4000 G63/83 Type 4-cycle Arrangement 16V Displacement/cylinder:l(cuinch) 76.3(4656) Bore:mm(inch) 170(6.69) Stroke:mm(inch) 210(8.27) Compressionratio 16.5:1 Ratedspeed:rpm/50Hz 1500 Ratedspeed:rpm/60Hz 1800 EnginegovernorElectronicisochronous(ADEC) Standbyratedpower/50Hz:kWm(hp) 2,185(2,930)Standbyratedpower/60Hz:kWm(hp) 2,500(3,352)Primeratedpower/50Hz:kWm(hp) 1,965(2,635)Primeratedpower/60Hz:kWm(hp) 2,280(3,057)Continuousratedpower/50Hz:kWm(hp) 1,635(2,192)Continuousratedpower/60Hz:kWm(hp) 1,950(2,614) Speedregulation ±0.25% Airfilter Dry

Liquid capacity (lubrication)Totaloilsystem:l(gal) 300(79.3) Totaloilchange:l(gal) 240(63.4)Enginejacketwatercapacity:l(gal) 175(46.2) Aftercoolerwatercapacity:l(gal) 50(13.2) Systemcoolantcapacity:l(gal) 852(225)

Electrical ElectricvoltsDC 24 Coldcrankingampsunder-17.8°C(0°F) 2600

Fuel systemMaximumfuellift:m(ft) 3(10) Recommendedfuel Diesel#2 Totalfuelflow:l/hr(gal/hr) 1200(317)

GeneratorManufacturer LeroySomerModel LSA52,3L12/4RInsulationclass HVoltageregulation(steadystate) ±0.25%Radiointerferenceclass N

Fuel consumption1)

50Hz Standby Prime Continuous At100%ofpowerrating: l/hr(gal/hr) 500(132) 435(115) 367(97) At75%ofpowerrating:l/hr(gal/hr) 371(98) 329(87) 284(75)At50%ofpowerrating:l/hr(gal/hr) 254(67) 231(61) 201(53)

60Hz Standby Prime ContinuousAt100%ofpowerrating:l/hr(gal/hr) 613(162) 538(142) 458(121)At75%ofpowerrating:l/hr(gal/hr) 435(115) 397(105) 352(93)At50%ofpowerrating:l/hr(gal/hr) 303(80) 276(73) 254(67)

Cooling/Radiator SystemAmbientcapacityofradiator:°C(°F) 50(122) Max.restrictionofcoolingair,intake,and dischargesideofrad.:kPa(in.H20) 0.125(0.5) Waterpumpcapacity:l/min(gpm) 1,350(357) Heatrejectiontocoolant: kWe3B/D–50Hz(3B/D–60Hz) 904(1085) Heatrejectiontocoolant:kWe3A–50Hz(3A–50Hz) 802(927) Heatrejectiontoaftercooler: kWe3B/D–50Hz(3B/D–60Hz) 455(733) Heatrejectiontoaftercooler: kWe3A–60Hz(3A–50Hz) 288(566) Fanpower:kWe3B/D–50Hz(3B/D–50Hz) 41.3(68.8) Fanpower:kWe3A–50Hz(3A–60Hz) 30.8(51.4)

Air requirements2)

Engineroom:*m³/min(SCFM) 708(25,006) Airflowrequiredforrad. Cooledunit:*m3/min(SCFM) 4,200(148,344)

Exhaust system3)

Gastemp.(stack):°C(°F) 505(941) Gasvolumeatstacktemp:m3/min(CFM) 504(17,799)Maximumallowablebackpressure:kPA(in.H20) 8.5(34.1)

Page 3: Power Module MTU 16V4000 DS2560 · 2019-10-28 · 1 Fuel density = 0.84 Kg/L 2 Air 3density = 1.184 kg/m3 (0.0739 lbm/ft) 3 For 60 Hz standby rated power Application data Engine Manufacturer

Standardandoptionalfeatures

System ratings (kWe/kVA)

Voltage (L-L) 50 Hz 60 Hz

400V 400V 400V 480V 480V 480V

Application Continuous Prime Standby Continuous Prime Standby

Phase 3 3 3 3 3 3

Powerfactor(cosphi) 0,8 0,8 0,8 0,8 0,8 0,8

kVA 1,914 2,295 2,560 2,259 2,636 2,901

kWe 1,531 1,836 2,048 1,807 2,109 2,321

AMPS 2,763 3,313 3,695 2,717 3,171 3,490

GeneratormanufacturerLeroySomer

LeroySomer

LeroySomer

LeroySomer

LeroySomer

Leroy Somer

GeneratormodelLSA52.3L12/4p

LSA52.3L12/4p

LSA52.3L12/4p

LSA52.3L12/4p

LSA52.3L12/4p

LSA52.3L12/4p

skVA@30%voltagedip 4,530 4,530 4,530 5,750 5,750 5,750

Temprise 105°C/40°C 125°C/40°C 150°C/40°C 105°C/40°C 125°C/40°C 150°C/40°C

Connection 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE

Standardfeatures

— Globalproductsupport — Consultfactoryforspecificwarrantyterms — 16V4000dieselengine• 76.3literdisplacement• Commonrailfuelinjection• 4-cycle

— Engine-generatorresilientmounted — Completerangeofaccessories

— Generator• Brushless,rotatingfieldgenerator• 2/3pitchwindings• LeroysomerAREP,excitationwithR449AVR• 300%shortcircuitcapability

— Digitalcontrolpanel(s)• Completemeteringandprotectionsystem• LCDdisplay• TCP/IPconnectionforcustomers

— Coolingsystem• Separateroomforcoolingsystem/verticalsplitcores• Electricallydrivenfans/switchedin2stepsforhigherefficiency

Page 4: Power Module MTU 16V4000 DS2560 · 2019-10-28 · 1 Fuel density = 0.84 Kg/L 2 Air 3density = 1.184 kg/m3 (0.0739 lbm/ft) 3 For 60 Hz standby rated power Application data Engine Manufacturer

* Note:Airfilterwillcause5%derateinpoweroutput(kWe)andmayalsoaffectfuelconsumption.

Standardandoptionalfeatures

Engine — Aircleaners — Oilpump — Oildrainextension&S/Ovalve — Lubeoilsightglass — (Oilreservoir60literwithautomaticrefilling) — Returnfuelcooler — Fuelcleanerwithwaterseparatorswitchable — Lubeoilmulti-stagefilter — Closedcrankcaseventilation — Air-filter(Heavydutyair-filter) — Jacketwaterpump — Thermostats — Radiator-remotemounted — Electricstartingmotor-24V — Governor–electronicisochronous — Base-formedsteel — SAEflywheel&bellhousing — Batteryrack&cables — Fueloptimized(both50Hzand60Hz)

Digital control panel(s) — Digitalmetering — Engine/generatorprotectionfunctions — CANBusECUcommunications — Multilingualcapability — Programmablecontactoutputs — TCP/IPconnectionforcustomers

Generator * — LeroySomerLSA52,3L12/4R — NEMAMG1-32,IEC60034.1-60034.2andstandardscompliance fortemperatureriseandmotorstarting

— Sustainedshortcircuitcurrentofupto300%ofthe ratedcurrentforupto10seconds

— Self-ventilatedIP22 — Superiorvoltagewaveform — AnalogAVRR449(DigitalAVRD510) — Noloadtofullloadregulation — Brushlessalternatorwithbrushlesspilotexciter — 4pole,rotatingfield — 2bearing,regreasable — Closecoupling — Fullamortisseurwindings — 125%rotorbalancing — ±0.25%voltageaccuracyregulation — 100%ofratedload-onestep — 5%maximumTHDtotalharmonicdistortion

Container — 40’highcubeISOcontainerwithCSCcertification — Rearcontainerdoubledoors — Threelockablepersonnelaccessdoors — 1,500litersdieselfueltank — Externallyroofmountedcriticalgradeexhaustsilencer (storedduringtransportbetweenthesplitcoreradiator)

— Generatorcircuitbreakerwallmountedwithaccessfromoutside — Generatorcircuitbreakerrated3A3,200A3B/D4,000A100kA — 24VDCLEDlightswithbatterybackup

Page 5: Power Module MTU 16V4000 DS2560 · 2019-10-28 · 1 Fuel density = 0.84 Kg/L 2 Air 3density = 1.184 kg/m3 (0.0739 lbm/ft) 3 For 60 Hz standby rated power Application data Engine Manufacturer

Weights and dimensions

Drawingaboveforillustrationpurposesonly.Donotuseforinstallationdesign.

Subjecttochange.|32310361|Edition01/19|ESM2019-09.

Ratingdefinitionsandconditions

— Standbyratingsapplytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.Nooverloadcapabilityforthisrating.RatingsareinaccordancewithISO8528-1,ISO-3046-1,BS5514,andAS2789.Averageloadfactor:≤85%.Standby50Hzoperatinghoursperyear:Max.500.

— Primepowerandcontinuousratingsapplytoinstallationswhereutilitypowerisunavailableorunreliable.Atvaryingloadforprimepowerratingsornon-varyingloadforcontinuousratings,thenumberofgeneratorsetoperatinghoursisunlimited. A10%overloadcapacityisavailableforonehourintwelve forbothratings.RatingsareinaccordancewithISO8528-1, ISO3046-1,BS5514andAS2789. Averageloadfactor:≤75%(prime)≤100%(continuous).

— Continuouspowerratingsapplytoinstallationswherethegeneratorsetservesasutility.Atconstantload,thenumberofgeneratorsetoperatinghoursisunlimited.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO3046-1,BS5514andAS2789.Averageloadfactor:≤100%.Operatinghours/year:unlimited.

— ConsultyourlocalMTUdistributorforderatinginformation.

2896

4817

12192

2167

537

Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.

Sounddata

Sounddataisprovidedat7m(23ft).GeneratorsettestedinaccordancewithISO8528-10andwithinfiniteexhaust.

Unit type Full load - standby Full load - prime Full load - continuous

Powermodule C/F C/F C/F

ProductintendedforuseoutsideoftheUnitedStates.

C/F=ConsultFactory/MTUdistributor

N/A=NotAvailable

System Dimensions (L x W x H) Weight (dry/less tank)

Powermodule 12,203x2,438x2,896mm(480x96x114inch) 32,246kg(71090lbs)

Rolls-Royce Groupwww.mtu-solutions.com/powergen