6" S
CH
4
0 3
16
S
S
INV EL.
INFLUENT
PIPE
71.59
F
G
E
DD
NOTES:
1. EACH PUMP SHALL BE FITTED WITH 6 FEET OF TYPE 316 SS, 5/8"
CHAIN ATTACHED TO THE LIFTING MECHANISM AND AIRCRAFT
RATED 1/4" SS CABLE PROVIDED BETWEEN THE CABLE HOLDER
AND THE CHAIN.
2. PUMP MANUFACTURER'S MINIMUM SUBMERGENCE REQUIREMENT
SHALL BE PROVIDED AS A MINIMUM.
3. ALL HARDWARE IN WETWELL AND VALVE VAULT SHALL BE TYPE 316
STAINLESS STEEL, INCLUDING NUTS AND BOLTS FOR PIPE, VALVES,
AND APPURTENANCES.
4. 316 SS TO DI PIPE CONNECTIONS SHALL REQUIRE BOTH ENDS OF
THE SS FLANGES TO HAVE NON-CONDUCTIVE GASKETS ALONG
WITH PLASTIC/RUBBER INSERTS AND WASHERS ON BOLTS.
5. ALL MECHANICAL JOINTS SHALL BE RESTRAINED. ALL PIPE JOINTS
IN WETWELL, VALVE VAULT AND ABOVE GROUND SHALL BE
FLANGED TYPE.
PLAN
NTS
SECTION-A
NTS
ELEV V - HIGH LEVEL ALARMS
ELEV W - LAG PUMP ON
ELEV X - LEAD PUMP ON
Q
ELEV Z
ELEV Y - BOTH PUMPS OFF
A
SECTION-B
NTS
SS
DIP
36"
P
60°
~
6" MIN
36" MIN
B
ELEV T
CONC. PIPE SUPPORT
(TYP 5 PLACES)
SECOND HIGH
LEVEL ALARM
HEAVY DUTY TYPE
316 SS LIFTING CHAIN
(SEE NOTE 1)
POWER CABLE
2" MIN DIA SCH 40 TYPE
316 SS DUAL SLIDE RAIL
(PER MANUFACTURER)
EMERGENCY PUMP OUT CONNECTION
ASA FLANGE / FEMALE QUICK CONNECT
AND CHAIN LOCK DUST PLUG (MIN 6").
POSITION / ROTATION PER COUNTY
REPRESENTATIVE.
6" PV FLG. W/
WHEEL OPER.
(TYP)
6" CHECK VALVE
W/ LEVER & WEIGHT
(TYP)
6" TEE FLG
w/ BLIND FLG
(TYP.)
6" REST. FLG.
ADAPTER (TYP.)
1" SCH 80 PVC CONDUIT
TO SCADA PANEL
INSTALL ALUM ACCESS HATCH W/
LOCKSET AND RECESSED HANDLE
4" 316 SS GOOSENECK VENT w/
SS SCREEN, GROUT IN PLACE
(NOT SHOWN FOR CLARITY)
SEE DRAWING C-201
FOR CONTINUATION
EXISTING
CONCRETE
WETWELL
PRESSURE GAUGE
ASSEMBLY (TYP.)
INSTALL NEW 8" THICK
PRECAST CONC. TOP SLAB
w/ HDPE UNDERSIDE LINING
PLUG EXISTING HOLES,
CORE-DRILL NEW HOLES
AS NEEDED (TYP.)
INSTALL CABLE
HOLDER
OUTLINE OF
ACCESS OPENING
INSTALL
PROTECTIVE
LINER
EXIST CONC WET
WELL STRUCTURE
TO REMAIN
INSTALL NEW
8" THK TOP SLAB
EXIST. 8" DI
SAN SEWER
SECTION VIEW DISCHARGE
PIPING IS ILLUSTRATIVE, SEE
THE PLAN VIEW ABOVE FOR
ACTUAL PIPING ORIENTATION
BASE ELBOW
6" REST. FLG.
ADAPTER (TYP.)
6" CHECK VALVE W/
LEVER & WEIGHT (TYP)
6" PV FLG. W/ WHEEL
OPER. (TYP)
6" PV FLG. W/
WHEEL OPER.
(TYP)
INSTALL NEW CABLE HOLDER
6" PV FLG. W/
WHEEL OPER.
(TYP)
EMERGENCY PUMP OUT CONNECTION
ASA FLANGE / FEMALE QUICK CONNECT
AND CHAIN LOCK DUST PLUG
WELDED THRUST
RING (TYP.)
6" TEE w/ BLIND
FLG
TOP OF WW
ELEV T
INSTALL HEAT
SHRINK SEAL (TYP.)
GROUT
(TYP)
LOWER EXISTING
WETWELL TOP 1.22 FT
6" 90° BEND FLG (TYP)
2-6" SS 45° BENDS
4" X 6" SS REDUCER
PROTECTIVE LINER
LIQUID LEVEL
CONTROLS (TYP)
COMBINATION
AIR/VACUUM
RELEASE VALVE
ASSEMBLY
CONC PIPE
SUPPORT
(TYP 6 PLCS)
1. (*1) PER PUMP MANUFACTURER
REQUIREMENTS
2. DIMENSION P AND ELEVATION Y AND Z MUST
MEET BOTH PUMP MFR'S REQUIREMENTS
3. EL X - EL Z ≥ 5 FEET
4. TOP ELEVATION OF WETWELL SHALL BE
A MIN OF 1 FT ABOVE 100 YR FLOOD
ELEVATION AND THE ELEVATION OF THE
CROWN OF THE ROAD
5. SYMBOLS SHOWN IN THE TABLE ARE
USED IN THE ADJACENT PUMP STATION
PLAN AND SECTION VIEWS
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 P-200.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
PS 3268 HARBOR POINT DESIGN SPECIFICATIONS
DESIGN A SPECIFICATIONS DESIGN B SPECIFICATIONS
MANUFACTURER: SULZER-ABS MANUFACTURER: XYLEM-FLYGT
MODEL: XFP100E CB1 PE 105/4 VOLTAGE: 230 V MODEL: CP 3152 HT3 VOLTAGE: 230V
IMP: CB1-2 PHASE: 3 IMP: 488 PHASE: 3
DIA: 9.45" RATED POWER: 14.1 HP DIA: 9.76" RATED POWER: 15 HP
SPEED: 1750 RPM IMPELLER THROUGHLET: 3" SPEED: 1750 RPM IMPELLER THROUGHLET: 3"
DISCHARGE SIZE: 4" CURVE NUMBER: N.A. DISCHARGE SIZE: 4" CURVE NUMBER: N.A.
DESIGN COND.: 200 GPM @ 88 FT. DESIGN COND.: 200 GPM @ 88 FT.
HIGH HEAD COND.: N.A. HIGH HEAD COND.: N.A.
MIN. HEAD COND.: 600 GPM @ 58 FT. MIN. HEAD COND.: 600 GPM @ 58 FT.
SHUTOFF HEAD: 100 FT. SHUTOFF HEAD: 100 FT.
DESCRIPTION SYMBOL DIM ELEV DIM ELEV DESIGN A & B SPECIFICATION NOTES
THICKNESS OF WALL A EXIST. EXIST.
DIAMETER OF WET WELL B 6'-0" 6'-0"
WIDTH OF BOTTOM FILLET C EXIST. EXIST.
C\L OF WET WELL TO C\L OF PIPES D *1 *1
LENGTH OF PUMP ACCESS OPENING E *1 *1
WIDTH OF PUMP ACCESS OPENING F *1 *1
CENTER OF WET WELL TO EDGE OF HATCH G *1 *1
VALVE BOX HATCH OPENING H
VALVE BOX HATCH OPENING I
LIP WIDTH OF WET WELL BASE R EXIST. EXIST.
THICKNESS OF WET WELL BASE S EXIST. EXIST.
TOP OF WET WELL T 83.14 83.14
FINISHED GRADE U VARIES VARIES
HIGH LEVEL ALARMS V 71.5 71.5
LAG PUMP ON W 71.0 71.0
LEAD PUMP ON X 70.5 70.5
PUMPS OFF (TOP OF PUMP VOLUTE)
Y 68.0 68.0
BOTTOM OF PUMP TO FLOOR OF WET WELL P 4.6" *1
STEP HEIGHT (IF REQUIRED)Q *1 *1
FLOOR OF WET WELL Z 66.5 66.5
PS 3268 HARBOR POINT PUMP STATION PLAN,
SECTION AND NOTES
P-200
2038
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
GENERAL NOTES:
1. ALL MATERIALS AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE ORANGE COUNTY UTILITIES STANDARDS AND SPECIFICATIONS MANUAL (LATEST EDITION),
AND/OR AS SPECIFIED HEREIN.
2. ALL EXPOSED METAL OUTSIDE OF THE WET WELL SHALL BE IN ACCORDANCE WITH ORANGE COUNTY STANDARDS AND SPECIFICATIONS MANUAL (LATEST EDITION).
3. A CRYSTALLINE WATER PROOFING ADMIXTURE SHALL BE ADDED TO THE CONCRETE DURING THE MIXING CYCLE FOR THE WET WELL PRECAST STRUCTURES. THE
CRYSTALLINE WATER PROOFING ADMIXTURE SHALL BE APPROVED PRODUCT AS LISTED IN OCU APPENDIX D.
4. FOR EXISTING WET WELLS AND MANHOLES, THE INSIDE SHALL BE LINED WITH A FIBERGLASS REINFORCED POLYESTHER (FRP) LINER. FINAL SEALS AND SEALING TO BE MADE
IN THE FIELD. FOR NEW CONSTRUCTION, THE INSIDE OF WET WELLS AND MANHOLES SHALL BE LINED WITH EITHER A HIGH DENSITY POLYETHYLENE (HDPE) LINER, A
FIBERGLASS REINFORCED POLYESTHER (FRP) LINER , OR AN ACCEPTABLE EQUAL AS LISTED IN OCU APPENDIX D. FINAL SEALS AND SEALING TO BE MADE IN THE FIELD.
5. WET WELL ACCESS OPENING SHALL BE COVERED ON ALL FOUR VERTICAL SIDES WITH A PROTECTIVE LINER.
6. WET WELL ACCESS HATCH AND COVER SHALL BE ALUMINUM WITH 316 STAINLESS STEEL HARDWARE AND LOCK BRACKET PLATE WITH THE WORDS "CONFINED SPACE"
STAMPED (ETCHED)ON THE TOP SIDE. EACH DOOR WILL BE EQUIPPED WITH RECESSED HASP ENCLOSURE.
7. ALL PIPING AND HARDWARE IN THE WET WELL SHALL BE 316 STAINLESS STEEL SCHEDULE 40.
8. THERE SHALL BE NO VALVES OR ELECTRICAL JUNCTION BOXES IN THE WET WELL.
9. ALL PIPING AND CONDUIT PENETRATIONS THROUGH CONCRETE SHALL BE WATERTIGHT. CAST-IN-PLACE SLEEVES SHALL BE PLACED IN ALL OPENINGS WHERE PRESSURE PIPE
ENTER OR LEAVE THE WET WELL. PENETRATIONS THROUGH WET WELL SHALL BE A COMPRESSION TYPE SEAL, SUCH AS "LINK-SEAL", OR AN ACCEPTABLE EQUAL AS LISTED IN
OCU APPENDIX D.
10. ALL CONNECTIONS WITHIN THE WET WELL AND ABOVE GRADE SHALL BE FLANGED JOINTS. ALL REMAINING JOINTS BETWEEN THE WET WELL AND THE CONNECTION TO THE
EXISTING FORCE MAIN SHALL BE RESTRAINED MECHANICAL JOINTS. (SEE TABLE ON DETAIL SHEET D100).
11. CONTRACTOR SHALL, AS DIRECTED BY THE COUNTY REPRESENTATIVE, REMOVE AND SALVAGE TO THE COUNTY, ALL EXISTING PUMP STATION EQUIPMENT, INCLUDING
PUMPS, CHECK VALVES, SHUTOFF VALVES, AND CONTROL PANEL.
12. CONTRACTOR SHALL DEMOLISH AND REMOVE FR0M SITE ALL DEBRIS RESULTING FROM THE REMOVAL OF THE EXISTING STRUCTURES.
13. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS PRIOR TO ORDERING ANY MATERIALS OR EQUIPMENT.
14. CONTRACTOR SHALL GROUT FLOOR OF WET WELL, AS REQUIRED BY MANUFACTURER'S SPECIFICATIONS, TO ACCOMMODATE INSTALLATION OF THE NEW PUMPS.
15. STRUCTURAL DESIGN OF THE PRECAST WET WELL, TOP SHALL BE THE RESPONSIBILITY OF THE PRECAST MANUFACTURER. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
FOR THE PRECAST WET WELL, THE PRECAST WET WELL TOP AND HATCH COVER, AND RISERS TO THE ENGINEER.
16. 100-YEAR FLOOD ELEVATION: N.A., SURVEY AREA IS OUTSIDE THE (FIRM) FLOODPLAIN.
17. ALL EXTERNAL JOINTS SHALL BE COVERED WITH A HIGH STRENGTH, WATER TIGHT, PRESS-TO-SEAL TYPE TAPE/AS LISTED IN OCU APPENDIX D.
18. A SECOND HIGH LEVEL ALARM LIQUID FLOAT SHALL BE INSTALLED TO PROVIDE DRY CONTACT FOR SCADA. REFER TO PUMP CONTROL SCHEMATIC.
19. ALL SPOOLS SHALL BE MINIMUM OF SIX INCHES WHERE SPACE ALLOWS.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR ALIGNMENT FROM THE BASE PLATE TO THE RISER PLATE AT NO EXTRA COST TO OCU.
21. VALVES SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATION.
SC
H 4
0 3
16
S
S
P
C
B
12"
12
"
ELEV U
24"
MIN
36"
FINISHED GRADE
MIN
MIN
ELEV T
3"
(T
YP
)
36"
A
PVCDIP
INV EL.
ELEV V - HIGH LEVEL ALARMS
ELEV W - LAG PUMP ON
ELEV X - LEAD PUMP ON (SEE NOTE 4)
Q
ELEV Z
ELEV Y - BOTH PUMPS OFF (SEE NOTE 5)
12"
INFLUENT
PIPE
4"
1
12
60°
72.6
SLOPE
12"
MIN
NOTES:
1. EACH PUMP SHALL BE FITTED WITH 6 FEET OF TYPE 316 SS, 5/8"
CHAIN ATTACHED TO THE LIFTING MECHANISM AND AIRCRAFT
RATED 1/4" SS CABLE PROVIDED BETWEEN THE CABLE HOLDER
AND THE CHAIN.
2. PUMP MANUFACTURER'S MINIMUM SUBMERGENCE REQUIREMENT
SHALL BE PROVIDED AS A MINIMUM.
3. ALL HARDWARE IN WETWELL AND VALVE VAULT SHALL BE TYPE 316
STAINLESS STEEL, INCLUDING NUTS AND BOLTS FOR PIPE, VALVES,
AND APPURTENANCES.
4. 316 SS TO DI PIPE CONNECTIONS SHALL REQUIRE BOTH ENDS OF
THE SS FLANGES TO HAVE NON-CONDUCTIVE GASKETS ALONG
WITH PLASTIC/RUBBER INSERTS AND WASHERS ON BOLTS.
5. ALL MECHANICAL JOINTS SHALL BE RESTRAINED. ALL PIPE JOINTS
IN WETWELL, VALVE VAULT AND ABOVE GROUND SHALL BE
FLANGED TYPE.
PLAN
NTS
F
G
E
DD
8"
(TYP)
H
(MIN)
2"
3' MIN
SECTION
NTS
9" MIN9" MIN
R
S
I
3" SCH 80 PVC VALVE
VAULT DRAIN (SLOPE
DRAIN PIPE 1/2" PER FOOT)
4" TEE MJ RJ
316 SS TO DI TRANSITION
RESTRAINED FLANGE ADAPTER
316 SS PIPE SUPPORT
(TYP 2 PLACES)
(SEE DETAIL A402-6)
6" 90° BEND FLG w/
QUICK CONNECT
(ROTATED FOR
CLARITY)
6" PV FLG
6" DI FLG RISER
3'x4'x6" THK
CONC PAD
4" PV MJ RJ
INSTALL ALUM ACCESS HATCH
w/ LOCKSET AND RECESSED
HANDLE
INSTALL NEW PRECAST CONC
VALVE VAULT W/ INT. LINING
RESTRAINED
JOINT
(TYP)
SECOND HIGH
LEVEL ALARM
HEAVY DUTY TYPE
316 SS LIFTING CHAIN
(SEE NOTE 1)
POWER CABLE
2" MIN DIA SCH 40 TYPE
316 SS DUAL SLIDE RAIL
(PER MANUFACTURER)
SEE SHT. C-301
FOR CONT.
4" 22.5° BEND
MJ RJ
BASE ELBOW
GROUT
(TYP)
GEOFABRIC
LINER (60 MIL)
(TYP)
CRUSHED
STONE
(TYP)
SLOPE TO DRAIN 1/4" PER FOOT
INSTALL ALUM ACCESS HATCH W/
LOCKSET AND RECESSED HANDLE
4" 316 SS GOOSENECK
VENT w/ SS SCREEN,
GROUT IN PLACE
PRESSURE GAUGE
ASSEMBLY (TYP.)
INSTALL FORCE MAIN
SEAL (TYP)
INSTALL NEW 8" THICK
PRECAST CONC. TOP SLAB
w/ HDPE UNDERSIDE LINING
INSTALL NEW CABLE
HOLDER
INSTALL HEAT SHRINK
SEAL (TYP.)
INSTALL FORCE
MAIN PIPE SEAL (TYP.)
EMERGENCY PUMP OUT CONNECTION
ASA FLANGE / FEMALE QUICK CONNECT
AND CHAIN LOCK DUST PLUG (MIN 6").
POSITION / ROTATION PER COUNTY
REPRESENTATIVE.
INSTALL CABLE
HOLDER
OUTLINE OF
ACCESS OPENING
INSTALL
PROTECTIVE
LINER
4" PV FLG. W/
WHEEL OPER.
(TYP)
4" CHECK VALVE
W/ LEVER & WEIGHT
(TYP)
4" TEE FLG
w/ BLIND FLG
4" FCA
(TYP)
1" SCH 80 PVC CONDUIT
TO SCADA PANEL
SEE DRAWING C-301
FOR CONTINUATION
INSTALL NEW
8" THK TOP SLAB
INSTALL LINED 6' DIA CONC WET
WELL STRUCTURE w/ ALUM
HATCH AND BACKPLATE
INSTALL PROTECTIVE
LINING TO VALVE
VAULT INTERIOR
INSTALL 10" PVC SAN
SEWER
FDOT # 57
STONE
UNDISTURBED SOIL OR SELECTED
COMMON FILL COMPACTED TO 98%
MAX DENSITY PER AASHO T-180
INSTALL ARV
6"x4" RED MJ RJ
1. (*1) PER PUMP MANUFACTURER
REQUIREMENTS
2. DIMENSION P AND ELEVATION Y AND Z MUST
MEET BOTH PUMP MFR'S REQUIREMENTS
3. EL X - EL Z ≥ 5 FEET
4. TOP ELEVATION OF WETWELL SHALL BE
A MIN OF 1 FT ABOVE 100 YR FLOOD
ELEVATION AND THE ELEVATION OF THE
CROWN OF THE ROAD
5. SYMBOLS SHOWN IN THE TABLE ARE
USED IN THE ADJACENT PUMP STATION
PLAN AND SECTION VIEWS
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 P-300.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
PS 3470 WILMER AVENUE DESIGN SPECIFICATIONS
DESIGN A SPECIFICATIONS DESIGN B SPECIFICATIONS
MANUFACTURER: ABS MANUFACTURER: FLYGT
MODEL: XFP 100 G CB1 PE 185/4 VOLTAGE: 230 V MODEL: CP 3152 HT3 VOLTAGE: 230V
IMP: CB1-6 PHASE: 3 IMP: 454 PHASE: 3
DIA: 10.2" RATED POWER: 24.8 HP DIA: 10.83" RATED POWER: 20 HP
SPEED: 1780 RPM IMPELLER THROUGHLET: 3" SPEED: 1750 RPM IMPELLER THROUGHLET: 3"
DISCHARGE SIZE: 4" CURVE NUMBER: 6 DISCHARGE SIZE: 4" CURVE NUMBER: NA
DESIGN COND.: 300 GPM @ 95 FEET DESIGN COND.: 300 GPM @ 95 FEET
HIGH HEAD COND.: NA HIGH HEAD COND.: NA
MIN. HEAD COND.: 600 GPM @ 70 FEET MIN. HEAD COND.: 600 GPM @ 70 FEET
SHUTOFF HEAD: 120 FT SHUTOFF HEAD: 120 FT
DESCRIPTION SYMBOL DIM ELEV DIM ELEV DESIGN A & B SPECIFICATION NOTES
THICKNESS OF WALL A 8" MIN 8" MIN
DIAMETER OF WET WELL B 6'- 0" 6'-0"
WIDTH OF BOTTOM FILLET C *1 *1
C\L OF WET WELL TO C\L OF PIPES D *1 *1
LENGTH OF PUMP ACCESS OPENING E *1 *1
WIDTH OF PUMP ACCESS OPENING F *1 *1
CENTER OF WET WELL TO EDGE OF HATCH G *1 *1
VALVE BOX HATCH OPENING H 72" 72"
VALVE BOX HATCH OPENING I 56" 56"
LIP WIDTH OF WET WELL BASE R 18" MIN 18" MIN
THICKNESS OF WET WELL BASE S 12" MIN 12" MIN
TOP OF WET WELL T 83.45 83.45
FINISHED GRADE U VARIES VARIES
HIGH LEVEL ALARMS V 72.10 72.10
LAG PUMP ON W 71.60 71.60
LEAD PUMP ON X 71.10 71.10
PUMPS OFF (TOP OF PUMP VOLUTE)
Y 67.60 67.60
BOTTOM OF PUMP TO FLOOR OF WET WELL P *1 *1
STEP HEIGHT (IF REQUIRED)Q *1 *1
FLOOR OF WET WELL Z 66.10 66.10
PS 3470 WILMER AVE PUMP STATION
PLAN, SECTION AND NOTES
P-300
2138
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
GENERAL NOTES:
1. ALL MATERIALS AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE ORANGE COUNTY UTILITIES STANDARDS AND SPECIFICATIONS MANUAL (LATEST EDITION),
AND/OR AS SPECIFIED HEREIN.
2. ALL EXPOSED METAL OUTSIDE OF THE WET WELL SHALL BE IN ACCORDANCE WITH ORANGE COUNTY STANDARDS AND SPECIFICATIONS MANUAL (LATEST EDITION).
3. A CRYSTALLINE WATER PROOFING ADMIXTURE SHALL BE ADDED TO THE CONCRETE DURING THE MIXING CYCLE FOR THE WET WELL AND VALVE VAULT PRECAST
STRUCTURES. THE CRYSTALLINE WATER PROOFING ADMIXTURE SHALL BE APPROVED PRODUCT AS LISTED IN OCU APPENDIX D.
4. FOR EXISTING WET WELLS, VALVE VAULTS AND MANHOLES, THE INSIDE SHALL BE LINED WITH A FIBERGLASS REINFORCED POLYESTHER (FRP) LINER. FINAL SEALS AND
SEALING TO BE MADE IN THE FIELD. FOR NEW CONSTRUCTION, THE INSIDE OF WET WELLS, VALVE VAULTS AND MANHOLES SHALL BE LINED WITH EITHER A HIGH DENSITY
POLYETHYLENE (HDPE) LINER, A FIBERGLASS REINFORCED POLYESTHER (FRP) LINER , OR AN ACCEPTABLE EQUAL AS LISTED IN OCU APPENDIX D. FINAL SEALS AND SEALING
TO BE MADE IN THE FIELD.
5. WET WELL ACCESS OPENING SHALL BE COVERED ON ALL FOUR VERTICAL SIDES WITH A PROTECTIVE LINER.
6. WET WELL ACCESS HATCH AND COVER SHALL BE ALUMINUM WITH 316 STAINLESS STEEL HARDWARE AND LOCK BRACKET PLATE WITH THE WORDS "CONFINED SPACE"
STAMPED (ETCHED)ON THE TOP SIDE. EACH DOOR WILL BE EQUIPPED WITH RECESSED HASP ENCLOSURE.
7. ALL PIPING AND HARDWARE IN THE WET WELL SHALL BE 316 STAINLESS STEEL SCHEDULE 40.
8. THERE SHALL BE NO VALVES OR ELECTRICAL JUNCTION BOXES IN THE WET WELL.
9. ALL PIPING AND CONDUIT PENETRATIONS THROUGH CONCRETE SHALL BE WATERTIGHT. CAST-IN-PLACE SLEEVES SHALL BE PLACED IN ALL OPENINGS WHERE PRESSURE PIPE
ENTER OR LEAVE THE WET WELL AND/OR VALVE VAULT. PENETRATIONS THROUGH WET WELL AND VALVE VAULT SHALL BE A COMPRESSION TYPE SEAL, SUCH AS "LINK-SEAL",
OR AN ACCEPTABLE EQUAL AS LISTED IN OCU APPENDIX D.
10. ALL CONNECTIONS WITHIN THE WET WELL , VALVE VAULT, AND ABOVE GRADE SHALL BE FLANGED JOINTS. ALL REMAINING JOINTS BETWEEN THE WET WELL AND THE
CONNECTION TO THE EXISTING FORCE MAIN SHALL BE RESTRAINED MECHANICAL JOINTS. (SEE TABLE ON DETAIL SHEET D100).
11. PIPE SUPPORTS SHALL BE 316 STAINLESS STEEL, PROVIDED AND INSTALLED TO SUPPORT AND ANCHOR THE PIPING SECURELY IN THE VALVE VAULT.
12. VALVE VAULT SHALL BE SIZED TO PERMIT EASY REMOVAL OF CHECK VALVE SPINDLES, WITH MINIMUM CLEARANCE, AS SHOWN FOR 8" DIAMETER PIPE, OR SMALLER.
13. CONTRACTOR SHALL, AS DIRECTED BY THE COUNTY REPRESENTATIVE, REMOVE AND SALVAGE TO THE COUNTY, ALL EXISTING PUMP STATION EQUIPMENT, INCLUDING
PUMPS, CHECK VALVES, SHUTOFF VALVES, AND CONTROL PANEL.
14. CONTRACTOR SHALL DEMOLISH AND REMOVE FR0M SITE ALL DEBRIS RESULTING FROM THE REMOVAL OF THE EXISTING STRUCTURES.
15. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS PRIOR TO ORDERING ANY MATERIALS OR EQUIPMENT.
16. CONTRACTOR SHALL GROUT FLOOR OF WET WELL, AS REQUIRED BY MANUFACTURER'S SPECIFICATIONS, TO ACCOMMODATE INSTALLATION OF THE NEW PUMPS.
17. STRUCTURAL DESIGN OF THE PRECAST WET WELL, TOP, AND VALVE VAULT SHALL BE THE RESPONSIBILITY OF THE PRECAST MANUFACTURER. CONTRACTOR SHALL
SUBMIT SHOP DRAWINGS FOR THE PRECAST WET WELL, THE PRECAST WET WELL TOP AND HATCH COVER, RISERS AND THE VALVE VAULT, TO THE ENGINEER.
18. 100-YEAR FLOOD ELEVATION: N.A., SURVEY AREA IS OUTSIDE THE (FIRM) FLOODPLAIN.
19. ALL EXTERNAL JOINTS SHALL BE COVERED WITH A HIGH STRENGTH, WATER TIGHT, PRESS-TO-SEAL TYPE TAPE/AS LISTED IN OCU APPENDIX D.
20. A SECOND HIGH LEVEL ALARM LIQUID FLOAT SHALL BE INSTALLED TO PROVIDE DRY CONTACT FOR SCADA. REFER TO PUMP CONTROL SCHEMATIC.
21. ALL SPOOLS SHALL BE MINIMUM OF SIX INCHES WHERE SPACE ALLOWS.
22. CONTRACTOR SHALL BE RESPONSIBLE FOR ALIGNMENT FROM THE BASE PLATE TO THE RISER PLATE AT NO EXTRA COST TO OCU.
23. VALVES SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATION.
(S
EE
N
OT
E 2
)
TR
EN
CH
B
AC
KF
IL
L
12
" L
IF
TS
M
AX
IM
UM
w/ SIZE OF PIPE
VARIES
SEE NOTE 4
PIPE O.D.
COMMON FILL
BEDDING MATERIAL
12" (TYP)
UNDISTURBED EARTH
FINISHED GRADE
NOTES:
1. INITIAL BACKFILL: SELECT COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE
MAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE MAXIMUM
DENSITY AS PER AASHTO T-180.
3. TYPE A BEDDING MATERIAL SHALL CONFORM TO FDOT NO. 57 AGGREGATE.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPE DIAMETER
24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE FLOW.
7. BEDDING DEPTH SHALL BE 4" MINIMUM FOR PIPE DIAMETER UP TO 12" AND 6" MINIMUM FOR PIPE
DIAMETER 16" AND LARGER.
8. DEPTH FOR REMOVAL OF UNSUITABLE MATERIAL SHALL GOVERN DEPTH OF BEDDING ROCK
BELOW THE PIPE. UTILITIES SHALL DETERMINE IN THE FIELD REQUIRED REMOVAL OF UNSUITABLE
MATERIAL TO REACH SUITABLE FOUNDATION.
9. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
REGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION WITHIN ORANGE COUNTY
RIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF R/W UTILIZATION REGULATIONS AND
ROAD CONSTRUCTION SPECIFICATIONS.
TRENCH WIDTH
SELECT COMMON
FILL
INITIAL
BACKFILL
(S
EE
NO
TE
1
)
(S
EE
NO
TE
3
)
HAUNCHING
BEDDING
(SEE NOTES 7 & 8)
BEDDING AND TRENCHING - TYPE A FIGURE A101DATE: July 2014
(S
EE
N
OT
E 2
)
TR
EN
CH
B
AC
KF
IL
L
W/ SIZE OF PIPE
VARIES
SEE NOTE 4
PIPE O.D.
COMMON FILL
12" (TYP)
FINISHED GRADE
NOTES:
1. INITIAL BACKFILL AND HAUNCHING: SELECT COMMON FILL COMPACTED TO 95% (98% UNDER
PAVEMENT) OF THE MAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE
MAXIMUM DENSITY AS PER AASHTO T-180.
3. PIPE BEDDING UTILIZING SELECT COMMON FILL OR BEDDING ROCK IN ACCORDANCE WITH
TYPE A BEDDING AND TRENCHING DETAIL MAY BE REQUIRED AS DIRECTED BY UTILITIES.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPE
DIAMETER 24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE FLOW.
7. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
REGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION WITHIN ORANGE COUNTY
RIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF RIGHT-OF-WAY UTILIZATION
REGULATIONS AND ROAD CONSTRUCTION SPECIFICATIONS.
TRENCH WIDTH
SELECT COMMON
FILL
INITIAL
BACKFILL
(S
EE
N
OT
E 1
)
HAUNCHING
12
" L
IF
TS
M
AX
IM
UM
UNDISTURBED EARTH
(SEE NOTE 3)
BEDDING AND TRENCHING - TYPE B
FIGURE A102DATE: July 2014 FIGURE A104-2RESTRAINED PIPE TABLE
WASTEWATER FORCE MAINS
36"
43
100
38
88
30"
20
13
112
223
18
11
194
98
26
65
20"16"
23
55
12"
18
43
PVC PIPE SIZE
10
13
9
70
139
11
8
9
6
117
59
90
45
10"
15
38
6"
10
24
13
31
8"
8
5
79
40
6
4
5
3
50
25 32
65
45° BEND
90° BEND
VALVE
OF TEE
11-1/4° BEND
22-1/2° BEND
PLUG OR BRANCH
82
163
15
31
75
24"
MINIMUM LENGTH (FT) TO BE RESTRAINED ON EACH SIDE OF FITTING(S)
4"
TYPE
8
18
4
2
38
19
NOTES:
1. FITTINGS SHALL HAVE RESTRAINED JOINTS UNLESS OTHERWISE INDICATED.
2. INSTALL FULL LENGTH JOINTS WITH TOTAL LENGTH EQUAL TO OR GREATER THAN
LENGTH SHOWN IN THE TABLE.
3. WHERE TWO OR MORE FITTINGS ARE IN SERIES, SELECT FITTING RESTRAINT LENGTH THAT
YIELDS THE LONGEST RESTRAINT DISTANCE.
4. ALL INLINE VALVES SHALL BE RESTRAINED.
5. WHERE INTERNAL RESTRAINED JOINTS ARE USED, THE ENTIRE BELL SHALL BE PAINTED RED.
6. LENGTHS SHOWN IN THE TABLE WERE CALCULATED IN ACCORDANCE WITH
PROCEDURES OUTLINED IN "THRUST RESTRAINT DESIGN FOR DUCTILE IRON PIPE"
GUIDELINES PUBLISHED BY DIPRA, USING THE ASSUMPTIONS SHOWN BELOW:
WORKING PRESSURE: 100 PSI
SOIL DESIGNATION: SM (SAND SILT)
LAYING CONDITIONS: 3
DEPTH OF COVER: 3 FT
SAFETY FACTOR: 1.5
CONVERSION FACTOR FOR PVC PIPE: 1.25
THE DESIGN ENGINEER SHALL INCREASE THE VALUES IN THE TABLE AS WARRANTED BY
SITE-SPECIFIC PARAMETERS, SUCH AS SOIL DESIGNATIONS AND LAYING CONDITIONS.
REDUCER
VARIES BY SIZE; TO BE DETERMINED BY THE
DESIGN ENGINEER.
DATE: July 2014
VERTVERT
HORIZVERTHORIZVERTHORIZ HORIZ
HORIZONTAL & VERTICAL SEPARATION REQUIREMENTS
FIGURE A116SEPARATION REQUIREMENTS FOR
WATER, WASTEWATER AND RECLAIMED WATER MAINS
NOTES:
1. THIS SEPARATION REQUIREMENT IS TO PROVIDE ACCESSIBILITY FOR CONSTRUCTION AND
MAINTENANCE. THREE FEET OF HORIZONTAL SEPARATION IS THE MINIMUM FOR PIPES WITH THREE
FEET OF COVER. FOR PIPES INSTALLED AT GREATER DEPTHS, PROVIDE AN ADDITIONAL FOOT OF
SEPARATION FOR EACH ADDITIONAL FOOT OF DEPTH.
2. THE 18-INCH SEPARATION REQUIREMENT APPLIES WHEN THE STORM PIPE CROSSES ABOVE THE
OCU MAIN, AND WHEN THE STORM PIPE HAS A DIAMETER EQUAL TO OR GREATER THAN 24 INCHES.
OTHERWISE, THE REQUIRED SEPARATION IS 12 INCHES.
3. THIS SEPARATION REQUIREMENT COMPLIES WITH MINIMUM FDEP SEPARATION REQUIREMENTS
OUTLINED IN 62-555.314, FAC. VARIANCES FROM THE FDEP REQUIREMENTS MUST COMPLY WITH
62-555.314(5), FAC AND MUST BE APPROVED INDIVIDUALLY BY BOTH FDEP AND OCU.
4. DISTANCES GIVEN ARE FROM OUTSIDE OF PIPE TO OUTSIDE OF PIPE.
5. NO WATER PIPE SHALL PASS THROUGH OR COME IN CONTACT WITH ANY PART OF SANITARY OR
STORM WATER MANHOLE OR STRUCTURE.
PROPOSED
UTILITY
POTABLE WATER
RECLAIMED
WATER
WASTEWATER
(GRAVITY AND FM)
POTABLE
WATER
RECLAIMED
WATER
WASTEWATER
(GRAVITY & FM)
STORM SEWER
3'
NOTE 1
6'
NOTE 3
12"
12"
NOTE 3
3'
NOTE 1
3'
NOTE 1
3'
NOTE 1
3'
NOTE 1
3'
NOTE 1
3'
NOTE 1
12"
NOTE 3
12"
NOTE 3
12"
6'
NOTE 3
12"
NOTE 3
12"
12"12"
12"/18"
NOTE 2 & 3
12"/18"
NOTE 2
12"/18"
NOTE 2
RIGHT OF WAY
3'
NOTE 1
3'
NOTE 1
3'
NOTE 1
N/A N/A N/A N/A N/A
3'
NOTE 1 & 3
3'
NOTE 1 & 3
3'
NOTE 1 & 3
DATE: July 2014
FINISHED GRADE
LOCATING WIRE
SET TOP OF VALVE BOX
TO FINISHED GRADE
PLUG
VALVE
ADJUSTABLE SCREW
TYPE DUCTILE IRON
VALVE BOX
ALIGNMENT RING
VALVE BOX PAD (SEE
FIGURE A 112)
6" FDOT #57
STONE
UNDISTURBED
EARTH
COMPACTED SELECT
COMMON FILL
FIGURE A109PLUG VALVE AND BOX
WASTEWATER
3'-0
" M
IN
NOTES:
1. PVC PIPE OR DUCTILE IRON PIPE EXTENSIONS SHALL NOT BE USED ON VALVE BOX INSTALLATION.
2. THE VALVE ACTUATING NUT SHALL BE EXTENDED TO BE WITHIN 3' OF FINISHED GRADE.
3. PROVIDE A PLASTIC DEBRIS SHIELD / ALIGNMENT RING WHICH INSTALLS BELOW THE VALVE
ACTUATING NUT. THIS SHIELD SHALL CENTER THE RISER PIPE BOX OVER THE ACTUATING NUT
AND MINIMIZE INFILTRATION.
4. LOCATING WIRE SHALL BE CONTINUOUS WITH NO SPLICES AND SHALL EXTEND 12" ABOVE TOP OF
COLLAR. WIRE SHALL BE COLOR CODED TO MATCH THE UTILITY INSTALLED.
5. FOR NEW CONSTRUCTION, THE VALVE BOX SHALL BE ADJUSTED TO MIDRANGE TO ALLOW FOR
FUTURE BOX ADJUSTMENTS.
6. REFER TO FIGURE A111 FOR INSTALLATIONS AT A DEPTH OF 6' OR GREATER.
DRILL HOLE IN BOX 3"±
1
4
"
FROM TOP
LOOP WIRE (SEE NOTE 4)
DATE: July 2014
SEWER
WASTE WATER
RECLAIMED WATER
RECLAIMED
WATER
POTABLE WATER
NOTE:
1. LOCKING LIDS ARE REQUIRED ON ALL VALVE BOXES.
TYPICAL LOCKING
BOLT
TYPICAL VALVE BOX COVER FIGURE A110DATE: July 2014
WATER
OUTSIDE PAVEMENT
INSIDE PAVEMENT
FIGURE A112
24" X 24" SQUARE (ROUND OPTIONAL)
CONCRETE OR POLYMER PAD
TYP EACH VALVE BOX
VALVE BOX AND
LOCKING COVER
6" THICK 2500 PSI
(MIN) CONCRETE WITH
#4 REBAR CONTINUOUS (SEE
NOTE 2) OR 4" THICK
POLYMER MIX MATERIAL
24
"
24"
NOTES:
1. BRONZE (OR STAINLESS STEEL) IDENTIFICATION DISC SHALL BE REQUIRED FOR ALL VALVES,
EXCEPT HYDRANT VALVES.
2. IN LIEU OF PRECAST CONCRETE PAD, A 6" THICK X 24" (ROUND OR SQUARE) POURED
CONCRETE PAD WITH TWO #4 REBAR AROUND PERIMETER MAY BE USED.
VALVE BOX AND
COVER (SQUARE FOR
RECLAIMED WATER)
IDENTIFICATION DISC (SEE
NOTE 1 AND DETAILS
BELOW)
O.C.U
AFC 6" MANUFACTURER AND SIZE
RWGV TYPE OF VALVE
WATER UTILITY
L-20 DIRECTION AND NUMBER OF TURNS
2009 YEAR
IDENTIFICATION DISC
EXAMPLE
OUTSIDE PAVEMENT
INSIDE PAVEMENT
LETTERING TO BE MACHINE
ENGRAVED WITH
1
4
" TO
3
8
" CAP.
LETTERS
3" MIN
1 8
" M
IN
2" M
IN
THEFT PROOF
ANCHOR PIN
DISC TO BE EMBEDDED IN PAD
O.C.U
AFC 6"
RWGV
WATER
L-20
2009
DISC TO BE HANGING IN THE BOX
ANCHORED TO THE LOCATING WIRE.
3" MIN
1 4
"
APPROX. 3"
VALVE BOX PAD
BASE
TOP FLUSH
WITH
FINISHED
GRADE
VALVE BOX
AND COVER
(TYP)
ASPHALT
SURFACE
LOOP WIRE
LOCATING
WIRE
DATE: July 2014
A
SECTION A - A
PLAN
FIGURE A121-2
MJ TAPPING
SLEEVE
NEW PIPE
EXISTING
PIPE
RESILIENT SEAT TAPPING
GATE VALVE
RESTRAINED
MECHANICAL JOINT
MJ TAPPING SLEEVE AND GATE VALVE WITH
PLUG VALVE FOR WASTEWATER
RESTRAINED
MECHANICAL JOINT
PLUG VALVE
RESTRAINED
MECHANICAL
JOINT
RESILIENT SEAT TAPPING
GATE VALVE
RESTRAINED
MECHANICAL JOINT
PLUG VALVE
NOTES:
1. PLUG VALVES GREATER THAN 4" SHALL BE GEAR ACTUATED.
2. PLUG VALVE TO BE INSTALLED VERTICALLY, AND TAPPING GATE VALVE TO BE INSTALLED
HORIZONTALLY AND ABANDONED IN THE OPEN POSITION.
SPLIT GLAND
TAPPING
SLEEVE
5' M
IN
F
RO
M B
AC
K
OF
B
EL
L A
ND
S
PIG
OT
IN
SE
RT
IO
N L
IN
E
A
NEW PIPE
DATE: July 2014
CONSTRUCTION DETAILS
D-100
2238
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 D-100.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
FINISHED GRADE
LOCATING WIRE
LOCATING WIRE
PIPE LOCATING WIRE FIGURE A114
WATER,
WASTEWATER,
OR RECLAIMED MAIN
NYLON STRAPS,
3 PER JOINT
(SEE NOTE 1)
NOTES:
1. ALL PIPE SHALL REQUIRE INSULATED LOCATING WIRE (10 GAUGE SOLID COPPER) CAPABLE OF
DETECTION BY A CABLE LOCATOR AND SHALL BE WRAPPED WITH NYLON STRAPS TO TOP
CENTERLINE OF THE PIPE.
2. LOCATING WIRE SHALL BE CONTINUOUS INSIDE VALVE BOXES AND SHALL EXTEND 12" ABOVE TOP
OF COLLAR.
3. WIRE INSULATION SHALL BE COLOR CODED FOR THE TYPE OF PIPE BEING INSTALLED.
DATE: July 2014
OUTSIDE WALL
5" MIN
2"
4'-0" MIN
12" MIN
3'-0" MAX
1'-6" MIN
2" MIN
8" MIN
9"
INSIDE WALL
2 COURSES OF BRICK (MIN)
PRECAST CONCRETE MANHOLE FIGURE A301DATE: February 11, 2011
NOTES:
1. DROP CONNECTIONS ARE REQUIRED WHENEVER INVERT OF INFLUENT SEWER IS 24" OR
MORE ABOVE THE INVERT OF THE MANHOLE. SEE MANHOLE CONNECTION DETAIL.
2. ECCENTRIC CONE DESIGN MAY BE USED FOR CONFLICT RESOLUTION WITH OCU
APPROVAL.
3. A FLOW CHANNEL SHALL BE CONSTRUCTED INSIDE MANHOLE TO DIRECT INFLUENT INTO
FLOW STREAM.
4. LIFT HOLES THROUGH STRUCTURE ARE NOT PERMITTED.
5. WRAP TIGHTLY AROUND CASTING JOINTS AND APPLY HIGH INTENSITY PROPANE TORCH
TO EFFECTIVELY SEAL THEM FROM GROUND WATER INFILTRATION.
6. HDPE ADJUSTING RINGS MAY BE SUBSTITUTED FOR BRICK RISERS.
7. SECTION HEIGHTS VARY AS REQUIRED, AND AS AVAILABLE, FROM APPROVED
MANUFACTURERS LISTED IN APPENDIX D.
SET COVERS FLUSH IN
PAVED AREAS
MANHOLE FRAME & COVER
(SEE STANDARD DETAIL)
FRAMES BEDDED IN MORTAR
EXTERNAL MANHOLE
HEAT SHRINK SEAL
(TYP) SEE NOTE 5
APPROVED LINER
PER SPECIFICATIONS
BENCHING PER
SPECIFICATIONS
9"
9"
6"
MIN
PRE-PRIMED
JOINT SURFACES
PRE-MOLDED PLASTIC JOINT
SEALER, APPLIED TO BOTH
LIPS
COMPLETED
JOINT WITH
SQUEEZE-OUT
PRE-PRIMED
JOINT SURFACES
4 COURSES (MAX) OR MIN 5" TO
MAX 10" HDPE ADJUSTING RING
2'-0"
FDOT # 57 STONE
0.8D (EFFLUENT PIPE DIAMETER)
SQUEEZE-OUT, MIN
1
2
"
INTERIOR AND EXTERIOR
9"
CONCRETE WITH ADMIX
8"
6"
MIN
2500 PSI CONCRETE
AROUND MANHOLE
MANHOLE IN GRASS AREA FIGURE A303
NOTES:
1. CLEARANCE OF 30" FREE FROM OBSTRUCTIONS IN ALL DIRECTIONS.
2. AREAS SUPPORTING CONCRETE COLLAR OR SLAB SHALL BE PROPERLY COMPACTED.
3. TOP OF MANHOLE SHALL BE 2" ABOVE FINISHED GRADE, CROWN OF ADJACENT
ROADWAY, OR 100 YEAR FLOOD ELEVATION, WHICHEVER IS GREATER.
MANHOLE
COVER
FINISHED GRADE
2" M
IN
6"
MIN
2500 PSI CONCRETE
AROUND MANHOLE
4" BAR CONTINUOUS AROUND
COLLAR. 3" MIN. COVER (TYP)
12" MIN
7" M
IN
DATE: February 11, 2011
2 - NON PENETRATING
PICK HOLES
PLAN
ELEVATION
1-1/2" MIN
MACHINED
MATING
SURFACES
39"
7"
25 3/4"
24" ± 3/8"
NOTES:
1. ONLY APPLIES TO UTILITIES OWNED AND MAINTAINED MANHOLES. "ORANGE COUNTY"
SHALL NOT APPEAR ON PRIVATE MANHOLES.
SANITARY
SEWER
O
R
A
N
G
E
C
O
UNT
Y
F
L
O
R
I
D
A
4-3/4" MIN
STANDARD MANHOLE FRAME AND COVER FIGURE A304
RAISED 1-1/2" LETTERS
FLUSH WITH TOP OF COVER
B
O
A
R
D
O
F
C
O
U
N
TY
C
O
M
M
I
S
S
I
O
N
E
R
S
DATE: February 11, 2011
(TYP.)
2'-0"1'-6"
1. BASE REPLACEMENT SHALL BE 3000 PSI HIGH
EARLY STRENGTH CONCRETE.
2. ASPHALTIC CONCRETE SURFACE MATERIAL
SHALL BE REPLACED WITH THE SAME TYPE OF
MATERIAL THAT EXISTED AT THE TIME OF
REMOVAL.
3. MINIMUM ASPHALTIC CONCRETE THICKNESS
SHALL BE (1"- 5") INCH/ES, TO MATCH EXIST
ASPHALT THICKNESS.
4. ALL JOINT CUTS SHALL BE MECHANICALLY
SAW-CUT.
5. SUB-GRADE TO BE COMPACTED TO 98% MAX.
DENSITY AS DETERMINED BY AASHTO T-180.
6. CUT AREA TO BE PLATED OR PROTECTED ON
DAY OF POUR.
GENERAL NOTES:
CONCRETE
REPLACEMENT
HOT PATCH
PAVEMENT RESTORATION
EXIST SUBGRADE
1. SEE DETAIL A-702.
EXIST BASE
SAW CUT
ASPHALT
(TYP.)
MIN 8" HIGH
EARLY CONC
(TYP.)
2'-0"1'-6"
(TYP.)
PERMANENT HOT ASPHALT
REPLACEMENT APPLIED IN
2 INCH MAX LAYERS
FRAME BEDDED
IN MORTAR
INSTALL NEW MANHOLE
FRAME AND COVER TO
MATCH FINISHED GRADE
2 COURSES OF BRICK (MIN)
4 COURSES (MAX)
FIBERGLASS INSERT
HIGH COMPRESSION STRENGTH
GROUT BETWEEN EXIST MH AND
FIBERGLASS INSERT
REPAIR EXIST BENCHING
PRIOR TO INSTALLATION
AND SEALING OF FIBER
GLASS INSERT
EXIST CORBEL SECTION
TO BE REMOVED
MANHOLE FRAME AND
COVER TO BE REMOVED
BRICK TO BE
REMOVED
EXIST MANHOLE DETAIL
SCALE: N.T.S.
REHABILITATION DETAIL
SCALE: N.T.S.
VA
RIE
S
TO
R
EM
AIN
VARIES
TO BE REMOVED
FIBERGLASS MANHOLE INSERT SYSTEM FIGURE A-608DATE: February 2013
ASPHALT PAVEMENT RESTORATION AT MANHOLE
FIGURE A-610DATE: August 2012
FRAME AND COVER REPLACEMENT
1/2"(MIN)
CUT AND REMOVE
EXISTING BOLT, LADDER,
REINFORCEMENT OR
OTHER EMBEDDED METAL
EXISTING WALL OR
OTHER CONCRETE
REMOVE EXISTING
COATING (WHERE
APPLICABLE)
NEW COATING / LINING
CONCRETE SURFACE
BONDING AGENT
CRACK/HOLE/SPALLED AREA
CUT AND REMOVE
EXISTING CORRODED
REINF, AS DIRECTED
BY ENGINEER
REPLACE WITH
GRADE 40 REINF
OF SAME SIZE
REPAIR AND FILL MATERIAL
RECOMMENDED BY THE
COATING MANUFACTURER AND
APPROVED BY THE ENGINEER
TYPICAL REPAIR OF CONCRETE SPALL
TYPICAL BOLT, LADDER, REINFORCEMENT AND
EMBEDDED METAL REMOVAL
ORIGINAL/RESTORED SURFACE
CONC FACE AFTER WATER BLASTING AND CHIPPING
EXISTING REINFORCING
EXISTING CONC
REPAIR AND FILL MATERIAL RECOMMENDED BY
THE COATING MANUFACTURER AND APPROVED
BY THE ENGINEER
WELDED SPLICE, TYP
6" OR AS REQUIRED
BY WELDER
(TYP)
EXISTING WALL OR
OTHER CONCRETE
3"
3/8
"
CONCRETE
SURFACE
REPAIR MORTAR
OR GROUT WHERE
APPLICABLE
SAWCUT 1/8" WIDE X 3/8"
DEEP GROOVE IN CONCRETE
PROTECTIVE COATING
EDGE OF
NOTE:
1. SAWCUT BULK CONCRETE 3" BELOW TOP AND FEATHER
AN ADDITIONAL 3" AS SHOWN IN THIS DETAIL.
REPAIR AND FILL MATERIAL
RECOMMENDED BY THE COATING
MANUFACTURER AND APPROVED
BY THE ENGINEER
PROTECTIVE EDGE TERMINATION
CONCRETE RESTORATION AT MANHOLE OR WETWELL FIGURE A-611DATE: August 2012
MODIFICATIONS OF EXISTING CONCRETE
1. THE FOLLOWING NOTES ON MODIFICATION OF EXISTING CONCRETE ARE
GENERAL AND APPLY TO THE ENTIRE PROJECT EXCEPT WHERE THERE ARE
SPECIFIC INDICATIONS TO THE CONTRARY.
2. WHERE "TIE TO EXISTING STRUCTURE" IS INDICATED, CONTRACTOR SHALL
STRAIGHTEN AND SANDBLAST REINFORCEMENT AND SPLICE WITH NEW
REINFORCEMENT AS DETAILED ON THE DRAWINGS OR AS DIRECTED BY THE
ENGINEER. IF CONDITIONS WARRANT WELDING OF REINFORCING, WELDING
WILL BE SUBJECT TO ENGINEER'S APPROVAL.
3. EXISTING CONCRETE SURFACES TO BE JOINED WITH NEW CONCRETE
SHALL BE THOROUGHLY CLEANED BY SANDBLASTING AND COATED WITH
EPOXY BONDING COMPOUND JUST PRIOR TO PLACEMENT OF NEW
CONCRETE.
4. SURFACES SHALL BE NEATLY SAW CUT TO A DEPTH OF 1/2 INCH PRIOR TO
REMOVING THE EXISTING CONCRETE.
5. WHERE WATERSTOP BETWEEN NEW AND EXISTING CONCRETE IS
REQUIRED, CONTRACTOR SHALL CUT SUITABLE GROOVE IN THE EXISTING
CONCRETE AND INSTALL WATERSTOP WITH EPOXY AND BONDING
COMPOUND PRIOR TO CONCRETE WORK.
6. STRUCTURAL DIMESIONS RELATED TO OR CONTROLLED BY EXISTING
STRUCTURES SHALL BE VERIFIED IN FIELD BY THE CONTRACTOR PRIOR TO
CONCRETE WORK.
CONCRETE STRUCTURAL REINFORCING REPAIR
NEW COATING / LINING
NEW COATING /
LINING
NEW COATING /
LINING
CONSTRUCTION DETAILS
D-101
2338
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 D-101.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
PUMP BASE PLATE FIGURE A402-4
NOTES:
1. PLATE ANCHORS TO BE 6" MIN, 3/4" DIAMETER, WITH EPOXY ADHESIVE CAPSULE PROVIDING A MINIMUM
EMBEDMENT DEPTH OF 6 5/8".
2. NO EXPANSION ANCHORS ALLOWED
3. PLATE SIZE: 6" LARGER THAN BASE ELBOW & PUMP VOLUTE TYP. ALL AROUND. BASE PLATE SHALL BE
TRIMMED TO FIT, IF REQUIRED.
4. BASE ELBOW BOLTS, PLATE ANCHORS, AND STUDS TO BE STEEL (MIN ASTM A307 GRADE B AND A563).
SECTION VIEW IF NO STEP REQUIRED
1" THICK STEEL
BASE PLATE
PLAN VIEW
PUMP BOLTS TO BE WELDED
TO BOTTOM SIDE OF PLATE
1
2
LENGTH
6" MIN
PLATE ANCHORS
6" M
IN
6" MIN
2" MIN (TYP)
2" M
IN
(T
YP
)
6" M
IN
STEP TO BE STEEL, WELDED TO
BASE PLATE AND SUPPLIED BY
PUMP MANUFACTURER
PUMP BOLTS TO BE WELDED
TO BOTTOM SIDE OF STEP
BASE ELBOW
PLATE ANCHORS (6" MIN)
1" MINIMUM LEVELING
COURSE
6
5
8
" MIN. PENETRATION (SEE NOTE 1)
WET-WELL BOTTOM SLAB
SECTION VIEW WITH STEP
DATE: February 11, 2011
TEE
PRESSURE GAUGE
NTS
PIPE SUPPORT
1/4" BV MATERIAL TO MATCH PIPE
MATERIAL
1/4" TO MATCH SEAL MATERIAL
SS TEST TAP (1/4" PIPE). LOCATE ON
LOWER DIAPHRAGM FLUSHING
CONNECTION WITH TEE.
PRESSURE SEAL WITH 1/4" NPT
CONNECTIONS (SEE SPECIFICATIONS)
PIPE CONNECTION AS PER PIPE MFG
RECOMMENDATION
24
" M
AX
.
FIGURE A402-6DUPLEX PIPE SUPPORT AND GAUGE
DIAPHRAGM ASSEMBLY
GAUGE / DIAPHRAGM ASSEMBLY
NTS
316 SS
1
4
" NEOPRENE LINER
LOCKNUT
DATE: February 11, 2011
N.T.S.
TEE
PRESSURE
GAUGE
1/4" BV MATERIAL TO
MATCH PIPE MATERIAL.
1/4" TO MATCH SEAL MATERIAL
S.S. TEST TAP (1/4" PIPE). LOCATE
ON LOWER DIAPHRAGM FLUSHING
CONNECTION WITH TEE.
PRESSURE SEAL WITH 1/4"
NPT CONNECTIONS (SEE
SPECIFICATIONS.)
PIPE CONNECTION AS PER
PIPE MFG RECOMMENDATION
24
" M
AX
.
FIGURE A403-6TRIPLEX CONCRETE PIPE SUPPORT AND
GAUGE DIAPHRAGM ASSEMBLY
GAUGE/DIAPHRAGM ASSEMBLY
PIPE
1
4
" NEOPRENE
LINER
3000 PSI
CONCRETE
N.T.S.
ABOVE GROUND CONCRETE PIPE SUPPORT
3
8
"X4" 316 S.S.
PIPE STRAP
3
1
2
"
VA
RIE
S
3"
#4 BAR
2 #5 DOWELS AT 24" OC
4"
MIN
VARIES
8"
5
8
" 316 S.S. ANCHOR
BOLTS (TYP)
SECTION
PLAN
DATE: February 11, 2011
GRADE
FIGURE A120 WATER AND RECLAIMED WATER SERVICES
(TYPICAL)
CORPORATION
STOP (TYP)
PE TUBING
STANDARD
CURB
ROADWAY
CENTERLINE
NOTES:
1. CURB STOP SHALL BE INSTALLED ON STREET SIDE OF THE SIDEWALK BETWEEN SIDEWALK AND
CURB.
2. CONTRACTOR TO LOCATE CURB STOP BY PLACING A 2" X 2" SQUARE STAKE RISING 24" ABOVE THE
GROUND. TOP OF STAKE SHALL BE PAINTED THE COLOR OF THE UTILITY SERVICE AND LABELED
WITH THE LOT NUMBER(S) IT SERVES.
STAKE
(SEE NOTE 2)
CURB STOP
(SEE NOTE 1)
CURB STOP
(SEE NOTE 1)
STAKE
(SEE NOTE 2)
SIDEWALK (TYP)
RIG
HT
O
F W
AY
LIM
IT
S
30" MIN
RIG
HT
O
F W
AY
LIM
IT
S
DATE: July 2014
GRAVITY OUTSIDE DROP CONNECTION (NEW MANHOLE)
FIGURE A302
NOTES:
1. DROP PIPE AND FITTINGS SHALL BE OF EQUAL SIZE AND MATERIAL AS THE INFLUENT
SEWER.
2. AN OUTSIDE DROP CONNECTION SHALL BE REQUIRED FOR ALL INFLUENT LINES WHICH
HAVE AN INVERT 2' OR MORE ABOVE THE MANHOLE INVERT.
3. CONTRACTOR TO COORDINATE THE PRESENCE OF UTILITIES INSPECTOR DURING
CORING AND CONNECTIONS TO EXISTING MANHOLES.
PRECAST MANHOLE WALL
INLET CONNECTION AT INVERT
CONCRETE ENCASEMENT
OF VERTICAL PIPE
DROP PIPE
(SEE NOTE 1)
90° BEND
2"
INFLUENT SEWER
(SEE NOTE 2)
PRECAST
MANHOLE
WALL
STAINLESS STEEL BAND
RESILIENT CONNECTOR
STAINLESS STEEL PIPE CLAMP
PRECAST
MANHOLE
WALL
CAST IN-PLACE
SEAL
STANDARD CONNECTION
PVC PLUG WITH TOP HALF
AREA OPEN
PVC
PVC
TEE
GRAVITY OUTSIDE DROP CONNECTION (EXISTING MANHOLE)
NEW AND EXISTING MANHOLES NEW MANHOLES ONLY
GRAVITY MANHOLE CONNECTION
6"
MIN
6" M
IN
6" M
IN
6"
MIN
#4 90° HOOK AT 8" O.C.E.W.
DATE: February 11, 2011
NOTES:
1. CONTRACTOR SHALL REPAIR DETERIORATION ON INSIDE CIRCUMFERENCE OF PIPE WALL TO FORM A
SMOOTH SURFACE FOR THE END OF CIPP LINER.
2. IF POLYETHYLENE IS USED FOR INTERIOR OF LINING, CONTRACTOR SHALL ABRADE THE POLYETHYLENE
LAYER PRIOR TO APPLYING THE EPOXY.
3. COMPLETE MANHOLE REHABILITATION PRIOR TO PIPE LINING.
TYPICAL CIPP LINER END
DETAIL A - AT MH OPENING DETAIL B - IN PIPE OR AT MH INVERT
NEW CIPP
LINER
SEE DETAIL B
POLYMERIC EPOXY
(TYP.)
SEE DETAIL A
LINER
TEMINATION
NOTE: IF THICKNESS IS GREATER THAN
1
2
",
CONTRACTOR MAY USE RAPID SET MOTAR w/
MIN.
1
4
" THICK POLYMERIC EPOXY TOP COAT.
12
" M
IN
.
OV
ER
LA
P
EXIST. MH
WALL
HOST
PIPE
12" MIN.
OVERLAPMIN.
1
4
" POLYMERIC
EPOXY
NEW CIPP
LINER
HOST PIPE
NEW CIPP
LINER
MIN.
1
4
" POLYMERIC
EPOXY
12" MIN.
OVERLAP
LINER TERMINATION AT MANHOLE FIGURE A-604DATE: August 2012
HOST
PIPE
EXIST.
MH WALL
BENCHING
NEW CIPP
LINER
SEE DETAIL B
POLYMERIC EPOXY
(TYP.)
SEE DETAIL A
LINER
TEMINATION
HOST
PIPE
4" MIN.
SEWER MAIN
LATERAL
DOUBLE
SPRING LINE
LATERAL
SINGLE
R / W
SERVICE LATERAL FIGURE A305
NOTES:
1. INVERT OF SERVICE LATERAL SHALL NOT ENTER SEWER MAIN BELOW SPRING LINE.
2. SERVICE LATERAL SHALL BE CAPPED BY DEVELOPER'S SITE-WORK CONTRACTOR.
3. WYE TO BE NO SHALLOWER THAN 3-FEET AND NO DEEPER THAN 5-FEET.
4. LOCATOR BALLS TO BE INSTALLED BY DEVELOPER'S SITE-WORK CONTRACTOR, ONE
PER SERVICE.
5. ALL FITTINGS SHOWN ARE TO BE INSTALLED.
6. SERVICE CONNECTIONS SHALL BE PERMANENTLY MARKED BY CUTTING AN "S" IN THE
CURB DIRECTLY OVER THE LATERAL.
7. BUILDER'S PLUMBER WILL REMOVE PLUG, INSTALL CLEANOUT, AND CONNECT
SERVICE LATERAL TO HOUSE.
6" 45°
BEND
WYE WITH
6" BRANCH
S
6" 45°
BEND
WYE WITH 6"
BRANCH
SEWER MAIN SIZE
VARIES
DOUBLE WYE
WITH 6"
BRANCH
CLEAN-OUT
(TYP)
ROTATE
30° (TYP.)
LOT
LINE
SLOPE TO TERMINAL
DEPTH
@ 1.0% MIN (TYP.)
CURB (SEE NOTE 4)
3' M
IN
(S
EE
N
OT
E 3
)
TEMP PLUG
(TYP.) (SEE
NOTES 2
AND 7)
R / W
R / W
R / W
STAKE TO SHOW LOCATION OF
TEMPORARY PLUG. (TYP.)
(TYP.) BUILDER'S
PLUMBER (SEE
NOTE 7)
(TYP.) TEMP. PLUG
(SEE NOTES 2 AND 7)
PROFILE
NTS
PLAN
NTS
(TYP.) BUILDER'S
PLUMBER (SEE
NOTE 7)
LOCATOR BALL
6" MAX BELOW PIPE
(TYP) SEE NOTE 4
FINISHED
GRADE
DATE: February 11, 2011FIGURE A115-2 COMBINATION AIR RELEASE VALVE
FOR WASTEWATER
VENTED ARV ENCLOSURE
(GREEN) (SEE NOTE 4)
2" AIR
RELEASE VALVE
2" BALL/PLUG VALVE
ADJUSTABLE CAST IRON
VALVE BOX
FDOT #57 STONE
2" ELBOW AND TUBING
(THREADED)
MIN 2%
SLOPE
2" PIPE
2" ELBOW
2"CORP STOP
2" NIPPLE
2" SADDLE TAP
VARIES-SEE NOTE 1
NOTES:
1. OFFSET DISTANCE TO BE FIELD DETERMINED AND AS CLOSE TO THE RIGHT OF WAY AS POSSIBLE
AND CLEAR OF PEDESTRIAN WALKWAYS. IF PIPE IS AT RIGHT OF WAY LINE, NO OFFSET IS
REQUIRED.
2. ABOVE DETAIL APPLIES TO A 2" ARV. FOR LARGER ARVS, PIPE DIAMETER AND VALVES SHALL BE
EQUAL TO THE SIZE OF THE ARV.
3. ALL PIPING, VALVES AND APPURTENANCES TO BE BRASS OR 316 S.S. EXCEPT WHERE SPECIFIED
OTHERWISE.
4. THE ENCLOSURE VENTS MUST BE CAPABLE OF ALLOWING AT LEAST THE SAME AMOUNT OF
AIRFLOW AS THE VALVE.
2" PLUG VALVE WITH 2"
SQUARE NUT
2' M
IN
1' MIN
RIGHT OF WAY PRIVATE PROPERTY
18"
MIN
MAIN DIAMETER ARV
12" AND SMALLER 2"
16" 3"
20", 24" 4"
30", 36" 6"
6" M
IN
DATE: July 2014
CONSTRUCTION DETAILS
D-102
2438
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 D-102.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
CHAIN LINK FENCE FIGURE A406
NOTES:
1. TRUSS BARS ARE REQUIRED FOR EACH GATE SECTION AND THE FIRST SPAN ON EACH
SIDE OF A CORNER POST ONLY.
2. PROVIDE CHAIN AND LOCK FOR SECURING GATE.
3. FENCING AND POSTS SHALL BE BLACK, VINYL CLAD.
FENCE DETAIL
DOUBLE SWING GATE DETAIL
#9 GALV CLIPS
2'-MAX SPACING
POST CAP
3" POST CORNER
SCH. 40
FINISHED
GRADE
STRETCHER BARS
2" MESH FABRIC
BLACK VINYL
COATED
3/8" ROUND
TRUSS BARS
TURNBUCKLE
#9 TIE WIRES
12" OC
2
3
8
" LINE POST
SCH. 40
TENSION WIRE
2500 PSI
CONCRETE
3" GATE POST
SCH. 40 (TYP)
GATE
CORNER
3/8" ADJ
TRUSS RODS
1
5
8
" GATE FRAME
SCH. 40
CENTER STOP
12" X 12" X 12"
(SEE NOTE 2)
2500 PSI
CONCRETE
36
"
10'-0" TO CENTER (MAX)
1
5
8
" TOP RAIL
SCH. 20 (TYP)
36
"
6"
12"
6'-0
"
2"
8' 0" 8' 0"
12"
6"
6"
12"
FINISHED GRADE
PAVEMENT
BOX OUT (TYP)
DATE: February 11, 2011FIGURE A708
NON STANDARD
FENCING AS
SHOWN ON PLANS
14" OR
AS SHOWN
ON PLANS
PROPERTY LINE OR AS
SHOWN ON PLANS
6" X 18" CONC. CURB @
2500 PSI. CURBING SHALL
BE USED WITH FENCING.
4" FDOT TYPE 57 STONE.
GRADE
NOTES:
1. SEE PUMP STATION SITE PLAN FOR LOCATION AND LIMITS OF CURB SHOWN
AS EDGING FOR ROCK BEDS.
2. CURBING IS REQUIRED WHERE SHOWN ON PLANS.
CURB SET BACK = 2" MIN.
FROM PROPERTY LINE
60 MIL. NON-WOVEN
GEOTEXTILE FABRIC
12" CIRCULAR POST FOOTING.
WEEP HOLES (AS REQUIRED).
4"
4"
FENCE/CURB DETAILS
N.T.S
FIGURE A704-BDATE: NON-STD
YARD HYDRANT/HOSE BIBB
24
"
(M
IN
)
MALE QUICK CONNECTION AND
CHAIN-LOCK CAP. POSITION/ROTATION
PER COUNTY REPRESENTATIVE
90° ELBOW
2" SCH 80 PVC PIPE
2" BRASS PIPE
PVC TO BRASS ADAPTER
3
4
" BRASS HOSE BIB
2" TEE WITH 2" X
3
4
"
REDUCER
2" LOCKABLE BALL
VALVE (BRASS)
FINISHED GRADE
SECURE PIPE TO POST
WITH SS STRAPS (TYP)
4"X4" PRECAST
CONCRETE POST
2" 90° ELBOW
ANTI-SIPHON DEVICE
CO
VE
R
18
" M
IN
2'-0
" M
IN
.
FIGURE A707BSCADA POLE DETAILDATE: NON-STD.
NOTE:
1. THE CONTRACTOR SHALL PROVIDE INSTALLATION DESIGN WITH DETAILS OF
THE POLE EMBEDMENT AND STRUCTURAL CALCULATIONS FOR APPLICABLE
WIND LOADING, SPECIFIC HEIGHT AND LOADING OF THE POLE, INCLUDING THE
ANTENNA . THE CALCULATIONS SHALL BE PREPARED BY A STRUCTURAL
ENGINEER, REGISTERED IN THE STATE OF FLORIDA.
2. SHOP DRAWING SUBMITTALS FOR POLE SHALL INCLUDE ALL INSTALLATION
DESIGN AND DETAILS AS REQUIRED.
SEE NOTES
SEE NOTES
PO
LE
H
EIG
HT
=
P
ER
P
LA
NS
CONCRETE COLLAR/
EMBEDMENT PER
INSTALLATION DESIGN,
SEE NOTES
PRECAST CONC. PULL BOX
W/ TRAFFIC RATED STEEL
COVER, BROOKS 36 SERIES
OR EQUAL
3/4" x 30' GROUND ROD,
BOND TO SCADA POLE
GROUND WIRE AND TO
PUMP STATION GROUND
GRID
TO SCADA PANEL
3"x5" HANDHOLE W/ COVER
SQUARE CONCRETE POLE,
SEE DETAIL THIS SHEET
ANTENNA BY ORANGE
COUNTY UTILITIES
SEE NOTES
FIGURE A709
DATE: April 14, 2017
SCADA PANEL CONDUIT LAYOUT
(NTS)
SCADA PANEL
CENTERED ALONG 36"
FREE SPACE OF NEW
CONTROL PANEL RACK
1.75" 6.5" 2.375" 3.5"
4.375"
1" PVC SCH 80
CONDUIT TO
VALVE VAULT
1" PVC SCH 80
CONDUIT TO RPZ
(OCU WATER ONLY)
2" SCH 80 PVC
CONDUIT TO
SCADA POLE
(3) 1" PVC SCH 80 CONDUIT
TO PUMP PANEL
BOTTOM OF ENCLOSURE KNOCKOUT DETAILS
BACK
FRONT
FRONT OF ENCLOSURE
4"1.625"
FIGURE A707TYPICAL SCADA POLE
#8 GROUND WIRE
A
E
D
C
5"
B
STANDARD FEMALE THREADED PIPE
TENON
2
1
2
" O.D.
1
1
4
" POLY
PIPE
3"X5" HAND
HOLE WITH
ALUMINUM
COVER
1
1 4
" E
LB
OW
#8 G
RO
UN
D W
IR
E
TO
S
CA
DA
P
AN
EL
CRITERION
B
EMBEDMENT
A 50'
SPECIFIED
HEIGHT ABOVE
GROUND
14
5
8
"
C 8'-6"
D 3'-8"
E 6
1
2
"
10'
40'
WIND VELOCITY (MPH) 160
19.9
WEIGHT (LBS.) 5840
170
15.8
180
11.5MAXIMUM EPA (SQ. FT.)
35'
12"
5'-8"
3'-6"
6 "
7'
28'
170
4.9
3110
175
3.5
180
2.2
50 FT.
TYPE III-O POLE
35 FT.
TYPE I-O POLE
2"
NOMINAL
DIAMETER (IN.)
OUTSIDE
DIAMETER (IN.)
2
1
2
"
STANDARD PIPE TENON SIZE
DATE: April 7, 2017
1. CONTRACTOR SHALL PROVIDE
INSTALLATION DESIGN WITH NECESSARY
DETAILS OF THE POLE EMBEDMENT AND
STRUCTURAL CALCULATIONS FOR
APPLICABLE WIND LOADING, SPECIFIC
HEIGHT, AND LOADING OF THE POLE,
INCLUDING THE ANTENNA. THE
CALCULATIONS SHALL BE PREPARED BY A
STRUCTURAL ENGINEER, REGISTERED IN
THE STATE OF FLORIDA.
2. SHOP DRAWING SUBMITTALS FOR POLE
SHALL INCLUDE ALL INSTALLATION DESIGN
AND DETAILS AS REQUIRED.
3. DETAIL IS NOT INTENDED AS AN
INSTALLATION GUIDELINE.
GENERAL NOTES:
TO
SE
RV
IC
E
FIGURE A708A
18
" W
ID
E B
Y 6
" T
HIC
K
WIT
H #
4 B
AR
A
LL
AR
OU
ND
(2
R
EQ
UIR
ED
),
OR
F
IB
ER
ME
SH
NO
TE
S:
1.
AL
L P
IP
E F
IT
TIN
GS
S
HA
LL
B
E B
RA
SS
.
2.
PA
IN
TIN
G IN
A
CC
OR
DA
NC
E W
IT
H T
HIS
M
AN
UA
L.
3.
PR
ES
SU
RE
T
RA
NS
DU
CE
R A
ND
W
AT
ER
M
ET
ER
ON
LY
R
EQ
UIR
ED
F
OR
W
AT
ER
S
UP
PL
IE
D B
Y
OC
U
FR
OM
MA
IN
FIN
AL
G
RA
DE
REDUCED PRESSURE BACKFLOW PREVENTER,
1 INCH (OR LARGER) WITH PRESSURE
TRANSDUCER AND WATER METER
9"
MIN
BR
AS
S O
R G
AL
VA
NIZ
ED
NON STANDARD
0-1
00
P
SIG
PR
ES
SU
RE
G
AU
GE
PR
ES
SU
RE
T
RA
NS
DU
CE
R -
WIN
TE
RS
P
TP
10
0 O
R E
QU
AL
4-2
0 m
a O
UT
PU
T 0
-1
00
P
SI
RA
NG
E
SE
E D
ET
AIL
A
DE
TA
IL
A
2" T
O 3
/4
" T
EE
1/4
" x 3
/4
" T
EE
2 #
18
T
SP
( 1
P
R 1
2V
DC
,
1 P
R- 4
-2
0 M
A S
IG
NA
L)
1" P
VC
W
EA
TH
ER
HE
AD
1" S
CH
80
P
VC
T
O
SC
AD
A P
AN
EL
BU
RIE
D 3
" X
3
"
CO
NC
RE
TE
PO
ST
(2
' M
IN
D
EP
TH
)
3/4
" G
AT
E V
AL
VE
BA
CK
FL
OW
P
RE
VE
NT
ER
IN
A
CC
OR
DA
NC
E W
IT
H
ST
AT
E A
ND
C
OU
NT
Y
RE
QU
IR
EM
EN
TS
GA
TE
V
AL
VE
90° BEND
(2
R
EQ
UIR
ED
)
GA
TE
V
AL
VE
GA
TE
V
AL
VE
16" MAX
12" MIN
2" W
AT
ER
M
ET
ER
(B
y O
CU
)
TH
RE
AD
ED
NIP
PL
E
GA
TE
V
AL
VE
BA
CK
FL
OW
P
RE
VE
NT
ER
IN
A
CC
OR
DA
NC
E W
IT
H
ST
AT
E A
ND
C
OU
NT
Y
RE
QU
IR
EM
EN
TS
UN
IO
N
(2
R
EQ
UIR
ED
)
90° BEND
(2
R
EQ
UIR
ED
)
TO
SE
RV
IC
E
FIGURE A409
GA
TE
V
AL
VE
TH
RE
AD
ED
NIP
PL
E (T
YP
)
TE
ST
C
OC
K (T
YP
)
18
" W
ID
E B
Y 6
" T
HIC
K
WIT
H #
4 B
AR
A
LL
AR
OU
ND
(2
R
EQ
UIR
ED
),
OR
F
IB
ER
ME
SH
NO
TE
S:
1.
AL
L P
IP
E F
IT
TIN
GS
S
HA
LL
B
E B
RA
SS
.
2.
PA
IN
TIN
G IN
A
CC
OR
DA
NC
E W
IT
H T
HIS
M
AN
UA
L.
FR
OM
MA
IN
FIN
AL
G
RA
DE
16" MAX
12" MIN
REDUCED PRESSURE BACKFLOW PREVENTER,
2 INCH AND SMALLER
9"
MIN
9"
MIN
BR
AS
S O
R G
AL
VA
NIZ
ED
DATE:
MODIFIED
MODIFIED
MODIFIED
CONSTRUCTION DETAILS
D-103
2538
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 D-103.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
DUPLEX PUMP STATION SITE PLAN FIGURE A402-5
R/WR/W
FM
E.O.P.
GRAVITY SEWER
NOTES:
1. THIS DRAWING IS PROVIDED AS REFERENCE ONLY. DESIGN ENGINEER SHALL PROVIDE A SITE SPECIFIC DRAWING
TO A SCALE OF 1"=10'.
2. FOR NON-RESIDENTIAL ROADS, DISTANCE BETWEEN EDGE OF PAVEMENT AND GATE SHALL BE 20' MINIMUM.
3. PUMP STATION TRACT (INCLUDING DRIVEWAY) AND UTILITY EASEMENT SHALL BE DEDICATED TO ORANGE
COUNTY UTILITIES.
4. THIS DIMENSION, AS MEASURED FROM THE CENTER OF THE WET WELL TO THE PUBLIC UTILITY EASEMENT LIMIT,
SHALL BE EQUAL TO OR GREATER THAN THE DEPTH OF THE WET WELL.
5. CONTROL PANEL DOOR HINGES TO BE LOCATED ON THE SIDE OF THE PANEL FARTHEST FROM THE WELL.
6. DRIVEWAY SUBGRADE TO BE 8" THICK. SUBGRADE TO BE COMPACTED TO A MINIMUM DENSITY 98% OF THE MAX
DENSITY AS DETERMINED BY ASTM DI557.
7. THE BOUNDARY OF ALL NEW PUMP STATION TRACTS SHALL BE LOCATED A MINIMUM OF 50 FEET AWAY FROM ANY
SINGLE FAMILY RESIDENTIAL LOT INCLUDING TOWNHOMES.
6" THICK 3000 PSI CONCRETE
WITH 6"X6"XW2.9XW2.9
WELDED WIRE FABRIC
WM
MANHOLE, LINED (TYP)
FORCE MAIN
(SEE NOTE 5)
5'
MIN
5
8
" WATER METER
1' (TYP)
16' WIDE 8'-0" PANELS
SWING GATE
9'
MIN
1' MIN
RPZ
1" WATER SERVICE
CONTROL PANEL
(MIN 4 FT CLEARANCE
FROM FENCE)
HOSE BIBB
3' MIN
4' MIN
3'
MIN
18'
6" (TYP)
SEE NOTE 4
SEE NOTE 4
WET WELL
VALVE VAULT
LIMITS OF
UTILITY
EASEMENT
35' MIN TRACT
CHAIN LINK FENCE INSIDE
6"X18" CONCRETE CURB
WITH 4" REVEAL ALL
AROUND
FM
3' MIN
1' (TYP)
3' MIN
PUMP
OUT
4" OF FDOT #57 STONE,
60 MIL GEOFABRIC
WEED CONTROL LINER
UNDER STONE
SE
E N
OT
E 4
6' MIN
EXPANSION JOINTS
(TYP)
1
1
45' MIN TRACT
14' DRIVEWAY
DATE: February 11, 2011
2'
EXPANSION JTS. @ 15' O.C. CONTROL JTS @ 5' O.C.
MATCH EXIST. SIDEWALK WIDTH
3.
2.
3000 PSI @ 28 DAYS
SAW CUT ALL JOINTS IN EXIST. SIDEWALKS1.
NOTES:
CLASS CONCRETE
4" SIDEWALKS
SIDEWALK REPAIR DETAIL
N.T.S.
0.50" JOINT
3' 7'
TOP OF CURB
10
'
DROP CURB (WIDTH VARIES)
5' (TYP)
WARP
GUTTER
PLAN (WITH SIDEWALK)
PROFILE
6'4'
R/W LINE
VA
RIE
S
VA
RIE
S
UTILITY STRIP (VARIES)
7'
B
(EXAGGERATED VERTICAL SCALE)
0.50" JOINT
WITH CURB WITHOUT CURB
10'
0.50" JOINT
DRIVEWAY CONTINUATION
(SEE SITE PLAN)
SLOPE FROM GUTTER
(OR EDGE OF PAVEMENT)
TO FRONT OF SIDEWALK
SLOPE VARIES:
0.02 NORMAL
0.01 MIN.
0.04 MAX.
SLOPE VARIES:
0.04 NORMAL
0.02 MIN.
0.08 MAX.
DROP
CURB
SLOPES CAN BE ADJUSTED WITHIN THE
RANGES SHOWN TO IMPROVED TIES TO
ADJACENT PROPERTY AND ARE TO BE
TRANSITIONED TO AVOID DISTORTION IN
SIDEWALK CONTINUITY
SIDEWALK WIDTH
(AS SHOWN ON PLANS)
0.50" JOINT
0.50"
JOINT
0.125" OPEN JOINT
AT 10' CTRS. WITH
INTERMEDIATE
DUMMY JOINTS
BACK OF SIDEWALK
0.50"
JOINT
3' MIN.
4" THICK CONC.
SIDEWALK
4" THICK CONC.
SIDEWALK
6' CURB
TRANSITION
R/W LINE
WIDTH VARIES
UTILITY STRIP 10'
AND GREATER
BACK OF
SIDEWALK
POINT OF WARP AT BACK
EDGE (SEE ABOVE)
FRONT OF
SIDEWALK
SLOPE 1/8" / FT.
(OR AS INDICATED ON SITE PLAN)
4000 P.S.I. CONC.
WITH FIBERMESH
REINF. (TYP)
16'-0" WIDE (TYP)
(OR AS INDICATED ON THE SITE PLAN)
*
*
*
0
.
7
5
"
R
1
.
7
5
"
R
3"
*SEE NOTE BELOW
TYPE E
6" MIN.
7.50" STD.
1'-2"
2'-3"
1'-6"
2'-0"
1'-6"
1'-0
"
DRIVEWAY
SLOPE TO FIT
2
"
R
3
"
R
0
.
7
5
"
R
6"
6"
6"
TYPE F
10"
6" MIN.
2"
5"
11
"
9"
8"
6" MIN.
2'-0"
*SEE NOTE BELOW
DROP CURB
*NOTE: WHEN USED ON HIGH SIDE OF ROADWAYS, THE CROSS SLOPE OF THE
GUTTER SHALL MATCH THE CROSS SLOPE OF THE ADJACENT PAVEMENT. THE
THICKNESS OF THE LIP SHALL BE 6", UNLESS OTHERWISE SHOWN ON PLANS.
SECTION VIEW A-A
(ALONG WIDTH OF DRIVEWAY)
7.50" STD.
7.50" STD.
0
.
7
5
"
R
0.75"R
0
.
7
5
"
R
0
.
7
5
"
R
6.2
5"
POINT OF WARP
*SEE NOTE BELOW
W/ FIBERMESH REINF.
DRIVEWAY DETAILS FIGURE A705 DATE: October 31, 2016
NOTES
1. CONCRETE DRIVEWAY, SIDEWALKS, PAVEMENT AND DROP CURB SHALL MEET THE MATERIAL REQUIREMENTS OF SECTION 02576 AND
CONSTRUCTION REQUIREMENTS OF INDEX NO. 515, ROADWAY AND TRAFFIC DESIGN STANDARDS, STATE OF FLORIDA, DEPARTMENT
OF TRANSPORTATION. CONCRETE SHALL BE REINFORCED WITH FIBERMESH REINFORCEMENT FIBERS, 2 TO 3 INCHES COLLATED
POLYPROPYLENE, PER ASTM C94, TYPE III 4.13 AND APPLICABLE BUILDING CODES.
2. CONSTRUCT DRIVEWAY ON COMPACTED SUB GRADE COMPACTED TO 98 % MAX. DENSITY AS DETERMINED BY AASHTO T-180.
3. WHERE TURNOUTS ARE CONSTRUCTED WITHIN EXISTING CURB AND GUTTER, THE EXISTING CURB AND GUTTER SHALL BE REMOVED
EITHER TO THE NEAREST JOINT BEYOND THE FLARE POINT OR TO THE EXTENT THAT NO REMAINING SECTION IS LESS THAN 5 FEET
LONG.
4. REFER TO SITE PLANS FOR LIMITS OF CONCRETE DRIVEWAY. CONSTRUCTION OF CONCRETE WET WELL APRON AND\OR EQUIPMENT
PADS SHALL BE IN ACCORDANCE WITH THE ABOVE DETAILS.
5. ALL 0.50" JOINTS SHALL BE CONSTRUCTED WITH PREFORMED JOINT FILLER. 0.50" JOINT FILLER SHALL BE PLACED IN JOINTS BETWEEN
DRIVEWAY AND CONCRETE APRONS, WET WELLS, VALVE VAULTS, OR ANY OTHER CONCRETE STRUCTURE.
6. JOINTS IN CURB AND GUTTER ARE TO BE PLACED TO MATCH JOINTS IN DRIVEWAYS.
7. DRIVEWAYS SHALL BE OF A UNIFORM WIDTH FROM THE POINT OF WARP TO THE RIGHT OF WAY LINE.
8. WHERE NOTED ( ) OPEN JOINTS ARE TO BE 0.125" WIDE AND PLACED AT 5' CTRS. IF REQUIRED, THE 5TH JOINT IS TO BE 0.50" WIDE.
PLAN (WITHOUT SIDEWALK)
SECTION VIEW B-B
(ALONG C/L OF DRIVEWAY)
5' M
IN
.
10' M
AX
.
6" THICK (TYP)
UTILITY STRIP
LESS THAN 10'
(6" THICK CONCRETE DRIVEWAY AND SIDEWALK)
(6" THICK CONCRETE DRIVEWAY)
A
A
3'
1'
1'
B
GENERAL NOTES:
1. ALL JOINT CUTS SHALL BE MECHANICALLY SAW-CUT.
2. SUB-GRADE TO BE COMPACTED TO 98% MAX. DENSITY
AS DETERMINED BY AASHTO T-180. CUT AREA TO BE
PLATED OR PROTECTED ON DAY OF POUR. EXISTING
SURFACE TO BE SAW CUT TO AN AREA 5 FEET BEYOND
BASE CUT.
PAVEMENT RESTORATION:
1. LONGITUDINAL CUTS MAY REQUIRE MILLING AND
OVERLAY/RESURFACING OF THE COMPLETE WIDTH OF
THE TRAVELED WAY.
2. REFER TO PLANS FOR LIMITS OF RESTORATION.
3. CONTRACTOR SHALL REPLACE ALL PAVEMENT
STRIPING AND MARKINGS IN LIKE KIND.
12"
10"
1 1/2" TYPE SP12.5
ASPHALTIC CONC.
EXIST ASPHALT
TO BE MILLED
(WHERE REQ'D)
SUBBASE (TYPE B, LBR40)
BASE (SOIL CEMENT
CONSTRUCTION DETAILS
D-104
2638
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 D-104.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*
ELECTRICAL NOTES, ABBREVIATIONS
AND SYMBOLS
E-001
2738
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-001.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
REMOTE TERMINAL UNIT
BELOW OR ABOVE AND BE LOCATED EQUALLY SPACED FROM EQUIPMENT
CONDUIT ENTRY INTO ELECTRICAL EQUIPMENT SHALL BE DIRECTLY
CONTRACTOR SHALL PROVIDE ADDITIONAL PULLBOXES WHERE REQUIRED
BY THE NEC AND/OR TO MAKE A WORKABLE INSTALLATION.
EXPOSED FLEXIBLE CONDUITS SHALL NOT EXCEED 30 INCHES
IN LENGTH FOR SIZES 2 INCHES AND LARGER, MAXIMUM OF 18
INCHES FOR SIZES 1-1/2 INCHES AND SMALLER
AGAINST SHOP DRAWINGS BEFORE STUBBING UP CONDUITS.
BOXES, PANELBOARDS, CONDUITS, CONTROL PANELS ETC,
THE CONTRACTOR SHALL VERIFY EXACT LOCATION OF TERMINAL
OF ALL EQUIPMENT.
AND APPROVED SHOP DRAWINGS FOR THE EXACT LOCATION
MECHANICAL, STRUCTURAL, CIVIL AND ARCHITECTURAL DWGS
DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO THE
ALL WORK SHALL COMPLY WITH THE 2011 NEC.
GENERAL NOTES
CENTERLINE
6.
5.
4.
3.
2.
1.
XFMR
SWGR
MFM
W
MAGNETIC FLOW METER
DIFFERENTIAL PRESSURE REGULATOR
DAMPER MOTOR OR DEMAND METER
FT
FS
FM FACTORY MANUAL
FLOW SWITCH
FEET
ELECTRICAL MANHOLEEMH
EWC
F
FACP
FLA
FIT
FAAP
°F
EXIST
EXH
EWH
ES
EUH
EVA
ESB
ETM
EO
ER
EP
ENCL
EMT
ELECTRIC WATER COOLER
FIRE ALARM ANNUNCIATION PANEL
ELECTRIC WATER HEATER
DEGREES FAHRENHEIT
FULL LOAD AMPERES
FLOW INDICATING TRANSMITTER
FIRE ALARM CONTROL PANEL
FORWARD
EXISTING
EXHAUST
ELECTRIC UNIT HEATER
ENERGY SAVING BALLAST
EXPLOSION PROOF
ELECTRICALLY OPERATED
ELECTRICAL METALLIC TUBING
ELAPSED TIME METER
ELECTRODE RELAY
ELECTRIC VALVE ACTUATOR
END SWITCH
ENCLOSURE
DPS
EF
ELR
EM
ELEC
EL
EC
DVLS
DS
DPST
DPR
DPDT
DN
DO
DIA
DM
DI
DC
DIFFERENTIAL PRESSURE SWITCH
DISCHARGE VALVE LIMIT SWITCH
EMERGENCY LOCKOUT RELAY
DISCONNECT SWITCH
EXHAUST FAN
ELEVATION
ELECTRICAL
EMERGENCY
EMPTY CONDUIT
DOOR INTERLOCK
DOUBLE POLE DOUBLE THROW
DOUBLE POLE SINGLE THROW
DRAW OUT
DOWN
DIAMETER
DIRECT CURRENT
PRGS PVC COATED RIGID GALVANIZED STEEL
PRESSURE SWITCH
PROXIMITY SWITCHPRS
PS
PRI PRIMARY
OWNER FURNISHED CONTRACTOR INSTALLED
OCCUPATIONAL SAFETY AND HEALTH ACT
NATIONAL FIRE PROTECTION ASSOCIATION
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION
NORMALLY OPEN, NUMBER
MANUAL TRANSFER SWITCH
PHASE, CHEMICAL TERM
PROGRAMMABLE LOGIC CONTROLLER
PUSH BUTTON OR PULL BOX
NATIONAL ELECTRICAL CODE
MILLIVOLT OR MERCURY VAPOR
MANUAL MOTOR STARTER
MOTOR PROTECTION RELAY
MOTOR OPERATED VALVE
MANHOLE, MOUNTING HEIGHT OR METAL HALIDE
NOT IN CONTRACT
PHOTO CONTROL
POWER FACTOR
OVERLOADS
OVERLOAD
NOT TO SCALE
OVERHEAD
ON CENTER
NON-FUSED
NORMALLY CLOSED
MEGA VOLT AMPERE
MAIN LUGS ONLY
MOTOR SPACE HEATER
MANUFACTURER
NIC
OSHA
PNL
PLC
PR
PF
PH
P
PC
PB
PAIR
PANEL
POLE
OLS
OFCI
OH
OL
OC
NTS
O
NO
OPEN
MV
NEMA
NFPA
NECA
NEC
NF
MVA
N
NC
NEUTRAL
MSH
MTS
MTD
MPR
MS
MIN
MLO
MOV
MFR
MH
MOUNTED
MINIMUM
Y
Ø
ZS
XTMR
X
WP
WT
WH
WM
CLOSE, COUNTER, CONTACTOR OR CONDUIT
CERTIFIED BALLAST MANUFACTURERS
AMERICAN STANDARDS ASSOCIATION
AMERICAN NATIONAL STANDARDS INSTITUTE
CYCLE TIMER OR CURRENT TRANSFORMER
WHEN BREAKER IS CLOSED OR TRIPPED)
(CLOSED WHEN BREAKER IS OPEN AND OPEN
CIRCUIT BREAKER AUXILIARY CONTACT
CLOSED WHEN BREAKER IS CLOSED OR TRIPPED)
(OPEN WHEN BREAKER IS OPEN AND
CIRCUIT BREAKER AUXILIARY CONTACT
BARE COPPER OR BATTERY CHARGER
CS
CTM
CWP
CU
CT
CTC
CR
CPT
CONN
COS
CP
CI
CLG
CONC
COND
CKT
CL2
CBM
CB"B"
CONTROL POWER TRANSFORMER
COLD WATER PIPE
CYCLE TIMER MOTOR
CYCLE TIMER CLUTCH
CONTROL STATION
CURRENT OR CONTROL RELAY
CABLE OPERATED SWITCH
COPPER
CONTROL PANEL
CONNECTION
CELL INTERLOCK
CONCRETE
CONDUCTOR
CHLORINE
CEILING
CIRCUIT
°C
CB
CB"A"
CAB
CAP
C
BR
BT
BIL
BLDG
BKR
BC
B
AUX
AWG
AT
ATS
CIRCUIT BREAKER
DEGREES CENTIGRADE
BEARING TEMPERATURE
CAPACITOR
CABINET
BRAKE
BASIC IMPULSE LEVEL
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAGE
BUILDING
BREAKER
BLUE
AUXILIARY
AMPERE TRIP
AM
ASA
AR
AS
ANSI
ANN
AHU
ALUM
AIC
AFG
AFF
ACCU
AF
ACB
AC
A
AMPS INTERRUPTING CAPACITY
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMMETER SWITCH
ABOVE FINISHED FLOOR
AMMETER
ALARM RELAY
ANNUNCIATOR
ALUMINUM
AIR COOLED CONDENSING UNIT
AIR CIRCUIT CURRENT
ALTERNATING CURRENT
AMBER, AMPERE, ALARM
AMPERE FRAME
HP HORSE POWER
MOTOR CIRCUIT PROTECTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
ILLUMINATING ENGINEERING SOCIETY
ELECTRONIC ENGINEERS
INSTITUTE OF ELECTRICAL AND
HIGH PRESSURE SODIUM
THOUSAND CIRCULAR MIL
MAGNETIC MOTOR STARTER
LIMIT OR LEVEL SWITCH
LIGHTING CONTRACTOR
LOW WATER CUTOFF
MOISTURE DETECTOR
MILLIAMPERE
LOCAL-OFF-REMOTE
LIGHTNING ARRESTED
LOW, LEVEL
KILOWATT HOUR
INSTRUMENTATION
KILOVOLT AMPERE
KEY INTERLOCK
JUNCTION BOX
INPUT/OUTPUT
HERTZ (CYCLE)
HIGH WATER CUTOFF
KW KILOWATT
LWCO
MCM
MCP
MCB
MCC
MD
MAX
M
MA
MAXIMUM
LTG
LOR
LS
LT
LC
KWH
L
LA
LIGHTING
LIGHT
INST
KVA
KVAR
KV
K
ISO
J
KILOVAR
KILOVOLT
ISOLATION
IEEE
I/O
IES
HWCO
HPS
HZ
HR HOUR
TYP
VA
VSD
VSC
VS
VLS
VM
VPI
VFD
VAR
V
UV
UPS
UL
UON
UG
T
TTC
TTB
TM
TQ
TEMP
TC
TEL
TD
TB
TACH
SV
SW
SWBD
ST
SUPV
SS
SPDT
SPST
HIGH MOTOR TEMPERATURE
GROUND FAULT INTERRUPTER
GROUND FAULT RELAY
HAND-OFF-REMOTE
HAND-OFF-AUTO
HANDHOLE
HOT CIRCUIT
HIGH OR HUMIDISTAT
GENERATOR BREAKER
GALVANIZED
GENERATOR
GROUND DETECTOR
ABBREVIATIONS
H
HMT
HOA
HOR
HC
HH
GFR
GND GROUND
GEN
GFI
GALV
GD
GB
SH
SN
SP
SCH
SEC
RTD
RTU
RS
RT
RGS
RMS
RES
R
RECP
WHITE, WATTS OR WIRE
YELLOW
POSITION SWITCH
PHASE
TRANSFORMER
AUXILIARY RELAY
WATTHOUR METER
TRANSFORMER
WATER TIGHT
WEATHER PROOF
WATT METER
TYPICAL
VARIABLE FREQUENCY DRIVE
UNLESS OTHERWISE NOTED
VARIABLE SPEED DRIVE
VARIABLE SPEED CONTROLLER
UNDERWRITERS LABORATORIES
VALVE POSITION INDICATOR
UNINTERRUPTIBLE POWER SUPPLY
VOLT AMPERE
VOLTMETER SWITCH
VALVE LIMIT SWITCH
VOLTMETER
VARMETER
UNDER VOLTAGE
VOLTS
UNDERGROUND
TELEPHONE TERMINAL CABINET
TELEPHONE TERMINAL BOX OR BOARD
TIMER CLUTCH OR TIME CLOCK
THERMOSTAT, TIMER, OR TOTALIZER
SUPERVISORY CONTROL
SELECTOR SWITCH OR STAINLESS STEEL
SINGLE POLE SINGLE THROW
SINGLE POLE DOUBLE THROW
TIME DELAY RELAY
TERMINAL BLOCK
TORQUE
TIMER MOTOR
TEMPERATURE
TELEPHONE
TACHOMETER
SOLENOID VALVE
SWITCHGEAR
SWITCHBOARD
SWITCH
STATION TIE BREAKER
RIGID GALVANIZED STEEL
SPACE HEATER OR SHIELD
RESISTANCE TYPE TEMP DETECTOR
RED, RAISE, RELAY OR REVERSE
REPEATING TIMER
SCHEDULE
SINGLE POLE
SOLID NEUTRAL
SECONDARY
RAPID START
ROOT-MEAN-SQUARE
RESISTOR
RECEPTACLE
POTENTIAL TRANSFORMER, PROGRAM TIMER
POLYVINYL CHLORIDE
PWR
PVC
PT
POWER
OCU ELECTRICAL NOTES
1. ALL WORK SHALL COMPLY WITH THE 2011 NEC.
2. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EXACT LOCATIONS
OF EQUIPMENT OR ALL REQUIRED FITTINGS AND HARDWARE. PROVIDE ALL EQUIPMENT, MATERIALS, AND
LABOR REQUIRED FOR A COMPLETE OPERATING SYSTEM. COORDINATE EQUIPMENT LOCATIONS AND
WIRING WITH ACTUAL FIELD CONDITIONS AND EQUIPMENT ACTUALLY PROVIDED.
3. CIRCUIT BREAKER SHALL BE AS LISTED IN APPENDIX D.
4. UNDERGROUND CONDUITS SHALL BE SCHEDULE 80 PVC BELOW GRADE. MINIMUM CONDUIT SIZE SHALL BE
0.75" ABOVE GRADE, AND 1.00" BELOW GRADE. UNDERGROUND CONDUIT SHALL BE RUN A MINIMUM OF
24" BELOW BELOW GRADE.
5. CABLE AND WIRE SHALL BE COPPER, DUAL RATED, TYPE THNN/THWN, EXCEPT GROUND CONDUCTORS
SHALL BE SOFT DRAWN COPPER.
6. GROUND RODS SHALL BE COPPER CLAD STEEL, 0.75" BY 10 FT., DRIVEN SO TOP OF ROD IS BELOW
GRADE. ALL GROUNDING CONDUCTORS ARE 30" BELOW GRADE. ALL CONNECTIONS TO GROUND
RODS SHALL BE EXOTHERMIC WELDS, ERICO "CADWELD" OR EQUAL, UNLESS OTHERWISE NOTED.
7. INSTALL AND CONNECT ALL ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS.
8. WARRANTEE ENTIRE ELECTRICAL INSTALLATION FOR A PERIOD OF ONE YEAR FROM THE FINAL
ACCEPTANCE DATE. PROMPTLY REPLACE AND/OR REPAIR ANY EQUIPMENT OR WIRING PROVIDED
UNDER DIVISION 16 DURING THE WARRANTEE PERIOD WITH NO ADDITIONAL COSTS TO THE OWNER.
9. PUMP CONTROL PANEL WILL BE FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED AND WIRED
BY ELECTRICAL CONTRACTOR. CIRCUIT DIAGRAM AND DETAILS ARE PROVIDED FROM DATA RECEIVED
FROM THE VENDOR, AND ARE PROVIDED FOR THE CONTRACTOR'S CONVENIENCE. ACTUAL CIRCUITRY
AND SPECIFIC DETAILS OF EQUIPMENT PROVIDED MAY VARY. PUMP CONTROL PANEL SPARE PARTS ARE
NOT REQUIRED.
10. CONTRACTOR TO INSTALL ADDITIONAL 1" PVC CONDUIT FROM RPZ TO SCADA PANEL WHEN ORANGE
COUNTY UTILITIES IS THE WATER SERVICE PROVIDER.
ELECTRICAL SYMBOLS
E-002
2838
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-002.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LOCAL CONTROL SWITCH
SPEED CONTROL
START/STOP SWITCH
PRESSURE SWITCH
TORQUE SWITCH
SINGLE RECEPTACLE OUTLET
WHERE THE TYPE OF RECEPTACLE AND USAGE IS NOTED.
NUMERICAL SUBSCRIPT INDICATES THE SHEET NOTE
FLOOR TELEPHONE OUTLET-PRIVATE
FLOOR TELEPHONE OUTLET-PUBLIC
FLOOR SPECIAL PURPOSE OUTLET
FLOOR DUPLEX RECEPTACLE
FLOOR SINGLE RECEPTACLE OUTLET
FAN HANGER RECEPTACLE
FOR CONNECTION
CLOCK HANGER RECEPTACLE
MULTIOUTLET ASSEMBLY
SPECIAL PURPOSE CONNECTION OR PROVISION
DUPLEX RECEPTACLE SPECIAL PURPOSE OUTLET
SINGLE SPECIAL PURPOSE RECEPTACLE OUTLET
TRIPLEX RECEPTACLE OUTLET-SPLIT WIRED
DUPLEX RECEPTACLE OUTLET-SPLIT WIRED
SIGNALING SYSTEM
PUSHBUTTON FOR OTHER THAN
MOMENTARY CONTACT SWITCH OR
CIRCUIT BREAKER SWITCH
SWITCH AND DOUBLE RECEPTACLE
SWITCH AND SINGLE RECEPTACLE
VOLTAGE SWITCHING SYSTEM
MASTER SWITCH FOR LOW
SWITCHING SYSTEM
SWITCH FOR LOW VOLTAGE
DIMMER SWITCH
HAZARDOUS AREA SWITCH
KEY OPERATED SWITCH
SWITCH WITH PILOT LAMP
WEATHERPROOF SWITCH
FOUR-WAY SWITCH
THREE-WAY SWITCH
DOUBLE POLE SWITCH
SINGLE POLE SWITCH
(CLOSING ON RISING TEMPERATURE)
(NORMALLY CLOSED, OPENING ON INCREASING DIFF.)
(NORMALLY OPEN, CLOSING ON INCREASING DIFF.)
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE SWITCH
(NORMALLY CLOSED, HELD OPEN)
LIMIT SWITCH
(NORMALLY CLOSED)
LIMIT SWITCH
(NORMALLY OPEN, HELD CLOSED)
LIMIT SWITCH
(NORMALLY OPEN)
LIMIT SWITCH
(NORMALLY CLOSED)
TORQUE SWITCH
(NORMALLY OPEN)
TORQUE SWITCH
CLOSING AFTER COIL IS DE-ENERGIZED)
(NORMALLY CLOSED WITH TIME DELAY
OFF TIME DELAY SWITCH
OPENING AFTER COIL IS ENERGIZED)
(NORMALLY CLOSED WITH TIME DELAY
ON TIME DELAY SWITCH
OPENING AFTER COIL IS DE-ENERGIZED)
(NORMALLY OPEN WITH TIME DELAY
OFF TIME DELAY SWITCH
CLOSING AFTER COIL IS ENERGIZED)
(NORMALLY OPEN WITH TIME DELAY
ON TIME DELAY SWITCH
(OPENING ON INCREASE IN FLOW)
FLOW ACTUATED SWITCH
(CLOSING ON INCREASE IN FLOW)
FLOW ACTUATED SWITCH
(OPENING ON RISING TEMPERATURE)
TEMPERATURE SWITCH
AMP SWITCH
AMPMETER
VOLT SWITCH
AS
AM
VS
NOTE 1:
AC MOTOR, NUMBER INDICATES HORSEPOWER
LIGHTNING ARRESTOR
NO. INDICATES FRAME SIZE
MOTOR CIRCUIT PROTECTOR
VOLT METER
QUANTITY AS NOTED
POTENTIAL TRANSFORMER,
FUSE
SURGE CAPACITOR
SURGE SUPPRESSOR
VM
7
MCP
DRAW-OUT TYPE
MEDIUM VOLTAGE CIRCUIT BREAKER
DRAW-OUT TYPE
LOW VOLTAGE CIRCUIT BREAKER
GENERATOR, SIZE AS NOTED
THERMAL OVERLOADS
TWO WINDING
FULL VOLTAGE, TWO SPEED
G
5
S F
1
(SEE NOTE 1)
1
F
1
C
1
(SEE NOTE 1)
(SEE NOTE 1)
(SEE NOTE 1)
(SEE NOTE 1)
1
1
1
RANGE OUTLET
(SEE NOTE 1)
(SEE NOTE 1)
(SEE NOTE 1)
1
TEMPERATURE SWITCH
(OPENING ON INCREASING VACUUM)
VACUUM SWITCH
(CLOSING ON INCREASING VACUUM)
VACUUM SWITCH
(OPENING ON RISING PRESSURE)
PRESSURE SWITCH
(CLOSING ON RISING PRESSURE)
PRESSURE SWITCH
(OPENING ON RISING LEVEL)
FLOAT SWITCH
(CLOSING ON RISING LEVEL)
FLOAT SWITCH
ELECTRODE
V
V
P
P
MANUAL STARTER
TRANSFORMER
CONTROL POWER
POTENTIOMETER
INDICATING LIGHT
NORMALLY OPEN GEARED LIMIT SWITCH
SWITCH
MS
RESISTOR
DIODE
RES
FUSE
CAPACITOR
MOMENTARY MUSHROOM HEAD
WIRE INTERSECTION POINT
NORMALLY CLOSED GEARED LIMIT SWITCH
MAINTAINED PUSH BUTTON
NORMALLY CLOSED PUSH BUTTON
NORMALLY OPEN PUSH BUTTON
STARTER, CONTACTOR OR RELAY COIL
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
EXTERNAL CONNECTION POINT
1 FLUORESCENT TROFFER
L
AUTOTRANSFORMER (CLOSED TRANSITION),
COMBINATION MOTOR STARTER WITH MOTOR
LETTER SUBSCRIPT INDICATES FIXTURE TYPE AS DESCRIBED
EMERGENCY LIGHT FIXTURE
POLE MOUNTED FIXTURE
RECESSED EXIT LIGHT
SURFACE OR PENDANT MOUNTED
SINGLE SPEED
FULL VOLTAGE REVERSING
SINGLE SPEED OR SOLID STATE SOFT START
REDUCE VOLTAGE NON-REVERSING
NON-REVERSING, SINGLE SPEED
CIRCUIT PROTECTOR. FULL VOLTAGE,
CIRCUIT BREAKER
R
2S
1S R
R
IN THE LIGHTING FIXTURE SCHEDULE.
1
NOTE 1:
J
B
11
JUNCTION BOX
BLANKED OUTLET
EXIT LIGHT
R
B
J
FT
TS
PS
T
LS
FS
THERMOSTAT
LIMIT SWITCH
FLOW SWITCH
MS
CB
S
MC
S
T
S
FLOAT SWITCH
MOTION SWITCH
TIME SWITCH
S
D
S
S
LM
S
DOOR SWITCH
BARE LAMP FLUORESCENT STRIP
RECESSED TANDEM FLUORESCENT
TANDEM FLUORESCENT FIXTURE
RECESSED FLUORESCENT FIXTURE
FLUORESCENT FIXTURE
SURFACE OR PENDANT MOUNTED
SURFACE OR PENDANT MOUNTED FIXTURE
CEILING
1
1
1
R
1
1
R
WITH GUARD
FIXTURE
R
1
R
1
RECESSED FIXTURE
1
1
R
1
1
WALL
D
S
H
S
P
S
K
S
WP
S
S
3
4
S
2
S
S
DESKTOP HANDSET
EXTERIOR HANDSET
WALL MOUNTED SPEAKER
EXTERIOR HORN SPEAKER
INTERIOR CEILING SPEAKER
PERPENDICULAR TO STRUCTURE OR WALL
CONDUIT RUN EXPOSED. RUN PARALLEL OR
OR UNDERGROUND
CONDUIT CONCEALED IN OR BELOW FLOOR
CEILING
CONDUIT CONCEALED IN WALL OR ABOVE
INDICATE 2#12 CONDUCTORS.
AWG. CONDUCTORS. NO HASH MARKS
HASH MARKS INDICATE NO. OF #12
ARROWS INDICATE NO. OF CIRCUITS,
HOME RUN TO PANELBOARD. NO. OF
S
WP
S
TT
JUNCTION BOX
ROOFTOP BONDING CONDUCTOR
EXHAUST FAN HOUSING.
BASE MOUNT FOR USE ON TOP OF
AIR TERMINAL WITH CAST ADHESIVE
BURIED COUNTERPOISE CONDUCTOR
ROOFTOP
MAIN CONDUCTOR CONCEALED BELOW
ROOFTOP MAIN CONDUCTOR
CONDUCTOR TURNED DOWN
TEE SPLICE
BONDING PLATE
BASE MOUNT
AIR TERMINAL WITH CAST ADHESIVE
TELEPHONE TERMINAL BOARD
SYSTEMS CABINET
TRANSFORMER, SIZE AS NOTED
250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, OVER
J
G
G
G
15
LIT
LE
DIT
FIT
FE
PT
EXISTING AS NOTED
MOTOR CONNECTION, FUTURE OR
250 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANEL BOARD, UNDER
250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER
SIZE AS NOTED
COMBINATION MAGNETIC MOTOR STARTER,
DISCONNECT SWITCH, SIZE AS NOTED
MOTOR CONNECTION, AS NOTED
SIZE AS NOTED
MAGNETIC MOTOR STARTER OR CONTACTOR
5
5
00
F
D
F
DENSITY INDICATING TRANSMITTER
LEVEL INDICATING TRANSMITTER
LEVEL ELEMENT
PRESSURE TRANSMITTER
FLOW INDICATING TRANSMITTER
FLOW ELEMENT
TEMPERATURE TRANSMITTER
DUCT SMOKE DETECTOR
SMOKE DETECTOR
HORN/LIGHT COMBINATION
PULL STATION
ELEMENTARY SYMBOLS
SINGLE LINE POWER DIAGRAM SYMBOLS
LIGHTING OUTLETS
RECEPTACLE OUTLET SYMBOLS
SWITCH SYMBOLS SERVICE AND DISTRIBUTION
LIGHTNING/GROUNDING SYSTEM
RACEWAY SYSTEM
COMMUNICATIONS
FIRE ALARM SYSTEM
PLAN SYMBOLS
DC MOTOR, NUMBER INDICATES HORSEPOWER
VIBRATION SWITCH
SOLENOID VALVE
VS
SV
FLUSH OUTLET BOX AND COVER PLATE
FLUSH FLOOR MOUNTED OUTLET BOX
AND COVER PLATE
S
5
ELEMENTARY SYMBOLS (CON'T)
GROUND ROD
PS 3198 LAKE LAWNE
OFFSITE ELECTRICAL POWER
SITE PLAN
E-100
2938
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
0
SCALE: 1" = 5'
50
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-100.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
PS 3198 LAKE LAWNE
ELECTRICAL POWER SITE PLAN
E-101
3038
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
N.T.S.
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-101.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
CONTROL
PANEL
METER
RELOCATED
RTU
CLASS 1 DIV. 2 AREA
CABLE HOLDER
BOND #4 STRANDED TINNED
COPPER TO ACCESS COVER
AND FRAME
GND TEST BOX
COUNTERPOISE 2/0 STRANDED
TINNED COPPER MIN. 30" BELOW
GRADE
VA
LV
E V
AU
LT
CAP
BOND TO FENCE
(TYPICAL)
BOND #4 STRANDED TINNED
COPPER TO ACCESS COVER
AND FRAME
MB
SPD
BOND GATE (TYP.)
PUMP 1
1"C WITH
PULLSTRING
PUMP 2
SHEET NOTES
TO CONTROL PNL (SEE RISER)
TO POLE MOUNTED TRANSFORMERS (SEE E-100)
2" TO RTU
EXISTING
ANTENNA
EXISTING PUMP STATION ANTENNA POLE & RTU
EXISTING ANTENNA
TO REMAIN
RTU TO BE MOVED
TO NEW CONTROL
PANEL RACK WITHIN
A 36" FREE SPACE
SCADA POLE COORDINATION
1. CONTRACTOR SHALL INSTALL CONDUIT AND PULL STRING BETWEEN
SCADA PANEL AND PUMP CONTROL PANEL.
2. SCADA SECTION WILL ACTIVATE SCADA PANEL AFTER STATION
ACCEPTANCE BY ORANGE COUNTY.
3.
1.
2.
SPECIFIC NOTES
IF GRAPHIC SCALE DOES NOT MATCH INDICATED SCALE, DRAWING IS REDUCED AND
ADJUSTMENT SHALL BE MADE AS REQUIRED
CONTRACTOR TO REMOVE EXISTING ELECTRICAL EQUIPMENT AND DISPOSE OF AS DIRECTED
BY OWNER'S REPRESENTATIVE.
SEE ELECTRICAL DETAILS 240 VAC FOR ELEVATIONS OF EQUIPMENT RACK.
PS 3198 LAKE LAWNE
SINGLE LINE DIAGRAM
E-102
3138
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-102.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
Amps
Phase B
54
Amps
Phase A
Amps
Phase C
11
14
123
Load
Pump #2-20 HP
Pump #1-20 HP
Electrical Load Calculations
LAKE LAWNE #3198
Total
25% Largest Motor
Available Voltage 120/240V - 3 Phase, 4W, Solid Ground
Maximum Available Fault Current = Amperes at Transformer Secondary
Misc. Controls (At 240 Volts)
- - -
ELECTRICAL ONE-LINE DIAGRAM
PANEL
240 - 3Ø
POINT OF SERVICE
UTILITY COMPANY
SERVICE FROM
UNDERGROUND
INCOMING
FLOAT SWITCHES INSTALLED AND WIRED
CABLES FURNISHED WITH PUMPS AND
3#3/0, 1#2N,1-#2 GROUND, 2"C.
SCADA
(SEE DETAILS)
PUMP CONTROL PANEL
METER
ELECTRIC
TO
FLOATS
~
3#3/0,1#2-2"
5 - 2/C FLOAT SWITCH CABLES
3 COND. W/GND PUMP CABLES
2"C (MIN) TO WET WELL WITH
1" C (CONTROL)
1" C (CONTROL)
1" C (POWER)
UNDER THIS CONTRACT
RIGID ALUM.
--
SPD
--
NEC Service Size = 200 Amperes
DOUBLE LUGS FOR SPD
200A 3P, MB, NEMA 4X
2" TO ANTENNA
14 14
54 54
54 54 54
123 122
1" TO VALVE VAULT
~
PS 3268 HARBOR POINT
ELECTRICAL POWER SITE PLAN
E-200
3238
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
N.T.S.
FENCE BOND
(TYP.)
BOND TO FENCE (TYPICAL)
CONTROL
PANEL
SPD
MB
METER
RELOCATED RTU
COUNTERPOISE #2/0 STRANDED
TINNED COPPER MIN. 30" BELOW
GRADE (TYP.)
TEST WELL
EXISTING PUMP STATION RTU
SCADA POLE COORDINATION
1. CONTRACTOR SHALL INSTALL CONDUIT AND PULL STRING BETWEEN
SCADA PANEL AND PUMP CONTROL PANEL.
2. SCADA SECTION WILL ACTIVATE SCADA PANEL AFTER STATION
ACCEPTANCE BY ORANGE COUNTY.
3.
1.
2.
SPECIFIC NOTES
IF GRAPHIC SCALE DOES NOT MATCH INDICATED SCALE, DRAWING IS REDUCED AND
ADJUSTMENT SHALL BE MADE AS REQUIRED
CONTRACTOR TO REMOVE EXISTING ELECTRICAL EQUIPMENT AND DISPOSE OF AS DIRECTED
BY OWNER'S REPRESENTATIVE.
SEE ELECTRICAL DETAILS 240 VAC FOR ELEVATIONS OF EQUIPMENT RACK.
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-200.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
RTU TO BE MOVED
TO NEW CONTROL
PANEL RACK WITHIN
A 36" FREE SPACE
PS 3268 HARBOR POINT
SINGLE LINE DIAGRAM
E-201
3338
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-201.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
Amps
Phase B
42
Amps
Phase A
Amps
Phase C
11
96
1
11
1
11
96 95
Load
Pump #2-15 HP
Pump #1-15 HP
Electrical Load Calculations
HARBOR POINT #3261
Total
25% Largest Motor
Available Voltage 120/240V - 3 Phase, 4W, Solid Ground
Maximum Available Fault Current = Amperes at Transformer Secondary
Misc. Controls (At 240 Volts)
- - -
42 42
42 42 42
NEC Service Size = 200 Amperes
ELECTRICAL ONE-LINE DIAGRAM
PANEL
240 - 3Ø
POINT OF SERVICE
UTILITY COMPANY
SERVICE FROM
UNDERGROUND
INCOMING
FLOAT SWITCHES INSTALLED AND WIRED
CABLES FURNISHED WITH PUMPS AND
3#3/0, 1#2N,1-#2 GROUND, 2"C.
SCADA
(SEE DETAILS)
PUMP CONTROL PANEL
METER
ELECTRIC
TO
FLOATS
~
3#3/0,1#2-2"
5 - 2/C FLOAT SWITCH CABLES
3 COND. W/GND PUMP CABLES
2"C (MIN) TO WET WELL WITH
1" C (CONTROL)
1" C (CONTROL)
1" C (POWER)
UNDER THIS CONTRACT
RIGID ALUM.
--
SPD
--
DOUBLE LUGS FOR SPD
200A 3P, MB, NEMA 4X
2" TO ANTENNA
1"C TO ABOVE GRADE PAD
SV
SV
PS 3470 WILMER AVENUE
ELECTRICAL POWER SITE PLAN
E-300
3438
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
N.T.S.
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-300.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
CONTROL
PANEL
METER
RELOCATED
RTU
BOND TO FENCE
(TYPICAL)
MB
SPD
BOND GATE (TYP.)
PUMP 1 PUMP 2
EXISTING WOOD SERVICE
POLE
RISER WITH
WEATHERHEAD
EXISTING PUMP STATION ANTENNA POLE & RTU
EXISTING ANTENNA
TO REMAIN
CAPPED
SCADA POLE COORDINATION
1. CONTRACTOR SHALL INSTALL CONDUIT AND PULL STRING BETWEEN
SCADA PANEL AND PUMP CONTROL PANEL.
2. SCADA SECTION WILL ACTIVATE SCADA PANEL AFTER STATION
ACCEPTANCE BY ORANGE COUNTY.
3.
1.
2.
SPECIFIC NOTES
IF GRAPHIC SCALE DOES NOT MATCH INDICATED SCALE, DRAWING IS REDUCED AND
ADJUSTMENT SHALL BE MADE AS REQUIRED
CONTRACTOR TO REMOVE EXISTING ELECTRICAL EQUIPMENT AND DISPOSE OF AS DIRECTED
BY OWNER'S REPRESENTATIVE.
SEE ELECTRICAL DETAILS 240 VAC FOR ELEVATIONS OF EQUIPMENT RACK.
RTU TO BE MOVED
TO NEW CONTROL
PANEL RACK WITHIN
A 36" FREE SPACE
PS 3470 WILMER AVENUE
SINGLE LINE DIAGRAM
E-301
3538
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 E-301.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
Amps
Phase B
68
Amps
Phase A
Amps
Phase C
11
154
Load
Pump #2-25 HP
Pump #1-25 HP
Electrical Load Calculations
WILMER AVE. #3470
Total
25% Largest Motor
Available Voltage 120/240V - 3 Phase, 4W, Solid Ground
Maximum Available Fault Current = Amperes at Transformer Secondary
Misc. Controls (At 240 Volts)
- - -
ELECTRICAL ONE-LINE DIAGRAM
PANEL
240 - 3Ø
POINT OF SERVICE
UTILITY COMPANY
SERVICE FROM
UNDERGROUND
INCOMING
FLOAT SWITCHES INSTALLED AND WIRED
CABLES FURNISHED WITH PUMPS AND
3#3/0, 1#2N,1-#2 GROUND, 2"C.
SCADA
(SEE DETAILS)
PUMP CONTROL PANEL
METER
ELECTRIC
TO
FLOATS
~
3#3/0,1#2-2"
5 - 2/C FLOAT SWITCH CABLES
3 COND. W/GND PUMP CABLES
2"C (MIN) TO WET WELL WITH
1" C (CONTROL)
1" C (CONTROL)
1" C (POWER)
UNDER THIS CONTRACT
RIGID ALUM.
--
SPD
--
NEC Service Size = 200 Amperes
DOUBLE LUGS FOR SPD
200A 3P, MB, NEMA 4X
2" TO ANTENNA
1"C TO VAULT
68 68
68 68 68
17 17 17
154 154
ELECTRICAL DETAILS
ED-100
3638
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 ED-100.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
PUMP STATION CONTROL PANEL (480V )
BACK TO BACK FRONT & PLAN VIEW
PUMP STATION CONTROL PANEL (480V)
BACK TO BACK REAR VIEW
GENERATOR
RECEPTACLE
PAD LOCK
BRACKET
AH
DOOR
LATCH
MOUNTING
BRACKETS
AL
MOUNTING BRACKET
ECBMCB
CC
B
MECHANICALLY
INTERLOCKED
MB2MB1
DR
B
PL4
R
PL3
A
R
ETM2
RL2
PL2
A
PL1
A
R
ETM1
RL1
HOA
ASB
HOA
ATS
GFDR
DOOR STOP
WITH LOCK
FOR DEAD
FRONT.
NOTES:
1. DEADFRONT LAYOUT NEMA TYPE 3R SS ENCLOSURE W/CONTINUOUS HINGE. ALL
HARDWARE TYPE 316 SS TYPICAL, ACTUAL LAYOUT MAY VARY WITH HORSEPOWER.
2. THIS CONTROL PANEL, INCLUDING THE GENERATOR RECEPTACLE, COMPLIES WITH THE
STANDARD LIST OF COMPONENTS REQUIRED BY UTILITIES.
3. ALL CONTROL WIRE TO BE #14 AWG MINIMUM.
4. CONTROL PANEL SHALL BE UL LISTED AND LABELED.
5. 30 SPARE TERMINALS (TB2).
6. PHASE MONITOR CIRCUIT BREAKER TO BE SEIMENS P/N: MSP10G, OR SQ-D P/N: MG24532.
DUPLEX CONTROL PANEL ENCLOSURE
DEAD FRONT LAYOUT
1.
2.
3.
4.
5.
6.
8.
9.
7.
BE SOFT DRAWN COPPER.
BELOW GRADE.
ACTUAL FIELD CONDITIONS AND EQUIPMENT ACTUALLY PROVIDED.
EXOTHERMIC WELDS, ERICO "CADWELD" OR EQUAL, UNLESS OTHERWISE NOTED.
DETAILS OF EQUIPMENT PROVIDED MAY VARY.
INSTALL AND CONNECT ALL ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS.
CIRCUIT BREAKER SHALL BE SQ-D, OR EQUAL (AS LISTED IN APPENDIX D).
ALL WORK SHALL COMPLY WITH THE 2011 NEC.
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EXACT LOCATIONS OF
EQUIPMENT OR ALL REQUIRED FITTINGS AND HARDWARE. PROVIDE ALL EQUIPMENT, MATERIALS, AND LABOR
REQUIRED FOR A COMPLETE OPERATING SYSTEM. COORDINATE EQUIPMENT LOCATIONS AND WIRING WITH
UNDERGROUND CONDUITS SHALL BE SCHEDULE 80 PVC BELOW GRADE. MINIMUM CONDUIT SIZE SHALL BE 0.75"
ABOVE GRADE, AND 1.00" BELOW GRADE. UNDERGROUND CONDUIT SHALL BE RUN A MINIMUM OF 24" BELOW
CABLE AND WIRE SHALL BE COPPER, DUAL RATED, TYPE THNN/THWN, EXCEPT GROUND CONDUCTORS SHALL
WARRANTEE ENTIRE ELECTRICAL INSTALLATION FOR A PERIOD OF ONE YEAR FROM THE FINAL ACCEPTANCE
DATE. PROMPTLY REPLACE AND/OR REPAIR ANY EQUIPMENT OR WIRING PROVIDED UNDER DIVISION 16
DURING THE WARRANTEE PERIOD WITH NO ADDITIONAL COSTS TO THE OWNER.
PUMP CONTROL PANEL WILL BE FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED AND WIRED BY
ELECTRICAL CONTRACTOR. CIRCUIT DIAGRAM AND DETAILS ARE PROVIDED FROM DATA RECEIVED FROM THE
VENDOR, AND ARE PROVIDED FOR THE CONTRACTOR'S CONVENIENCE. ACTUAL CIRCUITRY AND SPECIFIC
ALL GROUNDING CONDUCTORS ARE 30" BELOW GRADE. ALL CONNECTIONS TO GROUND RODS SHALL BE
GROUND RODS SHALL BE COPPER CLAD STEEL, 0.75" BY 10 FT., DRIVEN SO TOP OF ROD IS 12" BELOW GRADE
ELECTRICAL NOTES
2" SCH 80 PVC
2" SCH 80 PVC
6'
48
" M
IN
24
"
24
" M
IN
SEE NOTE #4
SPD
AA
PANEL INSTALLATION NOTES:
1. PUMP MOTOR CONDUIT SHALL BE SIZE TO ACCOMMODATE 40% CONDUIT FILL. MINIMUM
CONDUIT SIZE TO BE 2" SCH 80 PVC.
2. POWER SUPPLY SHALL BE UNDERGROUND ON THE LIFT STATION SITE AND SHALL BE
3-PHASE, FROM A 3-PHASE SOURCE ONLY.
3. AN ELECTRICAL GROUNDING SYSTEM SHALL BE INSTALLED AS PER THE NATIONAL
ELECTRICAL CODE, LOCAL CODES AND ORDINANCES, AN UNDERGROUND PERIMETER
CABLE GROUNDING SYSTEM SHALL BE INSTALLED WITH CONNECTIONS TO AT LEAST
WET WELL COVER, VALVE VAULT COVER, CONTROL PANELS, GENERATOR, UTILITY
COMPANY TRANSFORMER, MANUAL DISCONNECT SWITCH, AND METAL FENCE. SEE
GROUNDING DETAILS.
4. THE STATION NAME, ORANGE COUNTY I.D. NUMBER, AND ADDRESS SHALL BE AFFIXED
TO THE FRONT OF THE METER CABINET.
5. ALL MOUNTING HARDWARE & BRACKETS AND ELECTRICAL ENCLOSURES SHALL BE 316
STAINLESS STEEL.
6. THE SCADA PANEL SHALL BE RELOCATED AND MOUNTED ON THE PANEL RACK BY
CONTRACTOR.
7. A MINIMUM OF 36-INCH CLEARANCE SHALL BE PROVIDED FOR SCADA PANEL
REGARDLESS OF SIZE OF EXISTING SCADA PANEL.
CONTROL PANEL
SCADA PANEL (FUTURE)
3" 316 S.S. PIPE (SCH 40)
VIEW A-A
1-1/2" MIN. MOUNTING BRACKET
WITH PROTECTIVE CAP
RIGID ALUMINUM
ENCASED IN CONCRETE
(12 Ø TYP)
INCOMING POWER FROM UTILITY POINT
OF SERVICE (MINIMUM 2" SCH 80 PVC)
SWEEP ELBOWS (TYP)
MINIMUM 2" SCH 80 PVC
5 OHM MAX. GROUND RODS (10' APART)
CONTROL CONDUIT
2" SCH 80 PVC
MOTOR CONDUCTOR CONDUIT
2" SCH 80 PVC (SEE NOTE #1)
FROM CONTROL PANEL
SEAL OFF - TYPE ESYR
(TYP)
S.S. PIPE CAP
(TYP)
316 S.S. METER BASE
WITH BY-PASS
UTILITY POWER
DISCONNECT
UTILITY
DISCONNECT
METER
MAIN
BREAKER
SCADA PANEL (FUTURE)
3-1" SCH 80 PVC
TO ANTENNA POLE
FRONT VIEW
NTS
FINISHED GRADE
CONTROL PANEL
SPD
DIST "Y"
Y
15"
18"
12"
12"
24"
SCADA
PANEL
(NOTE 6)
CONTROL
PANEL
PANEL
HEIGHT
30"
36"
24"
24"
42"
36"
60"
48"
PANEL & SEAL-OFF
MOUNTING HEIGHTS
FOR PANELS NOT LISTED ADJUST
MOUNTING HEIGHTS ACCORDINGLY
DIST "X"
INCOMING POWER FROM
UTILITY POINT OF
SERVICE (MINIMUM 2"
SCH 80 PVC)
SWEEP
ELBOW
X
SWEEP ELBOWS MINIMUM
2" SCH 80 PVC
REAR VIEW
NTS
24" M
IN
48" M
IN
SEAL OFF - TYPE ESYR
24" MIN.
STUB UP
1" SCH. 80 PVC CONDUIT FOR FUTURE
PRESSURE TRANSDUCER
PANEL INSTALLATION NOTES:
1. PUMP MOTOR CONDUIT SHALL BE SIZE TO ACCOMMODATE 40% CONDUIT FILL. MINIMUM
CONDUIT SIZE TO BE 2" SCH 80 PVC.
2. POWER SUPPLY SHALL BE UNDERGROUND ON THE LIFT STATION SITE AND SHALL BE
3-PHASE, FROM A 3-PHASE SOURCE ONLY.
3. AN ELECTRICAL GROUNDING SYSTEM SHALL BE INSTALLED AS PER THE NATIONAL
ELECTRICAL CODE, LOCAL CODES AND ORDINANCES, AN UNDERGROUND PERIMETER
CABLE GROUNDING SYSTEM SHALL BE INSTALLED WITH CONNECTIONS TO AT LEAST
WET WELL COVER, VALVE VAULT COVER, CONTROL PANELS, GENERATOR, UTILITY
COMPANY TRANSFORMER, MANUAL DISCONNECT SWITCH, AND METAL FENCE. SEE
GROUNDING DETAILS.
4. THE STATION NAME, ORANGE COUNTY I.D. NUMBER, AND ADDRESS SHALL BE AFFIXED
TO THE FRONT OF THE METER CABINET.
5. ALL MOUNTING HARDWARE & BRACKETS AND ELECTRICAL ENCLOSURES SHALL BE 316
STAINLESS STEEL.
6. THE SCADA PANEL SHALL BE RELOCATED AND MOUNTED ON THE PANEL RACK BY
CONTRACTOR.
7. A MINIMUM OF 36-INCH CLEARANCE SHALL BE PROVIDED FOR SCADA PANEL
REGARDLESS OF SIZE OF EXISTING SCADA PANEL.
PUMP
1
PUMP
2
OL
MB1
MS1
OL
MB2
MS2
RL1
FB210AMP
GFDR
TB3-2
2KVA
XFMR
120V NEUTRAL
TB
GND
B
C
NG
GR
A
MCB
480V N
ECB
1.6-2.4A
10AMP
120V
20AMP
TB3-1
480V
CCB
SCB
DRB
PM
PM CB
SPD
3Ø
480V
480V
NEUTRAL
60Hz
GENERATOR
RECEPTACLE
(1)
R
RL2
(2)TTS
(3)(4)
AH
TTS
A1
MS1
C
MS1A
MS2
C
A2
R5
5
MS2A
OL
ETM
OL
ETM
R5
AL
C
DPDT
R
PL3
PL4
A4
FL
A3
1
R5
C
R4
DPDT
#1
X00
H-O-A
#2
00X
00X
X00
H-O-A
ALT
81
PM
9
R3
6
6
R2
8
8
8
65
8
TEST
6
OFF
AUTO
R4
ATS
72
13
R3
75VA
XFMR
78
PM
3AMP
FB3
FR4
HIGH
5AMP
(7)
120V
(8)
24V
8
ASB
3
A
PL2
A
PL1
R3
C
C
R2
31
R1
R1
C
DPDT
DPDT
DPDT
1
1
4
3
R2
R1
86
R1
FR2
LEAD
(5)
(3)
FR1
OFF
TB1
(1)
(6)
(4)
(2)
A
FR3
LAG
R
120V
SCADA
POWER
SUPPLEMENTAL
PROTECTION
BREAKER
(10)(9)
FR5
HIGH
HIGH LEVEL ALARM
INPUT TO SCADA
DUPLEX PUMP CONTROL SCHEMATIC (480V)
24"
Y
X
SCADA
PANEL
(NOTE 7)
CONTROL
PANEL
SEAL OFF
TYPE ESYR
FINISHED
GRADE
INCOMING POWER FROM
UTILITY POINT OF SERVICE
(MINIMUM 2" SCH 80 PVC)
METER
MAIN BREAKER
SPD
PUMP STATION CONTROL PANEL (240V)
SIDE BY SIDE FRONT VIEW
ALL NOTES ON THIS SHEET APPLY
TO THIS VIEW
ELECTRICAL DETAILS
ED-101
3738
2014-28-06
DEC 2017
WCH
DJK
WCH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Thursday, August 31, 2017 5:31:20 AM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 ED-101.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
________
WILLARD HOANSHELT P.E.
42593
EB: 6160
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
G
G
G
PUMP 2PUMP 1
G
G
G
G
G
G
ONE TYPICAL PER STATION
GROUND TEST ENCLOSURE
VALVE VAULT
G
CABLE HOLDER
G
TO FENCE
(NOTE #2)
2/0 STRANDED
TINNED COPPER TO
FENCE
COUNTERPOISE 2/0
STRANDED TINNED
COPPER MIN 30"
BELOW GRADE
BOND 316 SST STRAP TO
ACCESS COVER AND
FRAME
BOND #4 STRANDED
TINNED COPPER TO
ACCESS COVER AND
FRAME
NOTES:
1. DETAIL IS GENERIC. SPECIFIC LOCATIONS OF EQUIPMENT MAY VARY.
2. TIE TO FENCE, MINIMUM 2 LOCATIONS. NOT REQUIRED WHERE PVC COATED, BLOCK, OR
WOOD FENCE IS INSTALLED.
3. PROVIDE EXOTHERMIC WELDS UNLESS NOTED OTHERWISE.
ELEC PANEL
RACK AND
CONTROL PANEL
PUMP STATION GROUNDING
(TYPICAL)
3/4" PVC CONDUIT
1'-0" LONG
(SEE NOTE 2)
316 SST GROUND CLAMP,
BOLT TO FRAME
#4 AWG TINNED
COPPER GROUNDING
CONDUCTOR
TO GROUND
GRID/COUNTERPOISE
GROUND 316 SST CLAMP,
BOLT TO COVER
METAL ACCESS COVER
1/8" THICK X 1" WIDE
MULTI-STRAND, 316
STAINLESS STEEL BRAID
(LENGTH AS REQUIRED)
NOTES:
1. ON COVERS WITH MULTIPLE DOORS, PROVIDE BRAID FROM FRAME TO DOOR ON
EACH DOOR PROVIDE WATERPROOF CAULKING WHERE GROUND CABLE AND
CONDUIT PENETRATES WETWELL TO PREVENT INTRUSION OF GROUNDWATER
AND ESCAPE OF VAPORS FROM WETWELL.
2. INSTALL GROUND WIRE SO THAT IT WILL NOT CROSS CLEAR OPENING OR PREVENT
OR IMPEDE NORMAL METHOD OF REMOVING FLOATS OR PUMPS.
2"
GROUND TEST WELL
PRE-CAST
CONCRETE
3" HIGH LETTERS
CAST IN COVER
RECESSED
HOLD DOWN
(TYP)
BROOKS PRODUCTS
10" X 17" SERIES 36
PULL BOX, OR EQUAL
CAST IRON COVER
LIFTING HOLE
GROUND
TEST WELL
FINISHED
GRADE
DRILL & TAP
#4 AWG TINNED
COPPER GROUNDING
CONDUCTOR,
PROVIDE 36" SLACK
MECHANICAL CONNECTION
NO. 2/0 AWG TINNED
COPPER GROUNDING
CONDUCTOR TO
COUNTERPOISE
GRAVEL
GROUND ROD
BRAID CLAMP
(TYP)
1/8" THICK X 1" WIDE X 12" LONG
MULTISTRAND TINNED
COPPER BRAID
GATE POST
GATE PIPE
FENCE RAIL POST
GROUNDING CLAMP
FINISHED
GRADE
TO PUMP STATION
COUNTERPOISE
PERIMETER
GROUND LOOP
NO. 2/0 TINNED
COPPER
GROUNDING
CONDUCTOR
FENCE POST GROUNDING
(TYPICAL)
PROPERTY OR EASEMENT CORNER
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION
BOUNDARY
CORNER TYPE
COMMENTS
3268-C1 C-201 EASEMENT CORNERPB 9, PG 94
3268-C2 C-201 EASEMENT CORNERPB 9, PG 94
3268-C3 C-201 EASEMENT CORNERPB 9, PG 94
3268-C4 C-201 EASEMENT CORNERPB 9, PG 94
3470-C1 C-301 RIGHT OF WAYPB X, PG 14
3470-C2 C-301 RIGHT OF WAYPB X, PG 14
3470-C3 C-301 RIGHT OF WAYPB X, PG 14
3470-C4 C-301 RIGHT OF WAYPB X, PG 14
3470-C5 C-301 RIGHT OF WAYPB X, PG 14
PUMP STATION
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION COMMENTS
C102-PS1 PS 3198
C201-PS1 PS 3268
C301-PS1 PS 3470
FITTING
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION MAIN TYPE FITTING TYPE COMMENTS
3198-F1 C-102 FORCE MAIN 6" 45° BEND PS 3198
3198-F2 C-102 FORCE MAIN 6" 45° BEND PS 3198
3198-F3 C-102 FORCE MAIN 6" LINESTOP PS 3198
3268-F1 C-201 FORCE MAIN 6" 90° BEND PS 3268
3268-F2 C-201 FORCE MAIN 6" LINESTOP PS 3268
3470-F1 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F2 C-302 FORCE MAIN 8" 5.625° BEND PS 3470
3470-F3 C-302 FORCE MAIN 8" TEE PS 3470
3470-F4 C-302 FORCE MAIN 8" TEE PS 3470
3470-F5 C-302 FORCE MAIN 8" TEE PS 3470
3470-F6 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F7 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F8 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F9 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F10 C-302 FORCE MAIN 8" TEE PS 3470
3470-F11 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F12 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F13 C-302 FORCE MAIN 8" 11.25° BEND PS 3470
3470-F14 C-302 FORCE MAIN 8" 22.5° BEND PS 3470
3470-F15 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F16 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F17 C-302 FORCE MAIN 8" LINESTOP PS 3470
3470-F18 C-302 FORCE MAIN 8" CAP PS 3470
3470-F19 C-302 FORCE MAIN 8" LINESTOP PS 3470
3470-F20 C-302 FORCE MAIN 8" CAP PS 3470
3470-F21 C-302 FORCE MAIN 8" 45° BEND PS 3470
3470-F22 C-302 FORCE MAIN 8" 45° BEND PS 3470
OUTER LIMITS OF PUMP STATION IMPROVEMENTS
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION
DESCRIPTION OF
IMPROVEMENTS
3198-I1 C-102 CURB
3198-I2 C-102 CURB
3198-I3 C-102 CURB
3198-I4 C-102 CURB
3198-I5 C-102 DRIVEWAY
3198-I6 C-102 DRIVEWAY
3198-I7 C-102 DRIVEWAY
3198-I8 C-102 DRIVEWAY
3198-I9 C-102 DRIVEWAY
3198-I10 C-102 DRIVEWAY
3268-I1 C-201 CURB
3268-I2 C-201 CURB
3268-I3 C-201 CURB
3268-I4 C-201 CURB
3470-I1 C-301 CURB
3470-I2 C-301 CURB
3470-I3 C-301 CURB
3470-I4 C-301 CURB
3470-I5 C-301 CURB
3470-I6 C-301 CURB
MANHOLE
ID NUMBER PLAN SHEET # EASTING NORTHING
RIM
ELEVATION
INVERT ELV
N
INVERT ELV
NE
INVERT ELV
E
INVERT ELV
SE
INVERT ELV
S
INVERT ELV
SW
INVERT ELV
W
INVERT ELV
NW
MANUFACTURER COMMENTS
3470-MH2 C-302 PS-3470
3470-MH3 C-302 PS-3470
VALVE
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION VALVE TYPE MAIN TYPE VALVE SIZE VALVE MFR VALVE MODEL #
# OF TURNS TO
CLOSE
GEAR
ACTUATOR
GEAR RATIO SIDE ACTUATOR ACTUATOR MFR COMMENTS
3470-V1 C-302 8" TAPPING VALVE FORCE MAIN PS 3470
3470-V2 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V3 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V4 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V5 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V6 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V7 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V8 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V9 C-302 8" PLUG VALVE FORCE MAIN PS 3470
3470-V10 C-302 8" TAPPING VALVE FORCE MAIN PS 3470
3470-V11 C-302 8" TAPPING VALVE FORCE MAIN PS 3470
METER
ID NUMBER PLAN SHEET # EASTING NORTHING ELEVATION MAIN TYPE COMMENTS
3268-WM1 C201 PS 3268
AS-BUILT ASSET COORDINATE ASSET TABLES
X-100
3838
2014-28-06
DEC 2017
CKM
JAB
GJH
DECEMBER 2017 - BID SET
PUMP STATION R/R PACKAGE 15 IMPROVEMENTS
ORANGE COUNTY UTILITIES
9150 CURRY FORD ROAD
ORLANDO, FLORIDA 32825
LINE IS 2 INCHES
AT FULL SIZE
(IF NOT SCALE ACCORDINGLY)
No. REVISIONS BY DATE
PROJECT DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DRAWING FILE:
PROJECT No.:
SCALE:
DRAWING No.
SHEET
___ OF ___
AS NOTED SEE MARGIN
Tuesday, December 19, 2017 12:18:01 PM F:\CIVIL\PROJECTS\2014\2014-28 OCU Cont Eng Services\14-28.06 Pkg 15 PS\5.0 Drawings\2014-28-06 Package 15 X-100.dwg
DESIGN ENGINEER
FLORIDA REGISTRATION No.
58685
CYNTHIA K. MALONE, P.E.
BID SET *DATE**INI*
CONFORMED DRAWING *DATE**INI*
RECORD DRAWING *DATE**INI*