+ All Categories
Home > Documents > PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 —...

PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 —...

Date post: 24-Mar-2018
Category:
Upload: vodieu
View: 240 times
Download: 4 times
Share this document with a friend
114
HUMIDITY PRESSURE PRESSURE P74 Series | p. 1087 PTX1 Series | p. 1059 DPL Series | p. 1009 GC52 | p. 1047 SRCM | p. 1095 A2G | p. 1103 Kele Carries Reliable Instruments for Critical Environments and General Building Pressure Sensing.
Transcript
Page 1: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

HU

MID

ITY

PRESSUREP

RE

SS

UR

E

P74 Series | p. 1087

PTX1 Series | p. 1059

DPL Series | p. 1009

GC52 | p. 1047

SRCM | p. 1095

A2G | p. 1103

Kele Carries Reliable Instruments for Critical Environments and General Building Pressure Sensing.

Page 2: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

MODEL/SERIES PAGEProducts manufactured in the United States

Products that are new to the catalog

ke le .com

PRESSURE

DPAII | p. 1012

PTX1 Series | p. 1059

M264 | p. 1014

PR

ES

SU

RE

Controllers and MonitorsPCM Series — Pressure Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1092MRMS Series — Multi-Room Monitoring Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1094SRCM Series — Room Condition Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1095SRIM Series — Room Pressure Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097SRMD Series — Room Isolation Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1098SRPM Series — Room Pressure Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1099

Differential Pressure SwitchesKDPS Series — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1070AFS Series — Adjustable Differential Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1071RH-3, RH-3-2 — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1073NS2-0000-02 — Adjustable Differential Pressure Switch Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1075RFS-4001 — Differential Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1076RSS Series — Adjustablåe Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1077DDP-109 — Dual Setpoint Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1078DFS-221 — Fixed Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10791910 Series — Differential Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10801900-5-MR — Manual Reset Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1080P32 Series — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1081A2G-40 Series — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108224-013, 24-014 — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1085P74 Series — Differential Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1087J21K Series — Differential Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10883000 Series — Photohelic Differential Pressure Switch / Gauge . . . . . . . . . . . . . . . . . . . . . . . . . 1108

Differential Pressure TransmittersDPL Series — Low Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1009DPA, DPA-M Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1011DPA II Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1012M264 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014M265 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1016260 Series — Multirange Differential Pressure Transmitter with Display . . . . . . . . . . . . . . . . . . . 1018M267-MR — Multi-range Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1020269 Series — Precision Low Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . 1022CXLdp Series — Differential Pressure Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1023DXLdp Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1025XLDP Series — Differential Pressure Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1027ZPS Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1028PR274/275 Series — Differential Pressure Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1030A2G-50 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1032T30 Series — Differential Pressure Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1034PR264 Series — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035PR276 Series — Duct Static Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1037

Gauges and AccessoriesBVA-5 — Bypass Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1053DPW-3VLV, M230-3VLV, W30-3VLV — Three and Five-Valve Manifolds . . . . . . . . . . . . . . . . . . 1054K2000 Series — Low Cost Differential Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1101111.10, 111.12 Series — Dial Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11052000 Series — Magnehelic Differential Pressure Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106232.34, 233.34 Series — Dial Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1109Series A — Microprocessor Based Differential Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . 111025W100 — Refrigeration Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111PG Series — Pressure Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111147B-1, 47S-1, 747B, 747S, PT — Snubbers, Pigtail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1112A300 Series, RPS, SD-01, 21121, 60681 — Air Pressure Sensors, Surge Dampeners . . . . . . . 1113

Pressure SwitchesP10 Series — Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1084PK Series — Adjustable Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1089J54 Series — Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1091

Pressure TransmittersP51 Series — Stainless Steel Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1055PSS2 Series — Stainless Steel Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1057PTX1 Series — Stainless Steel Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1059209 Series — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106150 Series — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1063PVI-1, PVI-2 — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1066GC51 Series — Rangeable Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068MBS 1900 — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1065PSD-30 Series — Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1069A2G-05, -10, -15 Series — Pressure Gauges / Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1103

Wet/Wet Differential Pressure TransmittersDPW-692 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1039M230 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1041231 Series — Setra Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1043231RS Series — Remote Mounted Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . 1045GC52 Series — Wet/Wet Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1047PR282 Series — Wet to Wet Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . 1049W30 Series — Differential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1051

Page 3: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1009

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 4-20 mA Model 9-30 VDC 0-5, 0-10 VDC Model 9-30 VAC/VDCSignal Output DPL-XX-1 0-10 VDC (3-wire) DPL-XX-4 4-20mA (2-wire) DPL-XX-5 0-5 VDC (3-wire)Maximum Output Impedance 800ΩMinimum Output Impedance 5,000ΩAdjustments Adjustable via trim potsAccuracy ±1 .0% full scale

Thermal Effect Compensated temperature range: 0° to 150°F (-18° to 65°C)

Overpressure ±10 psig (68 .95 kPa) in positive or negative direction

Operating Temperature 0° to 150°F (-18° to 65°C)Storage Temperature -40° to 185°F (-40° to 85°C)Enclosure Rating Fire retardant glass filled polyester

(UL94V-0)Process Connection 1/4" OD press-on fittingWiring Terminations Screw terminal stripApprovals CEWeight 0 .3 lb (0 .15 kg)Warranty 1 year

LOW DIFFERENTIAL PRESSURE TRANSMITTERDPL SERIES

3.95 (10.0)

2.75(7.0) 3.49

(8.9)

in(cm)

DESCRIPTIONThe Kele DPL Series Low Differential Pressure Transmitters offer reliable pressure measurements as low as ±0 .10" w .c . (±25 Pa) with an exceptional 1% full scale accuracy . The rugged capacitance sensor can withstand up to 10 psig over pressure without damaging the unit . The transmitters feature reverse wiring protection and easily accessible zero and span pots . The DPL Series are designed for energy management systems, environmental pollution control, HVAC, and building automation applications .

FEATURES• 10 psig overpressure• ±1% full scale accuracy• Reverse wiring protection• 4-20 mA, 0-5 or 0-10 VDC output• Zero and span adjustment• Bidirectional ranges available

APPLICATION• HVAC and energy management systems• Variable air volume and fan control• Filter monitoring• Environmental pollution control• Furnace draft• Lab and fume hood control

DIMENSIONS

SPECIFICATIONS

4.27 (10.8)

0.60(1.5) 1.55

(3.9)

Page 4: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1010

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

+9 to 30 VDC

Currentmonitoring

device

–ModelDPL

+–

WIRING

LOW DIFFERENTIAL PRESSURE TRANSMITTERDPL SERIES

ORDERING INFORMATION

Readoutor

BAS

-COM

+EXC

OUT

Powersupply

ModelDPL

MODELDPL

DPL 10 4- -

DESCRIPTION

XXXDifferential pressure transmitter

Range Code (see table)

0-10 V output4-20 mA output0-5 V output

Example: DPL-10-4 Differentialpressure transmitter with4-20mA output, ± 0.1"w.c.

145

TABLE 1. RANGE CODESRANGE CODE PRESSURE RANGE "W.C. RANGE CODE BIDIRECTIONAL RANGE "W.C.

123456789

0 to 0.250 to 0.50 to 1.00 to 2.50 to 5.00 to 10.00 to 25.00 to 50.00 to 100

101112131415161718

±0.1±0.25±0.5±1.0±2.5±5.0±10.0±25.0±50.0

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SD-01 Surge dampener 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 5: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1011

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage DPA 24 to 36 VDC @ 23 mA, 24 VAC

±10% @ 0 .83 VA DPA-M (Voltage) 15 to 36 VDC @ 23 mA, 24 VAC ±

10% @ 0 .83 VADPA-M (Current) 12 to 36 VDC @ 23 mA, 24 VAC

±10% @ 0 .83 VASignal Output DPA 4-20 mA @ 500Ω, 1-5 or 2-10 VDCDPA-M 4-20 mA @ 500Ω, 0-5 or 0-10 VDCAccuracy ±1% Full Scale OutputRepeatability ±0 .3% Full Scale OutputOperating Humidity 10 to 95% RH, non-condensing

Operating Temperature DPA 32° to 185°F (0° to 85°C)DPA-M 32° to 140°F (0° to 60°C)Compensated Temperature Range 32° to 122°F (0° to 50°C)

Input Range 0-1" W .C . to 0-20" W .C .Media Compatibility Dry air or inert non-conductive gasesProof Pressure 100" W .C .Wiring Termination Terminal (16 to 22 AWG)Approvals CE, RoHS, REACHWeight 0 .32 lb (0 .14 kg)Warranty 2 years

DESCRIPTIONThe Kele DPA and DPA-M Series are very cost-effective, low-range differential air pressure transmitters for duct pressure applications where measurement of pressure differentials up to 10" W .C . is required . The DPA and DPA-M Series incorporate a piezoresistive, silicon, micromachined sensing element and integrated temperature compensation for excellent performance and accuracy .

FEATURES• Low cost• 4-20 mA output standard or 1-5/2-10 VDC outputs• 24 VAC or 24 VDC power• Brass barb fittings for 1/4" tubing• Two-year warranty

DIFFERENTIAL PRESSURE TRANSMITTERDPA, DPA-M SERIES

SPECIFICATIONS

DPA Mini

ORDERING INFORMATION

MODEL DESCRIPTIONDPA Differential pressure transmitterDPA-M Differential pressure transmitter mini INPUT RANGE ("W.C.) 1 0-1 2 0-2 3 0-3 4 0-4 5 0-5 10 0-10 20 0-20 300 0-0.3 KPa 500 0-0.5 KPa 1000 0-1.0 KPa 1600 0-1.6 KPa 2500 0-2.5 KPa OUTPUT SIGNAL 5 1-5 VDC 10 2-10 VDC 20 4-20 mA

DPA-M 10 5 Example: DPA-M-10-5 Differential pressure transmitter mini with input range of 0-10" W.C. and 1-5 VDC output signal

DPA-1-20

Wiring

Output Signal Supply Voltage Wire Connections

Output

Ground

VIN

Page 6: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1012

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

3.07"(78.02mm)

5.25"(133.45mm)

1.08"(27.52mm)

Factory Calibration DO NOT ADJUST!

Unit Select DIP Switches

Config DIP Switches

1/2" NPT Access Hole with Strain

Relief Fitting

Terminal Blocks 16-22 AWG ShieldedConductors Recommended

Brass Fittings (recommend 1/4" push-on tubing

DESCRIPTIONThe Kele DPA II Series Differential Pressure Transmitter is a cost-effective, versatile low-range differential air pressure transmitter for applications such as monitoring building static pressure, filter blockage, measuring flow, clean rooms, etc . It has field selectable pressure ranges and outputs through easy to configure DIP switches . The DPA II Series incorporates a durable piezoresistive sensing element and integrated temperature compensation for excellent performance and accuracy . Models with LCD feature an easy-to-read display for set up reference, trouble shooting assistance, and performance monitoring .

FEATURES• Field selectable pressure ranges• Field-selectable outputs 4-20mA, 1-5 VDC, or 2-10 VDC• LCD option for easy installation and setup• 24 VAC or 24 VDC power• Two-year warranty

Supply Voltage 15-36 VDC, 35 mA 24 VAC ±10%, 0 .83 VASignal Output 4-20 mA (two-wire) 1-5 or 2-10

VDC (three-wire) Dip switch selectable

Max Output Impedence (mA) 550Ω max

Min Output Impedance (VDC) 100 KΩ min

Accuracy ±0 .85% Full Scale Output, includes linearity, hysteresis, and repeatability

Thermal Effect ± 0 .067% FSO/°F (± 0 .12% FSO/°C)

Compensated Temperature Range 32 to 122°F (0 to 50°C) Media Compatibility Dry air or inert non-conductive

gasesOverpressure 100" W .C .Operating Humidity 0 to 95% non-condesning Operating Temperature -4° to 140°F (-20° to 60°C)Wetted Parts

Brass fittings, PVC tubing, and silicon

Enclosure Rating UL94-5VAProcess Connection 1/4 in barbed fittingsWiring Terminations Screw terminal with cable glandApprovals RoHS, CE, WEEE, REACHWeight 0 .45 lbs (0 .20 kg); 0 .50 lbs (0 .23

kg) with LCDWarranty 2 years

SPECIFICATIONS

DPAII-1-20

DIMENSIONS

DPAII-1-20-LCD

DIFFERENTIAL PRESSURE TRANSMITTERDPA II SERIES

Page 7: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1013

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

DIFFERENTIAL PRESSURE TRANSMITTERDPA II SERIES

WIRING / OUTPUT SELECTION / SPAN SELECTION

Table 2 Output Selection

Table 1 Wiring Connections

Table 3 Span Selection

ORDERING INFORMATION

RELATED PRODUCTS PAGESD-01 Surge dampener 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-308-K Duct static pressure fitting, 1/4" barb 1113

Example: DPAII-10-5-LCD Differential pressure transmitter with input range of 0 to 10" W.C. and 1 to 5 VDC output signal

MODEL DESCRIPTIONDPAII Differential pressure transmitter INPUT RANGE 1 0 to 1" w.c. 2 0 to 2" w.c. 3 0 to 3" w.c. 4 0 to 4" w.c. 5 0 to 5" w.c. 10 0 to 10" w.c. 20 0 to 20" w.c. 300 0 to 0.3 KPa 500 0 to 0.5 KPa 1000 0 to 1.0 KPa 1600 0 to 1.6 KPa 2500 0 to 2.5 KPa OUTPUT SIGNAL 5 1-5 VDC 10 2-10 VDC 20 4-20 mA DISPLAY OPTION LCD LCD Option

DPAII 10 5 LCD

JUMPER SELECTABLE *0 to 2" w.c. 0-300 Pa 0-500 Pa0 to 1" w.c. 0-300 Pa 0-500 Pa0 to 4" w.c. 0 to 5" w.c. 0-1000 Pa0 to 3" w.c. 0 to 5" w.c. 0-1000 Pa0 to 3" w.c. 0 to 5" w.c. 0-1000 Pa0-1600 Pa 0-2500 Pa NA0-3200 Pa 0-5000 Pa 0-5000 Pa0 to 1" w.c. 0 to 2" w.c. 0-500 Pa0 to 1" w.c. 0 to 2" w.c. 0-300 Pa0 to 3" w.c. 0 to 4" w.c. 0 to 5" w.c.0 to 10" w.c. 0-2500 Pa NA0 to 10" w.c. 0-1600 Pa NA

ModelDPAII - 1DPAII - 2DPAII - 3DPAII - 4DPAII - 5DPAII - 10DPAII - 20DPAII - 0.5DPAII - 0.5DPAII - 1.01DPAII - 1.11DPAII - 2.51

*Jumper selectable for customized applications

Page 8: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1014

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 9 to 30 VDC, 9 to 33 VDCSignal Output 4-20 mA (two-wire), 0-5 VDC (three-

wire), Current (two-wire) 4-20 mA, Voltage (three-wire) 0-5 VDC

Maximum Output Impedance mA 800Ω @ 24 VDC, 750Ω @ 24 VDCMinimum Output Impedance VDC 5000Ω, ≥5000ΩAccuracy ±1% FS, RSS (at constant temp)

±1% FS Non-linearity ±0 .96% FS Non-repeatability 0 .1% FS Hysteresis 0 .2% FS; ±0 .4% and ±0 .25% optional

Thermal Effect Zero/Span shift 0 .033°F (0 .018°C), Compensated temperature range 0° to 150°F (-18° to 65°C) Zero/Span shift 0 .033°F (0 .018°C)

Repeatability 0 .05% FSOverpressure Up to 10 psig (68 .95 kPa) range

dependant, ±10 psig (68 .95 kPa)Additional Specifications (Unit is factory calibrated at 0g effect

with diaphragm vertical),

Range Zero offset (%FS/G)Upto 0.5" WC 0 .60Upto 1.0" WC 0 .50Upto 2.5" WC 0 .22Upto 5.0" WC 0 .14, Position effect: (Unit is factory

calibrated at 0g effect with diaphragm vertical) Range (in) Zero offset (%FS/G) 0-10 0 .12 0-5 0 .14 0-1 .0 0 .22 0-0 .1 2 .10

Operating Temperature 0° to 175°F (-18° to 79°C)Storage Temperature -65° to 250°F (-54° to 121°C)Enclosure Rating Fire retardant, glass-filled polyesterProcess Connection 3/16" OD barbed brassDimensions 5 .06" x 2 .75" x 2 .38" (12 .86 x 6 .99 x

6 .03 cm), 3 .00"H x 5 .51"W x 1 .91"D (14 .00 x 7 .62 x 4 .85 cm)

Temperature Range 0° to 150°F (-18° to 65°C)Enclosure Fire-retardant glass filled polyester

(UL 94 V-0 approved)Hysteresis 0 .1% FSLinearity ±0 .96% FSApprovals CEWeight 0 .55 lb (0 .25 kg)Warranty 3 years

DIFFERENTIAL PRESSURE TRANSMITTERM264 SERIES

DESCRIPTIONThe Setra Model M264 Differential Pressure Transmitter is a low-air pressure transmitter able to sense differential pressure in both negative and positive ranges . The Model M264 incorporates a tensioned stainless steel diaphragm to form a variable capacitor that will produce variation in the output signal . The Model M264s durable design will tolerate an overpressure of 10 psig (68 .95 kPa) and has an unconditional three-year warranty .

FEATURES• 4-20 mA output signal • Voltage output signal optional • 10 psig (68.70 kPa) overpressure • Three-year unconditional warranty • 1% accuracy standard, 0.4% and 0.25% optional• Reverse wiring protected• Stainless steel diaphragm • Ideal for air and non-conducting gases

APPLICATION• HVAC building automation• Variable air volume control• Environmental pollution control• Lab and fume hood control• Filter monitoring• Medical instrumentation• Velocity pressure measurement

SPECIFICATIONS

M264 Series

Page 9: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1015

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Mo

del M

264

Hig

h

Lo

w

1.66(4.22)

5.06 (12.86)

2.75(6.99)

in(cm)

4.56 (11.59)

Zero

Sp

an

2.38 (6.03)

CO

M E

XC

OU

T

0-5 VDC

0-5 VDC Output4-20 mA Output

PowerSupply

9-30 VDCHigh Low

HighLow

PowerSupply

9-30 VDC

4-20 mA

WIRING

DIMENSIONS

DIFFERENTIAL PRESSURE TRANSMITTERM264 SERIES

ORDERING INFORMATION

MODEL DESCRIPTIONM264 Differential pressure transmitter XXX RANGE CODE (see Table 1 below) C 4-20 mA output (stocked at Kele) V 0-5 VDC output (call Kele for availability)

M264 - 2R5WB - CExample: M264-2R5WB-C Differential pressure transmitter with a 4-20 mA output proportional to a range of -2.5" to 2.5" W.C. (622 Pa)

RANGE CODE

RANGECODE

PRESSURE RANGE "W.C. Pa "W.C. Pa

BIDIRECTIONAL PRESSURE RANGE

0R1WDR25WD0R5WD001WD2R5WD005WD010WD025WD050WD100WD

0R1WBR25WB0R5WB001WB2R5WB005WB010WB025WB

0-0.10 0-24.9 0-0.25 0-62.2 0-0.50 0-124 0-1.00 0-249 0-2.50 0-622 0-5.00 0-1244 0-10.0 0-2488 0-25.0 0-6221 0-50.0 0-12441 0-100.0 0-24883

±0.1 ±24.9 ±0.25 ±62.2 ±0.5 ±124 ±1.0 ±249 ±2.5 ±622 ±5.0 ±1244 ±10.0 ±2488 ±25.0 ±6221

TABLE 1. SPECIFYING RANGE

RELATED PRODUCTS PAGE264-A1 Conduit housing for M264 A-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SD-01 Surge dampener 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

† add -E to the end of part number for 0.4% accuracy or add -F to the end of part number for 0.25% accuracy

Page 10: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1016

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 4-20 mA: 9-30 VDC @ 10 mA 0-5 mA: 9-30 VDC @ 10 mA, 9 to 3 VAC @ 0 .2 VA 0-10 mA: 12 to 30 VAC @ 0 .2 VASignal Output 0-5 VDC, 0-10 VDC, 4 to 20 mAMaximum Output Impedance mA 800ΩMinimum Output Impedance VDC 50,000ΩAccuracy ±1% of FS; Optional 0 .4% FS and

0 .25% FS

Thermal Effect Zero/Span Shift %FS: ±0 .033 °F (±0 .06 °C )

Overpressure Up to 10 PSI (Range Dependent)Measurement Range -50" WC to 100" WCResponse Time 20-30 msOperating Temperature 0° to 150°F (-18° to 65°C)Media Compatibility Dry Air or inert non-conductive gasesStability Long-Term Stability 0 .5% FS/YRApprovals RoHSWeight 0 .19 lbs (0 .09 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTERM265 SERIES

DESCRIPTIONThe Setra Model 265 differential pressure transducer provides superior positive and negative pressure sensing required for high efficiency, air-control systems . The Model 265 is a ±1 .0% Full Scale accuracy unit (±0 .4%, ±0 .25% FS optional) with an available snap-on conduit enclosure molded from high impact Lexan® .

FEATURES• 1% accuracy improves variable air volume system

performance• Optional accuracies as high as 0.25% FS• 24 VDC or 24 VAC excitation• High level 0-5 VDC , 0-10 VDC or 2-Wire• 4-20 mA analog outputs are compatible with energy

management systems• Fully protected against reverse wiring

Current Circuit Diagram Voltage Circuit Diagram

+EXC Connected to positive terminal of DC/AC power supply

-COM Connect as the reference for power supply and output signal

OUT Connected to positive terminal of control or pressure

2659 to 30 VDC

CurrentMonitoring

Device

Model 265

+EXC

-COM

OUT

Readout or

DAS

PowerSupply

WIRING

SPECIFICATIONS

M265 Series

Page 11: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1017

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

DIFFERENTIAL PRESSURE TRANSMITTERM265 SERIES

ORDERING INFORMATION

2651 2R5WD 11 T1 C Example: 2651-2R5WD-11-T1-C 265 transducer 0to 2.5" W.C. range, 4-20 mA output, terminal strip electrical connection, and ± 1% accuracy

PRESSURE RANGE "W.C.

R25WD 0 to 0.25 0R1WD ± 0.100R5WD 0 to 0.50 R25WB ± 0.25001WD 0 to 1.0 0R5WB ± 0.502R5WD 0 to 2.5 001WB ± 1.0005WD 0 to 5.0 2R5WB ± 2.5010WD 0 to 10 005WB ± 5.0025WD 0 to 25 010WB ± 10050WD 0 to 50 025WB ± 25100WD 0 to 100 050WB ± 50

MODEL DESCRIPTION 2651 Very low differential pressure transducer

E ± 0.4% FS with calibration certificate

F ± 0.25% FS with calibration certificate

G ± 1% FS with calibration certificate

Differential Bidirectional

EXCITATION / OUTPUT11 24 VDC/ 4-20 mA2B 24 VDC/ 0-5 VDCAB 24 VAC/ 0-5 VDCAC 24 VAC/ 0-10 VDC

ELECTRICAL TERMINATION T1 Terminal strip

ACCURACY C ± 1% FS without calibration certificate

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901SD-01 Surge dampener 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-308-K Duct static pressure fitting, 1/4" barb 1113DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

Page 12: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1018

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage Current Output 12-30 VDC Voltage Output 24 VAC/VDCSignal Output 4-20 mA (two wire) , 0-5 VDC (three-wire), 0-10 VDC (three-wire)Maximum Output Impedance 800Ω @ 30 VDCMinimum Output Impedance 10,000ΩAccuracy ±1 .0% FS at constant temperatureNon-linearity ±0 .96% FSNon-repeatability 0 .05% FSHysteresis 0 .1% FSCompensated Temperature Range 32° to 122°F (0° to 50°C)

Thermal Effect Zero/Span shift 0 .02% FS/°F (0 .036% FS/°C)

Overpressure 10 psig (69 kPa)Operating Temperature 32° to 122°F (0° to 50°C)Storage Temperature 23° to 131°F (-5° to 55°C)Enclosure UL 94V-0 flame resistant enclosure

plenum rated, glass filled polyesterProcess Connection 3/16" OD barbed brassApprovals Meets CE standardsWeight 0 .5 lb (0 .2 kg)Warranty 1 year

MULTIRANGE DIFFERENTIAL PRESSURE TRANSMITTER WITH DISPLAY260 SERIES

DESCRIPTIONThe Setra 260 Series Multirange Differential Pressure Transmitter with Display incorporates many powerful, attractive and easy to use features as standard in a multi-configurable package . One model with very low selectable differential pressure ranges is perfect for measuring space static pressure and duct airflow velocity pressure . A second model with higher selectable ranges is used for sensing duct static pressure . Two similar models, with Pascal engineering units instead of inches of water, are also available . The 260 Series comes standard with a wide variety of selectable output signals, 1-5 VDC, 0-5 VDC, 0-10 VDC or 4-20 mA, making it compatible with virtually any building automation controller .

FEATURES• Optional LCD on all models• Switches and jumpers for configuration• Selectable analog output• Designed for AC/DC unregulated power supplies• Display feedback of configuration selection• LCD flashes when out of range• Push button zero• Optional integral duct static probe • Models with ranges in Pascal units • Eleven-point NIST certification available

APPLICATION• Space static pressure• Duct static pressure• Duct airflow• Clean room pressure• Air lock/isolation rooms• Air filter monitoring

SPECIFICATIONS

260 Series

Page 13: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1019

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Model Unidirectional ranges Bi-directional ranges MS1 0" to 0.1" W.C. ±0.1" W.C. 0" to 0.25" W.C. ±0.25" W.C. 0" to 0.5" W.C. ±0.5" W.C. 0" to 1.0" W.C. ±1.0" W.C. MS2 0" to 1.0" W.C. ±1.0" W.C. 0" to 2.5" W.C. ±2.5" W.C. 0" to 5.0" W.C. ±5.0" W.C. 0" to 10.0" W.C. ±10.0" W.C. MS3 0 to 25 Pa ±25 Pa 0 to 50 Pa ±50 Pa 0 to 100 Pa ±100 Pa 0 to 250 Pa ±250 Pa MS4 0 to 250 Pa ±250 Pa 0 to 500 Pa ±500 Pa 0 to 1000 Pa ±1000 Pa 0 to 2500 Pa ±2500 Pa

4.75(120.7)4.25(108)

4.15(105.4)

1.50(38.1)

.59(14.9)

1.03(26.3)

.87(22)

LOW

9.20(233.7)

7.61(193.2)

Optional StaticProbe Diagram

LOW

150°

1.35(34.3)

.63(15.9)

.63(15.9)

.63(15.9)

1.3(31.83)

Ø.86(21.9)

in(mm)

Knockout for1/2" conduit

EXC

Power supply13 - 30VAC/VDC

24 VAC/DCnominal excitation

Voltagemonitor

++

+-

-+-

COM OUT

Voltage – Three-Wire, 0-5, 0-10 VDC Configuration

EXC

Power supply13 - 30VDC

24V (DC Only)nominal excitation

Currentmonitor

++ X-

-+-

COM OUT

Current – Two-Wire, 4-20 mA Configuration

WIRING

DIMENSIONS

MULTIRANGE DIFFERENTIAL PRESSURE TRANSMITTER WITH DISPLAY260 SERIES

ORDERING INFORMATION

Example: 2061MS1S Model 260 transducer 0" to 1.0" W.C.range with optional static pressure probe.MS12601 S

MODEL DESCRIPTION 260G Multirange differential pressure transmitter with display RANGES MS1 0-0.1" to 0-1.0" W.C. ranges, wall mount MS2 0-1.0" to 0-10" W.C. ranges, wall mount MS3 0-25 to 0-250 Pa ranges, wall mount MS4 0-250 to 0-2500 Pa ranges, wall mount PROBE OPTION S Static pressure probe DISPLAY OPTION D Display N No Display NIST OPTION NIST 11-point calibration certificate included

D

SELECTABLE RANGES PER MODEL

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SD-01 Surge dampener 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 14: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1020

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage Current Output 9 to 33 VDCVoltage Output 0 to 5 VDC models- 9 to 30 VAC/12

to 40 VDC, 0 to 10 VDC models- 11 to 30 VAC/13 to 40 VDC

Supply VA 0 .8 VASignal Output 4-20 mA (two-wire), 0-5 VDC (three-

wire), 0-10 VDC (three-wire)Maximum Output Impedance 800Ω @ 24 VDCMinimum Output Impedance ≥5000ΩAccuracy ±1 .0% FS at constant temperatureNon-repeatability 0 .05% FSNon-linearity ±0 .98% FS Hysteresis 0 .1% FSThermal Effect Zero/Span shift 0 .033% FS/°F

(0 .018%FS/°C), 40° to 150°F (5° to 65°C)

Overpressure Up to ±10 psig (68 .95 kPa) - range dependant

Position Effect (Unit is factory calibrated at 0g effect with diaphragm vertical)

Range (in) Zero Offset (%FS/G) 0-0 .5 0 .60 0-1 .0 0 .50 0-2 .5 0 .22 0-5 .0 0 .14Operating Humidity 35% to 95% non-condensingOperating Temperature 0° to 150°F (-18° to 65°C)Compensated Temperature Range 40° to 150°F (5° to 65°C)Enclosure Plastic glass-filled polycarbonateEnclosure Rating NEMA 4 (IP65)Process Connection 3/16" OD barbed brass, for 1/4" OD

tubingDimensions 2 .68"H x 6 .20"W x 2 .32"D

(6 .81 x 15 .25 x 5 .90 cm)Approvals CEWeight 0 .56 lb (0 .3 kg); 0 .59 lb (0 .27 kg)

with duct probeWarranty 1 year

MULTI-RANGE DIFFERENTIAL PRESSURE TRANSMITTERM267-MR

DESCRIPTIONThe Setra Model M267-MR Differential Pressure Transmitter is a multi-rangeable low air differential pressure transmitter . One Model M267-MR replaces six single-range pressure transmitters and is ideal for stocking . Each Model M267-MR is factory calibrated for its highest range but can easily be recalibrated . The rugged poly-carbonate NEMA 4 case protects the internal electronics from the environment .

FEATURES• Measure six ranges with one unit (three positive and

three bidirectional ranges) • 1% accuracy in each range • 10 psig (68.70 kPa) maximum overpressure • Rugged IP65/NEMA 4 case • Available in current or voltage outputs • Available in ranges up to 30" W.C. (7.473 kPa) • Easily reranged with dip switches

APPLICATION• HVAC building automation• Static duct pressure• Clean room pressure• Environmental pollution control• Filter monitoring

SPECIFICATIONS

M267-MR2-C

Page 15: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1021

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

High Low

1.73 (4.39)

0.80 (2.03)

1.18 (3.0)

1.29 (3.28)

7/8

0.93 (2.36)

3/16'' OD Pressure Fittingfor 1/4'' Push-on Tubing

6.20 (15.75)

5.60 (14.22)

0.18 (0.46)

0.75 (1.91)

0.50 (1.27)

in (cm)

1.34 (3.40)

2.68 (6.81)

PowerSupply

ON

1 2 3 4

EXC COM SIG

( )

( )

4-20 mA Signal

PowerSupply Voltage Signal

Current Voltage

WIRING

DIMENSIONS

MULTIRANGE DIFFERENTIAL PRESSURE TRANSMITTERM267-MR

ORDERING INFORMATION

M267 MR2 Example: M267-MR2-C Multirange differential pressure transmitterwith a 0-0.25" to 0-1.0" W.C. pressure range and a 4-20 mA output.

C

RANGECODE

PRESSURE RANGE

* MR1 is available only with 0-0.1" W.C. and ±0.05" W.C.

MR1*MR2

MR3

MR4

0-0.1 24.910-0.25 62.030-0.5 124.550-1.0 249.100-1.25 311.380-2.5 622.750-5.0 1245.500-7.5 1868.250-15 3736.500-30 7473.00

± 0.05 12.46 ±0.125 31.14 ±0.25 62.03 ±0.50 124.55 ±0.625 155.69 ±1.25 311.38 ±2.5 622.75 ±3.75 934.13 ±7.5 1868.25 ±15.0 3736.50

TABLE 1. SPECIFYING RANGE

"W.C. Pa "W.C. Pa

MODEL DESCRIPTIONM267 Multi-range differential pressure transmitter XXX RANGE CODE (see Table 1 below) C 4-20 mA output V5 0-5 VDC output V10 0-10 VDC output

Page 16: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1022

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 13 .5-30 VDCSignal Output 4-20mA (2-wire)Maximum Output Impedance 800ΩAdjustments Adjustable via an external security

keyAccuracy ±0 .5% full scaleThermal Effect Compensated temperature range:

20° to 140°F (-6 .7° to 60°C)Overpressure ±2 psig (14 kPa), positive or

negativeOperating Temperature -20° to 160°F (-29° to 71°C)Storage Temperature -40° to 185°F (-40° to 85°C)Enclosure Rating ABS plastic, fire retardant (UL94 V-0)Mounting Vertical, DIN railProcess Connection 3/16" O .D . brass barbed fittingsWiring Terminations Detachable screw terminal

connectorApprovals CEWeight 0 .56 lb (0 .3 kg)Warranty 1 year

3.9(9.9)

0.5(1.2)

0.75 (1.9)

1.3(3.2)

2.9 (7.3)

3.4 (8.6)

+-

DESCRIPTIONThe Setra 269 Series Precision Low Differential Pressure Transmitters are designed for high performance applications such as clean rooms, isolation rooms, and other critical environments . The transmitters offer full scale accuracy of ±0 .5% with excellent long term stability . Installation and calibration is easy with the removable process head, detachable terminal block and Din Rail mounting .

FEATURES

• 2 psig overpressure• 0.5% full scale accuracy• Reverse wiring protection• 4-20 mA output• Removable process head• Bidirectional ranges available

DIMENSIONS

PRECISION LOW DIFFERENTIAL PRESSURE TRANSMITTER269 SERIES

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTION 2691-001WB Differential pressure transmitter, ±1.0" W.C. 2691-001WD Differential pressure transmitter, 0-1.0" W.C. 2691-005WB Differential pressure transmitter, ±5" W.C. 2691-005WD Differential pressure transmitter, 0-5" W.C. 2691-010WD Differential pressure transmitter, 0-10" W.C. 2691-0R1WB Differential pressure transmitter, ±0.1" W.C. 2691-0R1WD Differential pressure transmitter, 0-0.1" W.C. 2691-0R5WB Differential pressure transmitter, ±0.5" W.C. 2691-0R5WD Differential pressure transmitter, 0-0.5" W.C. 2691-2R5WB Differential pressure transmitter, ±2.5" W.C. 2691-2R5WD Differential pressure transmitter, 0-2.5" W.C. 2691-R25WB Differential pressure transmitter, ±0.25" W.C. 2691-R25WD Differential pressure transmitter, 0-0.25" W.C.

ACCESSORIES269425-02 Security cal key (required for calibration)

Page 17: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1023

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

DESCRIPTIONThe Ashcroft CXLdp Series Differential Pressure Transmitters are designed for use with clean, dry, air and other clean, dry, non-corrosive gases . The CXLdp Series features a standard accuracy of 0 .80%, an optional accuracy of 0 .40%, 4-20 mA output, optional 0-10 V or 0-5 V output and a standard DIN rail mount .

FEATURES• Reliable and repeatable, stable capacitive sensor• Reverse polarity protected• High proof pressure, 15 psid• DIN rail mount• Power indication LED• Optional NIST traceable calibration

– +

+

––+

SPANZEROSPANZERO

+–

POWER SUPPLY

Zero adjustpotentiometer

Zero adjustpotentiometer

Span adjustpotentiometer

Span adjustpotentiometer

POWERSUPPLYCommon (V-) Vin (V+, Supply)

VOut

BCS

WIRING

DIFFERENTIAL PRESSURE TRANSMITTERSCXLDP SERIES

Supply Voltage 12-36 VDCSupply Current <6 mA for voltage outputSignal Output 4-20 mA, 0-10 VMaximum Output Impedance mA 545Ω @ 24 VDC

(up to 1091Ω @ 36 VDC)Accuracy 0 .8%, 0 .4% ± 0 .03% span/°FStability ±0 .5% FS/yrOperating Temperature 0° to 160°F (-18° to 71°C)Compensated Temperature Range 35° to 130°F (2° to 54°C)

Proof Pressure 15 psid (103 kPa)Burst Pressure 25 psisResponse Time 250 msMedia Compatibility Clean, dry air and non-corrosive

gasesDimensions 1 .9"W x 3 .3"H x 1 .3"D

(4 .8 x 8 .5 x 3 .3 cm)Approvals CE, RoHSWeight 0 .16 lb (0 .07 kg)Warranty 3 years

SPECIFICATIONS

CXLdp

Page 18: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1024

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

CX 7 MB2 42 P1IWL Example: CX-7-MB2-42-ST-P1IWL Differential pressure transmitter with 1.0% accuracy that measures from -0.1" to 0.1" W.C. with a 4-20 mA output

PRESSURE RANGE "W.C.P1IW 0-0.1 P1IWL ±0.1P25IW 0-0.25 P25IWL ±0.25P5IW 0-0.5 P5IWL ±0.51IW 0-1.0 1IWL ±1.02IW 0-2.0 2IWL ±2.02P5IW 0-2.5 2P5IWL ±2.53IW 0-3.0 3IWL ±3.05IW 0-5.0 5IWL ±5.010IW 0-10.0 10IWL ±10.0

XRH - NIST traceable 9 point calibration report

MODEL DESCRIPTION CX CXLdp differential pressure transmitter 4 0.4% accuracy 8 0.80% accuracy MB2 1/4" barbed stainless steel fittings F01 1/8" FNPT 42 4-20 mA signal output 10 0-10 VDC signal output

RELATED PRODUCTS PAGEDCPA-1.2 Power supply, 120 VAC In to 24 VAC/24 VDC Out 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995101A213-01 1/2" conduit/plenum kit for CXLdp transmitter

DIFFERENTIAL PRESSURE TRANSMITTERSCXLDP SERIES

Page 19: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1025

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 12-36 VDCSupply Current < 10 mA for voltageSignal Output 4-20 mA, 1-5 VDC, 1-6 VDC, 0-5 VDC, 0-10 VDCMaximum Output Impedance mA 545Ω @ 24 VDCAccuracy ±0 .25%, ±0 .5%, ±1 .0%Stability ±0 .25% FS/yrMaximum Pressure 25 psi (172 .4 kPa)Burst Pressure 25 psid (172 kPa)Proof Pressure 15 psid (103 kPa)Response Time 250 msOperating Humidity 10 to 95% RH (non-condensing)Operating Temperature -20° to 160°F (-28 .9° to 71 .1°C)Process Connection 1/8" NPTMedia Compatibility Clean, dry and non-corrosive gasEnclosure NEMA 1Dimensions 3 .9" W x 5 .0" H x 0 .9" D (9 .9 x 12 .7 x 2 .3 cm)Approvals CEWeight 0 .28 lb (0 .13 kg), NEMA 1 caseWarranty 3 years

DESCRIPTIONThe Ashcroft DXLdp Series Differential Pressure Transmitters are designed for critical, high accuracy, low pressure applications . The DXLdp Series is available in accuracies of ±0 .25%, ±0 .50% and ±1 .00% of Full Span which include non-linearity (Terminal Point Method) hysteresis, non-repeatability, zero offset, and span setting errors . It is available with voltage or milliamp outputs . The models are available in unidirectional and bidirectional ranges from 0 .10" W .C . to 50" W .C . and ±0 .05" W .C . to ±25" W .C . respectively .

FEATURES• Reliable and repeatable, stable capacitive sensor• Ultra-low pressure ranges 0 to 0.10" W.C. or ±0.05" W.C.• DIN rail mount reduces installation and calibration

costs• Easy access zero and span adjustments (optional)• 0.25% and 0.50% include NIST certificate, option on

1.00% accuracy• CE Standard with all outputs• 250ms response time• LED range status indicators

ELECTRICAL CONNECTIONS

Voltage Output Current Output

POWERSUPPLY

POWERSUPPLY

Rs

WIRING

DIFFERENTIAL PRESSURE TRANSMITTERDXLDP SERIES

SPECIFICATIONS

DXLdp Series

Page 20: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1026

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

DX 7 F01 05 ST P1IWL Example: DX-7-F01-05-ST-P1IWL Ultra-low differential pressure transmitter with 1.00% accuracy, 1/8" FNPT process connection, 0-5 VDC signal output, screw terminal electrical termination, 0.10" W.C. pressure range, no options

PRESSURE RANGE "W.C.

P1IW 0-0.10 P05IWL ±0.05P25IW 0-0.25 P1IWL ±0.10P5IW 0-0.50 P25IWL ±0.25P75IW 0-0.75 P5IWL ±0.501IW 0-1.00 P75IWL ±0.751P5IW 0-1.50 1IWL ±1.002IW 0-2.00 2IWL ±2.002P5IW 0-2.50 2P5IWL ±2.503IW 0-3.00 3IWL ±3.005IW 0-5.00 5IWL ±5.0010IW 0-10.0 10IWL ±10.00

*units include 9 point NIST traceable calibration certificate

MODEL DESCRIPTION DX DXLdp ultra-low differential pressure transmitter 3* 0.25% accuracy, ±0.02%/F° 5* 0.50% accuracy, ±0.02%/F° 7 1.00% accuracy, ±0.02%/F° F01 1/8" FNPT 05 0-5 VDC signal output 10 0-10 VDC signal output 15 0-5 VDC signal output 16 1-6 VDC signal output 42 4-20 mA signal output ST Screw terminal electrical termination

OPTIONAL X-VARIATION

XDL Optional LED

XPV Optional process valve actuator

XNL Optional text jacks

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901SD-01 Surge dampener 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-308-K Duct static pressure fitting, 1/4" barb 1113DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

DIFFERENTIAL PRESSURE TRANSMITTERDXLDP SERIES

Page 21: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1027

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 12-36 VDCSignal Output 4-20 mA, 1-5 VDCMaximum Output Impedance 545Ω @ 24 VDC (up to 1045Ω @

36 VDC)Accuracy 0 .25% or 0 .5% ±0 .015% span/°FStability ±0 .5% FS/yrOperating Temperature -20° to 160°F (-29° to 71°C)Compensated Temperature Range 35° to 135°F (2° to 57°C)Proof Pressure 10 psid (69 kPa)Burst Pressure 25 psig (172 kPa)Response Time 250 msMedia Compatibility Clean, dry air and

non-corrosive gasesDimensions 4 .6"W x 4 .2"H x 1 .9"D

(11 .7 x 10 .7 x 4 .8 cm)Enclosure 300 Series stainlessApprovals CEWeight 0 .9 lb (0 .4 kg)Warranty 3 years

DIFFERENTIAL PRESSURE TRANMITTERSXLDP SERIES

DESCRIPTIONThe Ashcroft XLdp Series Differential Pressure Transmitters are an industrial-quality, differential air pressure transmitter for use with air and other noncorrossive gases . The XLdp models are available in ranges from 0 .1" to 25" W .C . and can withstand up to 10 psid overpressure . They are highly accurate and available in accuracies of 0 .25% and 0 .50% .

FEATURES• Reliable, stable capacitive sensor• Low-range models down to ±0.05" W.C.• Positive or bidirectional ranges available• Reverse polarity protected• High proof pressure• Includes NIST certificate

1-5VDC

OUT V– V+

24 VDCPowerSupply

24 VDCPowerSupply

4-20 mA

WIRING

SPECIFICATIONS

ORDERING INFORMATION

XL 3 MB2 42 ST P1IWL Example: XL-3-MB2-42-ST-P1IWL Differential pressure transmitter with 0.25% accuracy that measures from -0.1" to 0.1" W.C. with a 4-20 mA output

PRESSURE RANGE "W.C.P1IW 0-0.1 P05IWL ±0.05P25IW 0-0.25 P1IWL ±0.1P5IW 0-0.5 P25IWL ±0.251IW 0-1.0 P5IWL ±0.52IW 0-2.0 1IWL ±1.02P5IW 0-2.5 2IWL ±2.03IW 0-3.0 2P5IWL ±2.55IW 0-5.0 3IWL ±3.010IW 0-10.0 5IWL ±5.0 10IWL ±10.0

MODEL DESCRIPTION XL XLdp differential pressure transmitter 3 0.25% accuracy 5 0.50% accuracy MB2 1/4" barbed stainless steel fittings 42 4-20 mA signal output 15 1-5 VDC signal output ST Electrical termination

XLDP Series

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 22: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1028

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 4-20 mA Models 7 to 45 VDC 0-5 VDC Models 7 to 45 VDC, 7 to 32 VAC 0-10 VDC Models 13 to 45 VDC, 13 to 32 VAC, Signal Output Two-wire, 4-20 mA or three-wire, 0-5

or 0-10 VDCStability ±0 .25% ful scale per yearMaximum Output Impedance 850Ω @ 24 VDCMinimum Output Impedance 1 kΩAccuracy ±0 .5% (on 0 to 0 .1" W .C ., 0-0 .25”

W .C ., ± 0 .1” W .C ., and ±0 .25” W .C . range models), ±0 .25 on all other range models

Thermal Effect ±2% of Span maximum (±1 .0 in WC @ 50°F to 104°F, 10 to 40°C)

Overpressure 1 psi proof pressure, 1 .5 psi burst pressure

Operating Humidity 0 to 95% RH, non-condensingOperating Temperature 32° to 140°F (0° to 60°C)Enclosure UV-resistant Polycarbonate, UL94,

V-0, IP66, NEMA 4Mounting Four external tabs with holes for #10 screwsProcess Connection 3/16" barbed fitting (use 1/8" to 3/16” ID tubing)Wiring Terminations 2 wires (4-20mA Current loop) 3 wires (AC or DC powered,

Voltage out)Approvals CE, RoHSWeight 1 .0 lb (0 .45 kg)Warranty 3 years

DIFFERENTIAL PRESSURE TRANSMITTERZPS SERIES

DESCRIPTIONThe BAPI ZPS Series Differential Pressure Transmitter is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure, room-to-room differential pressure or air flow velocities/volumes . The ZPS Series micro-machined silicon piezoresistive pressure sensor is specifically developed for low differential pressure . The sensor's custom ASIC (Application Specific Integrated Circuit) provides five-point error correction over the compensated temperature range for excellent accuracy, repeatability and stability .

FEATURES• Field-selectable ranges and output signals • Five direct and five bidirectional standard ranges • 4-20 mA, 0-5 VDC, or 0-10 VDC output signal • Inches of water or Pascal engineering units • Optional large LCD display • Microprocessor controlled auto-zero • Rugged IP66 (NEMA 4) housing • Short-circuit proof and polarity protected • Three-year warranty

DIMENSIONS

SPECIFICATIONS

ZPS Series

in(cm)

Page 23: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1029

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Powersupply +

+–

(black)

(red)

(white)X

Powersupply

ortransformer

+–

(black)

(red)

(white)

VDC Signal4-20 mA Signal

4-20 mA Wiring(See specifications for

power supply information)

0-5 VDC or 0-10 VDC Wiring(See specifications for

power supply information)

+–G

HZPS ZPS

WIRING

DIFFERENTIAL PRESSURE TRANSMITTERZPS SERIES

ORDERING INFORMATION

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SD-01 Surge dampener 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901ZPS-ACC01 2” X 4” Stainless steel wall plate with static pickup ZPS-ACC10 Rooftop or wall-mount outside air pressure pickup port ZPS-ACC12 Pitot pressure probe assy, 6” long (includes static & total probe assy)

Page 24: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1030

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 12-40 VDC; 12-35 VAC (VDC output units only)

Supply Current 10 mA max (VDC output units); 20 mA max (mA output units)

Signal Output 4-20 mA, 0-5 VDC, 0-10 VDCMaximum Output Impedance 600Ω at 24 VDC for mA output unitsMinimum Output Impedance 1K Ω for VDC output unitsAccuracy ±1% of FSEnclosure NEMA 4 (IP-65) or Panel MountMedia Compatibility Clean dry air or any inert gasThermal Effect ±0 .0125%/°F( .02%/°C)Overpressure 10 PSID

Measurement Range Uni-directional: 0 - 0 .10" W .C . to 0 - 30" W .C .; Bi-directional: ±0 .05" W .C . to ±15" W .C .

Operating Humidity 10-90% RH Non-CondensingOperating Temperature 0° to 175°F (-18° to 80°C)Dimensions 274 2 .2"H x 6 .0"W x 4 .0"D

(5 .6 x 15 .2 x 10 .2 cm) 275 2 .1"H x 5 .0"W x 2 .3"D

(5 .4 x 12 .7 x 5 .7 cm)Approvals CE, RoHSWeight Enclosure 1 .0 lb (0 .45 kg) Panel 0 .5 lb (0 .25 kg)Warranty 5 years

DIFFERENTIAL PRESSURE TRANSMITTERSPR274/275 SERIES

DESCRIPTIONThe MAMAC Systems PR274/275 Series Differential Pressure Transmitter incorporates a new micro-machined glass-on-silicon (Gl-Si) capacitance sensor . This technology revolutionizes very low pressure measurement . Temperature related zero drift, calibration shift due to overpressure, non-repeatability, non-linearity, and extremely low pressure sensitivity have been some of the problems which have plagued the controls industry . The PR274/275 Series with the new Gl-Si technology not only addresses all of the above shortcomings, but for the first time offers a reliable, accurate means to measure and control building/room pressure, air flow, duct pressure, filter pressure drop, or any other extremely low pressure application . Up to six field selectable direct or compound ranges, two enclosure types, field selectable outputs, fully temperature compensated NIST traceable accuracy, non-interacting zero and span adjustments, short circuit and reverse polarity protected output, and a liberal five year warranty are some of the features which make the PR274/275 Series the industry’s highest performance, ultra-stable, low pressure sensor .

FEATURES• 100% solid state, micro-machined, glass-on-silicon,

ultra-stable capacitance sensor• As low as ± 0.05" W.C. (± 12.5 pa)• Up to 6 field selectable ranges in one unit

SPECIFICATIONS

PR-274/275

• Can resolve less than 0.00001" W.C. (0.0025 pa)• Two rugged steel enclosure types NEMA-4 (IP-65) or panel

mount for ease of installation• Short circuit and reverse polarity protected• Conforms to EMC and RoHS standards

Page 25: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1031

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Wiring for mA Low Pressure Transducers with an External DC Power Supply

Wiring for mA Output Transducers where the Controller orMeter has Internal DC Power Supply

Wiring for VDC Low Pressure Transducers when Applied with External AC Supply

Wiring for VDC Low Pressure Transducers when Applied with External DC Power Supply

WIRING

DIFFERENTIAL PRESSURE TRANSMITTERSPR274/275 SERIES

ORDERING INFORMATION

R1 R2 R3 R4 R5 R6 R7 R8

0 to 0.10 / -0.05 to 0.05" W.C.0 to 1.0 / 0 to 0.5 / 0 to 0.25 / -0.5 to 0.5 / -0.25 to 0.25 / -0.125 to 0.125" W.C.0 to 5.0 / 0 to 2.5 / 0 to 1.25 / -2.5 to 2.5 / -1.25 to 1.25 / -0.625 to 0.625" W.C.0 to 30 / 0 to 15 / 0 to 7.5 / -15.0 to 15.0 / -7.5 to 7.5 / -3.75 to 3.75" W.C.0 to 25 / -12.5 to 12.5 Pa0 to 250 / 0 to 125 / 0 to 62.5 / -125 to 125 / -62.5 to 62.5 / -31.25 to 31.25 Pa 0 to 1250 / 0 to 625 / 0 to 312.5 / -625 to 625 / -312.5 to 312.5 / -156.25 to 156.25 Pa0 to 7500 / 0 to 3750 / 0 to 1875 / -3750 to 3750 / -1875 to 1875 / -937.5 to 937.5 Pa

Example: PR-274-R2-mA Low pressure sensor with enclosure mount, R2 range which has six (6) selectable field range options and 4-20 mA output.

PR-274 R2

MODEL DESCRIPTION PR274 Low pressure sensor with enclosure mount PR275 Low pressure sensor with panel mount

-

RANGE

OUTPUT mA 4-20 mA 2-wire VDC 0-5 VDC or 0-10 VDC field selectable

mA-

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901SD-01 Surge dampener 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-308-K Duct static pressure fitting, 1/4" barb 1113DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

Page 26: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1032

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 24 VAC or 24 VDC ±10%Signal Output 4-20 mA 2-wire, 0-10 V 3-wireMaximum Output Impedance mA maximum load 500ΩMinimum Output Impedance VDC Load R minimum 1kΩAccuracy ±1 .5% (±3% at range -0 .2/0 .2" W .C .)

of full spanCompensated Temperature Range 14° to 122°F (-10° to 50°C)Thermal Effect Included in total error band ±1,5%

+1Pa (including: general accuracy, temperature drift, linearity, hysteresis, long term stability and repetition error)

Overpressure Proof Pressure 100" W .C . (24 .9 kPa) Burst Pressure 120" W .C . (29 .9 kPa)Measurement Range up to 0 to 28" W .C . (0 to 7 .0 kPa)Operating Temperature -4° to 160°F (-20° to 71°C)Enclosure NEMA 3, Plastic (ABS)Process Connection Hose barb nozzles (ABS) for 3/16"

and 1/4" hose IDDimensions 3 .36" H x 2 .65" W x 1 .69" D (8 .53 x 6 .73 x 4 .29 cm)Approvals CEWeight 0 .3 lb (0 .14 kg)Warranty 2 years

DESCRIPTIONThe Wika A2G-50 Series differential pressure transmitter is the ideal accessory to complete a differential producer primary flow meter such as an averaging pitot tube . A DP transmitter that can be partnered with the AMP series, DPFS series and FXP series products to enable DP measurement with those devices . The unit is excellent for a room-to-room differential pressure signal to BAS . Each of the three range option code has eight selectable DP ranges within that option code . The user can select between two output signals (0 to 10 V or 4 to 20 mA) . There is an optional digital display for the measured value . The standard unit has a button for re-zeroing; but there is also an auto-zeroing option that enable the device to re-zero itself every ten minutes to prevent zero point drift .

FEATURES• Eight selectable ranges within each option code range• Selectable 0 to 10 V or 4 to 20 mA output signal• Compact size

DIFFERENTIAL PRESSURE TRANSMITTERA2G-50 SERIES

SPECIFICATIONS

A2G-50

WIRING

Page 27: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1033

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

ORDERING INFORMATION

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901A-308-K Duct static pressure fitting, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113DCPA-1.2 Power supply, 120 VAC In to 24 VAC/24 VDC Out 994691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

MODEL DESCRIPTIONA2G50-E00-7C-EO-M-Z-Z Differential pressure transmitter, 0 to 10 in WC; No digital display; No auto re-zeroA2G50-E00-7C-EP-M-Z-Z Differential pressure transmitter, 0 to 28 in WC; No digital display; No auto re-zeroA2G50-E00-7C-EQ-M-Z-Z Differential pressure transmitter, "-0.4 to +0.4 in WC; No digital display; No auto re-zeroA2G50-E00-7C-EO-M-A-z Differential pressure transmitter, 0 to 10 in WC; With digital display; No auto re-zeroA2G50-E00-7C-EP-M-A-z Differential pressure transmitter, 0 to 28 in WC; With digital display; No auto re-zeroA2G50-E00-7C-EQ-M-A-z Differential pressure transmitter, "-0.4 to +0.4 in WC; With digital display; No auto re-zeroA2G50-E00-7C-EO-M-A-1 Differential pressure transmitter, 0 to 10 in WC; With digital display; With auto re-zeroA2G50-E00-7C-EP-M-A-1 Differential pressure transmitter, 0 to 28 in WC; With digital display; With auto re-zeroA2G50-E00-7C-EQ-M-A-1 Differential pressure transmitter, "-0.4 to +0.4 in WC; With digital display; With auto re-zero

DIFFERENTIAL PRESSURE TRANSMITTERA2G-50 SERIES

DIMENSIONS

Page 28: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1034

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 11-32 VDC (protected against reversal of polarity)

Supply VA 1 VASignal Output 4-20 mAMaximum Output Impedance 700Ω @ 24 VDC (= 50 x VDC – 500)Adjustments Zero/Span adjustments: Non-interactive

adjustments by means of 20-turn potentiometers for fine resolution

Accuracy 1% of range (including non-linearity and hysteresis)

Thermal Effect Zero ±0 .05%/°C; Span ±0 .02%/°CMeasurement Range Up to 10" WC

Vibration Resistance 5G to 50 HzOperating Temperature 32° to 115°F (0° to 45°C)Storage Temperature -20° to 160°F (-30° to 70°C)Media Compatibility Air, Inert gasesEnclosure Not rated, Flame retardant, glass-

reinforced NORYLProcess Connection 3/16" diameter suitable for 1/8" or 5/32" ID

(1/4" OD) Tygon or polyurethane tubing; integral filters at both ports

Wiring Terminations 3/8" terminals, #6 screwsApprovals CEWeight 0 .42 lb (0 .19 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTERST30 SERIES

DESCRIPTIONThe Modus T30 Series Differential Pressure Transmitters are reliable, stable, low-air pressure transmitters with 4-20 mA outputs . The T30 Series is DC-powered . Higher ranges utilize piezo-resistive sensors . Ranges are available for 0" to 0 .3" W .C . to 0" to 10" W .C .

All models may be furnished in bidirectional ranges, which will measure both positive and negative pressure differentials .

FEATURES• Position insensitive• No moving parts to wear out• Compact size• Fast response time due to low internal volume• Solid-state circuitry for long life • Low power consumption• NEMA 4 enclosure and CE certification (Models M30/40)

SPECIFICATIONS

T30 Series

3.00(7.62)

Span Zero

Pressure Lo Hi

Two holes0.19 diameter (0.5)

5.15 (13.08)

4.7 (11.94)

4.25 (10.80)

1.50(3.81)- +

T30

3/8" Terminal stripwith #6 screws

3/16" OD Pressure fittings

1.48(3.76)1.13

(2.87)0.66

(1.68)0.13

(0.33)Side view T30

Power supply11-32 VDC

T30Transmitter

+–

4-20 mA Signal

DIMENSIONS / WIRING

ORDERING INFORMATION

T30 004 B

RANGE CODE

0-0.30-0.50-1.00-2.00-3.00-5.00-10.0

5" W.C.5" W.C.

20" W.C.20" W.C.20" W.C.5 psid5 psid

PRESSURE RANGE*

*Call Kele for higher pressure ranges or metric ranges

TABLE 1. RANGE

"W.C. Overpressure

Example: T30-004-B Differential pressure transmitter 4 mA @ -0.2" W.C., 12 mA @ 0" W.C., and 20 mA @ + 0.2" W.C., 24 VAC power

Note: NIST certification options available, consult Kele

003 005 010 020 030 050 100

GE MODEL

03E04E05E06E07E08E09E

MODEL DESCRIPTION T30 Differential pressure transmitter with NEMA 1 case 004 RANGE CODE (see Table 1 to the right) OPTIONS (leave blank for standard unit) B Bidirectional (12 mA @ zero pressure)

Page 29: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1035

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 12-40 VDC; 12-35 VAC (VDC output units only)

Supply Current 10 mA max (VDC output units); 20 mA max (mA output units)

Signal Output 4–20 mA 2-wire, 0–5 VDC/0–10 VDC (field selectable)

Maximum Output Impedance mA 600Ω @ 24VDC for mA output unitsMinimum Output Impedance VDC 1K Ω for VDC output unitsAccuracy ±1% of FSThermal Effect ±0 .025%/°F( .03%/°C)Media Compatibility Liquid/gases compatible to 316L

stainless steelOverpressure 300% of rated pressureBurst Pressure 500% of rated pressureMeasurement Range 0 to 100 / 0 to 50 / 0 to 25 psig, 0 to

300 / 0 to 150 / 0 to 75 psig, 0 to 500 / 0 to 250 / 0 to 125 psig, 0 to 700 / 0 to 350 / 0 to 175 kPa, 0 to 2000 / 0 to 1000 / 0 to 500 kPa, 0 to 3500 / 0 to 1750 / 0 to 875 kPa

Operating Humidity 10-90% RH Non-CondensingOperating Temperature 0° to 180°F (-18° to 82°C)Approvals CE, RoHSWeight 1 .0 lb (0 .45 kg)Warranty 5 years

PRESSURE TRANSMITTERPR264 SERIES

DESCRIPTIONThe MAMAC Systems Model PR264 Pressure Transmitter incorporates sophisticated integrated circuits and a new fused silicon monolithic cavity pressure sensor to not only provide a high-level, fully-conditioned and temperature compensated output, but also to offer up to three (3) field selectable pressure ranges in one unit . The field selectable feature eliminates costly inefficiencies by providing a single unit which can be configured to cover all the pressure ranges for a particular application . For instance, 25 .0, 50 .0, and 100 .0 psig in one unit . The stainless steel monolithic pressure cavity not only provides media compatibility for most of the applications, but also offers a leak-proof solution for today’s environment conscious customers . Two industry standard output versions are available, 4-20mA 2-wire loop or field selectable 0-5 VDC/0-10 VDC . Wide 12-40 VDC or 12-35 VAC unregulated supply voltage and a broad 0°F - 180°F compensated temperature range ensures compatibility to most of the applications . Rugged NEMA 4 (IP-65) enclosure, gasketed cover, external mounting bracket, fully temperature compensated NIST traceable accuracy and a liberal five year warranty are some of the features which make the Model PR264 the industry’s most reliable, rugged, and economical pressure sensor .

FEATURES• 100% solid state fused silicon pressure sensor• Rugged, leak-proof stainless steel monolithic

pressure cavity with no welds, o-rings, or seams/bonds

• Up to 3 field selectable ranges in one unit• Rugged NEMA-4 (IP-65) enclosure with external

mounting bracket• Short circuit and reverse polarity protected• Conforms to EMC and RoHS standards

DIMENSIONS

SPECIFICATIONS

PR264

Page 30: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1036

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

ON

ON

ON

Wiring Units with mA Output Wiring Units with VDC Output

Zero

Span

1/8"NPTFemale

Zero

Span

1/8"NPTFemale

Wiring for mA Output Pressure Transducers with an External DC Power Supply

Wiring for mA Output Transducers where the Controller orMeter has Internal DC Power Supply

Wiring for VDC Output Pressure Transducers when Applied with External AC Supply

Wiring for VDC Output Pressure Transducers when Applied with External DC Power Supply

WIRING

PRESSURE TRANSMITTERPR264 SERIES

Example: PR-264-R1-mA Pressure sensor, 0-25 / 50 / 100 psig range with 4-20 mA 2-wire output.

R1PR-264

MODEL DESCRIPTION PR264 Pressure sensor PRESSURE RANGE R1 0-25 / 50 / 100 psig R2 0-75 / 150 / 300 psig R3 0-125 / 250 / 500 psig R4 0-175 / 350 / 700 KPa R5 0-500 / 1000 / 2000 KPa R6* 0-875 / 1750 / 3500 KPa OUTPUT mA 4-20 mA 2-wire VDC 0-5 VDC or 0-10 VDC field selectable

mA

Page 31: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1037

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 12-40 VDC; 12-35 VAC (VDC output units only)

Supply Current 10 mA max (VDC output units); 20 mA max (mA output units)

Signal Output 4-20 mA, 0-5 VDC, 0-10 VDCMaximum Output Impedance 600Ω @ 24VDC for mA output unitsMinimum Output Impedance VDC 1K Ω for VDC output unitsAccuracy ±1% of FSThermal Effect ±0 .0125%/°F( .02%/°C)

Overpressure 10 PSIDMedia Compatibility Clean dry air or any inert gasMeasurement Range 0-1 .25" W .C . to 0-15 .0" W .C .Operating Humidity 10-90% RH Non-CondensingOperating Temperature 0° to 175°F (-18° to 80°C)Dimensions 2 .25"H x 5 .0"W x 2 .7"D

(5 .7 x 12 .7 x 6 .8 cm)Probe Length 8 .0" (20 .3 cm)Approvals CE, RoHSWeight 1 .0 lb (0 .45 kg) Warranty 5 years

DUCT STATIC PRESSURE TRANSMITTERPR276 SERIES

DESCRIPTIONThe MAMAC Systems Model PR276 Duct Static Pressure Transmitter incorporates sophisticated integrated circuits and a new micro-machined glass-on-silicon (Gl-Si) capacitance sensor to not only provide a high level, fully conditioned and temperature compensated output, but also to offer up to three (3) field selectable pressure ranges in one unit . The field selectable feature eliminates costly inefficiencies by providing a single unit which can be configured to cover all the pressure ranges for a particular application . For instance, 1 .25", 2 .50" and 5 .00" W .C . are in one unit . To substantially reduce installation cost and to eliminate costly control panels, the Model PR276 incorporates a pressure sensor and a static pressure tip integrated as one assembly . Two industry standard output versions are available, 4-20mA 2-wire loop or field selectable 0-5 VDC/0-10 VDC . Wide 12-40 VDC or 12-35 VAC unregulated supply voltage and a broad 25°F−150°F compensated temperature range ensures compatibility to most of the applications . Rugged NEMA 4 (lP-65) enclosure, gasketed cover, external mounting bracket, fully temperature compensated NIST traceable accuracy, and a liberal five year warranty are some of the features which make the Model PR276 not only the most reliable, but the lowest installed cost duct pressure sensor in the industry .

FEATURES• 100% solid state, micro-machined, glass-on-silicon,

ultra-stable capacitance sensor • Duct pressure transducer and static pressure tip

integrated as one unit• Up to 3 field selectable ranges in one unit

SPECIFICATIONS

PR276

• Rugged NEMA-4 (IP-65) enclosure with external mounting bracket

• Short circuit and reverse polarity protected• Conforms to EMC and RoHS standards

Page 32: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1038

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Wiring for mA Output Duct Pressure Transducers with External DC Power Supply

Wiring for mA Output Duct Pressure Transducers where Controller or Meter has Internal DC Power Supply

Wiring for VDC Output Duct Pressure Transducers when Applied with External AC Supply

Wiring for VDC Output Duct Pressure Transducers when Applied with External DC Power Supply

WIRING

DUCT STATIC PRESSURE TRANSMITTERPR276 SERIES

ORDERING INFORMATION

Example: PR-276-R10-mA Duct pressure sensor, 0 to 5.0 / 0 to 2.5 / 0 to 1.25" W.C. range with 4-20 mA 2-wire output.

R10PR-276

MODEL DESCRIPTION PR276 Duct pressure sensor PRESSURE RANGE psid (kPa) R10 0 to 5.0 / 0 to 2.5 / 0 to 1.25" W.C. R11 0 to 15 / 0 to 7.5 / 0 to 3.75" W.C. R12 0 to 1250 / 0 to 625 / 0 to 312.5 pa R13 0 to 3750 / 0 to 1875 / 0 to 937.5 pa OUTPUT mA 4-20 mA 2-wire VDC 0-5 VDC or 0-10 VDC field selectable

mA

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901SD-01 Surge dampener 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-308-K Duct static pressure fitting, 1/4" barb 1113DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

Page 33: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1039

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 11-33 VDCSignal Output Two-wire, 4-20 mAMaximum Output Impedance 800Ω at 24 VDCAccuracy < ±0 .5% FS (includes linearity,

hysteresis, and repeatability)Thermal Effect <0 .1% FS/°CMaximum Operating Pressure 0-60 psid 362 psig (2500 kPa) 100 psid and greater 725 psig (5000 kPa)Overpressure 0-60 psid 543 psi (3750 kPa) 100 psid and greater 1088 psi (7500 kPa)Response Time <5 ms

Maximum Differential: Port-to-Port 0-60 psid 174 psid 0-100 psid and Greater Hi: 464 psi, Low: 174 psiOperating Temperature 5° to 176°F (-15° to 80°C)Wetted Parts 303 stainless, FPM (Viton®) sealsEnclosure Rating NEMA 4 (IP65)Process Connection 1/8" FNPTWiring Terminations DIN 43650-A connector with terminal

blocksApprovals CE, RoHSWeight 0 .94 lb (0 .43 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTERDPW-692 SERIES

DESCRIPTIONThe Kele DPW-692 Series Differential Pressure Transmitter is ideal for monitoring pumps and piping differential pressures in HVAC systems and process systems including tank level monitoring . The DPW-692 Series incorporates proven, unique ceramic sensor technology and the stainless steel housing is compatible with a wide variety of liquid or gas media . The convenient DIN 43650-A wiring connector makes installation easy and provides NEMA 4 (IP65) environmental protection .

FEATURES• Competitively priced• Very high quality• Short-circuit proof• Protection from reverse polarity• Compact heavy duty housing• True differential pressure sensing• 1/2" NPT conduit connector• NEMA 4 (IP65) environmental rating• Mounting bracket included

SPECIFICATIONS

DPW-692-100-KIT

Note: The DPW-692 can be field calibrated ±10%; see installation instructions for this procedure . However, due tothe very small recessed calibration screws, field calibration is difficult and not recommended . Kele can providefactory custom calibration; please allow two weeks for delivery .

CAUTION: Not for use with ammonia.

Page 34: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1040

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

.59 (15)

.47 (12)

.78 (20)

1/8" NPT 5.12 (130)

.83 (21)

Lowport

Highport

1.18 (30)

3.74 (95)

1.73 (44)

Ø 1.57 (40)

Bracket

1/2"NPT

Wiring/conduit

connector

.20Ø(5)

+

– +

2

3

1

24 VDCPowersupply

DIN Connectorterminal block

with screwterminals

4–20 mA

Flatheadscrewdriver

2

1

WIRINGDIMENSIONS

DIFFERENTIAL PRESSURE TRANSMITTERDPW-692 SERIES

ORDERING INFORMATION

RELATED PRODUCTS PAGEG5100-1101000 DIN 43650-A replacement conduit connector with gasketDCPA-1.2 Power supply, 120 VAC In to 24 VAC/24 VDC Out 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995101999 DPW-692 Series replacement mounting bracket with screws

MODEL DESCRIPTIONDPW-692-25-KIT 0–25 psid, 4–20 mA, 1/8" FNPT with bracket and conduit connectorDPW-692-35-KIT 0–35 psid, 4–20 mA, 1/8" FNPT with bracket and conduit connectorDPW-692-60-KIT 0–60 psid, 4–20 mA, 1/8" FNPT with bracket and conduit connectorDPW-692-100-KIT 0–100 psid, 4–20 mA, 1/8" FNPT with bracket and conduit connectorDPW-692-200-KIT 0–200 psid, 4–20 mA, 1/8" FNPT with bracket and conduit connector

To order a DPW-692 pre-assembled in a five-valve bypass enclosure, replace -KIT with -BVA suffix .To order a DPW-692 pre-assembled with a three-valve manifold, replace -KIT with -3VLV suffix .To order a DPW-692 with factory custom range, add -C suffix to complete model number .To order a DPW-692 for use with refrigerants, add -R suffix after -KIT . A neoprene seal is used inplace of Viton® . Not applicable with -BVA or -3VLV assemblies .

Page 35: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1041

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage Current models Minimum 9 VDC + (0 .02 x circuit

resistance) Maximum 30 VDC + (0 .004 x circuit resistance)

Voltage Models 0-5 VDC 9-30 VDC 0-10 VDC 13-30 VDC, Signal Output 4-20 mA, 0-10 VDC, 0-5 VDCMaximum Output Impedance 100Ω @ 24 VDCMinimum Output Impedance ≥5000ΩAccuracy ±0 .25% FSNon-repeatability 0 .05% FSNon-linearity ±0 .20% FSHysteresis 0 .10% FSCompensated Temperature Range 30° to 150°F (-1° to 65°C)Thermal Effect Zero/span shift 2 .0% FS/100°F (1 .8% FS/50°C)Maximum Operating Pressure 250 psig (1723 .8 kPa) model

dependantOperating Temperature 0° to 175°F (-18° to 79°C)

Storage Temperature -65° to 250°F (-54° to 121°C)Wetted Parts 17-4 PH stainless, 300 Series

stainless steel, viton, silicon ringsEnclosure Rating NEMA 4 (IP65)Process Connection 1/4-18 FNPTApprovals CEWeight 0 .9 lb (0 .41 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTERM230 SERIES

DESCRIPTIONThe Setra Model M230 Differential Pressure Transmitter is a highly accurate differential pressure transmitter that incorporates a capacitive technology to produce a linear electronic signal proportional to the differential pressure . It will measure differential pressure in unidirectional applications as much as 100 psi and bidirectional applications as much as 50 psi . The stainless steel wetted parts and elastomer seals make this unit ideal for both liquids and gases . The NEMA 4 (IP65) case keeps the internal electronics protected from the environment .

FEATURES• 0.25% accuracy• NEMA 4 (IP65) protection• Stainless steel wetted parts• Elastomer seals• High proof pressure• Current or voltage outputs• Mounting bracket included

SPECIFICATIONS

PROOF PRESSURE (High Side) Range Proof Range Proof psid kPa psid kPa psid kPa psid kPa 0-1 6.89 20 137.9 ±0.5 ±3.45 20 137.9 0-2 13.79 40 275.8 ±1 ±6.89 40 275.8 0-5 34.47 100 689.5 ±2.5 ±17.24 100 689.5 0-10 68.95 100 689.5 ±5 ±34.47 100 689.5 0-25 172.4 250 1723.7 ±10 ±68.95 200 1379.2 0-50 344.7 250 1723.7 ±25 ±172.4 250 1723.7 0-100 689.5 250 1723.7 ±50 ±344.7 250 1723.7

M230-025PD-C

Page 36: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1042

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

3.01(7.65)

in(cm)

2.15(5.46)

Bleedscrews

2.44(6.20)

3.05(7.75)

1/4-18 NPTHigh pressureport

1.94(4.93)

1.00(2.54)

1.50(3.81)

1/4-18 NPTLow pressureport

2.00(5.08)

0.875 (2.2)Opening for1/2" conduit

1.00(2.54)

Span Zero

Conduit opening

(*red) (*brown)

(*red) (*brown)

(*yellow)

Current

Voltage

EXC OUT COM

Voltagesignal

EXC OUT COM

Powersupply

4-20 mA signal

* Wire colors when mounted in a BVA

* Wire colors when mounted in a BVA

+

+

+

+

+

Powersupply

+

WIRINGDIMENSIONS

DIFFERENTIAL PRESSURE TRANSMITTERM230 SERIES

ORDERING INFORMATION

OUTPUT C 4-20 mA V5 0-5 VDC V10 0-10 VDC OPTIONS BVA Bypass valve assembly 3VLV Three-valve manifold assembly

M230 010PD C

001PD 002PD 005PD 010PD 025PD 050PD 100PD 0R5PB 001PB 2R5PB 005PB 010PB 025PB 050PB

0-1.0 (6.90)0-2.0 (13.79)0-5.0 (34.48)0-10.0 (68.95)0-25.0 (172.38)0-50.0 (344.75)0-100.0 (689.50)±0.5 (±3.45)±1.0 (±6.90)±2.5 (±17.24)±5.0 (±34.48)±10.0 (±68.95)±25.0 (±172.38)±50.0 (±344.75)

M230-10PD-C Differential pressure transmitter ranging from 0-10 psid with a 4-20 mA output

Example:

MODEL DESCRIPTIONM230 Differential pressure transmitter PRESSURE RANGE psid (kPa)

Page 37: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1043

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage Current Model 12-30 VDC Voltage Model 12-30 VDC/18-28 VACSignal Output Current Model 2-wire, 4-20 mA Voltage Model 3-wire, 0-5, 0-10, or 1-5 VDCMaximum Output Impedance mA 600Ω @ 24 VDCMinimum Output Impedance VDC 5000 ΩAccuracy ±1 .0% FS

(±2 .0% FS for range D model )Overpressure 2 .2X full scaleBurst Pressure 15 X full scale (50 psi) 10 x full scale (75 x 150 psi) 8 x full scale (250 psi)Response Time 1-5 seconds (adjustable)Operating Temperature -4° to 185°F (-20° to 85°C)

Wetted Parts 17-4 PH Stainless SteelEnclosure Rating NEMA 4Process Connection 1/8" FNPTWiring Terminations 1/2" conduit entry (7/8" dia), screw/

crimp terminalsDimensions 4 .0"H x 6 .0"W x 2 .0"D

(10 .2 x 15 .2 x 5 .1 cm)Temperature Range 32° to 130°F (0° to 54°C)Enclosure Die Cast Aluminum, Powder CoatedMedia Compatibility Liquids or Gases Compatible with

17-4 PH Stainless Steel Note Hydrogen not recommended for use

with 17-4 PH stainless steel .Approvals CE, RoHS compliantWeight 1 .5 lbs (0 .68 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTER231 SERIES

4.0(10.2)

4.9(12.3)

5.1(12.9)

2.0(5.1)

5.2(13.1)

1.0 (2.4)

1.6(4.0)

High Low

1/2'' Conduitopening

2.0(5.1)

5.6(14.1)

6.0(15.2)

1.2(3.1) 1.7

(4.2)

0.4(0.9)

R0.1(0.3)

1/8''FNPT

DESCRIPTIONThe Setra 231 Series Multi-Range Differential Pressure Transmitter is ideal for monitoring pumps and load differential pressures in HVAC systems and processes where local indication is needed . The 231 Series design provides users with field accessible ranging, choice of outputs, and field zero adjustment .

FEATURES

• Field selectable ranges and outputs• Field accessible pushbutton zero and remote zero• Field selectable port swap• True 4-20 mA output, and choice of VDC outputs• Hinged cover• Heavy duty aluminum NEMA 4 housing• Optional LCD display• RoHS compliant

DIMENSIONS

SPECIFICATIONS

231 Series

Page 38: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1044

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

A B C DMS1 50 25 10 5MS2 100 50 20 10MS3 250 125 50 25

A B C D

RANGES

ZERO

OUTPUT

A B C D4-20 0-5 0-10 1-5

A B C DBARA.REVSLOWBI-DIRSWAP

PSINORMFASTUNI-DIRNORM

+ -

Power supply12-24 VDC onlydigital control

Current(4-20 mA)

+

Remote zerodigital output

+ –

Contact closure relay

+

2 wire current output

WIRING

DIFFERENTIAL PRESSURE TRANSMITTER231 SERIES

ORDERING INFORMATION

Example: 231G-MS1-2F-D-3VLV Setra differential pressure transmitter Model 231 ranging from 0 to 50 psid with LCD display and 3VLV bypass option.

Wet to wet differential pressure transmitter RANGES: UNIDIRECTIONAL AND BIDIRECTIONAL* MS1 5, 10, 25, 50 psid and ±5, ±10, ±25, ±50 psid MS2 10, 20, 50, 100 psid and ±10, ±20, ±50, ±100 psid MS3 25, 50, 125, 250 psid and ±25, ±50, ±125, ±250 psid PRESSURE CONNECTION 2F 1/8-18 NPT female (Standard) DISPLAY OPTION N No display D LCD display MANIFOLD OPTION 3VLV 3 valve bypass option

231G - MS1 - 2F - D - 3VLV

MODEL DESCRIPTION 231G

* Line Pressure determines selection of range code.

Remote zerodigital output

A B C DMS1 50 25 10 5MS2 100 50 20 10MS3 250 125 50 25

RANGES OUTPUT

A B C D4-20 0-5 0-10 1-5

Power supply12-24 VAC/VDC

Digital controlvoltage

+

+

+

A B C D ZERO A B C DBARA.REVSLOWBI-DIRSWAP

PSINORMFASTUNI-DIRNORM

+ -

+ –

+

Contact closure relay

3 wire voltage output

RELATED PRODUCTS PAGE47B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112PT 1/4" pigtail syphon with fittings 1112

Page 39: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1045

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

DC/ACPower Supply

ControllerVoltage

+

+

Relay

.

+EXC

.

COM

+OUT

+EXC

.

COM

+OUT

HI LO

Supply Voltage 15-30 VDC Supply Current 40 mA (typical) at 18-30 VACWarm Up Time <0 .12% FSSignal Output 4-20 mA, 0 to 5 VDC, 0 to 10 VDC, 1

to 5 VDCMaximum Output Impendence (Current) 250ΩAccuracy Pressure Ranges A, B, C ±1 .0% FS

Pressure Range D ±2 .0% FSThermal Effect Compensated 32° to 130°F (0° to 54°C) Zero Shift %FS/100°F (50°C) 2 .0 (1 .8) Span Shift %FS/100°F(50°C) 2 .0 (1 .8)Media Compatibility Liquids or Gases Compatible with

17-4 PH Stainless Steel Note: Hydrogen not recommended for use with 17-4 PH stainless steel

Maximum Operating Pressure Equal to top of maximum range

specified in orderOverpressure 2X full scaleBurst Pressure 15 x Full Scale (50 psi) 10 X Full Scale (75 x 150 psi) 8 x Full Scale (250 psi)Response Time 1-5 seconds (adjustable)Compensated Temperature Range 32° to 130°F (0° to 54°C)Operating Temperature -4° to 185°F (-20° to 85°C)Wetted Parts 17-4 PH Stainless SteelEnclosure Die Cast Aluminum, Powder CoatedEnclosure Rating NEMA 4Process Connection 1/4-18 NPT MaleWiring Terminations 1/2" conduit entry (7/8" dia), screw/

crimp terminalsDimensions 4 .0"H x 6 .0"W x 2 .0"D (10 .2 x 15 .2 x 5 .1 cm)Approvals CE, RoHS compliantWeight 1 .5 lbs (0 .68 kg) - case onlyWarranty 1 year

REMOTE MOUNTED DIFFERENTIAL PRESSURE TRANSMITTER231RS SERIES

DESCRIPTIONThe Setra 231RS Series Multi-Range Differential Pressure Transmitter is ideal for monitoring pumps and load differential pressures in HVAC systems and processes where local indication is needed .

Setra's 231RS Series with remote sensors reduces labor, materials, and time . The sensors are installed directly into the pipe and electrical connection is made between the remote sensors and the Model 231RS via cables or conduit . This reduces labor cost by one-third and the cost of copper to connect the pressure transducer to the pipe . Startup time is reduced since purging air out of the lines is not necessary .

The Multi-Sense® Model 231 wet-to-wet differential pressure transducer's all inclusive design provides users with field accessible ranging, choice of output and field zeroing .

FEATURES• Remote sensors• Conduit and cable versions• Field selectable output - 4 to 20 mA, 0 to 5, 1 to 5, and 0

to 10 VDC• Field accessible push-button zero and remote zero• Jumper selectable port swap• Optional LCD display• All cast aluminum, NEMA4 rated housing

APPLICATION• Energy management systems• Process control systems• Flow measurement of various gases or liquids• Liquid level measurement of pressurized vessels

SPECIFICATIONS

WIRING

Model 231RS

Page 40: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1046

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Pressure range selection: 1 . Examine the pressure application and determine the highest system line pressure . 2 . Determine the differential pressure being measured . 3 . Find the maximum line pressure in the table on the right that is higher than your highest system line pressure .4 . Verify that your DP falls within the selectable ranges in that row .5 . Follow that row to the left and select that range code .

Example: Highest System Line Pressure: 125 psigDifferential Pressure Measured: 75 psid"Max Line Pressure" Higher than System Line Pressure: 150 psid (75 psid DP falls within ranges in this row)Select Range Code: RS4

REMOTE MOUNTED DIFFERENTIAL PRESSURE TRANSMITTER231RS SERIES

ORDERING INFORMATION

OPERATION

DIMENSIONS

INMM

5.56141.2

6.00152.4

0.358.8

R 0.12.5

2.0050.8

1.2230.9

1.5639.6 0.95

24.11.2431.5

5.16131.1

1.9850.3

4.00102.0

Conduit Version

2 x0.8621.9

Side View Front View

Bottom View

Cable Version

0.951.5639.6

5.16131.1

INMM

Side View

4.0102

4.87123.6

5.08129.0

1.9850.3

6.0152.4

0.358.8

R 0.12.5

1.2231.0

1.6642.2

2.050.8

5.56141.2

Front View

Bottom View

*

Note: Line pressure determines selection of range code.

Page 41: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1047

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

+ -

Terminal box

Display (board)

Shield

Power source

+ - Receiver

Transmission cable +

Supply Voltage 12-32 VDCSignal Output 4-20 mA (2-wire)Maximum Output Impedance 500ΩAdjustments Zero and Span Adjustable -10% to

110% FSAccuracy ±0 .5% FS (includes linearity,

hysteresis, and repeatability)Thermal Effect Zero/Span Shift ±0 .03% FS/°C @ 73°F (23°C)Compensated Temperature Range 14° to 140°F (10° to 60°C)Overpressure Ranges 4IW, 8IW, 4IWL 30 psid (207 kPa) All Others 100 psid (690 kPa),

Display 4 digit, 10 mm LCD; ±0 .5% FS + last digit accuracy

Wetted Parts 316 SS, viton, and Alumina CeramicOperating Temperature 14° to 140°F (-10° to 60°C)Storage Temperature 5° to 150°F (-15° to 65°C)Enclosure Rating Epoxy coated aluminum, NEMA 4X

(IP65)Process Connection 1/4 FNPTWiring Terminations Screw terminalsApprovals CE, EN613261 1997, A1/1998,

A2/2001Weight 1 lb (0 .7 kg)Warranty 1 year

WET/WET DIFFERENTIAL PRESSURE TRANSMITTERGC52 SERIES

DESCRIPTIONThe Ashcroft GC52 Series Low Differential Pressure Transmitter offers reliable, low differential pressure measurement with an accuracy of 0 .5% . The transmitter is loop powered with an integral LCD display . The GC52 features zero and span adjustment, linear scaling function, digital filter function, and push button configuration . The rugged NEMA 4X enclosure allows usage in indoor or outdoor environments .

FEATURES• 0.5% accuracy• Push button configuration• Linear scaling function• LED back light• Loop check function• 4-20 mA output• NEMA 4X (IP65) protection• Scaling function• Flow measurement and totalization (square root

extraction)

WIRING

SPECIFICATIONS

Page 42: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1048

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

4 x Ø .22 (56)Panel mounting holes Bracket 0.08 (0.03) thick

0.42 (1.1)

Drain outlet

inH2OGC52

4.72(12)

5.12(13)

0.69(1.8)

1.97 (5)2.36 (6)

4.49 (11.4)

3.62 (9.2)

2.91 (7.4)

2.28 (5.8)

Ø 2.56(6.5)

2.07(5.3)

in (cm)

DIMENSIONS

WET/WET DIFFERENTIAL PRESSURE TRANSMITTERGC52 SERIES

ORDERING INFORMATION

GC52 40IW

4IW8IW20IW40IW80IW200IW400IW4IWL8IWL20IWL40IWL80IWL200IWL400IWL

0-4.0 (1.0)0-8.0 (2.0)0-20.0 (4.98)0-40.0 (9.95)0-80.0 (19.9)0-200.0 (49.7)0-400.0 (99.5)±4.0 (±1.0)±8.0 (±2.0)±20.0 (±4.98)±40.0 (±9.95)±80.0 (±19.9)±100.0 (±49.7)±400.0 (±99.5)

GC52-40IW Low differential pressuretransmitter ranging from 0-40"w.c.

Example:

MODEL DESCRIPTIONGC52 Low differential pressure transmitter PRESSURE RANGE "W.C. (kPa)

Page 43: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1049

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Differential Pressure Tranducer with mA Output

Supply Voltage 12-40 VDC; 12-35 VAC (VDC output units only)

Supply Current 10 mA max (VDC output units); 20 mA max (mA output units)

Signal Output 0-5 VDC, 0-10 VDC, 4-20 mAMaximum Output Impedance mA 600Ω @ 24VDC for mA unitsMinimum Output Impedance VDC 1K Ω for VDC output unitsAccuracy ±1% of FSThermal Effect ±0 .025%/°F( .03%/°C)Media Compatibility Liquid/gases compatible to 316L

stainless steel

Overpressure 300% of rated pressureBurst Pressure 500% of rated pressureMeasurement Range 0-20 psid, 0-30 psid, 0-50 psid,

0-100 psid, 0-200 psid, 0-300 psid Operating Humidity 10-90% RH Non-CondensingOperating Temperature 0° to 180°F (-18° to 82°C)Dimensions 3 .5"H x 5 .0"W x 2 .0"D

(8 .9 x 12 .7 x 5 .1 cm)Approvals CE, RoHSWeight 1 .7 lb (0 .75 kg) Warranty 5 years

WET TO WET DIFFERENTIAL PRESSURE TRANSMITTERPR282 SERIES

DESCRIPTIONThe MAMAC Systems Model PR282 Wet to Wet Differential Pressure Transmitter incorporates sophisticated integrated circuits and new fused silicon monolithic cavity pressure sensors to not only provide a high level, fully conditioned and temperature compensated output, but also to offer up to six (6) pressure ranges . The stainless steel monolithic pressure cavity not only provides media compatibility for most of the applications, but also offers a leakproof solution for today’s environmentally conscious customers . Three industry standard output versions are available: 4-20 mA 2-wire loop or 0-5 VDC/0-10 VDC . A wide 12-40 VDC or 12-35 VAC unregulated supply voltage and a broad 0°F−180°F compensated temperature range ensures compatibility to most of the applications . A rugged NEMA-1 (IP-30) enclosure, fully temperature compensated NIST traceable accuracy and a liberal five year warranty are some of the features which make the Model PR282 the industry’s most reliable, rugged, and economical pressure sensor .

FEATURES

• 100% solid state fused silicon pressure sensor• Rugged, leak-proof stainless steel monolithic

pressure cavity with no welds, o-rings, or seams/bonds

SPECIFICATIONS

PR282 Series

WIRING

Differential Pressure Transducer with VDC Output

• NIST traceable calibration• Rugged NEMA-1 (IP-30) enclosure• Short circuit and reverse polarity protected• Conforms to EMC and RoHS standards

Page 44: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1050

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Wiring for VDC Differential Pressure Transducers when applied with External DC Power Supply

Wiring for VDC Differential Pressure Transducers when applied withExternal DC Supply

VDC Output Transducer Only 12-35 VAC Transformer

Controller / Meter / Recorder

+ Input Signal- Common

Shield/Ground

VDC Output Transducer Only 12-40 VDC Power Supply

Controller / Meter / Recorder

+ Input Signal- Common

Shield/Ground

WIRING

WET TO WET DIFFERENTIAL PRESSURE TRANSMITTERPR282 SERIES

ORDERING INFORMATION

MODEL DESCRIPTION PR282 Differential pressure sensor OUTPUT 2 0-5 VDC 3 0-10 VDC 4* 4-20 mA PRESSURE RANGE psid (kPa) 1 0-20 (137.9) 2 0-30 (206.8) 3 0-50 (344.7) 4 0-100 (689.5) 5 0-200 (1379.0) 6 0-300 (2068.4) SUPPLY VOLTAGE A12B 24 VDC B12B 24 VAC

Example: PR-282-3-2-A12B Differential pressure sensor, 0-10 VDC output, 0-30 psid range, with 24 VDC supply voltage.

3PR-282 2 A12B

* Only available in VDC supply voltage.

RELATED PRODUCTS PAGEDCPA-1.2 Power supply, 120 VAC In to 24 VAC/24 VDC Out 994691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

Wiring for mA Differential Pressure Transducers with External DC Power Supply Wiring for mA Differential Pressure Transducers where the Controller or Meter has an Internal DC Power Supply

mA Output Transducer Only 12-40 VCD Power Supply

Controller / Meter / Recorder

mA Output Transducer Only Controller / Meter / Recorder

+ Input Signal- Common

Shield/Ground

+ Input Signal- Common

Shield/Ground

Page 45: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1051

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 11-32 VDC, 25 mA maximumSignal Output 4-20 mAMaximum Output Impedance 600Ω @ 24 VDCAccuracy ±0 .5% of differential pressure

range, including non-linearity and hysteresis, or ±1 .0% for 0-6 psid (0-41 .4 kPa) range

Thermal Effect Zero: ±0 .05% per °C Span: ±0 .03% per °C Zero: ±0 .05% per °C Span: ±0 .03% per °COverpressure 0 to 30 psid 100 psi (690 kPa) 60 to 200 psid 300 psi (2069 kPa)

Effect of Static Pressure Less than 0 .25% for static pressure

change from 0-100%Operating Humidity 10% to 90% RH non-condensingOperating Temperature 32° to 122°F (0° to 50°C)Wetted Parts 316 Stainless SteelDimensions 3 .56" x 4 .54" x 2 .18" (9 .01 x 11 .53 x 5 .54 cm)Enclosure NEMA 3Process Connection 1/8" FNPTWiring Terminations 14-26 AWG pluggable terminal blockApprovals CEWeight 1 .2 lb (0 .54 kg)Warranty 1 year

DIFFERENTIAL PRESSURE TRANSMITTERW30 SERIES

2.36 (6.0)

0.60(1.52)

0.26(0.65)

2 Mounting holes for#8 (4 mm) max screw

Bottom ViewFront View

4.02 (10.2)Mounting holes

4.54(11.53)

3.56(9.04)

2.18(5.5) 1.37

(3.48)

1.35(3.43)

4.92(12.50)

1/2'' Conduit connection1/8-28 Female NPT

2 Ports

Mountingholes

in(cm)

High

Low

DESCRIPTIONThe Modus W30 Series Differential Pressure Transmitters measure differential pressure in liquids and gases compatible with 316 stainless steel . They are an excellent choice for HVAC and process applications, including measurement of differential pressure across flow elements, heat exchangers, pumps, filters, coils, and liquid level monitoring .

W30 Series transmitters are housed in a compact, heavy-duty cast aluminum case designed to NEMA 4 (IP65) standards . The rugged design allows it to withstand high overpressure without damaging the unit or affecting calibration . It is ±0 .5% accurate and available in eight ranges up to 200 psi differential . The W30 Series is a 4-20 mA two-wire loop-powered device that operates on nominal 24 VDC .

FEATURES• 316 stainless steel wetted parts• 4-20 mA two-wire output• Operates on nominal 24 VDC• NEMA 4 cast aluminum enclosure• Accuracy of ±0.5%• Ranges to 200 psig (1379 kPa) differential

DIMENSIONS

SPECIFICATIONS

W30

Page 46: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1052

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

The W30 Series transmitter should be mounted on a stable surface, free of vibration and pipe strain . A Model PT steam syphon is recommended to protect the transmitter on steam applications . Another device that might be required is the Model 47 pressure snubber to protect the transmitter from pressure pulses .

4-20 mASignal

24 VDCPower supply

+ -

+

-+

-

Enclosureground

N/C

W30

WIRING

INSTALLATION

DIFFERENTIAL PRESSURE TRANSMITTERW30 SERIES

ORDERING INFORMATION

Example: W30-36E Stainless steel liquid differential pressure transmitter with a range of 0-100 psig (689.5 kPa)

* The maximum safe momentary over

pressure at any port is two times the

maximum operating static pressure.

RANGE

RANGE (call Kele for metric ranges)

MANIFOLD OPTION

W30

3VLV Three-valve manifold assemblyBVA Bypass valve assembly

DIFFERENTIALPRESSURE RANGE

psid (kPa)

MAXIMUM OPERATINGSTATIC PRESSURE*

psig (kPa)

31E32E33E34E35E36E37E38E

610153060100150200

(41.4)(69.0)(103.4)(206.8)(413.6)(689.5)(1034)(1379)

100(690)

300(2069)

Liquid differential pressure transmitterMODEL DESCRIPTION

W30 36E

1500

1000

500

00 10 20 30 40 VDC

Power Supply Voltage

OPERATING REGION

MAXIMUM R

ESISTANCE

Lo

op

Res

ista

nce

(O

hm

s)*

*Loop resistance = Wire resistance + Receiver resistance

RELATED PRODUCTS PAGE47B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112PT 1/4" pigtail syphon with fittings 1112

Page 47: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1053

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

ORDERING INFORMATION

Maximum Pressure 150 psi (1035 kPa)Additional Specifications 150°F (66°C)Dimensions BVA-5-W30, DPW 18"H x 10"W x 4"D (45 .7 x 25 .4 x 10 .2 cm) All Others 12"H x 10"W x 4"D (30 .5 x 25 .4 x 10 .2 cm)Weight BVA-5-W30, DPW 15 .5 lbs (7 .0 kg) All Others 10 .5 lbs (4 .8 kg)Warranty 1 year

BYPASS VALVE ASSEMBLYBVA-5

DESCRIPTIONDifferential pressure transmitters are often installed in systems with pressures much higher than the differential pressure being monitored . During installation, start-up, or shutdown, the pressure differential may exceed the transmitter differential pressure rating, resulting in severe damage to the transmitter . A Kele Model BVA-5 Bypass Valve Assembly will minimize this possibility . When it is purchased with a transmitter, the transmitter is assembled in a NEMA 1 or NEMA 3R enclosure with two isolation valves, an equalizing valve, and two vent valves mounted and piped . Optional pressure snubbers are also available mounted on the Model BVA-5 .The Model BVA-5 is designed for use on systems with maximum pressures less than 150 psig (1034 .3 kPa) at 150 Deg . F (65 Deg . C) .

To Place Transmitter in Service:1 . Open V-3 .2 . Open V-4 and V-5 .3 . Slowly open V-1 and V-2 to bleed the lines of air .4 . Close V-4 and V-5 .5 . Open V-1 and V-2 fully .6 . Close V-3 to read differential pressure .

To Take Transmitter Out of Service:1 . Open V-3 . This will equalize the pressure at the transmitter .2 . Close V-1 and V-2 .3 . Open V-4 and V-5 to release pressure .

OPERATION

NEMA 1enclosure

Transmitter

BVA-5 piping

Vent Vent

1/8" FNPT low pressure port

1/8" FNPT highpressure port

V-5V-4

V-3

V-2V-1

DIMENSIONSSPECIFICATIONS

BVA-5

CAUTION: A BVA-5 bypass valve assembly is for use on systems with a maximum pressure of 150 psig (1034.3 kPa) at 150

MODEL DESCRIPTIONBVA-5-DPW 5 VALVE BYPASS FOR KELE DPWBVA-5-PW2 5 VALVE BYPASS FOR PW2BVA-5-R 5 VALVE BYPASS FOR 360CBVA-5-SET 5 VALVE BYPASS FOR SETRABVA-SRS 5 VALVE BYPASS FOR SRSBVA-5-VER 5 VALVE BYPASS FOR VERISBVA-5-W 5 VALVE BYPASS FOR GE W30

To order NEMA 3R Enclosure add suffix -3R Example: BVA-5-DPW-3R

Page 48: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1054

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

DPTransmitter

High

High

Low

Low

V3

3VLV

V2

Close Close

V1

Close

Maximum Pressure 250 psig (1724 kPa)Maximum Temperature 200°F (93°C)Process Connection 1/4" FNPTDimensions DPW-3VLV 9 .75"H x 7 .24"W (24 .8 x 18 .4 cm) M230-3VLV 7 .875"H x 7 .25"W (20 x 18 .4 cm) W30-3VLV 11 .125"H x 7 .25"W

(28 .3 x 18 .4 cm) M230-5VLV 7 .83"H x 7 .05"W (19 .9 x 17 .9 cm)Warranty 1 year

DESCRIPTIONThese Three and Five-Valve Manifolds, machined from brass, are perfect for applications up to 200°F (93°C) and 250 psig (1724 kPa) . The manifolds can be ordered pre-assembled with a Model DPW-692, M230, or W30 Series differential pressure transmitter (see transmitter catalog page) . Each transmitter ordered with a manifold is assembled before shipping .

FEATURES• High temperature tolerance• High pressure tolerance• Brass construction• Easy to install• Easy to operate

SEQUENCE OF OPERATION

THREE-VALVE MANIFOLDSDPW-3VLV, M230-3VLV, W30-3VLV

SPECIFICATIONS

DPW-3VLV (shown with transmitter)

ORDERING INFORMATION

MODEL DESCRIPTIONDPW-3VLV Three-valve manifold for Kele DPW-692 (not included)M230-3VLV Three-valve manifold for Setra M230 (not included)W30-3VLV Three-valve manifold for Modus W30 (not included)M230-5VLV Five-valve manifold for Setra M230 (not included)

W30-3VLV (shown with transmitter)

M230-3VLV (shown with transmitter)

Ordering note: To order with manifold assembled with M230, DPW, or W30 transmitter use "3VLV" or "5VLV" suffix after appropriate model number.

To place transmitter in service1 . Open V-32 . Open V-13 . Open V-24 . Bleed air from system5 . Close V-3To take transmitterout of service1 . Open V-32 . Close V-13 . Close V-24 . Remove transmitter

To bleed system with 5VLV1 . Briefly open then close V4 to

remove excess air2 . Briefly open then close V5 to

remove excess air

5 VLV(shown with transmitter)

Page 49: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1055

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 8-30 VDCSupply Current <5 mA (1-5 VDC models)Signal Output 4-20 mA, 1-5 VDCOutput Current 0 .45 mA maximum

(sink or source, 1-5 VDC models)Maximum Output Impedance 800Ω at 24 VDCMinimum Output Impedance 50,000ΩAccuracy <0 .5% FS includes non-linearity,

repeatability, and hysteresis (<1% on models with range ≤50 psig)

Stability <0 .25% FS per year typicalThermal Effect <0 .5% FS (-40°C to 105°C) (<1% on models with range ≤50 psig)Overpressure 3X rated pressureBurst Pressure 5x rated pressureMeasurement Range 0-15 psi to 0-500 psiResponse Time <1 msOperating Temperature -40° to 221°F (-40° to 105°C)Weight 0 .25 lb (0 .11 kg)Warranty 1 year

STAINLESS STEEL PRESSURE TRANSMITTERP51 SERIES

DESCRIPTIONThe compact and robust Kele P51 Series Stainless Steel Pressure Transmitter is designed for use with a wide variety of liquid or gas media and for industrial, process or commercial applications . The 304L and 316L stainless steel wetted parts makes the transmitter ideally suited for media such as water, glycol, refrigerants, steam (w/pigtail), and ammonia . The P51 Series is available in models with a 4-20 mA output or with 1-5 VDC output and come standard with a 3 foot cable . It is very competitively priced and can be ordered in an optional enclosure assembly, or enclosed with a gauge for local pressure indication .

FEATURES• Robust compact package• Laser welded stainless steel design• Reverse polarity protection• 3' cable standard• Optional enclosure • Optional gauge assembly• Ranges up to 500 psi

4-20 mAsignal

24 VDCPowersupply

– –

+ + (red) (white)

4-20 mA

1-5 VDCsignal

24 VDCPowersupply

– –

+ + (red) (white)(black)

1-5 VDC

WIRING

APPLICATION• Hot/chilled water • Pneumatics• Steam (with pigtail) • Compressors• Refrigeration • Agriculture• Hydraulics • Process control• Flow

SPECIFICATIONS

P51 with optional enclosure and gauge

P51

Page 50: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1056

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

2.36 (60.0)

Cable length 36 (914.4)

0.86(22.0)

1/8" - 27 NPT

0.85 (21.5)0.51 (13)

0.16 (4.0)

0.86 (22.0)

HEX

Ø

Ø

DIMENSIONS

STAINLESS STEEL PRESSURE TRANSMITTERP51 SERIES

ORDERING INFORMATION

Example: P51-100-20 0-100 psi transmitter with 4-20 mA output, no options

100 P51 20

MODEL DESCRIPTION P51 Pressure transmitter RANGE psig (kPa) 15 0-15 (0-103) 50 0-50 (0-345) 100 0-100 (0-690) 200 0-200 (0-1379) 300 0-300 (0-2069) 500 0-500 (0-3448) OUTPUT SIGNAL 20 4-20 mA output 5 1-5 VDC output OPTIONS E Transmitter in watertight enclosure with stainless steel fittings E-G Transmitter in enclosure with a pressure gauge, brass fittings

RELATED PRODUCTS PAGE47B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994PT 1/4" pigtail syphon with fittings 1112ZG-R01 500Ω, 1/2W, 1% resistor 8

Page 51: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1057

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 8-30 VDCSignal Output 4-20 mAMaximum Output Impedance 800Ω @ 24 VDCAccuracy Models > 75 psi <0 .5% of span Models < 50 psi <1 .0% of spanStability <0 .25% of span/yearThermal Effect -40° to 221°F (-40° to 105°C), <0 .5%

FSOverpressure 3x rangeBurst Pressure 5x rangeMeasurement Range 0-15 psi to 0-1000 psi

Media Compatibility Fluids compatible with brass, 304L and 316 stainless steel

Response Time <1 msOperating Temperature -40° to 221°F (-40° to 105°C)Process Connection 1/8" MNPT, 316 stainless steelWiring Terminations Splash-proof Packard connector, 16

AWG cable, 36" lengthDimensions Enclosure: 5 .11"H x 5 .11"W x 2 .95"D

(13 .0 x 13 .0 x 7 .5 cm)Weight 0 .3 lb (0 .13 kg) with 36" cableWarranty 1 year

STAINLESS STEEL PRESSURE TRANSMITTERPSS2 SERIES

0.29(6.74)

36 (91)16 AWG Cable

in(cm)

0.86 dia(2.2)

0.86 Hex(2.2)

1/8'' NPT

3.5(8.89)

2.6(6.60)

DESCRIPTIONThe Kele PSS2 Series Stainless Steel Pressure Transmitter is highly accurate and compact, which makes it ideal for HVAC, building automation, and process gauge pressure applications . A splash-proof Packard-type electrical connector is provided for ease of installation . Eleven standard ranges are available for a wide variety of applications .

FEATURES• Splash-proof, plug-in electrical connector• For steam, water, glycol, refrigerant, and more• 4-20 mA output• 304L/316L stainless steel wetted parts• Wide range of pressures• High overpressure capability

-

+

-

+

4-20 mA Signal

24 VDC Power Supply

(red) (white)

in(cm)

WIRINGDIMENSIONS

SPECIFICATIONS

PSS2

PSS2 with optional enclosure and gauge

PSS2

Page 52: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1058

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Mount the PSS2 Series in a manner that protects it from steam or temperatures outside of its operating range . A Model PTsteam pigtail syphon must be installed in all applications where steam is to be monitored . When monitoring the pressure of amedium that is above or below the temperature operating range of the transmitter, the sensor should be isolated by a length oftubing . If 6" to 12" (15 .2 to 30 .5 cm) of brass tubing is used, temperatures up to 400°F (204°C) can be tolerated . See theTechnical Reference section for information on Steam Isolation and Temperature Protection .

If the PSS2 Series is to be subjected to fluid hammer, pressure surges, or pulsations, a Model 47 pressure snubber is recommended .

INSTALLATION

STAINLESS STEEL PRESSURE TRANSMITTERPSS2 SERIES

ORDERING INFORMATION

PSS2 100 G Example: PSS2-100-G Stainless steel pressure transmitter with a 4-20 mA output over the range of 0-100 psig, with pressure gauge, installed in a watertight enclosure with a transparent cover * Brass wetted parts option is only for those mediums compatible with brass.

MODEL DESCRIPTIONPSS2 Stainless steel 4-20 mA pressure transmitter PRESSURE RANGE psig (kPa) 15 0-15 (0-103.4) 30 0-30 (0-206.9) 50 0-50 (0-344.8) 75 0-75 (0-517.1) 100 0-100 (0-689.5) 150 0-150 (0-1034) 200 0-200 (0-1379) 300 0-300 (0-2068) 500 0-500 (0-3497) 750 0-750 (0-5171) 1000 0-1000 (0-6895) OPTIONS (leave blank for no options) E Watertight enclosure (with stainless steel bulkhead fitting) G* Enclosed with pressure gauge (watertight with transparent cover, brass fittings) LCD* Model LPI-1C LCD display with enclosure (not watertight, brass fittings) RED* Model LPI-1CR red digital display with enclosure (not watertight, brass fittings)

CAUTION: Not for use with ammonia. The PSS2 can be used with media that is compatible with 304L and 316L stainless steel.

RELATED PRODUCTS PAGE250R-3-1 250 OHM 3 WATT 1% resistor long leads 129947B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112PT 1/4" pigtail syphon with fittings 1112

Page 53: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1059

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Mount the PTX1 Series in a manner that protects it from steam or temperatures outside of its operating range . A Model PT steam pigtail syphon must be installed on all applications where steam is to be monitored . When monitoring the pressure of medium that is above or below the temperature operating range of the transmitter, the sensor should be isolated by a length of tubing . If 6" to 12" (15 .2 to 30 .5 cm) of brass tubing is used, temperatures up to 400°F (204°C) can be tolerated . See the Technical Reference section for information on Steam Isolation and Temperature Protection .

If the PTX1 Series is to be subjected to fluid hammer, pressure surges, or pulsations, a Model 47 pressure snubber is recommended .

Supply Voltage 10-30 VDC @ 25 mASignal Output 4-20 mAMaximum Output Impedance 650Ω @ 24 VDC maximumAccuracy ±1% FSThermal Effect ±0 .04% FS/°F zero and spanOverpressure 200%Burst Pressure 800%Response Time 1 msMedia Compatibility Fluids compatible with brass and

17-4 PH stainless steelWetted Materials Diaphragm: 17-4 PH stainless steelCompensated Temperature Range -20° to 160°F (-29° to 71°C)

Operating Temperature -40° to 200°F (-40° to 93°C)Transmitter Case 304 stainless steelProcess Connection 1/8" NPT male 316 stainless steel,

with enclosure: 1/8" FNPTWiring Terminations 72" (182 cm) jacketed leadsDimensions 7 .09"H x 4 .33"W x 3 .54"D (18 .0 x 11 .0 x 9 .0 cm)Weight PTX1 0 .45 lb (0 .20 kg) PTX1EG 2 .05 lb (0 .93 kg)Warranty 1 year

STAINLESS STEEL PRESSURE TRANSMITTERPTX1 SERIES

DESCRIPTIONThe Kele PTX1 Series Stainless Steel Pressure Transmitter utilizes a thin film strain-gauge bridge and stainless steel diaphragm to provide a highly accurate, stable means of measuring gauge pressures up to 2000 psig (13 .79 MPa) . Splash-proof cable connections protect the wiring, allowing the PTX1 Series to be mounted near the medium being measured . Optional indication is available as a digital display or as a 2" (5 .1 cm) gauge .

FEATURES• For steam, water, glycol, ammonia, refrigerants, and

more• 1% full scale accuracy• 200% proof pressure• Wide range of pressures• 4-20 mA output• Reverse polarity protected• Plug-in, splash-proof connector with 6' cable• Stainless steel wetted parts• Stainless steel case• Optional watertight polystyrene enclosure• Optional LCD/red digital indication• Optional gauge available for mediums compatible with

brass

INSTALLATION

SPECIFICATIONS

PTX1-07

PTX1-E-07

Page 54: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1060

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

72.0 Cable(182.88)

1/8" NPTmale

Hex

(white)

(black)

4-20 mA

24 VDCPower Supply

in(cm)

2.73(6.92)

0.63(1.59)

Splash-proofHirschmanConnector

WIRING

STAINLESS STEEL PRESSURE TRANSMITTERPTX1 SERIES

ORDERING INFORMATION

* Enclosed models not available in pressure ranges above 1000 psig ** Brass wetted parts; do not use with mediums that are not compatible with brass Note: NIST certificate available; contact Kele.

Example: PTX1 Stainless steel pressure transmitter with 100 psig pressure range in enclosure with LCD indication

01 02 03 04 05 06 07 08 09 10 11 12 13 14* 15 16

30" Hg Vacuum to 0 (-101.6 Vacuum to 0)30" Hg Vacuum to 15 (-101.6 Vacuum to 103.4)0-15 (0-130.4)3-15 (20.7-103.4)0-30 (0-206.9)0-60 (0-413.7)0-100 (0-689.5)0-150 (0-1034.3)0-200 (0-1379.0)0-300 (0-2068.5)0-500 (0-3447.5)0-750 (0-5171.3)0-1000 (0-6895.0)0-2000 (0-13,790.0)30'' Hg Vacuum to 30 (-101.6 Vacuum to 206.9)30'' Hg Vacuum to 60 (-101.6 Vacuum to 413.7)

MODEL DESCRIPTION PTX1 Stainless Steel Pressure Transmitter OPTIONS Leave blank for no options and specify E* Watertight enclosure (with stainless steel bulkhead fitting) LCD Model LPI-1C LCD display (enclosure not watertight) RED Model LPI-1CR red digital display (enclosure not watertight) G** Pressure gauge (includes enclosure with transparent cover) XX RANGE (see table above) (must specify range)

* Enclosed models not available in pressure ranges above 1000 psi ** Pressure gauge option available for all mediums compatible with brass

PTX1 E LCD Example: PTX1 Stainless steel pressure transmitter with 100 psig pressure range in enclosure with LCD indication

07

RANGE NUMBER

01 02 03 04 05 06 07 08

0-30" VAC 30" VAC to 15

0-15 3-15 0-30 0-60

0-100 0-150

0-101.6 -101.6 to 103.4

0-130.4 20.7-103.4

0-206.9 0-413.7 0-689.5

0-1034.3

PRESSURE RANGE psig kPa

RANGE NUMBER

09 10 11 12 13 14 15 16

0-200 0-300 0-500 0-750

0-1000 0-2000

30'' VAC to 30 30'' VAC to 60

0-1379.0 0-2068.5 0-3447.5 0-5171.3 0-6895.0

0-13790.0 -101.6 VAC to 206.9 -101.6 VAC to 413.7

PRESSURE RANGE psig kPa

PTX1E-LCD 07

MODEL DESCRIPTIONPTX1 Pressure transmitter with cablePTX1E Pressure transmitter in watertight enclosure, stainless steel fittingsPTX1E-G** Pressure transmitter in watertight enclosure, with gauge, brass fittingsPTX1E-LCD** Pressure transmitter enclosed (not watertight), with LCD, brass fittingsPTX1E-RED** Pressure transmitter enclosed (not watertight), with red LCD, brass fittings PRESSURE RANGE psig (kPa)

909

750

500

250

0

0 10 20 30

Lo

op

Res

ista

nce

)

Loop Supply Voltage (VDC)

Load Limitations 4-20 mA Output

Vmin = 10V + [0.022A*(R )]Loop

RELATED PRODUCTS PAGE47B-1 Brass piston style snubber 129947S-1 Stainless steel piston style snubber 1299DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994PT 1/4" pigtail syphon with fittings 1112

Page 55: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1061

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage Current 14 to 30 VDC (RL=250Ω), 2-wire Voltage 9 to 30 VDC, 3-wireSignal Output Current 4-20 mA Voltage 0 .5 to 5 .5 VDC Maximum Output Impedance 800Ω @ 24 VDCMinimum Output Impedance 5000ΩAccuracy ±0 .25% FS Stability 0 .5% FS/year Non-repeatability 0 .05% FS Non-linearity ±0 .22% FS Hysteresis 0 .10% FS

Thermal Effect Zero ±2 .0% FS/100°F (±1 .8% FS/50°C) Span ±1 .5% FS/100°F (±1 .3% FS/50°C)Overpressure See ordering informationMeasurement Range 0 - 1 psi to 2000 psiOperating Temperature -40° to 185°F (-40° to 85°C)Compensated Temperature Range -4° to 176°F (-20° to 80°C)Process Connection 1/4" 18 NPTEnclosure Stainless Steel, ValoxWetted Materials 17-4 PH stainless steelWiring Terminations Screw terminalsApprovals CE, RoHSWeight 0 .14 lb (0 .07 kg)Warranty 1 year

PRESSURE TRANSMITTER209 SERIES

GNDin

(cm)

COM OUT

1.62(4.1)

3.63(9.2)

EXC

DESCRIPTIONThe Setra 209 Series Pressure Transmitter is specifically designed for industrial applications with high performance requirements . It measures gauge pressure and can be used with gases or liquids compatible with 17-4 PH stainless steel . The 209 Series is packaged in a rugged, stainless steel/Valox housing, which is small and lightweight . The stainless steel capacitance sensing element and high level output, IC-based circuit assures excellent stability .

FEATURES• Low cost• Highly accurate• Current output• Lightweight• Compatible with most common applications• Stainless steel construction• Conduit adapter standard• Optional voltage output available

APPLICATION• HVAC/R equipment• Industrial equipment• Compressor control• Hydraulic systems• Process and refrigeration systems

DIMENSIONS

SPECIFICATIONS

209 Series

Page 56: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1062

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

4-20 mA 0.5-5.5 VDC

GND

Rload

Rload

COM OUT EXC

GND

COM OUT EXC

24 VDC*Power supply

* See Specifications on previous page for power supply requirements.

4-20mA

0.5-5.5VDC

24 VDC*Power supply

WIRING

PRESSURE TRANSMITTER209 SERIES

ORDERING INFORMATION

Example: 209-050P-G2M11-A1 0-50 psig transmitter with 4-20 mA output and conduit connection

209 050P G2M11 A1

MODEL DESCRIPTION 209 Pressure transmitter PROOF BURST RANGE psig (kPa) PRESSURE (psig) PRESSURE (psig) 001P 0-1 (0-7) 2 250 002P 0-2 (0-14) 4 250 005P 0-5 (0-34) 10 250 010P 0-10 (0-69) 20 500 025P 0-25 (0-172) 50 500 050P 0-50 (0-345) 100 750 100P 0-100 (0-690) 200 1000 200P 0-200 (0-1379) 400 2000 250P 0-250 (0-1724) 500 2000 500P 0-500 (0-3448) 1000 3000 10CP 0-1000 (0-6895) 2000 5000 20CP 0-2000 (13790) 3000 6500 OUTPUT G2M11 4-20 mA analog G2M24 0.5-5.5 VDC analog CONNECTION A1 Threaded conduit connection

RELATED PRODUCTS PAGEPT 1/4" pigtail syphon with fittings 1112

Page 57: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1063

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 14-30 VDC, 20 mASignal Output 4-20 mA @ 800ΩAccuracy <± 1% of spanThermal Effect (at 0 to 80°C)

Typ . 1% of span; Max: 2 .5% of spanOverpressure (dependent on calibrated range)

typ . ~2x rated pressureMeasurement Range 0-15 to 0-10,000 psiResponse Time <4 mS

Operating Temperature 32° to 176° F (0° to 80° C)Process Connection 1/4" NPT maleWiring Terminations DIN 175301-803 A and C, M12x1,

6 ft . cableMedia Compatibility 316L stainless steelStability 0 .1% of spanApprovals CE Weight 0 .14 lb (0 .07 kg)Warranty 1 year

PRESSURE TRANSMITTER50 SERIES

DESCRIPTIONThe Wika 50 Series pressure transmitter is precision engineered and manufactured to fit many industrial and OEM pressure measurement applications . The rugged design provides resistance to vibration, shock, wide temperature variations, RFI and other extreme environmental conditions that are typical of industrial and OEM applications . Performance and reliability is enhanced by the all stainless steel welded measuring cell that eliminates the need for soft sealing materials that may deteriorate over time . The state-of-the-art manufacturing and assembly process increases the long-term reliability of the 50 Series .

FEATURES• Pressure ranges: from 0...15 psi up to 0... 10,000 psi• Non-linearity: ≤±0.5% BFSL • Signal output: 4-20 mA and 0-10 V

1/4 NPT Male

1/4 NPT

1.06(27 mm)

.51

(13

mm

)

DIMENSIONS

SPECIFICATIONS

50 Series

L-connectorConductor outer diameter

.18" to .24"

1.06(27 mm)

.51 (13 mm)

1.14 (29 mm)

max. 1.5 (38 mm)

max. 1.9 (48 mm)EN175301-801-C

2.4

(60.

8 m

m)

1/4 NPT

DIMENSIONS

Page 58: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1064

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

PRESSURE TRANSMITTER50 SERIES

ORDERING INFORMATION

MODEL DESCRIPTION50426354 Pressure transmitter, 0-15 psia, 4-20 mA, 1/4 MNPT50426389 Pressure transmitter, 0-100 psia, 4-20 mA, 1/4 MNPT50426397 Pressure transmitter, 0-15 psi, 4-20 mA, 1/4 MNPT50426401 Pressure transmitter, 0-25 psi, 4-20 mA, 1/4 MNPT50426427 Pressure transmitter, 0-50 psi, 4-20 mA, 1/4 MNPT50372475 Pressure transmitter, 0-100 psi, 4-20 mA, 1/4 MNPT50398083 Pressure transmitter, 0-200 psi, 4-20 mA, 1/4 MNPT50426460 Pressure transmitter, 0-300 psi, 4-20 mA, 1/4 MNPT50426478 Pressure transmitter, 0-500 psi, 4-20 mA, 1/4 MNPT50426486 Pressure transmitter, 0-1000 psi, 4-20 mA, 1/4 MNPT50426494 Pressure transmitter, 0-1500 psi, 4-20 mA, 1/4 MNPT50426508 Pressure transmitter, 0-2000 psi, 4-20 mA, 1/4 MNPT50426516 Pressure transmitter, 0-3000 psi, 4-20 mA, 1/4 MNPT50372483 Pressure transmitter, 0-5000 psi, 4-20 mA, 1/4 MNPT50426532 Pressure transmitter, 0-10,000 psi, 4-20 mA, 1/4 MNPT50426737 Pressure transmitter, 0-15 psia, 0-10 V, 1/4 MNPT50426761 Pressure transmitter, 0-100 psia, 0-10 V, 1/4 MNPT50426770 Pressure transmitter, 0-15 psi, 4-20 mA, 1/4 MNPT50426788 Pressure transmitter, 0-25 psi, 4-20 mA, 1/4 MNPT50426800 Pressure transmitter, 0-50 psi, 4-20 mA, 1/4 MNPT50426818 Pressure transmitter, 0-100 psi, 4-20 mA, 1/4 MNPT50426834 Pressure transmitter, 0-200 psi, 4-20 mA, 1/4 MNPT50426842 Pressure transmitter, 0-300 psi, 4-20 mA, 1/4 MNPT50426851 Pressure transmitter, 0-500 psi, 4-20 mA, 1/4 MNPT50426869 Pressure transmitter, 0-100 psi, 4-20 mA, 1/4 MNPT50426877 Pressure transmitter, 0-1500 psi, 4-20 mA, 1/4 MNPT50426885 Pressure transmitter, 0-2000 psi, 4-20 mA, 1/4 MNPT50426893 Pressure transmitter, 0-3000 psi, 4-20 mA, 1/4 MNPT50426907 Pressure transmitter, 0-5000 psi, 4-20 mA, 1/4 MNPT50426915 Pressure transmitter, 0-10000 psi, 4-20 mA, 1/4 MNPT

RELATED PRODUCTS PAGEZG-R01 500Ω, 1/2W, 1% resistor 8PT 1/4" pigtail syphon with fittings 1112DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 99547B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112

Page 59: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1065

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 9-28 VSupply Current ≤ 5 mASignal Output 4-20 mA Ratiometric

(10-90% of V supp)Output Current up to 5mAMaximum Output Impedance Zero for 4-20 mA output < 25 Ω for ratiometric Minimum Output Impedance Zero for 4-20 mA output < 25 Ω for ratiometric Accuracy < ± 1 .0 % FS

Temperature Effect Included in accuracySystem Pressure 0 to 360 psiOverpressure 3X rated pressureBurst Pressure 4X rated pressureMeasurement Range 0 to 360 psiResponse Time < 4 msOperating Temperature -4° to 176°F (-20° to 80°C)Weight 0 .33 to 0 .66 lbs (0 .15 to 0 .30 kg)Approvals CE, UL File# E31024, RoHSWarranty 18 months from manufacture date

PRESSURE TRANSMITTERMBS 1900

A0, A1

DESCRIPTIONThis compact Danfoss MBS 1900 Series pressure transmitter is designed for use in air and water applications like booster pumps and air compressors . It offers a range of output signals and connection options .

FEATURES• Stainless steel (316) welded construction for sensor

element and package• Reverse polarity protection• EMC protection up to 100V/m• RoHS conformty• Digitally compensated• UL/CSA certified

Electrical Connection 4-20 mA Output (2 wire)

Pin 1: + supply = BlackPin 2: ÷ supply = White

Pin 3: not used

Earth: Connectedto MBS enclosure

Black

White

WIRING DIMENSIONS

SPECIFICATIONS

MBS 1900

ORDERING INFORMATION

MODEL DESCRIPTIONMBS19005811A36B04 Pressure transducer for water and air applications, 0-100 psiMBS19006211A36B04 Pressure transducer for water and air applications, 0-200 psiMBS19006411A36B04 Pressure transducer for water and air applications, 0-300 psi

RELATED PRODUCTS PAGEZG-R01 500Ω, 1/2W, 1% resistor 8PT 1/4" pigtail syphon with fittings 1112DCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 99547B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112

Cable

Page 60: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1066

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 24 VAC ±10% @ 80 mA 24 VDC ±10% @ 35 mASignal Output Current 4-20 mA (sourcing) Voltage 1-5 VDC, 2-10 VDC, 3-15 VDCMaximum Output Impedance (mA) 650ΩMinimum Output Impedance (VDC) 1-5 VDC: 1250Ω 2-10 VDC 2500Ω 3-15 CDC 3750ΩAccuracy ±0 .1 psig @ 77°F (25°C) Span Adjustments 3-20 psig (20 .7-137 .9 kPa) Zero Adjustments 0-17 psig (0-117 .2 kPa)Pressure Range 0-20 psig (0-137 .9 kPa) factory settingMedia Compatibility Air and non-conductive gases

Operating Temperature 32° to 122°F (0° to 50°C)Process Connection 1/4" barbWiring Terminations TerminalsDimensions PVI-1 3 .4"H x 4 .9"W x 2"D (8 .6 x 12 .4 x 5 .1 cm)* PVI-2 3 .25"H x 3 .25"W x 1 .75"D (8 .26 x 8 .26 x 4 .45 cm)*Approvals RoHSWeight PVI-1 0 .85 lb (0 .39 kg) PVI-2 0 .75 lb (0 .34 kg)Warranty 18 months

PRESSURE TRANSMITTERPVI-1, PVI-2

DESCRIPTIONThe Kele Model PVI-1 and PVI-2 Pressure Transmitters are designed to provide economical monitoring of control air pressure in HVAC applications . The Model PVI-1 is furnished in a unique slim-line design housing, which saves panel space, and can be ordered with an optional DIN rail-mounting adapter . The Model PVI-2 is a snap-track mounted version with identical operation . Both versions are available with an optional pressure indication gauge .Both units have LED indication for power and for output over range when input pressure exceeds maximum calibrated pressure . The output signal is limited to 110% of normal full scale (20 mA, 5/10/15V) .

FEATURES• AC or DC power• 0-20 psig (0-137.9 kPa) input pressure range• 4-20 mA and voltage outputs available simultaneously• Adjustable zero and span• LED indication of power and output over range• Optional pressure gauge

APPLICATIONModels PVI-1 and PVI-2 convert an input pressure to a 4-20 mA current sourcing and a jumper-selectable 1-5, 2-10, or 3-15 VDC output signal that is directly proportional to the input pressure . The zero and span potentiometers allow for adjustment if the output signal required is different from the standard calibration .

SPECIFICATIONS

PVI-1

PVI-2 with Optional Gauge

* Add 0 .6"H (1 .5 cm) each for mounting tabs and 2 .3"H (5 .8 cm) for gauge option .

Page 61: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1067

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Voltage Output Jumper(Shown in 1-5V Position)

PVI-1 (enclosed)PVI-2 (track mount)

OutputVoltageRange

Voltage OutmA Out

COM

24V Power

Voltage output and 4-20 mA outputs are simultaneously active.

OutOver

Power

Span

Zero

Zero and Span

PressureZero Range

PressureSpan Range

10V 15V

5V

Voltage Output

4-20 mA Output 650Ω max

24 VAC or VDCPower Supply

Zero and SpanSelection Dip

Switches

WIRING CALIBRATION

Models PVI-1 and PVI-2 are factory calibrated for 0-20 psig (0-137 .9 kPa) . If another pressure range is required, select the pressure zero range from Table 1 and set SW1 and SW2 accordingly . Then, select the pressure span range (high pressure minus low pressure) required from Table 2 and set SW3 and SW4 . Apply the low-end pressure and adjust the zero pot for the desired output . Apply the high-end pressure and adjust the span pot . Repeat as required .

Example: To monitor an 8-13 psig signal, the pressure zero range is 8, so set SW1 ON and SW2 OFF . The pressure span range is 5 (13-8 = 5), so set SW3 OFF and SW4 OFF .

PRESSURE TRANSMITTERPVI-1, PVI-2

ORDERING INFORMATION

OPTIONS (must be factory installed)PVI-1

Pressure indication gaugeDIN rail mountingSpecial calibration (specify range when ordering)

4347C

Example: PVI-1-43-47 Enclosed pressure transmitter with pressure indication gauge and DIN rail mounting

OPTIONS (must be factory installed)PVI-2

DESCRIPTIONMODEL

Pressure indication gaugeSpecial calibration (specify range when ordering)

GC

Example: PVI-2-G Track-mounted pressure transmitter with pressure gauge

DESCRIPTIONMODELPressure transmitter

Track-mounted pressure transmitter

TABLE 1. PRESSURE ZERO RANGEZERO SW1 SW20.00-4.25 psig (0-29.3 kPa) ON ON4.25-8.50 psig (29.3-58.6 kPa) ON OFF8.50-12.75 psig (58.6-87.9 kPa) OFF ON12.75-17.00 psig (87.9 kPa-117.2 kPa) OFF OFF

TABLE 2. PRESSURE SPAN RANGESPAN SW3 SW43.00-7.25 psig (20.7-50.0 kPa) OFF OFF7.25-11.50 psig (50.0-79.3 kPa) OFF ON11.50-15.75 psig (79.3-108.6 kPa) ON OFF15.75-20.00 psig (108.6-137.9 kPa) ON ON

Page 62: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1068

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 12-32 VDCSignal Output 4-20 mA (2-wire)Maximum Output Impedance mA 545Ω @ 24 VDCAdjustments Zero and Span Adjustable

-10% to 110% FSAccuracy ±0 .25% Full Scale (includes linearity,

hysteresis, and repeatability)Thermal Effect ±0 .02% FS (URL)/°C from 23°C reference Overpressure (Proof) 1500 psi FS and below 200% FS value 3000, 5000 psi 150% FS value 7500 psi 120% FS valueMeasurement Range Vac-15 psi (-101 .6 Vac to 103 .4 KPa) to

0-7500 psi (0-51710 .68 KPa)Display Type 4 digit, 10mm LCD with LED backlight Accuracy ±0 .25% FS (URL) + last digitOperating Temperature -10° to 60°C (14° to 140°F)Wetted Parts 316 Stainless Steel and 17-4PH SSStorage Temperature -20° to 70°C (-4° to 158°F)Enclosure Rating Epoxy coated aluminum, NEMA 4X (IP65)Process Connection 1/4 FNPTWiring Terminations Cable Gland

(Cable Diameters 0 .35" to 0 .47")Approvals CEWeight Approx . 1 .0 lb (0 .45 kg)Warranty 1 year

DESCRIPTIONThe Ashcroft GC51 Rangeable Pressure Transmitter is a compact alternative to the conventional process transmitter available in compound and gauge ranges . The ranges span from Vacuum to 15 PSI, 30 PSI, or 50 PSI compound ranges and 0 to 7500 PSI ranges . The GC51 Series features a two wire 4-20mA output, backlit LCD display, stainless steel wetted parts, and NEMA 4X, IP65, robust aluminum housing . The range and output allows for rescaling and setting of user defined units .

FEATURES• NEMA 4X (IP65) aluminum die cast housing• Backlit LCD display• Min./Max. hold to capture pressure events• Rotatable display• Adjustable pressure range and output• 2 wire 4-20mA output• Standard 120ms response time• Internal push button keys with key lock feature• Optional NIST certification

+ -

Terminal box

Display (board)

Shield

Power source

+ - Receiver

Transmission cable

WIRING

RANGEABLE PRESSURE TRANSMITTERGC51 SERIES

SPECIFICATIONS

GC51

ORDERING INFORMATION

RELATED PRODUCTS PAGEPT 1/4" pigtail syphon with fittings 1112DCPA-1.2 Power supply, 120 VAC In to 24 VAC/24 VDC Out 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 99547B-1 Brass piston style snubber 111247S-1 Stainless steel piston style snubber 1112

MODEL DESCRIPTIONGC51-15V Pressure transmitter, Vac to 15 psiGC51-30V Pressure transmitter, Vac to 30 psiGC51-50V Pressure transmitter, Vac to 50 psiGC51-50 Pressure transmitter, 0-50 psiGC51-100 Pressure transmitter, 0-100 psiGC51-150 Pressure transmitter, 0-150 psiGC51-300 Pressure transmitter, 0-300 psiGC51-500 Pressure transmitter, 0-500 psiGC51-1000 Pressure transmitter, 0-1000 psiGC51-1500 Pressure transmitter, 0-1500 psiGC51-3000 Pressure transmitter, 0-3000 psiGC51-5000 Pressure transmitter, 0-5000 psiGC51-7500 Pressure transmitter, 0-7500 psi

Page 63: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1069

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 15-35 VDC Contact Rating 24 VDC @ 500ΩContact Type Solid-state (PNP OR NPN)Accuracy 1 .00% of spanMeasurement Range 0-15 psi to 0-5000 psiShock 50gOperating Temperature 32° to 176°F (0° to 80°C)

Wetted Parts Pressure connection 316 L stainless steel (13-8 PH for ranges above 150 psi)

Process Connection 1/4" FNPTWiring Terminations 6 ft (2m) cableApprovals CE , UL File E12413, RoHSWeight 0 .44lbs (0 .45 kg)Warranty 2 years

PRESSURE SWITCHPSD-30 SERIES

DESCRIPTIONThe design and outstanding functionality of the Wika PSD-30 pressure switch received the IF Product Design Award in 2009 . The large, ergonomically designed programming push buttons provide the user with tactile feedback for immediate confirmation that the touch event was registered by the trans-mitter . The user-friendly menu navigation layout meets the new German Engineering Federation (VDMA) Standard form for fluid sensors (24574-1, Part 1, pressure switch) . The goal of the VDMA is to simplify the use of pressure switches by standardizing menu navigation and display parameters .The PSD-30 can be adjusted three different ways to fit specific installation requirements . The display and electrical connection can be rotated independently to maximize visibility while still orienting the electrical connection in the best position for the cable connector . If the transmitter is installed overhead or upside down the display can be electronically rotated 180° .Time tested, proven WIKA thin film and piezoresitive pressure sensor technology is an integral part of the PSD-30 providing the high quality and long term reliability users demand .

FEATURES• Available with single or dual Negative-Positive-

Negative (NPN) or Positive-Negative-Positive (PNP) solid state switches

• High visibility, rugged 14-segment red LED display electronically rotates 180° for top-down installation

• User-friendly, intuitive 3-key operation• Versions with 4-20 mA or 0-10V analog output

available• Programming menu meets VDMA Standards for user

friendly navigation.

2x PNP + analog output

U+ Positive supply connectionU- Negative supply connectionSP1 Switching point 1SP2 Switching point 2S+ Switching point 2

Legend:

Brown

White

Black

Gray

Blue

WIRING

SPECIFICATIONS

PSD-30

ORDERING INFORMATION

01 02 03 04 05 06* 07 08 091011

30" Hg Vacuum to 0 (-101.6 Vacuum to 0)30" Hg Vacuum to 100 (-101.6 Vacuum to 689.5)0-15 (0-130.4)0-25 (0-172.4)0-50 (0-344.7)0-100 (0-689.5)0-200 (0-1379.0)0-500 (0-3447.5)0-2000 (0-13,790.0)0-3000 (0-20,684.3)0-5000 (0-34,473.8)

Example: PSD-30-03 4-20 mA pressure transmitter with integral LED display, 0-15 psi range.

PSD-30 03

MODEL DESCRIPTION PSD-30 4-20 mA pressure transmitter with integral LED display PSD-30-10V 0-10 V pressure transmitter with integral LED display (models only with *)

-

PRESSURE RANGE psi (kPA)

Page 64: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1070

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Common

Normally Closed

Normally Open

1

2

3

2.5"

0" 5"

Contact Rating 1 .5A (0 .4A) @ 250VContact Type SPST or SPDTDifferential KDPS-02/03 0 .04" WC (10 Pa) KDPS-04/05 0 .08" WC (20 Pa) KDPS-10 0 .40" WC (100 Pa) KDPS-25 0 .60" WC (150 Pa)Operating Pressure 20" WC (5 kPa)Measurement Range KDPS-02 0 .08 to 0 .80" WC (20 to 200 Pa) KDPS-03 0 .12 to 1 .20" WC (30 to 300 Pa) KDPS-04 0 .16 to 1 .6" WC (40 to 400 Pa) KDPS-05 0 .20 to 2 .00" WC (50 to 500 Pa) KDPS-10 0 .80 to 4 .0" WC (200 to 1000 Pa)

KDPS-25 1 .0 to 10 .0" WC (500 to 2500 Pa)Media Compatibility Air, non-combustible and inert gasesOperating Temperature -40° to 185°F (-40° C to 85°C)Mounting Diaphram positioned in any vertical

planeEnclosure IP54 (with cover) similar to NEMA 12Process Connection 0 .25" (6 .0mm) diameter for 0 .25" ID

Tubing Wiring Terminations 0 .25" (6 .4 mm) copper alloyApprovals CE, RoHS, UR recognized File

MH46253Weight 6 oz (171 .4g)Warranty 1 year

DESCRIPTIONThe Kele KDPS Series Adjustable Differential Pressure Switches are general-purpose, airflow-proving switches designed for HVAC and building automation applications . The KDPS Series can be used to sense positive, negative, or differential air pressure . The silicone diaphragm and calibration spring are housed in a rugged plastic enclosure with a removable cover protecting the set point adjustment knob and snap action switch terminals . Electrical connections are made through a 7/8" diameter opening in the cover that accepts a 1/2" conduit connection . Air sampling connections accept 1/4" ID tubing .

FEATURES• Transparent cover for setpoint confirmation• Easy, field adjustable set point• Dual scales

WIRING

APPLICATION• Proving fan status• Monitoring filter for excess pressure drop• Monitoring duct static pressure• Proving air flow• Monitoring damper status

DIFFERENTIAL PRESSURE SWITCHKDPS SERIES

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTIONKDPS-02 Differential pressure switch, 0.08" to 0.80" WC (20 to 200 Pa)KDPS-03 Differential pressure switch, 0.12" to 1.20" WC (30 to 300 Pa)KDPS-04 Differential pressure switch, 0.16" to 1.6" WC (40 to 400 Pa)KDPS-05 Differential pressure switch, 0.20" to 2.00" WC (50 to 500 Pa)KDPS-10 Differential pressure switch, 0.80" to 4.0" WC (200 to 1000 Pa)KDPS-25 Differential pressure switch, 1.0" to 10.0" WC (500 to 2500 Pa)

KDPS Series

Page 65: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1071

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

APPLICATION• Proving fan status• Monitoring filter for excess pressure drop• Monitoring duct static pressure• Proving air flow • Monitoring damper status

Contact Rating AFS-145, 222, 262, 405 15A non-inductive, 277 VAC, 60 Hz

24 VAC @ 2 .4A AFS-460, 460-DSS 15A @ 125-277 VAC 1/4 HP @ 125 VAC 1/2 HP @ 250 VAC 1/2A @ 125 VDCContact Type AFS-145, 222, 262, 405 AFS-136, 460-137 SPDT AFS-460 SPST N .C . AFS-460-DSS 2-SPST N .C .Switch Differential AFS-145, 222, 262, 405 Progressive, increasing from

approximately 0 .02" W .C . (5 .0 Pa) @ minimum set point to approximately 0 .8" W .C . (199 Pa) @ maximum set point

AFS-460, 460-DSS None, manual reset

Overpressure 0 .5 psig (3 .5 kPa)Measurement Range AFS-145, 222, 405 0 .05" to 12 .0" W .C . (12 .5 to 2989 Pa) AFS-262 0 .05" to 2 .0" W .C . (12 .5 to 498 Pa) AFS-460 0 .4" to 12 .0" W .C . (99 .3 to 2989 Pa) AFS-460-DSS 2 .0" to 12 .0" W .C . (498 to 2989 Pa)Life Expectancy AFS-145, 222, 262, 405: 100,000

cycles minimum @ 0 .5 psig (3 .5 kPa) maximum pressure each cycle and at maximum electrical load AFS-460: 6000 cycles

Operating Temperature -40° to 180°F (-40° to 82°C)Process Connection AFS-145 1/8" NPTF All Others Ferrule and nut compression for 1/4" OD tubingApprovals CE, UL File MH6213, cCSAus, RoHSWeight 1 .2 lb (0 .54 kg)Warranty 2 years

ADJUSTABLE DIFFERENTIAL PRESSURE SWITCHESAFS SERIES

DESCRIPTIONThe Cleveland Controls AFS Series Adjustable Differential Pressure Switches are general-purpose, airflow-proving switches designed for HVAC and building automation applications . The AFS Series can be used to sense positive, negative, or differential air pressure . The diaphragm and calibration spring are housed in a plated enclosure with a removable metal guard protecting the set point screw and snap action switch terminals . Electrical connections are made through a 7/8 diameter opening in the metal guard that accepts a conduit connection . Air sampling connections accept OD rigid or semi rigid tubing . The Model AFS-460 features a manual reset button to close the switch following actuation . For low current applications use Model AFS-405 with gold contacts .

FEATURES• Adjustable set point• For static or differential pressure• 15A switch rating• Manual reset (Model AFS-460)• Gold contacts (Model AFS-405)• UR, CSA, FM approved• Two-year warranty

C US

SPECIFICATIONS

Action on a rise in differential pressure

CNO

NC

WIRING

C

NC

Opens on a rise in differential pressure

C

NC

C

NC

ALead

BLag

Opens on arise in

differentialpressure

Page 66: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1072

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

1.38 (3.50)

6.13(15.57)2.81

(7.14)

3.25 (8.23)

in(cm)

1.63(4.14)

Two mounting holes3/16 fastener required

1.94 (4.93)

3.88 (9.86)

3.25 (8.23)

0.44(1.12)

Low pressure inlet (B)

High pressure inlet (A)

0.710(1.80)

0.78(1.98)

C NO NC

OPERATION

DIMENSIONS

ADJUSTABLE DIFFERENTIAL PRESSURE SWITCHESAFS SERIES

ORDERING INFORMATION

MODEL DESCRIPTIONAFS-145* Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/8" NPTFAFS-222* Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" compression fittingsAFS-222-112 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" barbed fittingsAFS-262* Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" compression fittingsAFS-262-112 Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" barbed fittingsAFS-405 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), gold contactsAFS-460* Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), SPSTAFS-460-136 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 120 VAC, SPDTAFS-460-137 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 24 VAC, SPDTAFS-460-DSS* Manual reset differential pressure switch, 2" to 12" WC (498 to 2989 Pa), 2 SPST switches

* C models Kele calibration available

Select a mounting location that is free from vibration . The switch must be mounted with the diaphragm in any vertical plane in order to obtain the lowest specified operating setpoint . Avoid mounting with the sample line connections in the up position . Surface mount via the two 3/16" diameter holes in the integral mounting bracket .

The Model AFS-460-DSS has a lead switch (A) and a lag switch (B) . The lead switch trips according to the setpoint knob and the lag switch trips after the lead switch . If dual-switch simultaneous operation is required, order AFS-460-136 (120 VAC power) or AFS-460-137 (24 VAC power) .

Locate sampling probe a minimum of 1-1/2 duct diameters downstream from the air source . Install the sampling probe as close to the center of the airstream as possible .

Refer to the Dimensions drawing to identify the high pres-sure inlet (A) and the low pressure inlet (B), and connect the sample lines as follows:

Positive Pressure Only Connect the sample line to (A); (B) remains open to the atmosphere . Negative Pressure Only Connect the sample line to (B); (A) remains open to the atmosphere . Two Negative Samples Connect the higher negative sample to (B); Connect the lower negative sample to (A) . Two Positive Samples Connect the higher positive sample to (A); Connect the lower positive sample to (B) . One Positive and One Negative Sample Connect the positive sample to (A); Connect the negative sample to (B) .

RELATED PRODUCTS PAGE21122 6" aluminum impact tube, 1/4" OD connection 111321122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing 111360681 Static or total pressure sensing kit 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 67: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1073

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

MountingThe RH-3 and RH-3-2 may be used to sense pressure, vacuum, or differentials of pressure and vacuum . Using sheet metal screws, mount the control vertically on the duct or equipment . Avoid areas of high vibration . Connect the 1/4" tubing to the air flow switch using 1/4" compression fittings . Insert the other end of the tubing into area to be sensed . See ordering information for static pressure tips and duct impact (total pressure) tubes for use with RH-3 and RH-3-2 switches .

AdjustmentThe adjusting screw located in the junction box may be used to change the operating point . The operating range is 0 .05" to 12 .0" W .C . for the RH-3, and 0 .05" to 2 .0" W .C . for the RH-3-2 . The differential is 0 .02" rising to 0 .8" at the highest setting . The switch will operate at 0 .05" and reset before 0 .03" on the low end . It will operate at 12 .0" and reset before 11 .2" on the high end . Rotate the adjusting screw clockwise to increase setting .

Contact Rating 300 VA pilot duty @ 125-277 VAC, 15A resistive @ 125 VAC, 1/4 hp @ 125 VAC, 1/2 hp @ 250 VAC, 2 .4A @ 24 VAC, 0 .5A @ 24-125 VDC

Contact Type SPDTSetpoint Range RH-3 0 .05" to 12 .0" W .C . (12 .5 to 2989 Pa) RH-3-2 0 .05" to 2 .0" W .C . (12 .5 to 498 Pa)Differential 0 .02" W .C . (5 .0 Pa) @ minimum

setting, 0 .8" W .C . (199 Pa) @ maximum setting

Overpressure 0 .5 psig (3 .5 kPa)Operating Temperature -40° to 180°F (-40° to 82°C)Mounting Any vertical planeProcess Connection 1/4" compression, suitable for use

with 1/4" OD copper or plastic tubingApprovals UL listed, file #MH10196, CSAWeight 2 .0 lb (0 .91 kg)Warranty 1 year

DIFFERENTIAL PRESSURE SWITCHRH-3, RH-3-2

DESCRIPTIONThe Columbus Electric Model RH-3 and RH-3-2 differential pressure switches monitor low-air pressure, vacuum, or differentials of air pressure . These switches are commonly used to prove fan operation, to sense dirty filters, and to monitor pressure drop across coils .

Models RH-3 and RH-3-2 are shipped with 1/4" compression fittings, suitable for use with 1/4" OD copper or plastic tubing, and a 12" (30 .5 cm) length of 1/4" plastic tubing .

INSTALLATION

OPERATIONWhen pressure is applied to the high side of the airflow switch or vacuum is applied to the low side, an internal diaphragm moves against and operates the lever of the snap-switch . When the airflow switch is at rest (not operating), the snap-switch N .C . (normally closed) contact is made to the common terminal . When an increase in differential pressure operates the snap-switch, the N .O . (normally open) contact is made to the common terminal . The action of the diaphragm on the snap-switch is the same whether pressure or vacuum is being sensed . The wiring from the air sensing switch to other devices depends upon the application .

SPECIFICATIONS

RH-3

Page 68: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1074

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

Two #6 sheet metal,slotted pan head(mounting screwsprovided)

Scale plate

Junction boxand cover

6/32" Terminalswith screws andcup washers

(Connector with nut and ferrule,will accept 1/4" OD tubing of copper, aluminum, or plastic - bothinlets, typical)

Low pressure inletHigh pressure inlet

Adjustment screw (turn clockwiseto increase setpoint)

0.78(1.98) 0.71

(1.80)

3.38(8.58)

0.44(1.11)

1.31(3.33)

1.38(3.50)

3.75(9.53)

3/16" diameterTwo mounting

holes

3.88(9.85)

1.94(4.93)

2.81(7.14)

in(cm)

6.13(15.7)

1.63(4.10)

3.25(8.25)

0.671(1.70)

C

NO

NC

Contactdesignations

MODEL DESCRIPTIONRH-3 0.05" to 12.0" W.C. (12.5 to 2989 Pa)RH-3-C 0.05" to 12.0" W.C. (12.5 to 498 Pa) custom calibrationRH-3-2 0.05" to 2.0" W.C. (12.5 to 2989 Pa)RH-3-2-C 0.05" to 2.0" W.C. (12.5 to 498 Pa) custom calibration

DIMENSIONS

DIFFERENTIAL PRESSURE SWITCHRH-3, RH-3-2

RELATED PRODUCTS PAGE21122 6" aluminum impact tube, 1/4" OD connection 111321122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing 111360681 Static or total pressure sensing kit 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 69: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1075

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Contact Rating 1/10 hp @ 120-277 VAC; 28 VA pilot duty @ 24 VAC; 125 VA pilot duty @ 120 VAC

Contact Type SPDTSetpoint Spring Range Black 0 .10" to 0 .30" W .C . (25 to 75 Pa) Neutral 0 .30" to 0 .90" W .C . (75 to 224 Pa) Yellow 0 .90" to 2 .50" W .C . (224 to 623 Pa) Red 2 .5" to 5 .0" W .C . (623 to 1245 Pa) Blue 5 .0" to 10 .0" W .C . (1245 to 2490 Pa)Overpressure 14" W .C . (3486 Pa)Life Expectancy 100,000 cycles minimum

Operating Temperature -40° to 190°F (-40° to 88°C)Enclosure Glass-filled polycarbonateDiaphragm Material Post-cured siliconeProcess Connection 1/4" OD accepts 3/16" ID flexible

tubingWiring Terminations Male quick connect terminals 1/4" x 0 .032Approvals CE, CSA, UL Recognized File

MH6213Weight 0 .25 lb (0 .11 kg)Warranty 1 year

ADJUSTABLE DIFFERENTIAL PRESSURE SWITCH KITNS2-0000-02

Common

Normally closedterminal

0.4 (10)

terminal

3.08(78)

0.59 (15)

1.15 (29)1.27 (32)

1.67 (42)

3.06 (78)3.15 (80)

3.45 (88)

connectorNegative pressure

NS

2-0

001-

00D

AT

EC

OD

E

Positive pressureconnector

Normally openterminal

RU

R

CU

S

DESCRIPTIONThe economical Cleveland Controls Model NS2 Adjustable Differential Pressure Switch Kit is designed for positive, negative, or differential pressure monitoring with actuation on pressure rise or fall . The set point range can be field configured between 0 .10"w .c . to 10 .0"w .c . using the appropriate spring included in the kit . The kit includes a switch with quick-connect terminals, 5 different springs to change the set point range, orifice plugs to restrict air flow, mounting brackets, a hex wrench, and instructions .

FEATURES• Five pressure ranges in one unit• Field adjustable setpoint and setpoint range• Actuated by pressure or vacuum• SPDT switch

DIMENSIONS AND WIRING

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTIONNS2-0000-02 Adjustable differential pressure switch kit

NS2-0000-02

Page 70: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1076

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Contact Rating 300 VA pilot duty @ 115-277 VAC, 15A non-inductive to 277 VAC

Contact Type SPDTSetpoint Range 0 .15" to 5 .0" W .C . (37 .3 to 1245 Pa)Differential Progressive, increasing from 0 .05"

W .C . at minimum setpoint to 0 .3" W .C . at maximum setpoint

Overpressure 0 .5 psig (3 .5 kPa)Life Expectancy 100,000 cycles minimumOperating Temperature -40° to 180°F (-40° to 82°C)Mounting Any vertical plane, avoid upward

pressure connectionsProcess Connection RFS-4001-025 1/4" compression, suitable for use

with 1/4" copper or plastic tubing RFS-4001-031 Tri-barb connectors for 1/8", 1/4"

and 5/16" ID tubingWiring Terminations Screw terminals with cup washersApprovals UL File #MH6213, CSAWeight 0 .9 lb (0 .4 kg)Warranty 2 years

DIFFERENTIAL PRESSURE SWITCHESRFS-4001

4.625(117)

3.75 (95)

4.125 (105)

1.00(25)

4.098 (104)

1.365 (35)

2.959 (75)

0.798 (20)

0.173 (4)

1.421 (36)LOW

HIGH

DESCRIPTIONThe Cleveland Controls Models RFS-4001-025 and RFS-4001-031 Differential Pressure Switches are general-purpose, airflow-proving switches designed for HVAC and building automation applications . They may be used to sense positive, negative, or differential air pressure .

The plated housing contains a diaphragm, calibration spring and snap-acting switch . The Model RFS-4001-025 pressure connections located on each side of the diaphragm, accept copper or flexible 1/4" OD tubing . The Model RFS- 4001-031 has tri-barb connectors that accept 1/8", 1/4", and 5/16" ID flexible tubing . An enclosure cover guards against accidental contact with the live-switch terminal screws and the setpoint-adjusting screw . The enclosure will accept a 1/2" conduit connection .

FEATURES• Two-year warranty• Adjustable setpoint • Knockout for 1/2" conduit • Enclosed terminals • Compression or barb fittings

DIMENSIONS

SPECIFICATIONS

ORDERING INFORMATION

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

RFS-4001-031

MODEL DESCRIPTIONRFS-4001-025 Differential pressure switch 0.15" to 5.0" W.C., 1/4" compression fittingsRFS-4001-025-C Differential pressure switch 0.15" to 5.0" W.C., 1/4" compression fittings, custom calibratedRFS-4001-031 Differential pressure switch 0.15" to 5.0" W.C., tri-barb fittingsRFS-4001-031-C Differential pressure switch 0.15" to 5.0" W.C., tri-barb fittings, custom calibratedRFS-4001-092 Differential pressure switch

Page 71: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1077

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

4.62 (11.7)5.25 (13.3)

.070 Ø(0.2)

4.0(10.2)

2.13 (5.4)

0.25 (0.6)Male disconnects

High pressure inlet Low pressure inlet0.5 (1.3)1.22 (3.1)

CO

MN

C

NO

3.75 (9.5)4.12 (10.5)

Contact Rating 5A resistive, 120-277 VAC, 60 Hz; 1A pilot duty (120 VA) @ 120 VACContact Type SPDTSetpoint Range RFS-495-011 0 .20" to 1 .0" W .C . (49 to 249 Pa) RFS-495-013 1 .0" to 4 .0" W .C . (249 to 996 Pa)Overpressure 1 psi (0 .06 bar)Life Expectancy 100,000 cycles minimum @ 1 psi

maximum each cycle and maximum rated load

Operating Temperature -40° to 190°F (-40° to 88°C)Diaphragm Material EPDMEnclosure ThermoplasticProcess Connection Barbed fittings for 1/4" ID or 3/8" ID flexible tubingApprovals UL recognized, file #MH6213, CSA, CEWeight 0 .25 lbs (0 .11 kg)Warranty 1 year

DESCRIPTIONThe economical Cleveland Controls RSS Series Adjustable Differential Pressure Switches are designed for positive, negative, or differential pressure monitoring with actuation on pressure rise or fall . The unit is constructed with a high temperature thermoplastic housing, an internal EPDM diaphragm, and an externally mounted snap action switch . Male quick connect terminals allows easy installation . The field adjustability makes these switches ideal for light industrial and commercial HVAC applications .

FEATURES

• Adjustable set point• Actuated by a pressure or vacuum air flow• Quick connect terminals• 5A, SPDT switch

DIMENSIONS

ADJUSTABLE DIFFERENTIAL PRESSURE SWITCHRSS SERIES

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTIONRSS-495-011 Adjustable differential pressure switch, 0.20" to 1.0" W.C. (49 to 249 Pa)RSS-498-013 Adjustable differential pressure switch, 1.0" to 4.0" W.C. (249 to 996 Pa)

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

RSS-495-011

Page 72: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1078

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Contact Rating 15A resistive, 277 VAC, 60 Hz; 300 VA pilot duty @ 115-277 VAC, 60 Hz

Contact Type Dual SPDTSetpoint Range 0 .05" to 2 .0" W .C . (12 .5 to 498Pa)Differential Progressive, 0 .02" W .C . (5 .0 Pa) @

minimum setpoint to 0 .8" W .C . (199 Pa) @ maximum setpoint

Overpressure 0 .5 psi (0 .03 bar)Life Expectancy 100,000 cycles minimum @ 1 psi

maximum each cycle and maximum rated load

Operating Temperature -40° to 176°F (-40° to 82°C)Enclosure Zinc-coated steelDiaphragm Material SiliconeMounting Diaphragm in vertical planeProcess Connection Compression fittings for 1/4" OD

rigid or semi-rigid tubingWiring Terminations Screw terminals with cup washersApprovals CSA, UL Recognized File MH6213Weight 1 .5 lb (0 .68 kg)Warranty 1 year

DESCRIPTIONThe Cleveland Controls Model DDP-109 Dual Setpoint Differential Pressure Switch provides dual switch action for HVAC and energy management applications . Two separately operated, independently adjustable SPDT snap-acting switches are mounted on a common foot bracket . Since the switches are set independently, an adjustable "deadband" can be established for control circuits requiring both high and low actuation points . The unit can measure differential pressures up to 2" W .C .

FEATURES• Dual adjustable setpoints• Independent switch operation• Actuated by a pressure or vacuum air flow• 15A SPDT switches

CNO Alarm

Normal

Normal

Alarm

NC

NO

NC

C

To prove excessive air flow or pressure:

To prove insufficient air flow or pressure:

WIRING

DUAL SETPOINT DIFFERENTIAL PRESSURE SWITCHDDP-109

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTIONDDP-109 Dual setpoint differential pressure switch, 0.05" to 2.0" W.C. (12.5 to 498 Pa)

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

DDP-109

Page 73: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1079

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Contact Rating 15A resistive to 277 VAC, 60 Hz 300 VA pilot duty @ 115-270 VAC 15A resistive to 277 VAC, 60 Hz 300 VA pilot duty @ 115-270 VACContact Type SPDTSetpoints Fixed, 0 .05" W .C . (12 .5 Pa), ±0 .02"

W .C .Differential 0 .02" W .C ., ±0 .01" W .C .Overpressure 0 .5 psi (3 .5 kPa bar)Life Expectancy 100,000 cycles minimum @ 0 .5 psi

maximum each cycle and maximum rated load

Operating Temperature -40° to 180°F (-40° to 82°C)Mounting Diaphram in vertical plane to obtain

operating set pointProcess Connection Barbed fittings for 1/4" ID flexible

tubingWiring Terminations Male quick connect terminalsApprovals CE, CSA, FM, UL Recognized

File MH6213Weight 1 .2 lbs (0 .5 kg)Warranty 2 years

FIXED DIFFERENTIAL PRESSURE SWITCHDFS-221

3.25 (8.2) 2.94 (7.4)1.38(3.5)0.44

(1.1)

0.78(1.9)

0.71(1.8)

1.63(4.1)

2.84(7.1)

6.12(15.6)

3.88 (9.8)

1.94 (4.9)

4.38 (11.1)

0.19 (5)dia hole

(2 places)

Highpressureinlet

Low pressureinlet

CO

MN

.O.

N.C

.

DESCRIPTIONThe Cleveland Controls Model DFS-221 Fixed Differential Pressure Switch is an airflow proving switch designed for duct heater, oven, and other HVAC and energy management applications . The unit senses positive, negative, or differential pressure with SPDT switch actuation on pressure rise at 0 .05 WC, ±0 .02 WC . The model DFS-221 is equipped with two barbed sample line connections for use with ID flexible tubing . Electrical connections are made via male quick connect terminals for easy installation .

FEATURES• Fixed set point at 0.05 W.C. (12.5 Pa)• Prove excessive or insufficient pressure• Quick connect terminals• 15A, SPDT switch

CNO Alarm

Normal

Normal

Alarm

NC

NO

NC

C

To prove excessive air flow or pressure:

To prove insufficient air flow or pressure:

WIRING

FMAPPROVED

USC

DIMENSIONS

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTIONDFS-221 Fixed differential pressure switch, 0.05" W.C. (12.5 Pa)

DFS-221

Page 74: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1080

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

Contact Type SPDTContact 15A @ 120-240 VACOperating Temperature -30° to 180°F (-34° to 82°C)Process Connection 1/8" FNPTDimensions 3-1/2" diameter x 2-11/32" depth (8 .9 x 3 .4 cm)Weight 1 .28 lb (0 .58 kg)Approvals UL File #E38121

DIFFERENTIAL PRESSURE SWITCHES1910 SERIES

DESCRIPTIONThe Dwyer 1910 Series Differential Pressure Switches are designed to monitor the differential pressure of air in HVAC applications . These automatic reset switches are available in ranges from 0 .07" to 20" W .C . (17 .4 to 4982 .0 Pa) and have SPDT screw type electrical connections . The optional Model A-602 air filter kit includes two static pressure tips, aluminum tubing, and fittings, and it allows the 1910 Series to monitor filter pressure drop .

SPECIFICATIONS 1910-5

DESCRIPTIONThe Dwyer Model 1900-5-MR Manual Reset Pressure Switch is designed to monitor duct static and shut down the blower when excess pressure occurs . The switch must be manually reset before the system can start again . Switch contacts are SPDT with solder-type connections . The Model 1900-5-MR measures static pressure only, not differential pressure . Order the A-399 duct pressure kit separately .

MANUAL RESET PRESSURE SWITCH1900-5-MR

ORDERING INFORMATION

1900-5-MR

RELATED PRODUCTSA-399 Duct pressure kit for Series 1910 and 1900-5-MR, includes mounting flange, tubing, and 1/8" FNPT fitting.

FMAPPROVED

USC

Contact Type SPDTOperating Temperature -30° to 180°F (-39° to 82°C)Process Connection 1 .8" FNPTDimensions 3-1/2" dia x 2-11/32" depth (8 .9 x 6 .4 cm)Weight 1 .3 lb (0 .58 kg)

SPECIFICATIONS

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-602 Mounting kit for air filter applications. Includes two pressure tips, two 5-foot lengths of aluminum tubing and two adapters. T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

MODEL DESCRIPTION1910-0 Pressure Switch 0.15 to 0.50 "WC1910-00 Pressure Switch 0.07 to 0.015 "WC1910-1 Pressure Switch 0.4 to 1.6 "WC1910-10 Pressure Switch 3.0 to 11.0 "WC1910-5 Pressure Switch 1.4 to 5.5 "WC1910-20 Low differential pressure switch

*NOTE: Add a "-C" at the end of the model number to request special calibration

MODEL DESCRIPTION1900-5-MR Manual reset pressure switch, 1.5-5.5" W.C.1900-5-MR-C Manual reset pressure switch, 1.5-5.5" W.C. with custom calibration1900-1-MR Manual reset pressure switch, 0.4-1.6" WC1900-10-MR Manual reset pressure switch, 3-11" WC

*NOTE: Add a "-C" at the end of the model number to request special calibration

Page 75: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1081

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Overpressure 1 psig (6 .9 kPa)Indicator Yes, visual scaleElectrical Ratings P32AF Close differential, 1/4 hp P32AC Standard differential, 1/2 hpOperating Temperature -40°F (-40°C) to 165°F (75°C)Mounting P32AX-1 L Bracket P32AX-2 U Bracket

Process Connection High pressure: metal 1/8" FNPT inside x 1/2" NPSM outside; low pressure: molded 1/8" FNPT

Approvals UL Listed, file MH10588Weight 1 .0 lb (0 .45 kg); 1 .1 lb (0 .5 kg)

with fittingsWarranty 1 year

DIFFERENTIAL PRESSURE SWITCHP32 SERIES

DESCRIPTIONThe Johnson Controls P32 Series Differential Pressure Switch is used to detect differential pressure or low positive gauge pressure by using only the high pressure connection and leaving the low pressure connector open . It can also detect vacuum by using only the low pressure connection and leaving the high pressure connector open to ambient pressure .

The P32 Series is factory set at the bottom of its operating range with the diaphragm in a vertical plane . The setting will change if mounted in other positions .

The P32AF has a close differential, and the P32AC has a standard differential .

FEATURES• Easy-to-read setpoint scale• Versatile mounting options• Durable construction• Setpoint switching repeatability• One-year warranty

APPLICATION• Air proving with electric duct heaters, humidifiers,

and more• Maximum air flow controller for variable volume

systems• Reheat duct-powered systems• Clogged filter detection• Detection of icing of air conditioning coils and

initiation of defrost cycle

SPECIFICATIONS

P32 Switch with L Bracket

ORDERING INFORMATION

Specify model number as shown in specifications above .

Motor Ratings VACAC full load ampAC locked rotor amp

1205.834.8

Pilot duty - 125 VA, 24 VAC; 360 VA, 120-277 VAC Pilot duty - 125 VA, 24 VAC; 360 VA, 120-277 VACNon-inductive or resistive load 10A, 24-277 VAC Non-inductive or Resistive Load 10A, 24-277 VAC

2083.3520.1

2402.9

17.4

Motor Ratings VACAC full load ampAC locked rotor amp

1209.8

58.8

2085.6533.9

2404.9

29.4

Model

P32AC-1P32AC-2*P32AF-1P32AF-2*

ContactAction

SPDTSPDTSPDTSPDT

Setpoint

AdjustableAdjustableAdjustableAdjustable

Bracket

LULU

ScalePlate

YesYesYesYes

Differential"W.C. (Pa)

*Supplied with 1/4" compression fitting, 4" extension tube, two mounting screws, gasket, angle barb fitting installed

Minimum Setpoint0.07 (17.4)0.04 (10.0)0.025 (6.2)0.025 (6.2)

Maximum Setpoint0.6 (149.5)0.20 (49.8)0.11 (27.4)0.11 (27.4)

Range"W.C. (Pa)

0.15-12 (37.4-2990)0.05-5 (12.5-1246)0.05-5 (12.5-1246)0.05-5 (12.5-1246)

Y

B

R

P32 Series

Action on increaseof pressure

RELATED PRODUCTSFTG-18A-600R Sensing tube kit

Page 76: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1082

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Contact Rating 2 .0 A @ 250 VAC (with inductive load)Contact Type SPDTDifferential A2G40-S00-7C-EH 0 .04" W .C . (10 Pa) A2G40-S00-7C-EI/EJ 0 .08" W .C . (20 Pa) A2G40-S00-7C-EK 0 .12" W .C . (30 Pa) A2G40-S00-7C-EL 0 .30" W .C . (80 Pa) A2G40-S00-7C-EM 0 .70" W .C . (180 Pa)Operating Pressure 200" W .C . (49 .8 kPa)Measurement Range A2G40-S00-7C-EH .08 to .80" W .C . (20 to 200 Pa) A2G40-S00-7C-EI 0 .12 to 1 .2" W .C . (30 to 300 Pa) A2G40-S00-7C-EJ 0 .12 to 2 .0" W .C . (30 to 500 Pa) A2G40-S00-7C-EK 0 .16 to 2 .4" W .C . (40 to 600 Pa)

A2G40-S00-7C-EL 0 .40 to 6 .0" W .C . (100 to 1500 Pa) A2G40-S00-7C-EM 2 .0 to 18 .0" W .C . (500 to 4500 Pa)Media Compatibility air and other non-combustible gasesOperating Temperature -40° to 185°F (-40° to 85°C)Mounting Enclosure positioned in any vertical

planeEnclosure NEMA 3 Process Connection Hose barb nozzles (ABS) for 3/16"

and 1/4" hose IDWiring Terminations Screw terminals, PG-gland M16Approvals CE, IP54 NEMA 3Weight 0 .3 lb (0 .15 kg)Warranty 2 years

DESCRIPTIONThe Wika A2G-40 Series differential pressure switch is useful for DP and clogged filter monitor across filter banks; overpressure detection in rooms; and air flow proving for direct fire AHU's or duct heaters . The clearly visible adjustment knob makes it easy to set the switchpoint without tools . This SPDT switch can be set up as a N .O . or N .C . contact . It features a robust housing in a compact design .

FEATURES• Adjustment knob enables easy switch point setting• Switch can be set up as N.O. or N.C.• Compact size

DIFFERENTIAL PRESSURE SWITCHA2G-40 SERIES

SPECIFICATIONS

A2G-40

Micro SwitchOne (1) SPDT (single pole double throw)

1-3 opens / 1-2 cloese on reaching the set point(differential pressure)

WIRING

Page 77: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1083

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

ORDERING INFORMATION

MODEL DESCRIPTIONA2G40-S00-7C-EH Differential pressure switch, .08 to .8 in WCA2G40-S00-7C-EI Differential pressure switch, 0.12 to 1.2 in WCA2G40-S00-7C-EJ Differential pressure switch, 0.12 to 2.0 in WCA2G40-S00-7C-EK Differential pressure switch, 0.16 to 2.4 in WCA2G40-S00-7C-EL Differential pressure switch, 0.40 to 6.0 in WCA2G40-S00-7C-EM Differential pressure switch, 2.0 to 18.0 in WC

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901A-308-K Duct static pressure fitting, 1/4" barb 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-301-K Duct static pressure tip, 1/4" compression 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113

DIFFERENTIAL PRESSURE SWITCHA2G-40 SERIES

DIMENSIONS

Page 78: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1084

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

P10BC, P10FCElectrical ratings

Motor ratings VACAC full load ampAC locked rotor ampNon-inductive amp

Model

P10BC-7

P10FC-4

P10BG-3

Numberof

stages1

2

1

12016.096.016.0

Pilot duty - 125 VA @ 24-277 VAC

2089.2

55.29.2

2408.0

48.08.0

2777.042.07.2

P10BG

Maximum Allowable Pressure: 150 psig (1034 kPa)

Motor Ratings VACAC full load ampAC locked rotor ampNon-inductive amp

1206.036.06.0

Pilot duty - 125 VA @ 24-277 VAC

2083.420.43.4

2403.018.03.0

277____2.6

Contactaction

SPDT

2-SPDT

SPDT

Pressureconnector

NPT*1/8"

1/8"

1/8"

Weightlb

(kg)1.0 (0.45)

1.5 (0.68)

1.0 (0.45)

Factory setting

*Includes 1/4" barb fitting installed

psig(kPa)

12 (83) (R-Y cut-in)

12 (83)(R-Y cut-in)

(R-Y cut-out)Low stage

8 (55)

(R-Y cut-in)High stage

12 (82)

Switch Diffpsig (kPa)

2 (14)

0.2 (1.4)

Lowstage2 (14)

Highstage2 (14)

Rangepsig(kPa)

3-20(21-138)

2-20(15-138)

ORDERING INFORMATION

DESCRIPTIONThe Johnson Controls P10 Series Pressure Switches use changes in control air pressure to open or close an electrical circuit . The common terminal is red . The red-to-yellow terminals close an electrical circuit on a rise in pressure; the red-to-blue terminals close a circuit on a drop in pressure .

FEATURES• Easily accessible screw terminals for field wiring • Snap-acting contacts in a dust-tight enclosure • Visible calibration scale • Field adjustment possible with cover on or removed • Gas and oil resistant nylon-reinforced diaphragm • One-year warranty• Approvals UL File E6688 and CS LR948

B

Y

R

Action on increaseof pressure

WIRING

APPLICATIONTypical applications include pressure-electric switches in pneumatic systems, control of pumps or small air compressors, and pressure-electric interlock of fluid flow systems .

Specify model number as shown in specifications above.

PRESSURE SWITCHP10 SERIES

SPECIFICATIONS

P10BC-7

Page 79: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1085

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Contact Rating 5A resistive and inductive @ 125 VAC and 250 VAC, 1/4 hp 5A resistive and 3A inductive @ 30 VDC 0 .5A resistive and 0 .25A inductive @

125 VDC gold clad silver contacts for minimum

loads of 5 mA @ 6 VDC, 2 mA @ 12 VDC, and 1 mA @ 24 VDCContact Type SPDTAdjustments Multiturn screw, accessible from

outside enclosureRepeatability Typically ±1% of spanOverpressure 150 psid (1034 .3 kPa) with surges

up to 160°F (71°C) air temp, without loss of adjustability

Operating Pressure 0-150 psig (0-1034 .3 kPa) up to 160°F (71°C) air temp

Life Expectancy 10 million cycles (actual life depends on load and cycle frequency)

Shock 15G, 10 ms duration

Vibration Resistance MIL STD 810C, 2 .5G, 5-500 CPSOperating Temperature 30° to 160°F (-1° to 71°C)Wetted Parts Polyurethane diaphragm, ethylene

propylene, polysulphone, brassMedia Temperature Range 200°F (93°C) @ 100 psig (689 .5

kPa) working pressureStorage Temperature -20° to 180°F (-29° to 82°C)Enclosure Rating Reinforced nylon body, zinc-plated

steel cover with neoprene gasket, NEMA 4

Mounting Surface mount with two screws through clearance holes or mount by ports

Process Connection 1/4" FNPT brassWiring Terminations 7/8" hole for 1/2" conduit connector

(not provided), three screw terminals 16 AWG max wire size

Approvals UL File E42272, CSA, CEWeight 0 .4 lb (0 .18 kg)Warranty 1 year

DIFFERENTIAL PRESSURE SWITCH24-013, 24-014

DESCRIPTIONThe Delta-Pro Models 24-013 and 24-014 NEMA 4 Differential Pressure Switches offer a unique blend of small size, excellent performance, environmental protection, and attractive price . They can be used with liquids or gases .

The precision snap-acting switch and sensitive opposing diaphragms combine to provide a narrow deadband and repeatability of approximately ±1% of span . Mechanical contact life is 10 million cycles, and actual switch life can be very long with typical pilot duty loads . The Delta-Pro NEMA 4 enclosure is small, yet it can still accommodate a 1/2" NPT conduit connection and terminal block wiring .

The Delta-Pro is not only lightweight but also strong and durable . The multiturn adjustment screw is externally accessible for convenience and excellent resolution . The Delta-Pro's force-balance design provides excellent vibration resistance .

FEATURES• SPDT switch with screw terminals• Gasketed zinc-plated steel cover• Strong, corrosion-resistant polyester enclosure• External, multiturn adjusting screw for excellent

resolution• 7/8" hole for 1/2" NPT conduit connection• Corrosion-resistant brass port• Front accessible holes for surface mounting• NEMA 4 enclosure

APPLICATIONModels 24-013 and 24-014 are used typically to sense differential pressure across devices such as oil or water filters, pumps, heat exchangers, chillers, coils, etc . They normally provide an alarm or shutdown function in applications where there is insufficient flow in a system or when excessive pressure differential indicates a problem . They may also be used to indicate pump status .

SPECIFICATIONS

24-013

Page 80: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1086

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

MODEL*

24-01324-014

PORT

1/4 FNPTBrass

SWITCH

5A5A

DEADBAND

0.75 (5.2)1.0 (6.9)

ADJUSTABLE SETTING RANGE psid (kPa)

Minimum1.0 (6.895 kPa)4.0 (27.6 kPa)

9.0 (62.1 kPa)43.5 (299.9 kPa)

Maximum

On fall

* Add the suffix -C to have the unit precalibrated. Please specify the setpoint.

Minimum2.0 (13.8 kPa)5.5 (37.9 kPa)

10.0 (69.0 kPa)45.0 (310.3 kPa)

Maximum psig (kPa)On rise

NC NO COM

3.5(8.89)

Clearfor #6screw

1.84(4.68)

0.875dia

0.91 (2.31)

2.65 (6.75)

2.37(6.03)

Settingadjustment

2.0 (5.08)

3.13 (7.94)

in(cm)

2.375(6.03)

Top View

Factory adjustment only, do not change

INSTALLATION

DIMENSIONS

DIFFERENTIAL PRESSURE SWITCH24-013, 24-014

ORDERING INFORMATION

MODEL DESCRIPTION24-013 Differential pressure switch 1-10 psi SPDT24-013-C Differential pressure switch 1-10 psi SPDT, custom calibrated24-014 Differential pressure switch 4-45 psi SPDT24-014-C Differential pressure switch 4-45 psi SPDT, custom calibrated24-020 Differential pressure switch 1-10 psi SPDT

PERFORMANCE CHART

MountingMount unit in any position . Locate where shock and vibration are minimal and ambient temperature is below 160°F (71°C) .

Surface mountingInsert two #6 screws through holes on 2" (5 .08 cm) centers (recommended mounting for maximum vibration resistance) .

Suspended unit mountingMount unit from its two ports . Always hold a wrench on the pressure port when making pressure connection .

Making pressure connectionConnect the high side pressure to the port labeled high . Use a wrench on the pressure port and hold the unit steady . Then, thread a 1/4 NPTM fitting into the port .

WiringBack out the screw terminal just enough to put stripped wire under this terminal block clamp . Maximum wire size is 16 AWG .

Setpoint adjustmentUse a screwdriver to turn the external adjusting screw . Turn “in” (clockwise) to increase differential pressure setting . For best setting accuracy, set the switch using the actual working pres-sures encountered in the application . The switch will make on a differential pressure rise to setpoint and break on a fall below setpoint minus the deadband (subtractive deadband) .

CAUTION: Never tighten by turning the switch body into the fitting.

Page 81: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1087

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

These differential pressure controls are used as operating controls and/or alarm controls . They are available for applications sensing air, oil, or liquid . Typical applications include proof-of-flow across a chiller or water-cooled condenser, proof-of-flow in a heating system, and lube oil pressure sensing on refrigeration compressors . In the water chiller application, the control provides low temperature protection . On proof-of-flow applications, the control measures pressure drop across two different points in either a closed water circulating system or a city water supply system . On a proof-of-flow application in a water chiller system, the control activates an alarm or signal light to warn the operator if a loss of water flow occurs .

DESCRIPTIONThe Johnson Controls Model P74 Differential Pressure Switch measures the difference in pressure exerted upon its two sensing elements and operates an SPDT switch at the differential pressure setpoint . The setpoint may be adjusted without removing the cover and is visible on a calibrated scale .

FEATURES• Brass bellows • Completely enclosed contact mechanism • Externally adjustable with visual setpoint scale • Universal mounting bracket supplied • Heavy-duty elements withstand high overrun pressure • For air, oil, or other liquids• One-year warranty

APPLICATIONS

DIFFERENTIAL PRESSURE SWITCHP74 SERIES

SPECIFICATIONS

P74FA-1C

ORDERING INFORMATION

Specify model number as shown in specifications above.

Model*

P74FA-1

P74FA-5

P74JA-2

P74EA-8

Pressuredifferential range

psid (kPa)FAIC

8-60(55-414)

2-30(14-207)

Switchdifferentialpsig (kPa)

1.5(10)

3.5(24)

Maximum overrun pressure

psig (kPa)

180(1241)

Connectorsize

1/4" maleflare

1/4" FNPT

1/4" maleflare

36" capillarywith 1/4" flare

nut

Switchaction

SPDTsnap-acting

SPDTsnap-acting

SPDTfloatingSPDT

snap-acting

Electricalrating

6A120V, 50/60 Hz

6A120V, 50/60 Hz

1A24V, 50/60 Hz

16A120V, 50/60 Hz

Page 82: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1088

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Setpoint Range J21K-140 0 to 6 psi (0 to 41 kPa) J21K-150 0 to 40 psi (0 to 276 kPa) J21K-232 0 to 25 psi (0 to 172 kPa) J21K-254 0 to 90 psi (0 to 621 kPa) J21K-357 0 to 70 psi (0 to 483 kPa)Operating Pressure J21K-140 30" Hg vac to 30 psi (1241 kPa) J21K-150 30" Hg vac to 180 psi (1241 kPa) J21K-232 30" Hg vac to 110 psi (759 kPa) J21K-254 30" Hg vac to 120 psi (828 kPa) J21K-357 30" Hg vac to 350 psi (2413 kPa)Contact Rating 15A resistive, 125/250/480 VACContact Type SPDTDeadband J21K-140 0 .1 to 0 .4 psi (0 .7 to 3 kPa) J21K-150 0 .3 to 0 .7 psi (2 to 5 kPa) J21K-232 0 .6 to 1 psi (4 to 7 kPa) J21K-254 2 to 4 psi (14 to 28 kPa) J21K-357 2 to 4 psi (14 to 28 kPa)Operating Temperature -40° to 160°F (-40° to 71°C)Wetted Parts Brass or phosphor bronze bellowsProcess Connection 1/4 NPTFEnclosure Type 4X (with water tight conduit

fitting)Approvals UL listed, file #E42272, CEWeight 2 lb (0 .9 kg)Warranty 1 year

DIFFERENTIAL PRESSURE SWITCHESJ21K SERIES

1.06 (1.7)

4.22 (10.7)1.73(4.4)

0.33 (0.8)

0.56 (1.4)

1.88(4.8)

.875 (1.2)diameter hole

1.25(3.2)

Clearance for1/4 screw

A

2.66(6.8)

DESCRIPTIONThe United Electric J21K Series Differential Pressure Switches utilize opposing metal bellows to detect pressure differences between two pressure sources . When the pressure at the high port exceeds the pressure at the low port by a pre-determined amount (setpoint), the mechanism operates a single snap-action switch . The control setpoint can be adjusted by turning the internal adjustment hex screw .

FEATURES• Adjustable setpoint• Sealed metal bellows• 15A switch rating• Epoxy coated enclosure

DIMENSIONS

SPECIFICATIONSJ21K

ORDERING INFORMATION

MODEL DESCRIPTIONJ21K-140 Differential pressure switch, brass bellows, 0 to 6 psi (0 to 41 kPa)J21K-150 Differential pressure switch, brass bellows, 0 to 40 psi (0 to 276 kPa)J21K-232 Differential pressure switch, bronze bellows, 0 to 25 psi (0 to 172 kPa)J21K-254 Differential pressure switch, bronze bellows, 0 to 90 psi (0 to 621 kPa)J21K-357 Differential pressure switch, stainless steel bellows, 0 to 70 psi (0 to 483 kPa)

"A" DimensionJ21K-140/150 8 .0" (20 .5 cm)J21K-232/254 6 .5" (16 .6cm)K21K-357 6 .875" (17 .46 cm)

Page 83: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1089

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 9 .6 to 32 VDC, <25mAContact Rating 0 .5A DC PNP (sourcing)Contact Type 1 NO, 1 NC, open collector transistorAccuracy <±2 .5% of full scaleRepeatability <±0 .5% of full scaleMeasurement Range PK6224 0 to 145 psi PK6222 0 to 1450 psi PK6220 0 to 5800 psiLife Expectancy 50 million switching cyclesVisual Indication Power Green LED Switching status

Yellow LED (Energized = Switched)Shock 50g (11ms)Operating Temperature -13° to 176°F (-25° to 80°C)

Wetted Parts Stainless 316LMedia Temperature Range

-13° to 176°F (-25° to 80°C)Enclosure Rating IP67, PBT (Pocan); PC (Makrolon);

FPM (Viton); stainless steel 316LProcess Connection ¼" NPTWiring Terminations 4 pin M12 Electrical connector (order separately)Dimensions 1 .06" diameter x 2 .78"H (2 .7 x 7 .06 cm)Approvals UL File E174189, CEWeight 0 .2 lb (0 .091 kg)Warranty 2 years

PRESSURE SWITCHPK SERIES

1.06 (2.7)

2.7 1/4'' NPT

M12x1

0.51

(1.3

)

0.30

(0.

75)

2.39

(6.

1)2.

78 (

7.1)

1

in (cm)

DESCRIPTIONThe IFM Efector PK Series is a low cost series of pressure switches . Each switch uniquely features a set of two radial dials for set point and reset . The PK Series has one normally open and normally closed contact and a green LED for power indication and a yellow LED for switching status . Each switch carries an IP67 rating for protection for the harshest of environments . The PK Series is available in three models that will switch on pressures ranges up to 5800 psi .

FEATURES• Two, easy to use dual setup dials• Solid state electronics• Two PNP switching outputs (1-NO, 1-NC)• No software needed• Local LEDs for power and switching status

4

12

3

1: V+2: Switched output NC4: Switched output NO3: V- (Blue) common

4: 2:

1

2

4

3

V+

V-

Switched output NC

Switched output NOBlack

Blue

Brown

White

3 3

WIRINGDIMENSIONS

SPECIFICATIONS

PK Series

Page 84: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1090

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

SETTING / CONNECTION DIAGRAM

PRESSURE SWITCHPK SERIES

3: A green LED inidcates power on and supply voltage normal4: Process connection ¼” NPT; tightening torque 25 Nm5: Setting marks6: Yellow LED: Set value reached, OUT1 = ON / OUT2 = OFF7: internal thread M5

ORDERING INFORMATION

MODEL DESCRIPTIONPK6220 PK Series pressure switch, 0 to 5800 psi, 1 NO 1 NC contactsPK6222 PK Series pressure switch, 0 to 1450 psi, 1 NO 1 NC contactsPK6224 PK Series pressure switch, 0 to 145 psi, 1 NO 1 NC contacts

1

2

3

4

5

6

7

Set

Reset

12

3 4

pnp

500mA

500mA

pnp

9.6 to32 VDC

1: Locking ring: unlock the pressure switch by rotating the locking ring (1) to the unlocked position

2: Set and Reset Rings: Set rings to desrired "Set" and "Reset" positions

a) Minimum distance between Set and Reset = 2% of the final value of the measuring range . b) To obtain the setting accuracy: Set the rings to the

minimum value, then set the requested value .

RELATED PRODUCTSEVC001 6’ foot straight connectorEVC002 15’ straight connectorEVC003 30’ straight connectorEVC004 6’ right-angled connectorEVC005 15’ right-angled connectorEVC006 30’ right-angled connectorEVC008 15’ right angled connector with LED indicationEVC009 30’ right angled connector with LED indicationE30094 PK Series protective cover

Page 85: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1091

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Setpoint Range J54-24 3 to 30 psi (21 to 207 kPa) J54-25 10 to 100 psi (69 to 690 kPa) J54-27 30 to 300 psi (207 to 2070 kPa) J54-28 50 to 500 psi (345 to 3448 kPa)Deadband J54-24 0 .4 to 1 .5 psi (3 to 10 kPa) J54-25 1 to 2 .5 psi (7 to 17 kPa) J54-27 1 .3 to 4 psi (9 to 28 kPa) J54-28 1 .5 to 5 psi (10 to 34 kPa)Contact Rating 15A non-inductive, 125/250/480

VAC, 60 HzContact Type SPDTOverpressure 200 psi (1379 kPa) above setpoint,

maximum 600 psi (4137 kPa)Operating Temperature 0° to 160°F (-18° to 71°C)Wetted Parts Buna-N diaphragm and O-ring,

aluminumProcess Connection 1/4" MNPTApprovals UL listed E42272, CEWeight 0 .75 lb (0 .34 kg)Warranty 1 year

3.5 (8.9)

1.9(4.9)

1.7(4.2)

NC NO Common

#6-32 Terminal screw7/8 Diameter hole

electrical connection

0.69 (1.8)

Adjustment: removeplastic cover and turnadjusting screw in forhigher pressure setting

0.63(1.6)

Wrench flats

1/4 MNPT

4.38(11.1)

1.69(4.3)

0.88(2.2)

1.75(4.4)

1.4(3.6)

2.8(7.1)

DESCRIPTIONThe United Electric J54 Series Pressure Switch uses a diaphragm to sense changes in pressure to open or close an electrical circuit . The control setpoint can be varied by turning the internal adjustment hex screw . The switch is available with adjustable ranges from 3 psi (21kPa) to 500 psi (3448 kPa) .

FEATURES• Low cost• NEMA 1 enclosure• Compact size• 15A SPDT switch

DIMENSIONS

PRESSURE SWITCHJ54 SERIES

SPECIFICATIONS

J54 Series

ORDERING INFORMATION

MODEL DESCRIPTION J54-24 Pressure switch, 3 to 30 psi (21 to 207 kPa) J54-25 Pressure switch, 10 to 100 psi (69 to 690 kPa) J54-27 Pressure switch, 30 to 300 psi (207 to 2070 kPa) J54-28 Pressure switch, 50 to 500 psi (345 to 3448 kPa)

Page 86: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1092

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 24 VDC +15%, -10%Supply Current 75 mA maxSignal Output 4-20 mA sourcingMaximum Output Impedance 650Ω maxLocal Setpoint Input Built-in three-wire potentiometerRemote Setpoint Input 4-20 mA, 1-5 VDCAccuracy ±2% of range including non-linearity

and hysteresis

Maximum Overpressure 800% of the pressure rangeResolution 255 stepsOperating Humidity 0% to 90% non-condensingOperating Temperature 32° to 125°F (0° to 52°C)Process Connection 3/16" dia suitable for 1/4" OD

polyethylene tubingApprovals RoHSWeight 1 .3 lb (0 .61 kg)Warranty 18 months

PRESSURE CONTROLLERPCM SERIES

1.5 (3.81)

4.8 (12.19)

2.9 (7.37)

4.0 (10.16)

3.4 (8.64)

0.7 (1.78)

4.6 (11.68)

2.0 (5.08)

2.75 (6.99)

Mounting Slotsfor optional

DIN RailAdapter

Setpoint Knob

High Pressure Port Low Pressure Port

Pressure Ports

in (cm)

DESCRIPTIONThe Kele PCM Series Pressure Controller is a low air pressure transducer combined with a microprocessor-based proportional or Proportional plus Integral (PI) controller . The compact size and ease of installation and setup makes this unit ideal for standard HVAC applications . Ranges are available from 0-2, 3, or 5 "W .C . The setpoint adjustment knob is clearly marked with the appropriate scale for ease of use . All setup and tuning is easily accomplished by DIP switches and bottle plug jumpers . Mounting is a snap with the convenient mounting tabs or with the DIN rail mounting option . Remote setpoint is also possible with voltage or milliamp signals . The PCM Series can be configured for direct or reverse acting control .

FEATURES• Proportional or PI control• Easy setup• DIP switch/jumper setup and tuning• Selectable proportional band• Selectable integral reset rate• Direct or reverse acting • Optional DIN rail mounting• Compact size• Position insensitive

APPLICATION• Controlling duct pressures• Isolation rooms• VAV systems• Inlet guide vanes and VFDs• Paint booths• Relief damper control• Pressure bypass damper control

DIMENSIONS

SPECIFICATIONS

Page 87: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1093

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

1 . Switch A1 off and switch A2 on .

2 . Set jumper positions to 1, 8, and 11 .3 . Set switch A3 in the on position for direct acting control and in the off

position for reverse acting control .4 . Set switches A4 and A5 in the off position .5 . Set switches A6, A7, and A8 in the on position . This will set the

proportional band at 100% .6 . Set all B switches to the off position .

7 . All systems will require a fine-tuning process . Start the tuning process by decreasing the proportional band in increments through switches A6 through A8 until the system becomes unstable . Then, return to the DIP switch settings before the system started to hunt .

8 . Switches A4 and A5 are used to select the integral reset rate . This feature corrects the offset that is inherent with proportional-only controllers . If it is determined that the integral reset is needed, increase the rate until this offset is corrected and still maintains stability .

A6 0 0 0 0 1 1 1 1A7 0 0 1 1 0 0 1 1A8 0 1 0 1 0 1 0 1

A4 0 0 1 1A5 0 1 0 1 PWM

INPUTPWM INPUT

REM SPT INPUT

LOC SPT POT +

LOC SPT INPUT

LOC SPT POT –

FEEDBK INPUT

24 PWR

COMMON

MA SIGOUTPUT

LOC

AL

SE

TP

OIN

TF

EE

DB

AC

KR

EM

OT

E

SE

TP

OIN

T

B

A1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

4-20 mA Sourcing Output Signal toControlled Device

–+

PCM DIP SWITCH SETTINGS1=ON 0=OFF

PCM JUMPER POSITIONS

A1 0 1A2 1 0

Local Setpoint Remote Setpoint

A3 0 1 Reverse Acting Direct Acting

Reset Per Minute Rate

Proportional Throttling Range Settings

Off 0.5 1.0 2.0

This Unit’sRange Is:0-2" W.C.0-3" W.C.0-5" W.C.

10% 20% 35% 50% 65% 80% 90% 100%

All B switches should be in the off positionLocal Setpoint Jumper Positions 1, 8, 11For Remote Setpoint: Voltage Input Jumper Positions 2, 8, 11 Current Input Jumper Positions 1, 8, 11

ON

ON

12

3456

78910

–+ 24 VDC Power

1112

Remote Setpoint Input 4-20 mA or 1-5VRemote Setpoint

+

Common

Optional Remote Setpoint Wiring4-20 mA or 1-5 VDC

WIRING

SETUP FOR LOCAL SETPOINT OPERATION (FACTORY SETTINGS)

PRESSURE CONTROLLERPCM SERIES

ORDERING INFORMATION

PCM — 47020 — Example: PCM-020-47 Pressure controller for a 0-2" W.C. range with DIN rail mounting

MODEL DESCRIPTIONPCM Pressure setpoint controller PRESSURE RANGE 020 0-2" W.C. 030 0-3" W.C. 050 0-5" W.C. OPTIONS 47 DIN rail mounting (must be factory installed)

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-308-K Duct static pressure fitting, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SD-01 Surge dampener 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 88: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1094

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

Supply Voltage 18-32 VAC, 50-60HZSupply Watts 10 WSignal Output BACnet MS/TP ASCOperating Humidity 5 to 95% RH (Non-condensing)Operating Temperature 32° to 120°F (0° to 50°C)Enclosure Rating Fire retardant plastic UL94V-0Wiring Terminations Removable terminal blockDimensions 5 .84"H x 7 .45"W x 2 .38"D (14 .8 x 18 .9 x 6 .05 cm)Approvals RoHSWeight 1 .1 lb (0 .51 kg)Warranty 1 year

MULTI-ROOM MONITORING STATIONMRMS SERIES

DESCRIPTIONThe Setra Multi-Room Monitoring Station (MRMS) is a remote monitoring device to view the status of up to 8-Rooms equipped with other Setra Room Pressure/ Condition Monitors .

FEATURES• Remotely monitor up to eight rooms• Auto-discover setra room pressure/condition

monitors• Built-in audible & visual alarm• Display room status and room condition• Flush mount design• Reduce total installation cost• BACnet® MS/TP protocol• High definition color (TFT) touchscreen display

Rear view of the MRMS monitor to show wiring and plumbing connections

The back of the MRMS has electrical connectors labeled with their function. Themating electrical connectors (supplied) are color coded, keyed, and labeled withthe matching function.

WIRING

MODEL DESCRIPTIONMRMSS Multi-room monitoring station with logo on face plateMRMSB Multi-room monitoring station without logo on face plate

SPECIFICATIONS

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979

MRMS Series

Page 89: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1095

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 18-32 VAC, 50-60 HZSupply Watts 10W maximum, 3W typicalSignal OutputCurrent 4-20 mAVoltage 0 to 5, 0 to 10 VDCMaximum Output Impedance 510ΩMinimum Output Impedance 5000ΩRelay Output SPDT: 0 .6A @ 120 VAC, 2A @ 30 VDCAccuracy ±0 .5% ±0 .25% (optional) ±0 .5% ±0 .25% (optional)

Overpressure ±1 psi (15" WC for 0 .10" WC or less models)

Operating Humidity 5 to 95% RH (Non-condensing)Operating Temperature 32˚ to 120˚F (0˚ to 50˚C)Mounting Flush MountProcess Connection Barbed Fittings for 1/4" TubingWiring Terminations Removable Terminal BlockDimensions 5 .84"H x 7 .45"W x 0 .38"D (14 .8 x 18 .9 x 1 .0 cm)Enclosure Fire retardant plastic UL94-1CApprovals CE (EMC Directive 2004/108 EC)Weight 1 .2 lb (0 .55 kg)Warranty 1 year

ROOM CONDITION MONITORSRCM SERIES

DESCRIPTIONThe Setra SRCM Series is a 2-in-1 solution incorporating the best of the SRPM and adding room condition monitoring capability . A large 4 .3" TFT displays room conditions such as room ID, room pressure mode, room status, room pressure and a slide bar that indicates pressure relative to set point . It is also capable of displaying a full screen room condition banner to communicate the current room status and is easily programmed through the SmarTTouch™ display

The SRCM Series incorporates a flush mount design for the most esthetic installation . The display hinges up for easy access to a USB port that is provided for quick cloning of multiple units . The SRCM Series also has Multi-room dP measurement capabilities with the use of a remote dP transmitter, as well as the ability to display up to eight parameters utilizing BACnet® MSTP . In addition to the standard analog and relay outputs, the SRCM Series is available in a BACnet® MSTP configuration that is easily setup through the SmarTTouch™ display .

The SRCM Series is perfect for applications in laboratory, pharmaceutical, research, isolation room, and surgical suite applications or anywhere maintaining and monitoring differential pressure .

FEATURES• Color coded room status indication• Flush mount design• New intuitive interactive interface• Clone configuration capability• Selectable analog voltage and milliamp outputs• SPDT alarm relay• 4.3" TFT LCD display• Optional BACnet MSTP• SPDT relay output• Analog current or voltage outputs

SPECIFICATIONS

Optional Remote AnnunciatorSetra’s SRAN annunciator allows remote indication of room status at monitoring or nurses station . A GREEN LED indicates a normal room condition, a RED LED and audible alarm signal a breach in room pressure status .

Page 90: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1096

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ANALOG (ANL) OUTPUT

COM COMmA Current Output (4-20 mA)Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)

INPUTS (wired to door N.O. contact)

COM COM DoorDI Digital Input

COM COM Analog Input2IN2 Analog Input2 (0-5, 0-10Vdc) +15 15 Vdc COM COM Analog Input1IN1 Analog Input1 (0-5, 0-10Vdc) +15 15 Vdc

Earth GroundL1 24 VacL2 24 Vac

HIGH or room pressure tubing contacts here

LOW or reference pressure tubing connects here

POWER

RELAY

COM COM+15 +15 VdcNO Normally OpenRC Relay COMNC Normally Closed

COM

B (+) A (-)GND

REAR VIEW

WIRING

ROOM CONDITION MONITORSRCM SERIES

ORDERING INFORMATION

RELATED PRODUCTS PAGERPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901SRAN Remote annunciator with red and green status LEDs, audible alarm and acknowledge switch

Page 91: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1097

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 18 to 32 VDC @ 5 mASignal Output 0 to 5 VDC, 0 to 10 VDC, 4 to 20 mA

(loop-powered)

Accuracy ±1 .0% full scale RSS, ±0 .5% FS RSS, or ±0 .25% FS RSS

Overpressure Up to 10 psiOperating Humidity 5 to 95% RH (non-condensing)Operating Temperature 21° to 140°F (-6° to 60°C)Enclosure Rating Fire retardant plastic UL94V-0

Process Connection Barbed fittings for 1/4" ID tubingWiring Terminations Screw terminalDimensions Wall: 4 .44"H x 6 .19"W x 1 .7"D

(11 .3 x 15 .7 x 4 .3 cm) Duct: 2 .90"H x 5 .67"W x 1 .7"D

(7 .4 x 14 .4 x 4 .3 cm)Approvals CE, RoHSWeight Wall: 0 .6 lb (0 .28 kg) Duct: 0 .56 lb (0 .25 kg) Warranty 1 year

DESCRIPTIONThe Setra SRIM Series room pressure monitor is designed for critical care low differential pressure applications that require stringent pressure monitoring and alarming . True differential pressure is measured and displayed . The SRIM Series is a complete system that includes a convenient 2-Line Character LCD display with an intuitive interface for pressure, calibration, and alarm setup .

FEATURES• Large 2-line LCD display• Membrane keypad for ease of configuration & menu

navigation• Upper/lower alarm limit setting• Wall & duct mount versions• Mounting thickness <50mm• Easy calibration without removing the wiring or

plumbing

Wiring for 4-20 mA and VDC outputs

WIRING

SPECIFICATIONS

SRIM Series

ORDERING INFORMATION

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979

MODEL DESCRIPTIONSRIM Room isolation monitor

ROOM PRESSURE MONITORSRIM SERIES

Page 92: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1098

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 15-32 VDC or 24 VACSupply Watts 50mA max (per display)Accuracy ±1% FS ±2 CountsOperating Humidity 5 to 95% RH (non-condensing)Operating Temperature 14° to 122°F (-10° to 50°C)Enclosure Rating Fire retardant UL94V-0Wiring Terminations Screw terminalsDimensions 5 .8"H x 5 .8"W x 1 .25"D (14 .7 x 14 .7 x 31 .4 cm)Approvals CEWeight 0 .8 lb (0 .37 kg)Warranty 1 year

DESCRIPTIONThe Setra SRMD Model's temperature and humidity display panel features a CE compliant, high visible, large 1 inch 3 .5 digit LCD display and an attractive flush mounted faceplate bezel . This display panel is compatible with any temperature, humidity, CO2 sensor that has a 0 to 5 VDC or 0 to 10 VDC analog output .

FEATURES• Highly visible 1" LCD display• Single LCD display or dual LCD display model• Available in red, green or blue LCD backlight• Available with White or Metallic Bezel• Flush mount design• Wipe down capable• Mount in standard 4-11/16" sq. electrical box• Compatible with any analog sensor with 0-5VDC or

0-10VDC output

Input Wiring

WIRING

ROOM ISOLATION MONITORSRMD SERIES

SPECIFICATIONS

SRMD Series

ORDERING INFORMATION

SW SM

White bezelMetallic bezel

Example: SRMD-SW-R-T-WNN SRMD single display, white bezel, red display, temperature, with SRH wall mount sensor.

SRMD SW

MODEL DESCRIPTION SRMD Room monitoring display, single display

-

DISPLAY BEZEL COLOR

R G B

RedGreenBlue

DISPLAY COLOR

MEASUREMENT PARAMETERNTH

NoneTemp (14 to 140°F)Humidity (0.0 to 100.0% RH)SENSOR OPTIONNNNWNNDNN

NoneSRH Wall mount SRH12PW2CT5NSRH Duct mount SRH12PD2CT5N

R T WNN- - -

DW DM

White bezelMetallic bezel

Example: SRMD-DW-R-T-W-G-H SRMD dual display, white bezel, red display with temperature on

top, SRH wall mount sensor green display with humidity on bottom.

SRMD DW

MODEL DESCRIPTION SRMD Room monitoring display, dual display

-

DISPLAY BEZEL COLOR

R G B

RedGreenBlue

DISPLAY COLOR

MEASUREMENT PARAMETERNTH

NoneTemp (14 to 140°F)Humidity (0.0 to 100.0% RH)SENSOR OPTION

NWD

NoneSRH Wall mount SRH12PW2CT5NSRH Duct mount SRH12PD2CT5N

R T W- - -

R G B

RedGreenBlue

DISPLAY COLOR

MEASUREMENT PARAMETERNTH

NoneTemp (14 to 140°F)Humidity (0.0 to 100.0% RH)

R T--

RELATED PRODUCTS PAGET-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113691-K0A Control transformer, 120:24 VAC, 40 VA, Class 2 979

Page 93: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1099

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Supply Voltage 18-32 VAC 50/60 Hz, 85-265 VAC 50/60 Hz

Supply Watts 5WSignal Output 0-5 VDC (2 .5 V @ 0 pressure) 0-10

VDC (5 V @ 0 pressure) 4-20 mA sourcing (12 mA @ 0 pressure)

Alarm Relay Output SPDT, 5A @ 30 VDC, 120 VACAccuracy 0 .25% FS or 0 .5% FSDisplay LCD, 128x128 RGB backlitDisplay Resolution 0 .001" WCDisplay Units Inches of Water ("WC), Pascals (Pa)Protocol BACnet

Operating Humidity 5 to 95% (non-condensing)Operating Temperature 32° to 120°F (0° to 50°C)Enclosure Rating NEMA 1, Fire retardant plasticMounting Mounts to a 4" x 4" electrical boxElectrical Connection Removable terminal blocksProcess Connection Barbed fittings for 1/4" OD tubingDimensions 8 .0"H x 5 .4"W x 1 .6"D (20 .3 x 13 .7 x 4 .1 cm)Approvals CSA C22 .2 No . 1010 Safety, ANSIWeight 1 .5 lb (0 .69 kg)Warranty 1 year

ROOM PRESSURE MONITORSRPM

DESCRIPTIONThe Setra Model SRPM Room Pressure Monitor provides a system for monitoring differential pressures in critical low pressure applications . A backlit LCD provides an intuitive graphic user interface for ease of unit, security and alarm setup . Installation costs and on going calibration costs of ownership are significantly reduced . A red LED, green LED, backlit LCD, local audible alarm and optional remote annunciator alert personnel of the status of the system . A SPDT relay output is also available for additional status indication . Three analog outputs are available in the same unit to interface with BAS system . The Model SRPM is housed in a tough fire resistant plastic housing designed for surface mounting . The attractive case fits into Hospital and Pharamceutical applications . Models are available for 120/240 VAC or 24 VAC . The optional SRAN remote annunciator provides a visual and audible warning of room conditions at a remote location .

FEATURES• Easy, menu-driven programming• Large 2" x 2" LCD touch screen display• 0.25% or 0.5% accuracy • Visual and audible local alarms w/ alarm silence• Built in alarm horn with local alarm silence• Optional remote annunciator available• Selectable analog voltage and milli-amp outputs• SPDT alarm relay• Red and green room status LEDs• Display resolution of 0.001"• Door status monitor• Variable alarm delay• NIST certification included• Optional BACnet MSTP

APPLICATION

Typical applications include positive-pressure clean rooms such as pharmaceutical processing areas and negative-pressure isolation rooms such as hospital rooms housing contagious patients .

SPECIFICATIONS

BACNET VERSIONS

Optional Remote AnnunciatorSetra’s SRAN annunciator allows remote indication of room status at monitoring or nurses station . A GREEN LED indicates a normal room condition, a RED LED and audible alarm signal a breach in room pressure status .

Page 94: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1100

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

WIRING

ROOM PRESSURE MONITORSRPM

ORDERING INFORMATION

SRPM

R05WB

0R1WB

R25WB

0R5WB

001WB

2R5WB

005WB

A1

V1

E

24 VAC Supply, BACnet

120 VAC Supply voltage

0.5% Accuracy

±0.5" WC

±1.0" WC

±2.5" WC

±5.0" WC

Setra Room Pressure Monitor

±0.05" WC

±0.1" WC

±0.25" WC

Example: SRPM-001WB-A1-E SRPM pressure monitor measuring ±1.0" W.C. pressure 24VAC supply voltage at 0.5% accuracy.

0.25% AccuracyV

A2V2

24 VAC Supply voltage

120 VAC Supply, BACnet

Model Description

RELATED PRODUCTS PAGE4BX11234 4" square steel box 1-1/2" deep, 1/2" and 3/4" KO 218RPS Stainless steel room pressure sensor, 1/4" barb 1113RPS-I Ivory plastic room pressure sensor, 1/4" barb 1113RPS-W White plastic room pressure sensor, 1/4" barb 1113SRAN Remote annunciator with red and green status LEDs, audible alarm and acknowledge switch T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 95: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1101

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Accuracy ±2% of FS through out ranges @ 70°F (3% on 0 .5" ranges and 4% on 0 .25" ranges)

Operating Pressure -20" Hg to 15 psig (103 kPa)Media Compatibility Air and compatible gasesOperating Temperature 20° to 140°F (-7° to 60°C)Enclosure Die-cast aluminum case and bezel

with acrylic coverProcess Connection 1/8" NPT female high and low

pressure taps, duplicated-one pair side and one pair back .

Included Accessories Two 1/8" FNPT barbed fittings, two plugs for duplicate pressure taps, and three flush mounting tabs with screws

Weight 1 .1 lb (0 .51 kg)Warranty 2 years

DIFFERENTIAL PRESSURE GAUGEK2000 SERIES

0.5(1.3)

1/8 FNPThigh pressure port

1/8 FNPTlow pressure port

4.5(11.4)

3-M4

4.1(10.3)

0.7(1.8)

1.8(4.5)

4.7(12.0)

1.3(3.18)

0.4(1.11)

1.7(4.3)

in(cm)

DESCRIPTIONThe K2000 Series Differential Pressure Gauges can be used in applications for measuring positive, negative, or differential pressure with an accuracy of 2% . The gauge includes a 4" (10 .2 cm) easy-to-read dial, housed in a rugged die cast aluminum housing . The K2000 Series has both back and side connections so that it may be either surface- or flush-mounted . Ranges are available from 0" to 0 .25" W .C . up to 10" W .C .

FEATURES• 2% full-scale accuracy• Easy-to-read 4" (10.16 cm) white dial and red-tipped

pointer• Flush or surface mounting• Easily accessible zero adjustment• Corrosion-resistant cast aluminum housing• Back and side connections

APPLICATIONThe K2000 Series is ideal for monitoring filter status, duct static pressure, room pressure, fan or blower pressure, paint booths, dust collectors, and cabinet purging .

DIMENSIONS

SPECIFICATIONS

K2000

Page 96: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1102

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Mounting the K2000 Series Differential Pressure Gauge: Mount the K2000 with the dial face in the vertical plane . Avoid areas of excessive vibration, pulsating pressures, or extreme temperature swings . Long runs of pneumatic tubing will not affect performance but it may affect response times . Once the K2000 is mounted, the pointing needle of the K2000 may need to be adjusted to the zero position . If adjustment is required, slightly turn the external pointer adjustment screw in either direction as required .

Using the K2000 to measure differential pressure: The high pressure ports will always be connected to the higher of the two pressures that are being monitored . Conversely the lower pressure ports will always be connected to the lower of the two pressures being measures .

Monitoring variable positive pressures: This application will measure the positive pressure as it varies with respect to the atmosphere . Port the highest pressure source to a high port connection of the K2000 and leave the low pressure ports open to the atmosphere . Make sure any unused high pressure port is plugged .

Monitoring variable negative pressures: This application will measure the negative positive pressure as it varies with respect to the atmosphere . Port the low pressure source to a low port connection of the K2000 and leave the high pressure ports open to the atmosphere . Make sure any unused low pressure port is plugged .

INSTALLATION

DIFFERENTIAL PRESSURE GAUGEK2000 SERIES

ORDERING INFORMATION

* These ranges are calibrated for vertical scale position

MODEL

K2000-00*K2000-0*K2001K2002K2003K2004K2005K2006K2008K2010

RANGE "W.C.

0-0.250-0.50-1.00-2.00-3.00-4.00-5.00-6.00-8.00-10

MINOR DIV.

0.005 0.01 0.02 0.05 0.10 0.10 0.10 0.20 0.20 0.20

MODEL RANGE DUAL SCALE

"W.C./Pa

MINOR DIV.

K2000-00D*K2000-0D*K2001DK2002DK2003DK2004DK2006DK2008DK2010DK2020D

0-0.25/0-600-0.5/0-1250-1.0/0-2500-2.0/0-5000-3.0/0-7500-4.0/0-10000-5.0/0-1.5k0-6.0/0-2.0k0-8.0/0-2.5k0-10/0-5.0k

0.0050.010.020.050.100.100.100.200.200.20

Order by model number from selection chart above. Contact Kele for pressure ranges, metric ranges, and air velocity scales other than those shown.

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-368-K Surface mounting plate 1113A-605 Mounting kit for air filter application. Includes aluminum surface mounting brackets with screws, two 5 ft. lengths of 1/4" aluminum tubing, two static pressure tips and two plastic vent valves. 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 97: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1103

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Output signal 4 ... 20 mA, 2-wire

Output signal 0 ... 10 V, 3-wire

Supply Voltage 15 to 35 VDC (A2G-15 only)Signal Output 4-20 mA, 0-10 VDC (A2G-15 only)Maximum Output Impedance mA 600Ω @ 24 VDCDial Size 4 .5" (11 .4 cm)Maximum Pressure 80" WCAccuracy ±5% of full span ranges< 0 .5" WCRange 0 to 0 .2" WC to 0 to 50" WCOperating Temperature -22° to 176°F (-30° to 80°C)Gauge Movement Frictionless magnetic transmissionMaterials Of Construction Case: Aluminum Pointer: Plastic black Set Pointer: Plastic red Window: Makrolon Mounting Case: Black thermoplastic,

high impact resistant

Diaphragm Material Silicone rubberEnclosure Rating NEMA 3 (NEMA 4 Optional)Mounting LM = lower mount (surface mount)

(A2G-10, 15) CBM = center back mount (panel

mount) UBM = recess mount (recess mount)

(A2G-05)Process Connection 1/8" - 3/16" hose barbed adapters

includedWiring Terminations PG gland M12 (A2G-15 only)Approvals CEWeight 1 .0 lb (0 .45 kg)Warranty 2 years

DESCRIPTIONThe Wika A2G-05, -10, -15 Series pressure gauges/transmitter are the latest innovation in accurate, full-featured pressure gauges and are ideally suited for the measurement of low pressure and differential pressure from 0 .2” to 50” WC .

The A2G-05 Series is ideal for installations with space limitations . The unit features a slim case (1 .65 in .) which works well for recessed installation in the walls of clean rooms or in panel doors that have little room behind the panel to spare .

Both the A2G-10 and the A2G-15 Series incorporate a two-piece modular design . A benefit of the modular design is a two-part assembly that separates the measuring system from case components . This allows the replacement of only the measuring system, which provides reduced repair costs .

In addition to the local display, the A2G-15 features an electronic output signal and is available with a 2-wire, 4 to 20 mA or 3-wire 0 to 10 VDC output signal . This A2G-15 gauge is ideal for applications where a local indication and remote monitoring or evaluation is needed .

The panel mount version of all three models is extremely easy to install and requires no tools .

FEATURES• Zero adjustment in front• Red mark pointer standard• Simple mounting and dismounting• Installation depth 1.65 in. (A2G-05)• Two part construction (A2G-10, A2G-15)• Analog output signal (A2G-15)

PRESSURE GAUGES/TRANSMITTERA2G-05, -10, -15 SERIES

SPECIFICATIONS

A2G-05-BTF

A2G-10

A2G-15

WIRING (A2G-15 ONLY)

Page 98: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1104

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

ORDERING INFORMATION

PRESSURE GAUGES/TRANSMITTERA2G-05, -10, -15 SERIES

MODEL DESCRIPTIONA2G WIKA differential pressure gauge series

CONFIGURATION

10 WIKA differential pressure gauge, standard case15 WIKA differential pressure gauge, standard case, analog output signal

- Surface mount (LM), models -10 and -15 onlyP Panel mount (CBM), threaded flange on rear of case models -05, -10 and -15

ANALOG SIGNAL (A2G-15 only)420 4-20 mA analog signal010 0-10 VDC analog signal

RANGE CODESP25 0 to 0.25" WCP50 0 to 0.05" WC01 0 to 1.0" WC 02 0 to 2.0" WC03 0 to 3.0" WC04 0 to 4.0" WC05 0 to 5.0" WC06 0 to 6.0" WC07 0 to 8.0" WC08 0 to 10.0" WCCP10 ±0.1" WCCP20 ±0.2" WCCP50 ±0.5" WCC10 ±1.0" WCC20 ±2.0" WCC40 ±4.0" WCC60 ±6.0" WC

05 WIKA differential pressure gauge, thin case (1 inch case length)

BTF Recess mount (UBM), mounting ring on panel/wall surface with gauge bayonet connection (twist in)

RELATED PRODUCTS PAGEDCPA-1.2 Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994DCP-1.5-W Power supply, 24 VAC IN to 24 VDC OUT 995

Page 99: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1105

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Accuracy +3/2/3% of span (ASME B40 .100 Grade B)

Measurement Range 30" Hg Vacuum to 5000 psiOverpressure Steady 3/4 of FS value

Fluctuating 2/3 of FS value Short time FS valueOperating Temperature Ambient -40°F to 140°F (-40°C to 60°C) Media 140°F (60°C) maximum Wetted Parts Copper AlloyCasing Black Plastic

Window Material Crystal-clear plastic, snap-fitDial Size 1 .5" (3 .8 cm), 2 .0" (5 .1 cm), 2 .5" (6 .4 cm),

or 4 .0" (10 .2 cm) (111 .10 Series only)Dial White plastic with stop pin (1 .5", 2 .0",

2 .5") White aluminum with stop pin (4")

(111 .10 Series only) Black or black and red letteringProcess Connection 111.10 Series 1/8" or 1/4" NPT lower mount 111.12 Series 1/8" or 1/4" NPT center back mountApprovals RoHS, UL File SA6444Warranty 1 year

DIAL GAUGE111.10, 111.12 SERIES

DESCRIPTIONDesigned for long, reliable service under rugged conditions, the Wika 111.10 and 111.12 Series pressure gauges are typically used in applications where the media does not corrode brass . The low cost 111.10 Series has a lower mount connection and features a black ABS or painted steel case standard, and a coiled safety Bourdon tube for 800 psig and higher . The 111.12 Series is specifically designed for flush mounting into panels . This center back mount pressure gauge features a black ABS or black-painted steel case, a coiled safety Bourdon tube for 800 psig and higher, and option for U-clamp mounting .

FEATURES• Copper alloy wetted parts• Black ABS or painted steel case• Cost effective design• Pressure ranges from 30" Hg vacuum to 5000 psig• Center back mounting with option for U-clamp (111.12

Series only)• Available in 1-1/2" through 4" sizes

SPECIFICATIONS

111.10 Series

ORDERING INFORMATION

111.12 Series

GAUGE MODEL 111.10 111.12

Dial Size 1-1/2" 2" 2-1/2" 4" 1-1/2" 2" 2-1/2"Connection 1/8" LM 1/4" LM 1/4" LM 1/4" LM 1/8" CBM 1/8" CBM 1/4" CBMPressure Range 30" Hg Vacuum 9747214 4252901 4253027 4255900 9690128 9690357 425337130" Hg Vacuum -15 psi 52234681 50786563 4253035 4255918 N/A N/A 425338930" Hg Vacuum -30 psi N/A 50786571 4253043 4255926 N/A 50741713 425339730" Hg Vacuum -60 psi N/A N/A 4253051 4255934 N/A N/A 425340030" Hg Vacuum -100 psi 50169025 50302418 4253060 4255942 N/A N/A 425341830" Hg Vacuum -160 psi N/A N/A 4253078 4255951 N/A N/A 425342630" Hg Vacuum -200 psi N/A 50657569 4253086 4255969 N/A N/A 42534340-15 psi 9747222 4252919 4253108 4255977 9690209 9690438 42534510-30 psi 9747230 4252927 4253116 4255985 9690217 9690446 42534600-60 psi 9747249 4252935 4253124 4255993 9690225 9690455 42534780-100 psi 9747257 4252943 4253132 4256000 9690234 9690463 42534860-160 psi 9747265 4252951 4253141 4256018 9690242 9690471 42534940-200 psi 9747273 4252960 4253159 4256026 9690250 9690489 42535070-300 psi 4233372 4252978 4253167 4256034 4233355 9690497 42535150-400 psi 4233398 4252986 4253175 4256042 4354385 4386082 42535230-600 psi N/A 4252994 4253183 4256051 9690285 4228930 42535310-800 psi 50646605 N/A 4253191 4256060 N/A N/A 42535410-1000 psi N/A 4253001 4253205 4256078 9765654 4256585 42535590-1500 psi N/A 50786598 4253213 4256086 N/A N/A 42535670-2000 psi 50989309 50786601 4253221 4256094 N/A N/A 42535750-3000 psi N/A 4253019 4253230 4256107 N/A 50075322 42535830-5000 psi N/A N/A 4253248 4256115 8986154 N/A 4253591

Page 100: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1106

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Accuracy ± 2% of FS (3% on -0 and 4% on -00 ranges) throughout range

System Pressure -20" Hg to 15 psig (103 kPa)Overpressure Relief plug designed to open at 25

psig (172 kPa)Enclosure Die-cast aluminumOperating Temperature 20° to 140°F (-7° to 60°C)Process Connection 1/8" NPT female high and low

pressure taps, duplicated-one pair side and one pair back

Standard Accessories Two 1/8" NPT plugs for duplicate pressure taps, two 1/8" pipe thread to rubber tubing adapters, and three flush mounting adapters with screws

Approvals RoHSWeight 1 .12 lb (0 .51 kg)Warranty 1 year

DIFFERENTIAL PRESSURE GAUGES2000 SERIES

MAGNEHELIC®

Zero Set

Pressure

0

.20

.40 .60

.80

1.0

0.5(1.27)

Suction

0.69(1.75)

1.69(4.29)

0.5(1.27)

0.48(1.11)

1.25(3.17)

4.5 Hole(11.43)

Pressure

Suction

0.5(1.27)

4.75(12.06)

in(cm)

Note: Dimensions are slightly different on medium and high pressure models.

DESCRIPTIONThe Dwyer 2000 Series Magnehelic® Differential Pressure Gauges provide an accurate, economical indication of positive, negative, or differential air pressure . The gauge includes a 4" (10 .2 cm) easy-to-read dial and a frictionless magnetic movement in a cast aluminum housing, and it is resistant to shock, vibration, and overpressure . The Magnehelic® Gauge has both back and side connections, so that it may be either surface- or flush-mounted . Ranges are available from 0" to 0 .25" W .C . up to 10'' W .C .

FEATURES• 2% full-scale accuracy• Easy-to-read 4" (10.16 cm) white dial and red-tipped

pointer• Flush or surface mounting• Easily accessible zero adjustment• Corrosion-resistant cast aluminum housing• Back and side connections

APPLICATIONThe 2000 Series is ideal for monitoring fan and blower pressures, filter resistance, air velocity, and pressure drop across coils . It may be used to measure positive, negative, or differential pressures of air or compatible gases .

DIMENSIONS

SPECIFICATIONS

2001

Page 101: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1107

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Mount the 2000 Series Magnehelic Gauge® with the dial in a vertical position in a location free of excessive vibration or pulsating pressures . Sensing lines may be run any distance necessary, but long tubing lengths will increase response time slightly . If the pointer is not exactly on the zero mark with both the high- and low-pressure connections open to the atmosphere, adjust with the external zero adjust screw .

To monitor positive pressure, connect tubing from the source of pressure to either of the two high-pressure ports . Plug the other high-pressure port, and vent one or both low-pressure ports to atmosphere .

To monitor negative pressure, connect tubing from the source of negative pressure to either of the two low-pressure ports . Plug the other low-pressure port, and vent one or both high-pressure ports to atmosphere .

To monitor differential pressure, connect tubing from the source of the higher pressure to either of the two highpressure ports . Connect tubing from the source of the lower pressure to either of the low-pressure ports . Plug both unused ports .

ORDERING INFORMATION

INSTALLATION

Order by model number from selection chart above. Contact Kele for pressure ranges, metric ranges, and air velocity scales other than those shown.

DIFFERENTIAL PRESSURE GAUGES2000 SERIES

* These ranges are calibrated for vertical scale position

MODEL

2000-00* 2000-0* 2001 2002 2003 2004 2005 2006 2008 2010

RANGE "W.C.

0-0.25 0-0.50 0-1.0 0-2.0 0-3.0 0-4.0 0-5.0 0-6.0 0-8.0 0-10

MINOR DIV.

0.005 0.01 0.02 0.05 0.10 0.10 0.10 0.20 0.20 0.20

MODEL

2300-0* 2301 2302

RANGE ZERO CENTER

"W.C.

0.25-0-0.25 0.5-0-0.5

1-0-1

MINOR DIV.

0.01 0.02 0.05

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113A-368-K Surface mounting plate 1113A-605 Mounting kit for air filter application. Includes aluminum surface mounting brackets with screws, two 5 ft. lengths of 1/4" aluminum tubing, two static pressure tips and two plastic vent valves. 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

Page 102: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1108

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

N.C.

Right SetpointKnob

COM

(HI)

Left SetpointKnob

N.C. COM

-110 Volt

+110 Volt

(LOW) Reset Reset

Supply Voltage 110 VAC, 50/60 Hz, 5WContact Rating 10A @ 120 VAC, 60 Hz resistiveAccuracy ±2% of full scale @ 70°F (21°C),

±3% on -0 models, ±4% on -00 models

Overpressure 20" Hg to 25 psig (172 kPa) total pressure on either side of diaphragm

Operating Temperature 20° to 120°F (-7° to 49°C)Process Connection 1/8" FNPT

Conduit Entrance 3/4" conduitCutout Size 4 .75" (12 .06 cm) diameterDepth Required 7 .63" (19 .37 cm)Dimensions 5 .0"H X 5 .0"W X 8 .44"D (12 .7 X 12 .7 X 21 .4Approvals UL listed, file #E38121, CSA, CEWeight 4 .0 lb (1 .81 kg)Warranty 1 year

DIFFERENTIAL PRESSURE SWITCH / GAUGE3000 SERIES

DESCRIPTIONThe Dwyer Series 3000 Photohelic® Differential Pressure Switch/Gauge combines two versatile, precise pressure switches with a time-proven Magnehelic® pressure gauge . The gauge reading is unaffected by switch operation . External knobs are used to adjust the two DPDT switch setpoints . Switch setpoints (indicated by red pointers) and system pressure are fully visible at all times . Ranges are available from 0" to 0 .25" W .C . up to 10'' W .C . full scale . The 3000 Series may be ordered with the switch assembly remote mounted to facilitate panel mounting .

FEATURES• Two DPDT switches, externally adjustable• Dependable Magnehelic® pressure indication• 2% F.S. accuracy• Visible switch set points and pressure indication• Easily accessible zero adjustment• 4" (10.2 cm) easy-to-read white dial• Optional manual reset• Optional remote mounting of switch assembly• UL listed, CSA and CE certified

SPECIFICATIONS

A3002

ORDERING INFORMATION

A3000-00A3000-0A3001A3002A3003

RANGE "W.C. MINOR DIVISION0-0.250-0.500-1.00-2.00-3.0

0.0050.010.020.050.10

A3004A3005A3006A3008A3010

MODELMODEL RANGE "W.C. MINOR DIVISION0-4.00-5.00-6.00-8.00-10

0.100.100.200.200.20

OPTIONS RMR Remote mounting gauge and separate relay assembly with 5ft (12.7 cm) interconnecting cable (additional cable available in 5ft increments) TAMP Tamper-proof knobs A-601 Manual reset switch (one required for each circuit)

Contact Kele for pressure ranges otherthan those shown (metric ranges, air velocity scales, etc.)

RELATED PRODUCTS PAGEA-301-K Duct static pressure tip, 1/4" compression 1113A-302-K Duct static pressure tip, 1/4" barb 1113A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 1113T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 901

WIRING

Page 103: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1109

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Accuracy ±0 .5% of span (ASME B40 .100 Grade 2A)

±1 .0% of span (ASME B40 .100 Grade 1A) (for 20,000 psi range and above)

Measurement Range 30" Hg Vacuum to 0 to 0-20,000 psiOverpressure Steady FS value Fluctuating 90% of FS value Short Time 150% of FS valueOperating Temperature Ambient -40°F to 150°F (-40°C to 66°C) dry -4°F to 150°F (-20°C to 66°C)

glycerine filled -40°F to 150°F (-40°C to 66°C)

silicone filled Medium max 212°F (100°C)Wetted Parts 316L stainless steelWindow Material Clear acrylic with Buna-N gasketDial Size 4 .5" (11 .4 cm)Dial White aluminum with black lettering,

stop pin at 6 o'clockPointer Black aluminum, adjustableRestrictor Stainless steel (0 .6 mm)Fill Fluid Glycerine 99 .7% (233 .34 Series)Process Connection 1/4" or 1/2" NPT with M4 internal tap,

lower mount Approvals RoHSWarranty 1 year

DESCRIPTIONSpecifically designed for the chemical and petroleum, and processing industries, the Wika 232.34 and 233.34 Series pressure gauges feature 316 stainless steel wetted parts, a solid-front, blowout back safety case, and adjustable pointer . Available in 4-1/2" or 6" dial size, this pressure gauge is field repairable and field liquid-fillable .FEATURES• Excellent load-cycle stability and shock resistance• Solid front thermoplastic case• Positive pressure ranges to 30,000 psi• XSEL® Process Gauge with 5 year warranty on gauge

and 10 year warranty on pressure system (see terms and conditions)

• All lower mount connection gauges are factory prepared

DIAL GAUGE232.34, 233.34 SERIES

SPECIFICATIONS

232.34 Series

233.34 Series

ORDERING INFORMATIONGAUGE MODEL

232.34 233.34Dial Size 4-1/2" 4-1/2" 4-1/2"Connection 1/4" LM 1/2" LM 1/2" LMPressure Range 30" Hg Vacuum 9834478 9834729 983391430" Hg Vacuum -15 psi 9834486 9834737 983392230" Hg Vacuum -30 psi 9834494 9834745 983393030" Hg Vacuum -60 psi 9834508 9834753 983394830" Hg Vacuum -100 psi 9834516 9834761 983395630" Hg Vacuum -160 psi 9834524 9834770 983396530" Hg Vacuum -200 psi 9834532 9834788 983397330" Hg Vacuum -300 psi 4260163 4260180 N/A30" Hg Vacuum -400 psi 4260171 4260198 N/A0-15 psi 9834559 9834800 98339810-30 psi 9834567 9834818 98339990-60 psi 9834575 9834826 98340060-100 psi 9834583 9834834 98340150-160 psi 9834591 9834842 98340230-200 psi 9834605 9834850 98340310-300 psi 9834613 9834869 98340490-400 psi 9834621 9834877 98340570-600 psi 9834630 9834885 98340650-800 psi 9835008 9834974 98341550-1000 psi 9834648 9834893 98340740-1500 psi 9793318 9834907 98340820-2000 psi 9793661 9834915 98340900-3000 psi 9748911 9834923 98341040-5000 psi 9793521 9834931 98341120-10000 psi 9793679 9834940 98341200-15000 psi N/A 9834958 98341380-20000 psi N/A 9834966 9834146

Page 104: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1110

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Supply Voltage 24-240 VAC/VDC, 7 VASignal Output 4-20 mA (optional), 120 mA (VDC)Maximum Output Impedance 750ΩRelay Output (2) SPDTRelay Output Rating 8 Amps @ 250 VAC, 5A @30 VDCAccuracy 1 .0% standard (0 .5% and 0 .25%

optional)Thermal Effect +/- 0 .02% FS/°FMaximum Pressure ≤4" WC 2 psi; 5" WC or more 10 psi Display 4 Digit, red LED, ½" digits, LCD

programming display (A3 and A4 only)Response Time <100 msOperating Temperature -10° to 140°F (-23° to 60°C)Media Compatibility Air and compatible non combustible,

non corrosive gassesEnclosure Glass Filled NylonEnclosure Rating Face designed to meet NEMA 4X with

optional cover

Process Connection Push on connection for 3/16" tubingWiring Terminations screw terminalsApprovals ETL, CE Warranty 1 year

Ø5.1(129.5)

1.61(41)

0.32(8.1)

4.57

(116

)

2.33(59.1)

LOW HIGH

V V 4/20 4/20

C

1 N

CI N

01

0.95(24.1)

DESCRIPTIONThe Sensocon Series A1 and A2 digital differential pressure gauges utilize a patent pending microprocessor based digital pressure gage for positive, negative, and differential measurement designed to be a direct replacement for mechanical gauges . The Series A digital differential pressure gauges utilize an extremely stable piezoresistive sensing technology to give a standard full scale accuracy of 1% . For applications requiring better accuracy, the Series A1 and A2 are also available with 0 .5% or 0 .25% accuracy . The Series A1 and A2 also have an optional 4-20 mA output for applications requiring an output signal . While the A1 features a bright LED display, the A2 adds a bright process arch which gives the gauge improved visibility, readability and precision . Both the Series A1 and A2 digital differential pressure gauges also feature 5 user selectable engineering units including inches of W .C ., mm W .C ., cm W .C ., kPa, and Pa .

The Sensocon Series A3 and A4 digital differential pressure controllers are a patent pending microprocessor based pressure controllers for positive, negative, and differential pressure as well as velocity and flow . These Series A3 and A4 differential pressure controllers include (2) 8A SPDT relays and an associated programming menu that allows full configuration of variables such as setpoints, dead band, engineering units, flow coefficients, and more . The programming is done from a user friendly menu on the LCD(A3) or OLED (A4) display or uploaded using an Opti Link

FEATURES• Mounts in industry standard holes• 1.6” (41 mm) panel depth• LED or OLED program display• Measures flow & velocity• Optional 4-20 mA output• Universal power 24-240 VAC/VDC• Two 8A SPDT relays

DIMENSIONS

DIGITAL GAUGESERIES A

SPECIFICATIONS

ORDERING INFORMATION

A Series A 4.5" panel mount display

DI SPLAY CONFI GURATI ON

1 LED display

2 LED display, process arch

3 LED display, process arch, and LCD

4 LED display, process arch, and OLED

FUNCTI ON

0 Indicat ion

1 Cont rol (2) SPDT relays (A3 and A4 only)

TRANSMI TTER

0 None

1 4-20 m A

ACCURACY

0 1%

1 0.50%

2 0.25%

PRESSURE RANGE*

0 0 – 0.25" (60 Pa)

1 0 – 0.5" (125 Pa)

2 0 – 1" (250 Pa)

3 0 – 2" (500 Pa)

4 0 – 3" (750 Pa)

5 0 – 4" (1 kPa)

6 0 – 5" (1.25 kPa)

7 0 – 8" (2.0 kPa)

8 0 – 10" (2.5 kPa)

9 0 – 15" (3.75 kPa)

10 0 – 20" (5.0 kPa)

11 0 – 30" (7.5 kPa)

12 0 - 40" (10 kPa)

13 0 - 50" (12.5 kPa)

* All ranges are bi-direct ional

Model Descpition

Page 105: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1111

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Dial Size 2 1/2" (6 .4 cm)Accuracy 1%-2%-5%Measurement Range 30" Hg vac to 120 psi (retard to 250

psi)Wetted Parts Brass socket, phosphor bronze

bourdon tubeProcess Connection 1/8" NPT, lowerEnclosure Window: PolycarbonateCase ABS plasticWarranty 1 year

REFRIGERATION GAUGE25W100

DESCRIPTIONThe Ashcroft Model 25W100 Refrigeration Gauges are ideal for installation on refrigeration manifolds for testing air conditioning units . The compound scale is designed specifically for R134A refrigerant testing . FlutterGuard™, a standard feature of these gauges, eliminates pointer flutter .

SPECIFICATIONS

25W100

ORDERING INFORMATION

MODEL DESCRIPTION25W1007PH01L-R134A Re f r i ge r a t i on gauge f o r

R134A

Overpressure 125% of FS valueOperating Temperature -40° to 150°F (-40° to 65°C)Wetted Parts Brass socket, phosphor bronze

bourdon tubeWindow Material Acrylic

Process Connection 1/8" NPT or 1/4" NPT, depending on model (LM = lower mount, CBM = center back mount, PM = panel mount)

Warranty 1 year

PRESSURE GAUGESPG SERIESDESCRIPTION

The PG Series Pressure Gauges are durable, cost-effective, general-purpose gauges for use in a wide variety of HVAC controls applications . All gauges are compatible with air, oil, and water and have a bronze bourdon tube, acrylic lens, and dual unit psi/kPa scale . The PG Series (except model PG-05) has a recalibrator screw . A wide variety of models, options, and accessories are available, including panel-mount models, specialty gauges, and diaphragm seals .

SPECIFICATIONS

PG Series

ORDERING INFORMATION

DIAL SIZECONNECTIONACCURACY

CASE MATERIAL

PRESSURE RANGE30" Hg VAC/kPa30" Hg VAC-30 psig0-15 psig/kPa0-30 psig/kPa0-60 psig/kPa0-100 psig/kPa0-160 psig/kPa0-200 psig/kPa0-300 psig/kPa0-400 psig/kPa0-600 psig/kPa

ECONOMY1-1/2"

1/8" CBM3-2-3%BLACKSTEEL

N/AN/AN/A

PG-05N/AN/AN/AN/AN/AN/AN/A

1-1/2"1/8" LM2-1-2%BLACKSTEEL

PG-15-30-0-8LN/A

PG-15-0-15-8LPG-15-0-30-8LPG-15-0-60-8LPG-15-0-100-8LPG-15-0-160-8LPG-15-0-200-8LPG-15-0-300-8LPG-15-0-400-8LPG-15-0-600-8L

1-1/2"1/8" CBM

2-1-2%BLACK STEEL

PG-15-30-0-8CN/A

PG-15-0-15-8CPG-15-0-30-8CPG-15-0-60-8CPG-15-0-100-8CPG-15-0-160-8CPG-15-0-200-8CPG-15-0-300-8CPG-15-0-400-8CPG-15-0-600-8C

GAUGE TYPE

2"1/4" CBM

2-1-2%BLACKSTEEL

PG-20-30-0-4CN/A

PG-20-0-15-4CPG-20-0-30-4CPG-20-0-60-4CPG-20-0-100-4CPG-20-0-160-4CPG-20-0-200-4CPG-20-0-300-4CPG-20-0-400-4CPG-20-0-600-4C

2-1/2"1/4" LM2-1-2%BLACK STEEL

PG-25-30-0-4LPG-25-30-30-4LPG-25-0-15-4LPG-25-0-30-4LPG-25-0-60-4LPG-25-0-100-4LPG-25-0-160-4LPG-25-0-200-4L

N/AN/AN/A

CONTRACTOR4-1/2"

1/4" LM1%

STAINLESSSTEEL

PG-45-30-0-4LPG-45-30-30-4LPG-45-0-15-4LPG-45-0-30-4LPG-45-0-60-4LPG-45-0-100-4LPG-45-0-160-4LPG-45-0-200-4L

N/AN/AN/A

2-1/2"1/4" PM2-1-2%BLACKSTEEL

PG-25-30-0-4P N/APG-25-0-15-4PPG-25-0-30-4PPG-25-0-60-4PPG-25-0-100-4PPG-25-0-160-4PPG-25-0-200-4P

N/AN/AN/A

QUALITY2"

1/4" LM2-1-2%BLACKSTEEL

PG-20-30-0-4LN/A

PG-20-0-15-4LPG-20-0-30-4LPG-20-0-60-4LPG-20-0-100-4LPG-20-0-160-4LPG-20-0-200-4LPG-20-0-300-4LPG-20-0-400-4LPG-20-0-600-4L

2"1/4" PM2-1-2%BLACKSTEEL

PG-20-30-0-4PN/A

PG-20-0-15-4PPG-20-0-30-4PPG-20-0-60-4PPG-20-0-100-4PPG-20-0-160-4PPG-20-0-200-4PPG-20-0-300-4PPG-20-0-400-4PPG-20-0-600-4P

Page 106: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1112

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Maximum Pressure Brass Snubbers 3000 psig (20,685 kPa) SS Snubbers 5000 psig (34,475 kPa) PT 250 psig (1724 kPa)Maximum Temperature PT 400°F (204°C)Materials Of Construction Snubbers Brass, Stainless Steel PT SteelProcess Connection Snubbers 1/8" MNPT PT 1/4" NPT (1/8" NPT fittings providedDimensions 747 Series 1 .2"H X 0 .69" diameter (3 .05 X 1 .75 cm) 47 Series 1 .5"H X 0 .69" diameter (3 .81 X 1 .75 cm) PT 5 .5" L (14 cm)

0.688(1.75)

Instrument connection Instrument connection

in(cm)

Model 47Model 747

1/8" FNPT

1/8" MNPT

Pressure source Pressure source

1.2(3.05)

0.688(1.75)

1/8" FNPT

1/8" MNPT

1.5(3.81)

Maximum pressure747B - 3000 psig (20,685 kPa) 47B - 3000 psig (20,685 kPa)747S - 5000 psig (34,475 kPa) 47S - 5000 psig (34,475 kPa)

DESCRIPTIONSnubbers will stop shocks and pulsations that damage pressure instruments, thus cutting costs of maintenance, calibration, and repair . They will also assure accuracy of the instruments and the readings, increase life of instruments, and prevent false operation of control equipment . Kele offers two types of pressure snubbers; piston and porous .

Model 47 SnubbersModel 47 incorporates a piston that moves up and down inside of an internal tube within the snubber . This movement of the piston, caused by the shocks and pulsations of the fluid, dampens the effect of these pulsations .

Model 47 comes with three piston sizes: #02, #2, and #3 . Piston #2 is installed in the factory in the snubber . It is used for most applications, such as water, air, and steam . The #3 piston is used for a greater snubbing effect, while the #02 piston is used for relatively thick fluids or low pressure water applications .

Model 747 SnubbersModel 747 is a porous snubber and a low-cost alternative to piston snubbers . There are no moving parts . It uses a porous material to dampen the effect of shocks and pulsations . The Model 747 is available in stainless steel and brass, and it is ordered based on the application, gases or liquids .

Model PTIn steam pressure monitoring, the temperature of the steam is higher than the maximum operating temperature of most pressure transmitters . A Model PT steam pigtail syphon will protect a pressure transmitter applied to steam systems . See the "Technical Reference" section in the Kele catalog for more detailed information .

DIMENSIONS

SNUBBERS, PIGTAIL47B-1, 47S-1, 747B, 747S, PT

SPECIFICATIONS

ORDERING INFORMATION

MODEL DESCRIPTION47B-1 Brass piston style snubber47S-1 Stainless steel piston style snubber747BE-1 Brass porous style snubber for light oil and water747BG-1 Brass porous style snubber for air, steam, and other gases747SE-1 Stainless steel porous style snubber for light oil and water747SG-1 Stainless steel porous style snubber for air, steam, and other gasesPT 1/4" pigtail syphon with fittings

PTX1 with

47S-1

PT (Steam Syphon)

747B Snubber

The Model PT is constructed of steel and is suitable for steam pressure to 250 psig (1724 kPa) 400°F (204°C) . Each is furnished with two 1/4" FPT x 1/8" FPT couplings and one 1/8" MPT x 1/8" MPT nipple for convenient installation .

Page 107: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1113

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

1. Positive static pressure increases as the filter gets dirty.2. Differential across filter changes as filter gets dirty.3. Flow is reduced as filter gets dirty.

4. Negative pressure increases as the filter gets dirty.5. Fan operation and true air flow: varying amounts of static pressure. Probes must be perpendicular to air flow.

1 2 3

4 5

DESCRIPTION

Static Pressure SensorsThe A-300-K Series sensors are used with pressure transmitters and pressure switches to sense duct pressures . Two sensors are required to monitor pressure across coils, filters, blowers, etc . A-301-K and A-302-K have four radial sensing holes and 4" (10 .2 cm) insertion depth . The A-308-K should be used only where accuracy is not critical . All mount in a 3/8" hole in the duct . If the interior of the duct is not accessible, an optional A-345-K flange mounting kit may be used .

Room Static Pressure or Total Pressure Sensor KitThe versatile Model 60681 Pressure Sensing Kit is used for monitoring static pressure (aspiration) or total pressure (impact) . The kit includes a 7" (17 .8 cm) universal sensing probe, adjustable mounting flange, 1/4" adapter, and 3' (0 .9 m) length of tubing (1/4" ID x 3/8" OD) . For total (impact) pressure applications, install the curved tip opening facing into the air stream or away from the air stream for vacuum applications .

Total Pressure SensorThe Model 21122 (4") and 21123 (8") sensors are used primarily for proving air flow in ducts . The opening in the tip of the 4" (10 .2 cm) aluminum tube faces upstream and senses impact (total) pressure . The "-112" models accept 1/8" to 1/4" ID flexible tubing .

Outdoor Static Pressure SensorThe A-306-K Outdoor Static Pressure Sensor provides an outdoor pressure signal for reference in building pressurization applications . The A-306-K includes the sensor, 50' (15 .24m) of vinyl tubing, mounting bracket, and hardware .

Room Static Pressure SensorThe Model RPS is a stainless steel, wall-mounted room static pressure sensor . It mounts directly to the wall or to a standard electrical box . The Model RPS-W is a white plastic, wall-mounted room static pressure sensor, and the Model RPS-I is ivory . The RPS sensors have a 100 micron stainless steel breather vent .

Filter KitThe Model A-605 Filter Kit includes an aluminum surface mounting bracket and screws, two 5 ft lengths of 1/4" aluminum tubing, two static pressure tips, and two plastic vent valves .

Surge DampenerSurge Dampener Model SD-01 absorbs rapid pressure fluctuations to provide steady pressure outputs . The dampener has two independent channels - one for the low pressure tubing and one for the high pressure tubing . Surge dampeners are typically used with outdoor pressure sensors, which are subject to wind gusts, and isolation rooms, clean rooms, or operating rooms where opening or closing doors creates sudden pressure changes .

APPLICATION

AIR PRESSURE SENSORS, SURGE DAMPENERSA300 SERIES, RPS, SD-01, 21121, 60681

A-300 Series

ORDERING INFORMATION

60681

RPS-W

RPS & SD-01

MODEL DESCRIPTION60681 Static or total pressure sensing kitA-301-K Duct static pressure tip, 1/4" compressionA-302-K Duct static pressure tip, 1/4" barbA-308-K Duct static pressure fitting, 1/4" barbA-345-K Flange mounting kit (1 required for each A-301-K or A-302-K)A-3145K A-301-K duct static pressure tip, 1/4" compression with A-345-K mounting flangeA-3245K A-302-K duct static pressure tip, 1/4" barb with A-345-K mounting flangeA-3845K A-308-K duct static pressure fitting, 1/4" barb with A-345-K mounting flange21122 4" aluminum impact tube, 1/4" OD connection21122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing21123 8" aluminum impact tube, 1/4" OD connection21123-112 8" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubingA-306-K Outdoor air static pressure kitA-605 Mounting kit for air filter application. Includes aluminum surface mounting brackets with screws, two 5 ft. lengths of 1/4"

aluminum tubing, two static pressure tips and two plastic vent valves.RPS Stainless steel room pressure sensor, 1/4" barbRPS-I Ivory plastic room pressure sensor, 1/4" barbRPS-W White plastic room pressure sensor, 1/4" barbSD-01 Surge dampenerB-137 1/4" barb adapter for #21122 and #21123 (standard pack-50)

Page 108: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1114

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

A REFRESHER ON 4-20 MA SIGNAL

The control signal, 4-20 mA, is the most common type of analog/proportional/modulating (these terms tend to be used interchangeably in our industry) signal we deal with and there are some fundamental facts about the 4-20 mA signal that we all know but are worth reviewing .

The 4-20 mA control signal is, of course, a variable current signal where 4 mA typically represents the low end of a range, for example 0%, and 20 mA represents the high end, for example 100% . This works great for measuring a given pressure range in a duct, the stroke position of a damper actuator, or the speed command being sent to a variable frequency drive . With the low end of the signal being 4 mA rather than zero, the instrumentation, and the technician, can distinguish between a zero signal and a broken wire or broken instrument .

When referring to sensors, there are two-wire 4-20 mA signals, in which the sensor and the output signal are “loop-powered” with a 24 VDC power supply (Fig . 1), and three-wire 4-20 mA signals where the device requires 24 VAC (or VDC) power and generates the 4-20 mA signal (Fig . 2) directly . The examples shown are based on the Kele DPA Series differential pressure transmitters, but the wiring is typical of all the 4-20 mA sensors in our catalog .

Any 4-20 mA signal can be converted to a 2-10 VDC signal by putting a 500Ω resistor across the signal +/- terminals . The controller will “see” 2-10 VDC across the resistor as the 4-20 mA flows through it (Ohm’s Law, V=IR) . In the example above, if a controller analog input requires a voltage instead of a current signal, installing the resistor across the two input terminals at the controller will do the trick .

The same resistor solution holds true for sending a signal to an actuator used to drive a damper or valve . If a controller analog utput is 4-20 mA, and the actuator requires a 2-10 VDC signal, just install the resistor at the actuator signal input terminals . For 1-5 VDC, substitute a 250Ω resistor instead of 500Ω .

Verifying the signal is easy; put a meter in series with the 4-20 mA signal wires so the current flows through the meter . Set it to measure DC milliamps, make sure the leads are plugged into the common and milliamp sockets, and set the scale to read in the range that includes 20 mA . See the sidebar at the top of the next page to avoid a pitfall that we hear about all too frequently!

There you have it . Give us a call if you have questions . Did you know the Technical Sales Reps in the Kele Sales Department have combined over 120 years in the HVAC Controls business? We know our business, we can help, and we’re here to make it easy for you!

24 VDCPower Supply

4-20 mA

Two-wire 4-20 mAwith 24 VDC Power Supply

24 VACTransformer

4-20 mA

Three-wire 4-20 mAwith 24 VAC Transformer

VAC

G

H

Fig. 1 Fig. 2

24 VDCPower Supply

4-20 mA

Two-wire 4-20 mAwith 24 VDC Power Supply

24 VACTransformer

4-20 mA

Three-wire 4-20 mAwith 24 VAC Transformer

VAC

G

H

Fig. 1 Fig. 2

Page 109: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1115

PRESSUREPRESSURE

18

PSIPRESSURE EQUATIONS

PRESSURE CONVERSION FACTORS

psig = in of H20 x 0 .0361 in of H20 = psig x 27 .71psig = ft of H20 x 0 .4335 ft of H20 = psig x 2 .31psig = mm of H20 x 0 .0014 mm of H20 = psig x 703 .1psig = cm of H20 x 0 .0142 cm of H20 = psig x 70 .31psig = in of Hg x 0 .4912 in of Hg = psig x 2 .036psig = mm of Hg x 0 .0193 mm of Hg = psig x 57 .71psig = cm of Hg x 0 .193 cm of Hg = psig x 5 .771psig = kg/cm2 x 14 .22 kg/cm2 = psig x 0 .0703psig = bar x 14 .50 bar = psig x 0 .0689psig = mbar x 0 .0145 mbar = psig x 68 .95psig = Pa x 1 .45 x 10-4 Pa = psig x 6895psig = kPa x 0 .1450 kPa = psig x 6 .895psig = atm x 14 .696 atm = psig x 0 .068psia = psig + 14 .696 (sea level)

AIR PRESSURE / FLOW FORMULAS

V = 4004 Pv Where: V = Velocity (fpm) Pv = Velocity pressure ("W .C .)Pv* = V 2 Pt = Total pressure ("W .C .) 4004 Ps = Static pressure ("W .C .)

Pv = Pt - Ps * Pv may be determined by a pitot tube . Scim = SCFM*1728

HEAD PRESSURE FORMULAS

Head (feet) = psig x 2 .31 psig = feet head x specific gravity* specific gravity 2 .31

PRESSURE DEFINITIONS

Absolute Pressure The sum of gauge pressure and atmospheric pressureAtmospheric Pressure The pressure existing at the surface of the earth caused by the weight of a

column of air above the point of measurement; varies with altitude and weather conditions, but 14 .696 psia is generally accepted except in high altitude locations

Gauge Pressure A pressure reading above atmospheric pressure; most instruments read gauge pressure

Pitot Tube A tube that is inserted in a duct to measure both total pressure and static pressure and has separate connections so each pressure may be sensed

Pressure Transmitter A device that converts a pressure input into an electrical signalSnubber A device used to dampen pulsations to pressure instrumentsStatic Pressure The outward push of a fluid against the walls of a container in every directionTotal Pressure The sum of static pressure and velocity pressureVelocity Pressure The pressure exerted by the velocity of a fluid; generally obtained by measuring

total pressure and static pressure and subtracting the static pressure from total pressure

( )

(*Water - 1 .00, Ethylene glycol - 1 .125)

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

Page 110: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1116

NEW!PRESSURE

PSI

18

MEASURING AIRFLOW

Building automation systems (BAS) are often required to measure the actual airflow in air handling systems . Although there are many ways to measure airflow, the two most com-monly used with a BAS are the hot wire anemometer and various devices that measure the velocity pressure of the air . Once the velocity pressure is known, the BAS is then able to calculate airflow . Each method has advantages as well as disadvantages .

Hot Wire AnemometersThe primary advantage of the hot wire anemometer is that it can provide an analog output that is proportional to flow, and no square root calculation is required to measure airflow . The disadvantages of the hot wire anemometer are that it mea-sures only one point in the cross section of the duct, and it may require periodic recalibration (see Model AVS-200 and Model EE65 in the Flow section) .

Differential Pressure DevicesPitot tubes and averaging tubes are among the flow measur-ing devices that measure velocity pressure . The pitot tube may be used with a differential pressure transmitter to deter-mine airflow at a relatively low cost; however, the BAS con-troller must be able to calculate the square root of the velocity pressure . Also, the pitot tube measures the velocity at only one point in the duct .

Airflow Calculations with a Pitot TubeFigure 1 shows a typical pitot tube . In this diagram, Ps is the static pressure exerted in all directions, such as the pressure inside a balloon . This is sensed by the radial holes in the pitot tube . Pv is the velocity pressure caused by the momentum of the air moving in the duct . Pt is the total pressure and is the sum of the static pressure and velocity pressure (Pt= Ps+Pv) .

The opening in the tip of the pitot tube measures total pres-sure . Since only velocity pressure is required to calculate air

flow, the total pressure is piped to the high-pressure port of a differential pressure transmitter, and the static pressure is piped to the low-pressure port of the transmitter . The differ-ential pressure that is then measured is the velocity pressure (Pv=Pt-Ps) . Once the velocity pressure is known, velocity may be calculated by the following formula:

Air density is normally assumed to be 0 .075 lb/ft3, based on 70°F dry air at 29 .9” Hg barometric pressure . If corrections must be made for barometric pressure or air temperature, the air density may be calculated by the following formula:

If air density is assumed to be standard (0 .075 lb/ft3), the output of the differential pressure transmitter may be used to calculate air velocity by the following formula:

For accurate results, a differential pressure transmitter should be selected that corresponds as closely as possible to the velocity pressure to be measured (see Figure 2).

Once the air velocity is known, airflow in cfm is simply the duct inside area multiplied by air velocity .

Notice that V is average duct velocity . When using a pitot tube, velocity can be measured at only one point in the duct . In a straight duct run, the velocity will be greatest in the center of the duct and lowest near the duct wall where the effects of friction slow airflow . The size and the shape of the duct determine how much the center velocity will deviate from the average velocity . To obtain an approximate average duct velocity when a pitot tube is installed in the center of a straight duct, reduce the center velocity by 10% . This will yield results that should be accurate to within ±5% .

Air Velocity (fpm) = (Cf) x Mo - 4

where Cf = flow coefficient from Figure 2 Mo= pressure transmitter mA output

Airflow (cfm) = V x A

where V = average duct velocity (ft/min) A = duct cross sectional area (ft2)

PAIRFLOWP

Static PressureConnection

TotalPressure

Connection

160-xxxPitotTube

Low-Pressure PortHigh-Pressure Port

T30-xxxDifferentialPressure

Transmitter

ControllerInput

DCP-25024 VDC

Power Supply

PT

V+( )S

PS

PS

120 VAC

FIGURE 1. MEASURING AIRFLOW WITH A PITOT TUBE

Air Density = 1.325 x PB Twhere PB = barometric pressure in "Hg T = absolute temperature (°F + 460)

Velocity (fpm) = 1096 Pv

Dwhere Pv = velocity pressure in “W .C . D = air density in lb/ft3

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

Page 111: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1117

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

CONTROLLING DUCT PRESSURE

In this example, we are using the setpoint potentiometer on the UCM-420A to adjust the pressure, so the local setpoint should be enabled and the remote setpoint disabled. As the pressure in the duct increases, the control signal from the UCM-420A must decrease to slow down the fan speed, assuming the VFD is direct acting (speed increases with an increase in control signal); therefore, reverse-acting control should be selected for the UCM-420A. The integral reset rate and throttling range required will vary from system to system and must be determined in the field.

Since pulse-width modulation is not to be used in this example, all PWM functions are disabled. The jumpers will be set for three-wire potentiometer local setpoint and 4-20 mA input from the pressure transducer. The instructions furnished with the UCM-420A explain in detail how to set the DIP switches and jumpers to accomplish the above setting. The input to the UCM-420A from the static pressure transducer has a range of 0-3” W.tC. Therefore, when there is no pressure in the duct, the input will be 4 mA; when the static pressure in the duct is 3” W.C., the input will be 20 mA. The setpoint potentiometer scale on the UCM-420A is labeled 0-100%. In our example, we require 2” W.C. in the duct, so the setpoint potentiometer should be set for 2/3 x 100 = 67%. Tuning the SystemAs stated earlier, the throttling range and integral reset must be fine-tuned in the field and cannot be calculated. The throttling range is defined as the amount of signal change at the input required to cause the output to go through its entire range (4-20 mA). For example, a 50% throttling range means

that for every 1 mA change in the input, there will be a 2 mA change in the output. To properly adjust the throttling range, first disable the integral reset and set the throttling range at 100%. Then, reduce the throttling range in increments until the controller begins to hunt. When the controller begins to hunt, the throttling range is too narrow, so widen it one step. The integral reset rate may now be adjusted. The integral reset corrects the output of the UCM-420A to compensate for the offset inherent in proportional-only controllers. The integral reset ramps the output in the direction that forces the input signal to exactly match the setpoint. The number of times per minute this offset is overcome by the output signal is the integral reset rate. The quicker the system responds, the higher (more resets per minute) the reset rate may be set. A Good SolutionThis control system will provide very smooth, precise static pressure control in the discharge duct. It will also save energy since the fan will use only as much horsepower as required to maintain the setpoint pressure. In this example, the pressure is adjusted with the setpoint potentiometer on the UCM-420A. This pressure could also be controlled by a remote potentiometer or an analog or pulse width signal from a BAS controller.

Another application would be controlling multiple zones (such as VAV boxes) from one BAS controller output by using the multiplex PWM mode. In this application, a Precon Type 3 thermistor could be used as the temperature input to each UCM-420A, and the BAS controller could send eight different setpoint signals to the zones. Multiple UCM-420As could receive the same setpoint signal.

PWM INPUTPWM INPUT

REM SPT INPUT

LOC SPT POT +

LOC SPT INPUT

LOC SPT POT –

INPUT

24 PWR

COMMON

MA SIG1112

B3

0

0

0

0

1

1

1

1

B6

0

0

0

0

1

B7

0

0

1

1

X

B8

0

1

0

1

X

B4

0

0

1

1

0

0

1

1

B5

0

1

0

1

0

1

0

1

MUXADDR

1

2

3

4

5

6

7

8

A6

0

0

0

0

1

1

1

1

A7

0

0

1

1

0

0

1

1

A8

0

1

0

1

0

1

0

1

PROPT .R .

10%

20%

35%

50%

65%

80%

90%

100%

UCM-420A DIP SWITCH SETTINGSTIMEBASE

2 .65

5 .2

12 .85

25 .6

.59-2 .93

A4

0

0

1

1

A5

0

1

0

1

RESETPER MIN

OFF

0 .5

1

2

"1" MEANSTURN SWITCH ON

"0" MEANSTURN SWITCH OFF

A3A2A1B1B2

LOCA

LSE

TPO

INT

FEED

BACK

REM

OTE

SE

TPO

INT

STATUS

B

A1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

MODEL DT13ESignal Isolator*

DCP-250

12

3456

78910

INPUT

OUTPUT +–+–

SIG IN

SIG IN

SIG OUT

SIG OUT

AC PWR

AC PWR

Isolated ControlSignal to VFD

* Required only if the VFD used requires an isolated control signal

+ –

Power Supply24 VDC

120 VAC

+–

Connect to duct

Open to the atmosphere

Hi

LoT30-030

Transmitter

UCM-420A

SWITCH OFF SWITCH ON

REVERSE ACTING

BOTH OFF >> REMOTE SETPT

SAMPLE AND HOLD MODE

BOTH OFF >> ANALOG

REMOTE SETPOINT

DIRECT ACTING

LOCAL SETPT ENABLE

REMOTE SETPT ENABLE

PWM REM SETPT SGLE UNIT

PWM REM SETPT MUX MODE

FIGURE 1. VARIABLE AIR VOLUME SYSTEM WIRING

Page 112: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1118

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

PROVIDING STEAM ISOLATION AND TEMPERATURE PROTECTION

Steam IsolationAll pressure transducers installed on steam lines should be isolated from the steam to protect them from damage. A steam pigtail syphon, such as the Model PT, may be used for this purpose.

Temperature ProtectionFrequently, it is necessary to measure the pressure of fluids at temperatures either above or below the operating range of available transducers. The expense of a special transducer can often be avoided if the pressure transducer is isolated from the pressure source by a short length of pipe or tubing.

The curves on Figure 1 show how to limit the temperature at the transducer to a range of 0° to 200°F (-17.8° to 93.3°C) for fluid temperatures between -400° and 1700°F (-204.4°C to 926°C). Figure 1 shows the various tubing lengths, sizes, and materials that can be used.

Deviation from these conditions will require some slight adjustments in the length of tubing selected, or if there is any doubt, a Model TM99A handheld thermometer on the transducer will readily verify proper operating conditions.

Note that a 6” (15.2 cm) length of 1/4” (0.64 cm) stainless steel tubing will effectively protect a transducer from a 1000°F (537.8°C) pressure source. Thus, pressure transducers capable of operating at 200°F (93.3°C) can measure the pressure of fluids having much higher temperatures.

Model PT

FIGURE 1. TUBING LENGTH TO ISOLATE TRANSDUCER FROM TEMPERATURE SOURCE

The curves shown on the chart are based on the following assumptions:

1. The pressure vessel is insulated to limit radiant heat transfer to the transducer. Thus, the major source of thermal input is via the connecting tube.

2. The pressure medium has a coefficient of thermal conductivity less than 0.4 BTU/hr/ft2/ft/°F (6 cal/hr/cm2/cm/°C). This figure encompasses a wide range of liquids and gases.

3. The ambient temperature around the transducer is 100°F (37.8°C).

4. The heat-transfer rate (convection) from the tubing to still air is 1.44 BTU/ft2/hr°F (1 cal/cm2/hr°C).

From Data Instruments Reference

L = Length of Tubing (inches)

OT

=

Tem

per

atu

re o

f P

ress

ure

So

urc

e (˚

F) T = 100˚F Maximum transducer temperature 200˚F

Minimum transducer temperature 0˚F

1 2 3 4 5 6 7 8 9 10

303SS 0 .25 OD X 0 .18 ID(0 .635 cm OD X 0 .457 cm ID

303SS 0 .25 OD X 0 .18 ID(0 .635 cm OD X 0 .457 cm ID

BRASS 0 .25 OD X 0 .18 ID(0 .635 cm OD X 0 .457 cm ID)

303SS 0 .125 OD X 0 .07 ID(0 .318 cm OD X 0 .18 cm ID)

2000

1800

1600

1400

1200

1000

800

600

400

200

0

-200

-400

A

Page 113: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!

1119

PRESSUREPRESSURE

18

PSI

WE MAKE IT EASY. kele.com 888-397-5353 USAMarch 2014

CONTROLLING DUCT PRESSURE

The Model UCM-420A is one of the most versatile products sold by Kele. Although this product is capable of performing many control functions, it was primarily designed as a setpoint controller. Since the introduction of the UCM-420A, responses from customers indicate that pressure control is a popular application for this product.

Controlling static pressure in a duct by varying fan speed with a variable frequency drive (VFD) is a common application. This system could also be used to control the pressure with inlet vanes, discharge dampers, bypass dampers, etc. The same principles involved in this application could be used in other control applications, such as controlling water pressure with variable speed pumping, VAV zone control, or humidifier control. A Model PCM pressure controller may be used to sense duct pressure and provide an analog Proportional plus Integral (PI) control signal to control this pressure. However, in this article, we utilized a DPL Series pressure transmitter and a UCM-420A setpoint controller so the relationship between the system components would be more clearly defined. A VAV ApplicationFigure 1 shows a simple variable air volume (VAV) system. As the spaces served by the VAV terminals are satisfied, the zone dampers will modulate closed and, without a pressure control system, the static pressure in the duct will rise. For this example, assume that a static pressure of 2” W.C. is required. To monitor the static pressure in the duct, we will use a DPL Series differential pressure transmitter with a range of 0-3” W.C. The 4-20 mA signal from this device will be fed into a UCM-420A setpoint controller, which in turn will control the speed of the fan by sending a 4-20 mA control signal to the fan’s VFD. The manual potentiometer on the UCM-420A will be used to

set the static pressure at the desired level. See the wiring diagram in Figure 2 on the next page for system wiring. This wiring diagram shows a Model DT13E signal isolator. The DT13E will not be needed unless the VFD requires an isolated control signal.

Programming the UCM-420AAll programming of the UCM-420A is done by DIP switches and jumpers. A list of the functions programmed by DIP switches, as well as those programmed by jumpers, is shown in Table 1. The proper settings for this example are also shown.

VAV Terminal

VAV Terminal

Supply

Air

Return

Air

PIControlSignal

AC Power In UCM-420A

24 VDC

T30-030

4-20 mAVFD

StaticPressureTubing

VAV Terminal

FIGURE 1. VARIABLE AIR VOLUME SYSTEM

TABLE 1. PROGRAMMED FUNCTIONS

DIP Switch Functions

Remote setpoint Disableenable/disableLocal setpoint Enableenable/disableDirect-/Reverse-acting Reverse actingIntegral reset rate As requiredThrottling range As requiredSingle unit PWM Disableenable/disableMultiplex PWM Disableenable/disable Multiplex unit address OffPWM time base Off

Jumper Functions

Remote setpoint signal None

Local setpoint signal Three-wire

potentiometer

Input signal 4-20 mA

Page 114: PRESSURE - Building Automation Products | Kele — Bypass Valve Assembly ... 25W100 — Refrigeration Gauge ... pressure applications where ...

NEW!PRESSURE

1120

NEW!PRESSURE

PSI

18

WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.kele.com888-397-5353 USA March 2014

BACK TO BASICS PRESSURE

One of the many common ties that bind all building automa-tion and energy management systems is sensing pressure . Pressure readings throughout a system are great indicators of system performance . Sensed pressure can also be used to in-directly control other variables like temperature and flow . Here are some of the pressures associated with Building Automation and Energy Management Systems:

Absolute Pressure The sum of gauge pressure and atmospheric pressure .

Atmospheric Pressure The pressure existing at the surface of the earth caused by the weight of a column of air above the point of measurement . Atmospheric Pressure varies with altitude and weather condi-tions, but 14 .696 psia is generally accepted except in high altitude locations .

Compound PressurePressure ranging from vacuum to gauge pressure .

Differential PressureThe difference between two pressures .

Gauge Pressure A pressure reading above Atmospheric Pressure . Most instru-ments read gauge pressure .

Static Pressure The outward push of a fluid against the walls of a container .

Total Pressure The sum of Static Pressure and Velocity Pressure .

Velocity Pressure The pressure exerted by the velocity of a fluid . Velocity pressure is generally obtained by measuring Total Pressure and Static Pressure and subtracting the Static Pressure from Total Pres-sure . The remainder is Velocity Pressure .

The two types of pressure most commonly applied in Building Automation and HVAC systems are Gauge Pressure and Differ-ential Pressure . Gauge pressure is often used to indicate things like the efficiency of compressors (via pressure transducers), to protect equipment (with pressure switches) . Differential pres-sure is often used to control building static pressure (through differential pressure transmitters), protect equipment (through differential pressure switches), and to indicate flow (usually by employing a pitot tube or venturi pressure sensor) .


Recommended