SCHOOL OF ARCHITECTURE, BUILDING & DESIGN Modern Architecture Studies in Southeast Asia (MASSA) Research Unit Bachelor of Science (Honours) (Architecture) BUILDING SCIENCE 2 [ARC 3413] Project 2 : Integration with Design Studio 5 Lighting Analysis Name: Eleanor Ng Cui Shan ID: 0302936 Lecturer Mr Sivaraman
Transcript

SCHOOL OF ARCHITECTURE, BUILDING & DESIGN

Modern Architecture Studies in Southeast Asia (MASSA) Research

Unit

Bachelor of Science (Honours) (Architecture)

BUILDING SCIENCE 2 [ARC 3413]

Project 2 : Integration with Design Studio 5 Lighting Analysis

Name: Eleanor Ng Cui Shan ID: 0302936

Lecturer Mr Sivaraman

Zoning of Spaces

GROUND FLOOR MEZZANINE PLAN

FIRST FLOOR MEZZANINE PLAN

ZONE 1

FIRST FLOOR PLAN

ZONE 2

FIRST FLOOR PLAN

ZONE 4

FIRST FLOOR PLAN

SECOND FLOOR PLAN

ZONE 5

FIRST FLOOR PLAN

ZONE 6

FIRST FLOOR PLAN

Standard MS 1525 LUX Recommendation - Lighting Standard MS1525 2001

Lighting must provide a suitable visual environment within a particular space

following the Code of Practice on Energy Efficiency and Use of Energy

Sufficient and suitable lighting for the performance and range of tasks and

provision of a desired appearance for general building area and restaurant.

Type of Interior, Task or

Activity

Em

LUX

UGRI Ra Remarks

1. General Building Areas

Entrance Halls 100 22 60

Lounges 200 22 80

Circulation Areas, Corridors 100 28 40 At exit and entrance

provide an transition zone

and avoid sudden change

Stairs, Escalators,

Travelators

150 25 40

Loading, Ramps, Bays 150 25 40

Canteen 200 22 80

Restroom 100 22 80

Room of Physical Exercise 300 22 80

Cloakrooms, Washrooms,

Bathrooms, Toilets

200 25 80

Sick Bay 500 19 80

2. Restaurant & Hotels

Reception, Cashier Desk 300 22 80

Kitchen 500 22 80

Restaurant, Dining Room 200 22 80 The lighting should be

designed to create

intimate atmosphere

Self-Services Restaurant 200 22 80

Buffet 300 22 80

Corridors 100 25 80 During night-time, lower

levels are acceptable

Multipurpose Hall 300 22 80 Figure 1: MS 1525 Standard Recommendation for Lighting

Lighting Analysis and Calculation

Daylight Factor

Defined as the ratio (in percentage, of indoors work plane illuminance (at a

given point) to the outdoor illuminance on a horizontal plane.

In order to calculate daylight factor, formulae below is used:

DF = E i

E ox 100%

Where,

DF = Daylight Factor

Ei = Illuminance due to daylight at a point on the indoors working plane

Eo = Simultaneous outdoor illuminance on a horizontal plane from an unobstructed

hemisphere of overcast sky = 32000 lux

(Malaysia standard outdoor daylight level: 32000 lux)

According to MS 1525 (2007),

DF (%) Distribution >6 Very large with thermal and glare problem

3-6 Good

1-3 Fair

0-1 Poor

Table 1: Daylight Factor and its distribution respectively

Lumen Method Calculation

Also called zonal cavity method, is a simplified method to calculate the light

level in a room. This method includes a series of calculations that uses

horizontal illuminance criteria to create a uniform luminaire layout in a space.

In short, it is the total number of lumens available in a room divided by the

area or zoning of the room. In order to perform this calculation, many factors,

coefficients, lamp lumen data and other quantities must be gathered.

Step 1:

Determine the light reflectance (%) for ceiling, wall, window and floor in the

overall space based on the reflectance table.

Table 2: Light reflectance table

Step 2:

Determine room index.

Room index (RI) is the ratio of room plan area to half the wall area between

the working and luminaire planes.

RI = L x W

Hm x (L+W)

Where,

L = Length of room

W = Width of room

Hm = Mounting height (vertical distance between the working plane and the

luminaire)

Step 3:

Identify utilization factor (UF) from table below.

Table 3: Utilization Factor Table

Step 4:

Determine number of fittings required, N.

N = E x A

F x UF x MF

Where,

E = MS 1525 standard illuminance over the specific zone

F = Lighting design lumens per lamp

UF = Utilization factor

MF = Maintenance factor

A= Area of horizontal working plane

Step 5:

Identify the Spacing to Height Ratio (SHR),

SHR is the ratio of distance between adjacent luminaires to their height

above working plane. For a rectangular arrangement of luminaires and by

approximately,

SHR = 1

Hm √

A

N

Where,

A = Total floor area

N = Number of luminaires

Hm = Mounting height (vertical distance between the working plane and the

luminaire)

Calculate minimum spacing between each fixtures.

Calculate number of row fixtures required along the width of the room.

Calculate number of fixtures required in each row.

Calculate axial spacing between each fixture.

Calculate transverse spacing between each fixture.

Daylight Factor Analysis

1. Second Floor – Zone 5 Foot Spa Hub

Time Luminance (lux) Average

11AM - 2PM 300 - 750 525

3PM - 6PM 200 - 220 210

DF = E i

E o x 100

Where, E o= Direct Sunlight = 32000 lux

DF = 525

32000 x 100

= 1.64%

According to the Standard MS1525 Daylight factor,

1.64% is located in the range of 1-3%, which Zone 3 is

considered as a FAIR zone.

ZONE 5

FIRST FLOOR PLAN

Diagram 1: Day Lighting Contour Diagram of second floor generated using Ecotect

2. Second Floor - Zone 6 Reading Lounge

Time Luminance (lux) Average

11AM - 2PM 300 - 888 594

3PM - 6PM 185 - 201 193

DF = E i

E o x 100

Where, E o= Direct Sunlight = 32000 lux

DF = 594

32000 x 100

= 1.86%

According to the Standard MS1525 Daylight factor,

1.86% is located in the range of 1-3%, which Zone 5 is considered as a

FAIR zone.

ZONE 6

FIRST FLOOR PLAN

Diagram 2: Day Lighting Contour Diagram of second floor generated using Ecotect

Artificial Lighting Analysis

1. Ground Floor Mezzanine – Zone 2 Restaurant

Location Ground Floor Mezzanine - Zone 2 Restaurant

Room Length, L 15.2m

Room Width, W 4m

Mounting Height of

Fitting (from work

plane),Hm

2.1m

For Ambient LED Lustre

Room Index, RI RI = L x W

Hm x (L+W)

RI = 15.2x 4

2.1x (15.2+4)

RI = 1.51

Reflection Factors Ceiling- greyish-White Plaster 60%

Wall - Brick 40%

Floor - Oak light 25%

Utilization Factor, UF 0.61

ZONE 2

FIRST FLOOR PLAN

Lighting Design

Lumens per lamp, F

136 l

Maintenance Factor,

MF

0.85

Area of Horizontal

Working Plane, A

60.8 m²

MS 1525 Standard

Luminance

200 lux

Number of fittings

required, N

For Ambient LED Lustre

N = E x A

F x UF x MF

N = 200 x 60.8

12x 136 x 0.61 x 0.85

N = 14.37~ 14

Conclusion Zone 2 need 14 fittings of Ambient LED Lustre in order

to perform its task with sufficient lighting.

Spacing to Height

Ratio (SHR) SHR =

1

Hm √

A

N

SHR = 1

2.1 √

60.8

14

SHR = 0.476 √4.32

SHR = 0.99

Spacing between

each fixtures (m)

S

Hm = 0.99

S

2.1 = 0.99

S = 2.08m

Number of row fixtures

required along the

width of the room

N = W

𝑆

N = 4

2.08

N = 1.92~ 2

Number of fixtures

required in each row N =

14

2

N = 7

Layout

plan of

lighting

fixtures

Diagram 3; Artificial Lighting Contour Diagram of Ground floor mezzanine generated using

Ecotect

1. First Floor Mezzanine Floor - Zone 4 Cafe

Location First Floor Mezzanine Floor - Zone 4 Cafe

Room Length, L 12.2m

Room Width, W 6m

Mounting Height of

Fitting (from work

plane), Hm

2.1m

2 Head Spotlight –LED

Room Index, RI RI = L x W

Hm x (L+W)

RI = 12.2 x 6

2.1 x (12.2+6)

RI = 1.92

Reflection Factors Ceiling- greyish-White Plaster 60%

Wall - Brick 40%

Floor - Oak light 25%

Utilization Factor, UF 0.67

Lighting Design

Lumens per lamp, F

500 l

ZONE 4

FIRST FLOOR PLAN

Maintenance Factor,

MF

0.85

Area of Horizontal

Working Plane, A

73.2m²

MS 1525 Standard

Luminance

200 lux

Number of fittings

required, N

For 2 Head Spotlight –LED

N = E x A

F x UF x MF

N = 200 x 73.2

2 x 500 x 0.67 x 0.85

N = 25.7 ~ 26

Conclusion Zone 4 need 26 fittings of 2 Head Spotlight LED in

order to perform its task with sufficient lighting.

Spacing to Height

Ratio (SHR) SHR =

1

Hm √

A

N

SHR = 1

2.1 √

73.2

26

SHR = 0.476 √2.82

SHR = 0.80

Spacing between

each fixtures (m)

S

Hm = 0.80

S

2.1 = 0.80

S = 1.68m

Number of row fixtures

required along the

width of the room

N = W

𝑆

N = 6

1.68

N = 3.57~ 4

Number of fixtures

required in each row N =

26

4

N = 6.5 ~ 7

Layout

plan of

lighting

fixtu

Diagram 4 : Artificial Lighting Contour Diagram of First floor mezzanine generated using

Ecotect


Recommended