MC-DPTAC www.amana-ptac.com 9/12 Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Supersedes 6/12 PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS WITH OUR DIGISMART® CONTROL BOARD & EMS PTAC SPECIFICATIONS AND ACCESSORIES CATALOG Assembled in the USA for 30 years: Units are 100% run-tested and triple-tested for leakage. First-Year Warranty: Parts & Labor on entire unit Second through Fifth Year: Parts & Labor on certain sealed system components Second through Fifth Year: on certain functional parts only * Complete warranty details available from your local dealer or at www.amana-ptac.com.
Transcript
Page 1: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 9/12Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Supersedes 6/12

Packaged Terminal air condiTioners and HeaT PumPs

wiTH our digismarT® conTrol Board & ems

PTac sPecificaTions and accessories caTalog

Assembled in the USA for 30 years: Units are 100% run-tested and triple-tested for leakage.

• First-Year Warranty: Parts & Labor on entire unit• Second through Fifth Year: Parts & Labor on certain sealed

system components

• Second through Fifth Year: on certain functional parts only* Complete warranty details available from your local dealer or

at www.amana-ptac.com.

Page 2: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

2 www.amana-ptac.com MC-DPTAC

• EnergyEfficiencies:WithEERsupto11.7andCOPsupto3.4,ourunit’shighefficienciesmayqualifyyouformanyoftherebatesofferedbyelectricalpowercompanies.

• QuietOperation:OurPTAChasbeenredesignedtobethequietestPTACwe’veeverbuilt.Theunit’sstate-of-the-artdesignandconstructionprovideaquietenvironment,allowinggueststoenjoypeaceful,sleep-fillednights.• Twofanmotors(indoor/outdoor)• Indoortangentialfanforquietoperation• STCof28

• AssembledintheUSAfor30years:assembledatourplantinFayetteville,TN,usingGoodmanresourcesincludingengineering,production,andtesting.

• IncreasedDehumidificationCapacity:Maintainlowerhumiditylevelsinroomswhilecoolingthemwithouttheneedforexpensiveadd-ons.Asaresult,guestsfeelmorecomfortableathighertemperatures,thusreducingcoolingcosts.

• Seven-ButtonTouchPad:Providescompletecontroltoguestsforin-roomcomfortwhilemaintainingenergyefficiency.• Five-YearLimitedWarranty:Enjoyoneofthemostcomprehensivewarrantiesintheindustry:FirstYear:parts&labor;Secondthroughfifthyears:parts&laboroncertainsealedsystemcomponents;secondthroughfifthyears:oncertainfunctionalpartsonly.Forcompletewarrantydetails,visitwww.amana-ptac.com.

• 100%RunTested:Allunitsare100%runtestedatourplantinFayetteville,TN,includingleakchecksduringmanufacturingandagainpriortoshipmentatthewarehouse.

• 7⅝”UnitFrontDepth:Enhancevaluableroomspacewithourslimunitfront,whichhasasleek7⅝”depth,oneoftheshallow-estsilhouettesintheindustrytoday.Inaddition,toinhibitguest-tampering,thefrontcanbesecuredtothechassiswithahiddenscrew.

• RemovableCondenserShroud:Allowseasyaccesstoenableregularcleaningofcoils,whichisessentialtomaintainunitefficiencyandprotectthecompressorforlongunitlife.

• EasyPull-OutFilters:Ourfiltersarewashableandeasytomaintain.• FilterDryerforSealedSystemRefrigerant:Standardinallunitstoprotectthecompressorandlengthenthelifeoftheunitbyremov-ingmoistureandpreventingacidformation.

Removable/Cleanable ShRoud foR eaSy Cleaning

filteR dRyeR

eaSy Pull-uP filteRS

Control Board

sTandard feaTures

Page 3: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 3

sTandard feaTures (conT.)• CondensateDispersionSystem:Ourcondensatedispersionsystemremovescondensatefromindoorcoolingoperationbythrowingwaterdirectlyontotheoutdoorcoilforrapidevaporationandincreasedcoolingefficiencies.Theslingerringonthenew,enhancedfandrawswaterupandintothefanblades.Thiswateristhenatomizedandevaporatedintotheatmospherethroughthecondenser.Increasedsurfaceareafromthecoilallowsmorewatertobeevaporatedonthesidesofthecoilsandhelpstominimizecondensaterun-off.

• FrontDeskControl:EachunitcomesequippedwiththeDigiSmart™controlandenergymanagementsoftware.WithDigi-Smart™usingtheoptionalRFAntennae,allunitscanbewirelesslyconnectedtoacentralhubforenhancedenergysavingsanddiagnostics.AmanabrandPTACsalsohavealow-voltageinterfacecapabilitywithafield-suppliedfront-deskON/OFFswitch.(SeePage4.)

• RoomFreezeProtection:Whentheunitsensestemperaturesof40°Forbelow,theunitactivatesthefanmotorandeithertheelectricresistanceheaterorthehydronicheater.

• Easy-to-useControls:Nocomplexcontrolstoconfuseyourguestsandcreatephonecallsforyourmanager.Controlsareeasytoread,understand,andactivate.Ournew7-buttoncontrolpanelprovidesguestswithcompletecontroloftheunitfortheirin-roomcomfortwhilemaintainingoverallenergyefficiency.

• EasytoServicewithOn-BoardLEDDiagnostics:Themaincomponentsareeasilyservicedandthereisnoguessingtodeterminetheproblemwithoureasy-to-readdiagnostics.

• StonewoodRoomFront:OurStonewoodroomfrontstrikesthebalancebetweenattractivestylingandpracticaldesign.Distinc-tivecontoursandamodernappearanceenhancethecharacterofeventhemostluxuriousroom,whilethesleek7⅝”depthmaximizesusablespaceforyourguests.

• RemoteThermostatControl:WhentheDigiSmart™wirelessremotethermostat(DS01E,soldseparately)issetup,boththeremotethermostatandunitcontrolpanelcontinuetocontroltheunit,providingflexibilityandhome-likesystemcontrol.Installa-tionrequiresnomorethanpressingtwobuttons.Noneedtorunwiresormakeelectricalconnections.

• RemoteTemperatureSensing:Guestsenjoyultimatecomfortwithconsistentclimatecontrol.Whenthefield-installedthermistor(RTS03)isused,theunit-mountedthermostatisoverriddentoallowmoreaccurate,internalwall-sensingofroomambienttemperature.

• ExtendedHeatPumpHeating:Heatpumpmodelswilloperateintheheatingmodedowntoaslowas24°Foutdoorambienttem-perature.

• ZeroFloorClearance:Theunitcanbeinstalledflushtoafinishedfloor,ifdesired.(Someaccessoriesdonothavezeroclearance).• 30-SecondFan-OffDelay:Thefancontinuestorun30secondsafterthecompressorhasstoppedineithercoolingorheatpumpmodeandafterelectricheathasbeenturnedoff.Thisimprovesefficiencybydispersingtheconditionedaironthecoilsintotheroom.

• CompressorLock-In:Thisfeaturehelpsprolongthelifeofthecompressorbypreventingshort-cycling.WhenthecompressorisswitchedfromOfftoOnbecauseroomtemperaturehasrisenorfallenbelowthespecifiedlimit,itwillremainonforatleast4minutes.Ifthetemperatureset-pointischangedduringthis4minutes,thelock-infeatureisoverridden.

• AutomaticEmergencyHeat:Nomore“myunitisnotheating”complaintsduringthemiddleofthenight.Heatpumpunitswillautomaticallyswitchovertoelectricresistanceheatiftheheatpumpcompressorsystemfailsoriftheheatingloadisgreaterthantheunitcapacity.

• ConstantFanMode:Takeadvantageofeachunit’sdualoptions—selectcontinuousfanoperationorcyclethefanONandOFFwiththethermostat.Ournew7-buttondesignallowsgueststoselectfanperformancewhileallowingtheownertohavetheunitreverttothedesiredprogramofcontinuousfanorcyclewithconditioning.

• HiddenVentilationControl:Theventilationcontrolleverishiddenfromtheoccupant'sviewtoallowyoutomanageventilationrequirements.

• High-PressureSwitch:Protectstheunitfromhighpressureanddamagetotheunit,helpingtoensurelongunitlife.

Page 4: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

4 www.amana-ptac.com MC-DPTAC

brings together our best PTAC everwith our best EnergyManagement Software andnow integrationwithPropertyManagementandFrontDeskManagementSoftware.ReducePTACenergy consumptionby35%ORMORE* throughthepowerofthein-unitEnergyManagementSystem,programmabletemperatureset-backandlimitscombined.ReducePTACmaintenancecostthroughourautomatedmaintenancenotificationsystem.Improvedmaintenancesustainsenergyefficiency(EER)andprolongsPTAClife,keepingequipmentrunningatitsdesignedefficiencylevelandroomguestsmorecomfortable.

THe amana Brand digismarT soluTion

in-room: “self-insTallaBle” wireless PeriPHerals

TheDigiSmartOccupancySensorcompletesthein-roomequipment.Thisinfraredsensorcandetermineiftheroomisoccupiedorempty,andwhenemptysignalsthePTACtoadjustthetemperaturetosaveenergybasedonprogrammablesetbacks.

TheDigiSmartWirelessRemoteThermostatcanmountonthewallanywhereintheguestroom.BatterypoweredandwithitsownwirelessabilitytocommunicatewiththePTACtomaintainroomtemperature.Bestofall,nowirestorun.ThePTACandThermostatconnectatthepressofabuttonandarepermanentlylinked.ThethermostatandPTACworkin-synctodisplayaccuratetemperature.

TheDigiSmartWirelessAntenna installs inside thePTACwitha snap-inconnector. Installing theantennaallows thePTAC tocommunicatewirelesslywithotherdevicesintheroomandtotheDigiSmartnetwork.>45,000+roomshavehadwirelessinstallationssince2005>Totalwirelessdevicesdeployedtodate:120,000+

TheAmanabrandDigiSmartPTACwithantenna,combinedwiththeself-installable,wirelessThermostatandOccupancySensorgivethepropertyownercompletecontrolovertheequipmentsettingsandcanreducePTACenergyusageby35%ORMORE.*

siTe-level —cenTral wireless conTroller

>Site-widePTACConfiguration>Site-widePTACDiagnostics>FrontDeskSystemInterface>EmailReporting>InternetAccessibleWebUserInterfaceEnterprise

*ThesesavingsrepresentestimatedsavingsovertimeascomparedtothesamePTACmodelwithouttheDigiSmartEMSSysteminstalledandweregeneratedusinggeneralassumptionsincludingenergyloads,localweatheraveragesanduseofoccupancycontrols.Actualsavingswillvaryaccordingtoactualusehabits,roomsquarefootage,andhowtheunitisinstalled.

Page 5: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 5

enTerPrise — mulTiPle wireless conTrollers

CentRal monitoRing and

ContRol of multiPle PRoPeRtieS

>DataWarehousing>SavingsAnalysis>EmailReporting>VirtualMetering>LoadShedding

weB-Based, real-Time moniToringamana® Brand digismarT™ conTroller:AllofthePTACsinthebuildingcanbemanagedthroughasingleinterfaceonaPC.

FEATURES INCLUDE: Full unit details for every PTAC, visible from the front desk or home office, automatic emails for PTACmaintenance,abilitytochangeallsettingsontheunit,andenhanceddiagnostics.Monitorupto170PTACs,WIRELESSLY,withonecontroller.Additionalcontrollerscanexpandthenetworkforadditionalrooms/properties.

>SystemVerification>GlobalSetbacks>EMSConfiguration>SiteStatistics>BatteryNotices>EmailReporting>UnitHealth>UnitCodeAlerts

Temp Limiting – Each PTACcanbe configuredwith a heat-ing and cooling temperatureset-pointlimit.Setbacks–Oncearoomisdeclaredunoccupiedbytheoccupancysensor,thePTACprogressesthroughthreedifferenttemperaturesetbacks,configuredasthreedegreeandtimepairs(Anexampleconfigurationislistedbelow).1st:2°,30mins–Setbackthetemp2degreesafter30minutes2nd:4°,1hr–Setbackthetemp2moredegreesafter30moreminutes3rd:8°,3hrs–Setbackthetemp4moredegreesafter2morehoursUnrentedSet-Points–Byintegratingwithyourproperty'sFrontDeskSystem,thePTACswilladjusttospecificset-pointswhennolongeridentifiedasrentedinthesystem.

Page 6: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

6 www.amana-ptac.com MC-DPTAC

nomenclaTure

 

Basic  Model  Type Engineering  PTC Standard  Cooler  PTAC Major  &  Minor  RevisionsPTH Standard  Heat  Pump  PTHPDRY Dehumid  Cooler  PTAC Features  Code

A Standard  ModelCooling  Capacity C Corrosion  Protec>on  (Seacoast)07 7000BTU/h 60  Hz D Power  Door09 9000  BTU/h 60  Hz F Fuse  Holder  (230/208  Only)12 12000  BTU/h 50  or  60  Hz H Hydronic  Heat-­‐Capable15 14000  BTU/h 60  Hz P Condensate  Pump  (PTH  Only)

Q Quiet  STC  31  ChassisRated  Voltage R RF  Antenna2 115V,  60  Hz,  1  Ph V Power  Vent3 230/208V,  60  Hz,  1  Ph X placeholder4 265V,  60  Hz,  1  Ph W Hard-­‐Wired  (PTQC)5 240/220V,  50  Hz,  1  Ph

Use  up  to  4  as  needed  in  alphabe>cal  orderDesign  Series Examples:E R-­‐410A PTC123E50AXXX PTC073E35CRXXG R-­‐410A PTC123E50CXXX PTC073E25CQRWHeater  Size00 No  Electric  Heat 3.5  kW  (230/208V)15 1.5  kW 3.7  kW  (265V)25 2.5  kW 5.0  kW50

35

AA

1,2,3 4 5 6 7,8,9 10,11,12,13 14

PTC 07 3 E 35 AXXX

Allunitscomewithfactory-installedpowercords.Allunitslessthan250voltscomewithLCDIdevice.

PowerReceptacleConfiguration

NEMA6-30R; 250V receptacle,used on 230/208V units

GNEMA7-30R; 277V receptacle,used on 265V units

G NEMA6-15R; 250V receptacle,used on 230/208V units

G NEMA6-20R; 250V receptacle,used on 230/208V units

G

WNEMA7-20R; 277V receptacle,used on 265V units

G

277VRatingPowerCordPlugsNEMA7Configuration

G

W

20 amp

G

W

30 amp

250VRatingPowerCordPlugswithLCDIDeviceNEMA6Configuration

PowerCordPlugs

15 amp 20 amp 30 amp

Power cord configuraTion

Page 7: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 7

ProducT sPecificaTions: PTc models — cooling/elecTric HeaT (conT.)230/208 Volts

Model ⁶, ⁸, ⁹PTC

073G***XXXPTC

093G***XXXPTC

123G***XXXPTC

153G***XXX

Voltage ³ 230 / 208 230 / 208 230 / 208 230 / 208

Capacity (BTU/h) 7,700 / 7,700 9,000 / 9,000 11,700 / 11,500 15,000 / 14,700

Amps ¹⁰ 3.5 / 3.5 4.1 / 4.1 5.6 / 5.6 7.0 / 7.0

Watts ¹⁰ 670/660 805/785 1135/1105 1500/1470EER 11.5/11.7 11.2/11.5 10.3/10.4 10.0/10.0

Unit without Electric Heater

Min. Circuit Amps ², ⁴, ¹⁰ 4.2 4.9 6.8 8.5

CFM (Cool/Wet Coil)High 290 290 290 340

Low 264 264 264 314

CFM (Dry Coil)High 310 310 310 360

Low 282 282 282 332

Ventilated Air, CFM (Fan Only)* 65* 65* 65* 65*

Dehumidification (Pints/Hr.) 1.7 2.2 3.6 4.4

Net Weight (lbs.) 98 102 102 113Ship Weight (lbs.) 113 117 119 130

265/277 Volts

Model 1, 6, 8 PTC074G***XXX

PTC094G***XXX

PTC124G***XXX

PTC154G***XXX

Voltage ¹, ³ 265 265 265 265

Capacity (BTU/h) 7,700 9,000 12,000 14,800

Amps ¹⁰ 3.0 3.6 4.8 6.0

Watts ¹⁰ 670 795 1,165 1,480EER 11.5 11.3 10.3 10.0

Unit without Electric Heater

Min. Circuit Amps ², ⁴, ¹⁰ 3.6 4.4 5.9 7.4

CFM (Cool/Wet Coil)High 290 290 290 340

Low 264 264 264 314

CFM (Dry Coil)High 310 310 310 360

Low 282 282 282 332

Ventilated Air, CFM (Fan Only)* 65* 65* 65* 65*

Dehumidification (Pints/Hr.) 1.7 2.2 3.6 4.4

Net Weight (lbs.) 98 102 102 113Ship Weight (lbs.) 113 117 119 130

* Actual vent CFM performance will vary due to application and installation conditions.Notes¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply. ³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts. ⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and

factory-installed on all Amana® brand 265-volt chassis). See heater performance ⁵ Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.

Page 8: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

8 www.amana-ptac.com MC-DPTAC

230208 voltS

Model ⁶, ⁸, ⁹PTH

073E**AXXXPTH

093E**AXXXPTH

123E**AXXXPTH

153E**AXXX

Voltage ³ 230 / 208 230 / 208 230 / 208 230 / 208

Capacity (BTU/h) 7,600 / 7,500 9,000 / 8,900 11,500 / 11,100 14,000 / 13,900

Amps ¹⁰ 3.5 / 3.5 4.1 / 4.1 5.6 / 5.6 7.0 / 7.0

Watts ¹⁰ 650 / 620 770 / 765 1095 / 1065 1460 / 1465

EER 11.3 / 11.4 11.1 / 11.1 10.2 / 10.1 9.6 / 9.5

Unit without Electric Heater

Min. Circuit Amps ², ⁴, ¹⁰ 4.2 5.0 6.8 8.5

CFM (Cool/Wet Coil)High 290 290 290 340

Low 264 264 264 314

CFM (Dry Coil)High 310 310 310 360

Low 282 282 282 332

Ventilated Air, CFM (Fan Only)* 65* 65* 65* 65*

Dehumidification (Pints/Hr.) 1.7 2.2 3.6 4.4

Net Weight (lbs.) 108 112 115 126

Ship Weight (lbs.) 123 127 132 143

265,277 voltS

Model ¹, ⁶, ⁸PTH

074E**AXXXPTH

094E**AXXXPTH

124E**AXXXPTH

154E**AXXX

Voltage ¹, ³ 265 265 265 265

Capacity (BTU/h) 7,500 9,000 11,500 14,000

Amps ¹⁰ 3.0 3.6 4.8 6.0

Watts ¹⁰ 635 780 1115 1430

EER 11.6 11.1 10.0 9.7

Unit without Electric Heater

Min. Circuit Amps ², ⁴, ¹⁰ 3.6 4.4 5.9 7.3

CFM (Cool/Wet Coil)High 290 290 290 340

Low 264 264 264 314

CFM (Dry Coil)High 310 310 310 360

Low 282 282 282 332

Ventilated Air, CFM (Fan Only)* 65* 65* 65* 65*

Dehumidification (Pints/Hr.) 1.7 2.2 3.6 4.4

Net Weight (lbs.) 108 112 115 125

Ship Weight (lbs.) 123 127 132 142

* Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions. See Notes on previous page

ProducT sPecificaTions: PTH models — cooling/HeaT PumP/elecTric HeaT

Page 9: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 9

230/208 voltS

Heating CapacityPTH

073E**AXXXPTH

093E**AXXXPTH

123E**AXXXPTH

153E**AXXX

Voltage ³ 230 / 208 230 / 208 230 / 208 230 / 208

BTU/h ⁵ 6,800 / 6,800 8,300 / 8,100 10,900 / 10,500 13,500 / 13,300

Amps ¹⁰ 3.5 / 3.5 4.1 / 4.1 5.6 / 5.6 7.0 / 7.0

Watts ¹⁰ 605 / 605 735 / 720 1040 /1020 1365 / 1345

COP5 3.3 / 3.3 3.3 / 3.3 3.1 / 3.1 2.9 / 2.9

CFM (Dry) 310 310 310 360

265/277 voltS

Heating CapacityPTH

074E**AXXXPTH

094E**AXXXPTH

124E**AXXXPTH

154E**AXXX

Voltage ³ 265 265 265 265

BTU/h ⁵ 6,800 8,200 11,000 13,500

Amps ¹⁰ 3.0 3.6 4.8 6.0

Watts ¹⁰ 585 730 1040 1365

COP ⁵ 3.4 3.3 3.1 2.9

CFM (Dry) 310 310 310 360

COP=CoefficiencyofPerformance;perARItestprocedures,unitsareratedforcapacitiesandefficiencies.SeeNotesonPage7.

ProducT sPecificaTions: PTH models — reverse-cycle HeaTing Performance

ProducT sPecificaTions: PTc / PTH models — elecTric HeaT Performance(PrimaryHeatingforPTCModels;AuxiliaryHeatingforPTHModels;SeebelowforPowerCordConfiguration)

VoltageElectric

Heat (kW)No. of Stages

Nominal Heating (BTU/h)Total

Watts6

Total Amps

Min. Circuit Ampacity²

MOP4 (amps)

Power Cord

@ 230V @ 208V @ 265V

230/208V 2.5 1 8,500 6,800 - - 2,570 / 2,115 11.2 / 10.1 14.0 15 6-15 P

230/208V 3.5 1 12,000 9,900 - - 3,570 / 2,935 15.5 / 14.1 19.4 20 6-20 P

230/208V 5 1 17,100 14,000 - - 5,070 / 4,160 22.1 / 20.0 27.5 30 6-30 P

265V 2.5 1 - - - - 8,500 2,570 9.7 12.1 15 7-20 P

265V 3.7 1 - - - - 12,600 3,770 14.2 17.8 20 7-20 P

265V 5 1 - - - - 17,100 5,070 19.2 23.9 25 7-30 P

Page 10: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

10 www.amana-ptac.com MC-DPTAC

accessories

14⅛"42"

161 /1

6"

StandaRd outdooR gRille

SGK01B SinglePack

SGK01TB StonewoodBeige

aRChiteCtuRal outdooR gRille

AGK01CB AnodizedAluminum(Silver)

AGK01DB DarkBronze/Brown

AGK01TB StonewoodBeige

AGK01WB AmanaWhite

AGK01SB CustomColors

PGK01DB DarkBronze/Brown

PGK01TB StonewoodBeige

PGK01TB AmanaWhite

PWHK01C Wire Harness Kit

Wall SleeveS

Allourwall sleeveshave industry standarddimensionsof42”wide x16⅟₁₆”high. All Stonewood Beige G-90 metal wall sleeves are thermally insulatedand include a weather board for use during construction. The WS900D, SCandINTERNAL14⅛”depthistheindustrystandard. Sleevesmaybeshippedseparatelytoallowforinstallationduringconstruction.

outdooR gRilleS

Availableinstamped-aluminumorarchitecturallylouveredforapplicationwithanAmanabrandWS900Dwallsleeve.AGK—Extrudedaluminumarchitecturalgrilleavailablewithanodizedalu-

minumfinishorabaked-onpaintfinishfordurability.Choosefrom3stockcolorsoracustomcolortoblendwithyourbuilding’sexteriorcolorscheme.Colorsinclude:CB(ClearAnodized),DB(DarkBrown/Bronze),TB(StonewoodBeige),WB(White),SB(Special/CustomColors)

PGK—One-pieceinjectionmoldedgrilleusingapolymerblendofengi-neeredthermoplastichigh-impactstrengthmaterialwithchemicalresistanceandanexteriorUVprotectivecoating.Choosefrom3stockcolors:DB(DarkBrown/Bronze),TB(StonewoodBeige),WB(White)

Skirting Skirting

Leveling Legs

Optional Fuse Holder Location

Optional Power Switch and Circuit Breaker Location

Power Receptacle

Subbase Box Assembly

PTSB320E 230/208V 15/20A

PTSB330E 230/208V 30A

PTSB420E 265V 15/20A

PTSB430E 265V 25A

PTSB000E Non-electrical

Sub-baSe Kit

The fully skirted sub-base concealswiringwhile providing strong support, ifneeded.Plug-inreceptacleandfield-wiringaccessspeedsinstallation.Electricalaccessories,suchasfuseholders,circuitbreakersanddisconnectswitches,meetN.E.C.requirements.

loW-voltage WiRe haRneSS Kit

Forquickconnectionsoftheremote,orwired,thermostats,wiredEMS,orfrontdeskwithjumpersandconnectors.

REK10B Remote Escutcheon Kit (10-pack)Remote eSCutCheon Kit (not ShoWn)Optionalkitforusewithunitscontrolledviaawired,remotethermostat.Coverscontroltouch-padforwiredthermostatinstallations.

Eachkitcontains80wiresandwirenuts,enoughtoattachathermostatandoneadditionalaccessoryto10PTACunits.Wirescomeinassortedcolorsforeasyattachment.

DK900DCondensate Drain Kit (use with WS900E)

DK9001D Condensate Drain Kit (use with WS900B)

CondenSate dRain Kit

Attachestothewallsleevebasepanforcontrolledinternalorexternaldisposalofcondensate.

DK900D

StandaRd dePth SleeveS

WS900E StandardPTACsleeve

WS900SC Seacoasttripleprotected

WS900D-INTERNAL

Internaldrainonlyforwindow-wallinstallations(DK900Dsoldseparately)

extRa deeP SleeveS

We offer sleeves in several depths for thickerwallinstallationsorspecialroomconfigurations

WS9xxD1 16”to24”in1”increments

WS928D1 Extradeep28”

WS930D1 Extradeep30”

WS936D1 Extradeep36”

AGK or

PGK

SGK

PTPWHWK4 Armored Cable - all voltages

PTQC03A Quick Connect - 230/208 V

PTQC04A Quick Connect - 265 & 115 V

haRd-WiRe KitS

Usedtopermanentlywiretothechassiswhenastandardsub-baseandpowercordarenotused.

LL2B Leveling legs for WS9** sleeves

leveling legS

Giveswallsleevefrontsupportandhelpstoleveltheunitforinstallation.

Page 11: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 11

accessories (conT.)

FHK315C 230/208V 15A

FHK315E 230/208V 15A (R-410A)

FHK320C 230/208V 20A

FHK320E 230/208V 20A (R-410A)

FHK330C 230/208V 30A

FHK330E 230/208V 30A (R-410A)

fuSe holdeR Kit

Cartridge-stylefusescanbeinstalledinthefuseholderforuseinthesub-baseorchassis.Availablein15,20and30amp(includedon265-voltunit).

CBK3**C Circuit Breaker KitCiRCuit bReaKeR Kit (230/208v only) Thecircuitbreakerkit,availablein15,20or30amp,canbeusedwithAmanabrandsub-bases.Itgivesovercurrentprotection,anditslocationallowsyoutoturntheunitonoroffwithouttools.

Basepan

Condenser

Condenser BafflesDGK1B Condenser Baffle Kit

CondenSeR baffle Kit

For use on non-baffled grilles. These deflectors direct the air in toward thecenterandawayfromtheinlettopreventrecirculationofthehotcondenserair.

PSHW03A 230/208V

PSHW04A 265V

PoWeR diSConneCt SWitCh

ThePSHW**Apowerdisconnectswitchcanbeusedfor265-voltor230/208-voltphysicaldisconnect,whererequiredbylocalcodes.Theswitchisratedat30-ampcapacity.TheswitchisforusewithandAmana®brandstandardsub-basesorPTPWHWK4HardWireKit.

MDK02B Main Duct – R-22

MDK01E Main Duct – R-410A

EDK02B Extension Duct

duCt extenSion Kit

Extendsairdistributiontoanadjoiningroom.Consistsofamainductfortheroomoforiginandanextensionducttoreachtheadjoiningroomandterminalduct.PTDK01Aallowsforthenew“B”seriesunittoworkwiththe“A”seriesductkits.

Extension Duct Kit

TRANSITION BAFFLES

Main Duct Kit

Terminal Duct Kit

TDK02B Terminal Duct

PTDK01A Transition Duct Only – R-22

PTDK01E Transition Duct Only – R-410A

PVK3A 230/208V – R-22

PVK4A 265V – R-22

PoWeR vent Kit

InstallationofPowerVentincreasesCFMuptoapproximately95.Ventdoorwillautomaticallyclosewhenunitfanisoff.

R-410Amodelsmusthavethesekitsinstalledatthefactory.

CDP302 230/208V – R-22

CDP402 265V – R-22

CDP302E 230/208V – R-410A

CondenSate Removal PumP Canbefield-installed.Assistsinremovingcondensatedevelopedbyheatpumpoperationand transfers it to indoorcoil todissipate into roomwhileaddinghumiditytotheroom.

Sub-baSe extenSion CoveR Kit

Convertsolder30-ampsub-basestoallowforinstallationofthelarger30-ampLCDIpowercordandplugs.

SBEC10A 10 Pack

Page 12: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

12 www.amana-ptac.com MC-DPTAC

accessories (conT.)

ModelHeat

StagesCool

StagesDisplay Type

Shape & Orientation

D9945801 2** 1 Mech. Manual Rect./Horiz.1246001 1* 1 Digital Manual Rect./Horiz.1246003 2** 1 Digital Manual Rect./Horiz.

theRmoStatS

The following thermostats offer remote control. Any thermostat other thanthoselistedmustbesubmittedtoGoodmanCompany,L.P.,forapprovalpriortouse.

PDK3A 230/208V – R-22

PDK4A 265V – R-22

PDK3E 230/208V – R-410A

PDK4E 265V – R-410A

PoWeR dooR Kit Ventdoorwillautomaticallyopenwhenunitfanison.

HWK03B Hydronic Water Kit – R-22

HVK03B Hydronic Steam Kit – R-22

HWK03E Hydronic Water Kit – R-410A

HVK03E Hydronic Steam Kit – R-410A

hydRoniC heat Kit

Add-on kits fit all units allowing the additionof hydronicwater or hydronicsteamheat to cooling andheatingunits. The kits feature left- or right-handpiping.Unitretainscompleteserviceaccesswithakitinstalled.Unitmustbeconnectedtoandoperatedbyawallthermostat.

Hydronic Heat Kit-Top View

Hydronic Heat Kit-Right View

Hydronic Heat Kit-Side View

VS2WNCA* 2-way/24V/NC/Steam

VS2WNOA* 2-way/24V/NO/Steam

VW2WNCA* 2-way/24V/NC/End Switch

VW2WNOA* 2-way/24V/NO/End Switch

VW3WNC2B* 3-way/24V/NC/NO/End Switch

* Pop-top Actuator

hydRoniC valveS

WaterandsteamvalvesareavailableforusewiththeHWK03(water)andHVK03(steam)heatkits.

KL03B Security Key Lock (R-22)

KL03E Security Key Lock (R-410A)

SeCuRity Key loCKS

Inconjunctionwiththetamper-resistantfront,theinstallationofAmana®brandsecuritykeylockspreventstamperingofthecontrolsusedtosettemperature,heatingandcoolingfunctions.ULapprovedforinstitutionaluseonly.

RTS03 Remote wall-mounted sensorRemote temPeRatuRe SenSoR

Unit can bewired to sense room temperature away from the PTAC to haveaccuratereadings.

DS01E Thermostat: 2-way communications

DD01E Occupancy Sensor: EMS activation

DT01A Antennae / Router

GT01A Generic Radio Antenna / Router

DD01F Door Switch: EMS Activation

DP01E Web-enabled Platform Server

DL01E Web-enabled Platform Server Link

WiReleSS Rf (Radio fRequenCy) ContRolS

AllDigiSmartPTACscomefactory-readytobecontrolledviawirelessRFdevices.2.4Ghz80215.4protocolassuresrobustcommunicationsandresponse.

Page 13: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 13

accessories (conT.)WEMR01W Recess-mounted door switch

WEMS01B Surface-mounted door switch (Brown)

WEMS01W Surface-mounted door switch (White)

WiRed eneRgy management ContRol

Includes PIR occupancy sensor power from the DigiSmart control and doorswitch;cannotbeusedwitharemotewiredthermostat.

SECM1001AClimate Master 12½” Sleeve Extension (10 Pack)

SEZA0501AZone Aire 11½” Sleeve Extension (5 Pack)

Wall Sleeve extenSion adaPteR KitS

Room-sideextensionkitstoincreasethedepthoftheexistingsleevetoallowforanindustry-standardPTACtobeinstalled.

PTCB10B 10 Pack for R-22 units

PTCB10E 10 Pack for R-410A units

CuRtain baffle Kit

Thecolor-matchedpolymercurtainbaffleshelptopreventcurtainsfromfallinginto thedischarge air streamand causing recirculation, reducing efficienciesandshorteningcompressorlife.

inTake air filTersIt isextremely important toclean the inletairfiltersonceamonth (ormoreoften ifoperated industyordirty locationsorconditions)toproperlymaintaintheoperationalperformanceofthePTACunit.Thetwointakeairfilters(constructedofdurablepolypropylene)canbeeasilyinsertedintothecabinetfrontusingthecabinetfilterguides.Beforecleaningtheintakefilters,turntheunitoffbysettingthemodeswitchtotheOFFposition.Filtersshouldbecleanedasrequired.Thefollowingprocedureisusedtoremovetheintakefilters:1.Facingtheunit,pulluponthefilterhandleslocatedatthefronttopoftheunit.2.Pulleachfilterupwardandremove.3.Cleanfilterswithvacuumorwithrunningwater.Reversethisproceduretoreinstallthefilters.

Note:Accessoryfilterkitsareavailablefromyoursalesperson.Allfiltersarepermanentandcleanable.ConsultyourI&OManualforothermonthlycleaninginstructions.

monTHly mainTenance

sPare filTers Helpskeepdirtandlintoutoftheairandoffthecoil,thus increasing the unit's efficiency. Amana® brandfiltersareeasytoremove,washandreplace.

FK10A 10-pack - A Series

FK10B 10-pack - B, C & D Series

FK10E 10-pack - E Series (This model requires 2 filters per change.)

rePlacemenT cHarcoal filTer kiTAbsorbs airborne odors caused by cigarette, pipeor cigar smoke and odors caused by mold, mildew,etc. Filters are made of polyester fibers coated withactivatedcharcoalandareindividuallywrapped.Thesefilters are permanent and canbewashedor cleaned.CallyourAmana®brandPTACsalespersonfordetails.10filtersperpack.

CFK10A 10-pack - A Series (R-22)

CFK10B 10-pack - B, C & D Series (R-22)

Page 14: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

14 www.amana-ptac.com MC-DPTAC

uniT wiTH accessory wall sleeve and suB-Base accessory

3 "

1"1"

6 - 1 / 8" 9 - 9 / 16"24 - 5 / 16"

40"

42"

Location of external drain holes on bottom flange of Wall Sleeve

3" Clearanceto side walls

AirFlow

AirFlow

AirFlow

Air Discharge Grille ControlDoor

ToP view

11-3/8"

40°

21-1/2"

1 -3 /8"13/16"

14-1/8"

4"

2-3/4"

15°

7-3/8"

1/2" O.D.COPPER

DRAIN TUBE

AIR DISCHARGE GRILLE IS REVERSIBLE TO PROVIDE EITHER 15° OR 40° DISCHARGE ANGLE

HINGED CONTROL

DOOR

OPTIONALSUBBASE

13/16"

7/8"STAMPED GRILLE

1-3/8"ARCH GRILLE

WALL SLEEVE

16-1/16"

rigHT view

fronT view

58” lcdi cord seT — 230v/208v uniT*

58" CORD SET 230V/208V UNIT*

18" CORD SET 265V UNIT*

3-1/4" MIN

2"MAX

2-5/8"

42"

16-1/16"

R IGHTLEFT

1" AND 3/4" CONCENTRIC KNOCKOUTS BACK & BOTTOM OF SUBBASE (ELECTRICAL ONLY)

Page 15: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

MC-DPTAC www.amana-ptac.com 15

FINISHED FLOOR

42 1/4"

16 1/4" MIN

MAIN STUD

JACK STUDS

HEADER - 4" x 4" OR DOUBLE 2"x 4" ON EDGE

SUB-FLOOR

CRIPPLE

JACK STUD

ADJUST FRAMING TO SECURE THIS DIMENSION

framing for accessory wall sleeve (ws9XX)

Wall sleeve opening height should be squared with wall sleeve opening width.

H = 16¼"

W = 42¼"

Fastening Wall SleeveWhen installed in an opening, the Wall Sleeve must be horizontally level (side-to-side) and pitched ¼ bubble to the outside.

(NOTE: To ensure unit’s maximum efficiency, DO NOT over- or under-pitch.)

Installation Notes1. If Sub-base (PTSB***E) is installed, allow minimum 3¼” height clearance and maximum 5” height clearance between wall sleeve and floor; allow minimum

2¾” protrusion from a finished wall. See Note 4 if using hydronic units.2. Drain Kit (DK900D) shipped separately. Can be mounted either right side, left side or bottom of sleeve. If mounted to bottom of sleeve, allow 2” height

clearance from floor to bottom of sleeve.3. For UL approval, 265V units must use Amana® brand Sub-base (PTSB***E) or Amana® brand Hard Wire Kit (PSHW04A). Overcurrent protection on 265V

units must be by cartridge-style time delay fuses, which are included and factory-installed on the Amana® brand 265V chassis.4. If Hydronic Kit (HWK03 or HVK03) is installed, Wall Sleeve must extend exactly 3" into the room from the finished interior wall. If using the Amana® brand

Sub-base (PTSB***E), only the minimum 3¼” height clearance between wall sleeve and floor is permissible. Unit must also be operated with a remote-mounted thermostat.

5. If Duct Kit (MDK***) is installed, allow a minimum of 2⅜” into the room from the finished interior wall.

MountingHoles(Drilled by Installer)

PlasticAnchor

Screws

ExpansionAnchor Bolt

Toggle BoltWood Screw

AlternativeFastening Method(Field Supplied)

Wall Sleeve must extend a minimum of ¼” beyond outside wall to allow for proper caulking.

Page 16: PTac sPecificaTions and accessories caTalog · 2015. 5. 14. · wiTH our digismarT® conTrol Board & ems PTac sPecificaTions and accessories caTalog Assembled in the USA for 30 years:

16 www.amana-ptac.com MC-DPTAC

Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our continuing commit- ment to quality products may mean a change in specifications without notice. © 2012 • Goodman Company, L.P. • Houston, Texas • Printed in the USA.

Packaged Terminal air condiTioners and HeaT PumPs

wiTH conTrol Board

7-Button Control Pad• One-TouchActivation• TotalFanControl• Easy-to-ReadDisplay

AssembledintheUSAfor30years:Unitsare100%run-testedandtriple-testedforleakage.

First-YearWarranty:Parts&LaboronentireunitSecondthroughFifthYear:Parts&LaboroncertainsealedsystemcomponentsSecondthroughFifthYear:oncertainfunctionalpartsonly* Completewarrantydetailsavailablefromyourlocaldealeror

atwww.amana-ptac.com.


Recommended