SERIES 1000 DATA SHEETS
PROCESS AUTOMATION
PURGE/PRESSURIZATION SYSTEM
2 Singapore: +65 [email protected]
USA: 330 486 [email protected]
Germany: +49 621 776 [email protected]
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
Type Y and Z Systems (1000 Series) 1001A:ClassIEnclosureVolumes≤2ft3andClassIIEnclosureVolumes≤10ft3,WPSOnly..............3 1001B:ClassIIEnclosureVolumes≤50ft3............................................................................................5 1001C:ClassIIEnclosureVolumes≤250ft3...........................................................................................7 1002:ClassIEnclosureVolumes≤15ft3................................................................................................9 1003:ClassIEnclosureVolumes≤75ft3...............................................................................................11 1004:ClassIEnclosureVolumes≤200ft3.............................................................................................13 1005:ClassIEnclosureVolumes≤450ft3.............................................................................................15 11:ClassIEnclosureVolumes≤2ft3andClassIIEnclosureVolumes≤10ft3,WPSandWPSA........17
Type Z Systems (1000 Series) 1011:ClassIEnclosureVolumes≤2ft3andClassIIEnclosureVolumes≤10ft3..................................19 1012:ClassIEnclosureVolumes≤15ft3..............................................................................................21
Accessories.......................................................................................................................................................23
Type Y
& Z
1000SERIES
3
Type Y & Z
Description
Model1001Aisanenclosurepressurizationorpurgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertopreventcombustibledustaccumulationorremoveandpreventflammablegasorvaporaccumulations.InClassIIareas,thesystemmaintainsa"safe"(1.0")pressure.InClassIareas,thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.Theseprocessesreducethehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.InClassIIareas,alldustmustberemovedfromtheenclosure(s).Theenclosureprotectionvent(ifused)mustbetestedandenclosure(s)mustbesealed.Theenclosurepressurecontrolregulatoristhenusedtosetasafereadingontheenclosurepressuregauge.InClassIIareas,powercanbeenergizedwhensafepressureisstable.InClassIareas,theusermustperformanexchangecycle(determinedbythesafepressureflowrate—fiveminutesminimum)beforepowercanbeenergized.LossofsafepressureinClassIorIIareasrequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage4ShippingWeight: LPS-5lb/WPS-10lbTemp.Range: -20°Fto+120°FSupplyPressureRange: *5-120psiSupplyRequirements: CleanairorinertgasSafePress.(CI/CII): 0.25"/1.0"SafePress.FlowRate: **0.1-3.5SCFHSystemSupplyFitting: 1/4"tubefittingEnclosureSupplyFitting: 1/4"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(CI/CII,Decr): 0.15"/0.5"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRatingWPSStyle: 120VAC@15AWPSAStyle: ***120VAC@10A,125VDC@50mA
Switch(WPSA)PowerRequirement: 24VDC@3watts 120VAC@4watts 240VAC@11watts
* WithEPV-1Vent-120psimax.to5psimin. SystemsinstalledwithoutVentmustbeequipped withredundantregulatorsetto5psimax.
** Enclosureintegritydeterminesactualflowrate
***Supplyvoltages24VDCand240VACavailableuponrequest.
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model Number: 1001A-CI Type ZDesignation: PurgingSystemEnclosureVolume: 2ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
WPSA StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Model Number: 1001A-CII Type ZDesignation: PressurizationSystemEnclosureVolume: 10ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
Model Number: 1001A-CI Type YDesignation: PurgingSystemEnclosureVolume: 2ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.I,Div.1, GroupC&DRatingReduction: Div.1toDiv.2
WPSA StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
Model Number: 1001A-CII Type YDesignation:PressurizationSystemEnclosureVolume: 10ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
Standard Model Applications
Model 1001A
Class I (≤ 2 ft3) and Class II ( ≤ 10 ft3)
Type Y
& Z
1000SERIES
4
Type Y & Z
Material Specifications
RegulatorBody: Zincw/EnamelFinishRegulatorHandle: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishTubeFittings: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSSLexan®isaregisteredtrademarkoftheGeneralElectricCompany
Model Number Designations
1001A - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS - lesspressureswitch WPS - withpressureswitch WPSA - withpressureswitchArea Classification CI -ClassIArea CII -ClassIIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
MountingPlate
EnclosurePressureControl
Regulator
Enclosure Supply Outlet
System Supply Inlet
VenturiOrifice
EnclosurePressureGauge
EnclosureReference
Inlet
LH -lefthand
7/12
8/8
5.5/7.25
LPS / WPS
Height
Width
Depth
RH -righthand
7/12
8/8
5.5/7.25
BM -bottommount
7/8
8/13.375
5.5/7.25
WM-wallmount
7/12
8/8
7.5/9.25
FM & PM -surface
9/14
10/10
5/6.5
TM -topmount
7/8
8/13.375
5.5/7.25
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-8hx9wWPS-13hx9wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
``
Model 1001A System Accessories (See accessories page for complete details)
FACTORY INSTALLED FITTINGS
ECK-1001A EnclosureConnectionKitCONNECTION FITTINGS
EFC-4 1/4"FlushConnectorEBC-4 1/4"BulkheadConnectorEPC-10 1/2"PipeConnector
ADDITIONAL ITEMS
ILF-4 1/4"FilterSMK-1,-4or-6 SystemMountingKitEPSK-1or-2 ExplosionProofSwitchKit
GPSK-1or-2 General-purposeSwitchKitRAH Div.1RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitOPTIONAL ENCLOSURE PROTECTION VENTS
EPV-1-SA-00 Straightw/SparkArrestorEPV-1-SA-90 RtAnglew/SparkArrestor
OPTIONAL HEX KEY REGULATOR HANDLE
TR-10G TamperProofRegulatorWARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningEWN-2 ClassIIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0197 Inst.&OperationManual
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
MountingKitSMK-1
EnclosureProtectionVentEPV-1-SA...
(EPV vent not required when using the TR-10G tamper proof regulator
as redundancy)
PressurizedProtectedEnclosure
System Accessories Diagram
Note: ECK-1001A, Enclosure Connection Kit includes (2) EFC-4, and tubing mounted to panel
1/4"TubingReference
EnclosureSupplyFittingEBC-4
EnclosureReferenceFittingEFC-4
1/4"SupplyTubing
WarningNameplateEWN-__(IncludedwithPanel)
Type Y
& Z
1000SERIES
5
Type Y & Z
Description
Model1001Bisanenclosurepressurizationsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertopreventcombustibledustaccumulationbymaintaininga"safe"(1.0")pressure.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Beforestart-up,alldustmustberemovedfromtheenclosure(s).Theenclosureprotectionvent(ifused)mustbetestedandenclosure(s)mustbesealed.Theenclosurepressurecontrolregulatoristhenusedtosetasafereadingontheenclosurepressuregauge.Powercanbeenergizedwhensafepressureisstable.Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage6ShippingWeight: LPS-7lb/WPS-12lbTemp.Range: -20°Fto+120°FSupplyPressureRange: *5-120psiSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 1.0"SafePress.FlowRate: **0.1-3.5SCFHSystemSupplyFitting: 3/8"tubefittingEnclosureSupplyFitting: 3/8"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.5"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRating: 120VAC@15A
* WithEPV-3Vent-120psimax.to5psimin. SystemsinstalledwithoutVentmustbeequipped withredundantregulatorsetto5psimax.
** Enclosureintegritydeterminesactualflowrate
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model 1001B
Model Number: 1001B-CII Type ZDesignation:PressurizationSystemEnclosureVolume: 50ft3max.
LPS StyleUL&FMCertified: Cl. II, Div. 2, GroupF&GRatingReduction: Div. 2 to Nonhazardous
WPS StyleUL&FMCertified: Cl. II, Div. 2, GroupF&GRatingReduction: Div. 2 to Nonhazardous
Model Number: 1001B-CII Type YDesignation: PressurizationSystemEnclosureVolume: 50ft3max.
LPS StyleUL&FMCertified:Cl.II,Div.1,GroupF&GRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl. II, Div. 1, GroupF&GRatingReduction: Div.1toDiv.2
Standard Model Applications
Class II ( ≤ 50 ft3)
Type Y
& Z
1000SERIES
6
Type Y & Z
Material Specifications
RegulatorBody: Zincw/EnamelFinishRegulatorHandle: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishTubeFittings: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
MountingPlate
EnclosurePressureControl
RegulatorEnclosure
Supply Outlet
System Supply Inlet
VenturiOrifice
EnclosurePressureGauge
EnclosureReference
Inlet
LH -lefthand
7/12
8.875/8.875
6/7.25
LPS / WPS
Height
Width
Depth
RH -righthand
7/12
8.875/8.875
6/7.25
BM -bottommount
7/8
8.75/14.25
6/7.25
WM-wallmount
7/12
8.875/8.875
7.5/9.25
FM & PM -surface
9/14
10.875/10.875
4.75/6.5
TM -topmount
7/8
8.75/14.25
6/7.25Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-8hx9.875wWPS-13hx9.875w
Height&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
``
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
System Accessories DiagramModel Number Designations
1001B - LPS - CII - YZ - LH - ##
Series Model NumberSystem Style LPS -lesspressureswitch WPS -withpressureswitchArea Classification CII -ClassIIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 1001B System Accessories (See accessories page for complete details)
CONNECTION FITTINGS & FILTER
EFC-4 1/4"FlushConnectorEFC-6 3/8"FlushConnectorEBC-6 3/8"BulkheadConnectorEPC-13 1"PipeConnectorILF-6 3/8"Filterw/ClearBowl
ADDITIONAL ITEMS
ILF-6 3/8"FilterSMK-1,-4or-6 SystemMountingKit
EPSK-2 ExplosionProofSwitchKitGPSK-2 General-purposeSwitchKitRAH Div.1RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitOPTIONAL ENCLOSURE PROTECTION VENTS
EPV-3-SA-00 Straightw/SparkArrestorEPV-3-SA-90 RtAnglew/SparkArrestor
OPTIONAL HEX KEY REGULATOR HANDLE
TR-10G TamperProofRegulatorWARNING NAMEPLATES
EWN-2 ClassIIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0201 Inst.&OperationManual
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
MountingKitSMK-1
EnclosureProtectionVentEPV-3-SA...
(EPV vent not required when using the TR-10G tamper proof regulator
as redundancy)
PressurizedProtectedEnclosure
1/4"TubingReference
EnclosureSupplyFittingEBC-6
EnclosureReferenceFittingEFC-4
3/8"SupplyTubing
WarningNameplateEWN-2(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
7
Type Y & Z
Description
Model1001Cisanenclosurepressurizationsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertopreventcombustibledustaccumulationbymaintaininga"safe"(1.0")pressure.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Beforestart-up,alldustmustberemovedfromtheenclosure(s).Theenclosureprotectionvent(ifused)mustbetestedandenclosure(s)mustbesealed.Theenclosurepressurecontrolregulatoristhenusedtosetasafereadingontheenclosurepressuregauge.Powercanbeenergizedwhensafepressureisstable.Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage8ShippingWeight: LPS-7lb/WPS-12lbTemp.Range: -20°Fto+120°FSupplyPressureRange: *5-120psiSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 1.0"SafePress.FlowRate: **0.1-3.5SCFHSystemSupplyFitting: 1/2"tubefittingEnclosureSupplyFitting: 1/2"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.5"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRating: 120VAC@15A
* WithEPV-4Vent-120psimax.to5psimin. SystemsinstalledwithoutVentmustbeequipped withredundantregulatorsetto5psimax.
** Enclosureintegritydeterminesactualflowrate
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model 1001C
Model Number: 1001C-CII Type ZDesignation: PressurizationSystemEnclosureVolume: 250ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
Model Number: 1001C-CII Type YDesignation: PressurizationSystemEnclosureVolume: 250ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
Standard Model Applications
Class II ( ≤ 250 ft3)
Type Y
& Z
1000SERIES
8
Type Y & Z
Model 1001C System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
Material Specifications
RegulatorBody: Zincw/EnamelFinishRegulatorHandle: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishTubeFittings: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
MountingPlate
EnclosurePressureControl
Regulator
Enclosure Supply Outlet
System Supply Inlet
VenturiOrifice
EnclosurePressureGauge
EnclosureReference
Inlet
LH -lefthand
7/12
8.875/8.875
6/7.25
LPS / WPS
Height
Width
Depth
RH -righthand
7/12
8.875/8.875
6/7.25
BM -bottommount
7/8
8.75/14.25
6/7.25
WM-wallmount
7/12
8.875/8.875
7.5/9.25
FM & PM -surface
9/14
10.875/10.875
4.75/6.5
TM -topmount
7/8
8.75/14.25
6/7.25
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-8hx9.875wWPS-13hx9.875wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
``
CONNECTION FITTINGS & FILTER
EFC-4 1/4"FlushConnectorEFC-8 1/2"FlushConnectorEBC-8 1/2"BulkheadConnectorEPC-14 11/2"PipeConnectorILF-8 1/2"Filterw/ClearBowl
ADDITIONAL ITEMS
ILF-8 1/2"FilterSMK-1,-4or-6 SystemMountingKit
EPSK-2 ExplosionProofSwitchKitGPSK-2 General-purposeSwitchKitRAH Div.1RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitOPTIONAL ENCLOSURE PROTECTION VENTS
EPV-4-SA-00 Straightw/SparkArrestorEPV-4-SA-90 RtAnglew/SparkArrestor
OPTIONAL HEX KEY REGULATOR HANDLE
TR-30G TamperProofRegulatorWARNING NAMEPLATES
EWN-2 ClassIIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0202 Inst.&OperationManual
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model Number Designations
1001C - LPS - CII - YZ - LH - ##
Series Model NumberSystem Style LPS - lesspressureswitch WPS - withpressureswitchArea Classification CII -ClassIIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
MountingKitSMK-1
EnclosureProtectionVentEPV-4-SA...
(EPV vent not required when using the TR-30G tamper proof regulator
as redundancy)
PressurizedProtectedEnclosure
System Accessories Diagram
1/4"TubingReference
EnclosureSupplyFittingEBC-8
EnclosureReferenceFittingEFC-4
1/2"SupplyTubing
WarningNameplateEWN-2(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
9
Type Y & Z
Description Model1002isaRapidExchange®purgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertoremoveandpreventflammablegasorvaporaccumulations.Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.APepperl+FuchsModelEPV-2EnclosureProtectionVentisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Theenclosureprotectionventmustbetestedandtheenclosure(s)mustbesealed.Theenclosurepressurecontrolvalveisthenusedtosetasafereadingontheenclosurepressureindicator.Whensafepressureisstable,theRapidExchangecontrolvalvemustbefullyengaged.UponcompletionoftheRapidExchangecycle,(fiveminutesminimum)theRapidExchangecontrolvalvemustbedisengagedtoreturntoasafeenclosurepressure.Powercanthenbeenergizedtotheprotectedenclosure(s).Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage10ShippingWeight: LPS-10lb/WPS-15lbTemp.Range: -20°Fto+120°FSupplyPressureRange: 80-120psiCapacity&Filtration: 1.5oz@20MicronSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 0.25"SafePress.FlowRate: *0.1-3.5SCFHExchangePressure: 3"-5"ExchangeFlowRate: **4SCFM/240SCFHExchangeTime: 1min/ft3
SystemSupplyPort: 1/4"FPTEnclosureSupplyFitting: 1/4"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.15"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRatingWPSStyle: 120VAC@15AWPSAStyle:***120/220VAC,24VDC@10A;125VDC@50mA
Switch(WPSA)PowerRequirement: 24/120/240VDC@3/4/11watts
* Enclosureintegritydeterminesactualflowrate
** Withregulatorsetto60psimin.duringexchange.RapidExchange®isaRegisteredTrademarkofPepperl+Fuchs.
***Supplyvoltages24VDCand240VACavailableuponrequest.
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model 1002
Model Number: 1002 Type ZDesignation: PurgingSystemEnclosureVolume: 15ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
WPSA StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Model Number: 1002 Type YDesignation: PurgingSystemEnclosureVolume: 15ft3max.
LPS StyleUL&FMCertified: Cl. I, Div. 1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl. I, Div. 1, GroupC&DRatingReduction: Div.1toDiv.2
WPSA StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
Standard Model Applications
Class I ( ≤ 15 ft3)
Type Y
& Z
1000SERIES
10
Type Y & Z
Material Specifications
FilterRegulatorBody: Zincw/EnamelFinishRegulatorHandle&Bowl: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishRapidExchangeGauge: PolyCase&BrassTubeTubeFittings&Valves: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
Enclosure Supply Outlet
MountingPlate
System Supply Inlet
FilterRegulator
RapidExchange®
ControlValve
VenturiOrifice
EnclosurePressureGauge
EnclosurePressure
ControlValve
EnclosureReference
Inlet
LH -lefthand
10/15
11/11
6/7.5
LPS / WPS
Height
Width
Depth
RH -righthand
10/15
11/11
6/7.5
BM -bottommount
10/10
11/16
6/7.5
WM-wallmount
10/15
11/11
7.75/9.25
FM or PM -flatpanel
12/17
13/13
5/6.5
TM -topmount
10/10
11/16
6/7.5
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-11hx12wWPS-16hx12wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
CONNECTION FITTINGS
NC-4 1/4"NinetyConnectorSC-4 1/4"StraightConnectorEFC-4 1/4"FlushConnectorEBC-4 1/4"BulkheadConnectorEPC-12 3/4"PipeConnector
ADDITIONAL ITEMS
SMK-2or-8 SystemMountingKitEPSK-1 ExplosionProofSwitchKitGPSK-1 General-purposeSwitchKit
RAH RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKit
ENCLOSURE PROTECTION VENTS ONE VENT REQUIRED WITH EACH SYSTEM
EPV-2-SA-00 Straightw/SparkArrestorEPV-2-SA-90 RtAnglew/SparkArrestor
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0196 Inst.&OperationManual
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
SupplyInletFittingSC-4orNC-4
MountingKitSMK-2
EnclosureProtectionVentEPV-2-SA...
1/4"TubingReference
EnclosureSupplyFittingEBC-4
EnclosureReferenceFittingEFC-4
1/4"SupplyTubing
PressurizedProtectedEnclosure
Model Number Designations
1002 - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS - lesspressureswitch WPS - withpressureswitch WPSA - withpressureswitchArea Classification CI -ClassIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 1002 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
System Accessories Diagram
WarningNameplateEWN-1(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
11
Type Y & Z
Description Model1003isaRapidExchange®purgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertoremoveandpreventflammablegasorvaporaccumulations.Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.APepperl+FuchsModelEPV-3EnclosureProtectionVentisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Theenclosureprotectionventmustbetestedandtheenclosure(s)mustbesealed.Theenclosurepressurecontrolvalveisthenusedtosetasafereadingontheenclosurepressureindicator.Whensafepressureisstable,theRapidExchangecontrolvalvemustbefullyengaged.UponcompletionoftheRapidExchangecycle,(fiveminutesminimum)theRapidExchangecontrolvalvemustbedisengagedtoreturntoasafeenclosurepressure.Powercanthenbeenergizedtotheprotectedenclosure(s).Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage12ShippingWeight: LPS-12lb/WPS-17lbTemp.Range: -20°Fto+120°FSupplyPressureRange: 80-120psiCapacity&Filtration: 3.8oz@40MicronSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 0.25"SafePress.FlowRate: *0.1-3.5SCFHExchangePressure: 3"-5"ExchangeFlowRate: **10SCFM/600SCFHExchangeTime: 1min/2.5ft3
SystemSupplyPort: 3/8"FPTEnclosureSupplyFitting: 3/8"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.15"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRatingWPSStyle: 120VAC@15AWPSAStyle:***120/220VAC,24VDC@10A;125VDC@50mA
Switch(WPSA)PowerRequirement: 24/120/240VDC@3/4/11watts
* Enclosureintegritydeterminesactualflowrate
** Withregulatorsetto60psimin.duringexchange.RapidExchange®
isaRegisteredTrademarkofPepperl+Fuchs.
***Supplyvoltages24VDCand240VACavailableuponrequest.
LPS Style (Less Pressure Switch)
Model 1003
Model Number: 1003 Type ZDesignation: PurgingSystemEnclosureVolume: 75ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
WPSA StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Model Number: 1003 Type YDesignation: PurgingSystemEnclosureVolume: 75ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.I,Div.1, GroupC&DRatingReduction: Div.1toDiv.2
WPSA StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
Standard Model Applications
Class I ( ≤ 75 ft3)
WPS/WPSA Style (With Pressure Switch)
Type Y
& Z
1000SERIES
12
Type Y & Z
FilterRegulator
Model Number Designations
1003 - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS - lesspressureswitch WPS - withpressureswitch WPSA - withpressureswitchArea Classification CI -ClassIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 1003 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
Material Specifications
FilterRegulatorBody: Zincw/EnamelFinishRegulatorHandle&Bowl: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishRapidExchangeGauge: PolyCase&BrassTubeTubeFittings&Valves: 316SSForgedBodyTubing: 316SS1/4"&3/8".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
Enclosure Supply Outlet
MountingPlate
System Supply Inlet
RapidExchange®
ControlValve
VenturiOrifice
EnclosurePressureGauge
EnclosurePressure
ControlValve
EnclosureReference
Inlet
LH -lefthand
12/15
11.5/11.5
6/7.5
LPS / WPS
Height
Width
Depth
RH -righthand
12/15
11.5/11.5
6/7.5
BM -bottommount
12/12
11.5/15.25
6/7.5
WM-wallmount
12/15
11.5/11.5
7.75/9.25
FM or PM -flatpanel
14/17
13.5/13.5
5.75/7.25
TM -topmount
12/12
11.5/15.25
6/7.5
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-13hx12.5wWPS-16hx12.5wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
CONNECTION FITTINGS
NC-6 3/8"NinetyConnectorSC-6 3/8"StraightConnectorEFC-4 1/4"FlushConnectorEFC-6 3/8"FlushConnectorEBC-6 3/8"BulkheadConnectorEPC-13 1"PipeConnector
ADDITIONAL ITEMS
SMK-2or-8 SystemMountingKitEPSK-1 ExplosionProofSwitchKit
GPSK-1 General-purposeSwitchKitRAH RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitENCLOSURE PROTECTION VENTSONE VENT REQUIRED WITH EACH SYSTEM
EPV-3-SA-00 Straightw/SparkArrestorEPV-3-SA-90 RtAnglew/SparkArrestor
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0195 Inst.&OperationManual
SupplyInletFittingSC-6orNC-6
3/8"SupplyTubing
MountingKitSMK-2
EnclosureProtectionVentEPV-3-SA...
System Accessories Diagram
1/4"TubingReference
EnclosureSupplyFittingEBC-6
EnclosureReferenceFittingEFC-4
PressurizedProtectedEnclosure
WarningNameplateEWN-1(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
13
Type Y & Z
Description
Model1004isaRapidExchange®purgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertoremoveandpreventflammablegasorvaporaccumulations.Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.APepperl+FuchsModelEPV-4EnclosureProtectionVentisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Theenclosureprotectionventmustbetestedandtheenclosure(s)mustbesealed.Theenclosurepressurecontrolvalveisthenusedtosetasafereadingontheenclosurepressureindicator.Whensafepressureisstable,theRapidExchangecontrolvalvemustbefullyengaged.UponcompletionoftheRapidExchangecycle,(fiveminutesminimum)theRapidExchangecontrolvalvemustbedisengagedtoreturntoasafeenclosurepressure.Powercanthenbeenergizedtotheprotectedenclosure(s).Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage14ShippingWeight: LPS-15lb/WPS-23lbTemp.Range: -20°Fto+120°FSupplyPressureRange: 80-120psiCapacity&Filtration: 8.5oz@40MicronSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 0.25"SafePress.FlowRate: *0.1-3.5SCFHExchangePressure: 3"-5"ExchangeFlowRate: **30SCFM/1800SCFHExchangeTime: 1min/7.5ft3
SystemSupplyPort: 1/2"FPTEnclosureSupplyFitting: 1/2"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.15"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRatingWPSStyle: 120VAC@15AWPSAStyle:***120/220VAC,24VDC@10A;125VDC@50mA
Switch(WPSA)PowerRequirement: 24/120/240VDC@3/4/11watts
* Enclosureintegritydeterminesactualflowrate
** Withregulatorsetto80psimin.duringexchange.RapidExchange® isaRegisteredTrademarkofPepperl+Fuchs.
***Supplyvoltages24VDCand240VACavailableuponrequest.
LPS Style (Less Pressure Switch)
Model 1004
Model Number: 1004 Type ZDesignation: PurgingSystemEnclosureVolume: 200ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
WPSA StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Model Number: 1004 Type YDesignation: PurgingSystemEnclosureVolume: 200ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.I,Div.1, GroupC&DRatingReduction: Div.1toDiv.2
WPSA StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
Standard Model Applications
Class I ( ≤ 200 ft3)
WPS/WPSA Style (With Pressure Switch)
Type Y
& Z
1000SERIES
14
Type Y & Z
Material Specifications
FilterRegulatorBody: Zincw/EnamelFinishRegulatorHandle&Bowl: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishRapidExchangeGauge: PolyCase&BrassTubeTubeFittings&Valves: 316SSForgedBodyTubing: 316SS1/4"&1/2".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
VenturiOrifice
EnclosurePressureGauge
EnclosurePressure
ControlValve
EnclosureReference
Inlet
CONNECTION FITTINGS
NC-8 1/2"NinetyConnectorSC-8 1/2"StraightConnectorEFC-4 1/4"FlushConnectorEFC-8 1/2"FlushConnectorEBC-8 1/2"BulkheadConnectorEPC-14 11/2"PipeConnector
ADDITIONAL ITEMS
SMK-2or8 SystemMountingKitEPSK-1 ExplosionProofSwitchKit
GPSK-1 General-purposeSwitchKitRAH RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitENCLOSURE PROTECTION VENTSONE VENT REQUIRED WITH EACH SYSTEM
EPV-4-SA-00 Straightw/SparkArrestorEPV-4-SA-90 RtAnglew/SparkArrestor
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0203 Inst.&OperationManual
LH-lefthand
12/16.25
13.5/13.5
6.75/8.25
LPS/WPS
Height
Width
Depth
RH-righthand
12/16.25
13.5/13.5
6.75/8.25
BM-bottommount
12/12
13.5/16.75
6.75/8.25
WM-wallmount
12/15
13.5/13.5
7.75/9.25
FMorPM-flatpanel
14/18.25
15.5/15.5
6.75/8.25
TM-topmount
12/12
13.5/16.75
6.75/8.25
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-13hx14.5wWPS-17.25hx14.5wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
FilterRegulator
Enclosure Supply Outlet
MountingPlate
System Supply Inlet
RapidExchange®
ControlValve
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model Number Designations
1004 - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS - lesspressureswitch WPS - withpressureswitch WPSA - withpressureswitchArea Classification CI -ClassIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 1004 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
SupplyInletFittingSC-8orNC-8
1/2"SupplyTubing
MountingKitSMK-2
EnclosureProtectionVentEPV-4-SA...
System Accessories Diagram
1/4"TubingReference
EnclosureSupplyFittingEBC-8
EnclosureReferenceFittingEFC-4
PressurizedProtectedEnclosure
WarningNameplateEWN-1(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
15
Type Y & Z
Description Model1005isaRapidExchange®purgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertoremoveandpreventflammablegasorvaporaccumulations.Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.APepperl+FuchsModelEPV-5EnclosureProtectionVentisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Theenclosureprotectionventmustbetestedandtheenclosure(s)mustbesealed.Theenclosurepressurecontrolvalveisthenusedtosetasafereadingontheenclosurepressureindicator.Whensafepressureisstable,theRapidExchangecontrolvalvemustbefullyengaged.UponcompletionoftheRapidExchangecycle,(fiveminutesminimum)theRapidExchangecontrolvalvemustbedisengagedtoreturntoasafeenclosurepressure.Powercanthenbeenergizedtotheprotectedenclosure(s).Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage16ShippingWeight: LPS-15lb/WPS-25lbTemp.Range: -20°Fto+120°FSupplyPressureRange: 80-120psiCapacity&Filtration: 8.5oz@40MicronSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 0.25"SafePress.FlowRate: *0.1-3.5SCFHExchangePressure: 3"-5"ExchangeFlowRate: **60SCFM/3600SCFHExchangeTime: 1min/15ft3
SystemSupplyPort: 1/2"FPTEnclosureSupplyFitting: 1/2"FPTEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(Decr): 0.15"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRatingWPSStyle: 120VAC@15AWPSAStyle:***120/220VAC,24VDC@10A;125VDC@50mA
Switch(WPSA)PowerRequirement: 24/120/240VDC@3/4/11watts
* Enclosureintegritydeterminesactualflowrate
** Withregulatorsetto80psimin.duringexchangeRapidExchange® isaRegisteredTrademarkofPepperl+Fuchs,Inc.
***Supplyvoltages24VDCand240VACavailableuponrequest.
LPS Style (Less Pressure Switch)
Model 1005
Model Number: 1005 Type ZDesignation: PurgingSystemEnclosureVolume: 450ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
WPSA StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Model Number: 1005 Type YDesignation: PurgingSystemEnclosureVolume: 450ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.I,Div.1, GroupC&DRatingReduction: Div.1toDiv.2
WPSA StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
Standard Model Applications
Class I ( ≤ 450 ft3)
WPS/WPSA Style (With Pressure Switch)
Type Y
& Z
1000SERIES
16
Type Y & Z
Model Number Designations
1005 - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS -lesspressureswitch WPS -withpressureswitch WPSA -withpressureswitchArea Classification CI -ClassIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 1005 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
SupplyInletFitting
1/2"SupplyPipe
MountingKitSMK-2
EnclosureProtectionVentEPV-5-SA...
System Accessories Diagram
1/4"TubingReference
EnclosureSupplyFittingEPC-10
EnclosureReferenceFittingEFC-4
PressurizedProtectedEnclosure
CONNECTION FITTINGS
EFC-4 1/4"FlushConnectorEPC-10 1/2"PipeConnectorEPC-15 2"PipeConnector
ADDITIONAL ITEMS
SMK-2or-8 SystemMountingKitEPSK-1 ExplosionProofSwitchKitGPSK-1 General-purposeSwitchKitRAH RemoteAlarmHorn
RAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKit
ENCLOSURE PROTECTION VENTSONE VENT REQUIRED WITH EACH SYSTEM
EPV-5-SA-00 Straightw/SparkArrestorEPV-5-SA-90 RtAnglew/SparkArrestor
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0204 Inst.&OperationManual
Material Specifications
FilterRegulatorBody: Zincw/EnamelFinishRegulatorHandle&Bowl: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishRapidExchangeGauge: PolyCase&BrassTubeTubeFittings&Valves: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
Enclosure Supply Outlet
MountingPlate
System Supply Inlet
FilterRegulator
RapidExchange®
ControlValve
VenturiOrifice
Enclosure Pressure Gauge
EnclosurePressure
ControlValve
EnclosureReference
Inlet
LH -lefthand
13.5/17.75
13.5/13.5
6/7.5
LPS / WPS
Height
Width
Depth
RH -righthand
13.5/17.75
13.5/13.5
6/7.5
BM -bottommount
14/13
13.5/16.125
6/7.5
WM-wallmount
15/17.75
13.5/13.5
7.75/9.25
FM or PM -flatpanel
15.5/19.75
15.5/15.5
5/6.5
TM -topmount
14/13
13.5/16.125
6/7.5
OverallSystem
Dimensions
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-14.5hx14.5wWPS-18.75hx14.5wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
WPS/WPSA Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
WarningNameplateEWN-1(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
17
Type Y & Z
Description
Model11isanenclosurepressurizationorpurgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertopreventcombustibledustaccumulationorremoveandpreventflammablegasorvaporaccumulations.InClassIIareas,thesystemmaintainsa"safe"(1.0")pressure.InClassIareas,thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.Theseprocessesreducethehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.InClassIIareas,alldustmustberemovedfromtheenclosure(s).Theenclosureprotectionvent(ifused)mustbetestedandenclosure(s)mustbesealed.Theenclosurepressurecontrolregulatoristhenusedtosetasafereadingontheenclosurepressuregauge.InClassIIareas,powercanbeenergizedwhensafepressureisstable.InClassIareas,theusermustperformanexchangecycle(determinedbythesafepressureflowrate—fiveminutesminimum)beforepowercanbeenergized.LossofsafepressureinClassIorIIareasrequiresimmediateattention,unlesspowerisdeenergized.WPSstylesystemsincludeanexplosionproofdifferentialpressureswitchwithform"C"contactsforaudibleorvisualalarmsystems.
Specifications
SystemDimensions: Seepage18ShippingWeight: LPS-5lb/WPS-10lbTemp.Range: 40°Fto+120°FSupplyPressureRange: *5-120psiSupplyRequirements: cleanairorinertgasSafePress.(CI/CII): 0.25"/1.0"SafePress.FlowRate: **0.1-3.5SCFHSystemSupplyFitting: 1/4"tubefittingEnclosureSupplyFitting: 1/4"tubefittingEnclosureReferenceFitting: 1/4"tubefittingSwitchSetting(CI/CII,Decr): 0.15"/0.5"±0.02"SwitchConduitPortSize: 1/2"FPTSwitchContactRating: 120VAC@15A
* WithEPV-1Vent-120psimax.to5psimin. SystemsinstalledwithoutVentmustbeequipped
withredundantregulatorsetto5psimax.
** Enclosureintegritydeterminesactualflowrate
WPS Style (With Pressure Switch)
LPS Style (Less Pressure Switch)
Model 11
Model Number: 11-CI Type ZDesignation: PurgingSystemEnclosureVolume: 2ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.I,Div.2, GroupC&DRatingReduction: Div.2to Nonhazardous
Model Number: 11-CII Type ZDesignation: PressurizationSystemEnclosureVolume: 10ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
WPS StyleUL&FMCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
Model Number: 11-CI Type YDesignation: PurgingSystemEnclosureVolume: 2ft3max.
LPS StyleUL&FMCertified: Cl.I,Div.1, GroupA-DRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.I,Div.1, GroupC&DRatingReduction: Div.1toDiv.2
Model Number: 11-CII Type YDesignation: PressurizationSystemEnclosureVolume: 10ft3max.
LPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
WPS StyleUL&FMCertified: Cl.II,Div.1, GroupF&GRatingReduction: Div.1toDiv.2
Standard Model Applications
Class I (≤ 2 ft3) and Class II ( ≤ 10 ft3)
Type Y
& Z
1000SERIES
18
Type Y & Z
Model Number Designations
11 - LPS - CI - YZ - LH - ##
Series Model NumberSystem Style LPS -lesspressureswitch WPS -withpressureswitchArea Classification CI -ClassIArea CII -ClassIIAreaSystem Type YZ -Div.1toDiv.2,Div.2toNonhazardousMounting Configuration LH -lefthand leftsideofenclosure RH -righthand rightsideofenclosure TM -topmount topofenclosure BM -bottommount bottomofenclosure WM -wallmount wallsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout (Not available in WPS Style)
## - See Accessories Page 130 for additional factory installed accessories
Model 11 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
Material Specifications
RegulatorBody: Zincw/EnamelFinishRegulatorHandle: PolycarbonateEnclosurePressureGauge: ABSPlasticTubeFittings: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: SilkscreenedLexan®&SSFastenerHardware: Alum.&StainlessSteelMountingPlate: 31614Ga#3BrushSSEXPPressureSwitchBody: AnodizedCastAlum.EnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
LH -lefthand
6.25/10.75
6/7.5
5.5/7.25
LPS / WPS
Height
Width
Depth
RH -righthand
6.25/10.75
6/7.5
5.5/7.25
BM -bottommount
6.25/8.5
7.5/13.375
5.5/7.25
WM-wallmount
6.25/10.75
6/7.5
5.5/7.25
FM & PM -surface
8.25/12.75
8/9.5
4.5/7
TM -topmount
6.25/8.5
7.5/13.375
5.5/7.25
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:LPS-7.25hx7wWPS-11.75hx8.5wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
MountingPlate
VenturiOrifice
EnclosurePressureControl
Regulator
Enclosure Supply Outlet
System Supply Inlet
EnclosurePressureGauge
EnclosureReference
Inlet
WPS Style (With Pressure Switch)
FACTORY INSTALLED FITTINGS & FILTER
ECK-11 EnclosureConnectionKitCONNECTION FITTINGS
EFC-4 1/4"FlushConnectorEBC-4 1/4"BulkheadConnectorEPC-10 1/2"PipeConnector
ADDITIONAL ITEMS
ILF-4 1/4"FilterSMK-1,-4or-6 SystemMountingKit
EPSK-1or-2 ExplosionProofSwitchKitGPSK-1or-2 General-purposeSwitchKitRAH Div.1RemoteAlarmHornRAB-1 Div.1RemoteAlarmBeaconRAB-2 Div.2RemoteAlarmBeaconLCK LFittingConduitKitTCK TFittingConduitKitOPTIONAL ENCLOSURE PROTECTION VENTS
EPV-1-SA-00 Straightw/SparkArrestorEPV-1-SA-90 RtAnglew/SparkArrestor
OPTIONAL HEX KEY REGULATOR HANDLE
TR-10G TamperProofRegulatorWARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningEWN-2 ClassIIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0207 Inst.&OperationManual
LPS Style (Less Pressure Switch)
PressurizedProtectedEnclosure
System Accessories Diagram
MountingKitSMK-1
EnclosureProtectionVentEPV-1-SA...
(EPV vent not required when using the TR-10G tamper proof regulator
as redundancy)
Note: ECK-11, Enclosure Connection Kit includes (2) EFC-4, and tubing mounted to panel
1/4"TubingReference
EnclosureSupplyFittingEBC-4
EnclosureReferenceFittingEFC-4
1/4"SupplyTubing
WarningNameplateEWN-1(IncludedwithPanel)
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Z
1000SERIES
19
Type Z
Description
Model1011isanenclosurepressurizationorpurgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosures,inordertopreventcombustibledustaccumulationorremoveandpreventflammablegasorvaporaccumulations.InClassIIareas,thesystemmaintainsa"safe"(1.0")pressure.InClassIareas,thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.Theseprocessesreducethehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.InClassIIareas,alldustmustberemovedfromtheenclosure(s).Theenclosureprotectionvent(ifused)mustbetestedandenclosure(s)mustbesealed.Theenclosurepressurecontrolregulatoristhenusedtosetasafereadingontheenclosurepressuregauge.InClassIIareas,powercanbeenergizedwhensafepressureisstable.InClassIareas,theusermustperformanexchangecycle(determinedbythesafepressureflowrate—fiveminutesminimum),beforepowercanbeenergized.LossofsafepressureinClassIorIIareasrequiresimmediateattention,unlesspowerisdeenergized.Systeminstallationmaybeenhancedwithastand-alonePepperl+FuchsModelEPSKexplosionproofswitchkittoprovideform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage20ShippingWeight: 7lbTemp.Range: -20°Fto+120°FSupplyPressureRange: *5-120psiSupplyRequirements: cleanairorinertgasSafePress.(CI/CII): 0.25"/1.0"SafePress.FlowRate: **0.1-3.5SCFHSystemSupplyFitting: 1/4"tubefittingEnclosureSupplyFitting: 1/4"tubefittingEnclosureReferenceFitting: 1/4"tubefitting
* WithEPV-1Vent-120psimax.to5psimin. SystemsinstalledwithoutVentmustbeequipped withredundantregulatorsetto5psimax.
** Enclosureintegritydeterminesactualflowrate
Front View
Model 1011
Model Number: 1011-CII Type ZDesignation: PressurizationSystemEnclosureVolume: 10ft3max.ULCertified: Cl.II,Div.2, GroupF&GRatingReduction: Div.2to Nonhazardous
Model Number: 1011-CI Type ZDesignation: PurgingSystemEnclosureVolume: 2ft3max.ULCertified: Cl.I,Div.2, GroupA-DRatingReduction: Div.2to Nonhazardous
Standard Model Applications
Class I ( ≤ 2 ft3) and Class II ( ≤ 10 ft3)
Type Z
1000SERIES
20
Type Z
Material Specifications
RegulatorBody: Brass,Zincw/EnamelFinishRegulatorHandle: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishTubeFittings: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: Silkscreen&Lexan®FastenerHardware: Alum.&StainlessSteelMountingPlate&Bracket: AnodizedAluminumEnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
SystemSupply
Inlet
EnclosurePressureControl
Regulator
EnclosureSupplyOutlet
UniversalMountingBracket
EnclosurePressureGauge
EnclosureReference
Inlet
VenturiOrifice
MountingPlate
Rear View
UM -lefthand
8
8.25
5
Configuration
Height
Width
Depth
UM -righthand
8
8.25
5
UM -bottommount
8.25
8
5
FM-framemount
8
8
5
PM -panelmount
8
8
5
UM -topmount
8.25
8
5
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:7.625hx7.625wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
CONNECTION FITTINGS
EFC-4 1/4"FlushConnectorEBC-4 1/4"BulkheadConnectorEPC-10 1/2"PipeConnector
ADDITIONAL ITEMS
ILF-4 1/4"FilterSMK-1or-4 SystemMountingKitEPSK-1or-2 ExplosionProofSwitchKit
GPSK-1or-2 General-purposeSwitchKitRAH Div.1RemoteAlarmHornRAB-2 Div.2RemoteAlarmBeaconOPTIONAL ENCLOSURE PROTECTION VENTS
EPV-1-SA-00 Straightw/SparkArrestorEPV-1-SA-90 RtAnglew/SparkArrestor
OPTIONAL HEX KEY REGULATOR HANDLE
TR-10G TamperProofRegulator
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningEWN-2 ClassIIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0205 Inst.&OperationManual
Model 1011 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
MountingKitSMK-1
EnclosureProtectionVentEPV-1-SA...
(EPV vent not required when using the TR-10G tamper proof regulator
as redundancy)
PressurizedProtectedEnclosure
System Accessories Diagram
Note: ECK-1011, Enclosure Connection Kit includes (2) EFC-4, and tubing mounted to panel
1/4"TubingReference
EnclosureSupplyFittingEBC-4
EnclosureReferenceFittingEFC-4
1/4"SupplyTubing
WarningNameplateEWN-__(IncludedwithPanel)
Model Number Designations
1011 - CI - Z - UH - ##
Series Model NumberArea Classification CI -ClassIArea CII -ClassIIAreaSystem Type Z -Div.2toNonhazardousMounting Configuration UM -universalmount externalsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout## - See Accessories Page 130 for additional factory installed accessories
FM&PMconfigurationmountingplatesincludefour(4)1/4"mountingholesateachcorner,on5/16"centers.
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Z
1000SERIES
21
Type Z
Description
Model1012isaRapidExchange®purgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosure(s),inordertoremoveandpreventflammablegasorvaporaccumulations.Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressure.APepperl+FuchsModelEPV-2EnclosureProtectionVentisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Operation
Inaccordancewithsysteminstructions,start-uprequiresairsupplytobeengagedandenclosurepowertobedeenergized.Theenclosureprotectionventmustbetestedandtheenclosure(s)mustbesealed.Theenclosurepressurecontrolvalveisthenusedtosetasafereadingontheenclosurepressureindicator.Whensafepressureisstable,theRapidExchangecontrolvalvemustbefullyengaged.UponcompletionoftheRapidExchangecycle,(fiveminutesminimum)theRapidExchangecontrolvalvemustbedisengagedtoreturntoasafeenclosurepressure.Powercanthenbeenergizedtotheprotectedenclosure(s).Lossofsafepressurerequiresimmediateattention,unlesspowerisdeenergized.Systeminstallationmaybeenhancedwithastand-alonePepperl+FuchsModelEPSKexplosionproofswitchkittoprovideform"C"contactsforaudibleorvisualalarmsystems.
System Specifications
SystemDimensions: Seepage22ShippingWeight: 10lbTemp.Range: -20°Fto+120°FSupplyPressureRange: 80-120psiCapacity&Filtration: 1.5oz@20MicronSupplyRequirements: cleanairorinertgasSafePress.Setpoint: 0.25"SafePress.FlowRate: *0.1-3.5SCFHExchangePressure: 3"-5"ExchangeFlowRate: **4SCFM/240SCFHExchangeTime: 1min/ft3
SystemSupplyPort: 1/4"FPTEnclosureSupplyFitting: 1/4"tubefittingEnclosureReferenceFitting: 1/4"tubefitting
* Enclosureintegritydeterminesactualflowrate
** Withregulatorsetto60psimin.duringexchange.RapidExchange® isaRegisteredTrademarkofPepperl+Fuchs.
Front View
Model 1012
Standard Model Applications
Class I ( ≤ 15 ft3)
Model Number: 1012-CI Type ZDesignation: PurgingSystemEnclosureVolume: 15ft3max.ULCertified: Cl.I,Div.2,GroupA-DRatingReduction: Div.2toNonhazardous
Type Z
1000SERIES
22
Type Z
Material Specifications
FilterRegulatorBody: Zincw/EnamelFinishRegulatorHandle&Bowl: PolycarbonateEnclosurePressureGauge: Alum.w/EnamelFinishRapidExchangeGauge: PolyCase&BrassTubeTubeFittings&Valves: 316SSForgedBodyTubing: 316SS1/4".035WeldedSystemNameplates: Silkscreen&Lexan®
FastenerHardware: Alum.&StainlessSteelMountingPlate&Bracket: AnodizedAluminumEnclosureWarningNameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCompany
UM -lefthand
12
12.25
5
Configuration
Height
Width
Depth
UM -righthand
12
12.25
5
UM -bottommount
12.25
12
5
FM-framemount
12
12
5
PM -panelmount
12
12
5
UM -topmount
12.25
12
5
Dimensionsininches.Mountingdimensionsavailableuponrequest.FM&PMpanelcutoutdimensions:11.625hx11.625wHeight&widthdimensionsreflectmountingplatemeasurements.Depthdimensionreflectsoverallmeasurementofsystem,includingcomponents.
OverallSystem
Dimensions
RapidExchangeControlValve
Regulator
SystemSupply
Inlet
EnclosureSupplyOutlet
UniversalMountingBracket
EnclosurePressureGauge
EnclosureReference
Inlet
VenturiOrifice
MountingPlate
EnclosurePressureControlValve Rear View
CONNECTION FITTINGS
NC-4 1/4"NinetyConnectorSC-4 1/4"StraightConnectorEFC-4 1/4"FlushConnectorEBC-4 1/4"BulkheadConnectorEPC-12 3/4"PipeConnector
ADDITIONAL ITEMS
SMK-1or-4 SystemMountingKitEPSK-1 ExplosionProofSwitchKit
GPSK-1 General-purposeSwitchKitRAH RemoteAlarmHornRAB-2 Div.2RemoteAlarmBeacon
ENCLOSURE PROTECTION VENTSONE VENT REQUIRED WITH EACH SYSTEM
EPV-2-SA-00 Straightw/SparkArrestorEPV-2-SA-90 RtAnglew/SparkArrestor
WARNING NAMEPLATES
EWN-1 ClassIEnclosureWarningETW EnclosureTemperatureWarning
INSTALLATION & OPERATION MANUAL
129-0206 Inst.&OperationManual
SupplyInletFittingSC-4orNC-4
MountingKitSMK-2
EnclosureProtectionVentEPV-2-SA...
1/4"TubingReference
EnclosureSupplyFittingEBC-4
EnclosureReferenceFittingEFC-4
1/4"SupplyTubing
PressurizedProtectedEnclosure
Model 1012 System Accessories (See accessories page for complete details)
ONE (1) ENCLOSURE WARNING NAMEPLATE & ONE (1) INSTALLATION & OPERATION MANUAL ARE PROVIDED WITH EACH SYSTEM
System Accessories Diagram
WarningNameplateEWN-1(IncludedwithPanel)
Model Number Designations
1012 - CI - Z - UH - ##
Series Model NumberArea Classification CI -ClassIAreaSystem Type Z -Div.2toNonhazardousMounting Configuration UM -universalmount externalsurface FM -framemount externalframeorrack PM -panelmount enclosuresurfacecutout## - See Accessories Page 130 for additional factory installed accessories
FM&PMconfigurationmountingplatesincludefour(4)1/4"mountingholesateachcorner,on5/16"centers.
CONNECTION POINTS SHOWN ABOVE IN BOLD TEXT ON SYSTEM DIAGRAM
Type Y
& Z
1000SERIES
23
Type Y & Z
11/1000 Series — Model Number Designations and Accessories Guide
Series Model Number 11, 1001A, 1001B, 1001C, 1002, 1003, 1004, 1005, 1011, 1012System Style LPS - Lesspressureswitch WPS - Withpressureswitch WPSA - Withpressureswitch(120VACStandard)Area Classification CI -ClassIArea CII -ClassIIAreaSystem Type YZ -Div.1toDiv.2, Div.2toNonhazardousMounting Configuration LH -Lefthand(leftsideofenclosure) RH -Righthand(rightsideofenclosure) TM -Topmount(topofenclosure) BM -Bottommount(bottomofenclosure) WM -Wallmount(wallsurface) FM -Framemount(externalframeorrack) PM -Panelmount(enclosuresurfacecutout,not available in WPS or WPSA Style)Enclosure Connection Kit ECK -EnclosureconnectionkitCooler Indicator Gauge (seepage97) VX -VortexVoltage (forWPSAswitchonly) 24 VDC -VoltageDirectCurrents 240 VAC -VoltageAlternatingCurrents
11/1000 - - - - - - -
Pepperl+Fuchssuppliespurge/pressurizationsystemscustombuilttoyourspecifications.Toensuretheintegrityofyoursystem,certainaccessoryitemsmustbefactoryinstalled.
TheModelNumberandAccessoriesGuideidentifiesthosepartsthatmustbeincludedonyourpurge/pressurizationsystemorder.
Type Y & Z
Type Y
& Z
1000SERIES
24
Type Y & Z
Special Note
TOORDERPURGE/PRESSURIZATIONUNITSEqUIPPEDWITHACOOLER
INDICATIONGAUGE,SPECIFy‘VX’INTHEMODELNUMBERDESIGNATION.
Description
Thecoolerindicatorgauge,sometimescalledtheVortexindicatorgauge,isusedonsystemswerethereiscoolingrequiredafterpurging.Normallyafterthepurgingcycle,thereisasmallflowofprotectivegasrequiredtocompensateforleakages,andtokeepaconstantpressurewithintheenclosuresothattheingressofhazardousatmospherecannotgetinsidetheenclosure.Thisisknownaspressurization.Iftheequipmentinsidethepressurizedenclosurerequirescooling,eitherahigherflowrateofprotectivegasisrequiredthroughthepressurizationvalve,orasecondsourceofcoolinggasisintroducedintotheenclosure.Thestandarddifferentialpressuregaugewillindicatepressurizationonlyupto0.5inches(13mm)water,whichmaynotbeenoughforcoolingindication.Thecoolerindicatorgaugeisinstalledontothepressurization/purgepanel,andallowsmonitoringofthesystemduringnormaloperationofthepurge/pressurizationsystem.
Cooler Indicator Gauge
Specifications
OPERATING RANGEFullrange: 0to5"(0to127mm)waterLowrangered: 0to0.5"(0to13mm)waterSaferangegreen: 0.5to1.5"(13to38mm)waterCooler/Rapidexchangerangeyellow: 1.5to4.5"(38to114mm)waterHighrangered: 4.5to5"(114to127mm)water
BODY COMPONENTSCover: acrylicHousing: diecastaluminumcoatedtowithstand 168hoursaltspraycorrosiontest
TECHNICAL DATAMaximumoverloadpressure: 15psigAccuracy: ±2%offullscaleWeight: 1.2lb(510g)Processconnection: 1/8”FemaleNPTduplicatehighand lowpressuretaps,onepairside,onepairback
Indicator Gauge
Cooler Indicator Gauge(Vortex Indicator Gauge)
5 1
8
4
2
6
7
3
Subject to modifications • © 2010 PEPPERL+FUCHS, INC. • Printed in USA • Part No. TDOCT-B061_USA
www.pepperl-fuchs.com
PROCESS AUTOMATION – PROTECTINg yOUR PROCESS
Worldwide/german Headquarters Pepperl+Fuchs GmbH Mannheim · GermanyTel. +49 621 776 2222
E-Mail: [email protected]
1
Asia Pacific HeadquartersPepperl+Fuchs PTE Ltd.
SingaporeCompany Registration No. 199003130E
Tel. +65 6779 9091E-Mail: [email protected]
2
Central/Western Europe & Africa HeadquartersPepperl+Fuchs N.V.
Schoten/Antwerp · BelgiumTel. +32 3 6442500
E-Mail: [email protected]
3
Middle East HeadquartersPepperl+Fuchs M.E (FZE)
Dubai · UAETel. +971 4 883 8378
E-Mail: [email protected]
4
North/Central America Headquarters Pepperl+Fuchs Inc.
Twinsburg · Ohio · USATel. +1 330 486 0002
E-Mail: [email protected]
5
Northern Europe HeadquartersPepperl+Fuchs GB Ltd.
Oldham · EnglandTel. +44 161 6336431
E-Mail: [email protected]
6
Southern/Eastern Europe HeadquartersPepperl+Fuchs Elcon srl
Sulbiate · ItalyTel. +39 039 62921
E-Mail: [email protected]
7
Southern America HeadquartersPepperl+Fuchs Ltda.
São Bernado do Campo · SP · BrazilTel. +55 11 4341 8448
E-Mail: [email protected]
8
For over a half century, Pepperl+Fuchs has provided new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce and distribute electronic interface modules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to offer complete individual solutions – wherever and whenever you need us. We are the recognized experts in our technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies with the broadest line of proven components for a diverse range of applications.