XXXXXX XXXXXXXXX XXXXXX XXXXXXXXX EXPLOSION PROTECTION by R. Stahl 1-800-782-4357 PurgEx™ Z, Y, and X PURGE INDICATORS / CONTROLLERS 8626 SERIES INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 PURGE / PRESSURIZATION G Globally Certified Z,Y,X Purge Indicators / Controllers and Accessories Features: Stainless steel or anodized aluminum construction for superior corrosion resistance (NEMA 4,4X) Small Profile and light weight reduces installation footprint Global Certifications. Certified to: ATEX / IECEx / NEC / CEC in a single part number. Ideal for global companies look- ing to standardize on a single design Dry contact outputs for remote monitoring comes standard.
Transcript
Page 1: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

XXXXXXXXXXXXXXX

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G#

PURGE / PRESSURIZATIONXXXXXXXXXXXXXXX

EXPLOSION PROTECTION by R. Stahl 1-800-782-4357 #

XXXXXPurgEx™ Z, Y, and X PURGE INDICATORS / CONTROLLERS

8626 SERIES

INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G

Globally Certified Z,Y,X Purge Indicators / Controllers and Accessories

Features:• Stainless steel or

anodized aluminum construction for superior corrosion resistance (NEMA 4,4X)

• Small Profile and light weight reduces installation footprint

• Global Certifications.Certified to: ATEX / IECEx / NEC / CEC in a single part number. Ideal for global companies look-ing to standardize on a single design

• Dry contact outputs for remote monitoring comes standard.

Page 2: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx™ Z, Y, and X PURGE INDICATORS / CONTROLLERS

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G1

Selecting Purge Indicators / ControllerHere are key questions you will need to know in selecting your purge indicator / controller:

1. What protection method do you need? Z, Y, or X?

Type “Z”This system reduces the classification within protected enclosures from Division 2 / Zone 2 to non-hazardous. Automatic power control disconnects are not required, but visual and / or audible alarms must be initiated when there is loss of pressure within the enclosure.

Type ‘Y”This system reduces the classification within protected enclosures from Division 1 / Zone 1 to Division 2 / Zone 2. All protected equipment inside the enclosure must be rated for Division 2 / Zone 2. Automatic power control disconnects are not required, but visual and/or audible alarms must be initiated when there is loss of pressure. In addition to all requirements in Z, there must be a remote monitor alarm.

Type “X”This system reduces the classification within protected enclosures from Division 1 / Zone 1 to nonhazardous. It is required to automatically control electrical power to all protected equipment.

2. Is this a dust or gas environment? Is the hazard a Class I (Vapor, Liquid, Gas) or Class II (Dust)?

Purged and pressurized systems are an ideal method of explosion protection where com-ponents internal to the enclosure cannot be specifically rated for the area. They provide a light weight, corrosion resistant alternative to traditional explosion proof enclosures. The protection concept maintains an above atmospheric pressure within the enclosure not allowing hazardous gas and/or dust to enter and to come into contact with possible sources of ignition.

1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge gas source. The enclosure is diluted between 4 to 5 times its cubic capacity with this purge gas, eliminating ignitable amounts of hazardous materials from being present inside the enclosure.

2) Pressurized Phase. In this phase, we have eliminated ignitable amounts of hazard-ous materials from being inside the enclosure. To prevent outside hazardous materials from entering the enclosure, the enclosure is then slightly pressurized above the outside environment.

The Purge Process

Page 3: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx™ Z, Y, and X PURGE INDICATORS / CONTROLLERS

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G2

PURGE / PRESSURIZATION

3. How big is your enclosure?What is the cubic volume of your enclosure? Small - Up to 15 Cubic Feet Medium - Up to 75 Cubic Feet Large - Up to 200 Cubic Feet

4. Voltage? PurgEx offers the following: Z - 12 VDC, 24 VDC, 115 VAC, 230 VAC Y - 12 VDC or 24 VDC X - 115 or 230 VAC (for other voltages please consult factory)

5. Material Construction Do you require 316 Stainless (NEMA 4X) or Anodized Aluminum? (NEMA 4)

6. What type of Purge Gas Inlet Kit do you plan to use? CONTINUOUS PURGE / PURGE GASIn Continuous Purge, purge gas is continuously passed through the enclosure at a maintained pressure during and after the dilution cycle, and discharged to the outside atmo-sphere through an exhaust vent. This method is preferred for applications where heat builds up from the electronics within the pressurized enclosure.

LEAKAGE COMPENSATIVE / PRESSURIZATION PURGELeakage compensation allows a higher volume of purge gas during the dilution cycle, which is then reduced to only what is required to maintain the required pressure within the enclo-sure. This is preferred when a source of instrument grade air is limited.

7. Location of the exhaust vent. Side or Top? Traditional purge systems require an accessory exhaust vent. When one is required, its location needs to be determined (side or top mount). Please Note: If enclosure is 15 cubic feet or smaller, a seperate vent is not required.

Page 4: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 Y/Z Purge / Pressurization IndicatorCUSTOM CONFIGURATION LOGIC

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G3

CLASSIFICATIONS FOR Z PurgEx NEC / CEC / UL / CSA / ANSI / ISA 12.4 & NFPA 486 Certified Class I, Division 2, Groups A,B,C,D, T6 Class II, Division 2, Groups F & G, T6

ATEX & IECEx II 3 G Ex nA ic [pz] IIC T6 Gc II 3 D Ex tc IIIC T79°C Dc IP66 IECEx DNV 14.0029X DNV 14 ATEX 5461X

CLASSIFICATIONS FOR Y PurgEx

NEC / CEC / UL / CSA / ANSI / ISA 12.4 & NFPA 486 Certified Class I, Division 1, Groups A,B,C,D, T4 Class II, Division 1, Groups F & G, T4

ATEX & IECEx II 2 G Ex ib [py] IIC T4 Gb II 2 D Ex tb IIIC T79°C Db IP66 IECEx DNV 14.0029X DNV 14 ATEX 5460X

Ambient Temperature Range: +65˚C (+150˚F) Max.

–40˚C (–40˚F) Min. Globally Certified Y/Z Purge Indicators and

Accesories

Features:• Integral Vent standard on 15 CU FT or

smaller indicators (no need to purchase or install accessory vents)

• Stainless Steel or Anodized Aluminum Construction for Superior Corrosion Resistance (NEMA 4, 4X)

• Smallest Profile and Lightest Weight on the market reduces installation footprint

Global Certifications

• Certified to ATEX / IECEx / NEC / CEC in a single part number.

• Dry Contact Outputs for Remote Monitoring Come Standard.

• CE Marked

General Specifications: Casing Dimensions4.5” diameter x 1.9” tall (114.3 mm diameter x 48.3 mm tall).

Operating Temperature

-40˚F to 150˚F (-40˚C to 65˚C)

Purge Pressure Lower Limit:0.50 inch H20 (1.25 mbar).

CasingAnodized aluminum 2.48 lbs (1.13 kg), IP66, NEMA 4, (standard).316 stainless steel, 6.80 lbs. (3.04 kg), IP66, NEMA 4X, (optional).

Power Input / Consumption 0.5 Watts max.

Voltage:12 VDC model (11 VDC to 16 VDC), 47 to 63 Hz24 VDC model (19 VDC to 28 VDC), 47 to 63 Hz115 VAC model (85 VAC to 160 VAC), 47 to 63 Hz230 VAC model (130 VAC to 265 VAC), 47 to 63 HZ

Dry Contact RatingContact open on alarm (standard) Contact closed on alarm (optional) 265 Volts AC / DC, 150mA max

Standard HardwareAll stainless steel mounting fasteners, o-ring, 1/4” (6.4 mm) diameter vent restrictor, warning label, and CD with all required documentation

626/1-D

Y = Y PurgeZ = Z Purge

S = Up to 15 Cubic FeetM = Up to 75 Cubic FeetL = Up to 200 Cubic Feet

1 = 12VDC2 = 24VDC

3 = 115VAC*

4 = 230VAC*

Type of Purge Size of Enclosure Voltage

Start Here

7 = Dust8 = Gas

Dust or Gas

* Z Purge Only

8 626/1-D Y M 2

INTERNAL VENT ELIMINATES THE NEED FOR

EXTERNAL VENTS ON ENCLOSURE VOLUME UP TO 15 CUBIC FEET

AVAILABLE IN 316

STAINLESS STEEL OR ANODIZED ALUMINUM

BRILLIANT LED INDICATOR

GIVES 180° VIEWING

Page 5: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 Technical / Dimensional InformationCUSTOM CONFIGURATION LOGIC

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G4

PURGE / PRESSURIZATION

OPTIONS & ACCESSORIES AVAILABLE CONTINUED:

Protective Gas Loss Indicator Kit: An explosion-proof differential pressure switch may be installed to provide an alarm contact out-put signal to indicate the loss of the backup source of protective gas. Another explosion-proof differential pressure switch may be installed on the main protective gas supply to indicate that the primary protective gas pressure is adequate. Model number is PSO-PGLI-K.

Differential Pressure Gauge Kit: R. STAHL also offers an all stainless steel differential pressure gauge kit, which can be mounted on the left side model number PSO-DPG-L, right side model number PSO-DPG-R, top model number PSO-DPG-T or bottom model number PSO-DPG-B of enclosure.

4.50Ø (114.30Ø) REF.

1.88 (47.75)

2.13 (54.10) REF.

2.58 (65.53)

2.83 (71.88) REF.

ENCLOSUREWALL

FRONT VIEW

SIDE VIEW

SLOTS IN PROTECTIVE COVERTO VIEW LED FROM SIDE

HOLE IN PROTECTIVE COVERTO VIEW LED FROM FRONT

TERMINAL BLOCKS

POWER TERMINAL STRIP

ALARM TERMINAL STRIP

ENCLOSURE VENT PORT

PURGE PRESSURE REFERENCE PORT

INTERNAL VIEWMOUNTED ON ENCLOSURE

TOP OF PurgEx0.28" (7.0mm) DIA. THRUTYP. 5 PLACES72 DEGREES APARTON A 3.50" (88.9mm) DIA. B.C.

3.00" (76.2mm) DIA. THRU

AND HOLE TEMPLATE

* Z Purge Only

O = Normally open contactX = Normally closed contact

T = Continuous Purge Inlet P = Manual Leakage Compensation Purge InletN = No Inlet Kit (Must be ordered separately. See pages G9-G14 for details on dimensions)

A = AluminumS = 316 Stainless

S = Side MountedT = Top Sided MountedO = Specify if ordering less than 15 cu.ft. indicator, or if ordering vent separately

Alarm 05 Inlet Kit Accessory Material Construction

Exhaust Vent Mounting

B

OS 05 T S B

Page 6: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge Controllers (XP Series)

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G5

PurgEx X-Purge Controller (D)

• Integral Exhaust Vent Standard. No need to order and assemble accessory vent for enclosures with a volume up to 15 cubic feet.

• Available in Anodized Aluminum or 316 Stainless Steel 115 VAC up to 25 amps or 230VAC up to 12.5 Amps.

• Rugged, visual LED indicator for local monitoring is supplied as standard.

X Purge Controllers enable the use of general purpose components to be placed inside the enclosures the X Purge will be monitoring and placed in a Class I Division 1, and ATEX/ IECEx Zone 1 hazardous area. These PURGEx X-Purge units come with global certifications. These units offer the lightest weight, and smallest profile controllers on the market. Because these designs mount directly on the enclosure, no additional holes, sheet metal, or plumbing is required.

CLASSIFICATIONS NEC / CEC / CSA / ANSI / ISA 12.4, & NFPA 496 Certified Class I, Division 1, Group B,C, & D, T4 Class II, Division 1, Group E,F, & G, T4

ATEX & IECEx II 2 G Ex e mb ib [px] IIC T4 II 2 D Ex tb IIIC T119°C Db IP66 IECEx DNV 14.0029X DNV 14 ATEX 5460X

Ambient Temperature Range: +65˚C (+150˚F) Max.

–40˚C (–40˚F) Min.

Dust or Gas 626/1

7 = Dust8 = Gas

S = Up to 15 Cubic FeetM = Up to 75 Cubic FeetL = Up to 200 Cubic Feet

X = X-PurgeD = Housing Mounted on enclosureN = Externally Mounted Housing

Mounting Method Type of Purge

Size of Enclosure

Start Here

626/1 D X M8

CUSTOM CONFIGURATION LOGIC

Globally Certified X Purge Indicators and Accesories

Features:• Integral Vent standard on 15 CU FT or

smaller indicators (no need to purchase or install accessory vents)

• Stainless Steel or Anodized Aluminum Construction for Superior Corrosion Resistance (NEMA 4, 4X)

Global Certifications

• Certified to ATEX / IECEx / NEC / CEC in a single part number.

• Dry Contact Outputs for Remote Monitoring Come Standard.

• CE Marked

Page 7: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge Controllers (XP Series)

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G6

PURGE / PRESSURIZATION

External Mounted (N) Vent Included

• Available in Anodized Aluminum or 316 Stainless Steel 115 VAC up to 25 amps or 230VAC up to 12.5 Amps.

• Rugged, visual LED indicator for local monitoring is supplied as standard.

CUSTOM CONFIGURATION LOGIC

05Voltage

A = AluminumS = 316 Stainless

O = Normally open contactX = Normally closed contact

T = Continuous Purge Inlet P = Manual Leakage Compensation Purge InletA = Automatic Leakage Compensation Purge InletN = No Inlet Kit (Must be ordered separately. See pages G9-G17 for details on dimensions)

S = Side T = Top O = None (will order seperately, or 15 cubic feet or smaller)

S = Class I, Division 1T = ATEX / IECEx Zone 1

Material Alarm Type of Compensation Exhaust Vent Mounting

Classification

A3 O T S C

3 = 115VAC4 = 230VACFor DC volt-age, consult factory

05

Page 8: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge Controllers (XP Series)GENERAL SPECIFICATIONS

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G7

Casing Dimensions8.0” diameter x 1.9” tall (203.2 mm diameter x 48.3 mm tall), protrudes outside of purged enclosure.6.5” diameter x 4.50” tall (65.1 mm diameter x 114.0 mm tall), protrudes inside of purged enclosure.

Operating Temperature-40˚F to 150˚F (-40˚C to 65˚C)

Purge Pressure Lower Limit:0.50 inches H20 (1.25 mbar) Purge Controller will disconnect power to protected enclosure electronics.

CasingAnodized aluminum 16.09 lbs (7.30 kg), NEMA 4, (IP66).316 stainless steel, 37.98 lbs. (17.23 kg), NEMA 4X, (IP66).

Power Control Capability115 VAC up to 25 Amps RMS continuous over specified voltage ranges.230 VAC up to 12.5 Amps RMS continous over specified voltage ranges. Power Input / Consumption2 Watts max.

Voltage:115 VAC model (85 VAC to 160 VAC), 47 to 63 Hz230 VAC model (130 VAC to 265 VAC), 47 to 63 HZ

Dry Contact Outputs & Rating1. Enclosure purge pressure is below 0.50 inches H20 (1.25 mbar). 2. Enclosure exhaust flow has stopped.3. Purge Controller is in maintenance mode. Normally open contacts (standard).Normally closed contacts (optional). All rated to 265 Volts AC/DC, 150mA max.

Standard HardwareAll stainless steel mounting hardware, o-ring, 1/4” (6.4 mm) diameter exhaust vent restrictor, CD with all required documentation.

Hazardous Area ApprovalsATEX and IECExII 2 G EX e mb ib [px] IIC T4 Gb “for Zone 1 gas hazardous areas”II 2 D EX tb IIIC T119˚C Db IP66 “for Zone 1 dust hazardous areas”

ANSI / ISA 12.4, CEC, NEC, and NFPA 496 Class I, Division 1, Group B,C, & D, T4 “for gas hazardous areas”Class II, Division 1, Group E,F, & G, T4 “for dust hazardous areas”

Certified to an Ambient Temperature Range of -40˚F (-40˚C) <Tamb< + 150˚F (+65˚C)

CE Marked

Page 9: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge Controllers (XP Series)DIMENSIONAL INFORMATION

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G8

PURGE / PRESSURIZATION

9

FRONT VIEW OF UNIT

SIDE VIEW OF UNIT

6.40" DIA.

8.00" DIA.(203.2mm DIA.)

2.50"(63.5mm)

(162.6mm DIA.)

4.50" INSIDE ENCLOSURE(114.3mm) INSIDE ENCLOSURE

1.82"(46.2mm)

OUTSIDE ENCLOSURESEALING SURFACE

10.30" (261.6mm)

LOCAL LED STATUSINDICATOR

0.25" (6.4mm) OUTER DIA. TUBECOMPRESSION FITTINGUP TO 6 PLACES TYP.

X - PURGE CONTROLLER 10.42" (264.7mm)

8.34" (211.8mm)

Page 10: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 Sheet Steel X Purge Controllers

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G9

PurgEx X-Purge Controller (E)

• Integral Exhaust Vent Standard. No need to order and assemble accessory vent enclosure with a volume up to 15 cubic feet.

• 316 Stainless Steel 115 VAC up to 25 amps or 230VAC up to 12.5 Amps.

• Rugged, visual LED indicator for local monitoring is supplied as standard.

X Purge Controllers enable the use of general purpose components to be placed inside the enclosures the X Purge will be monitoring and placed in an ATEX or IECEx Zone 1 hazardous area. These units offer the lightest weight, and smallest profile controllers on the market. Because these designs mount directly on the enclosure, no additional holes, sheet metal, or plumbing is required.

CLASSIFICATIONS ATEX & IECEx II 2 G Ex e mb ib [px] IIC T4 Gb II 2 D Ex tb IIIC T119°C Db IP66 IECEx DNV 14.0029X DNV 14 ATEX 5460X

Ambient Temperature Range: +65˚C (+150˚F) Max.

–40˚C (–40˚F) Min.

Dust or Gas 626/1

7 = Dust8 = Gas

S = Up to 15 Cubic FeetM = Up to 75 Cubic FeetL = Up to 200 Cubic Feet

X = X-PurgeE = Housing Mounted on enclosureM = Externally Mounted Housing

Protection Method Type of Purge

Size of Enclosure

Start Here

626/1 E X M8

CUSTOM CONFIGURATION LOGIC

Globally Certified X Purge Indicators and Accesories

Features:• Integral Vent standard on 15 CU FT or

smaller indicators (no need to purchase or install accessory vents)

• Stainless Steel Superior Corrosion Resistance (NEMA 4X)

Global Certifications• Certified to ATEX / IECEx in a single part number.

• Dry Contact Outputs for Remote Monitoring Come Standard.

• CE Marked

Page 11: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

05

PurgEx External Mount (M)

Vent Included

PurgEx ™ 8626 Sheet Steel X Purge Controllers

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G10

PURGE / PRESSURIZATION

Voltage

S = 316 Stainless

O = Normally open contactX = Normally closed contact

T = Continuous Purge Inlet P = Manual Leakage Compensation Purge InletA = Automatic Leakage CompensationN = No Inlet Kit (Must be ordered separately. See pages G9-G13 for details on dimensions)

S = Side T = Top O = None (will order seperately, or 15 cubic feet or smaller)

Material Alarm Type of Compensation Exhaust Vent Mounting

z

3 O T S Z

3 = 115VAC4 = 230VACFor DC volt-age, consult factory

CUSTOM CONFIGURATION LOGIC

05S

Page 12: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge ControllersGENERAL SPECIFICATIONS

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G11

Operating Temperature-40˚F to 150˚F (-40˚C to 65˚C)

Purge Pressure Lower Limit:0.50 inches H20 (1.25 mbar) Purge Controller will disconnect power to protected enclosure electronics.

Enclosure14 gage 316 stainless steel, 11.00 lbs. (5.00 kg), NEMA 4X, (IP66).

Power Control Capability115 VAC up to 25 Amps RMS continuous over specified voltage ranges.230 VAC up to 12.5 Amps RMS continous over specified voltage ranges.

Power Input / Consumption0.5 Watts max.

Voltage:115 VAC model (85 VAC to 160 VAC), 47 to 63 Hz230 VAC model (130 VAC to 265 VAC), 47 to 63 HZ

Dry Contact Outputs & Rating1. Enclosure purge pressure is below 0.50 inches H20 (1.25 mbar). 2. Enclosure exhaust flow has stopped.3. Purge Controller is in maintenance mode. Normally open contacts (standard).Normally closec contacts (optional). All rated to 265 Volts AC/DC, 150mA max.

Standard HardwareAll stainless steel mounting hardware, gasket, and CD with all required documentationHazardous Area ApprovalsATEX and IECExII 2 G EX e mb ib [px] IIC T4 Gb “for Zone 1 gas hazardous areas”II 2 D EX tb IIIC T119˚C Db IP66 “for Zone 1 dust hazardous areas”

Certified to an Ambient Temperature Range of -40˚F (-40˚C) <Tamb< + 150˚F (+65˚C)

CE Marked

Page 13: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

PurgEx ™ 8626 X Purge ControllersDIMENSIONAL INFORMATION

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G12

PURGE / PRESSURIZATION

13

FRONT VIEW RIGHT SIDE VIEW

X - PURGEx CONTROLLER

ENCLOSURE SHALL NOT BEOPENED UNLESS POWER IS

REMOVED OR AREA HAS BEENPROPERLY TESTED AND IS KNOWN

WARNING

0575

II 2 G Ex e mb [px] IIC T4 GbII 2 D Ex tD [px] A21 T119°C IP66 Db

TO BE NON-HAZARDOUS.

DRY CONTACT RATING = 265 AC/DC, 150 mA

_____ 115 VAC, 50/60 Hz, 25 Amps

Serial No.______________________

_____ 230 VAC, 50/60 Hz, 12.5 Amps

DNV-2008-OSL-ATEX-10575IECEx DNV 08.0323

8.23 (209.0)

7.25 (184.2) 3.38 (85.9)

6.25 (158.8) 8.23 (209.0)

3.92 (99.6)

2.00(50.8)

1.17 (29.7)

ATMOSPHERIC VENTSPARK ARRESTORINSTALLED

0.50 (5.1) TO EDGE OFHUB PANEL OPENING

7.00 (177.8) HUB PANEL OPENING

3.87 (98.3) TOEDGE OF HUB

PANEL OPENING

PANEL OPENING1.53 (38.9) HUB

7.00 (177.8)

REMOVABLE HUB PANEL OPENING

10.38 (263.7)

10.70 (271.8)9.00 (228.6)

6.50 (165.1)

0.28 (7.1) TYP. 4 PLACES

1.17 (29.7) TYP. 3 PLACES

1.92 (48.8) TYP. 3 PLACES

ENCLOSURE 3 PRESSURE

ENCLOSURE 2 PRESSURE

ENCLOSURE 1 PRESSURE

ENCLOSURE 3 EXHAUST

ENCLOSURE 2 EXHAUST

ENCLOSURE 1 EXHAUST

0.25 (6.4)Ø O.D. TUBECOMPRESSION FITTINGTYP. 6 PLACES

0.50 (12.7)0.50 (12.7)

1.50 (38.1)

1.50 (38.1)

2.50 (63.5)

2.50 (63.5)

CL

Page 14: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Continuous Dilution Purge Gas Inlet Kits

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G13

Size Information

Size A (mm) B (mm) C (mm) Purge Gas Inlet Size Enclosure Volume

Small 5.15 (130.8) 4.44 (112.8) 4.00 (101.6) 1/4 - 18 FNPT Up to 15 Cubic Feet

Medium 6.19 (157.2) 4.68 (118.9) 4.23 (107.4) 3/8 - 18 FNPT Up to 75 Cubic Feet

Large 6.19 (157.2) 4.68 (118.9) 4.23 (107.4) 1/2 - 14 FNPT Up to 200 Cubic Feet

Ordering Information

Size Enclosure Type Catalog Number

SmallAluminum PSO-SCD-A

Stainless PSO-SCD-S

MediumAluminum PSO-MCD-A

Stainless PSO-MCD-S

LargeAluminum PSO-LCD-A

Stainless PSO-LCD-S

ENCLOSUREWALL

OUTSIDE

FRONT VIEW SIDE VIEWMOUNTING HOLE PATTERN

NOTE: PURGE GAS INLET = 1/4 - 18 FNPT

ON

ON

ENCLOSUREWALL

INSIDE

0.77Ø (19.6Ø) THRUENCLOSURE WALL

FOR MOUNTING

1.81 (46.0)

0.92 (23.4)

5.15 (130.8)

4.44 (112.8)

4.00 (101.6)

PRESSUREGAUGE

SHUT-OFF VALVESHOWN IN ON POSITION

PRESSUREREGULATOR

ADJ. KNOB

0.22Ø (5.6Ø) THRUENCLOSURE WALL

FOR MOUNTING

A

B

C

Page 15: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Manual Leakage Compensation Purge Gas Inlet Kits

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G14

PURGE / PRESSURIZATION

Size Information

Size A (mm) B (mm) C (mm) Purge Gas Inlet Size Enclosure Volume

Small 5.15 (130.8) 4.44 (112.8) 4.00 (101.6) 1/4 - 18 FNPT Up to 15 Cubic Feet

Medium 6.19 (157.2) 4.68 (118.9) 4.23 (107.4) 3/8 - 18 FNPT Up to 75 Cubic Feet

Large 6.19 (157.2) 4.68 (118.9) 4.23 (107.4) 1/2 - 14 FNPT Up to 200 Cubic Feet

Ordering Information

Size Enclosure Type Catalog Number

SmallAluminum PSO-SMLC-A

Stainless PSO-SMLC-S

MediumAluminum PSO-MMLC-A

Stainless PSO-MMLC-S

LargeAluminum PSO-LMLC-A

Stainless PSO-LMLC-S

ENCLOSUREWALL

OUTSIDE

FRONT VIEWSHOWN IN FAST DILUTION ON POSITION

0.45Ø (11.4Ø) THRUENCLOSURE WALL

FOR MOUNTING

SIDE VIEWMOUNTING HOLE PATTERN

NOTE: PURGE GAS INLET = 1/4 - 18 FNPT

ON

ON

ENCLOSUREWALL

INSIDE

0.77Ø (19.6Ø) THRUENCLOSURE WALL

FOR MOUNTING

2.49 (63.3)

0.92 (23.4)

LEAKAGECOMPENSATION

SET SCREW

5.15 (130.8)

4.44 (112.8)

4.00 (101.6)

JAM NUT

PRESSUREGAUGE

DILUTION VALVESHOWN IN ON POSITION

PRESSUREREGULATOR

ADJ. KNOB

B

A

C

Page 16: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Automatic Leakage Compensation Purge Gas Inlet Kits

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G15

*X Purge Controllers Only

Size Information

Size A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) Purge Gas Inlet Size Enclosure Volume

Small 3.57 (90.7) 4.44 (112.8) 3.28 (83.3) 4.95 (125.7) 2.53 (64.3) 3.31 (84.1) 1/4 - 18 FNPT Up to 15 Cubic Feet*Medium 4.89 (124.2) 4.68 (118.9) 3.84 (97.5) 4.31 (109.5) 2.75 (69.8) 3.93 (99.8) 3/8 - 18 FNPT Up to 75 Cubic Feet*

Large 4.89 (124.2) 4.68 (118.9) 3.84 (97.5 4.31 (109.5) 2.75 (69.8) 3.93 (99.8) 1/2 - 14 FNPT Up to 200 Cubic Feet*

Size Enclosure Type Voltage Enclosure Type Catalog Number

Small

Aluminum

115VACDiv 1 PSO-SALC-D1A

Zone1 PSO-SALC-Z1A

230VACDiv 1 PSO-SALC-D2A

Zone 1 PSO-SALC-Z2A

Stainless

115VACDiv1 PSO-SALC-D1S

Zone 1 PSO-SALC-Z1S

230VACDiv 1 PSO-SALC-D2S

Zone 1 PSO-SALC-Z2S

Medium

Aluminum

115VACDiv 1 PSO-MALC-D1A

Zone 1 PSO-MALC-Z1A

230VACDiv 1 PSO-MALC-D2A

Zone 1 PSO-MALC-Z2A

Stainless

115VACDiv 1 PSO-MALC-D1S

Zone 1 PSO-MALC-Z1S

230VACDiv 1 PSO-MALC-D2S

Zone 1 PSO-MALC-Z2S

Large

Aluminum

115VACDiv 1 PSO-LALC-D1A

Zone 1 PSO-LALC-Z1A

230VACDiv 1 PSO-LALC-D2A

Zone 1 PSO-LALC-Z2A

Stainless

115VACDiv 1 PSO-LALC-D1S

Zone 1 PSO-LALC-Z1S

230VACDiv 1 PSO-LALC-D2S

Zone 1 PSO-LALC-Z2S

Ordering Information

Page 17: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Automatic Leakage Compensation Purge Gas Inlet Kits

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G16

PURGE / PRESSURIZATION

EN

CLO

SU

RE

WA

LLO

UTS

IDE

FRO

NT

VIE

W

0.45

Ø (

11.4

Ø)

THR

UE

NC

LOS

UR

E W

ALL

FOR

MO

UN

TIN

G

SID

E V

IEW

MO

UN

TIN

G H

OLE

PA

TTE

RN

NO

TE:

PU

RG

E G

AS

INLE

T =

1/4

- 18

FN

PT

EN

CLO

SU

RE

WA

LLIN

SID

E

0.77

Ø (

19.6

Ø)

THR

UE

NC

LOS

UR

E W

ALL

FOR

MO

UN

TIN

G

LEA

KA

GE

CO

MP

EN

SA

TIO

NS

ET

SC

RE

W

4.44

(11

2.8)JA

M N

UT

PR

ES

SU

RE

GA

UG

E

PR

ES

SU

RE

RE

GU

LATO

RA

DJ.

KN

OB

3.57

(90

.7)

0.55

(14

.0)

1.06

(26

.9)

2.53

(64

.3)

3.31

(84

.1)

4.95

(12

5.7)

3.28

(83

.3)

A

B

D

E

F

C

Page 18: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

A

B

Back-Up Vents, Top Mount

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G17

Size Side Dimensions

SmallA 2.14Ø (54.4Ø)

B 4.00 (101.6)

MediumA 3.50Ø (88.9Ø)

B 5.75 (146.1)

LargeA 5.12Ø (130.1Ø)

B 7.62 (193.6)

Size Catalog NumberSmall PSO-SBUV-T

Medium PSO-MBUV-T

Large PSO-LBUV-T

Size Box Hole Size RequiredSmall 0.57Ø (14.5Ø)

Medium 1.31Ø (33.3Ø)

Large 2.38Ø (60.5Ø)

Page 19: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Back-Up Vents, Side Mount

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 G18

PURGE / PRESSURIZATION

Size Side Dimensions

Small

A 2.50 (63.5)

B 5.00 (127.0)

C -

Medium

A 4.28 (108.7)

B 7.36 (186.9)

C 6.47 (163.3)

Large

A 6.03 (153.2)

B 10.42 (264.7)

C 9.11 (231.4)

Size Box Hole Size RequiredSmall 0.57Ø (14.5Ø)

Medium 1.31Ø (33.3Ø)

Large 2.38Ø (60.5Ø)

Size Box Hole Size RequiredSmall 0.57Ø (14.5Ø)

Medium 1.31Ø (33.3Ø)

Large 2.38Ø (60.5Ø)

A

CB

Size Catalog NumberSmall PSO-SBUV-S

Medium PSO-MBUV-S

Large PSO-LBUV-S

Page 20: PurgEx™ Z, Y, and X PURGE PURGE / PRESSURIZATION …1) Purge Phase. In this phase, hazardous gases are removed from the enclosure by diluting the inside of the enclosure with a purge

Top & Side Vent Mount ConfigurationsFOR EXTERNAL MOUNTED (N) AND (M) MODELS ONLY

EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PURGE / PRESSURIZATION

G19

Top Vent Mount Option

Side Vent Mount Option

VENT CAP ASSY.

PIPE NIPPLE1/4 INCH TUBE x PIPE NIPPLE FITTING

PIPE NIPPLE x STRAIGHT THREAD FITTING

HEX NUT TOP INSIDE WALL OF ENCLOSURE

PIPE TEE

TOP OUTSIDE WALL OF ENCLOSURE

NOTES:

1. REQUIRED HOLE THRU ENCLOSUREWALL FOR VENT IS 0.57Ø (14.48Ø)

VENT CAP ASSY.

PIPE NIPPLE

PIPE TEE

1/4 INCH TUBE x PIPE NIPPLE FITTING

PIPE NIPPLE x STRAIGHT THREAD FITTING

SIDE OUTSIDE WALL OF ENCLOSURE

SIDE INSIDE WALL OF ENCLOSURE

HEX NUT

NOTES:

REQUIRED HOLE THRU ENCLOSURE WALLFOR VENT IS 0.57Ø (14.48Ø)

SIDE INSIDE WALL OF ENCLOSURE

HEX NUT

PIPE THREAD x STRAIGHT THREAD FITTING

PIPE NIPPLE

PIPE TEE

SIDE OUTSIDE WALL OF ENCLOSURE

1/4 INCH TUBE x PIPE NIPPLE FITTING

VENT CAP ASSY.

NOTES

1. REQUIRED HOLE THRU ENCLOSURE WALL FOR VENT IS 0.57 (14.48Ø)

Vent Mount Size

Small 0.57Ø (14.48Ø)

Medium 1.31Ø (33.3Ø)

Large 2.38Ø (60.5Ø)

Size Box Hole Size Required

Size Top / Side Catalog Number

Small

Top DO-11068-B

SideDO-11069-B

DO-11070-B

Medium

Top DO-11113-B

SideDO-11114-B

DO-11115-B

Large

Top DO-11128-A

SideDO-11129-A

DO-11130-A

R. STAHL, Inc.

13259 N. Promenade Blvd Stafford, TX 77477

Phone: 1-800-782-4357 www.rstahl.com

Literature Order: CY 040215


Recommended