QA3 Cable Supports Cable Supports QA3 For Threaded Rigid Conduit & IMC with pOZi-grip Wedging Plug TypeS For two or more wires Use: For supporting non-armored electrical cables in vertical conduit risers. Features: • Use with all types of insulations at volt- ages to and including 600V. • The fastest and easiest type cable support to install. • The knurled insulating inner surface and impregnated hardwood pOZi-grip Plug pro- vide positive support well in excess of code requirements. Material/Finish: Bodies of fittings are Malleable or Ductile iron with Hot Dip Galvanized Finish. Optional Material/Finish: Bodies of fittings are also available in cast aluminum. Contact your local representa- tive. Specify: 1 Catalog Number 2 Type and number of conductors in conduit 3 Outside diameters of each conductor Third Party Certification: ^ UL Listed: E-11853 EXPRESS SHIPMENT PROGRAM •Denotes ESP Availability TypeS Complete Fitting Conduit Ha 1!4" 2" 2W 3" 3^" 4" 5" 6" 2-4 Same Size Wires S-1500-1 S-2000-1 S-2500-1 S-3000-1 S-3500-1 S-4000-1 S-5000-1 S-6000-1 SOP More OP Different Size (Minna iflPBJJ S-1500-2 S-2000-2 S-2500-2 S-3000-2 S-3500-2 S-4000-2 S-5000-2 S-6000-2 Catalog Number Body Only S-1500-BO S-2000-BO S-2500-BO S-3000-BO S-3500-BO S-4000-BO S-5000-BO S-6000-BO Plug (My 24 Same Size Wipes SPLG-1500-1 SPLG-2000-1 SPLG-2500-1 SPLG-3000-1 SPLG-3500-1 SPLG-4000-1 SPLG-5000-1 SPLG-6000-1 5 or More or Different Size Wipes SPLG-1500-2 SPLG-2000-2 SPLG-2500-2 SPLG-3000-2 SPLG-3500-2 SPLG-4000-2 SPLG-5000-2 SPLG-6000-2 Dim. in Inches Outside Nametei 2% 3% 3% 4 1 /* 5 1 ^ 5% 6 7 A 8% Overall i* Height 2% 2% 3 3)4 3^ 3% 4!4 51* Cable support plugs will not be supplied undrilled. CSA Certified: 11584 Applicable Third Party Standards: UL Standard: 5146 CSA Standard C22.2 No. 18 NEC 300-19 Note: Due to the possibility of magnetic heating effects, a single alternating current conductor should not be used in these fittings. tFor EMT or plastic conduit, the above standard fittings can be used on the male thread of an EMT connector or plastic adapter. For fibre conduits, asbestos cement ducts or special applications of EMT, set screw type fittings can be furnished at a price addition. O-Z/GEDIMEV
Transcript
Page 1: QA3 Cable Supports QA3 Cable Supports · A) Spacing Intervals - Maximum. Conductors in vertical raceways shall be supported.One cable support shall be pro-vided at the top of the

QA3Cable Supports

Cable Supports QA3

For Threaded Rigid Conduit & IMC with pOZi-grip Wedging Plug

TypeSFor two or more wires

Use:For supporting non-armored electricalcables in vertical conduit risers.

Features:• Use with all types of insulations at volt-ages to and including 600V.• The fastest and easiest type cable supportto install.• The knurled insulating inner surface andimpregnated hardwood pOZi-grip Plug pro-vide positive support well in excess of coderequirements.

Material/Finish:Bodies of fittings are Malleable or Ductileiron with Hot Dip Galvanized Finish.

Optional Material/Finish:Bodies of fittings are also available in castaluminum. Contact your local representa-tive.

Specify:1 Catalog Number2 Type and number of conductors in conduit3 Outside diameters of each conductor

Third Party Certification:^ UL Listed: E-11853

EXPRESS SHIPMENT PROGRAM

•Denotes ESP Availability

TypeS

Complete Fitting

ConduitHa

1!4"2"2W3"

3^"4"5"6"

2-4 SameSize Wires

S-1 500-1S-2000-1S-2500-1S-3000-1

S-3500-1S-4000-1S-5000-1S-6000-1

SOP More OPDifferent Size

(MinnaiflPBJJ

S-1 500-2S-2000-2S-2500-2S-3000-2

S-3500-2S-4000-2S-5000-2S-6000-2

Catalog Number

BodyOnly

S-1500-BOS-2000-BOS-2500-BOS-3000-BO

S-3500-BOS-4000-BOS-5000-BOS-6000-BO

Plug (My

24 SameSize Wipes

SPLG-1 500-1SPLG-2000-1SPLG-2500-1SPLG-3000-1

SPLG-3500-1SPLG-4000-1SPLG-5000-1SPLG-6000-1

5 or More orDifferent Size

Wipes

SPLG-1 500-2SPLG-2000-2SPLG-2500-2SPLG-3000-2

SPLG-3500-2SPLG-4000-2SPLG-5000-2SPLG-6000-2

Dim. in InchesOutsideNametei

2%3%3%41/*

51^5%67A8%

Overalli* Height

2%2%33)4

3^3%4!451*

Cable support plugs will not be supplied undrilled.

CSA Certified: 11584

Applicable Third Party Standards:UL Standard: 5146CSA Standard C22.2 No. 18NEC 300-19

Note:Due to the possibility of magnetic heating effects,a single alternating current conductor should notbe used in these fittings.

tFor EMT or plastic conduit, the above standard fittingscan be used on the male thread of an EMT connector orplastic adapter. For fibre conduits, asbestos cement ductsor special applications of EMT, set screw type fittings canbe furnished at a price addition.

O-Z/GEDIMEV

Page 2: QA3 Cable Supports QA3 Cable Supports · A) Spacing Intervals - Maximum. Conductors in vertical raceways shall be supported.One cable support shall be pro-vided at the top of the

QA1 Cable Supports QA1

Cable SupportsGeneral Information

Cable Supports are used to support cablesin vertical raceways or risers. Cables, whenthey are supported, relieve the strain thatwould be placed on the interior of panels orother devices to which the cables are con-nected. Properly designed cable supportsmust not only be capable of supporting agiven weight of cable with a good margin ofsafety but must also support the cable with-out damaging the insulation or excessivelyreducing the amount of insulation over theconductor in the area where the cable issupported. O-Z/Gedney has been furnishingCable Supports to the electrical industry forover 75 years that meet these requirements.

The National Electrical Code forCable Supports reads as follows:Section 300-19. SupportingConductors in Vertical RacewaysA) Spacing Intervals - Maximum.Conductors in vertical raceways shall besupported.One cable support shall be pro-vided at the top of the vertical raceway oras close to the top as practical, plus a sup-port for each additional interval of spacingas specified in Table 300-19(a).

TABLE 300-19(a). SPACING FOR CONDUCTOR SUPPORTS

AWGorCircular-MillSize of Wire

ConductorsSupport of

Conductors inVertical Raceways

Aluminum orCopper-CladAluminum Copper

18 AWG - 8 AWG Not greater than 100 feet. . . 100 feet6 AWG - 0 AWG Not greater than 200 feet. . . 100 feet2/0 AWG - 4/0 AWG Not greater than 180 feet . . . 80 feetover 4/0 AWG - 350 MCM. . . . Not greater than 135 feet . . . 60 feet

over 350 MCM - 500 MCM . . . Not greater than 120 feet . . . 50 feetover 500 MCM - 750 MCM . . . Not greater than 95 feet . . . 40 feetover 750 MCM Not greater than 85 feet . . . 35 feet

The chart below indicates the support we recommend for several of the most common applications.

Recommended O-Z/GedneyApplication Cable Supports Page

Indoors -Indoors -OutdoorsOutdoors

at voltages to 600Vat voltages above 600V- vertical Steel conduit pole risers- vertical PVC conduit pole risers

Type SType RType CMTType V

QA3QA4QA7QA9

O-Z/GEDIMEV

Page 3: QA3 Cable Supports QA3 Cable Supports · A) Spacing Intervals - Maximum. Conductors in vertical raceways shall be supported.One cable support shall be pro-vided at the top of the

QA2

Cable SupportsGeneral Information

Two basic types of cable supports areoffered for use with non-armored cable.They both utilize the pOZi-grip® WedgingPlug. pOZi-grip® is a unique manufacturingtechnique for lining the cable grooves with acoarse grain grit using a high strengthepoxy adhesive. This grit improves theCable Support holding power and does notinjure the jacket or insulation on the cable.Other features of these types and theirapplications are illustrated below.

Cable Supports QA2

One Piece Plug TypeThis type consists of a metal body havingan insulating liner with a knurled andtapered inside surface and a one pieceimpregnated hardwood wedging plug hav-ing a groove for each wire. This type sup-port is recommended for use with all typesof non-armored cables 600 volts or less, asit is the easiest to install, impossible toinstall incorrectly and it provides ventilationof the conduit. This design is used in ourTypes "S" and "D" Cable Supports. Thebasic principles of their assembly are illus-trated below.

1 Screw bodyon the end of theconduit or connec-tor in place of theregular insulatingbushing.

Multiple Segment Plug TypeThis type consists of an all metal body hav-ing a tapered inner surface and a canvasbakelite multiple segment wedging plug soconstructed that each cable is supportedbetween grooves in adjacent segments.This construction provides the uniform pres-sure distribution required by the softer typesof insulations frequently used at higher volt-ages. This design is used in no-ventilatingtypes "R," "DR," "W," "C," "K" and "M," andVentilating Compound Types "CMT," and"V." The basic principles of their assemblyare illustrated below.

1 Screw bodyon the end of theconduit or connectorin place of the regu-lar insulating bush-ing.

2 Pull wires andarrange temporarymeans of support.

2 Pull wires andarrange temporarymeans of support.

3 a. Remove allpulling compoundfrom wires in thearea where theypass through thecable support,b. Place the plugbetween the wiresas close to the top

of the body as possible. (Where more thanone wire size is involved, care should betaken to locate each in the proper groove.)

4 Tap the plug firmlyinto the support body.

3 a. Remove allpulling compoundfrom wires in thearea where theypass through thecable support,b. Place the seg-ments of the plugaround the wires.Where more than

two segments are involved the top of eachplug segment has numbers at each endand it is important that these are paired withthe corresponding numbers on the adjacentplug segments.

4 Drive the plugsegments evenlyand hard into thesupport body.

OZ/GEDNEY


Recommended