LIEBERT® RDU-S™ RACK MANAGEMENT DEVICEProduct SpecificationDescriptionThe Liebert RDU-S is a compact rack processing unit designed to monitor the environment in electronic equipment racks and rooms through various types of sensors and cameras. The unit can accommodate multiple sensors, such as temperature, humidity, water, smoke, motion and door sensors. It can also be used for remote notification such as activating a beacon light to report problems.
The compact design makes it suitable for installation in a rack, where it takes up little space, or it may be mounted on a wall for access without opening the equipment rack.
Hardware and Components - What’s IncludedThe unit comes standard with the following components:
DimensionsThe dimensions of the unit are shown below:
Mounting OptionsMount the Liebert RDU-S securely before connecting equipment, typically in a 19" rack or mounted on a wall. Mounting options include:
• Horizontal mounting in a rack with factory-supplied brackets and screws (shown below)
• Wall mounting with factory-supplied brackets and screws• Vertical mounting in a rack with a factory-supplied round hangers
(shown at right)
Item Quantity Item Quantity
• Liebert RDU-S Rack Management Device 1 • Mounting brackets 2
• Power cords 2 • Round hangers for vertical mounting
2• IEC-320-C13 to NEMA 5-15P power cord 1
• IEC-320-C13 to IEC-320-C14 power cord 1 • Quick-start guide, SL-31305 1
Height1-3/4" (45mm)
Width17-3/8"
(441mm)Depth2-1/4" (57mm)
MountingHole
REAROF
UNIT
TOPOF
UNIT
RoundHanger
Mounting holes A-H for round hanger
EF
GH
AB
CD
Vertical Rack Mounting
Mounting hole for rack mounting
Bracket flush with front of unitFRONT OF UNIT
Horizontal Rack Mounting
2
Ports and IndicatorsFigure 1 shows the front panel of the Liebert RDU-S. The ports and their functions are listed in Table 1.
Figure 1 Ports and indicators on front of unit
Status Indicators
Refer to Table 2 for details on the unit’s status indicators: relay outputs, power, alarm and run.
Table 1 Port descriptions
Port # Label Function
Power input 1 100-240V~Input Input power to the unit: 100-200VAC, 50 and 60Hz
Relay output ports 2 DO1, DO2 Connect to output relays 1 and 2
12VDC output 1 12V Power to external sensor (12VDC power)
Ground connector 1 GND 12VDC ground
Micro SD card slot 1 Micro SD Expand storage capacity with 2G, 4G or 8G Micro SD card
USB ports 2 USB1, USB2 Connect to a camera or a GPRS modem
Ethernet port, RJ45 1 ETH Connect to a 10/100 Ethernet port for Web access & SNMP connectivity
RJ45 sensor ports*
Digital input ports 3 DI1, DI2, DI3 Connect digital sensors (one sensor per port)—on/off, dry contact sensors such as smoke detectors and motion detectors
Liebert SN™ ports 2 Connect Liebert SN sensors for temperature, humidity and other conditions
* See Sensor Port Connections on page 3 for details on connecting sensors to RJ45 sensor ports (excluding Ethernet port).
Table 2 Indicator descriptions
Indicator Status of: Color Status - Indicator On / Flashing Status - Indicator Off
DO1, DO2 Relay outputs Yellow On Relay DO1 or DO2 is closed. Off Relay DO1 or DO2 is open.
POWER Input power Green On Input power is present. Off Input power is not present.
ALARM Alarms Red On An alarm has been detected. Off No alarms detected.
RUN Unit operation Green Flashing Unit is operating normally. Off Unit is not running.
FRONT OF UNIT
Power input
Relayoutput
ports
Groundconnector
Micro SD card slot
RJ45 sensorports
Ethernetport
Statusindicators
12VDCoutput
USB ports
DO1
DO2 Run
Power Alarm
Not Used Not Used
Not Used
DO1/DO2outputs
Run
Power Alarm
STATUS INDICATORS
3
Sensor Port ConnectionsThe Liebert RDU-S has five sensor ports—three digital input ports and two Liebert SN sensor ports.
Digital Input Ports DI1, DI2, DI3
The three digital input ports DI1, DI2 and DI3, shown at right, may be used to connect digital sensors, such as smoke detectors and motion detectors.
Liebert SN Sensor Ports
The two ports labeled with a Liebert SN icon , shown at right, are designed for use with Liebert SN sensors. Each sensor is shipped with a cable to connect to one of the Liebert SN ports on the Liebert RDU-S. You may use this cable or another standard straight-through cable.
Liebert SN sensors may be connected in a string up to 65.6 ft. (20m) in length. Each Liebert RDU-S unit can support a maximum of 10 temperature probes, 10 humidity probes, 9 dry contacts and 6 door switches.
Web InterfaceA Web interface allows users to browse and view areas monitored by connected sensors, as well as configure the unit.
Digital input portsDI1-3
Connect other end to sensor
Liebert SN ports
Connectone endof an RJ45 cable to a Liebert SN port
DEFAULT OPENING VIEWMonitor tab/Environmental subtab
TABLEVIEW
GRAPHVIEW
SN Temp1 SN Temp2 SN Temp3 SN Temp4 SN Hum1
SN Hum2
SN Temp4SN Temp3
SN Hum1SN Hum2
SN Temp1SN Temp2
4
© 2010 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-31315_REV0_07-10
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229
Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com
Specifications
Ordering Information
Input Power Requirements 100-240 VAC 50&60 Hz; 0.5A maximum draw
Dimensions W x D x H, in. (mm) 17.375 x 2.25 x 1.75 (441.3 x 57.2 x 44.5)
Unit Weight - lb. (kg) 2.34 (1.1)
Shipping Weight - lb. (kg) 2.875 (1.3)
Mounting 0U, 1U rack-mount, wall-mount or desktop
Ambient Operating Environment, °F (°C) 41 to 131 (5 to 55); 10-95% RH non-condensing
Communication
Network Interface HTTP (Web), E-mail, SNMP
Modem GPRS modem
Agency Listings FCC, UL and CE
LEDs Power, Run, Alarm and Digital Outputs
Liebert SN Sensor Ports 2
Temperature, °F (°C), with ranges -22 to 248 (-30 to 120)
Humidity with ranges 0 to 100% RH
Digital Input Ports 3
Contact closure Normally Open / Normally Closed
Digital outputs 5A 220VAC/24VDC
Quantity Part # Description
RDU-S Liebert RDU-S Rack Management Device
AD-IM Infrared Motion Sensor
AD-S Smoke Sensor, including Mounting Magnet & Mounting Bracket
AD-SUSBC Stationary USB Camera
AD-TPUSBC Tilt & Pan USB Camera, including Tilt & Pan USB Camera Mounting Bracket
AD-GPRSUSBM USB GPRS Modem
AD-RB Rack Beacon, including Mounting Magnet & Mounting Bracket
AD-MICROSD8 Liebert RDU-S Micro SD 8G
SN-T Modular Temperature Sensor
SN-TH Modular Temperature and Humidity Sensor
SN-2D Modular Door Contact Sensor
SN-3C Modular Contact Closure Sensor
SN-Z01 Integrated with Single Temperature Sensor
SN-Z02 Integrated with 3 Temperature Sensors
SN-Z03 Integrated with 3 Temperature Sensors and 1 Humidity Sensor