REGUPOL AMERICA 12 DOCUMENT CONTROL TEST DATE 06/30/19 ISSUE DATE 07/09/19 RECORD RETENTION END 06/30/23 REPORT NUMBER J8051.12-113-11-R0 PAGES ACOUSTICAL SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON CERAMIC TILE WITH REGUPOL SONUS UNDERLAYMENT - AMERIFORM NOCOM STRUCTURAL MAGNESIUM BOARD PERFORMANCE SPECIMEN TYPE 254 mm Steel C-Joist Assembly with Regupol® SonusClip™ Sound Isolation Clip and Two-Layer Ceiling TEST REPORT ATI 00629 (03/21/18) RTTDS-R-AMER-Test-2844 © 2017 INTERTEK
Transcript
  • REGUPOL AMERICA

    12

    DOCUMENT CONTROL

    TEST DATE06/30/19

    ISSUE DATE07/09/19

    RECORD RETENTION END 06/30/23

    REPORT NUMBERJ8051.12-113-11-R0

    PAGES

    ACOUSTICAL

    SCOPE OF WORK

    ASTM E90 AND ASTM E492 TESTING ON CERAMIC TILE WITH REGUPOL SONUS

    UNDERLAYMENT - AMERIFORM NOCOM STRUCTURAL MAGNESIUM BOARD

    PERFORMANCE

    SPECIMEN TYPE

    254 mm Steel C-Joist Assembly with Regupol® SonusClip™ Sound Isolation Clip and

    Two-Layer Ceiling

    TEST REPORT

    ATI 00629 (03/21/18)RTTDS-R-AMER-Test-2844© 2017 INTERTEK

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    SECTION 1SCOPE

    REPORT ISSUED TOREGUPOL AMERICA11 Ritter WayLebanon, Pennsylvania 17042

    Intertek Building & Construction (B&C) was contracted to perform testing in accordance with

    ASTM E90 AND ASTM E492 on Ceramic Tile with Regupol Sonus Underlayment - Ameriform

    NOCOM Structural Magnesium Board. This report is a reissue in the name of Regupol America

    through written authorization from the original report holder. Results obtained are tested

    values and were secured by using the designated test method(s). Testing was conducted in the

    VT test chambers at Intertek B&C located in York, Pennsylvania.

    SECTION 2SUMMARY OF TEST RESULTS

    DATA FILE NO.

    09/11/19

    STCIIC

    J8051.08

    6158

    SERIES/MODEL:Ceramic Tile with Regupol Sonus Underlayment - Ameriform NOCOM

    Structural Magnesium Board

    Engineer, Team Lead -

    Acoustical Testing

    COMPLETED BY:

    TITLE:

    SIGNATURE:DATE:

    Jordan Strybos

    DATE:

    This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek

    and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek

    assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or

    damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this

    report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of

    the tested material, product or service must first be approved in writing by Intertek. The observations and test

    results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material,

    product, or service is or has ever been under an Intertek certification program.

    09/11/19

    This report does not constitute certification of this product nor an opinion or endorsement by

    this laboratory.

    COMPLETED BY:

    TITLE:

    SIGNATURE:

    David M. Dacheux IIITechnician - Acoustical

    Testing

    Version: 09/19/17This page alone is not a complete report.

    Page 2 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    The full test specimen was assembled on the day of testing by B&C. All materials provided by

    the original client were installed on an existing B&C assembly (254 mm Steel C-Joist Assembly

    with Regupol® SonusClip™ Sound Isolation Clip and Two-Layer Ceiling) utilizing B&C-supplied

    materials. The assembly was installed in a steel test frame which was installed into the

    opening between the source and receive rooms in the test chamber. The test frame was

    isolated from the structure with dense neoprene gasket.

    SECTION 3

    The specimen was evaluated in accordance with the following:

    This report is reissued in the name of Regupol America through written authorization from the

    original report holder. The original Report No. is J8051.08-113-11.

    B&C will service this report for the entire test record retention period. Test records, such as

    detailed drawings, datasheets, representative samples of test specimens, or other pertinent

    project documentation, will be retained by B&C for the entire test record retention period.

    TEST METHODS

    The total weight of the floor/ceiling assembly was 796.7 kg. B&C will store samples of the test

    specimen for four years. Photographs of the test specimen are included in the report. The

    client did not supply drawings of the test specimen.

    MATERIAL SOURCE/INSTALLATION

    Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

    SECTION 4

    ASTM E492-09(2016)e1, Standard Test Method for Laboratory Measurement of

    ASTM E413-16, Classification for Rating Sound Insulation

    ASTM E90-09 (2016), Standard Test Method for Laboratory Measurement ofAirborne Sound Transmission Loss of Building Partitions

    ASTM E989-18, Classification for Determination of Impact Insulation Class (IIC)

    ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates forUse in Sound Insulation Test Methods

    Version: 09/19/17This page alone is not a complete report.

    Page 3 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    *

    *

    *

    Intertek B&CSeth J. Allen

    * The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

    INSTRUMENT MANUFACTURER MODEL DESCRIPTION

    SECTION 5EQUIPMENT

    156.8 m³

    190 m³

    COMPANYIntertek B&C

    NAMEMichael K. Daniel

    LIST OF OFFICIAL OBSERVERSSECTION 6

    VT RECEIVE ROOM VOLUME

    VT SOURCE ROOM VOLUME

    ASSET # CAL DATE

    Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card INT00977 08/18

    Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card 65124 05/18

    Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card 63763-1 06/18

    Microphone Calibrator Larson Davis CAL200 Acoustical Calibrator INT00852 09/18

    Receive Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 63741 04/19

    Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63739 04/19

    Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 67340 04/19

    Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63746 09/18

    Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63747 07/18

    Receive Room Environmental

    IndicatorComet T7510

    Temperature and Humidity

    Transmitter

    63810 10/18

    63811 10/18

    Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 65029 03/19

    Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 65586 02/19

    Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier INT01089 01/19

    Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier INT00652 01/19

    Source Room Microphone PCB Electronics 378C20 Microphone and Preamplifier 63742 03/19

    INT00936 12/18

    T7510Temperature and Humidity

    Transmitter63812 10/18

    Source Room Environmental

    IndicatorComet

    Tapping Machine Norsonic Nor277 Tapping Machine

    Version: 09/19/17This page alone is not a complete report.

    Page 4 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    The microphones were calibrated before conducting the tests. The air temperature and

    relative humidity conditions were monitored and recorded during all measurements. The

    average temperature and humidity of both the source and received rooms are listed in

    Sections 10 and 11. The maximum and minimum temperatures and humidities of the receive

    room from the duration of the test are listed in Sections 12 and 13.

    The airborne transmission loss test was conducted in accordance with the ASTM E90 test

    method using the single direction method. Two background noise sound pressure level and

    five sound absorption measurements were conducted at each of five microphone positions.

    Two sound pressure level measurements were made simultaneously in both rooms, at each of

    five microphone positions.

    The impact sound transmission test was conducted in accordance with the ASTM E492 test

    method. Two background noise sound pressure level, two sound pressure level measurements

    with the tapping machine operating at each position specified by ASTM E492, and five sound

    absorption measurements were conducted at each of five microphone positions.

    SECTION 8TEST CALCULATIONS

    The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated in

    accordance with ASTM E413 and ASTM E989, respectively.

    Detailed test procedures, data for flanking limit tests, repeatability measurements, and

    reference specimen tests are available upon request.

    TEST PROCEDURESECTION 7

    Version: 09/19/17This page alone is not a complete report.

    Page 5 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    1219 by 3023 15.9USG SHEETROCK® Brand

    FIRECODE® C Core10.98 m²

    Gypsum Panel

    11.91 kg/m²

    Note: Fastened to the channels on 305 mm centers with 41.3 mm Type S bugle head screws. The

    seams of the gypsum panels were sealed with Pecora AC-20 FTR caulk and covered with pressure

    sensitive tape.

    Note: Installed into the isolation clips, spaced 610 mm on center

    Gypsum Panel

    1219 by 3023 15.9USG SHEETROCK® Brand

    FIRECODE® C Core10.98 m² 11.91 kg/m²

    Note: Fastened to the channels on 305 mm centers with 25.4 mm Type S bugle head screws. The

    seams of the gypsum panels were sealed with Pecora AC-20 FTR caulk and covered with pressure

    sensitive tape.

    Furring/Hat

    Channel

    3658 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

    Note: Installed on 610 mm centers using JUS414 hanger brackets

    Note: Installed in a 610 mm by 1219 mm grid pattern

    3023 by 41.3 254.0

    19.2 Ameriform NOCOM

    31.8 Regupol® SonusClip™ 24 clips 0.06 kg/clip

    88.9

    ClarkDietrich S162

    10.98 m² 1.03 kg/m²

    TEST SPECIMEN DESCRIPTION

    Knauf EcoBatt®

    6 joists 11.6 kg/joist

    Fiberglass

    Insulation

    2940 by 406

    10.98 m²

    Note: Fastened to the floor joists with 41 mm #8 screws spaced on 152.4 mm centers along the

    perimiter and on 406.4 mm centers in the field

    Note: Laid directly over resilient channels

    1219 by 2438 19.82 kg/m²

    SECTION 9

    5.0 Regupol Sonus 10.98 m²

    Note: Loose laid

    4.3 kg/m²

    Structural

    Magnesium

    Board

    Steel C-Joist

    Daltile8.0304.8 by 304.8

    Rubber

    Underlayment

    3048 by 1219

    Note: Keracolor Sanded Tile Grout was placed into the 6.35 mm joints between the ceramic tile

    and wiped clean. The ceramic tile was placed with light pressure onto a bed of MAPEI mortar

    meeting ANSI A118.11 and A118.15. The mortar was set using a 19 mm by 10 mm by 14 mm

    trowel. Both the grout and mortar were allowed to cure to manufacturer's specifications.

    Resilient Sound

    Isolation Clip

    76.2 by 36.5

    DIMENSIONS

    (mm)

    THICKNESS

    (mm)

    MANUFACTURER AND

    SERIESQUANTITY

    AVERAGE

    WEIGHT

    15.87 kg/m²10.98 m²

    Ceramic Tile

    MATERIAL

    Version: 09/19/17This page alone is not a complete report.

    Page 6 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    102

    102

    96

    95

    90

    40

    9.4

    10.6

    11.2

    10.4

    103

    101

    102

    10.5

    11.3

    12.3

    22.2

    0.9

    0.5

    0.4

    0.6

    0.6

    0.4

    31

    29

    41

    12

    7

    0.4

    0.6

    0.6

    0.9

    37

    34

    0.8

    0.7

    26

    16

    76

    79

    10.6

    STC Rating 61

    102

    9.1

    11.5

    13.7

    11.6

    1038.9

    9.8

    Notes:

    21.7

    10000

    22.4

    18.0

    18.8

    15.0

    8.8

    10.7

    18.9

    14.9

    10.0

    500

    80

    11.5

    28.9

    18.0

    2500

    3150

    2000

    6300

    73

    10.9

    315

    400

    1000

    1250

    1600

    630

    800

    24.6

    100

    125

    160

    102200

    31.9

    33.1

    250

    21.9

    21.6

    22.3

    101

    39

    105

    103

    105

    63

    72

    0

    8000

    4000

    5000

    11.3

    81 -

    103 60 2

    47

    47

    102

    102

    103

    0

    0

    67

    68

    22.2 -

    14.1

    17.2

    82

    95%

    CONFIDENCE

    39

    55

    56

    58

    0.9

    0.5

    1.9

    1.3

    106

    43

    2

    62

    62

    1

    0.6

    0.5103

    1.5

    -

    -

    45

    42

    64

    65

    0.5

    1

    0

    0

    SPL

    (dB)

    Receive Temp.

    (dB) (dB)

    TL

    LIMIT

    DATA FILE NO.

    CLIENT

    SPECIMENRECEIVE

    58%Receive Humidity

    DESCRIPTION

    Source Temp.

    Source Humidity

    BACKGROUND

    TEST DATE

    (Hz)

    MKD

    SPL

    10.98 m²

    SOURCE

    m²(dB)

    6435.2 2.0107

    45 1.6

    OF

    DEFICIENCIES

    2

    42

    SPL

    -

    -

    56

    3

    4

    3

    4

    FREQ

    Sum of Deficiencies(Sound Transmission Class)

    NUMBER

    1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    2) Specimen TL levels listed in red are potentially limited by the laboratory flanking limit.

    3) Specimen TL levels listed in blue indicate the lower limit of the transmission loss.

    4) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

    28

    J8051.08

    Regupol America

    9.1

    66

    61

    SECTION 10TEST RESULTS - AIRBORNE SOUND TRANSMISSION LOSS

    6/30/2019

    8 mm Daltile Ceramic Tile, 5 mm Regupol Sonus Rubber Underlayment, 19.2 mm Ameriform NOCOM Structural

    Magnesium Board, 88.9 mm Knauf EcoBatt® Fiberglass Insulation, 254 mm ClarkDietrich S162 Steel C-Joist, 31.75 mm

    Regupol® SonusClip™ Resilient Sound Isolation Clip, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9

    mm USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel, 15.9 mm USG SHEETROCK® Brand FIRECODE® C Core

    Gypsum Panel

    SPECIMEN AREA 20.8°C

    TECHNICIAN

    20.4°C

    8.8

    ABSORPTION

    8.9

    8.6

    58%

    52

    51

    48

    4

    2

    50

    Version: 09/19/17This page alone is not a complete report.

    Page 7 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    DATA FILE NO.

    DESCRIPTION

    Source Temp.Receive Temp.

    Regupol America

    58%Receive Humidity

    20.4°C

    58% Source Humidity

    10.98 m²SPECIMEN AREA

    SECTION 11

    20.8°C

    TECHNICIAN MKD

    J8051.08

    CLIENT

    TEST RESULTS - AIRBORNE SOUND TRANSMISSION LOSS GRAPH

    TEST DATE 6/30/2019

    8 mm Daltile Ceramic Tile, 5 mm Regupol Sonus Rubber Underlayment, 19.2 mm Ameriform NOCOM Structural

    Magnesium Board, 88.9 mm Knauf EcoBatt® Fiberglass Insulation, 254 mm ClarkDietrich S162 Steel C-Joist, 31.75 mm

    Regupol® SonusClip™ Resilient Sound Isolation Clip, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9

    mm USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel, 15.9 mm USG SHEETROCK® Brand FIRECODE® C Core

    Gypsum Panel

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    1000

    2000

    4000

    8000

    Sou

    nd

    Tra

    nsm

    issi

    on

    Lo

    ss (

    dB

    re:

    20

    mP

    a)

    Frequency (Hz)

    Airborne Sound Transmission Loss

    Specimen TL

    Contour Curve

    Version: 09/19/17This page alone is not a complete report.

    Page 8 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    800 21.8

    Max. Humidity

    SPL

    5000 6.2

    (Hz)

    250 21.7

    9.7

    1250

    Regupol America

    DESCRIPTION

    TECHNICIAN

    20.6°CSPECIMEN AREA

    FREQBACKGROUND

    8 mm Daltile Ceramic Tile, 5 mm Regupol Sonus Rubber Underlayment, 19.2 mm Ameriform NOCOM Structural

    Magnesium Board, 88.9 mm Knauf EcoBatt® Fiberglass Insulation, 254 mm ClarkDietrich S162 Steel C-Joist, 31.75 mm

    Regupol® SonusClip™ Resilient Sound Isolation Clip, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9

    mm USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel, 15.9 mm USG SHEETROCK® Brand FIRECODE® C Core

    Gypsum Panel

    TEST DATE 6/30/2019

    SECTION 12TEST RESULTS - IMPACT SOUND TRANSMISSION

    (dB)

    DATA FILE NO. J8051.08

    CLIENT

    MKD

    11.7

    500 17.3

    10.98 m² Maximum Temp.

    18.4

    58%

    ABSORPTIONNUMBER

    17.4

    315

    80 35.5

    200 24.8

    125 32.2

    160 33.0

    100 28.6

    21.3

    17.9

    1000 20.4

    630 23.7

    400

    2500 8.5

    2000 11.5

    1600 12.3

    6300 6.4

    4000 6.8

    3150 7.5

    IIC Rating 58

    22.410000 7.1

    8000 6.7

    OF

    m² DEFICIENCIES

    59% Min. Humidity

    10.4

    Minimum Temp. 20.2°C

    2

    3

    -

    15.5 3

    58

    57

    56

    57

    4

    10.3 10.3

    3

    10.9

    57

    58

    55

    9.9

    355 0.3

    9.5 20.555

    8.5

    9.0 151 0.2

    8.8 354 0.2

    1

    8.8 0

    9.0 049 0.3

    8.8 47

    43

    12.5 -

    11.3 0

    0

    10.4 0

    39

    32

    26

    17.2 -9 0.3

    14.2 -15 0.6

    26

    9 0.4

    22.4 -9 0.3

    Notes: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    NORMALIZED IMPACT SPL

    (dB)

    95%

    CONFIDENCE

    LIMIT

    -

    (Impact Insulation Class) Sum of Deficiencies

    20

    1.3

    1.3

    1.7

    1.1

    0.5

    0.7

    0.3

    0.3

    0.3

    0.2

    0.3

    0.4

    Version: 09/19/17This page alone is not a complete report.

    Page 9 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    SECTION 13TEST RESULTS - IMPACT SOUND TRANSMISSION GRAPH

    TEST DATE 6/30/2019

    DATA FILE NO. J8051.08

    59%

    CLIENT Regupol America

    DESCRIPTION

    SPECIMEN AREA 20.2°C

    TECHNICIAN MKD Max. Humidity Min. Humidity 58%

    8 mm Daltile Ceramic Tile, 5 mm Regupol Sonus Rubber Underlayment, 19.2 mm Ameriform NOCOM Structural

    Magnesium Board, 88.9 mm Knauf EcoBatt® Fiberglass Insulation, 254 mm ClarkDietrich S162 Steel C-Joist, 31.75 mm

    Regupol® SonusClip™ Resilient Sound Isolation Clip, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9

    mm USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel, 15.9 mm USG SHEETROCK® Brand FIRECODE® C Core

    Gypsum Panel

    10.98 m² Maximum Temp. 20.6°C Minimum Temp.

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    1100

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    1000

    2000

    4000

    8000

    Imp

    act

    Insu

    lati

    on

    Cla

    ss (

    IIC

    )

    Sou

    nd

    Pre

    ssu

    re L

    eve

    l (d

    B r

    e: 2

    0 m

    Pa)

    Frequency (Hz)

    Impact Sound Transmission

    Normalized Impact SPL

    Contour Curve

    Version: 09/19/17This page alone is not a complete report.

    Page 10 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    Receive Room View of Test Specimen Installation

    Photo No. 2

    SECTION 14

    Photo No. 1

    Source Room View of Test Specimen Installation

    PHOTOGRAPHS

    Version: 09/19/17This page alone is not a complete report.

    Page 11 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building

  • 130 Derry Court

    Facsimile:

    TEST REPORT FOR REGUPOL AMERICAReport No.: J8051.12-113-11-R0

    717-764-7700

    York, PA 17406

    Telephone: 717-764-4129

    www.intertek.com/building

    Date: 09/11/19

    DATE

    07/09/19

    PAGES

    N/A

    DESCRIPTIONOriginal Report Issue - Reissue of Report No.

    J8051.08-113-11 in the name of Regupol

    America.

    SECTION 15REVISION LOG

    REVISION #

    R0

    Version: 09/19/17This page alone is not a complete report.

    Page 12 of 12 RTTDS-R-AMER-Test-2844

    http://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/buildinghttp://www.intertek.com/building