+ All Categories
Home > Documents > RPC2 Communications Module User Manual

RPC2 Communications Module User Manual

Date post: 27-Jan-2017
Category:
Upload: nguyenkhue
View: 281 times
Download: 7 times
Share this document with a friend
59
RPC2™ Communications Module Network Interface Card for the Rack PDU Family of Power Distribution Products Installer/User Guide
Transcript
Page 1: RPC2 Communications Module User Manual

RPC2™ Communications Module

Network Interface Card for the Rack PDU Family of PowerDistribution Products

Installer/User Guide

Page 2: RPC2 Communications Module User Manual

Technical Support Site

If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see ifthe issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/.

Page 3: RPC2 Communications Module User Manual

TABLE OF CONTENTS

1 Introduction 11.1 Features and Benefits 1

2 Installation and Configuration 32.1 Getting Started 3

2.1.1 Required cables 3

2.2 RPC2 Communications Module Ports 4

2.3 Monitoring and Configuration Overview 4

2.3.1 Vertiv™ Rack PDU monitoring structure 4

2.3.2 Rack PDU component ID 5

2.4 Creating a Rack PDU Array 5

2.5 Configuring an RPC2 Communications Module for Static IP 6

2.6 User Level Privileges 7

2.6.1 Using passwords 7

2.6.2 Group membership and access 7

2.7 Reboot and Reset to Factory Defaults 8

3 Accessing an RPC2 Communications Module via the Web Interface 93.1 Web Interface Overview for Administrators 9

3.2 RPC2 Communications Module Icons 9

3.3 Summary Tab 10

3.3.1 Recent events 11

3.4 PDU Explorer Tab 11

3.4.1 Measurements 12

3.4.2 Status 12

3.4.3 Settings tab 13

3.4.4 Branch settings 13

3.4.5 Receptacle settings 14

3.4.6 Sensors 16

3.4.7 Information 17

3.5 Device Explorer 17

3.5.1 Device Explorer - receptacle groups 20

3.6 Events Tab 20

3.7 System Tab 21

3.7.1 Support 21

3.7.2 Devices 22

3.7.3 Device change 22

3.7.4 Firmware update 22

3.7.5 Settings 22

3.7.6 Authentication 30

3.7.7 Authorization levels 32

4 RPC BDM™ (Optional) 354.1 Orientation of the RPC BDM 35

4.1.1 Navigation Tips 35

4.2 RPC BDM™ Installation 36

4.2.1 Set the IP address for the RPC2 communications module 37

4.2.2 Connect the RPC BDM to the RPC2 communications module 37

4.3 Placement of the RPC BDM™ 37

4.4 RPC BDM Operation 37

Vertiv | RPC2™ Communications Module Installer/User Guide | i

Page 4: RPC2 Communications Module User Manual

4.4.1 PDU level 38

4.4.2 RPC BDM contrast 40

4.4.3 Active alarms 41

4.4.4 Sensors 41

4.4.5 Types of data available at PDU, branch and receptacle levels 44

4.4.6 Viewing active events 44

5 Liebert® SN™ Sensor Installation (Optional) 455.1 Record the Sensor Address 45

5.2 Mount the Sensor 45

5.3 Connect the Sensor 45

5.4 Confirm the Module Change 46

6 Appendices 47Appendix A: Specifications 47

Appendix B: Troubleshooting 48

Appendix C: Factory Default Settings 50

Vertiv | RPC2™ Communications Module Installer/User Guide | ii

Page 5: RPC2 Communications Module User Manual

1 INTRODUCTIONThe Rack PDU Card (RPC2™) Communications Module provides network connectivity to the Vertiv™ rack PDU family ofproducts.

The RPC2™ communications module allows you to monitor the components connected to the rack PDU using various tools,including the module's web user interface and optional units, the Basic Display Module (BDM) device and Liebert® SN™sensor. The handheld display, the RPC BDM, allows you to view monitored data and the Liebert® SN™ is a sensor that canbe connected to rack PDUs to monitor temperature, humidity, door contacts and digital inputs.

The RPC2™ is factory installed in managed versions of the Vertiv™ MPH2™ Rack PDUs. It can be field-installed in Vertiv™MPH™ and MPX™ rack PDUs to provide network monitoring and control capabilities. The communications module isfactory set for service in DHCP-based applications. It can be configured for static IP applications.

In this guide, you will find sections dedicated to explaining how to use the web interface, as well as the optional devices.These devices, used in conjunction with the RPC2™ communications module, give you easy access to the data from the rackPDUs.

1.1 Features and Benefits

The RPC2™ communications module offers the following benefits and features for network connectivity to the family ofVertiv™rack PDU products:

• Interoperability - Integrates network management of the MPH™ rack PDU family and environmental sensorswith a local display interface. This ensures consistency of information available to both remote and local users— those in the data center — thus reducing mistakes during commission/decommission.

• Cable standardization - Uses standard cables. The LAN port is compatible with 1 Gbps Ethernet speeds withthe recommended CAT5E or CAT6 Ethernet cabling. The USB port connection uses standard USB cabling.

• Consolidation of IP addresses - Can be used to create a rack PDU array by interconnecting multiple MPH2Rack PDUs to minimize the number of IP addresses, consolidate monitoring and reduce overhead. The LANport is compatible with 1 Gbps Ethernet speeds with the recommended CAT5E or CAT6 Ethernet cabling. TheUSB port connection uses standard USB cabling.

• Receptacle group control - Enables grouping receptacles to apply the same action to all receptacles in thegroup with one operation. It also permits monitoring and management of receptacle groups through LiebertNform™ software.

• MPH2™ Rack PDU power conditioning monitoring - Enables monitoring of the Vertiv™ MPH2™, MPX™ andMPH™ rack PDUs. It provides rack PDU receptacle voltage and current draw, provides load-balancingcapability and monitors rack environmental conditions.

• Energy metering - Reports power consumption (kWh) at the PDU, branch and receptacle levels as calculatedby the MPH2™ rack PDUs circuitry.

• Receptacle load control - Interface permits controlling the power-up/wake-up state and sequencing ofreceptacles.

• Local display support - Provides an interface for a display option, the RPC BDM, to facilitate installation andlocal troubleshooting of interconnected MPH™ rack PDUs. The display may be user-mounted on or near racksfor optimal placement and viewing.

• Receptacle load control - Sends comprehensive event notifications via Simple Network Management Protocol(SNMP), e-mail, SMS text messages and cellular paging. It also provides notification status via a web page.

• MPH2 Rack PDU management - Used to interact with a rack PDU by referencing the user-assigned receptaclelabels or loads.

• Wide range of IT network capabilities - Provides a flexible set of IT networking capabilities, including DHCP,BOOTP, DNS, Simple Network Time Protocol (SNTP) and SNMP.

• Hot swappable - May be removed and reinserted without interrupting power from the rack PDU or affectingthe connected load.

• Flash upgradeable firmware - Enables the user to easily update the firmware as new features and capabilitiesbecome available.

• Web support - Delivers web management and control to Vertiv™ rack PDUs. All authorized users will be able toview status information on their network.

Vertiv | RPC2™ Communications Module Installer/User Guide | 1

Page 6: RPC2 Communications Module User Manual

• SNMP support - Enables SNMP management of Vertiv™ rack PDUs. To integrate the card into an SNMPimplementation, compile the Liebert® Global Products MIB on the Network Management System (NMS). Visitwww.Liebert.com to download the Liebert Global Products MIB.

• Liebert Nform® - Utilizing the SNMP and web technologies built into the RPC2 communications module,Liebert Nform centrally manages event notifications, accesses critical system information and manages thepower delivered to the connected load. Download the online edition at www.nform.liebert.com.

• Liebert SiteScan Web® - Integrates with Liebert SiteScan web software to monitor and analyze trends toensure high availability operation of critical facilities. Visit www.sitescan.liebert.com for more information on theLiebert SiteScan web.

• Monitoring and configuration overview - Vertiv™ rack PDUs are managed at three levels:

• At the rack PDU level, it provides aggregate input power monitoring of the rack PDU.

• At the branch level, it provides status information, including branch circuit breaker on some models, andaggregate power monitoring of branch receptacles.

• At the receptacle level, it provides status information and power monitoring of a single receptacle onsome models.

Vertiv | RPC2™ Communications Module Installer/User Guide | 2

Page 7: RPC2 Communications Module User Manual

2 INSTALLATION AND CONFIGURATIONThe following sections are provided to install and configure your RPC2 communications module.

2.1 Getting Started

The RPC2 communications module is factory installed on Vertiv® rack PDUs. If the module is being field-installed, see thefollowing section, Required cables, to ensure you have all the necessary items for proper installation.

Installation and utilization of the RPC2 module is identical for vertical and horizontal rack PDUs. The following figure showsan RPC2 module installed in a vertical MPH2™ rack PDU.

Figure 2.1 RPC2 Communications Module Configuration

ITEM DESCRIPTION

1 RPC2Communications Module

2 Additional MPH2Rack PDUs configured in an array

3 Sensor

4 Console server of switch

5 Basic Display Module (BDM)

6 Network

Table 2.1 RPC2 Communicatons Module Configuration Descriptions

2.1.1 Required cables

The following cables are not included but are necessary for RPC2 communications module functionality:

• RJ45 cable for connection to the serial port

• RJ45/DB9F adaptor or equivalent is required to connect to Avocent™ appliances.

• RJ45 CAT5E or CAT6 Ethernet cable for the network port connection

• RJ45 CAT5 or better Ethernet cable for the link port connection

Vertiv | RPC2™ Communications Module Installer/User Guide | 3

Page 8: RPC2 Communications Module User Manual

NOTE: Liebert 1-wire sensors and the local display, the RPC BDM, come with their own cables.

Field installation of an RPC2 communications module

Locate the communications card bay on the rack PDU and insert the RPC2 communications module into the card bay.Secure it with the captive thumb screws.

2.2 RPC2 Communications Module Ports

The module has six ports designated by icons. The following figure shows each port with its icon underneath it.

Figure 2.2 RPC2 Communications Module Ports

ITEM PORT DESCRIPTION

1 Serial Used for RS232 serial communication using the Command Line Interface (CLI).

2 USB Micro-AB Used for USB applications.

3 Sensor Used to plug in optional sensor accessories.

4 Display Used to plug in the RPC BDM (Basic Display Module).

5 Link

Used for: 

• Local configuration through interconnection to a computer.

• Creating a rack PDU array by interconnecting additional rack PDUs.

6 Network

Used for: 

• Plugging in the Local Area Network (LAN) via an Ethernet cable (not included).

• Creating a rack PDU array by interconneting additional rack PDUs.

7 Reset button access hole Used to reboot or reset themodule to its factory default settings.

Table 2.2 RPC Communications Module Ports Descriptions

To connect themodule to your network:

Connect one end of an Ethernet cable (not included) to the network port and the other end to the network.

2.3 Monitoring and Configuration Overview

The following sections outline how rack PDUs are configured and managed.

2.3.1 Vertiv™ Rack PDU monitoring structure

Vertiv™rack PDUs are managed at three levels:

• Rack PDU Level - provides aggregate input power monitoring of rack PDUs.

• Branch Level - provides status information of a branch circuit breaker and aggregate power monitoring ofbranch receptacles.

Vertiv | RPC2™ Communications Module Installer/User Guide | 4

Page 9: RPC2 Communications Module User Manual

• Receptacle Level - provides status information and power monitoring of each receptacle (available on certainmodels of the Vertiv® MPH2™ and MPX™ rack PDUs).

2.3.2 Rack PDU component ID

An alphanumeric ID consisting of up to three parts helps you identify components when displayed on the web interface orthe RPC BDM device. The component ID uses the format PDU-Branch-Receptacle. For example, the component ID 1-A-3identifies PDU1, Branch A and Receptacle 3.

NOTE: MPH2™ rack PDUs use alphabetical characters to designate a branch whereas MPX™ and MPH™ rack PDUsuse numerical characters. So Branch A on an MPH2™ PDU is effectively Branch 1 on an MPX™ or MPH™ PDU.

Figure 2.3 MPH2™ Branch and Receptacle Labeling Example

ITEM DESCRIPTION

1 Letters displaying the branch level.

2 Numbers displaying the receptacle level.

Table 2.3 Rack Component ID Descriptions

2.4 Creating a Rack PDU Array

Up to four MPH2 or Liebert MPX rack PDUs may be integrated into a rack PDU array, which permits central control andmonitoring of each rack PDU through a single web interface. Each rack PDU must have an RPC2 communications moduleinstalled.

NOTE: Creating a Rack PDU array does not require rebooting or powering off either the MPH2 rack PDUs or theconnected load. The level of monitoring and control depends on the model of rack PDU.

To set up a rack PDU array:

1. Log in with the required privileges.

2. Connect an Ethernet cable from a computer or network switch to the Network port of the master RPC2communications module.

3. Connect an Ethernet cable to the Link port of the master RPC2 communications module.

4. Connect the other end of the Ethernet cable to the network port of a slave RPC2 communications module on asecond MPH2. This RPC2 module is a sibling unit, accessible through the master RPC2 module.

NOTE: The RPC2 module connected to the LAN is the master and is positioned first in the rack PDU array.

5. The second RPC2 communications module automatically detects the connections and is discovered as asibling unit.

NOTE: If the sibling order needs to be changed, disconnect the cabling for 30 seconds and then reconnect in thedesired sequence. You do not need to reboot or power cycle the module.

6. Connect additional RPC2 communications modules as shown in the following figure. The Ethernet cableattaches from the link port of an RPC2 module that has been added to the array to the next module’s networkport. Each newly added module is discovered as the next sibling.

Vertiv | RPC2™ Communications Module Installer/User Guide | 5

Page 10: RPC2 Communications Module User Manual

Figure 2.4 Rack PDU Array Example

ITEM DESCRIPTION

1 RPC2 communications module in master rack PDU.

2 RPC2 communications modules in sibling rack PDUs.

3 Network connection.

4 Ethernet cable between Link port and Network port, connecting rack PDUs.

Table 2.4 Rack PDU Array Example Descriptions

IP ADDRESS RACK PDU 1 RACK PDU 2 RACK PDU 3 RACK PDU 4

Link Port 192.168.1.10 192.168.1.6 192.168.1.2 192.168.1.14

Network Port User Determined 192.168.1.9 192.168.1.5 192.168.1.1

Subnet Mask 255.255.255.252 255.255.255.252 255.255.255.252 255.255.255.252

Table 2.5 IP Addresses In A Rack PDU Array

2.5 Configuring an RPC2 Communications Module for Static IP

The RPC2 communications module is factory set for DHCP, making it ready for service immediately. The module can beconfigured for operation on a network using a static IP address.

To configure amodule for a network that uses static IP:

1. Connect an Ethernet cable (not included) to the module’s link port (see Figure 1.1).

NOTE: The card’s Link port should be used only for local configuration through interconnection to a laptop. Do notconnect the cable from the Link port to your company LAN.

2. Connect the other end of the Ethernet cable to a laptop.

3. Configure the laptop’s IP settings to communicate on a 192.168.1.X network with the following settings: 

• IP address: 192.168.1.9

• Subnet mask: 255.255.255.252

• Default gateway: 192.168.1.1

4. Open a web browser and enter the proper IP address. See the following table for a list of static IP addresses.

DEVICE RACK PDU 1 RACK PDU 2 RACK PDU 3 RACK PDU 4

Laptop Computer 192.168.1.9 192.168.1.5 192.168.1.1 192.168.1.13

Table 2.6 Static IP Settings for the RPC2 Communications Module Through the Link Port

Vertiv | RPC2™ Communications Module Installer/User Guide | 6

Page 11: RPC2 Communications Module User Manual

DEVICE RACK PDU 1 RACK PDU 2 RACK PDU 3 RACK PDU 4

Link Port 192.168.1.10 192.168.1.6 192.168.1.2 192.168.1.14

Subnet Mask 255.255.255.252 255.255.255.252 255.255.255.252 255.255.255.252

NOTE: The RPC2 communications module configures sibling connections automatically but must be rebooted if theconnection order is changed. For information about sibling connections, see "Creating a Rack PDU Array" on page 5.

5. Enter admin for both the login and password, then click the Login icon or press Enter.6. Click the System tab, then click Settings - Network in the navigation tree.

7. Click the Edit icon in the right pane.

8. (Optional) The default Speed/Duplex for the Ethernet port is Auto 1000 Mbs/Full Duplex (automatic). Use theSpeed/Duplex drop-down menu to change this.

9. Enter the hostname in the Host Name field.

10. Select Static for the IPV4 Boot Mode and enter the IP Address, Subnet Mask and Default Gateway in theproper fields. See your network administrator for these settings.

-or-

Select Static for the IPV6 Boot Mode and enter the Subnet Prefix Length and Default Gateway in the properfields.

11. Click the Save icon when finished and click the Reboot icon to restart the module.

2.6 User Level Privileges

The user interface’s appearance is different for each user level.

The RPC2 communications module provides four user levels:

• Administrator - configures and controls all rack PDUs in the system

• Poweruser - configures rack PDUs; no receptacle control

• Appliance - configured through the serial command line interface (CLI) when connected to an Avocentappliance

• User - can view rack PDUs specified by the administrator; no receptacle control

NOTE: It is recommended you change the password immediately to prevent unauthorized access to MPH2 rack PDUs.

2.6.1 Using passwords

Access to the RPC2 communications module requires entering a username and password that are case sensitive. Thedefault administrator level username and password is admin.

To change an administrator's password: 

1. Open a web browser and enter the IP address of the RPC2 communications module.

2. Log in with the default username admin and the default password admin, or enter the previous administratorcredentials.

3. Click the System tab, then click Authorization - Change Password.

4. Enter the new username and password, then confirm the new password.

5. Click the Save icon to make the change or click the Cancel icon to discard the changes.

2.6.2 Group membership and access

Adding a user to a default group automatically sets the user’s access. For example, adding a user to the User group permitsthat user to view his/her receptacles only, but does not allow the user to configure systems settings and manage otherreceptacles. See "Authorization levels" on page 32.

Vertiv | RPC2™ Communications Module Installer/User Guide | 7

Annotation [DD]I don't see an Edit icon. Should this come out?
Page 12: RPC2 Communications Module User Manual

2.7 Reboot and Reset to Factory Defaults

Restarting the RPC2 module can consist of a reboot of the system or a reset to factory defaults. To highlight the difference, areboot may be required after network or configuration changes. In contrast, performing a reset to factory defaults reverts allconfiguration parameters to the original default state. The module can be rebooted manually on the module through theMPH2 rack PDU's LCD or via the module's reset button or web interface. To locate the reset button access hole on themodule, see "RPC2 Communications Module Ports" on page 4 for an illustration of the module.

Tomanually reboot themodule: 

Press the reset button once, holding it down for one second. After a short time, the network port status lights turn off briefly,indicating the module is restarting.

Tomanually reset to factory defaults:

Press the reset button five times, one second apart. After a short time, the network port status lights turn off briefly,indicating the module is restarting.

NOTE: Use a paper clip to press the reset button.

To reboot from themodule's web interface:

1. From the side navigation tree of the System tab, click Settings.

2. Click the Reboot icon, then press OK to confirm the reboot.

NOTE: The Reboot icon appears on any System tab window where a reboot is required.

To reboot from the on-board LCD:

1. Use the arrow keys to highlight the Information icon and press the Select key.

2. Use an arrow key to highlight Reboot and press the Select key.

3. Use the arrow keys to highlight an up or down arrow on the bottom-left and press the Select key to highlightReboot.

4. Use the arrow keys to highlight the Play button and press the Select key.

5. At the confirmation screen, use the arrow keys to highlight the up or down arrow, and press the Select key tohighlight Yes/Reboot Now, then press the Select key to reboot the system.

To reset to factory defaults from the on-board LCD:

NOTE: The LCD screen reset to factory default is only available for the MPH2 rack PDU. If you are using an RPC2installed in an MPH or MPX rack PDU, you can only perform a reset to factory defaults using the recessed resetbutton on the module.

1. Use the arrow keys to highlight the Information icon and press the Select key.

2. Use an arrow key to highlight the Reboot/Restore-Defaults icon and press the Select key.

3. Use the arrow keys to highlight an up or down arrow on the bottom-left and press the Select key to highlightRestore Defaults.

4. Use the arrow keys to highlight the Play button and press the Select key.

5. At the confirmation screen, use the arrow keys to highlight the up or down arrow, and press the Select key tohighlight Yes/Reboot to Default, then press the Select key to restore the system default settings.

Vertiv | RPC2™ Communications Module Installer/User Guide | 8

Page 13: RPC2 Communications Module User Manual

3 ACCESSING AN RPC2 COMMUNICATIONS MODULE VIA THE WEBINTERFACEThe RPC2 communications module can be accessed with a web browser once it is connected to a network. The browserobtains direct access to the RPC2 module via a graphical user interface. The data and view varies according to the type ofrack PDU being viewed through the RPC2 module.

3.1 Web Interface Overview for Administrators

To log in to the web interface:

1. Open a web browser and enter the IP address of the rack PDU.

2. Log in as an administrator and press Enter to open the web interface.

Figure 3.1 Web Interface Window

ITEM AREA DESCRIPTION

1 Tab barDisplays the Summary, PDU Explorer, Device Explorer, Events and Systems tabs. The available tabschange based on user rights.

2 Side Navigation TreeMenu options for configuration, viewing of system information and access to devices. The options changebased on user rights. When the Summary tab is selected, the side navigation bar displays systeminformation. When other tabs are selected, it displays links to additional content.

3 Content area Displays content based on the options selected in the side navigation tree.

Table 3.1 Web Interface Window Descriptions

3.2 RPC2 Communications Module Icons

The following table displays the icons used in the web UI. Hovering over an icon displays its description in the web UI.

NOTE: The checkmark, red x and blue plus sign icons have more than one function, depending on their location.

Vertiv | RPC2™ Communications Module Installer/User Guide | 9

Page 14: RPC2 Communications Module User Manual

ICON DESCRIPTION ICON DESCRIPTION

SaveSystem OKNormal Operation

Download

CancelAlarmUnacknowledged Change

Export

Abnormal Operation Flush

Reset Selected Energy (at PDU level)

Reset Energy (at branch and receptacle level)Mixed State of Receptacles

Reset All Energy (PDU level) Warning

Enable Receptacle Power Open CLI

Disable Receptacle Power Print

Cycle Receptacle Power Reboot

EditEdit Group

Reset to Factory Default Settings

Lock Receptacle Restore Configuration

Unlock Receptacle Save Configuration

Blink Receptacle LED Verify SNMPv3 Change

Synchronize TimeNow Verify Email

Verify SMS Edit Group-Receptacle

Start Firmware Update Edit User

Device Acknowledgment Required

Table 3.2 RPC2 Communications Module Icon Descriptions

3.3 Summary Tab

The Summary tab window displays aggregate information about the MPH2™ rack PDU status, including: Recent Events,Primary Sensor and PDU status. The side navigation tree displays the rack PDU's overall status and system information. The

Vertiv | RPC2™ Communications Module Installer/User Guide | 10

Page 15: RPC2 Communications Module User Manual

content area displays recent events, including event codes and status of events. It also displays primary sensor informationand PDU status information, including a summary of the receptacle state and capacity utilization percentage.

NOTE: Sensor information is selectable from the Sensor view of the PDU Explorer tab.

3.3.1 Recent events

The Recent Events table displays information about branch, receptacle, sensor, PDU and system level events. You can viewthis table when you select a rack PDU.

Figure 3.2 Summary Tab Example

HEADING DESCRIPTION

Date/Time Date and time the event occurred

Code

Identifier for the event100-199: System level events200-299: PDU level events300-399: Branch level events400-499: Receptacle level events500-599: Sensor level events

Level Level where the event occurred: Receptacle, branch or system

ID ID where the even occurred

Event Listing of the event

Type Severity type of the event: Notification, warning or alarm

State Whether notification has been sent

Description Information about the event

Table 3.3 Recent Event Descriptions

To view recent events:

Under the PDU Summary tab, click a rack PDU in the Label column.

3.4 PDU Explorer Tab

The PDU Explorer window displays a hierarchical view of data from connected equipment. It also permits viewing sensorsand editing sensor settings. The top of the window displays the Rack PDU view. You can navigate to the PDU, branch andreceptacle levels from either using the link of the connected equipment or the side navigation tree.

Vertiv | RPC2™ Communications Module Installer/User Guide | 11

Page 16: RPC2 Communications Module User Manual

At the top of the PDU Explorer window, the displayed buttons are used to perform functions according to the current, activelevel. At the PDU level, you can use the buttons to reset all energy or reset energy on a selected PDU. Use the buttons on thebranch level to reset energy or return to the PDU level. Buttons that are displayed at the receptacle level are used to resetenergy, enable or disable receptacle power, power cycle the receptacles, lock or unlock receptacles, blink a receptacle'sLED or return to the branch level. The main PDU Explorer window shows detailed information about the rack PDU on theMeasurement, Status, Settings and Information tab windows.

Figure 3.3 PDU Explorer Tab Example

NOTE: For single-phase models with a neutral connection, the Neutral OK status displays in the Status tab. A redcircle with a white X signifies the line and neutral connections are swapped at the rack PDU plug's receptacle orupstream at the PDU.

3.4.1 Measurements

The PDU Explorer’s Measurements tab presents available data about the rack PDU, branch or receptacle. TheMeasurements tab displays current, voltage, power real, power apparent, power factor and energy for all three levels. At thebranch and receptacle levels, the crest factor is also displayed.

3.4.2 Status

The PDU Explorer’s Status tab window provides the status of the rack PDU, branch or receptacle. The Over Current, UnderCurrent and Hardware OK statuses are displayed for each of the three levels. At the Branch level, Under Voltage andBreaker Closed statuses are also displayed while Under Voltage and Neutral OK statuses display for the PDU level.

Figure 3.4 PDU Explorer Icon Descriptions

ICON CONDITION

Normal

Warning

Alarm

Abnormal

Vertiv | RPC2™ Communications Module Installer/User Guide | 12

Page 17: RPC2 Communications Module User Manual

3.4.3 Settings tab

The PDU Explorer’s Settings window permits entering a customized name and settings for a rack PDU, branch orreceptacle.

PDU settings

SETTING DESCRIPTION

Over Current Alarm Threshold Percentage of input current rating to exceed before the corresponding event notification occurs.

Over Current Warning ThresholdPercentage of input current rating to exceed before the corresponding event notification occurs.The valuemust be less than the alarm threshold.

Under Current Alarm ThresholdPercentage of input current rating to fall below before the corresponding event notification occurs.The valuemust be less than the warning threshold. A zero value disables the alarm.

Software Over Current Protection (SWOCP)

If enabled, the SWOCP automatically turns off the receptacle power to non-critical and unloadedreceptacles (no current draw) of all branches when the input over current alarm condition occurs.This mitigates the possible opening of circuit breakers in a PDU or upstream at the service.SWOCP is only displayed and configurable for models having receptacle management.

Table 3.4 PDU Settings Descriptions

To edit a rack PDU:

1. Log in with the required privileges.

2. From the PDU Explorer tab, highlight the rack PDU to be edited by clicking in one of its fields.

NOTE: Clicking a rack PDU opens its branch window.

3. In the table in the lower section of the window, click the Settings tab.

4. Check the boxes next to the settings to be edited.

5. Click the Edit icon.

6. Enter the new values.

-or-

Use the drop-down menu to do one of the following: 

• Enable or disable software overcurrent protection.

• Change whether the receptacle is designated as critical or non-critical.

7. When finished, click the Save icon to make the change or click the Cancel icon to abort the change. The iconsare in the column formerly occupied by the Edit icon.

The following table describes the settings at the PDU level.

3.4.4 Branch settings

The following procedures help you configure the branch settings. Review the table in this section for the branch settingsdescriptions.

SETTING DESCRIPTION

Over Current Alarm Threshold Percentage of branchcurrent rating to exceed before the corresponding event notification occurs.

Over Current Warning ThresholdPercentage of branchcurrent rating to exceed before the corresponding event notification occurs. Thevaluemust be less than the alarm threshold.

Under Current Alarm ThresholdPercentage of branchcurrent rating to fall below before the corresponding event notification occurs. Thevaluemust be less than the warning threshold. A zero value disables the alarm.

Software Over Current Protection(SWOCP)

If enabled, the SWOCP automatically turns off the receptacle power to non-critical and unloadedreceptacles (no current draw) of this branchs when the branch over current alarm condition occurs. This

Table 3.5 Branch Settings Descriptions

Vertiv | RPC2™ Communications Module Installer/User Guide | 13

Page 18: RPC2 Communications Module User Manual

SETTING DESCRIPTION

mitigates the possible opening of circuit breakers in the unit or upstream at the service. SWOCP is onlydisplayed and configurable for models having receptacle management.

NOTE: MPHX BRM, MPH2-C, MPH2-M and MPH2-R rack PDU models support the circuit breaker status. MPH2-B rackPDU models utilize a software Loss of Load detection, which detects a sudden reduction of branch current after itsovercurrent alarm threshold is breached. This active event implies the circuit breaker has opened.

To edit a branch:

1. Log in with the required privileges.

2. From the PDU Explorer tab, click the rack PDU with the branch to be edited.

3. Click in a branch field to highlight the branch and open its receptacle window.

4. In the table at the bottom of the window, click the Settings tab.

5. Check the boxes next to the settings to be edited.

6. Click the Edit icon.

7. Enter the new values.

-or-

Use a drop-down menu to do one of the following:

• Enable or disable software overcurrent protection.

• Change whether the branch is designated critical or non-critical.

8. When finished, click the Save icon to make the change or click the Cancel icon to abort the change. The iconswill be in the column formerly occupied by the Edit icon.

3.4.5 Receptacle settings

The following procedures help you configure the receptacle settings. Review the table in this section for the receptaclesettings descriptions.

SETTING DESCRIPTION

Over Current Alarm Threshold Percentage of receptacle current rating to exceed before the corresponding event notification occurs.

Over Current Warning ThresholdPercentage of receptacle current rating to exceed before the corresponding event notification occurs. Thevaluemust be less than the alarm threshold.

Under Current Alarm ThresholdPercentage of receptacle current rating to fall below before the corresponding event notification occurs.The valuemust be less than the warning threshold. A zero value disables the alarm.

Power Up StateAfter mains power is applied, the receptacle is either immediately turned on, turned off or is restored to thelast power state before the loss of power occurred and after the Power OnDelay has expired. If the lastpower state was off, the power remains off.

Power OnDelay The amount of time, in seconds, before the receptacle power is restored after mains power is applied.

Power Cycle Delay The amount of time, in seconds, that receptacle power is momentarily turned off.

Post On Delay The amount of time, in seconds, before receptacle power is turned on.

Post Off Delay The amount of time, in seconds, before the receptacle power is turned off.

Software Over Temperature Protection(SWOTP)

If enabled, affected receptacles automatically have power turned off after themeasured temperaturebreaches the over temperature alarm threshold of a temperature sensor for at least the duration of theSWOTP delay. The SWOTP can be configured for local mode which is only affected by alarm oftemperature sensor(s) connected to its RPC2module, or array mode which is affected by alarm oftemperature sensor(s) connected to any RPC2module in the array.

Receptacle Criticality

If disabled, the receptacle automatically turns off if SWOTP is enabled and the condition is active. SWOTPautomatically turns off receptacle power to non-critical and unloaded receptacles (no current draw) wheninput and/or branch overcurrent alarm conditions occur in order to mitigate a possible opening of circuitbreakers in the unit or upstream at the service.

Table 3.6 Receptacle Settings Descriptions

Vertiv | RPC2™ Communications Module Installer/User Guide | 14

Page 19: RPC2 Communications Module User Manual

To edit a receptacle:

1. Log in with the required privileges.

2. From the PDU Explorer tab, drill down to the receptacle to be edited by clicking on the rack PDU then thebranch with the receptacle.

3. Click on the receptacle to highlight it.

4. In the table at the bottom of the window, click the Settings tab.

5. Check the box or boxes next to the settings to be edited.

6. Click the Edit icon .

7. Enter the new values.

-or-

Use the drop-down menu to do one of the following:

• Enable or disable software overcurrent protection.

• Change whether the receptacle is designated critical or noncritical.

8. When finished, click the Save icon to make the change or click the Cancel icon to discard the change.

Vertiv | RPC2™ Communications Module Installer/User Guide | 15

Page 20: RPC2 Communications Module User Manual

Local Mass configuration

In addition to being able to configure a receptacle from its Settings window, an administrator can also configure one ormultiple receptacles from the Device Explorer tab window.

Figure 3.5 Mass Configuration Screen

To configuremultiple receptacles: 

1. From the side navigation tree of the Device Explorer tab window, click Config next to the rack PDU you want toconfigure.

2. Enter the desired settings for the receptacles you want to configure. You can configure threshold percentage,delay, power up state and enable or disable SWOTP or Receptacle Criticality.

-or-

To configure multiple receptacles with the same settings, enter the desired setting at the top of each columnand click the Fill Down icon.

3. Click Save.

3.4.6 Sensors

Information for the primary sensor is displayed on the Summary tab window. Clicking a displayed sensor opens the sensorwindow under the PDU Explorer tab. From this window, you can set and configure the primary sensor. Sensors areautomatically discovered when the RPC2 module reboots or when the first sensor is connected. After the initial sensor stringis discovered, you must manually re-discover a change in the sensor configuration by clicking the Discover icon under thePDU Explorer - Sensor configuration window.

To set the primary sensor: 

1. From the Summary tab, click the primary sensor to open the Sensor window in the PDU Explorer tab.

2. Click the radio button next to the sensor you want to be the primary sensor.

3. Click the Set Primary Sensor icon in the upper-left of the window.

Vertiv | RPC2™ Communications Module Installer/User Guide | 16

Page 21: RPC2 Communications Module User Manual

To discover sensors:

Click the PDU Explorer tab and from the side navigation tree, click Sensor to view a list of all the discovered sensors.

To reorder sensors: 

1. From the PDU Explorer - Sensor window, click the button next to the sensor you want to reorder.

2. Use the up and down arrows to reorder the sensor, then click the Save icon.

3. Repeat step 2 for any additional sensors to be reordered.

4. Click the Discover icon.

To configure a sensor:

1. Put a checkmark in the box to the left of the sensor to be changed.

2. Click the Edit icon.

a. If assigning a label, enter the new label (the default is the sensor’s serial number).

b. If changing the asset (sensor in this case), enter a new name for the sensor (default names are Tag01 andTag02.

c. If changing the Alarm Config, click the drop-down menu and choose Alarm when closed, Alarm whenopen or None.

3. Click the Save icon to save the change.

-or-

Click the Cancel icon to discard the change.

3.4.7 Information

The PDU Explorer’s Settings tab window displays read-only information about the rack PDU, branch or receptacle. At thePDU and branch levels, you can view the model number, serial number, rated voltage, rated current, rated frequency, plugpole/wire configuration, plug type, device firmware version and agent firmware version information. At the receptacle level,you can view current, voltage, power real, power apparent, power factory and energy information.

3.5 Device Explorer

The Device Explorer window displays the status of all receptacles on a rack PDU. Clicking a receptacle opens the PDUExplorer view of the selected receptacle. As with the PDU Explorer, use the icons in the upper-left of the window to reset theenergy for a receptacle, enable/disable/cycle a receptacle's power, lock/unlock a receptacle or blink a receptacle's LED.

The RPC2 communications module presents only available data. If the MPH2 rack PDU does not support branch andreceptacle capabilities, the RPC2 module displays grayed-out entries and that information is not shown.

Vertiv | RPC2™ Communications Module Installer/User Guide | 17

Page 22: RPC2 Communications Module User Manual

Figure 3.6 Device Explorer Tab Example

To reset energy for a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox in the upper-left of the table to select all the receptacles.

2. Click the Reset Energy icon, then click OK on the pop-up window to confirm to reset the energy of the selectedreceptacle.

-or-

Click Cancel to return to the Device Explorer window without resetting the energy.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

To enable power for a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

2. Click the Enable Receptacle Power icon, then click OK on the pop-up window to confirm to enable power forthe selected receptacle.

-or-

Click Cancel to return to the Device Explorer window without enabling the power for a receptacle.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

To disable power for a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

Vertiv | RPC2™ Communications Module Installer/User Guide | 18

Page 23: RPC2 Communications Module User Manual

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

2. Click the Disable Receptacle Power icon, then click OK on the pop-up window to confirm to disable power forthe selected receptacle.

-or-

Click Cancel to return to the Device Explorer window without disabling the power for a receptacle.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

To cycle power for a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

2. Click the Cycle Receptacle Power icon, then click OK on the pop-up window to confirm to cycle power for theselected receptacle.

-or-

Click Cancel to return to the Device Explorer window without cycling the power for a receptacle.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

To lock a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

2. Click the Lock Receptacle icon, then click OK on the pop-up window to confirm to lock a selected receptacle.

-or-

Click Cancel to return to the Device Explorer window without locking a receptacle.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

To unlock a receptacle:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

2. Click the Unlock Receptacle icon, then click OK on the pop-up window to confirm to unlock a selectedreceptacle.

-or-

Click Cancel to return to the Device Explorer window without unlocking a receptacle.

3. From the pop-up window, click OK to acknowledge the process completed successfully.

To cause a receptacle's LED to blink:

1. From the Device Explorer window, click the checkbox in the row of the appropriate receptacle.

-or-

Click the checkbox at the top of the table to select all the receptacles in the table.

Vertiv | RPC2™ Communications Module Installer/User Guide | 19

Page 24: RPC2 Communications Module User Manual

2. Click the Blink Receptacle LED icon, then click OK on the pop-up window to confirm to blink the LED on aselected receptacle.

-or-

Click Cancel to return to the Device Explorer window without causing the LED to blink on a receptacle.

3. From the pop-up window, click OK to acknowledge that the process completed successfully.

3.5.1 Device Explorer - receptacle groups

An administrator can create customized groups of rack PDU receptacles. The group appears in the side navigation tree anda summary of the parametric data from the group's receptacles is displayed in the window.

You can group receptacles on rack PDUs for management and monitoring purposes. When you group receptacles, it allowsyou to apply the same changes to all the receptacles in a group by performing a single operation. For example, you can turnall the receptacles on or off with one action, instead of performing this operation on each receptacle. Up to 64 receptaclegroups, including non-critical groups, are possible. All group names, except for the standard Noncritical group name, can bechanged.

NOTE: No receptacles are grouped in the factory-default setup of the RPC2 communications module.

Noncritical group

The Noncritical group is intended for linking receptacles powering non-essential equipment. This receptacle group can beshut down for power conservation and similar purposes, such as when utility power fails and a UPS is powering rackequipment.

All receptacles are critical by default. No receptacles can be in the Noncritical Group unless they are added by a user withadministrative privileges.

To create a receptacle group:

1. Navigate to the Device Explorer window and click Groups from the side navigation tree.

2. In the list of 64 empty groups, click the Edit icon next to the group you want to create.

3. In the list of receptacles, click to add a checkmark beside each receptacle to be added to the group.

4. Name the group or use one of the default group names.

5. Click the Save icon.

6. Repeat as needed for additional groups.

3.6 Events Tab

The Events window displays a list of events that have occurred on the MPH2 rack PDU system, with more recent events atthe top of the list. When the number of events exceeds the limit of 6,000, the oldest events are removed first. Use the drop-down menus to filter events. Events can be configured for SNMP Traps, Syslog, Email and SMS in the System Tab.

Information available includes the date and time of occurrence, the event code, receptacle or branch where the eventoccurred, name or description of the event, severity level and the event status (active, notification sent, clear and so on).

Figure 3.7 Events Tab

Vertiv | RPC2™ Communications Module Installer/User Guide | 20

Page 25: RPC2 Communications Module User Manual

To download a log file for all events:

Click the Events tab, then click the Download icon at the top of the window to download a log file for all events.

NOTE: A downloaded event log can be imported into Microsoft® Excel® and viewed as a spreadsheet.

To clear all events: 

Click the Events tab, then click the Flush icon at the top of the window to clear all events except for active alarms.

3.7 System Tab

The System window is the control and configuration center for the RPC2 rack communications module. Links on thenavigation tree allow you to update firmware, join networks, set security levels, add and remove users, set access privilegesand alarm thresholds and set automatic messages for events and alarms. The System window also displays informationabout the RPC2 communications module and the PDU, where it is installed, including location, contact personnel, technicalsupport, firmware version, serial number and MAC address. With administrative privileges, you can configure the RPC2communications module’s parameters, such as notifications and SNMP traps and access. You can also update the RPC2communications module’s firmware and change passwords.

Figure 3.8 System Tab

3.7.1 Support

The Support link in the navigation tree on the System tab is a read-only window. You can access this window to viewinformation about the RPC2 communications module and print the summary table via the Print icon.

Vertiv | RPC2™ Communications Module Installer/User Guide | 21

Page 26: RPC2 Communications Module User Manual

3.7.2 Devices

You can access the Devices window in the System tab navigation tree to view a read-only window about the rack PDU andthe RPC2 communications module. Available information includes the System Name (user specified), system location,system description, contact personnel names, rack PDU manufacturer, the RPC2 serial number and firmware label and therack PDU model, serial number and firmware version. You can also print the summary table via the Print icon at the top ofthe window.

3.7.3 Device change

Access the Device Change link in the System tab navigation tree to view device changes, such as a rack PDU array beingadded or removed, a rack PDU being added to an array, sensors being added or removed or a module added to a LiebertMPX. This window displays the module serial number and type and shows when modules are added and removed. You canuse the Acknowledge icon to acknowledge changes and remove them from the window.

NOTE: A notepad icon appears in the upper left corner when a device change is not acknowledged by the user. Thisoccurs at initial startup, when the RPC2 communications module is installed for the first time, when a sensor is addedor removed, when an MPXBRM is added or removed and after a reset to factory defaults is executed. After an event orchange is acknowledged, the event may take a few seconds to clear and the icon changes to Normal. If an alarmcondition is present, the Alarm icon appears.

3.7.4 Firmware update

Firmware updates can be downloaded from the Downloads section of the Vertiv™ web site(www.VertivCo.com/MPH2Downloads).

Once downloaded, the firmware update file is transferred to the RPC2 module's memory. The RPC2 module manages thefirmware update process for any connected devices and then for itself.

The RPC2 communications module permits unattended firmware updates. The browser being used can be closed after theprogress bar is displayed.

To update themodule's firmware: 

1. Click the System tab, then click Support - Firmware Update from the side navigation tree.

2. Select whether to update from the web (http), FTP or TFTP.

3. Click the Browse button to find and open the downloaded .epm file on the host PC or network. The selected filename is displayed in a text box.

4. Click the Start Firmware Update icon to begin updating.

-or-

Click the Cancel icon to clear the filename and begin again.

5. The firmware update progress is shown in the status. Once the process is finished, the system automaticallyrestarts and resumes displaying rack PDU information.

NOTE: The firmware update may take up to 15 minutes. If the update fails, try updating again. The previous workingfirmware is recoverable as the RPC2 module maintains the firmware image in its memory.

3.7.5 Settings

With permissions, you can access the Settings link in the System tab’s navigation tree to configure the settings for the RPC2communications module. Use the icons at the top of the window to save or cancel the changes. The Settings window alsopermits resetting the RPC2 communications module to factory defaults, rebooting the system and opening a command lineinterface session.

Tomanage RPC2 communications module settings:

1. From the System tab, click Settings in the side navigation tree.

2. Enter a system name and description for the RPC2 communications module.

3. Enter a contact name and location.

4. Use the drop-down menu to display the temperature in either Celsius or Fahrenheit.

Vertiv | RPC2™ Communications Module Installer/User Guide | 22

Annotation [DD]New text
Page 27: RPC2 Communications Module User Manual

5. Use the drop-down menu to select either Local or PDU Array for SWOTP scope.

6. Enter the SWOTP delay (how long the module waits before turning off receptacles) in seconds.

7. Use the drop-down menu to select either a 12-hour or 24-hour time format.

8. Click the Save icon.

Network

On the Network window, you can configure the speed/duplex, hostname, IPv4 or IPv6 static routes.

To configure network parameters:

1. From the side navigation bar of the System tab, click Network.

2. Use the drop-down menu to select Speed/Duplex.

3. Enter the hostname in the Host Name field.

4. Select the default IPv4.

-or -

Check the IPv6 checkbox.

5. For IPv4 or IPv6, select either Static or DHCP for the boot mode and enter the IP Address, Subnet Mask andDefault Gateway in the appropriate fields.

6. Click the Save icon.

DNS

From the Domain Name Server (DNS) settings menu, an administrator can configure the servers the RPC2 communicationsmodule will use for hostname resolution. When configured, host addresses for SNMP, Network Time and Email/SMS can bespecified in either full Domain Name format or host only format, provided that the appropriate Domain Name Suffix is used.

The DNS menu is used to set parameters for network access to the RPC card. Consult your network administrator for thesesettings.

To configure DNS Server settings:

1. From the side navigation bar of the System tab, click Network - DNS.

2. Select whether to obtain DNS server addresses automatically or to enter them manually.

3. If they will not be obtained automatically, enter the primary and secondary DNS addresses.

4. Enter the domain name suffix. This suffix is used for assembling a fully-qualified domain name when a host-onlyname is specified.

5. Click the Save icon.

DNS test

The DNS Test function checks whether the RPC2 communications module resolves a hostname to an IP address.

To run a DNS test:

1. From the side navigation bar of the System tab, click Network - DNS.

2. Under the DNS Test heading, use the drop-down menu to select a fully-qualified domain name or an IP address.

3. In the Question field, enter a value for the DNS to answer.

4. Click the Query icon in the upper-left of the window to attempt a lookup with the provided information.

Simple Network Time Protocol (SNTP)

The RPC2 communications module provides two options for setting the date and time. It can retrieve the date and timefrom an SNTP server, or the date and time can be set manually so that the internal clock of the rack PDU is used to providetime and date information.

Vertiv | RPC2™ Communications Module Installer/User Guide | 23

Page 28: RPC2 Communications Module User Manual

To set the date and time:

1. From the side navigation bar of the System tab, click Network.

2. Under the SNTP heading, select NTP Server to use an NTP server.

-or-

Select Local to manually set the date and time.

3. If using NTP, enter an NTP server site in the Time Server field.

4. Select either Hourly or Daily for the synchronize rate.

5. Use the drop-down menu to select the time zone.

6. If manually setting the date and time, enter the time in YYYY-MM-DD HH:MM:SS format in the System Dateand Time field.

7. Click the Save icon.

NOTE: To re-sync the time immediately, click the Sync Time Now icon at the top of the window.

NOTE: The date and time must be entered manually after every reboot or power cycle for MPX and MPH model PDUswith an RPC2 module installed and Local mode enabled.

Notification

The RPC2 communications module generates notifications for a wide variety of events. It can be configured to direct orstore those event notifications for immediate use or for analysis later.

To configure notifications:

1. From the side navigation bar of the System tab, click Notification.

2. For each notification type, check the boxes next to the type of notification to be sent.

-or-

Check the box next to the heading to select that type of notification for all events in the list: e-mail, SMS, SNMPTrap or SysLog notifications.

3. Click the Save icon.

Messaging

An administrator can configure email and SMS settings to be used for notifications from the Messaging window.

To verify the settings once configuration is complete:

1. From the side navigation bar of the System tab, click Notification - Messaging.

2. Check the box next to Email to enable the configuration of email settings.

3. Enter the sender and recipient's email addresses..

4. Check the radio button to either use the event or to create a custom subject for the email.

5. Enter the SMTP server and port number.

6. Click the Authentication checkbox to enable the subsequent fields.

7. Enter a username and then click the Password checkbox to enable the Modify Password field.

8. Enter a new password in the Modify Password field.

9. Choose the connection type from the drop-down list box.

10. Click the Save icon at the top of the window.

11. To verify the email configuration, click the Verify Email icon in the upper-left of the window.

To configure SMS settings:

1. From the side navigation bar of the System tab, click Notification - Messaging.

2. Check the box next to SMS to enable the configuration of the SMS settings.

Vertiv | RPC2™ Communications Module Installer/User Guide | 24

Page 29: RPC2 Communications Module User Manual

3. Enter the address sender and recipient's SMS notification addresses..

4. Check the radio button to either use the event or to create a custom subject for the email.

5. Enter the SMTP server and port number.

6. Click the Authentication checkbox to enable the subsequent fields.

7. Enter a username and then click the Password checkbox to enable the Modify Password field.

8. Enter a new password in the Modify Password field.

9. Choose the Connection Type from the drop-down list box.

10. Click the Save icon at the upper-left of the window.

11. To verify the SMS configuration, click the Verify SMS icon in the upper-left of the window.

Customize Message

An administrator can customize an email or SMS message as well as configure emails and SMS event consolidation.

To customize amessage:

1. From the side navigation bar of the System tab, click Notification - Messaging - Customize Message.

2. Under the Customize Message heading, check the items to be included for email and/or SMS messaging.

3. Click the Save icon.

To configure e-mail and SMS event consolidation:

1. From the side navigation bar of the System tab, click Notification - Messaging - Customize Message.

2. Under Configure Email/SMS Event Consolidation, check the boxes to enable email or SMS consolidation.

3. Enter the consolidation time limit using the number of seconds and enter the consolidation event limit innumber of events.

4. Click the Save icon in the upper-left corner of the window.

Syslog

Syslog notifications can be sent to up to four IPv4 or IPv6 addresses.

To enable Syslog notifications:

1. Log in with the required privileges.

2. From the side navigation bar of the System tab, click Notification - Syslog.

3. Check the box to enable either IPv4 or IPv6 addressing and enter up to four addresses.

4. Click the Save icon.

Datalog

An administrator can enable data logging for rack PDUs, branches or receptacles, and export the data log to an FTP site.

To enable data logging:

1. Log in with the required privileges.

2. From the side navigation bar of the System tab, click Notification - Datalog.

3. Under the Datalog heading, check the box to enable data logging.

4. Use the drop-down menus to enable or disable PDU, branch or receptacle data logging.

5. Use the drop-down menu to enter the data logging interval using the number of minutes.

6. Click the Save icon.

To export a data log:

1. From the side navigation bar of the System tab, click Notification - Datalog.

2. Under the Export heading, enter the IP address, username and password for the FTP site to receive the datalog.

Vertiv | RPC2™ Communications Module Installer/User Guide | 25

Page 30: RPC2 Communications Module User Manual

3. Enter the path and filename for the data log.

NOTE: The default filename is sys-data.log.

4. Click the Export icon when finished.

5. Click the Flush or Download icon at the upper-left of the window to clear or download the data log.

Backup and Restore

An administrator can configure an FTP site to back up a configuration file or restore a configuration from a backup file.

To configure the backup file location:

1. From the side navigation tree of the System tab, click Notification - Backup and Restore.

2. Check the radio button next to the FTP Site and enter the IP address, username and password for the FTP siteto receive the data log. Then enter the path and filename for the configuration file.

-or-

Check the radio button next to Local, click Choose File, browse to the location to save the file and enter a namefor the configuration file.

3. Click the Save icon.

To back up the configuration: 

Click the Save Configuration icon at the upper-left of the window and click OK.

To restore from the last saved configuration:

Click the Restore Configuration icon at the upper-left of the window and click OK.

Using a USB memory stick

A memory stick can be inserted into the RPC2 module's USB port using a Type A female to micro A/B male adaptor. Youcan use a memory stick to facilitate the initial setup of networking, protocol and device configurations.

Each RPC2 module's .csv configuration file is uniquely saved according to its MAC ID. To facilitate mass configuration,multiple .csv files can be saved to the memory stick and then edited in a spreadsheet program before being loaded backinto the respective module.

To back up a configuration to a USB memory stick: 

1. Insert a memory stick that does not already contain the module's unique configuration file into the module'sUSB port.

2. After a single beep, the module begins to save the configuration file to the memory stick.

3. After three consecutive beeps, the backup is complete and the memory stick is shut down for safe removal.

4. Remove the memory stick and repeat as desired for additional modules.

To restore a configuration from aUSB memory stick: 

1. Insert a memory stick that contains the module's unique configuration file into the module's USB port.

2. After five consecutive beeps, the restoration begins. To abort the restoration, remove the memory stick beforethe fifth beep.

3. After three consecutive beeps, the restoration is complete and the memory stick is shut down for safe removal.The configuration file is automatically deleted from the memory stick after restoration, and the module rebootsfor the new configuration to take affect.

NOTE: Wait a few minutes after the reboot completes to access to the unit.

Vertiv | RPC2™ Communications Module Installer/User Guide | 26

Page 31: RPC2 Communications Module User Manual

Manage Protocol

From the Manage Protocol window, an administrator can enable or disable the velocity server, SNMP agent, SSH support,Telnet and web server. From this window, an administrator can also disable or set the inactive timeout and configure themaximum number of Telnet sessions allowed.

Modifying the Velocity or SNMP requires rebooting the RPC2 communications module. The RPC2 communications modulecan be rebooted by accessing System - Settings - Reboot.

SNMP

An administrator can configure SNMP, which is needed if notifications are to be sent to an SNMP management application.The RPC2 communications module supports SNMP v1, v2 and v3.

To configure SNMP:

1. Log in with the required privileges.

2. From the side navigation bar of the System tab, click Manage Protocol - SNMP.

3. Use the drop-down menu to enable or disable SNMPv1/v2.

4. Use the drop-down menu to select either SNMPv1 or SNMPv2 for the SNMP traps.

5. Enter the port number for the SNMP UDP port and the SNMP Traps UDP port.

6. Use the drop-down menu to enable or disable the Liebert Global Products (LGP) MIB and MIB traps forquerying information in that MIB.

7. Use the drop-down menu to enable or disable the authentication trap. If enabled, an SNMP authentication trapis sent to all trap targets.

8. Use the drop-down menu to enable or disable the System Notify trap for system traps to be sent per the LGPMIB.

NOTE: The LGP MIB must also be enabled to enable system notify traps.

9. Disable or set the heartbeat interval using the number of minutes. This specifies how often a heartbeat trap issent to show that a device is online and functioning normally.

10. Use the drop-down menu to enable or disable SNMPv3.

11. Click the Save icon.

SNMPv1/v2 Access

From the side navigation bar of the System tab, click SNMPv1/v2 Access to configure the SNMPv1/v2 community's settings.Up to 20 devices can be configured with permission to access the RPC2 communications module, identified by IP addressor hostname, read/write privileges and community string.

PARAMETER DESCRIPTION

Entry As many as 20 devices can be configured for access.

NetworkName

The IP address of the target to receive traps.

AccessClick the ReadOnly radio button to allow users to view but not change data. Click the ReadWrite radio button to give full permissions forconfiguration, control and viewing.

Community The community string used by the IP host for this entry.

Clear Click Clear to delete all values for this entry.

Table 3.7 SNMPv1/v2 Access Description

NOTE: A network name of 0.0.0.0 with write access and a public community grants access to any host computer.

Vertiv | RPC2™ Communications Module Installer/User Guide | 27

Page 32: RPC2 Communications Module User Manual

SNMPv3 Access

From the side navigation bar of the System tab, click SNMP-V3 Access to configure the SNMPv3 community's settings. Upto 20 devices can be configured with permission to access the RPC2 communications module, identified by IP address orhostname, read/write privileges and a community string.

PARAMETER DESCRIPTION

Entry As many as 20 devices can be configured for access.

User EnableUser Enablemust be checked for each user to be configured for access. Amaximum of 20 devices may be configured foraccess.

User Name The IP address of the network host to receive access to device information or traps.

Authentication Type Options are none, MD-5 or SHA.

AuthenticationSecret

Password between 8-64 characters for SNMPv3 request.

Privacy Type Options are no encryption or DES.

Privacy Secret Password of 8-64 characters for SNMPv3 request.

Access No Access provides no access. ReadOnly provides only the ability to view data.

Source Either an IP address or the network name of the host. To enablemultiple hosts, enter network names separated by a comma.

Clear Click Clear to delete all values for this entry.

Table 3.8 SNMPv3 Access Description

NOTE: A configuration with sources set to 0.0.0.0 with write access and no authentication grants access to any hostcomputer.

SNMPv1/v2 Traps

An administrator can configure up to 20 users to receive notifications from the RPC2 communications module, identified byIP address or hostname, trap listen port and community string.

To configure SNMPv1/v2 traps:

1. From the side navigation bar of the System tab, click Manage Protocol - SNMP - V1V2 Traps.

2. Enter the network name, port number and community string in the appropriate fields.

3. Check the box to enable the heartbeat feature.

4. Click the Save icon in the upper-left of the window.

5. To verify the configuration, click the Verify icon at the upper-left of the window.

PARAMETER DESCRIPTION

Entry Enter up to 20 targets to receive traps.

Network Name The IP address or network name of the target to receive traps.

Port The Trap Listen Port where traps will be sent. Use 162 if the host computer uses standard ports.

Community The community string used the by the IP host for this entry (case sensitive, up to 32 characters).

Heartbeat Check the box to enable a heartbeat check.

Clear Click Clear to delete all values for this entry.

Table 3.9 SNMPv1/v2 Trap Descriptions

Vertiv | RPC2™ Communications Module Installer/User Guide | 28

Page 33: RPC2 Communications Module User Manual

SNMPv3 Traps

An administrator can configure up to 20 users to receive notifications from the RPC2 communications module. Users mustbe identified by IP address or hostname, trap listen port and community string.

To configure SNMPv3 traps:

1. From the side navigation bar of the System tab, click Manage Protocol - SNMP - V3 Traps.

2. Enter the user name, port number and destinations.

3. Use the drop-down menu to enable or disable notifications.

4. Check the box to enable the heartbeat feature.

5. Click the Save icon.

6. To verify the configuration, click the Verify icon.

PARAMETER DESCRIPTION

Entry Enter up to 20 targets to receive traps.

User Name The IP address or network name of the host to receive traps.

Notify Enable or disable notifications being sent to the user from themodule.

DestinationThe IP address or the network name of the network host to receive notifications from themodule. Use a comma to separatemultiplehosts.

Heartbeat Check the box to enable a heartbeat check.

Port The Trap Listen Port where traps are sent. Use 162 if the host computer uses standard ports.

Clear Click Clear to delete all values for this entry.

Table 3.10 SNMPv3 Traps Descriptions

Web Server

An administrator can configure access to the module through the web interface.

To configure access through the web interface:

1. From the side navigation bar of the System tab, click Manage Protocol - Web Server.

2. Use the drop-down menu to select either HTTP or HTTPS for the web server.

3. Enter the port number for the HTTP or HTTPS server.

4. Enter the amount of time in seconds the RPC2 communications module refreshes.

5. Click the Save icon when finished.

Certificate

The Network Interface Card allows you to either generate a new self-signed certificate or upload a new certificate.

To generate a new self-signed certificate:

1. From the side navigation bar of the System tab, click Manage Protocol - Web Server - Certificate.

2. Ensure the Generate a New Self-Signed Certificate radio button is selected.

3. Enter the certificate information in the following fields.

4. Click the Generate Certificate icon.

To upload a new certificate (Windows):

1. Install Git for Windows from https://git-for-windows.github.io/.

2. Accept the default settings and check for the GitBASH run icon to be placed on your desktop.

3. Run GitBASH. After a few moments, GitBASH presents a bash prompt.

4. Create a folder to hold the script and PEM files.

Vertiv | RPC2™ Communications Module Installer/User Guide | 29

Page 34: RPC2 Communications Module User Manual

5. Change the directory to the folder you created.

6. Copy the custom openssl script to your folder.

Example: Custom Openssl Script

#!/bin/bash workdir=/tmp/sslgenwdkeyfile="serverkey.key"crtfile="servercrt.crt"pcksfile="serverpcks.p12"pemfile="server.pem"logfile="sslupwd.log"installdir="C:\Users\emily2938\Desktop\Certificates"dstkeyfile="serverkey.pem"dstpemfile="server.pem"p12filepw=123456if [ $# -lt 6 ];then echo "1" > voutf exit 1 fisubjarg="//C=$5\ST=$4\L=$3\O=$2\CN=$1\emailAddress=$6"if [ ! -d $workdir ]; then mkdir $workdir ficd $workdirecho -e "#STEP 1: Generate a key"openssl genrsa -out $keyfile 1024if [ $? -ne 0 ];then echo "1" > voutf exit 1 fiecho -e "\n#STEP 2: Generate the self-signed certificate"openssl req -new -x509 -key $keyfile -out $crtfile -days 3650 -subj $subjargif [ $? -ne 0 ];then echo "1" > voutf exit 1 fiecho -e "\n#STEP 3: Combine key and crt into pem"openssl pkcs12 -export -in $crtfile -inkey $keyfile -out $pcksfile -passout pass:$p12filepwif [ $? -ne 0 ];then echo "1" > voutf exit 1 fiopenssl pkcs12 -in $pcksfile -nodes -out $pemfile -passin pass:$p12filepwif [ $? -ne 0 ];then echo "1" > voutf exit 1 fiecho -e "\n #STEP 4: Install file"cp$workdir/$keyfile $installdir/$dstkeyfile -fcp $workdir/$pemfile $installdir/$dstpemfile -f#echo "0" > voutf#

rm $workdir -rfcd

7. Modify the PEM install path and days as desired in script and run the script.

8. Modify your parametric information and email address accordingly.

NOTE: The four steps should complete without error and two PEM files should be created in your folder. Ensure thatthe RPC2 SNTP time is correct and in sync with the timestamp of the certificate.

9. In the application, from the side navigation bar of the System tab, click Manage Protocol - Web Server -Certificate.

10. Select the Upload a New Certificate radio button and click Choose File to browse for the PEM file.

11. Click the Upload Certificate icon. If the process is successful, you are prompted to restart your screen.

12. Restart your system to complete the process.

3.7.6 Authentication

Authentication can be performed locally or on a remote Kerberos, LDAP, Radius or TACACS+ authentication server. If therack PDU is managed by an Avocent® DSView™ Management Software server, DSView™ server authentication is also

Vertiv | RPC2™ Communications Module Installer/User Guide | 30

Page 35: RPC2 Communications Module User Manual

supported.

The rack PDU also supports remote group authorizations for the LDAP, Radius and TACACS+ authentication methods.

An administrator can configure authentication using the web interface or the command line interface. The defaultauthentication method for the rack PDU is Local. Any authentication method that is configured for the rack PDU is used forauthentication of any user who attempts to log in through Telnet, SSH or the web manager.

To select an authentication type:

1. From the side navigation bar of the System tab, click Authentication.

2. Use the drop-down menu to select the authentication type.

3. Click the Save icon in the upper-left of the window.

Remote servers

Using a remote server requires configuring its IP address and, in most cases, other parameters before it can be used. Thefollowing remote servers require configuration:

• DSView™ server

• RADIUS™

• TACACS+™

• LDAP(S) AD™

• Kerberos™

To configure a DSView™ authentication server:

1. From the side navigation bar of the System tab, click Authentication - Remote Servers - DSView.

2. Enter IP Address for the DSView™ servers.

3. Click the Save icon.

4. From the left navigation tree, click Groups.

5. Enable the Admin checkbox.

6. Click the Edit Users icon.

7. Enter the DSView username in the Remote User field and then click the right arrow to add the user to theGroup-User List field.

8. Click the Save icon.

To configure a RADIUS™ authentication server:

1. From the side navigation bar of the System tab, click Authentication - Remote Servers - Radius.

2. Enter the IP addresses of the First Authentication Server and First Accounting Server.

3. If used, enter the IP addresses for the Second Authentication Server and Second Accounting Server.

4. Enter the secret word or passphrase in the Secret field (applies to both first and second authentication andaccounting servers), then re-enter the secret word or passphrase in the Confirm Secret field.

5. Enter the desired number of seconds for server time-out in the Timeout field.

6. Enter the desired number of retries in the Retries field.

7. Click the Save icon in the upper-left of the window.

8. From the left navigation tree, click Groups.

9. Enable the Admin checkbox.

10. Click the Edit Users icon.

11. Enter the RADIUS™ username in the Remote User field and then click the right arrow to add the user to theGroup-User List field.

12. Click the Save icon.

To configure a TACACS+™ authentication server:

1. From the side navigation bar of the System tab, click Authentication - Remote Servers - TACACS+.

Vertiv | RPC2™ Communications Module Installer/User Guide | 31

Page 36: RPC2 Communications Module User Manual

2. Enter the IP addresses for the First Authentication Server and First Accounting Server.

3. If used, enter the IP addresses of the Second Authentication Server and Second Accounting Server.

4. Select the desired service (PPP, raccess or shell) from the Service drop-down menu.

5. Enter a secret word or passphrase in the Secret field (applies to both first and second authentication andaccounting servers), then re-enter the secret word passphrase in the Confirm Secret field.

6. Enter the desired number of seconds for server time-out in the Timeout field.

7. Enter the desired number of retries in the Retries field.

8. Use the drop-down menu to select the TACACS+™ version.

9. Click the Save icon in the upper-left portion of the window.

10. From the left navigation tree, click Groups.

11. Enable the Admin checkbox.

12. Click the Edit User icon.

13. Enter the TACACS+™ username in the Remote User field and then click the right arrow to add the user to theGroup-User List field.

14. Click the Save icon.

To configure an LDAP(S)|AD™ authentication server:

1. From the side navigation bar of the System tab, click Authentication - Remote Servers - LDAP(S)|AD.

2. Enter the IP address of the server.

3. Enter the base.

4. At the Secure drop-down menu, select Off, On or Start_TLS.

5. Enter the database username, then enter and confirm the database password.

6. Enter the desired login attributes.

7. Click the Save icon in the upper-left of the window.

8. From the left navigation tree, click Groups.

9. Enable the Admin checkbox.

10. Click the Edit Users icon.

11. Enter the LDAP(S)|AD™ username in the Remote User field and then click the right arrow to add the user to theGroup-User List field.

12. Click the Save icon.

To configure a Kerberos™ authentication server:

1. From the side navigation bar of the System tab, click Authentication - Remote Servers - Kerberos.

2. Enter the IP address (Realm) of the server.

3. Enter the Realm Domain Name (example: VertivCo.com).

4. Enter the Domain Name (example: VertivCo.com).

5. Click the Save icon in the upper-left of the window.

6. From the left navigation tree, click Groups.

7. Enable the Admin checkbox.

8. Click the Edit Users icon.

9. Enter the Kerberos™ username in the Remote User field and then click the right arrow to add the user to theGroup-User List field.

10. Click the Save icon.

3.7.7 Authorization levels

User groups are given access and authorizations either by default or as assigned by an administrator. Administrators canalter the permissions and access rights of users belonging to the appliance or user groups, or create additional groups withcustom permissions and access rights. Administrators can add, delete or modify permissions and access rights for usersfrom any group at any time.

There are four default user groups on an RPC2 communications module.

Vertiv | RPC2™ Communications Module Installer/User Guide | 32

Page 37: RPC2 Communications Module User Manual

• Admin

• Poweruser

• System User

• Custom User

Groups

An administrator can create a custom group and assign receptacles to users in the custom group. A user in a custom groupis able to view only the receptacles to which he is given access; the other receptacles do not appear. A user in a customgroup can lock and unlock only the receptacles he has access to. A user can belong to more than one group. Members canbe added or deleted from any group, but none of the default groups, (administrator, power user or system user) can bedeleted.

NOTE: Only one group can be modified at a time.

To add a group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. To add a group, click the Add icon in the upper-left of the window, then enter the name for the new group.

3. Set the access level for members of the group by granting access to receptacles.

4. Click the Save icon.

To delete a group:

1. Check the box next to the group to be deleted.

2. Click the Delete icon.

To add a user to a group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. Check the box next to the group to be edited.

3. Click the Edit User icon.

4. In the Local User List or the Remote User List, select the user to be added and click the right arrow.

5. Click the Save icon.

To delete a user from a group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. Check the box next to the group to be edited.

3. Click the Edit User icon.

4. In the Group User List, select the user to be removed and click the left arrow.

5. Click the Save icon.

To add a user to a group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. Check the box next to the group to be edited.

3. Click the Edit User icon.

4. In either the Local User List or the Remote User List, select the user to be added and click the right arrow.

5. Click the Save icon.

To delete a user from a group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. Check the box next to the group to be edited.

3. Click the Edit User icon.

4. In the Group User List, select the user to be removed and click the left arrow.

Vertiv | RPC2™ Communications Module Installer/User Guide | 33

Page 38: RPC2 Communications Module User Manual

5. Click the Save icon.

To assign receptacles to a user group:

1. From the System tab’s navigation tree, click Authorization - Groups.

2. Check the box next to either the user group or a custom group where the receptacles are added.

NOTE: Receptacles cannot be assigned to the administrator, poweruser or system user groups. Each of these defaultgroups has its access level set in the software.

3. Check the boxes next to the receptacles to be added to the group.

-or-

To assign all receptacles, click the box at the top of the column.

4. Click the Save icon.

Users

From the User Names window, an administrator can add or delete users and change user passwords.

NOTE: The administrator’s user password cannot be changed on this window.

To add a user:

1. From the System tab’s navigation tree, click Authorization - Users.

2. Click the Create Local User icon.

3. Enter the username and password and confirm the password.

4. Click the Save icon.

To delete a user:

1. From the System tab’s navigation tree, click Authorization - Users.

2. Check the box next to the user to be deleted.

3. Click the Delete Local User icon.

4. Click OK when prompted.

To change a user password:

1. From the System tab’s navigation tree, click Authorization - Users.

2. Check the box next to the user whose password needs to be changed.

3. Click the Change Local User's Password icon.

-or-

To change your own password, from the side navigation bar of the System tab, click Authorization - ChangePassword.

4. Enter and confirm the new password.

5. Click Save icon.

Vertiv | RPC2™ Communications Module Installer/User Guide | 34

Page 39: RPC2 Communications Module User Manual

4 RPC BDM™ (OPTIONAL)The RPC BDM is a small monitoring device that displays data from an Vertiv™ MPH2™, MPX™ or MPH™ unit through aconnection to an RPC2 communications module. The BDM device provides another way to browse PDU data using the PDUExplorer and Device Explorer, as in the web interface. Views shown by the RPC BDM are essentially the same as thoseshown by the MPH2's onboard LCD.

NOTE: The RPC BDM is a read-only display that can be used to view data but not to control or configure devices.

To perform control and configuration functions, use the web or SNMP interface. The display unit, which can be carried as ahandheld device or mounted on a wall or in the rack, permits users to:

• View monitoring data

• Identify the load of PDU input lines, branch circuit breakers and receptacles (varies by model)

• Identify the load of PDU devices using the user-assigned label

• View Liebert® SN™ sensor readings for areas monitored by connected sensors

• Identify the IP address and MAC address of the PDU

• Browse user-assigned receptacle labels to view parametric information

• View the active events list

• Balance PDU line loads

4.1 Orientation of the RPC BDM

The RPC BDM can be rotated for vertical or horizontal display, as shown in the following figure. When in the verticalorientation, the connection port is on the top while the scroll button is on the side. In the horizontal orientation, theconnection port is on the side with the scroll button on the top.

Figure 4.1 Vertical or Horizontal Orientation

To set the orientation:

Hold down the scroll button when first connecting the RPC BDM to the RPC2.

4.1.1 Navigation Tips

To navigate and select items:

1. Use the scroll button to move the cursor to highlight an item on the screen.

2. Press the scroll button to select the highlighted item.

Vertiv | RPC2™ Communications Module Installer/User Guide | 35

Page 40: RPC2 Communications Module User Manual

Figure 4.2 RPC BDM Scroll Button

ITEM DESCRIPTION

1 Scroll button

2 Connection port

Table 4.1 BDM Descriptions

System options

The icons shown in the following figure are displayed in the bottom right of the screen. These icons provide access to furthernetwork information, system and screen options. Use the scroll button to highlight and select these icons.

Figure 4.3 System Option Icons

ITEM DESCRIPTION

1 Play icon

2 Adjust screen contrast icon

3 System network icon

4 Return to previous level icon

Table 4.2 System Option Icon Descriptions

4.2 RPC BDM™ Installation

The RPC BDM comes with a factory-supplied Ethernet cable for connection to the RPC2. If additional or longer cables areneeded, use standard Ethernet cables.

Vertiv | RPC2™ Communications Module Installer/User Guide | 36

Page 41: RPC2 Communications Module User Manual

4.2.1 Set the IP address for the RPC2 communications module

The RPC2 module and the RPC BDM may be used on a network or on standalone rack PDUs. Either mode requiresinitializing the RPC2 module with an IP address before the RPC BDM can display data.

Follow the appropriate steps to initialize the RPC2 module in a network or standalone environment.

To initialize an RPC2module in a network environment:

1. Use an Ethernet cable to connect the network port to the network.

2. Use DHCP to have an IP address assigned to the network port automatically.

-or-

If DHCP is not used, use an Ethernet cable to connect the Expansion/Management port to a laptop. Then assigna static IP address to the network port. Click Restart to initialize the RPC2 module.

To initialize an RPC2module in standalonemode (non-networked):

1. Use an Ethernet cable to connect the link port to a laptop.

2. Assign a static IP address to the LAN port, then click Restart to initialize the RPC2 module. After the RPC2 isinitialized, the IP address can be viewed on the RPC BDM.

4.2.2 Connect the RPC BDM to the RPC2 communications module

To connect the RPC BDM to an RPC2 communications module:

1. Connect one end of the factory-supplied Ethernet cable into the RPC BDM port.

2. Connect the other end of the cable into the display port of the RPC2 module. Once the rack PDU is turned onwith these connections made, the RPC BDM is fully operational.

4.3 Placement of the RPC BDM™

The RPC BDM can be mounted in various locations inside a rack for easy access and viewing. It can also be handheld andused as a portable device for connecting to different rack PDUs. The device can be rotated for vertical or horizontal display.

4.4 RPC BDM Operation

The PDU Explorer hierarchy provides three levels for viewing Rack PDU data: PDU, branch and receptacle. The PDU level isthe default view.

Vertiv | RPC2™ Communications Module Installer/User Guide | 37

Page 42: RPC2 Communications Module User Manual

Figure 4.4 BDM Hierarchy

ITEM DESCRIPTION

1 PDU Level

2 Branch Level

3 Receptacle Level

Table 4.3 BDM Hierarchy Descriptions

The icon in the upper-left corner of the screen identifies the component type, PDU, branch or receptacle. The highlighted IDnumber in the lower-left corner indicates which component is currently displayed, for example PDU 1, Branch A, Receptacle5. A selected component blinks while data about it is displayed.

The component data includes a graph, amperage and status (V, W, VA for branch/receptacle). Navigation buttons appear inthe lower-right corner of each screen. When any events are detected, the display changes to the PDU view and an ActiveEvents icon appears in the lower-right corner.

4.4.1 PDU level

Select a PDU number in the lower-left corner to highlight it. The screen displays information for the selected PDU. Thefollowing figure is an example of data for PDU #1, one of two PDUs that are communicating with the BDM unit. The PDU viewdisplays information collected at the PDU input point for each of the three input phases: L1, L2 and L3. Up to three phasescan be used.

Vertiv | RPC2™ Communications Module Installer/User Guide | 38

Page 43: RPC2 Communications Module User Manual

Figure 4.5 PDU Level View

ITEM DESCRIPTION ITEM DESCRIPTION

1 Input-level metered information icon 9 Information icon

2 Configuration wheel 10 Receptacle icon

3 Bar graph of input current 11 Sensor icon

4 Active alarm 12 Alarm icon

5 Active warning 13 Real Power (Watts)

6 Temperature 14 Unit identification

7 Current 15 Voltage

8 Energy 16 Voltage phase

17 Unit identifier

Table 4.4 PDU Level View Descriptions

NOTE: On the PDU level, the BDM device displays temperature in Celsius or Fahrenheit if a temperature sensor isattached.

NOTE: The unit identification always shows 1 if connected to a single rack PDU, or shows all units (up to four) ifconnected to a rack PDU array.

Vertiv | RPC2™ Communications Module Installer/User Guide | 39

Page 44: RPC2 Communications Module User Manual

Figure 4.6 PDU System Information Screen

To view PDU system information: 

1. Use the scroll button to highlight the Information icon.

2. Press the scroll button to display the PDU model number, serial number, firmware version, power rating andnumber of receptacles.

NOTE: The energy measurement (#8 in the PDU Level View Descriptions table) reaches a display limit at 99.99 MW-h.The unit's energy display must be reset to restore the displayed values.

4.4.2 RPC BDM contrast

The RPC BDM is factory set to be easily viewed in common lighting conditions. Contrast adjustment may improve screenlegibility in a highly lit environment.

Figure 4.7 Contrast Screen

NOTE: Both lighting conditions and high-temperature operation can affect contrast and, as a result, require anadjustment.

To adjust the contrast of the RPC BDM: 

1. Use the scroll button to highlight the Information icon.

2. Press the scroll button to display the Information screen. Use the scroll button to highlight the Contrast iconand press the scroll button to display the Contrast screen.

Vertiv | RPC2™ Communications Module Installer/User Guide | 40

Page 45: RPC2 Communications Module User Manual

3. Use the scroll button to highlight the up or down arrow keys, then press the scroll button to increase ordecrease the contrast. When the contrast of the pattern on the screen is satisfactory, use the scroll button tohighlight the Return icon and press the scroll button to return to the Information screen.

4.4.3 Active alarms

The most recent alarms appear at the top of the list. Use the device's scroll button to review the list of active alarms.

Figure 4.8 Alarm List Screen

To view active alarms: 

1. Use the scroll button to highlight the Alarm icon.

2. Press the scroll button to display a list of active alarms.

3. Use the scroll button to highlight the up or down arrow keys to highlight an alarm.

4. Use the scroll button to highlight the Play button and press the scroll button to display the alarm details.

4.4.4 Sensors

The default label is the sensor's serial number, but it can be changed through the web interface.

Figure 4.9 Sensor List Screen

To view sensor information: 

1. From the PDU level, use the scroll button to highlight the sensor icon and then press the scroll button to displaya list of sensors in the order of their identification number.

Vertiv | RPC2™ Communications Module Installer/User Guide | 41

Page 46: RPC2 Communications Module User Manual

2. Use the arrow keys to highlight a receptacle and press the scroll button to select it.

3. Highlight the Play button and press the scroll button to display the sensor information. The following exampleshows temperature sensors and one humidity sensor.

Figure 4.10 Sensor Information Screen

Branch level

The availability of branch information depends on the capabilities of the PDU. Branch information and PDU information arethe same for rack PDUs without branch management; that information is seen at the PDU view level. The following figure isan example having data for Branch A, with one of two branches on PDU #1 communicating with the RPC BDM unit. You canview the information by selecting a branch. For MPH2 PDUs, the branch level is represented by alphabetical characters. ForMPH and MPX PDUs, the branch level is represented by numerical characters.

Figure 4.11 Branch PDU Level View

ITEM DESCRIPTION ITEM DESCRIPTION

1 Branch-level information icon 7 Information icon

2 Current bar graph 8 Real Power (Watts)

Table 4.5 Branch Level View Descriptions

Vertiv | RPC2™ Communications Module Installer/User Guide | 42

Page 47: RPC2 Communications Module User Manual

ITEM DESCRIPTION ITEM DESCRIPTION

3

Branch circuit-breaker status icon.

I = closed circuit breaker

O =open circuit breaker

9 Branch ID

4 Amperage (A) 10 Voltage (V)

5 Apparent Power (VA) 11 Branch identifier

6 Return icon

To view data for a branchmodule:

1. Use the scroll button to highlight a letter in the lower-left corner.

2. Press the scroll button to display the data for the selected branch module.

Receptacle level

The availability of receptacle information depends on the capabilities of the rack PDU. The following figure is an example ofdata for Receptacle 2, which is one of six receptacles on Branch A of PDU 1 that are communicating with the RPC BDM unit.

Figure 4.12 Receptacle Level View

ITEM DESCRIPTION ITEM DESCRIPTION

1 Component Identification 7 Information icon

2 Current bar graph 8 Real Power (Watts)

3 Receptacle Power Status 9 Receptacle ID

4 Amperage (A) 10 Voltage (V)

5 Apparent Power (VA) 11 Receptacle identifier

6 Return icon

Table 4.6 Receptacle Level View Descriptions

To view data for a receptacle:

1. Use the scroll button to highlight a receptacle number in the lower-left corner.

2. Press the scroll button to display the data for the selected branch module.

Vertiv | RPC2™ Communications Module Installer/User Guide | 43

Page 48: RPC2 Communications Module User Manual

Figure 4.13 Receptacle Information Screen

To view receptacle level information: 

1. Select the Information icon in the receptacle view.

2. Select the receptacle to be viewed.

3. Use the RPC BDM’s scroll button to highlight a receptacle in the list. If a scroll bar appears on the right, use thepage up and page down icons to display the rest of the list.

4. Press the scroll button to select the highlighted receptacle. The screen displays the PDU Explorer view for theselected receptacle.

4.4.5 Types of data available at PDU, branch and receptacle levels

The following table shows the types of data available at each level. Branch and Receptacle data may vary depending on therack PDU capabilities.

DATA AVAILABLE PDU BRANCH RECEPTACLE

Bar graph of power utilization Yes (each phase) Yes Yes

Amperage of selectedmodule Yes (each phase) Yes Yes

Voltage of selectedmodule Yes Yes Yes

Wattage of selectedmodule Yes Yes Yes

VA of selectedmodule No Yes Yes

State: On/Off Not applicable Yes Yes

Table 4.7 Monitoring Data Available on the RPC BDM Via the PDU Explorer

4.4.6 Viewing active events

When an event is detected, the display switches to the PDU view with an Active Events icon in the lower-right corner of thescreen. The information view displays a list of events with icons to indicate severity.

To view an active event: 

1. Scroll to the Active Events icon, then press the scroll button to select it.

2. Scroll to an event, then press the scroll button to view the event's details.

Vertiv | RPC2™ Communications Module Installer/User Guide | 44

Page 49: RPC2 Communications Module User Manual

5 LIEBERT® SN™ SENSOR INSTALLATION (OPTIONAL)The RPC2 module is designed to monitor Liebert® SN™ integrated and modular sensors:

• Integrated sensors are attached to a single cable. These Liebert® SN™ sensors are available in several varieties,including single or multiple temperature sensors.

• Modular sensors are separate probes shipped with a cable for connection to the RPC2 communications module.

• Liebert® SN™ sensors can be connected in a string, including a combination of modular and integrated sensors.

• The maximum string length is 65.6 ft. (20 m).

• The maximum number of probes that can be connected to a Vertiv™ MPH™ or MPX™ is 10. Refer also to thequick-start guides for integrated (SL-20840) and modular (SL-52405) sensors. See the sensor quick-startguides for details on the number of probes in each type of sensor. Liebert® SN™ sensors can be placed in anyarea, for example, in a Knurr® rack, to monitor conditions such as temperature and humidity levels or the stateof a contact.

5.1 Record the Sensor Address

During configuration, the web interface displays the addresses of all connected sensors. You need to be able to identifywhich address belongs to each sensor. Be sure to make a note of each sensor’s address before mounting and connectingsensors. The sensor address can be found on the sensor itself (modular sensors) or the RJ45 end of the sensor cable(integrated sensors).

5.2 Mount the Sensor

The sensor may be mounted in a Vertiv™ rack or another type of rack. For temperature and humidity sensors, be sure tochoose a place with unobstructed airflow, for example, on the rack door. Check to make sure the sensor does not cover anyvents that might impede airflow.

Search for Liebert®SN™ Sensors at www.VertivCo.com and refer to the modular or integrated sensor quick-start guide fordetailed instructions on each of the following four options:

• Mount on a Knurr rack frame or 19-inch rail

• Mount the sensor on the rack door

• Mount the sensor on a flat surface

• Mount the sensor on the rack rails

5.3 Connect the Sensor

Each sensor is shipped with a cable to connect to the Liebert® SN™ port on your Liebert® product. The RPC2 must beinstalled before the sensor can be connected.

ICON NAME DESCRIPTION

Liebert® SN™ Port Use this port ONLY to plug in optional sensor accessories.

Table 5.1 Liebert® SN™ Port Description

To connect the sensor:

1. After securely mounting the sensor, determine the location of the Liebert® SN™ port, identified by the icon inthe previous table.

2. Insert the RJ45 connector end of the sensor cable into the Liebert® SN™ port on the Liebert® product.

NOTE: When adding sensors to a string, disconnect the entire string from the sensor port and wait one minute, thenreconnect the string to the port. When the string is reconnected to the sensor port, all information is retained forsensors existing in a string prior to adding the new sensor.

Vertiv | RPC2™ Communications Module Installer/User Guide | 45

Page 50: RPC2 Communications Module User Manual

5.4 Confirm the Module Change

After connecting the sensor, you must acknowledge the change via the web interface before the sensor can be monitored.The viewing area in the right pane displays the data in the following table. Module changes must be acknowledged beforeremote management is enabled or disabled.

ELEMENT DESCRIPTION

Module Serial Number Displays the serial number for each listedmodule.

Module Type Indicates the kind of component, for example, auxiliary sensor string.

Added Indicates amodule is connected to the rack PDU.

Removed Indicates amodule is disconnected from the rack PDU.

Table 5.2 Module Change Descriptions

To confirm themodule change: 

1. From the System tab, click Device Change in the left pane to display a list of the added or removed PDUcomponents that are not acknowledged.

2. Click the Acknowledge icon to accept the changes.

NOTE: After a module is disconnected from the rack PDU and the change is acknowledged in the Device Changewindow of the System tab, the module’s information is removed from the system. If that same module is laterreinstalled, it must be reconfigured as a new module. Acknowledge the addition of the reconnected module in theModule Changes option of the Control tab, then make other configuration changes as needed.

Vertiv | RPC2™ Communications Module Installer/User Guide | 46

Page 51: RPC2 Communications Module User Manual

6 APPENDICESThe following tables display electrical and physical specifications and also communication interfaces and agency approval.

Appendix A: Specifications

PARAMETER LIMITS

Voltage 7-12 VDC

Power 6.5W Maximum

Operating Temperature Range, 41 to 140 (5 to +60) °F (°C)

Ambient Storage Temperature Range, -40 to 140 (-40 to +60) °F (°C)

Relative Humidity 0% to 95% (non-condensing)

Maximum Operating Altitude, ft. (m) 6560 (2000)

Dimensions, WxDxH, in. (mm) 4.0 x 0.84 x 1.78 (101.6 x 21.3 x 45.2)

Table 6.1 Electrical and Physical Specifications

COMMUNICATION PORTS DESCRIPTION

Ethernet 2 (one 10/100/1000Mbps Port; one 10/100Mbps Port)

I2C 1 (interface to the RPC BDM)

EIA562 RS-232 1 (interface to Avocent appliances)

1-Wire 1 (interface to Liebert 1-wire sensors)

USB 1 (supports memory stick configuration)

Safety Standards

(Vary by model and region)

IEC 60950-1:2005 (2nd Edition) +Amendment 1:2009

CSAC22.2 NO. 60950-1-07 (2nd Edition) +Amendment 1:2009

UL 60950-1 (2nd Edition) +Amendment 1:2009

IECEECBFull Certification Scheme

EMC Standards

(Vary by model and region)

FCC Class A, Part 15, Industrial

EN55022:2006+A1:2007, Class A, Industrial

EN55024:1998+A1:2001+A2:2003, Class A, Industrial

IEC61000-3-2:2006, IEC61000-3-3:1995+A1:2001+A1:2005

IEC61000-4-2/3/4/5/6/8/11

Agency Approvals (Vary by model and region) UL, cUL, CE, BV, PSE, CB, RoHS, REACH, WEEE

Table 6.2 Communication Interfaces and Agency Approval

Vertiv | RPC2™ Communications Module Installer/User Guide | 47

Page 52: RPC2 Communications Module User Manual

Appendix B: Troubleshooting

The following table contains recommended actions for troubleshooting.

CATEGORY ISSUE RECOMMENDED ACTION

ConfigurationThe USBmemory stick does not cause therack PDU to beep when first inserted.

Confirm the USB Type A connector is firmly connected to theMicro Type B adaptor.

Confirm thememory stick is not full.

Login

Login fails but the correct credentials wereentered.

If logging in as an administrator, confirm using the defaultadministrator credentials (admin/admin).

Delete the browser cache and restart the browser, then retype theIP address in the URL field. Login window may be slow to displaythe first time.

Session closes unexpectedly.Confirm the Inactive Session Timeout from the System-ManageProtocol window is configured with the desired value.

Firmware Update

Displays an error screen before the image isuploaded.

Restart the RPC2module and try again.

Networking disruption occurs in themiddle ofan update.

Browse to the refreshed URL and try again. The RPC2module andits devices are fully recoverable.

Power outage occurs in themiddle of anupdate.

Wait for restart of the RPC2module and try again. The RPC2module and its devices are fully recoverable.

Notification

A large error icon displays but the source of theerror is not found.

Check the Sensor window for errors caused by improperlyconfigured thresholds.

Acknowledge a device change, if any are pending.

Email and SMSFrom and To fields do notaccept entries.

Confirm the text string does not exceed 124 characters.

Settings

Settings change did not take effect.

The green checkmark must be clicked to save changes.

Confirm whether a power cycle or restart of the RPC2module isrequired.

When local time is configured for anMPH orMPX rack PDU, the time is incorrect after arestart or power cycle.

TheMPH andMPX rack PDUs do not support real-time clockhardware. Configure the time using an NTP server.

The SNMP community string is not accepted. Do not use a semicolon in the name.

Default SNMP community strings are notworking.

Confirm using the default ENPRackPDU_ROand ENPRackPDUfor read and write community strings.

Rack PDU Array

After login, not all devices’ measurements areshown.

Wait a few minutes until the rack PDU array is fully discovered andready to report all data.

The sibling RPC2module is not discovered.

Confirm the link cable is connected to the link port.

Disconnect the link cable to the upstream RPC2module, wait 30seconds and reconnect.

Perform a hardware reset of the upstream unit or remove andreinstall it to cause a power cycle.

General

Graphics don’t display correctly or showincomplete information.

Delete the browser cache and restart the browser. The loginwindow may be slower to display.

Increase the window size to view all tabs.

Check the browser compatibility in the firmware release notes.

Some features are not working correctly or areunavailable.

Confirm the device and agent firmware versions are the latestreleases from the System-Support-Devices window. Read theRPC2module release notes for a description of new features,changes and fixes. Perform a firmware update if needed.

Table 6.1 Troubleshooting

Vertiv | RPC2™ Communications Module Installer/User Guide | 48

Page 53: RPC2 Communications Module User Manual

CATEGORY ISSUE RECOMMENDED ACTION

Network Ports

The LAN facing RPC2module does not report avalid IP address in the subnet range, butdisplays 192.168.1.x on theMPH2 rackPDU onboard LCD or RPCBDM-1000module.

Confirm the LAN cabling is connected to the LAN port.

Confirm the link LED is solid green and the status LED is flashingyellow.

Disconnect the LAN cable, wait 30 seconds and reconnect.

Cannot access the link port using the clientcomputer.

Confirm the LAN cable is connected to the LAN port.

Confirm the computer’s network adaptor's IPv4 properties arecompatible with the RPC2module position in the array. See thelaptop IP settings for the RPC2module addresses.

Sensors are not discoverable.

Confirm the sensor cable is connected to the sensor port.

If adding a sensor to any existing string, make sure to click thediscover button on the sensor configuration window.

Confirm nomore than 10 sensors are connected to a single RPC2module.

Check that sensor cabling is routed away from the power andnetworking cables.

Read RPC2module technical bulletins about sensor compatibilityissues.

Serial PortThere is no serial communication with anAvocent® appliance.

Confirm serial cabling is connected to the serial port.

Confirm the correct serial adaptor is used.

Display Port

The BDM is not turned on.

Confirm the BDM cabling is connected to the BDM port.

For MPX rack PDUs, confirm themodules are also discovered. Ifnot, then check the integrity of module installation and examine thedatabus of theMPXPRC for possible debris bridging the traces.

No data is displayed for MPH2 rack PDUs.

If the BDM was previously used with an RPC-1000module, attachthe BDM to any RPC2module and perform an RPC2 firmwareupdate tomake it compatible. The compatible BDM firmwareversion is briefly displayed on the splash screen.

Vertiv | RPC2™ Communications Module Installer/User Guide | 49

Page 54: RPC2 Communications Module User Manual

Appendix C: Factory Default Settings

The following table displays the current factory default settings.

LEVEL SETTING DEFAULT VALUE

Settings

System Name System Name

Description Description

Contact Name Contact

Location Location

Temperature Display Celsius

SWOTP Scope Local

SWOTP Delay (seconds) 10

Audible Alarm Enabled

Time Format 12 hour

Network

Speed/Duplex Auto (1000Mbs/Full Duplex)

Host Name RPC2-551831G102C2015DEC150246

IPv4 DHCP

IPv6 DHCP

DNS

IPv4 Obtain DNS server automatically

IPv6 Obtain DNS server automatically

DNS Test Fully Qualified Domain Name

Time

External Time Source NTP Server

Time Server pool.ntp.org

Synchronize Rate Hourly

Messaging

Email Port 25

SMS Port 25

Consolidation Time (seconds) 60 (email and SMS)

Consolidation Event Limit (events) 10 (email and SMS)

Datalog

Enabled Yes

PDU Enabled

Branch Enabled

Receptacle Enabled

Logging Interval (minutes) 15

Manage Protocol

Velocity v.4 Server Enabled

SNMP Agent Enabled

SSH Support Enabled

Telnet Enabled

Web Server Enabled

Inactive Session Timeout 5minutes

Maximum Telnet Sessions 5

Table 6.1 Factory Default Settings

Vertiv | RPC2™ Communications Module Installer/User Guide | 50

Page 55: RPC2 Communications Module User Manual

LEVEL SETTING DEFAULT VALUE

SNMP

SNMP v1/v2 Enabled

SNMP Traps SNMPV1

SNMP UDPPort 161

SNMP UDP Port 162

Liebert Global Products MIB Enabled

Liebert MIB Traps Enabled

Authentication Traps Enabled

System Notify Trap Enabled

Heartbeat Interval 5 minutes

SNMPv3 Enabled

Web Server

Web Server HTTPS

HTTP Port 80

HTTPs Port 443

Refresh Interval (seconds) 30

Authentication Type Local

Credentials

AdminUsername: admin

Password: admin

PoweruserUsername: pwrusr

Password: pwrusr

ApplianceUsername: appliance

Password: rpc2k

PDU

Over Current Alarm Threshold

L1, L2, L3, N45%

Over Current Warning Threshold

L1, L2, L3, N40%

Under Current Alarm Threshold

L1, L2, L30%

Unbalanced Load Alarm Threshold 0%

Branch

Over Current Alarm Threshold 95%

Over Current Warning Threshold 90%

Under Current Alarm Threshold 0%

Vertiv | RPC2™ Communications Module Installer/User Guide | 51

Page 56: RPC2 Communications Module User Manual

LEVEL SETTING DEFAULT VALUE

Receptacle

State On

Over Current Alarm Threshold 95%

Over Current Warning Threshold 90%

Under Current Alarm Threshold 0%

Power Up State Restore

Power OnDelay 0 seconds

Power Cycle 8 seconds

Post On Delay 0 seconds

Post Off Delay 0 seconds

SWOTP Disable

Receptacle Criticiality Critical

Vertiv | RPC2™ Communications Module Installer/User Guide | 52

Page 57: RPC2 Communications Module User Manual

Vertiv | RPC2™ Communications Module Installer/User Guide | 53

Page 58: RPC2 Communications Module User Manual
Page 59: RPC2 Communications Module User Manual

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA

© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names,trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes noresponsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

590-1380-501A


Recommended