+ All Categories
Home > Documents > SECTION 26 00 10 BASIC ELECTRICAL REQUIREMENTS PART … Specs(7).pdf · BASIC ELECTRICAL...

SECTION 26 00 10 BASIC ELECTRICAL REQUIREMENTS PART … Specs(7).pdf · BASIC ELECTRICAL...

Date post: 23-Jul-2018
Category:
Upload: ledat
View: 216 times
Download: 0 times
Share this document with a friend
23
WISP January 23, 2018 Project No. 15033 SECTION 26 00 10 BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 Contract Documents: Sections of this division shall comply with Instructions to Bidders, General Conditions of the Contract for Construction AIA Document A201, Supplementary General Conditions, Division 1. General Requirements and other Contract Documents. 1.2 Intent of Documents: Labor, tools, materials, plant, transportation, taxes, related items, essential for installation of the Work. Systems complete and left in good operating condition. Apparatus, appliance, material, Work and accessories, reasonably inferable from Contract Documents, necessary to make Work complete and ready for operation. New equipment and material unless otherwise called for. Work shall be installed per written manufacturer's instructions. Notes or instructions included in the specifications and/or shown on any one drawing, apply where applicable, to all other drawings. Where there are discrepancies in the Contract Documents, the greater quantity, the greater quality and the greater total value shall be provided as part of the contract Work. 1.3 References to codes, specifications and standards called for in the Specification Sections and on the drawings mean the latest edition, amendment and revision of such referenced standard in effect on the date of these Contract Documents. 1.4 Code Compliance: The International Building Codes (2015), The International Mechanical Code (2015), The National Standard Plumbing Code (2015) and The National Electric Code (2014) as adopted by the State of Maryland and amended by County of Garrett. Occupational Safety and Health Administration (OSHA). Local Codes and Ordinances. Life Safety Code, NFPA 101. Contract Documents in excess of code/regulation requirements and not contrary to same. 1.5 Licensing: If required by local laws or ordinances, the Contractor shall hold a license to perform the Work as issued by the local jurisdiction. 1.6 Permits: Apply for and obtain required permits and inspections, pay fees and charges for same, including other service charges. 1.7 Fees: Apply for and pay fees and charges for utility meters and services. 1.8 GLOSSARY ACI American Concrete Institute AGA American Gas Association AGCA Associated General Contractors of America, Inc. AIA American Institute of Architects AISC American Institute of Steel Construction ABMA American Bearing Manufacturer's Association AMCA Air Moving and Control Association, Inc. ANSI American National Standards Institute BASIC ELECTRICAL REQUIREMENTS 26 00 10 - 1
Transcript

WISP January 23, 2018Project No. 15033

SECTION 26 00 10

BASIC ELECTRICAL REQUIREMENTS

PART 1 - GENERAL

1.1 Contract Documents: Sections of this division shall comply with Instructions to Bidders, General

Conditions of the Contract for Construction AIA Document A201, Supplementary General Conditions,Division 1. General Requirements and other Contract Documents.

1.2 Intent of Documents: Labor, tools, materials, plant, transportation, taxes, related items, essential forinstallation of the Work. Systems complete and left in good operating condition. Apparatus, appliance,material, Work and accessories, reasonably inferable from Contract Documents, necessary to make Work

complete and ready for operation. New equipment and material unless otherwise called for. Work shallbe installed per written manufacturer's instructions. Notes or instructions included in the specificationsand/or shown on any one drawing, apply where applicable, to all other drawings. Where there arediscrepancies in the Contract Documents, the greater quantity, the greater quality and the greater totalvalue shall be provided as part of the contract Work.

1.3 References to codes, specifications and standards called for in the Specification Sections and on thedrawings mean the latest edition, amendment and revision of such referenced standard in effect on thedate of these Contract Documents.

1.4 Code Compliance: The International Building Codes (2015), The International Mechanical Code (2015),The National Standard Plumbing Code (2015) and The National Electric Code (2014) as adopted by theState of Maryland and amended by County of Garrett. Occupational Safety and Health Administration

(OSHA). Local Codes and Ordinances. Life Safety Code, NFPA 101. Contract Documents in excess ofcode/regulation requirements and not contrary to same.

1.5 Licensing: If required by local laws or ordinances, the Contractor shall hold a license to perform the Workas issued by the local jurisdiction.

1.6 Permits: Apply for and obtain required permits and inspections, pay fees and charges for same, includingother service charges.

1.7 Fees: Apply for and pay fees and charges for utility meters and services.

1.8 GLOSSARY

ACI American Concrete InstituteAGA American Gas AssociationAGCA Associated General Contractors of America, Inc.AIA American Institute of ArchitectsAISC American Institute of Steel Construction

ABMA American Bearing Manufacturer's AssociationAMCA Air Moving and Control Association, Inc.ANSI American National Standards Institute

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 1

WISP January 23, 2018Project No. 15033

ARI Air-Conditioning and Refrigeration Institute

ASHRAE American Society of Heating, Refrigerating & Air ConditioningEngineers, Inc.

ASME American Society of Mechanical EngineersASPE American Society of Plumbing EngineersASTM American Society for Testing MaterialsAWSC American Welding Society Code

AWWA American Water Works AssociationCx CommissioningCxA Commissioning AgentFM Factory Mutual Insurance CompanyIBR Institute of Boiler & Radiation ManufacturersIEEE Institute of Electrical and Electronics Engineers

IRI Industrial Risk InstituteNEC National Electrical CodeNEMA National Electrical Manufacturers' AssociationNESC National Electrical Safety CodeNFPA National Fire Protection AssociationSBI Steel Boiler Institute

SMACNA Sheet Metal & Air Conditioning Contractors National AssociationUFPO Underground Facilities Protective OrganizationUL Underwriters' Laboratories, Inc.OSHA Occupational Safety and Health Administration

Approval/Approved Written permission to use a material or systemAs Called For Materials, equipment including the execution specified/shown in the

Contract DocumentsCode Requirements Minimum requirementsConcealed Work installed in pipe and duct shafts, chases or recesses, inside walls,

above ceilings, in slabs or below gradeExposed Work not identified as concealedEqual or Equivalent Equally acceptable as determined by Owner's Representative

Final Acceptance Owner acceptance of the project from Contractor upon certification byOwner's Representative

Furnish Supply and deliver to installed locationFurnished by Others Receive delivery at job site or where called for and installInspection Visual observations by Owner's site RepresentativeInstall Mount and connect equipment and associated materials ready for use

Labeled Refers to classification by a Standards AgencyOr Approved Equal Approved equal or equivalent as determined by Owner's

RepresentativeOwner's Representative The prime professional, an architect or engineerPrime Professional Architect or Engineer having a contract directly with the Owner for

professional services

Provide Furnish, install and connect ready for use

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 2

WISP January 23, 2018Project No. 15033

Relocate Disassemble, disconnect, and transport equipment to new locations,

then clean, test and install ready for useReplace Remove and provide new itemReview A general contractual conformance check of specified productsRoughing Pipe, duct, conduit, equipment layout and installationSatisfactory As specified in Contract DocumentsSite Representative Owner's inspector or "Clerk of Works" at the Work site

1.9 Equipment and Material Installation: Potable water systems and equipment shall be built according toAWWA Standards. Electrical equipment and systems shall meet UL standards and requirements of theNEC. Equipment and material for which there is a listing service shall bear a UL label. Materials shall havea flame spread rating of 25 or less and a smoke developed rating of 50 or less. Carefully checkmanufacturer's drawings and specifications as they affect their particular equipment; follow factory

instructions for roughing, installation, connection, filling, lubrication, testing, balancing, adjusting,alignment, wiring, and start-up operation.

1.10 Protection of Persons and Property: For requirements relating to this contract, refer to "GeneralConditions of the Contract for Construction". Contractor shall assume responsibility for constructionsafety. Provide as part of contract, trench or building shoring, scaffolding, shielding, dust/fume

protection, mechanical/electrical protection, special grounding, safety railings, barriers, and other safetyfeatures required to provide safe conditions for Workmen and site visitors.

PART 2 - SHOP DRAWINGS/PRODUCT DATA/SAMPLES

2.1 Submit seven copies of shop drawings within 30 days after Award, of items of equipment and materials tobe furnished and installed. Submission of shop drawings and samples shall be accompanied by a

transmittal letter, stating name of project and contractor, number of drawings, titles and other pertinentdata called for in individual sections.

2.2 Shop drawings shall be dated and contain: name of project; name of prime professional; name of primecontractor; description or names of equipment, materials and items; and complete identification oflocations at which materials or equipment are to be installed. Number each submittal by trade. Indicate

deviations from contract requirements on letter of transmittal.

2.3 Submittals shall be packaged based on Contract Document specification number. Submittals packaged byvendor, subcontractor grouping or other random assembly are not acceptable (i.e. if a vendor is supplyingconduit, lighting, panels and transformers, the submittal should be regrouped to be under the appropriatespecification number, not grouped together). The shop drawing submittal cover sheet should include the

specification section number.

2.4 Where shop drawings for similar items, such as fixtures, luminaires or other repetitive equipment areinvolved, submit in a bound brochure form. Individual piecemeal or incomplete submittals will not beaccepted. Similar items, (types specified) shall be submitted at one time.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 3

WISP January 23, 2018Project No. 15033

2.5 Each submittal will be returned to the contractor stamped or marked as follows:

Provide as Submitted: The contractor is advised that this means that fabrication, manufacture and/orconstruction may proceed providing the Work is in compliance with the Contract Documents.

Provide as Noted: The contractor is advised that this means that fabrication, manufacture and/orconstruction may proceed providing the Work is in compliance with the marked notations and the

Contract Documents. Also, the submittal should be corrected and resubmitted for final distribution.

Revise and Resubmit: The contractor is advised that this means no Work shall be fabricated,manufactured and/or constructed and that the contractor shall make a new submittal for the project. Product submissions marked with this ACTION or NOTATION will not be permitted on the site.

Rejected: The contractor is advised to revise and resubmit. Product submissions marked with thisACTION or NOTATION will not be permitted on the site.

2.6 In the case of shop drawings returned in the form of manufacturer's descriptive literature, catalog cutsand brochures stamped PROVIDE AS SUBMITTED or PROVIDE AS NOTED, the contractor shall beresponsible for distributing them in the field and to the subcontractors. If the returned shop drawings are

stamped REVISE AND RESUBMIT or SUBMIT SPECIFIED ITEM, the contractor shall submit new copies ofcomplete shop drawings revised to show compliance.

2.7 Shop drawings will be given a general review only. Corrections or comments made on the shop drawingsduring the review do not relieve contractor from compliance with requirements of the drawings andspecifications. Shop drawing check is intended solely for review of general conformance with the designconcept of the project and general compliance with the information given in the Contract Documents.

The contractor is responsible for: confirming and correcting quantities; checking electrical characteristicsand dimensions; selecting fabrication processes and techniques of construction; coordinating his Workwith that of other trades; and performing his Work in a safe and satisfactory manner.

2.8 Submit operating and maintenance manuals and parts lists.

PART 3 - EXECUTION

3.1 Equipment Arrangements: Since equipment of equal capacity is not necessarily of same arrangement, sizeor construction, the Contract Documents are prepared on basis of one manufacturer as "designequipment", even though other manufacturers' names are mentioned. If contractor elects to useequipment other than "design equipment" which differs in arrangement and size: submit detailed

drawings, indicating proposed installation of equipment. Show maintenance clearances service removalspace required, and other pertinent revisions to the design arrangement. Make required changes in theWork of other trades, at no increase in contract. If required, provide larger motors, and equipment,additional control devices, valves, fittings and other miscellaneous equipment required for properoperation, and assume responsibility for proper location of roughing and connections by other trades. Ifrevised arrangement submittal is rejected, revise and resubmit, or submit specified item which conforms

to Contract Documents.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 4

WISP January 23, 2018Project No. 15033

3.2 Trade Coordination: Install Work only after coordination with other trades. In general, each trade shall

coordinate and route its Work as close to ceiling deck as possible to permit: Ceiling heights as called for. Location of exposed or finish elements as shown on architectural reflected ceiling plans. Access to servicepoints. Crossing of piping, ductwork and conduits. Convenient removal of at least one 2' x 4' ceiling tilewithin each space or every 200 square feet of area for access to above ceiling components.

Coordination and Work required to accomplish above shall be provided as part of the contract Work with

no additional cost to the owner. Work to include: Offset of piping, ductwork and conduits as required(between rooms). Routing changes within rooms or spaces to avoid conflicts.

3.3 Substitutions: Refer to Supplementary General Conditions. The design equipment called for is therequired standard of quality and function. If contractor desires to bid on another kind, type, brand, ormanufacturer of material or equipment other than those named in specifications; submit complete

information in detailed tabulated form, comparing (item-for-item)material or equipment offered withdesign material or equipment. Include sufficient information to permit quick and thorough comparison,and include performance curves on same basis, capacities, power requirements, controls, materials, metalgauges, finishes, dimensions and weights of major parts. Owner's Representative shall be the sole judgewhether or not to accept proposed substitution.

3.4 Storage and Protection of Materials: Refer to General Conditions of the contract for construction. Storematerials: on dry base, at least 6 in. above ground or floor; in orderly manner so as not to interfere withother Work or obstruct access to buildings or facilities; with waterproof/windproof covering. Remove andprovide special storage for items subject to moisture damage; with protection against theft or damagefrom any cause; replace items stolen or damaged, at no cost to Owner.

PART 4 - OBSTACLES, INTERFERENCE COORDINATION AND ROUGHING

4.1 Obstacles, Interference Coordination and Roughing: Provide Work in compliance with general designarrangement. Install Work substantially as called for. Before installing, verify exact location andelevations at Work site. DO NOT SCALE plans. Due to small scale of drawings, it is not possible to indicateoffsets, fittings, changes in elevations and interferences. Make necessary changes in contract Work andequipment locations as part of contract to accommodate Work to obstacles and interferences

encountered. If field conditions, details, changes in equipment on shop drawing information require animportant rearrangement, report same to Owner's Representative for review. Obtain written approval formajor changes before installing. Submit five copies of drawings, detailing all such deviations or changes.

4.2 Interference: Install Work so that items are operable and serviceable. Eliminate interference withremoval of coils, motors, filters, belt guards and/or operation of doors. Provide easy, safe and code

mandated clearances at controllers, motor starters, valve access, and other equipment requiringmaintenance and operation.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 5

WISP January 23, 2018Project No. 15033

4.3 Coordination: Coordinate Work with other trades and determine exact route or location of each duct,

pipe and conduit before fabrication and installation. Coordinate with architectural drawings. Obtain fromOwner's Representative exact location of equipment in finished areas, such as thermostat, fixture andswitch mounting heights and equipment mounting heights. Obtain and coordinate Work with architectand architectural reflected ceiling plans. Mechanical and electrical drawings show design arrangementonly for diffusers, grilles, registers, air terminals, lighting fixtures, sprinklers, speakers and other items. Donot rough-in contract Work without reflected ceiling location plans.

4.4 Roughing: Before roughing for equipment furnished by Owner or in other Divisions, obtain from Ownerand other contractors, approved roughing drawings giving exact location for each piece of equipment. Donot "rough-in" services without final layout drawings approved for construction. Cooperate with othertrades to insure proper location and size of connections to insure proper functioning of systems andequipment. For equipment and connections provided in the contract, obtain equipment roughing

drawings and dimensions in ample time, then prepare roughing-in drawings. If such information is notavailable in time, obtain an acknowledgment in writing, then make special arrangements as required withOwner's Representative.

4.5 Concealment: Conceal contract Work above ceilings and in walls, below slabs, underground andelsewhere throughout building. If concealment is impossible or impractical, notify Owner's

Representative before starting that part of the Work and install only after his review. In areas with noceilings, install only after Owner's Representative reviews and comments on arrangement andappearance.

4.6 Chases, Recesses and Openings in New Construction: Certain chases, recesses, openings, shafts, and wallpockets will be provided as part of general building construction plans and specifications. Contractors formechanical and electrical Work shall provide other openings required for contract Work, and check

architectural and structural design and shop drawings to verify correct size and location for openings,recesses and chases in general building construction Work. Supply information in ample time, giving sizeand exact location, furnishing templates if required. Assume responsibility for correct and final locationand size of such openings. Rectify improperly sized, improperly located or omitted chases or openingsdue to faulty or late information or failure to check final location. Provide required sleeves and inserts ofmaterial and type specified. Set sleeves and inserts in place ahead of new construction, securely fastened

during concrete pouring. Correct, by drilling, omitted or improperly located sleeves. Assumeresponsibility for Work and equipment damaged during course of drilling. Plug abandoned sleeves asdirected. Provide angle iron frames where openings are required for contract Work, unless provided bygeneral construction contract.

4.7 Cutting and Patching: Include cutting and patching Work in this contract. Refer to "General Conditions of

the Contract for Construction", for additional requirements. Cut and drill from both sides of walls and/orfloors to eliminate splaying. Cut openings in prefabricated construction units in accordance withmanufacturer's instructions. Replace units which are improperly cut or drilled. Take care at vapor barriersand at insulation systems. Reseal/re-patch such barriers to be airtight to occupied side of insulation. Clean up any debris or insulation above ACT ceilings or in occupied spaces.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 6

WISP January 23, 2018Project No. 15033

4.8 Supports: Provide required supports, beams, angles, hangers, rods, bases, braces, and other items to

properly support contract Work. Supports shall meet the approval of the Owner's Representative. Modify studs, add studs, add framing or otherwise reinforce studs in metal stud walls and partitions asrequired to suit contract Work. If necessary in stud walls, provide special supports from floor to structureabove. Provide heavy gauge steel mounting plates for mounting contract Work. Wood not approved. Mounting plates shall span two or more studs. Size, gauge, and strength of mounting plates shall beconsistent with equipment size, weight, and required rigidity.

4.9 Concrete Bases: Provide concrete bases for floor mounted equipment. Provide 3000 lb. concrete,chamfer edges, trowel finish; securely bed to floor by roughening slab and coating with cement grout. Bases 4 in. high unless otherwise called for: shape and size to accommodate inside equipment, 6 inch highreinforced pad for exterior equipment. 6 inches beyond equipment footprint, all sides. Set anchor boltsin sleeves before pouring and, after anchoring and leveling, fill equipment bases with grout.

4.10 Waterproofing, Flashing, Caulking, Sealing, Fire Stopping

Opening through roofs: Flashed in manner not to affect roof guarantee or bond. Engage qualified roofingcontractor, as part of contract. Provide nonferrous flashing pieces, skirts, hoods and collars as required tomake ducts, pipes, conduits, and other penetrations watertight. Where curbs are called for with respect

to rectangular openings in roofs, flashing will be done by roofing trade unless specifically indicatedotherwise. Caulked and waterproofed, with additional material so as to seal airtight and watertight.

Opening through outside walls: Provide neoprene clamping/expanding seals; make: Link Seal, Calpico, orcaulked by fill ing space between pipes and sleeves with approved non-hardening caulking compound,from inside and outside, before backfilling, or special waterproof construction. Guaranteed thoroughlywatertight.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 7

WISP January 23, 2018Project No. 15033

Fire stopping for pipe, conduit and duct openings through fire or smoke rated wall and floor assembliesand for duct openings through non-rated floor assemblies. Provide materials and products listed orclassified by an approved independent testing laboratory for "through-penetration firestop systems". Thesystem shall meet the requirements of "Fire Tests of Through-Penetration Firestops" designated ASTME814. Provide firestop system seals at locations where piping, tubing, conduit, electrical busways/cables/wires, ductwork and similar utilities pass through or penetrate fire rated wall or floor assembly. Provide

intumescent, non-curing fire stop putty at each end of conduit sleeves which pass thru fire ratedassemblies. Putty to be installed prior to substantial completion and reinstalled as required as additionalwiring is installed within sleeves. Provide removable/reusable intumescent flexible fire blocks at largeropenings for cable tray or bus duct passing through rated assemblies. Provide new or retro-fit stylethrough wall assemblies at rated partitions along cable pathways. Systems shall be UL listed up to 4 hourrated, low air leakage, plenum rated and sized for cable bundles being installed. Adjustable doors allow

for adding or removing cables. The minimum required fire resistance ratings of the wall or floor assemblyshall be maintained by the firestop system. The installation shall provide an air and watertight seal. Themethods used shall incorporate qualities which permit the easy removal or addition of electrical conduitsor cables without drilling or use of special tools. The product shall adhere to itself to allow repairs to bemade with the same material and to permit the vibration, expansion and/or contraction of any itemspassing through the penetration without cracking, crumbling and resulting reduction in fire rating.

Penetration openings shall be as small as possible. Make: Hilti Firestop Systems, Dow Corning FirestopSystem Foams and Sealants, Nelson Electric Firestop System Putty, CKL and WRP, 3M Brand Fire BarrierSystem.

4.11 Access Panels: General contractor shall provide access panels. Furnish in ample time one set ofarchitectural black and white prints with size and approximate location of access panels marked thereon. Bear cost of construction changes necessary due to improper information or failure to furnish information

in ample time.

4.12 Painting: Prime coat and paint exposed pipe, fittings, conduit, supports, platforms, equipment and othercontract Work except those items with a factory finish. Prime and finish materials shall be of the samemanufacturer. Paint materials shall be durable, washable and suitable for each application. Number ofcoats and paint types shall be as recommended by the manufacturer. Deliver materials to the site in

original, new and unopened containers. Labels shall display name of materials, stock number, federalspecification number and application instructions.

4.13 Freezing and Water Damage: Take necessary precautions with equipment, systems and building toprevent damage due to freezing and/or water damage. Repair or replace at no change in contract, suchdamage to equipment systems and building. Perform first seasons winterizing in presence of Owner's

operating staff.

4.14 Electrical Equipment Connections: Provide complete power connections to electrical equipment. Providecontrol connections to equipment as called for. Provide heavy duty NEC rated disconnect ahead of eachpiece of equipment. Ground equipment per NEC. Locate switches, controls and wiring as called for.

Provide for Owner furnished equipment, connect complete and ready for use, including power andcontrol connections as required. Refer to manufacturer's drawings/specifications for requirements.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 8

WISP January 23, 2018Project No. 15033

PART 5 - ELECTRICAL IDENTIFICATION

5.1 Provide identification for panels, contactors, transformers, disconnects, and starters. Indicate byengraved plastic nameplate, ½ in. high letters and numbers, on cover of equipment. Label with numbersand letters as shown on plans. If no numbers or letters are designed, then label with name of equipmentand device served or protected. Punch type "stick-on" tags shall not be used.

5.2 Identify electric panels to conform with designations called for. Provide ½ in. panel identification, legibleand permanent, outside and inside. Permanently identify inside and indicate the control or feeder circuitbreaker number and panel supplying the electric panel.

5.3 Provide circuit distribution chart, permanently mounted inside each panel under transparent shield ascalled for. Copies of each circuit distribution chart identified by the panel shall be included in the

maintenance manual.

5.4 A permanent tag indicating the feeder panel number and circuit breaker number shall be affixed to onewire in each switch, toggle or disconnect.

5.5 Circuits in a panel shall be permanently labeled. Numbers affixed to the inside cover, not to the breakers.

PART 6 - CLOSEOUT

6.1 Testing of Three Phase Equipment or Special Receptacles: Test 3-phase equipment or special receptaclesfor proper voltage, phase, polarity, and grounding. Phase rotation of three phase receptacles shall betested; use a phase sequence meter. Achieve clockwise rotation from ground, A-B-C phase.

Testing of Grounding and Voltage: Check phase to phase, phase to neutral, phase to ground voltage. Usea 600 volt V-O-M. Check ground pin to ground continuity.

6.2 Test Report(s): Submit test report(s) for review prior to substantial completion. List testing procedure,equipment and Model No. used, and deficiencies corrected for each test procedure.

6.3 Owner Instructions: Before final acceptance of the Work, furnish necessary skilled labor to operatesystems for a period of not less than three (3) days. Instruct designated person on proper operation, careof systems/equipment. Repeat instructions, if necessary. Obtain written acknowledgment from personinstructed, prior to final payment. Contractor is fully responsible for systems until final acceptance, eventhough operated by Owner's personnel, unless otherwise agreed in writing. List operating, maintenanceand starting precaution procedures to be followed by Owner for operating systems and equipment.

Provide digital video recording of instructions for systems called for.

6.4 Provide a complete CD copy of all installed software for all equipment and systems. Provideadministrative user name, password and all other software keys required to access, modify and setparameters.

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 9

WISP January 23, 2018Project No. 15033

6.5 Instruction Portfolio: Prepare three (3) instruction and maintenance portfolios. Include one copy each of

approved shop drawings, wiring diagrams, piping diagrams, spare parts lists, manufacturer's instructionsand balance reports. Include typewritten instructions, describing equipment, starting/operatingprocedures, emergency operating instructions, precautions and recommended maintenance procedures. Include name, address, and telephone number of supplier, manufacturer’s representative and serviceagency for all major equipment items. Bind above items in a three ring binder with name of project onthe cover. Deliver to Owner's Representative for review before request for final acceptance. Obtain

written acknowledgment from person instructed, prior to final payment.

6.6 Record Drawings: Utilities below grade: Record drawing data, keep accurate records of final location andinverts of outside underground services and main utilities beneath grade and below floors. Takedimensions from given, fixed bench mark, such as corner of building. Electrical Record Drawing data shallbe provided to the Owner for power and light, fire alarm systems, exit light systems, emergency light

systems, communications, data and other systems on the original contract documents and adjustmentsmade via ASI, change order or coordination drawings. Neatly and clearly indicate record drawing data. Pay cost of making required corrections. Provide scanned PDF copies and files.

6.7 Transfer record drawing data to the building CAD drawing files. Provide one full size set of the correctedrecord drawings and a CD with electronic copy of the CAD drawing files and PDF plot files to the owner.

END OF SECTION

BASIC ELECTRICAL REQUIREMENTS26 00 10 - 10

WISP January 23, 2018Project No. 15033

SECTION 26 50 00

ELECTRICAL SPECIFICATION

PART 1 - GENERAL

1.1 The scope of work is to provide labor, materials, services, supplies, tools, equipment, permits,

transportation, and facilities necessary to furnish and install the complete and operable systems as calledfor.

1.2 Refer to specification section 26 00 10 for Basic Requirements of the contract for this work.

1.3 The complete installation shall be in compliance with the applicable latest or accepted edition of the

International Building Code as adopted by the State of Maryland and amended by the Town of McHenry, NFPA, and other applicable rules and regulations as prescribed by the administrative authority.

1.4 These drawings are diagrammatic only and indicate the general arrangement of systems and equipment. Basic design concepts must be followed or bettered. Do not scale drawings, field verify dimensions andfield conditions.

1.5 It is not intended that drawings show every detail. Provide offsets, changes in elevation and itemsnecessary for proper installation and operation of system so that work will be complete and ready foroperation.

1.6 Notes or instructions included in the specifications and/or shown on any one drawing, apply whereapplicable, to all other drawings.

1.7 Coordinate work with other trades, building conditions and structural conditions prior to installation.

1.8 Coordinate utility service work with local utility companies, general contractor, building conditions andsite conditions prior to installation. Provide advance coordination as required for timely connections oftemporary and permanent services. Contact utility companies prior to submission of bid. Include all

utility fees and costs related to this project in bid.

1.9 In the event of a discrepancy, immediately notify the owner's representative. Do not proceed withinstallation in areas of discrepancy until such discrepancies have been resolved.

1.10 Starters, contactors and controllers shall comply with NEMA Standards, short circuit protection shall be

time delay manual reset type, thermal overloads shall be manual reset type, pilot lights shall be six voltextended life. Each starter subject to electrical interlock or automatic control shall have the necessaryauxiliary contacts, equip with self-contained fused and grounded 120 volt control transformers.

1.11 Manual starters shall be toggle operated, single pole line to neutral, two pole line to line, flush mountedunless otherwise called for.

ELECTRICAL SPECIFICATION26 50 00 - 1

WISP January 23, 2018Project No. 15033

1.12 Install work only after coordination with other trades. In general, each trade shall coordinate and route

its work as close to ceiling deck as possible to permit: Ceiling heights as called for. Location of exposed orfinish elements as shown on architectural reflected ceiling plans. Access to testing and inspection servicepoints. Crossing of piping, ductwork and conduits. Convenient removal of at least one 2'x4' ceiling tilewithin each space or every 200 square feet of area for access to above ceiling components.

1.13 Coordination and work required to accomplish the above shall be provided as part of the contract work

with no additional cost to the owner. Work to include: Offset of piping, ductwork and conduits asrequired (between rooms). Routing changes within rooms or spaces to avoid conflicts.

PART 2 - PRODUCTS

2.1 Conduits shall be EMT, RMC or IMC metal conduit, PVC Conduit for Service entrances and site lighting

underground. Wiring installed in conduits shall be copper, THHN/THWN for up to #4 awg, THW or XHHWfor #3 AWG and larger. Aluminum conductors permitted for service entrance as called for. Minimum wiresize shall be #12 AWG. Conduit manufacturers Republic, General Electric, Triangle, Carlon. Wiremanufacturers American, General Cable, Capitol, Alcoa. Provide approved steel set screw fittings. Providesteel compression fittings in damp or wet locations.

2.2 Provide approved steel, clamps, straps and conduit hangers as required.

2.3 Wiring concealed in dry wall construction and above finished ceilings may be type AC cable, #12 minimum,copper conductors, with full size insulated ground conductor and approved connectors. Fire alarm wiringshall be #16 AWG minimum AC cable with red painted metal sheath. Provide metal nail plates wherecables are within 1-1/4 inch of face of framing members. AFC type "HCF90", equivalent by Alflex orCapitol.

2.4 Dimmers to be Decora plate, 1000 watt, slide type with off switch, single or 3 way type as called for,provide as solid state type with radio interference filter, non-illuminated type, color to match devices,gang with devices where shown. Leviton, General Electric, Pass & Seymour, Hubbell or Skylark controls.

2.5 Flush mounted exterior wall device boxes shall be flush mounted, deep metal box with gasketed cover and

weather proof-in-use rated cover. UL listed as complete assembly. Arlington Industries.

2.6 Wiring concealed in dry wall construction and above drywall ceilings may be non-metallic sheathed cable,Type "NM" type THHN insulated conductors in PVC sheath, bare ground conductor, copper conductors. Two or three conductor size as called for. #14 AWG for 15 Amp circuits, #12 AWG for 20 Amp circuits, #10AWG for 30 Amp dryer circuits #6 AWG for 50 Amp range circuits other circuits as called for. Fire alarm

cabling shall be limited energy fire alarm cable, minimum 16 AWG. Provide metal nail plates where cablesare within 1 1/4 inch of face of framing members. Secure with insulated cables. Secure within 6 inch ofnon-metallic boxes. Provide cast metal type "NM" connectors. Cable as Rome, General Cable as Rome"Romex"

2.7 Devices shall be as called for on symbol list. Install in metal box, sized for quantity of devices and wires

installed. Provide matching smooth, stainless steel plates. Devices as Leviton 1221 series switches, coloras selected by Architect, Leviton 5800 series receptacles, color as selected by Architect. Hubbell, Pass andSeymour or Leviton. Pass + Seymour lined plates not acceptable.

ELECTRICAL SPECIFICATION26 50 00 - 2

WISP January 23, 2018Project No. 15033

2.8 Non-metallic device boxes, not permitted.

2.9 Concrete Floor Boxes: UL Scrub Water Standard Adjustable, galvanized stamped steel box with separatelyadjustable bronze floor ring assembly; in concrete slab. Rough leveling accomplished by screws located ateach of four corners; final leveling by edge ring. Suitable cover plate assembly with hinged access coversfor duplex convenience outlet device. Covers and hinge assemblies to be gasketed and watertight. Heightof box to be suitable for depth of floor construction. Provide auxiliary items of equipment required for

leveling after installation of box and for mounting devices. Where surface mounted service fittings arecalled for, they shall be constructed of cast satin aluminum with required power or low tension deviceplates and accessories. Provide carpet flange fittings for outlets installed in carpeted areas. Floor plateshall be attached with three or more screws. Design Equipment: Steel City. Make: RACO, Thomas &Betts, Walkerduct.

2.10 Switchboards: Floor mounted, front access, NEMA 1, aluminum bus, full copper ground bus. IC groundbus where called for, ANSI 71 grey, ratings as called for, nominal 38" wide, 18" deep, 90" high. ITE, SquareD, General Electric, AS, ITE FC-1.

2.11 Lighting fixtures shall be as scheduled. Provide all required mounting, connection, and alignmentaccessories required for complete installation. Provide with “damp”, “wet”, “insulated ceiling” or other

ratings to meet conditions. All electronic ballast to have rating of less than 10% total harmonic distortion.

2.12 Exit and emergency lighting equipment shall be as scheduled.

X. Description: Universal mounted exit sign, brushed aluminum stencil face, matte black metalhousing, red panel, single or double face as specified, self-contained nickelcadmium battery power supply.

Manufacturer: LithoniaSeries: SignatureLamps: LED SeriesMounting: Surface, ceiling, pendant or wall mounted where noted or required.Notes: High Power FactorSubstitutes: Emergilite, Dual-lite, Lightalarms, Prescolite

BU. Description: Surface wall mounted battery unit with high-impact polycarbonate housing,white, dual integral heads and/or remote heads as called for, smooth corneredarchitectural design, 6 volt output.

Manufacturer: LithoniaSeries: 6ELM2

Lamps: (2) 8 watt halogen where called forMounting: Surface, wallNotes: Provide blocking.Substitutes: Dual-lite, Chloride

BU-0. Same as Type “BU”, except without heads.

ELECTRICAL SPECIFICATION26 50 00 - 3

WISP January 23, 2018Project No. 15033

EL. Description: Remote flood heads, thermoplastic, dual heads with common back plate. White on white or light surfaces, black on dark or brick surfaces.

Manufacturer: LithoniaSeries: PAR 36 SeriesLamps: (1) or (2) 8W 6 volt halogenMounting: Surface, wall

Substitutes: Emergency power from battery unit equipment.

2.13 Ceiling Mounted/High Wall Mounted Passive Infrared Motion Sensors: 24 VDC passive infrared sensorshall switch lighting on through separate power pack when a change in infrared heat radiated within thecontrolled space is detected. Unit shall turn lighting off when occupants leave control area after a user-adjusted time delay of 30 seconds to 30 minutes. Multi-element fresnel lens. Logic key/ON bypass.

Coverage 300, 1200, or 2000 sq. ft. as indicated on drawings - directional wide or standard angle, or 360degree high ceiling application, as indicated on drawings. Time delay and sensitivity adjustments shall beby dipswitches accessible from front of unit, without requiring removal of unit. Design Make & Model:Watt Stopper WPIR, CX-100 and CI-200 Series.

2.14 Dual Passive Infrared/Ultrasonic Motion Sensors: 24 VDC passive infrared and ultrasonic sensors shall

switch lighting on through a separate power pack when motion is detected within controlled space. Unitshall turn lighting off when occupants leave control area after a user adjusted time delay of 15 seconds to30 minutes. Multi-level fresnel lens. Ceiling or high wall mounted. Directional, wide angle, 2000 sq. ft.coverage. Time delay and sensitivity adjustments shall be by dipswitches accessible from front of unit,without requiring removal of unit. Design Make & Model: Watt Stopper DT-200.

Ultrasonic Occupancy Sensor: Sensor shall utilize ultrasonic omni-directional poppler technology to sense

occupancy. 24 VDC sensor shall switch lighting through separate power pack. Unit shall turn lighting offwhen occupants leave control area after a user adjustable time delay of 15 seconds to 15 minutes. Sensorsensitivity shall be adjustable. Unit shall have logic key/ON bypass. Coverage from 500 to 2000 sq. ft. or90 linear feet as indicated on drawings. Ceiling mounted. Time delay and sensitivity adjustments shall beby dipswitches accessible from front of unit, without requiring removal of unit. Design Make & Model:Watt Stopper WT Series.

Wall Switch Occupancy Sensor: 120/277 VAC operation. Built-in infrared sensor. Fresnel lens, 180degrees, 900 ft2 coverage. Sensitivity adjustable from 20% to 100%. Compatible with multi-levelswitching. Design Make: Wattstopper WS-200.

Sensor Power Pack: Unit shall provide 24 VDC operating voltage to 24 VDC sensors and shall be capable of

switching 20 amps of ballast load. Unit shall combine transformer and high-current relay in singlepackage. Design Make & Model: Watt Stopper.

2.15 Digital Timer Wall Switch: 120/277 VAC operation. Unit shall turn light on when on/off switch isactivated, and shall turn lights off after user adjustable time ranging from 5 minutes to 2 hours elapses. Unit shall enable user to manually turn off lights before on time expires. Unit shall enable user to

manually reset on time to start value before on time expires. Unit shall have 1-minute flash and beepwarning to alert user to on-time expiration. Back-lit LCD shall indicate time remaining until lights areturned off. Design Make: Watt Stopper TS Series.

ELECTRICAL SPECIFICATION26 50 00 - 4

WISP January 23, 2018Project No. 15033

2.16 Lighting Control Panel: Eight zone panel consisting of NEMA 1-rated enclosure (flush or surface mounted

as shown on drawings), relays, system clock, panel intelligence, power supply. Preprogrammed controlscenarios, seven day format with holiday scheduling, astronomic control, capability of integrating withexterior photocell. Non-volotile program memory. Eight universal switch inputs for low voltage switches,occupancy sensors, photocells, or other devices to control each relay. Push buttons for manual overrideof each relay. 120V power supply. Mechanically latching 20 amp relays with LED indicator and integralmanual override. Dimensions: 15" x 16.5", L x W x D. Design Equipment: Watts Stopper LP8 Peanut

Lighting Control Panel.

2.17 Low Voltage Switching: Compatible with lighting control panel. Low voltage momentary switch: 2 buttonwith 2 normally open 3 amp 28VAC contacts providing single-pole, double throw momentary operation. Top button ON. Bottom button OFF. Single gang cover to match material and colors of those for otherswitches. Design Make: Watt Stopper RS.

2.18 Automatic Control Switch: Compatible with lighting control panel. Operation as manual switch orautomatic control device when signaled by lighting control panel. When timed power interrupt signal isreceived from the lighting control panel, switch is commanded to automatically turn-on, turn-off, or delayoff. Switch will blink and beep to warn shut-off, which user may manually override. 3-way, 4-way, andmulti-way applications. Single gang faceplate to match material and colors of those for other switches.

2.19 Exterior Photocell: Compatible with lighting control panel. One set of normally open, isolated relaycontacts; closed when sensed light level is below dark setpoint, open when light level is above lightsetpoint. Eight second time delay and built-in setpoint deadband to prevent cycling. ½" threaded maleconduit base. 1-15 foot candle range. Isolated relay contacts lamp @ 30 VAC. Operating temperature -25to 125 degrees F. Design Equipment: Watt Stopper EM.

2.20 Panelboards to be full size, 20 inch minimum width, NEMA 1 panels with aluminum bus. Provide shopcoat of light grey paint on surface mounted tubs. Provide full neutral and ground bus. Locked doorskeyed alike, 2 keys per panel. Minimum size 5-3/4" deep, 20" wide. Panels rated over 225 Amps,minimum size 30" wide, 10" deep. Maximum height 72". Breakers as called for in schedules. Groundfault, ARC fault, shunt trip breakers as scheduled, non-padlock style breakers when called for. Fully ratedproducts (series rated not permitted). ITE CDP-7, Square D, Westinghouse, General Electric.

2.21 Provide building entrance surge protection device (SPD) designed to provide protection for sensitiveelectronic devices against the harmful effects of surges, transients and electrical line noise. System shallcontain a suppression filter assembly and individual fused MOVs contained in a metal enclosure withphase indicator lights, form C dry contacts, counter, and audible alarm. Protection modes shall be L-N, L-G, N-G, and L-L, with maximum surge current rating of 100 kVA per mode, 200 kA per phase. High

performance EMI/RFI noise rejection filter providing attenuation of 41 dB at 100 kHz, 31 dB at all otherfrequencies. Compliance with UL 1449, 3rd edition, 2009 revision. Voltage and phase as indicated onpower riser diagram shown on the contract drawings. Design Equipment: Current Technology Transguard100.

2.22 Ground rods to be 8' x 5/8" minimum, copper clad steel, Galvan, Chance. Clamps to be solid bronze,

suitable for direct burial, sized for rod and conductor combination.

ELECTRICAL SPECIFICATION26 50 00 - 5

WISP January 23, 2018Project No. 15033

2.23 Disconnects to be NEMA 1 or 3R as called for, heavy duty, 250 volt, fused, with neutral and ground kits.

Provide size as required for equipment being served. Confirm with approved equipment shop drawings. Provide fuses as required. Match equipment name plates. ITE, Square D, General Electric.

2.24 Time clocks to be 120 Volt, double pole, single throw, 40 Amp rated contacts, NEMA one enclosure,surface mounted, electronic type, with skipper feature and manual override. Make: TC1 - ExteriorLighting - 7 day or Tork, Paragon, Intermatic.

2.25 Pull boxes shall be underground enclosure, fiberglass reinforced polymer concrete. Pull box shape shallbe rectangular, 20 in. X 13 in. X 12 in. Deep, open base. Pull slot in cover, Cover logo "Communications"or "Power" as applicable. Stainless steel, penta bolts. Skid resistant surface. Heavy duty cover, 15,000 lbsfor 10 inch square area. Design Equipment: Quazite Style "PG".

2.26 Ductbank Marking Tape shall be labeled "CAUTION - ELECTRIC LINE BURIED BELOW". Orange color, 6"wide, 4 mil Polyethylene. Design Equipment: Panduit HTU60-T

2.27 Contactors to be NEMA 1, surface mount, 120 volt coil, 4 pole minimum or as called for, 30 Amp contacts,Square D, General Electric, Asco.

2.28 Photocells to be 120 volt, 20 amp rated contacts, NEMA 3R enclosure, surface mounted, adjustableknuckle on weatherproof, flush box, wall mounted, adjustable shield. Acceptable manufacturers: Tork,Paragon, Intermatic.

2.29 Single Station Smoke Detectors: 120 Volt smoke detector, surface mounted, interconnected, integral hornand strobe, comply with ADA standards, hard wired base, plug-in detector, twist lock installation BRK, ESLor Gentex as Gentex CS.

2.30 Fire Alarm System shall be new, analogue addressable non-coded fully supervised automatic and manualsystem. The complete system shall be UL listed as individual components and as a complete system. Strobe circuits shall be fully synchronized. System shall meet with approval of Maryland Fire Marshall’sOffice, Department of Labor and Industry and McHenry Fire Department.

Submit plans to Fire Department prior to rough-in for review.

Fire Alarm Control Panel (FACP) - Cabinet, main chassis with power supply, UDACT dialer, standbybatteries, integral annunciator. Detection loops to support number of addressable points required onplans, plus additional points for added devices. Capable of supporting at least two additional loops toaccommodate future expansion. Capable of supporting any combination of addressable sensors or

modules. Sensors configureable as alarm, verified alarm, latching or non-latching supervisory, monitor,and trouble only. Circuits configurable and Class “A” or Class “B”. Integral annunciator with backlit LCD 2-line by 20 character display. Numerical keypad, control switches, including system reset, signal silence,fire drill and acknowledge. City master box tie, back-up batteries, surface or flush enclosure as indicatedon drawings, remote annunciator connection. Acceptable manufacturers: FCI, Simplex, Notifier, Mircom,Gamewell, Edwards.

ELECTRICAL SPECIFICATION26 50 00 - 6

WISP January 23, 2018Project No. 15033

FACP Operation: Upon activation of fire alarm addressable input device (pull station, smoke detector,heat detector, water flow device, etc.) panel shall light the alarm indicator at panel and at remoteannunciator, cause alarm signal devices to sound throughout the building until silenced, cause visualsignals to activate, activate dialer or city tie, activate auxiliary contacts for elevator recall and fanshutdown as required. Alarm may be cleared from panel after devices no longer detect alarm condition. Supervisory alarm shall activate audible and visual indicator at panel and be capable of transmitting

supervisory alarm to monitoring agency. Supervisory signal alarm may be cleared from panel. Fire drillswitch shall activate all audible and visual devices. Alarm and event log each capable of containing at least200 events.

Remote Annunciator - Flush mount LCD display with 2 lines, each with 20 characters, control switchesincluding system reset, signal silence, fire drill and acknowledge, numeric keypad.

Dialer - Acceptable for two phone line input, UL listed, acceptable to monitoring agency and firedepartment.

Master Box - Weatherproof, flush installation, keyed, timed and coded to meet McHenry Fire Departmentrequirements. Gamewell.

Knox Box Key Lock Box - Provide flush mounted Knox box for building key management. Comply withMcHenry Fire Department requirements. Make: Knox 3200 Series with tamper switch, dark bronze color. Flush installation by General Contractor. Provide 3/4" conduit with (2) #12 wire to telephone serviceentrance backboard.

2.31 Initiation and Notification Devices: Manual pull stations, heat and smoke detectors, monitor and control

modules, and horn, strobe, speaker and combination notification devices shall be manufacturers standardproducts to match panel.

Manual Pull Station - Extruded aluminum construction (plastic housing NOT acceptable), red enamelfinish, raised letter label, single or double action per fire department requirements, resettable with keyswitch or screw driver per fire department requirements. Operation: pulling station’s handle will release

the internal switch to trigger the alarm detection circuit.

Automatic Thermal Detector: Addressable, plug in sensor, fixed or rate-of-rise as indicated on drawingswith temperature ratings as indicated on drawings, low profile housing, built-in test switch.

Photo Electric Smoke Detector - Addressable, plug-in optical sensor, programmable sensitivity with

continual monitoring, low profile housing.

Duct Smoke Detector - Ionization head with air tight chamber, sample tube, integral mounting base,sample tube with field trim able 48 inch sampling tube, capable of handling 500 to 4,000 fpm, auxiliarycontacts for fan shut-down wiring, weatherproof rated where shown on drawings at building exterior.

Horn, Strobe, Speaker, and Combination Notification Devices - Field selectable candela ratings, xenonflash tube, Class “A” and Class “B” compatible, synchronization module, ADA compatible, horn units shallhave frequency and sound levels per NFPA 72.

ELECTRICAL SPECIFICATION26 50 00 - 7

WISP January 23, 2018Project No. 15033

2.32 CATV system wiring to be 75 Ohm, coax cable, braided copper concentric ground, RG-6, General Cable,

Belden, West Penn or Carol.

2.33 CATV system outlets to be installed in flush device box. Plates to be color as selected by Architect smoothwith coax threaded fitting.

2.34 Telephone wiring within the individual units shall be CAT 6 wiring with CAT 6 compliant jacks at the work

area location. CAT 6 wiring shall be punch down on 110 or 66 blocks at the telephone backboard. Individual runs shall be labeled. Punch down blocks and wiring approach shall comply with CAT 6 wiringstandards found in TIA/EIA 568.

2.35 Wiring shall be tested to demonstrate compliance with BICSI standards electronic and paper copy of thetest report for each run within each building provided to the owner for review and record.

2.36 Voice and Data Cabling Systems: Provide labor, materials, equipment and services to perform operationsrequired for the complete installation and related Work as required in Contract Document.

Organize submittals in bound brochures containing descriptive sheets for each of the following items asincluded in the scope of this work: Work area outlets. Wall plates and jacks/connectors. Wall boxes,

surface housings, conduit, bushings, sleeves, raceway, and accessories. Horizontal cables. Cross connectblocks. Patch panels. Relay racks, cabinets, panels, and brackets. Cable management accessories.

Horizontal Cabling System: The Data Room shall contain the LAN server by Owner and the centralequipment for the telephone system. Category 6 UTP horizontal cabling from computer outlets in roomsterminate at a data rack (bracket) mounted patch panel mounted (on a backboard) in the Data Room. Category 6 UTP horizontal cabling from telephones shall terminate at a modular 110 cross connect block

mounted on a backboard in the Data Room.

Work Area (Station) Outlets: Faceplate with label strips and clear label strip plastic covers top andbottom, number of ports per faceplate as shown on drawings. Make: Hubbell IFP series or Siemens,Panduit, Ortronics.

Single port nylon faceplate to provide wall phone compatibility. Make: Hubbell BR630 series or Siemens,Panduit, Ortronics.

Category 6, 110 style modular jack, T568B wiring, with provision for strain relief after termination. Redcolor for data, grey color for voice. Make: Hubbell HXJ6 series or Siemens, Panduit, Ortronics.

Horizontal Cabling: Non-plenum rated Category 6 cabling shall be four-pair 100-ohm unshielded twisted-pair (UTP), 24 AWG, with solid copper conductors all insulated with the same material. Non-plenum ratedCategory 6 cabling shall meet requirements of ANSI/TIA/EIA-568-B and be UL listed for that purpose. Make: Superior Essex or Mohawk, General Cable, CommScope, Hitachi, Berk-tek.

Cross Connect Blocks: Category 6 modular 110 cross connect block with legs, labels, and holders, 50 pair.

Make: Hubbell Cat 6 110 series or Siemens, Panduit, Ortronics.

ELECTRICAL SPECIFICATION26 50 00 - 8

WISP January 23, 2018Project No. 15033

Floor Mounted Rack: Standard 19 inch aluminum frame communication rack, black color, floor mounted

with anchor bolts HPW84RR19. 3.5" high D-ring style wire management with covers accessories locatedhorizontally between patch panel sections HC219CE3N. 6" wide vertical wire management accessorieslocated front between racks with covers and dual sided - CS76. Center weighted 19 inch equipment tray -10 inch deep - black color. Provide on per rack as specified MCCCWS19. Blank filler sections as specified. Floor anchor kit. Make: Hubbell.

Patch Panels: Category 6 hinged, fold down, 48 port patch panel, T-568-B, designed to fold down for frontaccess termination at the 110 blocks on the rear of the panel. Make: Hubbell P648UF or Siemens,Panduit, Ortronics.

Patch Panels: 19" patch panel, rack mount type - (2) rows of 24 jacks, 3.5" high, Cat 6 compliant, 110termination - tin lead plated IDC, modular jacks meet, T-568-B wiring, Beryllium copper jack contacts with

minimum 50 micro-inch gold plating. Make: Hubbell P6E Series.

Cable Management Accessories: Non-metallic split rings for wire path management, with screw holes forsurface mounting to walls, ceilings, and backboards. Make: Hubbell MCCPSR Series or Siemens, Panduit,Ortronics.

Cable Tray: Provide straight aluminum tray, 12 inch wide x 4 inch deep, with solid sides and bottom. Material shall be hot galvanized steel. Hang with threaded roads on either side, trapeze bracket onbottom of tray. Make: Flex Tray or Cablofil, P & W.

Ladder Rack: 16 gauge steel construction, 9" rung spacing, nominal 1.5" deep x 12" wide, black powdercoat finish.

Verify location of all wall outlets with owner's representative before installing. This specification is basedon EIA/TIA T568A wiring terminations. This contractor shall verify with owner, in writing, if 568A or 568Bwiring is existing. This contractor shall then match that wiring.

Work Area Outlets shall consist of the following: One single gang faceplate, number of ports as shown ondrawings, color to match other face plates in room. One Category 6, 110 style modular jack, T568B wiring,

designated by label, color, & icon, quantity as shown on drawings. One outlet box installed in the wall,minimum 4 in. by 4 in. by 2-1/8 in. deep, with single gang extender ring to accommodate the thickness ofthe finish wall and provide a total box depth of at least 2-1/2" to provide room for proper cable bendradius.

Wall telephone outlets shall consist of the following: One single port stainless steel faceplate to provide

wall phone compatibility. One Category 6, 110 style modular jack, T568B wiring, designated by label,color, & icon. One outlet box installed in the wall, minimum 4 in. by 4 in. by 2-1/8 in. deep, with singlegang extender ring to accommodate the thickness of the finish wall and provide a total box depth of atleast 2-1/2" to provide room for proper cable bend radius.

ELECTRICAL SPECIFICATION26 50 00 - 9

WISP January 23, 2018Project No. 15033

CAT6 phone and data telecommunications outlets shall consist of the following: One single gangfaceplate, number of ports as shown on drawings, color to match other face plates in room. Category 6,110 style modular jack, T568B wiring, designated by label, color, & icon, quantity per outlet as shown ondrawings. One outlet box installed in the wall, minimum 4 in. by 4 in. by 2-1/8 in. deep, with single gangextender ring to accommodate the thickness of the finish wall and provide a total of depth of at least 2-1/2" to provide room for proper cable bend radius.

The length of each horizontal cable run shall not exceed 295 feet. Horizontal cable is defined as thatlength of cable from the back of the workstation outlet to the back of the Patch Panel or connecting blockin the telecommunications closet. Horizontal cable shall be a continuous run of cable with no splices,bridges, or other discontinuities.

Each work area jack for computer connection shall be supported by (1) Category 6 cables with orangesheath (or marked with orange tape). Cable ends and associated connectors shall be given a permanent,unique label at both work area and cross connect ends to clearly identify horizontal wiring connection andfunction (data).

Each work area outlet for telephone connection shall be supported by (1) Category 6 cable with blue

sheath (or marked with blue tape). Cable ends and associated connectors shall be given a permanent,unique label at both work area and cross connect ends to clearly identify horizontal wiring connection andfunction (voice).

Testing: Contractor shall provide all necessary testing equipment to test all cables. The permanent linktest configuration defined in TIA/EIA 568B shall be used to verify the performance of permanentlyinstalled cabling, using a Category 6 tester. All horizontal cabling shall be tested and certified for wire

map, length, attenuation, and near-end crosstalk (NEXT) loss and meet the requirements of TIA/EIA 568Bpermanent link specification.

Conduit: Minimum 1" conduit shall be installed in all new walls and shall be run to above accessibleceilings (see Drawings for conduit size). Terminate all conduits with bushings. Conduit bends must have aradius of not less than 6 times the internal diameter of conduits 2 inches or smaller, or 10 times the

internal diameter of conduits larger than 2 inches. Conduits for pulling UTP cabling runs shall contain notmore than (2) 90 degree changes of direction or a total of 180 degrees.

Cross Connect Blocks: Cross connect blocks shall be installed on telephone backboard, using wiremanagement devices such as split rings and hook and loop tie wraps to maintain proper support and bendradius for terminated UTP cables and patch cords to present an orderly, neat appearance.

PART 3 - EXECUTION

3.1 Work shall be completed by Maryland licensed electricians in a workmanlike manner, consistent withstandard practice, and present a neat and finished appearance prior to final acceptance by ownersrepresentative.

3.2 Verify structural, architectural, and mechanical conditions (beam clearances, door swings, counterheights, and duct clearances) prior to rough in.

ELECTRICAL SPECIFICATION26 50 00 - 10

WISP January 23, 2018Project No. 15033

3.3 Electrical work shall be carefully laid out and coordinated with other trades, utilities, and site conditions.

Cutting, drilling, and alterations to other work shall be planned in advance with the general contractorand be carefully done. Damage shall be repaired by skilled mechanics, to the satisfaction of the ownersrepresentative.

3.4 Receptacle outlets in residential construction to be laid out to comply with 6 foot and 12 foot spacings. Provide blocking between standard framing as required. Layout and planning on site to include centering

outlets under windows.

3.5 The contractor shall protect and keep clean electrical equipment, panels, fixtures, and devices.

3.6 The contractor shall provide information about his equipment to the General Contractor for coordination.

3.7 The contractor shall verify final locations and capacities of mechanical, HVAC, and owners equipment onsite prior to rough in.

3.8 Metal raceway systems, and electrical equipment shall be bonded and grounded as called for and per NEC250 and NEC 680 for pool areas. Conduit, cable and raceway fittings, lugs, bolts, and connections shall bedesigned for the purpose and conditions under which they are installed. Equipment shall be properly

installed and tightened to assure mechanical and electrical continuity. No conduit shall be installed abovetop chord of bar joists or steel beams.

3.9 Metal raceway systems, pool structure, pool accessories, pool equipment and electrical equipment shallbe bonded and grounded as called for and per NEC 250. Conduit, cable and raceway fittings, lugs, bolts,and connections shall be designed for the purpose and conditions under which they are installed. Equipment shall be properly installed and tightened to assure mechanical and electrical continuity.

3.10 Wiring shall be concealed in walls and above ceilings in finished areas and wherever possible. Wiring inutility areas may be exposed. Exposed wiring in utility areas shall be in conduit, be neat and parallel tostructure. No wiring shall be installed above top chord of joists.

3.11 Wiring shall be separated and marked to indicate phase and function. Wiring size # 10 and smaller shall

be solid color insulation. Wiring #6 and larger may be black insulation with phase tape applied to eachend and at junction boxes. Label all panels with wiring color scheme, per NEC. Building wiring shall becolor coded as follows:

Phase A BlackPhase B Red

Phase C BlueNeutral WhiteGround Green

3.12 Conduits, raceways, and cables shall be properly and securely attached to building structural componentsas called for and per NEC. Fasteners and hardware shall be approved for the installation and conditions

encountered.

ELECTRICAL SPECIFICATION26 50 00 - 11

WISP January 23, 2018Project No. 15033

3.13 Each outlet or junction in any wiring system shall be made in an approved, metallic junction box. Box shall

be suitable for the size and number of conductors and devices installed, and conditions encountered. Splices shall be made with approved mechanical connectors.

3.14 Installation of electronic occupancy sensor switches. Install flush within metal device box. Gang in multi-gang box with multi-gang plate where shown. Test load prior to switch installation. Comply withmanufacturers written instructions. Set dip switches for optional features as directed, room by room. Set

maximum time off at 5 minutes unless specifically noted otherwise. Confirm time settings with ownersrepresentative or room by room basis. Demonstrate sensor operation in one room for ownersrepresentative, architect and engineer. Document event, features covered, and attendance. Includelabor and materials to set switch settings on each device a total of 2 times; once after demonstration;once after punch list.

3.15 Circuits not otherwise called for shall be 20 amp, 120 volt, single phase, 2 wire with ground. Conduithome runs may be combined, properly phased and balanced, at the discretion of the electrical contractor. Confirm phase rotation of all equipment. Correct wiring as required for proper operation.

3.16 Fire alarm vendors/manufacturers shall prepare materials in coordination with Division 26 contractor. Division 26 contractor shall review, repackage and supplement vendor materials as required to comply

with above. Fire alarm submittal notebook shall be complete from Division 26 contractor and includematerials from variety of vendors and suppliers as may be needed.

3.17 Provide submittals for the entire system including: Complete equipment list including quantities. Catalogdescriptive literature for all equipment. Knox box. Master box. Short narrative prepared for this projectdescribing features, operations and reset. Riser wiring diagram showing all devices, wire quantities andsizes. Typical terminal wiring diagram for each type of device. Terminal wiring diagram for the fire alarm

control panel. Calculations, including actual equipment loads and quantities used to derive batterybackup ampere-hour rating.

3.18 Submittal of fire alarm shop drawings shall contain at least one (1) booklet of original manufacturerspecification and installation instruction sheets. Subsequent booklets may be copies. Confirmation ofsubmittal of copy of final plans, specifications and shop drawings to local and state fire department for

approval.

3.19 Division 26 contractor shall be responsible for coordination of the fire alarm system submittal. Suchcoordination shall include working with selected fire alarm system vendor, the project general contractor,the project fire protection/sprinkler system sub-contractor, and the Owner’s Representative as necessaryto secure written approvals of the fire alarm system prior to construction. Copies of written

correspondence received from the fire department or the State Fire Marshal shall be copied to theOwner’s Representative and the architect for review and comment prior to implementing any requestedchanges by either of these departments.

ELECTRICAL SPECIFICATION26 50 00 - 12

WISP January 23, 2018Project No. 15033

3.20 Vendor Layout: The intent of the contract documents is to provide a full alarm system with horns, strobes,

and/or combination units complying with codes and standards noted. System vendors and/ormanufacturer’s representative shall familiarize himself with the contract documents, including plans,details, architectural elevations and building sections and the location of alarm indicating appliances. Vendor shall confirm that the style, capacity, NEMA rating, and operational characteristics of thisequipment are suitable for the use and location shown. Specific attention is called to ADA Guidelines andNFPA 72, regarding strobe equipment layout, placement and candella rating. Vendor shall include written

confirmation as part of submittal that equipment as submitted complies with standards and intended use,spacing and location or provide written summary of any exceptions to such compliance on a case by casebasis.

3.21 Fire Alarm system shop drawings - including battery calculations and equipment cut sheets, along withcontract drawings, shall be submitted by Division 26 to both the McHenry Fire Department and the State

of Maryland Fire Marshall’s Office for review and approval. Submit in ample time to allow for review andapproval time prior to installation.

3.22 Fire Alarm system shall be 100% tested in accordance with NFPA 72. Provide written and signed reportindicating scope of test, date of test, person performing test, devices tested and any abnormalities. Useand complete form in NFPA 72. Submit completed form for review prior to final acceptance. Correct all

abnormalities and retest. Provide 100 per cent testing, coordinate with owner and McHenry FireDepartment.

3.23 Coordinate existing electrical systems serving owner occupied spaces and maintain service for owners use. Schedule all required system down times and outages with owner's representative in writing, minimum of48 hours in advance of work.

END OF SECTION

ELECTRICAL SPECIFICATION26 50 00 - 13


Recommended