Series 70 ePODs: Type-N Stac Transfer Switch → Distribuon ETL listed Cerfied To CSA Agency Cerficaon Safe Bypass Procedure Voice Guided Bypass Oponal Triple Modular Redundancy Insulated, Epoxy Coated Buswork Silver Plated Terminals Maintenance-Free Joints Machined Hardware Convecon Cooling Opcal Fiber Based Controls Serialized Crical Board Tracking Reliability InSight™ IR Portholes Seconalized Components Polycarbonate Windows Dead-Front Hinged Doors SafePanel™ Distribuon Ethernet Connecvity Modbus/TCP NTP Time Clock Synchronizaon SNMP Connecvity Safety Connecvity Waveform Capture “Black Box” Forensic Diagnoscs Touch Screen Interface Waveforms Automacally Emailed Power Quality Monitoring Up to 12 CB positions 1200A SafePanel 1 Source 1 Input Source 2 Input 480V, 3-phase, 3-wire or 600V, 3-phase, 3-wire 2 0 2 B C 1 0 2 B C 2 0 1 B C 1 0 1 B C C N C N NO NO CB302 CB301 NC NC NC CB604 NO CB605
Transcript
Page 1: Series 70 ePODs: Type-N - Power Solutions USA€¦ · Static Transfer Switch → Distribution ETL listed Certified To CSA Agency Certification Safe Bypass Procedure ... SafePanel™

Series 70 ePODs: Type-NStatic Transfer Switch → Distribution

ETL listed

Certified To CSA

Agency Certification

Safe Bypass Procedure

Voice Guided Bypass

Optional Triple Modular Redundancy

Insulated, Epoxy Coated Buswork

Silver Plated Terminals

Maintenance-Free Joints

Machined Hardware

Convection Cooling

Optical Fiber Based Controls

Serialized Critical Board Tracking

Reliability

InSight™ IR Portholes

Sectionalized Components

Polycarbonate Windows

Dead-Front Hinged Doors

SafePanel™ Distribution

Ethernet Connectivity

Modbus/TCP

NTP Time Clock Synchronization

SNMP Connectivity

Safety

Connectivity

Waveform Capture

“Black Box” Forensic Diagnostics

Touch Screen Interface

Waveforms Automatically Emailed

Power Quality Monitoring

Up to 12 CB positions1200A SafePanel 1

Source 1Input

Source 2Input

480V, 3-phase, 3-wireor

600V, 3-phase, 3-wire

202BC102BC

201BC101BC CNCN

NO NO

CB302CB301 NC NC

NCCB604 NO CB605

Series 70 ePODs: Type-N

Page 2: Series 70 ePODs: Type-N - Power Solutions USA€¦ · Static Transfer Switch → Distribution ETL listed Certified To CSA Agency Certification Safe Bypass Procedure ... SafePanel™

Series 70 ePODs: Type-N Product Overview

Technical Specifications

eSTS:Size: 250A, 400AVoltage: 480V, 3-W, 600V, 3-WRedundancy: Triple Modular Redundant (TMR)Single Module Redundant (SMR)Output Switch: Redundant, Non-redundant

Main Circuit Breaker Section: MCB optionalMounting: Fixed, Plug-InType: Molded Case Switch65kA, 100kAElectronic Trip 65kAIC, 100kAICAccessories: CB Shunt-trip120VAC, 24VDCCB Position Indication: Open, Tripped, Closed

Distribution Section: Sub-feed distribution1200A SafePanel

ePODs: Type-N Models with Withstand Ratings 120/208 V 480 V; 480/277 V; 415/240 V; 400/230

V; 380/220 V600 V; 575 V

150 A 200kAIC; 150kAIC; 100kAIC; 65kAIC

150kAIC; 100kAIC; 65kAIC; 35kAIC; 25kAIC

100kAIC; 65kAIC; 35kAIC; 25kAIC; 18kAIC

225 A150kAIC; 100kAIC; 65kAIC 65kAIC; 50kAIC; 25kAIC

250 A

200kAIC; 150kAIC; 100kAIC; 65kAIC150kAIC; 100kAIC; 65kAIC; 35kAIC;

25kAIC100kAIC; 65kAIC; 35kAIC; 25kAIC;

18kAIC400 A

600 A

800 A 200kAIC; 100kAIC; 65kAIC 100kAIC; 65kAIC; 50kAIC; 35kAIC 42kAIC; 35kAIC; 25kAIC; 20kAIC

1000 A 150kAIC; 100kAIC; 65kAIC 100kAIC; 65kAIC; 50kAIC 65kAIC; 50kAIC; 25kAIC

1200 A

Electrical CharacteristicsNumber of Inputs 2, 3

Number of Output CBs 1, 2

Frequency 50 Hz, 60 Hz

Poles 3-pole, 4-pole

Phases 3 Phase, 3 Wire, 4 Wire + Ground

Neutral Rating 100%, 150%, 200%

Transfer Time < 4ms (3 ms typical)

Redundancy Single Modular Redundancy, Triple Modular Redundancy Optional


Recommended