Date post: | 23-Aug-2014 |
Category: |
Documents |
Upload: | sivagurunathan-sp |
View: | 166 times |
Download: | 2 times |
SELECTION CHART : FUSE PROTECTED DOL STARTER FEEDERSTYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1Sr.Motor Rating: 1Ø, 240V, 50 HzMotor Rating: 3Ø, 415V, 50 Hz Contactor Overload Relay Nominal Backup fuse S - D - FNo. hp kW In (A) hp kW In (A) Type Type Range (A) Type Rating (A)1 0.125 0.09 0.4 MNX 9 MNX-R3 0.3 - 0.5 HF 2 FN 32 / FNX 322 0.16 0.12 0.45 MNX 9 MNX-R3 0.3 - 0.5 HF 2 FN 32 / FNX 323 0.2 0.15 0.57 MNX 9 MNX-R3 0.45 - 0.75 HF 2 FN 32 / FNX 324 0.25 0.19 0.75 MNX 9 MNX-R3 0.6 - 1.0 HF 4 FN 32 / FNX 325 0.33 0.25 0.9 MNX 9 MNX-R3 0.6 - 1.0 HF 4 FN 32 / FNX 326 0.5 0.37 1.2 MNX 9 MNX-R3 0.9 - 1.5 HF 6 FN 32 / FNX 327 0.75 0.55 1.6 MNX 9 MNX-R3 1.4 - 2.3 HF 6 FN 32 / FNX 328 0.25 0.18 2 1 0.75 2.1 MNX 9 MNX-R3 1.4 - 2.3 HF 8 FN 32 / FNX 329 0.5 0.4 3.6 1.5 1.1 2.7 MNX 9 MNX-R3 2.0 - 3.3 HF 10 FN 32 / FNX 3210 1.75 1.3 3 MNX 9 MNX-R3 2.0 - 3.3 HF 10 FN 32 / FNX 3211 2 1.5 3.5 MNX 9 MNX-R3 3 - 5 HF 16 FN 32 / FNX 3212 2.5 1.8 4.8 MNX 9 MNX-R3 4.5 - 7.5 HF 16 FN 32 / FNX 3213 3 2.25 5 MNX 9 MNX-R3 4.5 - 7.5 HF 16 FN 32 / FNX 3214 4 3 6.4 MNX 9 MNX-R3 4.5 - 7.5 HF 20 FN 32 / FNX 3215 1 0.75 7.5 5 3.7 7.9 MNX 9 MNX-R3 6 - 10 HF 20 FN 32 / FNX 3216 5.5 4 8.5 MNX 9 MNX-R3 6 - 10 HF 20 FN 32 / FNX 3217 1.25 0.9 8 6 4.5 9 MNX 12 MNX-R3 6 - 10 HF 25 FN 32 / FNX 3218 2 1.5 9.5 7.5 5.5 11.2 MNX 12 MNX-R3 9 - 15 HF 32 FN 32 / FNX 3219 3 2.25 14 10 7.5 14.8 MNX 18 MNX-R3 9 - 15 HF 32 FN 32 / FNX 3220 12.5 9.3 19 MNX 25 MNX-R3 14 - 23 HF 50 FN 63 / FNX 6321 15 11 22 MNX 25 MNX-R3 14 - 23 HF 63 FN 63 / FNX 6322 17.5 13 24 MNX 32 MNX-R3 20 - 33 HF 63 FN 63 / FNX 6323 20 15 29 MNX 32 MNX-R3 20 - 33 HF 63 FN 63 / FNX 6324 25 18.6 35 MNX 40 MNX-R4 30 - 50 HN, 000* 80 FN 100 / FNX 100 *25 30 22.5 40 MNX 45 MNX-R4 30 - 50 HN, 000* 80 FN 100 / FNX 100 *26 35 26 47 MNX 70 MNX-R4 30 - 50 HN, 000* 100 FN 100 / FNX 100 *27 40 30 55 MNX 70 MNX-R4 45 - 75 HN, 000* 100 FN 100 / FNX 100 *28 45 33.5 60 MNX 70 MNX-R4 45 - 75 HN, 000* 100 FN 100 / FNX 100 *29 50 37 66 MNX 80 MNX-R4 45 - 75 HN, 00 125 FN 125 / FNX 12530 60 45 80 MNX 95 MNX-R4 66 - 110 HN, 00 125 FN 125 / FNX 12531 75 55 100 MNX 110 MNX-R4 66 - 110 16032 90 67.5 120 MNX 140 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 20033 100 75 135 MNX 140 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 200
sheet 1 of 2
HN, 00 # FN 160 / FNX 160 #
ubs \ R1: 21.10.05
SELECTION CHART : FUSE PROTECTED DOL STARTER FEEDERSTYPE '2' Co-ordination, Iq=50 kA at 415V, 3Ø, 50 Hz.
as per Standards: IEC 60947-4-1, IS 13947 (Part 4/Sec 1), EN 60947-4-1Motor Rating: 1Ø, 240V, 50 HzMotor Rating: 3Ø, 415V, 50 Hz Contactor Overload Relay Nominal Backup fuse S - D - F
hp kW In (A) hp kW In (A) Type Type Range (A) Type Rating (A)34 110 80 139 MNX 185 MNX-R5 90 - 150 HN, 0 200 FN 200 / FNX 20035 125 90 165 MNX 185 MNX-R5 135 - 225 HN, 1 250 FN 250 / FNX 25036 150 110 200 MNX 225 MNX-R5 135 - 225 HN, 1 250 FN 250 / FNX 25037 175 130 230 MNX 265 MNX-R5 180 - 300 HN, 1 315 FN 315 / FNX 31538 197 147 260 MNX 265 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 40039 200 150 275 MNX 325 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 40040 215 160 280 MNX 325 MNX-R5 180 - 300 HN, 2 400 FN 400 / FNX 40041 225 168 300 MNX 325 MNX-R5 270 - 450 HN, 2 400 FN 400 / FNX 40042 245 180 320 MNX 325 MNX-R5 270 - 450 HN, 2 400 FN 400 / FNX 40043 270 200 340 MNX 400 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 63044 300 225 385 MNX 550 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 63045 335 250 425 MNX 550 MNX-R5 270 - 450 HN, 3 500 FN 630 / FNX 63046 400 300 500 MNX 550 MNX-R5L 340 - 570 HN, 3 630 FN 630 / FNX 63047 430 315 535 MNX 550 MNX-R5L 340 - 570 HN, 3 630 FN 630 / FNX 630
NOTES:1) The Full Load Current (FLC) indicated for Single phase motors are of 'Capacitor start motors' and for 3-phase motors are of
'Squirrel-cage Induction motors' at full load. Motors considered are with speeds more than that mentioned below:
Upto 10 hp - 750 rpm 30-125 hp - 500 rpm10-30 hp - 600 rpm 125-300 hp - 375 rpm
2) Contactors / S-D-Fs indicated are of the minimum ratings. Higher rating of Contactors and S-D-Fs can be used.3) Normal Motor starting time, Power factor and Efficiency is assumed in all cases.4) * : Only size '000' fuses to be used with FNX 100 S-D-F.5) # : Only size '00' fuses should be used with FNX 160 S-D-F.6) Selection is valid only for complete L&T combinations ie. "S-D-F + Fuse + Contactor + O/L. Relay".
Compliance to Type '2' co-ordination is not assured in case these combinations are changed to accommodate another brand / rating of products like S-D-F / Fuse etc.
7) All S-D-F ratings are AC-23A as per IS 13947 (Part 3), IEC 60947-3 & EN 60947-38) Switchgear selection for motors with longer starting times can be made available on request.
sheet 2 of 2ubs \ R0 : 15.02.05ubs \ R1: 21.10.05
- - UPTO 1.5 KW MOTOR DOL SFU Feeder
List Price QTYSFU FN 32 / FNX 33 16A 1910 1 1910Contactor MNX 9 775 1 775OLR MNX-R3 3 - 5 A 1175 1 1175Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
Fuse links 16A 169 3 507Wires, cable ducts, sleeves , feruuls, name plate, etc., 1250 1 1250Panel Enclosure with painting 1 2000
above 1.5KW and UPTO 3.7KW MOTOR DOL SFU Feeder
SFU FN 32 / FNX 33 20A 1910 1 1910Contactor MNX 9 775 1 775OLR MNX-R3 6-10A 1175 1 1175Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
Fuse links 20A 169 3 507Wiries, cable ducts, sleeves , feruuls, name plate, etc., 1250 1 1250Panel Enclosure with painting 1 2000
above 3.7KW and UPTO 7.5KW MOTOR DOL SFU Feeder
SFU FN 32 / FNX 33 32A 1910 1 1910Contactor MNX 18 965 1 965OLR MNX-R3 9 -15A 1175 1 1175Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340
Indicating lamps RED 170 1 170YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
Fuse links 32A 169 3 507Wires, cable ducts, sleeves , feruuls, name plate, etc., 1250 1 1250Panel Enclosure with painting 1 2000
above 7.5KW and UPTO 15KW MOTOR DOL SFU Feeder
SFU FN 63 / FNX 63 63A 2510 1 2510Contactor MNX 32 1105 1 1105OLR MNX-R3 20 - 33A 1600 1 1600Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
Fuse links 63 250 3 750Wires, cable ducts, sleeves , feruuls, name plate, etc., 1500 1 1500Panel Enclosure with painting 1 2000
above 15KW and UPTO 22.5KW MOTOR DOL SFU Feeder
SFU FN 100 / FNX 100 80A 5160 1 5160Contactor MNX 45 5250 1 5250OLR MNX-R4 30 - 50A 2160 1 2160Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
Fuse links 80A 250 3 750Wires, cable ducts, sleeves , feruuls, name plate, etc., 1500 1 1500Panel Enclosure with painting 1 2000
From 26KW and UPTO 33.5KW MOTOR DOL SFU Feeder
SFU FN 100 / FNX 100 100A 5160 1 5160Contactor MNX 70 7380 1 7380OLR MNX-R4 45 - 75A 3205 1 3205Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 100A 600 3 1800
96 x 96 x 96 100A 850 1 850
Fuse links 100A 250 3 750Wires, cable ducts, sleeves , feruuls, name plate, etc., 1500 1 1500Panel Enclosure with painting 1 2000
For 37 & 45KW MOTOR DOL SFU Feeder
SFU FN 125 / FNX 125 125A 6799 1 6799Contactor MNX 95 10720 1 10720OLR MNX-R4 66 - 110A 3205 1 3205Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 125A 750 3 2250
96 x 96 x 96 125A 1000 1 1000Fuse links 125A 394 3 1182Wires, cable ducts, sleeves , feruuls, name plate, etc., 2000 1 2000Panel Enclosure with painting 3000 1 3000
Ammeter with selector switches
Ammeter with selector switches
For 55KW MOTOR DOL SFU Feeder
SFU FN 160 / FNX 160 160A 7520 1 7520Contactor MNX 110 12155 1 12155OLR MNX-R4 66 - 110A 3205 1 3205Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 160A 1000 3 3000
96 x 96 x 96 160A 1050 1 1050Fuse links 160A 421 3 1263Wires, cable ducts, sleeves , feruuls, name plate, etc., 3000 1 3000Panel Enclosure with painting 4000 1 4000
For 75KW MOTOR DOL SFU Feeder
SFU FN 200 / FNX 200 200A 8660 1 8660Contactor MNX 140 16575 1 16575OLR MNX-R5 90 - 150A 6405 1 6405Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 200A 1000 3 3000
96 x 96 x 96 200A 1050 1 1050Fuse links 200A 520 3 1560Wires, cable ducts, sleeves , feruuls, name plate, etc., 4000 1 4000Panel Enclosure with painting 5000 1 5000
For 110KW MOTOR DOL SFU Feeder
Ammeter with selector switches
Ammeter with selector switches
SFU FN 250 / FNX 250 250A 8660 1 8660Contactor MNX 225 25415 1 25415OLR MNX-R5 135 - 225A 6405 1 6405Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 250A 1000 3 3000
96 x 96 x 96 250A 1050 1 1050Fuse links 250A 520 3 1560Wires, cable ducts, sleeves , feruuls, name plate, etc., 4000 1 4000Panel Enclosure with painting 5000 1 5000
For 150/160KW MOTOR DOL SFU Feeder
SFU FN 400 / FNX 400 400A 16150 1 16150Contactor MNX 325 35915 1 35915OLR MNX-R5 180 - 300A 7260 1 7260Control MCB Lexic 6032 27 2A 300 1 300Aux contactor MNX 9 - 40 340 1 340Indicating lamps RED 170 1 170
YELLOW 170 1 170BLUE 440 1 440
Push buttons RED 160 1 160GREEN 160 1 160
CTs 400A 1200 3 3600
96 x 96 x 96 400A 1250 1 1250Fuse links 400A 820 3 2460Wires, cable ducts, sleeves , feruuls, name plate, etc., 4000 1 4000Panel Enclosure with painting 5000 1 5000
Ammeter with selector switches
Ammeter with selector switches
Discount Discounted cost 25 1,433 25 581 30025 881 500
300 30025 255 300
170 300 170 440 340 160 160 507 1,250 2,000
8,307
25 1,433 25 581 25 881
300 25 255
170 170 440 160 160 507 1,250 2,000
8,307
25 1,433 25 724 25 881
300 25 255
123456
170 170 440 160 160 507 1,250 2,000
8,450
25 1,883 25 829 25 1,200
300 25 255
170 170 440 160 160 750 1,500 2,000
9,816
25 3,870 25 3,938 25 1,620
300 25 255
170 170 440 160 160 750 1,500 2,000
15,333
25 3,870 25 5,535 25 2,404
300 25 255
170 170 440 160 160 1,800
850
750 1,500 2,000
20,364
25 5,099 25 8,040 25 2,404
300 25 255
170 170 440 160 160 2,250 1,000
1,182 2,000 3,000
26,630
25 5,640 25 9,116 25 2,404
300 25 255
170 170 440 160 160 3,000 1,050
1,263 3,000 4,000
31,128
25 6,495 25 12,431 25 4,804
300 25 255
170 170 440 160 160 3,000 1,050
1,560 4,000 5,000
39,995
25 6,495 25 19,061 25 4,804
300 25 255
170 170 440 160 160 3,000 1,050
1,560 4,000 5,000
46,625
25 12,113 25 26,936 25 5,445
300 25 255
170 170 440 160 160 3,600 1,250
2,460 4,000 5,000
62,459