Multi-Panels Installation manual for Fiber Cement Siding: Color-Natura and Rustica
10
Siding Installation Manual for: Color – Natura – Rustica
Transcript
Page 1: Siding installation for color natura and rustica

1

Siding Installation Manual for:Color – Natura – Rustica

Page 2: Siding installation for color natura and rustica

2

Ventilated Siding, principle

Ventilated Siding systems consist of five main components:

1 Support structure 2 Ventilated cavity 3 Thermal insulation layer 4 Siding (Color – Natura – Rustica - 5/16” thickness) 5 Sub mounting frame (Wood – Aluminium – Galvanized steel)

1 Support structureThe exterior wall of a building is mainly made of concrete, CMU blocks, brick-work, steel or timber frame with studs and planked by gypsum panels, M4 panels, OSB or Plywood.

2 Ventilated cavityThe main task of the air cavity is the evacuation of moisture and excess heat. The air circulation occurs naturally thanks to the pressure difference between bottom and top.

3 Thermal insulation layerThe advantage of an exterior thermal insulation is to keep the entire building structure at a constant temperature and to minimize thermal bridges and thus reduce the loss of energy to a minimum. Economic as well as ecological advantages result.

Page 3: Siding installation for color natura and rustica

3

4 Siding (Color – Natura – Rustica)The outer skin of the building envelope has two main functions; to be aesthetically as well as protecting against influences from climate and environment.

5 Sub frameMulti-Panels facade panels are installed on wood, aluminium or metal supports.The Multi-Panels Siding concept is based on natural rear ventilation as It is most reliable, sustainable and provides maximum longevity to exterior Siding.

Important! Siding with Multi-Panels products must always be carried out as a ventilated facade with min 1” (25 mm) distance between the Siding and the rear wind barrier, lining (insulation material). In special situations (e.g. high rise buildings), local regulations may demand a larger ventilation gap, but normally 0,25% - 0,5% of the Siding area must be even ventilated or/and the inlet and outlet openings must have a cross section of at least 200 cm2/m2.

Fastening of Multi-Panels SidingMulti-Panels panels are installed on wood or metal substructures. The fastening method using “invisible” fastening as glue or “visible” as screws or rivets allows an efficient attachment to the supporting structures (see below drawings). In fact if using visible screws/rivets, (A2 material) screw heads are hardly visible even at a slight distance away as they fit with the overall surface and are available in the same shades of color as the panels delivered.Sub-frames are to be designed by structural engineer/contractor.Thermal expansion/retraction is to be accounted for.

Sub mounting frame of wood with visible Screw head,mounted to concrete or wood structure:

Page 4: Siding installation for color natura and rustica

4

Overview main components Ventilated Siding Concept with visible Screw – Wood Structure

Sub mounting frame of Steel with visible Screw head, mounted to M4 sheathing /structure

Overview main components Ventilated Siding Concept with invisible Screw – Wood Structure

With galvanized steel sub structure and EPDM

1 M4 Exterior Sheathing (structural)

2 Impregnated latch 1" x 2" / 1" x 4"

3 EPDM

4 Siding Panel (Color,Natura,Rustica)

5 Steam insulation (airtight)

6 V Stell

7 U Aluminium Profile (Black)

8 VBF Acrylic Tape

Fastening with visible Screws heads

Fastening with visible Screws heads- Joist spacing maximum 24” o.c. – Wood (see fig 1)

Multi-Panels panels are installed on timber or metal substructures with EPDM list (Detail E).

Fig 1a below. Center holes distance from edge, minimum 1" (25 mm) and to corners minimum 2,75" (70 mm), maximum distance between screws 16" o.c. ( 410 mm), always secure holes for fastening has space for thermal expansion. Drill 0,098" (2,5 mm) oversize hole compare to the screw core diameter size, or use the Multi-Panels screw concept with EPDM washer (Detail C). The installer is responsible for establishing a plane and strong sub-construction able to obtain the wind loads appearing on the actual facade and observing the fixing distances. Facade panels are normally installed in a vertical position on a vertical sub-structure. But It is also possible to install the panels in a horizontal position. The guidelines for fixing are the same.Thermal expansion/retraction is to be accounted for.

1

2

3

4

5

5

4

7

1

7

6

8

1

4

6 3

Page 5: Siding installation for color natura and rustica

5

Fig-1: Details fastening Ventilated Siding Concept with visible Screw heads

Item Part No. Number 1 Wood Rafters 2 Insulation Material

Class A1 3 Windbarrier 4 Facade Cladding 5 Steam Insulation 6 Inside Covering 7 EPDM 8 A2 Screw

1.9" x 0.13" 9 Impregnated Wood

Latch 1" x 4" 10 Impregnated Wood

Latch 1" x 2" 11 Washer 12 EPDM

Fig-1a: Screw distance to Edges (Screw heads are normally same color as the Siding Panel)

Drill 0,098” oversize hole compare to the screw core-diameter size, for thermal expansion issues.

Page 6: Siding installation for color natura and rustica

6

Fig-2

Fastening with Rivets when wind load

If wind load demand please see fig 2 below.This table applies to a 5/16” (8 mm) panels, fastened with rivets onto metal sub-framing. Panels vertical mounted. Structural Engineer / Contract or shall assume overall responsibility for the façade engineering. Intermediate values for wind load/ spacing can be interpolated. A safety factor of 3.0 is taken into account for the admissible system load (rivet and panel).The value means the actual wind load occurring on the Siding. Fastener to panel edge distance of 1,57” (40 mm) horizontally and 3,15” (80 mm) vertically. (see fig 2-2a)

Fastening In-Visible with sub structure of U profile and VBF Acrylic tape

Multi-Panels panels are installed on timber or metal substructures. Panel size max high 2’ (600 mm) and max length 4’ (1200 mm). The installer is responsible for establishing a plane and strong sub-construction able to obtain the loads appearing on the actual façade, also local laws and fire regulations must be observed. (if accepted installed with strong VBF Acrylic tape, same adhesive as used for structural glassing). Thermal expansion/retraction is also to be accounted for.VBF Acrylic tape and U aluminium (Detail C) are supplied by Multi-Panels. (see fig 3)

This table Fig 2 shows actual wind loads on the Siding and relates neither to landscape type nor to building height. Applicable wind load values are to be determined for each project inaccordance with the local standards and for high-rise buildings with specific wind load studies.

Wind Allowable Transverse Max fasters Max fasters speed windload in psf distance distance [km/h] 1psf = 0,0479 kPa Inch - vertical Inch - horisontal

206 42 41 19” 15”

280 73 70 16” 11”

>300 94 92 12,6” 11”

Fig-2a: Sub mounting frame of metal with Rivets, mounted to Concrete, Wood

Page 7: Siding installation for color natura and rustica

7

Fig-3: Fastening as “invisible” on metal/wood substructure with U profile – VBF tape

Item Part No. Number 1 Wood Rafters 2 Insulation Material

Class A1 3 Windbarrier 4 Butyl Asthalt Tape 5 Facade Siding 6 V Stell 25-110

Ventilated Profile 7 U Aluminium Profile 8 Steam Insulation 9 Inside Covering 10 VBF Acrylic Tape

Processing and StoringCuttingAll Multi-Panels panels may be cut with a circular saw or a jigsaw equipped with a diamond tipped blade. Sharp edges are made with fast running diamond tipped tools. Cutting to size may be done with normal slow or fast running hand tools or stationary equipment. When using fast running tools, dust exhaustion must be employed. Note! When using hand tools, cut the panels backside up. When using stationary saw equipment, cut the panels front-side up (the saw blade must always attack the board from the front-side).The periphery speed of the circular saw should be 40-50 m/s. Cutting depth 3/8” – 5/8” (10-15 mm) beyond the board.

Guideline operation parameters for Multi-Panels saw bladesSawblade 0,09” (2.4mm) 0,09” 0,1” 0,1” (2.6 mm) 0,11” (2.8 mm)thickness inch: Sawblade 5,9” (150 mm) 9,05“(230 mm) 9,84”(250mm) 10,23”(260mm) 13,78”(350 mm)Ø inch: Rpm: 3800 2500 2300 2300 1650

4

9

1

2

3

107

710

4

6

6

5

8

66

Page 8: Siding installation for color natura and rustica

8

Cut-outsCut-outs may be made with a jigsaw or a key-hole saw equipped with bi-metal or diamond tipped blade. It is recommended to drill a min 5/16” (8 mm) hole before cutting in the inside corner. In order to avoid creating a notch at the inside corner, cut edges should be sanded.

Cleaning of panels after cutting and drillingIt is important immediately to remove dust caused by cutting and drilling from the front and backside of the panels with a soft brush/duster or a vacuum cleaner as it otherwise might damage the panel surface. Ensure that the panels are properly cleaned before installation, and if necessary use clean water or water with a mild detergent and a soft sponge or brush to remove dirt and dust from the surface. Thereafter, wipe the panels with a damp cloth. It may also be necessary to wash the surface after installation, if the building site conditions have been unfavorable. This is done with lots of clean water or water with a mild detergent and a soft sponge or brush and finally wiping the panels with a damp cloth.

Protective filmMulti-Panels painted panels (Color and Natura) are equipped with polyethylene film between the panels for protection of the surface during transportation and processing, which can be disposed of by deposition.

SafetyAs for all other building materials, safety precautions must be taken into account and local laws and regulations must be observed. Cutting and drilling are subject to dust development, and proper precautions must be taken by using appropriate dust extraction equipment. Dust from fibre-cement panels is characterized as mineral dust and a prolonged exposure to this may cause lung disease. Fast running electrical equipment hand held circular saws leave a fine and sharp edge on the panels and provide fine dust. Due to the speed of the blade the dust is dispersed over a larger area. Therefore, it is necessary to establish sufficient exhaustion and it is recommended the operator carry personal safety equipment.

Application conditionsBoard temperature and ambient temperature should be + 44°F (+7 °C) - 86°F (+30 °C) and relative humidity <85 % (optimally 60 %). Process temperature must be min +44°F (+7 °C).

Application - Finishing the cut of edges with Hydro Block Edge SealerNote! The Instructions are mandatory for: Color, Natura and Rustica Siding panels. Before use, shake the Hydro Block thoroughly. In case of unventilated premises, use required protective respiratory equipment, wear protective clothing, safety goggles and gloves according to the Safety Datasheet. Carefully apply the solvent based Hydro Block in a thin layer with a short hair roller. Excess Hydro Block on top of the surface should be removed immediately after painting. Disposal of this product must be with reference to local and national regulations.

Page 9: Siding installation for color natura and rustica

9

Storing- Lifted offMulti-Panels products are delivered with plastic protection cover on the pallet. If undamaged, the plastic cover protects against weather conditions during transportation. The plastic cover is for dust protection only and should be removed upon arrival at the building site. Hereafter the pallets should be kept under a roof, leaving the possibility of ventilation around the panels. Multi-Panels must be stored on a flat and dry level surface on pallets or sleepers with max 400 mm distance. Note! max 5 pallets in a stack at the warehouse and on the building side max 2 pallets in a stack. The panels must be lifted off the pallet and not drawn over the next board, as this will cause scratches and damages on the surface. Lift pallet crosswise and set forks apart to minimize bending of pallet. Fork length must support pallet entirely; if required, use fork extensions.

General InformationAnnual InspectionNormally, a Multi-Panels facade does not require maintenance to maintain its strength, properties and function, but an annual inspection of the surface, ventilation gaps, joints and fixings is recommended. Environmental impacts may, however, influence the visual appearance of the façade, detection and repair of possible damages secure a prolonged lifetime for the facade.

High Pressure CleaningWarning High Pressure Cleaning is a rough treatment of a fiber cement Siding. Use of a high pressure cleaner may damage the surface. Therefore, high pressure cleaning is not recommended.

Cleaning of dirtNever clean a facade in bright sunlight, the Multi-Panels facade panels can be cleaned with cold or hot water with the addition of a mild household detergent not containing solvents, before cleaning full scale it is recommended to test the selected cleaning method on a smaller area to make sure it answers its purpose. Rinse with plenty of clean water until the facade is perfectly clean.

Moss and Algae removalNever clean a facade in bright sunlight, moss and algae growth can be removed with common detergents available on the market, examples are: “Klorin” or “Rodalon” 2.5% active that has a long-term effect preventing of new growth. After wetting the Multi-panels with clean water, the detergents is applied according to the supplier’s instructions. Do not leave the detergents to dry completely and rinse with lots of clean water to remove the moss and algae.

Impact by Pollution and NatureThe weather and nearby vegetation may affect the appearance of the panels. Could be pollution, dust and leaves from trees, bushes and flowers do all together have an impact on the panels.

Page 10: Siding installation for color natura and rustica

10

ServiceIf you have any questions regarding the Multi-Panels facade panels, our dedicated service are ready to assist you with advice and guidance. Please visit our website for more information.

WarrantyThis warranty covers: The warranty cover the ICC-ES certification AC 90 scope/values ( US certification of fibre cement) and we confirm that we give a warranty for a period of 10 years, beginning on date of delivery, provided that,the panels were cut/drilled/stored/installed/used prescribed system components etc according to this “ Installation Manual”.

The warranty does not cover: color fading due to the UV light, environment impact on the panels as pollution etc. For the Rustica panel further not covered: color differences between batch/production series, the Rustica panel have a “raw” look, including some small white spothish in different sizes and amount on the panels, as the raw material give the appearance and the color of the Rustica panel.

Replacement: Any Multi-panels product which does not comply with these results in the data sheet tested according ICC-ES AC 90 will be replaced free of charge, ex works Los Angeles, on condition that Multi-Panels Corporation are notified within a period of 4 weeks after the appearance of any accepted claim by Multi-Panel Corporation. In particular, the warranty covers neither the transport costs nor labor expenses for dismantling and dumping defective panels and installing new panels. Multi-Panels Corporation shall not be liable for failure of performance hereunder due to force majeure.

DisclaimerThe information contained in this manual is based on Multi-Panels general experience, best knowledge and belief, however because of factors that fall beyond Multi-Panels knowledge and control, which can affect the use and function of the products, no warranty is given or implied with respect to the information.

Multi-Panels policy is one of continuous improvement and therefore reserves the right to alter specifications at any time and without notice. In case of doubt, please contact your local Multi-Panels representative.