+ All Categories
Home > Documents > Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc....

Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc....

Date post: 10-Mar-2018
Category:
Upload: truongxuyen
View: 233 times
Download: 3 times
Share this document with a friend
65
Siemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog Module (EAM)
Transcript
Page 1: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Siemens Energy & Automation, Inc. Installation and Service Instruction

SD39EAM-1 Rev: 4 September 2005

APACS+™

Enhanced Analog Module (EAM)

Page 2: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Trademarks ProcessSuite, QUADLOG, 4-mation, and APACS+ are trademarks of Siemens Energy & Automation, Inc.

Other names in this publication might be trademarks, the use of which by third parties for their own purposes may violate the rights of the registered holder.

Copyright Siemens Energy & Automation, Inc. 2005 All rights reserved

The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent or registration of a utility model or design, are reserved. Siemens Energy & Automation, Inc. 1201 Sumneytown Pike P.O. Box 900 Spring House, PA 19477-0900

Disclaimer of Liability We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual is reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. ©Siemens Energy & Automation, Inc. 2005 Technical data subject to change.

Page 3: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Contents

September 2005 i

Table of Contents

Section Title Page

1 Introduction....................................................................................................................1-1 1.1 Product Description ......................................................................................................1-1 1.2 Product Support ............................................................................................................1-2 1.3 Related Literature .........................................................................................................1-4

2 Installation......................................................................................................................2-1 2.1 Preliminary Considerations and Preparation ................................................................2-1 2.2 Hardware Identification................................................................................................2-3 2.2.1 Enhanced Analog Module (EAM) Identification...................................................2-3 2.2.2 EAM Termination Strip and EAM Marshalled Termination Assembly ................2-3 2.3 Environmental Considerations .....................................................................................2-4 2.4 Equipment Delivery and Handling ...............................................................................2-4 2.4.1 Predelivery Test .....................................................................................................2-5 2.4.2 Factory Shipment ...................................................................................................2-5 2.4.3 Receipt of Shipment...............................................................................................2-5 2.4.4 Return of Equipment within North America..........................................................2-5 2.4.5 Return of Equipment outside North America ........................................................2-6 2.4.6 Equipment Handling ..............................................................................................2-6 2.4.7 Equipment Storage.................................................................................................2-6 2.5 EAM Termination Strip Installation.............................................................................2-6 2.6 EAM Marshalled Termination Assembly and I/O Cable Installation ..........................2-9 2.6.1 Marshalled Termination Assembly Installation to DIN Rail .................................2-9 2.6.2 Optional (Flat Surface) Marshalled Termination Assembly Installation .............2-12 2.6.3 Cable Installation .................................................................................................2-14 2.7 EAM Installation ........................................................................................................2-17 2.7.1 MODULRAC Mechanical Keying ......................................................................2-17 2.7.2 Module Installation ..............................................................................................2-19 2.8 Electrical Installation..................................................................................................2-19 2.8.1 I/O Cable Connections .........................................................................................2-20 2.8.2 Unterminated I/O Cable .......................................................................................2-20 2.9 APACS Calibration Verification Requirements - Long Term Drift...........................2-20

3 Maintenance ...................................................................................................................3-1 3.1 Tool and Equipment Requirements ..............................................................................3-1 3.2 Visual Inspection ..........................................................................................................3-1 3.3 Cleaning........................................................................................................................3-2 3.4 Troubleshooting............................................................................................................3-3 3.4.1 Main Fuse Replacement.........................................................................................3-4 3.5 EAM Removal/Replacement ........................................................................................3-7 3.6 EAM Termination Strip Removal/Replacement ..........................................................3-8 3.6.1 Removal Procedure ................................................................................................3-8 3.6.2 Replacement Procedure..........................................................................................3-8 3.7 EAM Marshalled Termination Assembly Removal/Replacement ...............................3-8 3.7.1 Removal Procedure ................................................................................................3-8

Page 4: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Contents SD39EAM-1r4

ii September 2005

3.7.2 Replacement Procedure..........................................................................................3-9 3.8 EAM Interconnect I/O Cable Removal/Replacement ..................................................3-9 3.8.1 Removal Procedure ................................................................................................3-9 3.8.2 Replacement Procedure........................................................................................3-10 3.9 Spare and Replacement Parts......................................................................................3-10

4 Circuit Description ........................................................................................................4-1 4.1 I/O Communications.....................................................................................................4-1 4.2 Channel Circuitry .........................................................................................................4-2 4.2.1 Field Connections ..................................................................................................4-4 4.2.1.1 Voltage Inputs ..............................................................................................4-4 4.2.1.2 Current Inputs...............................................................................................4-5 4.2.1.3 Current Outputs ............................................................................................4-5 4.3 EAM Redundancy ........................................................................................................4-5 4.4 EAM Diagnostics .........................................................................................................4-5

5 Model Designation .........................................................................................................5-1 5.1 Accessories ...................................................................................................................5-1 5.2 Options .........................................................................................................................5-2

6 Specifications..................................................................................................................6-1 6.1 Environmental Specifications.......................................................................................6-1 6.2 EAM Mechanical/Electrical Specifictions ...................................................................6-2 6.3 Electrical Classification................................................................................................6-3

Warranty

Page 5: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Contents

September 2005 iii

List of Tables

Table Title Page

Table 2–1 Field Wiring and Terminal ID ...............................................................................................2-21

Table 2–2 Channel Terminal Connections Versus Terminal Strip Number ID......................................2-22

Table 2–3 Unterminated I/O Cable.........................................................................................................2-23

Table 3–1 LED Status Indications ............................................................................................................3-3

Table 5–1 EAM Accessories ....................................................................................................................5-1

Table 5–2 EAM Options...........................................................................................................................5-2

Table 6–1 EAM Environmental Specifications ........................................................................................6-1

Table 6–2 EAM Specifications .................................................................................................................6-2

List of Illustrations

Figure Title Page

Figure 1–1 Enhanced Analog Module and Associated Hardware ............................................................1-5

Figure 2–1 Basic Local and Marshalled I/O Connections ........................................................................2-2

Figure 2–2 EAM Termination Strip and Interconnect I/O Cable Mounting.............................................2-8

Figure 2–3 EAM Marshalled Termination Assembly.............................................................................2-10

Figure 2–4 Marshalling Termination Panel ............................................................................................2-11

Figure 2–5 Marshalled Termination Assembly, Mounting and Removal...............................................2-13

Figure 2–6 EAM Marshalled Termination Assembly Flat Surface Mounting........................................2-14

Figure 2–7 Interconnect I/O Cable Assembly and Cable Keying...........................................................2-16

Figure 2–8 Module Keying Assignment and Installation .......................................................................2-18

Figure 2–9 Sample Input and Output Connections .................................................................................2-24

Figure 2–10 I/O Cable End Preparation..................................................................................................2-25

Figure 3–1 Cover Plate Securing Screws..................................................................................................3-5

Page 6: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Contents SD39EAM-1r4

iv September 2005

Figure 3–2 User Replaceable Fuse............................................................................................................3-6

Figure 4–1 EAM Block Diagram..............................................................................................................4-2

Figure 4–2 Typical EAM Channel............................................................................................................4-4

Page 7: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Contents

September 2005 v

Significant Changes for Revision 4

Section Description

Preface (Conventions and Symbols)—new section

1.2 Product Support Table 1-1—information added

2.8.1 I/O Cable Connections—DANGER alert added

3 Maintenance—DANGER alert added

Page 8: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Contents SD39EAM-1r4

vi September 2005

PREFACE

Conventions and Symbols

The following symbols may appear in this manual and may be applied to the equipment. The reader should become familiar with the symbols and their meaning. Symbols are provided to quickly alert the user to safety related situations, issues, and text.

Symbol Meaning

DANGER

Indicates an immediate hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in property damage.

NOTICE

Indicates a potential situation which, if not avoided, may result in an undesirable result or state.

Important Identifies an action that should be taken to avoid an undesirable result or state. Note Identifies additional information that should be read.

Electrical shock hazard. The included Warning text states that the danger of electrical shock is present.

Electrical shock hazard. Indicated that the danger of electrical shock is present.

Explosion hazard. Indicates that the danger of an explosion hazard exists.

Electrostatic discharge. The presence of this symbol indicates that electrostatic discharge can damage the electronic assembly.

Page 9: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Contents

September 2005 vii

Qualified Persons

The described equipment should be installed, configured, operated, and serviced only by qualified persons thoroughly familiar with this publication. The current version, in Portable Document Format (PDF), is available at http://sitescape.sea.siemens.com/.

For the purpose of this publication and product labels, a qualified person is one who is familiar with the installation, construction, and operation of the equipment, and the involved hazards. In addition, he or she has the following qualifications:

• Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices.

• Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.

• Is trained in rendering first aid.

Scope

This publication does not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to one of the support groups listed in the Product Support section of this manual.

The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements continued herein do not create new warranties or modify the existing warranty.

General Warnings and Cautions

WARNING

This equipment contains hazardous voltages, and it has been certified for use in the hazardous locations specified on the product nameplate and in the Model Designation and Specifications section. Death, serious personal injury, or property damage can result if safety instructions are not followed. Only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all warning, safety notices, and maintenance procedures contained herein. The successful and safe operation of this equipment is dependent upon proper handling, installation, operation, and maintenance.

The perfect and safe operation of the equipment is conditional upon proper transport, proper storage, installation and assembly, as well as, on careful operation and commissioning.

The equipment may be used only for the purposes specified in this publication.

Page 10: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Contents SD39EAM-1r4

viii September 2005

CAUTION

Electrostatic discharge can damage or cause the failure of semiconductor devices such as integrated circuits and transistors. The symbol at right may appear on a circuit board or other electronic assembly to indicate that special handling precautions are needed.

• A properly grounded conductive wrist strap must be worn whenever an electronics module or circuit board is handled or touched. A service kit with a wrist strap and static dissipative mat is available from Siemens (PN15545-110). Equivalent kits are available from both mail order and local electronic supply companies.

• Electronic assemblies must be stored in anti-static protective bags when not installed in equipment

DANGER

Electrical shock hazard Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there

are no hazardous voltages before working on equipment. • In potentially hazardous atmosphere, remove power from

equipment before connecting or disconnecting power, signal, or other circuit, or extracting/inserting module.

• Observe all pertinent regulations regarding installation in hazardous area.

• Ensure all devices are rated for hazardous (classified) locations.

Page 11: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Introduction

September 2005 1-1

1 Introduction

This Instruction provides installation and service information for the APACS+™ Enhanced Analog Module (EAM) Model 39EAMBAN and its associated I/O termination hardware as listed in Table 6-2.

This Instruction is divided into six major sections as follows:

• Section 1, Introduction - Provides product description and related literature sections

• Section 2, Installation - Describes mechanical and electrical installation.

• Section 3, Maintenance - Consists of preventive maintenance, troubleshooting, assembly replacement procedures, and spare and replacement parts suggestions.

• Section 4, Circuit Description - Gives a brief system description of the EAM.

• Section 5, Accessories and Options - Provides Model Designation, and tables of accessories and options.

• Section 6, Specifications - Consists of mechanical, electrical, and environmental specifications.

1.1 Product Description

The Enhanced Analog Module (EAM) is a plug-in I/O module which is part of the APACS+ series of control, interface and I/O modules. The EAM is capable of communicating with an APACS+ control module (ACM) way of the IOBUS. The EAM processes 16 field I/O signals. Figure 1-1 shows the EAM and its associated assemblies and cables.

The EAM Termination Strip and EAM Marshalled Termination Assembly each provide channel-to-channel and channel-to-ground isolated terminations for 16 channels of I/O. Each EAM channel can be separately configured using the 4-mation™ configuration software to be one of the following channel types:

• Analog Input/Output • Frequency Input • Totalizer Input • Discrete Input/Output

When a controller configuration is downloaded from a computer running 4-mation to a control module, the EAM portion of the configuration is automatically copied from the control module to the EAM. The control module retains a copy of the EAM configuration. This permits the on-line removal and replacement of the EAM without the need for reconfiguration.

EAM diagnostics can identify field and board level problems. All errors detected by the diagnostics are reported to the controller which maintains a current error log that can be accessed by 4-mation. EAM status is shown by “OK” and “ACTIVE” LED indicators located on the bezel.

Page 12: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Introduction SD39EAM-1r4

1-2 September 2005

The APACS+ architecture provides for rack-to-rack redundancy, where the redundant rack completely duplicates the control and I/O modules of the primary rack. Both racks share common I/O terminations at the Marshalled Termination Assembly via Interconnect I/O Cables.

1.2 Product Support

Our Technical Support Centers (TSC) offer a variety of technical support services that are designed to assist you with Siemens products and systems. Our support engineers have experience with troubleshooting, development, system startup, and system test. They will help you to solve your issues in an efficient and professional manner.

Customers in North America can contact Siemens Technical Support Center at 1-800-333-7421, on the web at: http://support.automation.siemens.com, or by e-mail: [email protected]

Customers outside North America can contact their local Siemens subsidiary; addresses and telephone numbers are listed on the Internet at the web site: http://support.automation.siemens.com.

When contacting Siemens, customers will be asked to provide site-contact information (name, address, and phone number), the product involved and detailed information regarding the nature of the issue.

Product documentation is now located in the Library forum of the Process Automation User Connection at: http://sitescape.sea.siemens.com/. The Process Automation User Connection is a secure site. Registration is open to all verified users of Siemens process automation systems. If you are not already, and would like to become a member, please visit our Process Automation User Connection web page at: http://www.sea.siemens.com/process/support/papauc.html

Contained within the Process Automation User Connection is the APACS+/QUADLOG Secure Site at: http://sitescape.sea.siemens.com/forum/aca-1/dispatch.cgi/f.apacsquadlo forum. This site is only open to customers with an active service agreement. It contains all service manuals, service memos, service notes, configuration manuals, etc. for the APACS+ and QUADLOG family of products. If you are experiencing technical difficulties with the site, please contact SiteScape technical support at: toll free 1-877-234-1122 (US) or 1-513-336-1474.

Page 13: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Introduction

September 2005 1-3

A&D Technical Support Worldwide, available 24 hours a day:

Beijing

Nürnberg

Johnson City

United States: Johnson City, TN Worldwide: Nürnberg Asia / Australia: Beijing Technical Support 24 hours a day, 365 days a year Phone:+49 (180) 5050-222 Fax:+49 (180) 5050-223 E-Mail: [email protected] GMT:+1:00

Technical Support and Authorization Local time: Monday to Friday 8:00 AM to 5:00 PM Telephone:+1 (423) 262 2522 or +1 (800) 333-7421 (USA only) Fax:+1 (423) 262 2289 Mail to: [email protected] GMT: -5:00

Authorization Local time: Monday to Friday 8:00 AM to 5:00 PM Phone: +49 (180) 5050-222 Fax: +49 (180) 5050-223 Mail to: [email protected] GMT: +1:00

Technical Support and Authorization Local time: Monday to Friday 8:00 AM to 5:00 PM Phone:+86 10 64 75 75 75 Fax:+86 10 64 74 74 74 Mail to:[email protected] GMT:+8:00

Automation and Drives Service and Support International http://www.siemens.com/automation/service&support

The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.

Page 14: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Introduction SD39EAM-1r4

1-4 September 2005

1.3 Related Literature

The following documents should be available during EAM installation and configuration.

• MODULRAC Installation and Service Instruction (document number SD39MODULRAC-1)

• SIXRAC Installation and Service Instruction (document number SD39SIXRAC-1)

• UNIRAC Installation and Service Instruction (document number SD39UNIRAC-1)

• Using the 4-mation Configuration Software (document number CG39-20)

• APACS+ I/O Module Configuration (document number CG39-24)

Page 15: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Introduction

September 2005 1-5

Figure 1–1 Enhanced Analog Module and Associated Hardware

Page 16: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog
Page 17: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-1

2 Installation

This section describes installation of the EAM and its associated assemblies. Review the steps in the following section before continuing with EAM installation.

2.1 Preliminary Considerations and Preparation

Figure 2-1 shows typical local and marshalled I/O wiring. I/O connections between field devices and either local or marshalled terminations are wired with user-supplied cable. Typical cable has a jacket and two insulated, twisted-pair conductors with shield. This cabling is referred to as I/O cable.

When marshalled termination is employed, an Interconnect I/O Cable Assembly connects the EAM Marshalled Termination Assembly to the MODULRAC and EAM. Interconnect I/O Cable Assembly part numbers and their standard lengths are presented in section 5. An Interconnect I/O Cable length must be determined before proceeding with the installation of hardware assemblies.

1. Install the MODULRAC and the Local Termination Panel (for local termination only) in the cabinet where EAMs are to be installed. EAMs should not be installed in the MODULRAC at this time; however, the MODULRAC slot numbers for EAM installation should be known.

2. If local I/O termination is employed, tag all I/O cables and route them into the cabinet. They should be ready for cable end preparation and connection to the EAM Termination Strips.

3. If remote termination is employed, tag all I/O cables and route them into the marshalling cabinet. They should be ready for cable end preparation and connection to the EAM Marshalled Termination Assemblies.

Also, route the EAM Interconnect I/O Cable (or Unterminated I/O Cable) between the marshalling cabinet and the cabinet containing the MODULRAC. See Figure 1-1; J1 will be installed in the MODULRAC and P2 will connect to the EAM Marshalled Termination Assembly in the marshalling cabinet.

Page 18: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-2 September 2005

Figure 2–1 Basic Local and Marshalled I/O Connections

Page 19: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-3

2.2 Hardware Identification

2.2.1 Enhanced Analog Module (EAM) Identification

The Enhanced Analog Module is identified by the letters “EAM” on the bezel and by two nameplate labels: a large label, shown here, located on the tracking plate (left side of module in Figure 1-1), and a small label inside the bezel compartment. Access to the bezel compartment is by loosening a captive screw in the hinged compartment cover. Both labels contain the module’s model designation, part number, ROM version identification, and serial number. The larger label also shows the module’s current and voltage requirements. Space is provided for additional information, such as agency certifications.

MODEL 39EAMBAN AMPS x.xxx A PN 16154-1 ROM VERSION 2.00 VOLTS 24 VDC S/N xxxxxxxx

2.2.2 EAM Termination Strip and EAM Marshalled Termination Assembly

The EAM Termination Strip and EAM Marshalled Termination Assembly are identified by the following information silkscreened on the component side of the appropriate assembly:

EAM EAM ENHANCED ENHANCED

ANALOG MODULE ANALOG MODULE MOORE PRODUCTS CO. MOORE PRODUCTS CO.

TERMINATION STRIP MARSHALLED TERMINATION PN 16189-1 ASSEMBLY

PN 16190-1

Page 20: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-4 September 2005

2.3 Environmental Considerations

Many industrial environments create severe operating conditions. The conditions at each EAM location must be within the specifications stated in section 6.

CAUTION

Exceeding the specified operating temperature limits can adversely affect performance and may cause damage. Air temperature should be periodically checked to ensure that this specification is not being exceeded.

To ensure reliable data communications, it would be prudent to locate APACS modules (enclosures) as far as possible from sources of interference such as high current electrical equipment which emit strong electromagnetic fields and switching transients.

Industrial environments often contain particulate, liquid, and gaseous contaminants. Particulate matter, usually dust and dirt, is abrasive and can cause intermittent contact in connectors associated with circuit assemblies. A layer of dust on circuit boards will interfere with semiconductor heat dissipation. Liquid and gaseous contaminants can have a corrosive effect on metal, rubber, plastic and circuit board components. Extended exposure to this environment may result in equipment malfunction.

To reduce contaminant related equipment malfunctions:

4. Identify contaminants and implement methods to reduce their presence.

2. When cleaning equipment and surrounding area, especially the floor, either vacuum away all dust and dirt or use a dampened rag or mop.

3. Clean or replace all air conditioning filters, room air filters, and equipment filters regularly. Inform personnel with access to APACS modules of the need for area cleanliness.

2.4 Equipment Delivery and Handling

The following subsections provide information of interest to shipping, receiving, and warehouse personnel.

Page 21: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-5

2.4.1 Predelivery Test

An EAM that will be installed by the user is fully tested and inspected to ensure proper operation. If the EAM is ordered factory installed in a MODULPAC or other enclosure, the EAM is tested as part of the APACS system and inspected to ensure proper operation.

2.4.2 Factory Shipment

EAMs to be installed by the user are placed in static shielding bags and packaged for shipment. Accessories are packaged separately.

If the EAM is ordered factory installed in a MODULPAC or other enclosure, the enclosure is bolted to a pallet and wrapped for protection during shipment.

2.4.3 Receipt of Shipment

All cartons should be inspected at the time of their delivery for possible external damage. Any visible damage should be immediately recorded on the carrier’s copy of the delivery slip.

Each carton should be carefully unpacked and its contents checked against the enclosed packing list. At the same time, each item should be inspected for hidden damage that may or may not have been accompanied by exterior carton damage.

If it is found that some items have been damaged or are missing, notify Siemens immediately and provide full details. In addition, damages must be reported to the carrier with a request for their on-site inspection of the damaged item and its shipping carton.

2.4.4 Return of Equipment within North America

US Customers:

• Call the Repair Order PAS Inside Sales/Order Management Group at (215) 646-7400, ext 4RMA (4762) weekdays between 8:00 a.m. and 4:45 p.m. eastern time to obtain an RMA number. Mark the RMA number prominently on the outside of the shipment.

• When calling for an RMA number, provide the reason for the return. If returning equipment for repair, a detailed description of failure symptoms and system behavior will be requested. Supply a purchase order number for repairs. Follow the TSC specialist's recommendation for battery connection, if applicable.

• If applicable, you must supply a Material Safety Data Sheet (MSDS) with each item being returned if it was stored or used in a location where hazardous materials were present.

Page 22: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-6 September 2005

• Package items to be returned in their original shipping containers. Otherwise, package it for safe shipment or contact the factory for shipping recommendations. A module must be placed inside a static shielding bag to protect it from electrostatic discharge.

Canadian customers:

Contact Siemens Canada.

2.4.5 Return of Equipment outside North America

Contact your Siemens Representative.

2.4.6 Equipment Handling

The EAM is completely enclosed and may be safely handled without undertaking special ESD handling procedures provided the bezel compartment door is closed and secured. DO NOT touch the connector pins on the back of the module. Handle the module carefully and do not subject it to excessive shock or vibration.

CAUTION

Use a grounded wrist strap to provide ESD protection whenever the bezel door is opened.

2.4.7 Equipment Storage

The storage temperature and humidity parameters of section 6 must be met for storage of an EAM.

2.5 EAM Termination Strip Installation

A EAM Termination Strip is to be installed at the MODULRAC slot location of each EAM when local I/O termination is employed. As shown in Figure 2-2, a Local Termination Panel must be installed. Refer to Figure 2-2 and the following installation procedure:

1. Consult user documentation and note the slot locations assigned to each EAM in each MODULRAC.

2. Note the following on a MODULRAC and Termination Strip:

• On a MODULRAC, locate and identify the extruded spacer to which the lower edge of the backplane is mounted. The bottom of the extruded spacer is grooved. The top edge of a Termination Strip will rest in this groove.

Page 23: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-7

• Identify ten alignment pins located below the MODULRAC frame that span the width of the MODULRAC panel. One of these pins will engage a hole located on the Termination Strip above the MOORE logo. The left-most pin corresponds to MODULRAC slot #1.

• The Termination Strip’s captive mounting screws can be seen projecting from the bottom of the plastic extrusion panel.

Page 24: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-8 September 2005

Figure 2–2 EAM Termination Strip and Interconnect I/O Cable Mounting

Page 25: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-9

3. Mount each Termination Strip at its assigned location as follows:

1) At the EAM slot, angle the top edge of the termination strip toward the backplane’s extruded spacer and insert the tip of the termination strip in the spacer’s groove.

2) Slide the termination strip in the groove until it is vertically and horizontally aligned with the appropriate pin (slot #).

3) Carefully lower the termination strip and engage the pin with the extrusion and board pin mounting hole. Firmly push down to seat the strip on the pin. When the strip is properly seated, the pin will be flush with or project slightly above the top surface of the termination strip.

4) Tighten the captive mounting screws which are automatically aligned with their respective panel mounting holes.

2.6 EAM Marshalled Termination Assembly and I/O Cable Installation

This section describes installing the Marshalled Termination Assembly to a DIN rail or flat surface and the installation of the Interconnect I/O Cable Assembly.

2.6.1 Marshalled Termination Assembly Installation to DIN Rail

The EAM Marshalled Termination Assembly snaps onto a user supplied DIN rail of the following type:

• Preferred: Top hat profile EN 50 022-35mm X 7.5mm or EN 50 022-35mm X 15mm

• Alternate: G-profile EN 50 035-G 32mm

Use the following procedure to install an EAM Marshalled Termination Assembly to a Utility Panel, a Marshalling Utility Panel, or a user fabricated panel.

1. Utility Panel or a user-fabricated panel - Mount user-supplied DIN rails and wire duct to the Panel.

1) Determine the mounting layout of Marshalled Termination Assemblies and wire duct. Refer to Marshalled Termination Assembly and Utility Panel dimensions in Figures 2-3 and 2-4.

2) Drill and tap DIN Rail mounting holes in the Utility Panel. Remove all burrs and metal debris and clean the panel before proceeding.

Page 26: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-10 September 2005

Figure 2–3 EAM Marshalled Termination Assembly

Page 27: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-11

Figure 2–4 Marshalling Termination Panel

Page 28: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-12 September 2005

2. Mount the Marshalling Utility Panel, Utility Panel or user fabricated panel in a MODULPAC marshalling cabinet or user supplied cabinet. Refer to Instruction SD39MODULPAC-1 for installation of the Utility Panel or Marshalling Utility Panel.

3. Retrieve the EAM Marshalled Termination Assembly to be mounted including a supplied bag of EAM labels (PN 14205-665) and a Cable Keying Kit (PN 16056-435). Set aside the Cable Keying Kit.

1) Consult user documentation and note the MODULRAC address number (1 to 16) and slot number (1 to 10) assigned to the EAM, and if applicable the redundant EAM that will be connected to this EAM Marshalled Termination Assembly. For rack-to-rack redundant EAMs connected to a MODULNET, the MODULNET node address must also be noted for each MODULRAC.

2) Retrieve an EAM label and record the noted MODULRAC and slot numbers on the label (see Figure 1-1) If MODULNET redundancy is applicable, record the appropriate node addresses on both EAM labels. Save the remaining labels for use in section 2.6.3.

4. Refer to Figure 1-1 and attach the EAM label adjacent to connector J1 as illustrated in the figure. If applicable, attach the redundant EAM label adjacent to J2. Ensure that J1 and J2 are factory keyed according to the pattern shown in Figure 2-3. The user then keys the connector on the mating Interconnect I/O Cable, in section 2.6.3. This prevents connection to the Termination Assembly of an Interconnect I/O Cable from another type of APACS I/O module (e.g. SDM or VIM).

5. Refer to Figure 2-5 to mount the EAM Marshalled Termination Assembly to a DIN rail.

2.6.2 Optional (Flat Surface) Marshalled Termination Assembly Installation

The removal of the DIN rail mounting feet from the EAM Marshalled Termination Assembly (MTA), in conjunction with the installation of four Mounting Ears (accessory item), permits the MTA to be flat mounted to a panel or bulkhead. Four P/N 16056-562 (single piece) Mounting Ears are required per MTA.

Refer to Figure 2-6 and the following installation procedure:

1. At one end of the MTA, remove the three end cap securing screws from the card holder End Cap. Remove and set aside the End Cap.

2. Slide the DIN rail mounting feet from the grooves in the bottom of the MTA card holder. Discard the mounting feet and re-install the just removed End Cap.

3. Retrieve four Mounting Ears and insert them in the appropriate mounting holes provided in the End Caps as illustrated in Figure 2-6.

4. Use the MTA as a template to mark the location of the mounting ear holes on the surface of the panel. Refer to Figure 2-3 for MTA dimensions.

5. Typical mounting screw size is M4, or users can select another size. After drilling or punching the holes, the holes should be threaded.

Page 29: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-13

Figure 2–5 Marshalled Termination Assembly, Mounting and Removal

Page 30: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-14 September 2005

Figure 2–6 EAM Marshalled Termination Assembly Flat Surface Mounting

2.6.3 Cable Installation

An Interconnect I/O Cable (Figure 2-7) is used to connect each EAM to an EAM Marshalled Termination Assembly when remote I/O termination is employed. Install cable-to-module connector J1 at the MODULRAC slot location of an EAM. It is assumed that as part of the site preparation procedure all tagged Interconnect I/O Cables have been routed and pulled into their respective cabinets and are ready for connection. EAM Marshalled Termination Assemblies should already be installed in the marshalling cabinet (see section 2.6.1) and be ready for cable connection. An Unterminated I/O Cable is installed similarly at the MODULRAC; however, terminations in the marshalling cabinet are user supplied.

1. Note the following on the cable’s J1 connector.

• The lower face of the molded connector has a “pin mounting hole” located above a captive mounting screw. This hole engages one of the MODULRAC Panel’s ten alignment pins.

• The top edge of J1 will rest in the groove of the backplane’s extruded spacer as illustrated by a detail in Figure 2-2.

2. Consult user documentation and note the MODULNET node address (if any), MODULRAC address number (1 to 16) and slot number (1 to 10) assigned to the EAM. J1 will be mounted at this location.

Page 31: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-15

3. Install J1 at its assigned location as follows:

1) Angle the top edge of J1 toward the backplane’s extruded spacer and insert it in the spacer’s groove.

2) Slide J1 in the groove until it is aligned vertically and horizontally with the correct slot # and pin.

3) Carefully lower J1 and engage the alignment pin with its pin mounting hole. Firmly push down to seat J1 on the pin. When J1 is properly seated, the pin will be flush with or project slightly above J1's face.

4) Tighten J1's captive mounting screw, which is automatically aligned with its panel mounting hole.

5) Get two labels from the bag of EAM labels. Record on each label the appropriate numbers noted in the above step 2 (see Figure 1-1). Attach one label to J1 as shown in Figure 1-1.

6) At the P2 end of the cable, attach a second label; see Figure 1-1.

4. Key cable connector P2.

1) Get the PN 16056-435 Cable Keying Kit set aside in step 3 of section 2.6.1.

2) Refer to Figure 2-7 for the assigned keying pattern and install the pins in accordance with the supplied Instruction.

5. Connect the free end of the I/O Cable to an I/O termination assembly. Perform either of the following steps 1) or 2) depending upon I/O Cable type.

Page 32: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-16 September 2005

Figure 2–7 Interconnect I/O Cable Assembly and Cable Keying

Page 33: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-17

1). Interconnect I/O Cable Assembly (P2 installed)

Connect P2 (Figure 2-7) to the “A” (J1) connector on the Marshalled Termination Assembly (Figure 1-1). A keying pin projecting from the face of P2 ensures a correct mating. Press P2 firmly onto J1 and torque the securing screw on the top of P2’s connector shell to 50 inch-pounds maximum.

2). Unterminated I/O Cable Assembly (P2 not installed)

Refer to Table 2-3 for color code identification and function of each unterminated wire. Refer to user wiring diagrams to make the proper cable connections to the termination assembly.

6. Redundant EAMs only.

Connect the redundant Interconnect I/O Cable’s P2 connector to “B” (J2) of the Marshalled Termination Assembly as described in the above step 5.

2.7 EAM Installation

Modules are shipped individually packaged in protective, sealed, static shielding bags. Refer to section 2.4 for module handling considerations.

Each MODULRAC slot and each module must be keyed to prevent accidental installation of a module into an incompatible slot, which may impair system performance. Keying is highly recommended; see Figure 2-8.

• Modules are keyed at the factory. The keying pattern is unique to each module type (e.g. ACM, EAM, SDM). See Figure 2-8 for the EAM keying pattern.

• A MODULRAC installed in a cabinet by the factory is keyed at the factory. A user-installed MODULRAC is keyed by the user according to the module type assigned to each slot. This keying pattern complements the module’s keying pattern. Stop plugs are supplied with the MODULRAC.

• When adding a module to a MODULRAC, be sure to key the MODULRAC slot. Section 2.7.1 describes keying a MODULRAC slot. Section 2.7.2 describes installing the module in the MODULRAC.

2.7.1 MODULRAC Mechanical Keying

1. Get the MODULRAC Keying Kit supplied with the MODULRAC.

2. Refer to Figure 2-8 and note the MODULRAC keying pattern. Also, locate the MODULRAC top and bottom rails. Press the stop plugs into the holes identified by the solid dots.

Page 34: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-18 September 2005

Figure 2–8 Module Keying Assignment and Installation

Page 35: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-19

2.7.2 Module Installation

Installation Procedure (Refer to Figure 2-8):

1. Refer to user documentation for the EAM MODULRAC slot number.

2. Remove the EAM from its static shielding bag and ensure that the module is keyed. Also, check the MODULRAC slot to be sure it is keyed. Refer to section 2.7.1 to install keying.

3. Insert the module in the assigned MODULRAC slot. Firmly seat the module in the backplane and termination board connectors. A properly seated module will have the rear of its bezel flush against the MODULRAC’s front rails. A keyed module that is not matched to a slot will not engage the backplane or termination board connectors or seat flush against the MODULRAC’s rails.

4. Pull open the bezel’s pivoting top and bottom handles to expose the slotted captive mounting screws and secure the module to the top and bottom rails. Close the bezel’s handles when finished.

IMPORTANT

Do not use the captive mounting screws to seat the module. Damage to the bezel can result.

2.8 Electrical Installation

The following sections describe I/O cable connections to an EAM Termination Strip or EAM Marshalled Termination Assembly. It is assumed that tagged I/O cables have been pulled into the cabinet and are ready for preparation and connection.

DANGER

Electrical shock hazard Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there

are no hazardous voltages before working on equipment. • In potentially hazardous atmosphere, remove power from

equipment before connecting or disconnecting power, signal, or other circuit, or extracting/inserting module.

• Observe all pertinent regulations regarding installation in hazardous area.

• Ensure all devices are rated for hazardous (classified) locations.

Page 36: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-20 September 2005

2.8.1 I/O Cable Connections

An EAM Termination Strip and an EAM Marshalled Termination Assembly provide for connection of up to 16 configurable input or output channels. Refer to the following for I/O cable connections:

1. Consult user EAM configuration documentation and wiring diagrams for assignments to each channel. Refer to Table 2-1 for terminal identification and connections and Figure 2-9 for wiring examples.

2. Prepare the cable conductors and shield (see Figure 2-10). Refer to Table 6-2 for wire size, stripping, and torque specifications.

3. Refer to Table 2-2 to correlate channel terminal connections and terminal strip numbers.

2.8.2 Unterminated I/O Cable

An Interconnect I/O Cable connects an I/O module to a Marshalled Termination Assembly. If the user is providing a remote termination assembly, an Unterminated Interconnect I/O Cable is required. The Unterminated I/O Cable does not have connector P2 installed. Wires are instead left for the user to terminate. Table 2-3 lists the wire color and identification information needed for termination. Refer to user wiring diagrams to make the proper cable connections to the termination assembly.

2.9 APACS Calibration Verification Requirements - Long Term Drift

The APACS analog I/O is designed to minimize calibration drift and the need for re-calibration over the life of the product. Design improvements include:

• Elimination of adjustable potentiometers • Elimination of adjustable resistors • Use of high quality, low drift components

Calibration is performed through mathematical compensation within the microprocessor program. This allows the use of matched resistors for voltage dividers and minimizes the problem of temperature coefficient matching.

Because the other sources of drift have been minimized, the dominant contributor to analog long term drift for all analog modules is the voltage reference used for the A/D or D/A circuit. Manufacturer data specifies a typical long term drift in terms of the first 1000 hours of operation. Typically, drift for the next 1000 hours will be less. In fact, studies have shown that the I/f noise model is valid for long term drift. This model indicates that the drift will be proportional to the square root of the time period as a limiting factor.

A drift of 20ppm over the first 1000 hours is a typical drift for a high quality reference such as used in all APACS analog modules. Using 30ppm to account for the other secondary drifts, such as precision resistor ratios, indicate it would, on average, take 126 years for a module to drift 0.1% from original calibration due to this mechanism. Drift of 0.05% would on average take 31 years.

Page 37: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-21

Using a more conservative 100ppm drift for 1000 hours as a worst case estimate indicate it would take greater than 11 years to drift 0.1%.

Long term drifts sigificantly greater than typical would be due to flaws inherent to the manufacturing process of the individual components or the module itself. APACS screens out even these unlikely occurrences through multiple additional layers of control. All calibration is done through mathematical compensation as mentioned above. In addition, the range of compenstion is restricted to prevent compensation for inherently defective devices. All APACS modules go through environmental stress screening before functional testing and calibration to precipitate failure of weak components. Finally, all APACS modules go through an elevated temperature burn-in followed by a final functional verification including calibration.

For these reasons, Siemens does not recommend the need for periodic verification of analog caibration more often than once every ten years if the system design can accommodate a 0.1% drift from original calibration. This recommendation is based on the assumption that specified limits for the modules have not been exceeded.

Calibration-related error messages and/or known overstress conditions being applied to analog I/O points could indicate the need for verification before the end of a ten year period.

Table 2–1 Field Wiring and Terminal ID

CHANNEL CONFIGURATION

CONNECTION TYPE (see note)

TERMINAL IDENTIFICATION

Analog Input Current · +24 Vdc to 2-Wire Transmitter · Signal Common (-) or return

PWR COM

Analog Input Voltage · (+) Input from 4-Wire Transmitter or (+) 1-5 Vdc voltage input · Signal Common (-) or return

VIN COM

Analog Output · +24 Vdc to I/P or Valve Positioner · Signal common (-) or return

PWR COM

Discrete Input Current · +24 Vdc to field contacts · Signal common or return

PWR COM

Discrete Input Voltage · +24 Vdc to field contacts · Signal common or return

VIN COM

Discrete Output · +24 Vdc to Solenoid or Relay · Signal common (-) or return

PWR COM

Frequency Input Current* · (+) frequency input (current) · Signal Common (-) or return

PWR COM

Frequency Input Voltage* · (+) frequency input (voltage) · Signal Common (-) or return

VIN COM

Totalizer Input Voltage · (+) Voltage Pulses · Signal Common (-) or return

VIN COM

Totalizer Input Current · (+) Current Pulses · Signal Common (-) or return

PWR COM

All I/O cable shield SHLD

Page 38: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-22 September 2005

NOTE: For a given channel configuration, not all connections stated will be needed (e.g. a 2-wire transmitter needs only PWR and COM connections).

*see note 7 on Figure 2-9

Table 2–2 Channel Terminal Connections Versus Terminal Strip Number ID

CHANNEL NUMBER & TERMINAL

TERMINAL STRIP

NUMBER

CHANNEL NUMBER & TERMINAL

TERMINAL STRIP

NUMBER

CHANNEL NUMBER & TERMINAL

TERMINAL STRIP

NUMBER

CHANNEL NUMBER & TERMINAL

TERMINAL STRIP

NUMBER 1-PWR 1 5-PWR 17 9-PWR 33 13-PWR 49 1-VIN 2 5-VIN 18 9-VIN 34 13-VIN 50 1-COM 3 5-COM 19 9-COM 35 13-COM 51 1-SHLD 4 5-SHLD 20 9-SHLD 36 13-SHLD 52 2-PWR 5 6-PWR 21 10-PWR 37 14-PWR 53 2-VIN 6 6-VIN 22 10-VIN 38 14-VIN 54 2-COM 7 6-COM 23 10-COM 39 14-COM 55 2-SHLD 8 6-SHLD 24 10-SHLD 40 14-SHLD 56 3-PWR 9 7-PWR 25 11-PWR 41 15-PWR 57 3-VIN 10 7-VIN 26 11-VIN 42 15-VIN 58 3-COM 11 7-COM 27 11-COM 43 15-COM 59 3-SHLD 12 7-SHLD 28 11-SHLD 44 15-SHLD 60 4-PWR 13 8-PWR 29 12-PWR 45 16-PWR 61 4-VIN 14 8-VIN 30 12-VIN 46 16-VIN 62 4-COM 15 8-COM 31 12-COM 47 16-COM 63 4-SHLD 16 8-SHLD 32 12-SHLD 48 16-SHLD 64

NOTES:

1. Table supports both the EAM Termination Strip and the EAM Marshalled Termination Assembly.

2. Channel numbers are printed on the assembly. Terminal Strip numbers (TS No) are molded into the assembly terminals.

Page 39: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-23

Table 2–3 Unterminated I/O Cable

J1, PIN P2, PIN WIRE/STRIPE COLOR

WIRE IDENT

J1, PIN P2,PIN WIRE/STRIPE COLOR

WIRE IDENT

A2 75 WH/BLK PWR 1 A20 56 GRN/WH PWR 10 C2 74 WH/RED VIN 1 C20 57 GRN/BLK VIN 10 E2 73 WH/BLUE COM 1 E20 41 GRN/RED COM 10 A4 65 WH/GRN PWR 2 A22 16 GRN/BLUE PWR 11 C4 49 WH/BRN VIN 2 C22 3 GRN/BRN VIN 11 E4 64 WH/OR COM 2 E22 17 GRN/OR COM 11 A6 91 WH/YEL PWR 3 A24 6 GRN/YEL PWR 12 C6 104 WH/VIO VIN 3 C24 19 GRN/VIO VIN 12 E6 0 WH/GRAY COM 3 E24 5 GRN/GRAY COM 12 A8 100 RED/WH PWR 4 A26 70 OR/WH PWR 13 C8 101 RED/BLK VIN 4 C26 71 OR/BLK VIN 13 E8 102 RED/BLUE COM 4 E26 72 OR/RED COM 13 A10 36 RED/GRN PWR 5 A28 85 OR/BLUE PWR 14 C10 47 RED/BRN VIN 5 C28 98 OR/GRN VIN 14 E10 46 RED/OR COM 5 E28 84 OR/BRN COM 14 A12 11 RED/YEL PWR 6 A30 96 OR/YEL PWR 15 C12 10 RED/VIO VIN 6 C30 94 OR/VIO VIN 15 E12 24 RED/GRAY COM 6 E30 95 OR/GRAY COM 15 A14 22 BLUE/WH PWR 7 A32 92 YEL/WH PWR 16 C14 8 BLUE/BLK VIN 7 C32 78 YEL/BLK VIN 16 E14 21 BLUE/RED COM 7 E32 79 YEL/RED COM 16 A16 14 BLUE/GRN PWR 8 Shield

Wire1 Shield

Wire -------

C16 27 BLUE/BRN VIN 8 E16 13 BLUE/OR COM 8 A18 44 BLUE/YEL PWR 9 C18 43 BLUE/VIO VIN 9 E18 45 BLUE/GRAY COM 9

NOTES: 1. Color for wire/stripe

Page 40: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Installation SD39EAM-1r4

2-24 September 2005

Figure 2–9 Sample Input and Output Connections

Page 41: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Installation

September 2005 2-25

Figure 2–10 I/O Cable End Preparation

Page 42: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog
Page 43: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Maintenance

September 2005 3-1

3 Maintenance

The Enhanced Analog Module and its associated I/O assemblies require minimal maintenance. Some routine maintenance is recommended in the form of a visual inspection and a possible cleaning.

DANGER

Electrical shock hazard Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there

are no hazardous voltages before working on equipment. • In potentially hazardous atmosphere, remove power from

equipment before connecting or disconnecting power, signal, or other circuit, or extracting/inserting module.

• Observe all pertinent regulations regarding installation in hazardous area.

• Ensure all devices are rated for hazardous (classified) locations.

3.1 Tool and Equipment Requirements

The following tools and equipment are necessary for servicing:

• Common electronic servicing hand tools • Digital Multimeter (DMM): Accuracy, ammeter section +/-0.05% of reading

3.2 Visual Inspection

The EAM and its associated assemblies should be subjected to a periodic visual inspection. The frequency of inspection will depend on the severity of the operating environment.

The primary aim of the inspection is to reveal any excessive accumulation of dust, dirt, or other foreign material adhering to the surfaces of transition board and protective covers of an EAM. Accumulation of dirt and dust prevents efficient heat dissipation and may cause module or system failure. An EAM installed in a cabinet complying with the NEMA 12/IP55 specification need not be inspected for cleanliness. Refer to section 3.3 for cleaning instructions.

The status of the EAM is indicated by an LED located on its bezel. Refer to section 3.4 for LED indications.

Page 44: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Maintenance SD39EAM-1r4

3-2 September 2005

3.3 Cleaning

Cleaning an EAM involves brushing or vacuuming the protective covers to restore cooling efficiency that may have been degraded by accumulated dust.

Cleaning a Termination Strip or EAM Marshalling Termination Assembly involves careful brushing and vacuuming to remove accumulated dust and dirt harboring chemical particulate that may accelerate terminal, switch, or connector contact corrosion.

Page 45: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Maintenance

September 2005 3-3

3.4 Troubleshooting

Errors are annunciated by:

• The module’s status LEDs (see Table 3-1) • The 4-mation configuration software - Error codes and messages; refer to Diagnostic Error Codes

and Software Messages (document number CG39-19) or 4-mation’s help file.

The 4-mation configuration software runs on an IBM-compatible PC or the APACS+ Rack-mounted Industrial Server (RIS).

Module status LEDs are located on the EAM’s bezel. Note LED indications, then refer to Table 3-1 for EAM status and 4-mation to determine the course of action.

Interconnect I/O Cable pin assignments are listed in Table 2-3. These are provided for troubleshooting a suspect cable.

As necessary, check field wiring and field-located devices.

The EAM, Termination Strip, and Marshalled Termination Assembly are not field serviceable, except for the EAM power fuse replacement. A failed assembly should be returned to the factory for repair.

Table 3–1 LED Status Indications

LED INDICATOR

LED INDICATION

MODULE STATUS USER ACTION

Solid Green Module OK; Configured with no faults --- Flashing Green/ Black Module Not Configured; No fault or

failure Configure module

Flashing Red/Green Fault Detected; One or more channel specific errors, or a less severe board level error

Replace module or channel fuse

Flashing Red/Black (1 per second)

1. Low or defective I/O supply 2. Failure Detected; Board level problem affecting more than one channel

Replace module

Flashing Red/Black (5 per second)

IOBUS Communication Error 1. Check ACM 2. Replace module

OK

Solid Red Module Fault, Severe Replace module Solid Green Module in Control --- ACTIVE OFF Redundant EAM in Standby Mode or

off-line configuration of module ---

Page 46: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Maintenance SD39EAM-1r4

3-4 September 2005

3.4.1 Main Fuse Replacement

The EAM’s main input fuse F1 is field replaceable. A failed main fuse is detected by on-board diagnostics and annunciated by 4-mation. Another indication of a failed main fuse is when both status LEDs on the module are OFF. A failed main fuse causes the EAM to be completely inoperative.

NOTE

A service kit containing a grounding wrist strap and static dissipative mat is required to change a fuse. Use the kit whenever the module’s protective cover is removed. A kit is available from Siemens under PN 15545-110, or a kit can be purchased locally.

Refer to Figures 3-1 and 3-2 and the following to replace a failed main fuse:

1. Prepare a work bench with a soft pad covered by a static dissipative mat.

2. Refer to section 3.5 for the EAM removal procedure. Carefully remove the module from the rack and set it on the prepared work bench. Connect the wrist strap’s ground wire to the static dissipative mat.

3. Refer to Figure 3-1 and remove the module’s protective cover. Refer to Figure 3-2 and locate and replace the failed fuse.

Fuse PN 7447-148 1.6A, 250V, FastBlo. Use a Ohmmeter to confirm that the removed fuse has failed.

4. Replace the module’s protective cover and torque all securing screws to 8 in.lbs. (+/- 1 in.lb.). Unsnap the wrist strap’s ground lead from the mat.

5. Refer to section 3.5 and install the module in the rack. Check the performance of the module. Operate the module for a period of time to ensure that a condition does not exist that will cause the replacement fuse to fail.

6. If applicable, activate the process.

Page 47: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Maintenance

September 2005 3-5

Figure 3–1 Cover Plate Securing Screws

Page 48: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Maintenance SD39EAM-1r4

3-6 September 2005

Figure 3–2 User Replaceable Fuse

Page 49: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Maintenance

September 2005 3-7

3.5 EAM Removal/Replacement

The MODULRAC/SIXRAC may remain powered while removing or installing a module.

3.5.1 Removal Procedure

1. As shown in Figure 2-7, pull open the bezel’s pivoted top and bottom handles to expose the module’s slotted captive mounting screws. Loosen the screws.

2. Grasp the top and bottom handles and pull the module from the rack.

3. Place the module in a static shielding bag and package for return. Refer to section 3.10 for return instructions.

3.5.2 Replacement Procedure

1. Remove the replacement EAM from its protective bag. The module may be safely handled, as the circuit card is shielded from access by protective covers.

2. Insert the EAM in its MODULRAC slot. Firmly seat the module in the backplane and termination board connectors. A properly seated module will have the rear of its bezel flush against the MODULRAC housing rails.

A keyed module that is not matched to a slot will not engage the backplane or termination board connectors or seat flush against the MODULRAC’s front rails.

3. As shown in Figure 2-7, pull open the bezel’s pivoted top and bottom handles to expose the module’s slotted captive mounting screws and secure the module to the top and bottom rails. Close the bezel’s handles when finished.

IMPORTANT

Do not use the captive mounting screws to seat the module. Damage to the bezel can result.

Page 50: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Maintenance SD39EAM-1r4

3-8 September 2005

3.6 EAM Termination Strip Removal/Replacement

3.6.1 Removal Procedure

Refer to Figure 2-2 and the following removal procedure:

1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field devices connected to the Termination Strip.

2. Remove the associated EAM from its slot in the MODULRAC. Place the EAM in a static shielded bag for protection.

3. Disconnect signal cables from the Termination Strip.

IMPORTANT

All signal cables should be labeled for correct reconnection.

4. Loosen the Termination Strip’s captive mounting screws. Gently lift the bottom of the Board in an arc until the board is free of its alignment pin located immediately above the "MOORE" logo. Pull the top of the Termination Strip from the grooved backplane spacer and lift it from the MODULRAC.

3.6.2 Replacement Procedure

Refer to Figure 2-2 and the following replacement procedure:

1. Refer to section 2.4 and install the replacement Termination Strip.

2. Reconnect the signal cables.

3. Install the EAM. See section 3.5.

3.7 EAM Marshalled Termination Assembly Removal/Replacement

3.7.1 Removal Procedure

Refer to Figure 2-5 and the following removal procedure:

1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field devices connected to the Termination Assembly.

2. Remove the associated EAM from its slot in the MODULRAC. Place the EAM in a static shielded bag for protection.

Page 51: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Maintenance

September 2005 3-9

3. Disconnect signal cables from the Termination Assembly.

IMPORTANT

All signal cables should be labeled for correct reconnection.

4. Refer to Figure 2-5. Press down on the Termination Assembly and carefully pull the Assembly away from the DIN rail.

3.7.2 Replacement Procedure

Refer to Figure 2-2 and the following replacement procedure:

1. Refer to section 2.5 and install the replacement Marshalled Termination Assembly.

2. Reconnect the signal cables.

3. Install the EAM. See section 3.5.

3.8 EAM Interconnect I/O Cable Removal/Replacement

3.8.1 Removal Procedure

Refer to Figure 2-2 and the following removal procedure:

1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field devices connected to the Termination Assembly.

2. Remove the associated EAM from its slot in the MODULRAC. Place the EAM in a static shielded bag for protection.

3. Disconnect Interconnect I/O Cable connector P2 or individual connections from the Termination Assembly.

IMPORTANT

All individual connections should be labeled for correct reconnection.

4. Loosen the Interconnect I/O Cable’s captive mounting screws. Gently lift the bottom of the Cable in an arc until the Cable is free of its alignment pin. Pull the top of the Cable from the grooved backplane spacer and lift it from the MODULRAC.

5. Remove the Cable from the cable tray or other cable routing equipment.

Page 52: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4

3-10 September 2005

3.8.2 Replacement Procedure

Refer to Figure 2-2 and the following replacement procedure:

1. Route the Interconnect I/O Cable between the MODULRAC and marshalling cabinet.

2. Reconnect the Cable as described in section 2.5.

3. Install the EAM. See section 3.5.

3.9 Spare and Replacement Parts

One spare EAM should be stocked for every 1 to 10 in service. A spare module or replacement termination board can be ordered from a local Siemens representative.

Part numbers are stated in section 5 and printed on most modules and associated hardware. Several module main fuses should be stocked. The part number and description are:

7447-148 1.6A, 250V, FastBlo (5 x 20 mm size)

When ordering, provide the model number, part number, and serial number from the module to be replaced or spared. A purchase order number should also be included for non-warranty purchases.

Page 53: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Circuit Description

September 2005 4-1

4 Circuit Description

The Enhanced Analog Module (EAM) is an APACS+ I/O module that is capable of communicating with an APACS+ control module (ACM) by way of the IOBUS. Figure 4-1 is a simplified block diagram of the signal processing portion of an EAM. Figure 4-2 is a block diagram of 1 of the 16 identical input/output channels.

An EAM plugs in to a single MODULRAC or SIXRAC slot. The module’s bottom rear connector mates with either the EAM Termination Strip for local I/O connections or the EAM Interconnect I/O Cable, which in turn connects to an EAM Marshalled Termination Assembly, for remote I/O connections. A Local Termination Panel is needed to mount an EAM Termination Strip when local termination is employed. The Panel is not needed when marshalled (remote) terminations are installed.

The EAM consists of the following elements:

• I/O Channel ASICs (Application Specific Integrated Circuits) - Process input/output signals. • CPU - Provides interfacing to the IOBUS and channel ASICs and control of I/O circuits. • Memory (RAM and EPROM) - Stores module executable code and configuration parameters. • IOBUS Modem - Provides digital data and command conversion needed for communication between

the EAM and control module. • I/O Communications Timing Circuit - Provides data/command and timing conversion needed for

communication between the CPU and 16 channel ASICs. • Redundancy circuit - Provides mode select/control/status signal conversion between the controller

and EAM. • Peripherals circuits - Provides data and command conversion needed for communication between the

CPU and the redundancy circuits, and channel Groups A and B optoisolators. • LED Indicators (on module bezel) - An “ACTIVE” LED indicates that the module is enabled. An

"OK" LED indicates the module status.

4.1 I/O Communications

Serial communication between Group A and B channel I/O ASICs and the CPU occurs via pulse transformers coupled to two (A and B) half-duplex, bi-directional, synchronous party-line data buses. The A and B party-line buses, each of which hosts 8 ASICs, are interfaced to serial multi-protocol ports of the CPU via an I/O communications timing circuit consisting of isolation transformers, dual high-speed line receivers and a programmable logic IC.

The communications format is a simplified HDLC (High-level Data Link Control) protocol. The clock used for I/O communications is the same as the ASIC clock. The ASIC clock is derived from a channel’s power transformer secondary waveform. A transformer is driven by a 368 KHz DC-to-DC converter.

Each channel ASIC produces an I/O value 180 times a second. Messages are sent to and from the ASIC at a rate of 180 Hz. Part of the ASIC’s internal timing is based on receiving a poll message from the CPU at precisely this rate. The I/O Communications Timing interface circuit ensures that messages between the CPU and ASIC are correctly “paced” to accommodate 1440 transmit messages per second (8 ASICs @ 180 Hz) per CPU multi-protocol port. Since each ASIC replies to its own message from the CPU, there are also 1440 receive messages per second per CPU multi-protocol port.

Page 54: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Circuit Description SD39EAM-1r4

4-2 September 2005

Figure 4–1 EAM Block Diagram

4.2 Channel Circuitry

All 16 channels have identical circuitry. As shown in Figure 4-2, the circuitry for a single I/O channel consists of the following principal components:

• An I/O ASIC • An output FET (Field Effect Transistor) • An opto-coupler • A precision 250 ohm current sense resistor • A DC-to-DC power rectifier and filter • A communications pulse transformer

Page 55: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Circuit Description

September 2005 4-3

Power is normally supplied to each isolated channel via an isolation power transformer driven by a power chopper DC-to-DC converter circuit. The transformer secondary’s voltage waveform is AC coupled into the ASIC’s clock input in addition to being rectified for isolated 24 Vdc ASIC and I/O power. The 24 Vdc I/O field power is switched through an opto-coupler and applied through a diode to the PWR terminal on a local or remote termination assembly. Additionally, the 24 Vdc is connected by a diode to the O-Sense pin of the ASIC. This pin is used for diagnosing the condition of the 24 Vdc supply and detecting the state of the external opto-coupler.

The ASIC features the following:

• An ADC (Analog-to-Digital Converter) for input signals of 0-5V or 0-20mA • A DAC (Digital-to-Analog Converter) for an output signal of 0-20 mA • Reads voltage or current frequency inputs at frequencies up to 46080 Hz • Contains built-in diagnostics • Designed for bi-directional Manchester encoded serial data over a communications transformer for

ease of isolation • Uses HDLC (Hi-Level Data Link Control) protocol • Synchronous internal digital circuits are clocked by an external clock derived from the power

transformer secondary

Each EAM channel can be separately configured via APACS 4-mation configuration software to be one of the following channel types:

• Analog input (4-20mA, 0-20mA, 1-5V, or 0-5V) • Analog output (4-20mA or 0-20mA) • Frequency input (0-46 kHz) • Totalizer input • Discrete input (sinking or sourcing) • Discrete output (sourcing)

An EAM configuration is downloaded into the module’s memory and a copy of the configuration is stored in the associated control module’s non-volatile memory.

Page 56: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Circuit Description SD39EAM-1r4

4-4 September 2005

Figure 4–2 Typical EAM Channel

4.2.1 Field Connections

The EAM Termination Strip and EAM Marshalled Termination Assembly each provide isolated termination for 16 channels of I/O. A channel comprises 4 terminals:

• PWR - Field Power Source • VIN - Field Signal (Analog/Discrete Voltage Input) • COM - Field Signal Common (Return) • SHLD - Cable Shield

There are three basic types of field terminal connections: voltage input, current input, and current output.

4.2.1.1 Voltage Inputs

Analog voltage input connections are made to the VIN and COM terminals. The COM connection is completed through the N-Channel FET Q2, which is turned on hard, and the current sense resistor R3.

The voltage signal at VIN is connected by R1 to the V-Sense input of the ASIC, which is an input to an internal ADC and pulse counting and timing circuits. In analog voltage input mode, resistor R1 is internally connected to external capacitor C1 on the C-Alias pin of the ASIC. This forms an anti-alias RC low-pass filter for the ADC.

Page 57: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Circuit Description

September 2005 4-5

R1 prevents excessive current into the ASIC when a signal up to 30 Vdc (or a miswiring up to 120 Vac) is applied to the VIN terminal. In addition, in the event of a fault within the ASIC, R1 prevents large currents from being supplied to field wiring.

4.2.1.2 Current Inputs

Current input connections are made to the PWR and COM terminals. For 2-wire (4-20 mA) current inputs, power is supplied through Opto-Coupler Q1 (which is saturated on) to the PWR terminal. The return is through Q2, which is turned on hard, and current sense resistor R3. R3 converts the current to a voltage, which is read by the ASIC at its I-Sense input through resistor R2.

The voltage input to I-Sense is an input to an internal ADC and pulse counting and timing circuits. In analog current input mode, the resistor R2 is internally connected to the external capacitor C1 on the C-Alias pin of the ASIC. This forms an anti-alias RC low-pass filter for the ADC.

4.2.1.3 Current Outputs

Current output connections are made to the PWR and COM terminals. Power is supplied through Opto-Coupler Q1 - which is saturated on - to the PWR terminal. The return is through Q2 and current sense resistor R3. However, in this case, Q2 is not turned on hard. Q2 is controlled by a feedback circuit within the ASIC so that current sensed by R3 and the I-Sense input agrees with the desired output current.

4.3 EAM Redundancy

EAM redundancy is accomplished by rack-to-rack type redundancy through pairs of duplicate racks of I/O and control modules that share a common I/O termination such as the EAM Marshalled Termination Assembly.

The EAM in standby mode is identified by a solid Green "OK" LED and a Black (OFF) ACTIVE LED. If the controller in the active rack detects an error in a module within its rack, it will transfer control to the controller in the redundant rack. The redundant controller will then enable all the I/O modules under its control. A solid Green ACTIVE LED indicates an enabled module.

4.4 EAM Diagnostics

Part of the EAM program includes the execution of diagnostics that can detect the following types of field and hardware errors.

Field Problems

• Open Circuit • Short Circuit • Under-Range • Over-Range

Page 58: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Circuit Description SD39EAM-1r4

4-6 September 2005

Board Problems

• Backplane Power Failure • Internal Module Overtemperature • RAM Checksum • ROM Checksum • Redundancy Switch-Over

An OK LED and an ACTIVE LED on the module’s bezel provide a local indication of the following module status:

• Module OK • Channel(s) Faulted • Module Faulted • Module Not Configured • IOBUS Communication Fault • Module Active (Redundancy Primary) • Module Inactive (Redundancy Backup)

The OK LED is the principal error annunciator. At initial turn on, the EAM’s CPU uses a common start up routine to perform certain self-diagnostics, such as ROM and RAM tests, and to setup specific board functions. If the common start up routine is successful, the OK LED will be set to a solid green color and the EAM begins to execute common I/O board diagnostics; if not successful, the OK LED will be set to a flashing red color at a 1 second flash rate.

The ACTIVE LED lights to a solid Green if the module is enabled. A redundant EAM in the standby mode will show a solid Green OK and Black (OFF) ACTIVE LEDs.

All errors generated by the diagnostics are reported to the control module (ACM), which maintains a current error log that can be accessed by any APACS+ operator interface or the 4-mation configuration software. The 4-mation software also provides additional diagnostic and status displays.

Page 59: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Model Designation

September 2005 5-1

5 Model Designation

Refer to the following to decode the model designation:

39EAM B A N Enhanced Analog Module (EAM) │ │ └── Electrical Approvals: N = Not Required │ └──── Design Level: A = Current Design └────── 4-mation Version: B=2.00, 2.01, 2.02, 2.03, 2.06, C=3.00 and later

5.1 Accessories

Table 5-1 lists the available EAM accessories.

Table 5–1 EAM Accessories

PART NUMBER DESCRIPTION

16114-97 Marshalling Utility Panel (Figure 2-4) Includes installed wire ducts and DIN rails for mounting APACS marshalled termination assemblies. For installation in an APACS MODULPAC cabinet.

16114-12 Blank Utility Panel (Figure 2-4) Similar to above but without installed ducts and rails. For installation in an APACS MODULPAC cabinet.

16056-468

End Stop Kit. End Stops prevent the sliding of an EAM Marshalled Termination Assembly along the mounting DIN rail.

16056-562 (single piece number)

Mounting Ear (Figure 2-6). Provides for a flat mounting of the EAM Marshalled Termination Assy. Four pieces required. Refer to section 2.6.2.

Page 60: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Model Designation SD39EAM-1r4

5-2 September 2005

5.2 Options

Table 5-2 lists the available EAM options. A selection of the type and quantity of terminaion assemblies is made by the user. When marshalled termination assemblies (P/N 16190-1 or 16805-7) are selected, a selection from the list of Interconnect I/O Cables must also be made.

Table 5–2 EAM Options

PART NUMBER DESCRIPITION 16189-1 EAM Local Termination Strip 16190-1 EAM Marshalled Termination Assembly 16805-7 EAM Marshalled Rail Termination Assembly (Consists of Phoenix Contacts)16137-122 Interconnect I/O Cable Assembly 5.7 ft. (1.75 m) 16137-114 Interconnect I/O Cable Assembly 10 ft. (3 m) 16137-115 Interconnect I/O Cable Assembly 26.2 ft. (8 m) 16137-116 Interconnect I/O Cable Assembly 49.2 ft. (15 m) 16137-117 Interconnect I/O Cable Assembly 98.4 ft. (30 m) 16137-118 Unterminated Interconnect I/O Cable Assembly 10 ft. (3 m) 16137-119 Unterminated Interconnect I/O Cable Assembly 26.2 ft. (8 m) 16137-120 Unterminated Interconnect I/O Cable Assembly 49.2 ft. (15m) 16137-121 Unterminated Interconnect I/O Cable Assembly 98.4 ft. (30 m)

Page 61: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Specifications

September 2005 6-1

6 Specifications

This section provides specifications for the APACS+ Enhanced Analog Module (EAM).

6.1 Environmental Specifications

Table 6-1 lists the environmental specifications for the EAM.

Table 6–1 EAM Environmental Specifications

CATEGORY SPECIFICATIONS DATA

Cooling Convection only IEC Class

Bx

Operating Temperature -25 to 60°C (-13 to 40°F), measured 1/4" below rack Operating Humidity 5 to 95% Non-Condensing

Temperature and Humidity

Maximum Moisture Limits 0.028 lb water/lb air Temperature -25 to 85°C (-13 to 185°F) Storage

Temperature & Humidity

Humidity 0 to 100% Condensing

Temperature -25 to 50°C (-13 to 122°F) Enclosure External Temperature and Humidty

Humidity 0-100% condensing

Immunity, Radiated IEC 801-3 Electromagnetic Field (RFI) 10 V/m @ 27 to 1000 MHz Immunity, Power Lines IEC 801-4 & I/O, Fast Transients Power: 4 kV, I/O: 2 kV Immunity, Surge, Power Lines

IEC 801-5, 4 kV

Electrical

Immunity, Electrostatic Discharge (ESD)

IEC 801-2 Contact Discharge: 8 kV Air Discharge: 15 kV Air

Page 62: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Specifications SD39EAM-1r4

6-2 September 2005

6.2 EAM Mechanical/Electrical Specifictions

Table 6-2 lists the EAM’s mechanical and electrical specifications.

Table 6–2 EAM Specifications

CATEGORY SPECIFICATION DATA Mechanical Module Weight 4.16 lbs. (1.86 Kg) EAM Termination Strip Wire Specification

Wire Strip Length Terminal Torque

14-22 AWG, solid or stranded 0.32" (8 mm) 3.48 in/lbs (0.6 mN)

EAM Marshalled Termination Assy.

Wire Specification Strip Length Terminal Torque

10-28 AWG, solid or stranded 0.32" (8 mm) 5 in/lbs (0.86 mN)

Module Power Dissipation

16 Analog Output Ch. @ 12 mA/Ch 16 Analog Output Ch. @ 20 mA/Ch 16 Discrete Output Ch.

15.5 watts typical 19 watts worst case 21.6 watts worst case

Module Input Voltage Voltage 24 Vdc +/- 5% Module Operating Current Inrush Current

16 Analog Output Ch. @ 12 mA/Ch 16 Analog Output Ch. @ 20 mA/Ch 16 Discrete Output Ch. Start Up Current

2.1 Amperes 0.64 Amperes typical 0.8 Amperes worst case 0.9 Amperes worst case Consult Factory

Module Heat Dissipation 16 Ch. @ 12 mA/Ch 16 Ch. @ 20 mA/Ch

53 BTU/hr (15.5 watts) 63 Btu/hr (18.5 watts)

Module, General Max. Continuous Input Field Power Source Linearity Scan Rate Input Impedance Common Mode Rejection

+/- 30 Vdc all channels 24 Vdc 0.025% of span 20 mS minimun > 2 Megaohms @ < 10 Hz 120 dB @ 50/60 Hz

Module Channels Number of Channels Dielectric Strength

16 (each configurable) Tested to 1950 Vdc for 2 seconds channel to channel and all channels to ground

Module Analog Input

Current Input Range Voltage Input Range Resolution Accuracy Repeatability

0-20 mA or 4-2 mA 0-5 Vdc or 1-5 Vdc 13, 14, 15, or 16 bits +/- 0.025% of span +/-0.003% of span @ 16 bits

Module Analog Output Current Input Range Resolution Accuracy Repeatability Load Limits

0-21 mA or 3.2-20.8 mA 14 bits 0.1% of span +/- 0.018% of span 50 to 800 ohms

Module Frequency Input Freqency Range Current Input Threshold Resolution Accuracy Repeatability

0.0000858 to 46080 Hz 10 mA +/- 1 mA 10, 12, 14, or 16 bits +/- 0.012% of span @ 16 bits +/- 0.002% @ 16 bits

Page 63: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

SD39EAM-1r4 Specifications

September 2005 6-3

CATEGORY SPECIFICATION DATA Minimum Pulse Width

Module Discrete Input Sourcing

Input Filter Delay Input Wetting Current

5.6 mS 20 mA

Module Discrete Input Sinking

Input Filter Delay 11 mS

Module Discrete Output

Maximum Output Current On State Voltage Range Off State Leakage Current

40 mA 14 to 24 Vdc 0.05 mA

6.3 Electrical Classification

IMPORTANT

Before installing, applying power to, or servicing an EAM, see the module’s nameplate for its electrical classification.

6.3.1 CSA Hazardous Locations Precautions

This section provides CSA hazardous location precautions that should be observed by the user when installing or servicing the equipment described in this Instruction. These statements supplement those given in the preceding section.

DANGER

Electrical shock hazard Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there

are no hazardous voltages before working on equipment. • In potentially hazardous atmosphere, remove power from

equipment before connecting or disconnecting power, signal, or other circuit, or extracting/inserting module.

• Observe all pertinent regulations regarding installation in hazardous area.

• Ensure all devices are rated for hazardous (classified) locations.

Page 64: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

Specifications SD39EAM-1r4

6-4 September 2005

Precautions - English

For Class I, Division 1 and Class I, Division 2 hazardous locations,

• Use only factory-authorized replacement parts. Substitution of components can impair the suitability of this equipment for hazardous locations.

For Division 2 hazardous locations:

When the equipment described in this Instruction in installed without safety barriers, the following precautions should be observed. Switch off electrical power at its source (in non-hazardous location) before connecting or disconnecting power, signal, or other wiring.

Précautions - Français

Emplacements dangereux de classe I, division 1 et classe I, division 2:

• Les pièces de rechange doivent être autorisées par l'usine. Les substitutions peuvent rendre cet appareil impropre à l'utilisation dans les emplacements dangereux.

Emplacement dangereux de division 2:

Lorsque l'appareil décrit dans la notice ci-jointe est installé sans barrières de sécurité, on doit couper l'alimentation électrique a la source (hors de l'emplacement dangereux) avant d'effectuer les opérations suivantes branchment ou débranchement d'un circuit de puissance, de signalisation ou autre.

Page 65: Siemens Installation and Service Instruction · PDF fileSiemens Energy & Automation, Inc. Installation and Service Instruction SD39EAM-1 Rev: 4 September 2005 APACS+™ Enhanced Analog

DECLARATION OF CONFORMITYaccording to EN 45014

Moore Products Co.Sumneytown PikeSpring House, PA 19477-0900

Declare under our sole responsibility that the product,

Models 39EAMBAN and QLEAMBAN with any factory installed options and in any configurationavailable from the factory to which this declaration relates is in conformity with the followingstandards:

EMC: EN50081-2 Generic Emission Standard: Industrial EnvironmentEN50082-2 Generic Immunity Standard: Industrial Environment

SAFETY: EN61010-1 Safety Requirements for Electrical Equipment for Measurement, Control, andLaboratory Use

following the provisions of the EMC and Low Voltage Directive.

Electromagnetic Compatibility Technical Construction File for APACS and QUADLOG, Issue 1.0,dated 11 January 1996 was issued certificate number RFI\CBCB1\32341A by

Radio Frequency Investigation LTDEwhurst ParkRamsdell, Basingstoke, Hampshire, ENGLANDRG26 5RQ

Safety Technical Construction File for Models 39EAMBAN and QLEAMBAN was created asIssue1.0, dated 10 September 1996.

Spring House, PA USA 11/1/96 -----------------------------date Edward Coll

Vice PresidentSystems Division


Recommended