B. 12
�
COUNTIS AdcCOUNTIS AMd/COUNTIS AMtCOUNTIS ATv2/COUNTIS ATiv2COUNTIS ATdCOUNTIS ATpCOUNTIS Ci
2 3
14
coun
t_10
4_a_
1_x_
cat COUNTIS ATv2/ATiv2
1. kWh display.
2. Visualisation of the total orpartial meter or to scrollthrough parameters.
3. Parameter and validationscrolling button.
4. Pulsed LCD indicates activeconsumption (10 Wh/pulse).
2 4
1
3
5
coun
t_11
9_a_
1_x_
cat
COUNTIS ATiv2dual tarif1. kWh display.
2. Visualisation of the total orpartial meter or to scrollthrough parameters.
3. Tarif visualisation key (t1, t2).
4. Parameter and validationscrolling button.
5. Pulsed LCD indicates activeconsumption (10 Wh/pulse).
FunctionsThe COUNTIS AT is an active energymeter designed for two phase and threephase networks.This product is available in 2 versions:• ATv2: non-insulated active energy meter
which cannot be used with earthed CT.• ATiv2: insulated active energy meter
which can be used with earthed CTsecondaries.
Conformity to standards• IEC 61036 class 1• IEC 61000-4-2• IEC 61000-4-3• IEC 61000-4-4• IEC 61000-4-5• IEC 61000-4-6• IEC 61000-4-8• IEC 61000-4-11• IEC 60068-2-6• IEC 60068-2-11• IEC 60068-2-30• IEC 61010-1
Applications
Countis ATv2 / ATiv2
Countis ATv2 / ATiv2
Countis ATv2 / ATiv2
coun
t_12
0_a_
1_x_
cat
Standard features include a totalisingmeter, a partial meter for direct reading inkWh and a pulse output. A partial meter(with RESET) enables totallisation ofenergy for specific time periods. The dual tarif COUNTIS ATiv2 is equipedof two totalising counters (t1, t2) allowinga direct reading in kWh and a pulse outputas standard. Two partials counters (t1, t2)with RESET will allow to count the energyon a specific period.
These three versions can be fully configuredby the user via the keypard and the display(CT ratio, pulse weight and RESET).Furthermore associated with a COUNTIS Ci,a consumption centralisation will bepossible via a PLC or a equipped PC withthe CONTROL VISION software.
Measurement control & energy management
COUNTIS ATv2COUNTIS ATiv2
COUNTIS®
system
SOCOMEC general catalogue
Standard device
B. 13
Measurement control & energy management
COUNTIS ATv2/COUNTIS ATiv2
References count_
104_
a_2_
cat
COUNTIS ATv25A CT
coun
t_11
9_a_
2_ca
t
COUNTIS ATiv25A CT
Connection Reference Reference
230 VAC/400 VAC 4850 2000 110.00 4850 2100 124.00
Accessories
Reference Reference
Panel mounting kit 192J 8015 9.31 192J 8015 9.31
Electrical characteristicsCurrent measurement (TRMS)
Type non-isolated (ATv2) / isolated (ATiv2)CT primary 5 … 6000 ACT secondary 5 A
Input consumption ≤ 1 VAPermanent overload 7 A
Voltage measurement (TRMS)
Direct measurement between phases 230 VAC -15% … 400 VAC +20%Input consumption ≤ 0.5 VA
Energy accuracy
Active (according to IEC 61036) class 1
Auxiliary power supply
Self-supplied yes
Frequency 50/60 Hz
Consumption ≤ 1 VA
Outputs (pulse)
Number 1Type reed relay 100 VDC - 0.5 A - 10 VAProgrammable impulse weight 100 Wh … 100 kWhImpulse duration 60 … 900 msMax. number of operations 5 x 107
Operating conditions
Operating temperature -5 … +45 °CStorage temperature -20 … +70 °CRelative humidity 85%
Overall dimensions70
85
44
58
45
kWhkWh
PROG
Tot.Tot. Part.Part.
COUNTIS ATV 2
coun
t_12
1_b_
1_x_
cat
Type modularNumber of DIN modules 4Dimensions H x W x D 70 x 85 x 58 mmCase protection rating IP20Front protection rating IP5XDisplay type LCDTerminal blocks type fixedFlexible cable connection section 0.5 … 6 mm2
Rigid cable connection section 1 … 10 mm2
Weight 500 g
SOCOMEC general catalogue
coun
t_15
2_a_
2_ca
t
COUNTIS ATiv2dual tarif 5A CT
Reference
Reference
192J 8015 9.31
Dual tarif device
Connection
230 VAC/400 VAC
Reference
4850 2102 161.20
B. 14
�
COUNTIS AdcCOUNTIS AMd/COUNTIS AMtCOUNTIS ATv2/COUNTIS ATiv2COUNTIS ATdCOUNTIS ATpCOUNTIS Ci
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
NL1L2L3
S2
S2
P1
S1
P1
S1
31 75 119
S2S1 S2S1 S2S1
ATiv2
coun
t_12
3_a_
1_gb
_cat
• 3/4 wires with 3 CTs
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
L1L2L3
S2
P1
S1
P1
S1
31 75 119
S2S1 S2S1 S2S1
ATiv2
coun
t_12
4_a_
1_gb
_cat
• 3 wires with 2 CTs
The use of 2 CTs reduces by 0.5% the accuracy of thephase whose current is determined by vector calculation.
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
L1L2L3
S2
S2
P1
S1
P1
S1
31 64 97
S2S1 S2S1 S2S1
ATiv2
coun
t_12
5_b_
1_gb
_cat
• 3 wires with 2 CTs
The use of 2 CTs reduces by 0.5% the accuracy of thephase whose current is determined by vector calculation.
Measurement control & energy management
COUNTIS ATv2COUNTIS ATiv2
COUNTIS®
system
SOCOMEC general catalogue
Terminals• COUNTIS ATv2 / ATiv2
kWh I1 I2 I3
L3L2L1N
2 4 6 10 12 148
S1 S2 S1 S2 S1 S2
COUNTIS ATv2COUNTIS ATiv2
1 3 7 9 115
coun
t_12
2_a_
1_x_
cat
1 - 3: phase 1 current input2, 4, 6 & 8: voltage inputs5 - 7: phase 2 current input9 - 11: phase 3 current input12 - 14: pulse output for external meter10: unused
• COUNTIS ATiv2 double rate
kWh I1 I2 I3
L3L2L1N
2 4 6 10 12 148
S1 S2 S1 S2 S1 S2
COUNTIS ATiv2double rate
1 3 7 9 115
t1 =
0 V
ACt2
= 2
30 V
AC
coun
t_14
9_a_
1_gb
_cat
1 - 3: phase 1 current input2, 4, 6 & 8: voltage inputs5 - 7: phase 2 current input9 - 11: phase 3 current input12 - 14: pulse output for external meter10: tarif changement input
Connections
�
Low voltage unbalanced network
Earthing of current transformers for COUNTIS ATiv2 only.
B. 15
Measurement control & energy management
COUNTIS ATv2/COUNTIS ATiv2
SOCOMEC general catalogue
�
Low voltage balanced network
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
S2
P1
S1
NL1L2L3
31 75 119
S2S1 S2S1 S2S1
ATiv2
coun
t_12
6_a_
1_gb
_cat
• 3/4 wires with 1 CT
The use of 1 CT reduces by 0.5% the accuracy of thephase whose current is determined by vector calculation.
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
S2
P1
S1L1L2
31 75 119
S2S1 S2S1 S2S1
ATiv2
coun
t_12
7_a_
1_gb
_cat
• Two phase
Fus.
0.5
A g
GB
S88
2A
gG
L3L2L1N
2 4 6 8
S2
P1
S1L1N
31 75 119
S2S1 S2S1 S2S1
ATiv2
coun
t_12
8_b_
1_gb
_cat
• Single phase
�
Other information
12 14
Us
000242kWh
coun
t_12
9_a_
1_x_
cat
• External meter with external powersupply
Connections