Installation manual SolarMax TS-SV 330TS-SV / 360TS-SV
Transcript
Page 1: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

Installation manual

SolarMax TS-SV330TS-SV / 360TS-SV

Page 2: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

SolarMax Produktions GmbH

Zur Schönhalde 10

D-89352 Ellzee

E-Mail: [email protected]

© SolarMax Produktions GmbH 2015

Page 3: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches
Page 4: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

4

Contents1 About this installation manual 61.1 Field of applicability 61.2 Target group 61.3 Where to keep this manual 61.3 Symbols used in this manual 6

2 Safety 72.1 Safety instructions 72.2 Appropriate use 8

3 Description of the station components 93.1 SolarMax TS-SV inverter 93.1.1 Block diagram of the TS-SV inverter 103.1.2 External operating elements and dimensions 113.1.3 Scope of delivery 113.2 TS-SV master control unit (MCU) 123.2.1 Exterior view and dimensions of the MCU 123.3 Configuration variants of the station 133.3.1 Multi MPPT operation mode 143.3.2 Single MPPT operation mode 153.4 Additional station components 163.4.1 DC fuse unit 163.4.2 Autonomous power supply transformer 163.4.3 Medium-voltage transformer 173.4.4 Medium-voltage switchgear 18

4 Installation 194.1 Transport & storage of the inverter 194.1.1 Means of transport 194.1.2 Storage conditions 204.2 Site selection and operating conditions of the inverter 204.2.1 Specifications and instructions for site selection 204.2.2 Operating conditions at the site 214.2.3 Cooling system of the inverter 224.3 Recommendations for station construction 224.3.1 Heating 234.3.2 Excavating the construction site 234.4 Lightning protection 244.5 Montage 244.5.1 Inverters 244.5.2 MCU 24

Page 5: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

5

en

5 Electrical connection 255.1 Guidelines for electrical installation 255.2 Earthing of the station components 255.3 Connecting the inverter 265.3.1 Interior view of the inverter 265.3.2 Connecting the inverters to the PV plant 275.3.3 Connecting the inverters to the medium voltage transformer 305.3.4 Connecting the inverters to the modular bus 325.3.5 Assigning addresses to the power units 335.3.6 Connecting the shutdown contact 1 (optional) 345.4 Connecting the MCU 365.4.1 Interior view of the MCU 365.4.2 Connecting the DC feed line to the MCU 375.4.3 Connecting the AC feed line to the MCU 375.4.4 Connecting the MCU to the modular bus 385.4.5 Connecting the protective earth (PE) line to the MCU 385.4.6 Interface and contacts of the MCU 385.5 Configuring the MCU 415.6 Connecting the other station components 425.7 Application examples for single-MPPT operation 435.7.1 DC fuse unit with several DC bus bars 445.7.2 DC Fuse unit with common DC bus bar 46

6 Commissioning 486.1 Inspections prior to startup 486.1.1 Identification and characteristics 486.1.2 Station 486.1.3 Inverters 496.1.4 Operational configuration and MCU 496.1.5 DC wiring in general 496.1.6 DC wiring for multi MPPT operation 496.1.7 DC wiring for single MPPT operation 506.1.8 AC wiring 506.1.9 Data communication 506.1.10 Earthing 506.2 Commissioning (Initial Setup) 51

7 Technical data 537.1 Efficiency curve 557.2 Temperature-dependent output reduction 577.3 Individual country settings 587.3.1 SM330TS-SV 587.3.2 SM360TS-SV 60

8 Warranty 63

Page 6: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

6

1 About this installation manual

1.1 Field of applicability

This installation manual describes how to install and commission the inverters SM330TS-SV, SM360TS-SV (TS-SV inverters) and the control unit TS-SV Master Control Unit (MCU).

1.2 Target group

This installation manual is intended for the station outfitter (responsible qualified elec-trician) who is responsible for building the station and designing the project-specific components.

1.3 Where to keep this manual

The system operator must ensure that this installation manual is available to those responsible for the power plant at all times. If this original manual is lost, an up-to-date version can be downloaded from our website at all times (www.solarmax.com).

1.3 Symbols used in this manual

From time to time you will see the following symbols when reading this installation manual:

DANGERThis symbol indicates that ignoring this instruction can lead directly to serious injury or death.CAUTIONThis symbol indicates that ignoring this instruction can lead to damage to your inverter or your PV power plant.NOTEThis symbol indicates information which is especially important for operating the inverter.

Page 7: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

7

en

2 Safety

2.1 Safety instructions

DANGER

■■ In daylight the PV generator supplies the inverter with a dangerously high DC voltage.

■■ Only qualified electricians who have already completely read and understood this manual in advance may install and open SolarMax inverters and the MCU.

■■ The inverter has to be installed in an enclosed electrical plant room.■■ The qualified electrician is responsible for adhering to the valid local application

installation and safety instructions.■■ Ignoring the installation and safety instructions shall cancel any and all warranty

and liability claims.■■ Touching live parts is life-threatening.■■ The inverters and the MCU must remain closed at all times during operation.■■ The DC and AC feed lines must be disconnected according to the instructions and

secured against being reconnected accidentally before you open the inverter or the MCU.

■■ After disconnecting the inverter wait at least 5 minutes before opening the device to permit internal capacitors to discharge.

NOTE

■■ This document cannot take the place of support from the distributor. For assis-tance please get in touch with your personal contact.

■■ Check that you have the current version of the document by visiting our website.

Page 8: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

8

2.2 Appropriate use

The SolarMax TS series inverters are designed exclusively to convert the direct current generated by PV modules into alternating current which conforms to the parameters of the public grid. Any other use is contrary to the purpose for which the inverters were designed.

The inverter may only be connected to a suitable medium-voltage transformer. It is not permitted to connect the unit directly to a medium-voltage switch circuit or to the power grid.

SolarMax Produktions GmbH accepts no liability for damages resulting from using inverters for purposes other than this. Any modifications to the inverter performed by the system operator or the electrician without a review and approval by SolarMax Produktions GmbH are prohibited.

Page 9: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

9

en

3 Description of the station components

This chapter describes the station components.

3.1 SolarMax TS-SV inverter

The main component of a station is the SolarMax TS-SV central inverter. It converts the PV generator’s direct current into alternating current which conforms to public grid parameters. The output of a station depends on the number of installed TS-SV inverters. One to four TS-SV inverters together with an MCU make up an inverter system that is connected to a medium-voltage transformer.

The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches on the DC and AC end (Q1 to Q6), a contactor at the AC end (K1 to K3) and EMV filters. All power switches are accessible from outside when the inverter casing is closed.

The control units of the power units have two digital signal processors (DSP) which assume all the monitoring, controlling and regulating tasks. All the safety-relevant values are continuously monitored and compared by both processors. The result is greater oper-ating safety and reliability. The DSP’s high performance enables precise and rapid identi-fication of the maximum power points (MPP) of the PV generator and, combined with the low-loss power unit, delivers maximum yields. The completely digital regulation ensures outstanding quality of the current fed into the grid which means extremely negligible grid reactions.

The inverters of the TS-SV series are capable of delivering reactive power if necessary to actively support the mains during short blackouts, to reduce output in response to rising mains frequency and to receive and implement remote control commands (power output reduction, etc.).

The inverter comes from the factory configured for multi-MPPT operation. All the DC inputs of the installed inverters must be connected in parallel and fitted with fuses for the single MPPT operating mode. A short description of these operating modes can be found in section 3.3 “Configuration variants of the station”.

The inverter is not fitted with potential separation. This is provided by the medium-voltage transformer.

Page 10: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

10

3.1.1 Block diagram of the TS-SV inverter

U

PU1

K1

Sola

rMax

TS-

SV

U

PU2

K2

U

PU3

K3

ModuarBus (MCU)

23

23

23

DC In

put 1

DC p

ower

sw

itch

Q4AC

pow

er s

witc

h Q1

AC o

utpu

t 2

AC o

utpu

t 3

AC o

utpu

t 1

DC p

ower

sw

itch

Q5AC

pow

er s

witc

h Q2

DC p

ower

sw

itch

Q6AC

pow

er s

witc

h Q3

DC In

put 2

DC In

put 3

EMC

�lte

r

EMC

�lte

r

EMC

�lte

r

EMC

�lte

r

EMC

�lte

r

EMC

�lte

r

Page 11: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

11

en

3.1.2 External operating elements and dimensions

1970

1090

690

80

1200

8064

0

800

80

80 493 54 493

4 x ø

20

4 xM16 threaded cylinder (Fastening nuts for lift assembly)

DC power switch

AC power switch

Type plate

Opening for the modular bus cable

3.1.3 Scope of delivery

The scope of delivery may vary depending on the project specifications. But as a rule, along with the inverter or the MCU, the following parts are supplied:

■■ Inverters: – 4 x short perforated grid front/back – 2 x long perforated grid side – Hardware (screws, spring washers, etc.) – Phase separation elements – 1 Network cable RJ45 Cat. 6 S/FTP (2 m) – 4 eye bolts M16

■■ MCU: – 1 Network cable RJ45 Cat. 6 S/FTP (5 m) – 1 Network cable RJ45 Cat. 6 S/FTP (10 m) – Fastening elements – Operating manual

Page 12: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

12

3.2 TS-SV master control unit (MCU)

The TS-SV master control unit (MCU) is the control and operating unit for as many as four TS-SV inverters. The interfaces and contacts of the MCU enable innumerable com-munications and monitoring variants, see 5.4.6 “Interfaces and contacts of the MCU”.

The MCU is connected to the TS-SV inverter via a modular bus interface. The MCU is powered both from the AC end (from the autonomous power supply transformer) as well as from the DC end. This enables the MCU to operate around the clock. The MCU has a switch that you can use to configure the single or multi MPPT operating mode see 5.5 “Configuring the MCU”.

The MCU has a mounting rail that enables the installation of the MaxWeb xp web-based data logger and the potential equalization set (PAS).

3.2.1 Exterior view and dimensions of the MCU

600 150

520

550

470

Graphics display

status LED

Main switch

Page 13: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

13

en

3.3 Configuration variants of the station

Using the TS-SV inverter as basic module, stations with the following output powers can be built:

Number of SM330TS-SV Max. apparent output [kVA]

1 340 kVA

2 680 kVA

3 1 020 kVA

4 1 360 kVA

Number of SM360TS-SV Max. apparent output [kVA]

1 370

2 740

3 1 110

4 1 480

The TS-SV inverter enables the realisation of stations in either a multi or single MPPT operating mode.

NOTE

■■ The station must be designed for either the multi MPPT or for the single MPPT operating mode. It is not possible to mix operating modes.

■■ The combination of SM330TS-SV and SM360TS-SV inverters in the same station is neither permitted nor technically possible.

Page 14: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

14

3.3.1 Multi MPPT operation mode

In the multi MPPT operating mode each power unit operates its own MPP tracker, allowing the connection of as many as three mutually independent PV generators to each TS-SV inverter.

Station with three TS-SV inverters in the multi MPPT operating mode

TS-SV

3

3

PU1

PU2

PU3

PU1

PU2

PU3

TS-SV

TS-SV

PU1

PU2

PU3 ModularBus

ModularBus

3

MCU

DC input 1

DC input 2

DC input 3

DC input 4

DC input 5

DC input 6

DC input 7

DC input 8

DC input 9

MV transformer

AC output

For this variant, the MCU assumes the master control of the TS-SV inverter, and also acts as a joint user interface and enables the integration of the station into a MaxComm communications network.

Page 15: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

15

en

3.3.2 Single MPPT operation mode

In single MPPT operating mode all the DC inputs of the inverters are wired parallel inside the station. The shared MPP tracker is monitored for all the power units by the MCU.

Station with three TS-SV inverters in the single MPPT operating mode

PU1

PU2

PU3

PU1

PU2

PU3

PU1

PU2

PU3

3

3

3

MCU

TS-SV

TS-SV

TS-SV

ModularBus

ModularBus

DC input1

DC input 2

DC input 3

DC input 4

DC input 5

DC input 6

DC input7

DC input 8

DC input 9

AC output

DC fuse units

MV transformer

DC fuse units

DC fuse units

For this variant, the MCU acts as a master MPP tracker control unit for all the TS-SV inverters, and also acts as a joint user interface and enables the integration of the station into a MaxComm communications network.

The DC inputs are connected in parallel outside the inverters, usually as part of the DC fuse box.

Page 16: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

16

3.4 Additional station components

The following station components are not supplied by SolarMax Produktions GmbH:

■■ DC fuse box■■ Autonomous power supply transformer (transformer for the station‘s own power

supply)■■ Medium voltage transformer and 400 V low-voltage installation■■ Medium voltage switchgear■■ AC fuses between each inverter and the medium-voltage transformer

The design of these components is in the hands of the station outfitter. The details con-tained in the following sections are only standard values and typical characteristics.

3.4.1 DC fuse unit

The DC fuse unit is only needed if the intention is to operate the station in single MPPT operating mode. The station outfitter is responsible for constructing the DC fuse unit. When you dimension the DC fuse unit keep in mind the connection conditions for the single MPPT operating mode, see 5.3.2 “Connect inverter to the PV plant”.

3.4.2 Autonomous power supply transformer

The autonomous power supply transformer powers the MCU and other, project dependent consumers (lighting, MaxWeb xp, fans, etc.) inside a station. The use of an autonomous power supply transformer is necessary if no local 230 V / 400 V mains are available. The selection and dimensioning of the transformer is in the hands of the station outfitter.

Typical characteristics

The actual size of the autonomous power supply transformer (if necessary) depends on the number and type of the additional consumers inside the station.

Technical data

Type 3 phases, 50 Hz

Power output ≥ 5 kVA

Number of 3-phase windings 2

Voltage 1 SM330TS-SV: 280 V (D)SM360TS-SV: 320 V (D)

Voltage 2 400 V (yn)

Vector group Dyn0

Protective class IP22

Page 17: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

17

en

Technical data

Max. ambient temperature 40 °C

3.4.3 Medium-voltage transformer

The medium-voltage transformer is the link between the local 280 V network within a sta-tion and the medium-voltage network. The inverter may only be connected to the power grid via a medium-voltage transformer. The medium-voltage transformer provides the potential separation between the PV power plant and the medium-voltage switch system or the power grid. The inverter does not have its own potential separation. The medium-voltage transformer is not included in the scope of supply.

Determining the size

The dimensioning of the medium-voltage transformer depends on the number of TS-SV inverters used. Dimension the medium-voltage transformer in such a way that its no-load losses remain as low as possible. The following reference values are applicable to a maximum ambient temperature of 40 °C.

Number of SM330TS-SV inverters Size of the medium-voltage transformer [kVA]

1 400

2 630

3 1 000

4 1 250

Number of SM360TS-SV inverters Size of the medium-voltage transformer [kVA]

1 400

2 800

3 1 000

4 1 600

Requirements

The requirements are listed in the following table, using a 1 000 kVA medium-voltage transformer as example:

1 000 kVA medium-voltage transformer

Type 3 phases / 50 Hz (on rollers)

Power output 1 000 kVA

Number of 3-phase windings 2 (1 MV, 1 LV)

Page 18: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

18

1 000 kVA medium-voltage transformer

Primary voltage (MV) 20 kV (depending on project and site)

Insulation level 24 kV

Primary (MV) tapping ±2.5 % and ±5 %

Secondary voltage (LV) SM330TS-SV: 0.28 kVSM360TS-SV: 0.32 kV

Standard IEC60076

Vector group Dd (no start point, phase is irrelevant)

Short circuit voltage UK 4 %…6 %

No-load losses < 1 300 W (oil) / < 2 000 W (dry) CC

Load losses (@75 °C) < 11 000 W CC

Environment Internal application (no air conditioning required)

Max. ambient temperature 40 °C

Max. installation altitude < 2 000 meters above sea level

Relative humidity 5 %…95 %

Insulation Basic insulation designed for pulse operation of an inverter

Test voltages 50 kV (medium voltage to low voltage) / 8 kV (low voltage to protective conductor PE)

In addition, the medium-voltage transformer must have a test record of the final test that con-tains details about the insulation measurements, no-load and full-load losses.

Requirements for oil-based medium-voltage transformers

In addition to the details in the “1 000 kVA medium-voltage transformers” table, oil-based medium-voltage transformers must have the following specification:

■■ Design Art IP00 NV / IP54 medium-voltage transformer and medium-voltage con-nector with hermetically closed tank

■■ Accessories: DGPT2 (full transformer protection)

3.4.4 Medium-voltage switchgear

The correct installation of the medium-voltage switchgear is in the hands of the station outfitter. The local regulations and guidelines must be followed.

Page 19: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

19

en

4 Installation4.1 Transport & storage of the inverter

DANGER

■■ The inverter is a heavy device which, if not handled properly, can tip over during transport and cause serious personal injuries.

■■ The inverter must be transported upright.

4.1.1 Means of transport

Forklift trucks

The inverter has openings in its base to allow it to be transported by a forklift truck. Secure the devices against falling.

Crane

At the upper corner struts the inverters have four M16 threaded cylinders (weld nuts). You can screw M16 eye bolts into these cylinders. These allow the inverter to be lifted by a crane or forklift truck.

DANGER

■■ If you use a forklift or some other lifting equipment take extreme caution. Make sure the lifting equipment has adequate lifting capacity.

■■ Secure the inverter against falling while it is being moved by a forklift truck.■■ Whenever this is done always make sure that the inverter’s weight is correctly

distributed on the lifting equipment (ensure that centres of gravity are properly distributed).

■■ Ropes or strips must have an angle of > 60° to the inverter top.

■■ Necessary minimum lifting capacity of the transport vehicle or lifting equipment: 950 kg (weight of the inverter).

Page 20: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

20

4.1.2 Storage conditions

Store the inverter in a dry, enclosed space.

CAUTION

Possible damage to the device! Never store the inverter outdoors. Not even for a short time.

4.2 Site selection and operating conditions of the inverter4.2.1 Specifications and instructions for site selection

Choosing a suitable location for the inverter is decisive for its operating safety as well as its expected service life and efficiency. An ideal location is indoors or in a container with the following characteristics:

■■ The site must be dry to prevent any condensation from collecting in the inverter: no puddles, no damp masonry walls, no openings where snow or rain can enter.

■■ The ambient air of the inverter must be free from dust, salt, and ammonium vapours. If required (e.g. for installations near the sea or in desert areas), the ambient air of the inverter must be filtered (e.g. with an air conditioning unit or a filter).

■■ Do not install the inverter in rooms or work areas which contain or are made of com-bustible materials. Follow the local fire safety regulations.

DANGER!

Fatal electric shock hazard! – The inverter must be installed in an enclosed electrical plant room so that unauthorized persons have no access.

CAUTION

Fire hazard! - Suitable for mounting on concrete or other non-combustible surface only!

■■ Because the inverter is a source of noise, do not install it near residential spaces.■■ Make sure that the floor of the installation site is level and its bearing capacity is

adequate. ■■ The inverter must be installed on the entire contact face of the 6 bases.

Page 21: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

21

en

■■ To ensure that the inverter is accessible for possible repair work the front side must be at least 1 m away from the nearest object (wall, other inverters, etc.). Do not install the inverter on a raised surface, platforms or consoles.

■■ Where the inverter and the medium-voltage transformer are installed in separate rooms, a warning note must be attached to both units: „Before carrying out any work to the AC connection between the inverter and the medium-voltage transformer, the electricity connection to the supply lines to the PV generator and the medium-voltage network must be switched off“.

4.2.2 Operating conditions at the site

■■ The ambient conditions are specified in the technical data, see section 7.■■ The installation location must meet the requirements contained in the standard for

electromagnetic immunity for industrial environments (EN 61000-6-2) and for emis-sions in industrial environments (EN 61000-6-4).

NOTE

■■ Please remember that the inverter and existing accessories give off heat during operation which can contribute to a serious heating up of the ambient air if the plant rooms are small or poorly ventilated.

■■ Our basic rule is always to recommend that the ambient temperature be kept under 30 °C.

■■ The ventilation at the site must provide an air change rate of 5000 m3 per hour and inverter. The air must flow through the inverter from bottom to top.

■■ Conditions in the plant room which could lead to even a short period of excessive ambient air temperature (TAmbient > 50 °C) make the installation of an additional ventilation system an absolute necessity.

Page 22: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

22

4.2.3 Cooling system of the inverter

The inverter’s heat sinks are actively cooled by internal fans. The cool, fresh air enters the inverter from below, is drawn in by the fans and is blown upwards through the ventilation screens out of the inverter.

For safety reasons the heat sink temperature is limited to 85 °C. When ambient tem-perature is over 45 °C the heat sink temperature can reach 80 °C. If this happens, the maximum feed output is temporarily reduced and a corresponding status message appears on the inverter’s display screen. But if the temperature still runs as high as 85 °C the inverter is shut down to prevent a thermal overload.

NOTE

Optimal cooling is decisive for maximum inverter output yield. Install inverters only at a site corresponding to the description in 4.2.2 “Site selection and operating conditions”.

4.3 Recommendations for station construction

The construction and setup of the inverters in a station must meet the requirements of the IEC 62271 202 industrial standard.

The TS-SV inverters are generally built into a concrete station. The conception of the station depends on the country-specific standards and regulations for the construction of rooms containing electrical facilities and is the responsibility of the station outfitter.

Page 23: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

23

en

Example of a station with three TS-SV inverters:

D

d

d

d

1

2

7

6

5

1

13 4

Legend:D Clearance as set by country-specific regulationsd 1 metre1 SolarMax TS-SV inverter2 MCU 5 AC distribution3 DC fuse box 6 Medium voltage transformer4 Own power supply transformer 7 Medium voltage switchgear

4.3.1 Heating

The inverters are tested to operate at temperatures to -20 °C. Remember to check the minimum operating temperatures of the other components and, if necessary, to install a heating unit.

4.3.2 Excavating the construction site

The construction site must be excavated following the instructions of the station outfitter. Stations fitted with a basement ventilation system must be effectively protected against the intrusion of rain, snow and water through the lateral cooling shafts. There must be drainage channels and pipes in place and the subsurface soil must be permeable.

Page 24: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

24

4.4 Lightning protection

The requirements for appropriate lightning protection for a PV power plant depend on many different factors (plant size, how the cables are run, the modules used, the sur-roundings, etc.).

A project-specific protection concept must be developed by a qualified person.

4.5 Montage4.5.1 Inverters

The inverters can be fastened to the floor with M12 screws. Use the hole pattern shown in 3.1.2 “External operating elements and dimensions”. In addition to anchorage to the ground the inverters can be anchored to the wall with a bracket above to the M16 threaded cylinders.

4.5.2 MCU

The MCU is usually mounted on the wall in the station. The hole pattern is shown in 3.2.1 “Exterior view and dimensions”.

Page 25: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

25

en

5 Electrical connection5.1 Guidelines for electrical installation

DANGER

■■ Only qualified electricians may install and start-up the TS-SV inverter and the MCU.

■■ The local regulations and guidelines for the installation of electrical devices must be followed.

■■ All the feed lines to the inverter and the MCU must be appropriate for the expected voltages, currents and ambient conditions (temperature, UV load, etc.).

■■ Make sure that all lines are laid tension-free.

5.2 Earthing of the station components

As a principle, all metal parts which are not protected against being touched must be earthed.

DANGER

A correct earthing is vital for the operation and safety of the devices (for example, by an earthing strap buried in the ground).

The station components must be earthed as follows:

■■ Each inverter with two 95 mm2 wires connected to M10 threaded bolts. The position of the MS threaded bolts: see 5.3.1 “Interior view of the inverter”.

■■ The MCU with one 10 mm2 wire (also important for perfect communication between the MCU and inverters). The position of the terminals: see 5.4.1 “Interior view of the MCU”. The MCU must be grounded independently of the inverters.

■■ Each of the DC fuse boxes with one 95 mm2 wire per box.■■ The star point of the 400 V coil of the autonomous power supply transformer.■■ The AC-side overvoltage protection of the inverter is earthed.

DANGER

Never ground the possibly existing low-voltage star point at the medium-voltage transformer!

Page 26: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

26

5.3 Connecting the inverter5.3.1 Interior view of the inverter

Open the inverter by loosening the four or three captive M5 screws of the left and right front cover.

DANGER

Make sure that all the DC and AC feed lines to the inverter are dead before you start the installation work.

16

8

1 2 3

15

14

13

9

10

11

12

7

4

5

6

15

Page 27: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

27

en

Legend:1 Power unit PU1 9 DC power switch Q42 Power unit PU2 10 DC power switch Q53 Power unit PU3 11 DC power switch Q64 AC power switch Q1 12 DC connections5 AC power switch Q2 13 Fuse holder (DC connection for MCU)6 AC power switch Q3 14 Shutdown contact 17 AC connections 15 Fans8 2 x M10 threaded bolts for earthing 16 Test contacts

5.3.2 Connecting the inverters to the PV plant

General connection conditions

■■ Per power unit as many as three DC feed lines (strings) can be connect in parallel.■■ Maximum DC input current per power inverter: 720 A■■ Maximum DC input voltage per inverter: 900 V■■ Maximum DC input current per power unit: 240 A■■ If the feed lines are long we recommend you use larger line cross sections to keep

down transmission losses. ■■ Maximum admissible over-dimensioning of the PV generator output power: 50 %.

NOTE

The DC inputs of the inverter are overvoltage protective Type 3.

Connection conditions for the multi MPPT operating mode

■■ It is not permitted to install a ground connection to the PV generator.■■ Starting from three DC feed lines for each power unit, the minimum cross section

increases because in case of a short circuit the two intact feed lines pass on all the return current to the defective line (the cross section increase for three DC feed lines can be dropped if all the DC feed lines are fitted with fuses):

Number of feed lines per power unit Minimum cable cross section

1 95 mm2

2 50 mm2

3 70 mm2

Page 28: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

28

Connection conditions for the single MPPT operating mode

■■ Minimum conductor cross section: 95 mm2

■■ All the DC inputs of the inverters in use must be connected in parallel.■■ The DC bus bars for connecting the inverters in parallel must be dimensioned for the

maximum current:

Number of inverters Maximum current in the DC bus bars [A]

2 720

3 960

4 1 440

■■ All DC feed lines must be individually fitted with fuses, both at the plus as well as the minus pole. Use 160 A NH fuses which have been certified for at least 1 000 VDC (the 160 A correspond to the max. DC total current of a MaxConnect combiner box).

■■ Installation of a ground connection to one pole of the PV generator is permissible (plus or minus pole).

DANGER

Fatal electric shock hazard! – When a pole of the PV generator is grounded (or func-tionally grounded), that pole must be considered as live and must be insulated.

Page 29: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

29

en

■■ Principle wiring diagram for single MPPT operating mode:

PU1

PU2

PU3

TS-SV

PU1

PU2

PU3

TS-SV

MCU

160 A /1000VDCNH fuses

DC input 1DC input 2

DC input n

DC input 1DC input 2

DC input n

DC bus bars

AC output

AC output

Procedure

DANGER

Make sure that all the DC and AC feed lines to the inverter are dead before you start the installation work.

1. Run the DC feed lines from below into the inverter and to the M8 threaded bolt connec-tions below the DC power switches.

2. Connect the DC feed lines of the strings correctly; (make sure the polarity is right). The correct order of the fastening elements is: Cable lug, spring lock washer, finally the M8 nut.

Tightening torque for the M8 nuts: minimum 20 Nm, maximum 25 Nm.

3. Implement the cable strain relief within the false floor of the station (in the inverter no cable strain relief is designed). The distance between DC connection within the in-verter and the cable strain relief should be less than 500 mm.

Page 30: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

30

DC connections

PU 1 PU 3PU 2

5.3.3 Connecting the inverter to the medium voltage transformer

Connecting conditions

■■ 3 x 95 mm2 per Phase (2 x 185 mm² per phase are also admissible).■■ The inverter is not fitted with potential separation. This is provided by the medium-

voltage transformer.■■ The maximum cable length between the inverter and the medium-voltage trans-

former must not exceed 30 meters.■■ The AC connection (280V / 320V) of the inverter must meet the requirements of the

overvoltage category II. The AC-side overvoltage protection must be correspondingly dimensioned.

■■ The AC connection of the inverter must be protected by an AC circuit breaker or an NH fuse switch disconnector (see chapter 5.6).

■■ If you use external residual current devices (RCDs), use the type A RCDs with a nominal fault current of at least 10 A per inverter. For PV plants with large stray cur-rent capacities, the RCDs to be used should have a nominal fault current capacity of at least 30 A per inverter.

Page 31: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

31

en

NOTE

■■ The inverter is not fitted with overvoltage protection on the AC side. ■■ The inverter does not have any devices (such as RCDs) for the protection against

dangerous touch currents or electric shock.■■ The inverter is fitted with a configurable DC insulation monitor (Vsym monitor, see

TS-SV operating manual).

Procedure

DANGER

Make sure that all the DC and AC feed lines to the inverter are dead before you start the installation work.

1. Run the AC feed lines from below into the inverter and to the M8 threaded bolt connec-tions below the AC power switches.

2. Connect the AC feed lines correctly.

– Remember that the rotating field of the mains phases must be clockwise.

– The correct order of the fastening elements is: Cable lug, spring lock washer, finally the M8 nut.

– Tightening torque for the M8 nuts: minimum 20 Nm, maximum 25 Nm.

3. Position the included phase separation elements between the cable lugs to ensure the isolation clearance.

4. Implement the cable strain relief within the false floor of the station (in the inverter no cable strain relief is designed). The distance between DC connection within the in-verter and the cable strain relief should be smaller than 500 mm.

Page 32: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

32

AC connections

L1 L2 L3 L1 L2 L3 L1 L2 L3

5.3.4 Connecting the inverters to the modular bus

Each power unit must be connected to a ModularBus. The power units in the inverter are already connected to each other ex factory. You only must implement the ModularBus connections amongst the inverters.

Cable requirements

Cat. 6 S/FTP cable, 2/10 metres (included in delivery)

Procedure

Please use the supplied cables only. Connect the inverters by connecting the cable to the ModularBus sockets X631 or X632 of the respective power unit. Always terminate the ModularBus with a terminating plug.

Page 33: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

33

en

ModularBus connections

TS-SV MCU

PU 1

PU 2

PU 3

PU n (max 12)

zur TS-SV MCU

ModularBus-Adressenotieren

Staubschutz

Abschlussstecker

Kon�gurationstecker

5.3.5 Assigning addresses to the power units

An unambiguous address must be assigned to each power unit with the help of the con-figuration plug.

Procedure

1. Disconnect the configuration plug (the figure in section 5.3.4. shows the position of the configuration plug).

2. Configure the address with the configuration plug. The addresses are as follows:

Inverter-No. Adress Rotary switch position

1

1 1

2 2

3 3

Page 34: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

34

Inverter-No. Adress Rotary switch position

2

4 4

5 5

6 6

3

7 7

8 8

9 9

4

10 A

11 B

12 C

3. Record the address set in front on the power unit.

4. Reconnect the configuration plugs.

5. Record the inverter number outside on the type plate.

Configuration plug

5.3.6 Connecting the shutdown contact 1 (optional)

Position of the shutdown contact 1 (SD1-SD4) in the inverter: see 5.3.1 “Interior view”.

The shutdown contacts 1 (SD1-SD4) enable remote shutdown of as many as eight inverters using an external break contact (e.g. an emergency off switch). If the shutdown function 1 is activated the current supply circuit of the AC contactor K1 is disconnected directly and the inverter is locked. This results in the immediate disconnection from the grid which is also effective when the control unit fails. The inverters remain locked until the external break contact is reclosed. In addition, the status message “Shutdown 1” is displayed.

The shutdown 1 is inactive if there is a short circuit between either the contact pair SD1 and SD2 (SD12) or SD3 and SD4 (SD34), e.g., with a plaited bridge. The shutdown 1 is only active if both contact pairs SD12 and SD34 are open. When shipped from the factory the contact pair SD12 is short-circuited with a plaited bridge.

Page 35: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

35

en

Cable requirements

Use the cable with the following line specifications for wiring the contacts:■■ Minimum cross section: 1.5 mm2

■■ Maximum cable length: 240 m (total length of break contact to the last inverter)

If you want to lock several inverters (as many as 8) with a single break contact, wire the shutdown contacts 1 as shown in the following diagram:

……

SD1

SD2

SD3

SD4

SD1

SD2

SD3

SD4

SD1

SD2

SD3

SD4

TS-SV #8TS-SV #1 TS-SV #2

Break contact

Page 36: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

36

5.4 Connecting the MCU

This section describes how to connect the MCU inside the station correctly.

DANGER

Make sure that all the DC and AC feed lines are dead before you start the installation work.

5.4.1 Interior view of the MCU15

VDC

24 V

DCPAS MaxWeb xp

11 1

- +

Sola

rpa

rkX

821

Ethe

rne

tX

601

mod

ula

rTS

X80

2

Stat

us R

elai

sX

411

Exte

rne

r Ala

rmX

501

WR-

Frei

gab

eX

511M

axC

omm

X62

1

MCU Mod eS231

Num of LTsS241

Ans

chlu

ss P

AS

X22

01

MCU10 0

1

PEPE NL

DC+

DC

1

2 3 4 5 6 7 8

Legend:1 MCU2 Potential equalization set (optional)3 MaxWeb xp (optional)4 15 VDC power supply for MaxWeb xp (optional)5 24 VDC power supply for the MCU6 Terminal for protective earth (PE)7 Terminals for the AC power supply (L1, N, PE)8 Terminals for the DC power supply (DC+; DC-)

Page 37: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

37

en

5.4.2 Connecting the DC feed line to the MCU

The connection to the DC voltage of the PV generator ensures uninterrupted operation of the MCU in the case of a failure of the AC mains. In addition, the connection permits measuring the DC voltage by the MCU.

Cable requirements

2 x minimum 2.5 mm2 (900 VDC)

Procedure

1. Connect the cable to the terminals “DC+” and “DC−” within the MCU. Position of the terminals, see 5.4.1 “Interior view of the MCU”.

2. Connect the cable to the fuse holders “DC+” and “DC−” within the nearest inverter. Make sure the polarity is right. Position of the fuse holders: see 5.3.1 “Interior view of the inverter”.

DC+

DC

5.4.3 Connecting the AC feed line to the MCU

The autonomous power supply transformer or an available 230 V mains supplies the AC power to the MCU.

Cable requirements

■■ Supply voltage: 230 VAC

■■ Maximum power consumption: 60 W■■ Three-core cable; L1, N and PE (230 V); 3 x minimum 1 mm2

Procedure

Connect the cable to the terminals L1, N, and PE within the MCU. Position of the terminals: see 5.4.1 “Interior view of the MCU”.

Page 38: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

38

5.4.4 Connecting the MCU to the modular bus

Cable requirements

Cat. 6 S/FTP cable, 5 metres (included in delivery)

Procedure

1. Connect the cable to the modular bus “X802” socket of the MCU.

2. Connect the cable to a free modular bus socket (X631 or X632) at the nearest power unit, see also 5.3.4 “Connecting inverters to the modular bus”.

5.4.5 Connecting the protective earth (PE) line to the MCU

Cable requirements

■■ Minimum cable cross section: 6 mm2, maximum cable cross section: 16 mm2

■■ The MCU must be grounded independently of the inverters.

Procedure

Connect the protective earth to the 16 mm2 terminal. The position of the terminal: see 5.4.1 “Interior view of the MCU”.

5.4.6 Interface and contacts of the MCU

Integrated RS485 and Ethernet interfaces enable many communications and monitoring options based on our MaxComm communications platform. The system communicates either directly via a PC with MaxTalk (from version 2.0) or via the Internet enabled MaxWeb xp data logger.

In addition, contacts for switching the inverters on and off, for remote monitoring of the MCU, for a MaxConnect alarm input as well as contacts for connecting the potential equalization set (PAS) are integrated.

NOTE

Additional information on the use of various interfaces and functions of the MCU can be found in the operating manual of the TS-SV inverter.

Page 39: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

39

en

Interfaces and contacts of the MCU

11 1

- +

Solar

park

X821

Ethe

rnet

X601

mod

ular

TSX8

02

Stat

us R

elais

X411

Exte

rner

Alar

mX5

01

WR-

Frei

gabe

X511

Max

Com

mX6

21

MCU ModeS231

Num of LTsS241

Ansc

hlus

s PAS

X220

1

MCU100

1

5.4.6.1 Cable requirements for the contacts

Unless otherwise stated, use cable with the following specifications for wiring the contacts:

■■ Minimum cross section: 0.75 mm2

■■ Minimum cross section: 4 mm2

■■ Maximum cable length: 50 m

5.4.6.2 Status signalling contact – X411

The status signalling contact X411 enables the MCU and the inverter to be remotely moni-tored. The MCU status can be recorded with the potential-free relay contacts NO and COM. How the status signalling contact works can be selected in the “Settings” menu (see the operating manual of the TS-SV inverter).

The list of events that trigger the status signalling contact can be found in the operating manual of the TS-SV inverter.

NC

1

NO C

X411

Page 40: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

40

■■ Specifications of the status signalling contact – Contacts potential-free (make contact), not fused – Max. switch voltage: 250 VAC / 100 VDC

– Max. switch current: 5 Aeff @ 250 VAC (cosφ = 1) or 30 VDC

– Continuous current: 2 Aeff

5.4.6.3 Shutdown contact 2 – X511

The shutdown contact 2 (X511) allows the inverter to be remotely shut down via an external break contact. The function is similar to the one of shutdown contact 1, but the separation from the grid is not made directly via the supply voltage of the AC contactor K1. It is controlled by software via the inverter’s control unit. The inverters remain locked until the external break contact is reclosed. In addition, the status message “Shutdown 2” is displayed. The shutdown 2 is inactive, if EN1 and EN2 (EN12) are short-circuited by a bridge (condition at the time of delivery). The shutdown 2 is active if the contact pair EN12 is open.

5.4.6.4 Alarm contact – X501

The alarm contact (X501) is used to display the status of the generator connection box MaxConnect plus in the graphics display. For this purpose use a two-wire cable to connect the contacts of the potential-free fault alarm output of MaxConnect plus to the STM and GND contacts on the inverter’s terminal block. As soon as the STM and GND contacts are short-circuited, the inverter display shows the status message “Warning MaxConnect”.

5.4.6.5 Connection PAS - X2201

Interface for the connection of the potential equalization set (PAS). Use the cable supplied with the potential equalization set.

NOTE

The potential equalization set (PES) may only be used for stations configured for single MPPT operation. Contact the SolarMax Service Center, if you want to connect the potential equalization set.

Page 41: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

41

en

5.4.6.6 RS485 interfaces – X621 / X 821 and Ethernet – X601

The MCU provides two RS485 interfaces and an Ethernet interface for data communica-tions. You can integrate the MCU with these RJ45 sockets into a MaxComm communi-cations network to use the extensive monitoring and remote control options offered by SolarMax Produktions GmbH. You can learn more about the advantages of the MaxComm communications platform in the operating manual of the TS-SV inverter.

Use the network cable (referred to as “patch cable”) to wire the Cat 5 interfaces.

5.5 Configuring the MCU

The switches for the necessary settings are located on the motherboard of the MCU and should be switched with a No. 2 screwdriver. The position of the switch: see 5.4.6 “Inter-faces and contacts of the MCU”.

Configuring the MCU for single or multi MPPT operating mode

Turn the switch “S231” (MCU Mode) to the required position.

TS-SV inverter Configuration Switch positionSM330TS-SV Single MPPT operating mode 2

Multi MPPT operating mode 3SM360TS-SV Single MPPT operating mode 4

Multi MPPT operating mode 5

Define the number of connected power units

Rotate the switch “S241” (Num of LTs) to the correct position:

Switch position 0 1 2 3 4 5 6 7 8 9 A B C D E F

Number of power units

N/A3

N/A6

N/A9

N/A12

N/ANumber of inverters 1 2 3 4

Page 42: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

42

5.6 Connecting the other station components

The correct electrical installation of the following components is in the hands of the sta-tion outfitter. SolarMax Produktions GmbH instructions in this regard are limited:

AC circuit breaker

To protect the inverter and to permit its complete AC-side disconnection, an AC power switch must be connected to the AC connection of the inverter.

Specification AC circuit breaker:

■■ Maximum current: 800 A■■ Maximum voltage: 280 V (SM330TS-SV) / 320 V (SM360TS-SV)■■ Thermal and magnetic overcurrent release

Alternatively, an NH switch disconnector fuse with 800A NH fuses may also be used.

Medium voltage transformer

Standard values for dimensioning and typical characteristics can be found in 3.4.3 “Medium-voltage transformer”.

Autonomous power supply transformer

The star point on the secondary side (400 V) must be earthed. On the primary side (280 V / 320 V), no star point is necessary. The autonomous power supply transformer must be fused on the primary and secondary sides.

Page 43: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

43

en

5.7 Application examples for single-MPPT operation

This section shows two examples of applications using three SM330TS-SV inverters and a TS-SV-MCU in each case. Both stations are designed for single-MPPT operation.

In the example in subsection 5.7.1 three DC bus bars are used. One DC bus bar for every central inverter. The DC bus bars are connected to each other with connection cables. The 315 amp fuses protect the connection cables. If the currents are balanced, no current flows in the connection cables. If the currents are not balanced, the current in the con-nection cables will not exceed 315 amp. The 315 amp fuses allow individual inverters to be disconnected from the DC input.

In the example in subsection 5.7.2 all DC inputs of the central inverters are connected in parallel to a common DC bus bar. In that case, the connection cables are not necessary. The 315 amp fuses can be dropped. Arrange the connections over the entire length of the DC bus bar, so that the current at a certain point cannot exceed 960 amp.

DANGER

■■ Only qualified electricians who have already completely read and understood this installation manual in advance may install and open SolarMax inverters.

■■ The qualified electrician is responsible for adhering to the valid local application installation and safety instructions.

Page 44: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

44

5.7.1 DC fuse unit with several DC bus bars

PU1

PU3

PU2

PU1

PU3

PU2

PU1

PU3

PU2

95 mm2 95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm295 mm2

95 mm295 mm2

95 mm295 mm2

95 mm295 mm2

SM330TS-SV

L1

L2

L3

X631

Adress #7(X541)

DC+DC-

L1

L2

L3

Terminal plug onModularTS X632

X631

Adress #9(X541)

L1

L2L3

X631

Adress #8(X541)

SM330TS-SV

L1

L2

L3

X631

Adress #4(X541)

DC+DC-

L1

L2

L3

X631

Adress #6(X541)

L1

L2

L3

X631

Adress #5(X541)

SM330TS-SV

L1

L2

L3

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

X631250 A250 A

Adress #1(X541)

DC+

DC-

L1

L2

L3

X631250 A250 A

Adress #3(X541)

L1

L2

L3

X631250 A

250 A

Adress #2(X541)

ModularBus

Cat. 6 S/FTP 2 m or 10 m (included in delivery)

Cat. 6 S/FTP 2 m or 10 m (included in delivery)

RS485PE

MaxConnect 16 plus

160 A

RS485 MaxConnect

5 x 160 A

5 x 160 A

5 x 160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

Overvoltage protection

Type 2

2 x 6 A

160 A1000 VDCNH

315 A1000 VDCNH

315 A1000 VDC

NH

DC bus bars

Connectioncables

720 A

185 mm2 185 mm2

DC fuse unit

Page 45: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

45

en

Page 46: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

46

5.7.2 DC Fuse unit with common DC bus bar

PU1

PU3

PU2

PU1

PU3

PU2

PU1

PU3

PU2

95 mm2 95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm2

95 mm295 mm2

95 mm295 mm2

95 mm295 mm2

95 mm295 mm2

SM330TS-SV

L1

L2

L3

X631

Adress #7(X541)

DC+DC-

L1

L2

L3

Terminal plug onModularTS X632

X631

Adress #9(X541)

L1

L2L3

X631

Adress #8(X541)

SM330TS-SV

L1

L2

L3

X631

Adress #4(X541)

DC+DC-

L1

L2

L3

X631

Adress #6(X541)

L1

L2

L3

X631

Adress #5(X541)

SM330TS-SV

L1

L2

L3

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

ModularTSX632

X631250 A250 A

Adress #1(X541)

DC+

DC-

L1

L2

L3

X631250 A250 A

Adress #3(X541)

L1

L2

L3

X631250 A

250 A

Adress #2(X541)

ModularBus

Cat. 6 S/FTP 2 m or 10 m(included in delivery)

Cat. 6 S/FTP 2 m or 10 m(included in delivery)

RS485PE

MaxConnect 16 plus

160 A

RS485 MaxConnect

5 x 160 A

5 x 160 A

5 x 160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

RS485PE

MaxConnect 16 plus

160 A

Overvoltage protection

Type 2

2 x 6 A

160 A1000 VDCNH

DC bus bars

960 A

DC fuse unit

Page 47: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

47

en

Page 48: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

48

6 Commissioning6.1 Inspections prior to startup

Go through the following check lists before you startup the inverters and the MCU for the first time. Keep the filled-out check lists for service requests.

6.1.1 Identification and characteristics

Plant nameStreet, postal code, townPlant outputDate of first startupTS-SV Master Control Unit: S/N:TS-SV inverter #1 S/N:TS-SV inverter #2 S/N:TS-SV inverter #3 S/N:TS-SV inverter #4 S/N:Type and quantity of generator connection boxesMaxWeb xp S/N:Quantity Power units

6.1.2 Station

Nr. OK NOK Check1. ❑ ❑ The station (site) meets the IP standard and the specs contained in the installation manual.2. ❑ ❑ The minimum ventilation of 5 000 m3/h per inverter is provided.3. ❑ ❑ The ventilation inlets and outlets are open and free of blockage.4. ❑ ❑ The ventilation inlets are at least 15 cm above the floor.5. ❑ ❑ The regulations regarding the replacement of ventilation filters (if necessary) are available

at the site.6. ❑ ❑ The thermostat is set to 30 °C.7. ❑ ❑ The covers on the ventilation inlets (if necessary, e.g. screens against rodents) are in

place. 8. ❑ ❑ Water or snow cannot penetrate into the station.9. ❑ ❑ Condensation (formation of droplets) cannot penetrate into the inverter.10. ❑ ❑ The inverters in the station are easily accessible for maintenance work.11. ❑ ❑ The minimum distances from the inverter to other inverters and objects in the station is at

least 1 meter.12. ❑ ❑ The minimum distance between the inverter and the ceiling is 50 cm.13. ❑ ❑ The maximum floor load of the site has not been exceeded.

Page 49: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

49

en

6.1.3 Inverters

Nr. OK NOK Check14. ❑ ❑ The inverter is clean and there is no visible mechanical damage.15. ❑ ❑ There are no tools or other foreign objects in the inverter.Nr. OK NOK Check16. ❑ ❑ The inverter is firmly screwed down (for transportable stations).17. ❑ ❑ The ventilation inlets and outlets of the inverter are open and free.18. ❑ ❑ The rubber bushings for the communications cable are in place.19. ❑ ❑ All the covers in the inverter are in place.20. ❑ ❑ All the circuit breakers of the inverter are switched off.21. ❑ ❑ The outer covers of the inverter are in place.

6.1.4 Operational configuration and MCU

Nr. OK NOK Check22. ❑ ❑ The wiring of the inverter does not allow a mixed multi MPPT and single MPPT operation.23. ❑ ❑ The MCU is configured for the correct operating mode: Multi MPPT or single MPPT operation.24. ❑ ❑ The MCU is configured for the right quantity of all power units in the station.25. ❑ ❑ The main switch of the MCU is off.26. ❑ ❑ The MCU is closed and locked.

6.1.5 DC wiring in general

Nr. OK NOK Check27. ❑ ❑ The connection of the strings to MaxConnect or another generator connection box (if pres-

ent) complies with local installation regulations.28. ❑ ❑ The maximum input voltage of the inverter of 900 V is not exceeded.29. ❑ ❑ The maximum input current of 240 A per power unit is not exceeded.30. ❑ ❑ The cross section of the line for the DC connection in the inverter is at least 2 x 95 mm2

and no more than 2 x 150 mm2 per power unit.31. ❑ ❑ The DC feed lines in the inverter have been connected correctly polarized. The tightening

torque of the nuts is in conformance with the specs in the installation manual.32. ❑ ❑ The DC voltage supply to the MCU is connected.

6.1.6 DC wiring for multi MPPT operation

Nr. OK NOK Check33. ❑ ❑ The inputs of the power units are not wired in parallel (there are no bridges between the

inputs of the power units).34. ❑ ❑ If the DC feed lines have no fuses: The minimum line cross section conforms with the num-

ber of DC feed lines as described in the installation manual.

Page 50: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

50

6.1.7 DC wiring for single MPPT operation

Nr. OK NOK Check35. ❑ ❑ The inputs of the power units are outside of the inverter wired in parallel with the DC

busbars.36. ❑ ❑ The DC feed lines between the DC busbars and the inputs of the inverter have been fused.37. ❑ ❑ The DC busbars have been dimensioned and fused for the maximum possible current

specified in the installation manual (see 5.7 Application examples).38. ❑ ❑ The DC feed lines between the PV module or MaxConnect and the DC busbars are fitted

with fuses. These have been fitted both on the plus pole and the minus pole. 39. ❑ ❑ The DC feed lines between the PV modules or between MaxConnect and the DC busbars

are dimensioned for the maximum possible current.

6.1.8 AC wiring

Nr. OK NOK Check40. ❑ ❑ The measurement of the AC voltage prior to commissioning the station revealed the follow-

ing values: SM330TS-SV: 270 V … 285 V / SM360TS-SV: 310 V … 330 V.41. ❑ ❑ The AC overvoltage protection conforms with the requirements of overvoltage category 2.42. ❑ ❑ The line cross section for the AC connection in the inverter is no less than

3 x 95 mm2 per phase.43. ❑ ❑ The AC feed lines in the inverter have been correctly connected (mains phases are

clockwise). The tightening torque of the 9 nuts is in conformance with the specs in the installation manual.

44. ❑ ❑ The delivered phase separation elements have been fitted between the lugs inside the inverter.

45. ❑ ❑ Each inverter can be disconnected separately by an AC circuit breaker or an 800A NH fuse switch disconnector on the AC side.

46. ❑ ❑ The autonomous power supply transformer is fused on the primary and secondary sides.

6.1.9 Data communication

Nr. OK NOK Check47. ❑ ❑ The modular bus connection between the MCU and the closest inverter is realised with the

Cat. 6 S/FTP communications cable included in the delivery (5m cable).48. ❑ ❑ The modular bus connections between the inverters are realised with the Cat. 6 S/FTP

communications cables included in the delivery (2 m and 10 m cable).49. ❑ ❑ The terminal plug for the modular bus is plugged into the final power unit.50. ❑ ❑ Each of the power units has a unique modular bus address. The addresses have been

assigned in conformance with the instructions in the installation manual.

6.1.10 Earthing

Nr. OK NOK Check51. ❑ ❑ All the earth connections have been check with the ohmmeter.52. ❑ ❑ The inverter is earthed with two 95 mm2 earthing cables.53. ❑ ❑ The MCU is earthed to the station with a 10 mm2 earthing cable.54. ❑ ❑ The star point of the 400 V-coil of the transformer for the station's own power supply is

earthed.55. ❑ ❑ The AC-side overvoltage protection of the inverter is earthed.56. ❑ ❑ the DC fuse box is earthed with a 10 mm2 earthing cable to the station.

Page 51: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

51

en

Nr. OK NOK Check57. ❑ ❑ The star point of the low-voltage (if present) of the medium-voltage transformer is

NOT earthed.

CAUTION

Before you switch on the inverter, fit all the available protective covers, cover plates and perforated grids. The AC and DC power switches, and the main switch, can be operated from outside the closed device.

6.2 Commissioning (Initial Setup)

If the inverter is being commissioned the initial setup will start automatically. This pro-cedure must only be carried out once as part of the commissioning process. Information about operating the display is contained in the operating manual of the TS-SV inverter.

1. Switching on the inverter Switch on the MCU and the inverters as described in the operating manual of the

TS-SV inverter.

2. Selecting the display language In this step select the language in which the following information and texts in the

display will appear.

3. Selecting the individual country settings The individual country settings permit making such settings as the required mains

voltage and mains frequency range used in the country of installation. The selection of the country of installation is independent of the selected display language.

4. Date and time Set the local time and current date. The date set is stored as the commissioning date

and can be accessed later in the “Information” menu.

5. Confirming the entries Now confirm the completion of the initial setup with the button .

Page 52: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

52

CAUTION

The individual country settings (step 3) must be entered with extreme care. Once the initial setup is completed the selections are permanently set and can no longer be modified. A wrong selection can lead to problems when operating the inverter and result in the license to operate being revoked by the local grid operator. An overview of the available country settings are contained in the operation manual of the TS-SV inverter.

NOTE

You can change all the settings in the initial setup (with the exception of the individual country settings) at any time in the “Settings” menu.

Page 53: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

53

en

7 Technical dataSM330TS-SV SM360TS-SV

Input values MPP voltage range 450 V…800 V 510 V…800 V

Maximum DC voltage 900 V 900 V

Maximum DC current 720 A 720 A

Number of MPP-Trackers 1 (Single MPPT operation) or 3 (Multi MPPT operation)

Isc PV 1 410 A (Single MPPT operation) / 3 x 470 A Multi MPPT operation

Reverse current 0 A (diode for protection against polarity reversal)

Connection type threaded bolts M8

Overvoltage category 2

Output values Rated output power 330 kW1) 360 kW2)

Max. apparent output power 340 kVA 370 kVA

Nominal mains voltage 3 x 280 V 3 x 320 V

Maximum AC current 700 A 666 A

Mains nominal frequency / range

50 Hz / 45 Hz…55 Hz (60 Hz / 55 Hz...65 Hz upon request)

Power factor cosφ adjustable from 0.8 overexcited to 0.8 underexcited

Harmonic distortionat rated output < 3 %

Connection type threaded bolts M8

Grid connection three-phase (without neutral conductor)

Maximum short-circuit current

1 506 A peak (1 ms) / 702 A RMS (≤ 1003) ms)

1 506 A peak (1 ms) / 666 A RMS (≤ 1003) ms)

Overcurrent protection 750 A (250 A per power unit)

Overvoltage category 2

Efficiency Max. efficiency 98 % 98 %

Europ. Efficiency 97.2 %4) 97.4 %4)

Power input Own consumption night < 7 W

Ambient conditions

Protection type compliant with EN 60529 IP20

Ambient temperature range −20 °C…+50 °C

Ambient temperature range for rated power output −20 °C...+45 °C

Relative humidity 0…98% (no condensation)

Degree of soiling PD2

Maximum altitudeabove sea level 2 000 m (without derating))

Noise emissions < 65 dBA (↔1.5 m)

Required fresh air 5 000 m3 / h

Page 54: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

54

SM330TS-SV SM360TS-SV

Configuration Casing Steel structure, powder-coated

Display (in MCU) Graphic LC display with backlight and status LED

Data logger (in MCU) Data logger for energy yield, peak output and operating duration for the last 31 days, 12 months and 10 years

DC power switch Thermomagnetic triggering, type N, 36 kA

AC power switch Thermomagnetic triggering, type N, 36 kA

Isolation monitoring yes (configurable function)

Protection class (EN61140) I

Galvanic isolation No galvanic isolation: direct connection to medium-voltage transformer

Standards &guidelines

CE-compliant yes5)

EMC EN 61000-6-2 / EN 61000-6-4

Standard / guideline compliance G59/2 / BDEW MV Guideline / PPC Guide / RD 661

Device safety IEC/EN 62109-1

Interfaces Data communication (in MCU) 2 x RS485 (RJ45) / 1 x Ethernet (RJ45)

Status signalling contact (in MCU)

Potential-free terminal contact pair (configurable function)

Alarm input (in MCU) Terminal contact pair for connection to MaxConnect plus

Inverter shutdown 1 Two terminal contact pairs (can be chain-linked via several MCU’s)

Inverter shutdown 2 (in MCU) Terminal contact pair

Test contacts For the functional test of grid monitoring

Weight & dimensions

Weight 950 kg

Dimensions (W x H x D) 1 200 x 1 970 x 800 mm

Warranty Standard warranty 2 years (free extension to 5 years after registration)

Warranty extensions to 10, 15, 20, or 25 years

1) at cosφ = 1, Uac = 280 V2) at cosφ = 1, Uac = 320 V3) up to 1 000 ms with activated FRT function (Fault-Ride-Through)4) in Single MPPT operation with active partial load optimisation (see operating manual parameter

configuration with MaxTalk 2 Pro)5) the complete conformity declaration can be found on our website at www.solarmax.com

Page 55: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

55

en

TS-SV Master Control Unit (MCU)

AC voltage supply Maximum input voltage 230 VAC

Maximum input current 1.05 A

Start-up current 100 A

Start-up current duration 30 ms

Frequency 50…60 Hz

DC voltage supply Maximum input voltage 900 VDC

Weight & dimensions Weight 10 kg

Dimensions (W x H x D) 600 x 520 x 150 mm

7.1 Efficiency curve

Efficiency curve Single MPPT - SM330TS-SV100 %

98 %

96 %

94 %

92 %

90 %

88 %

86 %

84 %

82 %

80 %0 % 10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 % 100 %

η 450 VDC

η 550 VDC

Effic

ienc

y η [

%]

Standardised output Pac/Pac max [%]

Page 56: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

56

Efficiency curve Multi MPPT - SM330TS-SV

100 %

98 %

96 %

94 %

92 %

90 %

88 %

86 %

84 %

82 %

80 %0 % 10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 % 100 %

η 450 VDC

η 550 VDC

Effic

ienc

y η [

%]

Standardised output Pac/Pac max [%]

Efficiency curve Single MPPT - SM360TS-SV100 %

98 %

96 %

94 %

92 %

90 %

88 %

86 %

84 %

82 %

80 %0 % 10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 % 100 %

η 510 VDC

η 600 VDC

Effic

ienc

y η [

%]

Standardised output Pac/Pac max [%]

Page 57: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

57

en

7.2 Temperature-dependent output reduction

The inverter can feed 100 % of its rated output for an unlimited time up to an ambient temperature of 45 °C. In the temperature range from 45 °C to 50 °C yield losses have to be expected, at 50 °C the inverter can still feed in 90 % of its rated output for an unlimited time. For this reason ambient temperatures exceeding 45 °C must be strictly avoided.

Stan

dard

ised

out

put [

PAC/P

nom

]

Ambient temperature [°C]

-20

1.2

1.0

0.8

0.6

0.4

0.2

0

-10 0 10 20 30 40 50

Umgebungstemperatur [°C]

Norm

iert

e Le

istu

ng [P

AC /

P NOM]

Page 58: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

58

7.3 Individual country settings

NOTE

MaxTalk 2 Pro can be used by authorized and trained personnel to individually adjust the operating parameters. MaxTalk 2 Pro: professional version of MaxTalk for the con-figuration of inverters. The required "SolarMax TS-SV series parameter configuration using MaxTalk 2 Pro" operating manual can be downloaded from our website at www.solarmax.com ("Downloads" area).

7.3.1 SM330TS-SV

Parameter Unit Germany Spain Italy France Great Britain

Vac min 1 V 224 238 84 224 246.4

t Vac min 1 ms 2000 200 2000 200 2500

Vac max 1 V 322 308 364 336 305.2

t Vac max 1 ms 100 200 200 200 1000

Vac min 2 V 126 - - - 226.8

t Vac min 2 ms 1500 0 0 0 500

Vac max 2 V - - - - 313.6

t Vac max 2 ms 0 0 0 0 500

Vac 10min max V - - - - -

f min 1 Hz 47.5 48 45.5 47 47.5

t f min 1 ms 100 200 200 200 20000

f max 1 Hz 51.5 51 54.5 52 51.5

t f max 1 ms 100 200 200 200 90000

f min 2 Hz - - - - 47

t f min 2 ms 0 0 0 0 500

f max 2 Hz - - - - 52

t f max 2 ms 0 0 0 0 500

Restart delay s 0 0 300 0 0

Mains check On/Off On On Off On On

- Vac MC max V 364 308 308 336 305.2

- Vac MC min V 266 238 238 224 246.4

- f MC max Hz 50.05 51 50.1 52 51.5

- f MC min Hz 47.5 48 49.9 47 47

- t MC monitoring s 0 180 30 0 180

Island Detection On/Off Off On Off Off On

OV Detection On/Off On On On On On

Soft Start W/s - - - - -

Pac Progression %/min - - 20 - -

P(f)-Mode (1/2/3/Off) 1 Off 3 Off Off

- f start Hz 50.2 50.2 50.3 50.2 50.2

- f stop Hz 50.05 - 50.1 - -

Page 59: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

59

en

Parameter Unit Germany Spain Italy France Great Britain

- MC f max Hz - - 50.1 - -

- MC f min Hz - - 49.9 - -

- MC time s 0 0 300 0 0

- Reduction %/Hz 40 40 83 40 40

- Re-increase %/min - 10 5 10 10

Q mode Off Off Off Off Off

FRT On/Off On On On Off Off

- K factor 2.0 1.0 0.0 0.0 0.0

S max SM330TS-SV kVA 342 342 342 342 342

Pac max SM330TS-SV kW 342 342 342 342 342

Iac max SM330TS-SV A 702 702 702 702 702

Parameter Unit China USA Other Other 60 Hz

Vac min 1 V 238 246.4 238.0 246.4

t Vac min 1 ms 2000 2000 1500 2000

Vac max 1 V 308 308 322.0 308

t Vac max 1 ms 2000 1000 200 1000

Vac min 2 V 140 140 - 140

t Vac min 2 ms 100 160 0 160

Vac max 2 V - 336 - 336

t Vac max 2 ms 0 160 0 160

Vac 10min max V - - - -

f min 1 Hz 49.5 59.3 47 59.3

t f min 1 ms 600500 2000 500 2000

f max 1 Hz 50.2 60.5 52 60.5

t f max 1 ms 120500 160 500 160

f min 2 Hz 48 57 - 57

t f min 2 ms 200 160 0 160

f max 2 Hz 50.5 - - -

t f max 2 ms 200 0 0 0

Restart delay s 0 0 0 0

Mains check On/Off On On On On

- Vac MC max V 308 296.8 322 296.8

- Vac MC min V 238 257.6 238 257.6

- f MC max Hz 50.2 60.5 51 60.5

- f MC min Hz 49.5 59.3 47 59.3

- t MC monitoring s 60 300 30 300

Island Detection On/Off On On Off On

OV Detection On/Off On On

Soft Start W/s 1140 - - -

Pac Progression %/min - - - -

P(f)-Mode (1/2/3/Off) Off Off Off Off

- f start Hz 50.2 60.2 50.2 60.2

- f stop Hz - 60.05 - 60.05

- MC f max Hz - - - -

- MC f min Hz - - - -

Page 60: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

60

Parameter Unit China USA Other Other 60 Hz

- MC time s 0 0 0 0

- Reduction %/Hz 40 40 40 40

- Re-increase %/min 10 - 10 -

Q mode Off Off Off Off

FRT On/Off On Off Off Off

- K factor 0.0 0.0 0.0 0.0

S max SM330TS-SV kVA 342 342 342 342

Pac max SM330TS-SV kW 342 342 342 342

Iac max SM330TS-SV A 702 702 702 702

7.3.2 SM360TS-SV

Parameter Unit Germany Spain Italy France Great Britain

Vac min 1 V 256 272 96 256 281.6

t Vac min 1 ms 2000 200 2000 200 2500

Vac max 1 V 368 352 416 384 348.8

t Vac max 1 ms 100 200 200 200 1000

Vac min 2 V 144 - - - 259.2

t Vac min 2 ms 1500 0 0 0 500

Vac max 2 V - - - - 358.4

t Vac max 2 ms 0 0 0 0 500

Vac 10min max V - - - - -

f min 1 Hz 47.5 48 45.5 47 47.5

t f min 1 ms 100 200 200 200 20000

f max 1 Hz 51.5 51 54.5 52 51.5

t f max 1 ms 100 200 200 200 90000

f min 2 Hz - - - - 47

t f min 2 ms 0 0 0 0 500

f max 2 Hz - - - - 52

t f max 2 ms 0 0 0 0 500

Restart delay s 0 0 300 0 0

Mains check On/Off On On Off On On

- Vac MC max V 416 352 352 384 348.8

- Vac MC min V 304 272 272 256 281.6

- f MC max Hz 50.05 51 50.1 52 51.5

- f MC min Hz 47.5 48 49.9 47 47

- t MC monitoring s 0 180 30 0 180

Island Detection On/Off Off On Off Off On

OV Detection On/Off On On On On On

Soft Start W/s - - - - -

Pac Progression %/min - - 20 - -

P(f)-Mode (1/2/3/Off) 1 Off 3 Off Off

- f start Hz 50.2 50.2 50.3 50.2 50.2

- f stop Hz 50.05 - 50.1 - -

- MC f max Hz - - 50.1 - -

- MC f min Hz - - 49.9 - -

Page 61: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

61

en

Parameter Unit Germany Spain Italy France Great Britain

- MC time s 0 0 300 0 0

- Reduction %/Hz 40 40 83 40 40

- Re-increase %/min - 10 5 10 10

Q mode Off Off Off Off Off

FRT On/Off On On On Off Off

- K factor 2.0 1.0 0.0 0.0 0.0

S max SM360TS-SV kVA 369 369 369 369 369

Pac max SM360TS-SV kW 369 369 369 369 369

Iac max SM360TS-SV A 666 666 666 666 666

Parameter Unit China USA Other Other 60 Hz

Vac min 1 V 272 281.6 272 281.6

t Vac min 1 ms 2000 2000 1500 2000

Vac max 1 V 352 352 368 352

t Vac max 1 ms 2000 1000 200 1000

Vac min 2 V 160 160 - 160

t Vac min 2 ms 100 160 0 160

Vac max 2 V - 384 - 384

t Vac max 2 ms 0 160 0 160

Vac 10min max V - - - -

f min 1 Hz 49.5 59.3 47 59.3

t f min 1 ms 600500 2000 500 2000

f max 1 Hz 50.2 60.5 52 60.5

t f max 1 ms 120500 160 500 160

f min 2 Hz 48 57 - 57

t f min 2 ms 200 160 0 160

f max 2 Hz 50.5 - - -

t f max 2 ms 200 0 0 0

Restart delay s 0 0 0 0

Mains check On/Off On On On On

- Vac MC max V 352 339.2 368 339.2

- Vac MC min V 272 294.4 272 294.4

- f MC max Hz 50.2 60.5 51 60.5

- f MC min Hz 49.5 59.3 47 59.3

- t MC monitoring s 60 300 30 300

Island Detection On/Off On On Off On

OV Detection On/Off On On On On

Soft Start W/s 1140 - - -

Pac Progression %/min - - - -

P(f)-Mode (1/2/3/Off) Off Off Off Off

- f start Hz 50.2 60.2 50.2 60.2

- f stop Hz - 60.05 - 60.05

- MC f max Hz - - - -

- MC f min Hz - - - -

- MC time s 0 0 0 0

- Reduction %/Hz 40 40 40 40

Page 62: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

62

Parameter Unit China USA Other Other 60 Hz

- Re-increase %/min 10 - 10 -

Q mode Off Off Off Off

FRT On/Off On Off Off Off

- K factor 0.0 0.0 0.0 0.0

S max SM360TS-SV kVA 369 369 369 369

Pac max SM360TS-SV kW 369 369 369 369

Iac max SM360TS-SV A 666 666 666 666

8 WarrantyGeneral Terms of Guarantee for SolarMax ProductsSolarMax Productions GmbH (herafter SOLARMAX) guarantees the correct function and absence of defects of your SolarMax tools for a particular, device -specific duration of guarantee. This duration of guarantee can be prolonged by an extension of guarantee according to these Terms of Guarantee.

This manufacturer’s guarantee exists in addition to legal warranty obligations of the vendor. In case of a content overlap, the claim under the manufacturer’s guarantee takes precedence, to the extent permitted by law, over the claim from warranty.

For the assertion of warranty claims please contact your vendor.

Page 63: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

63

en

1. Basic Guarantee BASIC

The services of the Basic Guarantee are only provided free of charge in countries released by SOLARMAX at the time of installation. Please clarify this with your dealer. You will find a current list of these countries in the appendix or on our homepage. On request we are happy to send you this list.

a) Duration of Guarantee BASIC

String Inverters:

■■ 60 months starting from purchase date, but max. 72 months after delivery of the device by SOLARMAX

Central Inverters:

■■ Series C/S/TS/TS-SV: 24 months from purchase date, but max. 30 months after delivery of device by SOLARMAX

■■ Series RX: 60 months from purchase date, but max. 66 months after delivery of device by SOLARMAX

Accessories:

■■ 24 months from purchase date, but max. 30 months after delivery of device by SOLARMAX■■ Junction-Box 32HT2: 60 months from purchase date, but 72 months after delivery of device by

SOLARMAXDeviating written confirmation from SOLARMAX have priority.

b) Scope of Guarantee BASIC

If a device shows a defect or malfunction within the duration of guarantee and if the conditions for the assertion of warranty as defined below are met, the device or device parts will be repaired or replaced by SOLARMAX free of charge at its discretion within an appropriate period of time, as shown below, provided that this is not disproportionate or impossible.

Free Replacement: This contains the provision of equivalent replacement devices or parts, which can be dispatched step by step against return of the defect devices or device parts or can be also delivered by order.

Free On-Site-Replacement: This contains material cost as well as labor and travel expenses of SOLARMAX staff or staff authorized by SOLARMAX, insofar as it was send to the operation site by SOLARMAX.

Further-reaching claims, especially claiming the replacement of direct and indirect damages, founded by the defect of the device or cost incurred by the implementation and removal or lost profit, are not covered by this guarantee.

2. Assurance of Repair and Replacement

SOLARMAX will provide repair material and replacement devices during the duration of guarantee in its discretion.

If repair material or replacement devices for particular devices are not available anymore, the fol-lowing applies:

SOLARMAX is authorized to install the device, which needs to be replaced, with a comparable device with an equivalent or higher performance.

Page 64: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

64

Necessary technical adjustments of the replacement device for the installation of such a replace-ment device are covered by the guarantee for expenditure of time and material to the extent of up to 10 % of the list price of the replacement device.

Not covered by the guarantee are, if need be, a required replacement and a connection of peripheral devices as well as, if need be, required adjustments of surrounding devices of an inverter (such as supply cord, ventilation and safety devices).

SOLARMAX does its level best to minimize the extent of adjustment.

If there is no replacement material available at a reasonable expense, SOLARMAX is authorized to replace the defect device. In this case the above mentioned terms of replacement are applicable.

3. Duration of Guarantee for Device Repair/ Device Replacement

In case of repair or replacement of devices within the scope of the guarantee, the remaining duration of guarantee of the original device applies to the repaired / replaced device.

4. Exclusion of Guarantee Services

Especially in following cases the guarantee claim is cancelled:

■■ In the event of transport damage or external influences■■ In the event of interference, changes, repairs by non-SOLARMAX-authorized staff or on one’s

own■■ In the event of inappropriate use, incorrect operation and installation■■ In the event of neglecting operating, installation and maintenance instructions ■■ In the event of non-compliant surrounding conditions (such as lack of ventilation, humidity, dust

pollution, etc.) ■■ In the event of higher force (such as lightning, overvoltage, water damage, fire etc.)

Not covered by the guarantee are wear parts, especially fuses and overvoltage protection

5. Assertion of Guarantee

For the assertion of the guarantee the SOLARMAX hotline must be contacted by phone or in written form and their instructions must be followed carefully.

You will find the Hotline number for your country on our homepage.

Please hold the series number, the article description, a short description of the defect and the purchase receipt ready.

Transactions in order to solve guarantee cases carried out by the buyer without the coordination with and approval by SOLAR MAX will not be compensated.

In case of neglecting this procedure SOLARMAX reserves the right to decline the delivery of of the guarantee service.

6. Exclusion of Guarantee

SOLARMAX reserves the right to temporarily or finally exclude the guarantee, if the parameters of the plant do not allow a proper function of the devices (e.g. in the event of a parameter as set out in number 4)

The exclusion of guarantee can be cancelled in accordance with SOLARMAX.

Therefore it is necessary to have a written confirmation by SOLARMAX, in order to restart the guarantee terms.

Page 65: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

65

en

7. Guarantee Extension

For devices with the Basic Guarantee BASIC the duration of guarantee can be prolonged by purchasing a guarantee extension within the following time periods. An extension for specific devices can be purchased on the basis of limited services. The extensions being available per device can be found on our homepage. The purchase of a guarantee extension will be confirmed by SOLARMAX with a Guarantee Certificate (Series Number of Product).

In case of a replacement this certificate will not be adjusted to the new series number. In this way the guarantee extension stays unaffected.

a) Time Limit for entry into Guarantee Extension

String Inverters / Junction-Box 32HT2: The extension of the guarantee can be purchased within 60 months starting from purchase date, but within max. 72 months after delivery of the device by SOLARMAX.

Central Inverters: The extension of the guarantee can be purchased within 3 months starting from purchase date, but max. 12 months after delivery of the device by SOLARMAX

b) Scope of the Guarantee Extension

The Scope of the Guarantee Extension contains all services of the Basic Guarantee BASIC.

c) Conclusion of a Guarantee Extension

In order to purchase a Guarantee Extension, it is necessary to fully complete and hand in a Gua-rantee Extension form.

The Guarantee Extension is completed with a written confirmation by SOLARMAX, the receipt of the Guarantee Certificate and the payment by the customer.

Deviating written confirmation from SOLARMAX have priority.

8. Conditions after the Extension of the Guarantee

The cost for repair and replacement after the extension of the guarantee period will be charged at cost. SOLARMAX ensures the repair and replacement ability beyond the guarantee period at its own discretion.

9. Applicable Law, Place of Jurisdiction

The Law of the Federal Republic of Germany is applicable, Place of Jurisdiction shall exclusively be Augsburg / Germany, as far as this is permitted by law.

Appendix Country List:

Austria, Belgium, Bulgaria, Czech Republic, Denmark, France, Germany, Greece, Italy, Liechsten-stein, Luxembourg, Netherlands, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland, United Kingdom

(Issued 10/2015 – subject to modifications)

Page 66: SolarMax TS-SV · 2020. 10. 2. · The TS-SV inverter consists of three independent power units. Each power unit has its own MPP tracker, DC-end overvoltage conductors, power switches

2015

/ 10

en