GypWall ISSUE DATE: NOVEMBER 2008 84 Standard clauses for GypWall Systems up to a height of 3,6m SYSTEM: GYPWALL STANDARD 30 MIN Rw 42dB Consisting of 63,5mm UltraSTEEL™ Drywall steel studs inserted at 600mm centres into 63,5mm Drywall steel track at top and bottom and clad both sides with 12,5mm Rhinoboard fixed with 25mm Drywall Streaker screws spaced at 220mm centres. Stagger joints between boards. All joints to be taped and jointed as per manufacturers instructions. 51mm studs and tracks may be used. SYSTEM: GYPWALL SILENT 60 MIN Rw 48dB Consisting of 63,5mm UltraSTEEL™ Drywall steel studs inserted at 600mm centres into 63,5mm Drywall steel track at top and bottom and clad one side with 12,5mm Firestop Rhinoboard fixed with 25mm Drywall Streaker screws spaced at 220mm centres. Insert RhinoFlam/Insulmat mineral fibre blanket in cavity. Clad the other side with a single layer of 12,5mm Taper-edge Rhino Firestop Board. Stagger joints between boards. All joints are to be taped and jointed in accordance with manufactur- er’s specifications. SYSTEM: GYPWALL TOUGH 60 MIN Rw 46dB Consisting of 63,5mm UltraSTEEL™ Drywall steel studs inserted at 600mm centres into 63,5mm Drywall steel track at top and bottom and clad both sides with two layers of 12,5mm Rhinoboard with base layer fixed with 25mm Drywall Streaker screws spaced at 220mm centres and face layer fixed using 41mm Drywall Streaker screws at 220mm centres. Stagger joints between all boards. Face layer joints to be taped and jointed in accor- dance with manufacturer’s specifications. SYSTEM: GYPWALL SILENT 52 120 MIN Rw 51dB Consisting of 63,5mm UltraSTEEL™ Drywall steel studs inserted at 600mm centres into 63,5mm Drywall steel track at top and bottom and clad with a double layer of 12,5mm Firestop Rhinoboard on both sides fixed with 25mm Drywall Streaker screws spaced at 220mm centres and a face layer 12,5mm Firestop Rhinoboard fixed with 41mm Drywall Streaker screws at 220mm centres. Insert RhinoFlam/Insulmat mineral fibre blanket in cavity. Stagger all joints. Facelayer joints to be taped and jointed in accordance with manufacturer’s specifica- tions. SYSTEM: GYPWALL SECURE 120 MIN Rw 51dB Consisting of 63,5mm UltraSTEEL™ Drywall steel studs inserted at 600mm centres into 63,5mm steel Drywall track at top and bottom, clad on both sides with a 12,5mm Firestop Rhinoboard. Base layer fixed with 25mm Drywall Streaker screws at 220mm cen- tres, 0,5mm galvanized steel sheet and a 12,5mm face layer Firestop Rhinoboard fixed using 41mm Drywall Streaker screws at 220mm centres. Stagger joints between boards. Face layer joints to be taped and jointed in accordance with manufactur- er’s specifications. SYSTEM: GYPWALL FIREBREAK 120 MIN Rw 50dB Consisting of 63.5mm UltraSTEEL™ studs inserted at 600mm centres into 63.5mm UltraSTEEL™ track at top and bottom, cladded with 12.5mm Taper-edge Firestop Rhinoboard on both sides fixed with 25mm Drywall Streaker screws at 220mm centres, and face layer 15mm Taper-edge Firestop Rhinoboard on both sides and fixed with 41mm Drywall Streaker screws at 220mm centres. Stagger joints between boards. Face layer joints to be taped and jointed in accordance with manufacturer's specifications. SYSTEM: GYPWALL DRYLINING Drylining consisting of 12.5mm Rhinoboard fixed with RhinoLite gypsum plaster to brick, block or masonry walls. RhinoLite to be applied in vertical dabs of 75 x 250 at 300mm centres. Dabs to be spaced at 600mm centres and continuous runs along top and bottom of wall. Rhinoboard to be supported off the floor with a 12.5mm Rhinoboard strip spacer. The Rhinoboard lining is to be firmly bedded onto the RhinoLite dabs, and then straight- ened with a straight edge in both vertical and hor- izontal plains. Only full length boards to be used. All vertical joints to be lined up, joints between adjacent boards to be 1 - 2mm. Joints to be re- inforced with RhinoTape, filled with RhinoGlide filler and finished off as per Gyproc’s jointing instructions. C Roc 12/8/08 2:29 PM Page 2
Transcript
Page 1: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 84

Standard clauses for GypWall Systemsup to a height of 3,6m

SYSTEM: GYPWALL STANDARD30 MIN Rw 42dB

Consisting of 63,5mm UltraSTEEL™ Drywall steelstuds inserted at 600mm centres into 63,5mmDrywall steel track at top and bottom and clad bothsides with 12,5mm Rhinoboard fixed with 25mmDrywall Streaker screws spaced at 220mm centres.Stagger joints between boards. All joints to betaped and jointed as per manufacturers instructions.51mm studs and tracks may be used.

SYSTEM: GYPWALL SILENT60 MIN Rw 48dB

Consisting of 63,5mm UltraSTEEL™ Drywall steelstuds inserted at 600mm centres into 63,5mmDrywall steel track at top and bottom and clad oneside with 12,5mm Firestop Rhinoboard fixed with25mm Drywall Streaker screws spaced at 220mmcentres. Insert RhinoFlam/Insulmat mineral fibreblanket in cavity. Clad the other side with a singlelayer of 12,5mm Taper-edge Rhino Firestop Board.Stagger joints between boards. All joints are to betaped and jointed in accordance with manufactur-er’s specifications.

SYSTEM: GYPWALL TOUGH60 MIN Rw 46dB

Consisting of 63,5mm UltraSTEEL™ Drywall steelstuds inserted at 600mm centres into 63,5mmDrywall steel track at top and bottom and clad bothsides with two layers of 12,5mm Rhinoboard withbase layer fixed with 25mm Drywall Streakerscrews spaced at 220mm centres and face layerfixed using 41mm Drywall Streaker screws at220mm centres. Stagger joints between all boards.Face layer joints to be taped and jointed in accor-dance with manufacturer’s specifications.

SYSTEM: GYPWALL SILENT 52120 MIN Rw 51dB

Consisting of 63,5mm UltraSTEEL™ Drywall steelstuds inserted at 600mm centres into 63,5mmDrywall steel track at top and bottom and clad witha double layer of 12,5mm Firestop Rhinoboard onboth sides fixed with 25mm Drywall Streakerscrews spaced at 220mm centres and a face layer12,5mm Firestop Rhinoboard fixed with 41mmDrywall Streaker screws at 220mm centres. InsertRhinoFlam/Insulmat mineral fibre blanket in cavity.Stagger all joints. Facelayer joints to be taped andjointed in accordance with manufacturer’s specifica-tions.

SYSTEM: GYPWALL SECURE120 MIN Rw 51dB

Consisting of 63,5mm UltraSTEEL™ Drywall steelstuds inserted at 600mm centres into 63,5mm steelDrywall track at top and bottom, clad on both sideswith a 12,5mm Firestop Rhinoboard. Base layer fixedwith 25mm Drywall Streaker screws at 220mm cen-tres, 0,5mm galvanized steel sheet and a 12,5mmface layer Firestop Rhinoboard fixed using 41mmDrywall Streaker screws at 220mm centres. Staggerjoints between boards. Face layer joints to betaped and jointed in accordance with manufactur-er’s specifications.

SYSTEM: GYPWALL FIREBREAK120 MIN Rw 50dB

Consisting of 63.5mm UltraSTEEL™ studs inserted at600mm centres into 63.5mm UltraSTEEL™ track attop and bottom, cladded with 12.5mm Taper-edgeFirestop Rhinoboard on both sides fixed with 25mmDrywall Streaker screws at 220mm centres, and facelayer 15mm Taper-edge Firestop Rhinoboard onboth sides and fixed with 41mm Drywall Streakerscrews at 220mm centres. Stagger joints betweenboards. Face layer joints to be taped and jointed inaccordance with manufacturer's specifications.

SYSTEM: GYPWALL DRYLINING

Drylining consisting of 12.5mm Rhinoboard fixedwith RhinoLite gypsum plaster to brick, block ormasonry walls. RhinoLite to be applied in verticaldabs of 75 x 250 at 300mm centres. Dabs to bespaced at 600mm centres and continuous runsalong top and bottom of wall. Rhinoboard to besupported off the floor with a 12.5mm Rhinoboardstrip spacer. The Rhinoboard lining is to be firmlybedded onto the RhinoLite dabs, and then straight-ened with a straight edge in both vertical and hor-izontal plains. Only full length boards to be used.All vertical joints to be lined up, joints betweenadjacent boards to be 1 - 2mm. Joints to be re-inforced with RhinoTape, filled with RhinoGlidefiller and finished off as per Gyproc’s jointinginstructions.

C Roc 12/8/08 2:29 PM Page 2

Page 2: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWall

For use in office walling, hotels, hospitals, schools

or wherever a 1/2 hour Fire rating is required.

ULTRASTEEL STUD DRYWALL - non-load bearing

12,5mm Rhinoboard - one layer each side.

RODENT PROOF CLASS B1

WALL PROPERTIES1/

2 hour fire rating

Sound Reduction Index

Approximate mass 23 kg/m2.

MATERIALS USED1. 51 mm or 63,5mm Drywall UltraSTEEL™ stud.

2. 51 mm or 63,5mm Drywall UltraSTEEL™ track.

3. 12,5 mm Taper-edge Rhinoboard.

4. 25 mm Drywall Streaker screws.

5. Rhino Drywall jointing system.

6. Floor and ceiling finishes (i.e. skirtings and

cornice/trim). To be specified separately.

APPLICATION DETAILS1. Set UltraSTEEL™ studs spaced at 600mm c/c

into equivalent UltraSTEEL™ track at floor

and ceiling.

2. Fix a single layer of 12,5mm Rhinoboard to

each side using 25mm Drywall Streaker screws

spaced at 220mm c/c. Stagger joints.

3. Tape and joint according to manufacturers

specifications.

4. Refer to data sheet Standard Clauses for

Specifiers: Drywall Systems.

5. Acoustic performance requires sealing between

UltraSTEEL™ track, floor, ceiling and any other

abutment joints.

ISSUE DATE: NOVEMBER 2008 85

GypWall Standard: 1/2 hour Fire Rating

51 mm 63,5mmSound ReductionIndex 39dB 42dB

Wall thickness 76 mm 89mm

Stud

C Roc 12/8/08 2:29 PM Page 3

Page 3: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 86

C Roc 12/8/08 2:29 PM Page 4

Page 4: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 87

GypWall Silent: 1 hour Fire Rating

For use in office walling, hotels, hospitals, schoolsor wherever a 1 hour Fire Rating or a highersound reduction index is required.

ULTRASTEEL STUD DRYWALL - non-load bearing12,5mm Firestop Rhinoboard - single layereach side with 80kg/m3 RhinoFlam/Insulmatwire mesh surfaced mineral fibre blanket.

RODENT PROOF CLASS B1

WALL PROPERTIES

1 hour fire rating.Sound Reduction Index withRhinoFlam/Insulmatt wire mesh surfaced fibreblanket of 80 kg/m3 - 48 dB.Wall thickness 89 mm.Approximate mass 30 kg/m2.

MATERIALS USED

1. 63,5 mm UltraSTEEL™ stud.2. 63,5 mm UltraSTEEL™ track.3. 12,5 mm Firestop Taper-edge Rhinoboard.4. 25 mm Drywall Streaker screws.5. Rhinoboard Drywall jointing system.6. Floor and ceiling finishes (i.e. skirting and

cornice/trim). To be specified separately.7. RhinoFlam/Insulmatt wire mesh surfaced fibre

blanket of 80 kg/m3.

APPLICATION DETAILS

1. Set 63,5 mm UltraSTEEL™ studs spaced at 600mm c/c into UltraSTEEL™ track at floor and ceiling.

2. Apply a single layer of FireStop Rhinoboardvertically to one side using 25mm DrywallStreaker screws at 220mm c/c.

3. Insert the 80kg/m3 RhinoFlam/Insulmat wire mesh surfaced fibre blankets between studs.

4. Install a single layer of FireStop Rhinoboard vertically to the other side using 25mm Drywall screws at 220mm c/c. Stagger joints.

5. Tape and joint according to manufacturersspecifications.

6. Refer to data sheet for Standard Clauses for Specifiers: Drywall Systems.

7. Acoustic performance requires sealing betweenUltraSTEEL™ track, floor, ceiling and any otherabutment joints.

C Roc 12/8/08 2:29 PM Page 5

Page 5: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 88

C Roc 12/8/08 2:29 PM Page 6

Page 6: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 89

GypWall: 1 hour Fire Rating

For use in office walling, hotels, hospitals, schoolsor wherever a 1 hour Fire Rating is required.

ULTRASTEEL STUD DRYWALL - non-load bearing12,5mm Rhinoboard - double layer each side.

RODENT PROOF CLASS B1

WALL PROPERTIES

1 hour fire rating.Sound Reduction Index 46 dB.Thickness 114mm.Mass 45kg/m2.

MATERIALS USED

1. 63,5mm UltraSTEEL™ stud.2. 63,5mm UltraSTEEL™ track.3. 12,5mm Taper-edge Rhinoboard.4. 25mm and 41mm Drywall Streaker screws.5. Rhino Drywall jointing system.6. Floor and ceiling finishes (i.e. skirting and

cove/trim). To be specified separately.

APPLICATION DETAILS

1. Set 63,5 mm UltraSTEEL™ studs spaced at 600mm c/c into UltraSTEEL™ track at floor and ceiling.

2. Fix a base layer of 12,5mm board, to both sidesto each side using 25mm Drywall Streaker screws at220mm c/c.

3. Fix a face layer of 12,5mm Rhinoboard. Using 41mm drywall Streaker screws spaced at220mm c/cStagger all joints.

4. Tape and joint face layer only in accordance with data sheet for Hand Jointing Application.

5. Refer to data sheet for Standard Clauses forSpecifiers: Drywall Systems.

6. Acoustic performance requires sealing betweenUltraSTEEL™ track, floor, ceiling and any otherabutment joints.

C Roc 12/8/08 2:29 PM Page 7

Page 7: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 90

C Roc 12/8/08 2:30 PM Page 8

Page 8: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 91

GypWall Silent 52: 2 hour Fire Rating

For use in office walling, hotels, hospitals, schools orwherever a 2 hour Fire Rating is required.

ULTRASTEEL STUD DRYWALL - non-load bearing12,5mm Rhino-Firestop board - two layers each sidewith RhinoFlam wire mesh surfaced mineral fibreblanket.

2 HOUR FIRE RATED WALL

RODENT PROOF CLASS B1

WALL PROPERTIES

2 hour fire rating with 50mm 80kg/m3

RhinoFlam/InsulmattSound Reduction Index 51 dB.Wall thickness 114mm. Approximate mass 50kg/m2.

MATERIALS USED

1. 63,5mm UltraSTEEL™ stud.2. 63,5mm UltraSTEEL™ track.3. 12,5mm Taper-edge FireStop Rhinoboard.4. 25mm and 41mm Drywall Streaker Screws.5. Rhino-Drywall jointing system.6. Floor and ceiling finishes (i.e. skirting and

cove/trim). To be specified separately.7. RhinoFlam/Insulmatt wire mesh surfaced

mineral fibre blanket of 80kg/m3.

APPLICATION DETAILS

1. Set 63,5 mm UltraSTEEL™ studs spaced at600 mm c/c into UltraSTEEL™ track at floor and ceiling.

2. Fix a single layer of Firestop Rhinoboard vertically to one side using 25 mm Drywall Streaker screws spaced at 220 mm c/c.

3. Insert the 80 kg/m3 RhinoFlam/Insulmatt wire mesh surfaced fibre blanket between UltraSTEEL™ studs.

4. Fix a base layer of Rhino-Firestop boardvertically to the other side using 25 mm Drywall screws at 220 mm c/c.

5. Fix a face layer of 12,5 mm Firestop Rhinoboard to both sides. Stagger all joints on each side using 41mm Drywall Streaker screws spaced at 220 mm c/c.

6. Tape and joint face layer in accordance with data sheet for Hand Jointing Application.

7. Refer to data sheet for Standard Clauses forSpecifiers: Drywall Systems.

8. Acoustic performance requires sealing betweenUltraSTEEL™ track, floor, ceiling and any other abutment joints.

C Roc 12/8/08 2:30 PM Page 9

Page 9: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 92

C Roc 12/8/08 2:30 PM Page 10

Page 10: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 93

GypWall Secure: 2 hour Fire Rating

For use in office partitioning, internal residentialwalling, hotels, hospitals, schools or wherever a 2 hour Fire Rating is required.

ULTRASTEEL STUD DRYWALL - non-load bearing12,5mm Firestop Rhinoboard plus 0,5mm steelplus 12,5mm Firestop Rhinoboard on each side.

2 HOUR FIRE RATED WALL

RODENT PROOF CLASS B1

WALL PROPERTIES

2 hours fire rating.Sound Reduction Index Rw 51 dB.Wall thickness 115mm.Approximate mass 50kg/m2.

MATERIALS USED

1. 63,5mm UltraSTEEL™ stud.2. 63,5mm UltraSTEEL™ track.3. 12,5mm Taper-edge Firestop Rhinoboard.4. 0,5mm galvanized steel sheet.5. 25mm and 41mm Drywall Streaker screws.6. Rhinoboard Drywall jointing system.7. Floor and ceiling finishes (i.e. skirting and

cove/trim). To be specified separately.

APPLICATION DETAILS

1. Set 63,5mm UltraSTEEL™ studs spaced 600mm c/c into 63,5mm UltraSTEEL™ track at floor andceiling.

2. Fix a base layer of 12,5mm Firestop Rhinoboardvertically to each side using 25mm Drywall Streaker screws spaced at 220mm c/c.

3. Apply a sheet of 0,5mm galvanized steel to each side.

4. Apply a face layer of 12,5mm Taper-edge Firestop Rhinoboard to both sides. Staggering all joints using 41mm Drywall Streaker screws spaced at 220mm c/c.

5. Tape and joint according to data sheet for Hand Jointing Application.

6. Refer to data sheet for Standard Clauses for Specifiers: Drywall Systems.

7. Acoustic performance requires sealing betweenUltraSTEEL™ track, floor, ceiling and any otherabutment joints.

C Roc 12/8/08 2:30 PM Page 11

Page 11: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 94

C Roc 12/8/08 2:30 PM Page 12

Page 12: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 95

GypWall FireBreak: 2 hour Fire Rating

For use in office walling, hotels, hospitals, schoolsor wherever a 2 hour Fire Rating is required.

ULTRASTEEL STUD DRYWALL - non-load bearing12,5mm Rhino-Firestop plus 15mm FirestopRhinoboard on each side.

2 HOUR FIRE RATED WALL

RODENT PROOF CLASS B1

WALL PROPERTIES

2 hours fire rating.Sound Reduction Index Rw 50 dB.Wall thickness 118mm.Approximate mass 50kg/m2.

MATERIALS USED

1. 63,5mm UltraSTEEL™ stud.2. 63,5mm UltraSTEEL™ track.3. 12,5mm Taper-edge Firestop Rhinoboard.4. 15mm Taper-edge Firestop Rhinoboard.5. 25mm and 41mm Drywall Streaker screws.6. Rhinoboard Drywall jointing system.7. Floor and ceiling finishes (i.e. skirting and

cove/trim). To be specified separately.

APPLICATION DETAILS

1. Set 63,5mm UltraSTEEL™ studs spaced 600mm c/c into 63,5mm UltraSTEEL™ track at floor andceiling.

2. Apply a base layer of 12,5mm Taper-edge Firestop Rhinoboard vertically to each side using 25mm Drywall Streaker screws spaced at 220mm c/c.

3. Apply a face layer of 15mm Taper-edge Firestop Rhinoboard to both sides. Staggering all joints using 41mm Drywall Streaker screws spaced at 220mm c/c.

4. Tape and joint according to data sheet for Hand Jointing Application.

5. Refer to data sheet for Standard Clauses for Specifiers: Drywall Systems.

6. Acoustic performance requires sealing betweenUltraSTEEL™ track, floor, ceiling and any otherabutment joints.

C Roc 12/8/08 2:30 PM Page 13

Page 13: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 96

C Roc 12/8/08 2:30 PM Page 14

Page 14: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 97

Window reveal

Door jamb

External angle

9.5, 12.5, 15mm

L

L

L

L

L

T

L

GypWall Drylining

C Roc 12/8/08 2:30 PM Page 15

Page 15: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 98

1 Estimated construction time 7m2 per man hour(ready for finishing).

2 Allow 10 mm plus the board thickness from the face of the background to the face of the lining to determine lining dimension at door/window reveals and soffits (this allowance may need to be increased if background is badly out of line).

3 Install the plasterboard ceiling, erect any abutting partitions and fill any joints in the masonry

background before commencing dry lining to thewalls.

4 Make provision for sealing the dry lining cavity of specified walls (normally internal face of external walls). The recommended method is to apply a fillet of RhinoLite around the perimeter of the wall and

any surface penetrations and openings, together witha continuous band of Rhinolite at the base.

5 Install services, such as pipes and cables, before drylining.

6 Consider skirting fixing - mechanical or using Silicone Sealant (the provision of a continuous band of

Rhinolite at the base provides a ground for mechanicalfixing).

7 Seal any small gaps at base of skirting, with Silicone Sealant.

8 Consider the provision of a flexible seal between suspended timber floors and the masonry wall.

9 Form vertical cavity barriers, using a continuous line of dabs, where specified in long runs of lining.

10 Install Control Joints, where specified.

11 Allow the lining to bridge any structural columns - do not locate dabs on the column.

Simple run of dry Approxlining 2.4m high quantities

per 10m2

Rhinoboard9.5mm or 12.5mm 10m2

RhinoLite 20kgRhinoTape 12l.mRhinoGlide 10kg

All joints should be jointed as per data sheet for RhinoDrywall Hand Jointing Application.N.B. From Data Sheet.

F INISHING

QUANTIT IES

BACKGROUNDS

Ensure masonry wall is dry. If extensive moisture is

present, consider using dehumidifiers or appropriate

heating/ventilation.

Concrete and/or painted surfaces treat with Grippon,

same as data sheet for Rhinolite.

PLANNING THE JOB

GypWall Drylining cont.

C Roc 12/8/08 2:30 PM Page 16

Page 16: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 99

FLOOR LAYOUT

1. Set out as per plan, allowing openings on

bottom track only for door frames. Fix Drywall

UltraSTEEL™ track to floor and ceiling support

structure at 600mm centres.

Drywall and UltraSTEEL™stud partitions

4 m

3 m

330 mm

Room Room

3,5 m

Typical Floor Plan

3,5 m

Twist UltraSTEEL™ studinto position

UltraSTEEL™ Track

Cut off sectionto be 83mm

UltraSTEEL™ StuTwist

A

BC

Drywall Screw

DrywallStuds

90 Degree Corner Detail

Corner Bead(External Corner)

InternalCorner

DrywallScrew

F

Centre Line

DrywallUltraSTEEL™

Stud

T - Junction

D

T-JUNCTION DETAIL

5. T-Junction UltraSTEEL™ studs erected as per

detail allowing clearance between D and F for

Rhinoboard.

*Drywall training videos are available.

Note: See our “Installation guide to GypWall

Drywall Solutions”.

90˚ WALL CORNER

4. Corner studs erected as per detail allowing

clearance between A and B for Rhinoboard. C is

for the fixing of skirtings.

TRACK CORNERS

3. Corner track fixed as per detail.

STUD ASSEMBLY

2. UltraSTEEL™ studs are inserted into floor and

ceiling UltraSTEEL™ track with a twist motion.

Allow a 10mm clearance between top of stud and

track. Erect studs at 600mm centres.

Guide to Steel Framing

C Roc 12/8/08 2:30 PM Page 17

Page 17: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 100

Service Holes(drilled or punched)

UltraSTEEL™ Stud

UltraSTEEL™ Track

Service Installation Detail

6. SERVICE CONDUITSUltraSTEEL™ studs should only be secured at cor-

ners, door frames or door openings with 3,2mm

diameter pop rivets.

7. STEEL DOOR FRAMESSteel door frames are fixed by screwing

UltraSTEEL™ stud to fixing plates welded inside

throat of frame. Allow clearance either side of

stud for Rhinoboard as per detail 1.

Note: where required timber doorframes can also

be used.

8. ALUMINIUM DOOR FRAME(where applicable)Door openings are constructed as per detail. Extra

support in the form of timber will be required

when hanging solid core doors.

9. CHECK LISTCheck that UltraSTEEL™ tracks are fixed securely.

Check that appropriate UltraSTEEL™ studs are

secured.

Check that all UltraSTEEL™ studs are properly

spaced.

Check all walls are level and plumb.

Check all door frames and openings are properly

fixed, level and plumb.

Note: See our installation guide to GypWallDrywall Solutions.

Door Detail

UltraSTEEL™ Stud

Track flangedand fixed to Stud

IntermediateStud

Door Opening

UltraSTEEL™ Track

UltraSTEEL™ Track

DrywallDoor Jamb

Fixing Plate

UltraSTEEL™ Drywall Stud

Self TappingScrew

Detail 1

Drywall Screw into UltraSTEEL™ studand covered with PVC infill

Doorframe(with side gasket)

UltraSTEEL™ Stud

Gypsum Board

Guide to Steel Framing cont.

C Roc 12/8/08 2:30 PM Page 18

Page 18: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 101

1. Rhinoboard can be applied vertically or

horizontally.

2. Cut Rhinoboard to size by using a utility knife.

Score face side of board, snap and cut the back.

3. Allow a 10 mm clearance between bottom of

Rhinoboard and floor.

4. In the horizontal and vertical application of

Rhinoboard ensure that all joints are staggered

and do not occur in a straight line.

5. Ensure that joints do not occur parallel with the

side of door frames or openings but are placed

towards the centre of these frames and

openings.

6. In double layer application both layers are clad

vertically with all joints staggered.

7. Fix Rhinoboard using a Drywall screw-driver

and screws at 220 mm centres.

8. The screwhead should be driven slightly below

the face of the board but not deep enough to

break the paper.

9. Unless specifically required the Rhinoboard

should not be fixed to the floor or ceiling

UltraSTEEL™ tracks.

CHECKLIST

1. Check that the Rhinoboard is correctly fastened

to the UltraSTEEL™ studs.

2. Check that the screws are not proud.

3. Check that screws are at least 9 mm from edges

and at most 13mm.

4. Check that door frames etc. are still level and

plumb.

5. Check that Rhinoboard surfaces have not been

damaged and that all joints are correctly butted

and staggered.

NOTE: Cladding to be done after building is

weather sealed.

Min 300 mmJoint

Door Frames

GypWall Drywall Cladding Application

C Roc 12/8/08 2:30 PM Page 19

Page 19: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 102

1. Cutting

The mat should be cut cleanly using a sharp

knife and in the case of Rhinoflam, tin snips is also

required to cut the wire. First cut and remove the

wire then cut the fibre with a knife.

2. Storage

The rolls should be left in the pack until required

and should ideally be stored under cover. If

stored on site, rolls should be raised off the

ground and covered completely with waterproof

sheeting.

The polythene packaging provides protection

only against short-term and accidental exposure.

3. Fixing

The insulation should be cut to size and sus-

pended within the partition so that it makes contact

with the metal studs, the floor and ceiling chan-

nels.

The insulation should be continuously supported

within the wall using the methods shown

opposite.

Fixing Instructions of RhinoFlam/Insulmat

C Roc 12/8/08 2:30 PM Page 20

Page 20: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 103

1. Pictures, Calendars, etc.

Use either a ‘stick-on’ type of picture hanger or the

nail and hook type as per detail. Ensure that the

nail is driven downwards into the Rhinoboard at an

angle of approx. 200.

2. Mirrors, Ornaments, etc.

Use a molly bolt type of fastener, which is fitted

onto the Rhinoboard in any position.

3. Shelves

Fix through the Rhinoboard into the UltraSTEEL™

stud with self tapping screws, or into a cross mem-

ber between UltraSTEEL™ studs which should be

provided during erection of the framing, or use a

molly bolt type fastener.

4. Hand Basins, Cisterns, etc.

UltraSTEEL™ studs should be spaced more closely

(e.g. 300 mm). Run horizontal timber noggins of up

to 114 mm x 38 mm or double nested track chan-

nels between the vertical notched UltraSTEEL™

studs and secure with screws. Fix objects to noggins

and UltraSTEEL™ studs.

NB: Items subject to severe abuse or impactshould be supported by a steel frameworkwhich is bolted to the floor and UltraSTEEL™studs. See detail A.See data sheet on Shear and Pull-out Tests ofVarious Fixings to Drywall.

Methods of Fixings to GypWall Drywall

C Roc 12/8/08 2:30 PM Page 21

Page 21: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 104

Levels of GypWall Drywall Finish

1. SCOPE

This is a recommended specification that describesvarious levels of finish for drywall systems prior tothe application of the final decoration. Each level isintended to supply the required surface finish forthe application of the drywall and should be usedto provide the most cost-effective alternative.

2. TERMINOLOGY

The following definitions are used in this docu-ment.

Accessories: Metal or plastic corner beads, trim ormouldings used to protect or conceal corners,edges or abutments.

Critical Lighting: Strong side lighting from win-dows, surface mounted lights or downlighters.

Oil Based Plaster Primer: A paint formulated to sta-bilize and equalize the suction difference betweenRhinoboard surface paper and the RhinoGlide com-pound used to finish joints angles, screw heads andaccessories. To be used on drywall prior to decora-tion.

Skim coat: A thin coat of plaster over the entirewall surface to fill any imperfections in the jointwork, smooth the paper texture, and provide acompletely uniform finishing surface. A skim coatof RhinoLite can be used as an alternative tojointing.

Spotting: To cover screw heads with jointingcompound.

3. LEVEL OF FINISH

The following levels of finish are proposed as aguide for specific final decoration. Each level willbe illustrated with an example.

LEVEL 1

No jointing or finishing at all.

This level of finish may be useful in temporaryconstructions.

LEVEL 2

All joints shall have the Rhinotape embedded inRhinoGlide jointing compound. Surface shall befree of excess jointing compound but tool marksand ridges are acceptable.

Frequently used in plenum areas above ceilings andin areas that are generally concealed.

LEVEL 3

All joints, angles and accessories shall have one coatof RhinoGlide jointing compound applied. All screwheads to be spotted. Surface shall be free of excessjointing compound but tool marks and ridges areacceptable.

This finish is suitable where moisture resistantboard is used as a substrate for tiling and may beused in garages or warehouse storage where sur-face appearance is not of primary importance.

LEVEL 4

All joints, angles and accessories shall have two separate coats of RhinoGlide jointing compoundapplied. All screw heads to be spotted. All jointingcompound shall be smooth and free of tool marksand ridges. All areas receive a coat of oil basedPlaster Primer before finishing.

This level is suitable for areas which are to receiveheavy or medium textured paint finishes, or whereheavy grade wallcoverings are to be applied.Where lightweight vinyls are to be used all jointsetc should be carefully sanded to provide asmoother surface.

LEVEL 5

A 3mm skim coat of RhinoLite plaster/Cretestoneplaster shall be applied to the entire surface of thedrywall. The surface shall be completely smoothand free of any marks and surface blemishes. Theentire surface of the drywall shall receive a coat ofoil based plaster primer before final decoration.

This level should be used where gloss, semi-gloss orMatt non-textured paints are specified. Any drywallthat is subjected to critical lighting must be finishedto this level.

4. COMMENTS

Wall and ceiling areas abutting window mullions orskylights, long hallways, or atriums with large sur-face areas flooded with artificial or natural lightare a few examples of critical lighting. Critical light-ing (especially side-lighting) may reveal even minor surface imperfections. Light striking the surfaceobliquely, at a very slight angle, greatly exagger-ates surface irregularities. If critical lighting can notbe avoided, the effects can be minimized by skimcoating the entire wall or by decorating the surfacewith medium or heavy textures (paint or vinyls).The use of drapes and/or blinds can also be used tosoften shadows. It is also important to rememberthat during the construction phase of a buildingthe lighting is often not fully functional and theappearance of the drywall could vary considerablyonce this is switched on.

In general smooth non-textured finishes highlightsurface defects and textures help to hide minorimperfections.

NOTE: All Drywall partition systems should be100% finished by the Drywall installer. It shouldnot be left up to contractor applying the final dec-oration to rectify and surface blemishes or marks.All joints should be completely finished.

C Roc 12/8/08 2:30 PM Page 22

Page 22: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 105

GypWall Drywall - Shear and pull-out tests

C Roc 12/8/08 2:30 PM Page 23

Page 23: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 106

C Roc 12/8/08 2:30 PM Page 24

Page 24: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 107

RhinoFlam/Insulmatt

Thickness (mm) 50

Lengths (m) 2,7

Density (kg/m3) 80

Standard width (mm) 600

DESCRIPTION

Resin bonded mineral fibre blanket stitched withgalvanised wire.

APPLICATIONAcoustic and fire infill for drywall systems.

Operating TemperatureCan be used at continuous operating temperaturesof up to 850oC.

Fire PerformanceNon-combustible - Conforms to SABS 0177 Part V.Class 1 Fire Index - Conforms to SABS 0177 Part III.

PermanenceRot-proof, odourless, does not sustain vermin andwill not encourage the growth of fungi, mould orbacteria. Will not settle under vibration and isdimensionally stable under varying conditions oftemperature and humidity.

Acoustic PerformanceWill provide effective acoustical insulation wherethere is a need to reduce noise levels in drywall orto absorb sound in other applications. Actual performance varies with thickness.

Chloride ContentContains inherently low levels of water-leachablechlorides, typically 2ppm (max 5ppm) and thus willneither cause nor promote corrosion.

STANDARD DIMENSIONS

C Roc 12/8/08 2:30 PM Page 25

Page 25: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 108

NB: Do not proceed with jointing if anyfaults remain from the previous stage oferection (Refer to data sheet for RhinoDrywall Wallboard Cladding Application).

1. Check board surface. Any repairs and/or joints wider than 5mm should be prefilled with RhinoGlide. Pull off any loose paper and retape where core is exposed.

2. Apply self-adhesive RhinoTape over the centre of the joint.

3. Apply 1st layer of RhinoGlide using a 125 mm taping knife (putty knife). Clean off edges. Allow to set.

4. Apply 2nd layer of RhinoGlide using a300 mm trowel. Clean off edges and allow to set.

5. A butt joint can be taped in the normal way using RhinoGlide. (As No.2 & 3). When set, apply the 2nd layer of RhinoGlide to each side of the tape with a 300 mm trowel. Clean off the outside edges. When set, apply the 3rd layer over the centre of the joint and allow to dry.

6. Apply RhinoTape to internal corner ensuring that the tape is evenly spaced either side. Apply a coat of RhinoGlide to one side using a 125 mm taping knife. Allow one side to set before beginning the other side.

7. To fit corner bead onto the external corner, apply a layer of RhinoGlide to each side of the corner bead. Press the corner bead firmly into postion. Using a 125 mm taping knife apply bead. When set apply a second layer using a 250 mm trowel. Clean off the outside edges

8. Screws can be flushed using a 125 mm taping knife. Apply a small amount of RhinoGlide over the screw head in one direction and wipe in a right angle direction. Apply 2nd coat in the same way.Note: Allow to set between each coat.

9. A control joint is fitted between brickwork and drywall where they are in the same line or as an expansion joint on a long continuous GypWall Drywall, e.g. walls longer than 10 m should have a control joint every 5 m. Note that a full height door frame acts as a control joint. Allow 1 cm gap between Rhinoboard and any brickwork abutment.

10. When all final coats are set, sand lightly to a smooth level finish using a fine grit sand paper (100 grit). Do not oversand.

NB (1): In points 2-9 it must be rememberedto clean off all excess RhinoGlide and feath-er out.

NB (2): Using a damp cloth remove all powderfrom the joint and surface of board prior to dec-oration.

DECORATION

A good quality plaster primer must be used onthe entire surface.

CHECK LIST

1. Make sure that the RhinoGlide is allowed to set thoroughly between coats.

2. Check that the screws and metal trims are completely covered with compound.

3. Check that all finished joints are smooth and dry for decoration.

4. Check surface generally for smoothness and possible unfinished work.

Keying slots

Drywall Cornerbead

85-87˚

Rhinoglide1st Coat

50 mm wideRhinoTape

Drywall Screwsat 220 mm spacing

Rhinoglide final coat

Taper edgeRhinoboard

Typical Joint

Rhinoboard Hand Jointing Application

C Roc 12/8/08 2:30 PM Page 27

Page 26: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 109

GLASS FIBRE WALL REPAIR TAPE

• Self-adhesive, bonds without pasting or stapling.• No shrinking, stretching or bubbling.• Ready for plastering as soon as it’s applied.

DRYWALL JOINTING

• Quick and easy joint taping.• Strong reinforcement.• Eliminates pre-plastering.• Does not blister or bubble.

Refer to Ceilings and Hand Jointing Applications

guidelines.

RhinoTape

C Roc 12/8/08 2:30 PM Page 28

Page 27: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 110

CALCULATION OF QUANTITIES

1. UltraSTEEL™ Track:Length of wall x 2 = Total length of track.Total length of track divided by 3 = No. of lengths of track.Standard width: 51 or 63,5 mm. Length: 3 000 mm

2. UltraSTEEL™ Studs:Length of wall in metres divided by 0,6 =Number of studs. Add 2 extra studs for each corner and 1 extra stud for each T-junction, wall starter and doorframe.Length of stud = ceiling height.Standard lengths = 2 100 - 3 600 (300 mm increments).Standard widths = 51 or 63,5 mm

3. Board:12,5mm taper-edge (specify Standard or Firestop).For single cladding.Length of wall divided by 1,2 - Bring to near-est whole number x 2 = Number of boards.Length of board = ceiling height.Standard length = 2 700 - 3 600 (300 mm increments).

Note: 6,4 mm and 9,5 mm Rhinoboard is not suit-able for Drywall Cladding.

4. Fixing and Finishing:For every 120 m2 of Board you will require:a) Screws: 2 000 x 25 mmb) RhinoTape: 3 x 45 m rollsc) RhinoGlide: 3 x 20 kg bags.

5. Skirting screws (45 mm long) = number of studs x 2.

6. Gypseal: (two coats where moisture resistant boardis utilised) Can be used on other Boards.Coverage = 7 m2 per litre per coat.

N.B.: Above calculation will provide approximatequantities and does not allow for wastage. (Normally 10% is allowed for wastage).

Quantity Estimation for Single Clad GypWall Drywall

C Roc 12/8/08 2:30 PM Page 29

Page 28: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 111

20

76

20

76

20

76

20

76

20

76

20

89

20

89

20

89

20

89

20

89

20

114

Accessories Description

114 mmALUMINIUM

DF Legged

89 mmALUMINIUM

DF Side gasket

Glazing(no bead)

Headchannel

DF Legged

Available for63,5mmStuds.

Wall channel

Available for63,5mmStuds.

76 mmALUMINIUM

DF Side gasket

Glazing

Headchannel

DF Legged

Wall channel

ACCESSORIES

Head channel, aluminium

door frames, glazing

sections, etc. available from

Gyproc, Donn or

Lightweight Building

Solutions.

63.5 mmStud & Track

51 mmStud & Track

GypWall Aluminium Accessories

}}

C Roc 12/8/08 2:30 PM Page 30

Page 29: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 112

ID D

RA

WIN

GS

UN

IT O

FM

EA

SU

RE

DE

SC

RIP

TIO

NM

AT

ER

IAL

CO

DE

CO

LO

UR

LE

NG

TH

Clip

on

glaz

ing

bead

Faire

ndse

ctio

n

90°

ext

corn

er

Hea

d/w

all

chan

nel

Sin

gle

glaz

ing

no le

gs

Dou

ble

glaz

ing

no le

gs

Sin

gle

glaz

ing

with

legs

Fem

ale

splic

e

Legg

ed d

oor

fram

e

ea ea ea ea ea ea ea ea ea

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

Nat

ural

anod

ised

5359

5360

5361

5362

5363

5364

5365

5366

5367

5368

5369

5702

5370

5371

5372

5376

5377

3660

2770

3000

2700

3000

3600

2700

3000

3600

3660

3660

3660

2700

3000

3600

5180

6400

Nouveau Aluminium Accessories

C Roc 12/8/08 2:30 PM Page 31

Page 30: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 113

DESCRIPTION

12,5mm Moisture Resistant (MR) Rhinoboards are

lined on both sides with a dinstinctive green paper to

ease identification. The core of the board is treated

with a silicone additive.

Size

MR Rhinoboard is available in the following sizes:-

12,5mm x 1200mm wide x 2400, 2700, 3000 long.

Weight

12,5mm MR Rhinoboard weighs 10-11kg/m2.

Applications

MR Rhinoboard is a silicone impregnated gypsum

board that is suitable for use in showers, bathrooms,

kitchens and protected external applications.

MR Rhinoboard is used in areas where ceramic wall

tiling is required.

MR Rhinoboard is not suitable for protection against

continuous dampness or as a base for cementitious

rendering.

MR Rhinoboards comply with the SABS 266 : 1982

Specifications for plasterboard.

PERFORMANCE

Effects of temperature

The boards are not suitable for use in temperatures

above 49oC, but can be subjected to freezing

temperatures without risk of damage.

When tests in accordance with SABS 266 : 1982, the

MR Rhinoboard absorbed less than 5% of water by

weight in the total immersion test.

Thermal properties

K = 0.25 W/m oC

R = 0.05m2 K/W

MR Rhinoboard will give similar performance to a

standard board when tested for fire rating or sound

insulation.

Moisture Resistant Rhinoboard

C Roc 12/8/08 2:30 PM Page 32

Page 31: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 114

The rigid metal is now an integral feature of theUltraSTEEL™ drywall systems. With this new patentedUltraSTEEL™ process it is clear that Gyproc and DONNcommit themselves to cost effective solutions, innova-tions and quality is setting new standards for thefuture in the use of drywall systems in the buildingindustry.

IMPROVEMENT THROUGH INNOVATION

The distinctive surface indentations are produced bythe patented UltraSTEEL™ process. This increases thedepth of the metal and, with work hardening, givesimproved sectional qualities. The result is that lightergauge steel gains significant strength characteristicssuperior to the present products on offer in the mar-ket.

THE MAIN BENEFITS ARE:

• More cost effective than present conventional drywall systems.

• Durable, strong and adaptable metal stud.

• Surface indentations in metal make screw location easier and reduce slip.

• Surface indentations also gives better handling and grip.

• Studs and channels are easier to cut.

Tested for strength

Easier fixing

Easier to cut

Improved handling

UltraSTEEL™ Drywalling

C Roc 12/8/08 2:30 PM Page 33

Page 32: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 115

UltraSTEEL™ CONVENTIONAL

FIRE TEST CARRIED OUT BY THE SABS PROVES

UltraSTEEL™ SUPERIOR PERFORMANCE

IMPROVEMENT THROUGH PRODUCTS

The UltraSTEEL™ metal studs and channels werefirst introduced by British Gypsum in March 1993.From the very start it was clear that the commit-ment to innovation and quality has produced yetanother success story.

In fact, so enthusiastic was the response world widethat as the market leader are now utilising thetechnology in its manufacturing process of drywallsystems. Exhaustive tests by the South AfricanBureau of Standards (SABS) has proven that drywallSystems surpass all national building regulationsand requirements which means a partition design-er can specify the correct UltraSTEEL™ drywallsystem with total confidence in its superiorcapabilities.

SETTING NEW STANDARDS INSOUTH AFRICA

Rigidised metal is now an integral feature of the

UltraSTEEL™ drywall systems.

Further peace of mind comes from knowing that

specifying UltraSTEEL™ drywall systems will ensure

that building standards and regulations are

surpassed.

UltraSTEEL™ Drywalling

C Roc 12/8/08 2:30 PM Page 34

Page 33: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 116

UltraSTEEL™ drywalling is a non-load bearing interi-

or walling system consisting of single or multiple lay-

ers of Rhinoboard which are screwed onto either side

of the patented UltraSTEEL™ cold rolled galvanised

steel sections. The tapered edged Rhinoboard is then

flush jointed to give a monolithic surface ready to

receive decoration.

All GypWall drywalling systems components are man-ufactured under the SABS ISO 9002 quality manage-ment system.

As the market leader, Gyproc and DONN is at theforefront of developing superior, cost effective solutions for further applications. You only have totake a closer look at our range of high performancesystems to discover just how true this is.

Note: Under a Patent know-how license grantedfrom Hadley Industries Ltd, United Kingdom, drywallstud and track products are produced using theirpatented UltraSTEEL™ process.

UltraSTEEL™ Drywalling

C Roc 12/8/08 2:30 PM Page 35

Page 34: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 117

Installation Details

C Roc 12/8/08 2:30 PM Page 36

Page 35: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 118

C Roc 12/8/08 2:30 PM Page 37

Page 36: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 119

Length: 2667 mmWidth: 25 x 25 mm

Sold per unit.

Right/Left Hand813 x 2032 with or without fanlight

5 l Tins

Length: 45 m/roll or 90 m/rollWidth: 48 mm

Sold per box of 1000

Widths

Lengths 51mm 63,5mm

2100 * *2400 * *2600 * *2700 * *3000 * *3300 * *3600 * *4200 * *

Widths

Lengths 51mm 63,5mm

3000 * *

10 and 20 kg bags

3m lengths

CORNER BEADS

BITS

DOORFRAMES

GYPSEAL

RHINOTAPE

SCREWS

ULTRASTEEL STUDS

DRYWALL ULTR-STEEL TRACKS

RHINOGLIDE

EXPANSION JOINT

Galvanised corner beads are used as a pro-tection for external corners. They are bed-ded and finished with RhinoLite/RhinoGlide.

No. 2 Philips Bits for use with electric screwdrivers.

Steel doorframes with mouth size of 90mmand lugs for fixing to studs and floor.

Used as a sealer on Rhinoboard in bathrooms and kitchens where tiles are to be used.

A self adhesive RhinoTape used forreinforcing jointing. Does not requireRhinoGlide underneath the tape.

25 mm Streaker - for fixing 12,5 mmRhinoboard to 0,5 mm UltraSTEEL™ Studs.32 mm Grabber screws to timber.41 mm Streaker - for fixing a double layer of12,5 mm Rhinoboard to steel studs.45 mm Skirting Screw - for fixing timberskirting to steel studs.

Galvanised UltraSTEEL™ studs used as the vertical members in the framing for DrywallSystems.

Galvanised UltraSTEEL™ tracks used as afloor and ceiling channel into which theGypWall UltraSTEEL™ studs clip.

RhinoGlide is a quick setting drywall jointfiller which can be sanded to a smooth finish. It is used with taper-edge Rhinoboardand RhinoTape.

A pre-formed galvanised or PVC joint usedwhere expansion joints are required in GypWallapplications or ceiling. It will accommodate upto 7mm expansion or contraction.

DESCRIPTION AND USES PACKAGING AND SIZESPRODUCT NAME

GypWall Products & Accessories

C Roc 12/8/08 2:30 PM Page 38

Page 37: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008

GypWall LC Crusader Partition System

Designed primarily for use with vinyl clad or fabriccovered Rhinoboard panels, and produces a linejoint between panels. It provides a low cost, highquality, partition system that is competitive withother conventional wall systems, even on a ”first-cost” basis. In addition, the elimination of taping,bedding and painting, reduces construction timeand site labour. The system allows for non-destruc-tive cavity access and complete movability with vir-tually 100% re-use of material.

Another factor to be considered is reducedmaintenance.

The vinyl clad surface of Partition resists scuffingand fading and requires only an occasional washdown to retain its original beauty.

The Partition System is manufactured in compli-ance with the requirements of SABS ISO 9002quality systems.

Advantages of the System

• Low initial cost• Ease of installation• Low maintenance• Ease of relocation• Re-use of materials• 100% accessible• Tax benefits• Service cavity

Executive Office / Fabric Covered

“High Tech Studio” / Vinyl Covered

General Office / Vinyl Covered

120

C Roc 12/8/08 2:30 PM Page 39

Page 38: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008

GypWall LC Crusader Partition System

PARTITION SYSTEM

Dimensions and MassAvailable in heights up to 3600mm and in modules600mm, 750mm and 1200mm wide. At a partitionheight of 2,7 metre, the mass per linear metre isapproximately 73kg. (For heights exceeding3600mm consult your nearest Gyproc, LBS or DONNoffice.

FinishingAll exposed trims for angles, doorframes, glazingand skirting are of aluminium finish in eitheranodised colour natural, black, mill or painted fin-ish. The panels used are 12,5mm thick Rhinoboardand covered with DonnClad paper backed vinyls orDONN fabric.

AssemblyThe installation of the Partition starts with the fix-ing of ceiling, wall and floor tracks by means ofshots, screws or self adhesive tape. Vertical studsare then clipped into position using the extensionclips. The vertical centres of these studs vary asrequired up to a max of 750mm and are positionedby means of horizontal spacer channels. For mod-ules in excess of the 750mm an additional stud shallbe installed at the midpoint of the module to pro-vide additional rigidity. The aluminium sections areclipped onto the studs in both horizontal and verti-cal directions.

DCR1 Extension Clip to Track and Stud

121

C Roc 12/8/08 2:30 PM Page 40

Page 39: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 122

LC Crusader Details

DCR1 EXTENSION CLIPPED INTO LCCRUSADER STUD AND TRACK

HEAD DETAIL

C Roc 12/8/08 2:30 PM Page 41

Page 40: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 123

Crusader Details

ABUTMENT DETAIL

C Roc 12/8/08 2:30 PM Page 42

Page 41: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 124

Steel Faced Crusader Details

90° CORNER DETAIL

DOOR DETAIL

C Roc 12/8/08 2:30 PM Page 43

Page 42: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 125

BASE DETAIL

TERMINATION DETAIL

C Roc 12/8/08 2:30 PM Page 44

Page 43: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 126

Partition Component Details

Steel Faced Crusader Details

C Roc 12/8/08 2:30 PM Page 45

Page 44: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 127

Crusader Partition Components

C Roc 12/8/08 2:30 PM Page 46

Page 45: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008 128

SPECIFICATION

Crusader

Supply and install Crusader Demountable partition asmanufactured by DONN Products (Pty) Ltd,Johannesburg.

Tel: +27 11 345 5300 P.O. Box 4594, Germiston South, 1411.

The vertical studs shall be Crusader studs and the pan-els used shall be 12,5mm thick Rhinoboard of a mod-ule width of 1211 or 911mm and shall be coveredwith vinyl or fabric to an approved type, pattern andcolour. The boards are square edged and shall bemanufactured and supplied by DONN Products.Crusader boards (panels) are held in place by meansof a batten which is clipped into the Crusader stud.

Steel Faced Crusader

Supply and install DONN (Steel Faced Crusader)(Marine Crusader) moveable partition systems asmanufactured by DONN Products (Pty) Ltd.Germiston.

Panels used shall be of chromodek polyester paintedsteel or stainless steel, in vivid white or sandstonebeige or galvanised steel covered with fabric backedvinyl’s from the vinyl range. The panels are to bebacked with 12,5mm Rhinoboard and shall be ofmodule size 600mm (750mm to maximum of 900mm).Steel faced panels are fitted into the Crusader stud.

SYSTEMS MODULE PANEL WIDTH SPACER LENGTH

CRUSADER 1211mm 1200mm 1211mm

STEEL FACED 750mm 750mm 750mm

STEEL FACED 600mm 600mm 600mm

Panel and Spacer Selection Chart

C Roc 12/8/08 2:30 PM Page 47

Page 46: Standard clauses for GypWall Systemsmedia.autospec.com/.../partitioning_rocscreen.pdf · 2011. 8. 5. · sides with 12,5mm Rhinoboard fixed with 25mm ... supported off the floor with

GypWallISSUE DATE: NOVEMBER 2008

Technical Details

TECHNICAL DESCRIPTIONThe partition system consists of vinyl faced panels

clip fixed to steel vertical studs.

The panels are 12,5mm thick Rhinoboard with

specially prepared bevelled edges clad in vinyl or

fabric coverings. The two Rhinoboard panels are

retained in position by metal spring clips and held

apart by the steel framework forming a 50mm

cavity in the partition. The studs and other sec-

tions are manufactured from galvanised steel with

the studs having 30mm x 50mm holes punched

out at nominal 100mm centres to accommodate

electrical and other services.

SPECIFICATIONSupply and install demountable partition as manu-

factured by DONN Products (Pty) Ltd,

Johannesburg.

The vertical studs shall be studs and panels used

shall be 12,5mm thick Rhinoboard of a module

width of 600mm, (750mm, or 1200mm) and shall

be covered with DonnClad vinyl (fabric) to an

approved type, pattern and colour. The boards

shall be manufactured and supplied by DONN

Products with the special edge detail.

The spring clips are pressed into the special edges

of the Rhinoboard at 450mm centres and retain

the board in place by locking around the edges of

the steel stud.

129

C Roc 12/8/08 2:30 PM Page 49