STANDARD OPERATING PROCEDURE KIDDE AEGIS CONVENTIONAL Design by @putra.poutz | Copyright ©2018. All Right Reserved. www.GMPRO.id AEGIS Fire Systems Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. Kondisi ini dak akan mengakibatkan HORN/SIRINE berbunyi. COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE AC ON PRE-RELEASE RELEASE POST-RELEASE ALM1 ALM2 WF/ALM3 MAN REL ABORT SUP1 SUP2 ALM1 TBL ALM2 TBL WF/ALM3 TBL ARC1 TBL ARC2 TBL MAN REL TBL ABORT TBL SUP1 TBL SUP2 TBL SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL NAC1 TBL NAC2 TBL NAC3 TBL SIGNAL SILENCED SYSTEM RESET OUTPUT DISABLE Fire Systems Indicating LAMP akan menunjukkan penyebab trouble Saat terjadi FAULT / Trouble... teett...tett.. Saat SUPERVISORY AKTIF... AEGIS Fire Systems teett...tett.. COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems Tekan ”SYSTEM RESET” Jika PIN Pressure Switch sudah diposisi “SET” RESET Kondisi ini dak akan mengakibatkan HORN/SIRINE berbunyi. Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. LED indicator “SPV-1” menyala, menandakan posisi PIN Pressure Switch belum kembali pada posisi “SET” SPV-1 bila buzzer control panel BUNYI TERUS-MENERUS... Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems GAS DISCHARGED EVACUATION AREA IMMEDIATELY Tekan ”SIGNAL SILENCE” untuk memakan suara HORN/SIRINE. teett...tett.. KRiiiiiiiNgGG... 2 JENIS INDIKASI FIRE ALARM... Terjadi indikasi alarm dari detector, HANYA PADA “SALAH SATU” ZONE. Terjadi indikasi alarm dari detector, SERENTAK PADA “KEDUA” ZONE. Zone 1 Zone 2 “ALARM-1” Zone 1 Zone 2 “ALARM-2” SAAT MASUK KONDISI ”ALARM-2”... COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL SYSTEM RESET OUTPUT DISABLE Fire Systems Tekan ”SYSTEM RESET” Jika kondisi dianggap sudah kembali normal. RESET COUNTDOWN TIMER (SECS) Setelah masuk kondisi 'ALARM-2", 3 digit Countdown Timer akan hitung mundur mulai dari 30 dek. Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. Tekan & Tahan “ABORT SWITCH" Jika diperlukan untuk menghenkan counter hitungan mundur dan akan berhen pada dek ke 10. PUSH/ HOLD SUPPRESSION SYSTEM ABORT AEGIS Fire Systems mode SUPERVISORY Tekan ”OUTPUT DISABLE” untuk mengakan. COUNTDOWN TIMER (SECS) ACKNOWLEDGE (HOLD FOR LAMP TEST) SIGNAL SILENCE AC ON PRE-RELEASE RELEASE POST-RELEASE ALM1 ALM2 WF/ALM3 MAN REL ABORT SUP1 SUP2 ALM1 TBL ALM2 TBL WF/ALM3 TBL ARC1 TBL ARC2 TBL MAN REL TBL ABORT TBL SUP1 TBL SUP2 TBL SYSTEM ALM SYSTEM TBL SYSTEM SUP PSU TBL GROUND TBL NAC1 TBL NAC2 TBL NAC3 TBL SIGNAL SILENCED SYSTEM RESET OUTPUT DISABLE Fire Systems Pada kondisi ini system dak dapat melakukan release gas secara mode otomas/ secara electrical. Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. OUTPUT DISABLE... SAAT TERJADI FAULT/TROUBLE 1. Tekan tombol "ACKNOWLEDGE" untuk menghilangkan bunyi buzzer. 2. Indicating Lamp akan menunjukkan penyebab trouble. 3. Kondisi ini tidak akan mengakibatkan Horn/Sirine berbunyi. SAAT SUPERVISORY AKTIF 1. Tekan tombol "ACKNOWLEDGE" untuk menghilangkan bunyi buzzer. 2. Kondisi ini tidak akan mengakibatkan Horn/Sirine berbunyi. 3. LED indicator “SPV-1” menyala. Menandakan posisi PIN Pressure Switch belum kembali pada posisi "SET". 4. Tekan tombol "SYSTEM RESET", jika Pressure Switch sudah diposisi "SET". BILA BUZZER CONTROL PANEL BUNYI TERUS MENERUS 1. Tekan tombol “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. 2. Tekan tombol “SIGNAL SILENCE” untuk mematikan suara Horn/Sirine. 2 JENIS INDIKASI FIRE ALARM ALARM-1 Terjadi indikasi alarm dari detector, hanya pada salah satu zone. ALARM-2 Terjadi indikasi alarm dari detector, serentak pada kedua zone. SAAT MASUK KONDISI ALARM-2 1. Setelah masuk kondisi Alarm-2, 3 digit countdown timer akan hitung mundur dari 30 detik. Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. 2. Tekan & Tahan tombol “ABORT SWITCH", jika diperlukan. Untuk menghentikan counter hitungan mundur dan akan berhenti pada detik ke 10. 3. Tekan tombol ”SYSTEM RESET” Jika kondisi dianggap sudah kembali normal. OUTPUT DISABLE 1. Fungsinya adalah untuk memutuskan koneksi dari Panel Kontrol ke Actuator/Solenoid, Horn dan system menjadi kondisi Supervisory. 2. Tekan tombol “OUTPUT DISABLE” untuk mengaktifkan. 3. Pada kondisi ini berarti system tidak dapat melakukan release gas secara otomatis atau secara kelistrikan. 4. Tekan tombol “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer. STANDARD OPERATING PROCEDURE CONVENTIONAL SYSTEM FM-200 PANEL CONTROL STANDARD OPERATING PROCEDURE CONVENTIONAL SYSTEM FM-200 PANEL CONTROL
Transcript

STANDARD OPERATING PROCEDUREKIDDE AEGIS CONVENTIONAL

Design by @putra.poutz | Copyright ©2018. All Right Reserved.

www.GMPRO.id

AEGIS

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

AC ON PRE-RELEASE

RELEASE

POST-RELEASE

ALM1

ALM2

WF/ALM3

MAN REL

ABORT

SUP1

SUP2

ALM1 TBL

ALM2 TBL

WF/ALM3 TBL

ARC1 TBL

ARC2 TBL

MAN REL TBL

ABORT TBL

SUP1 TBL

SUP2 TBL

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL

NAC1 TBL

NAC2 TBL

NAC3 TBL

SIGNALSILENCED

SYSTEMRESET

OUTPUTDISABLE

Fire Systems

Tekan “ACKNOWLEDGE”untuk menghilangkan bunyi buzzer.

Kondisi ini tidak akan mengakibatkanHORN/SIRINE berbunyi.

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire SystemsCOUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

AC ON PRE-RELEASE

RELEASE

POST-RELEASE

ALM1

ALM2

WF/ALM3

MAN REL

ABORT

SUP1

SUP2

ALM1 TBL

ALM2 TBL

WF/ALM3 TBL

ARC1 TBL

ARC2 TBL

MAN REL TBL

ABORT TBL

SUP1 TBL

SUP2 TBL

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL

NAC1 TBL

NAC2 TBL

NAC3 TBL

SIGNALSILENCED

SYSTEMRESET

OUTPUTDISABLE

Fire Systems

Indicating LAMP akan menunjukkan penyebab trouble

Saat terjadi FAULT / Trouble...

teett...tett..

Saat SUPERVISORY AKTIF...

AEGIS

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

AC ON PRE-RELEASE

RELEASE

POST-RELEASE

ALM1

ALM2

WF/ALM3

MAN REL

ABORT

SUP1

SUP2

ALM1 TBL

ALM2 TBL

WF/ALM3 TBL

ARC1 TBL

ARC2 TBL

MAN REL TBL

ABORT TBL

SUP1 TBL

SUP2 TBL

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL

NAC1 TBL

NAC2 TBL

NAC3 TBL

SIGNALSILENCED

SYSTEMRESET

OUTPUTDISABLE

Fire Systems

teett...tett..

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire Systems

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire Systems

Tekan ”SYSTEM RESET”Jika PIN Pressure Switch sudah diposisi “SET”

RESET

Kondisi initidak akan

mengakibatkanHORN/SIRINE

berbunyi.

Tekan “ACKNOWLEDGE”untuk menghilangkan bunyi buzzer.

LED indicator “SPV-1” menyala,menandakan posisi PIN Pressure Switch

belum kembali pada posisi “SET”

SPV-1

bila buzzer control panel BUNYI TERUS-MENERUS...

Tekan “ACKNOWLEDGE”untuk menghilangkan bunyi buzzer.

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire Systems

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire Systems

GASDISCHARGED

EVACUATIONAREA

IMMEDIATELY

Tekan ”SIGNAL SILENCE”untuk mematikan suara HORN/SIRINE.

teett...tett..

KRiiiiiiiNgGG...

2 JENIS INDIKASI FIRE ALARM...

Terjadi indikasi alarm dari detector,HANYA PADA “SALAH SATU” ZONE.

Terjadi indikasi alarm dari detector,SERENTAK PADA “KEDUA” ZONE.

Zone 1 Zone 2

“ALARM-1”

Zone 1 Zone 2

“ALARM-2”

SAAT MASUK KONDISI ”ALARM-2”...

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL SYSTEMRESET

OUTPUTDISABLE

Fire Systems

Tekan ”SYSTEM RESET”Jika kondisi

dianggap sudahkembali normal.

RESET

COUNTDOWN TIMER (SECS)

Setelah masuk kondisi 'ALARM-2",3 digit Countdown Timerakan hitung mundur mulai dari 30 detik.

Tekan “ACKNOWLEDGE”untuk menghilangkan bunyi buzzer.

Tekan & Tahan “ABORT SWITCH"Jika diperlukan untuk menghentikan counterhitungan mundur dan akan berhenti padadetik ke 10.

PUSH/HOLD

SUPPRESSION SYSTEM ABORT

AEGIS

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

AC ON PRE-RELEASE

RELEASE

POST-RELEASE

ALM1

ALM2

WF/ALM3

MAN REL

ABORT

SUP1

SUP2

ALM1 TBL

ALM2 TBL

WF/ALM3 TBL

ARC1 TBL

ARC2 TBL

MAN REL TBL

ABORT TBL

SUP1 TBL

SUP2 TBL

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL

NAC1 TBL

NAC2 TBL

NAC3 TBL

SIGNALSILENCED

SYSTEMRESET

OUTPUTDISABLE

Fire Systems

mode SUPERVISORY

Tekan ”OUTPUT DISABLE”untuk mengaktifkan.

COUNTDOWN TIMER (SECS)

ACKNOWLEDGE(HOLD FORLAMP TEST)

SIGNALSILENCE

AC ON PRE-RELEASE

RELEASE

POST-RELEASE

ALM1

ALM2

WF/ALM3

MAN REL

ABORT

SUP1

SUP2

ALM1 TBL

ALM2 TBL

WF/ALM3 TBL

ARC1 TBL

ARC2 TBL

MAN REL TBL

ABORT TBL

SUP1 TBL

SUP2 TBL

SYSTEM ALM

SYSTEM TBL

SYSTEM SUP

PSU TBL

GROUND TBL

NAC1 TBL

NAC2 TBL

NAC3 TBL

SIGNALSILENCED

SYSTEMRESET

OUTPUTDISABLE

Fire Systems Pada kondisi inisystem tidak dapat

melakukan release gassecara mode otomatis/

secara electrical.

Tekan “ACKNOWLEDGE”untuk menghilangkanbunyi buzzer.

OUTPUT DISABLE...

SAAT TERJADI FAULT/TROUBLE1. Tekan tombol "ACKNOWLEDGE" untuk menghilangkan bunyi buzzer.2. Indicating Lamp akan menunjukkan penyebab trouble.3. Kondisi ini tidak akan mengakibatkan Horn/Sirine berbunyi.

SAAT SUPERVISORY AKTIF1. Tekan tombol "ACKNOWLEDGE" untuk menghilangkan bunyi buzzer.2. Kondisi ini tidak akan mengakibatkan Horn/Sirine berbunyi.3. LED indicator “SPV-1” menyala. Menandakan posisi PIN Pressure Switch belum kembali pada posisi "SET".4. Tekan tombol "SYSTEM RESET", jika Pressure Switch sudah diposisi "SET".

BILA BUZZER CONTROL PANEL BUNYI TERUS MENERUS1. Tekan tombol “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer.2. Tekan tombol “SIGNAL SILENCE” untuk mematikan suara Horn/Sirine.

2 JENIS INDIKASI FIRE ALARMALARM-1 Terjadi indikasi alarm dari detector, hanya pada salah satu zone.ALARM-2 Terjadi indikasi alarm dari detector, serentak pada kedua zone.

SAAT MASUK KONDISI ALARM-21. Setelah masuk kondisi Alarm-2, 3 digit countdown timer akan hitung mundur dari 30 detik. Tekan “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer.2. Tekan & Tahan tombol “ABORT SWITCH", jika diperlukan. Untuk menghentikan counter hitungan mundur dan akan berhenti pada detik ke 10.3. Tekan tombol ”SYSTEM RESET” Jika kondisi dianggap sudah kembali normal.

OUTPUT DISABLE1. Fungsinya adalah untuk memutuskan koneksi dari Panel Kontrol ke Actuator/Solenoid, Horn dan system menjadi kondisi Supervisory.2. Tekan tombol “OUTPUT DISABLE” untuk mengaktifkan.3. Pada kondisi ini berarti system tidak dapat melakukan release gas secara otomatis atau secara kelistrikan.4. Tekan tombol “ACKNOWLEDGE” untuk menghilangkan bunyi buzzer.

STANDARD OPERATING PROCEDURE

CONVENTIONAL SYSTEM

FM-200 PANEL CONTROL

STANDARD OPERATING PROCEDURE

CONVENTIONAL SYSTEMFM-200 PANEL CONTROL