+ All Categories
Home > Documents > Steel Space Frames

Steel Space Frames

Date post: 28-Sep-2015
Category:
Upload: aman
View: 232 times
Download: 7 times
Share this document with a friend
Description:
Seismic Behaviour of Spatial Steel Space Frames
Popular Tags:
40
Journal of Earthquake Engineering, Vol. 8, No. 3 (2004) 457–496 c Imperial College Press SEISMIC BEHAVIOUR OF PERIMETER AND SPATIAL STEEL FRAMES ELENA MELE, LUIGI DI SARNO and ANTONELLO DE LUCA Department of Structural Analysis and Design, University of Naples Federico II, P.le V.Tecchio, 80, 80125 Naples, Italy Received 6 May 2002 Revised 26 August 2002 Accepted 11 June 2003 The present study deals with the seismic performance of partial perimeter and spatial moment resisting frames (MRFs) for low-to-medium rise buildings. It seeks to establish perimeter configuration systems and hence the lack of redundancy can detrimentally affect the seismic response of framed buildings. The paper tackles this key issue by com- paring the performance of a set of perimeter and spatial MRFs, which were “consistently designed”. The starting point is the set of low- (three-storey) and medium-rise (nine- storey) perimeter frames designed within the SAC Steel Project for the Los Angeles, Seattle and Boston seismic zones. Extensive design analyses (static and multi-modal) of the perimeter frame buildings and consistent design of spatial frame systems, as an alternative to the perimeter configuration, were conducted within this analytical study. The objectives of the consistent design are two-fold, i.e. obtaining fundamental periods similar to those of the perimeter frames, i.e. same lateral stiffness under design horizon- tal loads, and supplying similar yield strength. The seismic behaviour of perimeter and spatial configuration structures was evaluated by means of push-over non-linear static analyses and inelastic dynamic analyses (non linear time histories). Comparisons be- tween analysis results were developed in a well defined framework since a clear scheme to define and evaluate relevant limit states is suggested. The failure modes, either local or global, were computed and correlated to design choices, particularly those concerning the strength requirements (column overstrength factors) and stiffness (elastic stability indexes). The inelastic response exhibited by the sample MRFs under severe ground motions was assessed in a detailed fashion. Conclusions are drawn in terms of local and global performance, namely global and inter-storey drifts, beam and column plas- tic rotations, hysteretic energy. The finding is that the seismic response of perimeter and spatial MRFs is fairly similar. Therefore, an equivalent behaviour between the two configurations can be obtained if the design is “consistent”. Keywords : Seismic design; steel frames; perimeter; spatial; pushover; dynamic analysis. 1. Introduction The design criteria to obtain satisfactory seismic performance of steel moment re- sisting frame (MRF) buildings is a major research issue which has been deeply discussed during recent years (e.g. Luco and Cornell [2000], Yun et al. [2002], among others). Building damage survey carried out in the aftermath of the 1994 457
Transcript
  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Journal of Earthquake Engineering, Vol. 8, No. 3 (2004) 457496c Imperial College Press

    SEISMIC BEHAVIOUR OF PERIMETER AND

    SPATIAL STEEL FRAMES

    ELENA MELE, LUIGI DI SARNO and ANTONELLO DE LUCA

    Department of Structural Analysis and Design,

    University of Naples Federico II,

    P.le V.Tecchio, 80,

    80125 Naples, Italy

    Received 6 May 2002Revised 26 August 2002Accepted 11 June 2003

    The present study deals with the seismic performance of partial perimeter and spatialmoment resisting frames (MRFs) for low-to-medium rise buildings. It seeks to establishperimeter configuration systems and hence the lack of redundancy can detrimentallyaffect the seismic response of framed buildings. The paper tackles this key issue by com-paring the performance of a set of perimeter and spatial MRFs, which were consistentlydesigned. The starting point is the set of low- (three-storey) and medium-rise (nine-storey) perimeter frames designed within the SAC Steel Project for the Los Angeles,Seattle and Boston seismic zones. Extensive design analyses (static and multi-modal)of the perimeter frame buildings and consistent design of spatial frame systems, as analternative to the perimeter configuration, were conducted within this analytical study.The objectives of the consistent design are two-fold, i.e. obtaining fundamental periodssimilar to those of the perimeter frames, i.e. same lateral stiffness under design horizon-tal loads, and supplying similar yield strength. The seismic behaviour of perimeter andspatial configuration structures was evaluated by means of push-over non-linear staticanalyses and inelastic dynamic analyses (non linear time histories). Comparisons be-tween analysis results were developed in a well defined framework since a clear schemeto define and evaluate relevant limit states is suggested. The failure modes, either localor global, were computed and correlated to design choices, particularly those concerningthe strength requirements (column overstrength factors) and stiffness (elastic stabilityindexes). The inelastic response exhibited by the sample MRFs under severe groundmotions was assessed in a detailed fashion. Conclusions are drawn in terms of localand global performance, namely global and inter-storey drifts, beam and column plas-tic rotations, hysteretic energy. The finding is that the seismic response of perimeterand spatial MRFs is fairly similar. Therefore, an equivalent behaviour between the twoconfigurations can be obtained if the design is consistent.

    Keywords: Seismic design; steel frames; perimeter; spatial; pushover; dynamic analysis.

    1. Introduction

    The design criteria to obtain satisfactory seismic performance of steel moment re-

    sisting frame (MRF) buildings is a major research issue which has been deeply

    discussed during recent years (e.g. Luco and Cornell [2000], Yun et al. [2002],

    among others). Building damage survey carried out in the aftermath of the 1994

    457

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    458 E. Mele, L. Di Sarno & A. De Luca

    Northridge (California) and 1995 Hyogoken-Nanbu (Japan) earthquakes showed

    clearly widespread and unexpected damage modes in steel structures. Several

    types of brittle fractures were, indeed, found at welded connections in MRFs.

    As a consequence, a great deal of research in USA, Japan and Europe has

    been devoted to understand and prevent the causes of the observed poor per-

    formance of steel structures. For example, in the USA, the SAC Joint Venture

    was formed with the specific goal of investigating the damage to welded steel

    moment frame buildings in the 1994 Northridge earthquake and developing re-

    pair techniques and new design approaches to minimise damage to steel moment

    frame buildings in future earthquakes [SAC, 1995]. In the first part of the research

    program (SAC Steel Project) interim design guidelines [FEMA 267, 1995; FEMA

    267A, 1997; FEMA 267B, 1999] were developed and two sets of nine frame build-

    ings (low-, medium- and high-rise) were designed in compliance with both pre-

    Northridge design practice [UBC, 1994] and the Interim Guidelines. The structural

    systems of these nine model buildings are perimeter MRFs, designed for three dif-

    ferent earthquake prone zones. Such structures were considered as benchmarks in

    order to carry out analytical investigations on the seismic performance, with the

    aim of:

    Developing concepts and information needed to identify and predict local and

    global seismic demand parameters which have a significant effect on the seismic

    response of steel moment resisting frames;

    Identifying the effect on seismic performance of the strength, stiffness and

    hysteretic characteristics of realistic alternative connection types as well as of

    the system configuration and proportioning.

    In the present study, the SAC low- and medium-rise buildings were selected and

    assessed to establish the governing parameters in the seismic design and hence eval-

    uate the response of MRFs under severe earthquakes, varying the design criteria

    and the design parameter values. This paper focuses, however, on the influence of

    the configuration layout and redundancy of the lateral resisting system on the seis-

    mic performance of framed buildings. The SAC perimeter structures are analysed

    and contrasted to alternative structural configurations, i.e. spatial MRFs.

    2. Object and Layout of the Paper

    This analytical study deals with the seismic performance of partial perimeter and

    spatial MRFs for low-to-medium rise buildings. Its aim is to establish if the de-

    sign choice of employing perimeter configuration system, namely the lack of high

    redundancy, has detrimental effects on the seismic response of framed buildings.

    The effect of redundant seismic framing is a major topic, often appointed by the

    engineering community as one of the possible causes of the poor seismic performance

    [FEMA 350, 2000; Whittaker et al., 1999]. Nevertheless, few studies have been

    conducted so far to quantify systematically such an effect.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 459

    The framework employed within this study is based upon the comparison of

    the seismic performance of perimeter and spatial MRFs, which are consistently

    designed. Thus, the set of low- (three-storey) and medium-rise (nine-storey)

    perimeter frames designed within the SAC Steel Project for the Los Angeles, Seattle

    and Boston seismic zones was considered as a benchmark. The scheme of the study

    carried out can be summarised as follows:

    Definition of the design parameters for steel MRF systems. A critical assessment

    of MRF design procedures and approaches is carried out in order to establish the

    structural parameters governing the seismic design.

    Elastic analyses (static and multi-modal) of the SAC perimeter frame buildings

    under design load distributions and evaluation of major design parameters.

    Consistent design of spatial frame systems, as alternative structural configuration

    for the SAC model buildings. The design is consistent because it is carried out

    with two specific objectives: (i) obtaining the same period as the perimeter frame

    building, i.e. same lateral stiffness under design horizontal loads; (ii) supplying

    the same yield strength as perimeter frame building. It is also worth mentioning

    that the total weight of both configurations does not differ significantly.

    Assessment of the inelastic behaviour of perimeter and spatial frames and

    comparisons.

    Evaluation of the seismic performance and inelastic demands under severe

    earthquakes of perimeter and spatial frames and comparisons.

    The seismic behaviour of perimeter and spatial configuration structures was

    evaluated by means of push-over non-linear static analyses and inelastic dynamic

    analyses. Comparisons between analysis results were developed in a well defined

    framework. A clear scheme to define and evaluate relevant limit states (LSs) is

    suggested in agreement with a similar proposal available in the literature [Broderick

    and Elnashai, 1996; Elnashai et al., 1998]. Thus, the failure modes, either local or

    global, were computed and correlated to design choices, particularly concerning

    strength requirements (column overstrength factors) and stiffness (elastic stability

    indexes). Moreover, the inelastic response exhibited by perimeter and spatial MRFs

    under severe ground motions was assessed. Conclusions are drawn in terms of local

    and global performance, namely (i) global and inter-storey drifts, (ii) beam and

    column plastic rotations and (iii) hysteretic energy.

    3. Structural Systems

    3.1. Description

    The assessed structures are three- and nine-storey office buildings, designed

    according to the UBC 1994 provisions for three different seismic zones, respectively

    Los Angeles (LA), seismic zone 4, Seattle (SE), seismic zone 3 and Boston (BO),

    seismic zone 2A. They were designed by three U.S. professional firms, i.e. Brandow

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    460 E. Mele, L. Di Sarno & A. De Luca

    and Johnston Associates (three- and nine-storey LA buildings), KPFF Consulting

    Engineers (three- and nine-storey SE buildings) and LeMessurier Consultants

    (three- and nine-storey BO buildings). These MRFs have been extensively anal-

    ysed by Gupta and Krawinkler [1998a, 1998b, 2000a, 2000b] within SAC studies on

    structural system performance, and other Researchers [e.g. Maison and Bonowitz,

    1999; Mele et al., 2000].

    Low-rise buildings have a rectangular floor plan 56.08 37.80 m (Fig. 1). The

    structural configuration consists of six 9.15 m bays along the major side and four

    9.15 m bays in the orthogonal direction. The inter-storey height is 3.96 m. The

    lateral load resisting system consists of two four-bays perimeter moment frames in

    both principal directions, thus providing torsional resistance, and interior gravity

    frames with simple shear connections. In the LA perimeter frame there are only

    three moment resisting bays; the fourth bay includes pinned beams connected to

    weak axis columns. At the first and second floor, beam span loads (dead and live)

    are equal to 14.88 kN/m and joint vertical loads are equal to 158 kN and 107 kN

    at interior and perimeter joints, respectively. Beam loads of 12.65 kN/m and joint

    vertical loads of 140 kN (interior joints) and 92 kN (exterior joints) were respectively

    considered at the roof. At each storey level the slab consists of 76.2 mm metal

    decking with 63.5 mm of normal weight concrete (NWC). The latter is stiff enough

    to ensure the diaphragm (rigid) action. The total seismic load of the building is

    Wtot = 29 500 kN.

    The nine-storey buildings (Fig. 2) have a square floor plan 45.7 45.7 m, with

    five 9.15 m bays along both sides. The inter-storey height is 5.49 m at the first

    storey and 3.96 m at all other storeys, whilst the basement level is 3.66 m in height.

    Four MRFs are located along the perimeter of the buildings, two for both principal

    directions to provide lateral and torsion resistance, similarly to low-rise frames.

    Perimeter systems consist of four bays with strong axis columns rigidly connected

    to the girders plus an external bay where the girder is shear connected to the corner

    columns, thus biaxial bending is prevented in all building corner columns. Beam

    span loads and joint vertical loads are similar to the three-storey counterparts. The

    slab is a floor system (rigid plane) of composite metal deck (76.2 mm thick), with

    63.5 mm of NWC fill. The total seismic load of the building is Wtot = 90 140 kN.

    Element cross sections of perimeter and spatial frames employed in three- and

    nine-storey buildings are provided in Table 1 and Table 6, respectively.

    Nominal yield strength equal to 345 MPa (50 ksi) was used for girders and

    columns of all perimeter frames, except for LA frames, in which nominal yield

    strength equal to 248 MPa (36 ksi) was adopted for girders. Similar yield stress

    values were employed either for low- or medium-rise, spatial MRFs.

    In the following, low- and medium-rise perimeter frames are appointed as:

    LA-3P, SE-3P, BO-3P and LA-9P, SE-9P, BO-9P. Similarly, the spatial frames

    are appointed as: LA-3S, SE-3S, BO-3S and LA-9S, SE-9S, BO-9S. For example,

    LA-3P means that the frame is located in Los Angeles, it has three-storeys and

    perimeter configuration.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 461

    Fig

    .1.

    Geo

    met

    ryofth

    ree-

    store

    yM

    RFs:

    pla

    nla

    yout

    (lef

    t)and

    ver

    tica

    lse

    ctio

    n(r

    ight)

    .

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    462

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    Fig. 2. Geometry of nine-storey MRFs: plan layout (left) and vertical section (right).

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    463

    Table 1. Beam and column cross sections (three- and nine-storey perimeter MRFs).

    Beams Internal Columns External ColumnsFrame

    Storey LA SE BO LA SE BO LA SE BO

    01 W33 118 W24 76 W21 62 W14 311 W14 176 W14 99 W14 257 W14 159 W14 74

    Three-Storey 12 W30 116 W24 84 W21 57 W14 311 W14 176 W14 99 W14 257 W14 159 W14 74

    23 W24 68 W18 40 W18 35 W14 311 W14 176 W14 99 W14 257 W14 159 W14 74

    01 W36 160 W30 108 W24 68 W14 500 W24 229 W14 233 W14 370 W24 229 W14 159

    12 W36 160 W30 108 W36 135 W14 500 W24 229 W14 233 W14 370 W24 229 W14 159

    23 W36 160 W30 116 W33 118 W14 455 W24 229 W14 233 W14 370 W24 229 W14 159

    34 W36 135 W30 108 W30 116 W14 455 W24 229 W14 233 W14 370 W24 229 W14 159

    Nine-Storey 45 W36 135 W27 94 W30 116 W14 370 W24 207 W14 211 W14 283 W24 207 W14 132

    56 W36 135 W27 94 W30 108 W14 370 W24 207 W14 211 W14 283 W24 207 W14 132

    67 W36 135 W24 76 W30 99 W14 283 W24 162 W14 176 W14 257 W24 162 W14 99

    78 W30 99 W24 76 W27 94 W14 283 W24 162 W14 176 W14 257 W24 162 W14 99

    89 W27 84 W24 62 W24 76 W14 257 W24 131 W14 120 W14 233 W24 131 W14 68

    910 W24 68 W24 62 W18 40 W14 257 W24 131 W14 120 W14 233 W24 131 W14 68

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    464 E. Mele, L. Di Sarno & A. De Luca

    3.2. Modelling

    The structural analysis was performed through two finite element method codes.

    Elastic analyses were carried out by means of SAP2000 [SAP2000, 1999], while

    the computer code DRAIN-2DX [Prakash et al., 1993] was used to evaluate the

    responses of both perimeter and spatial MRFs beyond the elastic limit (inelastic

    static and non linear dynamic analyses). Moreover, DRAIN-2DX models were cali-

    brated on the basis of the SAP2000 counterparts. Bare frames, employing centreline

    dimensions, were modelled as two-dimensional assemblages of plastic hinge (lumped

    plasticity) beam and beam-column elements. The latter account for bending-axial

    interaction, through a linearised biaxial plastic domain (bending moment-axial

    load), characterised by horizontal and vertical straight lines corresponding to 10% of

    adimensionalised bending and axial capacity, with reference to full plastic bending

    moment and squash load, respectively. Bilinear elastic plastic behaviour with strain

    hardening of 1% was adopted to model plastic hinges. Shear behaviour of beams and

    columns was assumed to remain linearly elastic. Geometric non-linearities, i.e. P

    effects, were included within elastic and inelastic analyses. Panel zone yielding and

    deformation were not considered. Moreover, the additional stiffness and strength

    due to the presence of the concrete deck slab were not accounted for in the analysed

    plane systems. Dynamic elastic analyses were based upon a 5% equivalent viscous

    damping, whilst the latter was not accounted for in the inelastic analyses since

    dissipative sources other than material plasticity were not considered.

    4. Design Analyses of Perimeter Frames

    The design choices adopted for perimeter framed buildings were investigated with

    respect to the main structural properties, namely stiffness (fundamental period and

    lateral stiffness), strength (design stress level, column over-strength factor, yield

    strength) and stability (sensitivity to P effects). These analyses were based upon

    UBC94 seismic provisions [UBC, 1994], which defines the seismic base shear V as

    follows:

    V = C(T ) W , (1)

    where the seismic coefficient (C) is a function of the period (T ):

    C =1.25ZIS

    RwT2

    3

    , (2)

    where Z = zone factor, I = importance factor, S = soil response factor, Rw =

    response modification or force reduction factor.

    4.1. Period and design forces

    The design period at which the static lateral forces are computed deserves particu-

    lar attention and has been subjected to several adjustments in the Codes of Practice

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 465

    during recent years [Chopra and Goel, 2000]. However, it is common among pro-

    fessionals to adopt empirical formulas like that proposed by UBC (Method A):

    TA = Ct (Htot)3

    4 (3)

    (with Ct = 0.035 for steel frames and Htot is the global height in feet), albeit

    the code specifically advises the adoption of a more refined, Rayleigh type formula

    (Method B). In such case, as an upper limit of the period to be used in the as-

    sessment of structural deformations, the code requires, for high seismicity areas

    (Zone 4):

    TB,max = 1.30 TA , (4)

    whilst a longer value, i.e.

    TB,max = 1.40 TA (5)

    is allowed for low-to-intermediate seismicity, namely Zones 1, 2 and 3.

    For the assessed buildings Methods A and B were used to determine the design

    base shears. The period values computed by means of Eq. (3) and either Eqs. (4)

    or (5), depending on seismic zone, along with the actual values of the structure

    fundamental periods, are provided in Table 2 for three- and nine-storey perimeter

    MRFs. In these tables the design base shear (VUBC-A and VUBC-B) and maximum

    inter-storey and roof drift ratios (d/h and Dtop/H), computed by means of elastic

    analyses, are also given. For the sake of completeness, base shears corresponding to

    wind forces and the relative deformation parameters were evaluated; the latter are

    included in the above mentioned table. To evaluate wind actions and effects, wind

    speeds of 70 mph (LA) and 80 mph (BO and SE) and Exposure B were assumed.

    Large scatters can be observed between the actual natural periods and the

    counterparts based upon code equations. Standardised semi-empirical formulae are

    calibrated to account for the contribution of in-filled non structural elements. The

    latter increase the frame lateral stiffness. These contributions are, however, usually

    neglected in preliminary design models. For the set of SAC buildings, elastic anal-

    yses performed on 3D FEM frame models showed that, due to the contribution of

    the internal frames (gravity load system), the period values decrease by less than

    5% for the three-storey buildings and by approximately 10% for the nine-storey

    buildings. Thus, unless very stiff non-structural elements are adopted, empirical

    code formulas provide too low an estimate of the fundamental period. This finding

    is in agreement with previous studies [Gupta and Krawinkler, 1998b, 2000a].

    4.2. Lateral stiffness

    Elastic deformation parameters, i.e. inter-storey and global drifts, were computed

    through static analyses employing Methods A and B (UBC, 1994) horizontal force

    distributions, as well as through response spectrum analysis (Table 2).

    It is instructive to note that in steel MRF design, stiffness requirements, ex-

    pressed as either maximum inter-storey or roof drift limitations, are usually more

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    466

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    Table 2. Fundamental period, base shear, maximum drift index and roof drift (three- and nine-storey perimeter MRFs).

    Method A Method B Wind Loads Dynamic Analysis

    T V/W d/h Dtop/H T V/W d/h Dtop/H V/W d/h Dtop/H T Dtop/H

    Frame [sec] [%] [%] [%] [sec] [%] [%] [%] [%] [%] [%] [sec] [%]

    LA-3P 7.64 0.30 0.26 0.72 6.26 0.25 0.22 2.36 0.07 0.06 0.99 0.14

    SE-3P 0.55 5.73 0.38 0.33 0.77 4.48 0.30 0.26 3.08 0.15 0.13 1.31 0.09

    BO-3P 2.87 0.35 0.30 0.77 2.24 0.29 0.24 3.08 0.27 0.23 1.76 0.09

    LA-9P 4.04 0.30 0.28 1.79 3.39 0.25 0.24 2.53 0.18 0.13 2.53 0.12

    SE-9P 1.38 3.04 0.41 0.36 1.93 2.42 0.33 0.29 3.32 0.35 0.27 3.30 0.10

    BO-9P 1.51 0.28 0.21 1.93 1.21 0.22 0.18 3.32 0.59 0.32 3.63 0.10

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 467

    stringent than strength. For code compliant design [UBC, 1994] the inter-storey

    drift limitation is equal to either 1/300 or 1/400 for structures with fundamen-

    tal period respectively either lower or higher than 0.7 sec. Thus, for three-storey

    buildings, 1/300 applies when Method A is used, since Eq. (3) provides a period

    value equal to 0.55 sec; on the other hand, 1/400 applies if Method B or spectrum

    analysis are adopted.

    Inter-storey drift ratios computed for low-rise frames show that code limits

    are exactly fulfilled only in LA-3P, while they are slightly exceeded in SE-3P and

    BO-3P. However, for such buildings, the roof drift is respectively less than 1/300

    and 1/400 under Methods A and B design loads. Roof drift values obtained through

    response spectrum analyses are even smaller than the latter ones.

    It should be pointed out that for the BO-3P building the base shear due to wind

    actions is larger than the seismic shear. Nevertheless, the maximum deformations

    occur under the seismic force distribution, due to a larger overturning moment.

    Thus, it is likely that member proportioning was governed by the seismic load

    condition.

    With regard to the medium-rise buildings, the design load due to wind actions

    is higher than the seismic ones for BO-9P and SE-9P. It is interesting to note

    that whereas for BO-9P the effects due to wind actions (d/h and Dtop/H) are

    also greater than the seismic loads, for the SE-9P building the roof and inter-storey

    drifts induced by wind actions are slightly smaller than those induced by earthquake

    loading.

    The LA-9P building fully satisfies the drift limitation (1/400) under Method B

    design loads, while SE-9P and BO-9P slightly exceed it. However, the nine-storey

    buildings spectrum analysis provides values of the deformation parameters which

    are also by and large within code limitations.

    Concerning stiffness distribution, the structures exhibit a quite smooth variation

    of global stiffness over the height. In the low-rise frames while the beam cross

    sections are reduced over the frame height (with the exception of the SE-3P frame,

    which has second floor beams stiffer than first storey ones), the columns cross

    sections are the same. In the medium-rise frames both columns and beams are

    varied throughout the building height. Column splices are generally located at every

    third storey, and beams are consistently reduced. In SE-9P, as for SE-3P, second

    floor beams are stiffer than first storey ones.

    4.3. Design stress level and yield strength

    The stress level in structural members under gravity and seismic lateral loads

    (Methods A and B of UBC) was evaluated and very low stress values were obtained.

    Thus, the base shear Vy corresponding to first yield, i.e. onset of yield strength

    in the most stressed section, was evaluated. Values of Vy , normalised to seismic

    weight W and to the seismic base shears (VUBC-A and VUBC-B), are provided for

    three- and nine-storey buildings in Table 3; the values for wind actions are also

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    468

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    Table 3. Non-dimensional base shear (three- and nine-storey perimeter MRFs).

    VUBC-M.A/W VUBC-M.B/W VWIND/W Vy-triang./W Vy-unif./W Vy-triang./ Vy-triang./ Vy-unif./

    Frame [%] [%] [%] [%] [%] VUBC-M.A VUBC-M.B VWIND

    LA-3P 7.64 6.26 2.36 20.1 22.79 2.63 3.23 9.66

    SE-3P 5.73 4.48 3.08 18.59 21.02 3.24 4.15 6.82

    BO-3P 2.87 2.24 3.08 10.89 11.25 3.79 4.86 3.65

    LA-9P 4.04 3.39 2.53 10.18 10.61 2.52 3.00 4.19

    SE-9P 3.04 2.42 3.32 8.06 8.43 2.65 3.33 2.54

    BO-9P 1.51 1.21 3.32 7.53 7.79 4.99 6.22 2.35

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 469

    included. Design over-strength factors, herein defined as the ratio Vy/VUBC, are

    high. They range between 2.52 and 3.25, except where the design was governed by

    wind (BO frames). These large values are due to several features: (i) the ratio of

    yield-to-allowable stress (about 1.5), (ii) the compliance to drift limitations, (iii)

    the compliance of SCWB requirement and (iv) the different susceptibility to second

    order effects. The latter is significant for BO MRFs whose Vy/VUBC represent an

    outlier when compared to the mean values.

    It is worth mentioning that the design of BO-3P as well as SE-9P and

    BO-9P, which exhibit over-strengths equal to 3.80, 2.65 and 4.97, respectively, were

    governed by wind loading. Thus, the computed Vy/VUBC factors do not refer to the

    actual design condition.

    Finally, it is interesting to note that for BO frames (both low- and medium-

    rise), as well as for SE medium-rise frames, the over-strength factors due to the

    wind are lower than the seismic counterparts. By contrast, LA frames (three- and

    nine-storeys) and SE low-rise frame, exhibit design over-strength for wind greater

    than for earthquake loads.

    4.4. Column over-strength factor

    Column over-strength factors (COF s) were computed at each frame joint using the

    following standardised relationship [UBC, 1994]:

    COF =Zc(fyc fa)

    Zbfyb(6)

    in order to verify the fulfilment of the strong column weak beam (SCWB) re-

    quirement (COF 1). In the above equation Zc, Zb and fyc, fyb are section plastic

    modulus and yield stress respectively for columns and beams framing into the joint,

    while fa is the axial stress in column members. An adequate column over-strength

    factor gives rise to a configuration where columns are protected from plastic hinge

    formation. Hence, inelastic deformations should occur in beams.

    It is worth mentioning that COF s in three-storey frames (Table 4) are greater

    than unity, minimum values being 1.06, 1.23 and 1.94, respectively, for BO-3P,

    Table 4. COF s (three- and nine-storeyperimeter MRFs).

    Frame Minimum Maximum

    LA-3P 1.94 (1) 3.77 (3)

    SE-3P 1.23 (2) 3.60 (3)

    BO-P 1.06 (1) 1.87 (2)

    LA-9P 1.39 (7) 4.89 (8)

    SE-9P 1.17 (9) 3.66 (1)

    BO-9P 0.68 (2) 2.04 (1)

    Keys: Bracketed values show the floors.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    470 E. Mele, L. Di Sarno & A. De Luca

    SE-3P and LA-3P buildings. Moreover, for BO-3P nearly 80% of the total number

    of beam-to-column connections exhibit COF s between 1.0 and 1.50, thus show-

    ing high risk of extensive column hinging. Indeed, recent studies [Nakashima and

    Sawaizumi, 2000] showed that plastic hinges in columns cannot be prevented by

    simply satisfying the requirement COF 1. Minimum COF values strongly de-

    pend on ground motions and importance of higher vibration modes of vibration. As

    rule of thumb, COF s ranging from 1.5 to 2 are required to ensure elastic response of

    column members. As a consequence, for low-rise buildings, the adequate fulfilment

    of SCWB can be predicted only for LA-3P.

    Values of COF vary quite significantly for medium-rise buildings (Table 4) as

    a function of seismic hazard. Indeed, for LA-9P, values ranging from 1.4 to 1.9

    occur between the fourth and sixth floor, while values greater than 2 can be found

    elsewhere. In BO-9P building, COF values smaller than 1 characterise all beam-to-

    column joints from the third to seventh floor. Values equal to unity (eighth floor)

    or greater can be found in the remaining floors. An intermediate situation can be

    observed for SE-9P, exhibiting COF between 1.4 and 1.6 (first and third floor) or

    1.7 and 2.1 (fourth and seventh floor); values greater than 2 are located at the

    eighth floor. Thus, for LA-9P a SCWB behaviour is expected, while for BO-9P a

    weak column strong beam (WCSB) behaviour at intermediate storeys, with col-

    umn plastic hinges, seems to be unavoidable. Finally, in SE-9P, plastic hinges are

    expected mainly in beam members, although some column plastic deformations are

    likely to occur.

    4.5. Stability

    The design criteria for MRFs are based also on specific checks for second or-

    der effects at each storey and overall stability. P effects can be approximately

    evaluated through the stability index () expressed as follows:

    =Ptot drVtot h

    , (7)

    where Ptot is the total gravity storey load, Vtot the total seismic storey design shear,

    whilst dr and h are, respectively, the design inter-storey drift and relative height.

    The stability index expressed by Eq. (7) may be assumed approximately equiv-

    alent, for framed structures, to the elastic critical vertical load ratio [Horne, 1975],

    defined as the ratio (P/Pcr) in which P is the total vertical load and Pcr is the

    elastic critical load value for failure in a sway mode. Therefore, it represents a

    measure of the sensitivity to P effects. In International Standards [UBC, 1994;

    1997; EC8, 1998], it is required that the ratio should not to exceed 0.10 in order

    to neglect P effects. On the other hand, if 0.10 < 0.30, then P effects

    should be accounted for; the upper bound for is, however, assumed equal to 0.30.

    The -value was computed for all floors in low- and medium-rise frames, under

    seismic actions. The maximum values, along with the storey level where they are

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 471

    Table 5. Stability index (three- and nine-storey perimeter MRFs).

    Method A Wind

    Frame Minimum Maximum Minimum Maximum

    LA-3P 0.017 (3) 0.026 (2) 0.021 (3) 0.026 (2)

    SE-3P 0.029 (3) 0.043 (2) 0.038 (3) 0.044 (2)

    BO-P 0.049 (3) 0.039 (2) 0.064 (3) 0.080 (2)

    LA-9P 0.022 (9) 0.065 (1) 0.046 (7) 0.065 (1)

    SE-9P 0.030 (9) 0.096 (1) 0.057 (9) 0.097 (2)

    BO-9P 0.049 (9) 0.154 (1) 0.069 (7) 0.146 (1)

    Keys: Bracketed values show the floors.

    found, were also evaluated (Table 5). The values corresponding to wind effects were

    included for comparative purposes.

    For low-rise MRFs, the stability check is greatest at the second floor, indepen-

    dently of seismic region. The maximum values for are always lower than 0.10, with

    the highest value for BO-3P frame (max = 0.080), whilst the greatest safety margin

    for stability checks is exhibited by LA-3P (max = 0.026). Intermediate behaviour

    characterises the SE-3P building (max = 0.044).

    For nine-storey buildings the variation of stability index heightwise is more

    pronounced than in low-rise frames, with the highest values are at either the

    first or second floor, and a nearly linear reduction from the base to roof level.

    The most critical stability indexes were found for the BO-9P building (max =

    0.154), whilst greater safety margin for stability checks is exhibited by LA-9P frame

    (max = 0.065). An intermediate behaviour characterises the SE-9P frame (max =

    0.097).

    As a result, second-order effects can be significant for BO-9P and, to a lesser

    extent, SE-9P. These frames possess the highest values of the stability index; similar

    results were found for BO-9S and SE-9S. However, the latter are characterised by

    lower values than the perimeter frames, thus rendering the onset of instability

    more unlikely.

    5. Design of Spatial Frames and Comparison to Perimeter Frames

    Spatial MRF buildings possess the same layout as their perimeter counterparts,

    see for example Fig. 1 (low-rise) and Fig. 2 (medium-rise). For such structures, it

    was assumed that all frames along the North-South direction are special moment

    resisting frames. Braced frames are assumed to resist earthquake loads in the

    orthogonal direction.

    Floor masses for spatial MRFs were computed by considering 1/7 floor tributary

    area (low-rise) or 1/6 (medium-rise). The total seismic load of a three-storey

    building is Wtot = 29 500 kN; thus for spatial MRF is: WMRF-S = 4214 kN

    versus WMRF-P = 14750 kN for the perimeter MRF. For nine-storey buildings

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    472 E. Mele, L. Di Sarno & A. De Luca

    it is Wtot = 90 140 kN, thus for spatial MRF is: WMRF-S = 15023 kN versus

    WMRF-P = 45 070 kN for the perimeter MRF.

    The design of buildings with spatial frames was carried out according to UBC

    seismic provisions [UBC, 1994]. The design target was to match the stiffness

    and strength properties of their perimeter counterparts. Member cross sections

    employed are provided in Table 6.

    The results of comparative analyses for the design parameters of both spatial

    and perimeter frames are discussed hereafter.

    5.1. Period and design forces

    The fundamental periods of low- and medium-rise spatial frames are provided in

    Table 7. The values computed by means of code equations are equal to perimeter

    values because the building height does not change. Similarly, for the design base

    shears, which are based on the spectral ordinates.

    Negligible variations of the fundamental period were found for low-to-moderate

    seismic zone (BO and SE). Spatial frames are slightly stiffer than perimeter frames;

    however, variations do not exceed 8%. Similarly, medium-rise frames show roughly

    the same periods for either perimeter or spatial configurations.

    Finally, modal masses relative to the first vibration mode were computed for the

    assessed buildings; such values were then compared. Two points are worth noting:

    (i) all frames possess a modal mass nearly equal to 85% and (ii) modal masses of

    perimeter structures are roughly equal to spatial ones; the variations are, in fact,

    within 3%. As a result, a dynamic response correspondent to a single degree of

    freedom system (SDOF) may be predicted for the set of frames, either three- or

    nine-storeys.

    5.2. Lateral stiffness

    Table 7 provides maximum values of elastic deformation parameters (inter-storey

    and roof drift ratios) under design loads for low- and medium-rise spatial structures.

    Values relative to low-rise frames are compliant with code limitations, for either

    Method A (d/h 1/300) or Method B (d/h 1/400). This is not the case for SE-

    3S; however, the exceedence is around about 5% and hence is negligible. By contrast,

    the spatial nine-storey frame design gave rise to structures (LA-9S and BO-9S)

    exceeding slightly standardised values, namely 1/400; higher d/h were found for SE-

    9P. Maximum inter-storey drifts are not found at the same floor, being the second

    for BO-9S and fourth for LA-9S. Drift ratios computed for spatial configurations

    replicate the response established for perimeter frames.

    5.3. Design stress level and yield strength

    Base shears Vy corresponding to first yield, normalised to seismic weight (W),

    i.e. Vy/W , and to seismic base shears (VUBC-A and VUBC-B), are given in Table 8

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    473

    Table 6. Beam and column cross sections (three- and nine-storey spatial MRFs).

    Beams Internal Columns External Columns

    Frame Storey LA SE BO LA SE BO LA SE BO

    01 W18 71 W14 48 W14 26 W14 120 W14 99 W14 61 W14 120 W14 99 W14 61

    Three-Storey 12 W18 65 W14 48 W14 26 W14 120 W14 99 W14 61 W14 120 W14 99 W14 61

    23 W18 55 W14 26 W14 22 W14 120 W14 99 W14 61 W14 120 W14 99 W14 61

    01 W24 104 W18 71 W18 60 W14 283 W14 211 W14 211 W14 283 W14 211 W14 211

    12 W24 117 W18 71 W18 60 W14 283 W14 211 W14 211 W14 283 W14 211 W14 211

    23 W24 117 W18 71 W18 60 W14 211 W14 211 W14 211 W14 211 W14 211 W14 211

    34 W24 84 W18 71 W18 60 W14 211 W14 211 W14 211 W14 211 W14 211 W14 211

    Nine-Storey 45 W24 84 W18 76 W18 55 W14 159 W14 193 W14 193 W14 159 W14 193 W14 193

    56 W24 84 W18 76 W18 55 W14 159 W14 193 W14 193 W14 159 W14 193 W14 193

    67 W24 84 W18 76 W18 50 W14 120 W14 176 W14 176 W14 120 W14 176 W14 176

    78 W24 62 W18 71 W18 50 W14 120 W14 176 W14 176 W14 120 W14 176 W14 176

    89 W24 62 W18 71 W18 50 W14 90 W14 159 W14 159 W14 90 W14 159 W14 159

    910 W24 62 W18 71 W18 50 W14 90 W14 159 W14 159 W14 90 W14 159 W14 159

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    474

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    Table 7. Fundamental period, base shear, maximum drift index and roof drift (three- and nine-storey spatial MRFs).

    Method A Method B Wind Loads Dynamic Analysis

    T V/W d/h Dtop/H T V/W d/h Dtop/H V/W d/h Dtop/H T Dtop/H

    Frame [sec] [%] [%] [%] [sec] [%] [%] [%] [%] [%] [%] [sec] [%]

    LA-3S 7.64 0.30 0.25 0.72 6.24 0.25 0.20 2.36 0.07 0.06 0.99 0.15

    SE-3S 0.55 5.73 0.35 0.29 0.77 4.48 0.27 0.23 3.08 0.13 0.11 1.22 0.10

    BO-3S 2.87 0.32 0.26 0.77 2.24 0.25 0.21 3.08 0.25 0.20 1.63 0.10

    LA-9S 4.04 0.29 0.27 1.79 3.39 0.26 0.24 2.53 0.18 0.14 2.52 0.14

    SE-9S 1.38 3.04 0.40 0.33 1.93 2.42 0.27 0.23 3.32 0.39 0.27 3.30 0.10

    BO-9S 1.51 0.25 0.21 1.93 1.21 0.21 0.17 3.32 0.49 0.34 3.56 0.10

    Table 8. Non-dimensional base shear (three- and nine-storey spatial MRFs).

    VUBC-M.A/W VUBC-M.B/W VWIND/W Vy-triang./W Vy-unif./W Vy-triang./ Vy-triang./ Vy-unif./

    Frame [%] [%] [%] [%] [%] VUBC-M.A VUBC-M.B VWIND

    LA-3S 7.64 6.26 2.36 22.94 26.88 3.00 3.68 11.39

    SE-3S 5.73 4.48 3.08 22.38 30.23 3.91 5.00 9.81

    BO-3S 2.87 2.24 3.08 9.74 11.33 3.39 4.35 3.68

    LA-9S 4.04 3.39 2.53 7.32 11.44 1.81 2.16 4.52

    SE-9S 3.04 2.42 3.32 10.36 11.08 3.41 4.28 3.34

    BO-9S 1.51 1.21 3.32 7.85 8.80 5.20 6.49 2.65

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 475

    for three- and nine-storey spatial buildings; values due to wind actions are also

    provided.

    Slightly higher yield thresholds Vy/W were estimated for LA-3S, SE-3S and

    SE-9S. By contrast, smaller values arise for BO-3S and LA-9S.

    Over-strength factors (Vy/VUBC-A) for the spatial configuration exceeds

    perimeter values; this is not the case for BO-3S and LA-9S. Such design

    values range between 2.68 and 3.90 (low-rise), 1.81 and 5.20 (medium-rise).

    However, referring to the over-strength factor Vy/VWIND , where the design is

    governed by wind (SE-9S and BO-9S), the range upper bound is 3.34.

    Yield stress level in LA-9S drops off by about 40% with respect to LA-9P, while

    SE-9S gives rise to a Vy/VUBC-A that is nearly 30% higher than SE-9P.

    As a result, it can be argued that the design of spatial MRFs is governed by

    stiffness rather than strength requirements similar to perimeter configurations (see

    Sec. 5.2).

    5.4. Column over-strength factor

    To check SCWB fulfillment, COF s were computed by means of Eq. (7); minimum

    and maximum values are given in Table 9 for low-to-medium rise.

    Column over-strength factors in spatial frames are greater than unity, the mini-

    mum values being between 1.28 and 2.07 and the maximum varying between 4.3 and

    8.1. The latter occur at beam-to-external-column joints and can be explained by

    the design choice of adopting equal sections for either external or internal columns.

    However, three-storey frames exhibit on average higher COF s: in SE-3S these

    factors are at least 2.07, so that the occurrence of plastic hinges in beams can be

    safely predicted. Moreover, SCWB-type behaviour is likely to occur in LA-3S and

    BO-3S. COF s greater than 2 were computed at all beam-to-column connections

    in the first two storeys. Therefore, it can be stated that low-storey spatial frames

    were designed relying on high COF s in such a way as to guarantee plastification in

    beams; for perimeter frames this response can be predicted only for LA.

    In medium-rise frames, COF s are greater than 2 for BO-9S, except at the roof

    floor (1.38), thus the SCWB design was fulfilled. However, LA-9S and SE-9S are

    Table 9. COF s (three- and nine-storeyspatial MRFs).

    Frame Minimum Maximum

    LA-3S 1.28 (3) 4.29 (2)

    SE-3S 2.07 (3) 5.42 (2)

    BO-3S 1.76 (3) 5.87 (2)

    LA-9S 1.42 (1) 6.16 (8)

    SE-9S 1.25 (9) 5.50 (7)

    BO-9S 1.38 (9) 5.59 (1)

    Keys: Bracketed values show the floors.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    476 E. Mele, L. Di Sarno & A. De Luca

    characterised by intermediate floors where column over-strength drops below 2.

    Indeed, LA-9S, between the first and fifth floor, has COF s slightly lower than

    2, with minimum equal to 1.42 (Table 9). SE-9S shows values ranging between

    1.25 (roof level) and 5.50 (seventh floor); average values are, however, nearly 2.

    Maximum values of the column over-strength factor are generally higher than for

    the perimeter due to the design choice of employing similar column sections, either

    for interior or exterior bays.

    5.5. Elastic stability

    Stability indexes for spatial frames were evaluated through Eq. (8); the most critical

    values and the storey levels at which they occur are given in Table 10.

    For three-storey frames, -values were generally found to be more critical for

    perimeter rather than spatial configurations. Wind loads give rise to stability in-

    dexes as for seismic actions; the criticality is yet to be found at the second storeys.

    For BO-3P (Table 5) the maximum (0.080) is computed under wind loads; in

    BO-3S the same value ( = 0.069) was evaluated for earthquake and wind.

    On the other hand, nine-storey frames exhibit the highest -values (Table 10)

    either at ground (LA-3S) or second storeys (SE-9S and BO-9S); lower -values char-

    acterise spatial configurations. The variation of stability index throughout the build-

    ing height is more pronounced than in low-storey frames: a nearly linear variation,

    from ground floor to roof, is observed.

    Similarly to low-rise frames, higher -values characterise perimeter rather than

    spatial frames. Indeed a, stability index equal to 0.154 was computed for BO-9P

    when the seismic force distribution (Method A) is considered. By contrast, in LA-9S,

    the sensitivity to second order effects is negligible under both environmental actions,

    since = 0.065.

    The lowest elastic critical multiplier (1/) for medium-rise building was found

    for BO, namely 7.5 (6.5 in BO-9P); whilst a 1/ equal to 16.3 renders the LA

    structure safe for stability checks.

    Table 10. Stability index (three- and nine-storey spatial MRFs).

    Method A Wind

    Frame Minimum Maximum Minimum Maximum

    LA-3S 0.015 (3) 0.026 (3) 0.020 (1) 0.025 (2)

    SE-3S 0.026 (3) 0.039 (2) 0.027 (1) 0.039 (2)

    BO-3S 0.044 (3) 0.069 (2) 0.048 (1) 0.069 (2)

    LA-9S 0.018 (9) 0.061 (1) 0.042 (8) 0.061 (1)

    SE-9S 0.018 (9) 0.098 (2) 0.034 (9) 0.109 (2)

    BO-9S 0.029 (9) 0.134 (2) 0.053 (9) 0.123 (2)

    Keys: Bracketed values show the floors.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 477

    Therefore, the computed figures (Table 5 for perimeter and Table 10 for spa-

    tial frames), highlight a large increase of susceptibility to second order effects for

    medium rather than low rise frames, either perimeter or spatial.

    6. Inelastic Static Pushover Analyses

    Non linear static push-over analysis is a simplified but powerful tool [Krawinkler

    and Seneviratna, 1998; Mwafy and Elnashai, 2000]. It enables the assessment of the

    structural behaviour in the elastic and inelastic range and hence the strength and

    deformation capacity can be estimated. Therefore, the structural models described

    in Sec. 3.1 were implemented and global load-deformation curves were obtained for

    perimeter and spatial MRFs.

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-3P LA-3S UBC (MET.A) YLS ULS

    VB (kN)

    dtop / Htot (%)

    1/400

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-3P LA-3S UBC (MET.A) YLS ULS

    VB / W

    tot (%)

    dtop / Htot (%)

    1/400

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    SE-3P SE-3S UBC (MET.A) YLS ULS

    VB (kN)

    dtop / Htot (%)

    1/400

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-3P LA-3S UBC (MET.A) YLS ULS

    VB (

    kN

    )

    dtop / Htot (%)

    1/4

    00

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-3P LA-3S UBC (MET.A) YLS ULS

    VB /

    Wto

    t (%

    )

    dtop / Htot (%)

    1/4

    00

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    SE-3P SE-3S UBC (MET.A) YLS ULS

    VB (

    kN

    )

    dtop / Htot (%)

    1/4

    00

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    SE-3P SE-3S UBC (MET.A) YLS ULS

    VB /

    Wto

    t (%

    )

    dtop / Htot (%)

    1/4

    00

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-3P BO-3S UBC (MET.A) YLS ULS

    VB (

    kN

    )

    dtop / Htot (%)

    1/4

    00

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-3P BO-3S UBC (MET.A) YLS ULS

    VB /

    Wto

    t (%

    )

    dtop / Htot (%)

    1/4

    00

    Figure 3. - Push-over curves with triangular distribution (3-story MRFs): single frames (left) and buildings (right).

    0

    1000

    2000

    3000

    4000

    5000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-3P BO-3S UBC (MET.A) YLS ULS

    VB (kN)

    dtop / Htot (%)

    1/400

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-3P BO-3S UBC (MET.A) YLS ULS

    VB / W

    tot (%)

    dtop / Htot (%)

    1/400

    Fig. 3. Push-over curves with triangular distribution (three-storey MRFs): single frames (left)and buildings (right).

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    478 E. Mele, L. Di Sarno & A. De Luca

    Figures 3 and 4 provide the results of the analyses carried out on three- and

    nine-storey frames, respectively. The results of perimeter and spatial frames, are

    contrasted in the same plot. They are expressed in terms of base shear divided

    by tributary seismic weight, V/W , versus top displacement normalised to build-

    ing height (dtop/Htot). It is deemed useful for comparative purposes to include in

    Figs. 3 and 4, plots with curves employing the dimensional base shear V as or-

    dinates. Similarly, vertical lines corresponding to the code inter-storey drift limit

    [UBC, 1994)], i.e. d/h = 1/400, are also drawn.

    In order to assess strength and deformation capacities of MRF systems, two

    limit conditions, namely yield limit state (YLS) and ultimate limit state (ULS), were

    defined and relevant points are indicated on the curve response. These LS definitions

    were chosen consistently with (i) international codes and recommendations [UBC,

    0

    2000

    4000

    6000

    8000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-9P LA-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB (kN)

    1/400

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    LA-9P LA-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB / W

    tot (%) 1/400

    0

    2000

    4000

    6000

    8000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    SE-9P SE-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB (kN)

    1/400

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    SE-9P SE-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB / W

    tot (%) 1/400

    0

    2000

    4000

    6000

    8000

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-9P BO-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB (kN)

    1/400

    0

    10

    20

    30

    40

    50

    0.00 1.00 2.00 3.00 4.00 5.00 6.00

    BO-9P BO-9S UBC (MET. A) YLS ULS

    dtop / Htot (%)

    VB / W

    tot (%) 1/400

    Fig. 4. Push-over curves with triangular distribution (nine-storey MRFs): single frames (left)and buildings (right).

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 479

    1997; EC8, 1998; FEMA 350, 2000] and (ii) experimental and numerical studies

    available in the inherent literature [Elnashai et al., 1998; Mwafi and Elnashai, 2000].

    Performance criteria used to define the two LSs are briefly described in the following

    paragraph; then a detailed discussion of push-over results is provided.

    6.1. Yield and ultimate limit states definition

    YLS corresponds to the state at which inelastic deformations begin to contribute

    to the energy absorption. It can be reliably evaluated by means of static analyses

    and corresponds to the onset of the yield at the member far ends.

    The ULS definition appears more complex and controversial than YLS, since it

    deals with the structure collapse condition, which is always conventionally defined.

    In this paper different structural failure modes, both local and global, were con-

    sidered, and the corresponding performance criteria were defined. In the following

    section, local and global failure sources are described and the corresponding limit

    values of relevant performance parameters are provided.

    Local failure modes include either member or connection failure. In this paper

    only connection failure, due to the attainment of plastic rotation capacity for welded

    connections (set equal to SAC target plastic rotation 3%), was accounted for as a

    local failure mode. Moreover, base column rotations were also considered to detect

    the LSs.

    The global failure modes were defined either at the attainment of a collapse

    mechanism formation or when a specific threshold value of inter-storey drift,

    stability index, lateral resistance reduction, were attained.

    The inter-storey drift ratio (IDR) is an adequate structural parameter to assess

    the MRF performance. Indeed, it can be checked easily by field evidence in the

    aftermath of earthquakes as well as in experimental tests. So far, several researchers

    [Leelataviwat et al., 1999, Maison and Bonowitz, 1999] have proposed different IDR

    values, as a function of the probability of exceedance and the acceptable damage.

    In this paper the IDR value of 4% [FEMA 350, 2000] was assumed as a rational

    and reliable limit for structural integrity.

    The overall stability under seismic loading implies that the structural system

    may preserve its vertical load-bearing capacity at the occurrence of an input ground

    motion that provokes both horizontal and vertical vibrations and hence correspon-

    dent inertial forces. Indeed, P effects of each storey of the structure can be

    evaluated by means of the stability index ; in the present study the limit value of

    0.30 was assumed to be the critical threshold for .

    The occurrence of both local (i.e. soft storey) and global mechanisms was also

    checked. It is worth pointing out that, while a global mechanism failure mode can

    occur if there is not a concentration of deformation and strength demand anywhere

    in the frame (thus both IDR and -values are less than the limit values), the local

    mechanism is likely to be associated with the achievement of the ULSs specified

    above, e.g. inter-storey drift and storey stability index.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    480 E. Mele, L. Di Sarno & A. De Luca

    Finally, a strength degradation criterion, corresponding to a drop of 10% in

    the frame lateral resistance, was also considered. It is well known that a global

    force-displacement response characterised by a final negative slope occurs when

    P effects significantly affect the structural behaviour. Despite the decrease in

    the lateral resistance which does not imply failure in itself, the response tends to

    be unstable and unreliable, thus the above limit criterion was assumed and checked

    for the MRFs.

    6.2. Analysis results

    Pushover curves provided in Figs. 3 and 4 for low- and medium-rise frames respec-

    tively, confirm that frame designs were governed primarily by stiffness requirements.

    Indeed, UBC inter-storey drift limit, e.g. 1/400, intercepts the curves at base shears

    equal or greater than design values (VUBC). Furthermore, pushover curves provide

    information on structural over-strengths, deformation capacity and importance of

    P effects.

    Values of design, yield and ultimate base shear (respectively VUBC, Vy , Vu) are

    depicted on the curves by means of triangular, square, and circular markers, respec-

    tively; the same shear values, normalised to the tributary seismic weight, W , are

    reported in Table 11 for perimeter and spatial frames, together with the coefficients:

    y (design over-strength, equal to the ratio Vy/VUBC), u (global over-strength,

    equal to the ratio Vu/VUBC), and u/y (system over-strength).

    The ultimate strength, Vu, is the value of base shear corresponding to the struc-

    tural collapse, which has been conventionally defined as the minimum of a set of

    ULSs, as presented earlier.

    For all MRF buildings, particularly the spatial ones, a significant over-strength

    above the design base shear VUBC (allowable stress design level) can be observed.

    In particular, a global over-strength u, ranging between 3.55 (LA-3P) and 5.81

    (SE-3S) for three-storey buildings and between 3.13 (SE-9P) 7.59 (BO-9S) for

    nine-storey buildings can be derived from the curves.

    Global over-strength, given by the u coefficient, arises from different sources

    which can be quantified through the coefficients y and u/y. The contribution

    quantified by the y multiplier, which has been appointed as design over-strength,

    is partially related to the ratio of yield to allowable stress (about 1.5) and partially

    related to the fulfilment of drift limitations as well as to SCWB requirements.

    Furthermore, stress redistribution within member cross sections, which can be

    related to section shape factor (plastic-to-elastic modulus ratio, approximately 1.15

    for wide flange sections) is also to be considered. For over-strength contribution

    quantified by u/y, appointed as system over-strength, redistribution of internal

    forces among the structural system members is the primary source.

    By comparing the push-over curve response and the values provided in Table 11,

    it may be concluded that global and system over-strengths, namely u and u/y,

    for spatial frames are higher than for their perimeter counterparts.

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    481

    Table 11. Results from push-over curves (Triangular Distribution).

    Perimeter Spatial

    Frame du/dy Vy/VUBC Vu/Vy Vu/VUBC ULS du/dy Vy/VUBC Vu/Vy Vu/VUBC ULS

    LA-3 4.71 2.63 1.35 3.55 Mech. (g) 4.48 3.00 1.97 5.27 Mech. (g)SE-3 2.64 3.24 1.24 4.03 Mech. (g) 2.86 3.91 1.49 5.81 3% (b)BO-3 2.76 3.79 1.26 4.77 3% (c) 3.21 3.39 1.64 5.60 3% (b)

    LA-9 4.10 2.52 1.40 3.54 3% (b) 3.77 1.81 2.12 3.84 3% (b)SE-9 3.53 2.65 1.18 3.13 3% (b) 2.55 3.41 1.27 4.37 3% (b)BO-9 1.52 4.99 1.07 5.30 4% (1) 2.73 5.20 1.47 7.59 3% (b)

    Keys: 3% = TPR; 4% = IDR; (b) = beam; (c) = column; g = global; (1) = first storey.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    482 E. Mele, L. Di Sarno & A. De Luca

    It is also interesting to note that, although the two alternative configurations

    exhibit nearly similar yield strength, i.e. similar design over-strength y, perime-

    ter frame curves possess a sharp transition between elastic branch and the sub-

    sequent yield plateau. By contrast, such a transition is quite smooth for spatial

    configurations. As was observed in recent studies [Gupta and Krawinkler, 2000a],

    such a sharp transition is a consequence of the low relative importance of gravity

    moments in the beams of perimeter frames (high ratio of seismic to gravity loads). It

    is worth mentioning that the smoother the transition, the higher is the probability

    of high local ductility demands.

    The deformation parameters identified on pushover curves are roof drift val-

    ues at the onset of yield (dy) and at ULS (du), respectively. Both perimeter and

    spatial frames are characterised by a similar translation ductility (du/dy), with val-

    ues ranging between 2.64 (SE-3P) and 4.71 (LA-3P) for low-rise frames, and 1.52

    (BO-9P) and 4.10 (LA-9P) for medium rise frames. Furthermore, the storey drifts

    experienced by nine-storey perimeter and spatial frames at similar values of dtopcan be explained on the basis of their different deformed shapes estimated at dyand du, respectively.

    For spatial frames, the fulfilment of SCWB requirement was a specific design

    target which led to a limitation of negative stiffness branch in the push over curves

    (reduced P sensitivity). Indeed, the comparison between perimeter and spatial

    BO frames, show that the latter reaches higher ultimate displacements than the

    former, without showing significant strength loss. This result relates to low- and

    medium-rise frames; nevertheless, it is critical in medium-rise frames (Fig. 4).

    A further comparison of inelastic static performance for perimeter and spatial

    frames may be derived by considering the governing ULSs, as listed respectively in

    the sixth and eleventh columns of Table 11. Such ULSs are the onset of 3% plastic

    rotations in beams and global mechanisms for perimeter and spatial typologies;

    BO-3P exhibits 3% rotation in the columns, whilst BO-9P is characterised by a

    high IDR.

    It is instructive to correlate the values of the elastic critical multiplier for vertical

    loads to the slope of the descending branch of push-over curves (Figs. 3 and 4).

    As already observed, low-rise perimeter and spatial structures (three-storey) do

    not suffer any instability problem since the critical multiplier of vertical loads is

    consistently greater than 10. By contrast, some differences arise for the medium rise

    frames (nine-storey). LA-9P and LA-9S possess nearly the same critical multiplier

    (15.5 versus 16.5, respectively), thus negligible P effects are expected in both

    cases. For BO-9S a significant improvement in the P resistance with respect to

    the perimeter frame can be observed. Indeed, a comparison between the slope of the

    softening branch of the perimeter and spatial curves shows a significantly reduced

    slope for the BO-9S, corresponding to the increase in the critical multiplier value

    from about 6 (perimeter) to about 8 (spatial). This improved structural response

    is also confirmed by inelastic dynamic analyses, as discussed in the next section.

    Although perimeter and spatial configurations behave in a similar fashion in terms

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 483

    of global behaviour, e.g. same top displacement, the inter-storey drifts and plastic

    rotation demands in beams and columns are lower for the spatial than for the

    perimeter solution.

    7. Inelastic Time History Analysis

    The present study was focused on the non-linear global response and behaviour of

    the structure rather than on the detailed performance of any of its elements. To

    this end, emphasis was placed on investigating the beam and column maximum ro-

    tations, storey displacements and storey drift ratios. Inelastic time history analyses

    were performed on the set of three-storey and nine-storey perimeter and spatial

    frames by means of the computer program DRAIN 2DX [Prakash et al., 1993]. The

    aim is to evaluate and compare the seismic demand along the height for the sample

    structures. The analyses were carried out by employing three acceleration histories

    with different characteristics. The latter were derived from actual records of the El

    Centro, Northridge and Kobe earthquakes.

    It is worth mentioning that the design seismic loads adopted for the buildings

    at three locations (LA, SE, BO) were quite different, since they correspond to three

    different seismic hazard zones (namely, Z = 0.40 for LA, Z = 0.30 for SE, and

    Z = 0.15 for BO). Nevertheless, the same ground motions, representative of severe

    seismic input, were used for the seismic performance evaluation of the three sets of

    buildings. The choice of this approach in the analyses is related to several reasons,

    as specified in the following.

    The choice of an accelerogram is a very complex task due to the uncertainties

    involved. At the same site, as a result of the same source, the ground motions may

    be very different in character for different events. The use of artificial ground mo-

    tions, which can be generated with peak ground acceleration (PGA) matching those

    specified for the seismic zone, may be questionable due to the poor frequency con-

    tent of the generated acceleration history when compared to actual seismic records

    [Broderick and Elnashai, 1996]. Furthermore, the use of scaled natural records,

    obtained by either amplifying or reducing the PGA without changing other char-

    acteristics (periods, duration, velocities, etc.) is also debatable [Bommer and Scott,

    2000].

    Finally, the analysis of the MRF design process, carried out in Secs. 4 and

    5, has shown that stiffness, SCWB and stability, rather than strength (i.e. value

    of the design base shear), are the governing design issues. Thus, a satisfactory

    performance even under severe earthquakes, can be expected for MRF buildings

    when the above design issues have been addressed, independently of the seismic

    zone. Due to the fundamental period of vibration, i.e. 0.99 sec to 3.56 sec, a set

    of accelerograms with near- and far-field effects were selected for the nonlinear

    dynamic analyses. The latter were, however, conducted by using the same un-scaled

    historical records for all MRF buildings.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    484 E. Mele, L. Di Sarno & A. De Luca

    Table 12. Characteristics of ground motions.

    Earthquake Date Station Component Duration (sec) PGA (g)

    Imperial Valley 18.5.40 El Centro S00E 53.80 0.348

    Northridge 17.1.94 Newhall 340N/118W 59.98 0.583

    Hyogoken-Nanbu 17.1.95 Kobe EW3 56.40 0.834

    7.1. Ground motions

    The main properties of the ground motions adopted in the time-history analyses

    are summarised in Table 12. The selected ground motions cover a wide earthquake

    scenario because of their different characteristics in terms of frequency content

    and peak ground accelerations. The classical El Centro record exhibits a broad

    frequency range, whilst the Northridge and Kobe ground motions are representative

    of near-fault effects, especially in their few large pulses with a short duration.

    By superimposing the 5% damping elastic spectra upon the acceleration spectra

    of the considered records (Fig. 5) it may be observed that the UBC-94 spectrum

    (soil type S2, relative to LA) under-estimates the ordinates derived from Northridge

    and Kobe between 0.25 and 0.40 sec. By contrast, the smoothed spectra is more

    conservative in the long period range (specifically for T > 2.0 sec).

    7.2. Analysis results

    7.2.1. Global drifts

    Comparisons between maximum top displacements (adimensionalised to the total

    building height, H) of perimeter and spatial frames computed via time history

    analyses are provided in Fig. 6. Low-storey frames exhibit drift ratios greater than

    1%; in fact, the values range between 1.16% and 3.75%. Perimeter MRFs are less

    flexible than their spatial counterparts; the latter are characterised by an average

    Dtot/H value equal to 2.44% versus 1.83% computed for the former. The drift ratios

    vary as a function of the earthquake, El Centro and Kobe being respectively the

    least and the most demanding. The values of Dtot/H for medium-rise perimeter

    configurations range between 0.95% (LA-9P), and 1.55% (SE-9P). These values are

    much smaller than the three-storey counterparts due to the longer periods of the

    nine-storey frames and the shape of the spectral acceleration curves of the given

    records.

    It is interesting to point out that, except for LA, the maximum nondimensional

    top displacements exceeds 1.00%. The highest values for the BO and SE frames are

    induced by Newhall, whilst by Kobe for the LA frame. The drifts tend to be more

    uniform and hence less dependent upon the input earthquake than the three-storey

    frames. The range of variability is relatively narrow (1% to 1.5%).

    The spatial configuration is characterised by roof displacements similar to

    perimeter frames; by comparing the average values the difference is around 5%. The

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    485

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    3.0

    0.0 1.0 2.0 3.0 4.0 5.0

    ElCentro Kobe New ha ll UBC (Z= 0.40)

    T(sec)

    S

    a

    (

    g

    )

    0.0

    0.5

    1.0

    1.5

    2.0

    0.0 1.0 2.0 3.0 4.0 5.0

    ElCentro Kobe New hall UBC (Z=0.40)

    T(sec)

    S

    V

    (

    m

    /

    s

    e

    c

    )

    Fig. 5. Acceleration (left) and velocity (right) spectra.

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    486

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    LA -3P LA -3S SE-3P SE-3S BO-3P BO-3S

    ElCentro

    Newhall

    Kobe

    Three- Storey

    D

    t

    o

    p

    /

    H

    t

    o

    t

    (

    %

    )

    ! ! ! !

    ! ! ! !

    ! ! ! !

    " " " "

    " " " "

    " " " "

    # # # #

    # # # #

    # # # #

    $ $ $ $

    $ $ $ $

    $ $ $ $

    % % % %

    % % % %

    % % % %

    & & & &

    & & & &

    & & & &

    & & & &

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    LA -9P LA -9S SE-9P SE-9S BO-9P BO-9S

    ' ' ' '

    ElCentro

    ( ( (

    Newhall

    ) ) )

    Kobe

    Nine-Storey

    D

    t

    o

    p

    /

    H

    t

    o

    t

    (

    %

    )

    Fig. 6. Roof drifts for perimeter and spatial MRFs: three-storey (left) and nine-storey (right).

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 487

    minimum and maximum values are 0.84% (LA-9S) and 1.52% (SE-9S), which are

    comparable with the narrow range, e.g. 1% to 1.5%, evaluated earlier for perimeter

    frames.

    7.2.2. Inter-storey drifts

    A comparison of inter-storey displacements is provided in bar-chart format in Fig. 7.

    Inter-storey drift is adimensionalised with regard to inter-storey height (d/h).

    The results show that the maximum drifts are generally lower than the thresh-

    old value of 4%, corresponding to an inter-storey drift capacity (IDC) for MRFs

    classified as special [FEMA 350, 2000]. Values beyond 4% occur for the Kobe earth-

    quake, which frequently gives rise to high values of inelastic deformation demand.

    The major issues mentioned earlier for top displacements are confirmed from the

    drift results. However, a critical assessment of inter-storey drift values can pro-

    vide further information on the localisation of the plastic demand throughout the

    structural system.

    Medium-rise spatial frames exhibit d/h values (Fig. 7) on average lower than

    the perimeter ones. The results for the LA frame do not follow the same trend. The

    inter-storey drifts computed for spatial configurations are always lower than for the

    perimeter (except for LA). The scatter is lower for the spatial frames (1.40% and

    3.50% are the minimum and maximum values of d/h) than for perimeter frames

    (1.36% and 4.66% are the correspondent minimum and maximum d/h).

    It is remarkable to highlight that in high (LA) and medium (SE) seismic areas,

    the demand tends to be uniformly distributed, whilst a large variation characterises

    the response of BO frames (low seismicity). The latter is due to the assumptions

    adopted in the design. In the case of BO perimeter frames the SCWB require-

    ments are not fulfilled, but they are fulfilled for the spatial configuration. Thus,

    different plastic rotation demands are expected for such alternative configurations.

    The envelope of the distribution of the plastic rotations along the height of BO-9P

    shows that a concentration of plastic demand affects the first floor, thus leading to

    a soft storey mechanism. Similar envelopes, for the other frames, demonstrate that

    no soft mechanisms occur and the maximum plastic excursions affect the upper

    storeys, without any detrimental effect on the global hysteretic dissipation.

    The maximum inter-storey drifts for low-rise buildings are provided in Fig. 7.

    By comparing the results, it may be observed that spatial frames exhibit higher

    values of inter-storey drift (minimum d/h = 1.62% and maximum d/h = 5.06%);

    the highest values, greater than 4.5%, occurs for the Kobe record. For the perimeter

    frames a reduced variation of drift values is found. LA-3P experiences d/h = 1.70%

    for the El Centro record, whilst the maximum value is 3.83% and is due to BO-3P

    (Kobe ground motion).

    7.2.3. Plastic rotations

    Maximum plastic rotations for both perimeter and spatial typologies and low-to-

    medium rise buildings are provided below with regard to the beams (Fig. 8) and

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    488

    E.M

    ele,L.D

    iSarn

    o&

    A.D

    eLuca

    * * * *

    * * * *

    * * * *

    * * * *

    + + + +

    + + + +

    + + + +

    + + + +

    , , , ,

    , , , ,

    , , , ,

    , , , ,

    - - - -

    - - - -

    - - - -

    - - - -

    - - - -

    . . . . .

    . . . . .

    . . . . .

    . . . . .

    . . . . .

    / / / /

    / / / /

    / / / /

    / / / /

    0 0 0 0

    0 0 0 0

    0 0 0 0

    0 0 0 0

    1 1 1 1

    1 1 1 1

    1 1 1 1

    1 1 1 1

    1 1 1 1

    2 2 2 2

    2 2 2 2

    2 2 2 2

    2 2 2 2

    2 2 2 2

    3 3 3 3

    3 3 3 3

    3 3 3 3

    3 3 3 3

    3 3 3 3

    3 3 3 3

    4 4 4 4 4

    4 4 4 4 4

    4 4 4 4 4

    4 4 4 4 4

    4 4 4 4 4

    4 4 4 4 4

    5 5 5 5

    5 5 5 5

    5 5 5 5

    5 5 5 5

    5 5 5 5

    5 5 5 5

    6 6 6 6

    6 6 6 6

    6 6 6 6

    6 6 6 6

    6 6 6 6

    6 6 6 6

    6 6 6 6

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    7 7 7 7

    8 8 8 8

    8 8 8 8

    8 8 8 8

    8 8 8 8

    8 8 8 8

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    9 9 9 9

    : : : :

    : : : :

    : : : :

    : : : :

    : : : :

    : : : :

    : : : :

    : : : :

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    ; ; ; ;

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    LA -3P LA -3S SE-3P SE-3S BO-3P BO-3S

    < < < > > >

    Kobe

    Three-Storey IDC

    d

    i

    n

    t

    /

    h

    i

    n

    t

    (

    %

    )

    ? ? ? ?

    ? ? ? ?

    ? ? ? ?

    @ @ @ @

    @ @ @ @

    @ @ @ @

    @ @ @ @

    @ @ @ @

    A A A A

    A A A A

    A A A A

    A A A A

    B B B B

    B B B B

    B B B B

    B B B B

    B B B B

    C C C C

    C C C C

    C C C C

    C C C C

    C C C C

    C C C C

    D D D D

    D D D D

    D D D D

    E E E E

    E E E E

    E E E E

    E E E E

    F F F F

    F F F F

    F F F F

    F F F F

    F F F F

    G G G G G

    G G G G G

    G G G G G

    G G G G G

    G G G G G

    G G G G G

    H H H H

    H H H H

    H H H H

    H H H H

    H H H H

    I I I I

    I I I I

    I I I I

    I I I I

    I I I I

    I I I I

    I I I I

    I I I I

    I I I I

    J J J J

    J J J J

    J J J J

    J J J J

    J J J J

    K K K K

    K K K K

    K K K K

    K K K K

    K K K K

    K K K K

    L L L L

    L L L L

    L L L L

    L L L L

    L L L L

    L L L L

    L L L L

    M M M

    M M M

    M M M

    M M M

    M M M

    M M M

    M M M

    N N N N

    N N N N

    N N N N

    N N N N

    N N N N

    N N N N

    O O O O

    O O O O

    O O O O

    O O O O

    O O O O

    O O O O

    O O O O

    O O O O

    P P P P

    P P P P

    P P P P

    P P P P

    P P P P

    P P P P

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    LA -9P LA -9S SE-9P SE-9S BO-9P BO-9S

    Q Q Q

    ElCentro

    R R R R

    Newhall

    S S S

    Kobe

    IDCNine-Storey

    d

    i

    n

    t

    /

    h

    i

    n

    t

    (

    %

    )

    Fig. 7. Inter-storey drifts for perimeter and spatial MRFs: three-storey (left) and nine-storey (right).

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    489

    T T T T

    T T T T

    T T T T

    U U U U

    U U U U

    U U U U

    V V V V

    V V V V

    V V V V

    W W W W

    W W W W

    W W W W

    W W W W

    W W W W

    X X X X

    X X X X

    X X X X

    X X X X

    Y Y Y Y

    Y Y Y Y

    Y Y Y Y

    Y Y Y Y

    Y Y Y Y

    Z Z Z Z

    Z Z Z Z

    Z Z Z Z

    [ [ [ [

    [ [ [ [

    [ [ [ [

    [ [ [ [

    [ [ [ [

    \ \ \ \

    \ \ \ \

    \ \ \ \

    \ \ \ \

    ] ] ] ]

    ] ] ] ]

    ] ] ] ]

    ] ] ] ]

    ] ] ] ]

    ] ] ] ]

    ^ ^ ^ ^

    ^ ^ ^ ^

    ^ ^ ^ ^

    ^ ^ ^ ^

    _ _ _ _ _

    _ _ _ _ _

    _ _ _ _ _

    _ _ _ _ _

    _ _ _ _ _

    _ _ _ _ _

    _ _ _ _ _

    ` ` `

    ` ` `

    ` ` `

    ` ` `

    ` ` `

    ` ` `

    ` ` `

    a a a a

    a a a a

    a a a a

    a a a a

    a a a a

    a a a a

    a a a a

    a a a a

    b b b b

    b b b b

    b b b b

    b b b b

    b b b b

    b b b b

    b b b b

    b b b b

    b b b b

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    d d d

    d d d

    d d d

    d d d

    d d d

    d d d

    d d d

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    e e e e

    0.00

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    LA -3P LA -3S SE-3P SE-3S BO-3P BO-3S

    f f f

    ElCentro

    g g g g

    Newhall

    h h h

    Kobe

    m

    a

    x

    (

    r

    a

    d

    )

    TPRThree-Storey

    i i i i

    i i i i

    i i i i

    j j j j

    j j j j

    j j j j

    j j j j

    j j j j

    k k k k

    k k k k

    k k k k

    l l l l

    l l l l

    l l l l

    l l l l

    m m m m

    m m m m

    m m m m

    n n n n

    n n n n

    n n n n

    o o o o

    o o o o

    o o o o

    p p p p

    p p p p

    p p p p

    p p p p

    q q q q

    q q q q

    q q q q

    q q q q

    q q q q

    r r r r

    r r r r

    r r r r

    s s s s

    s s s s

    s s s s

    t t t t

    t t t t

    t t t t

    u u u u

    u u u u

    u u u u

    u u u u

    u u u u

    v v v v

    v v v v

    v v v v

    v v v v

    v v v v

    v v v v

    w w w w

    w w w w

    w w w w

    w w w w

    w w w w

    x x x

    x x x

    x x x

    x x x

    x x x

    y y y y

    y y y y

    y y y y

    y y y y

    y y y y

    y y y y

    y y y y

    z z z z

    z z z z

    z z z z

    z z z z

    z z z z

    0.00

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    LA -9P LA -9S SE-9P SE-9S BO-9P BO-9S

    { { {

    ElCentro

    | | |

    Newhall

    } } }

    Kobe

    TPR

    Nine-Storey

    m

    a

    x

    (

    r

    a

    d

    )

    Fig. 8. Beam plastic rotations for perimeter and spatial MRFs: three-storey (left) and nine-storey (right).

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    490 E. Mele, L. Di Sarno & A. De Luca

    columns (Fig. 9). In all bar charts the threshold of 0.03 rad (3%), target plastic

    rotation (TPR) of beam-to-column connections as defined within the SAC Steel

    Project [FEMA 350, 2000], is drawn.

    The end beam rotations for medium rise perimeter frames (Fig. 8) range from

    a lower bound of 1.01% (LA-El Centro) to an upper limit of 3.33% (BO-Kobe).

    Kobe is the most severe earthquake case: for all seismic zones the beams undergo

    plastic rotations greater than 2%. By contrast, the least demanding record is El

    Centro; it gives rise to plastic rotations of 1.07% on BO, 1.01% for LA and 1.12%

    in SE frame. Intermediate values ranging between 1.25% (LA) and 2.22% (SE) are

    induced by Newhall ground motion.

    A smoothed variation characterises the plastic demands on nine-storey spatial

    frames. The minimum plastic rotation was computed for BO-El Centro (1.23%)

    while the maximum (3.15%) is reached in the LA frame when the Kobe record is

    considered. The two sets of values show that, except for Kobe, the plastic rotation

    demands are lower than the 3% TPR required by SAC. The latter is a direct

    consequence of the SCWB fulfilment, adopted as a specific design target for spatial

    frames.

    Maximum plastic rotations in low-rise perimeter and spatial MRFs are also

    provided (Fig. 8). The values of inelastic demands in the beams of perimeter and

    spatial MRFs are quite close and do not generally overcome the 3% limit value.

    The Kobe earthquake provokes the largest plasticity in the beams of BO and SE

    frames (respectively 5.13% and 5.50%). These results may be justified in the light

    of the frequency content of Kobe. It is particularly severe in the neighbourhood of

    natural periods of low-rise frames. High values of beam rotations can be found in

    the case of perimeter as well as spatial frames; they were deliberately designed with

    similar fundamental periods.

    For the sake of completeness, the maximum plastic rotations in the column

    elements of the nine- and three-storey frames, both perimeter and spatial, are also

    considered. In the case of perimeter configurations (Fig. 9) the nine-storey Boston

    frame is characterised by relevant plastic demands, especially with regard to the case

    of the Newhall record (maximum rotation 3.53%), that corresponds to the highest

    demand for the perimeter configuration. The behaviour of the column elements

    of the LA perimeter frame is almost elastic, since the maximum value is equal to

    0.08%. The comparison with the spatial configurations suggests that for all but the

    LA and SE frames under the Kobe ground motion, the columns are in the elastic

    range.

    The values for the column plastic rotations of the three-storey frames are also

    shown in Fig. 9. The scenario outlined is quite different from the aforementioned,

    with regard to the spatial frames where the adopted design philosophy is slightly

    different from that adopted for the nine-storey spatial frames. While the plastic

    rotations required in the columns of the spatial configuration are lower than in

    perimeter layouts, some plastifications in the columns occur. Nevertheless, since

  • Feb

    ruary

    11,2004

    15:4

    7W

    SP

    C/124-J

    EE

    00136

    Seism

    icBehavio

    ur

    ofPerim

    ete

    rand

    Spatia

    lStee

    lFra

    mes

    491

    ~ ~ ~ ~

    0.00

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    LA -3P LA -3S SE-3P SE-3S BO-3P BO-3S

    ElCentro

    Newhall

    Kobe

    m

    a

    x

    (

    r

    a

    d

    )

    TPR

    Three-Storey

    0.00

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    LA -9P LA -9S SE-9P SE-9S BO-9P BO-9S

    ElCentro

    Newhall

    Kobe

    TPR

    Nine-Storey

    m

    a

    x

    (

    r

    a

    d

    )

    Fig. 9. Column plastic rotations perimeter and spatial MRFs: three-storey (left) and nine-storey (right).

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    492 E. Mele, L. Di Sarno & A. De Luca

    the design was based upon the fulfilment of SCWB, the maximum plastic rotations

    take place in the base column ends.

    The comparison between inter-storey drifts (Fig. 7) and beam plastic rotations

    (Fig. 8) shows close values for both set of data (low-to-medium rise and perimeter-

    spatial), especially for SCWB frames. It is, therefore, confirmed, as in previous

    studies [Mele et al., 1995], that plastic rotation can be predicted via the inter-

    storey drift index. Inelastic inter-storey drift can be related to the elastic inter-

    storey drift by means of the displacement amplification factor Cd, thus a reasonable

    prediction of plastic rotation demands can be obtained by means of a simple elastic

    analysis.

    7.2.4. Hysteretic energy

    Inelastic time history analyses also indicate the hysteretic energy dissipated during

    the ground motions. In Fig. 10 the energy time histories for perimeter and spatial

    Fig. 10. Hysteretic energy diagrams: three-storey (left) and nine-storey (right) MRF buildings.

  • February 11, 2004 15:47 WSPC/124-JEE 00136

    Seismic Behaviour of Perimeter and Spatial Steel Frames 493

    MRF buildings, under the El Centro, Newhall and Kobe seismic inputs, are pro-

    vided. They were computed by considering the energy dissipated by each MRFs and

    accounting for the actual number of frames used to withstand horizontal forces.

    It can be observed that the energy dissipated by the three pairs (LA, SE and BO)

    of buildings configurations (perimeter, spatial) is quite close. The total dissipated

    energy is a function of the building natural period and of the earthquake ground

    motion.

    With regard to the ground motion, Newhall represents the worst case scenario

    for the set of assessed buildings: the energy varies in the range 5000 kNm (BO-

    3) and 10 000 kNm (LA-9). Due to the higher values of beam plastic rotations

    (greater than 4%) and inter-storey drifts (around 3%) SE-3 MRFs dissipate a large

    amount of energy; the maximum values are comparable to the LA counterparts.

    These results were also found for medium-rise buildings; in this case, though, the

    influence of higher-mode effects gives rise to more complex responses. Concerning

    the dependence of the hysteretic energy on the building natural period, it may be

    observed that lower energy values can be found for longer period buildings (e.g.:

    BO-9 versus LA-9), as a consequence of a sort of self-isolation effect. As a result,

    the energy dissipated by the three pairs (LA, SE and BO) of buildings configurations

    (perimeter, spatial) is quite close. Therefore, it can be argued also that in terms of

    hysteretic energy, the dynamic response of the perimeter and spatial MRFs is fairly

    similar; thus, their equivalent behaviour is confirmed.


Recommended