1 | Page ATTACHMENT B STRUCTURED CABLING SYSTEM SPECIFICATIONS For City of Torrance Torrance Transit Crenshaw
Transcript
Page 1: STRUCTURED CABLING SYSTEM SPECIFICATIONS

1 | P a g e

ATTACHMENT B

STRUCTURED CABLING

SYSTEM SPECIFICATIONS

For

City of Torrance

Torrance Transit Crenshaw

Page 2: STRUCTURED CABLING SYSTEM SPECIFICATIONS

2 | P a g e

Scope of Work

1. Contractor shall provide all labor, materials, tools and equipment required for the

complete installation of work called for in the Construction Documents unless

explicitly instructed otherwise by your company.

2. Contractor shall be solely responsible for all parts, labor, testing, documentation and

all other associated processes and physical apparatus necessary to turn-over the

completed system fully warranted and operational for acceptance by City of Torrance.

3. Contractor shall provide performance verification testing of all installed cabling using up to

date and industry accepted test equipment appropriate to the types of cables being

tested. All testers used shall be factory calibrated within one year of use with

references set daily prior to testing.

4. Contractor shall provide valid test data in PDF or Excel format and a bound hard copy

indicating passing of all installed cabling.

5. Contractor shall provide all equipment brands and models are specified within this

document.

Page 3: STRUCTURED CABLING SYSTEM SPECIFICATIONS

3 | P a g e

PROJECT BASIC ELEMENTS

Installation

Install or utilize existing adequately sized and routed cable support pathway “systems”

throughout the ceiling areas wherever necessary to support new cabling.

Install and terminate the new cabling onto the appropriate jacks at the end location and on

the appropriate patch panels in the appropriate IDF/Data Center.

Wiring termination scheme for all CAT6 is 568-B.

Labeling

Utilize the labeling system that complies with TIA 606-A standards and the City’s needs. The

City using a specific labeling method (see page 5).

Testing

Test and certify each cable drop per the TIA 568 B-2 testing standards for Category 6 cabling.

Provide the City with hardcopy test results in a 3-ring binder and thumb drive.

Certification

Coordinate manufacturer certification and provide the City of Torrance CIT Dept. with

manufacturer certification/warranty documentation (if required by contract).

Warranty

Provide minimum one year labor and workmanship warranty.

Page 4: STRUCTURED CABLING SYSTEM SPECIFICATIONS

4 | P a g e

Materials Used

The City requests CommScope brand cable and CommScope brand connectors, faceplates,

and patch panels, on this project. Any substitutions not mentioned in this document must be

approved by City of Torrance Telecom.

Cables must be continuous in length, contain no splices, kinks or damage and cannot exceed

90 meters in length between workstation jacks and patch panel. No ty-wraps. Velcro only.

All interior cables will be Plenum-rated (CMP) Cables that run into a Data Center must be

100% Plenum even if in conduit.

Station Data Cable, WIFI devices, and TV/Monitor/Projector network connections for this

project will be CAT6 green jacket color.

Station RJ-45 Data locations will be terminated on rack mounted patch panels at IDF/Data

Room. Contact City of Torrance CIT Dept. for rack location approval.

Station Voice Cable for this project will be white jacket color.

All Voice Cables will be terminated on a Siemon 66 punch down block mounted on an IDF

backboard using standoff mounting blocks. Contact City of Torrance CIT Dept. for backboard

location approval.

Security Camera CAT6 Cables will be yellow jacket color. These will be terminated on a

separate patch panel below station cabling. Contact City of Torrance CIT Dept. for rack

location approval.

PA System CAT6 cabling will be grey jacket color. These will be terminated on a separate

patch panel below station cabling. Contact City of Torrance CIT Dept. for rack location

approval

Patch panels will be either 24 or 48-port.

All Data jacks terminated in 6 port faceplates will be green. Voice Jacks will be white.

One cable is to be split for 2 RJ11 jacks per faceplate. W/BL only would be first jack. W/GR

only would be second jack. Wrap the remaining two pairs around the sheath.

Faceplates, surface boxes, furniture outlets, etc. will be white in color.

Page 5: STRUCTURED CABLING SYSTEM SPECIFICATIONS

5 | P a g e

Any and all penetrations in walls or ceilings must be sleeved. Sleeves must meet minimum

fire standards where they are installed in fire walls or barriers.

Terminated CAT6 cabling must be terminated in numerical sequence on the patch panels

starting at 001 continuing on to end of patch panel. Each type of device/cable color will be

terminated on its own patch panels with its own numbering. Example: Station and Wi-Fi :

Green 1- 144, Security Cameras : Yellow 1-48, Etc. It is not necessary to have the cable

numbers in the work areas in sequential order unless the contractor wishes to do so.

The labeling scheme will be the Transit Center (TC), the Floor (1), the floor telephone room (1)

and the cable number 001 through 144. Therefore at the faceplate you would put the closet

number at the top, (example: TC 1.1) then the top two voice cables would share a number

taken from the 66 block location (example: V-1) and the data jacks at bottom of the faceplate

would show their positions on the patch panel and be marked below each jack. (Example: D-

1 and D-2).

Voice cabling will be used at all locations with a phone only or combined phone/data

faceplates. The numbering will be sequential 1, 2, 3 etc. on each 66 block. (Example the first

4 pair cable would be 1, the second four pair cable would be 2, etc.)

All Cables must be labeled appropriately in four (4) places:

1) At the Work station jack visible to technicians and other staff looking at the jack. This

label should be a machine-generated label such as a P-Touch label or Rhino label and be

affixed to the jack below the RJ-45 port.

2) At the Work station jack, on the cable sheath 2 inches before where the cable sheath

is stripped away. This label may either be a machine-generated label such as a P-Touch label

or be made with a Sharpie Fine-Point permanent marker. This label will only be visible when

the jack is disassembled.

3) At the front of the patch panel, on the patch-panel port covering the originally

stenciled numbers (whether above or below), where it is easily visible to personnel. This label

should be a machine-generated label such as a P-Touch label or Rhino label.

4) At the rear of the patch panel on the cable sheath approx. 6 inches or so before the

cable sheath is stripped away and the cable is terminated. This label may either be a

machine-generated label or be made with a Sharpie Fine-Point permanent marker.

Page 6: STRUCTURED CABLING SYSTEM SPECIFICATIONS

6 | P a g e

Applicable Standards

The following industry standards are the basis for the structured cabling system

described in this document. The list is incorporated by this reference to them.

TIA/EIA-568-C (Commercial Building Telecommunications Cabling Standard)

TIA/EIA-569-A (Commercial Building Standard for Telecom, Pathways and Spaces)

TIA/EIA-606 (Administration Standard for the Telecommunications, Infrastructure of

Commercial Buildings)

TIA/EIA-607 (Commercial Building Grounding/Bonding Requirements)

1.2.2. NFPA

NFPA-70 (National Electric Code (NEC) -1999)

ISO/IEC 11801 (Generic Cabling for Customer Premises)

1.2.4 IEEE 802.3an (Physical Layer and Management Parameters for 10 Gb/s Operation, Type

10GBASE-T)

The most recent versions of all documents apply to this project.

If there is a conflict between applicable documents, the order above shall dictate the

order of precedence in resolving the issue unless an enforceable local or national

code is in effect.

Page 7: STRUCTURED CABLING SYSTEM SPECIFICATIONS

7 | P a g e

PATHWAYS

ANSI/TIA reference 569-B

As part of this project, the Contractor is required to plan out and establish a TIA-569-B

compliant pathway and support “system” to properly accommodate new cabling. The

Contractor shall work closely with the General Contractor’s representative to establish this

pathway system to make sure it meets the needs of the City both now and in the future.

These new pathways must be properly routed through the ceiling areas and fastened to the

building structure in ways that do not violate the TIA building standards, the NFPA 70 NEC

and any other industry “standard” or practice.

ON-SITE SUPERVISOR/PROJECT COORDINATOR

The City requires that a Project Coordinator or Lead-person be assigned to this project and be

present the entire time work is going on. This person must have experience in the installation

and maintenance of a commercial high performance cabling system. They must also be

familiar with the TIA cabling standards, the NFPA 70 National Electrical code, BICSI standards

and practices and general building and construction knowledge and standards.

BICSI RCDD STAFF REQUIREMENT

The Contractor must have at least one full-time permanent employee on staff that is BICSI

RCDD certified and is available to the On-Site Supervisor/Lead Person running this project.

This person must be available for consultation should any issue arise.

EXTRA CABLING IN ACCESIBLE CEILING AREAS

The Contractor is to provide 4- Cat6 Data and 2- Voice cables, labeled, with approx. 20’ of

slack (neatly coiled in the ceiling and secured with Velcro) on each floor of both buildings.

These are to be pulled from the nearest IDF/Data Center to the farthest “accessible” ceiling

location near occupied spaces. These cables are to be numbered and properly terminated on

the Patch Panel (Cat6) or 66 block. They do not need to be jacked or certified.

Page 8: STRUCTURED CABLING SYSTEM SPECIFICATIONS

8 | P a g e

Approved Products (No substitutes without Torrance approval)

Patch Panels

CommScope CPP-UDDM-KJ-1U-24 Modular Panel Keystone Series 24 port

CommScope CPP-UDDM-HJ-2U-48 Modular Panel Keystone Series 48 port

Cabling

4 pair Plenum Cat 3 White (May substitute CAT5e/CAT6) (American made only, No offshore

cabling)

CommScope CS34P C6 4/23 U/UTP CPK 1KFT Category 6 "Media 6®" 250 MHz

Jacks

CommScope:

UKJ600- Uniprise UKJ Series Keystone Modular Jacks CAT6 (color matching cable jacket)

KJ510 Keystone Modular Jack CAT5e (for use with voice only)

May use as substitute for station cables, on Voice only:

41106-RW6 Leviton RJ11 Voice Grade Quickport Keystone Jack white

Voice wall jacks phone only

AT630A-6 Allen Tel Wall Phone Jack-Screw Terminal Stainless.

Station Faceplates

6-Port Faceplate with window- Keystone- Uniprise

Page 9: STRUCTURED CABLING SYSTEM SPECIFICATIONS

9 | P a g e

Station Cabling Exceptions

Transit East Building- Second Floor- Room 210 at each jack location along the perimeter walls

we request 2-voice and 4-CAT6 data jacks installed instead of the required 2-voice, 2-CAT6

data.

All ceiling Wi-Fi locations will have 2 data cables to each location, terminated, labeled and

tested.

Substitutions

Substitutions are highly discouraged. Substitutions must follow the same rigid standards for

quality and termination style as those products specified herein. Proof of equivalency is the

responsibility of the Contractor and must follow the procedure below.

Contractors wishing to offer structured cabling products other than those specified shall

submit a request for product substitution in writing.

Written requests for substitution shall be accompanied by all drawings, specification sheets

and engineering documents, as well as third party laboratory performance test results

proving equivalency in electrical and mechanical performance, as well as adherence to the

product features and manufacturing style outlined in this document.

This written documentation shall be accompanied by two each samples of the substitution

product being offered for evaluation. Equal product acceptance must be received from City of

Torrance Telecommunication Dept. in writing before substitutions are made.

Page 10: STRUCTURED CABLING SYSTEM SPECIFICATIONS

10 | P a g e

Scope of Copper Feed Work

General Description

The general description of the Scope of Work (SOW) for this project is to provide riser rated

CAT3 copper cabling at the Torrance Transit Crenshaw location. This cable will run from the

Data Center/MDF to the two IDF closets.

Product and Services Specifications

50 pair riser 24-25 UTP-CMR Solid Copper from Data Center/MDF to IDF on 2nd floor of East

Building

50 pair riser 24-25 UTP-CMR Solid Copper from Data Center/MDF to IDF on 1st floor of West

Building

Both ends terminated on M1-50 Siemon 66 punch down blocks mounted at MDF/ IDF

backboards using standoff mounting blocks.

Preferred cable manufactures General Cable, Superior Essex or Belden only.

Page 11: STRUCTURED CABLING SYSTEM SPECIFICATIONS

11 | P a g e

SCOPE OF FIBER WORK

General Description

The general description of the Scope of Work (SOW) for this project is to provide OM4 fiber

optic cabling at the Torrance Transit Crenshaw location. This fiber will run from the Data

Center/MDF to the two IDF closets.

Product and Services Specifications

12 Strands OS2 fiber to IDF on 2nd floor of East Building

12 Strands OS2 fiber to IDF on 1st floor of West Building

12 Strands OS2 fiber to Outside Cabinet near Bus Parking

Fiber must be from Corning’s product line and fusion spliced

To be terminated onto a 1U 19-inch rack mounted enclosure with Corning LC/UPC

Connectors.

The MDF/Data Center will have a single Corning rack mounted enclosure for all fibers

mentioned.

Changes to Scope of Work

Changes in the SOW shall be authorized by written “Change Order(s)”, signed by Torrance

Telecom.

Vendor Responsibilities

Furnish all labor, supervision, tooling, and miscellaneous mounting hardware for the fiber

system installed at the Transit Center.

Furnish, install, and terminate all fiber strands at each location according to the

manufacturer’s product and services specifications and best industry practices.

Develop and submit for approval a labeling system for the fiber installation. The labeling

system shall clearly identify all components of the system.

Page 12: STRUCTURED CABLING SYSTEM SPECIFICATIONS

12 | P a g e

Sample labels must be approved by the City.

Test (100%) all cables and termination hardware for defects in installation and certify fiber

performance

Supply documentation of testing and footage of each fiber strand installed both in a binder of

8.5 x11 paper and PDF or Excel format on a thumb drive.