Support systems Assembly instruction
Transcript
Page 1: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

Support systemsAssembly instruction

Page 2: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

2

Support systems | Light-weight designAssembly instruction

6 | Central suspension for wire mesh cable tray of up to 300 mm widthConnect the central hanger GBAG 20/30 to the dowel using sleeve VM M8*. Mount the tabs GV 30 as well as the profile rails together with the wire-mesh cable tray.

5 | Central suspension for wire-mesh cable tray of up to 100 mm widthConnect the central hanger GBAG 10 to the dowel using sleeve VM M8*. Mount the couplers GV 30 together with the wire-mesh cable tray.

4 | Wall mounting with bracket KWWFor mounting use dowels as e.g. SD 8/10*. Use outer slots of the profile.

3 | Wall mounting with bracket KWFFor mounting use dowels as e.g. SD 10/10*. The thick washer US 13x30x6 must be mounted as well.

2 | Wall mounting with bracket KSLWFor mounting use dowels as e.g. SD 8/30*. The spacer KSL-SP must be positioned first.

1 | Wall mounting with bracket KWLLFor mounting use dowels as e.g. SD 8/30* and replace the small washer US 8x17 with the large flat washer US 8x25*.

Assembly instruction for support systems of wire-mesh cable trays and cable trays in concrete.

* The article is not included in the scope of delivery and must be ordered separately.

Page 3: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

3

Support systems | Light-weight designAssembly instruction

15 | Ceiling mounting with trapezium bow TBSFold out the trapezium sheet, then attach the bow using the bolt and nut SES 8x110, SEM 8. Various connections are possible, as e.g. by means of threaded bar M8/10.

14 | Ceiling mounting with head plate BGA 41 and C-profile KHA 41For mounting use two dowels as e.g. SD 8/10*. Attach the C-profile using screw set KLS 10x20*. Fasten the bracket KA using screw set SES 10x20*, AMF22 M10*. The optional protection cap SA* is pushed onto the bracket from the bottom.

13 | Ceiling mounting with ceiling-fixed bracket KDAG 41For mounting use two dowels as e.g. SD 8/10*. Attach the bracket KA 30 using screw set SES 10x20*, AMF22 M10*. The optional protection cap SA* is pushed onto the bracket from the bottom.

12 | Ceiling mounting with bracket support KSLW For mounting use dowels as e.g. SD 8/30*. The spacer KSL-SP must be positioned first. Mount the bracket KSL using screw set FRS 8x20, SEMS 8.

11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50For mounting use two dowels as e.g. SD  8/10*. Mount the U-profile using screw set KLS 10x20*. Secure the bracket KUL with screw set KLS 10x20. The optional protection cap SU 50* is pushed onto the bracket from the bottom.

10 | Ceiling mounting with bracket support KDU 50 For mounting use two dowels as e.g. SD 8/10*. Secure the bracket KUL using screw set KLS 10x20. The optional protection cap SU 50* is pushed onto the bracket from the bottom.

9 | Ceiling mounting with ceiling-fixed bracket DBFor mounting use dowels as e.g. SD 8/30* and replace the small washer US 8x17 with the large flat washer US 8x25*.

8 | Central suspension for cable trays of up to 300 mm widthInsert the central hanger MA into the cable tray in a tilted position and clamp by turning. Insert the assembled threaded rod GB M10* sideways into the central hanger MA and secure using nut SEM 10*.

7 | Central suspension for cable trays of up to 300 mm widthConnect the central hanger GBAR to the dowel using sleeve VM M10*. Dismantle the profile rails and reassemble together with the cable trays.

* The article is not included in the scope of delivery and must be ordered separately.

Page 4: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

4

Support systems | Light-weight designAssembly instruction

16 | Ceiling suspension with pendulum suspensionConnect threaded rods GB M8 to dowel using sleeve VM M8, then mount the C-profile KHA 8 from the bottom.

Page 5: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

5

GB-M8

GB-M10

SES 8x110

SES 10x20

FRS 8x20

KLS 10x20

SEM 8

SEM 10

SEMS 8

AMF22 M10

VM M8

VM M10

US 8x25

US 8x17

US 13x30x6

US 10x21

SD 8/10

SD 8/30

SD 10/10

Support systems | Light-weight designAssembly instruction

Screw tightening torques

Legend Accessories

Underline Symbols

Bolt diameter Strength category screw (DIN 267 part 3)

Strength category nut (DIN 267 part 4)

Screw tightening torque (Nm) acc. VDI 2230

M8 4.6 5 8

M10 4.6 5 16

M12 4.6 5 32

M8 8.8 8 34

M10 8.8 8 68

M12 8.8 8 117

Correct

Wrong

Observe tightening torque for fasteners

Page 6: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

6

* The article is not included in the scope of delivery and must be ordered separately.

6 | Ceiling mounting with heavy bracket support KDU 60 For mounting use two dowels as e.g. SD 10/10*. Attach the bracket KW using screw set KLS 10x20*. If the bracket is longer than 500 mm, screw the support piece KHUSS together with the bracket. The optional protection cap SU 60* is pushed onto the bracket from the bottom.

5 | Ceiling mounting with ceiling-fixed bracket KDAG 41For mounting use two dowels as e.g. SD 10/10*. Attach the bracket KA 41 using screw set SES 10x20*, AMF22 M10*. The optional protection cap SA* is pushed onto the bracket from the bottom.

4 | Ceiling mounting with head plate BGU 50 and 2x U-profile KHU 50 For mounting use two dowels as e.g. SD 10/10*. Mount the U-profile using screw set KLS 10x20. For mounting the bracket KUM use screw set KLS 10x20. The optional two protection caps SU 50* are pushed onto the bracket from the bottom.

3 | Ceiling mounting with bracket support KDU 52 For mounting use two dowels as e.g. SD 10/10*. Secure the bracket KUM using screw set KLS 10x20. The optional protection cap SU 50* is pushed onto the bracket from the bottom.

2 | Ceiling mounting with ceiling-fixed bracket DKSL For mounting use dowels as e.g. SD 8/30*. The clamp piece KSL-SP must be positioned first.

1 | Wall mounting with bracket KWFor mounting use dowels as e.g. SD 10/10*.

Assembly instruction for support systems of wire-mesh cable trays, cable trays and cable ladders in concrete.

Support systems | Medium-weight designAssembly instruction

Page 7: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

7

* The article is not included in the scope of delivery and must be ordered separately.

11 | Ceiling suspension with pendulum suspension Connect threaded rods GB M10 to the dowel using sleeve VM M10. The C-profile KHA 41 is mounted from the bottom.

10 | Ceiling mounting with head plate BGI with I-profile KHI For mounting use two dowels as e.g. SD 10/10*. Attach the I-profile using screw set FRS 10x30 and SEM 10. The console mounting of KT or KTS is the same as the mounting of KDI. The optional protection cap SI* is pushed onto the bracket from the bottom.

9 | Ceiling mounting with heavy bracket support KDIFor mounting use two dowels as e.g. SD 10/10*. Fasten the bracket KTS using the enclosed clamping piece. The optional protection cap SI* is pushed onto the bracket from the bottom.

8 | Ceiling mounting with heavy bracket support KDI For mounting use two dowels as e.g. SD 10/10*. Fasten the bracket KT using the enclosed clamping piece. The optional protection cap SI* is pushed onto the bracket from the bottom.

7 | Ceiling mounting with head plate BGU 60 and U-profile KHU 60 For mounting use two dowels as e.g. SD 10/10*. Secure the U-profile with screw set SES 10x20, SEM 10 and US 10x21. Bracket mounting KW is done as with KDU 60. The optional protective cap SU 60* is pushed onto the bracket from the bottom.

Support systems | Medium-weight designAssembly instruction

Page 8: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

8

GB-M10

SES 10x20

FRS 10x30

KLS 10x20

SEM 10

AMF22 M10

VM M10

US 10x21

SD 8/30

SD 10/10

Support systems | Medium-weight designAssembly instruction

Screw tightening torques

Legend Accessories

Underline Symbols

Bolt diameter Strength category screw (DIN 267 part 3)

Strength category nut (DIN 267 part 4)

Screw tightening torque (Nm) acc. VDI 2230

M8 4.6 5 8

M10 4.6 5 16

M12 4.6 5 32

M8 8.8 8 34

M10 8.8 8 68

M12 8.8 8 117

Correct

Wrong

Observe tightening torque for fasteners

Page 9: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

9

6 | Ceiling suspension with pendulum suspension Fasten the head plates BGI with two dowels each as e.g. SD 12/10*. Secure the I-profiles horizontally to the head plates using screw set FRS 10x30, SEM 10. Screw the longitudinal profile to the support connector HKIQ.

5 | Ceiling suspension with pendulum suspension Fasten the head plates BGU 60 with two dowels each as e.g. SD 12/10*. Secure the U-profile using the screw set SES 10x20, SEM 10 and US 10x21 both horizontally and vertically.

4 | Mounting on steel girders using heavy bracket KISSFor mounting use four beam clamps SKS M*.

3 | Mounting on steel girders using heavy bracket KISFor mounting use four beam clamps SKS H*.

2 | Wall mounting with heavy bracket KWSSFor mounting use dowels as e.g. SD 12/10* for the top and bottom drill holes.

1 | Wall mounting with heavy bracket KWS For mounting use dowels as e.g. SD 12/10* in the top drill hole.

Assembly instruction for support systems of wire-mesh cable trays, cable trays, cable ladders and wide-span cable ladders in concrete.

Support systems | Heavy-weight designAssembly instruction

* The article is not included in the scope of delivery and must be ordered separately.

Page 10: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

10

SES 10x20

FRS 10x30

SEM 10

US 10x21

SD 12/10

SKS H

SKS M

Screw tightening torques

Legend Accessories

Underline Symbols

Bolt diameter Strength category screw (DIN 267 part 3)

Strength category nut (DIN 267 part 4)

Screw tightening torque (Nm) acc. VDI 2230

M8 4.6 5 8

M10 4.6 5 16

M12 4.6 5 32

M8 8.8 8 34

M10 8.8 8 68

M12 8.8 8 117

Correct

Wrong

Observe tightening torque for fasteners

Support systems | Heavy-weight designAssembly instruction

Page 11: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

11

Page 12: Support systems Assembly instruction - PUK · Assembly instruction 6 ... 11 | Ceiling mounting with head plate BGU 50 and U-profile KHU 50 ... (DIN 267 part 3) Strength category

www.puk.com© PUK Group  |  PUK-MV KB-TK EN  |  WEST  |  500  |  2016-02-01