+ All Categories
Home > Documents > Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the...

Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the...

Date post: 13-Aug-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
36
Fans | Data Center Cooling | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans Systemair DFC and IFC Modular Air Handling Unit for Data Center Cooling
Transcript
Page 1: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

1 DCC DFC and IFC units | Fans | Data Center Cooling | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans

Systemair DFC and IFCModular Air Handling Unit for Data Center Cooling

Page 2: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

for Data Center CoolingModular Air Handling Units

| DCC DFC and IFC units2

This catalogue contains a technical description of the air

handling unit series DFC and IFC in the range 23-325 kW

(5.000-43.000 m3/h).

Specially designed for Data Center facilities, Systemair Free Cooling units use the most energy efficient components which results in minimum operational costs and low car-bon footprint.

Systemair DFC and IFC units together with other Systemair ventilation products form complete solution for air condi-tioning and ventilation in Data Center facilities.

Systemair in SpainDCC DFC and IFC are produced in Madrid, Spain. Spanish factory has big experience in developing and manufactur-ing units for Data Centers. At this moment, factory has produced and supplied more than 250 Free Cooling units.

The Systemair GroupSystemair is an international group with its headquarters in Sweden and with sales companies all over the world. We offer a wide range of fans, fire, and smoke products and air distribution components.

Copyright: Systemair We accept no liability for printing errors or alterations of products. The dimensions and data used in this catalogue are a guideline only. Accurate calculations must be made in our selection program

Page 3: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

3 DCC DFC and IFC units |

Modular Air Handling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

for Data Center Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

About the DCC DFC and IFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Working Modes DCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Working Modes IFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Combination Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Damper type A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Damper type B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Mixing Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Prefilter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Prefilter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Plate Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Plate Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Air heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Air cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Air Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Steam Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Plug Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Sound Attenuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Content

Page 4: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units4

IFC and DFC units are specially devel-oped for cooling of process air in data centers or other premises with high heating load.

The IFC unit is a complete system for energy efficient and safe cooling even in extreme outdoor environ-ment.

The DFC unit is a complete system of energy efficient free cooling, while needed level of humidity is main-tained by optional dehumidifying sys-tem and steam lance.

Depending on outdoor air conditions, the control system switches between unit working modes to ensure most efficient performance and lowest energy consumption of the whole system.

DCC DFC and IFC units are designed as modular air handling units. Each

function is placed into an air handling unit casing consisting of one or more modules.

The modular functions can be config-ured for different applications to make up the heart of Data Center cooling system. The flexibility makes it possible to optimize the air han-dling unit for each project.

Sizes and airflows

DCC DFC and IFC units come in a range of 6 different sizes, with capac-ities from 25-230 kW or 5.000-43.000 m3/h, making it possible to always find optimized solution for any given requirement.

Casing The casing protects the inside func-tions and is very effective for thermal and sound insulation.

FunctionsData Center modular unit features a number of well-dimensioned func-tions, presenting a choice between different Free Cooling systems,

types of heat exchangers, cooling coils, humidifying and dehumidifying systems.

Selection programThe product selection program ensures optimal design of the air handling unit functions. The program is very user-friendly and makes it possible to quickly and easily combine air handling unit functions and per-form technical calculations. The selec-tion program calculates and optimizes the energy consumption, generates pPUE figures and OPEX graphics.

Airflow capacities for DCC DFC and IFC air handling units

Indicates airflow range at the shown combination examples with heat recovery and by specific fan power 2,1 kW/(m3/s). The exact values are calculated by Selection Program.

29400 41200 CFM1765011760588029401760

151053210,7 20 m3/s

190150

12060

5040

20

240

DCC DFC DCC IFC

About the DCC DFC and IFC

Page 5: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

5 DCC DFC and IFC units |

Frame profiles and cornersDCC DFC and IFC is constructed using a closed framing profile with cast painted aluminium corner pieces. The frame profiles are made of steel with alu-zinc corrosion protection. The result is a strong and robust construc-tion able to resist twisting and lateral movement, making the unit extreme-ly stable and strong.

PanelsThe panels of the DCC DFC and IFC are built using a sandwich construc-tion with double sheets and 60 mm mineral wool for sound and heat insulation. The mineral wool is com-pletely encapsulated, since the panels are closed on all sides.

The panels with alu-zinc surface are not only highly corrosion-resistant, but present an attractive, uniform appear-ance that can last for many years. Steel sheets which are protected with powder coated alu-zinc AZ185 ensure a corrosion protection in class C4 according to EN ISO 12944-2:2000.

Disc-LockAn air handling unit consisting of several sections in size 20-240 can be quickly and efficiently assembled using Disc-Lock, our unique assembly system.

Inspection doorsDCC DFC and IFC has large inspection doors, making service access easy. The doors are mounted using solid hinges with easily removable stain-less steel pins. This means that the doors can be easily removed, if there is no room for normal opening of the doors.

The doors are sealed using rubber profiles and locks with heavy-duty handles. They can only be opened using a key.

Roof unitsDCC DFC and IFC in the sizes 20-240 are available as roof units, designed for outdoor installation. In this version the unit features a roof construction which together with the double seal-ing of the panels provides protection against the effects of the weather. The unit is available with louvers for air intake and exhaust.

Control systemDCC DFC and IFC is always supplied with pre installed and fully integrated Systemair pCO5 control system from Carel. pCO5 is an advanced user-friendly system, that was specially developed for Data Center needs. It is a modern and complicated control system with a large number of fea-tures e.g. alarms, setting of time, operating values and operating sta-tus. The system is prepared for com-munication to a BMS system.

Page 6: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units6

Mode 1. 100% Free CoolingWhen outdoor air (OA) temperature and humidity correspond to needed supply air parameters, outdoor air (OA) is supplied directly to data center room. Warm air from data center is extracted through extract fan or overpressure damper.

Working Modes DCC

Mode 2. MixingDuring low outdoor air (OA) temperature periods, Mixing mode is turned on. Extract air (EA) is partly mixed with outdoor air (OA) in proportion, needed to maintain supply air (SA) parameters.

Mode 3. Cooling SupportIf outdoor air (OA) temperature is higher than needed supply air (SA) tempera-ture, and lower than extract air (EA) temperature, partial support mode starts. During this mode cooling coil maintains supply air (SA) temperature at needed level.

Mode 4. RecirculationIf outdoor air (OA) temperature is higher than extract air (EA) temperature, Recirculation mode starts. Process indoor air will be cooled down by built in cooling coil that is able to maintain 100% of needed cooling capacity. Cooling coil is supported by external chiller or condensing unit.

Humidity Control

If absolute humidity level is lower than demanded, optional steam lance mod-ule will be activated.

If absolute humidity level is higher than demanded, optional dehumidification module will be activated.

Page 7: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

7 DCC DFC and IFC units |

Mode 1. Heat ExchangerWarm air from data center room is supplied to plate heat exchanger. Cold out-door air passes through heat exchanger in counter flow air path, without any mixing with indoor air. Indoor air is cooled down by cooling power of outdoor air. In order to maintain needed capacity, outdoor airflow varies depending on air parameters: if temperature goes down airflow is reduced.

Mode 2. HE+AdiabaticWhen outdoor air temperature goes up and its cooling power is not enough to maintain needed capacity, adiabatic evaporative cooling mode starts: outdoor air passes through adiabatic humidifier, where water is evaporated and outdoor air temperature is reduced. Precooled outdoor air is supplied to plate heat exchanger and cools down process indoor air. In order to maintain minimal power consumption outdoor airflow is also reduced according to cooling need in this mode.

Mode 3. Partial SupportDuring very high outdoor air temperature periods partial support mode starts. In this mode there are 2 cooling stages of process indoor air: first it is precooled with help of evaporative cooling and heat exchanger, then it is cooled in built-in cooling coil stage.

Mode 4. Energy Recovery If there is need of Energy Recovery, ERE mode is activated. During this mode outdoor air fan is stopped and all the hot air from White Space (EA) is supplied to ERE coil, that performs as economizer.

Working Modes IFC

Page 8: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units8

Air handling unit casingRigid frames with sound and thermal insulated panels.

Materials

FramesClosed 1,3/1,5 mm steel profile.

Surface: Alu-zinc AZ 185.

CornersPlastic corners for low thermal loses.

PanelsInsulation sandwiched between two 0,8 mm steel sheets. The steel sheets are corrosion protected with alu-zinc AZ185.

Corrosion protectionPowder coated steel sheets which are protected with alu-zinc AZ 185 ensure a corrosion protection in class C4.

InsulationSound and thermal insulating mineral wool, which is completely encapsu-lated between two steel sheets.

Thickness: 50 mm.

Density: 50 kg/m3.

Operating pressureDifference between surrounding and pressure inside the air handling unit:

0 - 2000 Pa (20-150)

Operating temperatures

General temperatures General temperatures for the air in the air handling unit:

Standard design: -40/+40 ˚C

Special design: -40/+60 ˚C

Mechanical strengthClass D2

Casing air leakage Negative pressure: - 400 Pa: Class L2

Positive pressure: + 700 Pa: Class L2

Filter by-pass leakage Negative pressure: - 400 Pa: Class G1-F9

Positive pressure: + 400 Pa: Class G1-F9

Thermal transmittanceClass T2

Thermal bridging factorClass TB2

Acoustic insulation of casing Octave band Hz Insulation dB

125 17

250 23

500 24

1000 23

2000 25

4000 31

8000 38

Product Information

Page 9: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

9 DCC DFC and IFC units |

The above dimensions and weights are a guideline only. Accurate values and combinations are calculated in Selection Program.* Height excl. legs/base frame. Weight is calculated for indoor units.

The above dimensions and weights are a guideline only. Accurate values and com-binations are calculated in Selection Program. Weight is calculated for indoor units.

DCC DFC and IFC contains countless combination options. To ease the process of desig-ning a unit the most popular combinations are illustrated here.

Design an air handling unit

DFC Unit

Unit size

40 50 60 120 150 190 240

Unit Width 1720 2020 2170 2590 2890 3190 3490

Unit Height* 1145 1195 1370 1820 1970 2020 2320

D1 Length 2990 2540 3140 3660 3810 4410 4410

Weight kg 820 825 934 1440 1620 2170 2580

D2 Length 3960 3510 4110 4630 4780 5010 5010

Weight kg 950 995 1145 1700 1925 2380 2980

D3 Length 3960 3510 4110 4630 4780 5530 5380

Weight kg 987 1033 1194 1769 1994 2650 3050

D4 Length 4630 4410 4930 6050 6350 7140 8000

Weight kg 1298 1356 1499 2363 2735 3480 4150

D5 Length 5600 4710 5900 7020 7320 7700 8600

Weight kg 1428 1526 1710 2623 3040 3650 4320

D6 Length 5600 4710 5900 7020 7320 8150 9350

Weight kg 1465 1564 1759 2692 3109 3850 4550

IFC Unit

Unit size

20 40 50 60 120 150 190 240

Unit Width 1270 1720 2020 2170 2590 2890 3190 3490

Unit Height* 1590 2040 2340 2490 3390 3690 4040 4790

S1 Length 3590 4340 4340 4490 5680 5830 6430 6880

Weight kg 980 1682 2050 2162 3900 4451 6166 7499

S2 Length 3590 4480 4480 4780 5970 6270 6430 7330

Weight kg 1116 1890 2308 2285 4303 4663 6495 7857

S3 Length 3590 4710 4710 4860 6050 6350 6950 7850

Weight kg 1035 1796 2090 2268 3980 4683 6675 7705

S4 Length 3590 4710 4710 4860 6050 6350 6950 7850

Weight kg 1171 2003 2348 2391 4383 4895 6915 8063

S5 Length 3590 4710 4710 4860 6050 6350 6950 7850

Weight kg 1208 2040 2386 2440 4432 4944 6975 8133

Page 10: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units10

The above dimensions and weights are a guideline only. Accurate values and combinations are calculated in Selection Program. * Height excl. legs/base frame. Weight is calculated for indoor units.

IFC Unit with Counter-Flow

Unit sizes

20 40 50 60

Unit Width 1270 1720 2020 2170

Unit Height* 1590 2040 2340 2490

C1 Length 3590 4340 4340 4490

Weight kg 1050 1832 2220 2272

C2 Length 3590 4480 4480 4780

Weight kg 1186 2040 2478 2395

C3 Length 3590 4710 4710 4860

Weight kg 1105 1946 2260 2378

C4 Length 3590 4710 4710 4860

Weight kg 1241 2153 2518 2501

C5 Length 3590 4710 4710 4860

Weight kg 1278 2190 2556 2550

Product Information

Page 11: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

11 DCC DFC and IFC units |

DampersThe dampers used in DCC DFC and IFC comply with EN 1751:2014, sealing class 3. They have contra-rotating aerodynamically formed aluminium blades that ensure a low pressure loss when open.

The blades are equipped with special rubber sealing strips between the blades themselves and the frame, to prevent air getting in. For very cold areas, the blades can be insulated.

The dampers ensure a long and trou-ble-free operation, as the blades are mounted on sturdy square profile shafts and service-free synthetic bearings with large bearing surfaces. A pivoting system placed outside the airflow connects the blades, and it is fitted with brass bushings. This all-metal solution of the pivoting system ensures dampers smooth operation even in areas with extreme cold.

The dampers are fitted with a posi-tion indicator.

Damper (type A)Shutoff damper designed for efficient closing off of the outdoor and exhaust air. The damper is to be placed inside the unit and is prepared for internal damper motor. Read more, page 15.

Damper DVA

Damper DVB Bag filter DVF

Damper (type B)Shutoff damper fitted at the top of the unit, and is used where a damper is required for vertical air handling unit connection. Prepared for internal damper motor. Read more, page 17.

Mixing damperThis type of damper is used only in DFC units. Mixing damper with two built-in dampers that can either be used as a shutoff or recirculation damper. Prepared for internal damper motors. When combined with the damper, acts as a total mixing sys-tem, also ideal for recirculation. Read more, page 17.

Compact filterCompact basic filter class G4 accord-ing to EN 779:2012. It has a very short built-in length but it has a rela-tively large filter area due to the pleated filter construction. This gives the filter a relatively low pressure loss and long lifetime. It is ideal as a pre-filter, helping to prolong the lifetime of the main filter. The filter can be slotted into the filter frame of the air handling unit. Read more, page 18.

Bag filterFilter's special shape provides an extremely large filter area, which together with the filter material’s unique ability to collect dust particles, ensure that the filter has a long life-time, making it economical. The filter is composed of filter cells classes G4, M5, M6, F7, F8, F9 and F7 City-Flo according to EN 779:2012..

F7 City-Flo is a filter with particle and molecular filtration in the same media. This unique filter media has a very low initial and average pressure drop during its life time. Several glob-al standards require this kind of filter-ing solution in urban areas and areas with heavy traffic.

DVF 20-150: The filter cells are held in place using a simple but effective system of lateral locking rails with large handles, making filter changing quick and easy.

This system also ensures that the fil-ter cells form a tight seal with the unit frame to comply with EN 1886:2008 edition. All seals are fixed to the unit and do not need replace-ment when installing new filters. Filter cells from all major filter manu-facturers can be used in the unit.

Read more, page 19.

Compact filter DVG

Page 12: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units12

Plate Heat ExchangerPlate heat exchanger available in 3 versions. Cross flow heat exchanger for unit sizes 20 to 150 in standard version with efficiency up to 65%, counter flow heat exchanger for unit sizes 20-60, with average efficiency 79%.

The plate heat exchanger is thus ideal for situations where the separation of the two airflows is a necessity, to avoid the transfer of unpleasant odours to the supply air for example. Because humidity is not transferred between the airflows, it can also be used for dehumidifying.

The cross flow heat exchanger is available in two variants for use in different environments. The alumini-um variant is used for regions where no corrosive elements are present in the air. The corrosion resistant variant with coated aluminium plates is used in environments where the extract air can contain aggressive elements.

The counter flow heat exchanger ver-sion is only available in aluminium variant. The heat transfer capacity and anti-freeze protection can be regulated using the built-in by-pass damper. Cross flow versions are always fitted with a drip tray to col-lect condensed water from the extract air. The counter flow versions have drip tray fitted in both extract and supply air. Read more, page 20.

Adiabatic Humidifier It is Adiabatic Humidifier system that is designed so water evaporates nat-urally. Air passes across a sheet of

Plate heat exchanger DVQ

water partially Evaporates it and adds the water vapor to its composition. It is at the same time cooled because energy required for the evaporation is provided by the air. It is installed in outdoor air part of the unit. Cooling effect of the humidifier helps to increase the efficiency of free cooling system significantly. Adiabatic humid-ifier has saturation efficiency up to 95%. The effectiveness of the sys-tem depends on its construction and the volume of air.

The humidifier consists of a system of tubes from stainless steel, through which water is supplied to evapora-tive panel from Fibergalss, drain pan from stainless steel is installed under-neath. Droplet separator from PP panels is certified by VDI 60222.

Water is circulated with help of built-in water pump.

Heating coilThe heating coil is used as reheating

stage in dehumidifying system of the supply air, using either hot water, condensation of a cooling medium or electricity. Dimensioning the heating coil is done using the design pro-gramme, where the coil will be deter-mined optimally to solve the current task.

Heating coils are manufactured of materials adapted to the heating medium and the environment the coil is to operate in. Coils with copper tubes and aluminium fins are used for hot water and condensation. Electrical heating coils have stainless steel

heating elements and built-in safety control system.

As light corrosion protection the heat-ing coils can be supplied with fins in aluminium-magnesium or epoxy coat-ed aluminium. Coils for hot water can be supplied with a connection piece to fit a temperature sensor in the water circuit, in order to subsequently equip the unit with modulating frost protection. Read more, page 22.

Cooling coilThe cooling coil is used to cool down the supply air either with cold water, or direct expansion. The coil works as partly cooling support together with free-cooling system, or provides 100% of cooling capacity in extreme hot periods.

Calculation of the the coil is done using the Selection Program, where the coil will be determined optimally to solve the current task.

The coils are made with copper tubes and aluminium fins. As light corrosion protection the cooling coils can be supplied with fins in aluminium-mag-nesium or epoxy coated aluminium.

Cooling coils for direct expansion have the liquid distributor located in the unit. The expansion valve is fitted on the connection pipe inside the unit. Cooling coils are fitted with drip tray. The drain outlet must be con-nected to a water trap with sufficient locking height. The cooling coil can be supplied with a built-in droplet elimi-nator. The coil is fully built-in in the unit as standard. Read more, page 23.

Heating coil Cooling coil

Page 13: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

13 DCC DFC and IFC units |

Steam humidifierSteam humidifier is used for humidi-fying air that is supplied to data cent-er. Steam humidifier is used for very accurate control of humidity level, without influence on it’s temperature.

Steam humidifier consists of External unit, where steam is prepared and supplied through steam hose to steam manifold that is installed inside the DCC unit section.

Read more on page 26.

EC fan The fan has the fan impeller fitted directly to the motor, and enclosed into an acoustically insulated casing.

A plug fan is a single inlet, freeblow-ing fan, where the unit casing func-tions as fan housing. The fan has an efficiency of up to 98% and features low sound levels in the low frequen-cies. In order to optimize the fan effi-ciency a number of larger units are equipped with more fans for parallel operating.

Because of its construction, a plug fan can give a low and even air speed at the outlet of the fan unit. The fan is ideal for units where components are to be positioned after the fan.

In order to make service and inspec-tion access easy, the fan is fitted with a large hinged inspection door with a safety guard behind the door. Interior lighting is an option.

EC Blue compact plug fan is equipped-with an effective composite impeller, and EC external rotor motor with inte-

grated variable speed control. The EC motor is in efficiency class IE4.

All impellers are balanced statically and dynamically.

Read more, page 27.

Sound attenuatorAbsorption sound attenuator, fitted with baffles. The attenuator is used to reduce the sound power level from the air handling unit to the duct sys-tem.

For environmental reasons, the baf-fles have a surface lining that effec-tively prevents the entrainment of the sound-absorbing material. This surface lining comes in two variants:

1. Standard lining, suitable for all forms of comfort ventilation pur-poses. Baffles with a strongly, durable lining, resistant to mecha-nical wear and tear. Are used in situations where the baffles require dry cleaning, such as brushing or vacuum cleaning.

2. Baffles with a synthetic lining, ide-al for wet cleaning. Each baffle is enclosed in a stainless steel frame and used where high levels of hygiene require direct washing of the baffles.

The attenuator can by variant 1, as an option, be delivered with large inspection doors for easy cleaning. Inspection doors are standard by vari-ant 2. Read more, page 28.

Inspection SectionThe inspection section is an empty unit section with an inspection door. is used between components that require inspection and servicing. The inspection can be fitted with an inspection window and internal light. Read more, page 29.

Empty sectionEmpty unit section without inspection door. Can e.g. be used to create dis-tance between unit components with different shapes. Read more, page 29.

Plug fan EC Blue Sound attenuator DVD Inspection section DVI Empty section DVO

Page 14: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units14

Roof unit The DCC DFC and IFC air handling unit in the sizes 20 to 240 are available as roof units for outdoor installation. In this version the unit is assembled on a base frame and features a roof con-struction which together with the double sealing of the panels provides protection against the effects of the weather.

Metallic profile roof: Manufactured of alu-zink protected, corrugated steel sheets, and profiles for fastening and finishing the roof-ing. This type of roofing is supplied for local assembling on the air hand-ling unit. The metallic profile roof is a robust roofing where the surface matches the units panels.

Air intake and exhaust are available with louvers for effective protection against rain and snow. Outdoor air section (see page 30) features outlet of exhaust air on the back of the unit.

Systemair Carel pCO5 control systemDCC DFC and IFC is available with pre installed Systemair Carel pCO5 control system, fully tested at the factory. It is a flexible and user-friendly system, where operating and monitoring is carried out on a remote control panel, which can be posi-tioned freely up to 100 meter from the unit.

The control panel displays continu-ously operating status, operating val-ues, time settings and alarms.

Additions or changes to functions can be made via the control panel. The Carel pCO5 can communicate with BMS systems via Modbus.

Roof unit DV Steel profile roof

Carel pCO5 control panel

ATSDouble-Power feed intake unit, or ATS is three-phase automatic transfer witch with positive break indication.

The unit senses even small interrup-tion of the load supply and switches to alternative power source. ATS is mounted inside DCC unit.

UPSUninterrutable power supply unit Protects controller from disruptions electricity supply during switch between power sources. UPS unit is installed inside DCC unit.

ATS

UPS

Page 15: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

15 DCC DFC and IFC units |

FunctionSupply or extract air shutoff damper.

Air tightness classificationClass 3 according to EN 1751:2014.

Damper bladesAerodynamically formed aluminium profiles. Can be supplied as an option:

• Insulated • Anodized

BearingsSynthetic bearings with large bearing surfaces.

Damper fitted to the upper part of a double height unit

SealingRubber sealing strips between the damper blades. Special sealing between frame and damper blades.

Shafts

14,3 mm aluminium

16,3 mm aluminium with steel reinforcement

Blade pivoting systemSteel rods with maintenance free brass bushings.

Damper fitted to a single height unit

Blade position indicatorArrow for indication of the blade position.

Motor bracketBracket for fixing of a damper motor for each damper.

Damper motorThe dampers are activated by a motor for each damper.

Unit sizes

20-150: 1 damper motor. 190-240: 2 damper motors

3535

3535

35

H2 H1: Single height unit H2: Double height unit

Damper type M for sizes 20-240

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L 185 185 185 185 335 335 785 785

D 1200 1650 1950 2100 2520 2820 2600 2800

E 500 750 900 1000 1450 1600 1500 1800

F - - - - - - - 295

G - - - - - - - 410

Size 20 40 50 60 12 150 190 240

0 Pa 6 9 11 12 17 18 2*12 2*15

500 Pa 16 17 19 21 23 24 2*17 2*21

1000 Pa 20 22 24 26 28 29 2*22 2*26

Dimensions

Torque (Nm) for each damper

Required minimum torque per damper motor for opening/closing at varying differential pressure across the damper.

L

Damper type M for sizes 190 - 240

Damper type A

Page 16: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units16

Damper type B

FunctionExtract air shutoff damper.

Air tightness classificationClass 3 according to EN 1751:2014.

Damper bladesAerodynamically formed aluminium profiles. Can be supplied as an option:

• Insulated • Anodized

BearingsSynthetic bearings with large bearing surfaces.

Shafts

14,3 mm alu-minium

16,3 mm aluminium with steel reinforcement

SealingRubber sealing strips between the damper blades. Special sealing between frame and damper blades.

Blade pivoting systemSteel rods with maintenance free brass bushings.

Blade position indicatorArrow for indication of the blade position.

Motor bracketBracket for fixing of a damper motor for each damper.

Damper motorThe dampers are activated by a motor for each damper.

Unit sizes

20-150: 1 damper motor 190-240: 4 damper motors

L

Damper type B 20-240

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H 670 895 1045 1120 1570 1720 2170 2470

L 520 670 670 670 970 970 1120 1570

D 800 1200 1500 1600 2000 2300 2600 2800

E 300 400 400 500 700 700 1000 1200

F 235 260 260 285 295 295 295 345

K 110 135 135 85 135 135 60 185

Size 20 40 50 60 12 150 190 240

0 Pa 4 7 8 9 13 14 2*10 2*12

500 Pa 7 11 13 14 18 19 2*15 2*17

1000 Pa 9 15 17 19 23 24 2*20 2*22

Dimensions

Torque (Nm) for each damper

Required minimum torque per damper motor for opening/closing at vary-ing differential pressure across the damper.

L

Damper type M for sizes 190-240

Page 17: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

17 DCC DFC and IFC units |

FunctionSupply air shutoff and mixing damper.

Air tightness classificationClass 3 according to EN 1751:2014.

Damper bladesAerodynamically formed aluminium profiles. Can be supplied as an option:

• Insulated • Anodized

BearingsSynthetic bearings with large bearing surfaces.

L

Damper type M for sizes 20-240

Shafts

14,3 mm alumin-ium

16,3 mm aluminium with steel reinforcement

SealingRubber sealing strips between the damper blades. Special sealing between frame and damper blades.

Blade pivoting systemSteel rods with maintenance free brass bushings.

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H 670 895 1045 1120 1570 1720 2170 2470

L 520 670 670 670 970 970 1120 1570

D 800 1200 1500 1600 2000 2300 2600 2800

E 300 400 400 500 700 700 1000 1200

F 235 260 260 285 295 295 295 345

G 100 100 100 100 100 100 600 710

K 110 135 135 85 135 135 60 185

Size 20 40 50 60 12 150 190 240

0 Pa 4 7 8 9 13 14 2*10 2*12

500 Pa 7 11 13 14 18 19 2*15 2*17

1000 Pa 9 15 17 19 23 24 2*20 2*22

Dimensions

Torque (Nm) for each damper

Required minimum torque per damper motor for opening/closing at varying differential pressure across the damper.

Blade position indicatorArrow for indication of the blade position for each damper.

Motor bracketBracket for fixing of a damper motor for each damper.

Damper motorThe dampers are activated by a motor for each damper.

Unit sizes

20-150: 2 damper motors 190-240: 4 damper motors

Damper type M for sizes 190-240

L

Mixing Damper DVM

Page 18: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units18

Prefilter

FunctionPrefilter.

Filter classificationG4 according to EN 779:2012.

Filter materialSynthetic polyester fibres.

Unit size Number and size

20 1x[241x495x44] + 1x[495x495x44] + 1x[391x495x44]

40 6x[495x368x44]

50 6x[622x391x44]

60 8x[495x495x44]

120 15x[495x445x44]

150 21x[391x495x44]

190 15x[592x592x25] *

240 15x[592x592x25] + 8x[287x592x25] *

* Only in combination with DVF with inspection section for filter change on the dirty side.

Filter surface areaLarge surface area due to the pleated filter form.

Filter frameFramework encasing the filter with U-profiles.

AccessoriesU-tube manometer.

H1: Single height unit H2: Double height unit

DimensionsSize 20 40 50 60 120 150

B 1270 1720 2020 2170 2590 2890

H1 670 895 1045 1120 1570 1720

H2 1270 1720 2020 - - -

L 150 150 150 150 150 150

Page 19: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

19 DCC DFC and IFC units |

Prefilter

FunctionPrefilter, medium or fine filter.

Filter classificationG4, M5, M6, F7, F8, F9 and F7 City-Flo according to EN 779:2012.

Filter materialG4: Synthetic material. M5, M6, F7, F8 F9: Glass fibre material. F7 City-Flo glass fibre and coal with a wide spectrum.

Filter frameThe filter cells are supplied with 25 mm standard plastic frame. Therefore, used filters can be dis-

posed of in their entirety by combus-tion. Filter for size 40 is supplied only with steel frame.

SealingRubber sealing strips are fixed to the filter cabinet. Air tightness according to EN 1886:2008.

Fitting the filter cellsThe filter cells are pressed against the sealing strips and locked into place using a sliding rail system. This system is easy to operate by using a large handle.

Accessories• Inspection window • Pressure tapping • Light with external switch • U-tube manometer • Inclined tube manometer • Magnehelic manometer • Spare filter set • Stainless steel sheet under the

filters

H1: Single height unit H2: Double height unit

L1: G4, M5, F7, F9 L2: F7L, F9L

Sizes 20-150

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L1 600 600 600 600 600 600 600 600

L2 750 750 750 750 750 750 750 750

L3 - - - - - - 1200 1200

L4 - - - - - - 1350 1350

Unit

size Number and size of frames

"G4 370 mm

number of bags"

"M5 520 mm

number of bags"

"M6 520 mm

number of bags"

"520 mm number of

bags"

"F7L/F8-9L 640 mm

number of bags"

"F7 City-Flo 520 mm

number of bags"

20 1x[490x490] + 1x[592x490] 8+6 8+6 8+10 8+10 8+10 8+10

40 3x[490x742] (delivered with steel frame) 5 5 8 8 8 -

50 3x[592x490] + 3x[592x287] 6+6 6+6 10+10 10+10 10+10 10+10

60 8x[490x490] 5 5 8 8 8 8

120 4x[592x592] + 4x[592x490] + 4x[592x287] 6+6+6 6+6+6 10+10+10 10+10+10 10+10+10 10+10+10

150 9x[592x490] + 6x[490x490] 6+8 6+8 10+8 10+8 10+8 10+8

190 5x[592x592] 6 6 10 10 10 10

240 15x[592x592] + 3x[287x592] +5x[592x287] 6+3+6 6+3+6 6+3+6 10+5+10 10+5+10 10+5+10

Dimensions

34

Sizes 190-240

Page 20: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units20

FunctionRecuperative plate heat exchanger with high efficiency.

ApplicationThe plate heat exchanger is used where there are special requirements for separation of the two airflows, e.g. in order to avoid transfer of odours to the supply air.

VersionsS – Standard cross flow heat

exchanger Version Q20-240 Average efficiency up to 65%

VariantsThe versions are available in 2 variants:

A – Aluminium heat exchanger Version S, H and C is used in regions where the air does not contain corrosive elements. Many chemicals and solvents do not attack aluminum. This heat exchanger can be used where the air contains these substances. The conditions should be evaluated for each data center.

K – Corrosion resistant heat exchanger. Version S and H. The heat exchanger plates are coated with corrosion resistant synthetic material. Can be used in plants where the air contains elements which attack aluminium.

By-pass mixing damperUnit can be supplied with by-pass mixing damper that can regulate recovery side air temperature for

anti-freeze protection. By-pass damp-er consists of two mixing dampers: from exhaust and intake sides. By mixing of exhaust and intake air at the recovery side optimal low recovery air temperature is maintained.

Service-friendlyThe heat exchanger is equipped with large inspection doors that give access for inspection and service. As the heat exchanger has no rotating part, it requires very little service.

Drip trayA drip tray is fitted beneath the heat exchanger for collection of the water that can condense in the extract air. The drip tray drain outlet must be fit-ted with a water trap that is designed for the actual pressure difference. Refer to the assembly instructions. The counter flow heat exchanger is fitted with a drip tray in both extract and supply air sections.

Plate Heat Exchanger

Page 21: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

21 DCC DFC and IFC units |

Version C 20-60

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H 1270 1720 2020 2240 3140 3440 4340 4940

L vers. S 1570 2470 2470 2620 3140 3290 3740 4640

L vers. H 1570 2470 2470 2620 - - - -

L vers. C 1¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨

RG-S/H 2x1¨ 2x1¨ 2x1¨ 2x1¨ - - - -

RG-C 2 x 1" 2 x 1" 2 x 1"

Dimensions

Version S 20-190

Page 22: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units22

Air heater

FunctionAir heater

Heating mediaW – Hot water.

Max. temperature 100°C, max. working pressure 10 Bar. Available for temperatures up to 130°C.

C – Condensation of refrigerant. Max. working pressure depending on the type of refrigerant.

E – Electrical heating.

ConstructionFinned coils for hot water and con-densation consist of copper tubes with aluminium fins. Coils for electri-cal heating consist of stainless steel tube heating elements.

StandardDVH 10-150

MAXDVH 10-150

Electrical heating coil Hot water heating coil

Hot water Condensation

Pipe connections Inlet

Outlet

Copper tubesZ – Copper tubes ø10 mm. Used for

lower capacity heating coils.

Y – Copper tubes ø15 mm. Used for higher capacity heating coils.

FinsAl – Standard aluminium.

Alup – Aluminium with a synthetic coating. Used for mildly corrosive air.

AlMg₃ – Aluminium-magnesium alloy. Used for air in connection with seawater.

Frost protectionHeating coils for hot water are availa-ble with a connection piece for the fitting of a temperature sensor in the water circuit.

Electrical heatingThe inspection door, which can be opened only by using a key, gives access to a terminal box for the elec-trical connections. The coil has a built-in safety thermostat with an automatic reset function and an over-heating thermostat with manually resetting.

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 1270 1720 2020 2240 3140 3440 4340 4940

H2 1570 2470 2470 2620 3140 3290 3740 4640

L* 1570 2470 2470 2620 - - - -

- 1¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨

- 2x1¨ 2x1¨ 2x1¨ 2x1¨ - - - -

- 600 600 600 600 600 600 600 600

Dimensions

H1: Single height unit, H2: Double height unit.

* Heating coils for hot water (W), condensation (C) or electrical heating (E).

Standard

Page 23: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

Air cooler

23 DCC DFC and IFC units |

FunctionAir cooler.

Cooling mediaW – Cold water.

Max. working pressure 10 Bar.

D – Evaporation. Max. working pressure depending on the type of refrigerant.

ConstructionFinned coils consist of copper tubes with aluminium fins.

Copper tubesZ – Copper tubes ø10 mm.

Used for lower capacity cooling coils.

Y – Copper tubes ø15 mm. Used for higher capacity cooling coils.

FinsAl – Standard aluminium.

Alup – Aluminium with a synthetic coating. Used for mildly corrosive air.

AlMg₃ – Aluminium-magnesium alloy. Used for air in connection with seawater.

Pipe connectionsThe connection pipes for the cooling coil are placed outside of the air hand ling unit. The cooling coil for evaporation has the liquid distributor placed inside the unit section. The expansion valve can be fitted to the connection piece outside of the unit.

Drip trayThe cooling coil section is fitted with a drip tray for collection of condensed water. The drip tray drain outlet must be fitted with a water trap that is designed for the actual pressure dif-ference. Refer to the assembly instructions.

Droplet eliminatorThe Cooling coil is available with a droplet eliminator that prevents con-densed water droplets from being carried into the airflow.

Cooling coil fitted into a single height unit.

Cooling coil fitted into a double height unit.

StandardDVK 10-150

MAXDVK 10-150

RG – Drain connection

Cold water Evaporation

Pipe connections Inlet

Outlet

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L* 450 450 450 450 450 450 600 600

- 600 600 600 600 600 600 750 750

- 750 750 750 750 750 750 900 900

RG 1¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨ 1 1/2¨

Dimensions

H1: Single height unit, H2: Double height unit.

Standard

Page 24: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units24

Function The function is based on the natural process that water evaporates when air passes a wet surface. By uptake of water vapor in the air, the tempera-ture will decrease due to the fact that heat for the evaporation comes from the air. This is an adiabatic cooling, which means that the enthalpy con-tent of the air is unchanged during the process. This ensures that humidi-fication occurs without releasing drops, unless this is effected by entrainment. Entrainment may be avoided by passing the humidification elements with a suitable low speed or by mounting droplet eliminators, which can handle this.

Application

The humidifier is placed in the recov-ery side before heat exchanger to increase indirect free-cooling effect because of adiabatic effect in areas with high outdoor temperature and low humidity.

ConstructionThe humidifier is designed as a com-plete unit that fits the internal dimen-sions of a section of length 970 mm the units 20 to 240. The unit com-prises humidification elements, tray

and frame made of stainless steel AISI 304, circulation pump, balancing valves for irrigation, overflow, valve for adjusting bleed off, float valve for controlling the water supply to the tray and valve for emptying the tray. Droplet eliminator is included if nec-essary and sensor for protection of pump at low water level. The drain is led out of the sec-tion, and can be selected either on the inspection side or the backside. The drain must be connected to a water trap with sufficient locking height.

Humidification elementsHU-CELL humidification elements are stainless steel frames which contains corrugated fiberglass plates arranged in cross-channel configuration. The corrugated cross-channel configura-tion ensures that the air is in contact with a large surface area for evapora-tion, and at the same time provides a low pressure drop. The glass fiber material is impregnated with a stabi-lizing and absorbent additive which makes it possible to absorb water without loss of stability. The element is of inorganic material, and is there-fore not a feed source for bacteria and mould. The material contains sil-

ver ions, which acts as a growth inhibitor. This increases the resistance to the growth of microorganisms and helps to release deposits from the water on the material, so that this remains clean. Silver ions are encap-sulated in a chemical mixture, which ensures that their particles do not dissolve to either water or air. The elements are supplied in the thick-nesses 200 mm. This makes it possi-ble to optimize the pressure drop depending on the desired humidifica-tion/cooling requirement.

Technical dataThe Selection Program calculates all important data such as temperature, relative and absolute humidity after the humidifier, pressure drop and water consumption etc.

Air humidifier

Page 25: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

25 DCC DFC and IFC units |

A Process air

B Humidified air

C Water supply

D Overflow

E Constant bleed off

F. Draining

G. Water outlet to drain

1. Humidification element

2. Droplet eliminator (optional)

3. Water recirculations pump

4. Bleed off regulation valve

5. Irrigation regulation valves

6. Float valve

7. Draining valve

8. Filling solenoid valve (optional)

9. Max/min water level detector

10. Cut-off valve (depending on model)

Operating principles HEF2E (Recirculated water, standard on/off)

Water supply

Overflow

Bleed off

Water tray

Humidification element 2

3

C

F

E

D

7

68

5 5

49

G

4C

7DG

6

E

2

5

1

103

9

B

A

Humidification element 1

Page 26: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units26

FunctionThe function is based on the process

of humidifying air by injection of steam. With this type of humidifying is possible to maintain needed level of humidification, without significant influence on air temperature.

ApplicationThe steam manifold is installed in supply side of the unit after cooling coil to increase humidity level of sup-ply air.

ConstructionSteam humidifier consists of external unit, (carton outer), where water is supplied and steam is produced, steam line (steam and condensate hose) and steam manifold.

Description of workThe steam humidifier utilizes the con-ductivity normally present in tap water for steam production. Electrodes inside an enclosed steam cylinder are immersed directly into

the tap water. They are connected to the alternating current. The conduc-tivity of the water generates an elec-tric current between the electrodes. In this way, the electric power

supplied is converted directly into heat without energy loss.

Technical DataSize and capacity of steam humidifier are determined by need of humidifi-cation, and are calculated in Selection program.

Steam Humidifier

Page 27: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

Plug Fan DVE

FunctionPlug fan built into an acoustically insulated air handling unit.

ConstructionSingle inlet plug fan with open outlet into the air handling unit. The fan impeller is fitted directly to the motor. The backward curved impeller has low sound power levels in the lower frequencies. Static efficiency up to 98%.

EC Blue Compact plug fan with an effective composite impeller, and EC external rotor motor with integrated variable speed control. The EC motor is in effi-ciency class IE4.

Plug fanEC Blue is a compact plug fan with an impeller made of composite material, where all details are optimized in order to achieve a high efficiency. The impeller is fitted directly to an EC external rotor motor with integrated variable speed control. An EC motor is characterized by a high efficiency and excellent control features. For opti-mizing the efficiency in the operating points, the fan can be selected in several variations in each unit size. Several fans can be positioned in par-allel operation at larger units. The fans are mounted on the end wall of the fan section.

Positioning in the air handling unit A plug fan supplies air at the fan sec-tion outlet with a low and even air speed. Therefore, it is an advantage to position air handling components on the outlet side of the fan.

Service-friendlyThe fan section has a large inspection door giving easy access for service.

H1: Single height unit. H2: Double height unit.

Sizes 20-240Dimensions

* Space needed for extracting the fan.

Sizes 20-150 duct connections

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L, EC Blue-S 750 820 820 970 970 970 970 970

Dimensions

Size 20 40 50 60 120 150 190 240

D 1200 1650 1950 2100 2520 2820 3120 3420

E 500 750 900 1000 1450 1600 1950 2250

F, EC Blue 500 750 900 1000 1450 1600 1500 1500

27 DCC DFC and IFC units |

Page 28: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units28

Function The sound attenuator is used to reduce the sound power level from the air handling unit to the duct system.

ConstructionThe sound attenuator is an absorption attenuator with baffles. The baffles are surface treated in order to pre-vent the absorption material fibres from being carried away.

Mid-frequency Hz

Attenuation dB 63 125 250 500 1000 2000 4000 8000

Length 900 5 11 17 25 36 39 36 28

Length 1200 7 15 23 32 43 46 43 36

H1: Single height unit H2: Double height unit

Sound attenuator fitted to a double height unit.

Sound attenuator fitted to a single height unit.

Sizes 20-150

Dimensions

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L 900 900 900 900 900 900 900 900

L 1200 1200 1200 1200 1200 1200 1200 1200

Sound attenuator

Variants1 – As an option, the air handling unit

casing can be delivered with large inspection doors for easy clean-ing.

2 – Baffles with a synthetic lining, ideal for wet cleaning. Each baffle is enclosed in a stainless steel frame. The air handling unit cas-ing has large inspection doors, which makes it possible to pull out the baffles for cleaning.

Page 29: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

Inspection Section

Empty Section

29 DCC DFC and IFC units |

Function The section is used where the option of service, inspection or measuring is required, before or after an air hand-ling function.

H1: Single height unit H2: Double height unit

Sizes 20-150

ConstructionThe inspection section consists of an empty unit casing with an inspection door.

AccessoriesInspection window fitted into the access door. Bulkhead lamp with external switch.

Dimensions

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L DCC 20-150: 300 - 450 - 600 -750 - 900 - 1050 - 1200 - 1350 - 1500

L DCC 190-240: 300 - 450 - 600 -750

H1: Single height unit H2: Double height unit

FunctionUsed in units where space is required to fit a component, e.g. a tempera-ture sensor, or to have the option of applying an extra air handling func-tion at a later date.

Sizes 20-150Dimensions

Size 20 40 50 60 120 150 190 240

B 1270 1720 2020 2170 2590 2890 3190 3490

H1 670 895 1045 1120 1570 1720 2170 2470

H2 1270 1720 2020 - - - - -

L 300 - 450 - 600 -750 - 900 - 1050 - 1200 - 1350 - 1500

ConstructionThe empty section consists of an empty unit casing, where the side panels are assembled with screws.

AccessoriesInspection window fitted into the access door. Bulkhead lamp with external switch.

Sizes 190-240

Sizes 190-240

Page 30: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units30

FunctionOutdoor air section is used for air intake and outlet in roof units for combinations of DCC DFC and IFC 20-150. The outdoor air section has air intake through the end of the unit, and outlet of exhaust air through the back wall of the unit, opposite the inspection side.

ConstructionOutdoor air section consists of an air handling unit casing with inspection door. The openings for air intake and outlet have louvers for effective pro-tection against rain and snow.

Dimensions

Size 20 40 50 60 120 150

B 1270 1720 2020 2170 2590 2890

H 1270 1720 2020 2240 3140 3440

L 820 1120 1120 1420 1720 1720

Type 1

Type 2

Exhaust air Supply air

Outdoor Air Section

Page 31: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

31 DCC DFC and IFC units |

Base Frame DVZ

L

B

FunctionUnits in sizes 20-150 for indoor installation can be supplied with base frame in height 150 mm or 250 mm, and have feet which are adjustable from 30-55 mm. Units in sizes 190 and 240 are always supplied with 150 mm base frame. Units in sizes 20-150 for outdoor installation are always supplied with 250 mm base frame. Minimum length of base frame is 740 mm. Maximum length of base frame is 6200 mm. Units which are longer, are supplied divided on two or more base frames. Base frame is self-supporting, but as a

minimum it must be supported on the longitudinal profiles for each 4´ 1500 mm. Inserted, longitudinal profiles on units in sizes 50-240 do not require support.

ConstructionThe base frame consists of strong, galvanized steel profiles, in either 150 mm or 250 mm height assem-bled with bolts. For indoor installation feet are supplied, which are adjusta-ble from 30-55 mm. As extra protec-tion against corrosion 250 mm base frames for outdoor installation can be supplied hot dip galvanized.

Dimensions

B L

Unit width Unit length

H

Indoor unit 150 or 250

Roof unit 250

Supporting Legs

FunctionUnits in sizes 20-240 for indoor installation can be supplied with sup-porting legs.

Construction Supporting legs are made of sturdy galvanized steel. They are 100 mm high, and have feet which are adjust-able from 30-55 mm.

100

ø 50

Page 32: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units32

Double height unitDV 10-150

DV 10-50 DV 60-150

Single height unitDV 10-150

Double height unitDV 10-150

DV 10-50 DV 60-150

Single height unitDV 10-150

Dimensions for ducts on other unit functions

Size 20 40 50 60 120 150 190 240

D 1200 1650 1950 2100 2520 2820 3120 3420

E 500 750 900 1000 1450 1600 1950 2250

The DCC DFC and IFC can be supplied with rigid or flexible duct connection.

Unit 20-150

Unit 20-150

Dimensions for Ducts

Dimensions for ducts on all other unit functions:

Page 33: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

33 DCC DFC and IFC units |

Type 2DVT 10-150

Type 3DVT 10-240

Type 4DVT 10-240

Rigid connection part for connecting to 25/32¨ LS profile for C-rail.

Rigid connection part for connecting to 1 3/16¨ EP/LSM profile with holes in the corners.

Type 1DVT 10-150

Dimensions

Size 20 40 50 60 120 150 190 240

Variant A D - - - - - - 2600 2800

E - - - - - - 1500 1800

Variant B D 800 1200 1500 1600 2000 2300 2600 2800

E 300 400 400 500 700 700 1000 1200

Variant C D 1200 1650 1950 2100 2520 2820 3120 3420

E 500 750 900 1000 1450 1600 1950 2250

FunctionConnection part is used when connect-ing duct work to the DCC DFC and IFC air handling unit, either as rigid connec-tion or as rigid and flexible connection.

Variant A - Damper, mixing damper

B - Damper, mixing damper

C - Others

Flexible connection part for connecting to

25/32¨ LS profile for C-rail. For mounting in continuation of rigid connection part.

Flexible connection part for connecting to 1 3/16¨ EP/LSM profile with holes in the corners. For mounting in continuation of rigid connec-tion part.

Unit 20-150

Unit 20-150 Unit 20-150

Unit 20-150

Duct Connection Part DVT

Page 34: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units34

Installation examples

Page 35: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

35 DCC DFC and IFC units |

Page 36: Systemair DFC and IFC€¦ · DCC DFC and IFC contains countless combination options. To ease the process of desig - ning a unit the most popular combinations are illustrated here.

| DCC DFC and IFC units36

Systemair SLU 28942 Fuenlabrada Madrid, Spain

Phone: +34 91 600 29 00, Fax: +34 91 60 70 309

[email protected]

www.systemair.es

Syst

emai

r ES

•May

201

7 –V

2


Recommended